HomeMy WebLinkAbout20-22340 I
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING, CONSTRUCTION
Florida Department of Business and Professional Regulation -.Residential Performance Method
ProjectName: HIGHGATE Builder-Name: Mario's Air Cond'tioning and Heating Inc.
Street: 6426 Bradford Woods Drive Permit Office: .�,'a j s ze� y;�irffj
City,State,Zip: Zephryhills,FL,33542 Permit Number: ZZ ,
Owner: HIGHGATE Jurisdiction:_ 01(poD
Design Location: FL,Tampa County- PASCO(Florida Climate Zone 2)
:1. New construction or existing New(From Plans) 9. Wall Types.(1864.5 sgft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block.-Int Insul,Exterior R=4.1 1525.50 ft2
b.Frame-Wood,Adjacent R=13.0 339.00 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 4 d.N/A R= ft2
10.Ceiling Types (1779.0 sgft'.) Insulation Area
5. Is this-a worst case? Yes a.Under Attic(Vented) R=30.0 1779.00 ft2
6. Conditioned floor area above grade(ft2) 1850 b.N/A R= ft2
Conditioned floor area below grade(ft2) .0. c.N/A R= ft2
.11.Ducts R ft2
7.-Windows(221.1 .sgft.) Description Area a.Sup:Attic,Ret:LIVING,AH:LIVING .. . . 6 710 ..
a. U-Factor: Dbl,U=0:35 173:14 ft2
SHGC: SHGC=6.29
b. U-Fa ctor: Dbl,U=0.63 48.00 ft2 12.Cooling system_s kBtu/hr Efficiency:
SHGC: ... SHGC=0.32 a.Central Unit 30.0 SEER:15.00
c. U-Factor:- N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a.Electric Heat Pump 26.0 HSPF:8.50
SHGC:
Area Weighted Average Overhang Depth: 2.171 ft.
Area Weighted Average SHGC: 0.297 14.Hot water.systems
8. Floor Types (1779.0,sqft.) Insulation Area a.Electric Cap:40gallons
EF:0.920920
a.Slab-On-Grade Edge Insulation R=0.0 .1779.00 ft2 b.Conservation features
b.N/A R= ft2 None
c.N/A R= ft2 15.Credits Pstat
Glass/Floor Area: .0.120 -Total Proposed Modified Loads: 64.13 PASS
Total Baseline Loads: 65.44
I hereby certify that the plans and specifications covered by Review of the plans and ScTKE Sr9T.
this calculation are in compliance with the Florida Energy specifications covered by this, fyo�
Code. : ; calculation indicates compliance
with the Florida.Energy Code: rrrrr '•% %; �;ti O
PREPARED BY: i" �' �� Before construction is completed
DATE: 19iQt9n1 o this building will be inspected.for
compliance with Section 553.908
hereby certify that this building, as designed, is in compliance Florida Statutes.
with the Florida Energy Code. COD 1yy61��
OWNER/AGENT: Snezana Gurcinovska BUILDING OFFICIAL:
DATE: 1219119 DATE:
- compliance requires certification by the air handler unit.manufacturer that the air handier enclosure qualifies as . . . .
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project:requires
an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2).
12/9/201,9 1:36 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 5
I -
I
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
• PROJECT
Title: HIGHGATE Bedrooms: 4 Address Type: StreetAddress
Building Type: User ConditionedArea: 1850 Lotl#42
OwnerName: HIGHGATE Total Stories: 1 Block/Subdivision: 01
#of Units: I Worst Case: Yes PlatBook:
BuilderName: Mario's Air Conditioning and He RotateAngle: 180 Street:6426 Bradford Woods Drive
Permit Office: Cross Ventilation: No County: PASCO
Jurisdiction: Whole House Fan: No City,State,Zip:Zephryhills,FL,33542
FamilyType: Single-family
New/Existing: New(From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design DailyTemp
V Designt-ocation TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Tampa FL—TAMPA—INTERNATIO 39 91 70 75 645.5 54 Medium
BLOCKS
Number Name Area Volume
1 Entire House 1850 17390
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 OWNERS 258 2425.2 No 2 1 1 Yes Yes Yes
2 O.BTH 120 1128 No 0 1 Yes Yes Yes
3 WIC 56 526.4 No 0 1 No Yes Yes
4 BED4 121 1137.4 No 1 1 1 Yes Yes Yes
5 LAUND 49 460.6 No 0 1 No Yes Yes
6 FOYER 75 705 No 0 1 Yes Yes Yes
7 LIVING 800 7520 No 0 1 Yes Yes Yes
8 BED 137 1287.8 No 1 1 1 Yes Yes Yes
9 BA2 50 470 No 0 1 Yes Yes Yes
10 BED2 184 1729.6 No 1 1 1 Yes Yes Yes
FLOORS
y # FloorType Space Perimeter PerimeterR-Value Area 'Joist R-Value Tile Wood Carpet
I Slab-On-Grade Edge Insulation OWNERS 30 ft 0 224 ft2 ---- 0 1 0
2 Slab-On-Grade Edge Insulation O.BTH 12 ft 0 120 ft2 ---- 0 1 0
3 Slab-On-Grade Edge Insulation WIC I ft 0 56 ft2 ---- 0 1 0
4 Slab-On-Grade Edge Insulation BED4 lift 0 121 ft2 ---- 0 1 0
5 Slab-On-Grade Edge Insulation LAUND I ft 0 49 ft2 0 1 0
6 Slab-On-Grade Edge Insulation FOYER 5 ft 0 75 ft2 0 1 0
7 Slab-On-Grade Edge Insulation LIVING 56 ft 0 763 ft2 0 1 0
12/9/2019 1:36 PM EnergyGauge(D USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 5
i
i
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
FLOORS
I
# FloorType Space Perimeter PerimeterR-Value Area JoistR-Value Tile Wood Carpet
8Slab-On-Grade Edge Insulation BED lift 0 137ft2 0 1 0
I
9Slab-On-Grade Edge Insulation BA2 5ft 0 50ft2 ____ 0 1 0
10SIab-On-Grade Edge Insulation BED2 32ft b 184ft2 - ____ 0 1 0
ROOF
/ Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Gable orShed Composition shingles 1875 ft2 296 ft2 Medium N 0.01 No 0.9 No 0 18.4
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 300 1779 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) OWNERS 30 Blown 224ft2' 0.1 Wood
2 Under Attic(Vented) O.BTH 30 Blown 120 ft2 0.1 Wood
3 Under Attic(Vented) WIC 30 Blown 56ft2; 0.1 Wood
4 Under Attic(Vented) BED4 30 Blown 121 ft2. 0.1 Wood
5 Under Attic(Vented) LAUND 30 Blown 49 ft2, 0.1 Wood
6 Under Attic(Vented) FOYER 30 Blown 75 ft2 0.1 Wood
7 Under Attic(Vented) LIVING 30 Blown 763ft2 0.1 Wood
8 Under Attic(Vented) BED 30 Blown 137ft2 0.1 Wood
9 Under Attic(Vented) BA2 30 Blown 50ft2, 0.1 Wood
10 Under Attic(Vented) BED2 30 Blown 184 ft2 0.1 Wood
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
111P Ft In Ft In Area R-V;,111e Fraction AhSnr rrarip%
1 S=>N Exterior Concrete Block-Int Insul OWNERS 4.1 16 0 9 5 150.7 ft2 0 0 0.01 0
2 W=>E Exterior Concrete Block-Int Insul OWNERS 4.1 14 0 9 5 131.8 ftZ 0 0 0.01 0
3 S=>N Exterior Concrete Block-Int Insul O.BTH 4.1 12 0 9 5 113.0 ft2 0 0 0.01 0
4 S=>N Exterior Concrete Block-Int Insul BED4 4.1 11 0 9 5 103.6 ft2 0 0 0.01 0
5 E=>W Garage Frame-Wood BED4 13 11 0 9 5 103.6 ft2 0 0.25 0.01 0
6 E=>W Exterior Concrete Block-Int Insul FOYER 4.1 5 0 9 5 47.1 ft2 0 0 0.01 0
_ 7 S=>N Garage Frame-Wood FOYER 13 15 0 9 5 14113 ft2 0 0.25 0.01 0
8 N=>S Exterior Concrete Block-Int Insul LIVING 4.1 31 0 9 5 2911.9 ft2 0 0 0.01 0
9 W=>E Exterior Concrete Block-Int Insul LIVING 4.1 25 0 9 5 235.4 ft2 0 0 0.01 a
10 E=>W Garage Frame-Wood LIVING 13 10 0 9 5 942 ft2 0 0.25 0.01 0
11 N=>S Exterior Concrete Block-Int Insul BED 4.1 11 0 9 5 103.6 ft2 0 0 0.01 0
12 N=>S Exterior Concrete Block-Int Insul BA2 4.1 5 0 9 5 47:1 ft2 0 0 0.01 0
i
12/9/2019 1:36 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) ComIpliant Software Page 3 of 5
i
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
hie Ft In Ft In R- FraCtann Ah or &w1e%
13 N=>S Exterior Concrete Block-Int Insul BED2 4.1 13 0 9 5 122.4 ft2 0 0 0.01 0
14 E=>W Exterior Concrete Block-Int Insul BED2 4.1 13 0 9 5 122.4 ft2 0 0 0.01 0
15 S=>N Exterior Concrete Block-Int Insul BED2 4.1 6 0 9 5 56.5 ft2 0 0 0.01 0
DOORS
# Ornt DoorType Space Storms U-Value Width Height Area
Ft In Ft In
1 E=>W Insulated FOYER None .33 3 7 21 ft2
WINDOWS
Orientation shown is the entered orientation(_>)changed to Worst,Case.
/ Wall Overhang
�/ # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation IntShade Screening
1 W=>E 2 Vinyl Low-EDouble Yes 0.35 0.29 N 32.7 ft2 Oft 0 i in 0 ft 0 in None None
2 S=>N 3 Vinyl Low-EDouble Yes 0.35 0.29 N 4.0 ft2 0 ft Olin 0 ft 0 in None None
3 S=>N 4 Vinyl Low-E Double Yes 0.35 0.29 N 16.3 ft2 0 ft 0 in 0 ft 0 in None None
4 N=>S 8 Vinyl Low-E Double Yes 0.35 0.29 N 15.9 ft2 0 ft 0 in 0 ft 0 in None None
5 W=>E 9 Vinyl Low-EDouble Yes 0.35 0.29 N 49.5 ft2 0 ft 0 in 0 ft 0 in None None
6 W=>E 9 Vinyl Low-EDouble Yes 0.63 0.32 N 48.0 ft2 10 ft 0 in 0 ft 0 in .- None Exterior5
7 N=>S 11 Vinyl Low-EDouble Yes 0.35 0.29 N 15.9 ft2 0 ft 0 in 0 ft 0 in None None
8 E=>W 14 Vinyl Low-EDouble Yes 0.35 0.29 N 38.9 ft2 0 ft 0 in 0 ft 0 in None None
GARAGE
# FloorArea CeilingArea Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 382.8 ft2 382.8 ft2 64 ft 8 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse ProposedACH(50) .000418 2028.8 111.38 209.47 .1634 7
HEATING SYSTEM
# System Type Subtype Speed Efficiency Capacity Block Ducts
1 Electric Heat Pump/ Split Single HSPF:8.5 26 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split Single SEER:15 30 kBtu/hr 946 cfm 0.8 1 sys#1
I
I
I
I
12/9/2019 1:36 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Com pliant Software Page 4 of 5
I
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.92 40 gal 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC I Collector Storage
Cert # CompanyName System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
---Supply---- ----Return— Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area LeakageType Handler TOT OUT QN RLF Heat Cool
1 Attic 6 710 ft2 LIVING 30 ftZ DefaultLeakage LIVING (Default)c(Default)c 1 1
TEMPERATURES
ProgramableThermostat: Y Ceiling Fans:
Cooling [[ ]]Jan [[ ]]Feb Mar �Apr
a rj Jun ri
Jul Au rl
Se [ ]Oct [[ ]]Nov Dec
Heatin [X]Jan [X]Feb Mar Ar l ]May Jun Jul Au Sep []Oct [X]Nov Dec
Ventin [[ ]]Jan [[ ]]Feb X Mar Apr [ )May Jun Jul Aug Se [X]Oct [[XX]]Nov Dec
ThermostatSchedule: HERS 2006 Reference Hours
ScheduleType 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78— 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 681 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 6&- 68 68 66 66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8lbs/sq.ft. 0 ft2 Oft 0.3 OWNERS
Default(8 lbs/sq.ft. ft2 ft 0.3 O.BTH
Default(8 lbs/sq.ft. ft2 ft 0.3 WIC
Default(8 Ibs/sq.ft. ft2 ft 0.3 BED4
Default(8 lbs/sq.ft. ft2 ft 0.3 LAUND
Default(8 lbs/sq.ft. ft2 ft 0.3 FOYER
Default(8 Ibs/sq.ft. ft2 ft 0.3 LIVING
Default(8 Ibs/sq.ft. ft2 ft 0.3 BED
Default(8 Ibs/sq.ft. ft2 ft 0.3 BA2
Default(8 lbs/sq.ft. ft2 ft 0.3 BED2
I
12/9/2019 1:36 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 5 of 5
i
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
FJurisdiction: Permit#:
Job Informatiion
i
Builder: Mario's Air Conditioning and 1-10diftiUmity: !LOU NA
Address: 6426 Bradford Woods Drive
City: Zephryhills State: FL Zip: 33542
Air Leakage Test Results -Passing results must n*ef`either the Performance,,Pi-escr giie, or:ERI'Method ;
PRESCRIPTIVE METHOD-The building or dwelling unitshall be.tested and verified as;having an air 11. eakage rate of not exceeding 7 air
.
changes per flour at a pressure of0.2 inch w.g:;(50 Pascals)in Clirnate Zones.1 and 2.
0 PERFORMANCE or ERI METHOD-The building or dwielling unit`shall be tested and verified as having 66;air leakage rate of not exceeding
the,selected ACH(50)value,as shown on Form R405-2017(Performance),oi R406-2017"(ERI ,,section labeled;as infiltration;sub-section ACH50.`
,ACH(50)specifred'o'_Form R405-2017-Energy Caic(Peifonnance)or R406-201 T,,(ER 7.000
x 60 _ 17390 = Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
F-1 PASS •Code Is calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing.Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 Pascals).
Testing shall be conducted by either individuals as defined in Section 553.993(5)or(7),Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f),(g),or(i)or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and
provided tothecode official.Testing shall be performed at anytime after creation of all penetrations of the buildingthermalenvelope.
During testing:
1.Exteriorwindows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended we or other infiltration
control measures.
2.Dampers including exhaust,intake,makeup air,back draft and flue dampers shall be closed,but not sealed beyond intended infiltration control
measures.
3.Interior doors,if installed at the time of the test,shall be open.
4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5.Heating and cooling systems,if installed at the time of the test,shall be turned off.
6.Supply and return registers,if installed at the time of the test,shall be fully open.
Testing.Company,
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
I
Signature of Tester: Date of Test:
I
i
Printed Name of Tester:
License/Certification#: Issuing Authority:
I
12/9/20191:37:05 PM EnergyGaugeO USA 6.0.04(Rev.1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
1
i
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX*= 98
1
The lower the Energy Performance Index, the more efficient the home.
i
1. New home or, addition 1. New(From Plans) 12. Ducts, location &,insulation level
a) Supply ducts R 6.0
2. Single-family or multiple-family 2. Single-family b) Return ducts R 6.0
c)AHU location LIVING
3. No. of units (if multiple-family) 3. 1
4. Number of bedrooms 4. 4 13. Cooling system: Capacity 30.0
a) Split system SEER 15.0
5. Is this a worst case?(yes/no) 5. Yes b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area (sq.ft.) 6. 1850 d) Room unit/PTAC EER
e)Other
7. Windows,type and area
a) U-factor:(weighted average) 7a. 0.411
b) Solar Heat Gain Coefficient(SHGC) 7b. 0.297 14. Heating system: Capacity 26.0
c)Area 7c. 221.1 a) Split system heat pump HSPF 8.5
b) Single package heat pump HSPF
8. Skylights c) Electric resistance COP
a) U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE
b) Solar Heat Gain Coefficient(SHGC) 8b. NA e) Gas furnace, LPG AFUE
f) Other
9. Floor type, insulation level:
a) Slab-on-grade (R-value) 9a. 0.0
b)Wood, raised (R-value) 9b. 15.Water heating system
c) Concrete, raised (R-value) 9c. a) Electric resistance EF 0.92
b) Gas fired, natural gas EF
10. Wall type and insulation: c) Gas fired, LPG EF
A. Exterior: d) Solar system with tank EF
1. Wood frame (Insulation R-value) 10A1. e) Dedicated heat pump with tank EF
2. Masonry (Insulation R-value) 10A2. 4.1 f) Heat recovery unit HeatRec%
B.Adjacent: g) Other
1. Wood frame (Insulation R-value) 10131. 13.0
2. Masonry (Insulation R-value) 10132.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level a) Ceiling fans
a) Under attic 11 a. 30.0 b) Cross ventilation No
b) Single assembly 11 b. c) Whole house fan No
c) Knee walls/skylight walls 11 c. d) Multizone cooling credit
d) Radiant barrier installed 11 d. No e) Multizone heating credit
f) Programmable thermostat Yes
`Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature: Snezana Gurcinovska Date: 12./9/19
Address of New Home: LOT 42 BLK 01 -6426 Bradford Woods Drive City/FL Zip: , FL Zephryhills,FL,33542
12/9/20191:37:00 PM EnergyGauge®USA 6.0.04(Rev.1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
Load Short Form Date:'�- Wrightsof� Date:_ FQb.26,2019
Entire House By:
Mario's Air Conditioning and Heating Inc.
9213 Denton Ave,Hudson,FL34667 Phone:727-843-9598 Fax:727-645-6957 Email:info@mariosac.com Web:www.mariosac.com
Project • •
For: HIGHGATE, PULTE HOMES
LOT 42 BLK 02
Design Information
Htg Clg Infiltration
Outside db (6F) 43 91 Method Simplified
Inside db(°F) 70 75 Construction quality Semi-tight. .
Design TD (°F) 27 16 Fireplaces 0
Daily range - . L
Inside humidity (%) 50 55
Moisture difference (gr/lb) 22 47
HEATING EQUIPMENT COOLING EQUIPMENT
Make Lennox . Make . Lennox
Trade LENNOX Trade LENNOX
Model 14HPX-030-230-22 . Cond 14HPX-030-230-22
AHRI ref 201928156 - Coil CBA27UHE-030-230*++TDR
AHRI ref 201928156
Efficiency 8.5 HSPF Efficiency 13.0 EER, 15 SEER
Heating input Sensible cooling 24000 Btuh
Heating output 26000 Btu @ 47-F Latent cooling 6000 Btuh
Temperature rise 25 °F Total cooling 30000 Btuh
Actual air flow 946' cfm Actual air flow 946 cfm
Air flow factor 0.049 cfm/Btuh Air flow factor 0.039 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.88
Capacity balance point=35°F
Backup:
Input= 0 kW Output= 0 Btuh 100 AFUE
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF'
(ftz) (Btuh) (Btuh) (cfm) (cfm) .
OWNERS 224 3097 3913 150 153
O.BTH 120 1198 745 58 29
WIC 56 - 61 115 3 4
BED4 121 1536 1580 75 62
LAUND 49 54 .691 3 27
FOYER 7,5 1110 - 1009 54 39
LIVING 763 . 7455 11285 362 441
BED 137 1228 1126 60 44
BA2 50 485 .287 24 11
BED2 184 3276 3467 159 135.
BoldNtallc values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
,� -wright�oft' zols Deo-os 13.16.15
Right-Suite®Universal 2018.18.0.32 RSU1 8255 Page
...eDrive\PuRe HomesXLOAD CALC-FILESIHIGHGATE.rup Calc'=MJ8 Front Door faces:NW
Entire House d 1779 19500 24217 946. 946
Other equip loads 0 0
Equip. @ 0.96 RSM 23346
Latent cooling 3353
TOTALS I 1779 I 19500 I 26699 I 946 I 946
i
BoldQtalic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsofth 2019-Dec-09 13:16:15..
...,�.,,. ...;,�.gr., Right-Suite®Universal 2018 18.0.32 RSU18255
Page 2
/n+ ...eDrive\PuRe Homes\LOAD CALC FILES\HIGHGATE.rup Calc=MJ8 Front Door faces:NW
° Job:
Wf Ightso Duct S�/St@IYl SUIY11Y1117/ Date:.: Feb,26,2019
,Entire House By:
a
Mario's Air Conditioning and Heating-Inc.
9213 Denton Ave,Hudson,FL-34667 Phone:727-843-9598,Fax:727-645-6957 Email:info@mariosac.com Web:www.mariosac.com
Project Information
For: HIGHGATE,PULTE HOMES
LOT 42 BLK 02
i
Heating Cooling
External static pressure 0.50 In H2O 0.50 -in H2O
Pressure losses 0.22 in H2O 0.22 in H2O
Available static pressure 0.28 in H2O 0.28- in H2O
Supply:/return available pressure. 0.140/0.140 in H2O 0.140/0.140 in H2O
.Lowest friction rate 0.152 in/100ft 01.152 in/.100ft
Actual air flow - 946 cfm 946 cfm
Total effective length (TEL) . 184 ft
SupplyDetail Table
Design Htg Clg Design Diam H x W Duct -Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln (ft) Ln (ft) Trunk
BA2
h 485 24 11 0.162 4.0 Ox 0. VIFx 53.3 120.0 st2
BED _ h 1228 60 .44 . 0.175 5.0 Ox 0 VIFx . 44.7 115.0 st2
BED2 h 3276. 159 135 0.152 8.0 Ox 0 VIFx .: 64.4 120.0 st2
13ED4 h 1536 75 62 .0.170 6.0 Ox 0 VIFx 34.5 130.0 st1
FOYER h 1110 54 39 0.175 5.0 Ox 0: VIFx 44.6 115.0 st2
LAUND c 691 3 27 0.167 -4.0 Ox 0 VIFx 37.8 130.0 . st1
LIVING. c 3763. 121 :147 0.170 7:0 Ox 0 VIFx 44.6 120.0 st2
LIVING-A c 3762 121 147 0.188 . 7.0 Ox 0 VIFx 33.8 115:0 st2
LIVING-B c 3762 121 147 0.183 7.0 Ox0_ -VIFx 378 -115.0 st2
O.BTH h 1198 .58 29 0:168 5.0 Ox,O VIFx 36:9 130.0 st1 .
OMERS c '.3913 150 1.53 0.167 8.0 Ox0 VIFx 37.3 130.0 st1
`Mc. c 115 3 4 1 0 0 Ox 0 VIFx - 0 .0.
SupplyDetail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) -(cfm) FIR (fpm) .(in) (in)i Material . Trunk
st2 Peak AVF 658_ . 671 0.152 _ 480 16.0 0 x 0 VinlFlx
st1 Peak AVF 285 271 0.167 523 10.0- . :: 0 x 0 VinlFlx .
i
i
BoldRtalic.values have been manually overridden
.p wri,ghtsofv 2019-Dec-0913:16:15
!"�+`� Right-Suit Universal 2018 18.0.32 RSU18255 Pagel.
: ...eDdve\Pulte Homes\LOAD CALC FILES\HIGHGATE.rup Calc=MJ8 Front Door faces:NW
TableReturn Branch Detail
Grille Htg - Clg TEL Design Veloc Diam. H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Matl Trunk
rb1 Ox 0 946 - 946 0 0 0 0 Ox 0 VIFx.
i
i
I
AQ -�-wrilghtsoft' 2019-Dec-09'13:16:15
Right-Suite®Universal 201818.0.32 RSU18255 Page
eDrive\Pu@e Homes\LOAD CALC FILES\HIGHGATE.rup Calc=MJ8 Front Door faces:NW
i
- - wrightsoft" Manual S Compliance Report Date: Feb 26,2019
Entire House By:
Mario's Air Conditioning and Heating Inc.
9213 Denton Ave,Hudson,FL 34667 Phone:727-843-9598 Fax:727-645-6957 Email:info@mariosac.com Web:www.mariosac.com j
Project,
• •
For: HIGHGATE, PULTE HOMES
LOT 42 BLK 02 .
Cooling Equipment
.Design Conditions
Outdoor design DB: 91.4°F Sensible gain: 24217 . Btuh Entering coil DB: 75.0°F
Outdoor design WB: 77.2°F Latent gain: 3353 Btuh Entering coil WB: 64.0°F
Indoor design DB:. 75.07 Total gain: 27571 Btuh
Indoor RH: 55% Estimated airflow: 946 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Lennox Model: 14HPX-030-230-22+CBA27UHE-030-230"++TDR
Actual airflow: 946 cfm
Sensible capacity: 25418 Btuh 105% of load
Latent capacity: 5551 Btuh 166% of load
Total capacity: 30969 Btuh 1121/o of load SHR: 82%
Heating Equipment
Design.Conditions
Outdoor design DB: 42.9°F Heat loss: 19500 Btuh Entering coil DB: 70.0°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Lennox Model: 14HPX-030-230-22+CBA27UHE-030-230*++TDR
Actual airflow: 946 -cfm
Output capacity: 26000 Btuh 133% of load Capacity balance: 35 °F
Supplemental heat required: 0 Btuh Economic balance: , -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 946 cfm
Output capacity: 0 - kW 0% of load Temp. rise: 0 °F
Meets all requirements of ACCA Manual_S.
-> - wrilghtsoftm 2019-Dee-09 13:16:15
„�^ ,. .•, ..m..., Rig ht-Suits@ Universal 2018 18.0.32 RSU18255 Page 1
A+�► ...eDrive\Pulte Homes\LOAD CALC FILES\HIGHGATE.rup Calc=MJ8 Front Door faces:NW