HomeMy WebLinkAbout18-19417 CITY OF ZEPHYRHILLS
5335-8TH STREET
(813)780-0020 1
BUILDING PERMIT
= PERMIT INFORMATION LOCATION INFORMATION
Permit Number: 19417 Address: 5714 19TH ST
Permit Type: ADDITION/ALTERATION ZEPHYRHILLS, FL.
Class of Work: 434-ADD/ALT RESIDENTIAL Township: Range: Book:
Proposed Use: NOT APPLICABLE Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est. Value: Parcel Number: 11-26-21-0010-07800-0090
Improv. Cost: 19,179.00 OWNER INFORMATION
Date Issued: 3/12/2018 Name: KINGERY, KARL & FAY
Total Fees: 277.50 Address: 5714 19TH ST
Amount Paid: 277.50 ZEPHYRHILLS, FL. 33542
Date Paid: 3/12/2018 Phone: (813)715-2810
Work Desc: INSTALL SOLAR PHOTOVOLTAIC SYSTEM
CONTRACTORS APPLICATION FEES
SUN-T.E.0 BUILDING FEE 210.00
SUN-T.E.0 ELECTRICAL FEE 67.50
/ r
L
Ins ections Required
FOOTER 2ND R GH PLUMB MI C INSULATION CEILING
FOOTER BOND DUCTS INSULATED SEWER MISC.
ROUGH ELECTRIC LINTEL MISC MISC.
1ST ROUGH PLUMB PRE-METER INSULATION WALL MISC.
DUCTS INSTALLED WATER MISC DRIVEWAY
PRE-SLAB SHEATHING MISC. MISC.
CONSTRUCTION POLE FRAME MISC. MISC.
REINSPECTION FEES: (c)With respect to Reinspection fees will comply with Florida Statute 553.80 (2)(c)the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection,whichever is greater,for each such subsequent reinspection.
NOTICE: In addition to the requirements of this permit, there maybe additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permits required from other governmental
entities such as water management, state agencies or federal agencies.
"Warning to owner: Your failure to record a notice of commencement may result in your paying twice for
improvements to your property. If you intend to obtain financing,consult with your lender or an attorney
before recording your notice of commencement."
Complete Plans, Specifications Must Accompany Application. All work shall be performed in accordance with
City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
CONTRACTOR SIGNAT PERMIT OFFI R
PERMIT EXPI ES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
Date Received Phone Contact for Permitting = 571 _ 4141
Tr rrrr
Owners Name Karl&Fay Kingery Owner Phone Number 813-479-8244
Owners Address 1 5714 19th St.,Zephyrhills, FL.33542 Owner Phone Number
Fee Simple Titleholder Name I Owner Phone Number
Fee Simple Titleholder Address
JOB ADDRESS 5714 19th St. LOT# 9-11
SUBDIVISION City of Zephyrhills PARCEL ID# 11-26-21-0010-07800-0090
(OBTAINED FROM PROPERTY TAX NOTICE)
WORK PROPOSED e NEW CONSfR B ADD/ALT = SIGN = = DEMOLISH
INSTALL REPAIR
PROPOSED USE = SFR 0 COMM = OTHER
TYPE OF CONSTRUCTION = BLOCK 0 FRAME = STEEL =
DESCRIPTION OF WORK Install solar photovoltaic system
BUILDING SIZE SO FOOTAGE= HEIGHT
=BUILDING $19 079.00 VALUATION OF TOTAL CONSTRUCTION
=ELECTRICAL '100.00 AMP SERVICE = PROGRESS ENERGY = W.R.E.C.
i
=PLUMBING $ +
/
=MECHANICAL $ VALUATION OF MECHANICAL INSTALLATION
=GAS = ROOFING 0 SPECIALTY = OTHER
FINISHED FLOOR ELEVATIONS FLOOD ZONE AREA =YES NO
BUILDER •► �11 8 COMPANY• • LSCI, InC.
SIGNATURE REGISTERED Y/ N FEE CURREA Y/N
Address 4625 East Bay Dr.#305,Cle rwater,FL.33764 License# I CVC056656
ELECTRICIAN SC
C A NY LI, Inc.SIGNATURE d q REGISTERED I Y/ N I FEE CURREN Y/N
Address 4625 East Bay Dr. 05, earwater,FL.33764 License# EC13001300
PLUMBER COMPANY
SIGNATURE REGISTERED I Y/ N FEE CURREN I Y/N
Address License#
MECHANICAL COMPANY
SIGNATURE REGISTERED I Y/ N FEE CURREN, Y/N
Address License#
OTHER COMPANY
SIGNATURE REGISTERED I Y/ N FEE CURREN Y/N
Address License#
Iltttltllllttlllllllllltlttltllttltttttttltttltllttltllltlttltltlll
RESIDENTIAL Attach(2)Plot Plans;(2)sets of Building Plans;(1)set of Energy Forms;R-O-W Permit for new construction,
Minimum ten(10)working days after submittal date. Required onsite,Construction Plans,Stormwater Plans w/Silt Fence installed,
Sanitary Facilities&1 dumpster,Site Work Permit for subdivisions/large projects
COMMERCIAL Attach(3)complete sets of Building Plans plus a Life Safety Page;(1)set of Energy Forms.R-O-W Permit for new construction.
Minimum ten(10)working days after submittal date. Required onsite,Construction Plans,Stormwater Plans w/Silt Fence installed,
Sanitary Facilities&1 dumpster.Site Work Permit for all new projects.All commercial requirements must meet compliance
SIGN PERMIT Attach(2)sets of Engineered Plans.
****PROPERTY SURVEY required for all NEW construction.
Directions:• ��
Fill out application completely.
Owner&Contractor sign back of application,notarized
If over$2500,a Notice of Commencement is required. (A/C upgrades over$7500)
Agent(for the contractor)or Power of Attomey(for the owner)would be someone with notarized letter from owner authorizing same
OVER THE COUNTER PERMITTING (Front of Application Only)
Reroofs if shingles Sewers Service Upgrades A/C Fences(Plot/Survey/Footage)
Driveways-Not over Counter if on public roadways..needs ROW
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to"deed"restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or
contractors to undertake work,they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work,they are advised to contact the Pasco County Building Inspection Division—Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the"contractor Block"of this application for which they will be responsible. If you, as the owner sign as the
contractor,that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
TRANSPORTATION IMPACT/UTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings,change of
use in existing buildings, or expansion of existing buildings, as specified in Pasco County Ordinance number 89-07 and
90-07, as amended. The undersigned also understands,that such fees, as may be due,will be identified at the time of
permitting. It is further understood that Transportation Impact Fees and Resource Recovery Fees must be paid prior to
receiving a"certificate of occupancy"or final power release. If the project does not involve a certificate of occupancy or
final power release, the fees must be paid prior to permit issuance. Furthermore, if Pasco County Water/Sewer Impact
fees are due,they must be paid prior to permit issuance in accordance with applicable Pasco County ordinances.
CONSTRUCTION LIEN LAW(Chapter 713,Florida Statutes,as amended): If valuation of work is$2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law—Homeowner's
Protection Guide"prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the"owner",I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the"owner"prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and that all work
will be done in compliance with all applicable laws regulating construction,zoning and land development. Application is
hereby made to obtain a permit to do work and installation as indicated. I certify that no work or installation has
commenced prior to issuance of a permit and that all work will be performed to meet standards of all laws regulating
construction, County and City codes, zoning regulations, and land development regulations in the jurisdiction. I also
certify that I understand that the regulations of other government agencies may apply to the intended work,and that it is
my responsibility to identify what actions I must take to be in compliance. Such agencies include but are not limited to:
- Department of Environmental Protection-Cypress Bayheads, Wetland Areas and Environmentally Sensitive
Lands,Water/Wastewater Treatment.
- Southwest Florida Water Management District-Wells, Cypress Bayheads, Wetland Areas, Altering
Watercourses.
Army Corps of Engineers-Seawalls,Docks,Navigable Waterways.
Department of Health & Rehabilitative Services/Environmental Health Unit-Wells, Wastewater Treatment,
Septic Tanks.
US Environmental Protection Agency-Asbestos abatement.
Federal Aviation Authority-Runways.
I understand that the following restrictions apply to the use of fill:
Use of fill is not allowed in Flood Zone"V"unless expressly permitted.
If the fill material is to be used in Flood Zone "A", it is understood that a drainage plan addressing a
"compensating volume"will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida.
If the fill material is to be used in Flood Zone "A" in connection with a permitted building using stem wall
construction,I certify that fill will be used only to fill the area within the stem wall.
- If fill material is to be used in any area, I certify that use of such fill will not adversely affect adjacent
properties. If use of fill is found to adversely affect adjacent properties,the owner may be cited for violating
the conditions of the building permit issued under the attached permit application,for lots less than one(1)
acre which are elevated by fill,an engineered drainage plan is required.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate,cancel,alter, or
set aside any provisions of the technical codes,nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans,construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six(6)months after the time the work is commenced. An extension
may be requested, in writing,from the Building Official for a period not to exceed ninety(90)days and will demonstrate
justifiable cause for the extension. If work ceases for ninety(90)consecutive days,the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING,CONSULT
WITH YOUR LEND OR AN ATTORNEY BEFORE RECORDING YO NOTICE OF COMME EMENT.
FLORIDA JURAT(F. 1 .03)
OWNER OR AGE CONTRACT
Subscribed and m ( ra ed) of re met s S scribe o irme of-e- his
by , Z
Who is/are personally known to me or has/have produc Wh are so al kn n to me or has/have produced
as identification. C C(4- as identification.
Notary Public Notary Public
_ .a..
Commission No. -----•"" ComrilN"a3r_�
} 4,15l• •I Pr.� .S
Name=of'Notary typed,printed or stamped Name of Notary typed, 51,� bt�mpEkpires December 12,2018
,'4,,q 6�,,.`° Bonded Thru Tray Fdn Inenr®nea$00.385.7019
2018041288
Acpt:1938889 Rec: 10.00
Permit Number DS: 0_00 IT: 0.00
Parcel ID Number 03/12/2018 K. K. , Dpty Clerk
NOTICE OF COMAENCEMENT
State of Florida THIS AREA IS RESERVED FOR CLERK OF THE COURT CERTIFICATION
County of Pinellas
THE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with Section 713.13 of the
Florida Statutes,the following information is provided in this NOTICE OF COMMENCEMENT.
I.Description of property(legal description): 62:h tv-26PJ-Icrz A ti-c RZ, IPA_<q Lo,75 I Fa 1( Mta=3tog,79 eg-9y2.3 ?A
a)Street(job)Address: r71G( /00,5T, z_r,
9
2.General description of improvements: //,I 4QLJ*f2.__' V6ZJ-JqfC_,$
3.Owner Information or Lessee information if the Lessee contracted for the improvement:
a)Name and address:
b).Name and address of fee simple titlehiSider(if differeAt than'Owner listed above) 1
c)Interest in property:
4.Contractor Information
a),Name and address: LSCI,Inc.4625 East Bay Dr.,Ste.305,Clearwater,FL 33764
b)Telephone No.: 727-571-4141 Fax No.:(optional) 7i7-540-0804
5.Surety(If applicable,a copy of the payment bond is attached)
a)Name and address:I -.,AULA S-O'NEIL,Ph.D.PASCO CLERK & COMPTROLLER
b)Telephone No.: 03/12/2018 01-39 1 of 1
c)Amount of Bond: OR BK 969 f' P6 230
6.Lender
a)Name and address:
b)Telephone No.:
7.Persons within the State of Florida designated by Owner upon whom notices or other documents may be served as provided by Section
713.13(1)(a)7..,Florida Statutes:
a)Name and address:
b)Telephone No.: Fax No.:(optional)
8.a.In addition to himself or herself,Owner designates of
to receive a copy of the Lienor's Notice as provided in Section 713.13(1)(b),Florida Statutes.
b)Phone Number of Person or entity designated by Owner:
9.Expiration date of notice of commencement(the expiration date may not be before the completion of construction and final payment to the
contractor,but will be I year from the date of recording unless a different date is specified): 20
WARNING TO OWNER:ANY PAYMENTS MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICE OF COMMENCEMENT ARE
CONSIDERED IMPROPER PAYMENTS UNDER CHAPTER 713,PART 1,SECTION 713.13,FLORIDA STATUTES,A'ND CAN RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY.A NOTICE OF COMMENCEMENT MUST BE RECORDED AND POSTED ON
THE JOB SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN
ATTORNEY BEFORE COMMENCING WORK OR RECORDING YOUR NOTICE OF COMMENCEMENT.
Under penalty of perjury,I declare that I have read the foregoing notice of commencement and that the facts stated.therein are true to the best of MY
knowledge and belief.
RG ,\9A
,gnature-6f Owner or Less(M)or Ohner's or Lessee's(Authorized Officer/Director/Partner/Manager) '(Print Name and Provide SIgnatory's Titte/Office)
T f 'going instrument day of ��4yq 20/,4�g
The ent was acknowledged before me this 5Lf .
by Will X1_ K 1,qc� g4 as ,)A 1,6 I(L— (type of at e.g.officer,trustee,attorney in fact)
for as
(Name of Person) (type of authority,...e.g.officer,trustee,attorney in fact)
for (name of(name of beh f w:h instry instrument was executed).
Personally Known ❑ Produced ID �m
Type of ID Notary Signature
Print name
CHRISTIAN C I
Commission#FF 915:405
"P Sj
My Commission Ex 'i"'s 0
Mcirch 24, 2020
` .
'
~ / OF FLOR�K\ COUNTY OF PASCO
- -\--TOCEF���Y � THE FOREGOING|SA
''-
TRUE AND CORRECT COPY OF THE DOCUMENT
UN FILE OROF PUBLIC RECORD\N THIS OFFICE
WITNESS MY HAND AND OFFICIAL SEAL THIS
.. ;'r
City of Zephyrlulls
BUILDING PLAN REVIEW COMMENTS
MMENTS
Contractor/Homeowner: k S CI 1h G
Date Received: ��zzz/,q-
Site: 66 y
Permit Type:
Approved w/no comments: Approved w/the below comments: ❑ Denied w/the below comments: ❑
This comment she shall be kept with the permit and/or plans.
f f�
K vin S er—Plans Examiner Date Contractor and/or Homeowner
(Required when comments are present)
I
i
LSCI Inc.
4625 East Bay Dr. #305
Clearwater, FL 33764
727-571-4141
Attn: All jurisdictions in the State of Florida
To whom it may concern,
I, Douglas Dankner, License#EC13001300,do hereby authorize Corey Weaver, Donald Nicholson,
Christian Corpe, Michael Dunlap and Marcus Marnell to register my license,sign for, drop off and pick
up my permits on my behalf.This letter supersedes and replaces any previous authorizations.
Sincerely,
Douglas Dankner
Notary Seal
Si a u e of Notary
Sw rn and subscribed before me this day of
X 20A
if Vnh, orld LrLc� ( ] Personally Known
Printed am Ne [ roc
Identification
Kimberly Grove
COMMISSION # FF191670
January 2i,
OFFt �` wxww.AARONNOTARY COOM,
nnua
LSCI Inc.
4625 East Bay Dr.
Clearwater, FL 33764
I
727-571-4141
Attn: All jurisdictions in the State of Florida
To whom it may concern,
I, Raymond Mead, License#CVC056656,do hereby authorize Corey Weaver,Christian Corpe, Donald
Nicholson, Michael Dunlap and Marcus Marnell to register my license, sign for,drop off and pick up my ,
permits on my behalf.This letter supersedes and replaces any previous authorizations.
Sincerely,
Raymond Mead
NEE
State of Florida
RTES
n GG 136238
/2021
Notary Seal
Signature of Notary
Sworn and subscribed before me this A day of
20
[ personally Known
[ ] Produced Identification
5.3KW Grid Interactive Photovoltaic System
System Summary
Provided by Sun-Tec
Project: Kingery, Karl
I
Verdiseno,Inc.,its subsidiaries,officers,directors,employees and its suppliers specifically disclaim any Implied warranties or representations that the information contained in this document
('Document")is complete or error-free.This Document is not provided as an engineering service and Verdiseno,Inc.is not an engineering firm.This Document is provided as an aid to those involved in
the potential purchase or installation of a PV system,and is meant to facilitate the production of a final PV system design('Design')by a qualified professional.This document does not contain enough
information to fully represent a system design and should not be relied upon to perform an installation.If you require a Design that has been produced or approved by a qualified engineer,please be
advised that you MI need to hire a qualified engineer to produce or approve the needed Design and related documents.Please refer to the Terms and Conditions page at solardesigntool.com for the full
Terms and Conditions agreement
I. System Summary
M. System Data
1.1.1. Summary
Location Info
Project Site 571419th St,Zephyrhills,FL 33542
Climate Data Source Location Zephyrhills,FL 33542 United States
Latitude 28'14'N
Longitude 82°10'W
Design Low Temperature 34°F(1°C)
Design High Temperature 93°F(34-C)
Electrical Characteristics -
Summary
Inverter SE5000H-US
Module Q-Cells Q.PEAK BLK-G4.1 295(295W)
Number of Modules 18
Array Circuits 1 string of 18
STC power of array 5,310W
PTC power of array 4,893W(1)
DC String Operating Currents 13.97A
DC String Max Currents 15A
DC String Operating Voltage 380V
Number of Strings 1
CEC power output 4,786W(1)
Max AC output current 21A
First-Year PV Watts Prod.Estimate 7,672kWhr
1.PTC rating calculated using 45°C as the NOCT(Nominal Cell Operating Temperature)
I
t ,
F
• "
.:L
' Ff .
1.2.1. South
Installation Area
Installation area length 66.51ft
Installation area width 24ft
Slope 4/12(18.4°)
Installation area azimuth 179.4°(SE)
Configured Layout
Column spacing 0.25in
Row spacing 1 in
Module orientation portrait
Distance between tilted racks tin
Tilt angle of modules 0.
Clearance at left 1.61in
Clearance at right 1.611n
Clearance at top 11.39in
Clearance at bottom Oft
Total number of modules 18
Total number of rows 1
Layout length 59.41ft
Layout width 64.85in
Area of array 32156ft=
Max.Values for Installation Area
Max no.of modules 54
Maximum no.of rows 3
Max no.of modules in a row 18
Maximum row length 59.41ft
Maximum column length 16.38ft
Area if layout full 977.84ft2
20
N\M
NOA
2. System Design Calculations Report (Non-Code)
2.1. PV Source Circuit Voltage Range Test
This test confirms that the voltage of the PV Source Circuit will always remain within the DC input voltage window of the system's inverter,
microinverters,or power optimizers.
2.1.1.(1)Q.PEAK BLK-G4.12%(295"in series
Section Properties Validation Tests
Description (1)Q.PEAK BLK-G4.1 295(295W) The minimum Vmp must exceed the minimum PASS
in series input voltage of the connected device
Connected Device Solar Edge P320
Connected Device Type Power Optimizer 27.31V>8V=true
Design Low Temp. 1°C The maximum Voc must not exceed the.max input PASS
Desi n Hi h Temp. 340C voltage.of the connected device
Module Q.PEAK BLK-G4.1 295 295W 42.14V<48V=true
Module Vmp 32.19V
Module Voc 39.48V
Power Optimizer Min.Input Volta a 8V
Power Optimizer Max.Input Voltage 48V
Mounting Method Flush Roof Mount
Temp.Coefficient Voc -0.111V/C
Voltage Loss Due to Degradation 0.0
derate
Voltage Loss Due to Tolerance 0.0
derate
calculations
A. String Voc at Low Temperature 42.14V
The module Voc(39.48V)will increase to 42.14V at the design low
temperature(1°C).
(1°C-25°C)X-0.111 V/C+39.48V=42.14V
The total Voc for the string is 42.14V.
42.14V X 1=42.14V
B. String Vmp at High Temperature 27.31V
Estimated cell temperature equals the design high temperature(34°C)
plus 35°C(the estimated difference between ambient temperatures and
the cell temperature for a flush roof mount).
34°C+35°C=69°C
The module Vmp(32.19V)will drop to 27.31 V at the design high
temperature(34°C).
(69°C-25°C)X-0.111 V/C+32.19V=27.31 V
The total Vmp for the string is 27.31V.
27.31VX1=27.31V
RSTC Enterprises Inc
2214 Heimstead Road
Eau Claire, WI54703 LADECK
715-830-9997r-
Outdoor Pass thru enclosure: Model - 0786-313 5
Asphalt/Cedar Roof Systems
For AC or DC current - -- -- -- - -
ETL Listed and labeled to UL standards
Report#3125796 CRT-001 b Revised March 201277.
�"
. .
• UL50 Type 3R, 11 Edition Electrical i !
equipment enclosures
• CSA C22.2 #94-M91 special purpose
enclosures (2006) s
Cam ® di1 ® (opi�
£3:
Basic specifications • ;
Material- 18 Gauge G 90 Steel Base/Cover
Process- Seamless draw(stamped)
Flashing- 15" x 15"
Height- 2.626"
Cavity- 8"x 9" x 2.5" (162 Cubic inches)
Finish- Powder coat(1100 hours salt spray) SOLAaECK OT$6-3R5
Assembly: J
• Cavity Base and cover punched for matched assembly
• Base Flashing pre-punched for roof deck mounting -
• Cavity Base- (5)predetermined dimples
for fittings or conduit - -'
E.hown 2 Circ:uit AC P'Fass TY'1ru
Base plate: —" .••. '. _.
• 16 gauge galvanized steel anize
• Fastened to base flashing with toggle fastening system
• Finish- Powder coat(1100 hours salt spray)
• (5) Roof deck knockouts
• Knockout sizes-(3).5",(1).75"and(1)1"
• Rail-7"slotted 35mm _
Ground-Installed with steel stud and star nut �i •
(5) Position for wire size 14-6 ,
}- ,
Strain Relief Clip-Aluminum riveted installation £:
Hardware pack:
7- 1" Truss head screws
4-.5" 8-32 thread cutting screws --s
4-Bonded seal washers#10
2-10-32'/2" Steel studs
2-10-32 3/8"steel star nuts
1 -Foam Foam gasket seal
With 2 circuit AC pass thru kit
1 -Installation instructions Kit Part # 01612
*** Kit sold separately
EiCHNI A
KALT, 74
INN
3 O
PROFESSIONAL
30() GRADE POLYURETHANE SEALANT
1. PRODUCT NAME: Grade:Gun grade consistency
33000 Professional
Grade Polyurethane Sealant Primer:Not required on most
surfaces
2.MANUFACTURER:Geocel Products Group g'
Packa9 fn 10.111.oz.cartridges
Colors:White,
A Business Unit of � gray,limestone,
The Sherwin-Williams Company bronze,medium bronze,tan,
aluminum gray,black,and
("Geocel Products Group")
redwood tan
Cleveland,OH 44115 Application Standards: Meets
Phone:(800)348-7615 ASTM C 920 Type S,Grade NS,Class
Fax:(800)348-7009 25,Use NT,A,M,G,and 0;Meets
www.GeocelUSA.com Federal Specification TT S-0230 C,
0f`' . Type II,Class A;Meets Canadian
3. PRODUCT DESCRIPTION: Specification CAN/CGSB-19.13-M87
Polyurethane
Professional Grade
Sealant is a single F Class 2 Non-sag,Class 25,Class M.
component,high performance f� � Limitations:
polyurethane sealant that withstands •Do not apply over damp or
extreme weather conditions and cures RET"JE contaminated surfaces
Iirt40o Fnor•Esoxil
to a flexible weatherproof seal. R nE P •Do not apply to absorptive
Product Benefits: surfaces such as marble,
•Withstands extreme weather conditions °,yr limestone,or granite without prior
•Meets ASTM C 920 + 3 testing for discoloration or staining
•Moisture cure
•Flexible 4. INS T ALLATION:
•Minimal shrinkage Joint Design:The width of the joint
•Non-sag formula should be a minimum of 4 times the
•Primerless adhesion on most surfaces anticipated movement.In joints up to
•Paintable,non-corrosive 1/2"wide,the depth of the sealant
•Contains no TDI(toluene diisocyanate) should be equal to the width,but not
less than 1/4". In joints wider than
Basic Uses:3300 Sealant can be 1/2",the depth should be maintained
used in roofing applications such as , at 5/8".Lap shear joints should have a
concrete roofing tile,clay roofing tile, width of at least twice the anticipated
metal roofing, Kynar 5009 coated movement.
metal,and composition shingles. Surface Preparation:Joints to
Other applications include building receive sealant must be sound,
lath paper repair,gutters, seamVAC, Adheres To:Mason ceramics,wood, smooth,uniform in dimensions,and
flashing,skylights,roofing seams, Masonry,
roofing pra)'ectlons,termination steel,Kynar 50W1,aluminum,asphalt free from defects and foreign material.
points,and vents. shingles,building paper,BUR,concrete, They must be clean,dry,and free of
fiberglass,and other common building frost and all contaminants,such as
substrates. curing compounds,sealers
(waterproofing),coatings,etc.Sealant
THERE 15 A DIFFERENCE g
o Wye
FIGURE 2 FIGURE 3 s
FIGURE i LSILICCI�N
HANE
Proper Depth Control Joints without Bond Breaker Joints with Bond Breaker • • •
The effects on the sealant with and without bond breakers are illustrated in Figures Two and Three.
Kynar 5OV is a registered trademark of Arkema Inc.
, .
adhesion should be tested on eachRESPIRATOR failure,and as your solEfremedr,we
different substrate prior to caulking.To MAY BE EFFECTIVE.Follow directions will either replace the product at no
test adhesion,apply a sealant bead for respirator use.Wear the respirator for cost or refund the original purchase
and allow to cure thoroughly.Then pull the whole time until all vapors are gone. price for that portion of product that
one end m the bead oo test adhesive If you have any breathing problems fails to perform accordance with
strength. dudnguse,LEAVE THE AREA and g�d 1hiaUm -warranty.
Labor costsJoint BackinJoint depth should not fresh i/^|fproblemsremainorhappon omao���d�dh|ubcvomano1 exomod5/8" An open cell backer rod later,IMMEDIATELY call adoctor If not included.THIS LIMITED
should bo usedhu controlioimddepth. o»m|abVe getemergency medical WARRANTY|S|N LIEU OFALL
t�|n shallow/n|nbundbmmkortope �eaLmorVHeve�he|obe|withyou
---a ' ' OTHER EXPRESS
should be|D�aU8dtop� '-m8n� AU �pVGnU|g�onoaqu|�dwhan `
three-point contact. sanding
- robradinOthedhod0m'|f OR IMPLIED,INCLUDING
Elongation:881% adequate ventilation cannot beprovided MERCHANTABILITY,WHICH ARE
i ALL D}GCLA/&4EDAND/OR
Tack Free:3houm `-~' -'~,''-'--,------�--
(N|OGHa Follow respirator LIMITED|N DURATION TOTHE
Cure:1day manufacturer's directions for respirator EXTENT PERMITTED BY LAW.VVE
Service Temperature: use.IRRITATES SKIN AND EYES.Avoid SHALL NOT 8E LIABLE FOR
-20"Ftu150"F(-28"C0o06"q contact with eyes and skin, |n case of INDIRECT,SPECIAL,INCIDENTAL
Application Tem bmrn: eye uont�� 0uahimmedi�e�with OR CONSEQUENTIAL DAMAGES
��"-80"Fto150"F(-29"Chm86°O) �enh/ufwa�r for 15minutes (INCLUDINGLOGT
PROFITS)
and FROMANY CAUSE WHATSO
EVER
Application andTb |i h emergency medicaltmatnent,(n«aseo[ AND SUCH DAMAGES ARE
conventional caulking } ent pU| skin contact,wash thoroughly with soap EXPRESSLY EXCLUDED. Some
joints from the back to prevent voids and water.Clothes contaminated bya states do not allow the exclusion or
and air pockets, If application spillshould b removed and l underad limitation o[incidental m
temperature is below 40^Fcontainer closed when not in use. consequentialdam how long
precautions should um taken ozensure Reacts with water in closed container tn an implied warranty lasts,sothe
the substrates completely d nd produce pressurewhich m ouuoa above limitation ov exclusion may
frost free.Immediately after application, co/duinarhzbunt. Donct transfer notap | to you,This limited
tooling is recommended 0m ensure firm, contents to other containers for storage. warranty gives you specific l ga|
full contact with the joint sides. First Aid:|n case uf eye contact,flush rights,and you may also have other
Cleaning.Remove 3300 Sealant from thoroughly with large amounts ufwater. rights which vary from state t«
gun and toolsbefore b cures.This may Get medical attention ifirritation »iota'
be done by scraping and use of persists.If swallowed,call Poison
solvents such as Xylol. Rdbw � - 7' MAINTENANCE:
manufacturer's instructions for safe mom or h iia immediately.
U sealant iu damaged and the bond
use.Cured materials may beremoved DELAYED EFFECTS FROM LONG \o intact,cut out the damaged area
by cutting with sharp tools o, TERM OVEREXPOSURE.Abrading or and recauk.N primer is required.
oomdPaPehmQ. sanding mf the dry film may release |f the bond has been affected,
Storage and Shelf Life,U-�- ad n�amUinosiUcnwhich has been shown mmovethe no�ant,clean and
containers should be to uamae|mn0dmmagoandroncp under prepare the)o\nLinaccordance
heat,moisture,ondrau� |oo� |ongbenno«pnnune. wdhthe ino�ucUonsunder
' direct- �' - '-' "Su�aooPmpa�dun'"ondmc�uU�
open nont�namund)�| m preparatory Warnin�This pmductcontains
work has been completed.Material in chemicals known to the state of 8 T��HN|��L��R���E�'
uno�onedcontanernisuoob|ah�up Qdihxniotmcauaaounmxondt��h ' '
� 8eoo�{Pmduota8mup
to1 year when��o�dsd75°F(2S"{). defects or other ny m 'reproductive DO Cautions: NOT TAKE}NTERNALL�KEEP OUT OF '�p'=^=n�g�uethmu throughout ~U.S'
' THE are pr
ovide
AUPHATkCPOLY|GOCYANATE ' assistance.G000elPmduo+a
HEXAK0ETHYLENEOU8OCYANAJE
' Gr--'hin-house
�chnica|�u#
AROMATIC and laboratory facilities are
POLYMETHYLENE POLYPHENYL 5 /����LA�|�|TYAN�}(�Q8�
^ bomapnnd
/GOCYANAIE W)ETHYLENED�PH�NYL Available equippedto specific' requests for further information
DUSOCYANAJE.CRYSTALLINE SILICA hardware stores,home centers, and/or applications testing.
VAPOR HARMFUL Gives off harmful construction material and industrial
vapor ofsolvents andi mtem DO distributors.Cost and further
NOT USE|F YOU HAVE CHRONIC technical data are available from your THEORETICAL YIELD
(LONG-TERM) NGOABREATHING local Geooel Products Group Per 1».1«'oz.Cartridge
PROBLEMS,OR IF you HAVE EVER pso»t��eorYnomo«ro�»a� umm Linear Feet
HAD A REACTION TO|SOCYANATEG. 24.1
USE ONLY WITH ADEQUATE 1/4"x3/8^ 18.0
VENTILATION.A POSITIVE PRESSURE 6. LIMITED WARRANTY: 1/4"x1/2" 12.8
AIR SUPPLIED RESPIRATOR 8NK}GH |��hanop applied md�gio|aho| 1t2`«&0" 0'4
` 1/2"x1/2" 6O
SHOULD 8EVVORNTO d\��| this product f�|uto 3/4"x1/2" 4~
-
PREVENT EXPOSURE.!F perform in accordance withita
UNAVAILABLE,AN published literature, F� o��uoo/product
PROPERLYF[TTEDAPPR0VEON|OSH - For additional'-- - information,
satisfactory evidence ofproduct refer<o the product spec sheet
located ot=wv:G,o e1U0A.00s
Cleveland,nw ^°s
��o4��n^epvmm��/�» Atikj� ���:�m��p=��
oem^nmeoo^dom` ���.�r ,wwmoamwuaxxnm ���11 --'11- on*
-
E-Mount Installation Instructions
Installation Tools Required:tape measure,roofing bar,chalk line,stud finder,caulking gun,sealant compatible with roofing materials,
drill with 7/32"long-style bit,drill or impact gun with 1/2"deep socket.
WARNING:Quick Mount PV products are NOT desicIned for and should NOT be used to anchor fall Drotection eaumment.
1st course
Locate,choose,and mark centers of rafters to be Carefully lift composition roof shingle with roofing Insert flashing between 1st and 2nd course.Slide
mounted. Select the courses of shingles where bar,just above placement of mount.Remove nails up so top edge of flashing is at least 3/4"higher
mounts will be placed. as required.See"Proper Flashing Placement" on than the butt-edge of the 3rd course and lower
next page. flashing edge is above the butt-edge of 1 st course.
Mark center for drilling.
d course
Using drill with 7/32"bit,drill pilot hole into roof Clean off any sawdust,and fill hole with sealant Slide flashing into position. Prepare hanger bolt
and rafter,taking care to drill square to the roof. compatible with roofing materials. with hex nut and sealing washer. Insert into hole
Do not use mount as a drill guide.Drill should be and drive hanger bolt until QBlock stops rotating
'long style bit,aka'aircraft extension bit'to drill a easily.Do NOT over torque.
3"deep hole into rafter.
You are now ready for the rack of your
choice. Follow all the directions of
the rack manufacturer as well as the
module manufacturer.
All roofing manufacturers' written
' . instructions must also be followed
by anyone modifying a roof system.
ConsuItthe roof manufacturer's specs
and: instructions prior to touching
the roof.
_.
Insert EPDM rubber washer over hanger bolt into Using the rack kit hardware, secure the racking
block. (L-foot) to the mount using torque specs from
racking manufacturer.If racking manufacturer does
not specify torque setting,tighten to 13 ft:lbs.
BI 7.2.3-26 May-2017 Rev 6
E-Mount I OMSE
Elevated Water Seal Technotogyo
�--- --- - - - -- - ITEM ---- ---- --- ----- ----- ------1
THIS EDGE TOWARDS ROOF RIDGE NO DESCRIPTION QTY.I
1 FLASHING,ROUNDED CORNERS, 9"X 12"X 1
.040",5052,MILL
2 QBLOCK,CLASSIC,A360 CAST AL,MILL 1
I
HANGER BOLT,PLAIN CENTER,5/16"x 6",
3 18-8 SS 1
4 WASHER,SEALING, 5/16"ID X 3/4"OD, 1
EPDM BONDED SS
RACKING COMPONENTS 5 NUT,HEX,5/16-18,UNC-213,18-8 SS 2 I
NOT INCLUDED
6 WASHER,FLAT,19/64"ID x 7/8"OD x 1/8" 1
EPDM
5 7 WASHER,FENDER,5/16"ID X 1"OD,18-8 SS 1
12.00 8 --_-; 8 WASHER,SPLIT-LOCK,5/16"ID,18-8 SS 1
I �yF
7
' 6 I.
1
1.50 5
I
3.00 4
3 �
4.50
9.00
2.50 2
' 1
I
.29 ; Quick Mount PV,
1 _
TITLE:
QMSE: QMPV E-MOUNT
(3.00) (3.87) AVAILABLE IN MILL,AND
BLACK FINISHES. iUNLES50THERWISE SPECIFIED: SIZE DRAWN BY: RAD REV
DIMENSIONS ARE IN INCHES ,f
TO I A DATE: 5/9/2017 '+
- FRACTIONALS 1/e
reoruLTArr AxocoxxorxTLAt TWOPLACEDECIMAL -.19 -
THE Rl —TION COMAN®PT TH 1AM.. THE SOLED CFVTY0FQU1CKM0UM ANY R®ROWCT10NWPARLORASAW 0OfflTHOUTTHE DO NOT SCALE DRAWING I
wRmEN PExM o_FaulcKMouw Pva PRoreartEo. COPYRIGHT®2016 QUICK MOUNT PV THREE PLACE DECIMAL].094 SCALE:1:3 !WEIGHT:0.9172 �SHEETI OF I
5 — 4 31 - — 2 1
Lag pull-out(withdrawal)capacities(Ibs)in typical lumber:
Lag Bolt Specifications
Specific Gravity 5/16"shaft per 3"thread depth 5/16"shaft per 1"thread depth
Douglas Fir,Larch .50 798 266
Douglas Fir,South .46 705 235
Engelmann Spruce,Lodgepole Pine(MSR 1650 f&higher) .46 705 235
Hem,Fir .43 636 212
Hem,Fir(North) .46 705 235
Southern Pine .55 921 307
Spruce,Pine,Fir .42 615 205
Spruce,Pine,Fir(E of 2 million psi and higher grades of MSR and MEL) .50 798 266
Sources:American Wood Council,NDS 2005,Table 11.2 A,11.3.2 A
Notes:
1)Thread must be embedded in a rafter orother structural roof member.
2)See NDSTable 11.5.1 C for required edge distances.
Quick Mount PV°
RESPECT THE ROOF
BI 7.2.3-26 May-2017 Rev 6
Reference and Tips
Proper Flashing Placement
fNORM - - - - - , i
ECT POM Correct Acceptable Position
If shingle cutting is required,a Yz�'
gap between black and shingle is
; I
I
Additional tips and information for installing mounts:
■ See Quick Tips videos on nail removal,bolt prep,and more at:
http://wwW.quickmountpv.com/support/videos.htmi
■ It is not necessary or advisable to use nails or other fasteners to secure the perimeter of
the flashing.
■ The E-Mount is made to work with standard and high-definition composition/asphalt and wood
shingle roofs with 5"to 5-5/8"courses. If the exposed surface'of the course exceeds this measure-
ment you may need to use our Classic Shake Mount instead.
■ Depending on the season and climate,size and location of seal tabs,and quality of the shingles,
the seal tabs that adhere the shingle courses together may not effectively seal the shingles to the
flashings.If this is the case,simply add several quarter-sized dabs of manufacturer accepted sealant
or asphalt roofing cement,meeting ASTM D 4586 Type II,between the flashing and the shingle
above.
■ Mounts should not be installed in areas of the roof susceptible to ice damming.Water ponding un-
der the shingles can reach the bolt penetration.
■ Take care not to damage the roofing material while working on the roof. Removing stone granules
and deforming the shingles in anyway can shorten the lifespan of the roofing.The value of the solar
array is directly affected by the condition of the roof it is attached to.
BI 7.2.3-26 May-2017 Rev 6
SOLARSTANDARD
wool
; P A GE
___ _____________ ___________M__ _ _OUNT_________________________________________________________________IN STALLATION__ ____ __ ____G UIDE_____ ____ _____
WEEBLUG TERMINALTOROUE,
Single Use Only Install Conductor and
torque to the following:
6-14 AWG:5ft-lbs
Y ONE LUG PER OF MODULES: _ f�.^ _r °' �`
n l of modules is --� WEEBLUG CONDUCTOR-UNIRAC P/N 008002S:
Only one Lug,
d u J
t r Apply Anti Seize and insert a bolt in the aluminum rail and through the clearance
ee•Page or additl I Lu equired for PP y g
"1 trl. e n j hole in the stainless steel flat washer. Place the stainless steel flat washer on the bolt,
oints.x o � ." - •� F�+ .�'�Iits:.��
= oriented so the dimples will contact the aluminum rail.Place the Lug portion on the
bolt and stainless steel flat washer.Install stainless steel flat washer,Lock washer and
` - nut.Ti hten the nut until the dim les ar g p e completely embedded into the rail and lug.
r= TORQUE VALUE 10 ft lbs.(See Note on PG.A)
f See product data sheet for more details,Model No.WEEB-LUG-6.7
GROUNDING LUG MOUNTING DETAILS: Star Washer is i
Details are provided for both the WEEB and Ilsco products.The WEEBLug has a Single Use Only , r
grounding symbol located on the Lug assembLy.The ILsco lug has a green colored
set screw for grounding indication purposes.Installation must be in accordance f �`
with NFPA NEC 70,however the electrical designer of record should refer to the
Latest revision of NEC for actual grounding conductor cable size. TERMINALTOROUE,
Required if not using approved integrated grounding microinveters Install Conductor and
torque to the following:
4-6 AWG:35in-lbs
® 8 AWG:25 in-lbs
10-14 AWG:20 in-lbs
GROUNDING I LUG M BOLT SIZE W DRILL SIZE ILSCO LAY-IN LUG CONDUCTOR-UNIRAC P/N 008009P:Alternate Grounding Lug
GROUND LUG BOLT SIZE DRILL SIZE -Drill,deburr hole and bolt thru both rail walls per table.
WEEBLug 1/4" N/A-Place in TopSM Rail Slot TORQUE VALUE 5 ft lbs.(See Note on PG.A)
ILSCO Lug #10-32 7/32" See ILSCO product data sheet for more details,Model No.GBL-4DBT.
• Torque value depends on conductor size. NOTE:ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION
• See product data sheet for torque value.