•' FIRE STANDPIPES PERMIT
PERMIT INFORMATION LOCATION INFORMATION
Permit Number: 21533 Address: 4920 AIRPORT RD
Permit Type: FIRE SUPPRESSION SYSTEM ZEPHYRHILLS, FL.
Class of Work: FIRE-SUPPRESION SYS Township: Range: Book:
Proposed Use: NOT APPLICABLE Lot(s): Block: Section:
Square Feet: Subdivision: CITY OF ZEPHYRHILLS
Est.Value: Parcel Number: 13-26-21-0010-00000-0010
Improv. Cost: 2,450.00 OWNER INFORMATION
Date Issued: 8/01/2019 Name: BLACKLIDGE, LISA& BAILEY, PATRI
Total Fees: 130.00 Address: 123 CHRISTY LN
Amount Paid: 130.00 KOKOMO, IN 46901-3840
Date Paid: 8/01/2019 Phone:
Work Desc: INSTALLATION FIRE SUPPRESSION FOR PAINT BOOTH
CONTRACTORS APPLICATION FEES
FIRE FIGHTER, INC. FIRE PLAN REVIEW FEES 50.00 FIRE INSPECTION FEE 30.00
FIRE SUPPRESSION SYS ACCEPT 50.00
V
FINAL Ins ections Required
Chapter 633, Florida Statutes,authorizes the City to charge and collect user fees to pay for the costs of fire
prevention and protection related activities such as inspections, plan review,administrative fees,and other
costs related to the aforementioned.
Complete Plans, Specifications and Fee Must Accompany Application. Commencement of work without written approval of
the Fire Department's Fire Marshal or required permits or opening up for commercial activity without an approved final
inspection shall be charged double permit fee per day of operation or a minimum of$100.00, whichever is greater. All
work shall be performed in accordance with City Codes and Ordinances.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMM E%IfFM ENT "
fW- "4 0
O S GNATURE PERMIT OFFIC
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOURS NOTICE REQUIRED
ZEPHYRHILLS FIRE RESCUE DEPT- 813-780-0041
o
+F'
City of Zephyrhills
BUILDING PLAN REVIEW COMMENTS
Contractor/Homeowner: Uc
p
Date Received: 7—6— -/
Site: �� 2a ° ►�01� �` c
Permit Type:
d'
Approved w/no comments:C? Approved w/the below comments: ❑ Denied w/the below comments: ❑
CY
This comment sheet shall be kept with the permit and/or plans.
1
Gene B n—Fire Safety Officer Ijatk Contractor and/or Homeowner
(Required when comments are present)
813-780-0020 City of Zephyrhills Fire Fax-813-780-0021
Permit Application
Date Received Phony po B 70
ntact-for Permit;!."
Owner's Name 1 a umber-,!�,
Owner's Address
Fee Simple Titleholder Name Titleholder Phone Number
Fee Simple Titleholder 4ddress
Job Address #
Sub Division Parcai 16-60,W-6=6Z)
Bio-Hazard Waste Storage-ANNUAL Fumigation Tent
Comm Exhaust Kitchen Hood/Duct Hazardous Material(Tier 11 or RQ Facility)ANNUAL
Controlled Bum Hood Installation
F-1 Emergency Generator<30 kw LP/Natural Gas-installation
Emergency Generator>30 kw LP/Natural Gas-ANNUAL Sale
Fire Protection Maintenance-ANNUAL Places of-Assembly-ANNU,AL
FUTrTy-1 Pe-m-1, PFF71
Sprinkler 0 0 o F-1 Recreational Bum
Fire Alarm E] 0 0 o F-1 Sparklers
Hood Cleaning 1:1 0 El 0 Sprinkler System Installations
Hood Suppression 0 0 0 0 Standpipes(Sprinkler Sys)
F-1 Fire Alarm Installation Torch Roofing/Tar Kettle
= Fire Pumps Waste Tire Storage ANNUAL
F� Flammable Application-ANNUAL Valuation of Project
F-1 Fuel Tanks
0 Other: 54" 'aalA, 22-M W<
Contractor cza7_�-�Vr--z� Company i-,',ev
Signature Registered Y nq Fee6turrent Y/N
Address 'Z_- License# f) 13
C) 7
ELECTRICIAN Company
Signature Registered Y/N Fee Current Y/N
Address License#
PLUMBER Company
Signature Registered Y/N Fee Current L1/N_J
Address License#
MECHANICALI Company
Signature Registered Y/N Fee Current Y/N
Address License#
OTHER Company
Signature Registered Y/N Fee Current Y/N
Address License#
Directions:
Fill out application,completely.
Owner&Contractor sign back of application,notarized(Or,copy of signed contract with owner)
If over$2500,a Notice of Commencement is required(Mechanical work over$5000)
Supply two(2)sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel obtained from Property Tax Notice(hftp://appraiser.pascogov.com)
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to"deed"restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or
contractors to undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building Inspection Division—Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW(Chapter 713, Florida Statutes,as amended): If valuation of work is $2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law—Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the"owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the"owner" prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable laws regulating construction, zoning and land
development. Application is hereby made to obtain a permit to do work and installation as indicated. I certify
that no work or installation has commenced prior to issuance of a permit and that all work will be performed to
meet standards of all laws regulating construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. I also certify that I understand that the regulations of other
government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance.
If I am the AGENT FOR THE OWNER, I promise'in good faith to inform the owner of the permitting conditions set forth in '
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools,'air„conditioning, gas, or other installations not specifically included in the application. A
permit issued-shall be construed to'be a license to proceed with the work and not as authority to violate, cancel, alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six(6) months after the time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and will demonstrate
justifiable cause for the extension. If work ceases for ninety(90)consecutive days, the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
FLORIDA JURAT(F.S.117.03)
OWNER OR AGENT CONTRACTOR
Subscribed and sworn to(or affirmed)before me this Subscribed an o(or affi ed befo m is'..
by _by - �- _ == =` ` _ -
Who is/are personally known to me or has/have produced W /ar r ovally kryo n to mlor_h--as
_ have=produced'
as identification. M L!� as identification.
z
Notary Public Notary Public
Commission No. 6;/iSSIO&
Name of Notary typed,printed or stamped Name of Nota typed,printed or stamped
JACQua'NE 80%
10A. Ez December 16457
2,2022
�firu Troy Feh hS-.,o 8925.7019
; r
JLS Automotive
4920 Airport Rd.
Zephyrhills, FL 33542
Fire Suppression System For Paint Booth
Fire Fighter Inc.
P.O. Box 888
Land O'Lakes, FL 34639
813-996-6469
Gary F. Blair
Lic. # 01350500011997
.. . ...
(NOZZLE SPECIFICATIONS)
:: AMEREX INDUSTRIAL FIRE SUPPRESSION :SYSTEM
`X
q.
91.
.:. . q.
:.
.. .. : .. .. .. .. .. .. .. .. TFP .. .. .. .. ..
. . 2�
Is
261511
.14'
T.
. . Piping Requiremerits: System.piping:must be:balanced: Balanced-
NOT
piping is:that in which the difference between the shortest actual TO..SCALE. . ...
pipe length from.any %"-TEE to;nozzle and,the longest actual pipe
length.from any: 3%" TEE to:nozzle does not exceed 10% of the
-longest'actual pipe length from ariy W TEE to nozzle. Piping runs F/reFj9hter InC.:0,3505000,90:
from:the 1":TEE to:each of th:e 3/" TEE'§ must be:equal.ih ::PERMIT APPLICATION DRAWING J�sAucofTOtV ��_zooe 0000-0000
length. The.number:and t e.of:fittin g s for all'TEE to nozzle " " a z Airport Rd: ..
9. Yp 9 . :.
so
FL
sections must be equal. Zephyrhills,
. '.SCALE 1/4'=T.'.". REV - '. SHEET ,OF.f..
System Information For
JLS Automotive
• This is an AMEREX IS System:
• Piping to be 3/ & 1" galvanized
• Pull station is to be mounted at 48".
Detection to be fusible links of 280*
• Upon system actuation exhaust will shut down
System to be tied into bell
All penetrations shall be sealed.
• Installation will comply with FFPC 6th ed., NFPA 17
2013 ed., Manufacturers Specifications, and all local
codes and standards
,
- P/115040 System Design Page3A'16
`
3A.4 Vehicle Paint Spray Booths (VPSB):
The Amer6x Vehicle Paint Spray Booth Fire Suppression System isof the pre-engineered typeasdefinedbytheNFPA
Standard for Dry Chemical Extinguishing Systems,NFPA 17 and the Standard for Spray Application Using Flammable or
Combustible Materials,NFPA33. The extinguishing systems described in this manual are intended to be installed,
maintained,and serviced in accordance with NFPA17 and NFPA33' The Annerex Vehicle Paint Spray Booth System has
been evaluated by Underwriters Laboratories(UL) in accordance with the specific test protocol found in the UL1254
Standard (Pre-engineered Dry Chemical System Units).
Used for painting or coating cars,trucks, buses and large mobile equipment,Vehicle Paint Spray Booths come in a
variety of configurations and sizes. The basic volumes of a Vehicle Paint Spray Booth to be protected by the Amerex
System consists of three main components. They are:
Work Area�-Where the vehicle ispainted.
—Exhaust-channbersadUacenttotheVVorhA[aa. Plenums utilize filters to trap oveopray particles that
escape from the Work Area. The-primary purpose of the plenum is to expose a sufficiently large area of filter
media to the ovespray that|s carried along lna smooth current ofair,
-Fan-powered air channels that draw air through the Work Area,the Plenum(s),and finally out through the
Duct'
0FPA33 Standard for Spray App lication Using Flammable,and Combustible Materials classifies the interior sections
nf paint spray booths,and certain areas adjacent to booth openings,as Class' orcJass-1LDivison'1 or Divisioin-2
locations. Electrical components mfonindustrial Dry Chemical System,Such asthemmostatslocated within these
areas shall be rated for use ln classified areas,endal|mddngto1hesemonnponentsshaOconformniptheprovisionsof
NPP&7Q,National Electrical Code,for Class—1mrCXass-1,Dhvisipn-1or0]vYsion'2 locations. Any industrial System
Control Head with amoicrpsm/itcbis not suitable for use ina classified area.
Most of the time,the air isdrawn downward over the vehicle during the painting process(as\n eitheran Under Floor,
Pit,or Down Draft/Side-Exhaust\cnnMguration). Other booths,such asa Back Draft orPant-le8(Hooeshoe)design,
draw air down and across,toward the rear of the booth. Fresh air|s usually drawn in through intake filters either in
the Work Area telling or on the upper walls of the Work Area. Many installations ub|izea Heated Make-Up
/
Recirculation option,which re-circulates filtered,heated air through_the bo oth,thereby b ei-fig more energy efficient.
The Anlerex Vehicle Paint Spray Booth System requires that the booth exhaust fan(s) be shut doyvnpriortothe
discharge the
ABC drychemicaL This is accomplished with the use of the Mechanical Time Delay(P/0 15765) with
mechanically-released systems,or by the use of the Amerex Electric Control Panel (P/N 15780)with the use of the
timed.discharge c|rcuh. |tis the responsibility of the installer to prupedy}deotifvthe con-figuration of,the booth-and to
follow the requirements of this manual in order to achieve proper fire suppression. Sometimes,additional turns,
baffles,or obstructions in the booth's plenum and duct may dictate the use of additionalnozzles in order to.ensure
good distribution of dry chemical.
P/0:
TF 16172 Standard Work Area; 8ackdraft/Pande8/Underfloor Plenum
3-Way 16174 pit wf Tunnel(ceoteprnount);Downdraft Plenum with or without Vertical Transition(center-
mount)
D/P 16190 Exhaust Duct; Pit Plenum (end-position) '
TFP 17809 Module Perimeter Work Area Coverage,ONLY
'
Cylinders:
and IS 35 models are used for Duct and Plenum coverage, using either the DP,TF,or 3-Waynozdes.The |S45nnode|
must use two or fourTF nozzles (P/N16172) under Standard Work Area Coverage. The|S45 model uses one ortwo
TFP nozzles/p/Nl78O9\ under Module Perimeter Work Area Coverage.
ULE%5ZD8 April 9,2D13
,
P/N 15040 System Design Page34-17
3A.4 Vehicle Paint Spray Booths (continued):
Temperature Range: The operating temperature range for Vehicle Paint Spray Booth applications is -I0^Fto120"F�
29tto49°C).
Piping Requirements: Piping diagrams include limitations on pipe length and fittings. System piping must bebalanced.
Balanced piping is that in which the difference between the shortest actual pipe length from any Y4"tee to nozzle and
the longest actual pipe length from any Y4"tee to nozzle does not exceed 1O%of the longest actual pipe length from
any Y4"tee to nozzle. Piping runs from the 1"tee to each of the Y4"tees must be equal inlength. The number and
type of fittings for all tee to nozzle sections must 6eequal.
All piping must be Schedule 40, hot-dipped galvanized steel pipe,and all fittings must be 150 lb.class,minimum.
Examples of acceptable fitting materials include hot7dippedgalvanized malleable iron, ductile iron,orsteel. Couplings
and unions may be used where n ecessary,and reducing bushings or reducing tees can be used for changes in pipe
diameter. Note: Black steel pipe and fittings can be used in relatively noncorrosive atmospheres.
3A.4.1 Work Area Coverage, VPSB
There.are two distinctly different nozzle and piping arrangements for protecting the Work Area using the IS45ABC
cylinder. The first arrangement b and the second is"'Module Perimeter Work Area
Coverage outlined asfollows:
3A.A.1.1 Staridard
The Amerex Vehicle PaintSpray Booth System is flexible enough to protect a wide variety of Vehicle Booths ofvarious
dimensions. The maximum booth height isZ3'4". As noted,the |345 cylinderis used with two or four nozzles,and
each of the nozzles has been tested to protect a Work Area Module. A Work Area can be thought ofasa series of
'boxes', or Modules, stacked together, each protectedwith a nozzle. The maximum parameters for each Module are
given asfollows:
y '
1,U5O ftpernozde two or four TF nozzles per|545ABC
Maximum Mod.ule Area: 1O5*2 per nozzle for booths upto1U ft.\nbeigWt;*
.4Sft./for booths mt23ft,4in, height:*
Maximum Module Height: 23 ft"4in.
Maximum Module Side Length:
Module Center: 14 ft.for booths upto1Uft.tall*
Bft for booths at33'4 tall*
Booth Edge: 14ft for booths upto1Ufttall
Centerline: 15ft. ;booth height limited to1U taUwviththisoodon
*Note: For Module Center installations with booth heights between1O and I3'4", reference table 3A-1
Maximum Nozzle Offset—Module Center Entry: Within a3�ft. radius semicircle from center of module, noless than
12"from any side of the module (booth);the curved portion of the semicircle must curve away from the centerline of
the booth;the tip of the nozzle within G"ofceiling.
Maximum Nozzle Offset—Booth Edge Ent : Entry into the module at the closest point to the intersection mf the booth
wall and ceiling. The nozzle location, horizontally, is at the midpoint of the longest side of the module,+/-2 feet, The
tip of the nozzle must be within 6"nf its entry point. This option is allowable only for booths 1O feet or less!nheight.
ULEKSZOD April 9,Z013
P/N 15040 System Design Page 3A-38
3A.4.3 Duct Coverage, VPSB
The D/P Nozzle will protect either round or rectangular ducts up to 28 feet in length. Any change in duct direction or
additional length requires an additional D/P nozzle. The duct nozzle must be centered at the duct entrance, pointed in
the direction of air flow. The tip of the duct nozzle must be within 6"of the duct entrance.
Round Ducts
Maximum Diameter,Single Nozzle=46 Inches Rectangular Ducts
_Maximum Diameter,Two Nozzles=52 Inches The following table shows sample maximum rectangular
(nozzle spacing: .5 x duct diameter, located on the dimensions, based on the following two requirements:
same plane) Maximum Perimeter=144.5 Inches
Maximum Diagonal=46 Inches
Spacing for two nozzles, protecting a duct
diameter larger than 46", up to 52"maximum Rectangular Ducts
Side 1, Inches Side 2, Inches,
Maximum
12 44.4
14 43.8
16 43.1
18 42.3
.5 x DUCT
DIAMETER 20 41.4
22 40.4
24 39.2
26 37.9
28 36.5
30 34.8
32 33.0
32.5 32.5
34 31.0
36 28.6
38 25.9
40 22.7
42 18.7
44 13.4
UL EX 5208 April 9,2013
P/N 15040 System Design Page 3A-34
3A.4.2 Plenum,Coverage, VPSB
3A.4.2.1 Standard Plenum Coverage,VPSB
Plenum Type Nozzle Dimensions Maximum Nozzle Location Nozzle Nozzle
Used Per Nozzle Specifications Offset* Orientation
LxWxH
Backdraft(Option 1) TF 4'x 15'x 10' Volume=600ft3 12"x 12"Square, 0"to 6" Vertical, Pointing
Area=60ft2 Centered at Downward
Side 15' Ceiling
Backdraft(Option 2) TF 4'x 9'x 18' Volume=648ft3 12"x 12" 0"to 6" Vertical,Pointing
Area=36ft2 Square, Downward
Side=9' Centered at
Ceiling
Pantleg TF 4'x 15'x 12' Volume=720ft3 12"x 12"Square, 0"to 6" Vertical,Pointing
(Pantleg width Area=60ft2 Centered at Downward
dimensions: Side 15' Ceiling
1'minimum to
3' maximum)
Pit(Option 1) 3-Way 24'x 4'x 4' Volume=384ft' Centered,Length, 0"to 6" Vertical, Pointing
Area=96ft2 Width,and Downward;Two
Side=24' Height of Plenum Opposite Side
Holes Parallel to
Longest Side
Pit(Option 2) D/P, 24'x4'x4' Volume=384ft3 End, 0"to 6" Horizontal
Area=96ft2 Centered
Side=24'
Pit with Tunnel 3-Way Pit:24'x 4'x 4' Volume=576W Centered, Y2 Pit Vertical,Pointing
(Option 1) (Nozzle No Area=144ft2
Vertically; Height Downward;Each
Further than 12' Side=24' Centered,Length Side Hole Aligned
From Either Pit of Pit;12"From Parallel with Pit
End.) Start of Tunnel and funnel
Tunnel: Sections
12'x 4'x 4'
Downdraft,Side 3-Way Plenum: Volume=640ft3 Centered,Length Horizontal,Each
Exhaust With Vertical 24'x 4'x'4' Area=96ft2 of Plenum; Side Hole Aligned
Transition (Nozzle no Side=24' Centered, Parallel with
Further Than 12' Width of Plenum; Plenum and
From Either End Centered,Height Transition Sections
of Plenum.) of Plenum
Transition:
4'x 4'x 16'tall
Under Floor TF 14'x 15'x 1' Volume=210ft3 Side-Entry; 0"to 6" Horizontal
Area=2 10ft2 Centered,
Side 15' Vertically;
<> Centered,
I Lengthwise(±6") L
*Nozzle Offset is the maximum distance from the tip of the nozzle to the nearest edge of the protected zone.
UL EX 5208 April 9,2013
P/N 15040 System Design Page 3A-35
3A.4.2.1 Standard Plenum Coverage, VPSB (continued)
ON
PIT OPTION 2: '
D/P 24'
TNOZZLE24' "ONY
E
4'
\ /
i I +• O/P "4.
3-WAY NOZZLE
NOZZLE 12'
4 / 4. I
- 24'
WAY 24 O
1'MIN.; , NOZZL T'
3' MAX_.. 1
\ TF T \
NOZZLE
\ 16'
12'
12
1 MIN.;
3'MAX. J
OPTION'
1:
TF 4.
15' 4' IT NOZZLE - -
\/ I - 3-WAY 24'
NOZZLE
1 \ \
15'\` L/2\
4
28' \/�
MAXIMUM - 18'.
MAXIMUM TFP4¶21_Z"
NOZZLE
(2)
TF
NOZZLE
_ (2) %
rH/2 L/2
18'
MAXIMUM \
UL EX 5208
April 9,2013
P/N 15040 System Design Page 3A-40
3A.4.4 -Pipink Limitations. Plenum and Duct, VPSB (continued)
3/4
3/4
T1 Nozzle
3/4
Nozzle
Vehicle"Paint_Spray Booths,.,
DUCT and STANDARD,Plenum Coverages,lS18ABC,Two Nozzles
Cylinder 'Nozzle' Nozzle Type Piping 'Pipe' . Maximum Maximum
Size Quantity Section Size, in:. Length,ft. #of Elbows
1518A8C Any of the followina Cylinder % 36 4
2 coriibinzitions: to T1
one 3-Way'and one D/P;
-two D/P's;
-'two TF's;
one TF and one DIP
T1 to % 16 3
Nozzle
The maximum elevation of the'D/P,TF and 3-way nozzles above cylinder is 23'4".
UL EX 5208 April 9,2013
P/N 15040 System Design Page 3A-28
3A.4.1.2. Module Perimeter Work Area Coverage, VPSB (continued)
When determining how the Work Area of the Vehicle Paint Spray Booth is,-to be protected,the following information
must be established,based on the total width, length and height of the Work Area
Is Booth Height(Inside)Less Than or
Equal to 12.5 Feet?
Yes No
Use One IS45 for Booths with up to Is Booth Width(inside)Less Than or
435.2 Square Feet of Floor Area.Use Equal to 16 Feet?
Two Modules with Maximum Dimensions
of 16'x 13.6'x 125tall each
Yes/
Module Wdth=Booth Width No
Maximum Module Length=2,720_(Booth Height x Module Width);the
resulting value NOT to exceed 16'
Number of Modules, Lengthwise=Booth Length—Max.Module Length
Is Booth Width(inside)Greater Than
(round up to next MOLE number) 16 feet, But Less Than or Equal to 32
Actual Module Length=Booth Length+Number of Modules,Lengthwise;
Feet?
NOT to Exceed 16 Feet.
Number of IS45ABC Cylinders-=Number of Modules,Lengthwise+2;
(round up to the next WHOLE number)
Number of Nozzles=Number of Modules, Lengthwise
Yes/� No
Use Two Nozzles Across Width of Booth. Contact Amerex Engineedri
9
Module Width=Booth Width—2 for Assistance
Maximum Module Length=2,720+(Booth Height x Module Width);the
resulting value NOT to exceed 16'
Number of Modules, Lengthwise=Booth Length-Max.Module Length
(round up to next WHOLE number)
Actual Module Length=Booth Length_Number of Modules,Lengthwise;
NOT to Exceed 16 Feet.
Number of IS45ABC Cylinders=Number of Modules,Lengthwise
Number of Nozzles=Number of Modules Lengthwise x 2
Always round UP to calculate the number of IS45 cylinders required.
UL EX 5208 Apri19,2013
P/N 15040 System Design Page 3A-26
3A.4.1.2, Module Perimeter Work Area Coverage, VPSB
Module Volume: 2,720 ft.3 per nozzle, one or two TFP nozzles per IS45ABC
Maximum Module Area: 217.6 ft.2 per nozzle for booths up to 20 ft. in height;*
Maximum Module Height: 20 ft.
Maximum Module Side Length: 16 ft.
Maximum Nozzle Offset From Center of Wall: +/-10%of adjacent wall length
*Note: Reference Coverage Table 3A-2
Table 3A-2: Module Perimeter Vehicle Paint Spray Booth
Work Area Coverage
Booth Height,Feet Module Side 2,feet
13.60 14.00 14.50 15.00 15.50 16.00
12.5 16.00 15.54 15.00 14.50 14.03 13.60
13 15.38 14.94 14.42 13.94 13.49 13.07
14 14.28 13.87 13.39 12.95 12.53 12.14
15 13.33 12.95 12.50 12.08 11.69 11.33
16 12.50 12.14 11.72 11.33 10.96 10.62
17 11.76 11.42 11.03 10.66 10.32 10.00
18 11.11 10.79_ 10.42 10.07 9.74 9.44
19 10.52 10.22. 9.87 9.54 9.23 8.94
20 10.00 9.71 9.37 9.06 8.77 8.50
[Dimensions inside of table are Side 1]
Piping Requirements:
Piping diagrams include limitations on pipe length and fittings. System piping must be balanced.Balanced piping is
that in which the difference between the shortest actual pipe length from the 1"tee t 'nozzle and the longest actual
pipe length from the V'tee to nozzle does not exceed 10%of the longest actual pipe length from tee to nozzle. The
number and type of fittings for both tee to nozzle sections must be equal.
All piping must be Schedule 40, hot-dipped galvanized steel pipe, and all fittings must be 1501b.class. Examples.of
acceptable fitting materials include hot-dipped galvanized malleable iron,ductile iron,or steel. Couplings and unions
maybe used where Inecessary,and reducing bushings or reducing tees can be used for changes in pipe diameter.
Note: Black steel pipe and fittings can be used in relatively noncorrosive atmospheres.
Nozzle Placement and Orientation:
The TFP Nozzle has been developed to provide application of extinguishing agent from the upper perimeter of the
module being protected. The nozzle is to be installed through the top of the module, at the closest point to the
intersection of the module wall and module top. The nozzle location, laterally, is to be at the midpoint(+/- 10%)of the
adjacent module edge. The tip of the nozzle must be within 6"of its entry point. The nozzle is to be installed vertically,
with the orifices pointing downward, and the engraved arrow pointing into the protected module. The arrow must be
aligned perpendicular to the adjacent wall,when viewed directly from below. Proper nozzle placement is shown as
follows:
UL EX 5208 April 9,2013
^
^ ��1504 System Design Page3A�9
'
3A.4.1.2 Module Perimeter Work Area Coverage, VPSB (continued)
. �
*Example a booth ofdimensions
Module Dimensions:lBx13.6'x12.S'ta)l;
Use one |S4S with two TFPnozzles,two possible piping options are shown.
_ _
`u^
27'2
FRONT
OF �-
BOOTH
NOTE: Asin the figures above,the nozzle must either be located on the side of the module (booth)or with one nozzle
located at the edge of the module over the front end of the booth.
UL[X5ZUO April 5\%O13
P/M 15040 System Design Page 3A-33
3AA1Z Module Perimeter Work Area Coverage, VPSB (continued)
1 "
1 "
T1
Nozzle
1 "
Nozzle
Module Perimeter Work Area,VPSB,IS45ABC,Two TFP Nozzles
Pipe Size, in Maximum Maximum #of Tees
Length,ft #of Elbows Allowed
Cylinder to T1 1 36 4 1
T1 to Nozzle 1 10 2 0
Total 1" Pipe -- 56 --The maximum nozzle height above the agent cylinder is 20 feet.
UL EX 5208 April 9,2013
813-780-0020 City of Zephyrhills Permit Application Fax-813-780.0021
Building Department
Date Received19r+ phone Contact for Permitting
Owner's Name C= 7• {� Y 0J) O.wneuPhone..Nurtiber
Owner's.Address '! 3 �� GI+� Owner.-Phone Number
ebyv)c) Owner Phone•Number;
JOB ADDRESS 2- LOT
SUBDIVISION �: PARCEL ID#
(OBTAINED FROM PROPERTY TAX'NOTICE)
WORK PROPOSED NEW CONSTR. ; : ADD/ALT C�., SIGN, [� Q ., DEMOLISH
e INSTALL �. REPAIR
PROPOSED USE Q SFR COMM,� �. OTHER
TYPE OF CONSTRUCTION Q BLOCK
^ "FRAME STEEL
DESCRIPTION'OF WORK �'�� 9 121Z� G�sS JV S r op
BUILDINCrSIZE r SO FOOTAGE L �, HEIGHT
=BUILDING VALUATION OF T.OTAL.CONSTRUCTION
=ELECTRICAL AMP:SERVICE. Q DUKE'ENERGY 0 W:R:E.C.
=PLUMBING
=MECHANICAL $ VALUATION OF MECHANICAL INSTAL•LATIOW
=GAS Q ROOFING [�. SPECIALTY OTHER
FINISHED FLOOR ELEVATIONS FLOOD ZONE=AREA DYES NO.
BUILDER COMPANY
SIGNATURE REGISTERED Y/. N FEE CURREN
Address License.# I `
ELECTRICIAN' COMPANY.
SIGNATURE REGISTERED Y/ N FEE CURREN Y%N
Address License
PLUMBER COMPANY
SIGNATURE- REGISTERED Y/'N FEE CURREK
Address 71 License# �-
MECHANICAL COMPANY
SIGNATURE REGISTERED 1, :Y/,N:. FEE CURREN
Address License,# 17
t OTHER COMPANY
SIGNATURE t� REGISTERED Y.,/.-N. F E CURREN „Y/,N_...
Address O b7 N1 �Q L ..License# ;99 I1 I9 S
RESIDENTIAL Attach;(2)'PIoVPlans;:(2)sets'of.'Building,Plans;.(1)set of:Energy,Forms;,R-O-W, ,Permitfor=new;construction,
Minimum ten(10)working days after submittal date. Required'onsite;Construction•Plans Stbrmwater-Plans w/=Silt Fence:installed,' .
Sanitary Facilities&1 dumpster;Site Work Permit-for subdivisionsllarge projects
COMMERCIAL Attach(2)complete sets of Building Plans plus alifeSafety.Page;(1)set of Energy Forms.R-O-W Permit for new construction.
Minimum ten(10):working=days•after submittal date: Required.onsite,Construction Plans;.Stormwater,Plans.w/Silt:F.ence installed,
Sanitary Facilities&1 dumpster.Site Work Permit for all new projects.All commercial requirements must meet compliance
SIGN PERMIT Attach(2)aets of�Englneere6Plans.
""PROPERTY,SURVEY required for all NEW construction.
Directions:
Fill out application completely.
Owner&Contractor sign back-of application,notarized
If over$2500,a Notice of Commencement is required. (A/C upgrades over$7500)
" Agent(for the contractor)or Power of Attorney(for the owner)would be someone with notarized letter from owner authorizing same
OVER THE COUNTER PERMITTING (copy of contract-required)
Reroofs if shingles Sewers Service Upgrades A/C Fences(PlottSurvey/Footage) '
Driveways-Not over Counter if on public roadways..needs ROW
NOTICE O.F_DEED,RESTRICTIONS: The undersigned understands that this permit maybe subject to"deed"restrictions"
which maybe more restrictive-than County regulations. The undersigned assumes-responsibilityforeompliattce with any
applicable.�deed,restrictions... -
UNLICENSED CONTRACTORS:AND CONTRAGTOR"RESPONSIBILITIES:= If'-the•owner Chas hired=a.=contractor or
contractors-to-undertake.work,.#hey may=belrequired-to be licensed,in.accordance.with state and local regulation.,..:lf.the
contractor is not licensed as required by law, both the owner,and contractor-,may be cited--for--af:rnisdemeanor violation
under-state,law. -if the-owner.or;intended,c6htractor�are uncertain as-to.what.iicensing requirements.may.applyfpr.,the.
intended work, they are advised'to contact-the Pasco County'Building-Inspectiori Division==Licensing Section at 727=847-
8009: - Furthermore,:if-.the.owner has hired-a' contractor or contractors;, he,is. advised to have the contractors),sign
portions--of-the "contractor Block"-of-lhi&,application for which theywill-be' -responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.-
TRANSPORTATION:IMPACT/UTILITIES IMPACT AND RESOURCE RECOVERY FEES:,The.undersigned understands
that Transportation impact Fees,�and-Recourse-Recovery Fees may -the.construction of new buildings, change of
use,in existing buildings;.or expansion of existing'buildings,:as specified in iPasco County Ordinance-number 89-07 and
90-07,.as amended. The undersigned.also..understan &.ds,.:that sufees, as may be,due, will be identified at the time of
permitting. It is,further understood that.-Transportation,lmpact'Fees and Resource Recovery Fees must be paid prior to
receiving a "certificate of occupancy" or-final power release. if the,-project does not.involve a certificate of occupancy-or,
final power.release,.the fees must be,paid prior to permit issuance. Furthermore,.if:Pasco County Water/Sewer Impact
fees are�due;-theymust-be_paid:prior-to.permit,issuance.in accordance:with applicable Pasco County ordinances...
CONSTRUCTION:L:IEN LAW(Chapter 713, Florida Statutes,as>amended) .'if valuation of work7.is$2;500:00 or'more, I'
certify 'that I; the' applicant, have been provided, with a copy of the "Florida Construction Lien Law=-Homeowner's
Protection..Guide" prepared by the Florida Department of Agriculture and;Consumer'Affairs. if the appiicant.;is someone:
other than the"owner", I certify that I-have obtained a copy of.the:above•described document and promise in-good:faith-to
deliver it to the"owner"prior to.commencement,,;.
CONTRACOSIOWNER'S AF_FIDAVIT:.:I certify_that all the;information in.th TR' is`application..is accurate.and.that-bli'mork
will be done in compliance with all applicable_laws regulating construction,zoning.'andaand.development.'--Application,is
hereby made to obtain a permit to do'worW" t id'instaliation;as•indicated. if certify-that no work or installation_has
commenced. prior-to:issuance,of a,permit and,that all work will be performed to-:meet standards of all laws regulating
construction, County and City-6 de' ,'zoning regulations, and land- development regulations in-the jurisdiction: I also
certify.that I understand that the regulations of other government agencies mayapply to the intended work, and that'it is
my responsibility to identify what actions I must take to be incompliance. Such agencies include:but are not limited to:
- Department of Environmental Protection-Cypress Bayheads, Wetland Areas and Environmentally Sensitive
Lands,Water/Wastewater.Treatment.
- Southwest Florida Water Management District-V1%e11s, Cypress Bayheads, Wetland Areas, Altering
Watercourses.
- Army Corps of Engineers-Seawalls, Docks,_=Navigabl&Waterways.
- Department of Health & Rehabilitative Services/Environmental-:-Health-Unit-Wells, Wastewater Treatment,
Septic Tanks.
US:Environmental'ProtectionAgency=Asbestos.:abatement.,-
Federal Aviation Authority-Runways.
I understand that,the following..restrictions apply to the use of filh
- Use of,fill is-not allowed in Flood:Zone"V"unless-expressly.permitted.
If the fill material is:to be used in Flood Zone.."A", it is understood thato a drainage plan addressing a
"compensating volume"`will-be submitted at time.of.permitting which is prepared by.a professional.engineer
licensed by the State of Florida.
If the-fill--material is•-to be-used-in Flood.Zone "A" in connection with a permitted building-using stem-wall-
construction,'l.certify that fill will be-used only to fill the area within-the stem wall.
If fill material is to be used in any area, I certify that Use of such fill will not adversely-Affect adjacent
properties.- if.use.of`fill,is found.to adversely affect adjacent,properties,..the„owner-may,be cited.-for violating
the conditions of the building permit issued under the attached permit-application,--for-lots less than.one (1)
acre:which.,are eievated,by fill;an.,engineered drainage-plan is required.
If i am'the-AGENT:FOWTH€-OWNER, I promise--in good faith to-itiform,the-..owner of.the.permitting;conditions set forth:in .
thisi:affidavit, prior to commencing construction. I understand that a separate permit may required for-electrical work,
plumbing,-signs-, wells, pools; air--conditioning, gas,-.or other installations not,specifically included in.the.application. A
permit issued shall be construed to-be a license to proceed with,the work and not as authority to violate, cancel, alter, or
set aside.any provisions of the.-technical codes;'nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors-in-,-plans, construction or violations-of any codes.--Every permit issued shall-become invalid-
unless-the work.authorized by such=permit is commenced within six months of permit issuance,.or if work authorized.by
the.ipermit is suspended or abandoned'for a'period',rof six(6)months after,the-time-the=work-iscommenced., An extension
may-be-.requested,.ln..writing,_from the Building;Official for.a_period not to exceed ninety (90) days and will demonstrate
justifiable cause for-Ahe•extension. If work'.ceases for ninety�(90):consecutive days, the job is considered abandoned.
WARNING'-:TO,-OWNER: YOUR FAILURE TO RECORD A-NOTICE,.-OF=COMMENCEMENT:MAY-RESULT lWYOUR
PAY04"T' III'CE`FOR'IMPROVEMENTSTO'YOUR`PROPERTY:-:IFhYOUINTEND,TO`�OBTAIN:FINANCiNGi.CONSULT
-WITH=YOUR.LENDER'ORANIATTORNEY-BEFORE RECORDING YOURNOTICEOF"COMMENCEMENT:
FLORIDA JURAT(F.S:-11.7..03)_
OWNER.OR"AGENT CONTRACTOR
Subscribe8 and s'Wom'to(or affrimed)-before ine,this- Subscribed and:savorn-to,(or-affirmed):before,nie'this
by by -. _
Who Is/are personalty known to me or has/have produced Who is/are personally known,to,me�or't�as/haGe::produced
as identification. --r "':Y1 -'__--------as';ldentification, ,
..` :.•..:y,.-.,ten—��
Notary Public Notary=Public .
Commission No. Commission No.
Name of Notary typed,printed or stamped Name of Notary typed,printed or.stamped
7/8/2019 13-26-21-0010-00000-0010 1 Pasco County Property Appraiser
Parcel ID 13-26-21-0010-00000-0010 (Card: 1 of 2)
Classifi8ation 04800-Wareh/Dist Term
Mailing Address Property Value
BLACKLIDGE LISA D & Ag Land $0
BAILEY PATRICIA A & ET AL Land $86,043
C/O ROBERT JACKSON Building $907,973
123 CHRISTY LN Extra Features $12,261
KOKOMO, IN 46901-3840
Physical Address - See All 17 Just Value $1,006,277
addresses Assessed (Non-School Amendment 1) $1,006,277
4918 AIRPORT ROAD,
ZEPHYRHILLS, FL 33542 Non-School Taxable Value $1,006,277
39240 SOUTH AVENUE, School District Taxable Value $1,006,277
ZEPHYRHILLS, FL 33542
Legal Description (First 200 characters)
See Plat for this Subdivision
ZEPHYR AIR PARK A COMMERCIAL
SUBDIVISION PB 24 PG 82 LOTS 1 2 &
4 OR 9168 PG 3387
Jurisdiction
CITY OF ZEPHYRHILLS
Land Detail (Card: 1 of 2)
Line Use Code Description Zoning Units Type -Price JCondition Value
- t ,-----f—------- -- 1
1 4800S_1 4AA-1 Warehouse_ _OOLI 12,000.00 SF $1.42 1.00 $17,040_
- -- -
2 -j 4800S I 4AA-2 $0.66 SF 04,550.00 Warehouse OOLI 1 1.00 $69,003
-- I I I
Additional Land Information
-_Acres - '_ Tax Area -I FEMA Code Res Code Co_m Code ,-Condo_Code -
----- 2.68T-----� 30ZH � -- IZPK ---- IZPK---------- IZPK --
View Sketch Building Information - Use 8000-Metal Buildings (Card: 1 of 2)
Year Built 2001 Stories 1.0
Exterior Wall 1 Modular Metal Exterior Wall 2 None
Roof Structure Steel Frame or Truss Roof Cover Min Roof(Corr. or Sh M)
Interior Wall 1 Masonry or Minimum Interior Wall 2 None
Flooring 1 Finished Concrete Flooring 2 None
Fuel None Heat None
/C None Baths 9.0
Line Code IDescription 'Sq. Feet __ _ .Value
1 BAS01 1 LIVING AREA r 11,300- - - $445,855
Extra Features (Card: 1 of 2)
Line Code_ _ Description___ _ _ _ Year __]Units
—1 CPAVASP� _ PAVING ASPHALT 2001 - I _27,227 - $7,964
2____T CSWC SIDEWALK CONCRETE 2001 1 2,604 $4,297
Sales History
Previous Owner: BOLENDER INVEST INC
--�--- ---------------- ---------------------- ---- ----,----------------
Month/Year -iBook/Page -�- Type - M- _jDOR Code Condition (Amount
03/2015 - 9168 / 3387 i Warranty Deed I 01 j Improved--� $1,000,000
07/1998 1 3975 / 1748 i Warranty Deed i Vacant 1 $42,000
07/1998 ---'j - 3975 / 1727 -- --f- Warranty Deed - -- -- - --- -- - ` Vacant $0
07/1998 I 3975 / 1742 j- Warranty Deed -� --- - Vacant - $0 - -
08/1995 3466 / 1661 ? Warranty Deed Vacant $0
04/1983 1247 / 0762 Warranty Deed 1 Vacant ! -$0 T
search.pascopa.com/parcel.aspx?parcel=2126130010000000010 1/1