HomeMy WebLinkAbout18-20305 CITY OF ZEPHYRHILLS /
5335-8TH STREET
(813)780-0020 0305
FIRE SPRINKLER SYSTEM PERMIT
PERMIT INFORMATION LOCATION INFORMATION
Permit Number: 20305 Address: 39317 AIR PARK RD
Permit Type: FIRE SPRINKLER SYSTEM ZEPHYRHILLS, FL.
Class of Work: FIRE-SPRINKLER SYS Township: Range: Book:
Proposed Use: NOT APPLICABLE Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est. Value: Parcel Number: 13-26-21-0000-00100-0020
Improv. Cost: 7,250.00 OWNER INFORMATION
Date Issued: 10/05/2018 Name: CITY OF ZEPHYRHILLS
Total Fees: 145.00 Address: 39317 AIR PARK RD
Amount Paid: 145.00 ZEPHYRHILLS, FL. 33542
Date Paid: 10/05/2018 Phone:
Work Desc: INSTALLATION FIRE SPRINKLER SYSTEM
CONTRACTORS APPLICATION FEES
BENEFIC AL FIRE PROTECTION INC FIRE SPRINKLER SYS 50.00 FIRE PLAN REVIEW FEES 50.00
FIRE INSPECTION FEES 45.00
f
2�J
l
FIRE-PRESSURE TEST Ins ections Re uired
FIRE ACCEPTANCE Final
Chapter 633, Florida Statutes,authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review,administrative fees,and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of$100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMEN ENT."
CONTRACTOR SIGNATURE PERMIT OFFICE
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT- 813-780-0041
813-780-0020 City of Zephyrhills Fire Fax-813-780-0021
C Permit Application
Date Received _ 'Zis Phone Contact for Permit
_ ---
Owner's Name Cl f/ d�Y/� GL� Owner's Phone Number
Owner's Address
Fee Simple Titleholder Name Titleholder Phone Number
Fee Simple Titleholder Address
Job Address �/ / r' �` ��G d /��� / �S^ Lot#
Sub Division Parcel#
F7 Bio-Hazard Waste Storage-ANNUAL Fumigation Tent
Comm Exhaust Kitchen Hood/Duct Hazardous Material(Tier II or RQ Facility)ANNUAL
Controlled Burn Hood Installation
Emergency Generator<30 kw LP/Natural Gas-Installation
Emergency Generator>30 kw LP/Natural Gas-ANNUAL Sale
Fire Protection Maintenance-ANNUAL Places of Assembly-ANNUAL
r y emi ®n ter
Sprinkler ❑ ❑ ❑ Recreational Bum
Fire Alarm ❑ ❑ ❑ �Srsparkle /
Hood Cleaning � ❑ ❑ ❑ Sprinkler System Installations
Hood Suppression ❑ ❑ ❑ Standpipes pnn er Sys)
Fire Alarm Installation Torch Roofing/Tar Kettle
Fire Pumps Waste Tire Storage ANNUAL b C
Flammable Application-ANNUAL 277 Valuation of Project
Fuel Tanks
Q Other: �/L 1 GGE� / n+ i 1"
Contractor `� Company -4-d e . ..�
Signature ` Registered . Y/N Fee Current I Y/N
Address L S .fj - i✓ a- f✓r/�/ J a I f License# P (0,6'a �
ELECTRICIAN Company
Signature Registered Y/N Fee Current Y/N
Address License#
PLUMBER Company
Signature Registered Y/N Fee Current Y/N
Address License#
MECHANICAL Company
Signature Registered Y/N Fee Current
Address License#
OTHER Company c
Signature Registered Y/N Fee Current Y/N
Address License#
Directions: 9
Fill out application completely.
Owner&Contractor sign back of application,notarized(Or,copy of signed contract with owner)
If over$2500,a Notice of Commencement is required(Mechanical work over$5000)
Supply two(2)sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel#-obtained from Property Tax Notice(http://appraiser.pascogov.com)
NOTICE OF DEED S: The undersigned understands that this permit may be subjectho"deed"
which may be rea�k�vethan Count v `_ 8 m� respon�dbi|i ! for ` nnodha ' with any
*p*uu*m�w��ur�mo�uoom.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor cr
contractors to undertake work, they may be required to be licensed in accordance with state arid local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited fora misdemeanor violation
under state |emv. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised b1 contact the Pasco County Building Inspection Division-Licensing Section at 727-847-
8009. Furthermore, if the owner has hired o contractor or oontraubmrs, he is edV|nad to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be naopmne|b|e. If you, as the owner sign as the
contractor, that may.be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW(Chapter.713, Florida Statutes, as,amended): If valuation of work ha$2.GOD'OOor more, I
.certify that |, the applicant, have been provided with a copy of the "Florida Construction Lien Law—Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs: If the applicant iosomeone
other than the"owner", I certify that I have obtained a copy of the above described�document and promise in good faith to
deliver itho the"omne/'prior tucommencement.
' CONTRACTOR'S/OWNER'S AFFIDAVIT: | certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable |axm* regulating construction, zoning and land
' development. Application is hereby made to obtain a permit to do work and installation as indicated. IomdKy
that no work or installation has commenced prior bo issuance ofa permit�and that a UvvorkwNU bepe�onnedbo
meet standards of all laws regulating -construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. | also uadifv that | understand that the regulations of other
government agencies may | h»the intended work, and that itionnY responsibility to identify what actions
must tahmtobeincompliance. '
If am the AGENT FOR THE OWNER, I promise in good faith tm inform the owner of the parmdbnQ conditions set forth in
this affidavit prior to commencing construction. | understand that o separate permit may be required for electrical work,
p|unlbing, aigne, xveUm, pools, air conditioning, gas, or other installations not opedificaUy include in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authorityalter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit is U ouedmh� 6ecomeinva|id
unless the work authorized by such permit is commenced within six months' of permit isouanna, or if work authorized by
the permit is suspended or abandoned for a period of six (6) months after the.time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety(910) days andwill demonstrate
justifiable cause for the extension. If work ceases for ninety(90)consecutive days,the job ks considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAY8MXG TWICE FOR IMPROVEMENTS TO YOUR PROPERTY' IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOURNOTIOE OFCCMMENCEMENT/.
OWNER OR AGENT CONTRACTORA/&fz'1/40�
^ Subscribed and owomto(or affirmed)before methis Subscribed
by
Who__-personally known_m_— h_-h_.-,.-_--- Who_is/are personally known~....-. ...~...,e
produced
idwnbomalinn. uidentification.'
Notary Public Notary,Public
�
Commission No. Commission No.
typed,Name of Notary printed or stampedNotary typed,printed or stamped �
'
`
'
I LOIIIUfl
iD
City of Zephyrhills
BUILDING PLAN REVIEW COMMENTS
Contractor/Homeowner: AL
Date Received:
Site: v�cl�/ //QGL/ eoad---"
Permit Type:
Approved w/no comments: Approved w/the below comments: ❑ Denied w/the below comments: ❑
This comment sheet shall be kept with the permit and/or plans.
Gene Brown—Fire Safety Officer Date Contractor and/or Homeowner
(Required when comments are present)
11/30/2018 1:58PM FAX @0002/0002
SIM lIIII111111111111�18111�111111 ��1111�1�11
pw NO. PmW ID No
,.{ NOTICE OF 60WENCEN r
stateaa T ���IU�y Coadyor Pa�r.� .�
IMUf GNEOberfygheeroanOWimpnwommtwilbemoatboarlalnreefwpeetyetaineGorrees+�e,.ibowpw?101,RwwSlaAN,
1. t)e5+aipomarpoportlr.Paraei Na.
slmetAM43 611 ..
21 2r I
3. O»Tre(u�Klarnteaen�a LAmsmth4amoh BO�t! e conveexea tatAe tnDm+A3ment
—...3.1�1�i�-� �11�(„'Ya�•�r 5P,,.,f�rtr:� ..
{N 511 at�t�sriLRd & r i �15
ADUM [Sly t
Namadpve8lnpiaTilleholder: ,
Ndd�ienlflenl0lrn.r' a0ow)
4, lvOrlp'RC
3p01
OeNretlorlt Talnpl�ro N.- 11 9 D V q �'
4. Su+vtY NWO
fit N AaM —
&�+� AnwldBw*S TiplgplgrqNa
i6"p 6. teaoer
Name
r, Aaatrtaa city sum
r" 7. P.ueo+►s*Ua IM SUn ar Florida*iigmW by dm cww Upon Mtiaa tatieea or allmr docomft aw bo atrved et pmwMed by
Serlldr719.t9(1)(a}(7},WoeiQaStm+lmr
J
M
Ad&m Cyr &ite
H�� 7eteplfoaetYunbetotCmlpteeddPem�rc
�j��. S 4iaddllonithl'rvdf,t)19oWnerde6lSrYa89 t�^,�
3 fa re0eive t+mprdrAe 11anOf�Mbtioo RavlQea ki5xlfon 713 t°{t1lD�Fioffd8
aa•. TeiepFWnpNumtr�a/RxWnor6ttgtbaneleabYowfee
9. E7N1181Jatt date d Natloe W OnnnrproeeneM ia+t aNtisAion dale may rot bt before tee ooraplertm of oort94trpOrl iAd�Pe��to the
ooRnaaeoor Euty9!oeorwyear Varathe4r+4d reowdtny urleee a dI(l�ertdettta epeo'Oetlk
WAltN1N0 T O OYYN� ANY PAYtNiIS MACE BV'MBE yiYVlafR AFTER ttiE F�WI(tAT�fl of TItE H07iCE QF tilAtFNCFaIENT
ARE OONSIDERW INPROAFR PAYM@7f5lhIPRUYII�NfS�QR1 GURP�. A 7t3.CE 6F� HA�FM ht�UST�dC RESULT W YQUR PAYR4Ci 7VYICE FOR
M WAN EApRANATtCER1 �BEFCOMh{ltiRItORRCC9�fYCiN3YOURNOiiOF� 7
Ua�der dldarp401hm rasa ftfel�f ftAift tandim. 30 -V%9MMW&brebrtl bW
w
STKEOFFlOttfCA Mali ash
$ COUNTY OF PASM
ar d'Lteaut, er Le�es"a ArlMb+d
mad
.
a0 At
(YAMAN A lb VNIsN
i
7lletbleponpnebvaencwcaetlaorrloa�dbb�� wtrra a+rd
l;I Y�. ttM� fix,ep,aver,tns!%aoomey fn teW to
(�cof onbehalfd eminuneatrrmmma,bodb
N1�ffi Praaueea weM�n� Nata+y here
71"ardwArMiUeProrhroad --dL a {Pr:,t) N Nlrila /11f RM
&L
•�dl1Mr-..�.�.r:
NEN17A B.IMPERATC
. Notary Public•State of Florida
•. •z My Comm.Explfes Jon 4.2019
Commbsten 0 PF 169902
d�ir BolldedUlrollQhN�ntlaf lJalaryAssn,
11 "
SUBMITTAL DATA FOR:
HAWK AIRCRAFT
39317 AIRPARK RD.
ZEPHYRHILLS, FLORIDA
SEPTEMBER 19, 2018
BENEFICIAL FIRE PROTECTION, INC.
12522 US Highway 301 N. Suite 1
Thonotosassa, Florida 33592
Phone: (813) 986-5819
Fax: (813) 986-5831
State Certification: #45018800011989
State Certification: #67451300012005
INDEX
SPRINKLER HEADS:
Globe 1/a".QR 212' Brass ELO-231 Pendent TY5211 — 11.2 K-Factor
Globe 1/z" QR 155' Chrome Semi-Recessed Pendent GL5601 -- 5.6 K-Factor
PIPE:
Black Thinwall Pipe
Black Schedule 10 Pipe
Black Schedule 40 Pipe
VALVES:
Riser Butterfly Control Valve
Riser Check Valve
2"Angle Valve
FITTINGS:
Threaded Fittings
Grooved Fittings
Welded Fittings
MISC:
Hanger Rings
Hanger Fasteners
Electric Bell
Flow Switch
CO� Worldwide www.tyco-fire.com
Contacts
Series ELO-231 - 11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General and gas/chemical velocity, should be
considered, as a minimum, along with
Descri t�On the corrosive nature of the chemical to !^ 1
jp which the sprinklers will be exposed.
TYCO Series ELO-231 11.2K Stan- An upright intermediate level version
dard Response, Standard Coverage of the Series ELO-231 Sprinklers for
Upright and Pendent Sprinklers (Ref. in-rack applications can be obtained
Figure 1) are automatic sprinklers of by utilizing the Series ELO-231 Upright
the fusible solder type.They are stan- Sprinkler with the WSG-2 Guard &
dard response, spray sprinklers that Shield, and a pendent intermediate
produce a hemispherical water distri- level version of the Series EL07231
bution pattern below the deflector. Sprinklers can be obtained by utilizing
The 11.2 K-factor, ELO-231 Sprinklers the Series ELO-231 Pendent Sprinkler
were subjected to full scale,high-piled with the WS-2 Shield: If there is a pos-
storage, fire tests to qualify their use sibility of the pendent intermediate level
in lieu of 5.6 or 8.0 K-factor standard version being exposed to mechanical
spray sprinklers for the protection of damage,a G-2 Guard can be added.
high-piled storage.
Higher flow rates can be achieved at he 11.2 K-factor, Series. ELO-231
much lower pressures with the 11.2 T and Pendent Sprinklers
K-factor, ELO-231 Sprinklers, making Upright p
their use highly advantageous in high described herein must be installed
density applications, such as the pro- and maintained in compliance with this
tection of high-piled storage. document,as well as with the applica-
ble standards of the National Fire Pro-
Wax or lead coatings can be used tection Association(NFPA),in addition Technical
to extend the life of the copper alloy to the standards of any other authori-
components used in Series ELO-231 ties having jurisdiction.Failure to do so Data
sprinklers beyond that which would may impair the performance of these
otherwise be obtained when exposed devices. Approvals
to corrosive atmospheres. Although UL and C-UL Listed
wax and lead coated sprinklers have The owner is responsible for main- FM Approved
passed the standard corrosion tests of taining their fire protection system NYC Approved
the applicable approval agencies, the and devices in proper operating Refer to Table C for specific details
con-
testingis not representative of all os- dition. Contact the installing contrac-
p P
sible corrosive atmospheres. Conse- for or product manufacturer.with any
on laboratory listings and approvals,
p including corrosion-resistant status.questions.
quently,it is recommended that the end The approvals apply to the service user be consulted with respect.to the Installation of Series ELO-231 Pendent con-
ditions indicated in the Design Criteria
suitability of these corrosion resistant Sprinklers in recessed escutcheons will section.
coatings for any given corrosive envi- void all sprinkler warranties,as well as es
Finish
ronment. The effects of ambient tem- possibly void the sprinkler's Approvals Refer Table C
perature, concentration of chemicals, and/or Listings.
Physical Characteristics
Frame ............................Bronze
Sprinkler Seal Disc......................... Copper
IMPORTANT Cap..............................Bronze
Always refer to Technical Data Identification Strut Assembly..Solder,Bronze Stainless Steel
y Compression Screw..................Bronze
Sheet TFP700 for the "INSTALLER Deflector.............. ...Bronze
WARNING" that provides cautions Numbers (SIDS) HelerS Spring
p p p g...............Stainless Steel
With respect to handling and instal- Refer to Table A for sprinkler identifica- Elector Spring...................... Nickel lation ofsprinklersystemsavd com- tion numbers. Strut Clip................... Stainless steel
ponents. Improper handling and Additional Technical Data
installation can permanentlydainage Refer to Table A for additional techni-
a sprinkler system or its compo- cal data.
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6 MAY 2018 TFP340
s
TFP340
Rage 2 of 6
1/2"(12,7 mm) Components:
NOMINAL MAKE-IN
1 - Frame
N
PT
2- Seal Disc
PT 1 3- Cap
4- Strut
2-13/16" . 2 Assembly
(71,4 mm) WRENCH THRE7 5- Compression
TYP. FLATS RELI3 Screw
/ 8 6- Deflector*
4 7- Helper
9 Spring
1/2" 3/4" 5 8- Ejector
NPT NPT Spring
7/16"(11,1 mm) 1/2"(12,7 mm) 6 9- Strut Clip
NOMINAL MAKE-IN NOMINAL MAKE-IN *Temperature
rating is
UPRIGHT UPRIGHT PENDENT CROSS indicated on
TY5811 TY5111 TY5211 SECTION deflector
FIGURE 1
SERIES ELO-231 11.2K UPRIGHT-3/4"NPT(TY5111), UPRIGHT- 1/2"NPT(TY5811),AND
PENDENT-314"NPT(TY5211)SPRINKLERS
Operation Item Description
A fusible alloy is sealed into a bronze TY5111-Upright-3/4 in.NPT
actuating rod (center strut) by a stain- TY5211-Pendent-3/4 in.NPT
less steel ball.When the alloy melts at Sprinkler Identification Number(SIN) TY5811 -Upright-1/2 in.NPT
its rated tem erature,the ball is forced TY5111 Is a redesignation for Central SIN C5111.
p TY5211 is a redesignation for Central SIN C5211.
upward into the center strut, releas- TY5811 is a redesignation for Central SIN C5811.
ing the two ejectors and operating the
sprinkler. K-factor,(gpm/psi)(Ipm/bar) 11.2 gpm/psi%(161,4 Ipm/bar%)
165°F(74°C)t
Design Temperature Rating IF(°C)1 212°F(100°C)
286°F(141"C)
Criteria Thread Size 3/4 in.NPT or ISO 7-R 3/4
1/2 in.NPT
UL and C-UL
Listing Requirements Sprinkler Orientation Upright/Pendent
TYCO Series ELO-231 11.2K Stan- Maximum Working Pressure,psi(bar) 175 psi(12,1 bar)
dard Response, Standard Coverage
Upright and Pendent Sprinklers are Notes:
to be installed in accordance with 1. Refer to Table C for laboratory listings and approvals.
NFPA 13 standard sprinkler posi- TABLEA
tion and area/density flow calcula- SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLER
tion requirements for light, ordinary, TECHNICAL DATA
or extra hazard occupancies, as well
as high piled storage occupancies,
such as solid piled, palletized, rack
storage, bin box, and shelf storage
including but not limited to Class 1.4V
and Group A plastics,with a minimum
residual (flowing) pressure of 7 psi
(0,5 bar)for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231
Sprinklers are to be installed in accor-
dance with the applicable control mode
density/area,guidelines provided by FM
Global.
Note: FM Approval guidelines may
differ from UL and C-UL Listing criteria.
TFP340
Page 3of6
Storage Type NFPA FM Global
Sprinkler Type Standard Coverage Storage
Response Type SR SR
System Type Wet Wet
165°F(74°C)1 165°F(74°C)1
Temperature Rating OF(°C)1 212°F(100°C) 212°F(100°C)
286°F(141°C) 286°F(141°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9
B Plastics
Solid Pile or Palletized Storage of Class ]-IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0,8-9,and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage(Refer to the Standard) Refer to NFPA 13 Refer to FM 8-21
Flammable/Ignitable Liquid Storage(Refer to the Standard) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage(Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks N/A N/A
(Control mode only;refer to the Standard)
Notes:
1. Refer to Table C for laboratory listings and approvals.
N/A—Not Applicable
TABLE B
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
SPRINKLER FINISH
SPRINKLER TEMPERATURE FRAME
TYPE RATING COLOR NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
165°F(74°C) Unpainted
UPRIGHT 212°F(100°C) White 1,2,3,4 1,2,3,4
(TY5111&TY5811)
286°F(141°C) Blue 1,2,3,4 1',2',3',4'
165°F(74°C) Unpainted
PENDENT 1,2,4
212°F(100°C) White 1,2,3,4
(TY5211)
286°F(141°C) Blue 1,2,4 1',2,4
Notes: 3. FM Approved
1. UL Listed 4. Approved by the City of New York(NYC)under MEA 291-04-E
2. C-UI Listed ' Listed/Approved for a maximum ceiling temperature of 150°F(66°C)
TABLE C
11.2K SERIES ELO-231 UPRIGHT&PENDENT SPRINKLERS,STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
QUICK RESPONSE
AUTOMATIC SPRINKLERS
OmanOman GGL SERIES
``�' B UPRIGHT• PENDENT
FIRE SPRINKLER CORPORATION VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
DESCRIPTION AND OPERATION CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a low profile
yet durable design which utilizes a 3mm frangible glass ampule as the
thermosensitive element. This provides sprinkler operation approxi-
mately six times faster than ordinary sprinklers. While the Quick —
Response Sprinkler provides an aesthetically pleasing appearance, it (
can be installed wherever standard spray sprinklers are specified when
allowed by the applicable standards. It offers the additional feature of
greatly increased safety to life and is available in various styles,orifices, __s=
temperature ratings and finishes to meet many varying design require- I
ments. Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating QUICK RESPONSE
assembly is a hermetically sealed frangible glass ampule that contains UPRIGHT CONVENTIONAL
a precisely measured amount of fluid. When heat is absorbed,the liquid _
within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure within the ampule exceeds
the strength of the glass causing the glass to shatter. This results in
water discharge which is distributed in an approved pattern depending 1
upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. As-
sembly is done in the field. -
TECHNICAL DATA QUICK RESPONSE
•See reverse side for Approvals and Specifications. PENDENT VERTICAL
•Temperature Ratings - 1350F (57°C), 155°F (680C), 175°F (790C), SIDEWALL
200°F (93°C), 286°F (141°C).
•Water Working Pressure Rating - 175 psi (12 Bars). --,,
L __
•Factory tested hydrostatically to 500 psi (34 Bars).
•Maximum low temperature glass bulb rating is -67°F (-550C). `t
•Frame - bronze • Deflector- brass • Screw - brass
• Bulb seat- copper • Spring - nickel alloy • Seal -teflon
• Bulb - glass with alcohol based solution, 3mm size. QUICK -RESPONSE
HORIZONTAL SIDEWALL
• SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER F BULB N.FP.A. MAXIMUM
TEMPERATURES COLOR CEILING TEMPERATURE
ORDINARY r7g5
55 F 57°C/68°C ORANGE/RED 100°F 38°C
INTERMEDIATE 00°F 79°C/93°C YELLOW/GREEN 150°F 66°HIGH F 141°C BLUE 225°F 107°C
4077AIRPARK DRIVE,STANDISH,MICHIGAN 48658 989-846-4583 FAX989-846-9231
DECEMBER 2006 A-20 BULLETIN GL5615, REV. #6
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT• PENDENT* VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL"K" FACTOR THREAD SIZE LENGTH ' FINISHES
2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2
Bright Chrome .
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) White Polyester
7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Black Polyester 3
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Lead Coated 2
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'HORIZONTAL SIDEWALL IS 2 9/16".
2 FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED CORROSION
APPROVALS RESISTANT WHEN SPECIFIED ON ORDER.
STYLE SIN K 135*F 155*F 175*F 200*F 286*F cULus F.M. LPC CE NYC-DOB
MODEL FACTOR 57 C 68"C 79 C 93*C 141 C MEA101-92-E
GL2815 2.8 X X X X X X — — — X
GL4215 4.2 X X X X X X — — — X
UPRIGHT GL5615 5.6 X X X X X X X X X X
GL8115 7.8* X X X X X X X — — X
GL8118 8.1 X X X X X X X X X X
GL2801 2.8 X X X X X X — — — X
GL4201 4.2 X X X X X X — — — X
PENDENT GL5601 5.6- X X X X X X X X X X
GL8101 7.8* X X X X X X X — — X
GL8106 8.1 X X X X X X X X X X
VERTICAL GL5632 5.6 X X X X X X X — — —
SIDEWALL GL8133 8.1 X X X X X X — — — —
GL2826 2.8 X X X X X X — — — X
HORIZONTAL GL4226 4.2 X X X X X X — — — X
SIDEWALL§ GL5626 5.6 X X X X X X X — — X
GL8127 8.1 X X X X X X — — — —
CONVENTIONAL GL5624 5.6 X X X X X — — X X —
(OLD STYLE) GL8125 8.1 X X X X X — — X X —
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4"TO 12"BELOW THE CEILING,FM APPROVED 4"TO 6".
t VERTICAL SIDEWALL SPRINKLER cULus LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6'MIN.SPACING.
UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9'MIN.SPACING.
ORDERING INFORMATION *1/2"NPT.
SPECIFY GLOBE@ PRODUCT WARRANTY
•Quantity • Model Number • Style Globe agrees to repair or replace any of its own
•Orifice • Thread Sizes • Temperature manufactured products found to be defective in mate-
•Finishes desired rial or workmanship for a period of one year from date
•Quantity-Wrenches- P/N 325390 (1/2"); of shipment.
P/N 312366 (L.O.) For specific details of our warranty please refer to
Price List Terms and Conditions of Sale(Our Price List).
GLk J3E 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
FIRE SPRINKLER CORPORATION 1-800-248-0278 www.globesprinkler.com
DECEMBER 2006 PRINTED U.S.A. BULLETIN GL5615, REV.#6
yo, ot mr Tube
T" "Quality by the Foot"
Schedule 7 Sprinkler Pipe
"Fire-Flo"
Youngstown Tube manufactures Fire-Flo(schedule 7)pipe in sizes 1 1/i'thru 4"using only high quality domestic steel coils.This
ensures a uniform superior product for roll grooving,welding or plain end uses.Youngstown Tube's Fire-Flo pipe is produced under
ASTM Al35/A795 Type E,Grade A,NH standards.Every piece is Eddy-Current tested and conforms to internal SPC testing and
recording.
Fire-Flo pipe is manufactured with.lighter gauge steel than conventional schedule 10 pipe.This creates a lighter,cost effective
product with increased hydraulics over schedule 10 pipe.
Youngstown Tube Fire-Flo steel sprinkler pipe is coated with a waterbased black enamel coating,YTC Guard®antimicrobial coating
and a continuous color coded yellow stencil,and stored indoors ready for immediate shipment.
Approvals:UL Listed,CUL Listed,FM Approved
Youngstown Tube schedule 7 pipe meets the rigorous testing and certification processes of Underwriters Laboratory and Factory
Mutual for steel sprinkler pipe with working pressures of 300 psi or less.It also meets the requirements of NFPA 13.
"Fire-Flo" Schedule 7
Pieces Weight UL
Pipe Pipe Nominal Weight per Standard Feet per
Size OD Pipe ID Wall Foot Length per Bundle per IUnthreaded
Bundle Bundle CRR
1 Y2 1.900 1.732 F . 884 F924 1,497 2.85
F 2.375 2.207 .084 F 1,593 2.31
2�/e F2.8751F.0867 21 F1,981 1.43
3.500 3.314 .093 3.38 21 24 504 1,704 1.34
4.500 4.304 098 4.37 21 19 399 1,744 1.0
Fire-Flo pipe can not be threaded or cut-grooved.
Youngstown Tube Company
401 Andrews Avenue
Youngstown,Ohio 44505
1-866-The-Tube
www.youngstowntube.com
Project: Contractor:
Submitted By: Date Submitted:
Yaungs U � i Tub
"Quality by the Foot" �"
Schedule 10 Sprinkler Pipe
Youngstown Tube manufactures Schedule 10 pipe in sizes 1 1/a" thru 6" using only high quality domestic steel
coils. This ensures a uniform superior product for roll grooving, welding or plain end uses. Youngstown Tube's
schedule 10 pipe is produced under ASTM Al35/A795 Type E, Grade A, NH standards. Every piece is Eddy-
Current tested and conforms to internal SPC testing and recording.
Youngstown Tube Schedule 10 steel sprinkler pipe is coated with a waterbased black enamel coating, YTC
Guard®antimicrobial coating and a continuous color coded white stencil, and stored indoors ready for
immediate shipment.
Approvals: UL Listed, CUL Listed, FM Approved
Youngstown Tube schedule 10 pipe meets the rigorous testing and certification processes of Underwriters
Laboratory and Factory Mutual for steel sprinkler pipe with working pressures of 300 psi or less. It also meets
the requirements of NFPA 13 and can be used in wet, dry, deluge and preaction systems.
Schedule 10
Pipe Pipe Pipe Nominal Weight Standard Pieces Feet Weight UL
Size OD ID Wall per Foot Length Per per per Untreaded
Bundle Bundle Bundle CRR
1 1/a 1.660 1.442 .109 1.81 21 61 1,281 2,319 8.5
1 '/2 1.900 1.682 .109 2.08 21 924 1,921 6.8
2.375 2.157 .109 2.64 21 37 777 2,051 5.5
2 /z 2.875 2.635 .120 3.53 21 37 777 2,742 4.1
3.500 3.260 .120 4.33 21 24 504 2,182 3.0
4.500 4.260 .120 5.61 21 19 399 2,238 1.8
6.625 6.357 .134 9.29 21 10 210 1,951 1.16
* Schedule 10 pipe can not be threaded or cut-grooved.
Youngstown Tube Company
401 Andrews Avenue
Youngstown, Ohio 44505
1-866-The-Tube
www.youngstowntube.com
Project:1 Contractor:
Submitted By: Date Submitted:
Youngstoly
"Quality by the foot" n
Schedule 40- Sprinkler Pipe
Youngstown Tube manufactures Schedule 40 pipe in sizes 1"thru 2" using only high quality domestic steel
coils. This ensures a uniform superior product for threading, roll grooving, welding or plain end uses.
Youngstown Tube's schedule 40 pipe is produced under ASTM A135/A795 Type E, Grade A, NH standards.
Every piece is Eddy-Current tested and conforms to internal SPC testing and recording.
Youngstown Tube Schedule 40 steel sprinkler pipe is coated with a waterbased black enamel coating, YTC
Guard®antimicrobial.coating and a continuous color coded red stencil, and stored indoors ready for
immediate shipment.
Approvals: UL Listed, CUL Listed, FM Approved
Youngstown Tube schedule 40 pipe meets the rigorous testing and certification processes of Underwriters
Laboratory and Factory Mutual for steel sprinkler pipe with working pressures of 300 psi or less. It also meets.
the requirements of NFPA 13 and can be used in wet, dry, deluge and preaction systems.
Schedule 40
Pipe Pipe Pipe Nominal Weight Standard Pieces Feet Weight UL
Size OD ID Wall per Foot Length Per per per Threaded
Bundle Bundle Bundle CRR
TI 1.315 1.049 .133 1.68 21 61 1,281 2,152 1.00
1 7/a 1.660 1.380 .140 2.27 21 61 1,281 2,907 1.00-
1 '/z 1.900 1.610 .145 2.72 21 924 2;511 1.00
0 2.375 2.067 .154 3.65 21 37 777 2,836 1.00
Youngstown Tube Company
401 Andrews Avenue
Youngstown, Ohio 44505
1-866-The-Tube
www.you ngstowntube.com
Project: Contractor:
Submitted By: Date Submitted:
® GLR30OG
tialLOB
%t FIRE SPRINKLER GmovedButterfly Valves
CORPORATION. Grooved End, Sizes :
3" 4", 6"andV
Specifications
Working Pressure : 300 PSI (21.4 Bars)
Max. Test Pressure : 600 PSI (42.8 Bars)
Max. Working Temp : 250°F (120°C)
Factory installed UL Listed Double Tamper
Switch For Indoor and Outdoor Use.
'Materials of Primary Components
Body: ASTM A-536 Nylon-11 Coated
Disc : ASTM A-536 EPDM ,q
Encapsulated
Upper and Lower Stems : AISI 420-SS
Worm Gear Shaft : AISI 410-SS
Housing : ASTM A-536
Hand Wheel : ASTM A-536
Flag Indicator : ASTM A-536
Sheer Pin : ASTM A-510
Segment Gear : ASTM B-148 or B-584
Housing Gasket : EPDM Grade "E"
O-Rings (All) : EPDM Grade "E"
Approvals
NYC - DOB MEA Approved 155-06-E
UL, ULC Listed
FM Approved
r~- A
E
E
l i _ O
O
5.00 0 I 0 4.37
(l 27.0) (1 1 1 .0)
DIMENSION UNIT:IN(mm)
SIZE A B C D.. E Part No.
2'/=" 5.31 (135) 5.04(128) 4.13(105) 3.30(85) 3.80(96.4) 311785-G
3" 5.59(142) 5.04(128) 4.41 (112) 3.60(92) 3.80-(96.4) 311790-G
4" 6.89(175) 5.04(128) 5.71 (145) 4.30(108) 4.54(115.4) 311795-G
6" 8.23(209) 8.66(220) 7.05(179) 5.71 (145) 5.21 (132.4) 311805-G
B" 9.21 (234) 8.613(220) 8.03(204) 6.70(170) 5.80(147.4) 311815-G
AUGUST2006 Page4 BULLETIN BUTTERFLY REV#2
GROOVED END.
Flow Characteristics
1.2 _
2'/2" 3" 4 - 6 --- --g„ - a
1.0
oz C
0.8
WW
w 0.6
z
IL
0.2
J
-
0.0
100 1,000 10,000
FLOW RATE IN GALLONS PER MINUTE(GPM)
WAFER AND GROOVED END
Friction Loss
Friction Loss in Friction Loss in
Valve Size in. Equiv. Feet of Valve Size in. Equiv. Feet of
Valve Model (mm) Pipe Valve Model (mm) Pipe
DW(Wafer) 2'%(65) 4.8 DG(Grooved) 2'/(65) 6.9.
3(76.2) 3.5 3(76.2) 4.1
4(100) 2.4 4(100) 3
6(150) 5.1 6(150) 5.5
8(200) 5.4 8(200) 5.4
GROOVED END
Flow coefficient : Cv
DN (nun) SIZE(in) Disk Open Angle
300 400 500 600 700 800 900
65 2Y2' 12 27.4 .53.1 96 .138 156 163
80 3" 18.9 39.4 78.9 144 210 243 249
100 4" 30 65.1 129 22.6 377 488 514
150 6" 84 184 369 634 964 1196 1286
200 8" 165 339 677 1230 2002 2850 3129
WAFER TYPE
Flow coefficient : Cv at full open
DN (mm) 65 80 100 150 200
Size(in.) 2%2' 3" 4' 6" 8"
Cv 222 389 1000 1998 4619
Cv_ flow(9pm) _ Q
pressure loss(psi) P
AUGUST2006 Page6 BULLETIN BUTTERFLY REV#2
SWING CHECK
VALVE
"" STANDARD & "SHOTGUN
MODEL RCV
FIRE SPRINKLER CORPORATION _ GROovE/GROOVE
DESCRIPTION AND OPERATION 2 2 �"" 3" 4" & s" SIZES
Globe Model RCV Swing Check Valves feature a swing type
clapper,designed for use.in fire sprinkler or other types of water
.piping systems that incorporate grooved connecting pipe ends.
They are effectively used when it is necessary to permit water flow
in one direction only, preventing flow in the reverse direction (non-
return). Because the RCV incorporates a spring-loaded clapper
assembly; it may be installed in either the vertical or horizontal
position. Most commonly, it is used with various configurations of
fire department connections for fire sprinkler .systems, by-pass
connections,gravity pressure tank and, pump discharge in connec-
tions from public water supplies to automatic sprinkler systems,etc.
As an alternative to using an alarm check valve with a wet
sprinkler system, an RCV Swing Check Valve may be used in a
"Shotgun" arrangement whereby the valve is trimmed in a similar
manner but utilizes an electric water flow switch and alarm bell
instead of a water motor gong for fire notification.
The body of the Globe RCV Swing Check Valve is constructed
of high tensile strength cast iron having considerable ductility to MODEL RCV
reduce damage infield handling. It meets the ASTM A126 Class B SWING CHECK VALVE
rating. The RCV.clapper assembly is made of stainless steel and
has an E:P.D.M. rubber facing. The RCV incorporates a special
stainless steel spring assembly which allows its use in the down-
ward flow direction. It effectively provides a leak tight seal against
back pressures greater than one (1) psi. PHYSICAL DIMENSIONS
APPROVALS
• cULus Listed "H"
• FM Approved AO
OPTIONAL FOR RISER
• NYC - DOB MEA 305-05-E INSTALLATION
TECHNICAL DATA "I'"
•Water Working Pressure Rating-300 psi (20.7 Bars).
Factory tested hydrostatically to 600 psi (41.4 Bars_). E O
Equivalent feet of pipe: 2"Valve=7.2 feet,2 1/2" x
Valve= 7.2 feet, 3"Valve=7.2 feet,4"Valve-9.9 feet,
6"Valve= 16.1 feet. �!�-14NPT
L.
WEIGHT
SIZE A C E F G H 1 ) K L (Ibs.)
no trim
2" 1" 4" 3 1/2" 4 1/2" 6 1/2" 1/4" 1 1/2" 2 I/4" 2 1/2" 4 3/4" 4.5
2 1/2" 1 04" 4 1/2" 4" 5" 7" 1/4" 1 1/2" 2 1/2" 2 3/4" 5 1/2" 8
3" 1 1/4" 5" 4 1/2" 6" 7 3/4" 1/4" 2" 3" 3 3/4" 6 3/4" 12
4" 2" 6 1/4" 4" 6 1/2" 8 1/2" 1/4" 2 1/2" 3 1/2" 4 1/4" 7 1/2" 17.5
6" 2" 8" 1 5" 8" 10 1/2" 1/4" 3 1/4 4 1/4" 5 I/2" 10" 40.5
4077AIRPARK DRIVE,STANDISH,MICHIGAN 48658 989-846-4583 • FAX989-846-9231
OCTOBER2005 IM0 BULLETIN RCV REV.#1
SWING CHECK VALVE - 2", 2 %", 3" 4" & 6"
MODEL RCV - STANDARD & "SHOTGUN"
GROOVE/GROOVE
ITEM DESCRIPTION MATERIAL 2"PIN 2 A"P/N 3"PIN 4"PIN 6"PIN
3
I Hinge Pin Stainless Steel 321521 321528 321535 321541 321549
7
12 2 Torsion Spring Stainless Steel 321523 321531 321531 321545 321554
2 3 Machined Body Cast Iron 321501 321503 321505 321507 321509
g 10 4 1/2"NPT Plug Cast Iron 311003 311003 311003 311003 311003
5 Seat Ring Brass 321516 321530 321537 321543 321551
1
6 Locknut Stainless Steel 321556 321556 321556 321556 321556
po 9 7 Nameplate Aluminum 321558 321558 321558 321558 321558
5 8 Clapper Stainless Steel 321515 321527 321534 321540 321548
4 9 Clapper Facing Disc EPDM 321516 321529 321536 321542 321550
11
6 10 Sealing Washer Hard Fiber 321518 321518 321518 321518 321518
CROSS SECTION I I Disc Retainer Stainless Steel 321517 321517 321517 321544 321544
12 Hex Head Bolt Stainless Steel 321519 321519 321555 321555 321559
"SHOTGUN" TRIM ARRANGEMENT
2 SIZE A B C 4
3 A 2" 10" 8 3/4" 2 1/4" 5
i
J2 I/2" II" 9 I/4" 2 I/4"
1 "
3" 12" 9 I/2" 2 I/2" 4
4" 13 1/2" IT3 1/4" $
O 5
6" 1 14 1/4" 10 3/4" 1 4" 6
TOP VIEW FRONT VIEW
ITEM DESCRIPTION 2" 2%i" 3" 4" 6" QTY.
I RCV 321526 321533 321539 321547 321557 1
2 Angle Valve 311614(1") 311615(1 1/4") 311615(1 1/4") 311617(2") 311617(2") 1
3 Close Nipple 310500(1") 310600(1 1/4") 310600(1 1/4") 310800(2") 310800(2") 1
4 1/4"Water Gauge 300119 300119 300119 300119 300119 2
5 1/4"'3 Way Valve 311683 311683 311683 311683 311683 2
6 1/4"Plug 311001 311001 311001 311001 311001 2
7 1/4"Nipple 311101 (1 1IT-) 311102(2") 310102(2") 310103(21/2") 310103(2 1/2") 1
8 1/4"x 5 1/2"Nipple 310109 310109 310109 310109 310109 1
ORDERING INFORMATION GLOBE° PRODUCT WARRANTY
Globe agrees to repair or replace any of its own
SPECIFY manufactured products found to be defective in material
•Quantity • Model Number or workmanship for a period of one year from date of
•Standard or Shotgun style. shipment.
For specific details of our warranty please refer to
Price List Terms and Conditions of Sale(Our Price List).
GLt)13E
4077AIRPARK DRIVE,STANDISH,MICHIGAN 48658
FIRE SPRINKLER CORPORATION 989-846-4583 FAX989-846-9231
OCTOBER2005 PRINTED U.S.A. BULLETIN RCV REV.#1
UNITED BRASS WORKS, INC. R
p 714 S. Main St., Randleman, NC 27317
Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com IS09001
tEGISTEREO COMPANY
Model 126SUL Angle Valve
Soft Disc
u
C usUL Listed for Fire Sprinkler Service at 250 WOG
200 WOG @ 180 ° Max
100% Pressure Tested
Threaded Ends
Risinu Stem • Integral Seat
B
' 3
- 4
C
MATERIAL LIST
\ \ 5
NO. DESCRIPTION MATERIAL \
1 Hex Nut Steel '
2 Hand Wheel Aluminum 6
3 Packing Nut Brass
4 Packing Graphite Non-Asbestos
5 Bonnet('/z" —I") Brass
Bonnet(1 ''/4"—2") Bronze i
6 Stem&Seat Assembly Brass 8
i
7 Disc Buna N
8 Body Bronze A
Size '/2" 3j4" 1" 1 1/4" 1 1/2" 2"
A 1.03 1.22 1.47 1.75 2.00 2.34
B 2.03 2.38 2.75 3.00 3.72 3.72
C(closed) 3.13 3.25 4.38 4.50 5.25 5.63
Ship Wt. (lbs.) 0.69 0.94 1.76 2.50 3.26 5.32
Qty.Unit Pack 12 6 6 4 2 2
Qty.Per Case 72 60 36 24 12 12
y PRODUCTS
ISHURTOINTOmmshug
Approvals Products for Fire Protection Piping Systems
COUPLINGS AND FITTINGS
Listing Pipe Rated Working Pressure Pipe Notes(See Coupling and
Shudoint Approval Size Range Wall ❑ psi Fitting Notes on page Pub.
Product❑Model Agency Inches Standard Light 13-14) No.
IPS Carbon Steel Grooved Couplings
#7705 Flexible Coupling 1"-8" 300 300
UL 8"(7705M 450 450 1,2-1,14,15
10"-12" 175 175
C-01
1"-8" 300 300
FM 8"(7705H) 450 450 2-2,18,19
10"-12" 250 250
#7707 Flexible Coupling 3/4"-1 1/4'"' 500 500
UL 2"-8" 500 450 1,3-1,14,17
10"-16" 300 -
18"-24" 250
C-02
1 1/2"-10" 500 500
FM 12" 300 300 3-2,18,19
14"-22" 175 175
24" 250 250
#7771 Rigid Coupling 2"-8" 300 300
UL 10"-12" 175 175 1,5-1,
14"-20" --- 300
22"-24" --- 250
1 1/2" 500 500 C-05
2"-8" 300 500
FM 10" 200 200 5-2,
12" 300 300
14"-24" 175 175
#Z07 Angle Pad Coupling 1 14'4" 500 500
III, 5"-8" 400 400 1,8-1
10" 350 350
12" - -
C=06
11/4"-4" 500 500
FM 5"-8" 400 400 8 2,
10" 350 350
12". 350 350
#K9 Lightweight Rigid
Coupling UL 1-1/4"-8" 300 300 1,4-1,
8"(K-9H) 350 300
G-01
FM 1-1/4"-8" 300 300 42
8"(K-9H) 300 300
1/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products . 1 800 746-GROOVED 9 Las Vegas,Nevada USA 9 www.shudoint.com .
SHURJOINT® FIRE PROTECTION PRODUCTS
www.shu joint.com
#C-7T Outlet Couplings
UL 1-1/2"x 1/2"- 300 300 1
6"x 1-1/2"
r 'r C-10
FM 1-1/2"x 1/2"- 300 300 -
6"
#C-7G Outlet Couplings
UL 2"x 1" 300 300 1,
6"x 2"
C-10
6
FM 2"x 1" 300 300
6"x 2"
#723 Saddle Let 1 1/4"x 1/2"-
UL 300 300 1,12-1,
3"x 1"
F-03
1 1/4"x 1/2"-
7, 17 FM 300 300 12-2
3"x 1"
IPS Carbon Steel Grooved Fittings
#901 Short Radius 90°Elbow
UL 2"-8" 300 300 1,
G-02
FM 2"-8" 300 300
#903 Short Radius Tee
UL 2"-8" 300 300 I,
G-02
FM 2"-8" 300 300 —
#7110 90°Elbow
LTL. V—18" 300 300 1
20"—24" 250 250
V—8" 500 500 E-02
10"—12" 300 300
FM 14"48",24" 175 175
20" 250 250
3/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products a 1 800 746-GROOVED e Las Vegas,Nevada USA• www.shudoint.com
SHURJOINT® _ PROTECTION PRODUCTS
mmshugoint.com
#711145'Elbow
UL. 1-1/4"-18" 300 300 1,
20",24" 250 250
E-02
1-1/4"-8" 500 500
FM
10"-12: 300 300
175
14"-18",24" 175
20" 250 250
#7110DR Drain Elbow
UL 2"-6" 300 300 1,
G-05
FM 2"-6" 300 300
#7110LR 1.51)Elbows
U- 2"—8" 300 300 1
E-04
FM 2"—8" 300 300
#7112 22-1/2°Elbow
UL 1-1/4" 500 500 1
1-1/2"-8" 300 300
E-04
FM 2"-8" 300 300
#7113 11-1/4°Elbow
UL 2"—8" 300 300 1
E-02
FM 2"—8" 300 300 --
#7120 Tee
UL 1-1/4"-18" 300 300 1
20"—24" 250 250
E-05
1-1/4"—8" 500 500
FM 10"—14" 300 300 —
16" 175 175
#7121 Reducing Tee
UL 2"x 1-1/2"—12"x 306 300 1
10"
E-06
FM 2"x 1-1/2" 300 300 —
6"x 4"
4/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED • Las Vegas,Nevada USA• www.shugoint.com
SHUMOINT® FIRE PROTECTION PRODUCTS
mw.shudoint.com
#7151 Eccentric Reducers
UL 2 1/2"x 2"- 300 300 1,
8"x6"
E-07
FM 2 1/2"x 2" 300 300
8"x 6"
#7160 End Cap
UL 1-1/4"-8" 300 300 1,
E-08
FM 1-1/4"-12" 300 300 --
#7160H End Cap
UL 10"-18" 300 300 1
20"—24" 250 250
E-08
40
FM 10"-12" 300 300
14"—24" 175 175
#7160T Transition Fittings
21'xV,—
UL 6"x 2" 300 300 1,
G-08
FM 2"x 1"— 300 300 —
6"x 2-1
#7170 Flange Adapter
UL 21/2"-6" 175 175 1
D-04
FM 21/2"-6" 175 175
R
#7180 Universal Flange
Adapters
UL 2"-8" 300 300 --
D-08
FM 2"-8" 175 175 21
#55 Nipple Adapters
UL 1 1/2"-2" 3011 300 1
G-07
FM 1 1/2"-2" 300 300 --
6/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED • Las Vegas,Nevada USA• www.shudoint.com
SHURJOINT® PRODUCTS
www.shugomt.com
#899 End All Fitting
U 1 1/4"x 1/2"- 300 300 1,
G-06
oil
FM 1 1/4"x 1/2"- 300 300
2-1/2"x 1"
IPS Carbon Steel Outlet Fittings
#71 Female Threaded Outlet Outlet x Header
Fitting W.x 1"-8",
111x 1'/"-8"
1'Wx2"-8"
UL 1'/"x 2"-8" 300 300 1,
2"x2"-8"
2'/s"x2'/s"-8"
2'/2(76.1)"x2,/s"-8"
3"x 3"-8" H-01-
4"x 4"-8"
%,"31"x 1"-8"
V/4",1'/2.x 2"-8"
FM 2"x 2'Y?-8" 300 300
2,Y2"x3"-8
3"x 4",-8"
4"x 5"-8"
#72C Cut Grooved Outlet
2"x 2"-8"
Fittings 2-1/2"x2-1/2"-8"
UL 3"x 3"-8" 300 300 1,
4"x4"-8"
E 6"x6"x8"
r
8"x8"x10"
H-02
f 2-1/2"x3"-8
3"x 4"-8"
FM 4"x 5"-8" 300 300
6"x 8"
8"x 10"
#72R Roll Grooved Outlet 1-1/4"x 1-1/2"-8"
Fittings 1-1/2"x 1-1/2"-8"
UL 2 x 2_8 300 300 1,
2-1/2"x2-1/2"-8
3"x 3"-8"
4"x 4"-8"
H-03
1-1/4"x 1-1/2"-8"
1-1/2"x 2"-8"
FM 2"x 2-1/2"-8" 300 300 -
2-1/2"x3"-8
3"x 4"-8"
4"x 5"-8"
7/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED 9 Las Vegas;Nevada USA• www.shudo!6t.com
SHUPWINT® FIRE PROTECTION PRODUCTS
wm.shugant.com
#74 Universal Threaded 1/2"x 1"-8"
Outlet Fitting 3/4"x 1"-8"
UL V x 1-1/4"—1-1/2" 300 300 1,
l"x 2"—2-1/2"
H-04
1/2"x 1"--8"
3/4"x 1"-8"
FM 1"x 1-1/4"--1-1/2" 300 300 —
V x 2"—2-1/2"
1"x 3"—8"
Ductile Iron Fittings .
#811 90"Elbow
UL 1/2"-2-1/2" 300 300 1
I-01
FM 1/2"-2-1/2" 300 300
#812 Reducing 90"Elbow 3/4"x 1/2"—
UL 2-1/2"x 2" 300 300 1
I-01
3/4"x 1/2"—
FM 2-1/2"x 2" 300 300 —
#813 45"Elbow
UL 1/2"—2-1/2" 300 300 1
1t I-01
r
FM 1/2"—2-1/2" 300 300 -
#814 Straight Tee
UL 1/2"-2-1/2" 300 300 1
1-01
FM 1/2"—2-1/2" 300 300 —
#815 Reducing Tee
UL 3/4"—2-1/2" 300 300 1
I-01
3/4"x3/4"xl/2"
FM — 300 300
2-1/2"x2"x3/4"
8/14
SHURJOINe IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 600 746-GROOVED • Las Vegas;Nevada USA• www.shudoint.com
SHUWOINT® FIRE PROTECTION PRODUCTS"
www.shudoint.com
#816 Reducing Coupling
3/4"xl/2"—
UL 300 300 1
2-1/2"x 2"
I-01
-
FM 300 300
2"x 1-1/2"
#817 Cross
UL 1"-2" 300 300 1
I-01
1/2"-2"
FM 300 300
1-1/4"xl"-2"xl" —
#818 Straight Coupling
UL 1/2"—2-1/2" 300 300 1
I-01
FM 1/2"—2-1/2" 300 300 -
#819 Plug
UL 1/2"—2" 300 300 1
I-01
FM 1/2"—2" 300 300 -
#820 Caps
UL 1/2"—2-1/2" 300 300 1,
I-01
FM 1/2"—2-1/2" 300 300
#825 Extension Pieces UL 300 300 1,
3/4"x 2"
I-01
1/2"x 1-1/2"L—
FM 3/4"x 2"L 300 300 —
9/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products e 1 800 746-GROOVED • Las Vegas,Nevada USA. www.shudoint.com
SHURJOINT® PRODUCTS
www.shurjoint.com
Couplings and Fittings Notes
1. MEA Approved#322-06-E.
2. 2-1)UL Listed at 300 psi on the following sizes&pipe.
1-1/4"--4"on XL,XL-11 pipe,Dyna-Flow,Super-Flo pipe manufactured by Allied Tube&Conduit Corp,1-1/4"-6"on BSI387(M),British
Standard Medium Steel pipe,
1-1/2"-3"on Eddy Flow pipe.,1-1/4"-2"on Eddylite pipe manufactured by Bull Moose Tube Co,
1-1/4"-2"on Fire-Line Threadable pipe manufactured by Western International Forest Products Inc.
UL Listed at 175 psi on the following sizes&pipes.
1-1/2"-3"on Eddy Flow Pipe manufactured by Bull Moose Tube Co,
1-1/4"-4"on Fire-Line Flow pipe manufactured by Western International Forest Products Inc.,
1-1/4"-2"&3"on SPS pipe manufactured by Yieh Phui Enterprise Co.,Ltd.
1-1/4"-3"on Sch.5 pipe,10"on Sch.10(0.188 in)pipe,12"on Sch.30(0.330 in)pipe.
2-2)FM approved at 300 psi on the following sizes&pipes.
1-1/4"-6"on BS 1387M or heavier grade pipe.
1"--4"on Dyna-Flow,Super-Flow(Allied)pipe
1"-2"&3"on Super 40,Super-XL(Allied)pipe.
1"-�3"on XL-II(Allied)pipe
1"-2"on BLT,Dyna Thread(American Tube),Fire-Thread,Eddylite(Bull Moose),TL(Central),LS pipe,
1-1/2"-4"on Eddy Flow(Bull Moose Tube)pipe
1-1/4"&1-1/2"on Fire-Flow pipe
FM approved at 175 psi on the following sizes&pipes.
1"-2"on WST(Weatland),Ultra Eddy(Bull Moose)pipe.
3. 3-1)UL Listed on the following sizes&pipe.
At 500 psi in 2-1/2",5"-6"on BS1387(M),British Standard Medium Steel pipe pipe,
At 450 psi in 1-1/2"&4"on Dyna-Flow pipe manufactured by Allied Tube&Conduit Corp,
At 300 psi in size 10"&12"on sch.10(0.188 in)pipe,14"&16"on Sch.30(0.375 in)pipe,
At 250 psi in 18"-24"on Sch.20(0.375 in)pipe.
3-2)FM approved on the following sizes&pipe.
At 500 psi in 2-1/2",5"-6"on BS 1387 medium or heavy grade pipe
4. 4-1)UL Listed at 300 psi on the following sizes&pipe.
1-1/4"-8",3.00D,6.50D on BS 1387(M),British Standard Medium Steel pipe pipe,
1-1/4"&2"on Eddylite pipe manufactured by Bull Moose Tube Co,
1-1/4"-2"on Fine-Line Threadable pipe manufactured by Western International Forest Products Inc.,
2"on Eddythread 40 pipe manufactured by Bull Moose Tube Co.
UL Listed at 115 psi on the following sizes&pipes.
2"-3"on XL-II,XL pipe manufactured by Allied Tube&Conduit Corp,
2"-4"on Dyna-Flow,Super-Flo pipe manufactured by Allied Tube&Conduit Corp,
1-1/4"-4"on FLF pipe manufactured by Western International Forest Products Inc.,
1-1/4",2"-3"on SPS pipe manufactured by Yieh Phui Enterprise Co.,Ltd.,
1-1/4",2"-3"on Sch.5 pipe.
4-2)FM approved at 300 psi on the following sizes&pipes.
2-1/2",5"-6"on BS1387(M)medium or heavy grade pipe,
1-1/4",1-1/2"&4"on Fire-Flow(Allied)pipe,
1-1/2"&2"on Fire-Thread pipe,
1"-3"on Super4O,Super-XL pipe,
1"-2"on TL(Central)&LS pipe.
FM approved at 175 psi on the following sizes&pipes.
1-l/4"-3"on XL-II(Allied) pipe,
1-1/4"--2",3"-4"on BS1387 pipe,
1-1/4"--4"on Eddy-Flow,Super-Flo pipe,
1-1/4"-2"on BLT,Eddylite,WST(Wheatland),Gal-5(IDOD Systems)pipe,
1"-2"on Ultra Eddy(Bull Moose)pipe,
1-1/2"-4"on Eddy-Flow pipe.
5. 5-1)UL Listed at 300 psi on the following sizes&pipes.
2"-6"on BS1387(M),British Standard Medium Steel pipe pipe,
14"&16"on Sch.30 pipe,
18"&20"on Sch.20 pipe.
UL Listed at250 psi in size 22"&24"on Sch.20 pipe.
5-2)FM approved at 175 psi in size 22"&24"on Sch.20 pipe.
6. 6-1)UL Listed at 300 psi on the following sizes&pipe.
1-1/4"-6"on BS1387 pipe,1-1/4"-3"on Super 40,Super-XL pipe,1-114"--4"on Dyna-Flow,Super-Flo pipe,1-1/4"-1-1/2"on
Fire-Line Flow pipe,1-1/4"-2"on Fire-Thread pipe&Eddlylite pipe.
UL Listed at 175 psi in size 1-1/4"--2"on Sch.5 pipe.
6-2)FM approved at 300 psi on the following sizes&pipes.
1-1/4"-6"on BS1387 pipe,
1-1/4"-3"on Super 40,Super-XL(Allied)pipe,
1"7 4"on Dyna-Flow,Super-Flo(Allied)pipe,
1"-2"on Ultra Eddy(Bull Moose)pipe,
13/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shurjoint Piping Products 9 1 800 746-GROOVED • Las Vegas,Nevada USA. www.shudoint.com
SHUROINT 9PRODUCTS J
Ymmshuloint.com
1-1/2"-2"on Fire-Thread pipe,
1-1/4"--2"on Eddylite(Bull Moose),WST(Wheatland)pipe.
7. 7-1)UL Listed at 350 psi on the following sizes&pipe.
1-1/4"--4"on BS1387(M)British Standard Medium Steel pipe pipe
2"-4"on Dyna-Flow,Super-Flo pipe manufactured by Allied Tube&Conduit Corp,
UL Listed at 300 psi on the following sizes&pipe.
1-1/4"-2"on XL,BLT,WLT pipemanufactured by Allied Tube&Conduit Corp,
1-1/4"-2"on WLS manufactured by Wheatland Tube Co
1-1/4"-2"on Eddylite pipe manufactured by Bull Moose Tube Co.
1-1/4"-2"on Fire-Line Threadable pipe manufactured by Western International Forest Products Inc.1-1/4"-1-1/2"on Dyna-Flow,
Super-Flo pipe manufactured by Allied Tube&Conduit Corp,
1-1/4"--4"on Mega-Flow pipe manufactured by Wheatland Tube Co.
1-1/4"on Eddy Flow pipe manufactured by Bull Mosose Tube Co.
3"&4"on EZ-Flow pipe manufactured by Northwest Pipe Co.,
1-1/4"&2"on MT pipe manufactured by Wheatland Tube Co.
UL Listed at 175 psi on the following sizes&pipes.
1-1/2"-3"on Eddy Flow pipe manufactured by Bull Mosose Tube Co.,
1-1/4"-2"on Sch.5 pipe,
6"on EZ-Flow pipe manufactured by Northwest Pipe Co.,.
7-2)FM approved at 350 psi in size 1-1/4"on XL pipe.
FM approved at 300 psi on the following sizes&pipes.
2"--4"on Dyna-Flow,Super-Flo pipe,
1-1/4"--4"on Mega-Flow pipe.
FM approved at 175 psi on the following sizes&pipes.
2"-4"on Dyna-Flow,Super-Flo pipe,
1-1/4"--4"on Mega-Flow pipe.
1-1/2"-3"on Eddy Flow,Fire-Thread pipe.
S. 8-1)UL listed at 300 psi on the following sizes&pipe.
1-1/4"-4"on Dyna-Flow manufactured by Allied Tube&Conduit Corp.,and EF pipe manufactured by Bull Moose Tube Co.,and
Mega-Flow pipe manufactured by Wheatland Tube Co.
3"-4"on EZ-Flow pipe manufactured by Northwest Pipe co
1-1/4"-2"on Eddylite pipe manufactured by Bull Moose Tube Co.,and MLT,WLS pipe manufactured by Wheatland Tube Co.
UL Listed at 175 psi on the following sizes&pipe.
1-1/4"-4"on Eddy Flow pipe manufactured by Bull Moose Tube Co.
1-1/4"-2"on Sch.5 pipe,
6"on EZ-Flow pipe manufactured by Northwest Pipe Co.
8-2)FM approved at 350 psi in size 1-114"-2"on XL pipe.
FM approved at 300 psi in size 1-1/4"-4"on Mega-Flow pipe.
FM approved at 175 psi in size 1-1/211-3"on Fire-Thread,Eddy Flow pipe.
9. 9-1)UL listed at 175 psi on the following pipe.
3"OD,4"-5"on BS 1387(1VI)British Standard Medium Steel pipe pipe,
12"on Sch.30(0.330 in)pipe..
10"on Sch.10(0.188 in)pipe.
9-2) FM approved at 175 psi on the following pipe.
2-1/2,4 in.British Standard BS 1387 medium or heavy pipe.
2"-12",14",16"24"Min schedule cut groove pipe to be joined:8 in.or smaller Schedule 40.
2"-12",14",16"24"Min schedule rolled groove pipe to be joined:8 in.or smaller Schedule 10.
10. 10-1)UL listed at 300 psi in size 31lx2"-2-1/2",4"x2-1/2"-3",6"x4"on BS1387 and
10-2)FM approved at 300 psi on BS1387(M)or heavy grade pipe.
11. UL listed at 175 psi in size 1-1/4'-2"on BS1387 pipe.
12. 12-1)UL listed at 300 psi in size 1-1/4"2-1/2"on XL,Super-Flo pipe,175 psi in size 1-1/4"-2-1/2"on Dyna-Flow,XL II,BS1387 pipe.
12-2)FM approved at 300 psi in size 1-1/4"-2-1/2"on Dyna-Flow,XL,Super-Flo(Allied)pipe,1-1/4"-2"on BLT(Allied)pipe,TL
(Central),Eddylite(Bull Moose),WLS,LS (Wheatland)pipe.
13. 13-1)UL listed at 300 psi in size 2"x 2'/z"-8"x 4"on BS1387 pipe
13-2)UL listed at 300 psi in size 3"x x 4"on BS1387 pipe
14.Light wall pipe shall be of the minimum wall thickness 0.188 in.Sch.10.
15.Rolled and Cut grooved basked on Sch.30(0.330")pipe.
16.Rolled and Cut grooved based on Sch.20(0.375 wall thickness pipe)
17.Rolled and Cut grooved based on Sch.30(0.375 wall thickness pipe)
18.Minimum schedule cut groove pipe to be joined:6"in or smaller-Sch.40;8"in or larger-Sch.30
19.Minimum schedule roll grooved pipe to be joined:6"or smaller-Sch.10,8 and 10"-0.188 in wall;12"-0.250 in wall.
20.UL listed at 300 psi in size 76.1mm,139.7mm,165.1mm on Sch.10S,40S pipe.
21.a)Provides a rigid transition between flanged components and a grooved system.
b)Min schedule cut groove pipe to be joined:8 inches or smaller-Sch.40
c)Min schedule rolled groove pipe to be joined:8 inches or smaller-Sch.10.
14/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shurjoint Piping Products a 1 800 746-GROOVED e Las Vegas,Nevada USA• www.shudoint.eom
AD USTA � E SWI EL RIiNG ANGER=
FUNCTION: Designed for the suspension of non-insulated stationary pipe lines.The
knurled insert nut that allows a vertical adjustment after installation,is a iFg.141 & 1t4y1Fill'I li
topped to NFPA reduced rod size standards. Fig.141F has a layer of felt N¢FPA SWIVEIL f
which separates the pipe from the hanger to reduce vibration and sound. to I
APPROVALS: Uiiderivriters'Laboratories listed and Factory Mutual approved Fig.141 IZ�IIN�i HANCiE�It
%"to 8"sizes only.Complies with Federal Specification A-A-1192A(Type
10),Manufacturers'Standardization Society SP-69(Type 10)and NFPA Fig. 141 PRE-GALVANIZED
standards for reduced rod sizes.
Fig. 141F PRE-GALVANIZED
ORDERING: Specify pipe size and figure number. WITH FELT LINING
Rod
Pipe Sae. "Adj. Max.Rec.Wt. Each
Size B D E. Load/lbs. (inlbs.): -`
A C t
1/2 % 1 7/e 17/16 23/4 31/16 300 .10
3/4 % 111/16 11/e 21/2 31/16 300 .10
1 % 1 15/8 1 21/2 33/16 300 .10 1 C
11/4 % 115/16 11/16 213/16 39/16 300 .11 �� I B
11/2 % 21/s 1'/16 3'/s 37/6 300 .11 �' +
2 % 27/16 11/8 35/16 4% 300 .14 �� D
2'/z % 23/a 1'/a 311h6 5 525 .19• i E
3 % 27/e 11/e 33/4 59/16 525 .23 ;
31/2. % 33/e 1% 45/16 65/16 525 .25
4 3/8 37/e 11/2 41/2 7 650 .30
5 '/z 45/e 1% 5% 8% 1000 .50
6 '/z 5% 21/4 61/2 913/16 1000 .58
8 '/z 613/1s 21/16 r 715/1s 12'/a 1000 .90 O
FM �L
Note: If ordering Fig.141F felt lined hangers for pipe sizes of 3'/Z"or under,order the next
argest size to allow for the thickness of the felt lining. MATERIAL: Low carbon steel
FUNCTION: Designed for the suspension of non-insulated stationary pipe lines.The
aJ Fir 1�5L1 & 1►51F " j'
knurled insert nut,allows for vertical adjustment after installation.
Fig.151F has a layer of felt which separates the pipe from the hanger to �1� SWIVE9L
reduce vibration and sound.
APPROVALS: Underwriters'Laboratories listed and Factory Mutual approved Fig.151 RI�N ` HA�NGEiIZ
21/z"to 8"sizes only.Complies with Federal Specification A-A-1192A
(Type 10),and Manufacturers'Standardization Society SP-69(Type 10). Fig. 151 PRE-GALVANIZED
ORDERING: Specify pipe size and figure number. Fig. 151F PRE-GALVANIZED
WITH T LINING
Rod
Pipe Size . Adj.. Max.Rec.Wt.Each _Ff—�
Size A B C. :. p E:. Load/Ibs. (in Ibs.) `_..
21/2 1/z 23/4 11/4 311/16 51/s 600 .33 ✓ :. fY..
3 '/z 31/e 11/e 4 57/e 600 .35 f
31/2 '/z 1 3% 11/2 45/16 65/e 600 .37
4 % 37/e 11/a 415/16 71/e 1000 .48
5 % 43/e 13/6 55/e 81/2 1000 .57
y
6 3/4 55/16 2 611/16 101/e 1250 1.06
8 3/4 615/16 1 2% 85/16 1 127/8 1250 1.32 f
Note: I{ordering Fig.151F elt lined hangers or pipe sizes of Yh or under,order the next
argest size to allow for the thickness of the felt lining.
a r r a VL
MATERIAL: Low carbon steel
PHD Manufacturing, Inc. •44018 Columbiana-Waterford Road • Columbiana, OH 44408
Toll Free(800)321-2736•Phone: (330)482-9256•Fax: (330)482-2763•www.phd-mfg.com
ARGCO GUARANTEED
THREADED ROD FASTENERS FOR STEEL
BOTTOM MOUNT FOR STEEL
-One piece Self drilling and tapping in steel up to 3/16"thick
CROSS REFERENCE
EMBEDMENT MAX, ELCO ITW SAMMY
ITEM# ROD.SIZE SHANK DIA. SHANK LENGTH DEPTH PIPE SIZE REM# HANGERMATE" SUPERSCREW°
25-30-302A 3/8"-16 1/4" 1-1/2" 1-1/2" 4" 25-30-302A EZG-470 I DST-15
25.30-303A 3/8"-16 1/4- 2" 2" 4" 25-30-302A EZG-490 DST-20
25-30.302A
BOTTOM MOUNT WITH RETAINER NUT
• -One piece self drilling and tapping in steel up to 3/16"thick
e •Retainer nut included
EMBEDMENT
ITEM# ROD SIZE SHANK DIA. SHANK LENGTH DEPTH LOAD CAPACITY APPROVALS
25-30-310A 3/8"16 1/4" 1" 1" 1,500 nu,
25-30-310V 3/8"-16 1/4" 1" 1" 1,500 Ul
25-30-31OA 25-30-311A 3/8"-12-24 511 6" 1-1/2" 1-1/2" 1,500 UL •M
25-30-311V 3/8"-12-24 5/1 6" 1-1/2" 1-1/2" 1,500
CROSS REFERENCE
SCREW SHANK POINT MAX, MINIMUM ELCO ITW SAMMY
ITEM# &LENGTH STYLE PIPE SIZE STEEL THICKNESS UL TEST LOAD
ITEM# _ HANGERMATE• SUPERSCREVI'
25-30-310A 1/4"x 1" #3 4" .060"(1.5 MM) 1500 LBS.
25-30-310A EZG-471 DSTR-1
25-30-31OV 1/4"x 1" #3 4" .060"(1.5 MM) 1500 LBS.
25-30-311A 12124"x 1-1/2" #5 4" .060"(1.5 MM) 1500 LBS. 25-30-311A EZG-491
25-30-311V 12124"x 1-1/2" #5 4" .060"(1.5 MM) 1500 LBS.
Recommended to be installed with
Universal Steel&Wood Nut Driver(25-30-324V)
SYSTEM
SENSOR®
WFD Series
Waterflow Detector
System Sensor' WFD series is compatible
with schedule 10 through 40 steel pipe,sizes
2"through 8,and can be mounted in a vertical
or horizontal position.
Features Robust Construction.The WFD series consists of a rugged,
NEMA 4 rated enclosure.Designed for both indoor and outdoor
•Two-inch conduit openings in new WFD30-2 models use,the WFD series operates across a wide temperature range,from
•UL listed models are NEMA 4 rated 32°F to 120°F.
•Sealed retard mechanism immune to dust and other contaminants Reliable Performance.UL listed models are equipped with
•Visual switch activation tamper resistant cover screws to prevent unauthorized entry.Inside,
two sets of SPDT(Form Q synchronized switches are enclosed in a
•Field replaceable retard mechanism and SPDT switches durable terminal block to assure reliable performance.
•Rugged,dual SPDT switches enclosed in a durable terminal block
False Alarm Immunity.The WFD series incorporates a mechanical
•Accommodates up to 12 AWG wire retard feature,which minimizes the risk of false alarm due to
•Designed for both indoor/outdoor use pressure surges or air trapped in the sprinkler system.In addition,
the mechanical retard's unique sealed design is immune to dust and
•100 percent synchronization activates both alarm panel and other contaminants.
local bell
•Tamper resistant cover screws Simplified Operation.The WFD series is designed to simplify
installation.Two conduit openings permit easy attachment to the
local alarm system.The retard mechanism and dual SPDT switches
are field-replaceable.
Agency Listings
& O U�` s MEA FM
LISTED approved A0
5739 C5169 7770-1209.140 167-93-E 1W9A2AH
Waterflow Detector Specifications
Engineering Specifications
Vane-type waterflow detectors shall be installed on system piping as designated,on the drawing and/or as specified herein.Detectors shall mount on any
clear pipe span of the appropriate nominal size,either a vertical upflow or horizontal'run,at least 6"from any fittings which may change water direction,
flow rate,or pipe diameter or no closer than 24"from a valve or drain.Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a
static pressure rating of 456 psi*for 2"—8"pipes.The detector shall respond to waterflow in the specified direction after a preset time delay which is field
adjustable.The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation.The actuation mechanism shall include
a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism.Outputs shall consist of dual
SPDT switches(Form C contacts).Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors.
A grounding provision is provided.Unless noted,enclosures shall be NEMA 4listed by Underwriters Laboratories Inc.All detectors shall be listed by
Underwriters Laboratories Inc.for indoor or outdoor use.
Standard Specifications
Static Pressure Rating 450 PSI* Operating Temperature Range 32eF to 120eF(0eC to 49'Q
Maximum Surge 18 Feet Per Second(FPS) Enclosure Rating* NEMA 4—suitable for indoor/outdoor use
Triggering Threshold 4-10 GPM Cover Tamper Switch Standard with ULC models,optional for UL
Bandwidth(Flow Rate) models,part no.546-7000
Conduit Entrances Two openings for'/2"conduit. Service Use Automatic Sprinkler:NFPA-13
One open,one knock-out type One orTwo Family Dwelling:NFPA 13D
Residential Occupancies up to 4 Stories:NFPA 13R
National Fire Alarm Code:NFPA-72
Contact Ratings Two sets of SPDT(Form C) U.S.Patent Numbers 3,845,259
10.0 A,Y2 HP @ 125/250 VAC 4,782,333
2.5 A @ 6/12/24 VDC 5,213,205
Compatible Pipe Steel water pipe,schedule 10 through 40 Warranty 3 Years
WFDE Field Wiring Diagram Delay Adjustment Dial Overall Dimensions,Installed
Oetay
D a7a•
CommoneMBmmvw CONGCi MTpICs � Menl ��� °
di ldase*Tm n dial
0
desepetl.l.e.,wl�n er6 t25Q50 VAC tOAMPs
n°Mnp'DualeMblme pertM 24 VOp 26AMPs y O
oly4 tlona to po mmpnad O 34' WFD2o 4.W WFD40 69•---- sl,gb detetlor. WF025 4.6' WFD50 7.a'
VfFD WF➢ o WFD-2 52 WF060 9.0•
' __ WF035 97' WF080 tea'
a o 0 45
m roirstenceacaI e,ga.6re
If nMOC FACP py �u m esaddl.
I
------�-I Pipe mOdle
TWa FRCP c^,.onm" NOTE:Retard time may—W 90 semnQs.
Adjust and,or y mat time does not mooeed 90 se—dis
Pipe
TO�� loal
ine'oe wu ee1 a°eA.vo oa snnmror sooarwon
o4frw�nonpactlon DO NOTalinppyp,�
sx4tA nouWlp WNOTI pwtrei
TyprN sam e.o eoneealoe u eon
wFo
' .0.
Ordering
UL Model ULC Model Pipe Size Hole Size Shipping Weight
WFD20 WFD20A 2" 1'/4" 42lbs.
WFD25 WFD25A 2'/2" 11/4" 4.3lbs.
WFD30-2 WFD30-2A 3" 2" 4.5lbs.
WFD35 WFD35A 3'/2' 1'/4" 4.71bs.
WFD40 WFD40A 4" 2" 5.2lbs.
WFD50 WFD50A 5" 2" 6.3lbs.
WFD60* WFD60A 6" 2" 6.8lbs.
WFD80* WFD80A 8" 2" 7.5lbs.
Accessories
A3008-00 Retard mechanism
A77-01-02 Terminal block
546-7000 Tamper proof switch kit
WFDW Tamper proof wrench for cover
WFDN4 Gasket kit
*Maximum pressure rating 400 psi as approved by Factory Mutual.
SYSTEM 1120075ystem Sensor
3825 Ohio Avenue•St.Charles,IL 60174 Produasp-fi nssu abobjeatochangewi notice Visit
thout sit sym mwrisoncom for
4SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 wrrent product informirwr,induding the Wtestversionofttisdarasheet
A05-0180-011.3/07.81676
Beneficial Fire Protection Page 1
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
HVdraulic Design Information Sheet
Name - Hawk Aircraft Painting Date - 9/18/18
Location - 39317 Airpark Rd.
.Building - System No. -
Contractor - Beneficial Fire Protection, Inc. Contract No. -
Calculated By - SG Drawing No. - FP1
Construction: ( ) Combustible (X) Non-Combustible Ceiling Height - 16'
Occupancy - Extra Hazard II -- Paint Booth
S ( ) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 (X) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
S Other
T Specific Ruling Made By Date
E
M Area of Sprinkler Operation - 2500 SF System Type Sprinkler/Nozzle
Density - .40 (X) Wet Make Tyco
D Area Per Sprinkler - 100 SF ( ) Dry Model TY5211
E Elevation at Highest Outlet - 17.500 ( ) Deluge Size 3/4
S Hose Allowance - Inside - ( ) Preaction K-Factor 11.2
I Rack Sprinkler Al-lowance - ( ) Other Temp.Rat.212
G Hose Allowance - Outside - 500
N
Note
Calculation Flow Required - 1493.18 Press Required - 59.23 Riser
Summary C-Factor Used: 120 Overhead 140 Underground
W Water Flow Test: Pump Data: Tank or Reservoir:
.A Date of Test - 8/17/17 Cap. -
T Time of Test - Rated Cap.- Elev.-
E Static Press - 70 @ Press -
R Residual Press - 65 Elev. - Well
Flow - 1190 Proof Flow
S Elevation - -3
U
P Location - 39317 Airpark Rd.
P
L Source of Information - City of Zephyrhills Utilities
Y
C Commodity Class Location
0 Storage Ht. Area Aisle W.
M Storage Method: Solid Piled % Palletized % Rack
M
( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Enca
P•
S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non
T A ( ) Mult. Row ( ) Open Shelf
0 C
R K Flue Spacing Clearance:Storage to Ceiling
A Longitudinal Transverse
G
E Horizontal Barriers Provided:
����oo�'7ops
Water Supply Curve C
Beneficial Fire Protection Page 2
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
City Water Supply: Demand:
C1 -Static Pressure : 70 D1 - Elevation 8.879
C2- Residual Pressure: 65 D2-System Flow :993.18
C2 Residual Flow 1190 D2-System Pressure 59.237
Hose ( Demand) :500
D3-System Demand : 1493.18
Safety Margin 3.154
150
140
130
P 120
R 110
E 100
S 90
S 80
C1
U 70
D2
R 60
E 50
40
30
20
10 D1
200 400 600 800 1000 1200 1400 1600 1800
FLOW ( NA1.85)
Computer Programs by Hydratec Inc. Route 1.11 Windham N.H. USA 03087
Fittings Used Summary.
Beneficial Fire Protection Page 3
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
Fitting Legend
Abbrev. Name 1/2 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0
E 90'Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
K Generic Detector Check Valve 0 0 0 0 0 0 0 14 0 14 0 36 55 45 0 0 0 0 0 0
S Generic Swing Check Valve 4 5 5 7 9 11 14 16 19 22 27 32 45 55 65 76 87 98 109 130
T 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec'Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary STANDARD
Beneficial Fire Protection Page 4
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Reg.
D001 0.0 11.2 12.5 na 39.6 0.4 99 7.0
20 17.5 13.33 na
1A 17.5 K=K @ EQ01 12.81 na 39.78
1 B 17.5 K=K @ EQ01 12.71 na 39.62
1 C 17.5 K=K @ EQ01 12.7 na 39.6
1 D 17.5 K=K @ EQ01 12.71 na 39.62
1 E 17.5 K=K Ca EQ01 12.8 na 39.77
21 17.5 13.33 na
1 F 17.5 K=K @ EQ01 12.81 na 39.78
1 G 17.5 K=K @ EQ01 12.71 na 39.63
1 H 17.5 K=K @ EQ01 12.7 na 39.61
11 17.5 K=K @ EQ01 12.71 na 39.63
11 17.5 K=K @ EQ01 12.81 na 39.77
22 17.5 13.34 na
1 K 17.5 K=K @ EQ01 12.83 na 39.8
1 L 17.5 K=K @ EQ01 12.73 na 39.65
1 M 17.5 K=K @ EQ01 12.71 na 39.63
1 N 17.5 K=K @ EQ01 12.73 na M65
10 17.5 K=K @ EQ01 12.82 na 39.8
23 17.5 13.36 na
1 P 17.5 K=K @ EQ01 12.85 na 39.84
1 Q 17.5 K=K @ EQ01 12.75 na 39.69
1 R 17.5 K=K @ EQ01 12.74 na 39.67
is 17.5 K=K @ EQ01 12.75 na 39.69
IT 17.5 K=K @ EQ01 12.85 na 39.85
24 17.5 13.4 na
1 U 17Z K=K @ EQ01 12.9 na 39.91
IV 17.5 K=K @ EQ01 12.8 na 39.76
1 W 17.5 K=K @ EQ01 12.79 na 39.75
ix 17.5 K=K @ EQ01 12.8 na 39.77
1 Y 17.5 K=K @ EQ01 12.9 na 39.92
35 17.5 13.58 na
29 17.5 13.34 na
30 17.5 13.34 na
31. 17.5 13.34 na
32 17.5 13.36 na
33 17.5 13.4 na
34 17.5 13.46 na
36 17.5 13.88 na
TOR 17.5 14.6 na
BOR -3.0 25.99 na
BFD 3.0 34.92 na
BFS 3.0 42.11 na
UG1 -3.0 58.53 na
SRCE -3.0 5924 na 500.0
The maximum velocity is 24.14 and it occurs in the pipe between nodes BOR and BFD
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Beneficial Fire Protection Page 5
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv '*' Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
D00.1 39.60 2.067 T 10.0 1.500 12.501 K Factor= 11.20
to 120.0 0.0 10.000 0.0
EQ01 39.6 0.0170 0.0 11.500 0.195 Vel = 3.79
0.0
39.60 12.696 K Factor= 11.11
20 -100.14 2.703 T 18.651 1.670 13.329
to 120.0 0.0 18.651 0.0
1 A -100.14 -0.0255 0.0 20.321 -0.518 Vel = 5.60
1 A 39.78 2.703 0.0 10.080 12.811 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 B -60.36 -0.0100 0.0 10.080 -0.101 Vel = 3.37
1 B 39.62 2.703 0.0 10.080 12.710 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
10 -20.74 -6.0014 0.0 10.080 -0.014 Vel = 1.16
1 C 39.60 2.703 0.0 10.080 12.696 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 D 18.86 0.0012 0.0 10.080 0.012 Vel = 1.05
lb 39.62 2.703 0.0 10.080 12.708 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 E 58.48 0.0094 0.0 10.080 0.095 Vel = 3.27
1 E 39.77 2.703 T 18.651 3.000 12.803 K Factor @ node EQ01
to 120.0 M 18.651 0.0
30 98.25 0.0246 0.0 21.651 0.533 Vel = 5.49
0.0
98.25 13.336 K Factor= 26.90
21 -99.94 2.703 T 18.651 1.670 13.330
to 120.0 0.0 18.651 0.0
1 F -99.94 -0.0254 0.0 20.321 -0.516 Vel = 5.59
1 F 39.78 2.703 0.0 10.080 12.814 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 G -60.16 -0.0099 0.0 16.080 -0.100 Vel = 3.36
1 G 39.63 2.703 0.0 10.080 12.714 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 H -20.53 -0.0014 0.0 10.080 -0.014 Vel = 1.15
1 H 39.61 2.703 0.0 10.080 12.700 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
11 19.08 0.0012 0.0 10.080 0.012 Vel = 1.07
11 39.62 2.703 0.0 10.080. 12.712 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
11 58.7 0.0095 0.0 10.080 0.096 Vel = 3.28
1 J 39.77 2.703 T 18.651 3.000 12.808 K Factor @ node EQ01
to 120.0 0.0 18.651 0.0
31 98.47 0.0247 0.0 21.651 0.535 Vel = 5.51
0.0
98.47 13.343 K Factor= 26.96
22 -99.62 2.703 T 18.651 1.670 13.339
to 120.0 0.0 18.651 0.0
1 K -99.62 -0.0252 0.0 20.321 -0.513 Vel = 5.57
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Beneficial Fire Protection Page 6
HAWK AIRCRAFT ZEPHYRHILLS Date 09111.8
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv """' Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
1 K 39.80 2.703 0.0 10.080 12.826 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 L -59.82 -0.0098 0.0 10.080 -0.099 Vel = 3.34
1 L 39.65 2.703 0.0 10.080 12.727 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 M -20.17 -0.0013 0.0 10.080 -0.013 Vel = 1.13
1 M 39.63 2.703 0.0 10.080 12.714 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 N 19.46 . 0.0012 0.0 10.080 0.012 Vel = 1.09
1 N 39.65 2.703 0.0 10.080 12.726 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
10 59.11 0.0096 0.0 10.080 0.097 Vel = 3.30
10 39.79 2.703 T 18.651 3.000 12.823 K Factor @ node EQ01
to 120.0 0.0 18.651 0.0
32 98.9 0.0249 0.0 21.651 0.540 Vel = 5.53
0.0
98.90 13.363 K Factor= 27.05
23 -99.20 2.703 T 18.651 1.670 13.362
to 120.0 0.0 18.651 0.0
1 P -99.2 -0.0251 0.0 20.321 -0.510 Vel= 5.55
1 P 39.84 2.703 0.0 10.080 12.852 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 Q -59.36 -0.0097 0.0 10.080 -0.098 Vel = 3.32
1 Q 39.69 2.703 0.0 10.080 12.754 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 R -19.67 -0.0012 0.0 1.0.080 -0.012 Vel = 1.10
1 R 39.67 2.703 0.0 10.080 12.742 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
is 20.0 0.0013 0.0 10.080 0.013 Vel = 1.12
is 39.69 2.703 0.0 10.080 12.755 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 T 59.69 0.0098 0.0 10.080 0.099 Vel = 3.34
1 T 39.85 2.703 T 18.651 3.000 12.854 K Factor @ node EQ01
to 120.0 0.0 1.8.651 0.0
33 99.54, 0.0252 0.0 .21.651 0.546 Vel = 5.57
0.0
99.54 13.400 K Factor= 27.19
24 -98.72 2.703 T 18.651 1.670 13.402
to 120.0 0.0 18.651 0.0
1 U -98.72 -0.0248 0.0 20.321 -0.504 Vel = 5.52
1 U 39.92 2.703 0.0 10.080 12.898 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 V -58.8 -0.0095 0.0 10.080. -0.096 Vel = 3.29
1 V 39.76 2.703 0.0 10.080 12.802 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 W -19.04 -0.0012 0.0 10.080 -0.012 Vel = 1.06
1 W 39.75 2.703 0.0 10.080 12.790 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
ix 20.71 0.0014 M 10.080 - 0.014 Vel = 1.16
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Beneficial Fire Protection Page 7
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total :Pf Pn
ix 39.76 2.703 0.0 10.080 12.804 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
1 Y 60.47 0.0100 0.0 10.080 0.101 Vel = 3.38
1 Y 39.93 2.703 T 18.651 3.000 12.905 K Factor @ node EQ01
to 120.0 0.0 18.651 0.0
34 100.4 0.0256 0.0 21.651 0.555 Vel = 5.61
0.0
100.40 13.460 K Factor= 27.37
20 57.27 6.357 0:0 9.830 13.329
to 120.0 0.0 0.0 0.0
21 57.27 0.0001 0.0 -9.830 0.001 Vel = 0.58
21 99.94 6.357 0.0 9.830 13.330
to 120.0 0.0 0.0 0.0
22 157.21 0.0009 0.0. 9.830 0.009 Vel = 1.59
22 99.62 6.357 0.0 9.830 13.339
to 120.0 0.0 0.0 0.0
23 256.83 0.0023 0.0 9.830 0.023 Vel = 2.60
23 99.20 6.357 0.0 9.830 13.362
to 120.0 0.0 0.0 0.0
24 356.03 0.0041 0.0 9.830 0.040 Vel = 3.60
24 98.72 6.357 E 17.603 9.340 13.402
to 120.0 0.0 17.603. 0.0
35 454.75 0.0065 0.0 26.943 0.176 Vel = 4.60
35 0.0 6.357 G 3.772 4.670 13.578
to 120.0 T 37.72 41.492 0.0
36 454.75 0.0065 0.0 46.162 0.300 Vel = 4.60
0.0
454.75 13.878 K Factor= 122.07
20 42.87 .6.357 2E 35.205 46.000 13.329
to 120.0 0.0 35.205 0.0
29 42.87 0.0001 0.0 81.205 0.007 Vel = 0.43
29 0.0 6.357 0.0 1.000 13.336
to 120.0 0.0 0.0 0.0
30 42.87 0.0 0.0 1.000 0.0 Vel = 0.43
30 98.25 6.357 0.0 9.830 13.336
to 120.0 0.0 0.0 0.0
31 141.12 0.0007 0.0 9.830 0.007 Vel= 1.43
31 98.47 6.357 0.0 9.830 13.343
to 120.0 0.0 0.0 . 0.0
32 239.59 0.0020 0.0 9.830 0.020 Vel = 2.42
32 98.91 6.357 0.0 9.830 13.363
to 120.0 0.0 0.0 0.0
33 338.5 0.0038 0.0 9.830 0.037 Vel = 3.42
33 99.54 6.357 0.0 9.830 13.400
to 120.0 M 0.0 0.0
34 438.04 0.0061 0.0 9.830 0.060 Vel = 4.43
34 100.39 6.357 T 37.72 9.340 13.460
to 120.0 0.0 37.720 0.0
36 538.43 0.0089 0.0 47.060 0.418 Vel = 5.44
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Beneficial Fire Protection Page 8
HAWK AIRCRAFT ZEPHYRHILLS Date 091118
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv '*"`"` Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
538.43 13.878 K Factor= 144.53,
36 993.18 6.357 E 17.603 4.670 13.878
to 120.0 G 3.772 21.375 0.0
TOR 993.18 0.0276 0.0 26.045 0.720 Vel = 10.04
0.0
993.18 14.598 K Factor=259.94
TOR 993.18 6.357 E 17.603 20.500 14.598
to 120.0 S 40.235 70.411 8.879
BOR 993.18 0.0276 B 12.573 90.911 2.511 Vel = 10.04
0.0
993.18 25.988 K Factor= 194.82
BOR 993.18 4.1 3E 43.601 22.000 25.988
to 140.0 0.0 43.601 -2.599
BFD 993.18 0.1758 0.0 65.601 11.534 Vel = 24.14
BFD 0.0 4.1 E 14.534 6.000 34.923
to 140.0 K 20.347 34.881 0.0
BFS 993.18 0.1758 0.0 40.881 7.187 Vel = 24.14
BFS 0.0 4.1 E 14.534 35.000 42.110
to 140.0 T 29.067 43.601 2.599
UG1 993.18 .0.1758 0.0 78.601 13.819 Vel = 24.14
UG1 0.0 6.16 G 4.304 25.000 58.528
to 140.0 0.0 4.304 0.0
SRCE 993.18 0.0242 0.0 29.304 0.709 Vel = 10.69
500.00 Qa= 500.00
1493.18 59.237 K Factor= 194.01
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
SUBMITTAL DATA FOR:
HAWK AIRCRAFT
39317 AIRPARK RD.
ZEPHYRHILLS,FLORIDA
SEPTEMBER 19,2018
BENEFICIAL FIRE PROTECTION, INC.
12522 US Highway 301 N. Suite 1
Thonotosassa, Florida 33592
Phone: (813) 986-5819
Fax: (813) 986-5837
State Certification: #45018800011989
State Certification: #67451300012005
INDEX
SPRINKLER HEADS:
Globe 1/z"QR 212' Brass ELO-231 Pendent TY5211 — 11.2 K-Factor
Globe 1/z" QR 155' Chrome Semi-Recessed Pendent GL5601 -- 5.6 K-Factor
PIPE:
Black Thinwall Pipe
Black Schedule 10 Pipe
Black Schedule 40 Pipe
VALVES:
Riser Butterfly Control Valve
Riser Check Valve
2"Angle Valve
FITTINGS:
Threaded Fittings
Grooved Fittings
Welded Fittings
MISC:
Hanger Rings
Hanger Fasteners
Electric Bell
Flow Switch
CO� Worldwide www.tycb-fire.com
Contacts
Series ELO-231 - 11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General and gas/chemical velocity, should be
considered, as a minimum, along with
Descri t�On the corrosive nature of the chemical to ,'►
p which the sprinklers will be exposed. _
TYCO Series ELO-231 11.2K Stan- An upright intermediate level version
dard Response, Standard Coverage of the Series ELO-231 Sprinklers for
Upright and Pendent Sprinklers (Ref. in-rack applications can be obtained
Figure 1) are automatic sprinklers of by utilizing the Series ELO-231 Upright
the fusible solder type.They are stan- Sprinkler with the WSG-2 Guard &
dard response, spray sprinklers that Shield, and a pendent intermediate
produce a hemispherical water distri- level version of the Series ELO-231
bution pattern below the deflector. Sprinklers can be,obtained by utilizing
The 11.2 K-factor, ELO-231 Sprinklers the Series ELO-231 Pendent Sprinkler
were subjected to full scale, high-piled with the WS-2 Shield. If there is a pos-
storage, fire tests to qualify their use sibility of the pendent intermediate level
in lieu of 5.6 or 8.0 K-factor standard version being exposed to mechanical
spray sprinklers for the protection of damage,a G-2 Guard can be added.
high-piled storage.
•
Higher flow rates can be achieved at The 11.2 K-factor, Series ELO-231
much lower pressures with.the king Upright and Pendent Sprinklers
hfactor, highly 1 Sprinklers, making described herein must be installed.
their use highly advantageous in high
density applications, such as the pro- and maintained in compliance with this
tection of high-piled storage. document as well as with the applica-
ble standards of the National Fire Pro-
Wax or lead coatings can be used tection Association INFPA),in addition Technical
to extend the life of the copper alloy to the standards of any other authori-
components used in Series ELO-231 ties having jurisdiction.Failure to do so Data
sprinklers beyond that which would may impair the performance of these
otherwise be obtained when exposed devices. Approvals
to corrosive atmospheres. Although UL and O-UL Listed
Wax and lead coated sprinklers have The owner is responsible for main- FM Approved
passed the standard corrosion tests of taining their fire protection system NYC Approved
the applicable approval agencies, the and devices in proper operating con- Refer to
testing is not representative of all pos- dition. Contact the installing contrac- R labor Table C for specific details
atory listings and approvals,
sible.corrosive atmospheres. Conse- for or product manufacturer with any on
p questions. including corrosion-resistant status.
quently,it is recommended that the end The approvals apply to the service con-
user be consulted with respect to the Installation of Series ELO-231 Pendent ditions indicated in the Design Criteria
suitability of these corrosion resistant Sprinklers in recessed escutcheons will section.
coatings for any given.corrosive envi- void all sprinkler warranties,as well as Finishes
ronment. The effects of ambient tem- possibly void the sprinkler's Approvals
perature, concentration of chemicals, and/or Listings. Refer to Table C
Physical Characteristics
Frame ............................Bronze
Sprinkler Seal Disc.........................Copper
IMPORTANT Iificat . Cap...::..........................Bronze
dent ion
Always refer to Technical Data Strut Assembly. Solder,Bronze Stainless Steel
Compression Screw.................Bronze
Sheet TFP700 for the "INSTALLER Numbers (SINS) Deflector.........:.....:..........Bronze
WARNING"that provides cautions Helper Spring................Stainless Steel
Ejector spring...................... Nickel
with respect to handling and instal-
Refer to Table A for sprinkler identifica- Strut Clip...................Stainless Steel
lation of sprinklersystems and com- tion numbers.
ponents. Improper handling and Additional Technical.Data
installation can permanentlydainage Refer to Table A for additional techni-
a sprinkler system or its compo- cal data.
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Pagel of 6 MAY 2018 TFP340 -
TFP340
Page 2of6
1/2"(12,7 mm) Components:
NOMINAL MAKE-IN 1 - Frame
3/4" 2- Seal Disc
PT 1 3- Cap
1�'T4- Strut
2-13/16" 2 Assembly
(71,4 mm) WRENCH THREVgN
7 5- Compression
TYP. FLATS RELI3 Screw
/ 8 6- Deflector*
4 7- Helper
9 Spring
1/2" 3/4" 5 8- Ejector
NPT NPT Spring
7/16"(11,1 mm) 1 2"(12,7 mm) 6 9- Strut Clip
NOMINAL MAKE-IN NOMINAL MAKE-IN *Temperature
rating is
UPRIGHT - UPRIGHT PENDENT CROSS indicated on
TY5811 TY5111 TY5211 SECTION deflector
FIGURE 1
SERIES ELO-231 11.2K UPRIGHT-314"NPT(TY5111), UPRIGHT- 1/2"NPT(TY5811),AND
PENDENT-3/4"NPT(TY5211)SPRINKLERS
Operation Item Description
A fusible alloy is sealed into a bronze TY5111—Upright-3/4 in.NPT
actuating rod (center strut) by a stain- TY5211—Pendent-3/4 in.NPT
less steel ball.When the alloy melts at Sprinkler Identification Number(SIN) TY5811 —Upright-1/2 in.NPT
its rated era tem ture,the ball is forced TY5111 is a redesignation for Central SIN C5111.
p TY5211 is a redesignation for Central SIN C5211.
upward into the center strut, releas- TY5811 is a redesignation for Central SIN C5B11.
ing the two ejectors and operating the
sprinkler. K-factor,(gpm/psi)(Ipm/bar) 11.2 gpm/psi'/(161,4 Ipm/bar/2)
165°F(74°C)1
Design
Temperature Rating IF(°C)1 212°F(100°C)
286°F(141°C)
Criteria Thread Size 3/4 in.NPT or ISO 7-R 3/4
1/2 in.NPT
UL and C-UL
Listing Requirements Sprinkler Orientation Upright/Pendent
TYCO Series ELO-231 11.2K Stan- Maximum Working Pressure,psi(bar) 175 psi(12,1 bar)
dard Response, Standard Coverage
Upright and Pendent Sprinklers are Notes:
to be installed in accordance with 1. Refer to Table C for laboratory listings and approvals.
NFPA 13 standard sprinkler posi- TABLEA
tion and area/density flow calcula- SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLER
tion requirements for light, ordinary, TECHNICAL DATA
or extra hazard occupancies, as well
as high piled storage occupancies,
such as solid piled, palletized, rack
storage, bin box, and shelf storage
including but not limited to Class l-IV
and Group A plastics,with a minimum
residual (flowing) pressure of 7 psi
(0,5 bar)for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231
Sprinklers are to be installed in accor-
dance with the applicable control mode
density/area guidelines provided by FM
Global.
Note: FM Approval guidelines may
differ from UL and C-UL Listing criteria.
TFP340
Page 3 of 6
Storage Type NFPA FM Global
Sprinkler Type Standard Coverage Storage
Response Type SR SR
System Type Wet Wet
165°F(74°C)1 165°F(74°C)1
Temperature Rating OF(°C)1 212°F(100°C) 212°F(100°C)
286°F(141°C) 286°F(141°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class HV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9
B Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0,8-9,and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage(Refer to the Standard) Refer to NFPA 13 Refer to FM 8-21
Flammable/Ignitable Liquid Storage(Refer to the Standard) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage(Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks N/A N/A
(Control mode only;refer to the Standard)
Notes:
1. Refer to Table C for laboratory listings and approvals.
N/A—Not Applicable
TABLE B
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
SPRINKLER TEMPERATURE FRAME SPRINKLER FINISH
TYPE RATING COLOR NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
165°F(74°C) Unpainted
UPRIGHT 1,2,3,4
212°F(100°C) White 1,2,3,4
(TY5111 &TY5811)
286°F(141°C) Blue 1,2,3,4 1',2',3',4'
165°F(74°C) Unpainted
PENDENT 1,2,4
(TY5211) 212°F(100°C) White 1,2,3,4
286°F(141°C) Blue 1,2,4 1',2',4'
Notes: 3. FM Approved
1. UL Listed 4. Approved by the City of New York(NYC)under MEA 291-04-E
2. C-UI Listed . Listed/Approved for a maximum ceiling temperature of 150°F(66 IC)
TABLE C
11.2K SERIES ELO-231 UPRIGHT&PENDENT SPRINKLERS,STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
QUICK RESPONSE
13 AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT• PENDENT
FIRE SPRINKLER CORPORATION VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
DESCRIPTION AND OPERATION CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a low profile
yet durable design which utilizes a 3mm frangible glass ampule as the
thermosensitive element. This provides sprinkler operation approxi-
mately six times faster than ordinary sprinklers. While the Quick - =
1p , 'Response Sprinkler provides an aesthetically pleasingappearance, it
�•.
can be installed wherever standard spray sprinklers are specified when a
allowed by the applicable standards. It offers the additional feature of
greatly increased safety to life and is available in various styles,orifices, _
temperature ratings and finishes to meet many varying design require-
ments. Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating QUICK RESPONSE
assembly is a hermetically sealed frangible glass ampule that contains UPRIGHT CONVENTIONAL
a precisely measured amount of fluid. When heat is absorbed,the liquid _
within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure within the ampule exceeds
the strength of the glass causing the glass to shatter. This results in
water discharge which is distributed in an approved pattern depending
upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. As-
sembly is done in the field.
TECHNICAL DATA QUICK RESPONSE
•See reverse side for Approvals and Specifications. PENDENT VERTICAL
•Temperature Ratings - 1350F (570C), 1550F (680C), 1750F (790C), SIDEWALL
200OF (93°C), 2860F (141°C).
6 Water Working Pressure Rating - 175 psi (12 Bars). _
• Factory tested hydrostatically to 500 psi (34 Bars). '
• Maximum low temperature glass bulb rating is -670F (-550C). `
• Frame - bronze • Deflector- brass • Screw - brass
•Bulb seat- copper • Spring - nickel alloy . Seal - teflon
•Bulb - glass with alcohol based solution, 3mm size. QUICK RESPONSE
HORIZONTAL SIDEWALL
• SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER FBULB N.F.P.A. MAXIMUM
TEMPERATURES COLOR CEILING TEMPERATURE
ORDINARY 1'35°F/155°F 57°C/68°C; ORANGE/REDNZ12
00°F 38°C
INTERMEDIATE 115°F/200°F 79°C/93°C YELLOW/GREEN50°F 66°C
HIGH 286°F 141°C BLUE 5F 107°C
4077AIRPARKDRIVE,STANDISH,MICHIGAN 48658 9894346-4583 • FAX989-846-9231
DECEMBER 2006 A-20 BULLETIN GL5615, REV. #6
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT a PENDENT 411 VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL"K:":FACTOR THREAD SIZE LENGTH FINISHES
2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) Bright ChromeWhite Polyester3
7.8 (111 metric). 1/2" NPT 2 1/4" (5.7 cm) Black Polyester
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Lead Coated 2
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. I HORIZONTAL SIDEWALL IS 2 9/16".,
P FINISHES AVAILABLE ON SPECIAL ORDER.
a AVAILABLE AS CULus LISTED CORROSION
APPROVALS RESISTANT WHEN SPECIFIED ON ORDER.
STYLE SIN K 135•F 155°F 175°F 200*F 286oF CULus F.M. LPC CE NYC-DOB
MODEL FACTOR 57 C 68 C 79 C 93.C 141 C MEA 101-92-E
GL2815 2.8 X X X X X X - - - X
GL4215 4.2 X X X X X X - - - X
UPRIGHT GL5615 5.6 X X X X X X X X X X
GL8115 7.8* X X X X X X X - - X
GL8118 8.1 X X X X X X X I X X X
GL2801 2.8 X X X X X X - - - X
GL4201 4.2 X X X X X X - - - X
PENDENT GL5601 5.6 X X X X X X X X X X
GL8101 7.8* X X X X X X X - - X
GL-8106 8.1 X X X X X X X. X X X
VERTICAL GL5632 5.6 X X X X X X X - - -
SIDEWALL GL8133 8.1 X X X X X X - - - -
81_2826 2.8 X X X X X X - - - X
HORIZONTAL GL4226 4.2 X X X X X X - - - X
SIDEWALL§ GL5626 5.6 X X X X X X X - - X
GL8127 8.1 X X X X X X - - -
CONVENTIONAL GL5624 5.6 X X X X X - - X X
(OLD STYLE) GL8125 8.1 X X X X X - - X X -
§HORIZONTAL SIDEWALL CULus LISTED FOR DEFLECTOR 4"TO 12".BELOW THE CEILING,FM APPROVED 4"TO 6'.
t VERTICAL SIDEWALL SPRINKLER CULus LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL CULus LISTED FOR 6'MIN.SPACING,
UPRIGHT VERTICAL SIDEWALL CULus LISTED FOR 9'MIN.SPACING.
ORDERING INFORMATION *1/2"NPT.
SPECIFY GLOBE@ PRODUCT WARRANTY
•Quantity • Model Number • Style Globe agrees to repair or replace any of its own
•Orifice • Thread Sizes • Temperature manufactured products found to be defective in mate-
-Finishes desired rial or workmanship for a period-of one year from date
•Quantity-Wrenches- P/N 325390 (1/2"); of shipment.
P/N 312366 (L.O.) For specific details of our warranty please refer to
Price List Terms and Conditions of Sale(Our Price List),
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
GL&)33E
989-846-4583 FAX 989-846-9231
FIRE SPRINKLER CORPORATION 1-800-248-0278 www.globesprinkler.com
DECEMBER.2006 PRINTED U.S.A. BULLETIN GL5615, REV.#6
Youngst(unkTra 'tube
TM "Quality by the Foot" Ta
Schedule 7 Sprinkler: Pipe
"Fire-Flo"
Youngstown Tube manufactures Fire-Flo(schedule 7)pipe in sizes 1 1/2"thru 4"using only high quality domestic steel coils.This
ensures a uniform superior product for roll grooving,welding or plain end uses.Youngstown Tube's Fire-Flo pipe is produced under
ASTM A135/A795 Type E,Grade A,NH standards.Every piece is Eddy-Current tested and conforms to internal SPC testing and
recording.
Fire-Flo pipe is manufactured with lighter gauge steel than conventional schedule 10 pipe.This creates a lighter,cost.effective
product with increased hydraulics over schedule 10 pipe.
Youngstown Tube Fire-Flo steel sprinkler pipe is coated with a waterbased black enamel coating,YTC Guard®antimicrobial coating
and a continuous color coded yellow stencil,and stored indoors ready for immediate shipment.
Approvals:UL Listed,CUL Listed,FM Approved
Youngstown Tube schedule 7 pipe meets the rigorous testing and certification processes of Underwriters Laboratory and Factory
Mutual for steel sprinkler pipe with working pressures of 300 psi or less.It also meets the requirements of NFPA 13.
"Fire-Flo" Schedule 7
Pieces Weight UL
Pipe Pipe Nominal Weight per Standard Feet per
Size OD Pipe ID Wall Foot Length per Bundle per Unthreaded
Bundle Bundle CRR
1 �/z 1.900 1.732 .084. 1.62 21 44 924 1,497. 2.85
2.375 2.207 .084 2.05 21 37 777 1,593 2.31
2 1/ 2.875 2.703 .086 2.55 21 37 777 1,981 1.43
33 3.500 3.314 .093F 3.38 21 24 504 1,704 1.34
�4 4.500 4.304 .098 4.37 21 19 399 1,744 1.0
Fire-Flo pipe can not be threaded or cut-grooved.
Youngstown Tube Company
401 Andrews Avenue
Youngstown,Ohio 44505
1-866-The-Tube
www.youngstowntube.com
Project: Contractor:
Submitted By: Date Submitted:
a T
"Quality by the Foot" TM
Schedule 10 Sprinkler Pipe
Youngstown Tube manufactures Schedule 10 pipe in sizes 1 1/a"thru 6" using only high quality domestic steel
coils. This ensures a uniform superior product for roll grooving, welding or plain end uses. Youngstown Tube's
schedule 10 pipe is produced under ASTM Al35/A795 Type E, Grade A, NH standards. Every piece is Eddy-
Current tested and conforms to internal SPC testing and recording.
Youngstown Tube Schedule 10 steel sprinkler pipe is coated with a waterbased black enamel coating, YTC
GuardO antimicrobial coating and a continuous color coded white stencil, and stored indoors ready for
immediate shipment.
Approvals: UL Listed, CUL Listed, FM Approved
Youngstown Tube schedule 10 pipe meets the rigorous testing and certification processes of Underwriters
Laboratory and Factory Mutual for steel sprinkler pipe with working pressures of 300 psi or less. It also meets
the requirements of NFPA 13 and can be used in wet, dry, deluge and preaction systems.
Schedule 10
Pipe Pipe Pipe Nominal Weight Standard Pieces Feet Weight UL
Size OD ID Wall per Foot Length Per per per Untreaded
Bundle Bundle Bundle CRR
1 '/a 1.660 1.442 109 1.81 21 61 1,281 . 2,319 8.5
11/ 1.900 1.682 .109 2.08 21 44 924 1,921 6.8
2.375 2.157 .109 2.64 21 37 777 2,051 5.5
2'/2 2.875 2.635 .120 3.53 21 37 777 2,742 4.1
73 13.500 3.260 .120 4.33 21 24 504 2,182 3.0
F74E500F260 120 5.61 21 19 399 2,238 1.8
6.625 6.357 .134 9.29 21 10 210 1,951 1.16
* Schedule 10 pipe can not be threaded or cut-grooved.
Youngstown Tube Company
401 Andrews Avenue
Youngstown, Ohio 44505
1-866-The-Tube
www.youngstowntube.com
Project: Contractor:
Submitted By: Date Submitted:
F'H Tube
"Quality by the Foot"
Schedule 40 Sprinkler Pipe
Youngstown Tube manufactures Schedule 40 pipe in sizes 1"thru 2" using only high quality domestic steel
coils. This ensures a uniform superior product for threading, roll grooving, welding or plain end uses.
Youngstown Tube's schedule 40 pipe is produced under ASTM A135/A795 Type E, Grade A, NH standards.
Every piece is Eddy-Current tested and conforms to internal SPC testing and recording.
Youngstown Tube Schedule 40 steel sprinkler pipe is coated with a waterbased black enamel coating, YTC
Guard®antimicrobial coating and a continuous color coded red stencil, and stored indoors ready for
immediate shipment.
Approvals: UL Listed, CUL Listed, FM Approved
Youngstown Tube schedule 40 pipe meets the rigorous testing and certification processes of Underwriters
Laboratory and Factory Mutual for steel sprinkler pipe with working pressures of 300 psi or less. It also meets
the requirements of NFPA 13 and can be used in wet, dry, deluge and preaction systems.
Schedule 40
Pipe Pipe Pipe Nominal Weight Standard Pieces Feet Weight UL
Size OD ID Wall per Foot Length Per per per Threaded
Bundle Bundle Bundle CRR
1.315 1.049 .133 1.68 21 61 1,281 2,152 1.00
1 1/1 1.660 1.380 .140 2.27 21 61 1,281 2,907 1.00
1 1/z 1.900 1.610 .145 2.72 21 924 2,511 1.00
• � 2.375 2.067 .154 3.65 21 37 777 2,836 1.00
Youngstown Tube Company
401 Andrews Avenue
Youngstown, Ohio 44505
1-866-The-Tube
www.youngstowntube.com
Project: Contractor:
Submitted By: Date Submitted:
GLR30OG
FIRE SPRINKLER Grooved Butterfly Valves
CORPORATION Grooved End,Sizes :
21/2",3",4", 6"and 8
Specifications
Working Pressure : 300 PSI (21.4 Bars)
Max. Test Pressure : 600 PSI (42.8 Bars)_
Max. Working Temp : 250°F (120°C)
Factory installed UL• Listed Double Tamper
Switch For Indoor and Outdoor Use.
Materials of Primary Components
Body: ASTM A-536 Nylon-11 Coated
Disc : ASTM A-536 EPDM ,w
Encapsulated
Upper and Lower Stems : AISI 420-SS
Worm Gear Shaft : AISI 410-SS f
�r
Housing : ASTM A-536
Hand Wheel : ASTM A-536,
Flag Indicator : ASTM A-536
Sheer Pin : ASTM A-510
Segment Gear : ASTM B-148 or B-584
Housing Gasket : EPDM Grade "E"
O-Rings (All) : EPDM Grade "E"
Approvals
NYC - DOB MEA Approved 155-06-E
UL, ULC Listed
FM Approved
r - A
E
B
O
_ 5.00 C ► • D 4.37
(127.0)
DIMENSION UNIT:IN(mM)
SIZE A B C D E Part No.
2'/:" 5.31 (135) 5.04(128). 4.13(105) 3.30(85) 3.80(96.4) 311785-G
3" 5.59(142) 5.04(128) 4.41 (112) 3.60(92) 3.80(96:4) 311790-G
4" 6.89(175) 5.04(128) 5.71 (145) 4.30(108) 4.54(115.4) 311795-G
8" 8.23(209) 8.66(220) 7.05(179) 5.71 (145) 5.21 (132.4) 311805-G
8" 9.21 (234) 1.8.66(220) 8.03(204) 6.70(170) 5.80(147.4) 311815-G
AUGUST2006 Page4 BULLETIN BUTTERFLY REV#2
GROOVED END
Flow Characteristics
1.2
F 2Y211 3" 4�� 6�� 8" ,
i
1.0
0 0.8
cc
w 0.6 s
IL _ ,
z 00 0.4
0.2
0.0
100 1,000 10,000
FLOW RATE IN GALLONS PER MINUTE(GPM)
WAFER AND GROOVED END
Friction Loss
Friction Loss in Friction Loss in
Valve Size in. Equiv. Feet of Valve Size in. Equiv. Feet of
Valve Model (mm) Pipe Valve Model (mm) Pipe
DW(Wafer) 2'/s(65) 4.8 DG(Grooved) 2'/z(65) 6.9
3(76.2) 3.5 3(76.2) 4.1
4(100) 2.4 4(100) 3
6(150). 5.1 6(150) 5.5
8(200) 5.4 8(200). 5.4
GROOVED END
Flow coefficient : Cv
DN (mutt) SIZE(in) Disk Open Angle
300 400 500 -60° 700 800 900
65 2'/z" 12 27.4 53.1 96 138 156 163 -
80 3" 18.9 39.4 78.9 144 210 243 249
100, 4" 30 65.1 129 226 377 488 514
150 6" 84 184 369 634 964 1196 1286
200 8" 165 339 677 1230 2002 2850 3129
WAFER TYPE
Flow coefficient : Cv at full open
DN (mm) 65 80 100 150 200
Size(in.) 2%2' 3" 4" 6" 8"
CV 222 389 1000 1998 4619
Cv= flow(9pm) = Q
pressure loss(psi) d F
AUGUST2006 Page6 BULLETIN BUTfERFLYREV#2
SWING CHECK
VALVE
GL "" STANDARD & '.'SHOTGUNMUNN
6 FAA, MODEL RCV
FIRE SPRINKLER CORPORATION GROOvE/GROOVE
DESCRIPTION AND OPERATION 2', 2 Y', 3" 4" & 6" .SIZES
Globe Model RCV Swing Check Valves feature a swing type
clapper designed for use in fire sprinkler or other types of water
piping systems that incorporate grooved connecting pipe ends.
They are effectively used when it is necessary to permit water flow
in one direction only, preventing flow in the reverse direction (non-
return). Because the RCV incorporates a spring-loaded clapper
assembly' it may be installed in either the vertical or horizontal
position. Most commonly, it is used with-various configurations of
fire department connections for fire sprinkler systems, by-pass
connections,.gravity pressure tank and, pump discharge in connec-
tions from publicwater supplies to automatic sprinkler systems,etc.
As an alternative to using an alarm check valve with a wet
sprinkler system, an RCV Swing Check Valve may be used in a .
"Shotgun" arrangement whereby the valve is trimmed in a similar
manner but utilizes an electric water flow switch and alarm bell
instead of a water motor gong for fire notification.
The body of the Globe RCV Swing Check Valve is constructed MODEL RCV
of high tensile strength cast iron having considerable ductility to SWING CHECK VALVE
.reduce damage in field handling. It meets the ASTM A126.Class B
rating. The RCV.clapper assembly is.made of stainless steel and
has an E.P.D.M. rubber facing. The RCV incorporates a special
stainless steel spring assembly which allows its use in the down-
ward flow direction. It effectively provides a leak tight seal against
back pressures greater than one (1) psi. PHYSICAL DIMENSIONS
APPROVALS
• cULus Listed H"
e FM Approved o
OPTIONAL FOR RISER
• NYC - DOB MEA 305-05-E INSTALLATION
TECHNICAL DATA F..
• Water Working Pressure Rating -300 psi (20.7 Bars).
Factory tested hydrostatically to 600 psi (41.4 Bars). E O
Equivalent feet of pipe: 2"Valve =7.2 feet,2 1/2"
Valve=7.2 feet, 3"Valve=7.2 feet,4"Valve-9.9 feet,
6"Valve= 16.1 feet. mNPT „,.'-14
WEIGHT
SIZE A C E F G H 1 J K L (Ibs.)
no trim
2" 1" 4" 3 1/2" 4 1/2" 6 1/2 1/4" 1 1/2" 2 1/4" 2 1/2" 4 3/4" 4.5
2 1/2" 1 1/4" 4 1/2" 4" 5" 7" 1/4" 1 1/2" 2 1/2" 2 3/4" 5 1/2" 8
3" 1 1/4" 5" 4 1/2" 6" 7 3/4". 1/4" 2" 3" 3 3/4" 6 3/4" 12
4" 2" 6 1/4" 4" 6 1/2" 8 1/2" 1/4" 2 1/2" 3 1/2" 4 1/4" 7 1/2" 17.5
6" 2" 8" 5" 8". 10 1/2" 1/4" 3
4077AIRPARKDRIVE,STANDISH,MICHIGAN48658 989-846A583 FAX989-846-9231
OCTOBER2005 JMO BULLETIN RCV REV.#1
SWING CHECK VALVE - 2", 2 %", 3" 4" & 6"
MODEL RCV - STANDARD & "SHOTGUN"
GROO VE/GROO VE
ITEM DESCRIPTION MATERIAL 2"PIN 2 V2"PIN 3"PIN 4"PIN 6"PIN
3
I Hinge Pin Stainless Steel 321521 321528- 321535 321541 321549
12 2 Torsion Spring Stainless Steel 321523 321531 321531 321545 321554
2 3 Machined Body Cast Iron 321501 321503 321505 321507 321509
8 to 4 1/2"NPT Plug Cast Iron 311003 311003 311003 311003 311003
5 Seat Ring Brass 321516 321530 321537 321543 321551
1
6 Locknut Stainless Steel 321556 321556 321556 321556 321556
9
po 7 Nameplate Aluminum 321558 321558 321558 321558 321558
5 8 Clapper Stainless Steel 321515 321527 321534 321540 321548
4 9 Clapper Facing Disc EPDM 321516 321529 321536 321542 321550
77
6 10 Sealing Washer Hard Fiber 321518 321518 321518 321516 321518
CROSS SECTION I I Disc Retainer Stainless Steel 321517 321517 321517 321544 321544
12 Hex Head Bolt Stainless Steel 321519 321519 321555 321555 321559
'SHOTGUN" TRIM ARRANGEMENT
J02 SIZE A B C 4
A.. 2" 10" 8 3/4" 2 1/4" 5
2 1/2" 11" 9 1/4" 2 1/4" 63" 12" 9 I/2" 2 I/2" 4
4" 13 1/2' IT 3 1/4' 5 8
6" 14 1/4"1 10 3/4" 4" 6
.B„
TOP VIEW FRONT VIEW
ITEM DESCRIPTION 2" 2%i' 3" 4" 6" QTY.
I RCV 321526 321533 321539 321547 321557 1
2 Angle Valve 311614(1") 311615(1 1/4") 311615(1 1/4") 311617(2") 311617(2") 1
3 Close Nipple 310500(1") 310600(1 1/4") 310600(I 1/4") 310800(2") 310800(2") 1
4 I/4"Water Gauge 300119 300119 300119 300119 300119 2
5 1/4"3 Way Valve 311683 311683 311683 311683 311683 2
6 1/4"Plug 311001 311001 311001 311001 311001 2
7 1/4"Nipple 311101 (1 1/2") 311102(2") 310102(2") 310103(21/2") 310103(2 I/2") I
8 1/4"x 5 1/2"Nipple 310109 310109 310109 310109 310109 1
ORDERING INFORMATION GLOBE@ PRODUCT WARRANTY
Globe agrees to repair or replace any of its own
SPECIFY manufactured products found to be defective in material
•Quantity • Model Number or workmanship for a period of one year from date of
•Standard or Shotgun style. shipment.
For specific details of our warranty please refer to
Price List Terms and Conditions of Sale(Our Price List).
GLIbBE
4077AIRPARKDRIVE,STANDISH,MICHIGAN 48658
FIRE SPRINKLER CORPORATION 989-846-4583 FAX989-846-9231
OCTOBER2005 PRINTEDU.S.A. BULLETIN RCV REV.#1
UNITED BRASS WORKS, INC. R
D 714 S. Main St., Randleman, NC 27317
Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com IS09001
REGISTERED COMPANY
Model 12.6SUL Angle Valve
Soft Disc
Oc L usUL Listed for Fire Sprinkler Service at 250 WOG
200 WOG @ 180 ° Max
100% Pressure Tested
Threaded Ends
Rising Stem • Integral Seat
B
I
' 3
4
C
MATERIAL LIST
\ \ 5
NO. DESCRIPTION MATERIAL \
1 Hex Nut Steel
2 Hand Wheel Aluminum 6
3 Packing Nut Brass
4 Packing Graphite Non-Asbestos
i
5 Bonnet(1/2" — 1") Brass A i
Bonnet(1 1/4"—2") Bronze i
6 Stem&Seat Assembly Brass s
i
7 Disc Buna N
8 Body Bronze A
Size I/2" 3/4„ �7, 1 1/419 1 IV2" 211
A 1.03 1.22 1.47 1.75 2.00 2.34
B 2.03 2.38 2.75 3.00 3.72 3.72
C(closed) 3.13 3.25 4.38 4.50 5.25 5.63
Ship Wt. (lbs.) 0.69 0.94 1.76 2.50 3.26 5.32
Qty.Unit Pack 12 6 6 4 2 2
Qty.Per Case 72 60 36 24 1 12 12
SHURJOINT® _ PROTECTION "
mw.shugoint.00m
Approvals Products for Fire Protection Piping Systems
COUPLINGS AND FITTINGS
Listing Pipe Rated Working Pressure Pipe Notes(See Coupling and
Shudoint Wall El PSI Pub.
Product❑Model Approval Size Range Fitting Notes on page No.
Agency Inches Standard Light 13-14)
IPS Carbon Steel Grooved Couplings
#7705 Flexible Coupling 1"-8" 300 300
UL 8".(770513) 450 450 1,2-1,14,15
10"-12" 175 175
C-01
300 300
.m
FM 8"(7705H) 450 450 2-2,18,19
10"-12" 250 250
#7707 Flexible Coupling 3/4"-1 1/4"' 500 500
2"-8" 500 450
UL 1,3-1,14,17
10"-16" 300 -
18"-24" 250 -
C-02
11/2"-10" 500 500
FM 12" 300 300 3-2,18,19
14"-22" 175 175
24" 250 250
#7771 Rigid Coupling 2"-8" 300 300
10"-12" 175 175UL 1,5-1,
14"-20" --- 300
22"-24" — 250
,. 11/2" 500 500 C-05
2"-8" 300 500
FM 10" 200 200 5-2,
12" 300 300
14"-24" 175 175
#Z07 Angle Pad Coupling 1 1/4"4" 500 500
UL 5"-8" 400 400 1,8-1
10" 350 350
it i 12" - -
C-06
1 IW4 4" 500 500
FM 5"-8" 400 400 8 2,
10" 350 350
12" 350 350
#K9 Lightweight Rigid
Coupling UL 1-1/4"-8" 300 300 1,4-1,
8"(K-9H) 350 300
` G-01
FM 1-1/4"-8" 300 300 4-2,
8"(K-91) 300 300
1/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED . Las Vegas,Nevada USA• www.shudoint.com
SHUR IOINT 3PRODUCTS
vwnv.shugoinLcom
#C-7T Outlet Couplings
UL 1-1/2"x 1/2"- 300 300 1
6"x 1-1/2"
0
r, s C-10
FM 1-l/2"x 1/2"- 300 300 -
6"x 1-1/2"
#C-7G Outlet Couplings
UL 2"x 1" 300 300 1,
6"x 2"
C-10
FM 2"x 1" 300 300 -
6"x2"
#723 Saddle Let
UL 1 1/4"x 1/2"- 300 300 1,12-1,
3"x 1"
F 03
J' FM 1 1/4"x 1/2"-
F
3"x 1" 300 300 12-2
IPS Carbon Steel.Grooved Fittings
#901 Short Radius 90"Elbow
TJL 2"-8" 300 300 1,
G-02
FM 2"-8" 300 300
#903 Short Radius Tee
UL 2"-8" 300 300 1,
G-02
FM 2"-8" 300 300 —
#7110 90°Elbow
LJL 1"—18" 300 300 1
20"—24" 250 250
1"—8" 500 500 E-02
10"—12" 300 300
FM 175
14"-18",24" 175
20" 250 250
3/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED • Las Vegas,Nevada USA• www.shudoirit.com
SHURJOINT® FIRE PROTECTION PRODUCTS
www.shudoinl.com
#711145?Elbow
UL 1-1/4"-18" 300 300 1'
20",24" 250 250
E-02
1-1/4."-8" 500 500
10"-12: 306 300
FM 14"-1811,2411 175 175
20" 250 .250
#7110DR Drain Elbow
UL 2"-6" 300 300 1,
G-05
FM 2"-6" 300 300
#7110LR 1.5D Elbows
UL 2"—8" 300 300 1
E-04
FM 2"—8" 300 300 -
#7112 22-1/2'Elbow
UL 1-1/4" 500 500 1
1-1/2"-8" 300 300
E-04
FM 2"-8" 300 300
#7113 11-1/4°Elbow
UL 2"—8" 300 300 1
E-02
FM 2"—8" 300 300
#7120 Tee
UL 1-1/4"—18" 300 300 1
20"—24" 250 250
E-05
1-1/4"—8" 500 500
FM 10"—14" 300 300
16" 175 175
#7121 Reducing Tee
UL 2"x 1-1/2"—12"x 300 300 1
10"
E-06
FM 2"x 1-1/2"— 300 300 —
6"x 4"
4/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED • Las Vegas,Nevada USA• www.shudoint.com
MISHURJOINTO FIRE PROTECTION PRODUCTS
wmwshurjoinl.00m
#7151 Eccentric Reducers
UL 2 1/2"x 2"- 300 300 1,
8"x6"
E-07
FM 2 1/2"x 2"- 300 300
#7160 End Cap
UL 1-1/4"-8" 300 300 1,
E-08
FM 1-1/4"-12" 300 300 -
#7160H End Cap
UL 10"-18" 300 300 1
20"—24" 250 250
E-08
FM 10"-12" 300 30040 —
14"—24" 175 175
#7160T Transition Fittings
2"x1"_
UL 6" 2"
300 300 1,
Z x
G-08
FM 2"x 1" 300 300 —
6"x 2"
#7170 Flange Adapter
UL 21/2"-6" 175 175 1
y �
D-04
IFM 21/2"-6" 175 175 —
N
#7180 Universal Flange
Adapters
UL 2"-8" 300 300 --
D-08
FM 2"-8" 175 175 21
#55 Nipple Adapters
UL 1 1/2"-2" 300 300 1
G-07
FM 1 1/2"-2" 300 300 —
6/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products . 1 800 746-GROOVED • Las Vegas,Nevada USA. www.shudoi6t.com
SHURJOINT® PRODUCTS
wvnv.shugoint.com
#899 End All Fitting
UL 1 1/4"x 1/2"— 300 300 1,
2-1/2"x 1"
G-06
FM 1 1/4"x 1/2"= 300 300
IPS Carbon Steel Outlet Fittings
#71 Female Threaded Outlet Outlet x Header
Fitting yz'x 1"-8",
111x 1,/"_8"
1'/'x 2"—8"
UL 1'/i'x 2"-$" 300 300 1,
2"x2"-8"
2'/i'x2'YV--8"
2'%(76.1)"x2'/"--81-
3"x 3"-8" H-01
4"x 4"-•8"
'W',3K,1"x 1"-8"
1%",1'%x 2"-8"
FM 2"x 2'/2"-8" 300 300 —
2'/z"0"-8
3"x 4"-8"
4"x 5"-8'
#72C Cut Grooved Outlet
2"x 2"-8°
Fittings
2-1/2"x2-1/2"-8"
UL 3"x 3"-8" 300 300 1,
4"x4"-8"
6"x6"x8"
8"x 8"x 10"
H-02
2-1/2"x3"-•8
3"x 4"-8"
FM 4"x 5"-8" 300 300 —
6 x 8'
8"x 10"
#72R Roll Grooved Outlet 1-1/4"x 1-1/2"-8"
Fittings 1-1/2"x 1-1/2"-8"
UL 2 x 2'•—8"
300 300 1,
2-1/2"x2-1/2"-8
3"x 3"-8"
4"x 4"-8"
H-03
1-1/4"x 1-1/2"-8"
1-1/2"x 2"-8"
FM 2"x 2-1/2"-8" 300 300
2-1/2"x3"-8
3"x 4"-8"
4"x 5"-8"
7/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products 9 1 800 746-GROOVED • Las Vegas,Nevada USA a www.shudoint.com
SHUPWINT® FIRE PROTECTION PRODUCTS
www.shudoint.com
#74 Universal Threaded 1/2"x 1"-8"
Outlet Fitting 3/4"x 1"-8"
UL 1"x 1-1/4"�1-1/2" 300 300 1,
11,x 2"—2-1/2"
illx 3—8"
H704
1/2"x 1'!--8"
3/4"x 1".-8"
FM V x 1-1/4"-1-1/2". 300 300. —
1"x 2"—2-1/2"
1"x 3"—8"
Ductile Iron Fittings
#811 90"Elbow
UL 1/2"-2-I/2" 300 300 1
I-01
FM 1/2"-2-1/2" 300 300 _
#812 Reducing 90'Elbow
3/4"-x 1/2"—
UL 2-1/2"x 2" 300 300 1
I-01
3/4"x 1/2"—
FM 2-1/2"x 2" 300 300 -
#813 45'Elbow -
UL 1/2"—2-1/2" 300 300 1
I-01
FM 1/2"-2-1/2" 300 300
#814 Straight Tee
UL 1/2"—2-1/2" 360 300 1
I-01
i
FM 1/2"-2-1/2" 300 300
#815 Reducing Tee
UL 3/4"—2-1/2" 300 300 1
I-01
3/4"x3/4"xl/2"
FM — 300 300
2-1/2"x2"x3/4"
8/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shugoint Piping Peoducts . 1 800 746-GROOVED • Las Vegas,Nevada USA a www.shudoint.com
SHURJOINT® PRODUCTS
www.shuddint.com
#816 Reducing Coupling
3/4"xl/2"—
UL 300 300 1
2-1/2"x 2"
I-01
FM 3/4"x 1/2"— 300 300 -
22"x 1-1/2"
#817 Cross
UL 1"-2'.' 300 300 I
I-01
1/2"-2"
FM 1-1/4"xl"-2"xl" 300 300 —
#818 Straight Coupling
UL 1/2"—2-1/2" 300 300 1
I-01
FM 1/2"-2-1/2" 300 300 -
#819 Plug
UL 1/2"—2" 300 300 1
I-01
FM 1/2"—2" 300 300 -
#820 Caps
UL 1/2"—2-1/2" 300 300 1,
I-01
FM 1/2"-2-1/2" 300 300
#825 Extension Pieces
1/2"x 1-1/2"—
UL 3/4"x 2" 300 300 1,
I-01 FM 300 300
3/4"x 2"L -
{
9/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED • Las Vegas,Nevada USA• www.shudoint.com
R-T SHURJOINT® PRODUCTS
vmw.shudoint.com
Couplings and Fittings Notes
1. MEA Approved#322-06-E.
2. 2-1)UL Listed at 300 psi on the following sizes&pipe.
1-1/4"--4"on XL,XL-II pipe,Dyna-Flow,Super-Flo pipe manufactured by Allied Tube&Conduit Corp,1-1/4"--6"on BS1387(M),British
Standard Medium Steel pipe,
1-1/2"-3"on Eddy Flow pipe.,1-1/4"-2"on Eddylite pipe manufactured by Bull Moose Tube Co,
1-1/4"-2"on Fire-Line Threadable pipe manufactured by Western International Forest Products Inc.
UL Listed at 175 psi on the following sizes&pipes.
1-1/2"-3"on Eddy Flow Pipe manufactured by Bull Moose Tube Co,
1-1/4"-4"on Fire-Line Flow pipe manufactured by Western International Forest Products Inc.,
1-1/4"-2"&3"on SPS pipe manufactured by Yieh Phui Enterprise Co.,Ltd.
1-1/4"-3"on Sch.5 pipe,10"on Sch.10(0.188 in)pipe,12"on Sch.30(0.330 in)pipe.
2-2)FM approved at 300 psi on the following sizes&pipes.
1-1/4"-6"on BS 1387M or heavier grade pipe.
1"--4"on Dyna-Flow,Super-Flow(Allied)pipe
1"-2"&3"on Super 40,Super-XL(Allied)pipe.
1"-3"on XL-II(Allied)pipe
1"-2"on BLT,Dyna Thread(American Tube),Fire-Thread,Eddylite(Bull Moose),TT,(Central),LS pipe,
1-1/2"--4"on Eddy Flow(Bull Moose Tube)pipe
1-1/4"&1-1/2"on Fire-Flow pipe
FM approved at 175 psi on the following sizes&pipes. '
1"-2"on WST(Weatland),Ultra Eddy(Bull Moose)pipe.
3. 3-1)UL Listed on the following sizes&pipe.
At 500 psi in 2-1/2",5"-6"on BS 1387(M),British Standard Medium Steel pipe pipe,
At 450 psi in 1-1/2"&4"on Dyna-Flow pipe manufactured by Allied Tube&Conduit Corp,
At 300 psi in size 10"&12"on sch.10(0.188 in)pipe,14"&16"on Sch.30(0.375 in)pipe,
At 250 psi in 18"-24"on Sch.20(0.375 in)pipe.
3-2)FM approved on the following sizes&pipe.
At 500 psi in 2-1/2",5"-6"on BS 1387 medium or heavy grade pipe
4. 4-1)UL Listed at 300 psi on the following sizes&pipe.
1-1/4"-8",3.00D,6.50D on BS1387(M),British Standard Medium Steel pipe pipe,
1-1/4"&2"on Eddylite pipe manufactured by Bull Moose Tube Co,
1-1/4"-2"on Fine-Line Threadable pipe manufactured by Western International Forest Products Inc.,
2"on Eddythread 40 pipe manufactured by Bull Moose Tube Co.
UL Listed at 175 psi on the following sizes&pipes.
2"-3"on XL-11,XL pipe manufactured by Allied Tube&Conduit Corp,
2"-4"on Dyna-Flow,Super-Flo pipe manufactured by Allied Tbbe&Conduit Corp,
1-1/4"-4"on FLF pipe manufactured by Western International Forest Products Inc.,
1-1/4",2"-3"on SPS pipe manufactured by Yieh Phui Enterprise Co.,Ltd.,
1-1/4",2"-3"on Sch.5 pipe.
4-2)FM approved at 300 psi on the following sizes&pipes.
2-1/2",5"-6"on BS1387(M)medium or heavy grade pipe,
1-1/4",1-1/2"&4"on Fire-Flow(Allied)pipe,
1-1/2"&2"on Fire-Thread pipe,
1"-3"on Super40,Super-XL pipe,
1"-2"on TL(Central)&LS pipe.
FM approved at 175 psi on the following sizes&pipes.
1-1/4"-3"on XL-11(Allied) pipe,
1-1/4"-2",3"-4"on BS1387 pipe,
1-1/4"-4"on Eddy-Flow,Super-Flo pipe,
1-1/4"-2"on BLT,Eddylite,WST(Wheatland),Gal-5(IDOD Systems)pipe,
1"-2"on Ultra Eddy(Bull Moose)pipe,
1-1/2"-4"on Eddy-Flow pipe.
5. 5-1)UL Listed at 300 psi on the following sizes&pipes.
2"-6"on BS1387(K,British Standard Medium Steel pipe pipe,
14"&16"on Sch.30 pipe,
18"&20"on Sch.20 pipe.
UL Listed at250 psi in size 22"&24"on Sch.20 pipe.
5-2)FM approved at 175 psi in size 22"&24"on Sch.20 pipe.
6. 6-1)UL Listed at 300 psi on the following sizes&pipe.
1-1/4"-6"on BS1387 pipe,1-1/4"-3"on Super 40,Super-XL pipe,1-1/4"-4"on Dyna-Flow,Super-Flo pipe,1-1/4"-1-1/2"on
Fire-Line Flow pipe,1-1/4"-2"on Fire-Thread pipe&Eddlylite pipe.
UL Listed at 175 psi in size 1-1/4'1 2"on Sch.5 pipe.
6-2)FM approved at 300 psi on the following sizes&pipes.
1-1/4"--6"on BS1387 pipe,
1-1/4"-3"on Super 40,Super-XL(Allied)pipe,
1"-4"on Dyna-Flow,Super-Flo(Allied)pipe,
1"-2"on Ultra Eddy(Bull Moose)pipe,
13/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED • Las Vegas,Nevada USA• www.shudoint.com
SHURJOINT® F IRE PROTECTION
m-m.shudoint.com
1-1/2"-2"on Fire-Thread pipe,
1-1/4"-2"on Eddylite(Bull Moose),WST(Wheatland)pipe.
7. 7-1)UL Listed at 350 psi on the following sizes&pipe.
1-1/4"-4"on BS 1387(M)British Standard Medium Steel pipe pipe
2"-4"on Dyna-Flow,Super-Flo pipe manufactured by Allied Tube&Conduit Corp,
UL Listed at 300 psi on the following sizes&pipe.
1-1/4"-2"on XL,BLT,WLT pipemanufactured by Allied Tube&Conduit Corp,
1-1/4"-2"on WLS manufactured by Wheatland Tube Co
1-1/4"-2"on Eddylite pipe manufactured by Bull Moose Tube Co.
1-1/4"-2"on Fire-Line Threadable pipe manufactured by Western International Forest Products Inc.1-1/4"-1-1/2"on Dyna-Flow,
Super-Flo pipe manufactured by Allied Tube&Conduit Corp,
1-14'-4"on Mega-Flow pipe manufactured by Wheatland Tube Co.
1-1/4"on Eddy Flow pipe manufactured by Bull Mosose Tube Co.
3"&4"on EZ-Flow pipe manufactured by Northwest Pipe Co.,
1-114"&2"on MT pipe manufactured by Wheatland Tube Co.
UL Listed at 175 psi on the following sizes&pipes.
1-1/2"-3"on Eddy Flow pipe manufactured by Bull Mosose Tube Co.,
1-1/4"-2"on Sch.5 pipe,
6"on EZ-Flow pipe manufactured by Northwest Pipe Co.,.
7-2)FM approved at 350 psi in size 1-1/4"on XL pipe.
FM.approved at 300 psi on the following sizes&pipes.
2"--4"on Dyna-Flow,Super-Flo pipe,
1-1/4"-4"on Mega-Flow pipe.
FM approved at 175 psi on the following sizes&pipes.
2"--4"on Dyna-Flow,Super-Flo pipe,
1-1/4"-4"on Mega-Flow pipe.
1-1/2"-3"on Eddy Flow,Fire-Thread pipe.
8. 8-1)UL listed at 300 psi on the following sizes&,pipe.
1-1/4"-4"on Dyna-Flow manufactured by Allied Tube&Conduit Corp.,and EF pipe manufactured by Bull Moose Tube Co.,and
Mega-Flow pipe manufactured by Wheatland Tube Co.
3"-4"on EZ-Flow pipe manufactured by Northwest Pipe co
1-IA"-2"on Eddylite pipe manufactured by Bull Moose Tube Co.,and MLT,WLS pipe manufactured by Wheatland Tube Co.
UL Listed at 175 psi on the following sizes&pipe.
1-1/4"--4"on Eddy Flow pipe manufactured by Bull Moose Tube Co.
1-1/4"-2"on Sch.5 pipe,
6"on EZ-Flow pipe manufactured by Northwest Pipe Co.
8-2)FM approved at 350 psi in size 1-1/4"-2"on XL pipe.
FM approved at 300 psi in size 1-1/4"-4"on Mega-Flow pipe.
FM approved at 175 psi in size 1-1/211-3"on Fire-Thread,Eddy Flow pipe.
9. 9-1)UL listed at 175 psi on the following pipe.
3"OD,4"-5"on BS1387(Ivi)British Standard Medium Steel pipe pipe,
12"on Sch.30(0.330 in)pipe..
10"on Sch.10(0.188 in)pipe.
9-2) FM approved at 175 psi on the following pipe.
2-1/2,4 in.British Standard BS 1387 medium or heavy pipe.
2"-12",14",16"24"Min schedule cut groove pipe to be joined:8 in.or smaller Schedule 40.
2"-12",14",16"24"Min schedule rolled groove pipe to be joined:8 in.or smaller Schedule 10.
10. 10-1)UL listed at 300 psi in size 311x2"-2-1/2",4"x2-1/2"-3",6"x4"on BS1387 and
10-2)FM approved at 300 psi on BS1387(M)or heavy grade pipe.
11. UL listed at 175 psi in size 1-1/4"-2"on BS1387 pipe.
12. 12-1)UL listed at 300 psi in size 1-1/4"-2-1/2"on XL,Super-Flo pipe,175 psi in size 1-1/4"-2-1/2"on Dyna-Flow,XL-II,BS1387 pipe.
12-2)FM approved at 300 pit in size 1-1/4"-2-1/2"on Dyna-Flow,XL,Super-Flo(Allied)pipe,1-1/4"-2"on BLT(Allied)pipe,TL
(Central),Eddylite(Bull Moose),WLS,LS (Wheatland)pipe.
13. 13-1)UL listed at 300 psi in size 2"x 2%"-8"x 4"on BS1387 pipe
13-2)UL listed at 300 psi in size 3"x 11/2'-S"x 4"on BS1387 pipe
14.Light wall pipe shall be of the minimum wall thickness 0.188 in.Sch.10.
15.Rolled and Cut grooved basked on Sch.30(0.330")pipe.
16.Rolled and Cut grooved based on Sch.20(0.375 wall thickness pipe)
17.Rolled and Cut grooved based on Sch.30(0.375 wall thickness pipe)
18.Minimum schedule cut groove pipe to be joined:6"in or smaller-Sch.40;8"in or larger-Sch.30
19.Minimum schedule roll grooved pipe to be joined:6"or smaller-Sch.10,8 and 10"-0.188 in wall;12"-0.250 in wall.
20.UL listed at 300 psi in size 76.1mm,139.7mm,165.Imm on Sch.10S,40S pipe.
21.a)Provides a rigid transition between flanged components and a grooved system.
b)Min schedule cut groove pipe to be joined:8 inches or smaller-Sch.40
c)Min schedule rolled groove pipe to be joined:8 inches or smaller-Sch.10.
14/14
SHURJOINT®IS AN ISO 9001 CERTIFIED COMPANY
Shudoint Piping Products • 1 800 746-GROOVED 9 Las Vegas,Nevada USA• www.shudoint.com
ADJUSTAB E SWIVEL RIB G HANG '+R�
FUNCTION: Designed for the suspension of non-insulated stationary pipe lines.The +
knurled insert nut that allows a verticaladjustment after installation,is Fig* 141 141E
topped to NFPA reduced rod size standards. Fig.141F has a layer of felt NFPA SWIVE�I.
which separates the pipe from the hanger to reduce vibration and sound.
APPROVALS: Underwriters'Laboratories listed and Factory Mutual approved Fig.141 �. RING HANGE�IZ
3/"to 8"sizes only.Complies with Federal Specification A-A-1192A(Type
10),Manufacturers'Standardization Society SP-69(Type 10)and NFPA Fig. 141 PRE-GALVANIZED
standards for reduced rod sizes.
Fig. 141F PRE-GALVANIZED
ORDERING: Specify pipe size and figure number. WITH FELT LINING
Rod
Pipe Sze. Ad].: . :. Max.Rec.Wt.Each `_ �A
Size A B C- D E. Load/lbs. (in lbs j:
1/2 % 17/8 17/16 23/4 31/16 300 .10 = t
3A % 111/1s 11/e 21/2 3'/16 300 .10 - I
1 % 1 1% 1 21/2 33/1s 300 1 .10 C
11/4 3/1 175/16 11/16 213/16 39/16 300 .11
11/2 % 21/8 11/16 31/8 37/e 300 .11
2 % 27/16 11/8 35/16 4% 300 .14 1� D
21/2 3/e 23/4 11/4 311/16 5 525 .19
3 3/8 27/e 11/8 33/4 5!'/is 525 .23
31/2 3/e 3% 13/8 45/16 65/16 525 .25
4 3/8 37/e 11/2 41/2 7 650 .30
5 1/2 4% 1% 5% 8% 1000 .50
6 1/2 55/e 21/4 61/2 973/16 1000 .58
8 112 613/16 27/16 715/16 121/4 1000 .90 O
UL
Note: If ordering Fig.141F felt lined hangers for pipe sizes of 3'/2"or under,order the next
largest size to allow for the thickness of the felt lining. MATERIAL: Low carbon steel
FUNCTION: Designed for the suspension of non-insulated stationary pipe lines.The Fig. 151 151E
knurled insert nut,allows for vertical adjustment after installation.
Fig.151F has a layer of felt which separates the pipe from the hanger to SWIVE+I,
reduce vibration and sound.
APPROVALS: Underwriters'Laboratories listed and Factory Mutual approved Fig.151 IZIING HANGEIR
21/2"to 8"sizes only.Complies with Federal SpecificationA-A-1192A
(Type 10),and Manufacturers'Standardization Society SP-69(Type 10). Fig. 151 PRE-GALVANIZED
ORDERING: Specify pipe size and figure number. Fig. 151F PRE-GALVANIZED
WITH FELT LINING
Pipe Rod Max.Rec.Wt. Each
Size. .. Adj:. . : . . A,
Size A B C D E Load/Ibs. (in Ibs.)
21/2 1/2 23/4 11/4 311/16 51/B 600 .33 y} _
3 1/2 31/e 11/8 4 57/8 600 .35 s�
31/2 1/2 3% 11/2 45/16 65/g 1 600 .37
4 5/6 37/s 11/4 415/1s 71/e 1000 .48 GC B
5 % 43/e 1% 55/e 81/2 1000 .57
6 3/4 55/16 1 2 611/16 101/e 1250 1.06
D -
8 3/4 615/16 1 2% 85/16 127/s 1250 1.32 E
Note: If ordering Fig.151F elt lined hangers or pipe sizes of 3'lz"�or under,order the next �s =
argest size to allow for the thickness of the felt lining.
f
MATERTAL.: T.ow carbon steel
PHD Manufacturing, Inc. •44018 Columbiana-Waterford Road • Columbiana, OH 44408
Toll Free(800)321-2736•Phone:(330)482-9256•Fax:(330)482-2763•www.phd-mfg.com
x _
data she
ARGCO GUARANTEED
THREADED ROD FASTENERS FOR STEEL
BOTTOM MOUNT FOR STEEL
-One piece Self drilling and tapping in steel up to 3/16"thick
CROSS REFERENCE
EMBEDMENT MAX. ELCO ITW SAMMY
ITEM# ROD SIZE SHANK DIA. SHANK LENGTH DEPTH PIPE SIZE ITEM# HANGERMATE° SUPERSCREW
25.30-302A 3/8'A6 .1/4" 1-1/2" 171/2" 4" 25-30-302A EZG-470 I DST-15
25-30-303A 3/8"-16 1/4" 2" 2" 4" 25-30-302A EZG-490 DST-20
25-30.302A
BOTTOM MOUNT WITH RETAINER NUT
-One piece self drilling and tapping in steel up to 3/16"thick
-Retainer nut included EMBEDMENT
\,
APPROVALS
ITEM# ROD SIZE SHANK DIA. SHANK LENGTH DEPTH LOAD CAPACITY
25-30-310A 3/8"-16 1/4" 1'° 1° 1,500 �L
25-30-310V 3/8"-16 1X, 1" 1" 1,500 �L
25-30-310A 25-30-311A 3/8"-12-24 5/16" 1-1/2" 1-1/2" 1,500 UL PM
25-30-311V 3/8"-12-24 5/16" 1-1/2" 1-1/2" 1,500 UL FM
CROSS REFERENCE
SCREW SHANK POINT MAX. MINIMUM
ITEM# &LENGTH STYLE PIPE SIZE STEEL THICKNESS UL TEST LOAD ELCO ITW SAMMY
ITEM# HANGERMATE° SUPERSCREW
25-30-310A 1/4"x 1" #3 4" .060"(1.5 MM) 1500 LBS. 25-30-310A EZG-471 DSTR-1
25-30-310V 1/4"x 1" #3 4" .060"(1.5 MM) 1500 LBS.
25-30.311A 12/24"x 1-1/2" #5 4" .060"(1.5 MM) 1500 LBS. 25-30-311A EZG-491
25-30-311V MM'x 1-1/2" #5 4" .060"(1.5 MM) 1500 LBS.
Recommended to be installed with
Universal Steel&Wood Nut Driver(25-30-324V)
SYSTEM
SENSOR'
WFD Series
Waterflow Detector
System Sensor' WFD series is compatible
with schedule 10 through 40 steel pipe,sizes
2-through 8,and can be mounted in a vertical
or horizontal position.
Features Robust Construction.The WFD series consists of a rugged,
NEMA 4 rated enclosure.Designed for both indoor and outdoor
•Two-inch conduit openings in new WFD30-2 models use,the WFD series operates across a wide temperature range,from
•UL listed models are NEMA 4 rated 32°F to 1207.
-Sealed retard mechanism immune to dust and other contaminants Reliable Performance.UL listed models are equipped with
•Usual switch activation tamper resistant cover screws to prevent unauthorized entry.Inside,
two sets of SPDT(Form Q synchronized switches are enclosed in a
•Field replaceable retard mechanism and SPDT switches durable terminal block to assure reliable performance.
•Rugged,dual SPDT switches enclosed in a durable terminal block
False Alarm Immunity.The WFD series incorporates a mechanical
•Accommodates up to 12 AWG wire retard feature,which minimizes the risk of false alarm due to
•Designed for both indoor/outdoor use pressure surges or air trapped in the sprinkler system.In addition,
the mechanical retard's unique sealed design is immune to dust and
•100 percent synchronization activates both alarm panel and other contaminants.
local bell
•Tamper resistant cover screws Simplified Operation.The WFD series is designed to simplify
installation.Two conduit openings permit easy attachment to the
local alarm system.The retard mechanism and dual SPDT switches
are field-replaceable.
Agency Listings .
MEA <LISTED O approved ,�FM>
5739 CS169 7770-1209.140 167-93-E 1W9A2AH
Waterflow Detector Specifications
Engineering Specifications
Vane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein.Detectors shall mount on any
clear pipe span of the appropriate nominal size,either a vertical upflow or horizontal run,at least 6"from any fittings which may change water direction,
flow rate,or pipe diameter or no closer than 24"from a valve or drain.Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a
static pressure rating of 450 psi*for 2"—8"pipes.The detector shall respond to waterflow in the specified direction after a preset time delay which is field
adjustable.The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation.The actuation mechanism shall include
a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism.Outputs shall consist of dual
SPDT switches(Form C contacts).Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors.
A grounding provision is provided.Unless noted,enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc.All detectors shall be listed by
Underwriters Laboratories Inc.for indoor or outdoor use.
Standard Specifications
Static Pressure Rating 450 PSI* Operating Temperature Range 32eF to 120eF(O°C to 49eC)
Maximum Surge 18 Feet Per Second(FPS) Enclosure Rating* NEMA 4—suitable for indoor/outdoor use
Triggering Threshold 4-10 GPM Cover Tamper Switch Standard with ULC models,optional for UL
Bandwidth(Flow Rate) models,part no.546-7000
Conduit Entrances Two openings for 112"conduit. Service Use Automatic Sprinkler:NFPA-13
One open,one knock-out type One orTwo Family Dwelling:NFPA 13D
Residential Occupancies up to 4 Stories:NFPA 13R
National Fire Alarm Code:NFPA-72
Contact Ratings Two sets of SPDT(Form C) U.S.Patent Numbers 3,945,259
10.0 A,Yz HP @ 125/250 VAC 4,782,333
2.5 A @ 6/12/24 VDC 5,213,205
Compatible Pipe Steel water pipe,schedule 10 through 40 Warranty 3 Years
WFDE Field Wiring Diagram Delay Adjustment Dial Overall Dimensions,Installed
0
Delay o"o6u°aV1w sE°jb ��•
-� == Lv1nn1on ai°eG9"10LIp1$ co —as aqusimein °
wu msewnen°aro a O dial 0
MIMed,I.o.,Mren erh taY150 VAG IBANPS
60�9 Duel �pemil 2x VOC 25ANP5 y
epperatpre ra to wniCnoO
VIFau g'e 0etedor.— o
9LI W0
WFD 6.66' WFDO0 6
.9
52 =60 ad-
'
WD u eon run W035v e•5 T VlF00 10e'
OS
ofMMIN—i
—*----
Plpe mddle
Typleei FACP eortecrlon NOTE:Retard fine may exceed 90 as ..
Adjust and y ty Thal I—tloes not exceed 90 seconds
W�T��
ee=lorvupp n
olmnneevm DONOTalbwpeymtlxV WtxuWp.eDONOTIwpwiresueoH
Ordering Information
UL Model ULC Model Pipe Size Hole Size Shipping Weight
WFD20 WFD20A 2" 1Y4' 4.2lbs.
WFD25 WFD25A 21h" 11/4" 4.3lbs.
WFD30-2 WFD30-2A 3" 2" 4.5lbs.
WFD35 WFD35A 3%z" 1 A" 4.7 lbs.
WFD40 WFD40A 4" 2" 5.2lbs.
WFD50 WFD50A 5" 2" 6.3lbs.
WFD60* WFD60A 6" 2" 6.8lbs.
WFD80* WFD80A 8" 2" 7.51bs.
Accessories
A3008-00 Retard mechanism
A77-01-02 Terminal block
546-7000 Tamper proof switch kit
WFDW Tamper proof wrench for cover
WFDN4 Gasket kit
*Maximum pressure rating 400 psi as approved by Factory Mutual.
®20075ystem Sensor
"STEM
3825 Ohio Avenue•St.Charles,IL 60174 Roduaspecifioeonssuhjectrodtangewrthoutnotice.Nsrtsystemsensoxomfor
SENSOR, Phone:800-SENSOR2•Fax:630-377-6495 m entproduainfomwtion,indudingthelatest ionofthlsdaiashe
A05-M8D011.3/07•A1676
ZEPHYRHILLS FIRE'.DEPARTMENT,
38410 6th Ave Zephy'hills,A 33542 .
FIRE SERVICE•USER'F.EES increase 1/112018 .
Occupancy No::,
Plan No.: Contractor:
Business Name: Billing,Address:
Business Address: .
Business Phone,No:: Billing Phone No.:,
Business'Fax No.:: . :' . Billing Fax No.:
Contact: . . Contact:.
PLAN REVIEW.FEES INSPECTION FEES PERMIT FEE
Annual-
. . . . . . . .Education;healthcare;De. .
tention&Correctional- Public
Assembly,Business, -schools; '
c. Storage,Mercantile and Churches
H--Site-Plan N/C Industrial. no charge, Sprinkler $50
Multi-Family/Commercial .03:sf up to 800 sq ft $ 24.00 $50
(Minimum Charge$24.06. 801 -.1,500.sq ft $ 34.52 Fire Pump $50
❑:Plan Revisions DBL. 1,501'-2,500 sq ft $ 60.02 Hoods $50
2,501-3,500 sq ft $ . .90.02 . . Fire Alarm. $50
,SPRI 1F.M§ .: 3,501=5,000 sq ft $. 127.52. LP Gas $50 -
0=25 Heads 0_ ' 5,50177,500 sq.ft $ . 187.52 . Natural Gas $50. .
eads .100 7,501-10,000 sq ft. $. .262.52 Fuel Tanks= per.tank $50-.
STANDPIPE'SYSTEM. 101001-15,000 sq ft $. 375.02, Sparklers $100
Per Riser $50 15;001-20,000.sq ft $: :525:02 '; . . Fire;Works $500,
FIRE PUMP 20,00.1-30,000 sq ft $ ' 750.02 Camp Fire(recreation' $25
❑:Per Pump $100 30,001-40,000 sq:ft $.1,050:02', Controlled Bum(15da;.$100
-77
FIRE ALARM"SYSTEM... : 40.,001-60,000 sq ft. $,1,500;02 Hood/Duct $50
0-25°Devices $50 60,001-80,000 sq ft- $ 2,100.02' Place of Assembly-, $50 Annual: '
80,00.1-($2,100.02)per
26 plus Devices $100 ea add 1,000sq ft : . $ 0.06 Fire Protection $25.
SUPPRESSION SYSTEMS: (Business closed until Flammable Application $50 Annual
-Wet. $50' violations-corrected). Waste.Tire Storage' $50 Annual.
Dry. $50- . SPRINKLER:SYSTEMS". Generator'<KW: $100.
CO2. . $50 "Hydro Undergrounds $45 Generator>30 KW $100
Other $50 taticles persystem Bio Hazard Waste $100 Annual
KITCHEN EXHAUST. . cceptance Test per system Fumigation Tenting. $50
Hood/Ducts $50: Hy ran ow. $75 orch.PoUApplied $50
❑ . :
OTHER Haz.Materials. $50. Annual . . .
LP Installation per tank $50 . 'FIRE ALARM SYSTEM
Fuel Tank Installation . $50 System.Acceptance $50
(Per Tank). $50'�:Recall Acceptance $50
ElNatural Gas Installation: : :$50. . : ' OTHER
S Ste Fire WaIUSmoke Wall $15 per wall
P Gas $25 Per tank
Natural Gas $25 Per system
Tent 10'x10'or greater $15. per tent . .
Fire.Pump :$45.
Fire Suppression ' $30.
System "Acceptance
Exhaust Hood/Duct $30.: .
Re-inspection DBL .
(other than.annual)
Inspection scheduled DBL. .
and cancelled less than
24 hours . ..
Construction Insp. NIC
Emergency Vehicle Acce $50
PLANS TOTAL . INSPECTION TOTAL PERMIT TOTAL
GRAND TOTAL'
Comments: . .
Date: Inspector:
see back
mn
-FALSE.ALARM FEE. .
1'st Alarm N/C
2nd-Alarm N/C. . .
:3rd Alarm N/C
4th'Alarm $100
5th Alarm . . $150 . .
6th Alarm .$200
NON COMPLIANCE' $150
Cont.Annual Inspection Fees
3-11-Units price per unit $ ; .5.36-
12-25 Units price.per unit $ - 4.82
26-50 Units price par unit $ 4.29.
51A00 Units price,per unit. $.: :3.75
100.ormore Units price per unit. $ 2:68
Fire Safety rerinspection types -
First Re-inspectioi . ' N/C
Second re-inspect. : : ' $75-
Third re-irispectior..$ 125.00
Inspection scheduled,but cancelled 24 hrs $ 50.00
TOTAL
0
nii,:.