HomeMy WebLinkAbout5915 Gall BlvdDIMENSIONS: A. ALL DIMENSIONS ARE TO FACE OF STUD OR FACE OF CMU U.O.N. REFER TO FOUNDATION PLAN FOR FACE OF CONC. DIMENSIONS. B. DIMENSIONS NOTED AS "CLEAR" OR'HOLD' ARE MIN. REQ'D. NET CLEARANCE FROM FACE OF WALL / WAINSCOT FINISH. VERIFY FINAL EQUIPMENT SIZES W/ VENDOR PRIOR TO INT. WALL FRAMING. WINDOWS / DOORS: A. SEE SHT. A1.1 FOR WINDOW TYPES AND DOOR SCHEDULE. B. ALL DOOR AND WINDOW OPENING DIMENSIONS ARE TO ROUGH OPENING. FINISH SUBSTRATES: SEE WALL SCHEDULE THIS SHEET. DECOR: A. SEE SHEETA2.0. GENERAL: A. PROVIDE 5 FIRE EXTINGUISHERS -10 lb. ABC -AND INSTALL AS INSTRUCTED BY FIRE MARSHAL OR AUTHORIZING AGENT. B. DRAWINGS ARE BASED UPON STEEL FRAMING. UTILIZATION OF WOOD STUDS ON NON -BEARING INTERIOR PARTITIONS, BULKHEADS AND SOFFITS IS ACCEPTABLE. C. ALL ATTACHMENTS MADE THROUGH E.I.F.S. SHALL BE BUSHED TO PREVENT DAMAGE TO THE FINISH, PER 9/A6.2. D. ALL PENETRATIONS THROUGH STUCCO SHALL BE SEALED USING MFRS. APPROVED METHOD. 4 4 4 4 Nol 4 0 8� 8 13 4 4 FLOOR PLAN NOTES C 4 4 15 13 A8.0 4 3 DINING 4 "P•) TYPICAL EXTERIOR WALL (FOH): HOODWALL: PROVIDE 1/2" CEMENTITIOUS BOARD OVER EXISTING FURRING PROVIDE 1/2' CEMENTITIOUS BOARD OVER EXISTING TO 12" A.F.F. AND 1/2" GYPSUM BOARD ABOVE TO 6' MIN. - STEEL STUDS. OVERLAY CEMENTITIOUS BOARD WITH ABOVE CEILING. STEEL PANELS SUPPLIED BY HOOD VENDOR. TYPICAL EXTERIOR WALL @ TOWER VESTIBULE: TYPICAL INTERIOR WALL: PROVIDE 1/2" CEMENTITIOUS BOARD OVER EXISTING FURRING PROVIDE 1/2' CEMENTITIOUS BOARD OVER EXISTING '- -- TO 12" A.F.F. AND 1/2" GYPSUM BOARD ABOVE TO 6' MIN. STEEL STUDS AND 1/2' GYP BOARD ABOVE TO MIN. 6' ABOVE CEILING. ABOVE CEILING TYPICAL EXTERIOR WALL (BOH) �lz , PROVIDE 1/2" CEMENTITIOUS BOARD OVER EXISTING FURRING TO 48' A.F.F. AND 1/2' PLYWOOD ABOVE TO 6' MIN. ABOVE CEILING. WALL LEGEND 4 0 ►VI EXPEDITE O 12 liv i 12 ' 12 ', VESTIBULE ' O I 20 (TYP.) 2 COOK 2 1 PREP STORAGE ( " ) i I 1 19 CREW RR 4 7 Do 5 0 o (TY'•) 3 OEXISTING FRAMED WALL. PROVIDE SUBSTRATE ON ALL WALLS AFTER INSTALLATION OF ALL WIRING, PIPING, AND CONDUIT AS SHOWN IN WALL SCHEDULE. O HOOD WALL, SEE WALL LEGEND. O EXISTING MOP SINK. ® EXISTING ELECTRICAL PANEL. SEE ELECTRICAL PLANS. O EXISTING GAS METER. CD EXISTING WALK-IN COOLER/FREEZER. O EXISTING ROOF LADDER. ® PROVIDE SOLID SURFACE SILL (S-1) AT ALL WINDOWS. SEE SHEET A8.0. O EXISTING LIGHTING CONTROL PANEL SURFACE MOUNTED. 10 EXISTING 5? HIGH LOW WALL. COORDINATE WITH OWNER FOR INSTALLATION OF CD CUSTOM STAINLESS STEEL TABLES AND SHELVING BY VENDOR. 11 PROVIDE CAP (S-1) ON EXISTING FREESTANDING 42' HIGH LOW WALL 12 EXISTING DOOR. 13 HAND SINK SEE PLUMBING PLANS. 14 SERVER COUNTER BY VENDOR. GC SHALLINSTALL. CDPROVIDE S-T BI-FOLD DOOR. IG1 MCI rz O V CIO CD Z CD W co V A� con U) DLr) - 0N cf) Phi U r, c� z U) co w VwY0 —j ~Qr.-U D v x CC VzUM= N� Ir U N Q cn � rA z cn m a 17 0 v r ���O.D0000 w O� .\ p � U) OoUQ�CD _U 18 o' oo m d AR97470 o ��°° °tio •0 2 z Y; 05'0�' ��00CiDO ui Y U3 1 m w J FLOOR PLAN 1/4"=1'-0A 16 EXISTING OPAQUE WINDOW FILM ON INSIDE OF WINDOW. FIELD VERIFY. j 7 EXISTING & TALL COMPOSITE FENCE, 18 EDGE OF EXISTING REAR SLAB/RETAINING WALL 19 PROVIDE SOUND BATT INSULATION IN ALL RESTROOM WALLS PRIOR TO INSTALLATION OF SUBSTRATE. ®SPLASHGUARD. SEE DETAIL 9/A6.3 INSTALLATION SHALL BE COORDINATED WITH INSTALLATION OF ADJACENT EQUIPMENT. 21 PROVIDE STAINLESS STEEL SILL AND CORNER GUARDS AT WALK-UP WINDOM KEY NOTES D 0 0 0 0 0 0 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL PHASE 11 FLOOR PLAN 100 PLOT DATE: May 12, 2018 - 9:03am U 12'-8' 10'-8' 9'-4" 7'-0" 9'-4" 7'-0" )m 9'-4" 7'-0" B B B A6.1 A6.1 A6.1 O TYP. N-10' L 2' TYP• 4'-10" L 2" TYP 5'-4" j, EQ. U.EQ. EQ j. EQ. EQ. Uv EQ. T T T. rJwl EQ. EQ. L N B © N © B O O 0 B 0 B 9 co N C A6.1 0 MAIN ENTRY -ALUM. VESTIBULE DOOR (EXISTING) M A6.1 ll u imilm co N DINING WINDOW ALUM. (EXISTING) F A6.1 8'-0" EQ. EQ. I- I L3'-0" i- 3'-0" 1 L 1 B 1 ( © B N 0 INTERIOR VESTIBULE DOOR - ALUM. (EXISTING) 0 MAIN ENTRY -ALUM. VESTIBULE DOOR (EXISTING) B A6.1 2' TYP. 1'-6" LL, 3-0" 1'-6" O SIDE ENTRY DOOR - ALUM. (EXISTING) 2" TYP. r-;w.iu O INTERIOR SERVICE WINDOW - ALUM. (EXISTING) VESTIBULE WINDOW ALUM. (EXISTING) o 60 PICK-UP WINDOW ALUM. (EXISTING) 1. DIMENSIONS ON THIS DWG. ARE TO FRAME EDGE. REFER TO SHEETS A1.0 AND A5 SHEETS FOR ROUGH OPENING DIMENSIONS. 2. ENTIRE STOREFRONT SYSTEM SHALL BE CLEAR ANODIZED. 3. ALL SPANDREL GLASS SHALL BE CLEAR ANODIZED TO MATCH FRAMES. 4. SEE SCHEDULE FOR GLASS TYPES. 5. REFER TO FLOOR PLAN, ELEVATIONS AND WALL SECTIONS FOR ROUGH OPENING DIMENSIONS. 6. ALL STOREFRONT MATERIAL AND GLAZING SHALL BE SUPPLIED AND INSTALLED BY G.C. U.O.N. GLASS SCHEDULE OA 1" INSULATED GLASS OD SAFETY GLASS BY MFR. © 1' INSULATED TEMPERED GLASS © 1/4' TEMPERED GLASS NOTE: SHADING COEFFICIENT SPECIFICATION PER LOCAL CODE REQUIREMENTS. DAYTIME VISIBILITY INTO DINING ROOM SHALL BE MAINTAINED. **** ALL STOREFRONT GLAZING SHALL BE LOW "E" SOLAR GLASS **** NOTES A 1. LAMINATE DOORS 7 AND 8 2. ALL HARDWARE SHALL BE US32D U.O.N. 3. ALL HM FRAMES SHALL BE 16 GA STEEL U.O.N. 4. ALL LOCKS SHALL BE FALCON 6 PIN INTERCHANGEABLE CORE SUPPLIED AND INSTALLED BY THE G.C. ALL EXTERIOR LOCKS SHALL BE PROVIDED WITH CONSTRUCTION CORES. ALL PERMANENT CORES SHALL BE KEYED ALIKE. 5. MOUNT DOOR CLOSERS ON RESTROOM OR KITCHEN SIDE ONLY. 6. LOCKNET SECURITY DOOR. COMPLETE DOOR, FRAME, AND HARDWARE PACKAGE 7. PROVIDE PUSH/ PULL PLATES. IF REQUIRED BY LOCAL CODE, STOREFRONT DOOR PANIC HARDWARE SHALL BE: DOR-O-MATIC 2092 RIM PANIC HARDWARE AND EXTERIOR PULLS WITH QUALITY #520 DOOR PULL. 8. MOUNT KICKPLATE ON PUSH SIDE ONLY. 9. MAXIMUM DOOR OPERATING PRESSURE: 5 LBS INTERIOR: 8 LBS EXTERIOR MEASURED AT 90 DEGREES TO THE DOOR AT THE STRIKE SIDE EDGE. 10. ADA COMPLIANT ACCESSIBILITY SIGNAGE WHERE REQUIRED (OR AS REQUIRED BY LOCAL JURISDICTION) - (1) MEN; (1) WOMEN 11. RESTROOM SIGN IF REQUIRED. VERIFY LOCAL REQUIREMENTS. 12. FRAMES SHALL BE PAINTED. 13. BOBRICK 1090 SERIES, WITH STAINLESS STL. 1 1/2" WALL POST, LATCH, KEEPER, COAT HOOK (DTL 20/ADA1.0) & MOUNTING BRACKETS. INSTALL PER MANUFACTURER'S SPECIFICATIONS & DETAILS. DOOR HANDLE AND LATCH SHALL BE MOUNTED AT 36" A.F.F. HINGES SHALL BE SELF -CLOSING, SEE NOTE 16. 14. PROVIDE SELF CLOSING HINGES AT THE ADA STALL DOORS ONLY. 15. PROVIDE BRUSH TYPE DOOR SWEEP AT ALL EXTERIOR DOOR LOCATIONS. DOOR SWEEP FINISH TO MATCH DOOR FINISH. 16. PROVIDE LATCH AND STRIKE PLATE HARDWARE BY DOOR MFR. TO BE COMPATIBLE WITH LOCKS 17. PROVIDE PULL HANDLE ON BOTH SIDES EVEN HEIGHT WITH DOOR LATCH. SEE DETAIL 16/ADA1.0. 18. 3-0" x T-0' H.M. DOOR WITH 2" H.M. FRAME MAY BE USED, 19. PROVIDE ELIASON SCP4 STAINLESS STEEL SELF CLOSING DOORS WITH WINDOWS. GLAZING SHALLBE 43" MAX ABOVE FINISH FLOOR DOOR SCHEDULE NOTES 1 DOOR BUTTS LOCKS CLOSERS KICKPLATE HRESHO DOOR STOP MISCELLANEOUS w NO. DOOR SIZE o� 00 = DETAIL LOCATIONS DOOR NOTES ❑ ,L 0 1 2 3 4 1 2 3 4 5 6 7 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 4 5 6 Y w O * LESS THAN DOOR } 0 z w � WIDTH v U w U 0 ° ❑ m0 x w U Z Z Q O ZZ a p J w m Cw7 ❑ co X- w cn 2❑ 0 0 o � o °_ w QY U Z o co x a> Fn Q Q Cn U Z Cn w w U N Q°Q Y ❑ - Oz U T N U2 w o U m Z ° r cW z o w �m r r-? a Y U w 0❑ w Q ti w > w U rn x UQ a w a z 0❑ O o o m a O ZO ❑_ =m ¢ 0 ❑w m am. V m w a¢ `� x Z °C ❑ o O 0 o 0 Z Z Q Y o- � > a CL ❑ J O 0° U = U z U rc u i 1 U Z ❑ Z cn b w ❑ p ❑ U o O °❑ �_ 0 2 cn w cn V m 0 9 w Cq z z w 0 o �2�p w m W> > -' o o Q � �_ w � �, Q LL }� LPL Q Z Z W tJ IJ ^ U U X co .tU J Z CL Q N 0 � o m 2 o �Q ? a zZ Q° Y c Z N cn m o °° o g � 7) ° 0 cn O Q w m = a a = Z U Z Q Q Q w _ CL 0 U Er°°M CL ❑❑ ° cn m ❑ d a F- m J 0 O0 m O g c g Z a w w oO w¢= a a w w m ❑ 0 \ J 0 O _ OU = m D uwi O2 0= w CL m u- 0 0 c~n Y Q= 2 0 a CL co U) Z 0 Q cn PHASE 11 3'-0" x 7-0' x 1-3/4' A AL AL X X X X X X X B/A6.1 - - 7, 9,15,16 PHASE 12 3'-0" x 7-0" x 1-3/4" A AL AL X X X X X X X B/A6.1 - - 7, 9,15,16 PHASE 13 PR. 3-0" x 7-0" x 1-3/4' A AL AL X X X X X X X F/A6.1 - - 7, 8, 9 PHASE 1 4 3'-0" x 7-0' x 1-3/4' A AL AL X X X X X X X B/A6.1 - - 7, 9,15,16 PHASE 15 4'-6" x 6-8" x 1-3/4" F HM HM X X X X X X X X L/A6.1 - - 5.6.8.9.12 PHASE II 6 3'-0" x 16-8" x 1-3/4" D WD HM X X X X X X X X - - 1, 5, 8, 9, 10, 11, 12 PHASE II 7 PR. 34Y x 6-8' x 1-3/4" E WD HM X X _ _ _ 1.19 PHASE II 8 PR. 3'-0" x 6'-8' x 1-3/4" E WD HM X X _ _ _ 1.19 PHASE II 9 3'-0" x 6-8" x 1-3/4" D WD HM X X X X X X X X - - 1, 5, 8, 9, 10, 11, 12 PHASE II 10 3-0" x 6-8" x 1-3/4" D WD HM X X X X X X X X - - 1, 5, 8, 9, 10, 11, 12 PHASE II 11 3'-0" x U-8" x 1-3/4" D WD HM X X X X X X - - 1, 8, 12, 17, 18 DOOR SCHEDULE __T2 PUSH PLATE OR L HANDLE, WHERE SIGN WHERE VA63'-0" 3'-0"3'-0" 3'-0'SCHEDULEDEQ. EQ. EQ. EQ. EQ. REQUIRED D C - o � PULL PLATE PULL PLATE b b b b b / © 1 1 1'-0 r; b 4 4 b T T T � 1u e a cr) b T O T T O[v N FINI H FLOOR KICKPLATE O O O O O O STOREFRONT STOREFRONT STOREFRONT WOOD DOOR KITCHEN DOORS HOLLOW METAL ICKPLATE SYSTEM SYSTEM SYSTEM (ELIASON) DOOR KITCHEN SIDE ALUM. DOOR ALUM. DOOR ALUM. DOORS (EXISTING) ONLY NOTE: ELEVATIONS DRAWN AS VIEWED FROM EXTERIOR OF BUILDING. (EXISTING) (EXISTING) (EXISTING) NOTE: ELEVATIONS DRAWN AS VIEWED FROM EXTERIOR OF BUILDING OR OUTSIDE ROOM. WINDOW TYPES 1/4' = V-0" 1 9 DOOR TYPES 1/4" = 1'-0" 3 91 A Z G� «co V CO w Lo w O C:)C\J Q � �w (o co C/) Lo C-) i J �- Q U VzU_`y'_ i- N� U N Q CIS � ui Z cn Z) m 'do a o o, o �c ARS7470 We1'ivIl 0 CD CD z w U � m d � U Z .12 a i-05:00' m w W 0 0 0 0 0 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5916 GALL BLVD. ZEPHYRHILLS, FL PHASE 11 DOOR/WINDOW ELEVATIONS & SCHEDULES I ml PLOT DATE: May 12, 2018 - 9:05am DIMENSIONS: A. ALL DIMENSIONS ARE TO FACE OF STUD OR FACE OF CMU U.O.N. REFER TO FOUNDATION PLAN FOR FACE OF CONC. DIMENSIONS. B. DIMENSIONS NOTED AS'CLEAR" OR "HOLD" ARE MIN. REQ'D. NET CLEARANCE FROM FACE OF WALL / WAINSCOT FINISH. VERIFY FINAL EQUIPMENT SIZES W/ VENDOR PRIOR TO INT. WALL FRAMING. WINDOWS / DOORS: A. SEE SHT. A1.1 FOR WINDOW TYPES AND DOOR SCHEDULE. B. ALL DOOR AND WINDOW OPENING DIMENSIONS ARE TO ROUGH OPENING. FINISH SUBSTRATES: A. PROVIDE 1/2" THICK CEMENTITIOUS BD. FROM FLOOR SLAB TO 12" A.F.F. MIN. IN LIEU OF GYP. BD. AT ALL WALLS EXCEPT SHEARWALL SURFACES, U.O.N. B. ALL JOINTS, GAPS OR SPACES LEADING TO ALL HOLLOW OR INACCESSIBLE SPACES SHALL BE SEALED WITH "NSF INTERNATIONAL" APPROVED SEALANTS. C. ALL BACK OF HOUSE AND OFFICE WALLS SHALL HAVE 1/2" CDX PLYWOOD SUBSTRATE, U.O.N. DECOR: A. SEE A2.0 FOR SEATING PLAN AND DETAILS. B. SEE A7.0 FOR FLOOR FINISHES. C. SEE A8.0 - A8.3 FOR WALL FINISHES. D. SEE A7.1 FOR CEILING FINISHES. GENERAL: A. PROVIDE 4 FIRE EXTINGUISHERS - (2) 10 lb. BC & (1) 10 lb. ABC, AND (1) TYPE K - TO COMPLY WITH LOCAL FIRE CODE. LOCATE PER DIRECTION OF FIRE MARSHALL OR LOCAL AUTHORIZING AGENT. B. DRAWINGS ARE BASED UPON STEEL FRAMING. UTILIZATION OF WOOD STUDS ON NON -BEARING INTERIOR PARTITIONS, BULKHEADS AND SOFFITS IS ACCEPTABLE. C. ALL ATTACHMENTS MADE THROUGH E.I.F.S. SHALL BE BUSHED TO PREVENT DAMAGE TO THE FINISH, PER 9/A6.2. D. ALL PENETRATIONS THROUGH STUCCO SHALL BE SEALED USING MFR'S. APPROVED METHOD. FLOOR PLAN NOTES C I I I I I C-01 i I I I I i C-01 i I I I I i C-01 i I I I I i G01 C-03 C-03 DINING SYM. QTY. ITEM ool> 10 BOOTH TABLE 6'-0" © 4 SINGLE SIDED BOOTH SEAT -FINISHED BACK, 6'-2" C-03 - 8 DOUBLE SIDED BOOTH SEAT, 6-2" C-04 15 TABLE, SQUARE, 36" © 0 TABLE, 24" X 30" 0-06 0 BENCH STYLE SETTEE, VARYING LENGTHS, 20'-0" TOTAL (-0 64 DINING CHAIR © 5 BENCH STYLE SETTEE, 5'-9" C-* 2 DOUBLE -SIDED BOOTH SEAT, 4-2" 0-10 1 TABLE, 30" X 48" C-11 2 TABLE, 30" X 48", ACCESSIBLE 16 a........ - -- 1 I I 8-001 N-001 15 B-005 E-003 D-001 N-008 r-- I I L ___ _J PREP r h O) V co ro Z W co W Lo .i Oo u a v��z w �w n) wV)Lo C7Y�� _ Vzv = N Sr) N < U) �M4 � rA z V ) D m 0 v n o w Z w O J .10 a :33-05b0' QTY CODE EQUIPMENT DESCRIPTION MANUFACTURER MODEL NO. NOTES ELECTRICAL PLUMBING FURNISH INSTALL RELOCATED FROM EXISTING STORE VOLTS/PH CW HW TW WASTE OWN GC OWN GC 2 T 1 TABLE S. S. 96' X 0" X X TBD 2 T-002 TABLE S.S. 24" X 24" X X TBD T-003 TABLE S.S. "X48" X X TBD 1 T-004 TABLE S.S. 30" X 82' CUSTOM W -TIER SHELF I X X YES 1 T-005 TABLE S.S. 301 X ' CUSTOM X X TBD 1 T-006 TABLE S.S. 30" X 82' CUSTOM W 3-TIER SHELF X X YES 1 R-001 IKEG COOLER CONTINENTAL KC-69 X X YES 2 R-002 MEGATOP SANDWICH PREP ATOSA MSF8307 X X YE 1 R-003 FREEZER UNDERCOUNTER BEVERAGE AIR UCF27A X X YES 1 R-004 CUBER AND BIN HOSHIZAKI KM- 15M H WITH BIN B-300 X X YE 1 R-005 MERCHANSING CABINET REFRIG TRUE G4SM-23PT-LD X X NEW 1 R-006 CUBER AND BIN SCOT MAN CMEBW WITH BIN X X YE 0 R-007 SOFT SERVE FREEZER TAYLOR 339 X X STORAGE 1 R-008 FOOD PREP TABLE TRUE TPP-93 X X YE 2 R-009 REFRIG FULL HEIGHT GLASS FRNT EXISTING 1 IR-010 REFRIG. HALF HEIGHT S.S. TOP X X YE 2 R-011 REFRIG HALF HEIGHT ATOSA MSF8402 S.S. TOP X X YES 1 R-012 SOFT SERVE FREEZER SPACEMAN SM- 250H X X NEW 1 R-013 HORIZONTAL FREEZER TRUE TFM-51AL X X NEW 1 R-014 UNDERCOUNTER REFRIGERATOR T RB AIR JUR-36 X X NEW 2 R-015 CHEF BASE ATOSA MGF8453 X X NEW 2 R-016 MOBILE ICE BIN BK RESOURCES BK-MIB-2411 X X NEW 1 H-001 WARMER BREAD 1 H-002 TEAM TABLE &COMPARTMENT UNKNOWN 1 H-003 WARMER HALF HEIGHT S.S. TOP 1 CW1 CONVECTION OVEN IMPERIAL I V -1 MOUNTED TWO HIGH 120 1 PH X X YE 3 C-002 S FRYER DEAN R42GN X X YE 1 C-003 I GAS BROILER 3'-0" COM-STOCK CASTLE 3236RB TABLE MOUNTED GAS K X X YES 1 C-004 STOVE, FOUR BURNER TABLE MOUNTED X X YE 2 C-005 RIDDLE FLAT T P 4'-0" VULCAN 948RX TABLE M UNTED 120 1 PH X X YE 1 C-006 RIDDLE FLAT TOP. G-0" VUL AN TABLE M UNTED X X YE 1 C-007 MICROWAVE SOLWAVE 180MW1000D X X YES 1 C-008 GAS STOVE SUNFIRE X60-1 ORR X X YE 3 C-010 TOASTER BELLECO JT1 X X YE 2 C-011 WAFFLE MAKER GOLDEN MALTED RT X X YE 4 C-012 FOOD WARMER APW WYOTT W-3VI X X YES 1 P-001 MIXER HOBART HL-800 1 P-002 CHOPPER SCHARFEN S2 1 P-003 SLICER BERKEL 813A 1 P-004 MIXER HOBART H -200 0 P-005 NVECTION OVEN IMPERIAL 1 P-006 BREAD RACK 3 P-007 BLENDER WARING BB160 3 S-001 COFFEE BREWER BUNN CWTF-DV-3 4 S-002 TEA URN 1 S-003 TEA BREWER BUNN T136 1 S-004 TWO DRAWER FOOD WARMER VULCAN 1 S-005 CO2 TANK MVE 14275347 1 S-006 WATER FILTER SYSTEM SHURFLO WB6-M3-22-003 1 S-007 SOFT DRINK BOOSTER TANK 1 S-008 BAG IN BOX SYRUP RACK CORNELIU EMCOR BNB12138P 4 N-001 SS HAND SINK AERO H K-A W NEE PEDAL AND FAUCET X X NEW 1 N-002 SHOWER STALL AQUATIC 1323CM X X NEW 1 N-003 24" MOP SINK AERO 3MP-2121 1P X X NEW 1 N-004 MOP SINK FAUCET T&S B-2465 X X NEW 1 N-005 1 COMP PREP SINK AERO 2F1211617LR X X NEW 1 N-006 WASTE DRAIN LEVER T&S S-20 X X NEW 1 N-007 PREP SINK FAUCET T&S B-2463 X X NEW 1 N-M 3-COMP SINK 2'-10 X 9-4" RELOCATED W AUCETS X X STORAGE 1 N-009 DIPPER WELL NEM 7736-10 X X STORAGE 1 N-010 HAND SINK JOHN BOOS PB-DSINK090905 1 N-011 HAND SINK J HN BOOS IPB-DSINK101405 QTY CODE EQUIPMENT DESCRIPTION MANUFACTURER MODEL NO. NOTES ELECTRICAL PLUMBING FURNISH INSTALL VOLTS/PH CW HW TW WASTE OWN GC OWN GC 7 B 1 WASTE R BBERMAJ SLIM JIM #3541 GREY 1 B-002 DRIVE-THRU WINDOW UIK-SERV SC-4030BR B IR R BOBRICK B-165-1836 4 B-004 OILET PAPER DISPENSER BOBRICK B-2890 B PAPER TOWEL DISPENSER BOBRICK B-262 3 B PAPER TOWEL DISPENSE IBOBRICK BOBRICK B-3944 B 7 GRAB BAR 1-1 "X . FIN—BOBRICK B6 3 B-008 GRAB BAR 1-1 ` X 42" S.S. FINBOBRICK B6806X42 B GRAB BAR 1-1 ' X 1S.S. FIN B6806XI18 3 B-010 SANITARY NAPKIN RECEPTACLE RUBBERMAID 6140 WST 1 D-001 DISH MACHINE CMA DISHMACHINES EST-44H PROVIDED BY OWNER 1 D DISH MACHINE TABLES K-001 SHELVING UNIT TIER TBD 24` X 48" 10 K-002 SHELVING UNIT 5 TIER TBD 24' X 60" 4 K-003 SHELVING UNIT 5 TIER TBD 24" X 72" 1 K-004 SHELVING UNIT 5 TIER TBD 18" X 42" 1 K-005 DISH RACK SHELVING 9'-6" PROVIDED BY OWNER 1 W-001 WALK-IN COOLS FREEZER KOLPAK 2 E-001 8'-0" HOOD TRANSFERRED EQUIPMENT 1 E-002 12-V HOOD 1 E-003 6-0" HOOD 4 0-001 POINT OF SALE UNIT 4 -002 RE EIPT PRINTER 4 0-003 CREDIT CARD MACHINE rn G� � 2:� � W wLr) w 00 � Uco�w Lb w u,�U J � v x�7— _ Vzc) N� Sr) 't Q �N U) 0 Lu Z U) m pi 1.4 0 h h rn d ww z w U Ed d 4 U z Q w Y 03 a m w 18014 0 0 0 0 0 0 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL PHASE 11 EQUIPMENT SCHEDULE 2ml KEY NOTES D PLOT DATE: May 10, 2018 - 7:36pm :a SEMI -RECESSED WASTE RECEPTACLE 1--I FASTEN 2X BLOCKING TO FACE OF .. PROTECT SYRUP LINES ADJACENT WALL OR TRUSS Z � (4) #12 S.S. WOOD PANEL WALL O FROM TRUSS PLATES SCREWS 3/4' LG. W/ S.S. F MO PLUMBER'S TAPE STRAP WASHERS. BUNDLED SYRUP LINES z r Z AND FILTERED WATER LINES 2 A N FOOD GRADE RTV SEALANT O f-1/2" RAD. EASED 1 1/4" TEK SCR INTERIOR BASE COVE TRIM vJ 7" DIA. OPENING IN CEILING TILE w " 7) L1� CORNER (TYP.) THINSET TILE O N EXTEND FRONT OF PANEL TC6`4 GROUT U ti Cy) Z a -' HIT FASTENER (p Lu BOTTOM CHORD w TO FRONT EDGE OF ADJ• r Cn co OF ROOF TRUSS 6" PVC PINK) APPROX. 24 (SEE SCREED CONCRETE SLAB V L� J 0 Y i6 GA. BRUSHED FU OPTIONAL INSTALLATION: 1" p o ,` ry I— Q WIDE GALV. STRAPS @ F�4. W HEM ON TOPNLESS , FRONT V ~ ~ CO W = (6 TRUSS (MAX. 6'-0" O.C.) AND BOTTOM EDGES. V Z U M = 2" FLANGE r BENT 90 _ U I NOTE: SECTION VIEW DEG. SEE SCOPE OF WORK FOR SYRUP LINE BUNDLE THRU CLG. BOTTOM EDGE OF (V O SCOPE DEFINITIONS SPLASH GUARD SHALL BE EVEN W/ THE EDGE [] N (n g NOTE: CAULK ALL SEAMS AT WALL OF THE HIGHEST ADJ. DYNATROL I•Ty (n } } SURFACE. SINK. SEALANT W Z SYRUP LINE IN CEILING N.T.S. 17 SYRUP BUNDLE CLG PENETRATION N.T.S. 13 SPLASH GUARD 1" =1'-0" 9 WASTE RECEPTACLE N.T.S. 5 WALK-IN TILE/BASE 1-1/2" = 1'-0' 1 Cn m �1 DOUBLE STUDS AT JAMB AND HEAD WITH ANCHOR STRAP. GYP. BD. FE CHAIR RAIL. ELEV. SOLID SURFACE CAP HM FRAME �N SILICONE SEALANT Lu O���OO Gs G 000� . z Er w w WD. DOOR ° v SEALANT w Z.cr NOTE: SEE SHEET A8.0 w ° ° AR97470 °ate 0 v SUBSTRATE AS NOTED ON ¢ �° FOR MOUNTING HEIGHT co SHEET AI.O m J' . "°° ° 1 �10 m 0000oo0�a � co SECTION AT CHAIR RAIL 3'=1'-0" 18 HOT USED 1" = 11-0" 6 JAMB @ H.M. DOOR N.T.S. 2 �- m w ` w J FRP 2" WALL 2' FASTEN S.S. in FINISH TABLE TOP HEIGHTS: FINISH WITH � LOW TABLETOP HGT. = 30" A.F.F. HIGH CONSTR. ADHESIVE _ (H) TABLE TOP HGT. = 42" A.F.F. 0 DINING COUNTER TOP HGT. = 42" A.F.F. CEILING TILE & GRID GUARD L WALL SUBSTRATE ,FNLUSH PER SHT. A1.0 z 18014 SURFACE MARMOLEUM FINISH PER w STEEL SUPPORT PLATE SURFACE FRP INTERIOR ELEVATIONS 0 STEEL SUPPORT 0 Q TILE GROUT HEIGHTBLOC ING CEILING Q WALL U 0 BASE SILICONE SEALANT w POUR -ROCK z FLOOR TILE FRP oq�c 0 COVE BASE TILE U CONCRETE SLAB SUBSTRATE PER PLAN Er FLOOR TILE N _ w FLOOR Ir U 0 a w a 3-1/2" DIA. Z CONTRACT DATE: 08.13.2017 t . NOTE: THIS DETAIL SHOW A 90 DEGREE CORNER. ADAPT THIS DETAIL 3-1/2' DIA. TABLES ONLY BUILDING TYPE: ONE-OFF AND APPLY WHERE WALLS EXTEND INTO SPACE. m J PLAN VERSION: S.S. CORNER A END WALL GUARD N.T.S. 19 LADDER DETAIL 1 - 1-0" 15 DINING LOW WALL 3 -1-� 11 CORE DRILL 1 1/2 -1-0 " - ' "- ' °- � ° 7 KITCHEN FINISH @CEILING 3 3"=1'-0" SITE NUMBER: STORE NUMBER: SUNRISE EATERY rn; WALL SUBSTRATE PER WALL SUBSTRATE PER WALL SUBSTRATE PER SH . A1.0 WALL SUBSTRATE PER SHT. A1.0 WALL SUBSTRATE PER SHT. A1.0 5915 GALL BLVD. SHT. A1.0 ......._ SHT. A1.0 ZEPHYRHILLS, FIL : \` WALL FINISH PER INTERIO WALL FINISH PER INTERIOR f WALL FINISH PER INTERIOR i WALL FINISH PER INTERIOR --� WALL FINISH PER INTERIOR ELEVATIONS \ ELEVATIONS \� ELEVATIONS ELEVATIONS ELEVATIONS CEMENT BOARD PER CEMENT BOARD c SHT. A1.0 PER SHT. A1.0 CEMENT BOARD PER SHT. A1.0 WALL SUBSTRATE PER SHT. A1.0 f J-MOLD SET IN SILICON SEALANT - FIT J-MOLD W/ SILICON PRIOR TO w w FINISH \ INSTALLING FRP, WIPE OFFS Z Lu w w EXCESSLu U COVE BASE TILE - U DETAILS _ = W SET FLUSH W/ FLOOR TILELLI U U - COVE BASE TILE - SET j COVE BASE TILE - SET a \ COVE BASE TILE - ¢ COVE BASE TILE - U FLUSH W/ FLOOR LE c=j FLUSH W/ FLOOR TILE Y SET FLUSH W/ FLOOR TILE u� SET FLUSH FLOOR TILE \ Lu Z co Y Y uw� ¢ ¢ Y ¢ ¢ ■ m m m J „— "_ ,- „ " _ „— PLOT DATE: May 10, 2018 - 7:37pm BASE @ KITCHEN EXT. SIDE WALLS 3 -1-0 20 BASE @ DINING ENT. SIDE WALLS 3 -1 0 16 BASE IN RESTROOM 3 - 1 0 12 BASE @ DINING ROOM INT. WALL 3 -1-0 8 KITCHEN FINISH @ BASE 3"=1'-0 4 A. 0 DENOTES FINISH MATERIAL, REFER TO SHT A7.2 FOR FINISHES. L:l TILE JOINTS (U.O.N.): 1. QUARRY FLOOR TILE: 1/4" 2. PORCELAIN FLOOR TILE: 3/16" 3. GLAZED WALL TILE: 1/8" 4. BASE, TRIM AND ACCESSORIES: MATCH ADJOINING TILE UNITS C. TILE INSTALLATIONS REQUIRE MANUFACTURERS STANDARD MOLDED CORNERS AT BOTH INSIDE AND OUTSIDE CORNERS. D. ALL BASE TILE SHALL BE SANITARY COVE STYLE WITH 3/8" MIN RADIUS UNLESS NOTED OTHERWISE. E. SEE SCOPE OF WORK SHEETS FOR RESPONSIBILITIES. F. PROVIDE CLEAR SILICONE CAULK WHERE FRP STOPS AT TOP OF COVE BASE. G. TILE CHIPPING AROUND CORE DRILL HOLES FOR SEATING FIXTURE WILL NOT BE ACCEPTED. O FACTORY FLOOR FINISH (GALV STL) W/ INTEGRAL COVE BASE O 6" COVE TILE BASE. SEE DETAILS 8/A6.3 (INTERIOR) AND 16/A6.3 (EXTERIOR) FOR INSTALLATION. O 6" SANITARY COVE TILE BASE. SEE DETAILS 4/A6.3. 4 PROVIDE FLOOR TILE INSIDE WALK-IN COOLER WITH FACTORY SUPPLIED STEEL BASE. FLOAT FLOOR TILE IN COOLERS TO DRAIN TO KITCHEN. O ALL BACK OF HOUSE LOCATIONS (TYP.). © NOT USED. FLOAT FLOOR TILE FOR FLUSH TRANSITION. ® INTEGRAL RAMP. 0 NOT USED. 10 PROVIDE 1/8" PER FOOT SLOPE AROUND BOH FLOOR DRAINS WITHIN 5'-0% OR TO NEAREST WALL TO FLOOR DRAINS OR FLOOR SINKS. 11 NOT USED. 12 PROVIDE TILE TO GRADE TRANSITION. 13 CERAMIC TILE TO QUARRY TILE TRANSITION POINT. FINISH PLAN 0 a oo w co n.°uj °^a10 oa o o 0 d. CE AR97470 05'00' �o��0OQO w Y co Z m w • e :� 0 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: 59UpWIPIBYND. ZEPHYRHILLS, FL REFLECTED CEILING PLAN 7ml FINISH NOTES KEY NOTES PLOT DATE: May 10, 2018 - 7:37pm • 0 DOWNLIGHT @ WALK-IN -0 (BY WALK-IN MFR.) HVAC RETURN GRILLE lw PENDANT FIXTURE F�� HVAC SUPPLY DIFFUSER Ce EMERGENCY LIGHTS BACK DOOR SECURITY STROBE LIGHT EXIT LIGHT (WALL MOUNTED) 0� OCCUPANCY SENSOR ® EXIT LIGHT (CEILING MOUNTED) B. ALLOWABLE VARIATIONS FROM FLAT AND LEVEL SURFACE: 1/8" IN 10'-0" MAX. C. ALLOWABLE VARIATIONS FROM PLUMB OF GRID MEMBERS: AS CAUSED BY ECCENTRIC LOADS, T MAX. D. INSTALL SYSTEM AFTER MAJOR ABOVE CLG. WORK IS COMPLETE. COORD LOCATIONS OF HANGERS WITH RELATED WORK. E. SEE SPECS FOR ADDITIONAL INFORMATION. GYPSUM BOARD CEILING: A. SUBSTRATE SHALL BE 1/2" THICK GYP BD. B. ACOUSTICAL SEALANT: APPLY TO GYP. BD. PANELS AS INDICATED IN SPECS. GYP. BD. FINISHING AND DECORATING: REFER TO DWGS FOR TEXTURE AND FINISHES. ELECTRICAL: A. SEE ELECT. DWGS. FOR FIXTURE SCHED. NOTE: LOW VOLTAGE WORK OTHER THAN THAT SHOWN SHALL BE PERMITTED SEPARATELY BY OPERATORS VENDOR :EILING PLAN CEILING FOR SYRUP LINES. OPERATOR TO FT DRINK VENDOR REQUIREMENTS. O STARTING POINT FOR FRONT OF HOUSE CEILING GRID. EXISTING CEILING LADDER. 7 U z WN Nt z cr) � Z Lii �OR � cUnco�w wcnTU �- Q U vco UJ r x o� co �QN� � N cn cn � Z Z) m moo o AR974 0 r OFj IAI FAI A CONTRACT DATE: BUILDING TYPE: PLAN VERSION: SITE NUMBER: STORE NUMBER: s0 no w Y z i 00 w w J 08.13.2017 ONE-OFF 597,61;9(LQI6WD. ZEPHYRHILLS, FL REFLECTED CEILING PLAN CEILING SYMBOL LEGEND E REFLECTED CEILING PLAN NOTES I D KEY NOTES 7ml PLOT DATE: May 10, 2018 - 7:38pm DOWNLIGHT @ WALK-IN (BY WALK-IN MFR.) HVAC RETURN GRILLE PENDANT FIXTURE HVAC SUPPLY DIFFUSER EMERGENCY LIGHTS BACK DOOR SECURITY STROBE LIGHT EXIT LIGHT (WALL MOUNTED) OC OCCUPANCY SENSOR ® EXIT LIGHT (CEILING MOUNTED) VVI 1 VIIIV /l1YV IIY IIIVL/"�LI\.11 YIYILIY I. ALLOWABLE VARIATIONS FROM FLAT AND LEVEL SURFACE: 1/8" IN 10'-0" MAX. ALLOWABLE VARIATIONS FROM PLUMB OF GRID MEMBERS: AS CAUSED BY ECCENTRIC LOADS, 20 MAX. INSTALL SYSTEM AFTER MAJOR ABOVE CLG. WORK IS COMPLETE. COORD LOCATIONS OF HANGERS WITH RELATED WORK. SEE SPECS FOR ADDITIONAL INFORMATION. GYPSUM BOARD CEILING: A. SUBSTRATE SHALL BE 1/2" THICK GYP BD. B. ACOUSTICAL SEALANT: APPLY TO GYP. BD. PANELS AS INDICATED IN SPECS. GYP. BD. FINISHING AND DECORATING: REFER TO DWGS FOR TEXTURE AND FINISHES. ELECTRICAL: A. SEE ELECT. DWGS. FOR FIXTURE SCHED. NOTE: LOW VOLTAGE WORK OTHER THAN THAT SHOWN SHALL BE PERMITTED SEPARATELY BY OPERATORS VENDOR CEILING PLAN -EILING FOR SYRUP LINES. OPERATOR TO =T DRINK VENDOR REQUIREMENTS. O STARTING POINT FOR FRONT OF HOUSE CEILING GRID. U z z Cy) Z o � A~ Lb Lo .. 00w U � Z L U3 W cr �C.) P� U w Ye -I W~Q�U }-- C�O�C~mow UzU(y)_ I- N U N Q Cn � Lli Z Cn D m 0 n v n rn Q w U) z w U J CD Q U Z Q Q w Y z Q m w w J 1Q REVISION 1 06.01.2018 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL REFLECTED CEILING PLAN CEILING SYMBOL LEGEND I E REFLECTED CEILING PLAN NOTES I D KEY NOTES 7ml PLOT DATE: Jun 14, 2018-10:13pm FLOORING WALL FINISHES LAMINATES CEILINGS SYM DESCRIPTION ALTERNATE / NOTE SYM DESCRIPTION ALTERNATE / NOTES■ SYM DESCRIPTION O DESCRIPTION ALTERNATE / NOTE T-1 MFR.: DAL TILE TYPE: QUARRY #OQ40 NON ABRASIVE COLOR: GREY SIZE: 616" GROUT: CUSTOM #95 SABLE BROWN EPDXY P-1 MFR.: SHERWIN WILLIAMS TYPE: SATIN / EGGSHELL LATEX COLOR: SW6689 "OVERJOY" PRIMER: #023 (WHITE) FRESH START 100% ACRYLIC VERIFY WITH OPERATOR FINAL PAINT SPECIFICATION FRP-1 MFR.: MARLITE TYPE: FIBERGLASS REINFORCED PANEL COLOR: FP-100 WHITE (PEBBLED FINISH) NOTE: NO COLOR VARIATIONS ACCEPTED CL-1 MFR.: CERTAINTEED TYPE: VINYLROCK #1140, WASHABLE NON -PERFORATED, 24W8%1/2" COLOR: WHITE GRID: WHITE SUSPENSION GRID W/ ALUMINUM FACE NOTE: FLAME SPREAD RATING 0-25, CLASS A MFR.: US GYPSUM CO. TYPE: CLIMAPLUS LAY -IN CEILING PANEL COLOR: FLAT WHITE #050, VINYL 3270 NOTE: 2411x48" NOTE: SEE SPECIFICATIONS NOTE: BOH, KITCHEN P-2 MFR.: SHERWIN WILLIAMSCL- TYPE: SATIN / EGGSHELL LATEX COLOR: SW7020 "BLACK FOX" PRIMER: #023 (WHITE) FRESH START 100% ACRYLIC � ) VERIFY WITH OPERATOR FINAL PAINT SPECIFICATION MFR.: TYPE: GYPSUM BOARD COLOR: NOTE: REFER TO A7.1 T-2 MFR.: DALTILE TYPE: TERRA ANTICA CERAMIC TILE COLOR: ROSSO TA-02 SIZE: 18"x18" VERIFY WITH OPERATOR FINAL TILE SPECIFICATION GROUT: MAPEI ULTRACOLOR PLUS #11 SAHARA BEIGE NOTE: ALL FRONT OF HOUSE LOCATIONS CL-3 MFR.: ARMSTRONG TYPE: 24" SQUARE LAY -IN COLOR: WHITE - FINE FISSURED GRID: ARMSTRONG PRELUDE XL 15/16" EXPOSED TEE COLOR: PRE -FINISHED WHITE P-4 MFR.: NOT USED TYPE: - COLOR: - PRIMER: - TM- MFR.: SCHLUTER TYPE: QUADEC-K COLOR: ANODIZED ALUMINUM ( BY G.C.) 0 MFR.: N/A VERIFY WITH OPERATOR FINAL TRIM AND COLOR TYPE: 1 x 2 OAK SPECIFICATION COLOR: PAINT P-2 ( BY G.C.) WT-1 MFR.: DALTILE VERIFY WITH OPERATOR FINAL TILE TYPE: TIMBERGLEN SPECIFICATION COLOR: DUNE P620 SIZE: 12"X24"X3/8" AT RESTROOMS GROUT: MAPEI #14 BISCUIT WALL BASE NOTE: TILE TO BE INSTALLED WITH THE GRAIN HORIZONTAL. USE RONDEC SYM DESCRIPTION ALTERNATE / NOTE ANODIZED ALUM RO 1ooAE FOR OUTSIDE SATIN CORNERS B-1 TYPE: QUARRY#QO1 MILLWORK DOORS COLOR: GREY TO MATCH T-1 SYM DESCRIPTION SYM 0 DESCRIPTION ALTERNATE/ NOTE SIZE: 6" x 6" GROUT: #95 SABLE BROWN - NON EPDXY 672 MFR.: DAL TILE TYPE: TERRA ANTICA CERAMIC TILE COLOR: ROSSO TA-02 x1 SIZE: 6"2" COVED BASE GROUT: CUSTOM #95 SABLE BROWN VERIFY WITH OPERATOR FINAL TILE SPECIFICATION S-1 MFR.: WILSONART TYPE: SOLID SURFACE COLOR: AVALANCHE MELANGE 9175ML WHITE WITH BRONZE SPECKLES DL-1 MFR.: WILSONART TYPE: PLASTIC LAMINATE COLOR: 7981-K12, WEAR LANDMARK WOOD * DOOR EDGES SHALL BE FINISHED SIMILAR TO FACES VERIFY WITH OPERATOR FINAL LAMINATE SPECIFICATION NOTE: ALL FOH LOCATIONS METAL TRANSITIONS DL-2 MFR.: WILSONART VERIFY WITH OPERATOR FINAL LAMINATE TYPE: PLASTIC LAMINATE SPECIFICATION COLOR: 7919, AMBER CHERRY SYM DESCRIPTION ALTERNATE / NOTE MT-1 MFR.: SCHLUTER TYPE: SCHLUTER DILE:X-AHKA80AE COLOR: AE, SATIN ANODIZED ALUMINUM SIZE: 3/8" profile DL-3 MFR.: NEVAMAR TYPE: S7027T COLOR: SMOKY WHITE VERIFY WITH OPERATOR FINAL LAMINATE SPECIFICATION MT-0 MFR.: SCHLUTER TYPE: KENO-U COLOR: ANODIZED ALUMINUM SIZE: 1. INSTALL FRP ON KITCHEN SIDE OF SERVING COUNTER WALL. 2. GALV STEEL WALL AND CEILING FINISHES BY WIC / WIF BOX MFR. 3. REFER TO INTERIOR ELEVATIONS FOR LOCATIONS OF TILE AND FRP. 4. FOR FINISH LOCATIONS REFER TO: SHEETS A4.0 & A4.1 - EXTERIOR ELEVATIONS SHEET A7.0 - FLOOR FINISH PLAN SHEET A7.1 -REFLECTED CEILING PLAN SHEETA8.0 -INTERIOR ELEVATIONS 5. APPROVED PAINT MANUFACTURERS: PORTER, BENJAMIN MOORE, SHERWIN WILLIAMS, ICI, & PITTSBURGH PAINTS. MATCH SPECIFIED SCHEDULE COLORS EXACTLY. 6. NOT USED 7. ALL MORTAR SHALL BE MIXED WITH WHITE SAND TO INSURE A COLOR CONSISTENT TO THE ORIGINAL DESIGN INTENT ROOM FINISH NOTES D NOT USED C ROOM FINISH SCHEDULE LEGEND A U Z rrhh O Mv�l O w `: V Q � w U.) � 0w (n (O LJ CO LD oC w�YMJ N~Q~U C) W�=OW UzvMv I— N � a: Q N 07 cn V� Lu _Z cn D m 18014 0 0 0 0 0 0 L R d n w m z w U J Ed d z -05'001 co CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL FINISH SCHEDULE 7m2 PLOT DATE: May 10, 2018 - 7:39pm A. PROVIDE PROPER 2x BLOCKING AT WALL RECE MOUNTED ACCESSORIES. B. GRAB BARS, FASTENERS AND MOUNTING DEVI( SHALL BE INSTALLED PER ADA REQUIREMENTS TO SHEET ADA1.0. C. REFER TO FLOOR PLAN NOTES FOR BLOCKING SUBSTRATE NOTES. D. REFER TO SHEET ADA1.0 FOR MOUNTING HEIGI AND CLEARANCES OF ACCESSORIES AND FIXTI E. ALL DIMENSIONS THIS DRAWING ARE TO FINISF SURFACE. TYPICAL RESTROOM ELEVATIONS 3/8'=1,-o,, P-1 / P-1 TM-3 3 3 3 3 3 TM-3 3 \ ol / \ S-1 S-1 S-1 IL / TM-3 B-2 lie oe - DL-2 B-2 B-2 TYPICAL DINING ELEVATIONS 3/8"=1'-(" C TYPICAL DINING ELEVATIONS 318"=1'-u ENLARGED RESTROOM / GENERAL NOTES 3i81=1'-0° A K ', CnAP Amn QAAllT17GQ nIQPGAIQGQC PQnVInGn QV \/GAInnQ n (` QUAI I IAICTAI I C U rn G� � � w coo � w oC �DLo Li Oo W U)(D�W w U)LU J H Y H v �u DD _ co w T — UzvC'= I— t — N� U v N Q 07 � Lu z U) m 04 0 w U) z w U m d U Z Q locl� w Y rn z cd w J 18014 0 0 0 0 0 0 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL RESTROOM PLAN AND TYPICAL ELEVATIONS 8mO PLOT DATE: May 10, 2018 - 7:41 pm U MIRROR MTD @ 40" A.F.F. Z MAX TO BOTTOM OF M.,y REFLECTING SURFACE .. LAV. �'' O INSULATE HOT WATER & DRAIN VERTICAL S.S. GRAB PIPES DRYER ICI 00 48" S.S. GRAB BAR BAR (IF RQ'D)/Z� T 0 NOTES: PAPER TOWEL DISPENSER L 1. TOP OF GRIPPING SURFACE T.S. COVER DISPENSER SHALL PULL STATION w " MAX > 0-25" BE MOUNTED 1 1/2" (MIN.) 14"MIN. / 17" MAX. �y TOTAL SEATS ACCESSIBLE SEATS THE BAR. SEE NOTESEBELOW [39'to 41" IIBELOW GRAB RAIL PROJECTION FROM WALL URINAL 2. 12 MINIMUM CLEAR 6" TO 12" MAX w � LLJ 1 - 20 1 ABOVE GRAB BAR — (] Ocn �- w a Phi U ti cy) z 21 - 40 2 z 36 S.S. GRAB BAR 2 0' g ¢ o o 0 gcr JLL ¢J LLJ � a w � � 00 N c _ 33" (EXCEPT @ w O ¢ o ¢ < Q — 41 - 60 3 �- TANK TOILETS, o z O¢ U¢� z U V U J 61 - 80 4 WHICH SHALL BE o o' w v v 2 9 CL O 2 2 Q� U � N Uj 81 -100 5 7"ti `�' z g O z v v �0 � y_ (p 101-120 s 19 U Z 2 19" TO 48" A.F.F. FOR OPERABLE " () 6 MAX. DEPTH x 30 MIN. WIDTH TOE 121 - 140 7 OPENING W/0 OBSTRUCTION CLEARANCE C\j Q FROM GRAB BAR SWITCHES 8" MIN. DEPTH x 30"MIN. THERMOSTAT co CV C� NUMBER OF ACCESSIBLE SEATS 10" MAX. 30" 30' 24" MAX. CONTROLS MOUNTED ON WIDTH KNEE SPACE o WIDE SIDE OF TOILET AREA FIRE ALARM $d Z MOUNTING HTS. & CLEARANCES FOR ACCESSIBILITY BY THE DISABLED N.T.S. 1 U) ' m CD S-O" MIN. (1525) M4 r f t PROTRUDING OBJECT Z 3'-0" MIN. ( 6" MAX. (150) U �o FREESTANDING OBJECT O EXAMPLE: DRINK MACHINE, ETC. MOUNTED ON POSTS OR ¢ J `" 28"-34" A.F.F. ) z � '- PYLON MAY OVERHANG 12" w O MAX FROM 2T TO 80' O 718"MAX TO ABOVE FINISH FLOOR 12" Z ¢ 0 � 0 cd co z -' = o 4° :z N I OBJECT PROJECTION FROM r CLEAR z GD T 0 Z Q 10" MAX > 10-24" MAX WALL BETWEEN 2T TO 80 0 FLOOR g 2 ABOVE FINISH FLOOR SHALL SPACE o 7 PROTRUDE NO MORE THAN z c� co TOILET PAPER co w n 4" 36" MIN. CLR. o N $ 4" MAX VERTICAL GRAB co 3a' IN ACCESSIBLE ROUTE r (100) BAR. SEE DTL 1 �Q�QO.DDo�oo \ Lu ELEVATION _ _ I \ \ OBJECT PROJECTION ( io FROM WALL LESS THAN 48 MIN2-8 w MIN. 2T ABOVE FINISH FLOOR 131/2" , U w _ 0 o O MAY PROTRUDE ANY MAX (815) ¢ z z0 �0' o a o O ao cc AMOUNT N ** IF TOILET STALL IS a Z Z CONDIMENTS FLOOR SHALL BE O U SLIP -RESISTANT SURFACE CONSTRUCTED OF SOLID WALLS w b - z WITHOUT 9" OF TOE CLEARANCE w s a........ � AND LEVEL WITH MAX 1/4 UNDER PARTITION, PROVIDE _ r' a � BD CHANGE IN LEVEL ADDITIONAL 6" WIDTH AND DEPTH 0 ¢ ' • a 05.10 SEATING AND TABLES N.T.S. 18 REACH RANGES N.T.S.114 INT. ACCESS. ROUTE CLEARANCES 1/2" = 1'-0" 1 O ACCESSIBLE URINAL 3/4 -1-0 8 STANDARD TOILET STALL N.T.S. 2 f" m w w J 8" 8" REQ'D IN MAX. REM IN CA ONLY 18014 CA ONLY SIGN POST OBSTRUCTION z O GRAB BAR SHALL BE 1-1/4" TO 2"MAX., F 4N_ OUTSIDE DIA.- TYPICAL z cr 0 w 1 4 v Zo z CLEAR Z Q p 12" MAX CLR. O SPACE 0 w w w m UOwLL � 17"MIN. 0 m C Z 2- 1/4"x& EXPANSION ANCHORS ATCl 0 Q K 0O � `$ MASONRY OR CONC. WALL 2- #10x2" J m f- _ z SCREWS AT WOOD OR STEEL STUD F O C� WALL-TYP. Q U~�= N O 48"MIN. ~BCD ~ 1/8"x2" BENT PLATE WELDED TO RAIL N z_ Q AND1/8"x3" DIAMETER MOUNTING r ACCESSIBLE ROUTE WALK PLATE @ 4'-0" CONTRACT DATE: 08.13.20 77 2"x6" BLOCKING AT WOOD STUD WALLS (OMIT BLOCKING AT MASONRY OR BUILDING TYPE: ONE-OFF CONC. WALL) - TYPICAL PLAN VERSION: ACCESSIBLE RESTROOM DOORS N.T.S. 15 PROTRUDING HAZARDS 1/2" =1'-0" 11 GRAB BAR 3" - T-0" 7 ACCESSIBLE LAVATORY 3/4"=T-a' 3 SITE NUMBER: STORE NUMBER: 19" 30" L 1. INDICATED DIMENSIONS, HEIGHTS, DEPTHS, AREAS AND OTHER GRAPHIC CLEAR INFORMATION ARE PROVIDED AS MINIMUMS THAT MUST BE MAINTAINED. THESE SUNRISE EATERY w MINIMUMS ARE BASED UPON YUM STANDARDS AND MAY EXCEED ADA MOUNT COAT HOOK ON o INSIDE OF TOILET STALL REINFORCED S.S. REQUIREMENTS. DOOR LATCH WITH THROUGH �� °C w THE DETAILS SHOWN ARE CONCEPTUAL ONLY AND INTENDED T 5915 GALL BLVD. BOLTED KEEPER. ADA o i� m O SHOW ZEPHYRHILLS, FL COMPLIANT c) _j � ABSOLUTE MINIMUMS AND SHALL BE COORDINATED WITH THE OTHER ®" U CONSTRUCTION DOCUMENTS ASSOCIATED WITH THIS PROJECT. w ¢ 2. 60" TURNING SPACE PERMITTED OVERLAP LIMITED TO 1 ARM OF T-SHAPED SPACE S.S. PULL (BOTH SIDES) CAN OVERLAP FIXTURE &DOOR CLEARANCE ON ALL ACCESSIBLECD '` h — — -DOOR CAN SWING INTO TURNING SPACE A MAXIMUM OF 12" TOILET STALLS. MOUNT ACCESSIBLE ROUTE PULLS BELOW LATCH 4811 3. RESTROOM, IN GENERAL, DOOR SWING MUST BE OUTSIDE OF HE FXTR CLEAR LL AND KEEPER. 19" 30" CLEAR FLOOR SPACE HOWEVER A DOOR CAN SWING INTO FIXTURE CLEAR FLOOR U- T CLEAR SPACE IF WHEELCHAIR SPACE 30"X48" IS PROVIDED BEYOND THE DOOR SWING. BOBRICK OR CHRISTY Q — — COMMERCIAL 8 2 4. TOILET ROOM MUST ALLOW FOR SIDE TRANSFER - 42" BETWEEN FIXTURES HARDWARE & SUPPLY NOTE: DOOR HOOKS 1 WAREHOUSE #039-6529 OR SIMILAR SHALL BE PLACED IN Z � o °C ACCESSIBILITY ACCESSIBLE STALLS co ADA COMPLIANT HOOK. BETWEEN 40' MIN TO U U REQUIREMENTS 48" MAX ABOVE FINISH CHRISTYHARDWARE.COM Q FLOOR 877-544-5400 M NOTE: P 1. AINTAIIIA16' MIN. CLEAR AISLE EGRESS PATHS TO EXIT NOTE: SEE DOOR SCHEDULE. AND DOOR SCHEDULE NOTES NOTE: SEE DOOR SCHEDULE. AND DOOR SCHEDULE NOTES 2. INT RNA NAL SYMBOL OF ACCESSIBILITY REQUIRED ON TOP EDGE OR FRONT OF ALL D ImO ACCESSIBLE TABLES. COAT HOOK N.T.S. 20 PARTITION DOOR LATCH @ PULL 18 CHANGES IN LEVEL N.T.S. 12 DINING ROOM SEATING CLEARANCES N.T.S. 8 GENERAL NOTES 4 PLOT DATE: May 10, 2018 - 7:42prr, TENANT FINISH ZEPHYRHILLS, FL A. ALL WORK SHALL CONFORM TO THE 6th EDITION OF THE FLORIDA BUILDING CODE (2017), AND ALL OTHER APPLICABLE CODES, STANDARDS, AND REGULATIONS OF THE CITY OF ZEPHYRHILLS, FLORIDA. B. IT IS INTENDED THAT A COMPLETE OCCUPIABLE BUILDING PROJECT IS PROVIDED. C. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION (A.I.A. A201 LATEST EDITION) ARE A PART OF THESE CONTRACT DOCUMENTS. A COPY IS ON FILE AT THE ARCHITECTS OFFICE. D. DO NOT SCALE THESE DRAWINGS. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD. ANY DISCREPANCIES IN THESE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO STARTING WORK. E. ALL PROPOSED SUBSTITUTIONS SHALL BE APPROVED BY THE ARCHITECT, IN WRITING, PRIOR TO INSTALLATION. F. SUBMIT, PAY FEES AND OBTAIN ALL PERMITS ASSOCIATED WITH THE PROJECT EXCEPT GENERAL BUILDING PERMIT. THIS INCLUDES, BUT IS NOT LIMITED TO ELECTRICAL, MECHANICAL, PLUMBING, FIRE SPRINKLER, OR OTHER RELATED FIRE PERMITS. ZEPHYR, LLC WILL PAY FOR "CONNECTION FEES" ASSOCIATED WITH UTILITY PERMITS. PAY FOR TEMPORARY FACILITIES FEES AS REQUIRED TO COMPLETE THE WORK IN A TIMELY MANNER. G. PROVIDE EACH SUBCONTRACTOR WITH A COMPLETE AGENCY -PERMITTED DRAWING SET AT TIME OF CONSTRUCTION. H. ALL ABBREVIATIONS INCLUDED FOLLOW INDUSTRY STANDARDS. CONTACT ARCHITECT IF ANY ABBREVIATIONS ARE NOT CLEAR. I. GC SHALL SUPPLY AND INSTALL ALL ASPECTS OF THE PROJECT DESCRIBED IN THIS DRAWING SET UNLESS OTHERWISE NOTED. SEE SCOPE OF WORK FOR EXCEPTIONS. J. GRAPHIC AND WRITTEN INFORMATION ON DRAWINGS SHALL BE COORDINATED WITH ALL TRADES PRIOR TO INSTALLATION. K. ALL MATERIALS STAGED TO BE USED FOR CONSTRUCTION SHALL BE PROTECTED FROM EXCESSIVE MOISTURE. IF THEY ARE EXPOSED TO MOISTURE THEY SHOULD BE ADEQUATELY DRIED BEFORE ENCAPSULATED INTO THE BUILDING. L. GENERAL CONTRACTOR SHALL PROVIDE PEST INSPECTION AND EXTERMINATION SERVICES PRIOR TO START OF WORK. PROVIDE INVOICES AND A REPORT FROM THE EXTERMINATION PROFESSIONAL TO THE OWNER. M. GENERAL CONTRACTOR SHALL PROVIDE WEEKLY CONSTRUCTION PROGRESS REPORTS TO THE OWNER, TENANT, AND ARCHITECT. PROJECT GENERAL NOTES NAME ROOM NAME 1 SHEET NUMBER 4OAX.X2 _� ELEVATION NUMBER 3 CEILING HEIGHT BLDG. SECTION LETTER X AX.X BLDG. SECTION SHEET DETAIL NUMBER X DIRECTION OF DETAIL DETAIL SHEET A REVISION NUMBER 0'-0" BLDG. HEIGHT ELEV REFERENCE POINT X ELEV. LETTER • ELEV. SHEET XO DOOR NUMBER O WINDOW NUMBER / DECOR ITEM NUMBER EXTERIOR WALL FINISH NUMBER OX KEY NOTE NUMBER X-000 EQUIPMENT NUMBER INTERIOR FINISH OINTERIOR WALL TYPE INTERIOR ELEVATION DESIGNATION IDSHEAR WALL TYPE (STRUCTURAL) XXX 000 EQUIPMENT / FIXTURE NUMBER (M.E.P.) INDICATES SUSTAINABLE DESIGN GREEN REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SHEETS FOR SPECIFIC SYMBOLS GENERAL DRAWING SYMBOLS nonnnern %einnii LEGAL JURISDICTION: CITY OF ZEPHYRHILLS, FLORIDA BUILDING CODE: 2017 FLORIDA BUILDING CODE FAMILY (6TH EDITION) BUILDING FOOTPRINT: 4873 S.F. FIRE AREA: 4916 S.F. (INCL. WALK-IN) OCCUPANCY: A2 TYPE CONSTRUCTION: TYPE II B-UNSPRINKLERED EXISTING BUILDING AREA AND OCCUPANT LOAD TYPE AREA FACTOR OCCUPANTS ASSEMBLY -STANDING AREA 200 S.F. 1:5 GROSS 40 ASSEMBLY -SEATING 1960 S.F. 1:15 GROSS 131 KITCHEN -COMMERCIAL 2325 S.F. 1:200 GROSS 12 TOTAL 183 OCCUPANTS PLUMBING FIXTURE CALCULATION WATER CLOSETS LAVATORIES DRINKING FOUNTAIN SERVICE SINK REQ./ ACTUAL REQ / ACTUAL REQ. / ACTUAL REQ. / ACTUAL MEN 2/ 2 112 1/ 0 (WATER AVAIL.) 1/ 1 WOMEN 2/2 1/2 UNISEX (EMPLOYEE) 1 PROVIDED 1 PROVIDED PROJECT SUMMARY REFER TO STRUCTURAL DESIGN CRITERIA REFER TO CIVIL DRAWINGS. LEGAL DESCRIPTION OWNER ARCHITECT ZEPHYR, LLC L.B. MANSKE ARCHITECTURE & DESIGN, INC. 7162 READING ROAD, STE 730 LEE B. MANSKE, AIA, NCARB CINCINATTI, OH 45237 2422 N. RUTGERS COURT WICHITA, KS 67205 316.749.5873 STRUCTURAL ENGINEER JOHN GUTHERMAN JR., P.E. 264 BUTTERCUP CIRCLE ALTAMONTE SPRINGS, FL 30714 407.701.0875 CIVIL ENGINEER MECHANICAL ENGINEER CORNELISON ENGINEERING & DESIGN, INC. JUSTIN HARDY, PE 38039 OLD 5TH AVENUE 33542 5014 KINGSBRIDGE PASS 813.788.7835 POWDER SPRINGS, GA 678.234.8156 ELECTRICAL ENGINEER GUIDO ALVAREZ, PE 5014 KINGSBRIDGE PASS POWDER SPRINGS, GA 678-234-8156 PROJECT DIRECTORY SEWER TELEPHONE (Company) (Company) (Address) (Address) (City, State, Zip) (City, State, Zip) Contact: Contact: Phone: Phone: WATER ROADS (Company) (Company) (Address) (Address) (City, State, Zip) (City, State, Zip) Contact: Contact: Phone: Phone: GAS OTHER (Company) (Company) (Address) (Address) (City, State, Zip) (City, State, Zip) Contact: Contact: Phone: Phone: ELECTRIC OTHER (Company) (Company) (Address) (Address) (City, State, Zip) (City, State, Zip) Contact: Contact: Phone: Phone: UTILITY CONTACTS TITLE SITE T1.0 TITLE SHEET CIVIL SITE EXISTING (CURRENTLY UNDER CONSTRUCTION) STRUCTURAL SHELL EXISTING (CURRENTLY UNDER CONSTRUCTION) ARCHITECTURAL A1.0 FLOOR PLAN A1.1 DOOR & WINDOW ELEVATION & SCHEDULE A3.0 ROOF PLAN A4.0 EXTERIOR ELEVATIONS A4.1 EXTERIOR ELEVATIONS A5.0 BUILDING SECTIONS A5.1 WALL SECTIONS A5.2 WALL SECTIONS A6.1 CONSTRUCTION DETAILS A7.1 REFLECTED CEILING PLAN ACCESSIBILITY ADA1.0 ACCESSIBILITY REQUIREMENTS MECHANICAL M0.1 MECHANICAL SCHEDULES AND DETAILS M0.2 MECHANICAL SPECIFICATIONS M1.0 MECHANICAL PLANS M1.1 MECHANICAL HOOD PLANS PLUMBING P0.1 PLUMBING SCHEDULES AND DETAILS P1.0 PLUMBING SANITARY PLAN P2.0 PLUMBING DOMESTIC WATER PLANS ELECTRICAL E0.0 ELECTRICAL GENERAL NOTES AND LEGEND E1.0 ELECTRICAL LIGHTING PLAN E2.0 ELECTRICAL POWER PLAN E3.0 MECHANICAL POWER PLAN E4.0 ELECTRICAL DETAILS SHEET INDEX • V M C) Z � ALb ~ � U7 00 W U Z a 18014 0 0 ti rn w W z w U J ED 60' z Q Q w Y z m w w J CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL TITLE SHEET T1.0 PLOT DATE: May 10, 2018 - 10:30pm J ELECTRICAL LEGEND F21 O FLUORESCENT TROFFER, TYPE AS NOTED q� tT' DUPLEX RECEPTACLE 18" AFF OR AS NOTED, NEMA 5-20R [A Lid FLUORESCENT TROFFER, TYPE AS NOTED SPO SURGE PROTECTION DUPLEX RECEPTACLE, 20A, 125V PROVIDE WITH EMERGENCY BALLAST HUBBELL CAT.NO HBL5360SA, NEMA 5-20R ® FLUORESCENT TROFFER, TYPE AS NOTED DUPLEX RECEPTACLE ABOVE COUNTER OR AS NOTED, NEMA 5-20R FLUORESCENT TROFFER, TYPE AS NOTED QUAD RECEPTACLE PROVIDE WITH EMERGENCY BALLAST 18" AFF OR AS NOTED, NEMA 5-20R Q RECESSED CAN FIXTURE, TYPE AS NOTED IG DUPLEX RECEPTACLE 18" AFF OR AS NOTED, NEMA 5-20R O RECESSED CAN FIXTURE, TYPE AS NOTED SPECIAL PURPOSE RECEPTACLE PROVIDE WITH EMERGENCY BALLAST 18" AFF OR AS NOTED, SEE SCHEDULE F--Q-� FLUORESCENT STRIP FIXTURE FQ/ JQ WALL / CEILING MOUNTED JUNCTION BOX ^ , �, jy WALL MOUNTED FIXTURE, TYPE AS NOTED 60/3/1 UNFUSED DISCONNECT SWITCH RATING/POLES/NEMA RATING 60/3/3R/40 FUSED DISCONNECT SWITCH PENDANT FIXTURE, TYPE AS NOTED RATING/POLES/NEMA RATING/FUSE SIZE PENDANT FIXTURE, TYPE AS NOTED ^- MOTOR PROVIDE WITH EMERGENCY BALLAST .��.j. TRACK LIGHT FIXTURE, TYPE AS NOTED �II GROUND EMERGENCY LIGHT 0 TELEPHONE OUTLET, PROVIDE 4" BOX SINGLE GANG PLASTER RING, 1" C STUBBED 6" ABOVE CEILING TELEPHONE OUTLET, PROVIDE 4" BOX EXIT/EMERGENCY LIGHT COMBINATION -T HALF SHADED- INDICATES SINGLE JACK, FULL SHADED INDICATES TWO JACKS. NETWORK WIRING SYSTEM: ® CEILING MOUNTED EXIT SIGN CAT 5E 110, RJ45 JACK WIRED TO SPEC 568B MODULAR JACK PROVIDE ONE JACK AND ONE POSITION IVORY FACEPLATE AT WALL MOUNTED EXIT SIGN SINGLE JACK LOCATIONS AND TWO AT DOUBLE LOCATIONS. CONTACT PHIL BENTON, 678-966-3335 FOR INFO. DOUBLE BOX, AS DESCRIBED ABOVE EXCEPT CONNECT 2 LINES SINGLE POLE SWITCH, 44" AFF V DIRECTLY FROM PUNCH BLOCK (D-MARK) TO DOUBLE BOX IN MANAGER' OFFICE TWO SINGLE POLE SWITCHES GANGED TOGETHER FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF THREE SINGLE POLE SWITCHES GANGED TOGETHER SINGLE BOX- MANAGER'S/FAX, DEDICATED ANALOG TELEPHONE 44" AFF ® LINE WITH RINGMASTER, CAT 5E, RJ11 - NOT TO BE ROUTED THROUGH TELEPHONE SYSTEM. TERMINATE AT PUNCH BLOCK THREE WAY SWITCH, 44" AFF (D-MARK) TWO THREE WAY SWITCHES GANGED TOGETHER SINGLE BOX- DSULSR DEDICATED ANALOG TELEPHONE LINE cl FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF 0 WITH RINGMASTER, CAT 5E, RA 1 - NOT TO BE ROUTED THRU TELEPHONE SYSTEM. TERMINATE AT PUNCH BLOCK (D-MARK) FOUR WAY SWITCH, 44" AFF q WALL BOX DIMMER 1000W UNLESS NOTED DIFFERENTLY SPEAKER STROBE 44" AFF $yip WEATHER PROOF SWITCH, 44" AFF HORN $M MOTOR RATED SWITCH, 44" AFF OR AS NOTED ® PULL STATION $OS COMBINATION SWITCH AND OCCUPANCY SENSOR, 44" AFF Q FIRE ALARM STROBE, MIN 75 CANDELA CEILING / WALL MOUNT $T DIGITAL TIMER SWITCH, 44" AFF DUCT MOUNTED SMOKE DETECTOR ®x CEILING MOUNTED OCCUPANCY SENSOR OS SMOKE DETECTOR �X WALL MOUNTED OCCUPANCY SENSOR, 44" AFF OH HEAT DETECTOR T� TIME CLOCK TS TAMPER SWITCH LJ� SINGLE DOME, CEILING AND WALL MOUNTED SECURITY FS FLOW SWITCH CAMERAS. FURNISHED AND INSTALLED BY OTHERS. ® PHOTO CELL RACEWAY CONCEALED IN WALL OR ABOVE CEILING 8" CONE SPEAKER IN CEILING _� RACEWAY EXPOSED EC TO PROVIDE BLACK SPEAKER (� 8" CONE SPEAKER IN WALL RACEWAY CONCEALED IN FLOOR SLAB, BELOW SLAB OR GRADE Y EC TO PROVIDE BLACK SPEAKER BELOW SLAB OR GRADE, OR UNDER RAISED ACCESS FLOOR VOLUME CONTROL DENOTES CONDUIT TURNING UP IN PLAN VIEW PLYWOOD EQUIPMENT BACKBOARD 3 DENOTES CONDUIT TURNING DOWN IN PLAN VIEW 4'X8' UNLESS NOTED OTHERWISE CCTV CLOSED CIRCUIT TELEVISION CAMERA STUB UP COAXIAL CABLE OUTLET XXXX SHORT CIRCUIT AVAILABLE CURRENT (NOTE: ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS AND ARE USED AS APPLICABLE TO THIS PROJECT) ABBREVIATIONS ELECTRICAL SPECIFICATIONS A. DEFINITIONS: 1. "PROVIDE": FURNISH AND INSTALL, COMPLETE AND READY FOR OPERATION. 2. "INSTALL": RECEIVE, MOUNT, AND CONNECT, COMPLETE AND READY FOR OPERATION. 3. "FURNISH": SUPPLY, DELIVER TO JOB SITE, PROTECT AND STORE. B. WORK INCLUDED: PROVIDE ALL LABOR, TOOLS, MATERIAL, EXCAVATION, BACKFILL, CUTTING, PATCHING, TESTING, ADJUSTING, AND TRADE COORDINATION REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL INSTALLATION, AS DESCRIBED ON THE DRAWINGS OR IN THE SPECIFICATIONS. C. CODES, RULES, AND REGULATIONS: COMPLY WITH ALL CODES ENFORCED BY THE LOCAL INSPECTION AUTHORITY, THE EDITION OF THE NATIONAL ELECTRICAL CODE BEING ENFORCED FOR THIS PROJECT BY THE LOCAL INSPECTION AUTHORITY, ALL APPLICABLE LAWS AND ORDINANCE, NFPA FIRE CODES, STANDARD BUILDING CODE. GIVE ALL NECESSARY NOTICES, OBTAIN ALL REQUIRED PERMITS, AND PAY ALL INSPECTION AND OTHER FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION OVER THE WORK. D. MATERIALS: ALL MATERIAL SHALL BE NEW, AND SHALL COMPLY WITH THE INDICATED STANDARDS. ALL MATERIAL SHALL BE UL LABELED OR UL LISTED. ALL MATERIAL SHALL BE OF A SUITABLE TYPE AND RATING FOR THE INTENDED USE, AND SHALL BE INSTALLED IN CONFORMANCE WITH THE INSTRUCTIONS AND RECOMMENDATIONS OF THE MANUFACTURER. E. DRAWINGS 1. THE DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL OF THE REQUIRED DETAILS OF THE WORK. ALL MATERIALS CUSTOMARILY CONSIDERED TO BE A PART OF THE ELECTRICAL WORK AND REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION SHALL BE PROVIDED WITHOUT ADDITIONAL COST TO THE OWNER. 2. THE CONTRACTOR SHALL REFER ALSO TO THE ARCHITECTURAL DRAWINGS AND TO THE DRAWINGS OF ALL OTHER TRADES TO COORDINATE THE ELECTRICAL INSTALLATION. WHERE ELECTRICAL EQUIPMENT IS SHOWN ON ARCHITECTURAL DRAWINGS OR DETAILS, THE EQUIPMENT SHALL BE INSTALLED AS SHOWN ON THE ARCHITECTURAL DRAWINGS. 3. EQUIPMENT OF OTHER TRADES IS SHOWN SCHEMATICALLY ON THE ELECTRICAL DRAWINGS. THE CONTRACTOR SHALL EXAMINE THE DRAWINGS OF THE TRADE PROVIDING THE EQUIPMENT BEFORE ROUGHING IN THE CONNECTIONS FOR IT. THE CONTRACTOR SHALL CONNECT THE EQUIPMENT WHERE ACTUALLY INSTALLED, INCLUDING WIRING THROUGH ANY LINE VOLTAGE CONTROLLERS, WITHOUT ANY ADDITIONAL COST TO THE OWNER. 4. PRIOR TO ROUGHING IN CIRCUITS FOR EQUIPMENT FURNISHED BY OTHER TRADES, AND PRIOR TO RELEASING FOR MANUFACTURE PANELBOARDS, STARTERS OR MOTOR CONTROL CENTERS FEEDING SUCH EQUIPMENT, THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL PROVISIONS BEING PLANNED WITH THE TRADE PROVIDING THE EQUIPMENT AND SUBMIT ANY CONFLICTS IN WRITING TO THE ARCHITECT. 5. THE ARCHITECT MAY DIRECT THE RELOCATION OF ANY ELECTRICAL OUTLET, FIXTURE, OR OTHER EQUIPMENT TO A LOCATION WITHIN 10 FEET OF THE LOCATION SHOWN ON THE DRAWINGS AT NO ADDITIONAL COST TO THE OWNER PROVIDED SUCH RELOCATION IS DIRECTED PRIOR TO THE INSTALLATION OF THE OUTLET, FIXTURE OR EQUIPMENT BEING RELOCATED. D. SUBMITTAL DOCUMENTS: PRODUCT DATA AND SHOP DRAWINGS SHALL BE SUBMITTED IN SIX COPIES TO THE ARCHITECT FOR REVIEW PRIOR TO THE RELEASE OF THE MATERIAL FOR MANUFACTURE. REVIEW OF SUBMITTALS BY THE ARCHITECT WILL BE ONLY FOR GENERAL CONFORMANCE WITH THE DRAWINGS AND SPECIFICATIONS. REVIEW WILL BE MADE ONLY OF INFORMATION CLEARLY AND SPECIFICALLY INDICATED IN THE SUBMITTAL, AND DOES NOT IMPLY THE ACCEPTABILITY OF DETAILS WHICH ARE NOT SO DESCRIBED IN THE SUBMITTAL. REVIEW OF THE SUBMITTAL DOCUMENTS BY THE ARCHITECT DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO COMPLY WITH ALL REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. SUBMITTAL IS REQUIRED FOR PANELBOARDS AND LOADCENTERS, LIGHT FIXTURES, WIRING DEVICES, FIRE ALARM DEVICES, AND SURFACE ALUMINUM RACEWAY. G. AS -BUILT DRAWINGS: AS -BUILT DRAWINGS SHALL BE MAINTAINED AT THE JOBSITE, AND SHALL BE AVAILABLE FOR REVIEW DURING CONSTRUCTION. AS -BUILT DRAWINGS SHALL BE KEPT CURRENT DURING THE COURSE OF CONSTRUCTION OF THE WORK. SUBMIT AS -BUILT DRAWINGS TO THE ARCHITECT AT THE COMPLETION OF THE PROJECT. H. TESTING: TEST ALL PARTS OF THE WORK TO VERIFY COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS. VERIFY TIGHTNESS OF ALL MECHANICAL AND ELECTRICAL CONNECTIONS. VERIFY INTEGRITY OF ALL WIRING SYSTEMS TO ASSURE CONTINUITY, ABSENCE OF UNINTENTIONAL GROUNDS, AND INTEGRITY OF REQUIRED GROUNDS. I. CHANGE REQUEST (CHANGE ORDER) APPROVAL: CHANGE REQUESTS WILL NOT BE CONSIDERED UNLESS THE CONTRACTOR'S DETAILED LABOR AND MATERIAL ESTIMATE DESCRIBING THE CHANGE IS SUBMITTED TO THE ARCHITECT ALONG WITH THE CHANGE REQUEST, WITH MATERIAL PRICES AND LABOR UNITS ASSIGNED TO EACH LINE ITEM OF THE ESTIMATE. MATERIAL PRICES SHALL BE THE ACTUAL PRICE PAID BY THE CONTRACTOR FOR MATERIAL PURCHASED OR THE ACTUAL PRICE QUOTED TO THE CONTRACTOR BY THE MATERIAL VENDOR PROPOSED BY THE CONTRACTOR. J. COORDINATION WITH THE WORK OF OTHERS: COORDINATE WITH EACH TRADE FURNISHING EQUIPMENT REQUIRING ELECTRICAL SERVICE TO INSURE THAT THE CHARACTERISTICS SHOWN ON THE DRAWINGS FOR THE CIRCUIT SERVING THE EQUIPMENT ARE COMPATIBLE WITH THE REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED. CIRCUIT BREAKERS, FUSES, DISCONNECT SWITCHES AND ASSOCIATED BRANCH CIRCUITS SHOWN ON THE DRAWINGS TO FEED HVAC EQUIPMENT, KITCHEN EQUIPMENT, ELEVATOR MOTORS, AND OTHER EQUIPMENT HAVE BEEN SELECTED BASED UPON THE CHARACTERISTICS OF EQUIPMENT BY ONE MANUFACTURER AND MAY NOT BE CORRECT FOR THE EQUIPMENT BEING PROVIDED BY THE CONTRACTOR. THE CONTRACTOR SHALL DETERMINE THE OPERATING CHARACTERISTICS OF THE EQUIPMENT ACTUALLY BEING PROVIDED AND SHALL PROVIDE AT NO ADDITIONAL COST TO THE OWNER CIRCUIT BREAKERS, FUSES, DISCONNECT SWITCHES AND BRANCH CIRCUITS AS REQUIRED BY THAT EQUIPMENT. K. EXISTING WORK: THE EXISTING ELECTRICAL INSTALLATION SHALL REMAIN AS -IS AND IN OPERATION EXCEPT WHERE OTHERWISE REQUIRED. GIVE WRITTEN NOTICE OF ANY UNFORESEEN EXISTING CONDITIONS WHICH MAY AFFECT THE WORK. WORK INVOLVING EXISTING SYSTEMS OR EXISTING SPACES SHALL BE ACCOMPLISHED WITH MINIMUM INCONVENIENCE TO THE OWNER, AND SHALL BE DONE IN A MANNER AND TIME APPROVED BY THE OWNER. ANY INTERRUPTIONS SHALL BE DURING TIMES DESIGNATED BY THE OWNER. L. DEMOLITION: IN THE AREA SHOWN ON THE ARCHITECTURAL DRAWINGS TO BE DEMOLISHED REMOVE ALL EXISTING A, AMPS AMPERES FLA FULL LOAD AMPERES NO NORMALLY OPEN, CONDUITS, CONDUCTORS, BOXES, FIXTURES, SERVICE ENTRANCE CONDUCTORS, DISTRIBUTION EQUIPMENT, AND A/C AIR CONDITIONER GND GROUND NUMBER ALL OTHER ELECTRICAL EQUIPMENT NOT SHOWN TO REMAIN. UNLESS OTHERWISE INDICATED, MATERIAL BEING AC ALTERNATING CURRENT GALV GALVANIZED NTS NOT TO SCALE REMOVED INCLUDING WIRE, CONDUIT, AND HANGING MATERIALS BEING REMOVED SHALL BECOME THE PROPERTY AF AMPERE FRAME PNL PANELBOARD OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES. EQUIPMENT NOTED TO REMAIN THE AFF ABOVE FINISHED FLOOR GRS GALVANIZED RIGID STEEL PVC POLYVINYL CHLORIDE PROPERTY OF THE OWNER SHALL BE STORED ON SITE AS DIRECTED BY THE ARCHITECT. COORDINATE WITH OTHER AFG ABOVE FINISHED GRADE GFCI GROUND FAULT RGS RIGID GALVANIZED TRADES AND DISCONNECT MOTORS, HEATERS, OR OTHER EQUIPMENT AS REQUIRED FOR THE DEMOLITION OF AIC AMPERE CIRCUIT INTERRUPTER STEEL CONDUIT OTHER TRADES WORK. CUT OFF ALL IN FLOOR CONDUITS, GRIND SMOOTH WITH FLOOR AND PREPARE FOR GFI GROUND FAULT INTERRUPTER RMC RIGID METALLIC PATCHING BY OTHERS. REMOVE CONDUCTORS AND DEVICES FROM WALL AND CEILING OUTLETS AND PREPARE INTERRUPTING CURRENT HD HEAT DETECTOR CONDUIT (GALVANIZED) OUTLET FOR PATCHING BY OTHERS. CONTRACTOR SHALL DENOTE ALL DEMOLISHED CIRCUITS ON EXISTING PANEL AL ALUMINUM HP HORSEPOWER RMS ROOT -MEAN -SQUARE DIRECTORIES AND NOTE ALL SPARE BREAKERS. ANSI AMERICAN NATIONAL STANDARDS INSTITUTE IMC INTERMEDIATE METAL CONDUIT RNC RIGID NON-METALLIC ISC INTERRUPTING SHORT CIRCUIT CONDUIT M. BASIC MATERIALS AND METHODS: AWG AMERICAN WIRE GAUGE IG ISOLATED GROUND SCA SHORT CIRCUIT BC BARE COPPER INST INSTANTANEOUS AVAILABLE 1. ALL WORK SHALL BE SUPPORTED FROM STRUCTURAL ELEMENTS OF THE BUILDING, EXCEPT BKBD BACKBOARD JB JUNCTION BOX SWBD SWITCHBOARD CEILING MOUNTED EQUIPMENT SUCH AS LIGHT FIXTURES, DETECTORS, REMOTE LAMPS, ETC. CEILING C CONDUIT KAIC KILO (THOUSAND) AMPERES SWGR SWIT ITCHGEAR MOUNTED EQUIPMENT SHALL BE SUPPORTED FROM CEILING STRUCTURAL MEMBERS, INDEPENDENT OF CB CIRCUIT BREAKER INTERRUPTING CAPACITY TBD TO DETERMINED CEILING TILES. SIZE AND SPACING OF SUPPORTS SHALL BE DETERMINED BY THE LOAD TO BE SUPPORTED SUCH CKT CIRCUIT KCMIL KILO (THOUSAND) TCP TEMPERATURE CONTROL THAT THE WORKING LOAD OF SUPPORTS WILL NOT EXCEED A SAFETY FACTOR OF 4:1. PLASTIC ANCHORS CU COPPER ARE NOT ACCEPTABLE. ELECTRICAL WORK SHALL NOT BE SUPPORTED FROM PIPING, DUCTS, OR WORK DIST DISTRIBUTION CIRCULAR MILS PANEL OF OTHER TRADES. KV KILO (THOUSAND) VOLTS TD TIME DELAY DN DP DOWN DISTRIBUTION PANEL KVA KILO (THOUSAND) TEL TELEPHONE 2. PROVIDE ENGRAVED PLASTIC NAMEPLATES FOR ALL SWITCHBOARDS, PANELBOARDS, MOTOR CONTROL DWG DRAWING VOLT-AMPERES TVSS TRANSIENT VOLTAGE CENTERS, STARTERS, DISCONNECTS, PRIMARY SELECTOR SWITCHES, AND TRANSFORMERS. INDICATE EB ENCASED BURIAL KW KILO (THOUSAND) WATTS SURGE SUPPRESSION EQUIPMENT NAME, CIRCUIT SOURCE AND NUMBER, CIRCUIT SIZE, AMPERE RATING, VOLTAGE AND PHASE. EC EMPTY CONDUIT KWH KILO (THOUSAND) WATT-HOURS TYP TYPICAL NAMEPLATES SHALL BE BLACK BACKGROUND LAMACOID PLASTIC WITH 0.25" WHITE LETTERS. LFMC LIQUID -TIGHT FLEXIBLE UG UNDERGROUND EEW ENERGIZED ELECTRICAL WORK METAL CONDUIT EGC EQUIPMENT GROUNDING MCB MAIN CIRCUIT BREAKER UL UNDERWRITER'S LABORATORIES CONDUCTOR MCM THOUSAND CIRCULAR MILS LION UNLESS OTHERWISE ELR END -OF -LINE RESISTOR MCCB MOLDED CASE UNDERGROUND PULLBOX EWC ELECTRIC WATER COOLER MLO MAIN LUGS ONLY V VOLTS <E> EXISTING N NEUTRAL VA VOLT-AMPERES <ER> EXISTING TO REMAIN NEC NATIONAL ELECTRICAL VFD VARIABLE <EX> EXISTING CODE FREQUENCY DRIVE FA FIRE ALARM NESC NATIONAL ELECTRICAL WH WATER HEATER FAA FIRE ALARM ANNUNCIATOR SAFETY CODE WP WEATHERPROOF FACP FIRE ALARM CONTROL PANEL NIC NOT IN CONTRACT WT WATERTIGHT NL NIGHT LIGHT XFMR TRANSFORMER 3. ALL PENETRATIONS OF FIRE RATED WALLS, SLABS, PARTITIONS, AND CEILINGS SHALL BE FIREPROOFED WITH A U.L. LISTED SYSTEM THAT WILL MAINTAIN THE ORIGINAL FIRE RATING OF THE PENETRATED STRUCTURE. ALL FIREPROOFING MATERIALS APPLIED AT ANY ONE PENETRATION SHALL BE THE PRODUCT OF ONE MANUFACTURER AND SHALL BE APPLIED AS DESCRIBED BY THE UL FIREPROOFING SYSTEM BEING CONSTRUCTED. FIREPROOFING OF SLEEVES, CABLE TRAYS, TROUGHS, AND NIPPLES TO BE USED FOR LOW VOLTAGE CABLES SHALL BE INDEFINITELY NON -HARDENING AND REMOVABLE WITH COMMON HAND TOOLS. 4. BACKBOARDS SHALL BE 8 FT. HIGH BY LENGTH SHOWN ON THE DRAWINGS AND SHALL BE UL LABELED FIRE TREATED PLYWOOD. 5. PROVIDE ALL POWER WIRING AND CONNECTIONS FOR ALL ELECTRICALLY OPERATED EQUIPMENT. POWER WIRING INCLUDES WIRING THROUGH ANY LINE VOLTAGE CONTROL DEVICES, SUCH AS THERMOSTATS AND MANUAL STARTERS. INSTALL ALL STARTERS AND CONTACTORS EXCEPT THOSE FURNISHED AS AN INTEGRAL PART OF THE EQUIPMENT. 6. CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT NOT INSTALLED IN A PLENUM SPACE SHALL BE MADE WITH A SHORT LENGTH OF LIQUIDTIGHT FLEXIBLE CONDUIT, MINIMUM 18", INSTALLED IN A MANNER TO PERMIT MOVEMENT OF EQUIPMENT. 7. PERFORM ALL EXCAVATING, BACKFILLING, CUTTING AND REPAIRING REQUIRED FOR INSTALLATION OF ELECTRICAL WORK. 8. CONTRACTOR SHALL X-RAY FLOOR SLABS, WALLS, OR CEILING CONCRETE PRIOR TO ALL CORE DRILLINGS. N. CONDUIT: FEEDERS AND BRANCH CIRCUIT HOME RUNS SHALL BE CONSTRUCTED OF EMT WITH ALL STEEL RAINTIGHT OR SET -SCREW FITTINGS. CONNECTORS SHALL BE INSULATED THROAT TYPE. PROVIDE METALLIC BUSHINGS WITH PLASTIC INSERTS FOR 3" OR LARGER. CONDUITS FEEDING OR CONNECTING TO EQUIPMENT PROVIDED BY OTHER TRADES SHALL NOT BE INSTALLED UNTIL SUCH EQUIPMENT IS INSTALLED OR UNTIL SPECIFIC ROUGH -IN INSTRUCTIONS ARE PROVIDED BY THE TRADE PROVIDING THE EQUIPMENT. UNLESS OTHERWISE INDICATED, CONDUITS SHALL BE CONCEALED. RACEWAYS INSTALLED IN OR UNDER SLABS, ON GRADE, OR AS EXTERIOR DUCT BANKS SHALL BE PVC SCHEDULE 40 OR 80. RUN EXPOSED CONDUITS PARALLEL OR PERPENDICULAR TO STRUCTURAL ELEMENTS. TWO OR MORE RACEWAYS RUN TOGETHER SHALL BE INSTALLED ON GANG TRAPEZE TYPE HANGERS. SUCH RACEWAYS ASSEMBLIES SHALL BE RUN PARALLEL OR PERPENDICULAR TO STRUCTURAL ELEMENTS. CONDUITS EMBEDDED IN SLABS SHALL HAVE A MINIMUM OF 1" COVER OF CONCRETE ON ALL SIDES. OUTSIDE DIAMETER OF CONDUIT SHALL NOT EXCEED 1/3 OF THE SLAB THICKNESS. PROVIDE 0.25" NYLON PULL TAPE IN ALL EMPTY CONDUITS. BRANCH CIRCUITS MAY UTILIZE TYPE MC ARMORED CABLE ASSEMBLY WITH COPPER CONDUCTORS AND FULL SIZE EQUIPMENT GROUNDING CONDUCTORS FOR INDIVIDUAL DROPS TO DEVICES. TYPE MC CABLE SHALL BE SUPPORTED AT 48" INTERVALS AND SHALL NOT LAY ON THE CEILING GRID OR INTERFERE WITH THE REMOVAL OF CEILING. 0. CONDUCTORS: ALL BUILDING WIRE SHALL BE 600 VOLT RATED THHN OR THWN COPPER, STRANDED FOR SIZES #8AWG AND LARGER, SOLID FOR SIZES 10 AND SMALLER UNLESS APPLIED FOR CONTROL. ALL BUILDING WIRE AND SPECIAL CABLES FOR SYSTEMS SHALL BE INSTALLED IN A RACEWAY. ALL WIRE AND CABLE SHALL BE DELIVERED TO THE JOBSITE IN ORIGINAL UNBROKEN PACKAGES, CARTONS OR REELS, WITH THE MANUFACTURERS NAME, UL LABEL, AND CHARACTERISTICS OF THE PRODUCT PLAINLY VISIBLE. ALL WIRE AND CABLE SHALL BE MANUFACTURED IN THE UNITED STATES OF AMERICA. WIRES SHALL BE COLOR CODED AS FOLLOWS (A,B,C,N,G): 120/208-BLACK, RED, BLUE, WHITE, GREEN; 480/277 - BROWN, ORANGE, YELLOW, GRAY, GREEN. SPLICES SHALL BE COMPRESSION TYPE. CONTROL CONDUCTORS SHALL BE TERMINATED WITH INSULATED CONNECTORS, T&B STAKON. 120 VOLT CIRCUITS WITH HOMERUN LENGTH OVER 125 FEET AND 277 VOLT CIRCUITS WITH A HOMERUN LENGTH OVER 250 FEET SHALL HAVE #10 MINIMUM HOMERUN CONDUCTORS. ALL THREE PHASE BRANCH CIRCUITS WITH A COMMON NEUTRAL SHALL HAVE #10 MINIMUM NEUTRAL. P. BOXES: OUTLET BOXES SHALL BE SHEET STEEL, MINIMUM 4" SQUARE, MINIMUM 1.5" DEEP, WITH PLASTER RING IN PLASTER OR BRICK CONSTRUCTION. OUTLETS BOXES IN POURED CONCRETE SHALL BE CONCRETE RINGS. MASONRY BOXES SHALL BE USED IN MASONRY OR TILE CONSTRUCTION. OUTLET BOXES FOR SURFACE ALUMINUM RACEWAY SHALL BE 4-11/16 WITH PLASTER RINGS ORIENTED HORIZONTALLY. BOXES SHALL BE SECURELY ANCHORED IN PLACE, AND SHALL BE SUPPORTED INDEPENDENT OF THE RACEWAY SYSTEM. PULL BOXES SHALL BE GALVANIZED SHEET STEEL, MINIMUM 12 GAUGE, WITH SCREW COVERS, AND WELDED CONSTRUCTION. WELDS SHALL BE COLD GALVANIZED. USING PERMANENT WATER PROOF WIDE BLACK MARKER, CLEARLY LABEL COVER OF ALL BRANCH CIRCUIT JUNCTION AND PULL BOXES WITH PANEL AND CIRCUIT NUMBER OF CIRCUITS CONTAINED IN OR PASSING THROUGH THE BOX. BRANCH CIRCUIT AND FEEDER JUNCTION AND PULL BOXES USED WITH EMERGENCY FEEDERS AND CIRCUITS SHALL BE PAINTED RED. PROVIDE P-TOUCH OR DYMO LABELS ON COVER OF EACH FEEDER PULL OR JUNCTION BOX INDICATING FEEDER DESIGNATION, SOURCE, LOAD, AND VOLTAGE. Q. WIRING DEVICES: SWITCHES FOR LIGHTING CIRCUITS SHALL BE 120/277 VOLT, 20 AMP, A.C. ONLY, QUIET TYPE, WITH GROUND BONDING SCREW, SPECIFICATION GRADE. MOMENTARY CONTACT SWITCHES SHALL BE SINGLE POLE DOUBLE THROW, CENTER OFF GE #5935 OR EQUAL. DUPLEX RECEPTACLES SHALL BE 15 AMP HUBBELL 5262 OR EQUAL. DEDICATED DUPLEX RECEPTACLES SHALL BE ORANGE 20AMP HUBBELL IG5362 OR EQUAL. SPECIAL RECEPTACLES SHALL BE OF SIMILAR CONSTRUCTION. FACE PLATES SHALL BE SMOOTH NYLON OR THERMOSET PLASTIC. ADJACENT OUTLETS SHALL BE INSTALLED IN MULTI -GANG BOXES WITH A SINGLE MULTI -GANG FACE PLATE. RECEPTACLES CONNECTED TO AN EMERGENCY CIRCUIT SHALL BE RED. COORDINATE COLOR OF DEVICES AND FACEPLATE WITH ARCHITECT. R. GROUNDING: ALL FEEDERS AND BRANCH CIRCUITS SHALL BE PROVIDED WITH INSULATED GREEN EQUIPMENT GROUNDING CONDUCTOR. CONDUIT GROUNDS ONLY ARE NOT PERMITTED. S. LIGHTING: SPARE FLUORESCENT LAMPS SHALL MATCH BUILDING STANDARD UNLESS OTHERWISE NOTED. INCANDESCENT LAMPS SHALL BE 130VOLT. NEW BALLASTS SHALL BE SOILD STATE ELECTRONIC. EXIT FIXTURES SHALL MATCH BUILDING STANDARD. FIXTURE LOCATIONS SHALL BE AS SHOWN ON THE REFLECTED CEILING PLAN. PROVIDE LAY -IN FIXTURES WITH TWO REMOVABLE CLIPS ATTACHING FIXTURE TO CEILING GRID. FLANGED FIXTURES SHOWN TO BE INSTALLED IN CONTINUOUS ROWS SHALL NOT HAVE INTERMEDIATE FLANGES. ALL PENDANT FIXTURES SHALL BE MOUNTED TO STRUCTURE. SEISMIC SUPPORT WIRES AND/OR COMPRESSION STRUTS FOR LAY -IN FIXTURES SHALL BE SUBJECT TO LOCAL AHJ LATEST REQUIREMENTS. T. FIRE ALARM DEVICES: NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH EXISTING BUILDING ADDRESSABLE FIRE ALARM SYSTEM. INSTALL NEW DEVICES AND CONNECT TO NEAREST SIGNALING OR NOTIFICATION DEVICE CIRCUIT WITHIN THE AREA. CONTRACTOR SHALL VERIFY CIRCUIT HAS CAPACITY FOR ADDED LOAD. SYSTEM SHALL BE CERTIFIED BY FIRE ALARM VENDOR AFTER COMPLETION OF WORK. U. PANELBOARDS: DEAD FRONT PANEL CONSTRUCTION WITH SEPARATELY MOUNTED INTERIOR TRIM. MAIN AND BRANCH DEVICES SHALL BE BOLT -ON. MULTI -POLE BREAKERS SHALL BE COMMON TRIP. WIDTH SHALL NOT EXCEED 22" FOR PANELBOARD AND ENCLOSURE SHALL MATCH BUILDING STANDARD. PROVIDE GROUND BUS IN PANELBOARD AND PROVIDE DEVICE MOUNTING HARDWARE WHERE A SPACE IS SCHEDULED. PANEL AND OCPD SHORT CIRCUIT RATINGS SHALL BE AT LEAST 10% GREATER THAN AVAILABLE SHORT CIRCUIT CURRENT AT PANELBOARD. V. DRY -TYPE TRANSFORMERS: TRANSFORMERS SHALL BE DRY -TYPE, ENCLOSED, SELF -COOLED, VENTILATED TYPE, DEAD -FRONT DRIP PROOF. PRIMARY AND SECONDARY TAPS SHALL BE ACCESSIBLE FROM THE FRONT. TRANSFORMERS SHALL MEET OR EXCEED BUILDING STANDARD TRANSFORMERS SPECIFICATIONS. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR IN THE PRIMARY FEED TO THE TRANSFORMER, SUPPLEMENTAL GROUND TO NEAREST ACCESSIBLE PRIMARY STRUCTURAL MEMBER OR EQUIPMENT ROOM GROUND BUS BAR. SIZE PER NEC AND RUN IN CONDUIT WITH BOND BUSHING AT EACH END. NEUTRAL AND GROUNDING CONDUCTOR SHALL BE BONDED TO ENCLOSURE. SF�9F1 E Noo W74056 S OF SF�0RIDP•��`;;`� o Q G ICi0 Digitally signed 4 z by Guido Inoa J nOa Alvarez Date:2018.05.10 A I Va reZ m 17:29:38-04'00' Q U z Q Q Ui U) Z Q cm w w J 0 ' • CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD, ZEPHYRHILLS, FL ELECTRICAL GENERAL NOTES & LEGNED EO.0 PLOT DATE: May 10, 2018 - 5:25pm EXTEND TO SWITCH LOCATION IDENTIFIED IN NOTE 4. LOCATE SWITCHES IDENTIFIED IN NOTE 3, IN THIS GENERAL LOCATION. COORDINATE WITH THE OWNER ON THE EXACT LOCATION PRIOR TO INSTALLATION. SEE TROFFER HANGING DETAIL THIS SHEET FOR SUPPORT REQUIREMENTS. PROVIDE SINGLE SWITCH FOR EXTERIOR LIGHTS. CIRCUIT THRU PHOTOCELL AND TIME CLOCK. ELECTRICAL LIGHTING PLAN. LUMINAIRE DESIGNATION PART NUMBER OR DESCRIPTION COLOR DESCRIPTION REMARKS VOLTAGE LAMPING COLOR CRI WATTS QTY TEMP. A CREE ZR SERIES #ZR24 40L 40K 10V WHITE RECESSED ZX4' LAY -IN TROFFER UNV LED 4000K 90 44 27 B CREE RC6-12W CAN HOUSING WITH CR6-800L WHITE RECESSED 6" DOWNLIGHT 120V LED 3500K 90 12 73 C CREE ZR SERIES #ZR14 40L 40K 10V WHITE RECESSED 1'X4' LAY -IN TROFFER UNV LED 4000K 90 44 4 EM CREE EXML1 RCW WHITE EGRESS DUAL HEAD 120V FURNISHE 5 13 D BLACK SURFACE DUAL HEAD COMBO DUAL SIDE WHITE EX BEST LIGHTING #CXTEU2RB-RC W/RED EM FIXTURE W/ REMOTE OR BLACK FINISH AS 120 FURNISHED 3500 K 86 LETTERS HEAD CAPABILITY CALLED FOR ON EXZ NORA #NE932 BLACK SURFACE MOUNTED REMOTE 120 F FURNISHED 3500 K 86 HEAD U ONO Z It o G� cy') Z W (.0 v- N Lo A Oo U ti co Z _ �rnco�w [�w02U UzUco= N U Ir N Q cn ct cn LIJ Z Cn 00 `� \ �\N0E N C vq9 �i T" NQ74056 �k - )••. S OF ol �' SS�OIVP►1-��:``� STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL ELECTRICAL LIGHTING PLOT DATE: May 10, 2018 - 5:26pm " n I�' A-42 \x i ELECTRICAL POWER PLAN. GFI .. A-42 GFI A-38 GFI POWER AND SYSTEMS NOTES: v Z 1. PROVIDE BLACK RECEPTACLES AND COVER PLATES IN THE ►� PUBLIC AREAS AND FOOD PRODUCTION AREA. ALL RECEPTACLES IN FOOD PREP AREAS OR KITCHEN SHALL BE V co GFI TYPE. zrlo 2. PROVIDE 3' X 4' X 3/4" FIRE RESISTANT PLYWOOD BACKBOARD l�• ^ N PAINTED WHITE FOR TELEPHONE SYSTEM. CONNECT #6 AWG, V gz Q INSULATED, STRANDED, COPPER GROUND WIRE FROM TELEPHONE SYSTEM TO GROUND BUS AT MAIN PANEL. L 3. PROVIDE DISCONNECT SWITCH UP HIGH AT SIGN FOR A OCD LIJ co z SIGNAGE CIRCUITS AS REQUIRED BY NEC 600. SIGNS SHALL BE RUN THROUGH A CONTACTOR, COORDINATE 000 L11 REQUIREMENTS AND MOUNTING LOCATION WITH OWNER AND W (n Lf) U LANDLORD. V Y 0) J 4. ALL RECEPTACLES IN FOOD PREP AREAS OR KITCHEN SHALL ~ Q ;' U BE GFI TYPE. D = Cfl LLJ 5. SEE REFRIGERATION MANUFACTURERS ELECTRICAL V Z U co _- DRAWINGS FOR ADDITIONAL POWER AND CONTROL WIRING. NN > () PROVIDE COMPLETE INSTALLATION, INCLUDING ALL FIELD > Iz SUPPLIED MATERIAL AND LABOR. CONTRACTOR TO PROVIDE ir I Q PROPER CONDUIT SEALING TO CONDUITS AND RACEWAYS N U) EXPOSED TO DIFFERENT TEMPERATURES AS PER NEC U) 300.7(A). PRIOR TO THE PIPING INSULATION, PROVIDE HEAT Lu TAPE FOR ALL CONDENSATE PIPING IN THE FREEZER. z 6. PROVIDE JUNCTION BOX AND CONDUIT THROUGH SEALED Cn OPENING FOR CONTROL WIRING POWER. WIRING TO D MECHANICAL UNITS ON THE ROOF. COORDINATE EXACT m EQUIPMENT LOCATIONS WITH MECHANICAL DRAWINGS PRIOR TO INSTALLATION. a 7. EXTERIOR RECEPTACLE SHALL BE "WEATHER RESISTANT" TYPE AND LABELED ACCORDINGLY BY THE MANUFACTURER. WEATHER PROOF COVER SHALL BE PROVIDED THAT IS WEATHER PROOF WHILE IN USE. THE RECEPTACLE SHALL BE GFI TYPE. 8. NETWORK WIRING SYSTEMS: PROVIDE OUTLET BOX (4X4 BOX •��GOANS'/ 9F� AND 1 1/2"C AT 12 PORT IN MANAGER'S OFFICE) WITH PULL ` �� STRING TO OPEN END 6" ABOVE CEILING FOR CAT 5E CABLE. '? CABLE BY OTHERS. OR COORDINATE WITH OWNER PROVIDED N0�7 SYSTEM. 9. REMOTE GLAZING HOOD EMERGENCY GAS SHUT OFF SWITCH AND RESET RELAY. MOUNT 48" AFF. PROVIDE 2"X6" PLASTIC S o LAMINATE "GAS RESET" SIGN ON RESET RELAY. COORDINATE ol'•'cCpRIDP••'.` WITH HVAC DRAWINGS AND HOOD INSTALLATION SHOP �� ss/ ....... 0) DRAWINGS. ��iil� Q w 10. WP ELECTRICALLY HELD REMOTELY CONTROLLED GAS SHUT z ui OFF VALVE, FURNISHED AND INSTALLED BY PLUMBING U CONTRACTOR, ELECTRICAL CONTRACTOR SHALL MAKE ALL J ELECTRICAL CONNECTIONS TO MAKE SYSTEMS OPERATIONAL. SEE PLUMBING DETAILS OF GAS PIPING. cm VERIFY OPERATION IN ACCORDANCE WITH NFPA 96 FOR Q SHUTTING DOWN THE SUPPLY FAN WHEN THE HOOD FIRE b SUPPRESSION SYSTEM IS ACTIVATED. COORDINATE WITH z MECHANICAL CONTRACTOR. PROVIDE ALL FIELD -INSTALLED Q MATERIALS AND LABOR REQUIRED FOR A COMPLETE Q OPERATING SYSTEM. L 11. AT NOTED DISCONNECT SWITCHES PROVIDE TYPE RK-1 FUSE Q KIT, VERIFY MAXIMUM OVERCURRENT PROTECTION RATING 2. WITH EQUIPMENT NAMEPLATE AND PROVIDE FUSES PER m Lu RISER KEY NOTE 6 TO MATCH MANUFACTURER'S MAXIMUM _Lu j OVERCURRENT PROTECTION RECOMMENDATIONS. 12. CONNECT WEATHERPROOF PUSHBUTTON AT REAR ENTRANCE TO BUZZER ON BELUBUZZER UNIT IN THE PRODUCTION ROOM AND TO THE BUZZER IN THE OFFICE ROOM. CONNECT PUSHBUTONS TO BUZZERS. PROVIDE 120V CONNECTION AS REQUIRED. 13. PROVIDE "AS BUILT" PANEL SCHEDULES TO HONEYBAKED OWNER AND A TYPED SCHEDULE IN PANELBOARD. 18014 GENERAL KITCHEN NOTE: 1. THIS PHASE DOES NOT INCLUDE KITCHEN EQUIPMENT. RECEPTACLES SHOWN ARE FOR FUTURE EQUIPMENT. CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL ELECTRICAL POWER PLAN E2.0 PLOT DATE: May 10, 2018 - 5:26pm MECHANICAL POWER PLAN_ ,r + € �i NOTE 1 t 1 � 1 i 30/ /3R MECHANICAL POWER NOTES: 1. PROVIDE JUNCTION BOX AND CONDUIT THROUGH SEALED OPENING FOR CONTROL WIRING POWER. WIRING TO MECHANICAL UNITS ON THE ROOF. COORDINATE EXACT EQUIPMENT LOCATIONS WITH MECHANICAL DRAWINGS PRIOR TO INSTALLATION. 2. EXTERIOR RECEPTACLE SHALL BE "WEATHER RESISTANT" TYPE AND LABELED ACCORDINGLY BY THE MANUFACTURER. WEATHER PROOF COVER SHALL BE PROVIDED THAT IS WEATHER PROOF WHILE IN USE. THE RECEPTACLE SHALL BE GFI TYPE. 3. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH MECHANICAL CONTRACTOR ON ALL EQUIPMENT PURCHASED SHOWN ON THESE PLANS. PROVIDE MANUFACTURER'S RECOMMENDED BREAKER, FEEDER, AND DISCONNECT FOR EQUIPMENT PURCHASED IF REQUIREMENTS DIFFER FROM WHAT IS SHOWN. MECHANICAL EQUIPMENT SCHEDULE EQUIPMENT NAME LOCATION t SERVFS VOLTAGE PHASE HP KW KWPOLE� 141CA MOCP KER AAZPABREAKER _ PANEL FEEDER DISCONNECT (NOTE 1) SIZE POLES SIZE FUSE ENCLOSURE CONTROL F-1 DININGKITCHEN 120 1 0.75 1.66 13.8 17.3 25 25 A-25 2 410 .A# 10 G- If2 s"C. 30 1 NF NEMA 3R BY DIVISION 15 F-2 DINING/KITCHEN 120 1 0,75 1.66 13.8 17.3 25 25 A-27 2 #-10 .1# 'I0 IIIG- 1/2 :"C. 30 1 NF NEMA 3R BY DIVISION 15 F-3 DINING'KITCHEN 120 1 0.75 1.66 13.8 17.3 25 25 A-29 2 # 10 A# 10 G- 1/2 "C. 30 1 NF NEMA 3R BY DIVISION 15 F-4 DINING/KITCHEN 208 3 1.50 0.83 6.9 8.6 15 15 A-19,21.23 3 # 12 .1# 12 G 1/2 "C, 30 3 NF NEMA 3R BY DIVISION 15 F-5 RESTROOMS 120 1 0.25 0.10 5.8 7.3 15 15 A-31 2 # 12 >I## 12 G• 1/2 "C. 30 1 NF NEMA 3R BY DIVISION 15 MAU-1 DINING/KITCHEN 208 3 1.00 0.58 4.8 6.0 15 15 A-14,16,18 3 412 '.1# 12 'G- 1/2 "C. 30 3 NF NEMA 3R BY DIVISION 15 MAU-2 DINING/KITCHEN 208 3 2.00 0,94 7.8 9.8 15 15 A-20>22,24 3 #''12 ',1# 12 ':G- 1/2 "C. 30 3 NF NEMA 3R BY DIVISION 15 RTU-1 DININGKITCHEN 208 3 4A3 36.9 46.1 60 60 A-7,9A 1 3 #'4 .1# 10 ':G- i "C. 60 3 NF NEMA I BY DIVISION 15 RTU-2 DINING/KITCHEN 208 3 4.43 36.9 46.1 60 60 A-2.4,6 3 #'4 1# 10 iG- 1 "C. 60 3 NF NEMA 1 BY DIVISION IS RTU-3 DINING/KITCHEN 208 3 4.43 36.9 46.1 60 60 A-13,15,17 3 #''4 .14 10 ',G- i "C, 60 3 NF NEMA 1 BY DIVISION I5 RTU-4 DINING/KITCHEN 209 3 2.63 21.9 27.4 40 40 A-8>10,12 3 #':8 1# 10 '''.G- 3/'4 "C. 60 3 NF NEMA 1 BY DIVISION 15 NOTES i, DISCONNECT SOWITC'H ISNOT REQUIRED IF UNIT ISPROVIDED WITH DISCONNECT OR IF UNIT HAS CORD/P L UG AND RECEPTACLE, V Z w O CD �y A gN � � C) W Cy) -W C)ror� LU co _j V ~ ~ O W x = T Vzocy)= N> U Ir N Q c/) rA U) Z Cn D In (4 0.4 \N0C E N N04056 S OF '.� • • �� o i ••'c�ORIDP` '��` � SS�Q ONA Lu w U) Z w U J m Q U Z Q Q ua Y U) Z Q CO W W J 18014 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL MECHANICAL POWER PLAN E3.0 PLOT DATE: May 10, 2018 - 5:26pm NEW 600A SERVICE ENTRANCE RATED FUSED DISCONNECT NEW 600A UTILITY GRADE METER UTILITY TRANSFORMER 2 SETS - 4#350KCMIL CU THHN/THWN, 1#1 CU GRID, WC. EACH. r%n KinT QEYH ME TA T-BAR (TYPIC m )UND NEW NEMA 3R 600A FUSED 208/120V EXTERIOR INTERIOR PANEL 'A' 600A MLO 208/120V NOTE 1 PANEL 'B' 250A MLO 208/120V NOTE 2 4#250KCMIL CU THHN/THWN, 1#1/0 CU GRID, 3"C. 1#1/0 GND �- 2 SETS - 4#350KCMIL CU THHN/THWN, IN 1"PVC 1#1 CU GRD, 3"C. EACH. GRADE N R RISER DIAGRAM. SCALE: NO SCALE TROFFER HANGING DETAIL NO SCALE RISER DIAGRAM NOTES: 1. NEW 600A, MLO, 3-PHASE, 208Y/120V TIN PLATED COPPER BUS PANEL WITH BOLT -ON BREAKERS. 2. NEW 250A, MLO, 3-PHASE, 208Y/120V TIN PLATED COPPER BUS PANEL WITH BOLT -ON BREAKERS. 3. PROVIDE ISOLATED GROUND BAR IN PANELBOARD. GENERAL SERVICE NOTES: A. FOR EACH PANELBOARD INSTALLED, SPACE EQUAL TO THE WIDTH AND DEPTH EXTENDING THE FLOOR TO 6'-0" ABOVE THE PANEL OR STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE DEDICATED FOR ELECTRICAL EQUIPMENT INSTALLATION ONLY. B. ALL SUPPORTS, BOLTS, STRAPS, SCREWS AND SO FORTH SHALL BE OF CORROSION-RESITANT MATERIALS OR PROTECTED AGAINST CORROSION. C. RACEWAY AND CONDUIT EXPOSED TO DIFFERING TEMPERATURES SHALL BE FILLED OR SEALED TO PREVENT THE CIRCULATION OF AIR AND FORMATION OF CONDENSATION. D. NEW SERVICE GROUND SHALL MEET ALL APPLICABLE REQUIREMENTS IN NEC ARTICLE 250. E. ALL FEEDERS ARE TO BE COPPER IN CONDUIT INCLUDING SERVICE ENTRANCE CONDUCTORS. PANEL NAME LOCATION: VOLTAGE: 208 Y/ 120V 3 PHASE 600 MLO MOUNTING/ ENCLOSURE: SURFACE / NEMA 1 A BACK OF HOUSE NEW AMPS POLES TYPE CIRCUIT DESCRIPTION KVA CKT A B C CKT KVA CIRCUIT DESCRIPTION TYPE POLE AMPS, 250 3 PANEL'B' 32.30 1 36.73 2 4.43 RTU-2 AC 3 60* 30.70 3 35.13 4 4.43 AC 28.50 5 32.93 6 4.43 AC 60* 3 AC RTU-1 4.43 7 7.06 8 2.63 RTU-4 AC 3 40* AC 4.43 9 7.06 10 2.63 AC AC 4.43 11 7.06 12 2.63 AC 60* 3 AC RTU-3 4.43 13 5.01 14 0.58 MAU-1 M 3 15 AC 4.43 15 5.01 16 0.58 M AC 4.43 17 5.01 18 0.58 M 15 3 M F-4 0.83 19 1.77 20 0.94 MAU-2 M 3 15 M 0.83 21 1.77 22 0.94 M M 0.83 23 1.77 24 0.94 M 20 1 M F-1 1.66 25 2.38 26 0.72 1 ROOFTOP RECEPTACLES R 1 20 20 1 M - 1.66 27 2.86 28 1.20 POS R 1 20 20 1 M F-3 1.66 29 2.86 30 1.20 POS R 1 20 20 1 M F-5 0.10 31 1.30 32 1.20 POS R 1 20 20 1 L LIGHTING 1.60 33 2.50 34 0.90 OFFICE RECEP R 1 20 20 l L LIGHTING 1.60 35 2.50 36 0.90 OFFICE RECEP R 1 20 20 1 L EXT LIGHTING 1.60 37 2.20 38 0.60 BATH GFI R 1 20 20 1 L LIGHTING 1.60 39 2.20 40 0.60 EXT RECEP R 1 20 20 1 L LIGHTING 1.60 41 2.50 42 0.90 RECEP R 1 20 PHASE TOTAL 56.5 56.5 54.6 IKVA TOTAL CONNECTED LOAD 168 KVA 465 A *PROVIDE HACR TYPE CIRCUIT BREAKER TOTAL DEMAND LOAD 170 KVA 1472 A PANEL NAME LOCATION: VOLTAGE: 208 Y/ 120V 3 PHASE 250A MLO MOUNTING/ENCLOSURE: SURFACE / NEMA 1 B BACK OF HOUSE NEW AMPS POLES TYPE CIRCUIT DESCRIPTION KVA CKT A B C CKT KVA CIRCUIT DESCRIPTION TYPE POLES AMPS 20 1 K KEG COOLER R-0 1 1.68 l 3.33 2 1.65 DLE ( -005) K 1 20 20 1 K SANDWICH PREP TABLE R-002 1.24 3 1.24 4 SHUNT 20 1 K SANDWICH PREP TABLE R-002 1.24 5 2.89 6 1.65 GRIDDLE -005) K 1 20 20 1 K - 0.90 7 0.90 8 SHUNT 20 1 K - 1.80 9 3.45 10 1.65 - K 1 20 20 1 K - 0.50 11 0.50 12 SHUNT 20 1 K 1.08 13 2.73 14 1.65 - K 1 20 20 1 K - 1.44 15 2.64 16 1.20 - K 1 20 20 1 K FRID FULL ( 0 1.40 17 2.60 18 1.20 (-010) K 1 20 20 1 K HALF SIZE FRIDG(R-010) 1.00 19 2.00 20 1.00 WAFFLE MAKER (C-011) K 1 20 20 1 K HALF SIZE FRIDG (R-0 11) 1.00 21 1 2.00 22 1.00 WAFFLE MAKER (C-011) K 1 20 20 1 K HALF SIZE FRIDG(R-010) 1.00 23 1.90 24 0.90 FOOD WARMER (C-0 12) K 1 20 20 1 K HALF SIZE FRIDG(R-012) 1.00 25 1.90 26 0.90 FOOD WARMER (C-0 12) K 1 20 20 1 K H - 3 1.32 27 2.22 28 0.90 FOOD WARMER (C-0 12) K 1 20 20 1 K FRIDGHALF (R-0 14) 1.20 29 2.10 30 0.90 FOOD WARMER (C-0 12) K 1 20 20 1 K 1.08 31 2.40 32 1.32 MIXER (P-001) K 3 30 33 1 1.32 34 1.32 K 20 1 K F T 1.08 35 2.40 36 1.32 K SHUNT 37 0.60 38 0.60 CHOPPER(P-002) K 1 20 20 2 K K STEAM TABLE (H-002) 1.65 39 2.25 40 0.60 SLICER (P-003) K 1 20 1.65 41 2.85 42 1.20 MIXER (P-004) K 1 20 20 1 K WARMER (H-003) 1.20 43 2.40 44 1.20 BLENDER (P-007) K 1 20 20 1 K CONV OVER (C-001) 1.08 45 2.28 46 1.20 BLENDER (P-007) K 1 20 SHUNT 47 1.20 48 1.20 BLENDER (P-007) K 1 20 20 1 K CONV OVER (C-00 1) 1.08 49 2.28 50 1.20 COFFEE BREWER (S•001) K 1 20 SHUNT 51 1.20 52 1.20 COFFEE BREWER (S•001) K 1 20 20 1 K KEG COOLER (R-00 1) 1.68 53 2.88 54 1.20 COFFEE BREWER (S-00 1) K 1 20 20 1 K FOOD WARMER (S-004) 1.24 55 5.44 56 4.20 DW (D-001) K 3 60 20 I K WATER FILTER (S-006) 1.24 57 5.44 58 4.20 K 20 1 K BAG IN BOX (S-008) 0.90 59 5.10 60 4.20 K 20 1 K HOOD (E-101) 1.80 61 3.00 62 1 1.20 1 COOLER LIGHT K 1 20 20 1 K HOOD(E-102) 0.50 63 1.70 64 1.20 COOLER EVAP K 1 20 20 1 K HOOD (E-103) 1.08 65 2.68 66 1.60 WIC CU K 3 30 30 3 K K WIF CU 2.10 67 3.70 68 1.60 K 2.10 69 3.70 70 1.60 K K 2.10 71 3.10 1 72 1.00 FREEZER LIGHT K 1 20 20 1 SPARE 0.00 1 73 1.20 1 74 1 1.20 1FREEZEREVAP K 1 1 20 PHASE TOTAL 32.3 1 30.7 28.5 JKVA TOTAL CONNECTED LOAD 92 KVA 1254 A *PROVIDE HACR TYPE CIRCUIT BREAKER ITOTAL DEMAND LOAD 1 59 KVA 1165 A L LIGHTING 0.0 0.0 R RECEPTACLE 0.0 0.0 M MOTOR 0.0 2.4 0.0 H HEATING 0.0 0.0 AC AC 0.0 K KITCHEN 91.5 65 o 59.5 MISCELLANEOUS 0.0 0.0 T ITRANSFORMED FROM SUB PANEL 1 0.01 0.0 TIME CLOCK C2 NC A-33 ( NO CIRCUIT INTERIOR LIGHTING ( COM NC A-37 NO CIRCUIT INTERIOR #2 LIGHTING COM NC A-39 NO CIRCUIT INTERIOR #3 LIGHTING COM NC A 41 CIRCUIT INTERIOR NO #4 LIGHTING COM CONTROL EQUIPMENT 120 VAC GROUND A-33 .................................. ............................ TIME CLOCK Cl NC A-37 ( NO CIRCUIT EXTERIOR -{ #1 SIGN ( COM NC CIRCUIT SPARE NO #2 COM NC CIRCUIT SPARE NO #3 COM NC CIRCUIT SPARE NO #4 COM CONTROL EQUIPMENT 120 VAC GROUND A-37 LIGHTING CONTACTOR DETAIL. SCALE: NO SCALE KITCHEN E UIPMENT SCHEDULE TAG DESCRIPTION VOLTAGE PHASE HP KW KW / PHASE FLA BREAKER AMPACITY SHUNT TRIP PANEL FEEDER DISCONNECT MOUNTINGHEIG-IT R-00I KEGCOOLER 120 1 1.68 14.0 20 NO B-1 2'# 12 ,1# 12 G- 1/2 "C. NEMA 3R 30AlNF/3 AT UNIT R-002 (2) SANDWICH PREP TABLE 120 1 1.24 10.3 20 NO B-3/5 2'# 12 ,l# 12 G- 112 "C. NEMA 5-20R, CFCI 24" AFF R-003 UNDERCOUNTER FREEZER 120 1 1.80 I5.0 20 NO B-7 2 #;12 3 # 12 G- 1/2 "C. NEMA 5-20R. GFCI 24" AFF R-005 MERCHANDISER FRIDG, 120 1 1.60 6.0 20 NO B-9 2 # 12 ,1# 12 G- 1/2 "C. NEMA 15-30R 24" AFF R-007 SOFT SERVE FREEZER 120 1 1.44 12.0 20 NO B-11 2 # 12 A# 12 G- 1/2 "C. NEMA 5-20R, GFCI 24" AFF R-008 FOOD PREP TABLE 120 1 1.40 11.7 20 NO B-13 2!#12 A#: 12 G- 1/2 "C. NEMA 5-20R, GFCI 48" AFF R-009 (2) FRIDG FULL GLASSFRONT 120 1 1.40 11.7 20 NO B-I5/17 2'# 12 ,1# 12 G- 1/2 "C. NEMA 5-20R- GFCI 48" AFF R-010 FRIDGHALF 120 1 1,40 I L7 20 NO B-19 2 #,' 12 ,1# 12 G- 1/2 "C. NEMA 5-20R. GFCI 48" AFF R-Oil (2) FRIDGHALF 120 1 1A0 11.7 20 NO B-21/23 2 # 12 A# 12 G- I/2 "C. NEMA 5-20R, CFCI 48" AFF R-012 FRIDGHALF 120 1 1.40 11.7 20 NO B-25 2'# 12 .1# 12 G- 1/2 "C. NEMA 5-20R, GFCI 48" AFF R-013 HORIZONTAL FREEZER 120 1 1.40 11.7 20 NO B-27 2 # 12 ,1# 12 G- 1/2 "C. NEMA 5-20R. GFCI 48" AFF R-014 FRIDGHALF 120 1 1.40 11.7 20 NO B-29 2 #' 12 ,1# 12 G- 1/2 "C. NEMA 5-20R. CFCI 48" AFF R-015 (2) CHEF TABLE 120 1 1.40 11.7 20 YES B-31,33/35-37 2'#' 12 A# 12 G- 1/2 "C. NEMA 5-20R, CFCI 48" AFF H-002 STEAM TABLE 208 1 0.86 8.3 20 NO B-39,41 2'#' 12 ,1# 12 G- 1/2 "C. NEMA 5-20R, GFCI 48" AFF H-003 WARMER 120 1 1.60 6.0 20 NO B43 2'#' 12 ,1# 12 G- 1/2 "C. NEMA 6-30R, CFCI 24" AFF C-001 () CONVECTION O�,TN 120 1 3.00 0.6 20 YES B45,47/49.51 2 #' 12 .1# 12 G- 112 "C. NEMA 6-50R, GFCI 24" AFF C-005 (2) GRIDDLE FLAT TOP 120 1 1.32 11.0 20 YES B-2,4/6,8 2 #" 12 ,1#' 12 G- 1/2 "C. NEMA 6-30R, GFCI 24" AFF C-006 GRIDDLE FLAT TOP 120 1 1.32 11.0 20 YES B-10,12 2 # 12 ,1# 12 G- 1/2 "C. NEMA 6-50R. GFC 24" AFF C-007 mw 120 1 1.32 11.0 20 NO B-14 2 #' 12 .l# 12 G- I/2 "C. NEMA 5-20R, GFCI 48" AFF C-010 (2) TOASTER 120 1 1.20 10.0 20 YES B-16/18 2,#` 12 .1#' 12 G- 112 "C. NEMA 5-20R, GF'CI 48" AFF C-011 (2) WAFFLE MAKER 120 1 1.20 10.0 20 YES B-20/22 2'## 12 ,1#'I 12 G- 1/2 "C. NEMA 5-20R,. GFCI 48" AFF C-012 (4) FOOD WARMER 120 1 1.20 10.0 20 YES B-24/26/28/30 2°4' 12 ,1#' 12 G- 1/2 "C. NEMA 5-20R. GFCI 48" AFF P-001 MIXER 208 3 1.32 ILO 30 NO B-32,34,36 3 #',10 A#' 10 G- 3/4 "C. NEMA 15-30R 24" AFF P-002 CHOPPER 120 1 1.08 9.0 20 NO B-38 2,# 12 .1# 12 G- 1/2 "C. NEMA 5-20R, GFCI 48" AFF P-003 SLICER 120 1 1.08 9.0 20 NO B-40 2 # 12 ,1# 12 G- 1/2 "C. NEMA 5-20R. GFCI 48" AFF P-004 MIXER 120 1 1.44 12.0 20 NO B-42 2`# 12 J# 12 G- 1/2 "C. NEMA 5-20R_ GFCI 48" AFF P-007 (3) BLENDER 120 1 1.73 14A 20 NO B-44146?48 2'r'4! 12 ,I# 12 G- 1/2 "C. NEMA 5-20R, GFCI 48" AFF S-001 (3) COFFEE BREWER 120 1 1.67 13.9 20 NO B-50/52/54 2#; 12 ,1# 12 G- 1/2 "C. NEMA 5-20R, CaF'C,I 48" AFF S•003 TEABREWER 120 1 1.67 13.9 20 NO B-53 2' #" 12 ,1# 12 G- 1/2 "C. NEMA 5-20R_ GFCI 48" AFF S-004 FOOD WARMER 120 1 1.67 13.9 20 NO B-55 2'#' 12 ,1# 12 G- 1/2 "C. NEMA 5-20R, GFCI 24" AFF S-006 WATERFILTER 120 1 1.67 13.9 20 NO B-57 2 #' 12 ,1# 12 G- 1/2 "C. NEMA 5-20R, CFCI 24" AFF S-008 BIB 120 1 1.67 13.9 20 NO B-59 2 # 12 ,1# 12 G- 1/2 "C. NEMA 5-20R. GFCI 24" AFF E-101 HOOD SYSTEM 120 1 0.00 20 NO B-61 2 # 12 J# 12 G- 1/2 "C. NEMA 5-20R. GFCI AT UNIT E-002 HOOD SYSTEM 120 1 0.00 20 NO B-63 2 #';12 ,1# 12 G- 1/2 "C. NEMA 5-20R, CFCI 48" AFF E-003 HOOD SYSTEM 120 1 0.00 20 NO B-65 2 # 12 .1#' 12 G- V2 "C. NEMA 5-20R, GF'CI 48" AFF W-001 DW 208 3 4.68 39.0 60 NO B-29 3 # 4 1# 10 G- i "C. DIRECT CONNECTION AT UNIT NOTES 1. DATA OUTLET TO BE SOME HEIGHT AS CORRESPONDINGPOWER RECEPTACLE. 2. REFER TO THE HOOD DRAWINGSAND PROVIDE THE ELECTRICAL CONNECTIONS REQUIRED TO BE MADE "IN -THE -FIELD". INCLUDING THE CONNECTIONS BETWEEN THE HOOD CONTROL PANEL AND THE FACP SYSTEM. U r� `./ O co Z w (.0 V CV � Lo Q �C W Cn CI)(.c)~W cl-, U) LLJ co L0 0 LLJ Uzv`y= 1- N C),I-Q N U) � Cn Lu z Cn m F� %** %\NOE � v'7q'. • ry Nm74056 oo OF ` '• F� o ice• 0RIDP.��`� rn Q w z w U J 18014 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD, ZEPHYRHILLS, FL ELECTRICAL DETAILS E4.0 PLOT DATE: May 10, 2018 - 5:26pm h w 6^ MECHANICAL GENERAL NOTES: 1. COORDINATE LOCATIONS WHERE NEW DUCTWORK CROSSES EXISTING CONDUITS, ETC. PROVIDE OFFSETS AS REQUIRED. 2, INSTALL FIRE DAMPERS AS REQUIRED WHENEVER NEW OR EXISTING DUCTWORK PASSES THROUGH FIRE REATED WALLS OR FLOORS. RETURN AIR OPENING IN FIRE RATED WALLS SHALL BE EQUIPPED WITH FIRE DAMPERS. SEE ARCH. DRAWINGS FOR RATED WALLS. 3. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY ENGINEER WITH ANY DISCREPANCIES BETWEEN DRAWINGS AND EXISTING CONDITIONS 4. COORDINATE EXACT LOCATIONS OF EQUIPMENT ON ROOF. PROVIDE DUCTED OUTSIDE AIR INTAKE DUCTS TO MAINTAIN 10'-0 CLEARANCE FROM EXHAUST OR FLUE DISCHARGE OPENINGS 5. NEW KITCHEN HOODS, EXHAUST FANS AND MAKE UP AIR UNIT BY KITCHEN EQUIPMENT SUPPLIER, VERIFY REQUIREMENTS AND PROVIDE GAS, ELECTRICAL CONNECTIONS AS REQUIRED. EXHAUST DUCT TO BE STAINLESS OR BLACK STEEL, ZERO CLEARANCE TO COMBUSTABLE, INSULATED WRAP. HOOD SHALL BE EQUIPPED WITH AN ANSUL FIRE SUPRESSION SYSTEM. MINIMUM AIR VELOCITY IN EXHAUST DUCTWORK SHALL BE A MINIMUM OF 1500 FPM 6. COORDINATE ALL WORK WITH ALL OTHER TRADES, RESOLVE CONFLICT PRIOR TO INSTALLATION OF EQUIPMENT. COORDINATE NEW DIFFUSER LOCATIONS WITH LIGHT FIXTURES, SPRINKLER HEADS AND PIPING, CEILING GRID LOCATION PRIOR TO INSTALLATION. 7. ALL NEW HVAC EQUIPMENT INCLUDING FANS, RTU AND MUA SHALL BE PROPERLY SUPPORTED FROM THE STRUCTURE. MOUNT ALL ROOFTOP UNITS ON CURBS. PROVIDE VIBRATION ISOLATORS ON ALL EQUIPMENT. ALL EQUIPMENT SHALL BE APPROVED FOR ITS SPECIFIC INTENDED INSTALLATION AND OPERATION. 8. DIFFUSER PER SCHEDULE. EACH SHALL BE PROVIDED WITH BALANCING DEVICE AT DIFFUSER RUNOUT WHERE POSSIBLE AND DEVICE FACE -MOUNTED DAMPER OTHERWISE. 9, THERMOSTATS FOR NEW RTU'S SHALL BE PROGRAMMABLE STYLE BY HONEYWELL. SUBMIT SHOP DRAWINGS AND VERIFY MODEL NUMBER PRIOR TO PURCHASE. THERMOSTATS MOUNTED AT 42" AFF 10. PROVIDE ROOF TOP AIR HANDLING UNIT AS INDICATED ON DRAWINGS. VERIFY EXACT LOCATION WITH ROOF PLAN AND STRUCTURAL DRAWINGS. PROVIDE GAS PIPING CONNECTION AND COORDINATE ELECTRICAL CONNECTION. MOUNT ALL UNITS ON 14" ROOF CURB. ROOF CURBS ABOVE OR A SINGLE FLOOR ABOVE MUSIC INSTRUCTION OR ASSEMBLY AREAS SHALL BE PROVIDED WITH VIBRATION ISOLATION ROOF CURBS. 11. PROVIDE NEW GAS SERVICE FROM NEW METER UP TO RTU'S AND EQUIPMENT GAS PIPING TO BE SCHEDULE 40 BLACK STEEL. PROVIDE METER AND PIPING CONNECTION TO ALL AHU'S DUCT FURNACES, HOT WATER HEATER, MAKE UP AIR UNITS AND KITCHEN COOKING EQUIPMENT. GAS PIPING FOR KITCHEN COOKING EQUIPMENT TO BE EQUIPPED WITH A SOLENOID SHUT-OFF VALVES CONNECTED TO HOOD FIRE SUPPRESSION SYSTEM DUCTWORK FOR GRILL HOOD (TYPE 1) SHALL BE WELDED 16 GAGE BLACK IRON, OR STAINLESS STEEL. 12. MAKE UP AIR UNITS AND ROOFTOP UNIT FANS AND OUTDOOR AIR DAMPERS SHALL BE INTERLOCKED WITH EXHAUST FANS. 13. TYPE I EXHAUST FAN TO TERMINATE AT A MINIMUM 40 ABOVE ROOF, PROVIDE FAN WITH 24" METAL ROOF CURB OR WITH HEIGHT SUFFICIENT FOR 18" CLEARANCE FROM ROOF FLASHING TO FAN BASE. 14. ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LOCALLY ADOPTED MECHANICAL CODE WITH ALL CURRENTLY APPLICABLE ERRATA AND AMENDMENTS. 15. CONTRACTOR SHALL COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES PRIOR TO FABRICATION AND INSTALLATION. DO NOT SCALE FROM DRAWINGS FOR ANY EXACT DIMENSION. SEE ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF DOORS, WINDOWS, AIR DISTRIBUTION DEVICES. 16. COORDINATE THE SIZE OF ALL WALL OPENINGS, ROOF OPENINGS AND EQUIPMENT PADS WITH ACTUAL EQUIPMENT PURCHASED. ALL MECHANICAL ITEMS EXTENDING THRU WALL & ROOF SHALL BE FLASHED AND COUNTER FLASHED. ALL ROOF CURBS FOR MECHANICAL EQUIPMENT SHALL BE BY MECHANICAL CONTRACTOR. 17. ROUTE FULL SIZE CONDENSATE DRAINS WITH P-TRAP AND VENT ON OUTLET SIDE. PIPE 12" AWAY FROM UNIT. SPILL ON CONCRETE SPLASH BLOCK WHERE ROUTED TO ROOF. 18. DUCT SMOKE DETECTORS IN SUPPLIES AND RETURNS PER LOCALLY ADOPTED CODE SHALL BE FURNISHED & WIRED BY DIV 16, INSTALLED BY DIV. 15. 19. ALL DUCTWORK SIZES ARE INSIDE CLEAR FREE AREA. INCREASE SIZE WHERE REQUIRED TO INCLUDE INTERNAL INSUALTION 20. MOTOR STARTERS AND DISCONNECTS SHALL BE FURNISHED UNDER DIVISION 15 AND INSTALLED BY THE ELECTRICAL CONTRACTOR. COORDINATE ELECTRICAL CHARACTERISTICS OF HVAC EQUIPMENT AND CONTROL SYSTEM SPIN -IN FITTING WITH VOLUME DAMPER METAL DUCT FOR SIZE SEE PLANS- % AIR SCOOF SUPPLY NLY) j �1 LOCKING QUADRANT DEVICE NECK SIZE TO MATCH RUN OUT STEEL WIRE TO STRUCTURE SUPPORT STRAP INSULATED FLEX DUCT HANGER (TYP.) INSULATED SUPPLY ADAPTER/PLENUM T-BAR FRAME TYP.)- PROVIDE METAL FRAME AT GYP INSTALLTIONS CEILING DIFFUSER / RETURN DETAIL REQUIREMENTS (VOLTAGE/PHASE, SIGNAL TYPE, AUXILIARY CONTACTS ETCO ) PRIOR TO PURCHASING. 21. CONTRACTOR SHALL NOTE THAT THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT INDICATE ALL OFFSETS, TRANSITIONS, OR OTHER APPURTENANCES REQUIRED FOR A COMPLETE HVAC SYSTEM. PROVIDE ALL EQUIPMENT NECESSARY FOR A COMPLETE SYSTEM. 22. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONTROL ITEMS NECESSARY FOR THE HEATING AND COOLING FUNCTIONS OF THE AHU AND MAU. THE AHU THERMOSTAT LAYOUT IS THE HONEYWELLT6590 FAN COIL CONTROLLED. THE MAU SHALL BE PROVIDED WITH ADJUSTABLE DISCHARGE AIR CONTROL WITH DISCHARGE AIR SENSOR AND MODULATING CONTROL VALVE. 23. ALL PIPING AND DUCTWORK SHALL RUN CONTINUOUSLY THROUGH FLOORS, ROOFS AND PARTITIONS. ENGINEER WILL REVIEW DUCT/PIPING SHOP DRAWINGS AT THE REQUEST OF THE CONTRACTOR. NO EXHAUST HOOD SHALL BE LEFT OPEN INTO BUILDING SPACE. 24. THIS CONTRACTOR SHALL PROVIDE & INSTALL ALL MISCELLANEOUS STEEL AS REQUIRED FOR INSTALLATION OF ALL MECHANICAL ITEMS. 25. ALL DIFFUSERS LOCATED IN CEILINGS WITH A NON -RETURN AIR PLENUM SHALL BE INSULATED AIR TIGHT WITH FOIL FACES 1 INCH FIBERGLASS INSULATION. 26. CONTRACTOR SHALL PURCHASE AIR FILTERS FROM THE OWNER -APPROVED AIR FILTER VENDOR WHERE OWNER HAS A SUPPLIER. ALL FILTERS SHALL BE REPLACED IMMEDIATELY PRIOR TO SUBSTANTIAL COMPLETION. 27. CONTRACTOR SHALL SUBMIT THE TAB AGENCY, 2 WEEKS PRIOR TO SCHEDULE TESTING AND BALANCING OF THE SYSTEM, AN UP-TO-DATE SET OF HVAC DRAWINGS, AND RELATED PRODUCT DATASUBMITTALS SUCH AS HVAC UNITS, FANS, DIFFUSERS, and CONTROL DIAGRAMS. 28. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE MECHANICAL SYSTEM IS PROVIDED WITH ALL NECESSARY EQUIPMENT AND CONTROLS. 29. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL SYSTEM REQUIREMENTS. 30. TESTING AND BALANCE: CONTRACTOR SHALL CONTRACT AN INDEPENDENT TESTING AND BALANCING COMPANY TO TEST THE EQUIPMENT AND ADJUST THE HVAC SYSTEM TO OBTAIN THE DESIGN AIR FLOWS AS SHOWN ON PLANS. THE TAB AGENCY SHALL BE NEBB CERTIFIED AND SHALL SUBMIT TAB REPORT AS REQUIRED BY THE NEBB. 31. ALL SUPPLY RETURN- AND OUTSIDE AIR DUCTWORK SHALL BE INSULATED. DUCT LINER SHALL BE 1 1/2" ELASTOMERIC RUBBER (ARMAFLEX OR EQ.); EXTERNAL INSULATION SHALL BE 2" THICK, 1 LB.CU.FT. DENSITY, FIBERGLASS TYPE, FOIL -FACED DUCT WRAP, COMMERCIAL GRADE. ALL EXPOSED DUCTWORK SHALL BE LINED. R-VALUE SHALL BE ADJUSTED PER LOCAL ENERGY CODE REQUIREMENTS. EXPOSED DUCT SHALL BE PROVIDED WITH APINT GRIP FINISH. 32. PROVIDE PVC WATER HEATER "CONCENTRIC TYPE THRU THE ROOF ARRANGEMENT" VENTING ASSEMBLY FOR FRESH AIR INTAKE AND EXHAUST AS RECOMMENDED BY MANUFACTURER. 33. DUCTWORK SHALL BE GALVANIZED STEEL FABRICATED PER SMACNA STANDARDS. VOLUME DAMPERS SHALL BE INSTALLED AT ALL DUCT BRANCHES AND DIFFUSER TAKE OFFS TO BE ABLE TO BALANCE THE AIR SYSTEM. DUCT SHALL BE HUNG WITH 1" WIDE DUCT STRAPS. 34. EACH AC UNIT SHALL BE CONTROLLED WITH A WALL MOUNTED 7-DAY PROGRAMMABLE THERMOSTAT WITH AUTO CHANGE OVER TO PROVIDE OCCUPIED/UNOCCUPIED MODES OF OPERATION. PROVIDE CLEAR PLASTIC COVER WITH LOCKING KEY ALL THERMOSTATS. 35. ALL UNIT HEATER TO HAVE, INTERNAL DISCONNECT, MAGNETIC OVERLOAD PROTECTION; INTEGRAL TSTAT AND 24 V CONTROLTRANSFORMER. 36. ALL PIPING SHALL BE INSULATED COMPLETELY AIR TIGHT WITH NO EXPOSED INSULATION MATERIAL. PROVIDE INSULATION OUTSIDE OF PIPING HANGERS OR SUPPORTS WITH RIGID INSULATION AND PIPING SADDLES AT SUPPORTS SUFFIECIENT TO PREVENT DEFORMATION OF INSULATION. 37. PROVIDE SIESMIC FITTINGS AND SUPPORTS AS REQUIRED BY THE LOCAL BUILDING CODE AND SIESMIC CHARACTERISTICS FOR THE CONSTRUCTION LOCATION. 38. ALL COOLING UNITS SHALL BE PROVIDED WITH DRAIN PANS AND FLOAT SIWTCHES TO PREVENT UNIT OPERATION WHERE CONDENSATE DRAINAGE CAN BE UNEXPECTEDLY INHIBITED, NO EQUIPMENT SHALL SIT DIRECTLY IN A DRAIN PAN. SUPPLY SUPPLY --4► RETURN/EXHAUST RETURN/EXHAUST 45° VD SUPPLY- RETURN/EXHAUST DUCT BRANCH DETAIL AIR DEVICE SCHEDULE DESIGN MARK LAYOUT BASIS TYPE FACE SIZE MOUNTING FINISH MATERIAL NOTES S-1 TITUS TMS CEILING DIFFUSER 24X24/12X12 2x2 T-BAR WHITE STEEL 1,4 S-2 TITUS PAR PATTERNLESS PERF GRILLE 24X24/ 2x2 T-BAR WHITE STEEL 1,4 R-1 TITUS 50 F 1/2" EGGCRATE RETURN 24X24 2X2 T-BAR WHITE ALUMINUM 2 NOTES 1 . NECK SIZE TO MATCH DUCT RUN OUT SIZE AS SHOWN ON MECHANICAL PLANS. 2 .PROVIDE MANUFACTURER'S ACCESSORY INSULATED PLENUM WITH RUN OUT SIZED CONNECTION. 3 .BALANCING DEVICE AT AIR DEVICE FACE 4 .BALANCING DEVICE AT RUN OUT TAKEOFF 5 .DIVERT BLADES TO 45 DEGREE LATERALLY AND 35 DEGREES BELOW HORIZONTAL 6 .3-WAY DIFFUSER I F I I END ABREVIATIONS AC ABOVE CEILING HR HOUR ACC ACCESS HW HOT WATER ACU AIR CONDITIONING UNIT HZ HERTZ AFF ABOVE FIN ISHED FLOOR IE INVERT ELEVATION AHU AIR HANDLING UNIT LAT LEAVING AIR TEMPERATURE AP ACCESS PANEL LBS POUNDS ARCH ARCHITECT LOB LEAVING DRY BULB BDD BACKDRAFT DAMPER LWB LEAVING WET BULB BTUH BTU PER HOUR LWT LEAVING WATER TEMP. CC COOLING COIL MAX MAXIMUM CCP CENTRAL CONTROL PANEL MBH THOUSAND BTU PER HOUR CD CEILIIYIG DIFFUSER EVAP EVAPORATOR CFM CUBIC FEET PER MINUTE MIN MINIMUM CG CEILING GRID MOD MOTORIZED DAMPER CONC. CONCRETE MTD MOUNTED CR CEILING REGISTER N.C. MORMALLY CLOSED CV CONTROL VALVE NIC NOT IN CONTRACT D DROP N.O, NORMALLY OPENED DB DRY BULB NO. NUMBER DIA. DIAMETER NPSH NET POSITIVE SUCTION HEAD DN DOWN NTS NOT TO SCALE DWG DRAWING OA OUTSIDE AIR EA EXHAUST AIR OD OUTSIDE DIAMETER EAT ENTERING AIR TEMP OS&Y OUTSIDE SCREW AND YOKE EDB ENTERING DRY BULB PD PRESSURE DROP EF EXHAUST FAN PSI POUNDS PER SQUARE INCH ELEV ELEVATION RA RETURN AIR ELEC ELECTRIC RM ROOM EWB ENTERING WET BULB RPM REVOLUTION PER MINUTE EWT ENTERING WATER TEMP SD SMOKE DAMPER ESP EXTERNAL STATIC PRESSUR SF SUPPLY FAN SP STATIC PRESSURE SF SUPPLY FAN EXH EXHAUST SP STATIC PRESSURE EXT EXTERNAL SPEC SPECIFICATIONS F DEGREES FAHRENHET SR SUPPLY REGISTER FC FLEXIBLE CONNECTION SS STAINLESS STEEL FCU FAN COIL UNIT TDH TOTAL DYNAMIC HEAD FD FIRE DAMPER TEMP TEMPERATURE AFG ABOVE FINISHED GRADE TG TRANSFER GRILLE FLD FLOOR DRAIN TV TURNING VANES FPI FINS PER INCH TYP. TYPICAL FPM FEET PER MINUTE UH UNIT HEATER FT FEET UC 3/4" UNDERCUT GV GATE VALVE V VOLTS G GAUGE VAV VARIABLE AIR VQLUME GAL GALLON VEL VELOCITY GPH GALLONS PER HOUR VERT. VERTICAL GPM GALLONS PER MINUTE W WIDTH HP HORSE POWER W/ WITHOUT HT HEIGHT W/O WITHOUT H2O WATER IWB WET BULB HORIZ, HORIZONTAL IW.C. WATER COLUMN ----------- LEGEND DUCT (SINGLE LINE) THERMOSTAT EXISTING DUCT/PIPE ss REMOTE SENSOR LINED DUCT (SINGLE LINE) O HUMIDISTAT HOOD ANSUL SYSTEM PULL STATION LINED DUCT jj....,, OVERFLOW NOZZLE EXPOSED SPIRAL W/ PAINT GRIP PIPE DROP ROOF DRAIN SUPPLYNENTILATION DROP _ __ _ - BALL VALVE RETURN DROP STRAINER EXHAUST DROP PRV SUPPLY DIFFUSER CHECK VALVE M METER RETURN GRILLE NAT GAS REGULATOR EXHAUST GRILLE CAP 3 WAY VALVE VOLUME DAMPER 2 WAY VALVE FIRE DAMPER BUTTERFLY VALVE MOTORIZED DAMPER CIRCUIT SETTER SMOKE DETECTOR FLOW CONTROL VALVE DUCT ELBOW WITH VANES -SINGLE LINE (EXCLUDE VANES IN GAGE GREASE EXHAUST) THERMOMETER DUCT ELBOW WITH VANES PT PLUG (EXCLUDE VANES IN GREASE EXHAUST) PUMP RADIUS ELBOW DOUBLE CHECK VALVE RPZ CHECK FLEX DUCT RUN OUT FLEXIBLE CONNECTION FLEX PIPE/CONNECTION AUTO AIR VENT INLINE CABINET FAN FROSTAT CEILING CABINET FAN UNION HORIZ. UNIT HEATER CEILING UNIT HEATER INTAKE/VENT HOOD EXHAUST/FLUE VENT HOOD ROOF FAN GAS PIPING CW PIPING HW PIPING HOT WATER RECIRCULATION PIPING VENT PIPING SANITARY PIPING (LONG DASH) GREASE WASTE (SHORT DASH) EXISTING PACKAGED GAS/ELECTRIC ROOFTOP UNIT SCHEDULE MIN FAN COOLING COOLING HEATING HEATING NOM UNIT QTY FAN OA FAN MOTOR TOTAL SENSIBLE MBH MBH HEATING VOLTS/ MARK SERVES MODEL TONS CONFIGURATION COMPR. CFM CFM ESP HP MBH MBH OUTPUT INPUT STAGES PHASE RTU-1 BOH TRANE YHC120 10 DOWNFLOW 1 4000 0.5 113.97 94.06 120 150 1 208/3 RTU-2 BOH TRANE YHC120 10 DOWNFLOW 1 4000 0,5 113.97 94.06 120 150 1 208/3 RTU-3 DINING TRANE YHC120 10 DOWNFLOW 1 4000 0.5 113.97 94.06 120 150 1 208/3 RTU-4 DINING TRANE YHC060 5 DOWNFLOW 1 2000 250 0.5 --- 63.49 47.33 48 60 1 208/3 NOTE 1: INDOOR COIL EAT = 80/67 FOR COOLING, 70 FOR HEATING. NOTE 2: OUTDOOR COIL EAT = 95 FOR COOLING, 17 FOR HEATING. NOTE 3: ESP DOES NOT INCLUDE FILTERS. FAN PERFORMANCE FOR DIRECT DRIVE UNITS IS AT HIGH SPEED. NOTE 4: PROVIDE HINGED ACCESS DOORS, UNIT MOUNTED DISCONNECT AND UNPOWERED RECEPTACLE, CONDENSER COIL GUARDS, STAINLESS STEEL HEAT EXCHANGER. NOTE 5: FACTORY MOUNTED SMOKE DETECTOR IN SUPPLY AND RETURN COMPARTMENTS AND INTERNAL FLOAT SWITCH WIRED FOR UNIT SHUTDOWN. NOTE 6: PROVIDE 2-POSITION MOTORIZED DAMPER AT OUTDOOR AIR HOOD. NOTE 7: ECONOMIZER WITH COMP ENTHALPY CONTROL MODULE. POWER EXHAUST FOR UNITS ABOVE 2000 CFM, BAROMETRIC RELIEF FOR 2000 CFM AND LOWER. NOTE 8: PROVIDE MANUFACTURER ACCESSORY ROOF CURB. CURB ADAPTORS SHALL REQUIRE SPECIFIC ENGINEER APPROVAL. NOTE 9: PROVIDE SPRING ISOLATION TYPE ROOF CURB. NOTE 10: COORDINATE VOLTAGES WITH ELECTRICAL DRAWINGS PRIOR TO ORDERING. SUBMITTALS SHALL BE REQUIRED TO HAVE ELECTRICAL ENG. APPROVAL NOTE 13: PROVIDE REFRIGERANT HOT GAS REHEAT DEHUMIDIFICATION. NOTE 15: PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT WITH REMOTE SENSOR. END EXHAUST/VENTILATION FAN SCHEDULE MOTOR VOLTS/ FAN TAG MODEL TYPE SERVES CFM ESP HP RPM SONES DRIVE PHASE INTERLOCK NOTES F-1 HOOD HOOD 1,350 0.925 0.75 1,164 11.8 DIRECT 120/1 TIMECLOCK SET FOR OCCUPIED SCHEDULE F-2 HOOD HOOD 2000 0.931 0.75 1377 16.1 DIRECT 120/1 TIMECLOCK SET FOR OCCUPIED SCHEDULE F-3 HOOD HOOD 2000 0.93 0.75 1377 16.1 DIRECT 120/1 TIMECLOCK SET FOR OCCUPIED SCHEDULE F-4 HOOD HOOD 3000 1.122 1.5 1120 13.6 DIRECT 120/1 TIMECLOCK SET FOR OCCUPIED SCHEDULE F-5 ACED DOWNBLAST RESTROOMS 300 0.250 1/3 1,325 8.9 DIRECT 1 120/1 TIMECLOCK SET FOR OCCUPIED SCHEDULE 1,2,3,4 1. COORDINATE VOLTAGES WITH ELECTRICAL DRAWINGS. 2. PROVIDE INDOOR FANS WITH BACKDRAFT DAMPER, SPRING/NEOPRENE ISOLATION HANGERS AND ACCESSORY ROOF CAP AT SIZE INDICATED ON DRAWINGS. END Z I"I O W co N a �00 Lo U W � z w Q I- LIJ UzU�= N� N U N Q V� LU z m . M� • E 0. 7 • . o Q 4 STAT OF • ��Lu i�0 •. Al .• �� z �O �pP w SS�OIVA •E � �, #oil Its m q c5 z q Q w Y U) Z Q 00 w w J 18014 0 CONTRACT DATE: 08-13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL MECHANICAL SCHEDULES AND DETAILS Mo. 1 PLOT DATE: I. GENERAL PROVISIONS A. OVERVIEW 1. ALL WORK DONE UNDER THIS CONTRACT SHALL COMPLY WITH ALL STATE AND LOCAL CODES HAVING JURISDICTION AND WITH THE REQUIREMENTS OF THE UTILITY COMPANIES WHOSE SERVICES MAY BE USED. ALL MODIFICATIONS REQUIRED BY THESE CODES SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGES. WHERE CODE REQUIREMENTS ARE LESS THAN THOSE SHOWN ON THE PLANS OR IN THE SPECIFICATIONS, THE PLANS AND SPECIFICATIONS SHALL BE FOLLOWED. WHERE APPLICABLE, NFPA REQUIREMENTS SHALL BE MET. 2. IN CASE OF ANY CONFLICTS BETWEEN CONTRACT DOCUMENTS, THE STRICTER/MORE STRINGENT SHALL GOVERN. 3. THE CONTRACTOR SHALL TAIN ALL PER IT IN P I A P OB M S SECT ONS AND P ROVALS AS RE UIRED BY ALL AUTHORITIES HAVING Q JURISDICTION AND DELIVER ERTIFI ATE F APPR VAL T C C S 0 0 TO HE ENGINEER. ALL FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS MUST BE ASSUMED AND PAID BY THE CONTRACTOR. 4. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE PROVISI NS F . .H.A. 0 0 OS 5. THE WORKMANSHIP AND MATERIALS COVERED BY THESE SPECIFICATIONS SHALL CONFORM TO ALL ORDINANCES AND REGULATIONS OF THE ITY NTY AND R T E C , COU /0 O H R AUTHORITIES HAVING JURISDICTION. 6. CONTRACTOR SHALL VISIT THE SITE AND EXAMINE EXISTING CONDITIONS BEFORE SUBMITTING BID. NO ALLOWANCE WILL BE MADE FOR LACK OF KN WLEDGE F EXISTIN CONDITI N WHEN H NDITI 0 0 G 0 S SUC CO ONS CAN BE DETERMINED BY OBSERVATION. 7. PRIOR TO SUBMITTIN D T F R R P R IN T G A A O O U CHAS G EQUIPMEN REQUIRING ELECTRICAL SERVICE, THE CONTRACTOR SHALL VERIFY THAT ELECTRICAL CHARACTERISTICS OF EQUIPMENT SUBMITTALS COMPLY WITH ELECTRICAL SERVICE PROVIDED FOR THE SPECIFIED ITEMS OF EQUIPMENT. 8. UPON RECEIPT OF THE CONTRACTOR OF REVIEWED SUBMITTALS FORE UIPMENT PROVIDED UNDER THI DI I 1 N THE Q S VSO , CONTRACTOR SHALL COORDINATE THE ELECTRICAL SERVICE RE UIREMENTS I.E. MOTOR HORSEPOWER AND F LL L AD AM Q U 0 PS, ELECTRICAL SERVICE CHARACTERISTICS VOLTAGE AND PHASE AND NUMBER OF SERVICES FOR EACH ITEM F E IPMENT ( ), 0 QU REQUIRING ELECTRICAL CONNECTIONS WITH THE ELECTRICAL DRAWINGS AND SPECIFICATIONS. 9. ITEMS ON OR PR JE IN TH H THE EILIN HA B I A O CT G ROUG C G S LL E COORD N TED WITH OTHER TRADES. 10.EQUIPMENT MODEL NUMBERS ARE PROVIDED FOR GENERAL GUIDANCE, CONTRACTOR SHALL PROVIDE EQUIPMENT THAT MEETS THE PHYSICAL CAPACITIES AS SCHEDULED AND GENERAL ARRANGEMENT AS INDICATED IN THE DRAWING SET. CONTRACTOR SHALL VERIFY EXACT, CURRENT MODEL NUMBERS WITH THE MANUFACTURERS. B. OPERATION AND MAINTENANCE INSTRUCTIONS 1. THE CONTRACTOR SHALL PROVIDE TWO OPERATION AND MAINTENANCE MANUALS. THE MANUALS SHALL BE COMPILED IN HARD BACK, THREE RING NOTEBOOKS. 0&M MANUALS SHALL HAVE PERMANENT LABELS ON FRONT AND SIDE. THE FOLLOWING INFORMATION SHALL APPEAR IN EACH MANUAL: 2. PROVIDE MANUFACTURER'S PRINTED OPERATING PROCEDURES TO INCLUDE START-UP, BREAK-IN, ROUTINE AND NORMAL OPERATING INSTRUCTIONS; REGULATION, CONTROL, STOPPING, SHUTDOWN AND EMERGENCY INSTRUCTIONS; AND SUMMER AND WINTER OPERATING INSTRUCTIONS. PROVIDE MAINTENANCE PROCEDURES FOR ROUTINE PREVENTATIVE MAINTENANCE AND TROUBLESHOOTING; DISASSEMBLY, REPAIR AND REASSEMBLY; ALIGNING AND ADJUSTING INSTRUCTIONS. SERVICING INSTRUCTIONS AND LUBRICATION CHARTS AND SCHEDULES. C. INSTRUCTIONS OF OWNER PERSONNEL 1. BEFORE FINAL INSPECTION, AT A TIME DESIGNATED BY THE DESIGNER, PROVIDE A COMPETENT REPRESENTATIVE TO INSTRUCT OWNER'S DESIGNATED PERSONNEL IN OPERATION, ADJUSTMENT AND MAINTENANCE OF PRODUCTS, EQUIPMENT AND SYSTEMS UNDER THIS DIVISION OF THE SPECIFICATIONS. FOR EQUIPMENT REQUIRING SEASONAL OPERATIONS, PERFORM INSTRUCTIONS FOR OTHER SEASONS WITHIN SIX MONTHS UNLESS REQUESTED OTHERWISE. D. COORDINATION 1. THE PRODUCTS OF PARTICULAR MANUFACTURERS HAVE BEEN USED AS THE BASIS OF DESIGN IN PREPARATION OF THESE DOCUMENTS. ANY MODIFICATIONS TO THE MECHANICAL SYSTEMS AND THEIR COMPONENTS, THE ELECTRICAL SYSTEMS, THE BUILDING STRUCTURE AND ARCHITECTURE, OR ANY OTHER PORTION OF THE BUILDING THAT RESULT FROM THE USE OF ANY OTHER THAN THAT BASIS OF DESIGN EQUIPMENT SHALL BE COORDINATED WITH ALL OTHER TRADES. SUCH COORDINATION SHALL OCCUR BEFORE PURCHASE OR DELIVERY OF PRODUCTS FROM THE MANUFACTURER DRAWINGS OR INSTALLED ACCORDINGLY. ANY RELATED MODIFICATIONS SHALL BE PERFORMED WITHOUT ANY ADDITIONAL COST TO THE CONTRACT. 2. RESIDENTIAL GRADE HVAC COMPONENTS SHALL NOT BE PERMITTED WITHOUT SPECIFIC OWNER INSTRUCTION AND ENGINEER APPROVAL. E. EXECUTION 1. THE PLANS DO NOT GIVE EXACT ELEVATIONS OR LOCATIONS OF LINES, NOR DO THEY SHOW ALL THE OFFSETS, CONTROL LINES, OR OTHER INSTALLATION DETAILS. THE CONTRACTOR SHALL CAREFULLY LAY OUT HIS WORK AT THE SITE TO CONFORM TO THE STRUCTURAL CONDITIONS, TO PROVIDE PROPER GRADING OF LINES, TO AVOID ALL OBSTRUCTIONS, TO CONFORM TO DETAILS OF INSTALLATION SUPPLIED BY THE MANUFACTURERS OF THE EQUIPMENT TO BE INSTALLED, AND TO THEREBY PROVIDE AN INTEGRATED, COORDINATED AND SATISFACTORY OPERATING INSTALLATION. DO NOT SCALE DRAWINGS. 2. IF THE CONTRACTOR PROPOSES TO INSTALL EQUIPMENT, INCLUDING PIPING AND DUCTWORK, REQUIRING SPACE CONDITIONS OTHER THAN THOSE SHOWN, OR TO REARRANGE THE EQUIPMENT, HE SHALL ASSUME FULL RESPONSIBILITY FOR THE REARRANGEMENT OF THE SPACE AND CONNECT ARRANGEMENT AT NO ADDITIONAL COST TO THE OWNER, AND SHALL HAVE THE ENGINEER REVIEW THE CHANGE BEFORE PROCEEDING WITH THE WORK. THE REQUEST FOR SUCH CHANGES SHALL BE ACCOMPLISHED BY SHOP DRAWINGS OF THE SPACE IN QUESTION. 3. TEMPORARY FILTERS SHALL BE PROVIDED FOR FANS THAT ARE USED DURING CONSTRUCTION. AT THE TIME OF STARTING THE BALANCING OF THE AIR DISTRIBUTION SYSTEM, NEW FILTERS SHALL BE INSTALLED. 4. THE CONTRACTOR IS RESPONSIBLE FOR THE PROPER LOCATION AND SIZE OF ALL SLOT, HOLES OR OPENINGS IN THE BUILDING STRUCTURE PERTAINING TO HIS WORK, AND FOR THE CORRECT LOCATION OF SLEEVES, INSERTS, CORES, ETC. 5. THE CONTRACTOR SHALL SO COORDINATE THE WORK OF THE SEVERAL VARIOUS TRADES THAT IT MAY BE INSTALLED IN THE MOST DIRECT AND WORKMANLIKE MANNER WITHOUT HINDERING OR HANDICAPPING THE OTHER TRADES. PIPING INTERFERENCES SHALL BE HANDLED BY GIVING PRECEDENCE TO PIPE LINES WHICH REQUIRE A STATED GRADE FOR PROPER OPERATION. FOR EXAMPLE SEWER LINES AND CONDENSATE PIPING SHALL TAKE PRECEDENCE OVER WATER LINES IN DETERMINATION OF ELEVATIONS. WHERE THERE IS INTERFERENCE BETWEEN SEWER LINES AND CONDENSATE LINES, THE SEWER LINES SHALL HAVE PRECEDENCE AND PROVISIONS SHALL BE MADE IN THE CONDENSATE LINES FOR LOOPING THEM AROUND THE SEWER LINES. IN ALL CASES, LINES REQUIRING A STATED GRADE FOR THEIR PROPER OPERATION SHALL HAVE PRECEDENCE OVER ELECTRICAL CONDUIT AND DUCTWORK. 6. ALL PIPING AND DUCTWORK IN FINISHED AREAS- EXCEPT WHERE NOTED TO THE CONTRARY- SHALL BE INSTALLED IN A CHASE, FURRED SPACE, OR ABOVE CEILINGS, ETC. IN ALL CASES, PIPES AND DUCTS SHALL BE INSTALLED AS HIGH AS POSSIBLE. RUNS OF PIPING SHALL BE GROUPED WHENEVER IT IS FEASIBLE TO DO SO. 7. PIPING SHALL BE INSTALLED TO PASS INSPECTIONS BY LOCAL PLUMBING INSPECTION DEPARTMENT, STATE AND FEDERAL AUTHORITIES AND INSURANCE COMPANY HAVING JURISDICTION. ANY CHANGES OR ADDITIONS WHICH MAY BE NECESSARY TO OBTAIN SUCH INSPECTIONS AND APPROVAL SHALL BE MADE BY THE CONTRACTOR AS PART OF THIS CONTRACT AND WITHOUT ADDITIONAL COST TO THE OWNER. 8. PIPING, DUCTWORK OR EQUIPMENT SHALL NOT BE INSTALLED IN ELECTRICAL EQUIPMENT ROOMS OR ELEVATOR MACHINE ROOMS EXCEPT AS SERVING ONLY THOSE ROOMS. OUTSIDE OF ELECTRICAL EQUIPMENT ROOMS, DO NOT RUN PIPING OR DUCTWORK OR LOCATE EQUIPMENT, WITH RESPECT TO SWITCHBOARDS, PANEL BOARDS, POWER PANELS, MOTOR CONTROL CENTERS, DRY TYPE TRANSFORMERS OR ROOF TOP AIR CONDITIONING UNIT ELECTRICAL PANELS. 9. PROVIDE ACCESS TO EQUIPMENT AND APPARATUS REQUIRING OPERATION, SERVICE OR MAINTENANCE WITHIN THE LIFE OF THE SYSTEM. INCLUDING, BUT NOT LIMITED TO, MOTORS, VALVES, FILTERS, DAMPERS, SHOCK ABSORBERS, ETC. EQUIPMENT LOCATED ABOVE LAY -IN TYPE CEILINGS IS CONSIDERED ACCESSIBLE. 10.DAMAGED EQUIPMENT SHALL BE REPAIRED OR REPLACED AT THE OPTION OF THE ARCHITECT. F. ELECTRICAL WORK 1. ALL ELECTRICAL EQUIPMENT PROVIDED UNDER THIS DIVISION SHALL COMPLY WITH THE ELECTRICAL SYSTEM CHARACTERISTICS INDICATED ON THE ELECTRICAL DRAWINGS AND SPECIFIED IN DIVISION 16. 2. EQUIPMENT UNIT MOTOR SPEED CONTROLS, STARTERS, SYSTEM CONTROLS, PILOT LIGHTS, PUSH -BUTTONS, ETC., SHALL BE FURNISHED COMPLETE AS A PART OF THE MOTOR APPARATUS WHICH IT OPERATES. ALL COMPONENTS SHALL BE IN CONFORMANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AND DIVISION 16. ALL MOTOR STARTERS SHALL BE PROVIDED WITH AN H-O-A SWITCH AND CONTROL TRANSFORMER. ALL STARTERS AND DISCONNECT SWITCHES SHALL BE FURNISHED UNDER DIVISION 15. COORDINATE INSTALLATION WITH ELECTRICAL CONTRACTOR PRIOR TO HIS WIRING OF EQUIPMENT. 3. CONTROL WIRING (120V AND LESS) SHALL BE PROVIDED UNDER DIVISION 15 AND EXTENDED FROM THE STARTERS, CONTROL TRANSFORMERS OR 120V POWER CIRCUITS INDICATED ON THE ELECTRICAL DRAWINGS. ALL WIRING FOR 120 VOLTS SHALL BE DONE BY A LICENSED ELECTRICIAN. 4. ALL ELECTRICAL CHARACTERISTICS SHALL BE TAKEN FROM THE ELECTRICAL DRAWINGS AND SPECIFICATIONS AND COORDINATED BEFORE EQUIPMENT IS ORDERED OR PURCHASED. G. CUTTING AND PATCHING 1. THE CONTRACTOR SHALL ASSUME ALL COST OF, AND BE RESPONSIBLE FOR, ARRANGING FOR ALL CUTTING AND PATCHING REQUIRED TO COMPLETE THE INSTALLATION OF HIS PORTION OF THE WORK. ALL CUTTING SHALL BE CAREFULLY AND NEATLY DONE SO AS NOT TO DAMAGE OR CUT AWAY MORE THAN IS NECESSARY OF ANY EXISTING PORTIONS OF THE STRUCTURE. 2. ALL SURFACES SHALL BE PATCHED TO THE CONDITION OF THE ADJACENT SURFACES. 3. THE CONTRACTOR SHALL MAKE SUITABLE PROVISIONS FOR ADEQUATELY WATERPROOFING AT HIS FLOOR PENETRATIONS OF WATER PROOF MEMBRANE FLOORS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO FLOOR DRAINS, OPEN SIGHT DRAINS, HUB DRAINS, CLEANOUTS, AND SLEEVES FOR THE VARIOUS PIPING. THIS ALSO APPLIES TO MEMBRANE ROOFING SYSTEMS. 4. ALL PENETRATIONS AND WATER PROOFING OF PENETRATIONS IN MEMBRANE ROOFING SYSTEMS SHALL BE COORDINATED WITH AND PERFORMED BY THE MANUFACTURER/INSTALLER. 5. THE CONTRACTOR SHALL INSTALL, AS REQUIRED, IN CONCRETE, CARPENTRY OR MASONRY CONSTRUCTION, ALL NECESSARY HANGERS, SLEEVES, EXPANSION BOLTS, INSERTS AND OTHER FIXTURES AND APPURTENANCES NECESSARY FOR THE SUPPORT OF PIPE, DUCT, EQUIPMENT AND DEVICES FURNISHED UNDER EACH SECTION OF THE SPECIFICATION. 6. FOR WALLS BETWEEN INTERIOR AND BELOW GRADE AREA, THE LINK -SEAL SYSTEM AS MANUFACTURED BY THUNDERLINE CORPORATION SHALL BE USED TO SEAL PIPE TO WALL PENETRATIONS. INSTALL SYSTEM IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. 7. ESCUTCHEONS SHALL BE INSTALLED ON ALL PIPES WHERE THEY PASS THROUGH FLOORS, CEILINGS, WALLS OR PARTITIONS IN FINISHED AREAS WHERE EXPOSED TO VIEW. 8. WHERE AND HVAC OR PLUMBING REPLACEMENT SCOPE IS INDICATED, MECHANICAL CONTRACTOR SHALL PROVIDE FOR THE DEMOLITION OF EXISTING SYSTEMS THAT ARE BEING REPLACED OR ABANDONED H. ACCESS DOORS 1. FURNISH AND INSTALL ACCESS DOORS AT EACH POINT REQUIRED TO PROVIDE ACCESS TO CONCEALED VALVES, CLEANOUTS AND OTHER DEVICES REQUIRING OPERATION, ADJUSTMENT OR MAINTENANCE. ACCESS DOORS SHALL BE 16 GAUGE STEEL, PRIME COAT FINISH, WITH MOUNTING STRAPS, CONCEALED HINGES AND SCREWDRIVER LOCKS, DESIGNED FOR THE DOORS TO OPEN 180 DEGREES. 2. ACCESS DOORS INSTALLED IN FIRE WALLS OR PARTITIONS SHALL BE UL LABELED TO MAINTAIN THE FIRE RATING OF THE WALL OR PARTITION. I. FLAME SPREAD AND SMOKE DEVELOPED PROPERTIES OF MATERIALS 1. MATERIALS AND ADHESIVES USED THROUGHOUT THE MECHANICAL AND ELECTRICAL SYSTEMS FOR INSULATION, AND JACKETS OR COVERINGS OF ANY KIND, OR FOR PIPING OR CONDUIT SYSTEM COMPONENTS, SHALL HAVE A FLAME SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED COMBUSTION AND WITH A SMOKE DEVELOPED RATING NOT HIGHER THAN 50. IF SUCH MATERIALS ARE TO BE APPLIED WITH ADHESIVES, THEY SHALL BE TESTED AS APPLIED WITH SUCH ADHESIVES, OR THE ADHESIVES USED SHALL HAVE A FLAME SPREAD RATING NOT OVER 25 AND A SMOKE DEVELOPED RATING NOT HIGHER THAN 50. 11. INSULATION A. GENERAL PIPE INSULATION 1. FIBERGLASS SHALL BE ACCEPTABLE FOR INDOOR HOT & COLD DOMESTIC; HYDRONIC PIPING; AND INSULATED DRAINAGE PIPING. PROVIDE PREFABRICATED FITTINGS FOR ELBOWS AND TEE'S. PROVIDE PREFAB PVC FITTINGS OR WHITE ALL SERVICE (INTEGRAL TO PREFAB PIPING ELBOW) PIPING ELBOW JACKETING. PROVIDE PIPE LABELING FOR ALL INSULATED, JACKETED INDOOR PIPING. PVC JACKETING SHALL NOT BE PERMITTED IN RETURN PLENUM AREAS. ALL JACKEING SEAMS SHALL BE SEALED AIR -TIGHT FOR CONTINUOUS VAPOR BARRIER. 2. FITTINGS AND VALVES SHALL BE INSULATED WITH PRE -FORMED FITTINGS, FABRICATED SECTIONS OF PIPE INSULATION, TANK INSULATION, BLANKET INSULATION, OR INSULATING CEMENT. THICKNESS SHALL BE EQUAL TO ADJACENT PIPE INSULATION. FINISH SHALL BE WITH PRE -FORMED PVC FITTING COVERS OR AS OTHERWISE SPECIFIED ON CONTRACT DRAWINGS. 3. FLANGES, COUPLINGS AND VALVE BONNETS SHALL BE COVERED WITH AN OVERSIZED PIPE INSULATION SECTION SIZED TO PROVIDE THE SAME INSULATION THICKNESS AS ON THE MAIN PIPE SECTION. AN OVERSIZED INSULATION SECTI N HALL BE D T F RM A COLLAR 0 S USE O 0 BETWEEN THE TWO INSULATION SECTIONS WITH LOW -DENSITY BLANKET INSULATION BEING USED TO FILL GAPS. JACKETING SHALL MATCH THAT USED ON STRAIGHT PIPE SECTIONS. ROUGH CUT ENDS SHALL BE COATED WITH ITABLE R M TI A SU WEATHER OR VAPOR ESISTANT AS C S DICTATED BY THE SYSTEM LOCATION AND SERVICE. ON HOT SYSTEMS WHERE FITTINGS ARE TO BE LEFT EXPOSED, INSULATION ENDS SHOULD BE BEVELED AWAY FROM BOLTS FOR EASY ACCESS. B. INSULATION THICKNESS 1. DOMESTIC COLD WATER INSULATION SHALL BE 1" MINIMUM OR AS RE UIRED BY LOCAL ENERGY CODES. Q 2. FOR MEDIA BELOW 60 DEGREES INSULATION SHALL BE 1" UP TO 1-'/," PIPE SIZE; 1.5" THICK UP TO 3" PIPE SIZE; AND 2" THICK BEYOND 3" PIPE SIZE. 3. CHILLED WATER PIPING INSULATION SHALL BE 1" UP TO 1-1/4" PIPE SIZE, 1.5" UP TO 3". C. FIBERGLASS PIPE INSULATION 1. ONE PIECE FIBROUS GLASS PIPE INSULATION WITH FACTORY APPLIED ALUMINUM FOIL AND WHITE KRAFT PAPER FLAME RETARDANT VAPOR BARRIER JACKET. 2. PROVIDE SELF-SEALING LONGITUDINAL JACKET LAPS AND BUTT STRIP . AVERA E T ER A ARE S G H M L CONDUCTIVITY• 0.23 BTU/IN PER SQU FOOT PER DEGREES F PER HOUR AT 75 DEGREES F MEAN TEMPERATURE. 3. PROVIDE INSULATION CEMENT FIBERGLASS REINFORCEMENT FABRI VAP R BARRI C 0 ER COATING FOR CONTINUOUS AIR TIGHT INSULATION WITH VAPOR BARRIER. D. FOAMGLASS PIPE INSULATION 1. FOAM GLASS TYPE PIPE INSULATION SHALL HAVE MAXIMUM K_FACTOR OF 0.38 AT 50 DEGREES F MEAN TEMPERATURE. MINIMUM DENSITY SHALL BE 8 LB/CU. FT., 1 1/2" THICK MINIMUM. PROVIDE MASTIC, FIBERGLASS REINFORCED STRAPPING TAPE TO ASSURE AIR -TIGHT MOISTURE -PROOF INSULATION. PROVIDE WITH ALUMINUM JACKETING THAT SHALL BE 0.016" THICK WITH FITTING COVERS 0.024" THICK. PROVIDE WITH 5 WATT/FT HEAT TRACING BELOW INSULATION FOR OUTDOOR, ABOVE -GROUND INSTALLATION. 2. PROVIDE FOAM GLASS INSERTS AT PIPE HANGERS, CLAMPS, OR OTHER SUPPORTS IN FIBERGLASS OR ELASTOMERIC PIPE INSULATION INSTALLATIONS INSERTS SHALL BE SAME THICKNESS AS ADJOINING PIPE INSULATION. VAPOR SEAL SHALL BE AS HEREINBEFORE SPECIFIED. ALUMINUM JACKETING SHALL NOT BE REQUIRED FOR INDOOR INSERTS (PVC OR WHITE ALL -SERVICE FOIL/KRAFTJACKETING MEDIA SHALL BE USED). E. ELASTOMERIC (CLOSED CELL FOAM) PIPE INSULATION 1. ELASTOMERIC SHALL BE PROVIDED FOR ALL REFRIGERANT PIPING AND OUTDOOR INSULATED PIPING AND MAY BE USED FOR INDOOR DOMESTIC OR CONDENSATE PIPING. PIPING WILL REQUIRE JACKETING- ALUMINUM FOR OUTDOOR PIPING OR FOIL/WHITE KRAFT MEDIA OR PVC FOR INDOOR PIPING. PROVIDE WITH FULL ADHESIVE ADHERING SEAMS AND JOINTS FOR CONTINUOUS VAPOR BARRIER. ELBOWS SHALL BE FORMED BY CUTTING SEGMENTS AT 30 DEGREE ANGLES (3 SEGMENTS AT EACH 90 DEGREE BEND) WITH MASTIC AT ALL SEAMS. PROVIDE PREFORMED JACKETING ELBOWS AT ALL PIPING ELBOWS. F. FIBERGLASS BLANKET INSULATION FOR DUCTWORK (INDOOR DUCT ONLY 1. INSULATION SHALL BE BLANKET TYPE FIBERGLASS INSULATION WITH AVERAGE THERMAL CONDUCTIVITY NOT EXCEEDING 0.29 BTU_IN. PER SQUARE FEET PER DEGREES F PER HOUR AT MEAN TEMPERATURE OF 75 DEGREES F. WITH A MINIMUM DENSITY OF 1 LB/CU. FT., 2" THICK MINIMUM AND FOIL INSULATION FACE. PROVIDE FIRE RETARDANT ADHESIVE OR FOIL REINFORCED KRAFTTAPE, 3" WIDE AT ALL SEAMS. SECURE INSULATION TO DUCT WITH 18 GAUGE TIE -WIRE OR 1/2" X 0.015" GALVANIZED STEEL STRAPS. PROVIDE COMPLETE AIR -TIGHT VAPOR BARRIER FOR ALL DUCTWORK. STAPLES SHALL NOT BE PERMITTED FOR ANY INSULATION ATTACHMENT. PROVIDE GRAY SEALER FOR SEALING JOINTS, PENETRATION AND PUNCTURES. 2. CONTINUE INSULATION THROUGH WALL AND CEILING OPENINGS AND SLEEVES, EXCEPT TERMINATE DUCT INSULATION AT FIRE DAMPERS AND AT FLEXIBLE DUCT CONNECTIONS AT AIR HANDLING UNITS. 3. PROTECT INSULATION FROM PHYSICAL DAMAGE AT POINTS OF SUPPORT WHERE INSULATION MUST CARRY LOAD IMPOSED BY SUPPORT. COORDINATE THIS REQUIREMENT WITH TYPES OF HANGER AND SUPPORT USED. HANGERS THAT PENETRATE INSULATION SHALL BE SEALED WITH MASTIC TO PRESERVE CONTINUOUS VAPOR BARRIER. G. ELASTOMERIC (CLOSED CELL FOAM) DUCT LINER 1. INSTALL INSIDE OF DUCT WITH FULL ADHESIVE COVERAGE ATTACHMENTTO THE SURFACE TO WHICH IT IS APPLIED; 1" FOR INDOOR AND 1-1/2" FOR OUTDOOR. R VALUES SHALL BE R-4.2 FOR 1" AND R-6.2 FOR 1-1/2". FIBERGLASS DUCT LINER SHALL NOT BE PERMITTED UNDER ANY CIRCUMSTANCES. PROVIDE WITH ANTIMICROBIAL PROTECTION. PROVIDE MASTIC AT ALL INTERIOR SEEMS FOR CONTINUOUS VAPOR BARRIER. PROVIDE DUCT LINER AT FIRST FIVE FEET OF SUPPLY DUCT FOR REFRIGERATION/COOLING AIR HANDLING EQUIPMENT, UPSIZING INDICATED DUCT SIZE TO ACCOUNT FOR INSULATION THICKNESS. FIBERGLASS DUCT LINER OR DUCT BOARD SHALL NOT BE PERMITTED. VIBRATION ISOLATION A. ALL MOTORIZED AIR MOVING AND FLUID MOVING EQUIPMENT PIECE SHALL BE PROVIDED WITH VIBRATION ISOLATION MOUNTING OR SUPPORTS. B. PAD -TYPE ISOLATORS SHALL BE NEOPRENE IN -SHEAR ISOLATION PADS WITH CROSSED DOUBLE RIBS. A STEEL SHIM PLATE SHALL BE PROVIDED BETWEEN THE TWO LAYERS. PADS SHALL BE MOLDED USING OIL RESISTANT 25,000 PSI TENSILE STRENGTH NEOPRENE. C. HANGING ISOLATORS FOR ITEMS 300 LBS OR LESS SHALL BE BRIDGE -BEARING NEOPRENE MOUNTINGS AND SHALL HAVE A MINIMUM STATIC DEFLECTION OF 0.2" AND ALL DIRECTIONAL SEISMIC CAPABILITY. THE ELEMENTS SHALL PREVENT THE CENTRAL THREADED SLEEVE AND ATTACHMENT BOLT FROM CONTACTING THE CASTING DURING NORMAL OPERATION. THE SHOCK ABSORBING NEOPRENE MATERIALS SHALL BE COMPOUNDED TO BRIDGE -BEARING SPECIFICATIONS. MASON HD, KINETICS D. HANGING ISOLATORS FOR EQUIPMENT ABOVE 300 LBS SHALL BE STEEL SPRING -TYPE INCORPORATING STEEL HOUSING, NEOPRENE OR LDS RUBBER SPRING CUP SIZED FOR 1" DEFLECTION. INSTALL SPRING IN PLUMB CONFIGURATION WITH MAXIMUM 1" DEFLECTION FROM ANY HORIZONTAL DISTORTION. THE ELEMENTS SHALL PREVENT THE CENTRAL THREADED SLEEVE AND ATTACHMENT BOLT FROM CONTACTING THE CASTING DURING NORMAL OPERATION. CONTRACTOR SHALL SELECT SPRING COLOR/RATING BASED ON EQUIPMENT WEIGHT. AMBER BOOTH SH, KINETICS SH, MASON 30 OR EQUIVALENT. IV. DUCTWORK AND FITTINGS A. MATERIAL AND TYPE 1. DUCT CONSTRUCTION SHALL CONFORM TO THE RECOMMENDATIONS OF THE SMACNA HVAC DUCT CONSTRUCTION MANUAL. DUCTBOARD SHALL NOT BE PERMITTED. 2. RIGID, SQUARE DUCTWORK SHALL BE CONSTRUCTED OF LOCK FORMING QUALITY GALVANIZED STEEL SHEETS PER ASTM A527. GALVANIZED COATING SHALL BE NOT LESS THAN 1.25 OUNCES (TOTAL FOR BOTH SIDES) PER SQUARE FOOT OF SHEET. DUCTWORK SHALL BE CLASSIFIED AND CONSTRUCTED SMACNA PRESSURE CLASSES: +2 FOR SUPPLY AND -2 FOR RETURN AND EXHAUST. DUCTWORK GAUGE SHALL BE 26 GAUGE UP TO 30" AND 22 GAUGE ABOVE 30" IN CROSS SECTIONAL HEIGHT, WIDTH, OR DIAMETER. 3. CONCEALED ROUND DUCTS UP TO 12" IN DIAMETER IN PRESSURE CLASSES 2" AND LOWER SHALL BE LONGITUDINAL SEAM CONSTRUCTION. 4. EXPOSED ROUND DUCTWORK OR ROUND ABOVE 12" SHALL BE SPIRAL LOCK_SEAM CONSTRUCTION. ROUND FITTINGS SHALL BE FUSION WELDED BUT SEAM TYPE WITH ALL WELDS CONTINUOUS ALONG SEAMS. ALL DIVIDED FLOW FITTINGS SHALL BE MANUFACTURED AS SEPARATE FITTINGS _TAP COLLARS WELDED INTO SPIRAL DUCT SECTIONS WILL NOT BE PERMITTED. ALL DIVIDED FLOW FITTINGS 12" IN DIAMETER AND SMALLER SHALL HAVE RADIUSED ENTRANCE PRODUCED BY MACHINE OR PRESS FORMING; ALL DIVIDED FLOW FITTINGS 14" AND LARGER SHALL HAVE CONICAL ENTRANCE PRODUCED BY MACHINE OR PRESS FORMING. ALL DIVIDED FLOW ENTRANCES SHALL BE FREE OF WELD BUILD-UP, BURRS AND IRREGULARITIES. FITTINGS SHALL BE OF THE SAME MANUFACTURER AS THE DUCTWORK. 5. DUCT SEALANT SHALL BE POLYMERIC RUBBER BASE MASTIC, MINERAL IMPREGNATED WOVEN FIBER TAPE WITH ADHESIVE, OR HEAT_SHRINK WITH ADHESIVE. TAPE THICKNESS UP TO 10" = 2"; UP TO 20" = 3"; OVER 20" = 4" 6. INSULATED FLEXIBLE DUCT SHALL BE CLASS 1 AIR DUCT IN ACCORDANCE WITH UL 181 AND SHALL COMPLY WITH NFPA 90A AND 90B. INSULATED FLEXIBLE DUCT SHALL CONSIST OF AN INNER FILM LAYER FOR MINIMUM WORKING PRESSURE OF 6" WATER GAUGE BONDED TO A STEEL OR ALUMINUM SPRING WIRE HELIX, FIBERGLASS INSULATION, AND A VAPOR BARRIER JACKET. INSULATION SHALL HAVE A MAXIMUM U_VALVE OF .23 BTU/HR/SQFT/DEG F AT 75 DEGREES F MEAN TEMPERATURE. VAPOR BARRIER JACKET SHALL HAVE A MAXIMUM VAPOR TRANSMISSION RATE OF 0.1 GRAINS/SQ. FT./HR/INCH HG (PERM). THE ASSEMBLY SHALL HAVE A MAXIMUM FLAME AND SMOKE RATING OF 25/50 PER ASTM E84 AND NFPA 255. FLEXIBLE DUCTS SHALL BE INSTALLED IN AN EXTENDED CONDITION FREE OF SAGS AND KINKS, USING ONLY THE MINIMUM LENGTH REQUIRED TO MAKE THE CONNECTION. ABRUPT BENDS AND TURNS THAT CRIMP THE DUCT AND RESTRICT AIR FLOW SHALL NOT BE PERMITTED. HORIZONTAL SUPPORTS SHALL BE 3/4" WIDE, 22 GAUGE FLAT GALVANIZED STEEL SHEET BANDING MATERIAL. FLEXIBLE DUCTS SHALL BE SUPPORTED ON 36" CENTERS. MAXIMUM LENGTH OF FLEXIBLE DUCT IN PRESSURE CLASS 2" AND BELOW SHALL BE 12 FEET. FLEXIBLE DUCT SHALL NOT BE USED ABOVE INACCESSIBLE CEILINGS. 7. GREASE DUCT SERVING TYPE I HOODS SHALL BE 16 GAUGE BLACK IRON OR 18 GAUGE STAINLESS STEEL WELDED WITH AIR TIGHT SEAM. PROVIDE DUCT CLEANOUTS AT ALL CHANGES OF DIRECTION. FOR INSTALLATIONS THAT WILL RESULT IN A DUCT OR SECTION OF DUCT WITHIN 18" OF COMBUSTIBLE MATERIAL, PROVIDE FIRE -RATED INSULATION AS REQUIRED FOR A ZERO INCH CLEARANCE TO COMBUSTIBLE INSTALLED PER MANUFACTURER'S AND/OR RATING AGENCY REQUIREMENTS COMPLETE WITH ALL REQUIRED PENETRATION TREATMENTS, NUMBER IF INSULATING LAYERS AND APPROVED PREFABRICATED, RATED ACCESS PANELS. DO NOT PROVIDE VENTED ROOF CURBS FOR FIRE WRAPPED GREASE EXHAUST DUCTS. 8. DISHWASHER EXHAUST DUCT SHALL BE STAINLESS STEEL. B. DAMPERS 1. DAMPERS SHALL BE SINGLE BLADE BUTTERFLY TYPE IN DUCTS UP TO AND INCLUDING 18" X 12" SIZE; FOR DUCTS LARGER THAN 18" X 12", IN EITHER OR BOTH DIMENSIONS, THE DAMPERS SHALL BE THE MULTI_BLADE TYPE. SINGLE BLADE BUTTERFLY DAMPER SHALL BE CONSTRUCTED OF NOT LESS THAN 16_GAUGE GALVANIZED STEEL BLADE MOUNTED IN A GALVANIZED STEEL FRAME. FOR RECTANGULAR DAMPERS, THE TOP AND BOTTOM EDGES OF THE BLADE SHALL BE CRIMPED TO STIFFEN THE BLADE. DAMPER SHALL BE PROVIDED WITH AN EXTENDED ROD TO PERMIT INSTALLATION OF A DAMPER REGULATOR. 2. MULTI_BLADE DAMPERS SHALL BE THE OPPOSED BLADE TYPE, CONSTRUCTED OF NOT THAN 16_GAUGE GALVANIZED STEEL BLADES MOUNTED IN GALVANIZED STEEL CHANNEL FRAME. BLADE SPACING SHALL NOT EXCEED 6 INCHES AND THE TOP AND BOTTOM EDGES OF THE BLADES SHALL BE CRIMPED TO STIFFEN THE BLADES. DAMPER BLADES SHALL BE INTERCONNECTED BY RODS AND LINKAGES TO PROVIDE SIMULTANEOUS OPERATION OF ALL BLADES. DAMPERS SHALL BE PROVIDED WITH EXTENDED RODS TO PERMIT INSTALLATION OF DAMPER OPERATORS. 3. DUCT MOUNTED DIAL REGULATORS WITH OPERATING HANDLE SHALL BE PROVIDED OR DAMPERS WHICH ARE LOCATED ABOVE HARD CEILINGS OR INACCESSIBLE LOCATIONS. CONCEALED CEILING MOUNTED DIAL REGULATORS SHALL BE PROVIDED ON VOLUME CONTROL DAMPERS WHICH ARE LOCATED ABOVE HARD CEILINGS. CONCEALED REGULATORS SHALL BE PROVIDED WITHIN DIFFUSER FACE WITH SCREW ADJUSTMENT. 4. PROVIDE DAMPERS AT ALL SUPPLY AND RETURN DUCT RUN OUTS TO EACH AIR DISTRIBUTION DEVICE WITH ACCESSIBLE ADJUSTMENT LEVER OR DIAL -TYPE REGULATOR ACTUATOR. C. DUCT FITTINGS 1. SPIN_IN COLLARS SHALL BE GALVANIZED STEEL FOR USE WITH RECTANGULAR OR SQUARE SHEET METAL DUCTWORK. SPIN -IN COLLARS SHALL HAVE AIR SCOOP (FOR SUPPLY DUCTS) AND DAMPER (SUPPLY AND RETURN). 2. TURNING VANES SHALL BE INSTALLED IN ALL 90 DEGREES SQUARE AND RECTANGULAR ELBOWS AND AT OTHER LOCATIONS SHOWN ON THE DRAWINGS WITH THE EXCEPTION OF KITCHEN EXHAUST. 3. CURVED ELBOWS SHALL HAVE A CENTERLINE RADIUS NOT LESS THAN 1 1/2 TIMES THE DUCT WIDTH. 4. DISSIMILAR METALS SHALL BE ISOLATED TO PREVENT GALVANIC CORROSION. JOINTS NOT PROVIDED WITH GASKETS SHALL BE ISOLATED WITH 1/161NCH MINIMUM THICKNESS ASPHALT IMPREGNATED BUILDING PAPER. 5. PROVIDE DAMPERS AT RETURN DUCT AND OUTSIDE AIR DUCT CONNECTIONS DOWNSTREAM OF ANY DUCT CONNECTIONS OR TAKE OFFS. 6. FLEXIBLE DUCT CONNECTIONS SHALL BE NON-COMBUSTIBLE GLASS FABRIC DOUBLE COATED WITH NEOPRENE 30 OZ. PER SQUARE YARD. 7. FIRE DAMPERS SHALL BE THE FOLDING BLADE FUSIBLE LINK TYPE CONFORMING TO UL 555 AND LABELED FOR INSTALLATION IN FIRE RATED WALLS AND FLOORS. DAMPERS IN FLOOR SHALL HAVE SPRING OPERATOR. DAMPERS, EXCEPT FOR LOWER SECTIONS OF A MULTIPLE SECTION ASSEMBLY, AND THOSE INSTALLED BEHIND GRILLES AND REGISTERS, SHALL HAVE BLADES OUT OF THE AIR STREAM WHEN DAMPER IS IN THE OPEN POSITION. DAMPERS IN WALLS OR FLOORS RATED 2 HOURS OR LESS SHALL BE RATED FOR 1 1/2 HOURS; DAMPERS IN WALLS RATED 3 OR 4 HOUR SHALL BE RATED FOR 3 HOURS. DAMPERS SHALL BE CONSTRUCTED OF GALVANIZED STEEL. PROVIDE AT EACH FIRE RATED WALL PENETRATION (REFER TO ARCH. DRAWINGS) 8. SMOKE DAMPERS SHALL BE THE MULTI -BLADE TYPE CONFORMING TO UL 555S WITH AN ASSEMBLY TEMPERATURE RATIN F 2 G 0 50 DEGREES F. DAMPER SHALL BE CONSTRUCTED OF GALVANIZED STEEL AND SHALL BE PROVIDED WITH A FACTORY-M UNTED ELE RI 0 CT C DAMPER OPERATOR, SUITABLE FOR OPERATION ON 120V, 60 HZ SUPPLY. PROVIDE AT EACH SMOKE BARRIER LOCATION (REFER TO ARCH DRAWINGS . 9. DUCT -TO -DUCT JOINTS IN ROUND DUCT UP TO AND INCLUDING 60" IN DIAMETER SHALL BE MADE BY USING SLEEVE COUPLINGS, REINFORCED BY ROLLED BEADS. DUCT -TO -FITTING JOINTS IN ROUND DUCT UP TO AND INCLUDING 60" IN DIAMETER HALL BE MADE Y S B SLIP_FIT OF THE PROJECTING COLLAR ON THE FITTING INTO THE DUCT. SLEEVE SHALL BE THE SAME GAUGE GALVANIZED STEEL AS TH D E UCT; INSERTION LENGTH OF SLEEVE COUPLING AND FITTING COLLAR SHALL BE NOT LESS THAN 2". AFTER THE JOINT IS SLIPPED TO ETHER E G SH ET METAL SCREWS SHALL BE INSTALLED FOR ECHANICAL STRENGTH• SCREWS SHALL BEE UALLY PA ED N M RE T A M Q S C 0 0 H N 12" ON CENTERS AND WITH A MINIMUM OF 3 SCREWS IN EACH JOINT. SCREWS SHALL BE PLACED AT 1/2" FROM THE JOINT BEAD. DUCT -TO -DUCT JOINTS IN DUCTS UP TO AND INCLUDING 12" IN DIAMETER FOR PRESSURE CLASS 2" AND BELOW MAY BE THE BEADED -CRIMP TYPE AND EACH JOINT SHALL BE FASTENED WITH SHEET METAL SCREWS, EQUALLY SPACED, NOT MORE THAN 12" ON CENTERS AND WITH A MINIMUM OF 3 SCREWS IN EACH JOINT. THE BEADED -CRIMP JOINT SHALL PROVIDE AT LEASTA 1 LAP TO ACCOMM DATE THE HEET META 0 S L SCREWS 10. ALL DUCT JOINTS LONGITUDINAL TRANSVERSE AND DUCT PENETRATIONS SHALL BE SEALED USING METHODS OUTLINED IN SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. 11. DUCT COLLARS SHALL BE PROVIDED WHERE DUCTS PASS THROUGH MASONRY WALLS AND PARTITIONS WHICH EXTEND FULL HEIGHT TO THE UNDERSIDE OF THE STRUCTURE AND SHALL BE FABRICATED FROM 22 GAUGE GALVANIZED STEEL SHEET. DUCT COLLAR SHALL BE PROVIDED ON BOTH SIDES OF WALL AND PARTITION EXCEPT OLLAR HALL BE M TTED S S C 5 0 I ON THAT SIDE OF THE WALL ON WHICH REGISTERS AND GRILLES ARE INSTALLED. FLANGES SHALL BE INSTALLED TIGHT AGAINST THE WALL. THE SPACE BETWEEN THE DUCT AND THE WALL SHALL BE PACKED WITH FIBERGLASS BLANKET IN ULATION. S 12. DUCT HANGERS AND SUPPORTS SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS. IN ADDITION, HANGERS SHALL BE SPACED NOT OVER 8'_0" ON CENTERS. FOR RECTANGULAR DUCTS, WITH LONGEST DIMENSIONS UP THROUGH 60" HANGERS, THE HANGERS SHALL BE GALVANIZED STEEL STRAP TYPE; WITH LONGEST DIMENSION 61" AND LARGER, HANGERS SHALL BE TRAPEZE TYPE CONSTRUCTED OF GALVANIZED STEEL ANGLES WITH ROUND HANGERS RODS. SIZES FOR STRAP HANGERS AND TRAPEZE ANGLES AND RODS SHALL BE BASED ON DUCT SIZE AS SCHEDULED IN THE SMACNA HVAC DUCT CON TRUCTION STANDARD . S S 13. FOR ROUND DUCTS; THE HANGERS SHALL BE THE GALVANIZED STEEL STRAP HANGERS. SIZES AND NUMBER FOR STRAP HANGERS SHALL BE BASED ON DUCT SIZE AS SCHEDULED IN THE SMACNA HVAC DUCT CONSTRUCTION STANDARDS. D. ROOF CAPS 1. UNLESS OTHERWISE SPECIFIED, ROOF INTAKE AND EXHAUST CAPS SHALL BE ROUND, MINIMUM 16 GAUGE SPUN -ALUMINUM WITH CONTINUOUSLY WELDED CURB CAP. PROVIDE WITH MANUFACTURER'S ROOF CURB. PROVIDE SLOPED CURB FOR PITCHED ROOFS. EXHAUST ROOF HOODS PROVIDED WITH BACKDRAFT DAMPER. OA HOODS SHALL BE PROVIDED WITH A 120/1 MOTORIZED DAMPER TO CLOSE WHEN EQUIPMENT SERVED IS POWERED DOWN UNLESS INDIVIDUAL MOTORIZED DAMPERS ARE INDICATED AT EQUIPMENT BRANCHES. E. LOUVERS 1. LOUVERS SHALL BE STATIONARY ALUMINUM, 4" DEEP WITH DRAINABLE BLADES, HIDDEN MULLION, ALL 0.081" ALUMINUM WALL THICKNESS, AND KYNAR FINISH TO BE COORDINATED WITH ARCHITECT FOR COLOR. LOUVER SIZED FOR 50% FREE AREA FOR 800 FPM AIRSPEED TO PREVENT WATER ENTRAINMENT. PROVIDE EACH LOUVER WITH A MINIMUM 18" DEEP FULL SIZE PLENUM WITH DUCT CONNECTION SIZED AS INDICATED. PROVIDE OUTDOOR AIR SUPPLY LOUVERS INLET PLENUMS WITH ELASTOMERIC LINER AND PROVIDE MOTORIZED DAMPER AT CONNECTED DUCT. LAYOUT BASIS IS RUSKIN ELF375DX. PROVIDE WITH INSECT SCREENING AT LOUVER FACE. V. HVAC EQUIPMENT A. CONTRACTOR SHALL VERIFY REASONABLE OPERATION OF EXISTING UNIT TO REMAIN IN USE AND MAKE ANY REPAIRS OR COMPONENT REPLACEMENT REQUIRED TO HAVE THE UNITS OPERATE A FULL CAPACITY. ALL RUST AND EXTERIOR DAMAGE SHOULD BE REPAIRED AND PAINTED. A TECHNICIAN'S REPORT SHOULD BE ATTAINED AND DELIVERED TO THE OWNER FOR APPROVAL FOR EXISTING EQUIPMENT REPAIRS. B. ALL NEW AND REUSED UNIT ACCESS AND CONNECTION OPENINGS SHALL BE SEALED WITH PROVIDED GROMMETS, GASKETS FOR AIR TIGHT CONSTRUCTION WITH CONTINUOUS CASE INSULATION. CONTRACTOR TO REPAIR OR REPLACE DAMAGED DOORS, SEALS, GASKETS, GROMMETS ETC... THAT PREVENT AIR -TIGHT CASING. C. ALL EXHAUST SHALL BE DUCTED FROM UNIT OUTLET TO ROOF CAP INLET OR LOUVER WITH CONTINUOUSLY SEALED DUCTING. NO EXHAUST SHALL BE OPENED INTO THE BUILDING EXTERIOR. PROVIDE ENCLOSED DUCT TRANSITION TO EACH ROOF CAM OR WALL LOUVER. D. ALL AIR MOVING EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION AND FLEXIBLE DUCT CONNECTIONS. E. CONTRACTOR SHALL PROVIDE GRAVITY DRAINAGE FOR ALL CONDENSATE -PRODUCING HEATING/COOLING EQUIPMENT VIA GRAVITY DRAINAGE OR CONDENSATE PUMP IF GRAVITY DRAINAGE CANNOT BE ACHIEVED. F. PROVIDE 2 SETS OF FILTERS FOR EACH FILTERED HVAC EQUIPMENT PIECE. PROVIDE FILTER AT INITIAL START-UP, JUST BEFORE TEST AND BALANCE AND AGAIN AT TURN OVER TO OWNER. ALL AIR INLETS AND UTLETS SHALL BE EALED WI H F T R M 0 S T IL E EDIA DURING GENERAL CONSTRUCTION PRIOR TO TEST AND BALANCE. G. ROOFTOP UNITS 1. PROVIDE PACKAGED DX ROOFTOP UNITS MANUFACTURED BY TRANE, LENNOX, AAON, CARRIER, OR YORK. PROVIDE WITH CAPACITIES AND ACCESSORIES PER UNIT SCHEDULE. PROVIDE CUSTOM SLOPED ROOF CURBS FOR ROOFS WITH GREATER THAN 2% SLOPE. PROVIDE VIBRATION ISOLATION TYPE ROOF CURBS FOR UNITS DIRECTLY OVER MUSIC REHEARSAL, PERFORMANCE OR OTHER ASSEMBLY AREAS. ALL UNITS SHALL BE PROVIDED WITH A MOTORIZED OA DAMPER OR ECONOMIZER, COIL GUARDS, HINGED ACCESS PANELS, SUPPLY AND RETURN SMOKE DETECTORS, STAINLESS STEEL DRAIN PAN AND BURNER (FOR GAS UNITS). PROVIDE EACH RTU WITH CONVENIENCE RECEPTACLE (SEPARATE CIRCUIT) AND DISCONNECT. OTHERWISE COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR FIELD -MOUNTED DISCONNECT AND RECEPTACLE. ROUTE ALL CONDENSATE PIPING TO NEAREST ROOF DRAIN OR OTHER LOCALLY APPROVED LOCATION WITH THE REQUIRED AIR GAP. NO PIPING SHALL SIT ON THE ROOF SURFACE. SHIFT EXISTING OR NEW VENTS OR EXHAUST TERMINATIONS OR SHIFT UNITS AS NEEDED TO ASSURE 10' BETWEEN ANY EXHAUST OR FLUE AND THE RTU INTAKE. 2. ADAPTER CURBS MAY BE USED WITH SPECIFIC ENGINEER APPROVAL OF SPECIFICALLY SUBMITTED ROOF CURBS (MAXIMUM OF 18" CURB HEIGHT). CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL ANALYSIS OF EXISTING CURBS AND UNIT SUPPORTS FOR ADAPTER CURB CONNECTIONS. G. SPLIT SYSTEMS 1. INDOOR UNITS SHALL BE INSTALLED DEAD LEVEL WITH PROVISIONS FOR POSITION, CONDENSATE DRAINAGE AND REFRIGERANT PIPE CONNECTIONS THAT DO NOT BLOCK EQUIPMENT SERVICE OR FILTER ACCESS. PROVIDE CONDENSERS WITH ANTI -SHORT CYCLE TIMER, CRANKCASE HEATER, LOW AMBIENT CONTROLS, COIL GUARDS. INDOOR AND OUTDOOR PIECES SHALL BE BY IDENTICAL MANUFACTURER LISTED BY THE MANUFACTURE AS COMPATIBLE. CASED COOLING COILS SHALL BE SPECIFICALLY LISTS AND WITH MATCHING SIZE WHEN USED WITH A FURNACE. FURNACES SHALL BE HIGH EFFICIENCY FOR USE WITH PVC FLUE AND INTAKE REQUIRING FLUE CONDENSATE NEUTRALIZER AND DRAIN. 2. REFRIGERANT PIPING SHALL BE RUN PARALLEL TO BUILDING WALLS IN WHICH INSTALLED UNLESS OTHERWISE INDICATED ON THE DRAWINGS WITH CONTINUOUS ELASTOMERIC INSULATION AND JACKETING INDOOR AND OUT. PROVIDE WITH AIR TIGHT VAPOR ENCAPSULATION BY USE OF MASTIC AND JACKETING. PROVIDE PIPE HANGER WITH SADDLES AT PIPE SUPPORTS FOR REFRIGERANT PIPING. TYPE L OR K (UNDERGROUND) COPPER TUBING INTENDED FOR ACR APPLICATIONS- DEHYDRATED, CHARGED WITH NITROGEN, AND PLUGGED BY THE MANUFACTURER. PROVIDE FORMED FITTINGS, SUCH AS ELBOWS (SHALL BE LONG SWEEP) AND TEES, ALL JOINTS SHALL BE BRAZED WITH OXY-ACETYLENE TORCHES BY A QUALIFIED TECHNICIAN. SOFT COPPER TUBING SHALL NOT BE ALLOWED UNLESS NOTED ON THE DRAWINGS. 3. PROVIDE INDOOR UNITS LOCATED ABOVE CEILINGS WITH SLOPED SECONDARY DRAIN PAN WITH A CAPPED VALVE AND THREADED HOSE OUTLET. UNIT AND EXTERIOR DRAIN PAN SUPPORT SHALL BE INDEPENDENT SUCH THAT DRAIN PAN CAN BE REMOVED WITHOUT AFFECTING AIR HANDLING UNIT INSTALLATION. 4. THE PREFERENCE SHALL BE A FLOAT SWITCH IN THE EXTERNAL DRAIN PAN TO SHUT THE UNIT DOWN. IF NOT ALLOWED BY CODE OR INSPECTOR, ROUTE THE CONDENSATE TO A CONSPICUOUS LOCATION- OVER A MOP SINK OR SERVICE SINK IF POSSIBLE. 5. FOR LONG REFRIGERANT LINE LENGTHS ABOVE 100', PROVIDE ALL ACCESSORIES, ACCUMULATORS, RESIZED PISTONS AND LINE SETS PER MANUFACTURER REQUIREMENTS. 6. FLOOR MOUNTED VERTICAL UNITS SHALL BE MOUNTED ON A 24" TALL, FULL SIZE RETURN PLENUM WITH METAL GAUGE SUFFICIENT TO SUPPORT UNIT WEIGHT. H. FANS -GENERAL 1. FANS SHALL BE TESTED AND RATED IN ACCORDANCE WITH AMCA 210. 2. ALL FANS SHALL BE SUPPORTED INDEPENDENT OF CONNECTED DUCT OR CEILING SUPPORTS AND PROVIDED WITH FLEXIBLE INLET/OUTLET CONNECTIONS. 3. FAN WHEELS SHALL BE STATICALLY AND DYNAMICALLY BALANCED. 4. FANS SHALL BE DIRECT DRIVE WITH SPEED CONTROLLER, DIRECT DRIVE ECM. FANS SHALL NOT BE BELT DRIVE UNLESS SPECIFICALLY NOTED ON PLANS. V-BELT DRIVES SHALL BE DESIGNED FOR NOT LESS THAN 150% OF CONNECTED DRIVING CAPACITY AND MOTOR SHEAVES SHALL BE ADJUSTABLE TO PROVIDE NOT LESS THAN 20% SPEED VARIATION. SHEAVES SHALL BE SELECTED TO DRIVE THE FAN AT A SPEED TO PRODUCE THE SCHEDULED CAPACITY INDICATED ON THE DRAWINGS WHEN SET AT THE APPROXIMATE MIDPOINT OF THE SHEAVE ADJUSTMENT. MOTORS WITH V-BELT DRIVES SHALL BE PROVIDED WITH ADJUSTABLE BASES. 5. SAFETY/DISCONNECT SWITCHES (UNLESS SCHEDULED AS UNIT -INTEGRAL) AND STARTERS SHALL BE PROVIDED 6. BY ELECTRICAL CONTRACTOR AND SHALL CONFORM TO REQUIREMENTS OF ELECTRICAL DRAWINGS AND SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL COORDINATE MOUNTING LOCATION TO MAINTAIN MAINTENANCE CLEARANCES. ALL THREE PHASE FANS SHALL BE PROVIDED WITH STARTER AND/OR CONTACTORS AS REQUIRED TO CONTROL FANS AND AUXILIARY DEVICES SUCH AS CONTROLS SYSTEM TIE-IN OR DAMPER ACTUATION. L CENTRIFUGAL ROOF FANS 1. FANS SHALL BE CENTRIFUGAL ROOF EXHAUSTERS WITH WATERPROOF DESIGN SO THAT WATER CANNOT ENTER THE BUILDING THROUGH FAN HOUSING WHETHER OR NOT FAN IS OPERATING. FAN SHALL BE EQUIPPED WITH A BACKDRAFT DAMPER ON INLET, A BIRD SCREEN ON OUTLET AND A FACTORY FABRICATED ROOF CURB. GENERAL EXHAUST LAYOUT BASIS (NON- KITCHEN APPLICATIONS)- COOK ACED 2. FAN SHALL HAVE A ONE-PIECE ALUMINUM HOUSING ENCLOSING THE MOTOR AND DRIVE, AN ALUMINUM SHROUD ENCLOSING THE FAN WHEEL, AND AN ALUMINUM CURB CAP. CURB CAP SHALL HAVE A 1 INCH WIDE BY 1/4 INCH THICK FOAM RUBBER GASKET FACTORY APPLIED TO UNDERSIDE PERIMETER OF CURB CAP. AN INTERNAL POWER WIRING POST SHALL EXTEND FROM MOTOR COMPARTMENT THROUGH CURB CAP. WHERE WIRING POST PENETRATES HOUSING AND CURB CAP, PENETRATION SHALL BE SEALED. 3. FAN WHEEL SHALL BE FORWARD CURVED OR BACKWARD INCLINED CENTRIFUGAL TYPE OF ALUMINUM CONSTRUCTION. FAN WHEEL SHALL BE STATICALLY AND DYNAMICALLY BALANCED. ON BELT DRIVE UNITS, SHAFT BEARINGS SHALL BE SELF -ALIGNING, PILLOW BLOCK BALL TYPE. BEARINGS NOT PERMANENTLY SEALED AND LUBRICATED SHALL HAVE EXTENDED GREASE FITTINGS FOR EASY ACCESS. 4. MOTOR AND DRIVE SHALL BE LOCATED IN A VENTILATED COMPARTMENT OUTSIDE OF THE AIR STREAM. FAN SHALL HAVE FACTORY INSTALLED DISCONNECT SWITCH PRE -WIRED TO MOTOR AND MOUNTED WITHIN MOTOR COMPARTMENT. MOTOR AND DRIVE SHALL BE MOUNTED ON VIBRATION ISOLATORS. 5. KITCHEN EXHAUST FANS SHALL BE UL 762 RATED AND PROVIDED WITH POWER/CONTROL WIRING OUTSIDE OF FAN HOUSING AND CURB. FANS SHALL BE MOUNTED WITH 18" MINIMUM HEIGHT FROM FAN BASE TO ROOF /FLASHING AND DISCHARGE HEIGHTA MINIMUM OF 40" ABOVE ROOF SURFACE. SIDE INLET FANS SHALL BE PROVIDED WITH INLET HEIGHT SUCH THAT ALL ROOF MOUNTED HORIZONTAL DUCT CAN BE MOUNTED 20" ABOVE ROOF. PROVIDE NON -VENTED CURB FOR FIRE -WRAP APPLICATIONS AND VENTED CURB FOR ENCLOSURE SHAFT APPLICATIONS. 6. LOCATE EXHAUST FAN DISCHARGE 10' FROM ANY INTAKE OR BUILDING OPENING OR 2' ABOVE SAID OPENINGS IF CODE ALLOWS. J. IN-LINE/CEILING FANS 1. FAN SHALL BE IN -LINE CENTRIFUGAL TYPE WITH SQUARE OR RECTANGULAR HOUSING AND BACKDRAFT DAMPER. FANS SHALL BE DESIGNED FOR HORIZONTAL OR VERTICAL MOUNTING. LAYOUT BASIS IS COOK GN/GC. 2. FAN HOUSING SHALL BE STEEL WITH FACTORY APPLIED BAKED ENAMEL PAINT ON EXTERIOR. HOUSING SHALL BE INTERNALLY INSULATED WITH 1/2" THICK (MINIMUM) COATED FIBERGLASS INSULATION. INSULATION SHALL COMPLY WITH ASTM E84 AND NFPA 255 FOR MAXIMUM RATINGS OF FLAME SPREAD RATING OF 25 AND SMOKE DEVELOPED RATING OF 50. HOUSING SHALL HAVE MOUNTING BRACKETS AT EACH CORNER. 3. FAN WHEEL SHALL BE BACKWARD INCLINED CENTRIFUGAL TYPE OF ALUMINUM CONSTRUCTION. ON BELT DRIVE UNITS, SHAFT BEARINGS SHALL BE SELF -ALIGNING, PILLOW BLOCK BALL TYPE. BEARINGS NOT PERMANENTLY LUBRICATED AND SEALED SHALL HAVE EXTENDED GREASE FITTINGS. 4. MOTOR AND DRIVE SHALL BE MOUNTED ON VIBRATION ISOLATORS. FAN SHALL HAVE A FACTORY INSTALLED DISCONNECT SWITCH MOUNTED ON EXTERIOR OF HOUSING AND PRE -WIRED TO FAN MOTOR. 5. PROVIDE ALUMINUM GRILLE OPTION FOR CEILING MOUNTED FANS. FANS SHALL BE ROUTED TO ROOF CAP OR LOUVER SIZED AT 800 FPM OUTLET AIRSPEED. VI. PIPING A. USE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED TOGETHER. B. DOMESTIC WATER & PUMPED CONDENSATE 1. UNDERGROUND WATER SERVICE PIPING 3" IN ZE AND LAR ER HAL SI G S L BE CLASS 50 DUCTILE IRON PIPE, AWWA C151, WITH HUB AND SPIGOT, PUSH_ON JOINTS, AND CLASS 50 OR GREATER MECHANICAL JOINT DUCTILE IRON FITTINGS ALL CEMENT LINED PER AWWA C104. MECHANICAL JOINTS FOR DUCTILE IRON PIPE SHALL BE MADE WITH A F LL ER 0 OW GLAND GASKET BOLTS AND NUTS. PUSH ON JOINTS F R 0 DUCTILE PIPE SHALL BE MADE WITH A NE PIE E L RI AT 0 C UB C ED COMPRESSION RUBBER GASKET AS PER AWWA Clll. 2. UNDERGROUND STEEL PIPE AND FITTINGS INCLUDING THE PORTION THROUGH THE FLOOR SHALL BE PROTECTED AGAINST CORROSION BY APPLICATION OF PROTECTIVE COATINGS. PRIOR TO COATING, PIPE AND FITTINGS SHALL BE CLEANED OF ALL RUST, SCALE, DIRT AND OIL. PIPES AND FITTINGS SHALL BE GIVEN TWO COATS OF A COAL -TAR BASE BITUMINOUS PROTECTIVE COATING, EACH HAVING A DRY FILM THICKNESS OF 7-9 MILS. THE COMBINED THICKNESS OF BOTH COATS COMBINED SHALL BE 15-18 MILS. 3. UNDERGROUND WATER SERVICE PIPING 2 1 2" IN SIZE AND SMALLER T A P - O DINT 1' 0" ABOVE THE FINISHED FLOOR SHALL BE. TYPE "K" HARD DRAWN COPPER TUBING, ASTM B88, WITH BRAZED JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS.. BRAZED JOINTS SHALL BE MADE USING BCUP-5 BRAZING ALLOY WITH A COMPATIBLE FLUX. 4. ABOVE -GROUND WATER PIPING - 4" AND SMALLER SHALL BE. TYPE "L" HARD DRAWN COPPER TUBING, ASTM B88, WITH SOLDERED JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS. SOLDER JOINTS SHALL BE MADE USING A 95-5 TIN -ANTIMONY SOLDER (NO -LEAD SOLDER) WITH A COMPATIBLE FLUX. 5. UNDERGROUND WATER PIPING TO TRAP PRIMERS OR HVAC CONDENSATE PUMP DISCHARGE SHALL BE. TYPE "L" SOFT DRAWN COPPER TUBING, ASTM B88, WITHOUT FITTINGS. 6. FLANGED JOINT SHALL BE MADE WITH RING TYPE N N-METALLI ASK T L 0 C G E S BO TS AND NUTS. 7. THREADED JOINTS AT EQUIPMENT CONNECTIONS SHALL BE MADE UP WITH TEFLON TAPE. AFTER CUTTING BUT PRIOR TO THREADING, PIPE SHALL BE REAMED AND SHALL HAVE BURRS REMOVED. 8. GROOVED MECHANICAL JOINTS: GROOVED JOINTS FOR COPPER AND GALVANIZED STEEL PIPES SHALL BE INSTALLED USING BOLTED MECHANICAL COUPLING, PRESSURE -RESPONSIVE GASKET ALONG WITH GROOVED AND FITTINGS. LAYOUT BASIS SHALL BE ANVIL GRUV-LOCK, 9. DIELECTRIC ADAPTERS SHALL BE PROVIDED BETWEEN COPPER AND IRON PIPE CONNECTIONS AND BETWEEN FERROUS AND NONFERROUS PIPING OR EQUIPMENT. 10. UNDERGROUND WATER PIPING SHALL HAVE A MINIMUM COVER OF 3'- 0" TO THE TOP OF THE PIPE. 11. INSTALL WATER HAMMER ARRESTORS ABOVE CEILING ON THE HOT AND COLD WATER BRANCH LINES SERVING A BATTERY OF FIXTURES; ON THE COLD WATER BRANCH LINES SERVING INDIVIDUAL FLUSH VALVE WATER CLOSETS AND URINALS; AND ELSEWHERE AS INDICATED ON THE DRAWINGS. PROVIDE ACCESS PANEL FOR WHA LOCATED ABOVE HARD CEILINGS. 12. VACUUM BREAKERS SHALL BE PROVIDED ON ALL HOSE OUTLETS, HOSE BIBS AND HYDRANTS UNLESS THE DRAWINGS INDICATE THAT A BACKFLOW PREVENTER IS TO BE PROVIDED ON THE PIPING SERVING THE OUTLET. 13. INSTALL 1/2" CW LINE FROM NEAREST CW MAIN OR BRANCH LINE TO ALL FLOOR DRAINS WITH TRAP PRIMER FOR TRAP PRIMING. UNDERGROUND PIPING FROM TRAP PRIMER TO FLOOR DRAINS SHALL BE INSTALLED WITHOUT FITTINGS. TRAP PRIMERS SHALL BE PROVIDED FOR ALL FLOOR DRAINS AND HUB DRAINS. 14. CONNECT HOT AND COLD WATER PIPING SYSTEM TO EQUIPMENT AS INDICATED, AND COMPLY WITH EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE SHUT-OFF BALL VALVE AND UNION FOR EACH CONNECTION, PROVIDE DRAIN VALVE ON DRAIN CONNECTIONS. PROVIDE SINGLE SHUTOFF BALL VALVE FOR HEADERS SERVING HOT OR COLD WATER TO MULTIPLE FIXTURES WITHIN A SINGLE WALL OR CHASE. PROVIDE ACCESS PANEL FOR VALVES INSTALLED ABOVE HARD CEILINGS. 15. ALL DOMESTIC WATER SERVICE AND SUPPLY PIPING INSTALLED UNDER THIS DIVISION SHALL BE DISINFECTED WITH CHLORINE BEFORE IT IS PLACED INTO OPERATION. THE CHLORINATING MATERIAL SHALL BE LIQUID CHLORINE CONFORMING TO FED. SPEC. BB-C-120 AND SHALL BE INTRODUCED TO THE SYSTEM BY EXPERIENCED OPERATORS ONLY. THE CHLORINE SOLUTION APPLIED TO THE PIPING SECTIONS OR SYSTEM SHALL CONTAIN AT LEAST FIFTY PARTS PER MILLION OF AVAILABLE CHLORINE AND SHALL REMAIN IN THE SECTIONS OR SYSTEM FOR A PERIOD OF NOT LESS THAN SIXTEEN (16) HOURS. DURING THE DISINFECTION PERIOD ALL VALVES SHALL BE OPENED AND CLOSED AT LEAST FOUR TIMES. ATTHE END OF THE RETENTION PERIOD, NO LESS THAN 50 PPM OF CHLORINE SHALL BE PRESENT IN THE EXTREME END OF THIS SYSTEM. AFTER THEDISINFE I PERI DTH CT ON 0 E CHLORINATED WATER SHALL BE FL USHER FROM THE Y TEM WI H L S S T C EAR WATER UNTIL THE RESIDUAL CHLORINE CONTENT IS NOT GREATER THAN TWO -TENTHS - (0.2) - PARTS PER MILLION. THE CONSTRUCTION MANAGER SHALL SUBMIT TO THE ARCHITECT WRITTEN CERTIFICATION THAT THE SYSTEM WAS DISINFECTED. CERTIFICATION SHALL INCLUDE NAME OF PROJECT, NAME OF OWNER, NAME OF OPERATORS, DATE OF DISINFECTION, TIMES OF DISINFECTION PERIOD, MAXIMUM CHLORINE LEVEL AND RESIDUAL CHLORINE LEVEL. C. NATURAL GAS 1. ABOVE-GR ND OU MAXIMUM 2 1 2' GAS PIPING SHALL BE BLACK STEEL PIPE .S HED LE 4 / C U 0, ASTM A53 WITH STANDARD WEIGHT WROUGHT STEEL SO KET-WELDFITTIN P C GS ER ASTM A234 OR THREADED CONNECTIONS. PIPE SIZES 3" AND UP OR WITH PRESSURE ABOVE 5PSI SHALL ONLY BE PERMITTED WITH SOCKET -WELDED JOINTS (NO THREADED CONNECTIONS). 2. STEEL GAS PIPING TO BE INSTALLED UNDERGROUND SHALL BE FURNISHED WITH A FACTORY APPLIED COATING WHICH SHALL CONSIST OF A RESILIENT, EXTRUDED, POLYETHYLENE SLEEVE WHICH IS SEALED TO THE PIPE. THE PLASTIC COATING SHALL BE NOT LESS THAN 25 MILS THICK AND SEALED TO THE PIPE WITH A HOT APPLIED ADHESIVE WHICH RETAINS ITS ELASTICITY IN HOT AND COLD ENVIRONMENTS. 3. FIELD APPLIED WRAPPING TAPE FOR FITTINGS AND JOINTS SHALL BE COAL TAR WITH HEAVY VINYL OR POLYESTER FILM BACKING MEETING FEDERAL SPECIFICATION HH-T-30A, TAPECOAT CT OR TAPECOAT 20 OR JT JOINT COATINGS, INC., WITH PRIMER, APPLICATION PROCEDURES AND HEATING IN ACCORDANCE WITH THE TAPE MANUFACTURER'S RECOMMENDATIONS. 4. ARRANGE WITH THE UTILITY COMPANY TO PROVIDE GAS SERVICE TO INDICATED LOCATION WITH SHUTOFF AT TERMINATION. MAKE ALL ARRANGEMENTS WITH UTILITY AS TO THE EXTENT OF ITS WORK, AND PAY ALL COSTS, FEES AND SECURE PERMITS INVOLVED TO OBTAIN SERVICE FOR THE BUILDING. 5. PROVIDE SHUTOFF IN GAS SERVICE PIPE AT ENTRY IN BUILDING, EXT/END PIPE TO GAS METER LOCATION INDICATED; PROVIDE PARTS AND ACCESSORIES REQUIRED BY UTILITY TO CONNECT TO METER. 6. PROVIDE VALVE AND UNION SHALL BE PROVIDED AT EACH CONNECTION TO A PIECE OF EQUIPMENT. EQUIPMENT PROVIDED WITH A FLANGED INLET SHALL HAVE A FLANGED CONNECTION. 7. DRIP LEGS, 6-INCHES LONG, SHALL BE PROVIDED IN GAS PIPING AT ENDS OF HORIZONTAL RUNS, AT THE BASE OF RISERS AND AT CONNECTIONS TO EQUIPMENT. DRIP LEG CAP SHALL BE REMOVABLE WITH MINIMUM 4" BETWEEN CAP AND WALL OR ROOF. 8. GAS PIPING WITHIN THE BUILDING SHALL BE RUN ABOVE FLOOR SLAB. 9. PRESSURE REGULATORS ARE TO BE PROVIDED ON ALL EQUIPMENT IF NOT PROVIDED AS PART OF THE EQUIPMENT. COORDINATE INLET/OUTLET PRESSURES WITH ACTUAL DELIVERED PRESSURE AND EQUIPMENT INLET PRESSURES. CONTRACTOR SHALL ARRANGE FOR ADJUSTMENT OF GAS PRESSURE TO PREVENT EXCESSIVE OR INSUFFICIENT GAS PRESSURE TO ALL EQUIPMENT PIECES. 10. PROVIDE FLEX HOSE CONNECTION TO ALL INDOOR APPLIANCES NOT SUPPLIED WITH THE EQUIPMENT PIECE BY THE OWNER OR EQUIPMENT PROVIDER. 11. THREADED JOINTS SHALL BE MADE WITH A MIXTURE OF GRAPHITE AND OIL APPLIED TO MALE THREADS ONLY. AFTER CUTTING AND PRIOR TO THREADING, PIPE SHALL BE REAMED AND SHALL HAVE BURRS REMOVED. 12. WELDED JOINTS SHALL BE FUSION WELDED IN ACCORDANCE WITH ANSI B31, SECTION 6. 13. FLANGED JOINTS SHALL BE FACED TRUE, PROVIDED WITH GASKET AND MADE SQUARE AND TIGHT. 14. BRAZED JOINTS SHALL BE MADE UP USING BCUP-5 BRAZING ALLOY WITH A COMPATIBLE FLUX. 15. ALL STEEL FITTINGS AND JOINTS IN UNDERGROUND PIPING SHALL BE FIELD -COATED USING A PRIMER AND FLEXIBLE POLYETHYLENE TAPE AND THE SAME MANUFACTURER AS THE PIPE COATING. DAMAGED COATING SHALL BE REPAIRED WITH PRIMER AND TAPE AS SPECIFIED FOR FITTINGS AND JOINTS. D. SANITARY WASTE &VENT, STORM, GREASE WASTE 1. UNDERGROUND SANITARY, WASTE AND VENT PIPING, AND STORM DRAINAGE PIPING, AND INDOOR PIPING ABOVE 8" IN SIZE SHALL BE SERVICE WEIGHT (COATED) CAST IRON SOIL PIPE AND FITTINGS, ASTM A74, WITH GASKET HUB AND SPIGOT JOINTS, ASTM C564. GASKET JOINTS FOR CAST IRON PIPE SHALL BE MADE WITH LUBRICATED NEOPRENE COMPRESSION GASKETS. PVC SHALL BE PERMITTED IF ALLOWED BY LOCAL CODE. UNDERGROUND PVC PIPING SHALL BE SCHEDULE 40 PVC WITH SOLVENT WELD JOINTS MEETING ASTM D-1785 AND ASTM D-2665. 2. ABOVE -GROUND SANITARY, WASTE AND VENT AND STORM DRAINAGE PIPING 8" AND SMALLER SHALL BE SERVICE WEIGHT CAST IRON SOIL PIPE AND FITTINGS, ASTM A888 AND CISPI 301, WITH STANDARD NO -HUB COUPLINGS. PVC SHALL BE PERMITTED OUTSIDE OF RETURN AIR PLENUMS WITH OWNER APPROVAL. NEOPRENE RUBBER GASKET AND MINIMUM 24 GAUGE TYPE 304 STAINLESS STEEL SHIELD AND FOUR STAINLESS STEEL BANDS FOR SIZES 1 1/2" THROUGH 4", SIX BANDS MINIMUM FOR SIZED 5" AND LARGER. 6" PIPE AND UP: NEOPRENE ELASTOMERIC GASKET AND SERIES 300 STAINLESS STEEL SHIELD AND MULTIPLE DRAW BANDS AND SCREW CLAMPS CONFORMING TO ASTM C-564 AND CISPI STANDARD 310-90. ABOVE -GROUND SANITARY PIPING, LOCATED OUTSIDE OF RETURN AIR PLENUMS MAY ALSO BE SCHEDULE 40 PVC WITH SOLVENT WELD JOINTS MEETING ASTM D-1785 AND ASTM D-2665 PER OWNER APPROVAL. 3. ALL WASTE PIPING 1" IN SIZE AND SMALLER SHALL BE TYPE "L" HARD DRAWN COPPER TUBING, ASTM B88, WITH SOLDERED JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS. SOLDERED JOINTS FOR TYPE'L' COPPER TUBING AND CAST DMV BRONZE PIPE SHALL BE MADE WITH 95-5 TIN -ANTIMONY (NO LEAD) SOLDER AND COMPATIBLE FLUX. E. PIPING HANGERS 1. PROVIDE CLEVIS SUPPORTS WITH BEAM CLAMP, CONCRETE ANCHORS (CONCRETE STRUCTURE), SCREWED BRACKET (WOOD STRUCTURE). PROVIDE HANGER OUTSIDE OF INSULATION WITH RIGID FOAM GLASS INSULATION SECTION AT HANGERS. PROVIDE 16 GAUGE PIPING SADDLE AT EACH HANGER. NO WELDING OR CUTTING OF STEEL STRUCTURAL MEMBERS SHALL BE PERMITTED. LAYOUT BASIS SHALL BE ANVIL 260. 2. PROVIDE SEISMIC HANGERS PER DRAWING REQUIREMENTS. 3. HANGER INSTALLATION FOR HOT WATER PIPING SHALL NOT PREVENT MOVEMENT FOR PIPING EXPANSION. 4. SPACING AS FOLLOWS: STEEL PIPE: 1/2" TO 1-1/4" - 7' ; 1-1/2" TO 2-1/2" - 9' ; 3"&4" -12' ; 6"&8" - 17' ; 10" AND UP- 22' COPPER PIPE: 1/2" TO 1" - 5' ; 1-1/4" TO 2" - 7' ; 2-1/2" AND UP - 9' CAST IRON: 10' WITH SUPPORT AT EACH JOINT, TAKEOFF, AND FITTING. PVC DRAINAGE (140 DEG F SERVICE UP TO 6"- 80 DEG F ABOVE 6"): UP TO 3" - 3' ; 4" TO 6" - 4' ; ABOVE 6" - 8' PVC VENT (80 DEG F SERVICE): UP TO 1-1/2" - 5' ; 2"-3" - 6' ; ABOVE 3" 7' U ICI � �� �/ O U) W O CD `T V A m N y W O w A N U t� � � Z w 11` W E-( cr 0 Lo U Ui w � 0 Q � 1O Lu V W ir - x = T I- C'7 U U z = N� N U cr N � v1 ui z_ cn D m • A4 • 14 SIN HA ♦ .• AGE Ng •.y 0. ♦ 1 i ♦ � o : 0. 7 •• . o v • r * rn • : Q STAT OF ; �% w i % z P• .� w D /ONA E . m Q U Z Q Q ui `1 cn Z Q m w w J •, • CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL MECHANICAL SPECIFICATIONS M0.2 PLOT DATE: S-1 360 4 S-1 360 7' i F Im rV MECHANICAL FLOOR PLAN. if I if S-1 1 01 o �� 10"0 t�lj S-1 10" o 300 r7z S-2L 400 16X12 S-2, 10"0 R-1 x 2 12 0_ l S-2 1270 N o r1 (I 12"0 .r-D S-1 h 470 12"0 X N S-1 \ 470 RTU-2 S-1 300 1 INa O 0 MECHANICAL KEY NOTES 1. NEW ROOFTOP UNIT. FULL SIZED SUPPLY TRANSITIONED TO SIZE SHOWN ON PLAN. FULL SIZE RETURN UP TO DUCT. 2. DUCTWORK LOCATED ABOVE CEILING. COORDINATE WITH STRUCTURE. 3. REMOTE SENSOR FOR UNIT DESIGNATED. MOUNT ON WALL AT 48" AFF. COORDINATE LOCATION IN FIELD. 4. RESTROOM EXHAUST FAN ON ROOF. COORDINATE CONTROLS WITH ELECTRICAL. RESTROOM EXHAUST SHALL BE INTERLOCKED WITH LIGHTING. COORDINATE WITH ELECTRICAL. 5. EXHAUST FAN, LOCATED ON ROOF, FOR TYPE I KITCHEN EXHAUST HOOD. 6. TYPE I KITCHEN HOOD INSTALLED BY CONTRACTOR. 7. PROVIDE 16 GA. EXTERNALLY WELDED LIQUID TIGHT KITCHEN HOOD EXHAUST DUCT. EXTEND UP TO ROOF MOUNTED FAN. PROVIDE TRANSITION FROM HOOD COLLAR TO ROOF FAN. 8. PROVIDE MANUAL VOLUME CONTROL DAMPER. (TYPICAL) 9. 7- DAY PROGRAMMABLE THERMOSTAT FOR UNIT DESIGNATED. COORDINATE LOCATION WITH OWNER AND OFFICE FURNITURE. WALL MOUNTED AT 48" AFF. 10. PROVIDE INSULATED PLENUM ABOVE AIR DEVICE. TYPICAL FOR THIS DEVICE. 11. MAKE-UP AIR UNIT LOCATED ON ROOF. PROVIDE FULL SIZE DROP. MAKE-UP AIR UNIT SHALL BE INTERLOCKED WITH HOOD CONTROLS. 12. MAKE-UP AIR SUPPLY DIFFUSERS- PERFORATED TYPE ���, ��S�G E•N SR�y,� � v 't o.STAdo O0. •,NA Q z w Y Q m w w 18014 A CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY I 5915 GALL BLVD. ZEPHYRHILLS, FL MECHANICAL PLANS M1.0 PLOT DATE: , / AD-2 HANGING ANGLE DETAIL FOE -IY LE:CIV I1UNI M P'IJ rcN FW 24 1.; =. , 4'f6" .74C" i.o 4 W,' 2.44. 2.14. - _ 3 X3: 1 - ,4 4E k4G' �i4 d SIIE 'i HANGING ANGLE' LC-CAT16 CALCULATIONS LITLIIED / a / BUILDING CODES - x. .5 H/.h C. ,11 f: FnR"�N:' 1. F5N 1 }!t,N, flu ,veu. > F RFA:,r:T:CN CLLARANC_ :O COMBUS IBLES I ICIL'.-iv:.A'1CH - ': ' �IfT'R'w, Nam.::eC T h.uf.:lr M'R.Ci:FlF`.� }utfr. a rx r a. ds.,n .,Ysx. 'I 1afJliiL.WL c(AHixcFlul i :F ...,xNun xu.. :GENERAI. NOTES K:ke l C,- I UL 1 sted, i>r..:.SCI iL Illll'I'. c15 bt ei,,, F­. 4 U St iak ss S(x:el FILTER DETA.E �uut1 t.a 'vnnxtJttuv _._.._rt.va�raTr TAC M-DF Fh G 7 H C_ IJ IIT6E_ J xI r-K r I , t N NU'c J _v 6 -.CO' D iy J4_•- K -r,D -? '7 ''.TS-F 8 is CU` U y 2130:J �4 CO' ' :0:-: ' PY.-ND-8 .t-SB-f' D:y q4 G PK-NJ-c--,1-Sis-F I2' O.00" D 5_ 3CuC L Si} PL ! JLL 7U:'JS k'JC ;GY -ND TO _.• ,." RJ'W RINT,': F M F.T. _.i 431 4'.._ 12' 1"350 -04@5'._. 6F ALOr.E C.:F�sed SLQNE a_ LL>F'saecJ 4` 14' 2f1'JO I I IIs�J LL- I %•,L:JN f, 4' 14' .-•11:i0 ;:.5:?I, �,,0. WY� Fxl,nivd MI D�:I' Al 9N. 4 1 le' 30C0 -0.Ec'E" [D3� a3L tiS K"RT yLONE Ex H'J ' ed HOOD L4F0 _UyIT10.4 HOOD iU. _ IAIa F'ETC] rr:Y P ,. TY?E U'Y lhElt, i LDr:GTE I'll P.irJS Rr:. W77 TYPE' ,WJ, RD_ Lf]LA'1JN SIZE I,, r' =�E'"TR[CnL -.-. -- -.-. _ i ,L >[L. M JL_ n f-H S -_. .[AVII Y - F SYSI Hll IN Hf .i: vlC.H! i C F.::'A'.e x.. I Ht_I"uil:r:: 1 4 i nla^an f•;- If I; : t?'xTa'x2e' A,:."ut R10' ''. 3.0 SC 1 1110-P 1 L'ght Far Y S LBO YES 4 L3S '3_ Ra:.'..: 1:.h 11-6l-:=. ::, :;1` :E.' �I .,_.. , ! S: a in -11,E;rn '' N :: L BS e. ".. R:,`^,e w,r I: rill.=•s 9 '0' 'F,' 'I. IEEE -0 S: ',w lr :"xloL en f: R.3ht :;%(I'x`4 x-'4" An ,d PHI' 'I -. 1. :. Cl;Sf r `:f. .VJ'..UFP ! Y-�• LBS FIG , O TAG ........ .............. U': IIUI4 _.__. ......_. __...... FIE"_D RAPPER ', JO` Hgh , V- 1_� RIgh 34C✓SPLASH 80;0D' H::g-, x 31-L L-IIg 43:1 SS �cl 1 IGFT QUAR.,R --ND PA>1FL 23' TCP `w.tlir..; 0' 3_t __r: WFs:h, 2.3' H'gn 431E SC -F"'-C;1 RT-R "Alf; PA.�F I. __-- i:J(, '.,:dt, -3. HiCt: 4iI SS :F IF. D -RA,PFR '.^1' F. oh. I N 2 .............................................................:......................................_....r_:..r......._....... ........... 'E,r5:1.00' x .3-(..fiL' nng .........._................................................... .."Sfl SS - ".:.................................._........_................._........ ............ ................-_......................... . .........__.....__._.........__...._ F ....................................._.....................................:.........................:..............._..'.�.�.`"..::..( GUAPT P _.vD P rL ? T r wdt" 0' D..t ry .Itch, ?T, Ilri' 430 SS a D gr rt IL L,v R rL: J !, yr nt, I.Isht i __-UL k .P :,,NO FANFANIL L r_ .CP wd'- G'tr t.'>r :blh, r"�'Z?FOIt�1m�'4� .xC%PP�Y P��'fYG-lufti') MO.;D :. O IAU :IUII, : WIDT- =NF. DIA, CFI:• S?. 28, 540 C.31, 1 tor, 114' 14` ML.a 1-,, 28' i40 C.37' 1 _ Gu, %60 2 F,­, 56' 11' S' :1..a = .'. B' 7E0 ...: ... ..... M A .... Pfi _....... 7n0._ 3 Fr .n 56, 113, NIL c'J' rEti ..._..... _._._..- - - _ _ _ __ ._..__ _._ : M- P.1 633 "A -------- 0,1.9' t .. f.l: r l7yr F 164' Is, 6, :1LA 63:i 01 AN- RESI J NI FIk' HE PP' -E^:G IJ Lkf__ YPF 'WTTI- F! "`D %o I AG:T TS 1_c1 T N ♦=T`,rr`.<K I- N.F-I l �F I TS'-- 'WITH .UNDER WRITERS LALOR.4TOR.-E�, NC :UL) :YSILM -I ALL. LL '. PA 1_C 0 Al UMA' IG C:1,N ND ACTU I.LN x1IH L:]_a'L Lk k'EMC E M.NUA_ BE L.,`JLAHL3 F_R IE.. HAN:CA.. _R __EC fR IC/'L LINE SHLT-CFF APrL..617IOh:;. kTIN ( IS NG AFF\ SHA. L PF 1 -ITA,SIUM CAR3'l lA P :T SS UM A.-- -ATF- a FD FORMItI rl'J DF t ,N 'I -OR F I KN- KD 'h AND SFC QFP.FNT U G<LA L LLATC➢Ilk :l SI A L Be AY) AB L I:N I LAN Ll_ L:CII. +_,_• RS ,.11H _NST-LL'TLUNS iLi,' LU.D L-N': -ANC I_JTa A:'J.J Uu ,j; l 'E RFGJ1 ATFD RELE S LR;H.ANl M SHAL_I_ BE CO='PAT_ .I.F d:TH 4 FJSID_F FINK DF`r--m% YS-N -::-IF I.SIB.F _Trk iHA`I P.`­Ff---- l AND iNSI LCD AC JRDINY, lC TI IC lr_ `Ar-hY ILM1'LkA LI.:E 14 IL vENIILA ITNu -1A. 1H F'. LBLE Lf:K SHf:'_L 13L SL.PPC:�T_D FY IE�TU' BPi•LK' I_IVk .',-iE ASSEMBLY, LUCT FRO'EC-ION ETFCT_RS -, = RE'"O M kunL v Pu_L T -N Y TEE SER EEDIER i ,G N- T,r W . A '1FM RFI t-A-,-,' - --_RACKLI ASSLNJL'i r• / --T -E--r` tY f L L 2' ,:rFF..IPNC". PRO T:EC-iO!, N 7ZL. E. OF 4 PRe` AIR _I_F PLC \ C�b• --RMNA LOx WITH WP.1Tx I i FS, 3 PHASL rofsTauJks .r_� _ NIL AD AN YNIu ..IEiH; F:.F A-F'LA::A3_E) Q7M1 ROL. PANE:. TYPIEA.L AVSUL .R 102 SY:5'TF.d3 LAYOUT %:Si1ST RISER 1.-. VlF �!`! H F cva3 F _E- AND k](iNT "Llt QTER ENL NL_C TT�lI,��i���iT�Tll 3° ..............._ i ...._____....__...... _..__._..._......................_.................................._........._..... .............. _.......... _..... _.............. -.__.__.._..___................... .........._.. .. ''/1 11' V 1514E _i,,,,..._......_.._.._...."'--'_._-......._.__"___"'-___............._......._._.....__._..__.._.._.._.._..._.._..._..._.__._.._.._.____._....___._..............___.__...._.._.._.....__................_........._....._...................._...._........_........_... % ='-"" 11, C114' ._._._-.._.�_._-......._.--_...._._ _......__-_...._._........_.._....._._.....-__.._...._..._..__..._.._.._.__.... '✓ ,.rl�€ _' yr, olt" YYr/ .. ....._.._.. 3- t E 1` , 14' U.L. LJstea ;crew In H.WaDerl Bulb U, Li>ted S-. ew In Halogen Buib� UL.L. sted S'. e rn Halogen Ruib 54' y8' i it ..._ .__. `� ____ '_' 1?°-` .__._.___. .. ._...__. ..... _.._.. IEEE, I IEEE t2•....... ....... _.. _._... ._. ... 12, _.-_.... _ - J i Utility u n . IEEE 12' -. i � , f ya ly, rrr� 9191 IN m 48' 49' 48' 48' 72, 72, 24' �- 48' 24' 48' -� �- 2D itc' -�-^ 41• 4- -I' 41' 8' QUJ`M::r<:./8' O.DO 01) 8' ?.00'Nol't.!8' C40'OD 12' 0.00`Now./12' 0.00'UD `0 13....8A0` OveratL Leng11; _-_ PLAN VIEW - Hoed 13' 0.'^JC;" ...ONG 542.4FK-ND-2 i-SB-F SPECIFiCATIONS THE RESTAURANT FIRE SUPPRESSION SYSTEM SHALL BE THE PRE-ENGINEERED TYPE WITH A FIXED NOZZLE AGENT DISTRIBUTION NETW'D IT SHALL BE LISTED W TH UNDERWRITERS LABORATORIES, INC. CJL) THE SYSTEM SHALL BE CAPABLE OF AUTOMATIC DETECTION AND ACTUATION diTH LOCAL OR REMOTE MANUAL ACTUATION, ACCESSORIES SHALL BE AVAILABLE FOR MECHANICAL OR ELECTRICAL GAS LINE SHUT-OFF APPLICATIONS. THE EXTINGUISHRJG AGENT SHALL BE A POT6,SSIUM CARBONATE, POTASSIUM AC---STATE-BASED FORMULATION DESIGNED FOR FLAME KNOCKDOWN AND SECUREMENT OF GREASE RELATED FIRES_ IT SHALL BE AVAILABLE IN PLASTIC CONTAINERS WITH INSTRUCTIONS FOR L`IZOUID AGENT HANDLING AND USAGE, THE REGULATED RELEASE MECHANISM SHALL BE COMPATIBLE WITH '1 FUSIBLE LINK DET_CTION SYSTEM. THE F:JSI LE LINK: SHALL BE SELECTED 11ND INSTALLED F,CCCIRD'NG TO THE OPERATING TEM.TRATLiRE :"R THE VENT_1LATING SYSTEM, THE FUSIBLE LINK SHPL:. BE SUPPORTED BY A DETECTOR BRACKET/ t_INKAGE ASSEMBLY, PLENUM PROTECTION NOZZI...E c,F>>L.:f AN::: I'Rt:EiE::C T LI:IPJ NOZZLE III'I:IDNAI. RIf 'IRE.D f.I FT.A .. TERMINrL hOX wI H TERMINAL STRIPS, 3 PtiASr L(.IIdIAI,T.I.S .,N. LIVE [I.ADS (IF APPLICABLE) FAN AND LIGHT CON'ROL PAN;_t. F'LJkN VI> W Hood #3 8' 0.00" LONG 5424PK-ND-2. n-SS-F DUCT PROTECTION NO77LE 3 /-DETECTORS TYPICAL_A_N_SULR-102 S_Y_STEAq_._LAPOU.' REM€.)T: MANUAL. FULL `:'A-IOrJ REMOvABLE STAINLESS 7 E ED RVIC. 1 _10R L AGENT :=,ItiK OEM RELEASE! BRACKET ASSEMBLY PLAN VIEVi 1 Jnod #4 0.00" LONG 54241'K-ND-2 Q-SB-F N7'E: Addlticnal hl-oil Q angles p ,ided For #-Dods 12' and conger. EXHAUST RISER HANGING ANGLE: 20" SS DAFFL.E WITH HANDLES AND HOOK 3' INTERNAL STANDOFF IT IS THE RESPONSIEIP TTY of -THE AP.-W FELT/OWNER TO ENSURE THAT THE HOEID CLEARANCE. FROM LIMITED- 0O12USTIRL.F AND COMBUSTIBLE. MATERIALS IS IN OOMPL IANCE WITH LOCAL LODE REQUIREMENTS. GREASE DRAIN WITH REMOVABLE CUF LEFT QUARTER END PANEL SLk IN FALL1uE J Ltr, ',. 4'a S i F.Lf, �ANIPY cu,Ht f_zl_N wt:H I r S na_v. 1 R'L'J➢k.S C LAN 1-:.1,MAL. AND �FU.Y :,LUKL 'RAPP'k J IMI nilI l i f v .:ell. r: Ls `i P SI'A_NL_Y) ME k-L kA'IE. GhNE_ PCTIO\i 4'TP.W 41013F1, 5124PR' \ ^-2 >7-P S_REW IN HALOGEN BULB, L55 SERIES E26 CANOPY LIGHT FIXTURE - HIGH TEMP ASSEMBLY, THERMAL AND SHOCK RESISTANT SECTION VIEW MODEL 5424PK--'ND -2 9 SB 1 /RAPPER I7 00' HIGHIOD OPTIONS TABLE) ?ACHING PLATES :UPPL.Y RISER Y!'TH 'OUJME DAMPER 235E OPEN STAiNLESi STEEL PEWEIRATEI PANEL r•••/.1.•.IC4�i�NZR?•!•%�/fiFil: l:fL./Yl �\✓_1f3�14Z{LLI+I6] F N - L f t4N i _C DWE ERECT 1 _'_M.T dG SJFP V 'J-TH It' HL 'r Elw IN L IN TH ,PE L C7t.T-7L. D 'T 7 E �U n J " I't h Ht ITH Fit. FRS IGIvN 7 C Mf _ Al L7•d RIL IT r- 4 k!i k 0.1 N' 4 • R: -' r F - H t - F 1' 'v 'R. LCY 1 s r'_K U_ tll AJL L G J .l 'ilC CU hL:L U V IL L_ YU U _J U:_:.L E If f (-K : ur:-' I _T­_ s: ��' CCL.IM_.JT GIRL A k JL, JFLI..:_tR I— C 13 LIIMEVSIGN. I_J:'_;S A.L A✓n.LAti''L U'2 F IT L DAL NUJI- .. .. F':.:C.' le EX4>'F•LE 7,12 '?ITCH - 30' SLOPE FAN UNI' AG NO i F AN UNI' MODE_ # CF M I ESP RPM HIP z 4 .P. 0 VOLT i I LA WEIGHT (LBS) iSLiNES -. _.......,_..... T 1 DU85HK 1350 j ' I 0.9`25 :' 164 0.750._ 0.3110 i 115 9.8 97 3 DU85HK 2000 0.930 137:' 0.7`-3 L5160 1 115 9.8 97 '6.1 4 DU85;ik_ C 11 0930 1377 0.750 0.5160 _ 115 9.8 97 16.1 5 3000 1.122 II20 1..500 1.0710 115 13..5 16E: h13.6 all/d WA:V 1J%7'n PMdT10 kT -- J1 h494dd417 FAN I UNIT TAG AN UNIT MODEL_ # BLiIW`ER HOUSING I DE SIGN - E:SP. RPM .,.. D.Fi.P. 0 i VOLT LA 1✓EIGHT S=ENE:; N0. .............................................................................................................................................................................................................................................................................................•...... M CM ......... _ ... .......... .... <L.BS.) .................. ......... ........... 2 K-Al-G,0 GILD AL IGS(I 0a37 840 1.aco !0.4710 1115 10.2 216 V 6 I K-A3-618 GIG_PB A3 565E 0, 738 54 2.000 11.60% I 1 115 18.6 4 50 ]-,,a 'AN OP710NS FAN UNIT: TAG OPTION (Qty. - Descr.) N0, .._....._..____...__..._.._-_.__..... ....... ._.............. ....._._._.`--._._._..........___........_.........................._........_.... I 1 ease Box P 1 - ECM 1,'ir irg Package-'SSuppiy - MaruG2 or ' 10\i DC Rer"ererce Speecr Co.^:trot <NIDEC Motor) 3 1 Grease Bo/ .._.... ..__ .__._.... .__..._. ......_... I ................ .. 4 -Grease Box ,7 1 - iY'eG Se Box PAN ACCESSORIES F'A^: EXHAUST SUPPI_'Y UNIT iTAG 1 NO. GREASE_ GRAVITY \JAL:.. SIDE C:RAVITY MOTORIZED WALL_ CUP DAMPER MOUNT D'SC:iARGE, DAMPER DAMPER MOUNT 1 YES '3 FS .... _..._..._._ .._._...__......_.____..__.__ . 5 _S I /'TTDD Al�CC3/DT TG'L IN0. j ON FAN I i # 1 WEIGHT .---..-..�..----.ti...._....._.._.._-._ 36 _BS ITEM Curb SIZE h_. _-., .......... ___- % , 000'W x ? OCO' x 20000,H - ___-_ V e r to:z _ HinDeLi 2 ! # c`' ` it 3 29 I..BS I ...... ., 36 LHS I Curb ........ .. Curb 21.000'w x 21.00o'!.. x 20.CIO 'H .... _._._. ....._... 23.00C'W x 23.0t,0 L x 2000.:"H ✓erte- .._.. Hnged 4 # A 36 LBS Curb 23.000°'w' x 23,000'i.. / 20.000'H ✓entea Hinged _ 5 a? LPS Curb I26,500'W :< 26,500'L. x 210.000•li Vented Hingea 6 ; # 6 43 LB3 Curia, 35.000',,; I, 35,010 L x 2Q.OV 13 A LL �'•CP': IC_ DI CNNcLT RL k K I'C1"OR Ar S1 D-OR 2i 'CI 1- A tat'} h -Vn, Rtf FT 1 iF- LIFTING _L.G 3111'dth IJl': 4 -u... CL<B"t j t I I ' I ' t rs ❑1JJ.' a «ININ� es Ara' ve' -.. SER'✓ICE S Ot vEC W;TCH 4:1 1/'t' ICE SS DJ IF. CIE'"•� N.._ KLU, t4 :: I• EN14L' U :MAL !A II,.N C 1I U:M:LNS:'iI FFF:S #I q3 #4 - DU85HK EXH.AiJST FAN 31 .;8 ______.... f I I 3P 1/2 1 i r GREASE DRAIN i 4 PI 244 r DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN (BY OTHERS; 26-- �-- DUCTWCIRK BE:.T\✓EEN EXHAU-_ RISER ON HCOD AND FAN (BY OTHERS) F'!':'.:A LIRA..S DIh':_C'I' DRIVE. ' LINSTRUCTION (NO BELIES/PULLEYS ROOF MOUNTED FANS RESTAURANT MODEL U J AN:I UL762 AR1 BLE SPE-D CONTROL "NTERNA!WIRING - .dLAFyERaRUC'' D:Sr)CNNECT DA D THERMAL �A,L O'v ER_PRUTL"?f0^(SINGE ?H '.. ) - HIGH HEAT OPERATION 300'F (149'C) GREASE ASTESTING NORMAL T -MPERAT IR TEST EXHAUST FAN MUST OPERATE CON7INUr1.'..F..Y WHI's_E EXHf^.LISTING AIR AT 300•F <149•C7 UNTIL ALL >AN 'ARTS HAVE REACH-D THE=MAL EGU51..13RIUM, AND WIT:HQCJ`: ANY DETERIORATING EFFECTS TO THE FAN -✓HIC- WOU..D E'At1 E UNSAFE.. OPERATION. EX -AUST F.4 MUST OPERa:t CCNT:NUOUSLY WI I E YI Ali. I IC BURNINn FR _:S: VAPORS AT 60r F 336FOR A PVRIOrj OF i_ MINUTE,, 41 HoUl THPN E dECOM1N3 DAMAGED TC ANY EXTENT TP!AT COULD CAUSE AN UNSAFE CONDITION. aPT D�_Na GREASE BOX FEATURES ROOF MOUNTED FANS - RES"ALIRANT MODEL UL115 AND UL.,62 - AMCA SL'uND AND AIR C-FIN-IIE.D 'WA?ING, FRONT MOTCR TO DISCONNECT S`+'ITCH VEA1HVRPRO1_1F' DISCONNECT HIGH HEAT OPERATION :3i)0'F Q49`C:, - GREASE C:_ ASSIFICAllui, TES:"ING VORMA'EP4PEkf UP TF 7 /8 7HA1,'I' FAN IN .7-;PrkAfl 'rJNTIN)ll'SI_Y WHIL EXHAU I>h .IR A.. VJ F (149 C) hTi ALL FAN AR S HAVE REACHED HERMAL Et7LIL1.,a21U`^., A.4D W.IHJJi AN' DE: EAR TING Er FELTS. TO Tlai: I N WF'.ICH W[NJ1..I' CAUSE:: LINSAFE O-E.RA.'I'ION. ADNEIRMAL F'AR- UP TCS EXHAUST FAN MUST I."rPE -A : CONTINUOUSLY WH E �kHAUSTING RUPN NC 6RL ASP- VAPORS AT �u0'F ('s16'C) 101 A PE?IOD OF 15 >11tJU ES W1- HOUT THE: FAN RECO+,ING DAMGFI TO ANY EXTENT T!-IAT EOu.i) -AUSE AN i1NSAFE CONDH LX I=k'.--tT'GJS GREASE BOX %� ��SZ W • •HgR�y,. .•�GENg•• �. ••• ♦ O • o. 7 !� • ♦ V • t� • Q 10'� STAT OF a - % U) 41 �•LU SS�aNA ••E `. CO CC Q CU Z Q Q LLI `1 Cn Z Q m w LID J VENTED CLRB Q � C F' -NSIRU TrOti �... ROUE. Ur^_NIN6 L1 DIMENSIONS FIT ICm ED CURIS ARE AVAI;_ABLE: r FOR PITCHED RCO=S 0' G. SPE'CIF( PITCH: EXAMP_E 7/12 PITCH 30• SLOPE. VENTED CURB ,. t $TRJI-TION FLANGE 24 PTCHE.1) C':IRBS AR= Ab'AtI..AEi_E �• FOR PI'I'L:H=:➢ ROI:IF'S. - c SPEC'F" PITCH 12- EXAMPLE:/12 PI rti - 30° SLOPE 18014 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL MECHANICAL HOOD PLANS M1.1 PLOT DATE: GENERAL PLUMBING NOTES ill 1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE PLUMBING AND FIRE PROTECTION SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED TO. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE PLUMBING AND FIRE PROTECTION SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, LOCAL AUTHORITIES AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT INCURRING ANY ADDITIONAL COST TO THE OWNER. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS. 2. COORDINATE ALL WORK WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL TRADES. PIPE ROUTING SHOWN IS DIAGRAMMATIC. PROVIDE ALL OFFSETS, ETC. TO AVOID INTERFERENCES WITH EQUIPMENT, PIPING, DUCT WORK, LIGHTS, CONDUITS, AND STRUCTURAL ITEMS, ETC... 3. ALL DRAINAGE PIPING AND POTABLE WATER PIPING SHALL BE CONCEALED INSIDE WALLS AND PIPE CHASES OR ABOVE CEILINGS AS HIGH AS POSSIBLE. 4. EXPOSED PIPING AT FIXTURES SHALL BE SECURED TO WALLS CONSTRAINED AGAINST ANY FREE -MOVEMENT OF PIPING. 5. CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL DOMESTIC WATER, SANITARY SEWERS, STORM DRAINS, FIRE SUPPLY AND GAS SERVICES AT APPROXIMATELY 5'-0" FROM BUILDING STRUCTURE UNLESS OTHERWISE NOTED. 6. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR LOCATION OF ALL PLUMBING FIXTURES. EXACT LOCATION OF ALL PLUMBING FIXTURES MUST BE VERIFIED IN FIELD PRIOR TO INSTALLATION. FINAL LOCATIONS AND HEIGHTS SHALL BE AS DIRECTED BY ARCHITECT. 7. PLUMBING CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL EQUIPMENT INDICATED ON DRAWINGS INCLUDING KITCHEN AND LAUNDRY EQUIPMENT PER MANUFACTURER'S SPECIFIC INSTALLATION INSTRUCTIONS. FINAL CONNECTION SHALL INCLUDE ANY ADAPTERS, NIPPLES SHUTOFF VALVES, PRESSURE REGULATING VALVES, SHOCK ABSORBERS, BACKFLOW PREVENTION DEVICES, ETC. CONTRACTOR SHALL COMPLETELY REVIEW EACH EQUIPMENT ITEM'S INSTALLATION INSTRUCTIONS PRIOR TO COMMENCEMENT OF WORK. ALL ITEMS REQUIRED FOR INSTALLATION ARE INCLUDED IN THE PLUMBING CONTRACTOR'S SCOPE. 8. DO NOT RUN PLUMBING OR FIRE PROTECTION PIPING THROUGH TRANSFORMER VAULTS, ELECTRICAL CLOSETS, ELECTRICAL SWITCHGEAR ROOMS, ELEVATOR EQUIPMENT ROOMS, COMPUTER ROOMS OR TELEPHONE ROOMS. DO NOT RUN ANY PIPING ABOVE ELECTRICAL PANELS OR OTHER ELECTRICAL/CONTROLS COMPONENTS. 9. ALL COMMERCIAL FIXTURES SPECIFIED BY AN EQUIPMENT PROVIDER SHALL OVERRIDE ANY SPECIFIED PLUMBING FIXTURES ON THIS PLAN. THE PLUMBER SHALL COORDINATE FINAL REQUIRED FIXTURES WITH OWNER/EQUIPMENT SUPPLIER. VERIFY CONNECTION SIZE AND LOCATION OF ALL ITEMS WITH KITCHEN EQUIPMENT DRAWINGS. 10.PROVIDE AN EXPANSION JOINT ON ALL PIPING SYSTEMS THAT CROSS BUILDING EXPANSION JOINTS. 11.PROVIDE CONNECTION TO EXISTING WATER SERVICE WHERE AVAILABLE. PROVIDE WATER METER, PRV STATION WITH FULL SIZE BYPASS, AND RPZ VALVE. COORDINATE METER AND BACKFLOW REQUIREMENTS WITH LOCAL AUTHORITY AND UTILITY COMPANIES. CONNECT TO EXISTING SANITARY AND KITCHEN WASTE STUB WHERE AVAIALBLE. CONNECTIONS TO EXISTING UTILITIES SHALL BE COORDINATED IN THE FIELD FOR EXACT LOCATION AND INVERT AVAILABILITY. 12.PROVIDE GAS CONNECTION TO EXISTING METER WHERE POSSIBLE. PROVIDE CONNECTION TO ROOF MOUNTED EQUIPMENT AND TO KITCHEN EQUIPMENT AS INDICATED ON KITCHEN EQUIPMENT DRAWING. PROVIDE SHUT-OFF VALVES AT ALL POINTS OF CONNECTION. PROVIDE SOLENOID SHUT-OFF VALVE FOR GAS ITEMS UNDER KITCHEN HOODS. INTERLOCK SOLENOID WITH HOOD FIRE PROTECTION SYSTEM. GAS PIPING SHALL NOT BE ROUTED BELOW FLOORS. PIPING INDICATED AS BELOW SLAB SHALL BE PROVIDED IN A PREFABRICATED MODULAR STAINLESS STEEL UTILITY TRENCH. 13.ALL PLUMBING FIXTURES, PIPING, AND MATERIALS SHALL BE LISTED OR LABELED AND INSTALLED AS PER A RECOGNIZED APPROVAL AGENCY. 14.ALL WORK WITHIN THIS SCOPE OF WORK SHALL COMPLY WITH ALL CITY, STATE AND NATIONAL PLUMBING CODES. ALL WORK SHALL CONFORM TO BUILDING STANDARDS. 15.PLUMBING CONTRACTOR SHALL VERIFY VOLTAGE, PHASE AND WIRE SIZE OF PLUMBING EQUIPMENT REQUIRING ELECTRICAL CONNECTION WITH ELECTRICAL CONTRACTOR PRIOR TO PURCHASE OF EQUIPMENT 16.COORDINATE ALL FLOOR PENETRATIONS WITH STRUCTURAL DRAWINGS. THE PLUMBER SHALL SET SLEEVES IN FLOORS AND WALLS AND ATTACHMENTS FOR HANGERS AS CONSTRUCTION PROGRESSES. COORDINATE THE EXACT SIZE AND LOCATION OF ALL SLEEVES WITH STRUCTURAL ENGINEER. ALL PENETRATIONS MUST BE SEALED AND HELD AS TIGHT TO COLUMNS OR WALLS AS POSSIBLE. 17.COORDINATE ALL UNDERGROUND PIPING WITH GRADE BEAMS, WALL FOOTINGS, COLUMN FOUNDATIONS AND OTHER STRUCTURAL CONDITIONS. 18.ALL DRAINAGE PIPING AND VENT PIPING SHALL SLOPE AT 1/8 INCH PER FOOT UNLESS OTHERWISE NOTED. 19.EXACT LOCATION OF ALL CLEANOUTS MUST BE COORDINATED AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION. 20. SANITARY VENTS MUST TERMINATE A MINIMUM OF 10 FT. FROM OR 2 FT. ABOVE AIR INTAKES, WINDOWS OR VENT SHAFTS. 21. ALL HOSE BIBBS AND WASHDOWN FAUCETS ARE REQUIRED TO HAVE PROPER BACKFLOW PREVENTERS WHERE HOSES ARE ATTACHED AND LEFT UNATTENDED. CHEMICAL FEED SYSTEMS AT COMMERCIAL KITCHENS SHALL HAVE DEDICATED BACKFLOW PREVENTERS SEPARATE FROM WASHO-DOWN OR HOSE BIB FIXTURES. 22. PROVIDE 12" x 12" ACCESS PANELS FOR SHOCK ABSORBERS, TRAP PRIMERS AND ALL VALVES LOCATED ABOVE NON -ACCESSIBLE CEILINGS AND INSIDE PIPE CHASES. EXACT LOCATION MUST BE COORDINATED WITH ARCHITECTURAL DRAWINGS AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION. ALL ACCESS PANELS SHALL BE LOCATED SO THAT THEY ARE NOT VISIBLE TO PUBLIC VIEW. 23. WALL HYDRANTS AND HOSE BIBBS SHALL BE MOUNTED 1' - 6" ABOVE GRADE OR FLOOR LEVELS. 24. PIPING INSULATION SHALL BE PROVIDED WITH CONTINUOUS AIR -TIGHT VAPOR BARRIER WITH NO LOOSE TAPE OR EXPOSED INSULATION MATERIAL. CONDENSATE PIPING SHALL BE PROVIDED WITH ELECTROMETRIC INSULATION. ALL INSULATION AND WRAPPING JOINTS AND SEEMS SHALL BE PROVIDED WITH 1 OVERLAP AND MANUFACTURER RECOMMENDED, AIR-TIGH MASTIC AT ANY INSULATION OR VAPOR BARRIER JOINTS. INSULATION SHALL BE INSTALLED WITH FULL THICKNESS, FREE OF ANY INSULATION COMPRESSION, PROVIDE RIGID INSULATION SECTION AT ALL PIPING HANGERS. 25. PROVIDE A VALVE BYPASS AT ALL EQUIPMENT INCLUDING WATER HEATERS, STORAGE TANKS WATER SOFTENERS, BOOSTER PUMPS, FIRE PUMPS, ETCO FOR MAINTENANCE OF EQUIPMENT. 26. PROVIDE BALL VALVES AT ALL BRANCH LINES SERVING MULTIPLE FIXTURES. PROVIDE ACCESSIBLE BALL VALVE AT EACH FIXTURE CONNECTION (IN ADDITION TO ANY EXPOSED STOPS) OR FIXTURE HEADER BRANCH CONNECTION. 27. ALL HAND -WASHING BASINS AND LAVATORIES INSTALLED SHALL BE EQUIPPED WITH HOT AND COLD WATER THROUGH A MIXING VALVE UNLESS A TEMPERED WATER SUPPLY IS INDICATED. 28. INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF A FIXTURE SERVED WITH NO SHUT-OFF DEVICES BEYOND THE DISCHARGE OF THE VACUUM BREAKER. 29. THE USE OF RISER CLAMPS TO SUPPORT VERTICAL PIPE ALONG WALLS, OR COLUMNS IS PROHIBITED. PROVIDE B-LINE 22 STRUT & B-2000 PIPE CLAMPS 30. CONTRACTOR SHALL HANG ALL PIPING FROM THE STRUCTURAL MEMBERS (W-SHAPES, BAR JOISTS) WITH CLAMP -TYPE CONNECTIONS. PIPING SHALL NOT BE SUPPORTED FROM THE METAL DECK. STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED. 31. ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS FOR FOOD SERVICE AREAS. 32. ALL ANNULAR SPACES ARE TO BE CLOSED AND ESCUTCHEON PLATES AT HAND WASHING AREAS MUST BE SECURED. 33. INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE SERVED WITH NO SHUT-OFF DEVICES BEYOND THE DISCHARGE OF THE VACUUM BREAKER. 34, ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS FOR FOOD SERVICE AREAS. CHROME WALLCI AND SCREW PLUGGED TEE W/CLEANOUT MAY EXTEND AS A WASTE OR VENT WALL FLOOR LINE WALL CLEAN OUT DETAIL SCALE: NONE BRASS FLOOR � DRAIN COVER I 1 12"X12" WHITE ENAMEL, I I CAST IRON 3/4 GRATE FINISH FLOOR I I DRAIN COVER I EQUIPMENT DRAIN 1 I 1 I •,!'r 1 I DOMED GRATE ; �.:• . LJ 04 CONCRETE SLAB CONCRETE SLAB ALL FLOOR SINKS MUST BE DEEP SEAL FLUSH WITH THE CONCRETE SLAB TRAP FLOOR DRAIN SCALE: NONE LAP SEALANT S/S CLAMPING RING PRE -MOLDED PIPE FLASHING BOOT.- , ATTACH BOOT TO ROOF PER ROOF MFR --s RECOMMENDATIONS. TO INDOOR GAS EQUIPMENT PRESSURE REGULATOR WITH INTERNAL VENT. STEEL SLEEVE WELD TO STRUCTURE AND FILL WITH WATER PROOF MASTIC GAS PIPING RUN TIGHT TO BOTTOM OF STRUCTURE GROUND JOINT UNION GAS COCK WITH PLUGGED 1/8" NPT TEST GAUGE CONNECTION DRIP/DIRT POCKET 2" MIN, TYP ROOF GAS PIPING DETAIL- ROOF INSTALLATION GAS PIPING ON ROOF. SEE P200 FOR ROUTING. GAS PIPE ADJUSTMENT AT ROOF OBSTRUCTIONS TYPICAL PILLOW BLOCK MODEL 3-R SHOWN. MODEL 1.5 MAY BE USED FOR SMALLER PIPING. BACKFLOW PREVENTER MATRIX MODEL SERVES TYPE IPC LISTING WATTS 009 WATER SERVICE OUTDOOR RPZ ASSE 1013 WATTS SD-3 CARBONATOR CO2 CHECK ASSE 1022 WATTS 7 FOOD SERVICE WATER FILTER DOUBLE CHECK ASSE 1024 WATTS 7 RINSE FAUCETS MULTI COMP SINK DOUBLE CHECK ASSE 1024 INTEGRAL TO FIXTURE HOSE BIB DOUBLE CHECK ASSE 1052 WATTS 7 CHEMICALS DISP. DOUBLE CHECK ASSE 1024 WATTS SD-3 CARBONATED DRINK DISPENSER CO2 CHECK ASSE 1022 WATTS 7 ICE MAKER DOUBLE CHECK ASSE 1024 WATTS 7 NON -GARB DRINK DISPENSER DOUBLE CHECK ASSE 1024 WATTS 288A WATER HEATER VACUUM BREAKER VACUUM BREAKER ASSE 1001 NOTES: 1. PROVIDE HANGING ALUMINUM TAG FOR EACH BFP WITH THE BFP DESIGNATOR AND LISTING ETCHED IN AS INDICATED ABOVE. 2. TENANT SHALL PROVIDE TESTING FOR EACH BFP AT THE TIME OF ISNTALLATION/RELOCATION AND ANNUALLY THEREAFTER 3. TESTING PROCEDURES TO BE PERFOMED PER LOCAL CODE 4. MOUNT WITH BFP ACCESSIBLE FOR TESTING/REPAIR AT A MINIMUM 1" ABOVE FLLOR AND MAXIMUMS ABOVE FLOOR 5. PROVIDE ACCESS PANELS FOR BFP THAT ARE INSTALLED WITHIN WALLS WHERE SURFACE MOUNTING IS NOT POSSIBLE. 6. PROVIDE IN ACCORDANCE WITH THE REQUIREMENTS OF LOCAL CODE. 7. ALL BFP MUST BE LEAD FREE ASSEMBLY END PLUMBING FIXTURE SCHEDULE FIXTURE TAG DRAIN VENT CW HW GAS FIXTURE DESCRIPTION FIXTURE SPECIFICATION VALVE/FACUET SPECIFICATION WC-1 3 1-1/2" 1-1/4" SLOAN VITREOUS CHINA, FLOOR MOUNTED SIPHON JET, 1-1/2" TOP SPUD; CENTOCO 500 STSCCSS, EXTRA HEAVY DUTY INTEGRAL PRESSURE ASSIST ADA FLOOR WATER CLOSET 1" CON. ST-2003-1.6 SOLID PLASTIC, ELONGATED OPEN FRONT SEAT, WHITE, INSTALLED PER ADA REQUIREMENTS LV-1 1-1/2" 1-1/4" 1/2" 1/2" KOHLER GREENWICH VITREOUS CHINA, 20"X18" WALL HUNG 4" CENTERS, WITH OVERFLOW AND GRID DRAIN, JAY R. SMITH 0700-M31 DELTA 2529 LF WALL LAVATORY K-2030 SERIES CARRIER. PROVIDE CHROME PLATED LOOSE KEY ANGLE STOP, ESCUTCHEON, P-TRAP AND SUPPLIES. 0.5GPM VANDAL RESISTANt AERATOR INSTALLED PER ADA ACCESSIBILITY; TRUEBRO LAV GUARD UNDERSINK PROTECTIVE COVERS FOR P-TRAP AND ANGLE VALVE ASSEMBLIES MODEL 102 MS-1 3" 1-1/2" 3/4" 3/4" FIAT ONE PIECE SERVICE BASIN; AND 3.0 GPM FLOW RESTRICTOR; DELTA 28T910 STAINLESS STEEL MOP HOLDER; DELTA 28T9 MOP SERVICE BASIN MSB-2424 28T911 HEAVY DUTY 31" LONG REINFORCED HOSE, BRASS COUPLING, STAINLESS STEEL HANGER BRACKET, WITH INTERGRAL VACUUM BREAKER FD-1 3" 1-1/2" JAY R. SMITH CAST IRON BODY WITH NICKEL BRONZE GRATE, 8-1/2" ROUND GRATE; SEDIMENT BUCKET; VANDLE PROOF GRATE; FLOOR DRAIN 2210.00 P050 TRAP PRIMER OPTION. CAST IRON GRATES NOT PERMITTED. FS-1 3" JAY R. SMITH CAST IRON FLANGED RECEPTOR WITH SEEPAGE HOLES; ACID RESISTANT COATED INTERIOR; 8-1/2" NICKEL BRONZE FLOOR SINK 3100.00 RIM AND SECURED GRATE; SEDIMENT BUCKET; P-050 TRAP PRIMER OPTION. CAST IRON GRATES NOT PERMITTED. FCO 4" JAY R. SMITH CAST IRON CLEANOUT; NICKEL BRONZE 6" ROUND ADJUSTABLE SCORIATED VANDAL PROOF TOP; GASKET SEAL FLOOR CLEAN OUT 4020S ABS THREADED PLUG WITH SLOT TO RECEIVE 1/2" BAR STOCK. ARFCO- ACID RESITANT OPTION. WCO 4" JAY R. SMITH CAST IRON SPIGOT FERRULE; CAST BRONZE TAPER THREADED COUNTERSUNK PLUG WITH SLOT TO RECEIVE 1/2" WALL CLEAN OUT 4420.00 BAR STOCK UR-1 2 1-1/4" 3/4" SLOAN VITREOUS CHINA, WALL HUNG SIPHON JET WITH FLUSHING RIM, 3/4" TOP SPUD; JAY R. SMITH 0644 FLOOR CARRIER. URINAL SU-1005-.5 MOUNT UR-2 AT HANDICAP HEIGHT. GCO 4" JAY R. SMITH CAST IRON SPIGOT FERRULE; CAST BRONZE TAPER THREADED COUNTERSUNK PLUG WITH SLOT TO RECEIVE 1/2" GRADE CLEAN OUT 4261L WHA JAY R. SMITH 5000 SERIES STAINLESS STEEL PRESSURIZED COMPRESSION CHAMBER; THREADED NIPPLE CONNECTION; SIZE AS INDICATED WATER HAMMER ARRESTOR MXV-1 1/2" POWERS MIXING VALVE, SOLID BRASS WITH INTEGRAL CHECK. THREADED UNION CONNECTIONS. ASSE1017 MIXING VALVE LM495- SINGLE FIXTURE MXV-2 3/4" POWERS MIXING VALVE, SOLID BRASS WITH INTEGRAL CHECK. THREADED UNION CONNECTIONS. ASSE1017 MIXING VALVE LM491 MULTI -FIXTURE VALVE 1. ALL FIXTURES, EQUIPMENT, TRIM, FITTINGS, ETC. SHALL COMPLY WITH LOCAL, STATE AND/OR FEDERAL REGULATIONS AND CODES, INCLUDING BUT NOT LIMITED TO WATER AND ENERGY CONSERVATION CODES, AND THE AMERICANS WITH DISABILITIES ACT (ADA). THE SCHEDULE REFLECTS FIXTURES AND EQUIPMENT WHICH ARE MINIMUM CRITERIA AND SHALL BE THE BASIS FOR CONTRACTORS BASE BID. WHERE SPECIFIED FIXTURES AND/OR EQUIPMENT ARE NOT IN COMPLIANCE WITH GOVERNING CODES AND REGULATIONS, THE CONTRACTOR SHALL PROVIDE AN ALTERNATE BID FOR THE SUBSTITUTIONS OF COMPLYING FIXTURES EQUIPMENT FITTINGS ETC. THE ABSENCE OF AN ALTERNATE BID SHALL BE CONSTRUED TO MEAN THAT THE CONTRACTORS BASE BID INCLUDES ALL COSTS NECCESSARY TO MEET ALL REGULATIONS AND CODES. WALL PLATE 1/4" CLOSE NIPPLE HINGED ---- -- / / FPIPE GER OR 1i" PPE u 1 1/4" MAX UNDER HOOD PIPE SUPPORT DETAIL SCALE: NONE AVOID DIRECT INSTALLATION TO PREVENT FOREIGN MATERIAL FROM ENTERING DIRECTLY INTO PRIMER -TRAP PRIMER VALVE -BACK FLOW PREVENTER VACUUM BREAKER PORTS PETERSON PLUMBING PRODUCTS P2-500 TRAP SEWER PRIMER OR EQUAL TRAP PRIMER VALVE SHOULD ATER BE MOUNTED V ABOVE THE FINISHED FLOOR FOR EVERY 20' OR PRIMER LINE. TRAP PRIMER DETAIL SCALE: NONE WATER HEATER SCHEDULE LAYOUT STORAGE GAS INPUT OUTPUT ELECTRICAL GPH RECOVERY TEMP ELEC EXPANSION TANK MARK TYPE BASIS GALLONS MBH MBH CAPACITY KW 980 DEG RISE SETTING VOLT/PHASE ACCPETANCE GAL WH-1 GAS - INSTANT NORITZ MC 380 -- 380 361 -- 173.00 140 120/1 -- 1. PROVIDE CONDENSATE NUETRALIZER AND CONDENSATE TRAP FOR WATER HEATER. ROUTE CONDENSATE TO EXTERIOR OR FLOOR DRAIN. 2. PROVIDE REGULATOR FOR WATER HEATER SERVED BY GAS PIPING PRESSURE GREATER THAN 10" WC. PROVIDE GAS SHUTOFF AT EACH WATER HEATER 3. PROVIDE INDIVIDUAL FIXTURE MIXING VALVES SET TO 110 DEGREES FOR HAND WASHING FIXTURES. 4. PROVIDE PVC FLUE AND COMBUISTION AIR VENT ITH WITH ACCESSORY TERMINATION KIT PER MFG INSTRUCTION. NICKLE BRONZE ADJUSTABLE SCORIATED SECURED COVER. FLUSH WITH FLOOR BRONZE TAPER THREAD PLUG LINE r�_ WITH COUNTER SUNK HEAD 45° WYE AND 118TH BEND FITTING OR COMBINATION FITTING WASTE LINE LENGTH TO SUIT i , 11 11 FLOW NOTE: CLEAN -OUT TO BE J.R. SMITH MODEL 4100-F SERIES OR EQUAL INSTALLATION SHALL BE FLUSH WITH SURROUNDING FLOOR SURFACES. FLOOR CLEANOUT DETAIL r N COPPER OR LEAD SLEEVE WITH FLANGE I 18" MAX r VENT PIPE CONTINUOUS CONTINUOUS 4" ( ROOF MASTIC WELD JOINTS _ _ WELD JOINTS I I ROOF DECK ROOF DECK BOLTS W/NUTS- ` - - THREADED JOINT VALVE I WELDED FLANGES I PACK W/OAKUM OR EQUAL WALL BRACKET SUPPORT i MATERIAL TO PREVENT WITHIN 12" OF FLANGES ASPHALT DRAINAGE GAS SHUTOFF VALVES DETAIL VENT THRU ROOF (MOUNT VERTICALLY) SCALE: NONE SCALE: NONE &P VALVE DRAIN VALVE /4" GAS DRAIN NATURAL GAS INST. WATER HEATER DETAIL �Q • U ICI V 0 Z c� A CV Q Q 00 vc/) � UJ .V �C/) co00 coz r- UJ U�UDa�-J EW�Qr"v UJ �z>U>C'oU I- �N> � N Q ui z D In MM• h� • I� w Y U z Q Do LU W J mm CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL PLUMBING SCHEDULES AND DETAILS Po. 1 FLOOR SINK SCALE: NONE PLOT DATE: LV-1 1 12" 1 1 --0------ 2„- 3" VTR �_..:__...__._..._.__ — . . L 2j O— FD-1 ,-t ----- \� I D-1 � J L tk =1 I 3" 1 \ I ............................................... -------------}--------------1----- --- L 1.5� - _----_ J-j--j SANITARY WASTE AND VENT FLOOR PLAN. 4" i-- �'I ---------- 3 . t' 3 0--3 i `1 \ ...... FD-1 /- F i HAND SINK n ,FUTURE HAND SINK 4 ............................... ------------------------ t--------------- 3" b FD-1 FCO ------------------------------------- 4-=- Q NEW 1250 GALLON GREASE INTERCEPTOR NEW 1250 GALLON GREASE INTERCEPTOR — 4" SAN EXIT AT -30"BFF. REFER TO CIVIL PLANS FOR AVAILABLE TIE-IN LOCATIONS � I U CD co Z `� W CD N cc DLo 0 CDcn _ �c0co co I—Lzu Nw��U l� u cn = N > U Q N � V� cn LLI z_ cn D In . its 1 �♦,,�S\GCD i o. 7 r .0� STAT OF %� •• FAO I % � w DP \ SS,ON11 q 18014 CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS, FL PLUMBING SANITARY PLAN P1.0 PLOT DATE: - _.. . ..........- .. .................. .............. .......... .. .... ..... .. . ......... I BEVT..... DIP WFi i z,, 1/2" FILTERED WATER BEV STATION DOMESTIC WATER AND GAS FLOOR PLAN 1 /4" = 1'-0" TP-1 RANGE 370 CFH — GAS _....... _ ... GAS a '. t°. ,I .........._ Q LL I Lo I ALL KITCHEN SINK FIXTURES- 1/2" HW/CW DROPS TO ANGLE STOPS IN WALLS WITH HOSE CONNECTIONS TO FAUCET. FAUCET SUPPORTS BY PLUMBER NEW 2" WATER SERVICE AND METER- 2,, BACK -FLOW AND METER AT SITE. COORDINATE WITH LOCAL JURISDICTION AND UTILITY COMPANY FOR SPECIFIC REQUIREMENTS. i NEW GAS METER AND SERVICE LINE BY ILL. COORDINATE WITH UTILITY COMPANY TO PROCURE SERVICE LINE AND NEW 3" SERVICE AND METER. APPROXIMATELY 3090 CFH. 110 FT PIPE LENGTH 150 FT DEVELOPED LENGTH FREEZE -PROOF WITH VAC. BREAKER AND HOSE CONN. 3090C FH U o Z� co t T w CV Lo 0o w a U � cy) Z Ili � C/) o w Uw C/) ) C� co w x =T� vzv>�= �N> rr U "�t Q CV U) X w Z r� P4 0.4 rl- rn w ••\GENS i z :� • v. C) • o. 7 J m OC ' STAT OF • • ',AO •. A� Z S/pNAfill %it E L Y ' � ;i a m m w J CONTRACT DATE: 08.13.2017 BUILDING TYPE: ONE-OFF PLAN VERSION: SITE NUMBER: STORE NUMBER: SUNRISE EATERY 5915 GALL BLVD. ZEPHYRHILLS. FL PLUMBING DOMESTIC WATER PLANS P2.0 PLOT DATE: J Q