: � September 6, 1994 �
the '
� Mr. James R. Gregory, Chief
edge �group � Health Facility Regulation -
Plans & Construction
Agency for Health Care Administration
���� 2727 Mahan Drive
Tallahassee, FL 32308
architects
RE: East Pasco Medical Center
d e s i g n e r s South Addition, Phase IV: Atrium Lobby
consultants �� Los #s-425-s�corr EX�t
AHCA Review Letter Dated July 13, 1994
planners
i n t e r i o r s Dear Mr. Gregory:
We are herewith submitting architectural responses to comments in
the above referenced letter. Mechanical, Electrical and Plumbing
' responses are provided. by Peninsula Engineering, and are attached.
In addition to revisions per review comments, there are several
plan changes. All of these are incorporated in Addendum #2, dated
September 6, 1994.
ARCHITECTUEtAL
' Comment: A-2/C The glass in the wall between medical records
suirE zo•� storage and the atrium shall be a 1-hour rated
444 BUNK=R ROAD
WEST PALfA eEncH assembly. Since this is a hazardous occupancy,
FLORIDA 33•�OS-3694 Exception 2 to Paragraph 6-2.4.6(g) of NFPA-101 .
does not apply. , �,
407/585i 9307
� FAX. 407/585-9628 Our previous response to this �comment generated ��
the following: The construction of shell space
p�NaP� is not approved, all spaces not otherwise
Donald R. Edge, AIA designated shall be labeled storage, comply-with
PNtitr�t ! I the comment.
Todd D. Reichard
AI.A '
A�q��i�cT ' Response: Addendum #4 dated June 15, 1994, Phase IV (AHCA '
Re�ee e. Hutcheson Log #H-425-R) eliminated the Medical Records
a�.a � Storage from this area. The space is not shell
���Y� i space; it is PCU patient rooms (Exempt
winifred M. IKennedy i #9402332. ) See Sheet Al-6 (or A2-5 Phase III,
i H425-R revised Star 4) , the windows that do open
into the atrium are treated same as AHCA
I i
� i criteria given us for Patient Rooms (see also
� � Response to Comment A-10. )
i �
� ,
�aacoaoes��
�
,
� ,
Page 2
September 6, 1994
Mr. James R. Gregory
I
I
,
Comment: A-9 Sheet A4-40: Show the 1-hour rated separation between the
� atrium and Floors 2, 3 and 4. The response to this comment
generated the following: The rated wall separating the
atrium from the fourth floor shall extend to the roof deck,
revise accordingly.
Response: The 1-hour rated wall separating the fourth floor from the
atrium has been revised to extend to the ceiling. A 1-hour
wall has also been added to isolate the Mechanical Room from
the unused (unaccessible) penthouse space facing the Atrium.
, The smoke system has now been ducted, �fire dampers have been
� added where these smoke ducts pass through rated walls (see
��
i M-18 & 19 attached) (see also Response to Coaunent A-22 & A- ,
23. ) See revised drawings A4-40, A4-42 and A5-12, Addendum I
#2, dated 9/6/94. ',
Comment: A-10 Sheet A4.41:
B. Show a window in the second floor patient room that
complies with the requirements of NFPA-101 and the
SBC.
The response to this comment generated the following:
Per NFPA-101, Chapter 6-2.4.6(g) Exception No. 2., the .
� glass in the separation walls of the�atrium shall be -
� tempered, wired or laminated glass set in gasketed
frames, revise all such openings to comply including �
the existing patient room windows. '
Response: Al1 glass in the separation walls of the atrium will be �
� � tempered or laminated glass and set in gasketed frames. See i
� � revised drawings A4-41, A4-42, and A6-4, Addendum #2, dated
i 9/6/94.
I I
� �
i
� ,
' ;
i � �
�
I ' ;
i �
� !
i
i i
� l ,
;
, .
�
�, ,
� .
�
� , �
I�age 3 � '
9eptember 6, 1994 � ,
Mr. James R. Gregory
i
i
i i
Comment: A-13 Sheet A5-12: I
I
� � B. Detail 4: Show the 1-hour rated wa�l assembly and the
i safing at the edge of the floor slabs. ,
i
� ; The response to this comment generaled the following:
� .
A. The 1-hour rated separation sYiall ,be a listed
assembly, provide the design number for the
j ' walls above and below the glass, these shall be
; , 1-hour rated assemblies from floor-to-floor or , '
floor-to-roof deck, revise accordingly.
I _ i
I ; B. Provide safing at the edge ofithe second floor
I slab, sealed against the passage of smoke at the ;
top side, revise accordingly. � '',
;I � � � �
Response: The 1-hour rated assembly has been revised and is listed
' assembly UL DES-U465. Safing has been added at the edge of
the Second Floor slab to prohibit passage �of smoke into
cavity of wall. See revised A5-12, Addendum #2, dated
i ; 9/6/94.
C�',omment: A-21 Sheet Al-5:
i ,
I� A. Provide an exit light at the north end of Waiting
� � 160C. Visible from Waiting 160C and 161. - i ;
,I � � ;
Response: The exit sign has been added. See revised drawing E-24, �
il Addendum #2, dated 9/6/94. I i,
New Comment A-22 Sheet A4-40: Section 1 shows a return air plenum above a 1- 1'�
� hour ceiling of drywall on metal suspension, provide a �
I design number for this assembly and coordinate with
Mechanical Sheet M-18.
� �
Response: � This air plenum has been eliminated. The �smoke evacuation ! '
, j system is now ducted. See revised drawings A4-40, A4-42, '
� and M-18, Addendum #2, dated 9/6/94. I � '
� � � �
, ! �
�
� �
I � ii
I
I
i
- i
I i
�
i
; , i
I i , ��
I '
;
.= . , .
!�age 4
::�eptember 6, 1994
1-ir. James R. Gregory �
i
� ' '
I
Comment: A-23 Sheet A5-12: �
; A. Section 4: The separation wall between Mechanical
i Room 401 and the atrium shall be a 1-hour listed
� � assembly from the floor-to-roof deck above per the
' AHCA letter of January 3, 1994. The store front and
� water curtain are not approved. Revise accordingly.
�
' B. Coordinate this section with the exhaust system
� indicated on Sheet M-18.
Response: A 1-hour rated wall now separates the (created) Vestibule
401 from Mechanical Room 402 isolating the Mechanical space
from the Atrium with space 401. Vestibule 401, being roof
only accessible, empty and non-hazardous should allow us to
return to the wetted (water curtain) storefront at this
Fourth Level. See revised drawing A2-12, addendum #2, dated
9/6/94.
New Comment: A-24 Sheet A6-4:
I '
A. Revise Details 3, 6-10 to comply with the glazing
requirement of NFPA-101 that all glass in the atrium
separation walls be wired, tempered or laminated, set
in gaskets to prevent breaking under heat stress.
B. Details 8-10 show wood blocking that is not fire
retardant treated within the building envelope, revise
to comply.
Response: Details 3 and 6-10 have been revised, likewise details 8-10 -
have been revised to show fire retardant treated wood ,
; blocking. (Al1 wood blocking throughout the building has I
� long been specified to be fire treated. ) See revised Sheet �
, A6-4, Addendum #2, dated 9/6/94. �
,�• Very t L��tly y ouurs,
- .= �'-�%� _ ' i
.. z���'�� �=
,-, Donald .R. Edg.e
� �Architect : ' �
Enclosurec Addendum #2
� Peninsula Response ;
cc: East �Pasco Medical Center
Penirisula Engineering ;
c:xin\0661.94 ,
I
f '
•t - -:
� the edge group, p.a.
444 BUNKF1t.ROAO WEST PA1JA BfJ1CH � �
fLORIDA 33405-36B4 407/585-8307 ,
I i
EA3T PASCO (MEDICAL CENTER ; I
SOUTH ADDITION-PHA3E IV: ATRIUM I,OBBY � �
AIHCA LOG #H-425-5
i i ,
ADDENDUM No. 2 - September 6, 1994
Issued to Poole Construction Company.
; I
I �
The intentiand purpose of this Revision is to augment or modify the Contract
Documents (Project Manual and/or Drawings) . This Revision shall supersede
conflicting requirements of the Contzact Documents. Mechanical and Electrical
drawings by Peninsula Engineering are attached. All are signed and sealed.
This Addenda and documents are the responses to AHCA comments of July 13,
1994.
A�. DRAWING REVI3ION
� Architectural �
�
i
1. �' A2-12 Revised Third Floor Reflected Ceiling Plan, Fourth Floor
Plan, Fourth Floor Reflected Ceiling Plan.
2. A4-40 Revised building section.
3. � A4-41 Revised, existing window replacement requirements.
4. A4-42 Revised building section/revised window requirement.
5. A5-12 Revised wall section.
6. A6-4 Revised window details.
7. ETO Gas Sterilizer renovations (this is a separate issue,
submitted at part of the Atrium project as recommended and
permitted by AHCA. ) -
I �
B. 3UPPLEMENTAL DRAWING3
I .
� Architectural j
1. SD-2 Relocate door at Vestibules (refer to A1-5�, A2-8 and A4-23) .
, 2. SD-5 Building Section/Mechanical 402�. _
3. SD-6 Building Section/Mechanical 402.
4. SD-11 East Elevation/Elevator relief louver (refer to A3-16) .
5. � SD-16 Detail of rated duct enclosure-Third Floor (refer to A2-12. )
I C. PROJECT MANUAL I
Architectural
� ' I
, � � ,
1. D5-26 Added Door 401A in 1-hour rated wall� - Fourth Floor. � �
2. � RFS-25 Revised room name to Future Corridor' (401) .
� , ;
' , � ,
I �
i
.; . . - :
C.� the edge group, p.a.
444 BUNKflt ROAO WEST PALA1 BFJICH �
fLORIDA�33405-3684 447/685-8307 � I
I � �
j �
EAST PASCO�,,MEDICAL CENTER
SOUTH ADDITION-PHA3E IV: ATRIUM LOBBY ' �
AHCA LOG #H-425-s
I �
ADDENDUM No. 2 - September 6, 1994
PAGE 2 !�
i
I
I �
D. MECFiANICAL DRAWING3:
M-14, M-15, M-16, M-17, M-18, M-19, M-20 with attached explanation of
each sheet (total 4 pages including below) dated 8/29/94 and 8/30/94.
E. ELECTRICAL DRAWING3: !
� E-24, E-25, E-26, E-27, E-28, E-29, E-31, E-32, E-33 with attached
explanation of each sheet (total 4 pages including above) dated 8/19/_9�1.
and 8/30/94. � ' - '
i � -
i i: , �
� �_' � .
./
` - �
� e��;, - - �� =
, , .
' '� - - �
; ,
; i _ �
- �
c:win\0638.94
I '
I � i
I
� �
i ' '
j � i
�._._._._ -- -•- -•-•� I .- -
_ ._.._ . •
H - -- ----
EKJt _—_______________________________ _ . _
__—�________________ ____
I �oCe oF boxed beon obovp i
� � I , g" 1 1�Z�� 18'-4 1�2,�
I/i 18�-4 1/2' � 11'-10 1 2' ---- ---- — --------- -----
—�I
I
� �
I �
I �
I �
� I
� I
I I�
I �
� � Fnciu above
I � � (3rd fU
STING I I
�Fatw Above � — — ——_—— — ——
I _'"_� '___ I
� '_ I' _—__—--_' _''_ _—_ _ _ ____ _ ' _ �___'__ ___'
' _ _ ' _ _'__ ____—
— ,•� L------------- ---------------------- -
— � i
— I i� ,
— I N 3-1/2" x 72" CHASE; BRING ;�i' � � �
I � CONDUIT UP WITHIN. � S ❑
I
— � NN � �� 3�-1" 6�-O�� CNT LN. OF CHAS ♦� j � �
_ � y� I bD (�oE / � �y � .,
i — .
; . � i>
� \�� �JC�__h�' /� � Z '�-' �•
i � .i. , � ' ,� � ���. i . �
i �. i � �� � .� i �. .
i .� � �. � w �, � � i `. ��,
� \���� ,' �� i `� ���� `_ � ry� � � ���
� �//\�� � i � �/\� 1 ��/ � � O �� / � \��\ �/�i�/ \\ c�wnl
�� �i� __�J ------ 9
----- ' - --�`------�-
�------�------� � � �(es�ti bule� ;
------- m
, 1les�ibule , �
�
------L-- ��Ob ------1- ---- ------------U------ ------L--- 1�°-E ----1------ ---
� H ' H =-
H ❑ —
� --- anv --r-----y--r----r-- ---- -------T----�—�—r----r-------
.e. � � � �� � MM I / \� �� M.a. \
I i� �� I I i� �� I
L�� �..! L � '�
tactile warning
strip
��
� � .
-- ----- — ---- - --- { � } � <i . . ---
„ , ,., � � -� ' ��, I�1•�
ooaarnw ar a¢r --- -- - - - --- �M° — ' \� ' �' / � _ �/ ��
e ed e rou .a. r1Fo1�MJlTtaJ DE'sK'— {2EYt5tatSs q�,pl•h�� � �� �T"
th g g P� P $
-- - - - � - -------- - -
---------- - ----
444 BUNKER ROAD NEST PnlA1 BEAqi vuaccr w� - w`—-�, -- '— �---�--- �--.�
�------
�����-�94 407/5Q59307 EPMG- ATa�� ��.�r- ----- --- ��� �J . ;� � 6�� `, � zt44
, �,.. c ., 81
._ , . . �
, .., .
,
. _ � � ,, �,,,
_ __ --- -- - --- �, � ��
2 N�, ���r�-AT�
I�o� �e� s�IP•FT wP.u.. �r-►c�os�a-E,
� , . L!Y ' �� • � �
� �(1-� �Ea►M ��. � --
. . . . . . . . . . ... .. . . . . ... _ . .. . :.. . . . .. . ..
---� _o � --- -------- -- -
-- - - - -- - -
- -- --- - - - - -- ---
�,�� -----------��Ft - ---
� - -------- -------------- -.____. ------- - � -- - ------------ ----------- s�z�
- ----�3-��- --1 p�� ---__��I-m��
------- -- ------ �x _. .�_ ------------------------------ , /j,'� — -- �GroF� 0�
2 _ Got.. ���1rzE
- - -- -- --- z - -- �co� - ---------
- — _� : --------- — --
� . 7z.x --
►�. -------
� . a aa. � - �o
��G�I O f�l T!-�(z� �0�1 IZTI-I ��-oo�-- M�I-4P�►.1 Ic�J_
p�M �K�� w�T T�w,�.� ���,o,Torzs, _
��� �i v�
P11•1�
S�
- - -- --- - - � � � �- ; , 5 Slztq4
� � � � the edge, group, p.a.
.` 0
- - -- --- -------- -- � -` -- ' � �� �
, �/�n ,�� A44 BUPlKEH-ROAD,-WEBT PALF1 BE:,:.�:
, L ' , fLORIDA 33406-3E94 306/EE6-G307 I
r' ' 1
' - . � ��. ��1.03 - �.Tw��
'� �, , '-2s-�14 sK_5
�Lca�F SI.Ab
. poo , .
:.�. -� �� 2 N�, ����-AT�v �-+AFr ���:�.� � � � �� � � � � . � �
, . .
---- - - -- - -- --- • -- --WAL1. �..J��c�j R..� - • -.—� � F�E� c��1IJ, � oNv -- -- —•-=�—:
� - - - . .
�--- —�_–__�=��.
�,���r � --��{� 3�x�Z-=- , __��_- .� . -� - ,�-�� �-- . ��
LaU V�� J • ?Jk�C 3Co� ,�I ' � I .,�j • . �
(�'-o X 4'-0 �,�. � ', : • � �. . — —� — ' � �� �——— �!_�-•_ �
—��..—
J �- j��
. � �
S -- �CO sc.z 2.
��-►�T j � 4bKq-� ���
BE��d � i MEGH'L I�M SEF- I r�'�``,��
� � � �¢,,Z
ra
�j-0 X��'P�.0. } ; � / T I i i � �
f� ; I ,�— � l ,���\ I
� iL
.� �\ 34��2 �,� �-----
(o" corJ�-• \
�o�R- 5i�v.� PP•�
o, . . , o. . I
3 �2.�J IS�b ��� lot.� ��S�
SD
M-�� ��' � �'-o° , �
--- - - ----- ------ - : � , , - - - - - - t 9
. . - � � � � �� �, � the edge group� p.a.
�., � ',
- ;: � . .. . . ,
'� �1 � 444 BUNKEFi ROAD, WE3T PALM BEACH
,, ''/(.� �
.
- ', ' ' --: —., �',� �--— •- -FL-OFIDA=33406-3894-30 8/6 8 6-9 3Q?--
--- - - - - ---- -- - — - " . :t- ,a + = ; JoP�, �301.03 - �TRI�JI-'1
•/� , �. , ,�i�G.�9�'�-�� ��Z�"�I4 SK_Co
, -, . .
, �; , � �,�.
�� � ,
..--�
��
IOIv l07 �}Cn
�
i � '
, I I
.5,'0„�. .. . '-'o" Z,�w �'-o„ i'�'-v"� , ,. -.
2-d ,
------- - r--��io'-o„ aEo�� �Q
----- -- -- _ � __� FYESN e.it � '
----- ---- O . �NtAKE ..
---__ --- _- - . �
- -_- -__--__ Q - � : i I
_--� -=--
E�i�; R� ��� �
�NS��Ar�o�
. . , . _ - . - . - . � � :
. , . .. �,
, �
� ,
� _ . . �
u_ G�lSr, R-oa� S�aP I
� � 2-I�R-�'i R-�*'(Fp i r.15?2�Jc��o�.l,
Q �
� ' , I
� i ' '
_� �Et�JG�G F�G.1-�AL�� D�G"r
� , w -�-�a., �� �
iJ ' v�/�l. u.v�
— ; � A�L ,3 slv�.
� D�s,� 1�438
� �
1�E(�� 5�ZE� Loc,�. lo�
� �-4,�J� �G w
' i ,
- E,u�-a�s� e�G'�
_ Ce�n1rJE 'r�oi.l .,v� FIR-E
_ _ , , �P�r7- c r.z.P�r o
... F�Gt,.oSU t�-C bE��(ohJ D�
� i �r�I� ��t�T��
� ; �.Y� � ��. R��roJE
' � s s���-�1 � �R�o AS
� =4 R�v. '
� '�
� ,
I ��G I or.l 'rj-�R� E�IS , Gd42�I Do I� ,
s�- 3 ��, � u
� �� 4- ' ��o i
i
��� �
, �, I
� �
,
. ; . . � �
i
_ _
� � �-
�- �:
� _ , � a.
. , `�\;
` ' �
�_
_ � - _- � � .
, �• �
� P0.(17ECf �ISSUED JOB N0.
the edge group, p.a. �,P, �,G, 2 •�R� ►2,o.��D '
� � ,
444 BUNKER ROAD, WEST PALM BEACH �}�f�y�5� DUG� �I�U�-E �� I
FLORIDA 3340b-389< 305/6a6-9307 I(p
, I
I
!,
� � � � �
�
.
..
.
�
. � � �
� ; . �
- � .
� � "". . .'- ■���„�
' • � � ,���„�
,---,,,
� � - - ����e�■
� ■����■■
� ■������ ■�■�
� ������■����■����
� �������������■��
� ������■��■■��■��
� ■����■�■���■■���
■�����■■���■��■�
���������■��■■��
�����������■�■��
����������■■����
�. ■������■��������
� ■���■��■��■�����
� ����������■�����
� ����������■■��e�
� ����������■■��■�
�. ����������������
� ■���■■■■��������
� �����■�■��������
� ����������■�����
� ■����■���������� .
� � �ti
� '
�
_ - - • • - • • • • • � �� -• - - �� ��
�� �
�• . a . — . -• - -
.
/ � � .�� ,
•
.
•
.
� �
• .
� � � e
�
�
• �
♦ �
•
Y
. •
.. . � ■■■■■■■■■■■■■■■■■■■■■■■■�� � � • � i'
• • ■■■■■■■■■■■■■■■■■■■■■■■■■■ � '
■■■■■■■■■■■■■■■■■■■■■■■■■■ ' '� � '
� ■■■■■■■■■■■■■■■■■■■■■■■■■■ • • '
■�■■■■■■■■■■■■■■■■■■■■■■■■ C��� •
■■■■■■■■■■■■■■■■■■■■■■■■■■ �� �
� � ; ■■■■■■■■■■■■■■■�■■■■■■■■■■ � � ��
. 1 ■■■■■■■■■■■■■■■■■■■■■■■■■■ •��
` '� �■����■�■���■�■■■������■■■ !
� � ■�■■■■�■■■■■�■■■■■■�■■■��� � .
■■■■■■■■■■.■■■.■■■■■■■■■■■
� ■■■■■■■■■■■■■■■■■■■■■■■■■■ � � ' �
' ■■■■■■■■■■■■■.■■■■■■■■■■■■ � � ' •
� ,
' ; �■�■■�■�■■■■�■■�■■■��■■■�� . • . :� •
�����������■..�����■������
1 �■■�■■■■■■■■■■■■■■■■�■■�■� ' •
' � : ■■■■■■�■■■■■■■■■■■■■■■■■■■ �
� � ' ■■■■■■�■■■■■��■■■■■■■■■■�■ '• �
. ` � �
� ,i
`� �������������������������� �
/ '�
� . � I
� � I
� i
II �
' �i 'I
I ,
I
August 3U, 1994 . � �
.
,
The Edge Group, P.A.
444 Bunker Road, Suite 201
West Palm Beach, FL 33405-3694
i �
Attn: � Todd Reichard
I ;
. � East Pasco Medical Center �
i South Addition - Phase IV Atrium
li
PEI Project No. H93-16BZ
� I
Dear Todd:
� j '
In regards to the above referenced project, please issue Drawings
. M-14, M-15, M-16, M-17, M-18, M-19, M-20, E-24, E=25, E-26, E-27,
E-28, E-29, E-31, E-32 and E-33 to satisfy the AHCA comments dated
July 13, �1994. All sheets are clouded Star 2 and dated August 19,
1994. '
.?�n addendum for the above mentioned sheets is included with this
:�letter. ;
:�Cf you have any questions or comments regarding the above, please
do not hesitate to contact this office.
;
Sincerely,
��Z%�� I�
I � ����
Harvey L. Wilcox �
Proj ect Manager �
�
HLW:mrp '
i � �
, (
; �
I � /J��
i ', /�'= GC��
� 31�� y -
� � ��!
. � ���
1833 Edgewater Drive � ■ Orlando, Florida 32804 ■ 407/246-1688 i FAX 407/246-1664 �
I � , �
�` n i
� �
i i
i
�
i East Pasco Medical Center
� � PEI Project No. H93-16BZ ,
I I
�
MECHANICA�L �
�
D�awing M-14 '
• Deleted additional ductwork and reheat coils from existing
AHU-�2.
• Adde�d new ductwork at Conference Room and Medical Staff and �
conn�ected to existing ductwork above Corridor 161C. '
• Adde�d fire/smoke dampers in ducts through existing fire/smoke �
wall� at Mens Room and Employee Locker Room. �
. i
� �
Drawing M-15 ,
� I
• Deleted reheat coils and piping as noted. �
i
Drawing M-16
��
• Deleted fire/smoke damper above Room 163D. I
• Added fire/smoke dampers at existing fire/smoke wall and new �
fire/smoke wall as noted. '
• Deleted supply at Passage 170 and Corridor 174.
•� Added supply and return to Rooms 171, 171A and 171B. Revised
ductwork sizes accordingly from AHU-14.
� Revised ductwork and air quantities at Data Processing Room
176iand Toilet Rooms 167 and 169. �
� Added transfer from Gift Shop to Atrium.
� ;
DrawinQ M-17
.
� Added reheat coils RH-128 and RH-129. � ,
Drawing M-18
i
• Revised ductwork, outdoor air intake and Exhaust Fan EF-18,
sizes and location as noted on partial third �floor plan.
• Rev�sed Sections 1, 2, 3, and 4 as noted.
• Rev�sed smoke purge system ductwork as noted 'on fourth floor ,
plari.
Drawing M-19
� Deleted fire dampers from all ductwork entering and leaving
Mezzanine Mechanical Area. �
�� Chariged dampers to fire/smoke at 18" x 14", 34 x 10, and
�, revised size 34 x 12 penetrating one hour fire/smoke wall at
i Col: Line (I) .
Revised ductwork at AHU-14 .
� Deleted fire dampers from ductwork at new rated walls in first �
i floor mechanical room. �
�
i
i �
; i
�
; i �
�
! y I i
' I�
i I
•I Revi�sed ductwork location and sizes for Smoke Exhaust Fan SEF-
1, a�s noted. i
•� Revi�sed Section 3 to match floor plan changes.
• Relo�cated outdoor air louver and duct serving AHU-17.
Drawing M-20
I
• Revi�sed Air Handling Unit Schedule: AHU-14, as noted; AHU-15,
as noted; AHU-16, as noted; AHU-17, as noted;
• Rev�sed reheat coil schedule for RH-124 and RH-125, as noted. '
Also, added RH-128 and RH-129. �
• Rev�sed Fan Schedule: EF-18, as noted. �
•� Rev�sed Diffuser/Grille Schedule, as noted. � ,
o, Revised outdoor air intake to a gooseneck, and' deleted Outdoor �
j Intake Schedule.
� i
� �
r]LECTRICAL
I �
Drawing E-24
m I
� Modified exit signs to match life safety plan. ;
� Revised background of vestibules. I
Revised background of Information Desk. , '
� Added circuits as noted. �
1rawing E-25
, ; ,
;� Moved Atrium main disconnect switch.
� Added smoke removal manual control switch.
• Revised receptacle layout to match new vestibule layout.
;• Revised information desk.
; Revised receptacle circuit in telephone equipment room to be
� on critical.
� Added fused disconnect for smoke damper control transformer. i
.
�
Drawing E-26 �
�
� Moved horn/strobe to Infectious Control wall. i
• Deleted two horn/strobes from exterior entrance. �
�• Moved fire alarm annunciator panel. ' �
I• Rev�ised vestibule background.
• Moved information desk.
�• Clarified elevator "Do Not Use" sign.
I
Drawing E-27
• Added walls to mechanical equipment room on fourth floor. �
�• Mod�if ied 1 ight switching. '
�• Added exit light.
� ,
, � � ,
iDrawing iE-28 � �
' �
i �
• Revised elevator circuits. ' �
�• Added Notes 19 and 20. �
, !
i '
_ - - . �
i
� i
L�'rawing E-29
•� Modified Note No. 6.
Drawing E-31
, I
• Revised feeder from MDP to Panel 1HE1, see Notes No. 1 and 2.
• Deleted need for expansion to MDP.
•� Revised ground wire size on feeder 21HN4.
� I
i
' i
Drawing E-32
� �
� Revised panel schedules as noted.
I
nrawing E-33
I i
m Added fused disconnect to "Smoke Damper + AHU Control"
� diagram.
' I
I Added fire alarm start for smoke exhaust fan to "Exhaust Fan
i + AHU Control" diagrams.
�
�
�
� '
i
� �
I i
� ;
� �
, I
�
�
I
�
I
� �
� �
� ,
� � ;
� i �
�
� j I
�
�
� i
�
l i �
� , ,
� ; �
i ��
� �
� �
1 li
�
� �
August 30, 1994 �
�
.
I
The Edge Group, P.A.
444 Bunker Road, Suite 201
West Pa1m� Beach, FL 33405-3694
j
Attn: Todd Reichard
RE: East� Pasco Medical Center
I South Addition, Phase IV
, Log No. H-425-5
' PEI Project No. H93-16BZ
i i
Dear Mr. Reichard:
� ��
The following are the AHCA comments dated July 13, 1994 and
Peninsula Engineering, Inc. �s responses, dated August 19, 1994:
� I
MECHANICAL
i
COMMENT• I
I
A(�:-2 iProvide fire/smoke dampers in the following duct
� ipenetrations of the fire/smoke wall:
i
; 'A. The 18x14 outside air duct above Volunteers 165.
i B. The 34x10 return duct above Office 165A. -
i C. The 14x8 return duct in Data Processing 176.
I D. The 26x10 return duct in Corridor 173.
I Please provide the appropriate fire/smoke dampers in lieu
, of the fire (only) damper shown on the floor plan. Also,
I, provide fire/smoke dampers for the 42x8 inch duct
i (Waiting 161) , 22x10 duct (Cashiers 163G) and the
existing 20x7 inch and 10 inch diagram duct which
� penetrates the smoke wall.
RESPONSE• �
I �
Have complied. See replacement Drawings M-14 and M-16,
Star 2, dated August 19, 1994. 42 x 8 duct and 22 x 10
duct do not penetrate rated walls. See; Drawing A1-5,
Star 1, dated March 28, 1994 for location of one hour �,
fire/smoke walls. i
�
I I I �
,
1833 Edgewater Drive � ■ Orlando, Florida 32804 ■ 407/246-1688 ■ FAX 407/246-1664
�
1 . � �
I
I
� I
i �
� I
M:r. Todd Reichard -2- August 30, 1994
�
, ;
'
. I
,
COMMENT:
AC-3 The outside air duct from OAI-1 and the exhaust duct for
EF-18 shall be located in a rated shaft with fire/smoke
; dampers installed at each duct penetration of the rated
' shaft.
;
The fire rated shaft shall run continuous to the roof.
i The main trunk duct for both outside air and exhaust must I
j !be run within this shaft from its origin at the second
I � floor penetrations to their respective roof mounted
' �outside air intake and exhaust fan. Fire/smoke dampers
i shall be provided for all branch duct penetrations of the
�rated shaft. The outside air intake shall be a minimum
� of 3-feet above the roof and a minimum of 10-feet clear
of any exhaust or plumbing vent.
I '
RESPONSE• � �
I
� Have complied. See Drawing M-18, Star 2, dated August
� ;19, 1994. Refer to Architectural Supplimental Drawing
�SD-16.
�
I� .
CC�MMENT: �
; ,
AC-5 �Provide a minimum air differential pressure of 75 CFM for
� �Toilet 164A.
I
RESPONSE: -
' �Room 164A is not a toilet room. This room is part of
� ;open Office Area 163.
i
I
COMMENT• �
AC-6 IProvide the air quantity for all existing air devices to
�remain and those that are to be removed. Provide
�information for the rebalancing of the existing systems
�after the air devices have been removed.
' Please show the air quantities for all the existing to
remain and the new air distribution devices on Drawing M-
�16. The drawings shall show how � the pressure
relationships of adjacent spaces are toibe maintained ;
during the demolition of the duct systems for the i
renovated areas. The drawings shall give the contractor ��
clear and specific direction on how the HVAC systems are �
' to be balanced. �
� ; �
�
I � I
�
I ' I I
� �
i � I I
�
I
I I
M�r. Todd �Reichard -3- August 30, 1994
�' I
RESPONSE•
! Air quantities within the new construction and renovation
� areas, both new and existing, are shown on M-16.
Existing devices have a blank hexagon with air quantity.
Existing devices not in the new construction and
renovation area are shown on M-14 with air quantities.
� Some additional air quantities are shown on replacement
' � Drawing M-14, Star 2, dated August 19, 1994..
CC�)MMENT•
Ac:-10 IWomen's Toilet 167 and Men's Toilet 169 are excessively
negative. Revise the air quantities in these rooms to
provide a maximum differential pressure of 100 CFM.
� The air quantities shown on Drawing M-16 have not been
� revised, please comply with this comment.
RESPONSE•
i
� Have complied. See replacement Drawing M-16, Star 2,
�dated August 19, 1994.
CGMMENT•
�
AC-11 Provide 90 percent filtration for AHU-16 and AHU-17 that
I serve the patient corridor system.
I
i Please revise the fan motor horse power requirements for
�, AHU-16 and 17 due to the increased static pressure drop
, imposed by the addition of the 90 percent filter Section
�
F-10 and F-11.
RESPONSE•
� Have complied. 90� filters have been scheduled and added
+ lon Sheet M-19, Star 1, dated March 28, 1994. See
replacement Drawing M-20, Star 2, dated August 19, 1994
for upgraded horse power on AHU-16 and AHU-17. ,
� �
COMMENT• ,
AC'-13 �Relocated the duct smoke detector for the return air to �
�� �AHU-14 as required to sample the total return air
i quantity including the 6-inch by 6-inch duct branch at �
j the main return drop to AHU-14. Indicate the air j
quantity and what this 6-inch by 6-inch duct serves. I
�
�
i
I
I - -
i I
i I
I
I
I
Nfr. Todd �Reichard -4- August 30, 1994
RESPONSE•
6 x 6 duct have been removed, smoke detector location is
correct. See replacement Drawing M-19, Star 2, dated
August 19, 1994. �
i
COMMENT• �
AC-14 Remove or explain the reason for the fire dampers which
are shown in the duct penetrations of non-rated walls in
' the rooms as follows: Office 171-A, Switchboard 164, and
� all the fire dampers in the corridor above the conference
,
room.
RESPONSE•
� They have been changed to fire/smoke dampers and are
� protecting duct penetrations through existing 1 hour
;, rated fire/smoke wall. See replacement Drawings M-14 and
M-16, Star 2, dated August 19, 1994. See Drawing A1-5,
' Star 1, dated March 28, 1994 for location of one hour
� rated fire/smoke wall.
C(�)MMENT: i
�i
Ac�:-15 Provide a 2-hour fire rated enclosure for the horizontal
36-inch by 24-inch elevator shaft relief duct which
� penetrates the elevator shaft in the fourth floor
i mechanical room and terminates in an exterior sidewall
� louver. Code Reference: Standard Building Code (1991) ,
' Section 2402.6.2 .
I
RESPONSE•
' Have complied. See Architectural Drawings SD-5, SD-6 and
M-19, Star 2, dated August 19, 1994.
i
�
FIRE PROTECTION
� I
C MMENT•
� I
FP-1 Provide for review complete hydraulic calculations for
the hydraulic design areas indicated on Sheet FP-8. �
I Calculations shall be provided per all requirements of I
NFPA-13, 1989 edition. I
I �
i
M;r. Todd Reichard -5- August 30, 1994
,
� �i
� .
iEach summary sheet of each individual unbound set of
i Ihydraulic calculations shall be signed, dated and sealed
by the engineer of record. Provide replacement
, calculations.
�
RESPONSE•
.
i
'� ' The calculations have been issued and have been approved
I �'ibased on the July 15, 1994 letter from James Gregory of
; AHCA.
i
EYLECTItICAL
�
CUMMENT• �
;
Sheet E-24•
E�1 !Coordinate the exit light locations with the
! ;architectural drawings and comments. Example: Lights at
� IWon door.
�
� �
i Exit lights are not shown at the Won-door location
separating the atrium lobby from the elevator lobby.
Comply with the original comment.
RESPONSE• �
� 'Have complied. See replacement Sheet E-24, Star 2, dated �
'�, August 19, 1994.
COMMENT• I -
� i �,
E-'2 ��Provide panel and branch circuit information for the
!light circuit in the telephone equipment room.
, i
', 'Branch circuit information has not been provided for this
ilighting. Comply with the original comment.
REISPONSE•
�
Have complied. See replacement Sheet E-24, Star 2, dated
� iugust 19, 1994.
i '
COMMENT• '�
E-iDelete the interconnection of the photocells controlling '
, �the life safety and normal lighting.
I
�� � � �
�
i �
, i - ---
M?^. Todd Reichard -6- August 30, 1994
; �
RESPONSE•
�
� Deleted
COMMENT•
I
Sheet E-26:
I I
E�-12 � Provide a fire alarm visual device outside Infection
; � Control.
;
IInformation has not been provided on the revised sheet.
�, Comply with the original comment.
RESPONSE•
Moved horn/strobe in Corridor 172 (north 'end) to outside
�
Infection Control.
IHave complied. See replacement Sheet E-26, Star 2, dated
, ; August 19, 1994.
i i
C�MMENT• '
E;-14 iSheets E-26, E-28, E-29 and Specifications: Coordinate
� the connection and control of the flashing "Do Not Use
i Elevator" sign with the comments and details on Sheets E-
� 28 and E-29. State Code 4A-47 allows only the machine
� room smoke detector to activate these lights. Provide
electrical details indicating the connection and control
; ; of these lights.
�
iRevise sheets do not address comment. Comply with the
ioriginal comment.
�
RESPONSE•i
Added note about existing equipment room S.P. clarified
by note, controls of "Do Not Use" sign. ,
Have complied. See replacement Sheet E-28, Star 2, dated ,
August 19, 1994. ; �
COMMENT• � '
� � I
E-15 Identify the life safety circuits serving, the lighting in �
the elevator lobbies on the second, third and fourth '
floors. �
i ; i
� � �
� �
I I I
� . I, - ,
I
� I
i �
ii
�
M.r. Todd Reichard -7- August 30, 1994
i
RESPONSE•
I
; Have complied. See replacement Sheet E-27, Star 2, dated
' August 19, 1994.
Connected to existing circuits in south addition.
�
COMMENT•
SYieet E-28:
E-�16 iIndicate compliance with NFPA-70-517-34-(b) (2) for
throw-over capabilities.
I �The referenced code deals with the other elevators having
� the capability of being connected to the equipment branch
for the emergency release of passengers and not for
portable sump pumps per the response. Comply with the
original comment.
RESPONSE: �
� IHave complied. See replacement Sheet E-28, Star 2, dated
IAugust 19, 1994.
� i
CQMMENT: i
i
E�17 iProvide the fire alarm devices in the elevator machine
room in accordance with State Code 4A-47. Provide
connection and control details as well as a narrative for
the control scheme. Indicate the location of the shunt
� trip device associated with the heat detectors.
Provide documentation substantiating the response.
RESPONSE•
� . I
Elevator machine room exists. Added note reminding to
extend function to atrium elevator controllers.
COMMENT•
�
Sh�eet E-2 9:
E;�19 Indicate the location of the manual coritrols for the i
�atrium exhaust system as required by the Standard '
iBuilding Code, Section 509.4. 6.
' �equested information was not shown on the revised sheet.
I
� �
� I - -
i I
� i �
. . , �
� �
,
� ;
�
�
M���. Todd Reichard -9- August 30, 1994
COMMENT•
Sheet E-24 :
E-�25 Indicate the panel and branch circuit information for the
; life safety lighting homerun shown at Corridor 174.
RF:SPONSE• �
I �
� ;Have complied. See replacement Sheet E-24, Star 2, dated
;August 19, 1994 .
� I
CC)MMENT• �
��
SYieet E-25•
EI26 Relocate the sprinkler pipe (Sheet FP-7) � that passes
through the dedicated space of Panel 1LN6.
� �
RESPONSE: i
'Sprinkler pipe re-routed.
;
CC�MMENT• '
—��
E�'27 ��Provide selected receptacles connected to the critical
�
�branch in the Telephone Equipment Room 168.
RESPONSE• �
iHave complied. See replacement Sheet E-25, Star 2, dated
August 19, 1994.
COMMENT: i
I
Sh'eet E-25 and E-28:
E�28 Provide overcurrent protection for the power transformer
for the smoke damper motors in accordance with Section
i 450-3 (b) (2) . Provide a wiring detail showing compliance. �
�
RESPONSE•
, ,
iProvided OCP and means of disconnect per diagram on Sheet �
�E-33.
i
i
'��
,�
� I
� ,
. � , . � i
I ��
+i I
j
Mi:�. Todd Reichard -10- August 30, 1994
i
�
COMMENT•
Sheet E-27�:
E-29 I�Indicate the panel and branch circuit information for the
�critical branch lighting in the waiting area on the
�second floor.
�
RESPONSE• �
�
�Have complied. See replacement Sheet E-27, Star 2, dated
August 19, 1994.
This concludes the Comments/Responses. If you have any questions
or�� comments regarding the above, please do not hesitate to contact
thi.s office.
I I
Si�cerely,i,
�2 I r��C/�G�
�
Harv�e L. Wilcox
Y
Pr�ject Manager
',