HomeMy WebLinkAbout6900 GALL BLVD (3)INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. TEN (10) DAYS PRIOR TO BID DATE FOR ENGINEER'S APPROVAL TO SUBMIT. ENGINEERS APPROVAL OF THE PRIOR APPROVAL PACKAGE WILL BE CONSIDERED 13.1. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE FUSES SHALL BE PRELIMINARY. FINAL APPROVAL WILL BE CONTINGENT UPON REVIEW OF FINAL SHOP THOSE MANUFACTURED BY EITHER BUSSMAN OR UTTLEFUSE. THE CONTRACTOR SHALL FURNISH DRAWINGS. ALL PROPOSED ALTERNATES MUST BE INDUSTRY STANDARD EQUALS TO THE ITEMS TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED, FUSES 600 AMPS SPECIFIED AS THE BASIS OF DESIGN; HOWEVER, IF THE ITEMS ARE NOT CONSIDERED EQUAL BY OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL THE ENGINEER, IT SHALL BE DISAPPROVED FOR FINAL SUBMITTAL IF ELECTRICAL CONTRACTOR/ BE CLASS L GENERAL CONTRACTOR DOES NOT SUBMIT SHOP DRAWINGS TO ELECTRICAL ENGINEER FOR ITEMS - LISTED ABOVE, ELECTRICAL ENGINEER WILL NOT BE RESPONSIBLE FOR ANY, AND OR OMISSIONS 14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE OR ERRORS DUE TO SHOP DRAWINGS NOT SUBMITTED. SHOP DRAWINGS WILL ONLY BE REVIEWED MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY TWICE AS PART OF THIS CONTRACT. ADDITIONAL SHOP DRAWING REVIEWS SHALL BE INVOICED PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND AT $85.00 PER HOUR, BILLABLE TO THE SUB -CONTRACTOR, C.O.D. PLATES SHALL BE DICTATED BY ARCHITECT/OWNER. 27. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH A. SWITCHES: LEVITON #CSB1-201 COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO B. RECEPTACLES: LEVITON R20 -I BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. ` EVERY UNIT OF #B EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE GREEN TO C. COVER PLATES: SMOOTH PLASTIC INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE $EQ TO INDICATE FIELD CHANGES. NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE. UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ARCHITECT. 15. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE 28. THE OWNER RESERVES THE RIGHT TO REVISE THE DRAWING FROM TIME TO TIME TO INDICATE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL CHANGES IN THE WORK. WHEN REVISED DRAWINGS AND/OR ANY REVISIONS ARE ISSUED, THE SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN CONTRACTOR SHALL EVALUATE THE CHANGES PROMPTLY. BEFORE INSTALLATION OF ANY ITEM OR PROPER WORKING ORDER. PERFORMANCE THE WORK INDICATED BY THE REVISED DRAWINGS OR REVISIONS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IN WRITING THAT THE REVISED DRAWINGS INVOLVE AN 16.1. A SEPARATE, GREEN TYPE THW COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF AN ADDITION OR DEDUCTION OF A SPECIFIC AMOUNT OF MONEY TO THE CONTRACT PRICE. THE EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET CONTRACTOR SHALL NDI PROCEED WITH THE REVISED WORK WITHOUT PRIOR WRITTEN APPROVAL BY BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. THE ARCHITECT/ENGINEER OF THE COST OF THE REVISED WORK. 16.2. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND 29. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250-95 OF THE N.E.C. ATTENTION OF THE ELECTRICAL ENGINEER/ARCHITECT/OWNER IMMEDIATELY. IF ELECTRICAL CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. CONTRACTOR PROCEEDS WITH ARY CHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER/ARCHITECT/OWNER WILL NOT BE COMPENSATED. 16.3. GROUND RODS SHALL BE 5/8" DIAMETER, TEN (10) FEET LONG COPPERCLAD STEEL OBTAIN FIVE (5) OHMS MAXIMUM RESISTANCE AS READ WITH A OHM METER, USING TWO REFERENCE RODS. IF FIVE (5) OHMS CANNOT BE ACHIEVED, CONTRACTOR SHALL PROVIDE ADDITONAL RODS, UNTIL FIVE (5) HAS BEEN OBTAINED. 4ole 0/w .�.�� L�� .a UL4I uu V co co cli cri 00 0o 00 Lo O � � r r O � M co OG ° a� S.. C ca ° I.,_ c) m I ul 4 rfir- 00 o� .� w ��N U w O Q X E o m Za Lij .. °' . N N I N F d- 41 � A co O to >.,, o CS$ o W U co UJ m _ c O 0 0 �i N Q CSS tet- w - r o p Q E F F r O E 0U- - cn = 00 a N - 0 0 U ry cn 0 < o <C w ct - Q F o� p u0 < o _ t� w to BT 04 748 E 26 AUG 04 D 0 L. ELECTRICAL SPECIFICATIONS 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE LATEST EDITION 17. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL OF THE NATIONAL ELECTRIC CODE, THE LATEST EDITION OF N.F.P.A., AND THE LATEST EDITIONS EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. OF THE LOCAL CODES AND ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND 18. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. ABOVE MEN110NED CODES. 19. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING 2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE WITH SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL MECHANICAL CONTRACTOR REGARDING SUPPLY AND INSTALLATION OF ALL REQUIRED CONTROLS. BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN THE DISCONNECT SWITCH, FUSE SIZES, CONDUIT AND WIRE SHOWN FOR ALL HVAC ARE SIZED PER 20. HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. THE MANUFACTURER, AND MODEL NUMBER LISTED ON THE MECHANICAL PLANS. IF THERE IS AN EQUAL MANUFACTURER, OR OTHER MANUFACTURER PROVIDED, THE MECHANICAL/ 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST-CLASS GENERAL CONTRACTOR SHALL BEAR ANY ADDITIONAL COST INCURRED IF THE ELECTRICAL WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF IS NOT EQUAL TO SPECIFICATIONS. THIS SYSTEM BY THE ENGINEER/ARCHITECT MUST BE A CONDITION OF THE SUB CONTRACT. 21. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL BE THE PRODUCT OF A SINGLE 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SQUARE "D"; HOWEVER, COMPARABLE EQUIPMENT PROGRESS OF CONSTRUCTION. BY SIEMENS AND CUTLER HAMMER ONLY WILL BE ACCEPTABLE. TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD 21.1. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED TO INSIDE SURFACE OF EACH PANELBOARD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. DOOR, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CIRCUIT PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED. 6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN 21.2. ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED DAMAGED THEREBY. ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING PANEL NAME, VOLTAGE AND AMPERAGE. 7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 22. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE. 8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPEC110NS AND TESTINGS. 23. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL COORDINATE TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND ALL RELATED WORK WITH THE UTILITY COMPANY'S RESPONSIBILITIES TO MEET THE OWNER'S TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. SCHEDULE. 10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL -24. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, RIGID BE #12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH GALVANIZED CONDUIT OR SCHEDULE 40 P.V.C. THERE SHALL BE NO TYPE 'NM', ELECTRICAL THWN/THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #8 NON-METALLIC TUBING, & FLEXIBLE METAL CONDUIT USED FOR BRANCH CIRCUITING. MAXIMUM - AND LARGER TO BE STRANDED. NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR 11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4% GALVANIZED RIGID STEEL CONDUIT OR CONDUCTOR AMPACITY AND CONDUIT FILL NO CONDUITS SHALL BE INSTALLED, EXPOSED ON SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL ROOF. HOSPITAL GRADE MC CABLE SHALL BE USED IN MRI TREATMENT ROOM. IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC 24.1. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: PAINT, KOPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL 208V SYSTEM 480V SYSTEM PHASE SEQUENCE SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR NEUTRAL - WHITE NEUTRAL - WHITE ABC, TOP TO BOTTOM OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. WHERE PHASE A - BLACK PHASE A -- BROWN LEFT TO RIGHT, FRONT SCHEDULE 40 PVC HAS BEEN INSTALLED BELOW GRADE OR SLAB, IT SHALL TRANSITION TO RIGID PHASE B - RED PHASE B - ORANGE TO BACK STEEL AT GRADE TO FIRST DEVICE OR WIREWAY, REGARDLESS OF LOCATION. PHASE C - BLUE PHASE C - YELLOW 11.1 ALL UNDERGROUND SERVICE CONDUITS aACEWAYS ENTERING BUILDING OR STRUCTURE FROM GRD.CON - GREEN GRD.CON - GREEN OUTSIDE TO INSIDE SHALL BE SEALED, INCLUDING SPARE CONDUITS. SEALANT SHALL BE SUITABLE 24.2. WHEN MAIN ELECTRICAL SERVICE HAS A WIREWAY, E.C. SHALL TAP OFF OF ALL SERVICE ENTRANCE FOR THIS USE. FEEDERS (PARALLEL CONDUCTORS) FOR TOTAL AMPACITY & BALANCING. 12. - OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS 25. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE. FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L ASSEMBLY STANDARDS. 13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION 26. CONTRACTOR SHALL PROVIDE SHOP DRAWING SUBMITTALS FOR LIGHT FIXTURES, SWITCHGEAR, PROOF ETC) ENGRAVED LAMINATED PLASTIC IDENIIFICA110N PLATES SHALL BE FURNISHED AND WIRING DEVICES, AND ALL SYSTEMS (FIRE ALARM, SECURITY, ETC.) PROVIDE TWO (2) COPIES, INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. TEN (10) DAYS PRIOR TO BID DATE FOR ENGINEER'S APPROVAL TO SUBMIT. ENGINEERS APPROVAL OF THE PRIOR APPROVAL PACKAGE WILL BE CONSIDERED 13.1. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE FUSES SHALL BE PRELIMINARY. FINAL APPROVAL WILL BE CONTINGENT UPON REVIEW OF FINAL SHOP THOSE MANUFACTURED BY EITHER BUSSMAN OR UTTLEFUSE. THE CONTRACTOR SHALL FURNISH DRAWINGS. ALL PROPOSED ALTERNATES MUST BE INDUSTRY STANDARD EQUALS TO THE ITEMS TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED, FUSES 600 AMPS SPECIFIED AS THE BASIS OF DESIGN; HOWEVER, IF THE ITEMS ARE NOT CONSIDERED EQUAL BY OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL THE ENGINEER, IT SHALL BE DISAPPROVED FOR FINAL SUBMITTAL IF ELECTRICAL CONTRACTOR/ BE CLASS L GENERAL CONTRACTOR DOES NOT SUBMIT SHOP DRAWINGS TO ELECTRICAL ENGINEER FOR ITEMS - LISTED ABOVE, ELECTRICAL ENGINEER WILL NOT BE RESPONSIBLE FOR ANY, AND OR OMISSIONS 14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE OR ERRORS DUE TO SHOP DRAWINGS NOT SUBMITTED. SHOP DRAWINGS WILL ONLY BE REVIEWED MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY TWICE AS PART OF THIS CONTRACT. ADDITIONAL SHOP DRAWING REVIEWS SHALL BE INVOICED PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND AT $85.00 PER HOUR, BILLABLE TO THE SUB -CONTRACTOR, C.O.D. PLATES SHALL BE DICTATED BY ARCHITECT/OWNER. 27. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH A. SWITCHES: LEVITON #CSB1-201 COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO B. RECEPTACLES: LEVITON R20 -I BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. ` EVERY UNIT OF #B EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE GREEN TO C. COVER PLATES: SMOOTH PLASTIC INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE $EQ TO INDICATE FIELD CHANGES. NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE. UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ARCHITECT. 15. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE 28. THE OWNER RESERVES THE RIGHT TO REVISE THE DRAWING FROM TIME TO TIME TO INDICATE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL CHANGES IN THE WORK. WHEN REVISED DRAWINGS AND/OR ANY REVISIONS ARE ISSUED, THE SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN CONTRACTOR SHALL EVALUATE THE CHANGES PROMPTLY. BEFORE INSTALLATION OF ANY ITEM OR PROPER WORKING ORDER. PERFORMANCE THE WORK INDICATED BY THE REVISED DRAWINGS OR REVISIONS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IN WRITING THAT THE REVISED DRAWINGS INVOLVE AN 16.1. A SEPARATE, GREEN TYPE THW COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF AN ADDITION OR DEDUCTION OF A SPECIFIC AMOUNT OF MONEY TO THE CONTRACT PRICE. THE EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET CONTRACTOR SHALL NDI PROCEED WITH THE REVISED WORK WITHOUT PRIOR WRITTEN APPROVAL BY BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. THE ARCHITECT/ENGINEER OF THE COST OF THE REVISED WORK. 16.2. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND 29. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250-95 OF THE N.E.C. ATTENTION OF THE ELECTRICAL ENGINEER/ARCHITECT/OWNER IMMEDIATELY. IF ELECTRICAL CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. CONTRACTOR PROCEEDS WITH ARY CHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER/ARCHITECT/OWNER WILL NOT BE COMPENSATED. 16.3. GROUND RODS SHALL BE 5/8" DIAMETER, TEN (10) FEET LONG COPPERCLAD STEEL OBTAIN FIVE (5) OHMS MAXIMUM RESISTANCE AS READ WITH A OHM METER, USING TWO REFERENCE RODS. IF FIVE (5) OHMS CANNOT BE ACHIEVED, CONTRACTOR SHALL PROVIDE ADDITONAL RODS, UNTIL FIVE (5) HAS BEEN OBTAINED. 4ole 0/w .�.�� L�� .a UL4I uu V co co cli cri 00 0o 00 Lo O � � r r O � M co OG ° a� S.. C ca ° I.,_ c) m I ul 4 rfir- 00 o� .� w ��N U w O Q X E o m Za Lij .. °' . N N I N F d- 41 � A co O to >.,, o CS$ o W U co UJ m _ c O 0 0 �i N Q CSS tet- w - r o p Q E F F r O E 0U- - cn = 00 a N - 0 0 U ry cn 0 < o <C w ct - Q F o� p u0 < o _ t� w to BT 04 748 E 26 AUG 04 D 0 L.