HomeMy WebLinkAbout147-85 Conditional Requirements-Bldgs. Over 30 ft. in HeightRESOLUTION NO. 147
A RESOLUTION OF THE CITY OF ZEPHYRHILLS ESTABLISHING
CONDITIONAL REQUIREMENTS FOR BUILDINGS OVER TWO
STORIES IN HEIGHT OR MORE THAN THIRTY (30) FEET IN
HEIGHT.
WHEREAS, the City of Zephyrhills owns and operates a
Municipal Fire Department, and
WHEREAS, the City of Zephyrhills recognizes that the
health and welfare of its citizens require additional
restrictions and requirements for high rise structures in
addition to the City of Zephyrhills adopted Building and
Fire Codes and State laws.
NOW, THEREFORE, BE IT RESOLVED, by the City of
Zephyrhills sitting in regular session that the following
shall be conditional requirements for high rise
structures (buildings over two stories or more and thirty
(30) feet in height); and the following additional
requirements shall apply for one through three story
buildings in height; where the adopted Bui1ding/Fire
Codes and State laws exceed the conditional requirements,
the more restrictive shall be followed.
I. Type III & VI construction shall not be used in
structures over two stones or thirty (30) feet in height
regardless of its occupancy classification.
II. Three Story Buildings - a maximum of 45 feet in
Hei ht. Regardless of the type of construction or its
occupancy classification:
(a) No structure shall be more than two stories or
a maximum of 30 feet in height unless the Zephyrhills
Fire Department has the manpower, apparatus, equipment,
water mains, and fire hydrants necessary to handle
emergencies in that particular structure(s).
(b) The buildings meets all the conditional
requirements for buildings three stories - a maximum of
45 feet in height.
9SI
III. Four and Five Story Buildings - a maximum of 60
- 75 feet in height. Regardless of the type of
construction or its occupancy classification:
(a) No structure shall be more than five stories -
a maximum of 75 feet in height.
(b) Four and five story buildings can be permitted
if the Zephyrhills Fire Department has the manpower,
apparatus, equipment, water mains, and fire hydrants
necessary to handle emergencies in that particular
structure(s).
(c) The Building meets a11 the conditional
requirements for buildings more than three stories.
IV. Conditional Requirements for Buildings Three
Stones - maximum of 45 feet in height.
(1) Full Automatic Sprinkler System as per NFPA 13
or NFPA 13D & SBC.
(a) Exception - Buildings three stories and a
maximum of 45 feet in height without interior halls or
corridors or stairs may be exempt from required sprinkler
protection if the guest areas, residential units, work
units, and office units have direct access to an exterior
non-combustible balcony or exit way that has a mim'mum of
two separate and remote exterior non-combustible stairs
that lead safely to the ground.
(b) Exception - Sprinkler heads may be omitted from
hazard areas when the hazard of water would create a
greater hazard than the hazard protected. These areas
shall be protected by Smoke/Heat Detectors and/or by
supression systems other than sprinkler heads.
(c) Exception - In Group R - Residential,
sprinklers may be omitted in closets 24 square feet or
less and in bathrooms 55 square feet or less.
2. Smoke Detectors - Single Station.
J
(a) All buildings regardless of the type of
construction or occupancy classification one through
three stories, not required to have an automatic fire
alarm system, shall have single station smoke/heat
detectors in all units.
(b) One every 30 feet of all hallways and corridors
or a part thereof.
(c) In every hazard area and unoccupied storage
areas.
(d), SBC -Group R . - .Residenti a1 occupancies shall
have smoke detectors for the deaf and hearing impaired in
multiple dwellings located in guest and living units and
in halls and corridors.
3. Standpipe - Wet.
(a) In all three story buildings with interior
halls, corridors, or stairs and in three story buildings
exempt from required automatic sprinklers that have any
single floor gross area of more than 3,000 square feet
shall have wet standpipe system as per NFPA 14.
(b) In three story buildings where full automatic
sprinklers are required, a Class I or Class III system
shall be installed and the sprinkler and standpipe system
may be combined.
(c) In three story buildings that are not required
to have full automatic sprinkler protection, a Class III
system shall in installed.
4. Types of Construction.
(a) Three story buildings that have full automatic
sprinklers shall be of Type I, Type II, Type IV, or Type
V construction. Three story buildings that are not fully
protected by automatic sprinklers shall be of Type I,
Type II, or Type IV construction.
5. Elevators - Firemen Service.
160
(a) All three story buildings with interior halls,
corridors, or stairs shall have at least one elevator
with full firemen emergency service.
6. Stairs & Stairwells.
(a) All three story buildings with interior stairs
and stairwells, the stairs and stairwells shall be of
non-combustible construction.
(b) The stairwell enclosure shall be of a minimum
of two hour fire rated.
(c) Doors from stairs on each floor will be a
minimum of "B" (1-1/2 hour) rated with automatic
closers.
7. Conditional Requirements for Buildin s
Four Story Buildings - a maximum of 60 feet in
height and Five Story Buildings - a maximum of
75 feet in height.
1. The Zephyrhills Fire Department shall have, or
pending delivery of, an aerial apparatus with a minimum
of 75 feet of verticle reach and the necessary manpower
to man it before a four or five story building can be
permitted.
2. Four story buildings shall be Type I, Type II,
or Type IV protected construction regardless of its
occupancy classification.
3. Five story buildings shall be Type I or Type II
construction regardless of its dassificatiori.
4. All four and five story buildings shall have
full automatic sprinkler system as per NFPA 13 with the
exceptions listed in IV, 1 (b) & (c).
5. Standpipe System - Wet.
(a) All four and five story buildings shall have a
wet standpipe system as per NFPA 14 and the SBC.
(b) Standpipe Systems shall be either Class I or
Class III and the Sprinkler and Standpipe may be
combined.
6. Automatic Fire Alarm; Supression System;
Smoke/Heat Detectors; Manual Pull Stations; and Visual
A1arms.
(a) All four and five story buildings shall have an
automatic fire alarm system.
(b) Smoke/Heat Detectors shall be located in each
unit, each guest and living unit, each hazard area, each
unoccupied storage area, and one for each 30 feet of
hallways and corridors or a part thereof.
(c) The automatic fire alarm, smoke/heat detectors,
manual pull stations, sprinkler systems and other types
of supression systems shall be tied into a central system
that when any part of the central system is activated, it
will sound an audible alarm in every portion of the
building and visual fire alarms will indicate an
emergency in all halls, corridors, and in all guest and
living units to notify the deaf and hearing impaired.
(d) The central fire alarm system shall be tied
into an announciator panel located in an area that would
be a normal entrance to the building by firefighters.
(e) All parts of the central system shall be
installed and maintained as per the NFPA number that
pertains t . that part and requirements of the SBC.
7. Elevators & Firemen Service.
(a) All four and five story buildings shall have
at least one elevator with full firemen service.
(b) Section 506.6 of the SBC shall apply to
elevators in four and five story buildings.
8. Stairs and Stairwells.
(a) A11 four and five story buildings of Group B -
Business, Group M - Merchantile, and Group R -
158
Residential shall have smoke proof enclosures as per SB
1104.5.
(b) All other four and five story buildings shall
comply with Section IV - 6a, 6b and 6c; stairs shall also
have automatic sprinkler protection.
9. Smoke Control. All four and five story
buildings regardless of the occupancy classification or
square footage shall comply with the SBC 506.5.
10. Standby Power and Light. All four and five
story buildings regardless of the occupancy
classification or square footage shall comply with the
SBC 506.7.
11. Exits - Doors Locking. All four and five story
buildings regardless of the occupancy classification or
square footage shall comply with the SBC 506.8 (a).
This Resolution shall become effective March 25,
1985, and shall remain in full effect and force until
modified by Resolution or Ordinance.