� Electrica! Notes
2002 Electrical Code
Ryr�an Construction
; 5906 Greenbriar
210.8(A): All 125-volt,single-phase, 15-and 20-ampere receptacles installed in the locations
� � specified in(1)through(8)shall have ground-fault circuit-interrupter protection for
� personnel.
(3)Outdoors
� (6)Kitchens—where the receptacles are installed to serve the countertop surfaces
I
210.11(C)(3): In addition to the number of branch circuits required by other parts of this section,at least
� � one 20-ampere branch circuit shall be provided to supply the bathroom receptacle
outlet(s). Such circuits shall have no other outlets.
Exception: Where the 20-ampere circuit supplies a single bathroom, outlets for other
I � equipment within the same bathroom shall be pe�mitted to be supplied in acco�•dance
with 210.23(A)
210.12(B): All branch circuits that supply 125-volt,single phase, 15-and 20-ampere outlets
(RECEPTACLES,LIGHTS,SMOKE DETECTORS)installed in dwelling unit
bedrooms shall be protected by an arc-fault circuit interrupter listed to provide protection
of the entire branch circuit.
�
240.24(B): ' � Each occupant shall ready access to all overcurrent devices protecting the conductors
supplyingthatoccupancy.
� 250.50: If available on the premises at each building or structure served,each item in
� 250.52(A)(1)through(A)(6)shall be bonded together to form the grounding electrode
system
.
210.52(A)(i): Receptacles shall be installed so that no point measured horizontally along the floor line
in any wall space is more than 1.8 m(6 ft)from a receptacle outlet.
i
210.52(C)(1): A receptacle outlet shall be installed at each wall counter space that is 300 mm(12 in.)or
, ! wider.Receptacle outlets shall be installed so that no point along the wall line is more
� than 600 mm(24 in.)measured horizontally from a receptacle outlet in that space.
406.8(A): '� , A receptacle installed outdoors in a location protected from the weather or in other damp
� locations shall have an enclosure for the receptacle that is weatherproof when the
, receptacle is covered(attachment plug cap not inserted and receptacle covers closed).
406.8(B)(1): 15-and 20-ampere, 125-and 250-volt receptacles installed outdoors in a wet location
shall have an enclosure that is weatherproof whether or not the attachment plug cap is
inserted.
I
� �
�
� ; i 10/28/02
,; I I 2:02 PM
�
. � �
;
� ' 905.1.2-905.2.5
has a direct exit to the outside of the bu�ldin�and 90�.i.j.4 Audible Alarms. Audible alarm �ndicatmo
the buildinQ is three stories or less in he�sht. appliances shall provide a distinctive sound which shall
2. Groups A,B,E,F, H, M, and R1. R2. R3�and R4 not be used for any purpose other than that of a fire
Small Facilities. The manual fire alarm boxes alarm. Such dev�ces shall prov�de a sound pressure
required�in 905.1 may be omitted in buildin�s level of 15 dBA above the a��era�e�amb�ent sound level
meeting all of the follo�vins requirements: � in every occup�ed space within the buildins.The mmi-
1. The building is equ�pped with an automat- mum sound pressure levels shall be: 70 dBA in build-
ic ,fire detection or automat�c spr�nkler sys- ings of Group R occupancy, 90 dBA in mechamcal
tem cover�ng all areas. equ�pment rooms; and 60 dBA in all other occupancy
2. Actuation of the automatic fire detection or classifications.The maximum sound pressure level for
automat�c sprinkler system will actrvate the audible alarm indicatin� appliances shall not exceed
fi�re alarm system. 130 dBA a: the minimum hearin� distance from the
3. Rrovisions are made to manually activate audible appliance. �
' tlie fire alarm system at a m�nimum of one
centrally located station. c�90�.L�.S Accessibility. Alarm systems required to =
I � be accessible by 11-4.1 shall comply wuh 11-4.28. -
: 905.1.2 Manual fire alarm boxes shall be located not more '
than 5 ft(1524 m�m) from the entrance to each ex�t. g0�.2 Automatic fire detection
905.1.3 Each fl I I r shall be zoned separately. No one zone 90�.2.1 Approved sin�le-station or muluple-staUon smoke
may exceed 15;,000 sq ft (1394 m'-). A zone indicator detectors shall be installed �n accordance w�th NFPA 72,
panel shall be located at�rade level at the normal point of Chapter 2, within every dwellinQ and every dwelling unit
fire department access or at a constantly attended buildin� �v�thin an apartment house, condominium or townhouse;
secunty control center. y and every guest or sleep�n�room in a motel, hotel or dor-
mitory and sleep�n�rooms m residential care/assisted liv-
Exception:Automatic spnnkler system zones shall not ino occupancies. Where more than one detector is
exceed the area permitted by NFPA 13. required to be installed within an individual dwelling unit,
�05.1.4 Upon completion of the fire alarm system, all the detectors shall be wired in such a manner that the actu-
alarm in►tiating devices and circuits, alarm �ndicatina at�on of one alarm will actuate all of the alarms in the indi-
appliances and� circu�ts, superv�sory signal �nivaUno vidual unit.
clevices and c�rcuits, sionaling line circu�ts and primary 90�.2.2 In dwellings and dwell�ng units, a smoke detector
and secondary p�ower supplies shall be subjected to a 100 shall be mounted on the ceilinQ or wall at a point central-
, percen[acceptance test in accordance �vuh NFPA 72. ly located in the comdor or area �iving access to each
905.1.5 Alarm�Indicating appliances sroup of rooms used for sleepin� purposes. Where the
905.1.5.1 R�e�quired. Alarm indicat�nQ appliances l�st- d�'elling or dwelhng unit contains more than one story,
ed for the purpose shall be provided. � detectors are required on each story includin� basements,
� but not includins umnhabitable att�cs,and shall be located
- in close proximity to the stairway leadinQ to the floor
= C,�905.i.5.2 �ticcessibility. Every requ�red fire alarm above. �
_ system shall� �nclude visible alarm indicatins appli-
_ ances �n pub'lic and common areas. For more spec�fic g0�.2.3 In dwelling units w�th split ]evels and without an
, _ accessibility�requirements related to alarm indicating �ntervening door between the adjacent ]evels, a smoke
_ appliances,irefer to 905.1.5.5 and 11-4.28. detector installed on the upper level shall suffice for the
� � ad�acent lower level provided that the lower ]evel is less
905.i.5.3 Activation. The alarm indicat�ng appliances than one full story below the upper level.
shall be automatically activated by all of the following
where provided: 905.2.4 Smoke detectors connected to a fire alarm system
1. Smoke detectors, other than single-station or shall be installed in accordance w�th NFPA 72.
multiple-station smoke detectors, as required by
905.2:Activation of the alarm system by smoke 905.2.5 In dwelling, dwelling units and sleeping rooms in
detectors shall be by either two cross-zoned res�dential care/assisted living occupanc�es, smoke detec-
smoke detectors within a single protected area or tors shall be hardwired into an ac electrical power source
a single smoke detector monitored by an alarm and shall be equipped with a monirored battery backup in
verification zone or an approved equivalent all new construction. A monrtored battery power source
metliod.
� shall be permitted in exist�ng construct�on.
2. Spr�nkler water-flow devices;
3. Manuial fire alarm boxes; and
4. Oth�I approved types of automatic fire detection
deu�ce suppression systems.
• jl
- � I
� i
` FLORIDA BUILDING CODE— BUILDING 9•5