HomeMy WebLinkAbout6013 Gall BlvdIII A GENERAL NOTES: - ALL WORK SHALL CONFORM TO THE CURRENT EDITION OF THE FLORIDA BUILDING CODES, AND ALL OTHER GOVERNMENTAL OR REGULATORY AUTHORITIES. - GENERAL CONTRACTOR AND ALL SUBCONTRACTORS TO VERIFY ALL DIMENSIONS IN THE FIELD. ANY DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK DO NOT SCALE PLANS. - THE CONTRACTORS SHALL BE RESPONSIBLE FOR FAMILIARIZING THEMSELVES WITH THE INTENT OF THE DRAWINGS. CONTRACTOR AGREES THAT HE SHALL BE HELD RESPONSIBLE FOR HAVING EXAMINED THE SiTE. THE LOCATION OF ALL PROPOSED WORK AND FOR HAVING SATISFIED HIMSELF, AS TO THE CHARACTER AND THE NATURE OF THE EXISTING CONDITIONS AND WORK TO BE PERFORMEDt ALONG WITH THE LOCATION OF EXISTING UTILITIES AND ANY OTHER OBSTRUCTIONS. - IT SHALL BE THE RESPONSIBILITY OF ALL SUBCONTRACTORS TO HAVE EXAMINED AND REVIEWED THE COMPLETE SET OF WORKING DRAWINGS AND/OR SPECIFICATIONS TO PROVIDE ALL LABOR AND MATERIALS FOR THEIR RESPECTIVE AREA OF WORK, FOR THE COMPLETE AND FINISHED INSTALLATION IN COMPLIANCE WITH THE INTENT OF THE DRAWINGS AND/OR SPECIFICATIONS WHETHER IT IS INDICATED OR NOT. ALL WORN(, WHETHER INDICATED OR NOT, SHALL BE IN COMPLIANCE WiTH ALL BUILDING CODES AND ORDINANCES WHICH ARE APPLICABLE TO THE PROJECT. - CONTRACTOR TO PROVIDE ALL BARRICADES, SCAFFOLDING, SIGNS, LIGHTING AND OTHER MEANS OF PROTECTION AS REQUIRED TO COMPLY WITH ALL STATE LAWS AND LOCAL ORDINANCES TO SAFEGUARD PROPERTY AND PERSONS. OBSTRUCTIONS SHALL BE PLACED SO AS NOT TO DIMINISH THE LIFE SAFETY REQUIREMENTS. - ALL WORK SHALL BE PERFORMED BY QUALIFIED CONTRACTORS IN STRICT ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND RECOMMENDATIONS. - ALL MATERIAL AND EQUIPMENT SHALL BE NEW, STORED AND INSTALLED IN A WORKMANLIKE MANNER STANDARD TO THE TRADE AND THE AMERICAN SOCIETY OF TESTING MATERIALS. - THE DESIGN INFORMATION INDICATED ON THE PLANS ARE INDICATED TO BE A COMPLETE AND WORKABLE SYSTEM IN ACCORDANCE WITH ALL PRODUCT MANUFACTURER'S SPECIFICATIONS, EXISTING AND/OR PROPOSED BUILDING DESIGN, FIELD CONDITIONS, ETC. ALL MISCELLANEOUS MATERIALS, PARTS, DESIGN DIMENSIONS, WHETHER INDICATED ON THE PLANS OR NOT, SHALL BE INCLUDED AS PART OF THIS DRAWING PACKAGE. - THE GENERAL CONTRACTOR OR SUBCONTRACTORS SHALL BE HELD RESPONSIBLE FOR THE REMOVAL AND THE PROPER DISPOSAL OF MATERIALS AND ITEMS REFERRED TO AS "DEBRIS" OR DETERMINED BY THE OWNER OR ARCHITECT TO BE REFUSED. - THE GENERAL CONTRACTOR SHALL HAVE MADE ALL REMIF ED PROVISIONS FOR THE REMOVAL OF THE DEBRIS ON SITE. - GENERAL CONTRACTOR SHALL TAKE ORDINARY PRECAUTIONS TO SECURE AND PROTECT MATERIALS. - ALL WOOD MEMBERS IN CONTACT WITH MASONRY SHALL BE PRESSURE TREATED. - ALL METAL USED FOR CONNECTING WOOD MEMBERS TO BE GALVANIZED OR CORROSION RESISTANT. - THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR ANY DEVIATION FROM THESE DRAWINGS. - SPECIFIC SECTIONS, DETAILS AND STANDARD DETAILS ARE INDICATED ON THE DWGS AT LOCATIONS WHERE THEY OCCUR; OR AT CHARACTERISTIC LOCATIONS, THEY APPLY, UON, TO OTHER LOCATIONS WHERE IMPLIED BY SIMILARITY OF CONSTRUCTION. - CONTRACTOR TO COORDINATE SPACE REQUIREMENTS AND INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WHICH ARE INDICATED DIAGRAMMATICALLY ON THE DRAWINGS. FOLLOW ROUTING SHOWN FOR PIPES, DUCTS, AND CONDUIT AS CLOSELY AS PRACTICABLE. PLACE RUNS PARALLEL WITH LINE OF BLDG. UTILIZE SPACES EFFICIENTLY TO MAXIMIZE ACCESSIBILITY FOR OTHER INSTALLATIONS AND FOR MAINTENANCE AND REPAIRS. - IN FINISHED AREAS, UON, CONCEAL PIPES, DUCTS, AND WIRING WITHIN THE CONSTRUCTION. COORDINATE LOCATIONS OF FIXTURES AND OUTLETS WITH FINISH ELEMENTS. - TRANSPORT AND HANDLE PRODUCTS IN ACCORDANCE W/ MFR INSTRUCTIONS. - PROMPTLY INSPECT SHIPMENTS TO ASSURE THAT PRODUCTS COMPLY W/ REQUIREMENTS, QUANTITIES ARE CORRECT, AND PRODUCTS ARE UNDAMAGED. - SHOULD MFR INSTRUCTIONS CONFLICT V THE DWUGS, REGI EST CLARIFICATION FROM ARCHITECT/ENGINEER BEFORE PROCEEDING. - ALL THRESHOLDS SHALL COMPLY WiT14 FLORIDA ACCISS181LITY CODE, 4.13h AS FOLLOWS: A. THRESHOLDS NOT TO EXCEED 3/4 NCH FOR EXTERIOR SLIONG DOORS. B. THRESHOLDS NOT TO EXCEED 1/2 NCH HEIGHT FOR OTHER DOOR TYPES. C. RAISED THRESHOLDS AND FLOOR LEVEL CHANGES AT ACCESSIBLE DOORWAYS SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. - G.C. SHALL FURNISH AND INSTALL CONT. WOOD BLOCK'G IN STUD PARTITIONS FOR ANCHORAGE OF WALL ATTACHED ITEMS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: GRAB BARS, TOILET ACCESSORIES, HANDRAIL BRACKETS, WALL CABINETS, WALL -MOUNTED FIXTURES ETC_ - THE OWNER SHALL BE RESPONSIBLE FOR PROVIDING THE CONTRACTOR W/ ROUGH-N INFO. NECESSARY TO ACCOMODATE THE INSTALLATIONS OF OWNER FURNISHED AND INSTALLED ITEMS. - THE CONTRACTOR SHALL INCLUDE ALL OWNER FURNISHED AND INSTALLED ITEMS IN THE CONSTRUCTION SCHEDULE, AND SHALL COORDINATE W/ THE OWNER TO ACCOMODATE THESE ITEMS. - COORDINATE ALL DEMOLITION EFFORTS W/ T14E OWNER EVERY EFFORT SHALL BE MADE TO MINIMIZE DISRUPTION OF OPERTATION AND TO PROVIDE PATRON SAFETY. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE -APPROVED AND COORDINATED W/THE OWNER - COORDINATE W/ THE OWNER THE PRE -APPROVED DISRUPTION AND VERIFICATION OF SERVICE WITHIN THE EXISTING BUILDING 50 AS TO MINIMIZE THE DISRUPTION OF SERVICE. - CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN THE EXISTING BUILDING WHICH OFFER AN ENCLOSURE TO ISOLATE ANY DEMOLITION/ CONSTRUCTION WORK FROM THE GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER ABBREVIATIONS: A M AD ANCHOR iOLT mm MAIO W AVV ABOVE MAIL MANINAL AC ACCENOM MAX MAXINM AC AIR CODMOFUNG Mc MEDICINE C NV ACP ACCLES6 FLOG" ACT AGOII6fICAL CEL M TLB nam MECHANICAL AD AREA DRAIN MR MItIFAICTUER ADD ADDEDIM ADJACENT MID MDDLE ADJ AIO.IISTA11lB MIN MINFLM ANP AD" RON FLOOR MMC F AHu Alt HA NXM LNT ML MATa4 LINE E ALT ALTERNATE MLDG MOULDING A AM ALNIlm MO PWACN RY OPENING ANOD ANODIED MODE HOOFED AP AOCM PANEL MID MOIMIED) (NW APIWk A"PRONMATE pTa maNTN6 Aw04 ARC MCT(t E) (WW MIL METAL ANN ASRLLT MILL MLLION AM A ff"TIC m ML LWCW AAD( AIDNLWIY AVG AVERAGE AWT ACOUSTICAL WW1. TREAVIENT N AIN AMA N NORTH D NA NOT APPLICABLE wNOT N COkIR CT lip a PaD No N aM: eeLGW I711Il4) M DOUR NOM NO0MINAKA L Drcoom inIrNLNDu6 wNONE pectic"GOE�1cBiT ELD DalARD GQAW F00TAIGE KDG auLDLNG NT6 NOTNr TOTO OCALE ILK(G) eloa(wG mm IELOW am BEAM/ iENCRw O iN BUNCH OA OVERALL BROW awac Oc ON CANTER m BOARD OD 011m DINTM an iRA RING OF affm FACE ow BRAM OH OVEaOAD as DOTE om OF'IDD OPPG I HAND ON lIORTOM CFO OPENING m OEME04 amp 0410 e an EULtAP ROOF 94 IEVELm P C PCJ PLASTIC Calm aWm CAD cAam p'ED PEDASTAL STAND CAP CAPAWf PL PRO°FRrR LNE co CATCH DASH/ COVE RMIN PLAIN PLASTIC LAMINATE cc CENTER TO CENTER PLA6 Kiww Cm c1arENr PLWO PLYWOOD CER CwAllc PNL PANE. CG CORDER GUYv PNT PANT Cl CA6TLRON FOL POLA ED cJ CONIROL JOINT PR POUR C G CELNN ma rARI1flON CLR CLEAR ro POUNDS PER SOLVE NCH CLOT CLOW PT PANT CM CROIW M=NG PIDID PAPER Tali C100IL011104 'DIAL CMU CaNCRE1E MAWO W UNR PVC POLY vm CH.ORDE cal COL" cam ca" Cal"TION LE G CONIC CONCOTE at GNAW TILE coif CONNECTCION) aJl1' Qwxm CUNT CONTLIm CONIR COOT OUNiRACM CONSINICTIOM R CPT CAMIT mm RADLO/NXIM) CR OHAIR RAL RA IW WN AIR cr CE RAMC TILE COUNTER TOP 0 RE6LL3lT BASE C TR caNTER RCP REINFORCED CONCRETE "ME cW CAD MAIM RC% RECEVN9 D DRYER DAA18 DLECT APPLED SYNNETIC STUCCO DE'10 O MOLIT" DEFT DE'ANRTMp1l! mtm% MAL DF DRN(NG FOINTAN 171NM DLQUI R DM DIMENSION ow WINNER Div pr#u I ON DOWEL OUR DocR D6 pm~ DWG DRAB N6 DOLL DOIaLE DW DIII#ASIEIt EA BA04 E EAST (7'S MMOR NILLATIONHIM 6TSTEM 61 WeAN/ION JOINT LL ELWATM mw Etcm m" ELEVATOR I0"ErR a BRGENc7 ENCL Enct oeLrE E' E.4STU"MPANT SO EOL4L EarlaOPT Er11LPF1Dtt END AaCMWATER COOLER am ELECTRIC WATER HUM 004 E)"w EXP pR"AN ION DGITNG won EXT ExTAaOR F FA FIRE ALARM F6 FAMWATION Fat FACE a: DIWOC PC FILE CABINET pD FLOM PRAM FUN POUFDATION IE FIRE 9014 MI 9t FIG M RE OM NK*H3t CABINET FF FNOW FLOOR PHc FIE NOSE CADWET m I%Yom) FO(T PWW FLOOR KA X Km FLOUR BOOR MOUNTED NILORT!mw p0 MNSW OPENING POD PACE OF a.M POS PRICE OF SM Fr F11EPIt0oFYNW pwl FR" IR FILL Gram Pt FiITADOT FTG POOTIN9 RUT mmmm G GA GAGE/GAM GAR GARAGE WLV GALVANiED am GRAD am GC GBERALCafRAGTOR GL CLAN GRIN QUIN (WOOD) am GROUND aRT am GIP GROSS SOARE FOOTAGE am GYSIMWALLBOARD 6RT GYPIIM HI ILOSE OD HR HouR HOt HpWIOWE HOLLQL COTE I4ATt,7WNE HDWD H,YCWOOD HGTALI(r IeaHr m I4dJ.al METAL HORrt NowaoNrAl HTCs HEATM WAG IEAITN%VENTL.ATNG A AR CONCWTO LLG Hu I NOT WATER 1p HIDE DIMtm LNOCE prONWION W44DNCW WAND INCL NCL.LDE(D) (Nw N:o Nv"T" NIIL NWLATION NT NMRIOR Hv HVEQ re IRON PIPE GE .LAIN AANTUR Ja JNCiONam Jr. ANVOR a.OW AST JOIST AT AaNr KiT Know KO KNOCKW KPL KICK PLATE LAM LNI NAED) L AV LAVATORY LD POW LiL LANE LF LINEAR FGCTATET LAOL LONIMM GN W LEFT HAND LILR LIFT HAND TEVEaLE LL LIVE LOAD LaA LACOER LlTw LIGHRNG LA. LAMNATV vow"Lalm LWLTV LJGHTL ONT REAEF Imm (R9;3E1NCE RECPT 100CEMAOLE REFL 1EFLBCm) (IVFJ REFR RE911GEeATTON / pe"SERATOR REG RBGWTER TELNt RESRDIRCDfD)(NW IEGp ROOMED Ras PERM IEV REVWIOFI 44 RIGHT kw *IR POW HAND REVERIE RD ROUGH OPENING RM mm Ro RAW RT wESLL3NT TLB RID RATED RD maw MC RAN WATER CoUrm 6 6 UTH SO SA SUPFLY AIR 645 SOUND ATTENUATION a.ANET ec ecaBISOLID OOZE Sate SaiDu=) w SECTION :m sewn Lr SOLWEFEEIA:OOT SGD SLDNG GLASS DOOR /W ON" HWG SLY SwLm be sww SM SWMLAR aLNT SEALANT am &WARY NAMON DMF'BNSEe DIR SANRARTNMIWIECERACLE EON GPL.AR - OT1'o m HAND SPEC IMEPICArCK SOU SOLVE IIR SHELF a ROD SST STASURS 611L ffrC 5awTRANNIN" IWD STAFDANRD MG SEATING STL WEEL brae STORAGE aiAvc Cur SWAM WIIP aMPAm /W sdTw w am T 6TAOW EASIER 4 DRYER SYmFEITIMCAL T THIEAD(b) TBA TO BE AISGF® TiL TABLE TC TOP a: Cm TO TOP OF DRAIN SUM SCAMUM) TE./TP Top RE.E'FIOFE TEMPERATILE / TE 1°EEu TER lomt4zw T N G Ta" 4 GRoo4E TIK INICKIFM TJ To= JOINT TOJ TOP OF JOIST TO6 TOP OF ILAa TOW TOP UP om Tm Tom PAPER DIImhm Tyr TYWCAL u U uNDHROiT W. u CfllW ITERs LANLORATORY ILI#1 IJwFNIW o UON ILIJ?J!6 OTHER" NOTED UrL UTILITY v VAR VAM11)(0) VD VAPUR DARNER/ VINYL DAZE va VM COMFOSTION TLB VIP vow N FLED VNt ve�Ie yr VINYL TILE VWO VN71 WILL Covom W W WD1W WWT / WISINaR lw WW WA WOOD DASE WC WATER CLOSET Wa WATER COOM LD WOOD/ WDCO VB®R WIT/ Wr WEIGHT W WATER WRATEV HYDRANT W WRaLGIiT MN Mr. WALK-IN CLOSET ON wcm UP WALLPAPER War WALL aMPER WM lamm WG WMTHOILT w WATERPROOF to WINE mvm Y T TARED BUILDING CODE SUMMARY -COMMERCIAL PROJECTS BUILDING DATA: EXIT REQWREME1dTO : MAXIMUM TRAVEL DISTANCE TO EXIT - 200'-O" FROM ANY PONT SQUARE FOOTAGE CALCULATIONS: SQUARE FOOTAGE UNDER IMPROVEMENT 1200 SF. PERMITTING AGENCY: CITY OF ZEPHRYHILLS BUILDING DEPARTMENT APPLICABLE CODES (CURRENT EDITIONS ONLYA FLORIDA BUILDING CODE 5TH EDITION (2014) BUILDING FLORIDA BUILDING CODE 5TH EDITION (2014) RESIDENTIAL FLORIDA BUILDING CODE 5TH EDITION (2014) EXISTING BUILDNG FLORIDA BUILDING CODE 5TH EDITION (2014) ENERGY CONSERVATION FLORIDA BUILDING CODE 5TH EDITION (2014) FUEL GAS FLORIDA BUILDING CODE 5TH EDITION (2014) PLUMBING FLORIDA BUILDING CODE 5TH EDITION (2014) MECHANICAL FLORIDA BUILDING CODE 5TH EDITION (2014) TEST PROTOCOLS FLORIDA BUILDING CODE 5TH EDITION (2014) ACCESSIBILITY CODE 2008 NATIONAL ELECTRICAL CODE 2010 FLORIDA FIRE PREVENTION CODE DESIGNED N ACCORDANCE WITH THE FLORIDA BUILDING CODE 2014, SECTION 1609 FOR DESIGN PRESSURES. WHOLE BUILDING: NUMBER EXITS: TOTAL SQUARE FOOTAGE 1200 Sr-. DIVIDED BY NET/sa FT PER OCCUPANCY 100 12 TOTAL NUMBER OF PEOPLE ON FLOOR NUMBER OF DOORS PROVIDED 2 NUMBER OF DOORS REQUIRED: 1 ACTUAL NUMBER OF SEALS: 13 FIXTURE COUNT SUMMARY• TOTAL NUMBER OF OCCUPANTS: 12 NUMBER OF FIXTURES REQUIRED: I SYMBOLS: NUMBER OF FIXTURES PROVIDED: I (I UNISEX) EXIT REOUIREMENTS : L ALL EXIT DOORS THAT RE6I<11RE PANIC HAROWARE WILL MEET TFE CRITERIA OF NFPA 1011211 2. PER NFPA 10112.L5, DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. FIRE PREVENTION CODES: L ALL CONSTRUCTION MUST MEET T1 E REQUIREMENTS OF NFPA 241, 2M EDITION FOR STANDARD OF SAPEGUARONG CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS. 2. ALL CONSTRUCTION MUST COMPLY WITH 2O10 FLORIDA FIRE PREVENTION CODE WA I AND NFPA 101) 3. ALL CONSTRUCTION MUST MEET THE CONDITIONS OF NFPA-101 20W EDITION CHAPTER 10, INTERIOR FINISH CLASSIFICATION LIMITATIONS. 4. MUST MEET THE REQUIFV'IENTS OF NFPA-10 200 EDITION AND NPA 101, SECTION 9.14, STANDARD FOR PORtAIBLE FIRE EXTINGUISHERS. 5. ALL FIRE EXTINGUISHERS MUST BE CERTPIED SY FIRE EXTINGUISHER COMPANY. INSULATION NOTE: THE EXISTING BUILDING WAS CONSTRUCTED UXTN INSULATION THAT MEETS THE 20104 FLORIDA ELUILDMG CODE, bN EDITION T EIREPOIRE, NO ADDITIONAL INSULATION WILL NEED TO BE ADDED IN THIS SCOPE OF WORK DRINKING FOUNTAIN NOTE: L PER TABLE 403.1(1), DRAWING FOUNTAINS ARE NOT REQUIRED ON OCCUPANCY LOAD OF PA OR FEWER THEREFORE OUR SPACE DOESN'T REQUIRE A DRWING FOUNTAIN AS OUR OCCUPANT LOAD iS B. AN INTERIOR BUILD OUT FOR: SUZIN NAILS AND SPA 6013 GALL BOULEVARD ZEPHRYHILLS, FL PROJECT RECORD ISSUE DATE: 01/0/6 REVISION DATE REMAI o PROJECT SUMMARY Nis PROJECT CONSISTS OF- -DEMOLITION OF EXISTING TENANT SPACE AS S 40M ON PLANS -RENOVATION OF SPACE ADDING NEW WALLS AND MILLWORK -MECHANICAL, ELECTRICAL, AND PLUMBING AS SHO LANE. SZ-t!y _3NIpvv)(AA � S SHEET INDEX A-1 SHEET INDEX / SPECIFICATIONS / VICINITY LS-I LIFE SAFETY PLAN j V� qa0,� J �?ICt7I:7�I �IQI�O i 1 '�'u )� t)1.[ZIt�n32ld A-2 RENOVATION PLAN 11VII IAI Alddhoj ,I1HITs NOn111V A-3 REFLECTED CEILING PLAN A-4 HC RESTP00M DETAILS AND ELEVATIONS E-1 ELECTRICAL LWTING s RECEPTACLE PLAN E-2 ELECTRICAL PANEL SCHEDULE AND SPECIFICATIONS P-1 SANITARY PLUMBING PLAN P-2 HOT 1 COLD WATER PLUMBING PLAN M-1 MECHANICAL PLAN M-2 MECHANICAL PLAN mould Y��T 1�o�3b pA ALL EXTERIOR WINDOWS AND GLASS DOORS ARE REQUIRED TO BE TESTED IN ACCORDANCE WITH ANSVAMMA/NWWDA 101/152 STANDARD AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING THE MANUFACTURER; PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT TESTING ENTITY. ALL WINDOWS AND WALK DOORS SHALL HAVE MINIMUM DESIGN PRESSURES OF +42.6 /-51.0 PSF ALL GARAGE DOORS SHALL HAVE MINIMUM DESIGN PRESSURES OF +38.1 /-480 PSF WIND DESIGN METHOD = ALTERNATE ALL HGT METHOD ULTIMATE WIND SPEED (3 SECOND WIND GUST) 146 MPH (3 SEC. GUST) NOMINAL WIND SPEED 16 MPH WIND IMPORTANCE FACTOR 1.0 RISK CATEGORY OF STRUCTURE 11 WIND EXPOSURE B WIND ENCLOSURE COEFFICIENT +/- 0.18 (ENCLOSED) DESIGN CLADDNG PRESSURE FOR WALL/ROOF ZONES I THRU 5 PER ASCE 1. COMPONENTS AND CLADDING ROOF 6 10 SQFT + 24D /- 822 PSF 20 SQFT + 22.4 /- 14.6 PSF 0 50 SOFT + 193 /- 643 PSF r 100 SOFT + 11.4 /- 51.0 1 % WALL r 10 SQFT + 42.6/- 51.0 PSF A 20 SCIIFT + 400- 532 PSF 50 SQFT + 381 /- 48.0 PSF a I00 SQFT + 363/- 442 PSF - 1334 PSF WIND TABLE SCALE: V.S. * TO THE BEST OF THE ARCHITECT OR ENGINEER'S KNOWLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING CODE, 5TH EDITION 2014. * THE DRAWINGS t DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF 13ENG SEALED. TO THE BEST OF THE KNOWLEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. 188E DATE BY: IWVIEW VlAbAb PERMIT OlAbA5 REV. REV. REV. REV. TH W DOGI!'B M MIGN6, NOTES, DETAILS AND 64XVCATM *0 CONCEM AM M SOLE PROPERTY OF PRAZE DE NC. AND 8-L4LL NOT BE REPRODILCEA, RE<JEED OR COPIED FOR OTHER MM10cM, IN WOLF OR PART W WCUT THE WNWM CONSENT OF FRANK FRAE, ARC14MSCT, AJA. ALL RNGHAD AN RISOMM BY THE ARCN-0TECT N ACCORDANCE WTN U& COPYRNWT *0 PATENT L4& IL AMiMt= IEPRODUCTION WILL W PROSECUTED TO THE FULL 17ew OF THE Lau III ¢ >?� Q ONp A 00 z N "00 1 � A w � W C� a a\ .o N N t` I b N CIS w � � U a O z x SHEET tItLE SKEET INDEX VICINITY MAP, 4 SPEC IP I CAT IONS e4-Er=T NUMBE Ir It EG EGRESS WIDTH 32" /(.2) = 160 OCCUPANTS .m EMERGENCY LIGHT ABOVE EMERGENCY LIGHT ABOVE LIFE SAFETY PLAN SCALE: 1/4" = 1'-0" EMERGENCY LIGHT ABOVE EXIT REQUIREMENTS : MAXIMUM TRAVEL DISTANCE TO EXIT - 200'-0" FROM ANY POINT SQUARE POOTA6E GA CU.ATI0N5: SQUARE FOOTA6E UNDER IMPROVEMENT 1200 S.F. WHOLE BUILDING NUMBER EXITS: TOTAL SQUARE FOOTASE 1200 5.F. DIVIDED BY NET/50. FT PER OCCUPANCY 12 NUMBER OF PEOPLE ON FLOOR, NUMBER OF DOORS PROVIDED NUMBER OF DOORS REQUIRED: I ACTUAL NUMBER OF SEATS: 13 FIXTURE COUNT 5UMMARY TOTAL NUMBER OF OCaPANT5: JEANS OF EGRESS 13 EGRESS WIDTH 32" /(.2) = 160 OCCUPANTS , NUMBER OF FIXT11RE5 PROVIDED: 12 (I UN15EX) * TO THE BEST OF THE ARCHITECT OR ENGINEER'S KNOXEME AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING CODE, 5TH EDITION 2014. * THE DRAWINGS t DESIGN AIRE VALID FOR 12 MONTHS FROM DATE OF BEING SEALED. TO THE BEST OF THE KNOWLEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. ISSUE DATE BY: REVIEW 01/15/15 PERMIT 01ASA5 REV. REV. FREV. Fitr=V. TIDE DOCU'EMM PEW" WO MAU AND EPECFICA7"AND CON EM AM M SOLE Pvmi , OF FRAM PEEi3N, NC. AND EI•WLL NOT EE REPROMM, RI 49M OR COPIED FOR MM P1lO,E M, N MOLE OR PART 1111 Off TiE WM CaMW OP FRW FRAM, ARM=" ALL R1fiFifB AN PMERVED dY M ARCHITECT N ACCORDANCE WTH A C0PYROM AND PATENT LAME MAN OR = PO ROMnON WLL BE PF40SEC 11E3) TO THE Fiu EX1w OF m U WL $MEET TITLE LIFE BAFSTY PLAN ROOM FIN 15H 50HEDULE ROOM NUMBER ROOM NAME FLOOR BASE WALL FINISH DOOR FINISH CEILING REMARKS NORTH EAST SOUTH WEST 100 REGEPTIONJMANICURE VCT NA PT PT -I PT PT PAINTED ACT 101 PEDICURE AREA VGT NA PT PT PT PT PAINTED ACT 102 MAS5ASE VCT NA PT PT PT PT PAINTED ACT 105 OFFICE VCT NA PT PT PT PT PAINTED ACT 104 UNISEX } , RR VCT NA CT CT CT CT PAINTED ACT 105 EMPLOYEE AREA VCT NA PT PT PT PT PAINTED ACT IOb MECHANICAL ROOM SEALED CON,. NA PT PT PT PT PAINTED EXP05W ABSREVIATION5 CT - CERAMIC TILE GYP - 6YP. BOARD CEILING LW - PORCELANOr'A VINTAGE FLOOR TILE PT - WHITE PAINT VCT - VINYL COMPOSITION TILE ST N - STAIN VB - VINYL BASE P._I _ MODULAR ARTS - MODULAR DUNE PAINT FINISH SC�TDULE 4 SCALE: I/4" = DOOR 50HEDULE MARK LOCATION DOOR FRAME REMARKS SIZE TYPE MAT FIN MAT FIN 102 MASSAGE ROOM V-0' x 1'-0' x 1 5/6' A WOOD PNT. WOOD PNT. 105 OFFICE 5'-0' x 'I'-0' x 1 5/6' A WOOD PNT. WOOD PINT. LOCK 4 CLOSER 105 UNISEX HC RR 5'-0' x'T'-O' x 1 5/6' A WOOD PNT. WOOD PNT. LOCK IOb MECHANICAL ROOM 5'-0' x V-6' x 1 5/6' B NOOD PINT. WOOD PNT. SINGLE BIFOLD ALL DOORS TO BE COMMERCIAL GRADE LOCKSET. DOOR SCHEDULE AND TYPES SCALE: 1/4" = P-O" FINISH FLOOR L. 3'-4" 5'-0' O H.M. INTERIOR DOOR 9, 5'-0' O INTERIOR BIFOLD 51N&LE _ Z VBIZON WIRELESS PAINT OVER BUSINESS OCCUPANCY EXISTTN6 DRYWALL 2 HOUR RAT® TENANT EXI5TIN6 INTERIOR SEPARATION WALL. METAL STUD WALL U.L. DETAIL U4011 +,N6 EJQS'�a100 RECEPTION 4 MANICURE AREA ® GL6. HT. II'-0' 3OT0 mtmx EXJ EMER 21AN I t FURRING STRIPS ON EXISTING EXTERIOR CMU WALL 20'-4' OVATION PLAN : 1/4" = 1'-0" BRACE TO STRUCTURE ABOVE + IBOTTOM OF ACT I Vl— r BOTTOM OF ACT 5 IN METAL STUDS AT 24" O.C. TYP. TO vEGK I LAYER J' 6YP9UM WALL EACH SIDE OF 5 IN METAL STUDS BASE V-10' O C 0 r A 105 OFFICE CL6. HT. I V-4' SOLIND I � T rION + 424 CONTINUOUS 25 6AU6E METAL STUD TRACK ANCHORED WITH IN DIAL PONDER ACTUATED TYPE FASTENED AT 2'-O' O.G. MAX. TRACK TO BE SAME 6AU6E A5 STUDS BASE NOT RATED: SOUND BAITS ONLY SAT4WOM WALL& 1'-0' 7'-10' TOP OF HALF WALL b" METAL STUDS AT 24' O.G. TYP. I LAYER i' GYPSUM NALL— EACH SIDE OF b' METAL STUDS BASE Im= PARTITION TYPES 2 SCALE: I/2. = I'-O" V-4' ENTJEK EXISTING EXTERIOR CMU WALL CONTINUOUS 25 6AUOE METAL STUD TRACK ANCHORED WITH I" DIA. POWDER ACTUATED TYPE FASTENERS AT 2'-0' O.G. MAX. TRACK TO BE SAME 6AU6E AS STUDS BASE RENOVATION NOTES: L ALL WORK TO BE DONE IN ACCORDANCE WITH THE LATEST STANDARD BUILDNG CODE AND ALL LOCAL BUILDING: CODES. 2. ALL DEMOLITION WORK SHALL BE PERFORMED WITH 'DUE CARE AND DILIGENCE" SO AS TO PREVENT THE AJa'' 5 RARY DESTRUCTION OF INTERRUPTION OF CONCEALED UTILITIES WHICH ARE INTENDED TO REMAN N USE AND THE ROUTING OF WHICH COULD NOT BE PRE -DETERMINED UNTIL DEMOLITION WAS STARTED. ALL SUCH DISCOVERIES OF UTILITIES DURING THE DEMOLITION PROCESS WHICH ARE IN A LOCATION DIFFERENT FROM THAT INDICATED, CHANGE DIRECTION, ETC, OR ARE UNIDENTIFIED, SHALL BE REPORTED TO THE ARCHITECT / OWNER BEFORE REMOVAL FOR FINAL DISPOSITION. 3. REMOVE ALL CONSTRUCTION DESIGNATED TO BE REMOVED AND CLEAR TO RELIEVE NEW WORK AS WERE -IN INDICATED. 4. REMOVE PORTIONS OF EXISTING CONSTRUCTION AS DRAWN AND PATCH TO MATCH ADJACENT 0"TRUCTION TO ACHIEVE INFORM, NEW APPEARANCE. S. THE OWNER WILL NOT BE HELD LIABLE FOR FELD CHANGES THAT ARISE FROM CONTRACTOR ERROR OR OMISSION OF MATERIALS 6. THE CONTRACTOR GUARANTEES ALL WORK AGAINST FAULTY OR IMPERFEC I MATERIALS OR WOIQGMANSHIP ALL WORK SHALL BE ENTIRELY WATERTIGHT AND LEAKPROOF. ALL MATERIALS ARE INSTALLED N ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. T. THE CONTRACTOR SHALL GIVE WRITTEN NOTICE TO THE ARCHITECT OF ANY MATERIALS, EQUIPMEMI OR DESIGN FEATURES W41CH HE BELIEVES INADEQUATE OR MITABLEt N VIOLATION OF LAM, ORDINANCES, OR RULES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION OVER THE WORKt AND OF ANY NECESSARY ITEMS OR WORK OMITTED FROM THE DRAWINGS OR SPECIFICATIONS. S. PLANS WERE DEVELOPED FROM INFORMATION SUPPLIED BY THE OWNER AND EXISTING CONDITIONS OBSERVED. ANY DISCREPANCIES BETWEEN DRAWINGS AND EXISTING CONDITIONS ARE TO BE REPORTED TO ARCHITECT PRIOR TO STARTING WORK ON A GIVEN ITEM AND BEFORE INCURRING ANY ADDITIONAL. COSTS. 5, CONTRACTOR SHALL FELD VERIFY ALL DIMENSIONS INDICATED. FABRICATION SHALL BE BASED ON THE ACTUAL FIELD DIMENSIONS ONLY. 10. ARCHITECT HAS NOT CONDUCTED ANY INVESTIGATION AS TO THE PRESENCE OF ASBESTOS OR ANY OTHER HAZARDOUS SUBSTANCE AND ASSUMES NO RESPONSIBILITY WITH RESPECT TO SAME. IL DESIGN DRAWINGS INDICATE SCHEMATIC STRUCTURAL MEMBER LAYOUT. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS INDICATING ACTUAL. LAYOUT OF ALL STUCTURAL MEMBERS FOR APPROVAL PRIOR TO INSTALLATION, ALONG WIT14 REGISTERED STRIICIURAL ENGINEER'S CALCULATIONS. ALL MEMBERS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS RECOMMENDATIONS INCLUDING BRACNG, SPACING, ETC, 12. CONTRACTOR PRIOR TO INSTALLATION SHALL FELD VERIFY ALL EXISTING CONDITIONS AND BRING TO THE ATTENTION OF THE ARCHITECT ANY DISCREPANCIES. 13. CONTRACTOR 15 REQUESTED TO VISIT THE SITE, COMPARE THE DRAWINGS AND SPECIFICATIONS WITH VISIBLE EXISTING CONDITIONS AND INFORM ARCHITECT AS TO ANY DISCREPANCIES PRIOR TO BID SUBMISSION SO AN ADDENDUM CAN BE ISSUED. FAILURE TO VISIT THE SITE WILL N NO WAY RELIEVE T14E CONTRACTOR FROM NECESSITY OF RM1514NG ANY MATERIALS OR FERFORMNG ANY WORK T14AT MAY BE REQUIRED TO COMPLETE WORK IN ACCORDANCE WITH DRAWINGS AND SPECIFICATIONS WTHOUT ADDITIONAL COSTS TO THE OWNER 14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE EQUIPMENT AND METHODS USED N THE ERECTION OF 1416 WORK COVERED BY 114E CONTRACT, BUT THE ARCHITECT RESERVES THE RIGHT TO APPROVE SUCH E UIPMENT AND METHODS. 15. THE CONTRACTOR SHALL BE TOTALLY RESPONSIBLE FOR ANY AND ALL DEVIATIONS FROM THE CONSTRICTION DRAWINGS INSTALLED WITHOUT APPROVAL OF ARCHITECT AND LOCAL JURISDICTION. THIS INCLUDES REPAIR COSTS NECESSARY TO CORRECT UNAPPROVED WORK INSTALLED. S" ENGINEER RESERVES THE RIGHT TO MAKE MODIFICATIONS AS CONSTRUCTION PROORESSE5. THIS 15 A REMODEL TO AN OLD HOME, AND AS SUCH, EXISTING CONDITIONS MUST BE ASSESSED BY CONTRACTOR alESTTONABLE AREAS MJST BE BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD. ENGINEER HA5 DONE NO FIELD INVE5TIOATTON PRIOR TO CONSTIWTIOK EASTIN5 CONDITIONS INDICATED IN T14I5 PLAN SET ARE ASSUMED. CONTRACTOR TO INFORM ENGINEER OF ANY DIFFIRENCE IN DIMENSION OR BEARING AS DEMOLITION COMMENCES. EWNEER MAY REQUIRE AD0111ONAL SUPPORT OR MAY MAKE CHANGES TO ATTACHMENT CRITERIA AS WORK PRO- SRESSES. CONTRACTOR IS NOT TO ASSUME ANYTHING, BUT 15 TO CONSULT WITH ENGINEER FOR CLARIFICATION OF ANY PLAN NOTES, OR FIELD CONDITIONS THAT ARE FOUND TO DIFFER FROM THOSE PRESENTED IN THE PLANS. WALL LEGEND # TO THE BEST OF THE ARCHITECT OR ENGNEER'S KNOWLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDNG CODE, 5TH EDITION 2014. * THE DRAWINGS 4 DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF BEING SEALED. TO THE BEST OF THE KNOWLEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MIN" BUILDNG CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. ISSUE DATE BY: REVIEW 0115/15 PERMIT 01/15A5 REV. REV. REV. REV. TIME DOCU'Bdfb, DEEIgi6, NOM MAU AND OPWA:CATIONE AND COiCB'IS ARE THE SOLE PROPERTY OF RPAZE DEE W NC. Alm 64ALL NOT BE REPRODucr�, RE�kED oR COPIED FOR DINER PR01E M N ME OR PART YAl;W THE MOTTE1 WOW OF FRANC FRM ARC 1W, ALA. ALL RIGHTS APE RESERVED BY THE ARCFNIECT N AOCOImANCE METH U& COPYRIGHT Alm PATENT LAZE. LWAUMORM IWFROD=ICN FALL ME PROEECIltFD TO THE FLLL EXTENT OF THE LALL 0 O �n Q T� I--i F-� 40-4 H OPIP ONN NMI N SHEET TITLE RUNOV14TION PLAN REFLECTED CEILING PLAN 1 �LSALE: 1,41 = I 1 22OV REGEPTAGLE - ------ - ---- .. -- - F-), LEX REGEPT wT; S WITCHED i DUPLEX (5FL,7 WIRE) --- WV C-AROUND FAULT CIRCUIT INTERUPTER SINGLE TOLE S ....................... WAS SWITCH SMOKE DETECTOR 5ED IGHT IGHT FIXTURE CEILINO MOUNT 250 V DRYER REGEPT --- ABOVE GNTR. T . ----RECEP A.F.F. DUPL REGEPT. DU= EX R-GEPT. PnTr ,RRG FAUN -W "` SWITCH DI` MER SD SW'TGH ......... ��P ...................................... WAT-R �RaaF ��' GfI�ING MOUNT r FLUORESCENT L GHT ........ ......................................... RECESSED HALOOEN 51=OT L10H7 FIXTURE SIGHT FIXTURE __.� CABINET LTG—. WALL MDUNT ABOVE & �s--- w __.._._ -- DIREGT WIRE ("J" BOX) ,L\ TRACK LIGHTING FOR APPLIANCE J! NGTION BOX DOUBLE FLCODLIOHT EQUIPMENT E D 5GONNEG7 rT DUPLEX REGEPT. wP FLOOR MOUNT F y CEILING FAN ONLY L CEILING FAN W/ LIGHT FIX I TO, 7TELEVISION GABLE JACK TELEPHONE OUTLET (LINE 1) L._...-- G� ...._............ .................... TELEPHONE CUTLET (L I NE 2) ............................. .. PE DOOR FELL cH DOOR CHIME Ec I NTERCOM STAT.ON --- ----------------------- s/cM - SMOKE DETECTOR/ CARBON MONOXIDE DETECTOR EXHAUST FAN EXHAUST FAN - L1(5-J7 COMBO 0 LTG/PAR BRANCH PANEL NOTES: I. PROVIDE AND INSTALL LOCALLY CERTIFIED SMOKE DE=ECTORS AND GARBCN MONOXIDE DETECTORS AS REOLPREI7 BY NATIONAL FIRE PRCTEGTION A550GIA7ION (NFPA) AND MEETINO THE REOUIREMENTS OF ALL OOVERNINO CODES. 2. PROVIDE AND 'INSTALL GROUND FAULT GIRGUI7-IN7ERUF7ERS (GFU AS REQUIRED BY NATIONAL ELECTRIC GODS (NEC) AND MEETING THE REOUIREIMENTS OF ALL 00VERNINO GORES. 5. JNLE-SS OTHERWISE INDIGA T ED, INSTALL SWITCHES & RECEPTACLES AT THE FOLLOWING HEIGHTS ABOVE FINISH FLOOR: 5W1TGHE5........ 42" OJTLETS.......... 1411 TELEPHONE .... 14'' TELEVISION ..... 14'' 4. ALL GROUND FLOOR ELECTRICAL ECUIPMENT TC E3E MOUNTED AT REQUIRED HEIOHT ABOVE F;-OCD LEVEL. GONTRAGTOR TC VERIFY EXACT HEIGHT 5. PROVIDE AND INSTALL ARC, FAULT GIRGUIT-IN7ERUP7ER5 (AFC;) AS REQUIRED BY NATIONAL ELECTRIC CODE (NEC) AND MEETINO THE REOUIREMEN75 OF ALL GOVERNINO GORES. &. ,ALL PL,;MBINO ELECTRICAL, AND MECHANICAL ROUGH -INS MU5T BE CCN(PLETE N5PEGTED, AND APPROVED BEFORE REOUE57ING THE FRAKNO INSPECTION. FBC 105.E * TO THE 1EE5T OF THE ARGPTECT OR ENGINEER'S KNOWLEDGE AND BELIEF, TLE5E PL4N5 AND 5PEGIFIG4TON5 COMPLI- WITH THE FLORIDA BUILDING CODE, STH EDI-ION 2014. THE DRAWING5 4 DESIGN ARE VALID FOR 12 11ONTH5 FROM DATE OF BEING 5E4LED. TO THE BEST OF THE <NOWLEDGE O¢ THE ARCHITECTS OR ENGINEERS, SAID FLANS AND 5=EGIFICATIONS GOMPLI- WITH %4E APPLIGABLE MINIMUM BUILDING CODES AND THE APPLICABLE MINIMUM FIRE SAFETY 5TAND4RDS. ALL DIMEN510N5 AND JOE3 CONDITIONS SMALL BE VERIFIED 5� THE CONTRACTOR, ANi- AND ALL D15CREfi ANGIES SMALL 5- REPORTED TO THE 4RC-1iTECT PRIOR TO GOMMENGEMENT OF GN5TRJICTI0N. 155UE DATE F5 r"= RE VIEUJ 07/I5/1E� - '=ERIYI T 0-T/I 5 RE V. REv. RE,V, THESE DOCIJMENT5, DE51GN5, NOTE5, DETAILS AND 5PECIFIC4TION5 [AND CONCEPTS ARE THE SOLE PROPERTY OF FRAZE DESIGN. INC, ANC 5HALL NOT 5E REPRODUCED, RE -USED OR COPIED FOR OTHER PROJECT5, IN WHOLE OR PART WITHOUT THE WRITTEN CON5EN" OF FRANK FRAZE, ARCHITECT, AIL_ ALL RIG=H-5 +RE RESERVED 5Y T+-,E ARCHITECT IN AGGORC4NCE WITH U.5. COPIRIGHT AND PATENT LAW°. JN4U7HORIZED REPRODUCTION WILL 5E IROSEGU'ED TO THE FULL EXTENT OF THE LAW. N V) I `0 . M N A zz cn A w H ac� .o � M i 00 N M N t` I w1 SHEET TITLE REF-ECT F-) CE INS 51"EET NUiYBER 0 9-1 1 TYPICAL HC RESTROOM SCALE: 12 = 1'-�" DELEVATION A SCALE: 1'-(d" 7'-4" DELEVATION B SCALE: 112" = 1'-0" GENERAL HANDICAPPED MOUNTING HEIGHTS FOR WALL ACCESSORIES SCALE: N.T.S. 9 E om IT i, r gr i= 4 ELEVA�1?� C SCALE: NOTE: PROVIDE INSULATION AT NOT WATER SERVICE LINES AND DRAIN PIPE. 7 MIRROR [B] SOAP DISPENSER F—cl TOILET TIME DISPENSER El6RAB BAR 56"x I )f DIA. MIN. El6RAB BAR 42"x 15' DIA. MIN. ElTOILET PAPER DISPEW;ER Hl BACKIN6 O5'-0" DIAMETER CLEAR ADA FLOOR AREA O50" x 46" CLEAR ADA FLOOR AREA O5&" x 60" CLEAR ADA FLOOR AREA TO T14E BEST OF THE ARCAITECT OR ENGINEER'S KNOWLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDNG CODE, 5TH EDITION 2014. * THE DRAWINGS 4 DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF BENG SEALED. TO THE BEST OF THE 14dOWLEDGE OF THE ARCHITECTS OR ENGNEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDNCs CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. ISSUE DATE BY: REVIEW OIA5115 PERMIT 01/15/15 REV. REV. REv. REV. IMM DOCI M, DEeM, KM, WAILS AV 614ECFICAr M AV CO C" AID M Sal FROMI I aF FRAM DESKS W- AND & ALL Nor BE IVErRODucED, �-ueED oR COPED FGR ar>.ER RWACM N WU OR PART WlFW M WFI 84 COFMW OF Fft" FRM ANCHMMr, AIA ALL FX*n ARE 160NAD BY M ARCWW N ACCOI®MM WiH UA COPYRIGFR AFD PAW LAMB. MAUMO M I!p' WOWI IAd WLL BE MQMECM romnLExwOFmLau 0 Q T� 1� W v1 1421 0 O Ro N SWEET TITLE Ho RESTRoo I DETAILS 4 ELEVATION& !"ii r=(- I 1 _ I. 9 1 1' --- -_ 36' inh TYPICAL HC RESTROOM 1 SCALE: 1/2" - 1'-0" —6' max iy e 2 ELEVATION A SCALE: 1/2" 1'-0" 1'-4' 3 ELEVATION B SCALE: 1/2" 1'-0" 9 F a SEA' J • �� � IIIIIIIIIIIIIIIIIIII,IIIIIIIIIIIIIIIIII, 1' 4 ELEV��1?� C SCALE: I'-3' NOTE: PROVIDE INSULATION AT NOT WATER SERVICE LINES AND DRAM PIPE. 1'-0" 3'-6" 17"-19" 1 1 /2" DIAM. ❑ W SAFETY " 6 max. O ❑o ❑o O o GRIP D a �p TOI ET x o o M TIS 3UE e _c E d d Lo � I 'h - - - a M M M n io INSULATE (V cv M t` M , I� I Y to e 04 co HOT WATER I I � N I AND DRAIN PIPES WASTE PAPER TOWEL FEMININE TISSUE SOAP ir TOWEL MIRROR & URINAL TOILET WITH GRAB BAR WATER TELEPHONE LIGHT FIRE DUPLEX THERMOSTAT RECEPTACLE DISPENSER NAPKIN DISPENSER DISPENSER BAR LAVATORY COOLER & SHELF SWITCH ALARM OUTLET GENERAL HANDICAPPED MOUNTING HEIGHTS FOR WALL ACCESSORIES SCALE: N.T.S. 7 MIRROR IESOAP DISPENSER FC TOILET TISS E DI5PEN5Bi IE6RAB BAR 56'x 1)" DIA. MIN. 1E6RAB BAR 42"x I Xs' DIA. MIN. ElTOILET PAPER DISPENSER FG] BACKING O50' x 46' CLEAR ADA FLOOR AREA < 56' x 60' CLEAR ADA FLOOR AREA * TO THE BEST OF THE ARCHITECT OR ENGINEER'S KNOWLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING CODE, 5T4 EDITION 2014. * THE DRAWINGS ! DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF BEING SEALED. TO THE BEST OF THE 14"ILEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. IO&JE DATE BY: REVIEW 01/15/15 PE110'11T 01/15/15 REV. REV. REV. REV. rAW DWIrWr6 DF.dIrA'I6, NOIE6, DETAU.B AND eFFCFICAIM AND CONCEPT" AN THE 0= PROPERIICF FR42 POW NC. AND SaLL NOT OE IEPRODM, le -OW OR COPED FOR OTHER PR01ECM, N UNCLE OR PART 011-M 1►E 11110 N CONSENT OF FRANK FRAM, ARCHTIEGT, AIA ALL Win AN WIRMPD BY THE ARq# W N ACC W MIGE ON U& COPYRIGHT AND PAMff LAID WAUIFIOPCM REPRODUCTION WU DE PROEECUM TO TIE FULL Ex1w OF THE Lm O O Q it ^mil v 1 W 424 O F—I NMI O N SHEET TITLE FCC REbTROOI" I DrmTA 11.6 4 ELEVATIONS SWEET NUIBEa A-20, SWITCH A 0 E;ECTRICAL RECEPTACLE PLAN 5GALE: 1/4" = P-O" LIGHTING NOTE: I. ALL 2 X 4 LIGHTS TO HAVE 0 52-WATT 91M PER FIXTURE. 2. ALL WaSSM CAN L16HM TO HAVE 14-WATT COMPACT F&OREscar BULBS A-50, SWITCH D A-27, SWITCH B E;ECTRICAL LIGHTING PLAN 50ALE: 1/4" = P-O" C A-22,24 5,26 ELECTRICAL LECEND 220V RECEPTACLE 25DR V REGEPT F CEILING FAN ONLY 9 DUPLEX ABOVE REGEPT. m SWITCHED 44" A.F.F. DUPL TT DUPLEX (SPLIT WIRE) REGEPT. (?T CEILING FAN W/ '?cFl.. nFr� LIGHT FIXTURE G RGU T........ R.. ............. ............�w.�G...._........�'r..�K .._. _.. _...._„_.. ... ....._,..._,._....,...__,....._.........._...................... w...,,...--.............................. $ POLESINOLE 83 5WHGY}{ Q TELEVISION GABLE JACK $4 4-HAY SD DimmSHIT �1 't EPI�iONE OUTLET 1-IR I (�'L-��'�''�E ...... ................................ ® ...-........_.,...,-,..,_........_...._......................ay............. SMOKE DETECTOR Atr _ .,.,_ .,.,.....,,.,,,,_._,......�....._.........._. _ _........................ OF GEILINS MOOUNT ......._......._..._. W.. .._........................... INE � NE OUTLET RECESSED FLUORESCENT KI DOOR BELL LIGHT FIXTURE .LI6FfT �v.. w �............._. HALOCPEN SPOT ® DOOR CHIME GEIILING LICWT�XTUREE INTERCOM STATION I,•O LIGHT FIXTURE ® s/cam SMOKE DETECTOR/ WALL MOUNT CARBON MONOXIDE DETECTOR TRACK LIGHTING ® DIRECT OR APPLIANCEII �� 0 EXHAUST FAN ❑J JUNCTION BOX EP DISCONNECT T L16HTEXHAUSTFAN COMBO DOUBLE FLOODLIGHT ®Gwnp FLPOW M 0 LTG/PWR BRANCH PANEL I`r��lE•�-� I. PROVIDE AND INSTALL LOCALLY CERTIFIED SMOKE DETECTORS AND CARBON MONOXIDE FDI DETECTORS �pN pGI,gTION �yFPAJ AND MEETING THE REQUIRE TS OF ALL E VERNINa GODE5. 2. LWI :MENTS TTI ALI. E�IN6CG� EL:5. -IN TT `rHE' A5 5. 4 I HEI 16�HT5 ABINISFi FL ITM i RECEPTACLES AT I 1 I0 N.....14" 4. T�1ljf% IXAGT T LOO FL I 0 LEYEL CNTRAGB TOR TED AT 5. �TS�FT'IONAL�N6G Tfaa?E 6. OOe,OL I3j5,%IVEZGAL ��ATI FRAMING INSPEGMTION.05 $ TO THE BEST OF THE ARCHITECT OR ENGINEER'S 104MEDGE AND 5ELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING CODE, DTH EDITION 2014. * THE DRAWINGS t DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF BEING SEALED. TO THE BEST OF THE KNOWLEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDNG CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISC EPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. ISSUE DATE BY: REVIEW CIADI15 PERMIT 01/15/15 REV. REV. REV. REV. &lWF CATWW *0 CaNCWM AM TILE BOLE FROFERIY OF FRAM DEBw NC. AND al I NOT w RPRODM, RE-WW OR C(rW FOR 0TWt FR7 W", N WIOLE OR PART WTNOUT M W MW CON W OF FRANK FRAM, ARCH= AIA ALL 000 ARE Itl8 oW BY THE ARCAW N ACf.OR MM WTH U& COFY1tlW AND PATENT LAWS. WNliNOMW R'sfWDUCIION WLL CE FFMCUIED TO THE RUl EXfW OF M LAW SHEET TITLE ELECTRICAL LIGHTING 4 RECEPTACLE PLAN SET NUMBED PANEL SCHEDULE AMPS: 100 AMP LOCATION: BACK VOLTS: 120 240V PHASE: 3 WIRE: GRN. BAR: SQ. D. TYPE:QO NEMA: 1 MTD: S SPACES: 30 FEEDER WIRES: CKT AMP. PHASE DESCRIPTION VA WIRE NOTES PHASE CKT AMP. PHASE DESCRIPTION VA WIRE NOTES NO. SIZE A B C NO. SIZE 1 20 NAIL TABLE 2 20 NAIL TABLE 3 20 NAIL TABLE 4 20 NAIL TABLE 5 20 NAIL TABLE 6 20 NAIL TABLE 7 20 TV RECEPTACLE 8 20 TV RECEPTACLE 9 30 DRYER 10 20 PEDICURE CHAIR 11 12 20 PEDICURE CHAIR 13 20 WASHER 14 20 PEDICURE CHAIR 15 16 20 PEDICURE CHAIR 30 HOT WATER 17 18 20 1 OFFICE & BATHROOM RECPETACLE 19 20 20 NAIL STATION LIGHTS 30 HOT WATER 21 22 50 AHU 23 20 PEDICURE CHAIR 24 25 20 PEDICURE LIGHT 26 50 A/C 27 20 SIGN 28 29 20 SHOW WINDOW 30 20 EXHAUST FAN TOTAL CONNECTED VA TOTAL CONNECTED VA NOTES: 1. PRIOR TO ANY WORK, FIELD MEASURE ACTUAL LOAD ON THIS PANEL TO CONFIRM THAT THIS PANEL IS CAPABLE OF SUPPORTING NEW LOADS SHOWN. REPORT RESULTS TO ARCHITECTURE IN WRITING PRIOR TO BEGINNING AND CONSTRUCTION ACTIVITIES. 2. * INDICATES EXISTING BRANCH CIRCUIT TO REMAIN. 3. FIELD VERIFY ALL ITEMS IN THIS PANEL SHOWN EXISTING TO REMAIN & ENSURE CONTINUITY OF SERVICE TO THESE CIRCUITS IF REQUIRED PER THE NEW DESIGN (E.G. EXHAUST FANS). 5. DEMAND LOAD CALCULATION: ITEM LOAD LIGHTS 3137.5 ® 100% WATER HEATER (2) 10,000 VA HEAT (1) 10,000 VA NAIL TABLE (6) 7200 VA PEDICURE CHAIRS (8) 8100 VA GP RECEPTACLES (5) 2000 VA EXHAUST FAN (2) 1200 VA DRYER (1) 5000 VA SIGN (1) 1200 VA LARGEST MOTOR 2500 VA SHOW WINDOW 1200 VA TOTAL 18,4000 AMPS FIRST 10,000 0 100% 10,000 REMAINDER ® 50% 19,200 1009E LIGHT 3137.50 TOTAL VA 32,337.5 TOTAL 89.826 AMPS 6013 EXISTING VERIZON LOAD 100 AMP TOTAL 6013 NEW NAIL SALON 83.993 AMPS TOTAL LOAD OF EXISTING 600AMP = 183.933 AMPS EMT—IN6 Fw-o AMP 120/708Y " NIPPLE W/ (4) 3/0 ALU XHHW ELECTRICAL SPECIFICATIONS: 1. GENERAL A. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM AS OUTLINED IN THE CONTRACT DRAWINGS AND THESE SPECIFICATIONS. B. NOTE THAT DRAWINGS ARE DIAGRAMMATIC ONLY AND INTENDED TO SHOW THE GENERAL ARRANGEMENT OF SYSTEMS. NOT EVERY MINUTE DETAIL C. DO NOT SCALE PLANS. D. PROVIDE ALL NECESSARY FITTINGS, BOXES, TRANSITIONS, CONNECTORS, ETC. WHETHER SHOWN OR NOT ON PLANS. E. ALL WORK IS NEW UNLESS OTHERWISE NOTED. F. THESE PLANS REPRESENT THE DESIGN INTENT BASED ON INFORMATION AVAILABLE AT THE TIME OF DESIGN. ANY SUBSTANTIAL MODIFICATIONS OR ALTERATIONS MADE DURING THE CONSTRUCTION PHASE SHALL BE REPORTED TO THE ENGINEER PRIOR TO WORK. MODIFICATIONS MADE WITHOUT THE ENGINEER'S WRITTEN APPROVAL SHALL REMAIN THE RESPONSIBILITY OF ,THE CONTRACTOR. G. IN CASE OF ANY DISCREPANCIES BETWEEN THE DRAWINGS, SPECIFICATIONS, FIELD CONDITIONS, CODES, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REFER ALL SUCH MATTERS TO THE ENGINEER IN WRITING IMMEDIATELY FOR RESOLUTION PRIOR TO EXECUTING ANY WORK. ANY WORK PERFORMED WITHOUT THE WRITTEN AUTHORIZATION OF THE ENGINEER SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. H. ALL WORK SHALL CONFORM TO THE FOLLOWING CODES (AS APPLICABLE) AS WELL AS ALL LOCAL REGULATIONS, ORDINANCES, AND AMENDMENTS 2010 FLORIDA BUILDING CODE 2008 NFPA-70 NATIONAL ELECTRICAL CODE 2005 NFPA-72 NATIONAL FIRE ALARM CODE 2. SCOPE OF WORK PROVIDE NEW ELECTRICAL DEVICES AND CONNECT TO EXISTING SYSTEM. PROVIDE NEW LIGHTING, RECEPTACLES, SWITCHES, ETC. AND CONNECT AS SHOWN ON PLANS. 3. ITEMS FURNISHED BY CONTRACTOR IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL MATERIALS, EQUIPMENT, AND ACCESSORIES NECESSARY TO MAKE A COMPLETE INSTALLATION. ALL EQUIPMENT SHALL BE STORED IN A SAFE, DRY PLACE IN THE MANUFACTURER'S ORIGINAL PACKAGING UNTIL READY FOR USE. THE OWNER SHALL NOT BE RESPONSIBLE FOR PROVIDING ANY PART OF THE PROJECT, UNLESS SPECIFICALLY NOTED. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR PAYING ALL REQUIRED FEES, OBTAINING ALL PERMITS. AND ARRANGING FOR ALL INSPECTIONS, INCLUDING COORDINATION WITH AND SATISFYING ALL REQUIREMENTS OF THE ELECTRICAL UTILITY COMPANY(IES) AS MAY BE REQUIRED TO EXECUTE THIS SCOPE OF WORK. 4. WORK IN EXISTING BUILDINGS A. DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE. B. ALL ITEMS REMOVED AND NOT RE —USED SHALL BE TURNED OVER TO THE OWNER. CONTRACTOR SHALL REMOVE ANY UNSATISFACTORY ITEMS FROM THE PROJECT SITE. C. SOME EXISTING ITEMS TO REMAIN WITHOUT WORK ARE SHOWN FOR CLARITY OR REFERENCE ONLY. NOTE THAT ADDITIONAL ITEMS WITHOUT WORK MAY ALSO BE PRESENT. D. DRAWINGS OF EXISTING SYSTEMS ARE BASED ON EXISTING DOCUMENTS AND FIELD CONDITIONS, SOME OF WHICH MAY BE UNVERIFIED. PRIOR TO SUBMITTING A BID, CONTRACTOR SHALL STUDY THE PLANS AND VISIT THE PROJECT SITE IN ORDER TO BECOME FAMILIAR WITH EXISTING CONDITIONS. ANY DISCREPANCIES IN THE CONTRACT DOCUMENTS WHICH COULD SIGNIFICANTLY IMPACT THE PROJECT BUDGET OR SCHEDULE MUST BE REPORTED TO THE ENGINEER IN WRITING IMMEDIATELY. FAILURE TO DO SO WILL NOT BE SUFFICIENT CAUSE FOR DELAYS OR CHANGES LATER IN THE PROJECT. CHANGE ORDERS RESULTING FROM FAILURE TO PROPERLY INVESTIGATE EXISTING FIELD CONDITIONS WILL NOT BE ACCEPTED. ALL WORK IS NEW UNLESS OTHERWISE NOTED. E. MODIFICATIONS TO EXISTING SYSTEMS NECESSARY TO CONNECT TO NEW WORK SHALL BE CONSIDERED TO BE PART OF THE BASIC WORK OF THIS CONTRACT. F. COORDINATE ALL WORK SCHEDULES WITH THE OWNER TO MINIMIZE DISRUPTIONS TO EXISTING SYSTEMS OUTSIDE THIS SCOPE OF WORK. 5 COORDINATION ALL WORK ON THIS PROJECT SHALL BE COORDINATED WITH THE OWNER AND ALL OTHER TRADES PRIOR TO BEGINNING AY WORK OR ORDERING ANY MATERIALS. CONTRACTOR SHALL REVIEW PLANS OF ALL DISCIPLINES INVOLVED AND ADVISE THE ARCHITECT IN WRITING OF ANY CONFLICTS, CODE OR SAFETY ISSUES THAT MAY EXIST PRIOR TO ANY FABRICATION OR ORDERING OF EQUIPMENT. RESOLUTION OF SUCH CONFLICTS WHICH ARE NOT REPORTED PRIOR TO CONSTRUCTION SHALL REMAIN THE RESPONSIBILITY OF THE CONTRACTOR AND CHANGE ORDER PROPOSALS FOR SUCH WORK WILL NOT BE ACCEPTED. PROVIDE ROUTING AND OFFSETS NECESSARY TO AVOID CONFLICTS WITH STRUCTURE, FINISHES, AND WORK OF OTHERS. CONTRACTOR SHALL PROVIDE ALL CORE PENETRATIONS AND PATCHING FOR FLOOR PENETRATIONS. S. DEVICE LOCATIONS A. INSTALL ALL DEVICES IN ACCESSIBLE LOCATIONS, EXCEPT AS SPECIFICALLY NOTED OR PROHIBITED BY NEC. B. PROVIDE MIN. 1808 INCH PAINTED ALUMINUM ACCESS DOORS WITH FULL HINGE AND KEY, FOR ACCESS TO ALL ELECTRICAL DEVICES, PULL BOXES, JUNCTION BOXES. AND ACCESSORIES IN PLASTER, DRYWALL. OR INACCESSIBLE CEILINGS. OR IN WALLS. GROUP DEVICES AT A SINGLE LOCATION, AS AVAILABLE. C. ACCESS DOORS IN RATED WALLS OR CEILINGS SHALL HAVE A RATING AT LEAST EQUAL TO THE RATING OF THE WALL OR CEILING. D. ALL DEVICES, RACEWAYS, ETC. WHICH ARE EXPOSED SHALL BE PAINTED TO MATCH THE ADJACENT SURFACE OR AS DIRECTED BY THE ARCHITECT. E. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED A MINIMUM OF 1'-0" ABOVE THE BASE FLOOD ELEVATION. 7. EQUIPMENT GENERAL ALL EQUIPMENT OF EACH TYPE SHALL BE BY ONE MANUFACTURER AND SHALL HAVE CHARACTERISTICS AS LISTED IN THE EQUIPMENT SCHEDULES. ALL EQUIPMENT SHALL BE UL LISTED, NO EXCEPTIONS I SUBSTITUTIONS ARE ACCEPTABLE PROVIDED THAT THE SUBSTITUTED EQUIPMENT HAS EQUIVALENT CHARACTERISTICS AS THAT SCHEDULED AND IS PROVIDED BY AN ACCEPTABLE MANUFACTURER AS LISTED FOR THAT EQUIPMENT TYPE. CONTRACTOR SHALL SUBMIT PRODUCT DATA FOR ALL EQUIPMENT TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING. SUBMITTALS SHALL INCLUDE DIMENSIONS, WEIGHT, VOLTAGE, AMPERAGE, HORSEPOWER, POWER FACTOR, INTERRUPTING CAPACITY, ETC. 8. CONDUCTORS A. PROVIDE ONLY DUAL RATED THWN-2/THHN-2 COPPER CONDUCTORS. MINIMUM SIZE IS NUMBER 12 AWG. B. CONDUCTORS SHALL HAVE COLORED INSULATION FOR IDENTIFICATION PURPOSES AS FOLLOWS: 2401208/120V PHASE A BLACK PHASE B RED PHASE C BLUE NEUTRAL WHITE GROUND GREEN C. GROUNDED CONDUCTORS WHICH CARRY OVER 250V TO GROUND SHALL BE TAGGED WITH VOLTAGE AT EACH TERMINATION POINT. D. DO NOT INSTALL MORE THAN THREE CURRENT CARRYING CONDUCTORS IN SINGLE RACEWAY (NOT INCLUDING NEUTRAL) WHICH WILL REQUIRE NEC TABLE 310-16 NOTE 8 DERAIING. E. PHASE AND GROUNDING CONDUCTOR SIZES SHALL BE INCREASED AS NECESSARY TO ACCOUNT FOR VOLTAGE DROP. 9. RACEWAYS A. INSTALL ALL WIRING ABOVE GROUND IN METALLIC CONDUIT (EMT INDOORS, RGS OUTDOORS OR IN EXPOSED LOCATIONS). B. ALL EXPOSED RACEWAYS SHALL BE RUN PARALLEL TO WALLS OR CEILINGS AND SHALL BE PAINTED TO MATCH ADJACENT SURFACES OR AS DIRECTED BY THE OWNER. C. WHERE MULTIPLE RACEWAYS ARE RUN EXPOSED, RUN ALL RACEWAYS SQUARE AND PARALLEL IN A NEAT AND ORDERLY MANNER. D. MAKE FINAL CONNECTIONS (NOT MORE THAN 6'-0- LONG) TO ALL EQUIPMENT WITH FLEXIBLE METALLIC CONDUIT (DRY LOCATIONS) OR LIQUID TIGHT FLEXIBLE METALLIC CONDUIT (DAMP OR WET LOCATIONS). E. INSTALL ALL WIRING BELOW GROUND IN RIGID NON—METALLIC CONDUIT (SCHEDULE 40 PVC). ALL EXTERIOR NONMETALLIC CONDUITS SHALL BE UV RESISTANT. ALL CONDUITS RUN BELOW GROUND SHALL BE INSTALLED ACCORDING TO NEC300-5. F. TYPE MC CABLE MAY BE USED AS AN ALTERNATIVE TO CONDUCTORS IN METAL RACEWAY IN DRY INDOOR LOCATIONS, PROVIDED IT IS INSTALLED PER NEC AND APPROVED BY THE AUTHORITY HAVING JURISDICTION. G. METALLIC CONDUITS SHALL. NOT BE USED AS GROUNDING CONDUCTORS. PROVIDE A SEPARATE GROUNDING CONDUCTOR IN ALL METALLIC CONDUITS, BONDED AT BOTH ENDS PER NEC. EXI5TIN& (2) 3" CONDUIT W/ (4) 350 MCM O O 200 AW 200 AW METER METER co 15 Zoo AW EXISTIN& DBC ON ECT 200 AMP w (5)150 AMP DISCOPIrEGT Fl� 2" NEW CONDUIT W/ (4) 3/0 ALU XHHW, (1) # 1 ALU XHHW GROUND ELECTRICAL RISER DIAGRAM SCALE: 1/4" = 1'-0" EXI5TINS 200 A1rP SWCE W 2SM 550 MGM 10. GROUNDING A. ALL ELECTRICAL SYSTEMS SHALL BE PROPERLY GROUNDED PER NEC 250. B. EXPOSED GROUNDING ELECTRODE CONDUCTORS SHALL BE PROTECTED BY RIGID NONMETALLIC CONDUITS, MIN SIZE - in. C. PROVIDE GROUNDING ELECTRODE CONDUCTORS TO DRIVEN GROUND RODS AT THE BASE OF ALL LIGHT POLES, REMOTE BUILDINGS, OR REMOTE EQUIPMENT. D. ALL METAL ITEMS OF THE ELECTRICAL SYSTEM INCLUDING RACEWAYS, BOXES, FIXTURES, ETC. SHALL BE BONDED AND PROPERLY GROUNDED. 11, SWITCHBOARDS AND PANEL BOARDS A. PROVIDE SWITCHBOARDS AND PANEL BOARDS, SIZE AND ARRANGEMENT AS INDICATED ON PLANS AND SCHEDULES. B. MOUNT PANEL BOARDS NOT MORE THAN 480 A.F.F. TO CENTER. C. ENCLOSURES SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE INSTALLED (NEMA 1 INDOORS, NEMA 3R OUTDOORS, ETC.) D. PROVIDE A TYPEWRITTEN PANEL SCHEDULE IDENTIFYING THE FUNCTION OF ALL CIRCUIT BREAKERS IN A CLEAR PLASTIC SLEEVE PERMANENTLY ATTACHED TO THE PANEL BOARD COVER. E. ALL SWITCHBOARDS AND PANEL BOARDS SHALL HAVE A THERMOPLASTIC IDENTIFYING NAMEPLATE PERMANENTLY AFFIXED TO THE FRONT OR COVER. F. PROVIDE ONE 1' EMPTY CONDUIT FROM PANEL TO 6' ABOVE CEILING FOR EVERY (3) SPARES OR SPACES. G. PANEL BOARDS AND SWITCHBOARDS BY: SQUARE D. CUTLER HAMMER. OR GE. 12, CIRCUIT BREAKERS A. ALL CIRCUIT BREAKERS SHALL BE BY A SINGLE MANUFACTURER, WITH SAME STYLE AND WITHSTAND RATING TO MATCH THE PANEL IN WHICH THEY ARE INSTALLED. B. PROVIDE MULTIPLE POLE CIRCUIT BREAKERS FOR MULTIPLE POLE CIRCUITS. HANDLE TIES ARE NOT PERMITTED. C. PROVIDE HACR TYPE CIRCUIT BREAKERS FOR ALL HVAC EQUIPMENT AND WATER HEATERS. D. PROVIDE GROUND FAULT CIRCUIT INTERRUPTER BREAKERS FOR ALL OUTDOOR. BATHROOM, AND KITCHEN BRANCH CIRCUITS WHICH DO NOT UTILIZE GFCI RECEPTACLES, OR AS OTHERWISE REQUIRED BY THE AUTHORITY HAVING JURISDICTION. E. NOT USED. F. NOT USED. G. PROVIDE INVERSE TIME CIRCUIT BREAKERS FOR MOTORS UNLESS SPECIFIED OTHERWISE. H. CIRCUIT BREAKERS SHALL BE PROVIDED WITH INDICATING ON/OFF HANDLES. J. CIRCUIT BREAKERS FOR FIRE ALARMS SHALL BE LOCKABLE. K. CIRCUIT BREAKERS BY: SQUARE D, CUTLER HAMMER. OR GE. 13, DEVICES A. PROVIDE GALVANIZED STEEL BOXES FOR ALL DEVICES IN EXPOSED LOCATIONS OR RECESSED INTO RATED WALLS. B. PROVIDE THERMOPLASTIC OR GALVANIZED STEEL BOXES FOR ALL DEVICES TO BE RECESSED INTO NON —RATED WALLS. C. FINISH OF ALL DEVICES AND COVER PLATES SHALL BE AS DIRECTED BY THE OWNER IN WRITING PRIOR TO ORDERING. D. ALL RECEPTACLES SHALL BE OF THE GROUNDING TYPE. E. ALL RECEPTACLES SHALL BE 20 AMP, 120 VOLT RATED, COMMERCIAL GRADE. F. PROVIDE DISCONNECT SWITCHES (WITH OR WITHOUT FUSES AS SPECIFIED) IN ENCLOSURES SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE INSTALLED (NEMA 1 INDOORS, NEMA 3R OUTDOORS & AT WATER HEATER, ETC.) G. ALL SWITCHES AND RECEPTACLES BY LEVITON, GE. OR EQUIVALENT. H. PROVIDE GFCI RECEPTACLES IN ALL KITCHENS. BATHROOMS. GARAGES, OUTSIDE, OR WHEREVER ELSE SHOWN ON DRAWINGS. LABEL ALL DEVICES DOWNSTREAM OF GFCI DEVICE AS 'GFCI PROTECTED'. PROVIDE AT LEAST ONE DUPLEX GFCI PROTECTED RECEPTACLE IN A WEATHERPROOF ENCLOSURE WITHIN TWENTY FIVE (25) FEET OF ALL ROOF OR GRADE MOUNTED EXTERIOR HVAC EQUIPMENT. J. FOR GFCI RECEPTACLES NOT ON A DEDICATED BRANCH CIRCUIT (SUCH AS OUTDOOR RECEPTACLES CONNECTED TO THE NEAREST INTERIOR CIRCUIT). MAKE EVERY ATTEMPT TO LOCATE THE GFCI RECEPTACLE AT THE END OF THE CIRCUIT RUN SO AS TO MINIMIZE THE POSSIBILITY OF CAUSING NUISANCE POWER LOSS TO OTHER DEVICES WHEN THE GFCI DEVICE TRIPS. 14. LIGHTING A. ALL LIGHT FIXTURES SHALL BE THOSE DESCRIBED IN THE LIGHTING FIXTURE SCHEDULE OR THEIR EQUIVALENT AS APPROVED BY THE ENGINEER PRIOR TO ORDERING. IF ALTERNATE FIXTURES ARE USED, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THEIR INSTALLATION DETAILS WITH ALL OTHER TRADES WITH REGARD TO SPACE REQUIRED, WIRING. POWER CONSUMPTION. ETC. B. LIGHTING BRANCH CIRCUITS SHALL NOT BE LOADED TO MORE THAN 80% OF THE CIRCUIT BREAKER AAPACITY. C. ALL LIGHT FIXTURES INSTALLED IN DAMP, WET, OR HAZARDOUS (CLASSIFIED) LOCATIONS SHALL BE LISTED FOR SUCH USE. D. INCANDESCENT LAMPS SHALL NOT BE USED EXCEPT FOR DIMMING PURPOSES OR AS OTHERWISE STATED ON PLANS OR PERMITTED BY THE AUTHORITY HAVING JURISDICTION. E. ALL FLUORESCENT OR HID LIGHT FIXTURES SHALL BE FUSED WITH ELECTRONIC BALLAST AS REQUIRED TO MEET THE SWITCHING REQUIREMENTS DESCRIBED ELSEWHERE IN THESE DOCUMENTS OR THE AUTHORITY HAVING JURISDICTION. PROVIDE MULTIPLE BALLASTS WHERE REQUIRED TO PROVIDE MULTIPLE LIGHTING LEVELS TO COMPLY WITH APPLICABLE ENERGY CODES. F. INTERIOR LIGHTING IN ALL BUILDINGS LARGER THAN 5.000 SQUARE FEET SHALL BE PROVIDED 5W& AUTOMATIC CONTROLS. CONTROLS SHALL CONSIST OF A CENTRAL TIME —OF —DAY SCHEDULING LLER OR OCCUPANCY SENSORS LOCATED IN EACH SPACE. OCCUPANCY SENSORS SHALL BE LOCATED SO THE OCCUPANT CAN SEE THE CONTROLLED LIGHTING AND SHALL BE CAPABLE OF A 4 HOUR OVERRIDE. LIGHTING CONTROL ZONES SHALL NOT EXCEED 2.500 SQUARE FEET. G. PROVIDE TIME CLOCKS OR NORTH FACING PHOTOCELLS TO CONTROL ALL EXTERIOR LIGHTING CIRCUITS AUTOMATICALLY. PROVIDE LIGHTING CONTACTORS AS REQUIRED. H. ALL EXIT SIGNS AND EMERGENCY EGRESS LIGHTING SHALL NOT BE SWITCHED AND SHALL HAVE BATTERY BACKUP OR BE CONNECTED TO THE EMERGENCY POWER SYSTEM. 15. WARRANTIES AND MAINTENANCE A. ALL EQUIPMENT SHALL BE STARTED, TESTED, ADJUSTED, LUBRICATED, CLEANED, AND PLACED IN GOOD OPERATING CONDITION BY THE CONTRACTOR. CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, MATERIALS, AND WORKMANSHIP TO BE FREE OF DEFECTS FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER AND THE CONTRACTOR SHALL REPAIR ANY SUCH DEFECTS AT NO COST TO THE OWNER. ALL EQUIPMENT INCLUDED IN THE PROJECT SHALL BE COVERED BY THE MANUFACTURER'S WARRANTY FOR THE DURATION OF THAT WARRANTY. COPIES OF ALL MANUFACTURER'S WARRANTIES AND CONTRACTOR WARRANTIES SHALL BE PROVIDED TO THE OWNER AT FINAL ACCEPTANCE. B. CONTRACTOR SHALL MEET WITH THE OWNER'S REPRESENTATIVE AND REVIEW ALL OPERATIONS AND MAINTENANCE OF ALL SYSTEMS. CONTRACTOR SHALL PROVIDE THE OWNER WITH BOUND COPIES OF ALL OPERATION AND MAINTENANCE MANUALS INCLUDING PARTS LISTS, MAINTENANCE SCHEDULES, ETC. C. THE CONTRACTOR SHALL CONTINUALLY RECORD ANY AND ALL DEVIATIONS TO THE CONTRACT DOCUMENTS MADE DURING CONSTRUCTION AND PROVIDE A COMPLETE SET OF THESE RECORD DRAWINGS TO THE OWNER WITHIN 30 DAYS OF COMPLETION OF CONSTRUCTION. IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE THE SERVICES OF A LICENSED PROFESSIONAL ENGINEER TO PROVIDE SIGNED AND SEALED RECORD DRAWINGS. 1 B. TESTING A. AT THE COMPLETION OF THE PROJECT, TEST ALL ELECTRICAL EQUIPMENT AND DEVICES FOR PROPER OPERATION. TEST FOR GROUNDS AND SHORTS. REPORT ALL RESULTS TO THE ARCHITECT IN WRITING. REPLACE ANY DEFECTIVE DEVICES OR EQUIPMENT. B. TEST ALL FIRE ALARMS, GENERATORS, AND OTHER LIFE SAFETY EQUIPMENT IN THE PRESENCE OF THE ENGINEER AND THE FIRE OFFICIAL TO DEMONSTRATE OPERATION. MAKE ANY MODIFICATIONS NECESSARY AS REQUIRED BY THE FIRE OFFICIAL AND REPAIR OR REPLACE ANY DEFECTIVE ITEMS AS NECESSARY. * TO 1I-E BEST OF TNT= ARCHITECT OR ENGINEER'S IQdOIIlLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA SUILDNG CODE, 5TH EDITION 2014. * THE DRAWINGS t DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF 5EING SEALED. ISSUE DATE BY: mvIEW 01/15/15 PERMIT 01/15/15 REV. REV. REV. REV. THEE DOGNByTb, MM WO MAU AW aPE WATM AW OONCF.P'P8 AM THE 6CLE PROMI I CP FRAM OBW NC. AM 61 NOT DE REPRODUCE, R -LM OR COPIED FOR OnOt PRMEM, N 04ME OR PART Wi W THE WiI EN COMM CP PRANK PRM AwZwn is AJAR ALL WAM ARE PROR Ep DY THE ARCHRECT N AOCOWW" WrtW U& CCPYN04 AW PAW LNtB LMANOFM 1i6°ROGuc m WLL EE PROEEC m TO THE FULL WW CP THE Last SHEET TITLE ELECTR I CAL PANEL SG-IEOULE 4 SPECII:ICATIONS. J v2" VTR SANITARY RISER DIAGRAM : 1/4" = 11-0" SANITARY PLUMBING PLAN 1/4" = 1'-0" 11 C.O. 4" * TO THE BEST OF THE ARCHITECT OR ENGINEER'S EDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING: CODE, 5TH EDITION 2014. * THE DRAWINGS t DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF BEING SEALED. TO THE BEST OF THE IMWLEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. ISSUE DATE 5Y: REVIEW 01/15/15 PERMIT 01/15/15 REV. REV. REV. REv. rEMATM *0 CO C" ARE M eoLE PRoI'Mi I OF REAM MW NG *V SK LL NOT BE NPROMM, RED OR COPED FAR OnM FlCIE:GT6, N UH" OR TART II1i W M WQM CO Mff OF F RAW FiiAZE, M MI M, A" ALL WOO AN WORM BY M AIiCFNW IN AGCOII MM IM UA. COF rnftg *0 PATENT LAM ULNlF CMW NrR=UG ION OU BE MweEcM TO TM FULL EX w OF M LmL O d' v-� A� �L T� FBI vL 40-4 �uu OO > M� H NMI SHEET TITLE "N I TARY PLUMBING PLAN 844EET NIIM19E p I PLUMBING SPECIFICATIONS: PLUMBING FIXTURE AND CONNECTION SCHEDULE 1. GENERAL 12, VALVES & ACCESSORIES A. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM AS A. PROVIDE WATER HAMMER ARRESTORS OR AIR CHAMBERS AS REQUIRED TO ELIMINATE WATER GENERAL CONNECTIONS NOTES OUTUNED IN THE CONTRACT DRAWINGS AND THESE SPECIFICATIONS. HAMMER AND COMPLY WITH LOCAL REGULATIONS, PARTICULARLY AT ALL APPLIANCES OR DEVICES TAG DESCRIPTION MTG. HEIGHT WASTE VENT CW HW B. NOTE THAT DRAWINGS ARE DIAGRAMMATIC ONLY AND INTENDED TO SHOW THE GENERAL WITH QUICK -CLOSING VALVES. ARRANGEMENT OF SYSTEMS, NOT EVERY MINUTE DETAIL B. PROVIDE A MAIN SHUTOFF VALVE AT THE BUILDING'S DOMESTIC WATER SERVICE ENTRANCE. P-1 SINGLE COMPARTMENT COUNTERTOP 1 1/2" 1 1/2" 1/2" 1/2" WHITE VITREOUS CHINA COUNTERTOP LAVATORY W/ 4" CENTER FAUCET C. DO NOT SCALE PLANS. C. PROVIDE VACUUM BREAKERS FOR ALL SILLCOCKS. HOSE BIBBS, AND WALL HYDRANTS. SINK FLOOR TO RIM HOLES. 0.5 GPM VANDAL RESISTANT FAUCET W/ EXTRA LONG LEVEL, D. PROVIDE ALL NECESSARY FITTINGS, TRANSITITONS, CONNECTORS, ETC. WHETHER SHOWN OR D. PROVIDE CLEANOUTS AT ALL CHANGES OF DIRECTION OF MORE THAN 45 DEGREES OR EVERY NOT ON PLANS. 50 FEET OF STRAIGHT PIPE FOR ALL SANITARY WASTE AND STORM DRAIN PIPING. PROVIDE 31 " MAX HOT LIMIT STOP, GRID DRAIN. 1 J" 17 GA. TRAP W/ CLEANOUT. E. ALL WORK IS NEW UNLESS OTHERWISE NOTED. CLEANOUTS AT THE BASE OF ALL STACKS. PROVIDE A YARD CLEANOUT FLUSH WITH FINISHED F. THESE PLANS REPRESENT THE DESIGN INTENT BASED ON INFORMATION AVAILABLE AT THE GRADE WITHIN 5 FEET OF THE BUILDING SEWER EXITING THE BUILDING. COORDINATE ALL TIME OF DESIGN. ANY O INSTALLATION. P-2 PEDICURE CHAIR NA 1 1 /2" NA 1 /2" 1 /2p LEXOR PIONEERING "SMART" PEDI-SPA. SEE ATTACHED SPEC SHEET. CONSTRUCTION PHASE SHALL B REPODRTED TO THE ENGINEER PRIOR IFICATIONS OR ALTERATIONS �TO WORK. MODIFICATIONS EDURING THE L PROVIDE EANOUT L DIELECTRIC UNIONS TIONS WITH THE AT CALL POINTS OFHITECT PRIOR TCONNECTION BETWEEN PIPES OF DISSIMILAR MADE WITHOUT THE ENGINEER'S WRITTEN APPROVAL SHALL REMAIN THE RESPONSIBILITY OF THE METALS. CONTRACTOR. F. APPLY MIN. 20 MILS THICK SCOTCHWRAP (OR EQUIVALENT) VINYL TAPE COVERING OVER ALL P-3 LAVATORY FLOOR TO RIM 1 1 /2" 1 1 /2" 3/8" 3/8" PROFLO 5514WH WALL HUNG LAVATORY WITH PROFLO WS4744CP SINGLE G. IN CASE OF ANY DISCREPANCIES BETWEEN THE DRAWINGS, SPECIFICATIONS, FIELD STEEL OR COPPER WATER PIPING IN CONTACT WITH MASONRY OR CONCRETE. (ADA) WALL HUNG 34" MAX LEVER FAUCET. PVD SLIP -JOINT P-TRAP. CR1912CP ANGLE STOP AND CONDITIONS, CODES, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REFER ALL SUCH G. PROVIDE CHROME PLATED ESCUTCHEONS WHERE PIPES PENETRATE ANY EXPOSED WALLS, PEX SUPPLIES MATTERS TO THE ENGINEER IN WRITING IMMEDIATELY FOR RESOLUTION PRIOR TO EXECUTING ANY PARTITIONS, ETC. TO COVER THE PENETRATION. WORK. ANY WORK PERFORMED WITHOUT THE WRITTEN AUTHORIZATION OF THE ENGINEER SHALL REMAIN THE RESPONSIBILITY OF THE CONTRACTOR. 13. FIXTURES P-4 WATER CLOSET-H/C FLOOR TO RIM 3" 2" 3/8" --- PROFLO MODEL 1403JWH ADA ELONGATED BOWL W/ PROFLO PF5112WHM H. ALL WORK SHALL CONFORM TO THE FOLLOWING CODES (AS APPLICABLE) AS WELL AS ALL A. FIXTURES HAVE BEEN SELECTED TO ESTABLISH A STANDARD OF QUALITY AND SUBSTITUTIONS (ADA) FLOOR MOUNTED 2 17" 1.6 GPF TANK IN WHITE. PROFLO TSCOF200WH ELONGATED BOWL WHITE LOCAL REGULATIONS, ORDINANCES, AND AMENDMENTS: ARE NOT PERMITTED UNLESS SUBMITTED AND APPROVED PRIOR TO USE. PIECE FLUSH TANK OPEN FRONT LESS COVER SEAT. 2006 INTERNATIONAL PLUMBING CODE B. ALL VITREOUS CHINA FIXTURES SHALL BE WHITE UNLESS OTHERWISE NOTED. 2006 INTERNATIONAL BUILDING CODE C. SEE ARCHITECHTURAL PLANS FOR EXACT FIXTURE LOCATIONS AND MOUNTING HEIGHTS. 2003 ACCESSIBLE & USABLE BUILDINGS & FACILITIES (ANSI IIICC A117.1) D. ALL FIXTURES IN THE SAME BUILDING OR AREA SHALL HAVE IDENTICAL FAUCETS, WH-1 ELECTRIC WATER FLOOR MOUNTED - - - 3/4" SEE DWGS SEE DWGS (2) A.O. SMITH ELECTRIC 40 GALLON WATER HEATER W SIAMESE CONNECTION CITY OF CHATTANOOGA LOCAL. AMENDMENTS & ORDINANCES (AS APPLICABLE) ESCUTCHEONS, AND TRIM KITS, UNLESS SPECIFICALLY NOTED ON PLANS. / E. INSTALL HOT WATER SUPPLY ON THE LEFT SIDE OF ALL FIXTURES. HEATER T & P 2. SCOPE OF WORK F. ALL LAVATORIES IN PUBLIC RESTROOMS SHALL HAVE 0.5 GPM FLOW RESTRICTING AERATORS. PROVIDE NEW FIXTURES AND PIPING AS SHOWN AND CONNECT TO EXISTING PLUMBING MAINS. G. FLUSH CONTROLS SHALL BE INSTALLED ON THE WIDE SIDE OF ALL WATER CLOSET STALLS. H. PROVIDE CONCEALED ARM CARRIERS OR 200 PT BLOCKING WITH ALL WALL MOUNTED 3. ITEMS FURNISHED BY CONTRACTOR LAVATORIES, URINALS, WATER CLOSETS, AND WATER COOLERS. CARRIERS OR BLOCKING SHALL IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL MATERIALS, EQUIPMENT, WITHSTAND A MINIMUM VERTICAL LOAD OF 250 POUNDS ON THE FRONT OF THE FIXTURE. CWM CLOTHES WASHER 48" A.F.F. 2" 2" 1/2" 1/2" CLOTHES WASHER PROVIDED BY OTHERS. ENCASED WASHING MACHINE VALVES W/ AND ACCESSORIES NECESSARY TO MAKE A COMPLETE INSTALLATION. ALL EQUIPMENT SHALL BE J. PROVIDE PROTECTIVE ANTI -MICROBIAL INSULATION ON THE SUPPLY SET AND WASTE DRAIN SINGLE LEVER HANDLEMOUNTING STRAPS, AND 2" WASTE TAILPIECEPROVIDE STORED IN A SAFE, DRY PLACE IN THE MANUFACTURER'S ORIGINAL PACKAGING UNTIL READY AND TRAP OF ALL HANDICAPPED LAVATORIES. , . BOX FOR USE. THE OWNER SHALL NOT BE RESPONSIBLE FOR PROVIDING ANY PART OF THE K. ALL WATER CLOSETS SHALL BE THE ELONGATED TYPE WITH OPEN FRONT SEATS. INTEGRAL WATER HAMMER ARRESTORS. PROJECT, UNLESS SPECIFICALLY NOTED. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR PAYING ALL REQUIRED FEES, OBTAINING ALL PERMITS, AND ARRANGING FOR ALL INSPECTIONS, 14• SUPPORTS & PENETRATIONS FD FLOOR DRAIN FLUSH W/ PROFLO PVC W/ 6" BRASS TOP INCLUDING COORDINATION WITH AND SATISFYING ALL REQUIREMENTS OF THE PLUMBING UTILITY A. PROVIDE MANUFACTURED PIPE HANGERS, RODS, AND INSERTS OR CLAMPS FOR THE PROPER 3" --- 1 /2" --- COMPANY(IES) AS MAY BE REQUIRED TO EXECUTE THIS SCOPE OF WORK. SUPPORT OF ALL PIPING. BAND IRON, TIE WIRE, OR WIRE STRAPPING ARE NOT ACCEPTABLE. FINISHED FLOOR ALL PIPES SHALL BE SUPPORTED AT REGULAR INTERVALS. PIPE SWAY AND/OR VIBRATION SHALL 4. WORK IN EXISTING BUILDINGS NOT BE ACCEPTABLE. DO NOT HANG PIPING FROM ANYTHING OTHER THAN THE BUILDING GRAVITY A. DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE. STRUCTURE. TP TRAP PRIMER UNDER -- B. ALL ITEMS REMOVED AND NOT RE -USED SHALL BE TURNED OVER TO THE OWNER. B. SUPPORT ALL PIPING ACCORDING TO THE FOLLOWING SPACING CRITERIA: LAVATORY 1 /2w - CONTRACTOR SHALL REMOVE ANY UNSATISFACTORY ITEMS FROM THE PROJECT SITE. HORIZONWED VERTICAL (ED C. SOME EXISTING ITEMS TO REMAIN WITHOUT WORK ARE SHOWN FOR CLARITY OR REFERENCE CAST IRON 5 15 ONLY. NOTE THAT ADDITIONAL ITEMS WITHOUT WORK MAY ALSO BE PRESENT. COPPER 6 10 WHA STAINLESS STEEL WATER HAMMER ARRESTOR WITH " I.P.S. THREADED PIPE CONNECTION D. DRAWINGS OF EXISTING SYSTEMS ARE BASED ON EXISTING DOCUMENTS AND FIELD CPVC 3 10 WATER HAMMER CONDITIONS SOME OF WHICH MAY BE UNVERIFIED. PRIOR TO SUBMITTING A BID CONTRACTOR PVC 4 10 ARRESTOR --- --- 3/4" --- AND TYPE 304 STAINLESS STEEL CASING AND BELLOWS. SHALL STUDY THE PLANS AND VISIT THE PROJECT SITE IN ORDER TO BECOME FAMILIAR WITH STEEL 8 10 EXISTING CONDITIONS. ANY DISCREPANCIES IN THE CONTRACT DOCUMENTS WHICH COULD C. PROVIDE PLASTIC OR RUBBER COATED ISOLATORS WHERE COPPER PIPING IS IN DIRECT SIGNIFICANTLY IMPACT THE PROJECT BUDGET OR SCHEDULE MUST BE REPORTED TO THE CONTACT WITH OR SUPPORTED BY STEEL PIPE HANGERS. ENGINEER IN WRITING IMMEDIATELY. FAILURE TO DO SO WILL NOT BE SUFFICIENT CAUSE FOR GENERAL NOTES DELAYS OR CHANGES LATER IN THE PROJECT. CHANGE ORDERS RESULTING FROM FAILURE TO 15, WARRANTIES AND MAINTENANCE 1. PROVIDE MCGUIRE PRO -WRAP INSULATION KIT FOR DRAIN, TRAP, & SUPPLY ON ALL ADA SINKS AND LAVATORIES. PROPERLY INVESTIGATE EXISTING FIELD CONDITIONS WILL NOT BE ACCEPTED. ALL WORK IS NEW A. ALL FIXTURES SHALL BE TESTED, CLEANED, AND PLACED IN GOOD OPERATING CONDITION BY UNLESS OTHERWISE NOTED. THE CONTRACTOR. CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, MATERIALS, AND 2. ALL DRAIN AND VENT LINES TO BE PVC E. MODIFICATIONS TO EXISTING SYSTEMS NECESSARY TO CONNECT TO NEW WORK SHALL BE WORKMANSHIP TO BE FREE OF DEFECTS FOR A PERIOD OF ONE YEAR FROM THE DATE OF 3. PROVIDE ALL BOLT CAPS, STRAINERS, STOPS, SUPPLIES, TRAPS, ETC. FOR A COMPLETE INSTALLATION. CONSIDERED TO BE PART OF THE BASIC WORK OF THIS CONTRACT. ACCEPTANCE BY THE OWNER AND THE CONTRACTOR SHALL REPAIR ANY SUCH DEFECTS AT NO 4. PROVIDE DEEP SEAL TRAPS FOR ALL DRAINS AND FLOOR SINKS. F. COORDINATE ALL WORK SCHEDULES WITH THE OWNER TO MINIMIZE DISRUPTIONS TO EXISTING COST TO THE OWNER. ALL EQUIPMENT INCLUDED IN THE PROJECT SHALL BE COVERED BY THE SYSTEMS OUTSIDE THIS SCOPE OF WORK. MANUFACTURER'S WARRANTY FOR THE DURATION OF THAT WARRANTY. COPIES OF ALL MANUFACTURER'S WARRANTIES AND CONTRACTOR WARRANTIES SHALL BE PROVIDED TO THE 5. COORDINATION OWNER AT FINAL ACCEPTANCE. PLUMBING SYSTEM DEMAND ALL WORK ON THIS PROJECT SHALL BE COORDINATED WITH THE OWNER AND ALL OTHER B. CONTRACTOR SHALL MEET WITH THE OWNER'S REPRESENTATIVE AND REVIEW ALL OPERATIONS TRADES PRIOR TO BEGINNING ANY WORK OR ORDERING ANY MATERIALS. CONTRACTOR SHALL AND MAINTENANCE OF ALL SYSTEMS. CONTRACTOR SHALL PROVIDE THE OWNER WITH BOUND FIXTURE QUANTITY DFU COLD HOT REVIEW PLANS OF ALL DISCIPLINES INVOLVED AND ADVISE THE ARCHITECT IN WRITING OF ANY COPIES OF ALL OPERATION AND MAINTENANCE MANUALS INCLUDING PARTS USTS, MAINTENANCE CONFLICTS, CODE OR SAFETY ISSUES THAT MAY EXIST PRIOR TO ANY FABRICATION OR ORDERING SCHEDULES, ETC. CLOTHES WASHER 1 2.0 1.0 1.00 OF EQUIPMENT. RESOLUTION OF SUCH CONFLICTS WHICH ARE NOT REPORTED PRIOR TO C. THE CONTRACTOR SHALL CONTINUALLY RECORD ANY AND ALL DEVIATIONS TO THE CONTRACT CONSTRUCTION SHALL REMAIN THE RESPONSIBILITY OF THE CONTRACTOR AND CHANGE ORDER DOCUMENTS MADE DURING CONSTRUCTION AND PROVIDE A COMPLETE SET OF THESE RECORD PEDICURE SINK 8 = 16.0 8.0 8.0 PROPOSALS FOR SUCH WORK WILL NOT BE ACCEPTED. PROVIDE ROUTING AND OFFSETS DRAWINGS TO THE OWNER WITHIN 30 DAYS OF COMPLETION OF CONSTRUCTION. IF REQUIRED BY LAVATORY 3 = 3.0 4.5 4.5 NECESSARY TO AVOID CONFLICTS WITH STRUCTURE, FINISHES, AND WORK OF OTHERS. THE AUTHORITY HAVING JURISDICTION, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR CONTRACTOR SHALL PROVIDE ALL CORE PENETRATIONS AND PATCHING FOR FLOOR TO SECURE THE SERVICES OF A UCENSED PROFESSIONAL ENGINEER TO PROVIDE SIGNED AND WATER CLOSET 1 = 4.0 5.0 PENETRATIONS. SEALED RECORD DRAWINGS. S. PLUMBING GENERAL 16. TESTING TOTAL FIXTURE UNITS 25.00 18.50 13.50 A. ALL PLUMBING SERVICES TERMINATE 5'-0" FROM THE BUILDING EXTERIOR WALLS. A. AT THE COMPLETION OF THE PROJECT, TEST ALL PLUMBING SYSTEMS AND FIXTURES FOR B. NO LEAD OR ASBESTOS CONTAINING MATERIALS OF ANY KIND SHALL BE USED IN THE PROPER OPERATION. TEST ALL PIPING FOR LEAKS ACCORDING TO FPC. REPORT ALL RESULTS TO FABRICATION OF POTABLE WATER SUPPLY SYSTEMS. GALVANIZED STEEL PIPING SHALL NOT BE THE ARCHITECT IN WRITING. REPLACE ANY DEFECTIVE DEVICES OR EQUIPMENT. MINIMUM SANITARY DRAIN SIZE (INCHES) 4" USED FOR POTABLE WATER SUPPLY PIPING. MINIMUM SERVICE FLOW (GPM) 12.00 10.00 C. INSTALL ALL WORK IN COMPLIANCE WITH ADA REQUIREMENTS. COLD WATER MINIMUM WATER SERVICE SIZE (INCHES) 1" 1" D. PROVIDE "P" TRAPS WITH CLEANOUTS IN THE DRAINS OF ALL FIXTURES EXCEPT THOSE WITH INTERNAL TRAPS OR AS SPECIFICALLY NOTED ON PLANS. NOTES E. PROVIDE FLOOR DRAINS WITH TRAP PRIMERS IN ALL PUBUC BATHROOMS. 1. DRAINAGE FIXTURE UNITS DETERMINED FROM 2014 F. ALL PIPING SHALL BE CONCEALED IN WALLS, CHASES, CEILINGS, ETC. UNLESS SPECIFICALLY NOTED ON DRAWINGS. ANY PIPING OR ACCESSORIES THAT MUST BE EXPOSED SHALL HAVE A FLORIDA PLUMBING CODE, TABLE 709.1. POLISHED CHROME FINISH. 2. SUPPLY FIXTURE UNITS DETERMINED FROM 2014 G. INSTALL ALL VALVES AND CONTROLS IN ACCESSIBLE LOCATIONS, EXCEPT AS SPECIFICALLY FLORIDA PLUMBING CODE, TABLE E103.3(2). NOTED ON PLANS OR PROHIBITED BY CODE. HOT WATER SUPPLY 3. SERVICE DEMAND GPM DETERMINED FROM 2014 H. PROVIDE MIN. 6x6 INCH PAINTED ALUMINUM ACCESS DOORS WITH FULL HINGE AND KEY, FOR TO FIXTURES (GPM) ACCESS TO ALL VALVES, CONTROLS, AND ACCESSORIES CONCEALED IN PLASTER, TILE, DRYWALL, OR INACCESSIBLE CEIUNGS OR IN WALLS. GROUP DEVICES AT A SIN TAP M TA E103.3(3). GLE LOCATION AS FLORIDA PLUMBING CODE TABLE, AVAIL ABLE. J. COORDINATE THE ELECTRICAL CHARACTERISTICS OF ALL ELECTRICAL EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO ORDERING. 3/ 4" L PIPING SHALL NOT PASS THROUGH K F ANY KIN G DUCTWORK 0 D UNLESS APPROVED BY THE ENGINEER. WATTS 36 OR EQ. M. PIPING SHALL NOT BE RUN ABOVE ELECTRICAL PANELS , THROUGH ELECTRICAL ROOMS OR VACUUM RELIEF VALVE ANY OTHER WATER SENSITIVE AREAS, EXCEPT AS SPECIFICALLY NOTED ON PLANS. 7. SANITARY WASTE & VENT PIPING A. ALL SANITARY WASTE & VENT PIPING ABOVE AND BELOW GROUND SHALL BE SCHEDULE 40 PVC. ALL SANITARY WASTE PIPING 3" TO 6" SHALL BE SLOPED AT NO LESS THAN 1/8" PER FOOT. ALL SANITARY WASTE 2" AND SMALLER SHALL BE SLOPED AT NO LESS THAN 34" PER c� FOOT. C. THE MINIMUM SANITARY WASTE & VENT PIPE SIZE SHALL BE 1". I D. VERIFY LOCATIONS AND INVERT ELEVATIONS OF ANY AND ALL EXISTING WASTE, VENT, AND I STORM DRAIN PIPING PRIOR TO BEGINNING ANY WORK. EXIST 1" TEMP. & PRESS. MAIN ALL BE TYPE "L" COPPER WITH WROUGHT / S. DOMESTIC WATER PIPING ........ ._.. _.. ........ ......... ......... ....._. ..... ............................ ._................................................. ........ .............................................................................. .. ....................... RELIEF VALVE ,....A. ALL DOMESTIC WATER PIPING ABOVE GROUND SHALL / ._...... ......... ..___.. COPPER FITTINGS AND LEAD FREES R B. ALL DOMESTIC WATER PIPING BELOW GROUND OR SLAB SHALL BE TYPE mKo COPPER WITH / \ WROUGHT COPPER FITTINGS AND NO JOINTS BELOW FLOORS DRAIN TO PAN P-3 C. CPVC PIPING WITH CPVC FITTINGS AND PRIMED/GLUED JOINTS IS AN ACCEPTABLE SUBSTITUTE P 1 FP-2 P 2 � � , I I'-4 JTO COPPER UR SD CTIONPIPING IF INSTALLED PER FBC AND APPROVED BY THE AUTHORITY HAVING \\\\ "HW D ALL NEW WATER SUPPLY PIPING SHALL BE RUN OVERHEAD (DO NOT RUN WATER SUPPLY \ \ �7I PIPING BELOW CONCRETE FLOOR SLABS) UNLESS SPECIFICALLY STATED ON PLANS OR AS PROVIDE APPROVED \ DRAIN VALVE H ABSOLUTELY NECESSARY TO MATCH AN EXISTING INSTALLATION. DRAIN PAN BELOW \ DRAIN TO PAN 1 "CW E yew HEATER, DRAIN TO ,.. D W ,... WATER S WITH 1 THICK, MIN. R-6, CLOSED FLOOR p CELL ALL INSULATION OR EQUIVALENT). OR EXTERIOR w ( NT) j"CW"CW"CW CV�I » 1wHW 1: I HW �,. I : j»HW L... I HW I 9. NOT USED CW" W 10. VENTS "HW A. ALL TRAPS OR TRAPPED FIXTURES SHALL BE PROVIDED WITH AN INDIVIDUAL VENT UNLESS OTHERWISE NOTED. B. CONNECT ALL VENT PIPING SHOWN T EXISTING IN 0 0 D( STI G BUILDING MAIN VENT IN LO CAITON INDICATED D GATED ELEC TRIC WATER HEA TER p p " w ON PLAN. W CW 1 CW 1 CW C C. SLOPE ALL HORIZONTAL VENTS SUCH THAT WATER MAY DRAIN BACK INTO THE SANITARY SCALE: N.T.S. l. I"HW 1:...... h J"HW I I j"HW I I i"HW 1 "CW SYSTEM."CW so "HW"CW»CWkD-+l� I A. THE�MAXIMUM HOT WATER DISCHARGE TEMPERATURE SHALL NOT EXCEED 110'F, UNLESS HW I-IW 1 HW:.. \ OTHERWISE NOTED ON PLANS. B. PROVIDE ISOLATION VALVES AT THE INLET AND OUTLET OF ALL WATER HEATERS. C. PROVIDE A SEPARATE DISCONNECT SWITCH FOR ALL ELECTRIC WATER HEATERS. PLUMBING LEGEND I -v---v- HOT & COLD WATER PLUMBING PLAN : 1/4" = 11-0" NEW SANITARY WASTE PIPING NEW COLD WATER PIPING NEW HOT WATER PIPING NEW VENT PIPING POINT OF COINNECTION GLOBE SHUTOFF VALVE * TO THE BEST OF TIE ARCHITECT OR ENGINEER'S KNOWLEDGE AND BELIEF, TI4ESE PLANS AND SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING: CODE, 51I4 EDITION 2014. $ THE DRAWINGS t DESIGN ARE VALID FOR 12 MONTHS FROM DATE OF 5EMG SEALED. TO T14E BEST OF THE IWOWLEDGE OF THE ARCHITECTS OR ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH TIE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE MINIMUM FIRE SAFETY STANDARDS. ALL DIi'1E 48IONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCI.41TECT PRIOR TO COMMENCEMENT OF CONSTRUCTION. ISSUE DATE BY: REVIEW 01/15/15 PERMIT 01ASAS REV. REV. REV. REV TNEEE DOW°B M DEEIGNE, Wft =AD *0 WECFICATM AND CONCE "AID M eoLE PR MI I OF FRAM DEW NC. AND SWI NOT BE F89i0MM, FE-UND OR COPED FOR OnVt PROEM N THOLE OR PART Qi W M UWM CO *W CP FROM NUM M CHMM, AW ALL RIAn AM FEE RAW Or TEE ARCI-0W N ACCOPOA42 tM UE: COP W*ff AND PAIW LM& INABfNORI M FEI'RMCnON WU EE PROEECUMD To TEE FULL Ex w CF M Lm 0 00 00 M g o0 rq z a 00 w I:k o � M 00 r% iw. a ' 00 M 4 b w r- U a 0 w�a SWEET TITLE Hot 4 COLD WATNR PI.Ui" ID ING PLAN SWEET NUMBS HVAC EQUIPMENT TAG LEGEND ZD EQUIPMENT DESIGNATION -SEE HVAC LEGEND EQUIPMENT TAG NUMBER 2-2 AIR CONDITIONING SYSTEM NUMBER HVAC ABBREVIATION LEGEND AHU AIR HANDLING UNIT CU CONDENSING UNIT RTU ROOFTOP PACKAGED UNIT PACU PACKAGED AIR CONDITIONING UNIT EF EXHAUST FAN DH DEHUMIDIFIER VAD VENTILATION AIR DAMPER ZD ZONE DAMPER BD BALANCE DAMPER T THERMOSTAT DHC DEHUMIDIFICATION CONTROL C CO2SENSOR /CONTROLLER S SHUT DOWN SMJKE DETECTOR AF AIR FILTRATION CP CONDENSATE PUMP SA SUPPLY AIR RA RETURN AIR ODA OUTDOOR AIR MUA MAKE-UP AIR HVAC DIFFUSER TAG LEGEND DIFFUSER SIZE LISTED IN INCHES DESCRIPTION j-LENGTH x WIDTH DESCRIPTION--,,. 2464 200—DESIGN AIRFLOW C HVAC DIFFUSER DESCRIPTION 8SUPPLY Ali DIFFUSER 0— 1 WAY CEILING MOUNT SUPPLY AR DIFFUSER 2W 2 WAY CEILING MOUNT 3W SUPPLY AR DIFFUSER 3 WAY CEILING MOUNT SUPPLY AR DIFFUSER 4W 4 WAY CEILING MOUNT $W SUPPLY AR DIFFUSER SIDEWALL MOUNT LR LAY -IN RETURN DIFFUSER LAY -IN LD SUPPLY DIFFUSER 4W DIFFUSER SIZES LISTED IN INCHES LENGTH x WIDTH HVAC DIFFUSER SPECIFICATIONS SUPPLY DIFFUSER -CEILING MANUFACTURER AIRGUIDE MODEL: CBHML-(1,2,3,4)ME DESCRIPTION: WHITE ALUMINUM ADJUSTABLE CURVED BLADE WITH PARALLEL BLADE DAMPER SUPPLY DIFFUSER - LAY IN T-BAR MANUFACTURER AIRGUIDE MODEL LCD-T DESCRIPTION: WHITE ALUMINUM 4 CONE HIGH CAPACITY LAY IN DIFFUSER FOR T-BAR CEIUNIG. RETURN DIFFUSER - LAY IN T-BAR MANUFACTURER AIRGUIDE MODEL: RA-T DESCRIPTION: WHITE ALUMINUM 38' BLADE NON -FILTER BACK DIFFUSER FOR T-BAR CEILING. FLEX DUCT TO METAL DUCT CONNECTION DETAIL TAKE -OFF COLLAR FOR ROUND PIPE WITH THERMA-SEAL GASKET FLANGE & BALANCE DAMPER METAL DUCT REDUCER SHEET METAL SCREW TO PIPE. SEAL WITH 0190 SILVER TAPE & rV HANGER STRAP FOR #9 MAS"IC AIR SEALAN I FLEXIBLE DUCT(EVERY + 4' OF FLEXIBLE DUCT) V METAL HANGER STRAP AT EACH END OF ROUND METAL DUCT. CLASS 1 FLEXIBLE AIR DUCT — R-6 INSULATION CONNECT FLEX TO METAL DUCT WITH 0810 SILVER TAPE, PANDUIT STRAP, & #9 MASTIC AIR SEALANT ROUND MEAL DUCT -GALVANIZED METAL SNAPLOCK PIPE. SEAL SNAP LOCK SEAM WITH 0180 SILVER TAPE. EXTERIOR WRAPPED INSULATION SHALL BE R-6. RETURN AIR GRILL PLENUM 12'0 or Larger Ductboard Ninlm— R-4 Insulation Return Air W RETURN DUCTS 12'0 OR LARGER SHALL TERMINATE AT A PLENUM STYLE REGISTER BOX BALANCE DAMPER COLLAR Ductwork Balance Damper(BD) Collar -Crown Product) 616-D or Equal A/C DUCT WORK SPECIFICATIONS SIZE/ROUND FLEXIBLE DUCT CLASS 1 FLEXIBLE DUCT WITH SILVER VAPOR JACKET. R-VALUE 6 MANUFACTURER: ATCO MODEL SIZE/ROUND METAL DUCT ROUND GALVANIZED METAL SNAPLOCK PIPE WITH SILVER DUCT WRAP. R VALUE = 6 MANUFACTURER:CERTAINTEED SOFT TOUCH SIZEANxH DUCTBOARD RECTANGLE CERTAINTEED BLACK 'TOUGHGARD" DUCT BOARD. R-VALUE 6 ALL DUCT SIZES LISTED ON PLANS ARE INSIDE DIAMETER AND ARE LISTED IN INCHES. ADD 3' TO EACH DIMENSIOV FOR OUTSIDE DIAMETER .....Y ... ,... . _. ... _. ,. __-,.. _.._... ... _. ..i __�... _.. ... ... ._ ,. ....,_._. _.. _. ..._.,..J. _. ....._._ ____ ..-.-_.. .J .... ___,. .. ... ... .. -., .. ._._. __ _. 1 MASSAGE' ROOM X H M GE{ R E CRi R 11 r.-.,._.....__._i..._._._.._._�..+ RECEPTION/MA NkURE i i ; i PEDICURE i ` s _ .._ _ _ _. __ _. i _ ._ _ _ i _ _... _ ._ EMP4OYEE AREAoo i I i I i , i P a" —r - OFFICE DIFFUSER COORDINATION PLAN SCALE: 1/4" = 1' HVAC PLAN SCALE: 1/4" = 1' N Vent Cap with Bads Draft Damper. No Screen. ewali Exhaust .ap with Screen _utdoor Air Intake Cap with Insect Screen TYPICAL VERTICAL AIR HANDLER DETAIL GALVANIZED METAL SUPPLY AIR PLENUM WITH R-6 LINED INSULATION — FIELD INSTALLED REFRIGERANT LINE SET WITH INSULATED SUCTION LINE(MINIMUM R-3) CONDENSATE DRAIN LINE CUT-OFF SWITCH 3/4" SCHEDULE 40 PVC — WITH 1/2" TUBE INSULATION RETURN AIR 4" POURED CONCRETE VERTICAL AIR HANDLING UNIT OUTSIDE AIR DUCT 1 (VAD) VENTILATION AIR DAMPER Oro MANUAL BALANCE DAMPER GALVANIZED METAL RETURN AIR BASE PLATFORM WITH R-4 LINED INSULATION TER LOCATION CONDENSING UNIT CONCRETE SLAB MOUNTING DETAIL 1 'MINIMUM CLEARANCE: TO WALL O VAN1.25' STE=L CONDENSER TIE DOWN CLIP. 114" TEK SCREWS ANCHORED TO UNIT PER MANUFACTURER'S SPECIFICATIONS. 2' TAPCON ANCHOR TO CONCRETE SLAB. TOTAL OF 4 CLIPS. 1 PER SIDE. MANUFACTURER-BMP INDUSTRIES OR EQUAL. PRODUCT MUST BE FBC APPROVED. LEVEL 1 J 00 rn� � v/ 0) ZI-- O l() CM D U N 4 m LLJ CL U Z Z � 4< U W - r -� O m U W= 1..� E V Z o. Q •c H Jr N r m Z Q � Q H C) Q Q w O O Z j _j Z Q 0 LL W U) O J J 0 Q of Z W Q }— Z (� Z N M = Z Z) r- �- Q U) � N DATE: 07.14.15 DR. BY: RM FILE: SUZINNAILSANDSPA—M SHEET _- - --- --- -- - -- - -- - �- - - -- - - - - r n i -- - .`r+' -J ' � �' - - - - L' i I � �,.ail�r�rrL+•-.----��. �� - -- �..-+�t� �' .. ----- � �_ly�+ --: �_ �1 ( '��i1{1..11\ SPLIT AIR CONDITIONING SYSTEM SCHEDULE TOTAL CAPACITY BTUH 53,845 SENSIBLE CAPACITY BTUH 41,878 w HEATING CAPACITY BTUH(47' ODT) - } MANUFACTURER CARRIER N SEER 14.50 NOMINAL TONNAGE 5.0 DESIGNATION AHU-1 MODEL NO. FV4CNB006L z UNIT WEIGHT LB. Na z z SUPPLY AIR CFM 1,750 x OUTDOOR AIR CFM 169 w ENTERINGAIR TEMP. DB/WB 75/63 a EXTERNAL STATIC PRESS. IN. W. G. 0.7" INDOOR FAN FLA 6.8 ELECTRIC HEAT KW 8 MCA/MOCP 48.5/50 DESIGNATION CU-1 I- MODEL NO. 24ACC46OA-30 3 O UNIT WEIGHT LB. Na z COMPRESSOR R.L.A. 20.8 0 OUTDOOR FAN FLA 1.52 U OUTDOOR DESIGN TEMP. DB 95 M CA/MOCP 27.5/40 IL ELECTRIC SERVICE 2081230-1-60 1. AIR FILTERS SHALL BE FIELD INSTALLED. PROVIDE WASHABLE FILTER FOR EACH AHU LOCATED AT AHU FILTER ACCESS. FILTER BACK RETURN AIR GRILLS SHALL NOT BE USED. 2. PROVIDE (T) 5-2 PROGRAMMABLE THERMOSTAT. 3. EQUAL ALTERNATIVE MANUFACTURER IS ACCEPTABLE. 4. ALTERNATE EQUIPMENT SHALL MEET THE TOTAL AND SENSIBLE BTUh CAPACITIES OF THE A/C EQUIPMENT SPECIFIED IN THESE PLANS. 5. ALTERNATE EQUIPMENT SHALL MEET THE SEER RATING OF THE EQUIPMENT SPECIFIED. EXHAUST FAN SCHEDULE DESIGNATION EF #1 FAN TYPE CEILING DRIVE TYPE DIRECT AIR FLOW CFM 68 STATIC PRESS. IN, W.G. 0.25 ELECTRIC SERVICE 120/l/60 MAX AMPS 0.4 MANUFACTURER BROAN MODEL NO. 684 ACCESSORIES 1 1. WIRE TO LIGHT SWITCH. VENTILATION AIR CALCULATIONS ASHRAE 62.2 - CHAPTER 4 REFERENCE TABLE 4.1 OCCUPANCY CATEGORY -BEAUTY/NAIL SALON RP 25 CFM OUTDOOR AIR FLOW RATE Pz 12 OCCUPANTS Vbz 300 CFM, BREATHING ZONE OA FLOW Ez 1.0 ZONE AIR DISTRIBUTION EFFECT Voz 300 MINIMUM REQUIRED ZONE OUTDOOR AIR FLOW 'OUTSIDE AIR REQUIREMENTS ARE IN ACCORDANCE WITH FLORIDA MECHANICAL CODE 2014 AND ASHRAE 2010-62.1, VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY CO2 CONTROL SCHEDULE SYSTEM DESGINATION CO2 BRAND CO2 MODEL DESCRIPTION SYSTEM #1 C HONEYWELL C7232A1006 WALL MOUNT CO2 FOR ON DEMAND VENTILATION. DUCT MOUNT CO2 SENSOR AND CONTROLLER. WIRE TO CORRESPONDING VENTILATION AIR DAMPER(VAD). SET CO2 SENSOR TO OPEN UPON CO2 RISE AT 1000 PPM. SET CO2 SENSOR TO CLOSE UPON A CO2 DROP OF 1D0 PPM. VENTILATION AIR DAMPER SCHEDULE VENT. DAMPER BRAND MODEL CFM LOCATION DESGINATION VAD #1 HONEYWELL EARD 6 300 CFM ODA #1 NOTES: VAD #1 VAD - NORMALLY CLOSED 24V DAMPER. ON DEMAND VENTILATION FOR OCCUPANCY. WIRE VAD TO OPEN WITH CORRESPONDING CO2 SENSOR. SEE CO2 SENSOR SCHEDULE FOR SENSOR SETTINGS. HVAC NOTES: GENERAL NOTES 1. ALL WORK TO BE DONE IN ACCORDANCE WITH THESE PLANS & THE 2014 FLORIDA BUILDING CODE. 2. MECHANICAL DRAWINGS ARE SCHEMATIC IN NATURE & ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL. THE HVAC CONTRACTOR SHALL INCLUDE THE FURNISHINGS OF ALL LABOR AND MATERIALS TO COMPLETE THE AIR CONDITIONING, HEATING, AND VENTILATION SHOWN ON THE DRAWINGS TO INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING: • PERMIT FEES • ALL AIR CONDITIONING EQUIPMENT • EXHAUSTFANS • SUPPLY, RETURN, VENTILATION, & EXHAUST AIR DUCT WORK • SUPPLY AND RETURN DIFFUSERS AND REGISTERS, DAMPERS, WEATHERPROOF VENTILATION & EXHAUST LOWERS • AIR FILTRATION • THERMOSTATS, CO2 SENSORS, SHUT DOWN SWITCHES & RELATED CONTROL WIRING • EQUIPMENT SUPPORTS, HANGERS, & RACKS • CONDENSATE DRAIN PANS & PIPING • REFRIGERANT FIELD COPPER LINE SET & PIPING 3. ALL WORK SHALL BE PERFORMED BY A LICENSED HVAC CONTRACTOR CERTIFIED IN THE STATE OF FLORIDA. z 4, THE HVAC CONTRACTOR SHALL VISIT THE JOB SITE, MEET WITH RELATED TRADES, & FAMILIARIZE THEMSELVES WITH ANY AND ALL CONDITIONS RELATED TO THEIR WORK. O 5. ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED. ANY CHANGES OR DEVIATIONS FROM THESE PLANS MUST BE APPROVED BY ENGINEER OF RECORD. Q O 6. AIR CONDITIONING AND HEATING EQUIPMENT SHALL BE NOT BE SIZED BASED ON A.R.I. CAPACITY RATINGS, BUT RATHER BASED ON SPECIFIC DESIGN CONDITIONS. 7. REVISIONS OR CHANGES FROM THESE PLANS THAT MAY BE REQUIRED BECAUSE OF CONTRACTOR OPTED REVISIONS, SHALL BE COMPENSATED TO THE ENGINEER OF RECORD BY THE J b fco REQUESTING CONTRACTOR. ♦� VJ Z� SPLIT SYSTEM AIR CONDITIONING EQUIPMENT V J O LC) 1. CONDENSING UNIT SHALL BE INSTALLED AS PER SECTION 304.1 AND 304.2 OF THE 2014 FLORIDA BUILDING CODE. Q v M 2. CONDENSING UNIT SHALL BE LOCATED SLAB ON GRADE. TIE DOWN WITH FBC APPROVED HURRICANE STRAPS. m ZLL W 3. 4. CLEARANCE AROUND NON SERVICE SIDES OF THE CONDENSING UNIT SHALL COMPLY WITH MANUFACTURERS RECOMMENDATIONS AS PER MANUFACTURERS INSTALLATION INSTRUCTIONS, CLEARANCE ABOVE THE CONDENSING UNIT SHALL COMPLY WITH RECOMMENDATION AS PER MANUFACTURERS INSTALLATION INSTRUCTIONS. U MANUFACTURERS c�Op 5. AIR HANDLERS SHALL BE INSTALLED AS PER MANUFACTURERS INSTALLATION INSTRUCTIONS AND THE 2014 FLORIDA BUILDING CODE. z -c 6. THE AIR HANDLER SHALL INCORPORATE A FILTER HOUSING WITH EASY ACCESS. THE FILTER COMPARTMENT SHALL NOT BE OBSTRUCTED IN ANY WAY BY THE REFRIGERANT PIPING, a Z / ) �/5 j CONDENSATE PIPING, ORANY OTHER ITEM WHICH MAY PREVENT REMOVAL AND INSTALLATION OF THE FILTER. � co 7. FILTERS SHALL BE LOCATED AT THE AIR HANDLER DIRECTLY BEFORE THE EVAPORATOR COIL. NO FILTER BACK GRILLS SHALL BE USED. V_ 11 ` (p 8. CLEARANCE AROUND THE AIR HANDLER SHALL BE 4" FOR NON -SERVICE SIDES AND 36' FOR SERVICE SIDE. tY 0 M r` -D > O �/� m L.L CONDENSATE DISPOSAL U W C 1. CONDENSATE DISPOSAL SHALL BE PROVIDED FOR EQUIPMENT AND APPLIANCES CONTAINING EVAPORATOR COILS. E 2. CONDENSATE DRAIN SYSTEM SHALL BE DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SECTIONS 307.2.1 THROUGH 307.2.4 OF THE 2014 FLORIDA BUILDING CODE. (D Q 3. ALL PRIMARY CONDENSATE PIPING LOCATED WITHIN THE INSIDE OF THE BUILDING SHALL BE INSULATED TO PREVENT CONDENSATION FROM FORMING ON THE EXTERIOR OF THE DRAIN z cl) LINE. 4. MAIN AND EMERGENCY CONDENSATE DRAIN LINES SHALL BE SCHEDULE 40 PVC. .� ~ 5. AUXILIARY DRAIN LINE CONNECTION AT THE EVAPORATOR DRAIN PAN SHALL INCORPORATE AN SAFETY CUT-OFF SWITCH. 6. AIR HANDLERS SHALL INCORPORATE AN EMERGENCY DRAIN PAN THAT IS PIPED TO A CONSPICUOUS LOCATION AT THE EXTERIOR OF THE BUILDING OR INCORPORATES A SAFETY CUT-OFF iV SWITCH. 7. SLOPE HORIZONTAL CONDENSATE DRAINS A MINIMUM OF 1/4" PER FOOT. co 8. CONDENSATE SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO A STREET, SIDEWALK, OR ANY OTHER LOCATION AS TO CAUSE A NUISANCE. IF NO APPROVED LOCATION IS AVAILABLE, THEN A DRY WELL SHALL BE INSTALLED. 9. ALL DRAIN LINES SHALL BE PROVED AND TESTED UPON EQUIPMENT START-UP. 10. ALL DRAIN LINE AND DRAIN PAN SAFETY CUT OFF CONTROLS SHALL BE TESTED UPON EQUIPMENT START-UP. DUCTWORK 1. DUCT CONSTRUCTION AND INSTALLATION SHALL COMPLY WITH SECTION M603 OF THE 2014 FLORIDA BUILDING CODE. 2. AIR CONDITIONING DUCT SYSTEM MATERIALS SHALL BE BASED ON THE FOLLOWING: • FLEXIBLE DUCT WORK - BRAND - ATCO #036 / UL 181, CLASS 1 AIR DUCT WITH REINFORCED METALLIZED POLYESTER JACKET WITH WIRE HELIX ENFORCED AIR TIGHT INNER LINER. INSULATION SHALL BE R-6. • ROUND METAL DUCT WORK - CROWN #101 SNAPLOCK ROUND PIPE. DUCT SIZE 14"0 OR LESS SHALL BE 30 GAUGE MINIMUM. DUCT SIZE OVER 14"0 SHALL BE 28 GAUGE MINIMUM. DUCT SHALL BE INSULATED WITH CERTAINTEED EXTERIOR WRAP WITH R-6 INSULATION & VAPOR RETARD FACING, • INSULATION VALUE SHALL BE R-6. • RECTANGLE DUCT - CERTAINTEED BLACK TOUGHGARD. UL 181 / CLASS 1 DUCT BOARD WITH BLACK MAT FACING AND VAPOR RETARD FACING. THE AIR STREAM SURFACE CONTAINS AN EPA REGISTERED ANTI -MICROBIAL AGENT IN ORDER TO REDUCE THE POTENTIAL OF MICRO GROWTH ON THIS PRODUCT. • INSULATION VALUE SHALL BE R-6. 3. ALL DUCT SIZES LISTED ARE NET INSIDE DIMENSIONS. Q Q 4. ALL DUCTS AND PLENUMS SHALL BE MADE AIR TIGHT. DUCT WORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE CURRENT EDITION OF CHAPTER 13 OF THE 2014 Z < a. Q FLORIDA BUILDING CODE. O_ 5. DUCT LEAKAGE SHALL NOT EXCEED 5% OF THE RATED AIR HANDLER FLOW.- �+ 6. BRANCH DUCT RUN -OUTS SHALL HAVE A MANUAL BALANCE DAMPER AT THE CONNECTION TO THE MAIN TRUNK LINE. DAMPER SHALL BE HAVE AN INDICATOR FLAG ATTACHED TO THE \ Q w O DAMPER FOR EASY IDENTIFICATION. / Z 7. FLEXIBLE DUCT SHALL BE EXTENDED TO ITS FULL LENGTH. EXCESS DUCT MATERIAL IN A RUN SHALL BE LESS THAN 5%. Z 8. FLEXIBLE DUCT SHALL BE SUPPORTED AT MANUFACTURERS RECOMMENDED INTERVALS, BUT AT NO GREATER DISTANCE THAN 4 FEET. MAXIMUM PERMISSIBLE SAG IS 1/2" PER FOOT OF W ♦ O I _ SPACING BETWEEN SUPPORTS. � V / U) 9. FIRE DAMPERS SHALL BE INSTALLED INSTALLED IN ACCORDANCE WITH SECTION 716 OF THE 2014 FLORIDA BUILDING CODE. N W J 10. DUCTS AND TRANSFER OPENINGS THAT PENETRATE FIRE RESITANT-RATED ASSEMBLIES AND ARE NOT REQUIRED BY THIS SECTION TO HAVE DAMPERS, SHALL COMPLY WITH THE 0 REQUIREMENTS OF SECTION 712 OF THE 2014 FLORIDA BUILDING CODE. �-/ J 11. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH SECTION M606 OF 2014 FLORIDA BUILDING CODE. Lu L.L Q �- Z_ (� �■ Z N or Z - r a - AIR REGISTERS BOXES AND DIFFUSERS Q C7 W N 1. REFER TO DIFFUSER LEGEND FOR MANUFACTURER TYPE AND MODEL. ALTERNATE DIFFUSERS MUST BE APPROVED BY ENGINEER OF RECORD. 2. DIFFUSER LOCATIONS ARE FOR GENERAL REFERENCE. FIELD VERIFY DIFFUSER LOCATIONS AND COORDINATE WITH CEILING LIGHTING AND INTERIOR CEILING ELEVATIONS. OUTDOOR AIR & EXHAUST AIR SYSTEMS 1. ALL EXHAUST DUCTS SHALL TERMINATE TO EXTERIOR ROOF CAP, SIDEWALL CAP, OR SOFFIT HOOD AS INDICATED ON THE HVAC PLANS. 2. EXHAUST FANS SHALL HAVE BACK DRAFT DAMPER INSTALLED, 3. OUTDOOR AIR DUCT SHALL BE CONNECTED TO THE RETURN SIDE OF THE AIR STREAM AT THE RETURN AIR PLENUM. 4. OUTDOOR AIR DUCT SHALL INCORPORATE A MANUAL VOLUME BALANCE DAMPER AT THE RETURN AIR PLENUM FOR INTAKE BALANCE. 5. OUTDOOR AIR SHALL INCORPORATE A NORMALLY CLOSED (24V) DAMPER(VAD). 6. WIRE VAD TO CO2 SENSOR. 7. VAD SHALL OPEN ON CO2 RISE. VAD SHALL CLOSE ON CO2 FALL. 8. SEE CO2 SENSOR SCHEDULE FOR SETTINGS. 9. OUTDOOR AIR INTAKES SHALL HAVE INSECT SCREEN AT INTAKE CAP. DATE: 07.14.15 10. KEEP ALL VENTILATION AIR INTAKES A MINIMUM 10' FROM EXHAUST FAN TERMINATION POINTS AND SANITARY SEWER VENT OUTLETS. DR. BY: RM FILE: SUZINNAILSANDSPA-M SHEET .;, M-2' U�