HomeMy WebLinkAbout21-1378 ' Cityof Ze h rhills
r p y PER,MiU NUMBER
5335 Eighth Street
Zephyrhills, FL 33542 FIRE-001378-2021
Phone: (813)780-0020
/- Fax: (813)780-0021 Issue Date: 01/25/2021
Permit Type: Fire
Property Number Street Address
35 25 210010 10500 0000 7050 Gall Boulevard
Owner Information Permit Information Contractor Information
Name: ADVENTIST HEALTH Permit Type:Fire Contractor: COX FIRE PROTECTION
SYSTEM/SUNBELT INC Class of Work:Sprinkler System
Address: 7050 Gall Blvd Building Valuation:$1,871.00
ZEPHYRHILLS,FL 33541-1347 Electrical Valuation:
Phone: (813)788-0411 Mechanical Valuation:
Plumbing Valuation: �vo- //11
Total Valuation:$1,871.00
Total Fees:$150.00 l ICn
Amount Paid:$150.00
Date Paid:1/25/2021 12:12:39PM
Project Description
INSTALLATION SPRINKLER SYSTEM
Application Fees
Sprinkler Permit Fee $50.00 Sprinkler System Plan Review $50.00
Fire Alarm Permit Fee(1-25) $50.00
REINSPECTION FEES: (c)With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c)the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection,whichever is greater,for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
"Warning to owner: Your failure to record a notice of commencement may result in your paying twice for
improvements to your property. If you intend to obtain financing,consult with your lender or an attorney
before recording your notice of commencement."
Complete Plans,Specifications add fee Must Accompany Application.All work shall be performed in
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
CONTRACTOR SIGNATURE : PE IT OFFICE
=- PERMIT EXPIRES-IN-61MO-NTHS WITHOUT APPROVED INSPECTIt3N
CALL FOR INSPECTION- -&-HOUR NOTICE REQUIRED" -------
PROTECT CARD FROM WEATHER
813-780-0020 City of Zephyrhills Fire Fax-813-780-0021
Date Received 01/19/2021 Permit ApplicationPhone Contact for Permit 813 980 3282
Owners Name Adventist Health System/Sunbelt Inc. Owners Phone Number
Owners Address 7050 Gall Blvd.,Zephyrhills,FL 33541-1347
Fee Simple Titleholder Name !Titleholder Phone Number
Fee Simple Titleholder Address
Job Address 7050 Gall Blvd.,Zephyrhills,FL 33514-1347 Lot#
I
Sub Division Parcel,# 35-25-21-0010-10500-0000
Bio-Hazard Waste Storage-ANNUAL 'Fumigation Tent
Comm Exhaust Kitchen Hood/Duct 'Hazardous Material(Tier II or RQ Facility)ANNUAL
Controlled Bum Hood Installation
Emergency Generator<30 kw LP/Natural Gas-Installation
Emergency Generator>30 kw LP/Natural Gas-ANNUAL Sale
Fire Protection Maintenance-ANNUAL Places of Assembly-ANNUAL
®y emi ®n er
Sprinkler 0 ❑ ❑ ❑ ® Recreational Bum
Fire Alarm ❑ ❑ ❑ Sparkle
Hood Cleaning ❑ ❑ ❑ Sprinkler System Installations
Hood Suppression El ❑ ❑ ❑ Stand i e r Sys) V
Fire Alarm Installation Torch Roofing/rar Kettle
Fire Pumps Waste Tire Storage ANNUAL
Fire Works
Fj Flammable Application-ANNUAL $1,871 Valuation of Project
Fuel Tanks
Q Other:
Contractor Company
Signature Registered Y/N Fee Current Y/N
Address License#
ELECTRICIAN Company
Signature I Registered Y/N Fee Current Y/N
Address License#
J
PLUMBER Company
Signature Registered Y/N Fee Current Y/N
Address License#
MECHANICAL Company
Signature Registered Y/N Fee Current Y/N
Address License#
OTHER Q ", Company Cox Fire Protection, Inc.
Signature ir(i/'<c�v Registered I Y/N Fee Current
Address 7910 Professional Place,Tampa, FL 33637 License# FPC14-000005
Directions:
Fill out application completely.
Owner&Contractor sign back of application,notarized(Or,copy of signed contract with owner)
If over$2500,a Notice of Commencement is required(Mechanical work over$5000)
Supply two(2)sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel#-obtained from Property Tax Notice(http://appraiser.pascogov.com)
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to"deed" restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or
contractors to undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building ,Inspection Division—Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW(Chapter 713, Florida Statutes, as amended): If valuation of work is$2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law—Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the"owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the"owner" prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable laws regulating construction, zoning and land
development. Application is hereby made to obtain a permit to do work and installation as indicated. I certify
that no work or installation has commenced prior to issuance of a permit and that all work will be performed to
meet standards of all laws regulating construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. I also certify that I understand that the regulations of other
government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate, cancel, alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six (6) months after the time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and will demonstrate
justifiable cause for the extension. If work ceases for ninety(90) consecutive days,the job is considered abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
FLORIDA JURAT(F.S.117.03)
OWNER OR AGENT CONTRACTOR l� nG:�/L�/( /. ( f�'—
Subscribed and sworn to(or affirmed)before me this Subscribed and sworn to(or affirmed)before me this '
by 01/19/2021 by Sandra C.Cress
Who is/are personally known to me or has/have produced Who is/are personally known to me or has/have produced
as identification. as identification.
I
Notary Public Notary Public
Commission No. Commission No. GG210684
Nicole Barton cauwr�E�, kiirnlaaRnrton
Name of Notary typed,printed or stamped Name of Notary typed,printej,or.s16_6q d•
Bonded T hr u Aaron Nota:r
i
FIRE C 7910 PROFESSIONAL PLACE_ PROTECTION TAMPA,FLORIDA
PHONE:(813)980-3282
FAX:(813)980.0631
WEB:COXFIRE.COM
August 27,2019
Interior Enterprises
23544 Sierra Rd.
Land O' Lakes, FL. 34639
Phone: 813-380-5353
Attn: Dan Monaghan
Re:AH Zephyrhills USP 800
I am pleased to provide you with the following proposal in the amount of-
ONE THOUSAND EIGHT HUNDRED SEVENTY-ONE DOLLARS-$1,871.00
1 am pleased to provide you with the following proposal for the modification of the existing wet type system within
the proposed space to accommodate the new floor and ceiling plan in accordance with the plans and specifications
provided. THREE(3)sprinklers are to be added or relocated to protect the proposed space using new sprinkler
heads.•
ADD ALTERNATE:Turn heads up for temporary protection during construction. $400.00
This proposal includes all necessary labor,materials,equipment,permit fees,and applicable sales taxes to perform the
work as it is described above.
We are excluding the following:
1. Painting of pipe
2. Electrical wiring of any kind
3. Fire Extinguishers
4. Painting or patching of ceilings
5. Payment and performance bond (Available upon request)
6. Any other wet or dry type fire protection work not specifically listed above
7. Fire Watch
8. BIM Design
Should you have any questions regarding the above,or require additional information,please do not hesitate to
contact me at(813)980-3282x117.
COX FIRE PROTECTION,INC CU (MEERR
'jlla�r(_7nGu�Pe "�C� -
Slgnature slgneture /Owner's Rep
Mark.Trimble'/service Sales
Print Name and Title Print Name and Title
7910 PROFESSIONAL PLACE;TAMPA,FLORIDA 33637 PHONE:(813)980-3282 1 FAX:(813)980-0631 WWW.COXFIRE.COM
Q
To: 0137800021 From: 3525450091 1-25-21 10:07am p. 2 of 2
LA -K-T N
iSERVlCES.LLC
14 t 30 SEVENTH STREET.DADE CITY.Ft_33525
P(352)545.00500 F(352)5415.009 t
INFO WLARKINWLEXOI"
1
PERMIT SEARCH
Property Information:
Owner of Record: C _ An+
Street Address:
Parcel ID: b_) t CA _Q[ '„ 1 tl50
, 13 p--�p�fl �t �,� ®u�" 2- %inn -C 114
5'J F
pen permits on this property 1
[]All permits closed/completed
Please complete the above search and return via email- If you need additional
information to complete the request please contact our office.
Ij - -
f
To: 8137800021 From: 3525450091 1-25-21 10:07am p. 1 of 2
LAR- q �N
_ -- LE SERVICES,LLC
MKIN&MKIN TITLE SERVICES,u.0
14130 r Street—Dade City,Ft 33525
352.545.0090 1352,545.0091
www.larkintitio.com
fax
To: Building Department FROM: Jordan Allison
FAX: PAGES: rr�� +•�
PHONE: DATE: ` t S• C�0+�
RE: Permit Search CC:
Urgent For Review Please Comment Please Reply Please Recycle
Comments: Please process the attached permit search and return to jordanA Iarkintitle.com.
Thank you I
C _ FIRE 7910 PROFESSIONAL PLACE
)X PROTECTION TAMPA,FLORIDA33637
PHONE:(813)980-3282
FAX:(813)980-0631
WEB:COXFIRE.COM
AH Zephyrhills USP 800
1-2-3471-10-20
FIRE SPRINKLER
Product Data
SUBMITTED: 11/17/2020
7910 PROFESSIONAL PLACE;TAMPA,FLORIDA 33637 1 PHONE:(813)980-3282 1 FAX:(813)980-0631 WWW.COXF[RE.COM
Table of Contents
AH Zephyrhills USP 800
1-2-3471-10-20
SPRINKLERS: VIKING VK462 CONCEALED PENDENT SPRINKLER HEADS
PIPE: SCHEDULE 10/SCHEDULE 40 BLACK STEEL PIPE
FITTINGS: BLACK DUCTILE IRON FITTINGS
GROOVED FITTINGS
GROOVED COUPLINGS
HANGERS: LISTED HANGER RINGS
LISTED ALL THREAD ROD
LISTED BEAM CLAMPS
LISTED CONCRETE HANGER
*ALL PRODUCTS USED ARE U.L. LISTED AND/OR F.M. APPROVED
FOR USE IN FIRE SPRINKLERS SYSTEMS
January 27, 2012 Sprinkler 54a
MIRAGE®STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-pro-
file cover assembly that provides up to%' (12.7 mm)of vertical adjustment.The two-
piece design allows installation and testing of the sprinkler prior to installation of the
cover plate.The"push-on", "thread-off'design of the concealed cover plate assembly .
allows easy installation of the cover plate after the system has been tested and the
ceiling finish has been applied. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out
of service or removing the sprinkler.
2. LISTINGS AND APPROVALS
A1 us cULus Listed: Category VNIV
FM FM Approval: Class 2015
vds NYC Approved: MEA 89-92-E,Volume 32
VdS Approved: Certificate G4080021
� LPCB Approved: Ref. No. 096e/12
E CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032
Refer to Approval Chart 1 on page 54c and Design Criteria on page 54d for cULus Listing requirements, and refer to
Approval Chart 2 and Design Criteria on page 54e for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum
7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP)sprinklers can be identified by
locating "250"stamped on the deflector.Sprinkler VK462 is rated to a maximum 175 psi(12 bar)wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metrict)
Glass-bulb fluid temperature rated to-65°F(-55*C)
Patents Pending
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi(0.35 bar).
tMetric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-Cl9500 for Sprinkler VK462 Viking Technical Data may be found on
Phosphor Bronze UNS-051000 for Sprinkler VK463 The Viking Corporation's Web site at
Deflector Pins: Stainless Steel Alloy hftp://Www.vikinggroupinc.com.
Bulb: Glass, nominal 3 mm diameter P clude aimore r.
The Web site may include a more recent
Pip Cap and Insert Assembly: Copper UNS-Cl1000 and Stainless Steel edition of this Technical Data Page.
UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze UNS-051000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Form No. F_103005 Replaces page 54a-f, dated April 8, 2011.
(Revised VdS Approval.)
Sprinkler 54b January 27, 2012
® MIRAGE®STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K6.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
Cover Assembly Materials:
Cover: Copper UNS-C11000
Base: Brass UNS-C26000 or UNS-C26800
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information:(Also refer to the current Viking price list.)
Viking Mirage®Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
Sprinkler: Base Part No. 13503A or HP Base Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:
Temperature Suffix: 155°F(68°C)=B, 175°F(79°C)= D, 200°F(93°C) = E
For example, sprinkler VK463 with a 155°F(68°C)temperature rating= 13667AB.
Cover Plate Assembly:Base Part No. 13504(2-3/4"diameter), Base Part No. 13642(3-5/16"diameter),or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B4B,
Brushed Copper=E413, Painted White=M-NV, Painted Ivory=M-/I, Painted Black=M413
Temperature Suffix: 135°F(57°C) UL(139°F(59°C) FM and LPCB)=A, 165°F(74°C)= C
For example, cover 13504 with a Polished Chrome finish and a 165°F(74°C)temperature rating= 13504FC.
Note:Square cover plate 15394 cULus Listing is for the 135°F(57°C)temperature rated cover plate only.Refer to the Approval Chart.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the"Sprinkler Accessories"section of the Viking data book.)
Sprinkler Wrenches':
A. Heavy Duty Wrench Part No. 14047W/B(available since 2006), or
B. Head Cabinet Wrench Part No. 14031***(available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover
(available since 2007)
—Requires a''/z'ratchet(not available from Viking).—Optional for removal of the protective cap.Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A(available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
6. OPERATION
During fire conditions,when the temperature around the sprinkler approaches its operating temperature,the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly.Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
January 27, 2012 Sprinkler 54c
® MIRAGE® STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP I Kj NKA; SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS ■ FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum,Ambient Temperature Rating of Cover
f Bulb Color
10WClassification_:. Tem eraturet.atin ? �_Ceilin Lem erature? _ Assembl _ Re uiced
_,.�__._-....... _a. _._ ......_.��.____.�__ �._._-._.._ _.vw
Ordinary 155°F(68° C) 100°F (38-C) 135°F(57°C)cULus Red
139°F(59°C) FM and LPCB
Intermediate 175-F(79°C) 150-F(65°C) 165°F (74°C) Yellow
Intermediate 200-F(93 °C) 150-F(65°C) 165°F (74-C) Green
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Footnotes
'The sprinkler temperature rating is stamped on the sprinkler deflector.
?Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
Ap,proual Chart 1 (+U OWING AL� Spdnklwe�erTe�rnpeiatua a'tlng
-min
Nall
Cover Plata Temperature RatingMirage C�oncealetl Pendent�Sprinklerrs V 2 and fC463 Cover+e�te Fnien KEY
NPT Thread Nominal Maximum Listings and Approvals"
Sprinkler 1 SIN Size K-Factor Water Working (Refer also to Design Criteria on page 54d.)
Base Part No. Inch mm U.S. metric? Pressure cULus' NYC VdS' LPCB E
Standard Response Applications
13503A VK462 1/2" 15 5.6 80.6 1 175 psi(12 bar) I -- -- AY1,CZ1 AY1,BZ1 AY1,CZ1'
Quick Response Applications
13503A VK462 1/2" 15 5.6 80.6 175 psi(12 bar) AV1, BX1 AV1,BW16 — — -
13667A VK463 1/2"' 15 5.6 80.6 1 250 psi 17.2 bar 3 AV1,BX1 AV1,BW16 -- -
Cover Plate Assembly Temperature Ratings' Cover Plate AssemblyFinishes"
Sprinkler Temperature Ratings V- 135°F (57 °C)cULus Listed cover 135041, 136421 (large diam-
eter),or 153941(square cover plate) 1- Polished Chrome,Brushed Chrome,
A-155°F(68°C) W-165°F(74°C)cover 135041 or 136421 (large diameter) Bright Brass, Antique Brass,
B-175°F(79°C)and 200°F(93°C) X-165°F(74°C)cover 135041,or 136421 (large diameter) Brushed Brass, Brushed Copper,
C-200°F(93°C) Y-135°F(57°C)cover 135041 LPCB Approved as 139°F(59°C) Painted White, Painted Ivory, or
Z-165°F(74°C)cover 135041 Painted Black
Footnotes
1 Part number shown is the base part number.For complete part number,refer to current Viking price list schedule.
?Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa, divide the metric K-factor shown b
10.0.
3 The Water Working Pressure rating is stamped on the deflector.
"This chart shows the listings and approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for an
additional approvals.
6 Listed by Underwriter's Laboratories for use in the U.S.and Canada.
6 Accepted for use,City of New York Department of Buildings,MEA Number 89-92-E,Vol.32.
'VdS Approved,standards VdS 2344:2005-12,VdS 2100-25:2008-01,and EN 12259-1:1999+A1:2001 +A2:2004+A3:2006,Certificate G4080021.
6((Certified,Standard EN 12259-1,EC-certificate of conformity 0832-CPD-2032.
'The 135/139°F cover has an orange label.The 165°F(74°C)cover has a white label.
1OPainted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer.Contact Viking for additional information.
NOTE:Custom colors are indicated on a label inside the cover assembly.Refer to Figure 1.
Sprinkler 54d January 27, 2012
® MIRAGE®STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP I KJ:N:GSPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
DESIGN CRITiERIA- UL
(&I Lol refer to Approval Krart 1 on page 54c.)
cULus Listing Requirements:
Mirage®Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
• For hazard occupancies up to and including Ordinary Hazard,Group II.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.Maximum spacing allowed is 15 ft.(4.6 m).
• Minimum spacing allowed is 6 ft.(1.8 m)unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in.(102 mm).
• Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
NOTE:Concealed sprinklers must be installed in neutral or negative pressure plenums only.
VdS Approval Requirements:
a)The sprinkler can be installed in a concrete ceiling(massive ceiling)or in a false ceiling made of light materials.
b)This sprinkler is deflector fixed type and can be only activated by heat.The housing is not tight.
c)Follow installation guidelines of current standards,CEA4001VdS and EN12845.These sprinklers can only be installed in LH and OH occupan-
cies,except in OH4.
NOTES: Due to the design the sprinkler type'Domed-CCP'shall not be installed in false ceilings in which the false ceiling space is protected by a
water extinguishing system.
Due to the design the sprinkler type'Domed-CCP'shall not be installed in false ceilings in which during a fire the pressure above the false ceiling
may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
1. Prepare the sprinkler key.
2. Remove the plastic cover.
3. Hold the sprinkler with the wrench and fasten it.
4. Replace the plastic cover and do not remove until the cover is installed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 -Care and Handling of Sprinklers.Also refer to page
SR1-3 or QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, LPCB,APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-
dards,whenever applicable.
CUSTo/J D❑ NOT PAINT
Q� 9f
o c�
�— O
J �
VIIdNG ��
Identification of Custom Paint Colors
All custom color painted cover plates will
have an identifying label affixed to the
inside of the cover that Indicates custom
color and will have a representative sample 3-5/16" (84.1 mIn)�
(a paint dot) of the paint on the label.
Figure 1: Identification of Custom Paint Color for Concealed Covers Figure 2: Square Cover Assembly 15394
January 27, 2012 Sprinkler 54e
® MIRAGE®STANDARD AND
QR CONCEALED PENDENT
A 1A A KjSPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
A . �"1' S dnldAAAerTem eratureRe`U-
pproval Chart 2 (FMI)" Cover Plate Temperature Raerg
Mirage®Standard Response=Concealed Pendent Sprinkler GK462 AWAwer Plate Flnlsn KEY,
i4+'! ,.ffi �f3k: s_:x -.ff. -
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum FM Approvals'
Part No.' SIN Water Working (Refer also to Design Criteria below.)
Inch mm U.S. metd& Pressure
13503A VK462 1/2" 15 5.6 80.6 175 psi(12 bar) AW1,BX1
Cover Plate Assembly Temperature Ratings° Cover Plate Assembly Finishes-'
Sprinkler Temperature Ratings W- 139 OF(59°C) cover 135041, 136421 (large diameter), 1 -Polished Chrome, Brushed Chrome, Bright
A-165 OF(68°C) or 153941 (square cover plate) Brass, Antique Brass, Brushed Brass,
B-175 OF(79°C)and 200 OF(93°C) X-165 OF(74°C)cover 135041,136421(large diameter),or Brushed Copper, Painted White, Painted
153941 (square cover plate) Ivory,or Painted Black
Footnotes
1 Part number shown is the base part number.For complete part number,refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
3 This chart shows the FM Approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any additional
approvals.
4 The 139 OF(59°C)cover has an orange label.The 165 OF(74°C)cover has a white label.
-' Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer.Contact Viking for additional information.
NOTE:Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DE$IGNa RIVERIA
i
(Also refe`rAo.App o aEChartZabm
i,:..a�+n;. <t�.. ..•ra:en.fw,xsxr:.�.'v"^';�i:�.sx
FM Approval Requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM
Approval Guide.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling.
NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers.Also refer to page
SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD,VdS or other similar organizations,and also with the provisions of governmental codes,ordinances,and
standards,whenever applicable.
Sprinkler 54f January 27, 2012
® MIRAGE® STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com
Sprinkler
Wrench
Sprinkler >�p Flat
2-1/4' (57.2 mm) Frame
diameter opening Arms
Is required In
the ceiling.
Sprinkler and —
Adapter Assembly
(Protective Cap
Is removed for INK
installation--use
Wrench 14031)Kx) ILL= LS
NEVER install the sprinkler
by applying the installation
Sprinkler wrench across the frame arms,
Wrench
oO (Part No, D❑ NOT overtighten.
14047W/B)K)K Use only the designated
is shown) sprinkler wrench, Viking Part
Number 14047W/B or 14031,
)KA 1/2' ratchet
is required (not D❑ NOT apply more than
available from Viking), 25 ft. lbs, of torque, A leak
tight seal should be achieved
Step 2: Carefully press the by turning the sprinkler
Step 1; Carefully slide the wrench upward and turn slightly clockwise 1 to 1-1/2 turns
wrench sideways around to ensure engagement with the beyond finger tight,
the deflector and pins. sprinkler wrench flats,
Figure 3: Sprinkler Installation and Correct Use of Wrenches
1/2'
(15 mm)
NPT
�— 2-9/16' 2-1/16'
2-3/16° (65 mm) (52 mm)
(55 mm) Maximum Minimum
2-3/4' (70 mm) o
3-5/16° (84.1 mm)
Note; Upon sprinkler activation, the deflector descends
to approximately 13/16' (20.6 mm) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Form No. F_103005 Replaces page 54a-f, dated April 8, 2011.
(Revised VdS Approval.)
Cox Fire Protection
Fitting Submittal
All fittings to be used on this project meets or exceeds the requirements of one or more of the
following standards as required by Section 6.4 of NFPA 13-2016 edition:
ASME B16.4 Cast Iron Threaded Fittings, Class 126 and 260
ASME B16.3 Malleable Iron Threaded Fittings, Class 150 and 300
ASME B16.9 Factory-Made Wrought Steel Buttweld Fittings
ASME B16.25 Buttwelding End for Pipe, Valves, Flanges, & Fittings
ASTM A 234 Specification for Piping Fittings of Wrought Carbon Steel and
Alloy Steel for Moderate and Elevated Temperatures
Threaded Fittings
All threaded fittings shall have threads cut to ASME B1.20.1, Pipe Threads, General Purpose
(Inch), per Section 6.5.1.1 of NFPA 13-2016 Edition.
Manufacturers may vary. All fittings shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• AnvilStar
• Anvil
• Smith Cooper
• Vanderwater International
• BIS
All threaded fittings shall be installed in strict accordance with the guidelines of NFPA 13 and
therefore requires no special submittal of specific manufacturer's installation instructions.
Cox Fire Protection
Fitting Submittal
Welded Fittings
All welded fittings shall be in accordance with Section 6.5.2.2 through 6.5.2.6, NFPA 13-2016
Edition. Welded sprinkler pipe shall be shop welded.
Manufacturers of welded outlets may vary. All fittings shall be of the same manufacturer for a
single project.
Acceptable Manufacturers may include:
• Aegis technologies
• Sigma Piping Products
• Anvil/Merit
• Smith Cooper
All welded fittings shall be installed in strict accordance with the guidelines of NFPA 13 and
therefore requires no special submittal of specific manufacturer's installation instructions.
Grooved Fittings
All grooved joints shall contain cut, rolled, or cast grooves that are dimensionally compatible with
the couplings, per Section 6.5.3.1 of NFPA 13-2016 Edition. All grooved couplings and fittings
shall be listed in compliance with standardized groove specifications.
Manufacturers may vary. All fittings shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• Victaulic/Firelock
• Anvil
• Titus
All grooved fittings shall be installed in strict accordance with the guidelines of NFPA 13 and
therefore requires no special submittal of specific manufacturer's installation instructions.
Cox Fire Protection
Hanger Submittal
All Hangers to be used on this project meets or exceeds the requirements standards required by
Section 9.1 of NFPA 13-2016 Edition.
All sprinkler piping shall be supported from the building structure. The components of hanger
assemblies shall that attach directly to the building structure and pipe shall be listed. Hanger
spacing shall not exceed the limits provided in NFPA 13-2016 Edition.
Hanger Rod
All threaded rod shall meet the requirements of NFPA 13-2016 Edition, Section 9.1.2.
Manufacturers may vary. All rod shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• Erico
• Caddy
• Anvil
• Vulcan
• FPPI
Concrete Fasteners
Concrete Fasteners shall be a listed insert set in concrete or list post-installed anchor.
Manufacturers may vary. All fasteners shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• Sammy
• Hilti
• Red Head
• Lansdale
• Simpson
• FPPI
All fasteners shall be installed in strict accordance with the guidelines of NFPA 13 and therefore
requires no special submittal of specific manufacturer's installation instructions.
Cox Fire Protection
Hanger Submittal
Steel Attachment
Steel attachments shall be a listed drilled fastener or listed beam clamp. Drilled fasteners may
attach to the beams, purlins, deck or any other acceptable steel structure.
Manufacturers may vary. All fasteners/clamps shall be of the same manufacturer for a single
project.
Acceptable Manufacturers may include:
• Sammy (Including Sammy Xpress)
• Anvil
• Globe Pipe Hangers
• nVent (Caddy & Erico)
All steel fasteners & clamps shall be installed in strict accordance with the guidelines of NFPA 13
and therefore requires no special submittal of specific manufacturer's installation instructions.
Wood Fasteners
Wood fasteners shall be a listed drilled fastener. Manufacturers may vary. All fasteners shall be
of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• Sammy
• Anvil
All wood fasteners shall be installed in strict accordance with the guidelines of NFPA 13 and
therefore requires no special submittal of specific manufacturer's installation instructions.
Cox Fire Protection
Steel Pipe Submittal
All of the steel pipe to be used on this project meets or exceeds the requirements of one or more
of the following standards as required by Section 6.3.2, 6.3.3 & 6.3.11 of NFPA 13-2016 edition:
ASTM A795 Specification for Black and Hot-Dipped Zinc Coated (Galvanized)
Welded and Seamless Steel Pipe for Fire Protection Use
ANSI/ASTM A 53 Specification for Black and Hot-Dipped Zinc Coated (Galvanized)
Welded and Seamless Steel Pipe
ASTM A 135 Specification for Electric — Resistance Welded Steel Pipe
Manufacturers may vary. As per Section 6.3.2, 6.3.3 & 6.3.11 of NFPA 13-2016 edition, all piping
shall be marked along its length to properly identify its type, schedule and manufacturing
standard.
Additional approvals or listings are not required when:
1. Steel pipe meeting the above referenced ASTM specifications is used and joined by welding
or roll-grooved pipe and fittings, the minimum nominal wall thickness for pressures up to 300
psi shall be in accordance with Schedule 10 for sizes up to 6 inches and .188 inches for 8" —
10" pipe.
2. Steel pipe meeting the above referenced ASTM specifications is used and joined by threaded
fittings, the minimum wall thickness shall be in accordance with Schedule 40 in sizes less than
8 inches for pressures up to 300 psi.
Exception: Pipe meeting the above referenced ASTM specifications with wall thickness and
pressure limitations less than Schedule 40 for threading or Schedule 10 for welding and roll-
grooving, which have been investigated for suitability in automatic sprinkler installations and listed
for this service, shall be permitted when installed in accordance with their UL or FM listing
limitations.
All steel piping is to be installed in strict accordance with the guidelines of NFPA 13 and therefore
requires no special submittal of specific manufacturer's installation instructions.