HomeMy WebLinkAbout21-1359 r
City of Zephyrhills PERMIT NUMBER
5335 Eighth Street
Zephyrhills, FL 33542 FIRE-001359-2021
Phone: (813)780-0020
Fax: (813)780-0021 Issue Date: 02/08/2021
Permit Type: Fire
Property Number Street Address
1126 21 0010 01200 0250 38112 15Th Avenue
Owner Information Permit Information Contractor Information
Name: MCALVANAH,TIMOTHY ANDREA, Permit Type:Fire Contractor: PASCO FIRE&SAFETY
ET AL Class of Work:Fire Suppression EQUIPMEN CO INC
Address: 38108 15Th Ave Building Valuation:$2,500.00
ZEPHYRHILLS,FL 33542 Electrical Valuation:
Phone: (937)489-1677 Mechanical Valuation: r,
Plumbing Valuation:
Total Valuation:$2,500.00 1l
Total Fees:$130.00
Amount Paid:$130.00
Date Paid:2/8/2021 10:09:42AM 1�
Project Description
SUPPRESSION INSTALLATION MEALS ON WHEEL
Application Fees
Fire Suppression Inspection $30.00 Suppression System Plan Review $50.00
Commercial Kitchen Hood/Ducts Exhaust $50.00
REINSPECTION FEES: (c)With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c)the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection,whichever is greater,for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
'Warning to owner:Your failure to record a notice of commencement may result in your paying twice for
improvements to your property.If you intend to obtain financing,consult with your lender or an attorney
before recording your notice of commencement."
Complete Plans,Specifications add fee Must Accompany Application.All work shall be performed in
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
L
C TRACTOR SIGNATURE PE IT OFFICE
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER
813ae0-0020 City of Zephyrhills Fre Fax-813-780-0021
Permit Application
Date Received
^.., _ - Phone Contact for Permit 17Z7 11
Owners Name 61045
o Aj 6P jF .1 Owners Phone Number 3 7 �9
Owners Address
Fee Simple Titleholder Name 4 A9W�L TitlaholderPhone Number
Fee Simple TifleholderAddress -
,_.—��„-.,.-.4t_
1<Y_.___.3'•.-.-.+.-,__i:s-�_:".�i�..'rr--..r+.�w S�:-..�..5'.......^..sc...:�..`x..1t_v1�-y' - '�' - " --xc a,S."t_^�;s- _..^'+^-_^�:'_`.r'4"_<..'^:sr,?r:y'_^.'-._��
Job Address 7 !�G ��� .y LG� 3�5�2 Lot#
Sub Division Parcel# 200'p7—
Bio-Hazard Waste Storage-ANNUAL F-1 Fumigation Tent
Comm Exhaust Kitchen Hood/Duct Hazardous.Material(Tier 11 or RQ Facl*)ANNUAL
Controlled Bum Hood Installation
Emergency Generator<30 kw LP/Natural Gas-Installatior
0 Emergency Generator>30 kw Q LP/Natural Gas-ANNUAL Sale
Fire Protection Maintenance-ANNUAL Q Pieces of Assembly-ANNUAL
❑® emi Q o er IS
Sprinkler ❑ ❑ ❑ Recreational Bum
44
Fire Alarm Ej ❑ ❑ ❑ Sparklers
Hood Cleaning ❑ ❑ ❑ Sprinkler System Installations
Hood Suppression ❑ ❑ ❑ Standpipes(Sprinkler Sys)
Fire Alarm Installation a Torch Roofingrrar Kettle
Fire Pumps o Waste Tire Storage ANNUAL
HFlammable Application-ANNUAL s� = Valuation of Project
Fuel Tanks
[� Other.
<_
Contractor F d/ O, /. Company
Signature Registered Y/N Fee Current -
Address A �2ig /7. L• License#
ELECTRICIAN Company
Signature Registered YIN Fee Current Y 7 N
Address License#
PLUMBER Company
Signature Registered Y/N Fee Current Y/N
Address License#
MECHANICAL Company -
Signature Registered Y/N Fee Current. Y IN
Address. License#
OTHER Company
Signature Registered Y/N tree Ctrrent Y/N .
Addressj License#'
Directions ,....__ .-.._
Fill out application completely.
Owner&Contractor sign back of application,notarized(Or,copy of signed contract with owner)
If over$2500.a Notice of Commencement is required(Mechanical work over$5000)
Supply two(2)sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel#-obtained from Property Tax Notice(httpJ/appraiser.pascogovcom)
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to"deed" restrictions"which
may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any applicable
deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or contractors
to undertake work, they may be required to be licensed'in accordance with state and local regulations. If the contractor is not
licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation under state law. If the
owner or intended contractor are uncertain as to what licensing requirements may apply for the intended work, they are advised
to contact the Pasco County Building Inspection Division—Licensing Section at 727-847-8009. Furthermore, if.the owner has
hired a contractor or contractors, he is advised to have the contractor(s) sign portions of the"contractor Block" of this application
for which they will be responsible. If you, as the owner sign as the contractor, that may be an indication that he is not properly
licensed and is not entitled to permitting privileges in Pasco County.
TRANSPORTATION IMPACTIUTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands that
Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings, change of use in
existing buildings, or expansion of existing buildings, as specified in Pasco County Ordinance number 89-07 and 90-07, as
amended. The undersigned also understands, that such fees, as may be due, will be identified at the time of permitting. It is
further understood that Transportation Impact Fees and Resource Recovery Fees must be paid prior to receiving a"certificate of
occupancy" or final power release. If the project does not involve a certificate of occupancy or final power release, the fees must
be paid prior to permit issuance. Furthermore, if Pasco: County Water/Sewer Impact fees are due, they must be paid prior to
permit issuance in accordance with applicable Pasco County ordinances.
CONSTRUCTION LIEN LAW(Chapter 713, Florida Statutes, as amended): If valuation of work is$2,500.00 or more, I certify
that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law—Homeowner's Protection Guide"
prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone other than the "owner", I
certify that I have obtained a copy of the above described document and promise in good faith to deliver it to the"owner" prior to
commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and that all work will be
done in compliance with all applicable laws regulating construction, zoning and land development. Application is hereby made
to obtain a permit to do work and installation as indicated. I certify that no work or installation has commenced prior to issuance
of a permit and that all work will be performed to meet!standards of all laws regulating construction, County and City codes,
zoning regulations, and land development regulations in the jurisdiction. I also certify that I understand that the regulations of
other government agencies may apply to the intended work, and that it is my responsibility to identify what actions I must take to
be in compliance. Such agencies include but are not limited to:
- Department of Environmental Protection-Cypress Bayheads, Wetland Areas and Environmentally Sensitive Lands,
Water/Wastewater Treatment.
- Southwest Florida Water Management District-Wells, Cypress Bayheads,Wetland Areas,Altering Watercourses.
- Army Corps of Engineers-Seawalls, Docks, Navigable Waterways.
- Department of Health & Rehabilitative Services/Environmental Health Unit-Wells, Wastewater Treatment, Septic
Tanks.
- US Environmental Protection Agency-Asbestos abatement.
- Federal Aviation Authority-Runways.
I understand that the following restrictions apply to the use of fill:
- Use of fill is not allowed in Flood Zone W" unless expressly permitted.
- If the fill material is to be used in Flood Zone "A", it is understood that a drainage plan addressing a "compensating
volume"will be submitted at time of permitting which is prepared by a professional engineer licensed by the State of
Florida.
- If the fill material is to be used in Flood Zone "A" in connection with a permitted building using stem wall
construction, I certify that fill will be used only to fill the area within the stem wall.
- If fill material is to be used in any area, I certify that use of such fill will not adversely affect adjacent properties. If
use of fill is found to adversely affect adjacent properties, the owner may be cited for violating the conditions of the
building permit issued under the attached permit application, for lots less than one (1)acre which are elevated by fill,
an engineered drainage plan is required.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in this
affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work, plumbing,
signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A permit issued shall
be construed to be a license to proceed with the work and not as authority to violate, cancel, alter, or set aside any provisions of
the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter requiring a correction of errors in
plans, construction or violations of any codes. Every permit issued shall become invalid unless the work authorized by such
permit is commenced within six months of permit issuance, or if work authorized by the permit is suspended or abandoned for a
period of six (6) months after the time the work is commenced. An extension may be requested, in writing, from the Building
Official for a period not to exceed ninety (90) days and 'will demonstrate justifiable cause for the extension. If work ceases for
ninety(90)consecutive days, the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING
TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR
LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
FLORIDA JURAT(F.S.117.03)
AOWNER OR AGENT CONTRACTOR
Subscribed and swog►,to(or affirmed)ref a me this Subscribed and sworn to(or affirrt}ed)pefgres�s
1�►I--;,nd by N\%C�P.` Y `51-,2swn 1 L751-"2( by M tCJItitKX �,�ic_ GYYI
o War personally known to me or has/have produced Who is/are personally known to me or has/have produced
_T, :3 1 Cf, S 6 7, as identification. C 1. r_fS V a �(�4�as identification.
Hog b
(LLA-A a Z Notary Public _`//-- Notary Public
C mission No. G Z 3 0-7 3 10 C mmission No. ( 'n 3 (�
Name of Notary typed,printed or stamped Name of Notary typed,printed or stamped
Susan Albanese Susan Albanese
Notary Public,State of Florida Su Su Public
My Commission #GG230736 Notary , State of Florida
Expires June 23, 2022 My Commission # GG230736
Bonded thru CNA SURETY Expires June 23, 2022
Bonded thru CNA SURETY
PASCO"FIRE=AN-0-SAFETY
.f
IPMENT Co.
EQU � ,�
Your Preferred Safety Supplier
Meals On Wheels
38112 15' Ave.
Zephyrhills F1. 33542
Install 1 Protex L3000 (UL 300)Fire Suppression System
Hazard Nozzle Flow# Total flow points
1Hood 8' 1-111 leach 1
1Duct 1-21) 2each 2
2Stove s 2-111 and 2-2L 6
1-L3000, 10 Flow points max Total needed 8
At System Discharge: Gas Off,Makeup air Off, Exhaust fan On,Bell On
1-2D
O Bell
❑ 1-1H
L3000
1-2L 14H 1-2L 1-lH
y8
Pull Station
Gas Valve
2-36"x24"6 Burner Stoves
Tf
K Class
REVIEW DATE i +
CITY OF ZEPHYR ILLS
®=Fuse link FIRE AND LIFE SAFETY EXAMINE
=Nozzle
ALL WORK SHALL COMPLY WITH
NFFA CODES AND STANDARDS
Pasco Fire and Safety 18820 Sakera Rd (727) 862-5045 mike@pascofiresafety.com
Equipment Co Inc Hudson,FL 34667 (352) 686-7922 www.pascofiresafety.com
Design Index Chart and Nozzle Coverage Summary Sheet
Min Max Max Max Max Nozzle Nozzle v
Nozzle Flow Depth Length Area Height Height Volume Chart .
Appliance Mount Figure Type Points Max Width(in) (in) (in) 00 (in) (in) -
Fryers w/out Drip Board .H 3-3 NL2H 2 19-A 19 24 48 1/4n pipe=20.5 m1s./ft.
Fryers w/out Drip Board L 3.4 NL2L 2 19-h 19 13 24
Fryers w/Drip Board H . 375 NL2H 2 Deep Vat 27% 324 24 48 Na"pipe=37.5 mis./ft.
(Condition 1) Overall Cooking Area _ 18 500 24 48 1/2n pipe=59.8 m1s./ft.
Fryers w/Drip Board H 3-5 NL2H 2 Deep Vat 191A 371 24 48 3/"pipe= 105.0 m1s./ft. .
(Condition 2) Overall Cooking Area 25% 495 24 48 '
Fryersw/Drip Board L 3-5 NL2L 2 Deep Vat 18 324 13 24 For more'Pipe Volume data,see page 59
(Condition I) Overall Cooking Area 27% 500 13 24
Fryersw/Drip Board L 3.5 NL2L 2 Deep Vat 1%6 371 13 24 Agent Distribution-Hose=300 ml/hose
(Condition 2) Overall Cooking Area 25% 495 13 24
Tilt Skillet/Braising Pan H 3-7 NL2H 2 27% 560 24 48
Tilt Skillet/Braising Pan L 3-8 NL2L 2 273Y, 500 13 24
j&all Range H 3-9 NLIH 1 12 28 336 40 5o CYLINDER CHART
fj.L�trge Range N/A 3-10 NL2L 2 28 28 784 34 48
Maximum Maximum Volume
Small Range w/Backshelf L 3-11 NLIL 1 12 28 336 13 24
Protection Maximum Pipe Allowed Between
Small Range w/Backshelf H 3-116 NL2L 2 12 28 336 24 35 Flow Volume First Nozzle&Last
Protection Cylinder Size Numbers (milliliters) Nozzle(milliliters)
Small Wok H 3-12 NLIH 1 24 Diameter Max. .6 24 48
Small Wok L 3.13 NLIL 1 24 Diameter Max. 6 '13 24 1.6 Gallon 5 1500 600
Large Wok H 3-14 NL2H 2 30 Diameter Max, 8 24 48 L1600
Large Wok L 3-15 NL2L 2 30 Diameter Max. 8 13 24
Small Griddle H 3-16 NLIH 1 36 _1080 24 48 3.o Gallon 10 1910 1125
Small Griddle L 3-17a NLIL 1 36 1080 10 24 L300o
Small Griddle L 3-17b NL2L 2 36 1080 13 24
Large Griddle H 3-I8 NL2H 2 48 1440 24 48 `4.6 Gallon 14 3400 3000
Large Griddle L 3-19 NL2L 2 48 1440 10 24 L4600 '
Radiant Char-Broiler H 3-20 NLIH 1 26 624 24 48
Radiant Char-Broiler L 3-21 NLIL 1 26 624 13 24 4.6 Gallon 15 2600 2000
Large Radiant Char-Broiler H 3-22 NL2H 2 36 864 36 48 L4600
Large Radiant Char-Broiler L 3.23 NL2L 2 36 864 13 36 6.o Gallon 19 4215 1688/side
Lava Rock Char-Broiler H 3-24 NL2L 2 26 624 24 35
Lava Rock Char-Broiler L 3.25 NL2L 2 26 624 15 24 L6000
Solid Fuel Char-Broiler H 3-26 NLIH 1 24 480 24 35
6.o Gallon 20 3465 1313/side
(max.fuel depth 6)
Solid Fuel Char-Broiler L 3-27 NLIL 1 24 480 15 24 L6000
Salamander Broiler N/A 3.30a NLIH 1 31 1% 16 is *All piping,including nozzle drops,must be included in the
Upright/Salamander Broiler N/A 3-30b NLIL 1 36 28 Front Edge
above the grate piping calculations
Hearty Penny Fryer Mono Rail N/A 3.31 NL2H 2+2 See Special Instructions
+NL2F
Henny Penny Fryer Dual Lift N/A 3-32- NL2H 2+2 See Special instructions
+NL2F
Niece Broiler ModelMPB N/A 3-33 NL2L 2 See Special instructions MINIMUM PIPE VOLUMES FORA
with Catalyst only .
FRYER,RANGE,AND WOK
Niece Broiler Model IF94B N/A 3-34 NL2H 2 See Special Instructions
Electric Broiler with Catalyst Cylinder
Bakers Pride Broiler N/A 3-35 NL2H 2+2+2 See Special Instructions 33 35 ,
with Smoker Box Size Entire System At or before appliance
Chain Broiler(internal Chamber) N/A 3-31 NLIL I 38 Front Edge I'-3'
above the drain L1600 239 ml-1 Flow Pt 18o ml-1 Flow Pt
num Single Bank/VBank H NLIH I 48 120 0-6"from end of L30oo 300 Jul—4 Flow Pts 239 ml—2 Flow Pts
plenum
Duct Perlin Diameter L4600 66o ml—lo Flow Pts 18o ml-2 Flow Pts
$Mctangular/Circular Duct NL2D 2 34 no limit 100 31%
Rectangular/Circular Duct NLIL I .17 50 16 L600o 960 m1-14 Flow Pts 120 ml-2 Flow Pts
2015-DEC-1,Rev D
UL EX4521 17 Part A PMAN2
Chapter 1—General Information
C
CHAPTER I
-. GENERAL INFORMATION
INTRODUCTION The shutdown of all soutanes of fuel and electric power that produce
This manual is intended for use with ProTex Er Restaurant Fire heat to all equipment protected by the system is required upon
Suppression Systems.Those who install,operate,recharge,or system actuation.Make up or supply air fans integral to the
maintain these fire suppression systems should read this entire eahanst hood(s)being protected,shall he shut down upon system
manual.Specific sections will he ofparticular interest depending actuation.Upon system actuation,exhaust fan operation shall be in
upon one's responsibilities, accordance with the locally adopted edition of NPPA 96.
Design,installation,recharge,and maintenance ofthe system must The ProTex 11 and the PwTex 2000 Restaurant Fire Suppression
conform to the limitations detailed in this manual and performed Systems are compatible as long as separate installation guidelines
by an individual who attended a ProTex II training Program and are followed per each system design manual.Exception:The-.
became trained to install,recharge,design,and maintain the actuation limitations for the ProTex U system may be utilized for
ProTex U system_ the FmTex2000system.AhA prior model mechawc;il control head
(PIN MCH)maybe utilized on ProTex 11 systems;provided that the
Firer suppression systems are mechanical devices,They need eons used with this control head are followed.
periodic rare.Maintenance is a vital step in the performance
ofyour fire suppression system.As such,it must be performed *gEMPERATURE LIMITATIONS
in accordance with NFPA 96{Standard for the Installation of The operating temperature range of the PwTex H Restaurant Fire
Equipment for the Removal of Smoke and Grease-Laden Vapors Suppression System is 3r F{0-C)minimum to 120°F{49a C)
from Commensal Cooking Equipment)and NFPA 17A(Standard maximum.
on Wet Chemical Extinguishing Systems)by an authorized
ProTex U distributor_To provide maximum assurance that the fire "WLLISTING
suppression system will operate dlfectively and safidy,maintenance
must be conducted at six-month hftxvais,or earlier ifthe The ProTex U Restaurant Fire Suppression System has been tested
situation dictates.Wielve year maintenance must include cylinder to the UL Standard for Fire Extinguishing Systems For Protection
hydrostatic testing, of Restaurant Cooking Areas,ULMO and Listed by Underwriters
Laboratories,Inc. The UL Listing No.is EX452L
The ProTex 11 Restaurant Fire System is a pre-engineered system
that uses a wet chemical extinguishing agent specifically designed; !(ULC LISTING
to suppress restaurant cooking area fires.The system provides The ProTex U Restaurant Fire suppression system is listed by
automatic actuation and can be manually actuated through a. Underwriters Laboratories of Canada(ULC).The ULC Listing No
_ RPSM Remote Mechanical Pull Station.Upon actuation,the system is EX4521.
_ discharges a pre-determined amount of agent to the duct,plenum;
and cooking appliances.The extinguishing agent acts to suppress 1VIEA APPROVAL
fires in thre ways:
The PraTex U Restaurant Fine Suppression System has been
L The chemical chain reaction causing combustion is inter- approved for use by MEA(Material and Equipment Acceptance
= rupted by both the agent itself and the resulting steam Division)for New York City.The MEA Certification No.is
formation. 249-03-E.
2. The agent cools the fire bringing it below auto-ignition
temperature.
3. The agent reacts with hot grease forming a soap-like
1� layer(saponification)that helps prevent the escape of
combustible vapors,thus preventing re-ignition.
i�
200-DEC-1,Rev D
TU-a a ID"AWT'W