Loading...
HomeMy WebLinkAbout38235 C Ave (2)L i i = E12-:1, r RIM rr , �r lip —_ ad��Dq 17 Zr a Qo z7O�o a � Q o Ada a aaa va Joao Ada o 7 a a o 0 0. LOIN/DR. HC-rT_ 0 21 4' 0 21 41 IN _ A, N A, A u N TABLE 1405.2 MINIMUM THICKNESS OF WEATHER COVERINGS COVERING TYPE MINIMUM THICKNESS (inches) Adhered masonry veneer .025 Aluminum siding 0.019 Anchored masonry veneer 2.625 Asbestos -cement boards 0,125 Asbestos shingles 0.156 Cold -rolled copper 0.0216 nominal Copper shinglesd 0.0162 nominal Exterior plywood (with sheathing) 0.313 Exterior plywood (without sheathing) See Section 2304.6 (HVHZ, see Section 2322) Fiber cement lap siding 0.25 c Fiber cement panel siding 0.25 c Fiberboard siding 05 Class -fiber reinforced concrete panels .375 Hardboard siding c .025 High -yield copperd 0.0162 nominal Lead --coated copperd 0.0216 nominal Lead -coated high -yield copper 0.0162 nominal Marble slabs 1 Particleboard (with sheathing) See Section 2304.6 (HVHZ, see Section 2315. 1. 11) Particleboard (without sheathing) See Section 2304.6 (HVHZ, see Section 2315. 1. 11) Porcelain Tile 0.025 Precast stone facing 0.625 Steel (approved corrosion resistant) 0.0149 Stone (cast. artificial anchored) 1.5 Stone (natural) 2 Structural glass .344 Stucco or exterior Portland cement. plaster Three -coat work over: Metal plaster base 0.875 b nominal Unit masonry 0.625 b nominal Cast -in -place or precast concrete 0.625 b nominal Two -coat work over: Unit masonry 0.5 b nominal Cast -in -place or precast concrete 0.375 b nominal Terra Gotta (anchored) 1 Terra Gotta (adhered) 0.25 Vinyl siding 0.035 Wood shingles 0.375 Wood siding (without sheathing) 0.5 For SI: 1 inch - 25.4 mm. a. Wood siding of thicknesses less than 0.5 inch shall be placed over sheathing that. conforms to Section 2304.6. (HVHZ, see Section 2322) b. Exclusive of texture. c. As measured at the bottom of decorative grooves. d. 16 ounces per square foot for cold -rolled copper and lead -coated copper,12 ounces per square foot for copper shingles, high -yield copper and leadcoat.ed high -yield copper. SECTION R704 INSPECTION FOR TERMITES In order to provide for inspection for termite infestation, clearance between exterior wall coverings and final earth grade on the exterior of a building shall not be less than 6 inches (152 mm). Except. i ons: 1. Paint or decorative cementitious finish less than 8 inch (17.1 [Tim) thick adhered directly to the masonry foundation sidewall. 2. Access or vehicle ramps which rise to the interior finish floor elevation for the width of such ramps only. 3. A 4-inch (102 mm) inspection space above patio and garage slabs and entry areas. 4. If the patio has been soil treated for termites, the finish elevation may match the building interior finish floor elevations on masonry construction only. 5. Masonry veneers constructed in accordance with Section R318.4. 1/4" TOOLED JOINT SMOOTH FINISH - HANDS CEMENT TEXTURES) FINISH ROUGH FIN15! TOOLED 5AND DETAIL N.T.S. e lw99 yytt t.�`� ..S lI y I 1/ Ng �� E b�,r�i AAi l S .! Y If 11 b 1 j I OR ,NA01-`�`:: m . Sk"11'iv{ •'dcd1cI.I 1 In' 11P i•i Thomas L Digitally signed by u�inginiIlr ii.l I t 1 !i Thomas t Pimtcd E ad thi 1 1 11 nt Hanson:A01410 Hanson:A01410D00000 a,not cmwd�i d I"'mdanl �r 3 177EF31134E000015ADA �ta,le•li ul t th sii n'Itu nr nu. I D00000177EF31 Date:2022.04.12 L B4E000015ADA 14:39:31-04'00' 'rf c O r� V C_ U) W C �i of U N O CN Z C� Elf 1 o U I B � `s J, ire z LL I \ 1 k R -r-ir-i IROOF PLAN TABLE 1609. 6(1) NOMINAL (ASD) GARAGE DOOR AND ROLLING DOOR WIND LOADS FOR A BUILDING WITH A MEAN ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE B (PSF) 1, 2, 3, 4, 5 ULTIMATE DESIGN WIND (%it)DETERMINED IN ACCORDANCE WITH SECTION 1609.3 (MPH - 3 SECOND GUST) Width (ft) Height (Ft) 100 MPH 110 MPH 120 MPH 130 MPH 140 MPH 150 MPH 160 MPH 170 MPH ISO MPH 190 MPH 200 MPH Roof Angle 0 - 10 degrees 8 8 +10. 0 -10, 0 -10. 5 -1 1. 9+ 12. 5 -14. 2 +14. 7 -16. 6 +17. 1 -19. 3 +19. 6 -22. 2 +22. 3 -25. 2 +25. 1 -28. 5 +28. 2 -31_ 9 +31. 4 -35. 5 +34. 8 -39. 4 10 10 +10. 0 -10. 0 +10. 2 -11, 4 +12. 1 -13. 6 +14. 2 -16. 0 +16. 5-18. 5 +18. 9 -21. 2 +21. 5 -24. 2 +24. 3 -27. 3 +27. 3 -30. 6 +30. 4 -34. 1 +33. 7 -37. 8 14 14 +10. 0 -10_ 0 +10. 0 -10, 8 +1 i. 5 _12. 8 +13. 5 -15. 0 +15. 7 -17. 4 +18. 0 -20. 0 +20. 5 -22. 8 +23. 1 -25. 7 -1-25. 9 -28. 8 i-28. 9 -32. 1 +32. 0 -35. 6 Roof Angle 0 > 10 degrees 9 1 7 I +10. 0 -10. 9 +11. 4 -12. 9 t 13. 7 15. 5 +16. 1 -18. 2 +18. 5 -20. 9 +21. 3 -24. 1 +24. 3 -27. 5 +27. 6� 31. 2 +30. 6 -34-. 6 +34. 2 -38. 6 +38. 0 -43. 0 16 7 I +10. 0 -10. 3 +10. 9 -12. 2+ 13. 1 14. 6 -15. 5 -17. 2 +17. 7 -19. 7 +20. 4 -22. 7 +23. 3 -26. 0 +26. 4 f 29. 4 +29. 3 -32. 6 +36. 4 -40, 5 78 MPH 85 MPH 93 MPH 101 MPH 108 MPH 116 MPH 124 MPH 132 MPH 139 MPH 147 MPH 155 MPH or Si: 1 foot = 304.8 mm, 1 mile per hour = 1.609 km/h, 1 psf = 47. 88 N/m2. Nominal Design Wind Speed ('Vosd) converted from Ultimate Design Wind Speed per Section 1609.3.1 '. o dco sizes or wind speeds between thr)se given above the load may be interpolated, otherwise use the ].odd associated with the lower door size. 2 lo,.,: .c es shall be adjusted for height and exposure by multiplying by the adjustment coefficient in table 1609.6(2). minirnurn positive wind load si.all b� 10 psf and minimum r!,;gative wind load shall be 10 psf. Pr a minus signs signify pressures acting toward and away from the building surfaces. l Ki,. , -, oIc I I I-o ..cc I ,mom, 'l-,.- k"c- 7 T�-i ,4 ..,,,fi t t- ,., k , , ; l,-l;,-v, --A S Tn-,I- --1 ,-, ;--I„A. + k o 0 r, 1.,.,4 .-ill,,.-+F„"+.,- ATTIC VENTILATION - FLORIDA BUILDING CODE Total Area Under Roof 1,024.00 Square Feet (SF) Total Required Ventilation 6.83 SF Total Area / 150 Area Total Required Ventilation 3.41 SF Reqd Area / 2 Area at Soffits Total Required Ventilation 3.41 SF Reqd Area / 2 Area at Roof Overhang Dimension 1,33 Feet Ventilation Examples -Owens Corning Ventilation Required At Soffit Units Units Ca acit Vent Triple 4" Center Vent 1.56 sq in / ft 315.08 Feet Triple 4" Full Vent 4.68 sq in / ft 105.03 Feet Double 5" Full Vent 4.25 sq in / ft 115.65 Feet Ventilation Required At Roof Units Units Capacity Vent Ventsure Metal Dame with Screen 144 sq in 4 Vents Ventsure High Profile Slant Back Roof Vent w/ 50 sq in 10 Vents Exterior Louver Ventsure Plastic Slant Back Roof Vent w / 61 sq in 9 Vents Interior Louver Ventsure Rigid Strip Ridge Vent, Externally 15 sq in / ft 33 Feet Baffled Truss Systems Ene -Ineer lne by others TRUSS MANUr- ACTURER TO PROVIDE SIGNED AND SEALED TRUSS DRAWINGS INCLUDING BRACING DETAILS, WIND DESIGN INI'OfIZ-1ATION I. Wind Speeds of 13e 1"iPH Vult 4 100 MPH Vaeb 2, Risk Category = II 3. Exposure Category B 4, Enclosed Building, (ecpi = +I- 0.18) 5, Component 4 Cladding Pressures (PSF): R = 31.2,-40.0 W = 33.2,-43.4 OH= -55.6 NOTE: WIND LOAD CALCULATION5 ARE EASED ON WORST CASE' . ALL CONNECTORS WILL BE UNIFORM FOR SIMILAR USES. THIS STRUCTURE HAS BEEN DESIGNED TO WITHSTAND INTERNAL PRESSURES, ENCLOeED BUILDING. I! ill1l1- 1112[agwoll,16'21 Ztlel[ll��► I. This C:Garage is to the ith Edition (2020) FEBC (Florida Bullding Code) type construction requirements. Construction shall comply with local County and state agenclee. 2. All openings around walls, partitions, pipes, ducts, conduits etc.-, shall be sealed fully and sound proofed with sealants of type for application. 3. Painting- All surfaces shall be properly prepared and cured to manufacturer's Instruction prior to painting. Paint shall be ''first line'' produced by PORTER, SNERWIN WILLIAMS, or equal with colors selected by the owner. All painted surfaces shall be painted with materials appropriate for the application in a workmanship manner to the paint manufacturer's instruction. 4. Caulk all exposed joints. Clean, prime, caulk and seal all joints between door and window frames with DOW CORNING silicon of type for application. Use foam back-up rods as required at wide joints. Use acoustical foam sealants by DAP or TREMCO at sound proofing applications at openings or cracks. 5. Energy Code - These plans where designed with common design practices. However, this does not guarantee that this plan will pass the "Florida Energy Code". These plans shall be reviewed by a proper HVAC professional and shall pass the "Florida Energy Code" or recommendations From such Professional shall be provided to the Home Designer (Corner Stone Design Group, Inc.) so as to meet such requirements. 2319. 17. 1. 2 Where a ceiling is to be attached directly to the underside of trusses, the trusses shall be laterally braced with continuous 1-inch by 4-inch (25 mm by 102 mm) members nailed with 8d common nails to the upper side of the bottom chord at panel points but not to exceed 10 feet (3 m) apart. This lateral bracing shall be restrained at each end and at 20-foot (6 m) intervals. Drywall may be considered a rigid ceiling in enclosed areas where it is protected from the elements. The drywall ceiling is not to be considered a ceiling diaphragm. TOP/BOTTOM CHORD GABLE END BRACING @ 48" C. C. MAX FOR THE FIRST 4 ROWS OF TRUSSES n t r C CONT. BOTTOM CHORD BRACING (1"x4" MIN. ) @ 10' -0" MAX. SEE TRUSS SYSTEM ENGINEERING DRAWINGS FOR ANY ADDITIONAL BRACING OR CROSS BRACING REQUIREMENTS 1 . L 2 4 " O.G. I (2) 166 NAILS 2x4 DIAG. BRACE (FOLLOW TRUSS RS MANUFACTURERS RECOMMENDATION (2) 16d NAILS \ "L" 5RAGE C�451_E END TRUSS /2X4xa LATERAL t31RACINIG GONTINOU5 9 40" O.C. (5) 16d NAILS GABLE D DIAGONAL BRACE DA"' signe 1 anal'clieJ I", I I I l ul�om III t h i ThomasDigitally signed by Tin,,.,nititill `;itg'!l.vr-!clI1,t,l„tr Thomas L III ill!Cd r„ric. „f thi' d(l,11mrn! Hanson:A01 41 0 ill,, ""i ""'�i`I",d ti,gned �,nd Hdnson:A01410D00000 �rnl<<1 an�i (hc �i nllurc-uu�! hr � �� D00000177EF31 177EF31134E000015ADA pli1i"d,,,,-11, ,1,.I!,,,,,; „ Date: 2022.04.12 b4E0000 15) DA 14:33:53-04'00' N O N 0 PROJECT 0 __D_00FZ ecHr=D"IE, OUT eu)IN 0O 15 ;BOOR FR ,4ME r 3L OCK D: SCRPT ION 71 _868 ---- - - - 3068 ROUGH OPENING 34" x 80 7/8" 38" x 80 7/8 ROUGH -37" x 8: 3 '8" -- 41 x 82 3/8" 3068 w/ NGLE 1068 LIGHT _ - - ( 51 1/2" x 80 7/8" 54 1/2" Y, 82 .3/8" 3068 w DOUBL.E 1068 ICHT i L - I 65" x 7 80 8" x 68' 82 3 8" 6068 75" x 80 7/8" 78" x 82 3/8" 2880 34" x 96 7/8" 37" x 98 1/2" 30800 3080 wl SING _E 1G8G LIGHT _ 3C80 w/ DOUBLE 1080 LIGHTS 6080 �w'" 6080 .,i DOUBLE 1180 LIGHTS 28 x 96 7/8" 96 7 _5i 1 2" x 8 65" x 96 7/8" 75" x 96 7/8� 102 1/4" x 96 7/8' 41 x 93 1121, x 54 1 /2 _ a 8 1/2" 64" x 98 1/2" y8" x 98 1 /2" 105 1/4_ x 98 1/2" 6080 w/ DOUBLE 3080 LIGHTS J 6080 w/ DOUBL: 2880 LIGHTS 6080 w/ DOUBLE 1280 LIGHTS 150 1/4_- x 96 7/8" 142 1/4" x 96 7/8" 69" x 96 7/8'. -153 1/4" k 98 1/2 145 1/4" x 98 1/2" 72" x 98 1/2" NOTE_ THE ABOVE )OOR CHART FITS MOST DOOR MANUFACTURERS DOORS HOWEVER THE CONTRACTOR SHALL VERIFY WITH CHARTS / DOCUMENTATION PROVIDED WITH SPECIFIC DOOR MANUFACTURER, 'UINi70UJ iOldC�i� tii��NINC� �I�;AR"i- __ _ - BLOCK CONSTRUCTION FRAME CONSTRUCTION WINDOW (1/2" FLANGE) -- (Ii2" FLANGE) CODE --- --- WII3TH HEIGHT WIDTH HEIGHT 12 SH 13 SH -I} 19 7/8",. x _-_ 20"_ 19 7/8"" x 38 3� 19 1/4„_---x 26 1/4" t9 1/4" _38 x 5 14 S _ 19 7/8"i; x- 5D 5/8" _ 19 7/4x 50 7/8" 15 SH - 19 7/8" x 63" 19 1/4 x 63 1/4" 16 SH 19 7/8"" x 76 4 19 1/4 x _ 76 3 4" H32 S'-i 27 1/4" x 26" 26 5/8" x 26 1/4� 1133_SH 1-1-135 27 1/4" x 35 1/4" 26 5/8' x 38 5/8'_I H34 SH 27 1/4" x NOW 26 5/8"_ x - 50_2�8" SH 27 1/4" x _ 83" 26 5/8" x_ _ 631Z4" -H36 SH 27 1/4" x _ 76 3 4" 26 5/8" x--__.76 3 4" 22 SH 37 3 4" x 26" 37 1 8" x 26IZ4" 23 SH 37 3/4" x 38 1/4" 37 / 38 5/8" 24 SH 3 3 4" x 50 5/8"_ _ 37 1�x 50 7/8" 2WE SH _ 37 3 4" x 56" �37_V8" --- x _ 56 1/4" 25 SH 37 3/4" x 63" _ 37 1/8" x 63 1/4" 266 SH 37 3/4" x 76 3 4" 37 1/8" x _ 76 3 4" 32 SH 53 7/8" x 26" --- i 53 1/4" x 26 1/4" ----- 33 SH 1--5 3 7/8" x 38 1/4" 53 1/4" x 38 5/8" _34 SH - L53 7/8" x 50 5/8" 53 1/450 7/8" I 3WE Si 53 !_ " 7 8" x 56 / _x -_-_.- " 53 1 4_ / x 56 1/4" _I 35 SFt +53 7/8" x 63" 53 1/4" x 63 1/4" 36 SH i 53 7/8" x -_ 76 3 d" 53 1/4" x ( 2) 22 SP' s (2) 32 SH' s ( 2) 23 SH' s 74 3/4" x 2C _ _ _1 107" x 26" 74 3 4" x 38 1/4 CHECK WITH MANUF. HEE CK WITH MANUF CH C4E WITH MANUF. (2) 33 SH's 107" x 38 1/4"__I CHECK WITH MANUF. (2) 24 SH' s 74 3 4" x 50 5/8" CHECK WITH MANUF. (2) 34 SH's 107" x 50 5/8" CHECK WITH MANUF_. (2) 25 SH's 74 3 4" x 63' CHECK WITH_ MANUF.____ I(2) 35 SH's _ 107" _ x 63" CHECK WITH MANUF. *NOTE: THE ABOVE WINDOW CHART FITS MOST WINDOW MANUFACTURERS WINDOWS HOWEVER THE CONTRACTOR SHALL VERIFY WITH CHARTS / DOCUMENTATION PROVIDED WITH SPECIFIC WINDOW MANUFACTURER- tt m I 2'-4" 1< 115'-0" ALL INTERIOR DIMENSIONS ARE GIVEN TO THE INDICATED CENTER OF THE STUD UNLESS NOTED OTHERWISE. ALL EXTERIOR DIMENSIONS ARE GIVEN TO E THE FACE OF THE STUD OR FACE OF BLOCK (AS APPROPRIATE) WHICH LINES WITH THE FOUNDATION BELOW. ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED OR APPROVED CEDAR, OR HAVE 15 LB. FELT BARRIER. SEE SHEETS - S1, S2 AND ADDITIONAL "S" SHEETS FOR ADDITIONAL STRUCTURAL DETAILS / NOTES R602.1 GENERAL. WOOD AND WOOD -BASED PRODUCTS USED F - - I ORLOAD SUPPORTING PURPOSES SHALL CONFORM TO THE APPLICABLE PRO -VISIONS OF THIS SECTION. R602.1.1 SAWN LUMBER. SAWN LUMBER SHALL BE IDENTIFIEDBY A GRADE MARK OF AN ACCREDITED LUMBER GRADING ORINSPECTION AGENCY AND HAVE DESIGN VALUES CERTIFIED BY ANACCREDITATION BODY THAT COMPLIES WITH DOC PS 20. IN LIEUOF A GRADE MARK, A CERTIFICATION OF INSPECTION ISSUED BY ALUMBER GRADING OR INSPECTION AGENCY MEETING THE REQUIRE-MENTS OF THIS SECTION SHALL BE ACCEPTED. R602.1.2 END -JOINTED LUMBER. APPROVED END-JOINTEDLUMBER IDENTIFIED BY A GRADE MARK CONFORMING TO SECTIONR602.1 SHALL BE PERMITTED TO BE USED INTERCHANGEABLY WITHSOLID-SAWN MEMBERS OF THE SAME SPECIES AND GRADE. END -JOINTED LUMBER USED IN AN ASSEMBLY REQUIRED ELSEWHERE INTHIS CODE TO HAVE A FIRE -RESISTANCE RATING SHALL HAVE THE DES-IGNATION "HEAT RESISTANT ADHESIVE" OR "HRA" INCLUDED INITS GRADE MARK. R602.1.3 STRUCTURAL GLUED -LAMINATED TIMBERS. GLUED -LAMINATED TIMBERS SHALL BE MANUFACTURED AND IDENTIFIED ASREQUIRED IN ANSI/AITC A190.1 AND ASTM D3737. R502.1.4 STRUCTURAL LOG MEMBERS. STRUCTURAL LOG MEM-BERS SHALL COMPLY WITH THE PROVISIONS OF ICC 400. R602.1.5 STRUCTURAL COMPOSITE LUMBER. STRUCTURALCAPACITIES FOR STRUCTURAL COMPOSITE LUMBER SHALL BE ESTAB-LISHED AND MONITORED IN ACCORDANCE WITH ASTM D5456. R602.1.6 CROSS -LAMINATED TIMBER. CROSS -LAMINATED TIM-BER SHALL BE MANUFACTURED AND IDENTIFIED AS REQUIRED BYANSI/APA ERG 320. R602.1.7 ENGINEERED WOOD RIM BOARD. ENGINEERED WOODRIM BOARDS SHALL CONFORM TO ANSI/APA ERR 410 OR SHALLBE EVALUATED IN ACCORDANCE WITH ASTM D7672. STRUCTURALCAPACITIES SHALL BE IN ACCORDANCE WITH EITHER ANSI/APAPRR 410 OR ESTABLISHED IN ACCORDANCE WITH ASTM D7672.RIM BOARDS CONFORMING TO ANSI/APA PRR 410 SHALL BEMARKED IN ACCORDANCE WITH THAT STANDARD. 32'-0" -4" I. 8'-0" I T-4" R602.1 GENERAL. WOOD AND WOOD -BASED PRODUCTS USED FORL..OAD-SUPPORTING PURPOSES SHALL CONFORM TO THE APPLICABLE PRO --VISIONS OF THIS SECTION. R602.1.8 WOOD STRUCTURAL PANELS. WOOD STRUCTURAL PANELSHEATHING SHALL CONFORM TO DOC PS 1, DOC PS 2 OR, Nd,H ENMANtJFACTURED IN CANADA, CSA 0437 OR CSA 0325. PA JtLSSrIALL BE IDENTIFIED NT ED OR F GRADE, BOND CLASSIFICATION, AND PER-FORMANCE CATEGORY BY A GRADE MARK OR CERTIFICATE ORINSPECTION ISSUED BY AN APPROVED AGENCY. R602. 1. 9 PARTICLEBOARD. PARTICLEBOARD SHALL CONFORM TOANSI A208.1. PARTICLEBOARD SHALL BE IDENTIFIED BY THEGRADE MARK OR CERTIFICATE OF INSPECTION ISSUED BY ANAPPROVED AGENCY. R602.1.10 FIBERBOARD. FIBERBOARD SHALL CONFORM TOASTM C208. FIBERBOARD SHEATHING, WHERE USED STRUCTUR-ALLY, SHALL BE IDENTIFIED BY AN APPROVED AGENCY AS CON -FORMING TO ASTM C208. P,602.2 GRADE. STUDS SHALL BE A MINIMUM NO. 3, STANDARD ORSTUD GRADE LUMBER. EXCEPTION: BEARING STUDS NOT SUPPORTING FLOORS AND NON -BEARING STUDS SHALL BE PERMITTED TO BE UTILITY GRADE I_.UMBER,PROVIDED THE STUDS ARE SPACED IN ACCORDANCE WITH TABLER602.3(5), R602.3 DESIGN AND CONSTRUCTION. EXTERIOR WALLS OF WOOD -FRAME. CONSTRUCTION SHALL BE DESIGNED AND CONSTRUCTED WITH INACCORDANC E HE PROVISIONS OF THIS T T CHAPTER ,AND FIGURESR602.3(1) AND R602.3(2), OR IN ACCORDANCE WITH AWC NDS.COMPONENTS OF EXTERIOR WALLS SHALL_ BE FASTENED IN ACCORDANCEWITH TABLES R602.3(1) THROUGH 13602.3(4). WALL SHEATHINGSHALL BE FASTENED DIRECTLY TO FRAMING MEMBERS AND, WHEREPLACED ON THE EXTERIOR SIDE OF AN EXTERIOR WALL, SHALL BE CAPA-BLE OF RESISTING THE WIND PRESSURES LISTED IN TABLE R301.2(2)ADJUSTED FOR HEIGHT AND EXPOSURE USING TABLE R301. 2( 3) ANDSI-TALL CONFORM TO THE REQUIREMENTS OF TABLE R602.3(3). WALLSHEATHING USED ONLY FOR EXTERIOR WALL COVERING PURPOSES SHALLCOMPLY WITH SECTION R703. STUDS SHALL BE CONTINUOUS FROM SUPPORT AT THE SOLE PLATE TO ASUPPORT AT THE TOP PLATE TO RESIST LOADS PERPENDICULAR 10 THEWALL. THE SUPPORT SHALL BE A FOUNDATION OR FLOOR, CEILING ORROOF DIAPHRAGM OR SHALL BE DESIGNED IN ACCORDANCE WITHACCEPTED ENGINEERING PRACTICE. EXCEPTION: JACK STUDS, TRIMMER STUDS AND CRIPPLE STUDS ATOPENINGS IN WALLS THAT COMPLY WITH TABLES R602.7(1) ANDR602. 7(2) . C 4R4 iE: 102.4 SF LE�END DOOR 51ZE FEET (HGT. (o'-8" UNLESS NOTED OTHERWI5E) DOOR 51ZE INCHES 0 PH EPiRE-HUNC:r (PH) or WRAP (W) or POCKET (PKT) WINDOW 51ZE 3� 5N PLATE HCzT. a 10'-0" A.F.F. ® BEARING WALL ALL CMU WALLS CONSIDERED SHEAR WALL CELL POURED 50LID W/ (I/*5 FROM FTG. TO BOND BEAM LOAD SUMMARY DESCRIPTION kVA GENERAL LIGHTING' 1024 Sq. Ft. @ 3 Watts per Sq. Ft = ' 3.1 First 10 kW @ 100% = 10.0 Remainder at 35% -10.0 kw x .35 _ -3.50 HEATING - _ 1-AH w/Heat = 6.8 1-HP _ 6.7 TOTAL CALCULATED 20.0 Calculated load for service size IE 20.0 kW divided by 230V = 87.0 Amps Amps 100A SERVICE. ------E Lo IS LZ A N ELECTRICAL sllr�BOLS LEGEND " CEILING LIGHT ® 200 AMP. PANEL Q TELEVISION PRE -WIRE J -{r} 4 RECESSED CAN LIGHT -'--------e r-------- SHOP FLUORESCENT LIGHT SZ TELEPHONE PRE -WIRE 110V DUPLEX RECEPTACLE f -------' 2'X 4' FLUORESCENT (1s, SMOKE ALARM CARBON MONOXIDE 220V OUTLET I LIGHT DETECT OR IF IIOV GP.I.. OUTLET TRACK LIGHTING JUNCTION BOX SWITCHED DUPLEX 4 PU5H BUTTON REC. A I HT BEAUTY BR LIGHT TCJ E CHIMES, Epbppbp�7 OUTLET (HWH, AH, ETC.) _ \\\� "N FLOOD LIGHT $ SINGLE POLE SWITCH d BRACE ! DOOR BELL CHIME $3 11 THREE WAY LIGHT SWITCH 1 / PRE -WIRE FOR FAN � ELECTRICAL WIRING V 1 GARAGE DOOR OPENER � i r 1 L J EXHAUST FAN O LIGHT/EX, FAN INTERIOR ELECTR IC4L OUTLET LOC147I ON PADDLE FAN SWITCH (LOCATE OVER FAN LIGHT SWITCH) LIGHT SWITCH DUPLEX OUTLET AT KITCHEN COUNTER, REFRIG., WASHER AND GARAGE OUTLETS DUPLEX OUTLET AT o VANITY COUNTER 0 STANDARD DUPLEX OUTLET 0 0 250.94 BONDING FOR OTHER SYSTEMS. AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES. THE INTERSYSTEM BONDING TERMINATION SHALL BE ACCESSIBLE FOR CONNECTION AND INSPECTION. THE INTERSYSTEM BONDING TERMINATION SHALL HAVE THE CAPACITY FOR CONNECTION OF NOT LESS THAN THREE INTERSYSTEM BONDING CONDUCTORS. THE INTERSYSTEM BONDING TERMINATION DEVICE SHALL NOT INTERFERE WITH OPENING A SERVICE OR METERING EQUIPMENT ENCLOSURE, THE INTERSYSTEM BONDING TERMINATION SHALL BE ONE OF THE FOLLOWING: (1) A SET OF TERMINALS SECURELY MOUNTED TO THE METER ENCLOSURE AND ELECTRICALLY CONNECTED TO THE METER ENCLOSURE. THE TERMINALS SHALL BE LISTED AS GROUNDING AND BONDING EQUIPMENT. (2) A BONDING BAR NEAR THE SERVICE EQUIPMENT ENCLOSURE, METER ENCLOSURE, OR RACEWAY FOR SERVICE CONDUCTORS. THE BONDING BAR SHALL BE CONNECTED WITH A MINIMUM r ALUG COPPER CONDUCTOR TO AN EQUIPMENT GROUNDING CONDUCTOR(S) IN THE SERVICE EQUIPMENT ENCLOSURE, METER ENCLOSURE, OR EXPOSED NONFLEXIBLE METALLIC RACEWAY. (3) A BONDING BAR NEAR THE GROUNDING ELECTRODE CONDUCTOR. THE BONDING BAR SHALL BE CONNECTED TO THE GROUNDING ELECTRODE CONDUCTOR WITH A MINIMUM 6 AUG COPPER CONDUCTOR (3)2/O,4C; (3)2/0 TO UTILI1 TRAN5FORM ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO ALL APPLICABLE CODES SUCH AS THE NATIONAL ELECTRICAL CODE 201-1, LOCAL ORDINANCES AND POWER COMPANY REGULATIONS. SUBCONTRACTOR SHALL BE LICENSED, CARRY ALL APPLICABLE.INSURANCE, AND HAVE A CURRENT COUNTY OCCUPATIONAL LICENSE. AS ALLOWED, CONNECT ADDITIONAL ELECTRICAL TO EXISTING CIRCUITS. SUBCONTRACTORS SHALL INCLUDE ALL SPECIAL FEES AND PERMITS, LABOR AND MATERIAL, EQUIPMENT AND ELECTRICAL ENGINEERING NECESSARY TO PROVIDE AN APPROvED WORKING SYSTEM. LIGHT FIXTURES EXCLUDED EXCEPT FOR FLUORESCENT FIXTURES AND REGE55ED LIGHTS, CONCRETE -ENCASED ELECTRODE. AN ELECTRODE ENCASED BY AT LEAST 2" GF CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF THE CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH THE r CONSISTING G;= AT LEAST 2Pr FT. OF ONE O MORE BARE OR ZING GALVANIZED OR OTHER ELECTRICITY EARTH, R R CONDUCTIVE COATED STEEL REINFORCING BAR5 OR RODS OF NOT LESS THAN 1/2 INCH DIAMETER, OR CONSISTING OF AT LEAST 20 FEET OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS." 210,12 ARC -FAULT CIRGUIT-INTERRUPTER PROTECTION. (A) DEFINITION: ARC -FAULT CIRCUIT INTERRUPTER (AFCI). A DEVICE INTENDED TO PROVIDE PROTECTION FROM THE EFFECTS OF ARC FAULTS BY RECOGNIZING CHARACTERISTICS UNIQUE TO ARCING AND BY FUNCTIONING TO DE -ENERGIZE THE CIRCUIT WHEN AN ARC FAULT IS DETECTED. (B) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLOR-5, LIBRARIES, DEN5, BEDROOMS, SUNRCOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, AND OTHER SPECIFIED ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC -FAULT CIRCUIT INTERRUPTER, COMBINATION -TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. CARBON MONOXIDE ALARMS R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL -FUEL -BURNING HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE 45 A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 mm) OF EACH ROOM USED FOR SLEEPING PURPOSES_ EXCEPTION: TH15 SECTION SHALL NOT APPLY TO EXISTING BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN SECTION R315.13. R315.1.1 CARBON MONOXIDE ALARM. THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS: 11) A HARD -WIRED CARBON MONOXIDE ALARM. 12) A BATTERY -POWERED CARBON MONOXIDE ALARM. (3) AHARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE ALARM. (4) A BATTERY -POWERED COMBINATION CARBON MONOXIDE AND SMOKE ALARM. R315.1.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. R315.13 ADDITION SHALL MEAN: AN EXTENSION OR INCREASE IN FLOOR AREA, NUMBER OF STORIES OR HEIGHT OF A BUILDING OR STRUCTURE ,4LL ELECTfRICAL SWITCHES/ OUTLETS, ETC- TO E3t'10UN T ED ,450VE THE 5,45E FLOOD ELEVATION. (SEE SITE f'LAN FOfR E3,45E EL V,47ON) GU :-CORDANCE 2�,O Digitally signed by 5i,'ned andsealed b 1.1- Vinson N lf)7/ /,,, IilC7�"1"1a5 g Y g u�ingel)�gitultiekn�hrr;uuielstc e T,-,f Thornas L Printed cep ies of Lhi dotum jif Hanson:A0141 0 Hanson:AO 14 1 OD000001 aI q 5 , n I eo nsidei d gn, i mid Q00077E 77EF31 B4E000015ADA �aLed Ind the s1� n �Wie must h its a�� Date: 2022,04.12 verified (m any eledre:ntc e Aw B4E000015ADA 14:35:37-04'00' �1�1_ 0� I:, 1 0. 11 V 51-011 V 51-oll V rol-oil 20"x Iro" CONTINUOUS CONCRETE FOOTING— w/(2)S REBAR ON CHAIRS e 41-011 O.C. 3-1/2" CONCRETE Lulro "X ro "X 10/10 W.W. MESH JI REINFORCING REQUIRED THROUGHOUT THE CONCRETE SLAB OR SYNTHETIC FIBER RE INFORCEMENT _W5� WICELL POURED SOLID ' a'-O'l O.C. MAX LI (STEM WALL) (BELOW FINISHED FLOOR) 100.00' (Y- NK_ W I" DEEP RECESS 10 WIDE (TTF,) X 2'-4" 4' V-011 2'-4" 0 21 4' WT11'14 1�1 I THE FOUNDATION HAS BEEN F_)E,5lGNEE) FOR A MINIMUM LOAD -BEARING PRESSURE OF 2000 POUNDS PER SQUARE FOOT SECTION 1907 MINIMUM SLAB PROVISIONS 1907.1 General. The thickness of concrete floor slabs supported directly on the ground shall not be less than 3 1/2 inches (89 mm). A 6-mil (0.006 inch; 0-15 rom) polyethylene vapor retarder with joints lopped not less or than 6 inches (152 mm) shall be placed between the base course subgrade and the concrete floor slob, or other approved equivalent methods or materials shall he used to retard vapor transmission through the floor slob. Exception: A vapor retarder is not required: 1. For detached structures accessory to occupancies III Group R-3, such as garages, utility buildings or other unheated f acilities. 2. For unheated storage rooms having an area of less than 70 square feet (6.5 m2) and carports attached to occupancies in Group R-3. 3. For buildings of other occupancies where migration of moisture through the slab from below will not be detrimental to the intended occupancy of the building. 4. For driveways, walks, patios and other flotwork which will not be enclosed at a later date. 5. Where approved based on local site conditions. tMENT"C' ALL GMU WALLS CONSIDERED SHEAR WALL CELL POURED SOLID wl (005 FROM FTC. TO BOND BEAM -30 WICELL POURED SOLID ,a V-0" O.G. MAX. (STEM WALL) CONTROL JOINT (SAW CUT) Ah 1.00-00' FINISHED FLOOR ELEVATION 1q__1 (ASSUMED DATUM) 0 TIE MAX BOLTS Q ro'-O" O.G. 4 12" FROM ANY CORNER E=_3 WINDOW OR DOOR OPENINGx LOCATIONS SECTION R318 PROTECTION AGAINST TERMITES R316J Termite Protection. Termite protection shall be provided by registered termitIcides, including soil applied pesticides, baiting eyetems, and pesticides applied tc wood, or other approved methods of termite protection labeled for use as a preventative treatment to now ccnstructIcn. See Section 202, REGISTERED TERNITfCIDE. Upon Completion or the application of the termite protective treatment, a Certificate of Compliance shall be Issued to the building department by the licensed peat Control company that contains the following statement; . The building has received a Complete treatment For the prevention of subterranean termites. Treatment 16 In accordance with rules and laws established by the Florida Department of Agriculture and Consumer Services:, R31511 If soil treatment is used For subterranean termite prevention, the initial chemical soil treatment Inside the foundation perimeter shall be done after all excavation, backnillne and compaction Is complete. R318.1.2 IF soil treatment Is used for subterranean termite prevention, soil area disturbed after Initial Chemical soil treatment shall be retreated with a cherrical soil treatment, including spaces boxed or formed. . R318.1.3 If soil treatment Is used for subterranean termite prevention, apace in Concrete floors boxed out or formed for the subsequent installation of Plumbing traps, drains or any other purpose shall be created by using plastic or metal permanently placed Forms or surnalent depth to eliminate any planned soil disturbance after Initial chemical soil treatment, R318.1.4 IF soil treatment Is used For subterranean termite prevention, clesmicalIV treated boll shall be otected with a minimum 6 mil vapor retarder to protect against rainfall dilution. if rainfall occurs before vapor retarder placement, retreatmeont Is required. Any work, Including placement of reinforcing steel, one after chemical treatment until the Concrete Floor is poured, shall be Core in such manner as to avoid penetrating or disturbing treated soil. R318.IAE5 IF soil treatment Is used For subterranean termite prevention, concrete overpour or mortar accumulated along the exterior foundation perimeter shall be removed prior to exterior chemical soil treatment to enhance vertical penetration or the ofnemicale. R315.1.6 If aoll treatment Is used for subterranean termiteprevention„ Chemical soil treatments shot[ also be applied under all exterior concrete or grade within I foot (305 mm) or the primary structure eldsswall&_ Also, a vertical Chemical barrier aha!] be applied promptly after construction is completed, including initial landscaping and Irrigation/sprinkler installation. Any soil disturbed after the Chemical vertical barrier is aptollsol erali be, promptly retreated. R3011 If a registered termitIctce formulated and registered as a bait system is used for subterranean termite prevention, Section R318.1.1 through Section R318.1,ro do not applV however, a elered Contract assuring the installation, maintenance and monitoring or the baiting system that is in compliance with the requirements or Chapter 482, Florida Statutes, shall be provided to the building official prior to the pouring OF the slab, and the system must be Installed prior to final building approval. IF the baiting system directions For use require a monitoring phase prior to installation of the pesticide active ingredient, the Installation of the monitoring phase components "If be deemed to constitute Installation or the system. R318J.8 IF a registered termiticlole Formulated and registered as a wood treatment Is used for subterranean termite prevention, Sections R3181.1 through R318.110 do not apply. Application or the wood treatment termiticicle shall be as required by label dlrectlon5 For use, and must be completed prior to Final building approval. R318.2 Penetration. Protective sleeves around piping Penetrating Concrete slab -on -grade floors al -all not be of callulosecontalnine materials. If soil treatment Is used for subterranean termite protection, the slasVs 61'1811 have a maximum wall thickness of 0,010 Inch (025 mm), and be sealed within the elab using a noncorrosive clamring device to eliminate the annular apace InCtweler the pipe and the sleeve- No termitloldes shall be 1, app led Inside the sleeve.- R-31,53 Clearing. Celle and cavities in masonry units and air gape, between br[ck, stone or masonry veneers and the structure of -all be cleared of all nonpre5ervative-treated or nonnaturally durable wood, or other cellulose -containing material prior to Concrete placement_ Exception:Inorganic material manufactured for closing Cella In foundation concrete masonry unit construction or clean earth fill placed In concrete masonry unit voids below elalb level before termite treatment is performed. R318A Concrete bearing ledge. Brick, stone or other veneer shall be supported by a concrete bearing ledge at least equal to the total thickness of the brick stone or other veneer which Is poured Integrally with the concrete foundation, No supplemental concrete Foundation pours which will create a hidden -old joint shall be used without supplemental treatment In the Foundation unless there is an approved physical barrier. An approved p+yjalcal barrier shall also be installed From below the wall slit plate or first block course horizontally to embed in a mortar joint. If masonry veneer extends below grade, a termite protective treatment must be applied to the cavity created between the veneer and the foundation, In ilou or a physical barrier. Exception: Veneer supported by a structural member secured to the foundation eldewall In accordance with ACI 530/ASCE 5/TMS 402, provided at least a & Inch (152 mm) clear Inspection apace of the Foundation sidewall exterior exists between the veneer and the top of any soil, sod, mulch or other organic landscaping component, deck, apron, porch, walk or any other work immediately adjacent to or adjoining the structure. R318.5 Protection against decay and termites. Condensate lines, Irrigation/sprinkler system risers for spray hsade, and roof downspouts shall discharge at least I foot (305 mm) away from the structure stclewall, whether by underground piping, tall extensions or splash blocks. Gutters with downspouts are required on all buildings with eaves of less than & inches (152 mm) horizontal projection except For gable end rakes or on a roof above another roof. R315b Preparation of building site and removal of debris. R318j6l All building sites shall be graded to provide drainage under all portions OF the t)ulldlne not occupied by basements. R315j62 The foundation and the area encompassed within I Foot (305 mm) therein shall have all vegetation, Stumps, dead roots, cardboard, trash and foreign material removed and the fill material shall be free of vegetation and Foreign material- The fill shall be Compacted to assure adequate support of the foundation R318k3 After 411 work is completed, looes wood and debris -shall be completely removed From under the building and within I Foot (305 mm) thereof. All wood Forms and supports shall be completely removed- This Includes, but is not limited to; wooden grade stakes, forms, contraction spacers, tub trap boxes, plumbing supports, bracing, shoring, forms or other cellulose -containing material placed in any location where such materials are not clearly visible and readily removable prior to completion of the work. Wood shall not be stored in contact with the ground under any buildine- R3181 Inspection for termites. In order to provide for Inspection For termite lnfest4t[on, clearance between exterior wall coverings and finale earth grade on the exterior, of a building shall not be leas than 6 inches (152 mm). Exceptions: I. Paint or decorative cementitroua finish less than 5/0 inch (IIJ mm) thick adhered directly to the masonry foundation sciewal . 2. Access or vehicle ramps which rise to the Interior finish floor elevation for the width of such ramps only. 3. A 4-Inch (102 mm) inspection space above patio and garage slabs and entry areas. 4. If the patio has been soil treated For termites, the finish elevation may match the building Interior Finish floor elevations on masonry construction only. 5. Masonry veneers constructed In accordance with Section R315.4. R318-8 Foam plastic; protection. In areas where the probability of termite Infestation Is very heavy, as Indicated n Flours R3012(6), extruded and expanded polystyrene, polulsocyanurats and other foam plastics shall not be Installed on the exterior fare or under Interior or exterior Foundation walls or slab Foundations located below grade. The clearance between Foam plastics Installed above grade and exposed earth shall be at least 6 Indies (152 mm). E e tions: l.;Z%Ing6 where the structural members of walls, floors, ceilings and roofs are entirely of noncombustible materials or preseure-preservative-treated wood. 2. Ukien in addition to the requirements of Section R3I8.1, an approved method of protecting the Foam plastic and structure From subterranean termite damage is used. 3. On the interior aide of basement walls. ENGINEEfR'5 NOTECS 0.) ALL WOW TO BE PONE ACCORDING TO ith Edition (2020) FBC_ (Florida Building Code) (2.) ASSUMED SOIL BEARING CAPACITY TO BE 2000 P5R SOIL CAPACITY TO BE VERIFIED BY CONTRACTOR PRIOR TO CON&TRUCTION, INFORM ENGINEER OF VARIATIONS. FOOTINGS TO BE EXCAVATED TO CLEAN SOIL, FREE OF VEGETATION AND DELETERIOUS MATTER. CONCRETE SHALL BE PLACED ON AN UNDISTURBED BASE. (3.) IT 15 THE CONTRACTOR'S SOLE RESFON515ILITY TO DETERMINE ERECTION PROCEDURE AND SEQUENCE TO INSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT FARTS DURING ERECTION. THIS INCLUDES, BUT 15 NOT LIMITED TO, THE ADDITION OF WHATEVER TEMPORA'R-' BRACING, GUYS, OR TIE DOWNS THAT MAY BE NECESSARY- SUCH MATERIAL SHALL BE REMOVED AND SHALL REMAIN THE PROPERTY OF THE CONTRACTOR AFTER COMPLETION OF THE PROJECT. (4.) ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE VERIFIED AND SHALL CONFORM TO THE ARCHITECTURAL DRAWINGS. (5.) CONCRETE - MINIMUM COMPRESSIVE CONCRETE STRENGTH TO BE 3000 F'51 IN 25 DAYS. ALL CONCRETE SHALL BE READY MIXED" AND IN ACCORDANCE WITH 14.5,T.M. SPECIFICATION C-e4. ALL CONCRETE MODULAR UNITS SHALL HAVE A COMPRESSIVE STRENGTH OF IeOO F51 WITH TYPE M OR S MORTAR, 2000 PSI, (ro.) SLAB ON FILL - INTERIOR CONCRETE SLABS POURED ON FILL TO BE POURED OVER WATERPROOF MEMBRANES. ALL 5LAE35 TO BE REINFORCED WITH 6X(o 10/10 WELDED WIRE MESH. CV LUMBER - I- STORE LUMBER OFF GROUND, KEEP WELL VENTILATED AND COVERED. 2- CURRENT EDITION, ASSOCIATION GRADING RULES GOVERN, 3, ALL LUMBER SHALL BEAR GRADE MARK OF AN ASIC BOARD OF REVIEW AGENCY. 4. ANY SPECIES ALLOWED UNLESS OTHERWISE NOTED, E5, SIZES ARE NOMINAL. ACTUAL SIZES SHALL CONFORM TO AMERICAN LUM5ER_UKASIR/Z;MNB64FZL IRS. 20-10. ro, MOISTURE CONTENT OF LUMBER 2" OR LESS IN THICKNESS SHALL BE 19 OR LESS AT THE TIME OF INSTALLATION. (ad TERMITE TREATING : SOIL BELOW STRUCTURE TO BE TERMITE TREATED TO A DISTANCE OF 5'-0'' BEYOND THE PERIMETER LINES OF THE BUILDING. (13,) ALL STEEL SHALL BE 40 <el WITH A MINIMUM CLEAR COVER OF 3" AGAINST SOIL, AND SHALL HAVE A MINIMUM LAP OF 40 TIMES THE DIAMETER OF THE RE514R, (10.) 2"XI2" HEADERS SHALL BE 2-2''XI2" LAMINATED W1 112" PLYWOOD GLUED W1 CONSTRUCTION ADHESIVE AND NAILED W1 5-411roL') COMMONS Iro" O.C. TO MEET LOADS AS INDICATE[), (11.) ALL FASTENERS SHALL COMPLY WITH THE DESIGN LOADS. (12.) CONTRACTOR SHALL HAVE MANUFACTURERS SPECIFICATIONS (CUT SHEETS) ON SITE AT THE TIME OF INSPECTION, FOR REVIEW BY THE 5UIL-DING INSPECTOR, TO MEET LOADS AS INDICATED. Thomas L Digitally signed by Thomas 1, Hanson:AO1 41 0 Hanson:A01410D00000 D00000177EF31 117EF31 134E00001 5ADA Date: 2022.04.12 B4EOOOO I 5ADA 14:36:03 -04'00' Signed aiid seaied by 1-1. 1 lanson PF tilliga Di�'61'11 Signaflucand dits . -ire not considered signcd and Z' se Fled and ills 111,411MUrC IIILItit he tZ C-11 0 N 01 I-- _T 0 ry n 0 0 WALL CONSTRUCTION FLORIDA BUILDING CODE RFSIDENiIAL, 6th FDtTION (2017) SIFCTION R609 EXTERIOR WINDOWS AND DOORS R609 -1 General. This section prescribes performance and construction requirements for exterior windows and doors installed in walls. Windows and doors shall he installed and flashed in accordance with the fenestration manufacturer s written instructions. Window and door openings shall be flashed in accordance with Section R703.4 Written installation instructions shall be provided by the fenestration manufacturer for each window or door. 8"X 8°X R609.2 Performance. Exterior windows and doors shall be designed to resist the design wind loads specified in Table R301.2(2) adjusted for height and exposure in d th T SHINGLES PER SPECIFICATIONS (w/ & FASTENERS PER SHINGLE) FELT UNDERLAlM 'ENT MUST BE 300 OR EQUIVALENT (ASTM D 220 TYPE 11, ASTM D48�o9 OR PEEL AND STICK ROOF UNDERLATMENT ON 1/2" PT LWOOD OR 055 W/H-CLIPS ON PRE-ENGINEERED WOOD TRUSSES � 24'O.C. (FOR NAILING SCHEDULE SEE SHEET S2G) - SEE ADDITIONAL INFO BELOW actor once wi able R301. 2(3) or determined to accordance with ASCE 7 using the allowable stress design load combinations of ASCE 7. Design wind BRICK MOULD HURRICANE ANCHORS loads for exterior glazing not part of a labeled assembly shall be permitted to be determined in accordance with Chapter 74 cif the Florida Building (SEE ROOF PLAN ) Code, Building. R609. 2. lCustom doors. DOOR FRAME MIN. Ix2 NAILING 5TRIP5 ATTACH SOFFIT TO STRIPS PER Custom (oneof- exterior door assemblies shall be tested by an approved testing laboratory or be designed and engineered in accordance with MANUFACTURERS PRODUCT APPROVAL SPECIFICATIONS R704.2.1 accepted engineering practices by a Florida registered design professional. Signed and sealed copies of the rational analysis and calculations shall be provided to the building official upon permit application. ALUM. DRIP EDGE-, R609.3 Testing and labeling. 3/1G"X 2-1/2" TAPGON Exterior windows and sliding doors shall be tested by an approved independent laboratory, and bear a label identifying manufacturer, performance FASTENERS INTO BL OGK characteristics and approved inspection agency to indicate compliance with AAMA/WDMA/CSA 101/I.S.2/A440 or TAS 202 (HVHZ shall comply with TAS 202 and ASTM E1300). Exterior side --hinged doors sholI be tested and labeled as conforming to AAMA/WDMA/CSA 101/I.S.2/A440 or ANSI/WMA 100, or comply with Section R609.5. Exterior windows and doors shall be labeled with a permanent label, marking, or etching providing traceability to the manufacturer and product. The following shall also be required either on a permanent label. or on a temporary supplemental label applied by the manufacturer: information identifying the manufacturer, the product model/series number, positive and negative design pressure rating, product maximum size tested, impact -resistance rating if applicable, Florida product approval number or Miami -Dade product approval number, applicable test standard(s), and approved product certification aaenr:y, testing laboratory, evaluation entity or Miami -Dade product approvI.il. 3/4" FURRING NAIL F D The Labels are limited to one design pressure rating per reference standard. The temporary supplemental label shall remain nn the window or door TO BLOCK -o allO.G. (2) until final approval by the building official. REQUIRED EACH LIFT Exceptions: • M006' u O O I.Door assemblies installed in nonhabitable areas where the door assembly and area are designed to accept water infiltration need riot be tested for /�/ water infiltration. 2.Door assemblies installed where the overhang (01I) calla is equal to or more than 1 need not be tested for water infiltration. The overhang rat8"x O"x 1&" G.M.U. io shall be calculated by the following equation: OH ratio = OH Length/OH Height 3/10" X 1-3/4" TAPCON FASTENERS INTO CONCRETE BLOCK 2X(c SUB FASCIA FASCIA COVER INSTALLED IN ACCORDANCE WITH FASCIA MANUFACTURER'S PRODUCT APPROVAL SPECIFICATION AND LIMITATIONS OF USE Where: OH length = The horizontal measure of how far an overhang over a door projects out from door surface. QD ESIVE JEALENT BOTH SURFACES OH height = The vertical measure of the distance from the door sill to the bottom of the overhang over a door. 3. Decorative glazed openings. PRIOR TO ATTACHING: BUCK TO GONG, BLK. 4.Pass-through windows for serving from a single-family kitchen, where protected by a roof overhang of 5 feet (1.5 m) or more shall be. exempted from the requirements of the water infi It.r ation test. 1/2'' DRYWALL R609. 3. lComparative analysis. Structural wind load design pressures for window and door units different than the size tested in accordance with Section R609.3 shall be permitted to be different than the design value of the Lested unit where determined in accordance with one of the following comparative analysis methods: 1.Structural r wind load design pressures for window and door units other than the size tested in accordance with Section R609.3 shall be, permitted Lo be different than the design value of the tested unit provided such different pressures are determined by accepted engineering analysis. All components of the alternate size assembly shall be the same as the tested or labeled assembly: however, lineal components shop be per rill tt.ed to vary in length compared to the tested or labeled assembly Exceptions: Ir7 l.Operable windows and doors rated in this manner shall comply with the following: 8"x i" SELF THREADING PHILLIP5 FLAT HEAD a.For windows and doors (other than .sliding or bi-fold), the frame area of the alternate size unit shall not exceed the frame area of the tested CADMINUM PLATE SCREW5 24" O.C. MAX. approved unit. b F 1'd' b' f I _1th WITHIN 4 OF CORNER . or s i ing c.Shot I vary or from - o oars, e panel or ea of the tested approved unit only in the alternate size unit shall not exceed the panel area of the width, height or load requirements. tested approved unit. d.ShaII not exceed 100 percent of the proportional deflection for fiber stress of the intermediate members of the approved unit. e.Sri aII not exceed 100 percent of the concentrated load at the juncture of the intermediate members and the frame of the approved unit. f.Sha11 not exceed the air and water infiltration resistance of the tested approved unit. g.Shall a licable not exceed the maximum cyciir. pressure of the tested approved unit when tested per TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where pp 3/I6"x 1-3/4" TAPCON FASTENERS 2. Nonoperable windows and doors rated in this manner shall comply with the following: INTO CONCRETE BLOCKS a. The frame area of the alternate size unit shall net exceed the frame area of the tested approved unit. b.ShalI vary from the tested approved unit anly in width, height or load requirements. CAULKING c.The maximum uniform load distribution (ULD) of any side shall be equal to the uniform load carried by the side divided by the length of the side. d.The OLD of any member shall not exceed the ULD of the corresponding member of the tested approved unit. MARBLE STOOL e.The ULD of each member shall be calculated in accordance with standard engineering analysis. f.SholI not exceed the air and water infiltration resistance of the tested approved unit. g.Shot I not exceed the maximum cyclic pressure of the tested approved unit when tested per TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where applicable. 1/2'' DfRYWALL ON Ix 3 P.T. 3. In accordance with WDMA 1. S. 11. FURRING -�D Iro" O.C. R609.4 Garage doors. Garage doors shall be tested for determination of structural performance under uniform static air pressure difference in accordance wit(? ANSI/DASMA 1.08, ASTM E330 Procedure A, or TAS 202. For garage doors tested in accordance with ASTM E330, acceptance criteria shall be in accordance with ANSI/DASMA 108. (HVHZ shall comply with TAS 202.) Design pressures shall be determined from Table 301.2(4) or ASCE 7. The design pressures, as determined from ASCE 7, are permitted to be multiplied by 0.6. PRECAST SILL R609.4.1 Garage door labeling. Garage doors shall be labeled with a permanent label provided by the garage door manufacturer. The label shall identify the garage door n n n 8 X 8 X 1� G.M.U. manufacturer, the garage door model series number, the g g / positive and negative design pressure rating, indicate impact rated if applicable, the Installation instruction drawing reference number, the Florida product approval or Miami -Dade, product approval number if applicable; and the applicable test standards. The required garage door components for an approved garage door assembly may be indicated using a checklist, form on the label. If a checklist format is used on the Lobel, the door installer or the garage door manufacturer shall mark the selected components or the checklist that are required to assemble an approved garage door system. The installation instructions shall be provided and available on the job St te.. R609.5 Other exterior window and door assemblies. Exterior windows and door assemblies not included within the scope of Section R609.3 or R609.4 shall be tested in accordance with ASTM E3.10, Glass ���� S W in assemblies covered by this exception shall comply with Section R308.5. ot Wind-borne debris protection. Protection 4 WINDOW W AT - A H N Prtion of exterior glazed openings in buildings located in wind-borne debris regions shall be in accordance with Section R301.2.1.2_. II I 1 R609.6.1 Fenestration testing and labeling. Fenestration shall be tested by an approved independent laboratory, listed by an approved entity, and bear a label identifying manufacturer, performance characteristics, and approved inspection agency to indicate compliance with the requirements of the following sc,ec:ification(s): 1.ASTM E1886 and ASTM E1996; or FILLED CELL (3) 1/2"x 8" "J" BOLTS OR 2. AAMA 506. w/ (1) * 5 VERT. HILTI DN50 (OR EQUAL) R609.7 Anchorage methods. The methods cited in this section apply only to anrhornq.e of window and glass door assemblies to the main force -resisting system. CONT. WOOD TRIM RF09.7.1 Anchoring requirements. Window and glass door ossemblies shall be anchored in accordance with the published manufacturer s recommendations to achieve `he design pressure specified. Substitute anchoring systems used for substrates not specified by the fenestration manufacturer shall provide equal or greater anchoring performance as demonstrated by accepted engineering practice,. R609.7.2 Anchorage details. Products shall be anchored in accordance with the minimum requirements illus'Lrated in Figures R609.7.2(1), R609. 7. 2(2), R60"1/ 2(3), P609. 7. 2(4), R609. 7. 2(5) , R609. 7. 2( 6) , R609. /. 2( 7) and R609. 7. 2(s) . 2x 6 P.T. WOOD JAMB R609 7 2 1 M th t r ATTACH SOFFIT TO FASCIA OR TO NAILING 5TRIP (NOT SHOWN) MAT VART (IF OVER 12'' - INTERMID IATE rt=url it�=n ctl -r-n n\/=r_&T-IIPEt REQ. v r-_ EXTERIOR SIDING-T OVER i X 2 P.T. FURRING � l�" O.C. *5 DWL w/ 10'' 5TD, NOOK J Z � M (1) 20'-0'' *5 REBAR TIED TO FTC. STEEL AND GRND. ROD (BT OTHERS) AT ELECTRICAL BOX LOCATION (2,", REBAR CONT. (3" MIN. COVER) GROUND ROD (BT OTHERS) SEE ELEVATIONS FOR ROOF SLOPE PANEL EDGE 5UPPORT FOR NARROW WIDTH ROOF SHEATHING" PER TECHNICAL NOTE *R275A 16-24 "-DOUBLE PLT GLIP THE SIDE ADJACENT TO THE FULL WIDTH PANEL - NONE REQUIRED AT RIDGE OR NIP, 12'' TO Ira" - LUMBER ONLY' BLOCKING (2x4) FLAT WI5E OR ENDWISE ON THE SIDE ADJACENT TO THE FULL WIDTH PANEL NONE REQUIRED AT RIDGE OR HIP. FOR PLTWOOD SHEATHING 12'' OR LESS - LUMBER ONL'r' BLOCKING, (2x4) FLAT WISE OR EDGEWISE ON BOTH PANEL EDGES - .sa TOP COURSE 5"X8"Xi011 GONG, K.O. BLOCK W/ • •"y POURED GONG. 4 t ', 1-*5 REBAR GONT, PRECAST GONG. LINTEL or POWER5 STEEL LINTEL W/ *5 POURED SOLID rr ,li i. WINDOW ��► �+'n � 1 RBLE SILL EC,45T GONG. 51LL (1) 20'-0'' 5 REBAR TIED TO FTG, STEEL AND GRND. ROD (BT OTHERS) AT ELECTRICAL 3000 PSI GONG. G "x &"x 10/10 E.W.W. ME5iL REINFORCING REQUIRED THROUGHOUT THE CONCRETE SLAB OR FIBER MESH PER SECTION IINI.2, 2010 FLORIDA BUILDING CODE. (o MIL. VAP. BARRIER G X&-*10 WWF OR FIBER MESH 1.5*/GU. YD. HEADER BLOCK W/*54 NOTE: IF WALL HEIGTH EXCEEDS 2'-0'' BRACE WALL UNTIL FLOOR IS POURED *50 W/CELL POURED SOLID 8'-0" O.C. MAX. *5� DOWEL SPACING PER FOUNDATION PLAN DE GROUND ROD (BT OTHERS) j� 2- ,� I L\ f SmTom rm �#1 W44LL) CONCRETE -ENCASED ELECTRODE, AN ELECTRODE ENCASED BT AT LEAST 2" OF CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF THE CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER ELECTRICiTT CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT LESS THAN 1/2 INCH DIAMETER, OR CONSISTING OF AT LEAST 20 FEET OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED TOGETHER BT THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS." . .. Where the asonry, ..oncre-e ar o er structural subst.rate. DOOR AND CONNECTION PER wood shim or- buck thickness is less than tl/2 inches (38 mm), window and glass door assemblies shall be anchored through the jamb, or by jamb clip and anchors shall be embedded directly into the masonry, concrete or other substantial substrate material. Anchors shall adequately GARAGE DOOR MANUFACTURER transfer load from the window or door frame into the rough opening substrate [see Figures R609.7.2(1) and R6097.2(2)]. Where the wood shim or buck thickness is 11/2 inches (38 mm) or more, the buck is securely fastened to the masonry, concrete or other substantial 0L-to substrate, and the buck extends beyond the interior lace of the window or door frame, window and glass door assemblies shall be anchored through 4INthe 0f '"R J rnb or by jamb clip or through 1 the flange trt the secured wood buck Anchors shall be embedded into the --n-ri v, 1 F)ir to nnerli t,=lv i '^IG transfer load from the window or door frame assembly [see Figures R609.7.2(3), P.6097.2(4) and R609.7.2(5)] R609.7.2.2 Wood or other approved framing material. Where the framing material is wood or other approved framing material, window and glass door assemblies shall be anchored through the frame, or by frame clip, or through the flange. Anchors shall be embedded into the frame construction to adequately transfer load [see figures R609 7.2(6), R609. 7. 2( 7) and R609. 7. 2( 8) ]. R609.8 Mullions. Mullions shall be tested by an approved Les tinq laboratory in accordance with AAMA 450, or be engineered in accordance with accepted engineering practice. Mullions tested as stand -atone units or qualified by engineering shall use performance criteria cited in Sections R609.8.1, R609.8.2 and R609 8.3. Mullions qualified by an actual test of an entire assembly shall comply with Sections R609.8.1 and R609.8.3. R609.8.1 Load transfer. Mullions shall be designed to transfer the design pressure loads applied by the window and door assemblies to the rough opening substrate. R609.8.2 Deflection. Mullions shot! be capable of resisting the design pressure loads applied by the window and door assemblies to be supported without deflecting niore than L/175, for spans up to and including 13 foot 6 inches, and L/240 + 1/4 inch for spans over 13 foot 6 inches, where L is the span of the mullion ;n inches. r<609.8.3 Structural safety factor. Mullions shall be capable of resisting a load of 1.5 Limes the design pressure loads applied by the window and door assemblies to be supported without exceeding the appropriate material stress levels. If tested by an approved laboratory, the 1.5 times the design pressure load shalt be sustained for 10 seconds, and the permanent deformation shall not exceed 0.4 percent of the mullion span after the 1.5 times design pressure load is removed. R609.9 Masonry rough openings. Masonry rough opening dimensions shall be within the tolerances specified in Section R606.3.1.1 and, in addition, shall provide for a window perimeter sealant joint a maximum of 1/4 inch (6.4 mrn) in width. R609.10 Door components. Substitution of door components shall comply with either: I.ANSi/WMA 100; or 2.P,e evaluated by on approved product evaluation entity, certification agency, testing laboratory, or engineer and may be interchangeable in exterior door assemblies if the components provide equol or greater structural performance as demonstrated by accepted engineering practices. R609 11 Impact -resistant coverings R609.11.1 Impact -resistant coverings shall be tested at 1.5 times the design pressure (positive or negative) expressed in pounds per square feet as determined by the Florida Building Code, Building Section 1609 for which the specimen is to be tested. The design pressures, as determined from Section 1609 of the Florida Building Code. Building or ASCE 7, are permitted to be multiplied by 0.6. R609. 11. 1. 1 Impact -resistant coverings shall be labeled in accordance with the provisions of Section R609.11. R609. 1 1. 2Labe 1 s. i\ permanent label shall be provided by the product approval holder on all impact -resistant coverings. R609. 11. 2. 1 The followina information shall be included on the ithels on impact. -resistant coverings: i.Product approval holder name and address. 2.AII applicable methods of approval. Methods of approval include, but, are not limited to Miami Dade NOA; Florida Building Commission, TDI Product Evaluation; ICC-ES. 3.The test standard or standards specified in. Section R?01 2.1.2, including standards referenced within the test standards specified in Section R301.2.1.2 used to demonstrate code compliance. 4. For products with a Florida product approval number or a Miami -Dade County Building and Neighborhood Compliance Department Notice of Acceptance Number (NOA), such numbers shall be included on the label. R609. 11. 3Loc a t I or) of label. The location of the label on the impact -resistant covering shall be as follows: 1.Accordiona: Bottom of the locking baror center rnat.e facing the exterior or outside. 2.Rollup: On the bottom of the hood facing the exterior or outside or on the bottom slat facing the exterior or outside. 3.Bohoma Awn ng or Colonial Hinged: On the bottom, placed on Lee back of the shutter. 4.Ponel-s: For metal and plastic panels the label may be embossed or printed spaced not more than every 3 lineal feet (914 mm) on each panel. The label shall be applied by the holder of the product approval and shall face the exterior or outside. 5.Framed products: The label shall be. on the side or bottom facing the exterior or outside. 6.1-abets on all other products shall face the exterior cr outside. R609 1!. •4 installation. All impact -resistant coverings shall be installed in accordance with the manufacturer s installation instructions and in accordance with the product. approval. Installation instructions shall be provided and shall be available to inspection personnel on the job site. Opening protection components, fasteners, and other parts evaluated by on approved product evaluation entity, certification agency, testing laboratory, architect, or engineer and approved by the holder of the product approval may be interchangeable in opening protection assemblies provided that the opening protection component s) oruvide equal or greater structural performance and durability as demonstrated by testing in accordance with approved test standards. Thomas L Digitally signed by Thomas L Hanson:A01410 Hdnson:A01410D000001 D00000177EF31 77EF31 B4E000015ADA Date: 2022.04.12 B4E000015ADA 14:36:30-04'00' Signodand .`aled1cI.L.liar "pi using a i hgitil Signature and I'll,, Printed Copies ies of the dcx um nt r>,•" ` .rreuotcon,idm(cdsigned .Irul ; s`aled wn t the `i!?nature nntct I", w , . I,cI lied on In, d"Ctonic CO 1H �b O FY (Z 0 U III Q i - -T FRI OVIDE MIN11"(l!M ]roll 20 GA VALLEY FLASHING AT ° ALL ROOF CHANGES AND SIDE WALL AREAS F'EF � F5C 1012.E� !§R_103 _15. -103.0., e03_2 AND 90-5 PLACE ° GOOF CEMENT COATING AT WOOF DECKS EDGES OF ° FLASHING AND ALL L,4f=5. NAiL FLASHING WITH 1 112'' ° ° FROOF NAILS 12'' OC ° ° % O i° N Frame Wall SiLL IH SIDE WALLS OF GHIt-IN / Y i"ilNiMUi"i £3"X8" 2& GA ANGLE ° °jOil S 1 EF' FLASHING, SEE NO- °// 0 ROOF DECK AT SIDE WALLS WINDOU) 4 D00.R 1 45T IN 2011 Flarlda ulldln�Gcdn NOTFga 1. ALL EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH AP451/AMMA/NIWWDA 101/152 STANDARD AND BEAR AN AMMA OR WDMA LA5EL INDICATING:, MANUFACTURERS PERFORMANCE ANC? APPROVED PRODUCT TErv-TiNGs ENT1 T i , IN ACCORDANCE WITH 201'1 Florida Bulldine Code, SECTION 1101,A.2.1 2. ALL EXTERIOR DOORS AND WINDOWS, SHALL BE ANCHORED IN ACCORDANCE WiTH MANUFACTURERS SPECIFICATIONS, IN ACCORDANCE WITH 2O11 FLOP;DA BUILDING CODE 1101.41 3. WINDOWS AND DOORS FASTENED TO FUCK STRIPS LESS THAN 1 1/2" SHALL BE ANCHORED THROUGH THE JAME TO THE STRUCTURAL 51185TRATE, IN ACCORDANCE WITH 2O11 Florida Bulldin!a Code_ 1101.4.42 4. WINDOW AND DOOR MULLION A55EME3LiE3 SHALL 5E DESIGNED AND TESTED TO TRANSFER 1.5 TIMES THE INDICATED DESIGN LOADS, TO THE STRUCTUfi L SUBSTRATE IN ACCORDANCE WITH, 2011 Florida Building Code 1101,4 7.1 AND 1101ABA. aw MINI 11RIM1711 A I I M'@GT"""fl `i OF WINE)OW TO Fib,4M W,4LL TO 5E FEfR M,4NUF,4C:TU S OMMENDATICAN. k e S c^: TABLE R301. MINIMUM UNIFORMLY D I S - _\ I BU TED L VE LOADS (in pounds per square foot) UJ I USE LIVE LOAD Uninhabitable attics without storage b,g 10 Uninhabitable attics with limited storage b,g 20 Habitable attics and attics served with fixed stairs Balconies (exterior) and decks e 30 40 Fire escapes 40 Guardrails and handrails d 200h Guardrail in -fill components f 50h Passenger vehicle garages a 50a Rooms other than sleeping room 40 Sleeping rooms 30 Stairs 40c For Sl: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1. pound = 4.45 N. a. Elevated garage floors shall be capable of supporting a 2,000-pound load applied over a 20-square-inch area. b. Uninhabitable attics without storage ar-e those where the maximum clear height between joists and rafters is less than 42 inches, or where there are not two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches high by 24 inches in width, or greater, within the plane of the trusses. ihis live load need not be assumed to act concurrently with any other live load requirements. c. Individual stair treads shall be designed for the uniformly distributed live load or a 300-pound concentrated load acting over an area of 4 square inches, whichever produces the greater stresses. d. A single concentrated load applied in any direction at any point along the top. e. See Section R502.2 for decks attached to exterior walls. f. Guard in -fill components (all those except the handrail, balusters and panel tillers shall be designed to withstand a horizon_ally applied normal load of 50 pounds on an area equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement. g. Uninhabitable attics with limited storage are those where the maximum clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. The live load need only be applied to those portions of the joists or truss 'bottom chords where all of the following conditions are me t : 1. The attic area is accessible from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is a minimum of 30 inches. 2. The slopes of the joists or truss bottom chords are no greater than 2 inches vertical to 12 units horizontal. 3. Required insulation depth is less than the joist or truss bottom chord member depth. The remaining portions of the joists or truss bottom chords shall. be designed for a uniformly distributed concurrent live load of not less than 10 lb/ft2. h. Glazing used in handrail assemblies and guards sliall be designed with a safety factor of 4. The safety factor shall be applied to each of the concentrated loads applied to the top of the rail, and to the load on the in -fill components. These loads shall be determined independent of one another, and loads are assumed not to occur with any other live load. Signe i to l �ralcd i '1' .. lin mi ]IF, Digitally signed j�Thomas L using ti)i irvlSign wfcmtict,r Thomas L Printed eclteaofthi I eurrtcnt �T; ' idi�SCi:%�fl� 4� Hanson:A01410D00000 `' "°' `O° ' I"� i ' °"t"nd alc I uut the si nMme nui t be D000 01%7EF31 177EF3134E000015ADA will,i on anpalcetI nice, Date: 2022.04.12 +; r- B4EO0 015ADA 14:37:02-04'00' n D 0 C? U) v v I` 0 v c' o' C N O N'I Q� zj CD n 0 — —7T It -r I -. T _ -- R502. 5 Allowable girder spans. The allowabie spans of girders fabricated of dimension lumber shall not exceed the values set forth in Tables R502. 5(1) and R502. 5(2). TABLE R502. 5( 1) GIRDER SPANSo AND HEADER SPANS i�OR EXTERIOR BEARING WALLS (Maximum spans for Douglas fir -larch, hem -fir, southern pine and spruce-pine-firb and required number of jack studs) GIRDERS AND HEADERS .SUPPORTING Roof and ceiling _ SIZE 2-2x4 Building widthc (feet) 20 28 36 SPAN 3--6-1 i NJcI SPAN NJd SPAN NJ 3-2 1 2-10 1 2-2x6 5-5 1 4-8 1 4-2 1 2-2x 8 6--0o 0 1 5-1 1 2 5-4 2 2-2x10 8-5 2 7-3 2 6-6 2 2-2x 12 9-9 2-- 8--5 2 7-6 2 3-2x8 8-4 - 1 7-5 1 6-8 1._ 3--2x 1 O 10-6 1 9-1 2 8-2 2 3-2x12 _12-2 2 10-7 2 9-5 2 4--2x 8 9-2 - 1 8-4 1 7-8 2 4-2x10 11-8 1 10-6 1 9-5 2 4-2x12 14-1 1 12-2 2 10-11_ 2 Roof, ceiling and one center -bearing f ioar Roof, ceiling and one clear span floor -_ 2-2x4 3-1 1 2-9 1 2-5 1 2-2x 6 _4-6 1 4-0 1 1 3-7 2 2-2x8 5-9 2 __ 5-0 6-2 2 4-6 2 2-2x10 7-0 2 2 5-6 2 2-2x12 8-1 2 7-1 2 6-5 2 3-2x8 7-2 1 6-3 2 5-8 2 3-2x 10 _ 8 -9 2_ 7-8 2 6-11 2 3-2x12 _ 10-2 2 8-11 2 8-0 2 4-2x8 8-1 _ 1 7-3 1 6-7 2 --2x 1 40 10-1 1_ 8-10 2 8-0 2 4-2x_12 2-2x4 1 1-9 2-8 _ - 2 1 �10-3 2-3 2 1 9-3 2-0 2 1 2-2x6_ 3-11 2 3-3 2 2-11 2 2-2x8 5-0 2 4-2 3 3-9 2 2-2x10 6-1 2 5-1 3 4-7 3 2-2x12 7-1 3 5-10 3 5-3 3- 3-2x 8 6= 3 2 5--2 2 4-8 2 3-2x10 7-7 2 6-4 2 5-8 2 3-2x12 8-1.0 2 7-4 3 6-7 2 4-2x8 7-2 T 1 6-0 2 5-5 2 4-2x10 8-9 2 2 6-7 2 4-2x 12 10-22 -7-4 8_6 2 7-8 2 Roof, cei 1 ing and two center -bear in floors g _ Ruci, ceiling and two clear span floor i 2-2x4 2-2x6 2-7 3-9 1 2 2-3 3-3 1 2 2-0 2-11 1 2 2-2x 8 4-9 2 ---4-2 .5--1 2 3--9 2 2-2x 10 5-9 2 4-7 3 2-2x 12 6-8 2 '_�-10 3 5-3 3 3-2x8 _5--11 2 5-2 2 4-8 2 3-2x i0 7-3- 2-- 6-4 2 5-8 2 3-2x12 8-5 { 2 7-4 2 6-7 2 4-2x8 6-10 1--�-5-0 2 5-5 2 4-2x1 O 8-4 2 7-4 2 6-7 2 4-2x12 2--2x4 9-8 2-1 2 1 8-6 -8 2 1 7-8 1-6 2 2 2--2x6 - 3--1 2, _1 2 2-4 2 2-2x8 3-'10 - 2 __2---8 3-4 _ 2 3-0 3 2-2x10 4-9 2 4-1 4-9 3 3 3-8 4-3 3 3 2-2x12 5-6 2 3-2x8 4-10 _ 2 4-2 2 3-9 2 3-2x10 3-2xl2 4-2x8 4-2x10 4-2x12 5-11 6-10 5-7 6-10 7-11 2 2 2 2 -2- 5-1 5-11 4-10 5-11 6-10 2 3 2 2 2 4-7 5-4 4-4 5-3 6-2 2 2 2 2 3 For Si: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m2. a. Spans are given in feet. and inches. b. labulated values assume #2 grade -lumber. c. Building width is measured per pendicuIor- to the ridge. For widths between those shown, spans or-e perrniI-Led to be Interpolated. d. NJ Number of ock studs required to support each end. Where the number of required jack studs equc;- one, the header is permitted to be supported by an opproved framing :,llchor attached to the full -height wall stud and to the header. e. Reserved. 24'' MIN, LAP 4 L=f f 7r�" MIN i .6.F% 3ro" MIN, LAP rL? 1:�IIvIrVI' C�II�IC.� � 1K d2" MIN I dp -- ".A P ePL( CM i�DII METAL LATH ATTACHED TO WOOD STUCCO FINISH OVER WOOD FRAMING FRAMING PER ASTM C 1063 PER ASTM C 926 & C 1063 STUCCO CONTROL JOINTS SPACED WOOD FRAMING - SEE DRAWINGS PER ASTM C 926 & C 1063 TWO LAYERS OF VAPOR Is" PLYWOOD OVER WOOD FRAMING 8d BARRIER BEHIND STUCCO COMMONS @ 6" O.C. MIN. MAINTAIN 8" - �.•_ GAP AT ALL ENDS OF PLYWOOD. - _ STUCCO WEEP SCREED - TYP. - - CONCRETE MASONRY CONSTRUCTION - SEE PLANS STUCCO FINISH OVER CONCRETE MASONRY PER ASTM C 926 & C 1063 TYPICAL STUCCO DETAIL GENERAL NOTES: 1. STUCCO ON WOOD FRAME SHALL BE MIN. 8" , 3-COAT APPLICATION. 2. STUCCO ON MASONRY SHALL BE MIN. 2" , 2-COAT APPLICATION OR 8". 3 COAT APPLICATION 3. WRB SHOULD EXTEND DOWN, OVER THE UPPER FLANGE OF WEEP SCREED OR ACCESSORY IN A SHINGLE -LAP FASHION. 4. METAL LATH TO BE ATTACHED WITH 11GA 1-2" LENGTH, 1-" HEAD NAILS (4D 1-1/2"x4 HEAD)NAILS TO FRAMING MEMBERS AT NOT MORE THAN 7 i n 0. C. WOOD r tf* v ■ ■ • ■ ■ .r mm ■ ■ mm COLLAR TIE Wo (MINJ EVERY OTHER RAFTER T-0" OR LONGER BLOCKING BELOW RIDGE ROOF 5HEATHINr, rASTENINrs SCHEDULE a b,c,d,e 8d Common (0.131 x 2-1/2 Inches) or Ring -Shank (0.135 X 2-1/2 inches) (Except Llhere Noted) for Exposure B, Enclosed Bulldings, Roof Framing Spaced 24 Inches o.c. or Less Roof Fastening Zone Overhang Wind Mafn Sheathing -to -(sable (eaves) velocity Roof End -Wall Framir2e (3-5econd Panel 1 2 3 2 3 2 3 Crust) Location Fastening Schedule (in(_-hes on center) Supported Panel ro 6 ro 6 6 150 mph F,e end and edges 3h Panel field 6 4 3 4 3 Supported Panel 120 mph f-g end and edges 6 6 6 6 (o 3 Panel field 12 (o 4 6 4 Supported Panel 50 mph end and edges ro ro ro 6 6 6 Panel field 12 12 6 6 6 a. Specific gravity (Cs) of lumber and panels shall be 0.42 or greater. b. For Exposure B and a 2-foot overhang. C. For median roof height 35 feet or less. d- (sable wall height of S feet or less from top floor ceiling to roof peak e. Provide adequate uplift hardware at truss -to -wall connections. Such connections are beyond the scope of this publication. F. When wind speed is 110 mph or greater and when median roof height is between 25 and 35 feet, use ad ring shank nails (0.135 x 2-1/2 inchesAijithin 48 inches of gable end walls. (IRC Table Rro02.3, footnote f) g. When wind speed is 100 mph or greater, block panel edges perpendicular to gable -end -wall framing members in the first two bays of framing. Blocking shall be spaced a maximum of 4 feet o.c. (Wood Frame Construction Manual, Section 3.5.5) h. 10d ring -shank nails (0.148x 3 inches). 1. Blocking not required. ROOF FASTENING ZONES FOR WIND UPLIFT Zones 1,2 and 3 shown below indicate areas of the roof that may have different fastening requirements. GABLE END WALL --- 2 WALL LINE 3 C.2'�F'i�IANC� Y: S. 2 I 1� I I f I l I - f 1.1 2 1 i.'.2' 2.' I I f! 12 N �j I I II I} I I i I iI ---------------- X ` WALL LINE A 3 OvERHANG - ` 1 �3 OVERHANG -" 3 OVERHANCs WALL LINE GABLE END WALL Distance a=4 ft, in most cases (10i of least building width or 0.4 times building height, whichever is smaller, but not less than either 451 of least building width or 3 ft.) ROOF P14F=�4iRX'l N,41L1\C$ eCHDULrz (Cx,45Lr=e) 2X(o VERTICAL 5C,45 OR KNEEWALL MID -POINT IN RAFTER W/ RAFTER SPAN LENGTH GREATER THAN 14 FT OR LONGER, CONN W/ 4-106 NAILS AT TOP 4 HURRICANE CLIP '�D 15OTTO1 1. 2X( (MINJ NO. 2 '1'P SIMPSON LSTA12 VALLEY' FRAMING (T�-F. (OR EON LS 2XO NO. 2 SPF r fi Li'WOOD 5HEATHINC; RiDGE BOARD (4) 106 '9D RIDGE BOARD END TRUSSES BELOW SHEATHED PRIOR TO VALLE T' FRAi"11NG INSTALLATION OR (o'-O'' O.G. TOP CHORD 511„1PS0N LSTA12 STRAP OR SIM1P50N 422 TIE EA, RAFTER W/ 10-106 NAILS (T' 'P.) 2X(o CONT. W/5LEEPER, CLIP ED OR STRAPPED TO TRUSS BELOW '' 1 C 01,1 \,,o \,.4,A, I I Lm.',0 M = �41"'O i k l,*w. rw� Em-'i 4 f L R 5AR LAP DIST,4NG I 25'' MIN, L,4P 25" MIN, LAP Fr z 'I v,rnn��'r�vr,l Q I G.M.U- I.UALL I i 7 R m i '``7 'REINFORCING; 5AR-. (1) *5 DOWEL I I (I) 05 DOWEL I I IN GORNI=R IN CORM=R I ( I I i ��r - SOOT ii�lC� A CsTt=1-fuJALL 5' PLATE HEIGHT = 5'-0" O.C. 10' PLATE HEIGHT = (�,'-Q" O.G. 12' PLATE HEIG3HT = 4'-0" O.C. "A" 14' PLATE HEIGHT = 2'-0" O.C. MAX. / PILASTERS'a 10'-0" O.C. ,4T EACH CORNER $ 50TH SiDES OF DOORS $ WINDOUJS OPENINGS COVER 5'-0'). BEFORE & AFTER SHEAR ,4LL SEGMENTS, 4 (2) BARS � EA. SIDE OF OPENING OVER 12'-Oil TABLE 2304. 10. 1 FASTENING SCHEDULE DESCRIPiION OF BUILDING ELEMENTS NUMBER AND TYPE OF FASTENER SPACING AND LOCATION Roof 3-8d common 2 x 0. 131: ; or 3-IOd box (3" x 0. 128, ); or 1. Blocking between ceiling joists, rafters or trusses to top 3-3" x 0.131" nails; or Each end, toenail plate or other framing below 3-3" 14 gage staples," crown 2-8d common (2�" X 0.131") 2-3" x 0.131" nails Each end, toenail Blocking between rafters or truss not at the wall top plate, 2-3" 14 gage staples to rafter or truss 2-16 d common (3 " x 0.162") 3--3" x 0.131" nails End nail 3-3" 14 gage staples 16d common ( 3j" X 0. 162" ) @ 6" o. c. 3"x 0.131" nails @ 6" o.c. Face nail Flat blocking to truss and we filler 3" 14 gage staples @ 6"o.c. 3-8d common (2j" X 0. 131")or 3-10d box (3" x 0.128")or Each joist, toenail 2. Ceiling joists to Lop plate 3-3" 0.131" nails; or 3-3" 14 gage staples, " crown _ 3-16d common (2�" X 0. 131")or 3. Ceiling joist not attached to parallel rafter, 4-10d box (3" x 0.128")or Each Nadi toenail laps over partitions (no thrust) 4-3"x 0.131" nails; or (see Section 2308.7)3.1, Table 2308.7.3.1) 4-3" 14 gage staples, ?g" crown 4. Ceiling joist attached to parallel rafter (heel joint) (see Per Sebteo@3280.2.1 Face nail 6edtmon2208172�.1, Table 2308.7.3.1) Per Table 2308.7.3.1 3-I0d common (3" X 0. 148"); or 5. Collar tie to rafter 4-10d box (3" x 0.128");or 5. Collar tie to rafter 4-3" 0. 131" nails; or Face nail 4-3" 14 gage staples, J" crown 3-10d common (3" X 0. 148") ; or 6. Rafter or roof truss to top plate 4-10d box (3" x 0.128");or SeRaSketion @a6t.21 uss to top plate 4-3" 0.131" nails; or Hoeoamdlil See Section 2308. 7. 5, Table 2308. 7. 5) 4-3" 14 gage staples, lT" crown 2-16d common (3 1./2" X 0. 162"); or 3-10d box (3" x 0. 128"); or 3-3" 0.131" nails; or End nail 7. Roof rafters to ridge valley or hip rafters; or roof 3-3" 14 gage staples, " crawn;or End nail FaffReoftoaPtenBhtDidadgbeumlley or hip rafters; or roof 3-100 6ommon rafter to 2-inch ridge beam 3-169 BOX (3 1/2" xOOAB35�);ort 4-10 BOX (3" x x012R'8%; oror Toeno i I 4-3"xx9. 131"' MailEm;; or 4-3" 14 goge staples, "corrown 16d common (3 1/2" X 0.162"); 24"o.c. face nail 8. Stud to stud (not at braced wall panels) 10d common 3 X 0.128 ;or 8. Stud to stud (not at braced wall panels) 3"x 0.131" nails; or 16" a. c. face nail 3-3" 14 gage staples," crown 9. Stud to stud and abutting studs at intersecting wall 16d common (3 1/2" X 0.162"); 16"a,c. face noil_ 16d box 3 1/2" X 0. 135" ; or 12" a. c. face nail 8orfikod at intersecting wall corners �otslbridcaddwa&11tit6ngls).uds at braced wall pone Ia 3"x 0.131 nails; or 3-3" 14 gage staples, ?g" crown 12"o.c. face nail 10. Built-up header, (2" to 2" header)) 16d common (3 1/2" X 0. 162'); 16"o. c. face nail 16d box (3 1/2" X 0.135");or 12"o.c. face nail 11. Continuous header to stud 4-8d common (21/2: X 0. 131, 4-8d common 2 1/2" X 0. 131or " ; Toenail 4-10d box (3" X 0.128") 16d common (3 1 2" X 0.162");or 16"a.c. face nail IOd common 3 X 0. 128 ; or 12. Top plate to top plate 3"x 0.131" nails; or 12"o.c. face nail 3" 14 gage staples, All crown 8-16d common (3 1/2" X 0. 162'); or Each side of end joint, face 12-10d box (3" x 0 128") or nail 13. Top plate to top plate, at end joints 12-3" 0.131" nails; or (minimum 24-" lap splice length 12-3" 14 gage staples, ?g" crown each side of end joint) I6d common (3 1/2" X 0. 162")_or 16"o. c. face nail 14. Bottom plate to joist, rim joist, band joist or blocking 16d box 3 1 2 X 0. 135T;­o� (not at braced wall panels) 3"x 0,131" nails; or 12"o.c. face nail 3" 14 gage staples, fi;" crown 2-16d common (3 1/2" X O. 1627'); or 15. Bottom plate to joist, rim joist, bond joist or blocking 3-16d box (3 1/2" x 0. 135"), or at braced wall panels 4-3" 0.131" nails; or Toenail 4-3" 14 gage staples, " crown 4-8d common (2 1/2" X 0.131");or 4-10d box (3" x 0.128");or Toenail 4-3" 0. 131" nails; or 4-3" 14 gage staples," crown 16. Stud to top or bottom plate 2-16d common (3 1/2" X 0.162");or 3-10d box (3" x 0.128");or 3-3" 0. 131" nails; or End nail 3-3" 14 gage staples," crown 2-16d common (3 1/2" X 0.162");or 3-1od box (3" x 0.128");or 17. fRepeoaetlottom plate to silud 3-3" O. 131" nails; or End nail 3-3" 14 gage staples, ?S" crown - _ 2--16d common (3 1/2" X 0.]6?_")or ; 18. Top plates, laps at corners and intersections 3-10d box (3" x 0.128");or 18. Top plates, laps at corners and intersections 3-3" 0. 131" na i 1 s; or Face nail 3-3" 14 gage staples, �" crown 2-8d common (2 1/2" X 0. 131"); or 19. 1" braceto each stud and plat 2-10d box (3" x 0.128");or 19, 1" brace to each stud and plat 2-3" 0.131" nails; or Face nail 3-3" 14 gage, staples, 1�" crown 20. 1"x6" sheathing to each bearing 2-8d common (2 1/2" X 0.131");or Face nail 20. 1"x6" sheathing to each bearing 3-IOd box (3" x 0.128");or 21. i x8 and wider sheathing to each bearing 3-8d common (2 1/2' X 0. 131"); or 21. 1"x8"and wider sheathing to each bearing 3-10d box (3" x 0.128");or nail _ Floor -Face 3-8d common (2 1/2" X 0.131");or 22. Joist to sill, top plate, or girder 3-10d box (3" x 0.128");or 22. Joist to sill, top plate, or girder 3-3" 0, 131" nails; or Toeno11 3-3" 14 gage staples, ?g" crown 8d common (2 1/2" X 0. 131"); or 23. Rim joist, band joist, or blocking to top plate, sill or 10d box (3" x 0. 128"); or @8heRifirgmiedj,bb&od joist, or blocking to top plate, sill or 3" 0.131" nails; or 6"a.c., toenail other framing below 3" 14 gage staples, ?g" crown 2-8d common (2 1/2" X 0.131");or 24. 1"x 6"subfloor or less to each joist 2-1Od box (3" x 0.128");or Face nail 25. 2" subfloor to joist or girder 2-16d common 3 1/2" X 0.162 Face nail 26. 2" lanks lank & beam - floor & roof' 2-16d common 3 1 2" X 0.162" Each bearing, face nail 32" o.c., face nail at top and 20d common (4"x 0.192") bottom staggered on opposite sides) 10d common 3 X 0.128 ;or 24" a.c., face nail at top and 27. Built-up girders and beams, 2. lumber layers 3"x 0.131" nails; or bottom 3" 14 gage staples, �" crown staggered on opposite sides) 2-20d common (4" X 0. 192") ; or 3-10d box (3" x 0.128");or Ends and at each splice, face 3-3" 0. 131" nails; or nail 3-3" 14 gage staples, ?6" crown 3-16d common (3 1/2" X 0. 162"); or 4-I0d box (3" x 0.128");or Each joist or rafter, face nail 28. Ledger strip supporting joists or rafters 4-3" 0.131" nails; or 4-3" 14 gage staples, ?6" crown 3-16d common (3 1/2" X 0.162");or 4-10d box (3" x 0.128");or End nail 29. Joist to band joist or rim joist 4-3" 0. 131" nails; or 4-3" 14 gage staples, �" crown 3-16d common (3 1/2" X 0.162");or 4-10d box (3" x 0.128");or End nail 30. Bridging or blocking to joist, rafter or 'truss 4-3" 0.131" nails; or 4-3" 14 gage staples, �g" crown Y1bzCt31 ssttrnitcilu a31 picuTFAIss (( j)„ suWRloariar„ rramclf coirdi iifttFffrJcrr vnUlll sdl tttdi t ttco flrrtamrii-rgq o7rcd p_urt.Yiku11t5sarancd wvsilll s4fog tt iirzgg ttco framing c framing a Edges intermediate (inches) supports (inches) 61 common or deformed (2" x 0.113") 6 12 sub Floor and we 10 onoPpr� g °bfdi'e(z �2 b./f 0.r113" 6 12 i��� a 31. 3/8 "- 1/2" 1i;;xH:113., R8H EHH88F 8R� w8i 9 l� 1i" 16 gage staple, ?g" crown 4 8 subfloor and wall 2�" x 0.113, nail (roof) 4 8 1 3/4"16 gage staple, J"cr-own(roof) 3 6 SO CG AtWAJNn (! 2/2'i /2x (c IC911),3 I'b�; or 8M RlT-fO6HFAUd( '2Apolt3i'°" SUBFLOOR AND 6 12 32. 19/32 "- 3/4" nail' or 19 �SL k�mfk 41re p�;ematr��raaMT113'Ll- _ QOgof-)ilrim AR�3O1>(30/§a8kq.;lka') nail 33. 7/8 - 11" r8d°Vdl`lormed (2 "x 0. 131" Other exterior wall sheathing 2R"x0.113"nai1; or 4 8 iTleQJPl�of n�r�Y31 3a. 7/8 *fibk}'board sheathing b dlomle �mgaq s pp elwi[�' or 1" Elea �2 ormec7 2 x 0. 131 Other exterior wan (4" X 0. 192"); or . i er oar s eaThing $L�7�3��°9�.�3113'z�Srl6Rfid19 nail 3 6 6?6,, hgRdjff�,,omp lli6),r?g" crown 3 6 fiberboard sheath n -I' �'09d structural panels, combination u�jr#dMgr un erlayment to framing - d-eamman--'-4=3 „ 0.1P2�`�xH or 36, 2 32afdbu srd sheathingb-£29dnl4dx((23'4/' Za<N- () �2 $Br-�'bRrtrWng�c�e 19��a{x16�,1 1"�FoWn 6 12 ' - -6d-fie-'-forme x -WUb7d­-s-tructuroI pone 1s, com in ion n a Troming r3 �, ,_ d common x 1 8' a 6 12 36. 3 4 and less Panel sidin 9 t c6dfrd�fidf9ned 2"xO. 113" 6 12 37, 7 8 "- 1" d s- " s n s'din 6 e r "x�. 1 83 6 12 d 8@PW19§'i(�-tie9id:c@ ing (2"X 9 1� 30. 1k2-z 11less dgjbme 2 1/2" x 0. 131-12BL Panel si ing o 4ia1'rrr�sion -resistant siding _or 6@FF@@}@R=F@@15E@Ri @&81fiq 6 12 WEl"1)3"e)r _ r+ SIR 39. 1/2, or less Interior pa (f)1:04") - t-a,^t -sTd-i-n gg $Q, ' �'8 „ 4(d2 c,'VylgibnX (cl. 42'i0",k; bk 080") ; or 48ldfdnirsbsidn-1re'a'kst r9t72c)sinq42. 602_ c14Q-2ti3'b).099"); or 6 12 '1n1S One Sa Or B --I n teF7S r e a 4d common (1 1/2"x 0.080"); or 6 12 41. 4d finish 1 i 2"x 0.072" 6d casing (2"x 0.099"); or 6 12 42 6d finish Panel su arts at 24" c Q 0 L c� C0 N 0 L O 0 U N N O Digitally signed by Thomas L Thomas L = Hanson:AO1410 Hanson:A01410D00000 D00000177EF31 A77EF31B4E000015AD Qf B4E000015ADA Date:2022.04.12 O J T 1 lI 14:37:29-04100' rlir l' f U ] �i 'w an ee \ . . allti 11 f,.. V� I �Y � �+ I IN I I � �C� I\ Y 11 rM® .o=��i =I I For S1: 1 inch = 25.4 mm ,. win1 U g i ltal Si n aloe nxl a. Nails spaced at 6 inches at intermediate supports where spans are 48 inches or more. For nailing of wood structural panel and Irintod oplesuFthi. luann of ..�% particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing. •lren<t�nnvderedvl,ncdanl �' 'O"� ._. b. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications. r,lledand [lie 'In atw-cmusthr Panel supports at 16 inches 20 inches if strength axis in the ion direction of the panel, unless otherwise marked).11:rilledonan}rlcctnulicrrl c. Wherepo rafter is fastened to on adjacent parallel ceiling joisg in accordance with this schedule and the ceiling joist is - ,_, to a fastened to the top plate in accordance with this schedule, the number of toenails in the rafter shall be permitted to be reduced by tpR=" ,z one nail. - Ii I W1 ® A. [M [7 au8 aF8-0E3/IT Of=a-05/2T 5F&-15/IT 5F`5-IE3/2T 4 ij ar-12-05/IT aF-12 -05/2T 5F12-IE3/IT 5F12-IE3/2T 7: ' r, aFI(o-OE3/IT &FIro-05/2T aFIro - IE3/]T aF10-15/2T 5 .I. F ORP10-05/1T 5fRr-10-05/2T OfRF-10-15AT *+ aF,F14-05/IT OFF14-05/2T 5RF10-15/2T j7 a OF20-OE3/IT OF20-05/2T OF20--15AT al`20-15/2T a'' L-IN'FEL 5ECTIONe 5fRFI5_i5/IT 1 all CE,5eE_[D LINT L SACI ION - SAFE (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. SAFE LATERAL LOADS FOR 8" PRECAST & PRESTRESSED U-LINTELS SAFE UPLIFT LOADS FOR 8" PRECAST & PRESTRESSED U-LINTELS 4=411mm SAFE LOAD PLF TYPE LENGTH 81J8 81`8 REINF* CMU* 2'-10"'34") PRECAST 1293 1642 2135 3'-6" (42") 1 PRECAST 1025 1024 1830 4'-0" (48") PRECAST 765 763 1365 4'-6" (54") PRECAST 592 5911 1057 5'-4" (64") PRECAST 411 411 734 5'- 10" (70") PRECAST 340 339 607 6'-6" (78") PRECAST I 507 721 483 7'-6" (90") PRECAST 424----534 _�357 9'-4" (112") PRECAST I 326 512 227 10'-6" (126") PRECAST 11'-4" (136") PRECAST 1 284 260 401 452 178 152 12'-0" (144") PRECAST 244 402 135 13'-4" (160") PRECAST 217 324 109 14'-0" (168") PRECAST 205 293 98 14'-8" (176") PRESTRESSED N.R. 284 89 15'-4" (i 84") PRESTRESSED 17'-4" (208") PRESTRESSED 19'-4" (232") PRESTRESSED 21'-4" (256") PRESTRESSED N.R. N.R. N.R. N.R. 259 194 148 125 82 63 51 r4 2 22'-0- (264") PRESTRESSED N.R. 116 39 24'--0" (288") PRESTRESSED N.R. 91 33 * SEE NOTE 18 CAST-C]'RETE HIGH 5TfRENC;;TH PRECAST LINTEL FILLED WITH GROUT SAFE LOAD - POUNDS PER LINEAR FOOT TYPE .LENGTH 8F8-1T 8F12-1T 81`16-1T 8F20-1T 8F24-1T 8F28-1T 8F32-1T 8F8-2T 8F12-2T 81`16-2T 8F20-2T 8F24-2T 8F28-2T 8F32-2T 2'-10"(34") PRECAST 1972 3173 4460 5747 7034 8321 9608 1972 3173 4460 5747 7034 8321 9608 3'-6" (42") PRECAST 1569 2524 3547 4569 5591 6613 7636 1569 2524 3547 4569 5591 6613 7636 4'-0" (48") PRECAST 1363 2192 3079 3966 4853 5740 6627 1363 2192 3079 3966 4853 5740 6627 4'-6" (54") PRECAST 1207 1940 2724 3508 4292 5077 5861 1207 1940 2724 3508 4292 5077 5861 5'-4" (64") PRECAST 1016 1632 2290 2949 3607 4265 4924 1016 1632 2290 2949 3607 4265 4924 5'- 10" (70 ") PRECAST 909 1492 2093 2694 3295 3897 4498 929 1492 2093 2694 3295 3897 4498 6'-6" (78") PRECAST 835 (12) 1340 1880 2419 2959 3498 4038 835 1340 1880 2419 2959 3498 4038 7'-6" (90") PRECAST 727 (23) 1021 1634(12) 2102 (11) 2571(1o) 3039(1o) 3508 (9) 727 1166 1634 2102 2571 3039 3508 9'-4" (112") PRECAST 591 680 1133(15) 1471 (15) 1811 (15) 2152(16) 2494 (15) 591 851 1326 1705 2084 2463 2842 10'-6" (126") PRECAST 530 552 1 914 (15) 1185(15)1 1458(15) 1732(n)j 2007 (15) 530 686 1183 1526 1865 2204 2544 11'-4" (136") PRECAST 474 485 798 (15) 1034(15) 1272(n) 1510 (15) 1749 (15) 494 599 1028 1422 1738 2053 2369 12'-0" (144") PRECAST 470 (9) 441 723 (14) 936 (4) 1151(15) 1366 (15) 1582(15) 470 1 543 928 1349 1649 1948 2247 1 13'-4" (160") PRECAST 418 (15) 373 606 (14) 783 (14) 962 (14) 1141(14) 1321(14) 428 455 770 1145 1444 1718 1993 14'-0" (168") PRECAST 384 (n) 346 559 (u) 723 (14) 887 (u) 1052(14) 1218 (14) 410 420 709 1050 1434 (8) 1694 (8) 1954 (7) 14'-8" (176") PRESTRESSED 239 323 519 (13) 671 (13) 823 (m) 976 (14)1 1129 (14) 246 1 390 655 968 1324 (8) 1625(11) 1874 (11) 15'-4" (184") PRESTRESSED 224 102 485 (13) 626 (13) 767 (13) 909 (13) 1052 (n) 230 364 609 897 1224 (8) 1562(14) 1801(14) 17'-4" (208") PRESTRESSED 187 255 404 (12) 520 (12) 637 (12) 754 (12) 872 (12) 192 303 500 732 993 (8) 1268(14) 1470(14) 19'-4" (232") PRESTRESSED 162 222 347 (11) 446 (ii)j 546 (12) 646 (12)j 746 (12) 166 261 424 616 831 (e) 1057(14) 1225(14) 21'-4" (256") PRESTRESSED 142 198 306 (11) 393 480 (11) 567 (11) 654 (11) 142 230 369 531 713 (7) 903 (13) 1046 (u) 22'-0" (264") PRESTRESSED 137 192 295 (io)I 378 461 (io) 545 (11) 629 (11). 137 221 354 508 681 (7) 861 (n) 997 (u) 24'-0" (288") PRESTRESSED 124 175 267 (io) 341 (io)j 416 (1o)l 491 (jo) 566 rya)124 200 316 450 1 600 (7)1 756 (121 875 m.. (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. #5 FEE3,4fR AS REQUIRED (2 MINIMUM) #5 REBAR IN VERTICAL GROUT FILLED CELL eO' ST,4N[)4FD NOOK 10" l`-1lNIl`-1UM (TYPICAL) C,4NT1LEVEf;P,EF_,) LINTEL DETAIL MASONRY TIES AS SPECIFIED CONCRETE FASTENERS SPLIT FACE WITH MINIMUM 4" MASONRY VENEER EMBEDMENT SPACED AS CONCRETE FASTENERS REQUIRED REQUIRED _ UA�)I-UHLIE U-LINTEL 4 4" FILLED w/ GROUT 4 CAST-CRETE LINTEL \CONTINUOUS FILLED WITH GROUT XCONTINUOUS SHELF ANGLE SHELF ANGLE SIZED AS REQUIRED SIZED AS REQUIRED VENEEF=, Sf=L IT FACE VENEE SAFE GRAVITY LOADS FOR 8" PRECAST w/ 2" RECESS DOOR U-LINTELS SAFE LOAD - POUNDS PER LINEAR FOOT TYPE LENGTH 8RU6 8RF6—OB BRF10—OB 8RF14—OB 8RF18-08 8RF22—OB 8RF26—OB 8RF30—OB 8RF6-1B 8RF10-1B 8RF14-1B 8RF18-18 8RF22-1B 8RI`26-113 8RF30-1B 4'-4" (52") PRECAST 1635 1749 3355 3280 4349 5421 6493 7567 1891 3699 5206 6639 8060 9479 10893 4'-6" (54") PRECAST 1494 1596 3063 2992 3968 4946 5924 6904 1756 3699 5206 6639 8060 9479 10893 5'-8" (68") PRECAST 866 920 1770 1716 2277 2839 3402 3966 1167 2481 4567 6389 8060(34) 7917(19) 9311(19) 5'- 10" (70") PRECAST 810 859 1653 1600 2124 2649 3174 3700 1113 2342 4242 6639 (1o) 8060(39) 7402(19) 8706 (19) 6'-8" (80") PRECAST 797 901 1825 3120 5048 7747 9448 7360 901 1825 3120 5048 7915 9479 10893(32) 7'-6" (90") PRECAST 669 755 1490 2459 3776 5743 7239 5623 755 1490 2459 3776 5743 8998(19) 10893(48) 9'-8" (116") PRECAST 411 466 999 1568 2253 3129 4091 3146 526 999 1 1568 1 2253 1 3129 4150 5891(4AI (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. NOTE: INFORMATION CONTAINED ON THIS SHEET PROVIDED BY AND PERTAINING TO CAST-CRETE CORP. ALTERNATE PRODUCTS OF EQUAL CAPACITY MAY BE USED. ALTERNATE PRODUCT MUST BE ACCOMPANIED BY F_ ENGINEERING DATA TO SUPPORT SUCH PRODUCT. ENGINEERING SPECIFICATIONS [�RypLIr,T DESCRIIPTIO�= High strength precast concrete lintels designed to be unfilled or filled to form a composite reinforced beam using concrete masonry units. MATERIALS • F'c &" precast lintels = 3500 P51 . Concrete masonry units (CMU) per A57M C9O with minimum net area • f'c 0" prestressed, b" and 12" precast lintels = 6000 psi compressive 61reneht = 1900 psi • f'c 4" precast lintels = 3000 psi . Rebar per ATM A615Grade 60 • Grout per A01M C416 fig = 3000 psi w/ maximum o Prestressing strand per 45TM A416 Grade 210 low relaxation 3/a inch aggregate and 0 to 11 inch slump. . 1/32 inch wire per A5TM A510 I. Mortar per A51TI C210 Type M or 5 GENERAL NOTES 1. Provide full mortar head and bed joints. Cast -in -place concrete may be provided in composite lintel in lieu of 2. 5hore filled Iin'66 as required. concrete masonry units. 3, installation of lintel must comply with architectural 9. Safe load ratings based on rational design analysis per AGI 310 and AGI 530 and/or structural drawings, 10. Product Approvals; Miami Bade County, Florida Nos. 03-0605,05 4, U-Lintels are manufactured with 5-1/2 inch lone notches at and 03-0605-04. Florida Certificate of Product Approval number FL150. ends to accomodate vertical cell reinforcing and grouting. ll. The exterior surface of lintels installed in exterior concrete masonry walls 5. Reference the CAST-CRETE Load Peflection Graph shall have a coating of stucco applied in accordance with A5TM C926 5roc4lre for lintel deflection information. or other approved coating. 6. 5ottom field added rebar to be located at the bottom 12. Lintels loaded simultaneously with vertical (gravity or uplift) and horizontal or lintel Cavity. (lateral) loads should be checked for the combined loading with the 1. 1/32 Inch diameter wire stirrups are welded to the bottom following equation: steel for mechanical anchorage. Applied vertical load +Applied horizontal load 1.0 Safe vertical load cafe horizontal load SAFE LOAD TABLE NOTES I I. All values based on minimum 4 inch nominal bearing. Exception: Safe loads for unfilled lintels must be reduced by 20 is if bearing length is less than 6-1/2 inches. 2. N.R. = Not Rated. 1 5afe loads are superimposed allowable load. 4, 5afe loads based on Grade 40 or Grade (oO field rebar. 5. Additional lateral load capacity can be obtained by the designer by providing additional reinforced masonry above the precast lintel. See Reinforced CMU or, Page 4. 6. One Ill rebar may be substituted for two S rebar5 in b" lintels only. 1. The designer may eyalute concentrated loads from the safe load tables by calculating the maximum resisting moment and shear at cl-away From the face of support. I(A=-4494" SAFE LOAD PLF TYPE REINF. LENGTH 8RU6 8RF6 CMU* 4' 4" (52") PRECAST 758 757 1365 4'-6" (54") PRECAST 694 693 1249 5'-8" (68") PRECAST 5'- 10" (70") PRECAST 6'-B" (80") PRECAST 408 382 595 407 381 1 788 734 687 510 7'-6" (9 0 ") PRECAST 509 674 393 9'-8" (116") PRECAST I 370 490 227 * SEE NOTE 18 0. For composite lintel heights not shown, use safe load from next lower height. 9. For lintel lengths not shown, use safe load From next longest length. 10. All safe loads in units of pounds per linear foot, 11. All 5afe loads based on simply supported span. 12. The number in the parenthesis indicates the percent reduction For grade 40 Field added rebar_ Example: T-b" lintel Type bF32-15 safe gravity load = 6412 (15) w/ 15% reduction =E 6412 (55) = 5501 P111 SAFE LOAD - POUNDS PER LINEAR FOOT i TYPE LENGTH 8RF6-1T 8RF10—IT 8RF14-1T 8RF18—IT 8RF22-1T 8RF26—IT 8RF30-1T 8RF6-2T BRF10-2T 8RF14-2T 8RF18-2T 8RF22-2T 8RF26-2T 8RF30-2T! 4'--4" (52") PRECAST 905 1748 2635 3522 4409 5296 6183 905 1748 2635 3522 4409 5296 6183 4'-6" (54") PRECAST 867 1675 2525 3374 4224 5074 5924 867 1675 2525 3374 4224 1 5074 5924 5'-8" (68") PRECAST 675 1301 1960 2618 3277 3935 4594 1 675 1301 1960 2618 3277 3935 4594 5'— 10" (7 0 "' PRECAST 655 1262 1900 2538 3176 3815 4453 655 1262 1900 2538 3176 3815 4453 6'-8" (80") PRECAST 570 1012 1651 2204 2758 3312 3865 570 1097 1651 2204 2758 3312 3865 7'-6" (90") PRECAST 506 797 1462 (B) 1952 2442 (6) 2931 (e) 3257 506 967 1462 1952 2442 2931 3421 9'-8" (116") PRECAST 3915 491 931 (12) 1301(15) 1640(15) 1980(15) 2322(16) 395 589 1 1135 1514 1893 2272 2652 J (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. Digitally signed by Thomas L Thomas H a n so n:AO 1410 Hanson:A01 41 ODOOOOO ei n­­­�id,­d k_jwd and 'nt, D00000177EF31 177EF31 134E00001 5ADA "ic"Iandthe i"J'atme mu'l 1� Date: 202 2.04. 12 134E0000 I 5ADA 14:38:12 -04'00' O CIL D 0 S1_ (D 0 C E 0 0 CN 0 n 01 0 - - - - - _f_ I 1 - - - - I I I — -1 - — I __ - 7 - - I CK:,A I'M "Alliance, T4" VINYL SOFFJT I7s41P1'pA.11' NOTE!, r ts3. v_ff1.._X7_T 11,11, NZA11 111�c_fqrWl as istfvf ort.1 c" Re ar it I N.1 ci (1w, t I e .as"fvv.",p J t­�A -lcz d-s7,irwj � Mtl wil ",omt" vi w"I 0 �b c ds kew, ftlts eyv�!,y 1, lo 21 0 A51',O +C'! WN1 r5C �ACI�c:f W� TABLE OF COWW5 3-Tif —dwal, I. . ........... . . Uc & FULL VENT GENTER-MENT 'S119JU111 �Ctr�'Af� D Or P7,C01XV NAIL 'TR f -,k �md i-x, 1. i N Wkj�, 4EY, SCIN Wr C ll 1al 11 Hi114 4 KNI. D ET A I L `C DETAR 'it)" C wifa i:lf _v i,Nbr. LXAAM 11 NN".t w CC I'll, N,�K xN­ 1!!� _-HOM SME VIEW SINGLE AN wi I-CHANNEILS . .. . .. .... .. . . .......... . ... .......... :-T 100.0 -49-0 if t vllX10 i"'I I'VfZ TV- it-_ T ts n r, 5 b i, PIZ[ 0- LAU! "ITNnE c X: 1, )y r Sir"j r 41 1 I 0 pAr" pmft x, f'A'r`a AWIF,,,�' -- -------- rxf- Ova:, 1k; 44 TEf wow I IWII ON, 1M_1iF1A1wi- s t r 0111_11M I 79M W ATT)"M 4 DID OF Zaii!"JA so=lrl pAi%fl (vF pf-'m %q Ihv P. GUT"S NAIK I-TITJ jqr.J& ,-zw mv. �n t� , e TKr;4�C,,q X oFF, cir PAR', UARM hF.411 rif) WC`! 15EL Ya wx DETAIL "C" a cll.c� 111MV-1 WCOV) DETAIL "A" V'Kiftw, N Aji. I. CCA WD V Mw r-*, LN�l XCfll F&WL Cf FACd KrF FANRI AT Al FACH R AMN Nff-t.7�71K,44 FAcR1_;1kvR4 MTKEC1014 ­ rF cs K 'N . ..... . .... . .... I j �J M.__u 3 L k. iS SIDE VIEW- SINGLtSPAN wj,.,3-C"ANNCL SWGU Mwqrof pC11Tihvf paga-ATN"r Vr c FAIPICI� M�_ 7 -i"M J Ot Rc"Wi x. wo's r- 12q-ait 7,iw lt­,tr,' wo ipwq 4vo rmccv_;nlou q 4 P'L-M'1721 1;4 ;4 J4, !7q dlf VIBR11 I R, - — --------- I Z7 j t I , rU k N 51,49 F5 1`45_41 t F ties: a k 1,3 LE ro.� ks r x s '.AK kwvl 41a 5f, 4 _0�% r I-, DETAIL "A" A�� i fI A.) 1 f4 1,�, P,3 i u flt_,t4 DETAIL "B" fli-A`IW t �f �'�R T NMI 0 C t IN % NG K11 Callff"100SRA11131 - DETAII "J" T I 5 f F Qf, I 'SUM MFM SIDE VIEW - DOUBLE SPA w BATTEN ... . ...... ..... .......... .... I)FTAR 'T DETAIL X' R,`L IV-�CfEA`­A 24 ArIG cc,.V­ IK1'l`Z i�:- 0 t r e IA; r_i` X, "g, Vl� r 6, AVI�AJAAL "f P�i%VL -5, wft MA HOW G, 2 �,p L t, In P.111 I 'Ffff- -4 MIFF U �Ml " L I T_9?`XiNSflRJ%` 67_,'­4` e t CW AVE 4 SOFFff A 0 �,A 5! 7 fou itkilil I.Cl 4.9% 1 1,WT NA, !_l*ixt P,-,: t_,! o — - - - - _-- - - 2.3 Jp 1 f" KC . .. . .... A, - A LUANCE fz RAW, Signed and caled he 1.1 � I fem-w P1 Digitally signed by Thomas L Thornas L plilllf!d copic,of 111i"I'millicilt Hanson:AO 1410 Hanson:A0141 OD000001 ... led iand the jpiawic niu,[ he 77EF31 B4E00001 5ADA D00000177EF31 co Date: 2022.04.12 B4EO00015ADA 14:30:51 -04'00' I - - --1— __ -T-1 T1 A I "A1,j j [0] 11 0 01k% 4 0O 1 MM 2 ff tTefl TLI "W W 1kjoSI l VIN 2 C LT/Wj I MY/A I lk _L Ak A, 'F'fR(_31DL_41CT AFF�OVAL GFEECIFICAT!ON SHEET MMA8 equired by Florida Statute 553-042 and Florida Administration Code 95-12, please provide the information and approval numbers an the building cornponert6 listed below if they will be utilized on the construction product For which you are applying For a building permit. We recommend you contact your local product supplier Should you not know the product approval number for any or the applicable listed products Category / Subcategory Manufacturer Product Description ,Approval Number(6) Test Pressures I- EXTERIOR DOORS A. SWINGING ThermaTru Fiberclassic FL 204(ol] +(0-1.0/-II per ThermaTru Smooth Star FL 21130-10 -rol'o psf ThermaTru Cla55!cCraft FL 28a97,14 +ro -1.0 / - (0 7.0 psf SLIDING t-11 UJInclows and Doors Series 420/430 FL 15332,1 FL 153273 +40.0 / -40.0 psf C. SECTIONAL Wayne -Dalton, a division of Overhead Door Corporation Model 08000/0100 111101 411104 S' Max width, 14' Max Height F1 0240,1 F1 a24& ,4 +22.1:� -2(o.3 sf +4(o.0 /-E,2,0 psf wayre-Dalton, a division of Overhead Door Corporation Model *IaOOO/0100 011211 - *11125 10' Max width, 14' Max HeightFl 02405 F-I a24a, e +IE�30 / -17.0 psf +411 /-52.0 psf D. OTHER 2, WINDOWS A. SINGLE HUNG MI Windows and Doors Series GA 155 Aluminum &H FL 321&E�A - FL 321053 +50,0 / -(01,0 Per MI Window& and Doors Series 1(o20 Vinyl SH FL 21(o3-1.1 FL 21(a3110 +50-0 / -61.0 per B. HORIZONTAL SLIDER MI Luindows and Doors Series H5 10a FL 15351-1 PL 15351,(o +50,0 -50'0 per MI Windows and Doors Series 1&30 Single Slider FL 21&30.1 FL 21&3,5-11 +50.0 -50.0 psf D. MULLION E. OTHER 13. PANEL WALL A. SIDING James Hardie Building f1robucts'Inc- Arti5ar@Lap 51dine FL 10411-1 5- SOFFITS Alside Solid and Vented! soffit FL 15212,1 - FL 15212-2 +10.0 __10'0 Per C. VINYL SIDING Certa-inteed Corp Siding F'roducts Certalli-Teed Vinyl Vinyl 5161ine +N1A1-1(o0,ro �4 ROOFING PRODUCTS !A, ASPHALT SHINGLES - Certain Teed Corporation CT20 (and AIR), Landmark 30 40 (and AIR,) XT30 (and AR) FL5444,1 N/A Metal R -aI Metal LA- t Union Corrugating Company Maaterf;;�ib Panel FLc3555,4 N/A 5. UNDERLAYMENT6 Tamko 151b Felt Underlaymert FL 12320,ro N/A G. ROOFING FASTENERS NOT USED D. ROOF VENTILATION Thompson Arch Metal Comp, off Ridge Vents F1_ 521e,1 - FL 5219_4 N/A GAF Attic, Ventilation Products vent fRvlo FL 02011 N/A E. ROOFING TILES Boral Tile I Villa e00 FL 7049,24 - FL 1049,2& N/A R OTHER j5. SHUTTERS IGlobal - Protection Products Galvanized Steel Storm flariela I FL 15016,1 - FL 15016.2 N/A NORM PANELS Global Protection Products Gfz)F Fabric Shutter Series 2000 FL 15000,1 N/A Town and Country Industries ISafty Edge Storm Panels FL 1285&,I I +54.0 / -54.0 psf co. oTRUGTUR�L C 0 MIN FOl 1 E N '16 Fasterfrie Specialists, Inc. Tie Max "Threaded Rool'' A. WOOD C-ONNEGTOR5 ANCHORS U&F:' Structural Corn, iSee chart Simpson Strong -Tie see chart 5- Tlue6 PLATES IITLU Building Components Alpine Truss Plates FL 1999.1 FL 19913.4 N/A MiTelk Industries, Inc. Truss Plates FL 21c3-1_1 FL 2191.5 N/A G. ENGINEERED LUMBER 5015e Eno Loob f-rod, Versa -Lam Sf=l FL 1644,1 N/A Boise Eng. Wood Prod. Wood-I-Jo-15ts ALL JOIST FL N/A Engineered lumber - TJI FL 1�30_1 - FL I ro 3 0.11 N/A Weyerhaeuser -Level Rim Board, LVL, F`&L, LSL FL II - FL &527-4 N/A D. MATERIAL Gast -Crete Corp, High Strength Concrete Lintels IFL 155,1 N/A Flowers Steel, inc., Rower Box Lintels FL 311S.] , 5450-1 11303,1 [, N/A A. SINGLE PLY ROOF SYSTEMS Mile -Hide Products Co, Inc- Thermoplastic. polyclefir single ply P L 12 1 -12,1 +N /A F;, 2 E� I roof Systems Sim Son Stock No, Florida Statewide Product Approval No. Evaluation Report Basis A23 FLI0446,11 ESR-2606 HU210-2 FL10531,9 E5R-2549 HUD212-2 1=1_10531_g E5R-25413 FLI0531.12 E&R-25413 HU25-2 FLIO531,e ESFR-2549 HU410 FLI0531.9 E5R-254e HU412 FL10531,9 E5R-25413 HUrofO 1=1_10531.9 E51R-2549 HrD412 FL14963 155R-2549 HDrolo FL14963 E51R-2549 HUCa410 FL1053I.9 5IM200004 HGAIOKT FL10446.16 SIM2OOaO3 HGAMIOKT FL11473,ro SIM200803 HCf'2 FLI0441.4 E51R-2551 HETAlro FL11413.4 SIM200002 HETA20 FL114134 SIM200002 HTTIro I'l-114133 ES-0130 HTT22 FL11413.5 ES-0130 HTSI& PLI1413.12 E6R-26I3 HT620 FL11413.12 ESIR-2613 HT524 F-L11413.12 E51R-2613 HT530 FL11413.12 E51R-2613 HTSM16 FI 114'13-12 5111200a02 HTSM20 FL11413.11 5IM200002 HGT2 FLIO,566.1 r=6R-2613 HGT3 FLI0066.1 E&R-2613 HU6210-2 FL10531,11 E.5R-25413 HU5212-2 FL10531.11 E51R-2549 HU52ro FL10531.11 E5R-25413 HU520 FLIO531.11 E51R-2549 HU52a-2 FL10531.9 E5R-2549 LU24 FLI0531.14 E8R-2549 LU2& FLI0531.14 E5R-254e LU5210-2 Fl-1o531.14 E6R-25413 LU524 FLIO531.lro E5R-2549 LU52ro FI-1053IJ6 E51R-2549 1-1.1526-2 FL10531,16 E5R-25413 LU52a FLI053TIra E5R-2549 LU646 FLI0531.16 ESR-25413 M5T&O FI-10456,20 E51`R-2105 L5TA12 FLI3&12,5 E5R-2105 L&TAI5 1=1_13012.5 E6R-2105 L&TAI& FL13512.5 E&R-2105 L5TA24 FL13812.5 ESR-2105 LSTA30 FL13&72,4 ESPI-2105 L5TA36 FL13a72-4 EeR-2105 LTT19 1=1_114136.5 ER-130 LTT205 FL1141365 ER-130 LTT131 FLI1496.5 ER-130 LT512 FL13512,5 E51R-2613 LGT2 FL11410.1 5IM2OOaO3 L630 FL10446.20 ESR-2606 A34 FL10446-1 E6R-260ro M5TA12 FL10456-21 E5R-2105 M5TA15 1=1_10456,21 ESIR-2105 M5TA15 FL1045ro,21 E51R-21OE3 MSTA24 FI_10456_21 E6R-2105 M5TA3ro FL1045621 E5R-2105 MSTC40 FL1045622 E81R-2105 M5TC52 FL1045622 EeR-2105 MT612 FL1045633 E51R-2613 MT516 FL1045ro.34 E5R-2613 MT510 FL1045635 E5R-2613 MTW20 FLI045636 ESIR-2613 MGT FLI3e04_B 511'1200a03 MBHA356/1125 PL13IE045 ESR-2(o16 M15H,43.56/16 Fl-1312045 EER-2616 ABU44 FL10060-2 E5R-1622 ABU6(o FL108602 ESR-1622 HDU2-SD52.5 FL10441.4 E5R-2330 GLTV3,516 FLIor0rC>_1Z ESR-2615 FGTR FL11413-2 5IM200002 C516 FL13512.1 r=6R-2105 1­41 1=104561 E6R-2roI3 Hio FL 10446fro E5R-2613 H10-2 FL 1044ro fro E5R-2613 H10A FL 1044ro fro E5R-2613 H3 FL10456.1 E5R-2613 H4 FLI04501 EBR-2013 HE, FLI0456.1 E51R-2613 H2.5 FL104E6.1 ESR-2613 H2_SA FLI04501 E51R-2613 Ha FL10456.1 5IM200003 SPI FI_1045&-R5 E5R-2613 5P2 FL.10456-R5 E51R-2613 61`14 FI_10450-R5 E8R-2613 spro F L 10 4 r: R-r;, E61R-2013 61"a F L 10 4 5 (o - R-5 ESIR-2613 5PH4 1=1_10456-R5 E5R-26I3 SPHro FL10456-R5 E51R-2613 SPHO FLI0456-F_5 E5R-2613 PqUS2a-2 FL1146B.1 ESR-2549 "HUS410 FL1146,5.1 E5R-2549 HGUS525/12 FL10531.4 5IM2OO8O4 14GU6414THID14414 FL10531.4 5IM200004 HDQa_5D53 I FL104413 ESR-2330 M5TAM24 PI-13512-4 5IM200802 MSTAM3ro FL13B12.9 6IM200802 M5TCM40 FL13812.13 5IM200002 HHETA20 FL 11413.1 5IM200002 LGT3-5D523 11413.5 5111200a03 I_CiUM26-2- FLl3c304_4 5IM200002 NSF Connector& USF Stock No. Florida statewide Product Approval No. Evaluation Rep ort Basis A3 FL11244.1 E-5IR-3455 HD210-2 FLI-1232.3 ESP-3445 HD212-2 FL112323 EFR-3445 HID216 FLI1232.3 EeR3445 HD216-3 FLI-12323 E61R-3445 HD26 FLI*1232.2 E51R-3445 HD20-2 FL11232,3 ESR-3445 HD410 FL17232,4 E5R-3445 HD412 FL11232.4 ESR-3445 HD&I0 PLI1232,4 EeR-3445 HDQ410 r-LI'122-1.2 ER-0201 W.iAIOKT FLI-1236.(o E5R-3445 HGAM10K7 Evaluation Report HHC,P2 FLI12361 E5R-3448 HTA16-15 FLI-1600.4 Evaluation Report HTA20-la FL11680.4 Evaluation Report HT7F7 FL1121IJ2 ER-0200 HTWI(o FLI1244,"l ESR-3455 HTW20 FLI12441 E5R-3455 HTW24 FLI1244.1 E5R-3455 HTW30 I'l-112441 E51R-3455 HTWMIro FL62232 Evaluation Report HTLLM20 FL6223.2 EO?R-3455 HUGT2 FL02233 Evaluation Report HUGT3 FL62233 Evaluation Report HU5210-2 FLI1232.5 ESIR-3455 HU6212-2 FL17232.5 HU626 FLI1232,o ESR-3455 HU628 FLI1232.ro EeR-3455 HU520-2 FLI1232,o E-5R-3455 JL24 FLI1232,10 ER-0201 JL26 FLI1232.10 ER-0201 JU-5210-2 FL11232J2 ESR-3445 JUS24 FL11232.13 E611R-3445 JU526 FLI1232J4 ESR-3445 JU526-2 FL11232.14 ESR-3445 JU52a FLI1232.14 E5R-3445 JU646 FLI1232.14 E5R-3445 KLEG3 FLI1241 E5R-3444 1<5T260 FL1-124414 ESR-3445 LSTA12 PLI1244,11 EeR-3445 L5TA15 PLI1244.11 ESIR-3445 L5TAla FLI1244,11 ESR-3445 LSTA24 FLI1244.11 E5R-3445 L5TA30 FL17244.11 E5R-3445 L5TA3ro FL11244,11 E5R-3445 LTSIS FL112192 FFR-0200 LT6205 rLI12192 ER-0200 LTTI3I FLI12192 ER-0200 LTW12 FL11244.19 E5R,-3455 LUGT2 FL112403 E5R-3441 MP3 FLI"124422 E5R,-3455 MF134 FLI1244-23 ESR-3455 MF14F F-1-11244.24 E5R-3455 MP5 FLI124425 E&R-3455 MPH3516 FLI1240.4 ESR-3441 M&T,412 FLI1244,11 F_ E51R­3455 M5TA15 FLI1244,11 l E5R-3455 1" I5TA15 FLI1244,11 E5R-3455 MSTA24 FLI1244]"I ESR-3455 MST,436 FLI1244.11 ESR-3455 MSTc4o FL17244,2-1 ESFR-3455 M5TC52 FL11244.21 ESR-3455 MTW12 FLI12441 ESR-3455 MTWIro FLI12441 E5R-3455 MTWIO FLI12441 EBR-3455 MTW20 FLI12441 E5R-3455 MUGT15 FL1124oe, ESIR-344-1 NFM35X12 FL5102 Evaluation Report NFM35X1(oU FL-51a3 I Evaluation Report PAU44 FLI1239.12 E6R-3449 FAU(oro FL11231312 ESR-3449 PHD2A FLI'12193 ER-0200 FHXU3516 PLI12412-1 EF?R-3444 RFU5 FL6223B Evaluation Report R15150 1=1_17244.2a E5R-.3455 RT15 FL1123(o.10 E5R-3448 RTI(a FLI-1236]1 E5R-3440 RT16-2 F-1-1-123roJI E5R-3440 RTI&A FLI-1236.11 E5R-3440 IRT3A FLI'1236.11 EeR-3448 RT4 FLI1230J0 ESR-3440 RT5 FLI1236,10 E5R-3445 RTI PLI1236.10 E5R-3448 RTIA FLI1236J0 ESR-344a RTOA FLI1236.10 E5R-344a 5FT22 FL11244,31 E51R-3455 5FIT24 FL1124431 ESR-3455 SPT4 SPT(o FLI124432 FL1124432 E51R-3455 E5R­3455 Sl'Ta FL1124432 EeR-3455 SPTH4 FL1124432 E5R-34E55 5FTH6 FLI124432 EeR_3455 5FTHO FLI124432 FSR-3455 5UH24 FLI1232J6 E6R-3455 THID20 FLI1232J9 EeR-3445 THD2a-2 FLI1232.19 E&R-3445 THD410 FL11232,19 E5R-3445 THED412 r-L11232.19 F-SR-3445 THID612 FL11232.I9 E5R-3445 THIDH414 FL17232J9 E51R-34415 UPHIDO r-L11219-15 ER-0200 U5C53 FL2033.2 Evaluation Report LJGT53F FL2033,2 Evaluation 'Report UGT,553 1=1_2033.2 Evaluation Report GEI FLI12411 GEL-1-22 PLI1241.1 E5R-1102 META, HETA, HHETA, and HETAL Embedded Truss Anchors. Embedded truss anchors are used to anchor a wood member (usually a truss) to masonry or concrete. Embedded truss anchors fasten to G single -ply wood truss with 0, 148" xl%" nails or Page 3 of 15 Simpson Strong -lie to a multi -ply truss with 0. 162"-3%" nails. META, HETA, and HHETA models can be installed in a single application or doubled to achieve additional capacity. They are embedded in the masonry or concrete to a depth indicated on the side of the anchor (4" for META, HETA, and HHETA, and 51 /16" for HETAL). The strop portion of the anchor is I"," wide. The anchors are manufactured from steel meeting ASTM A653 SS Grace 50, Class 1, with a G90 galvanized finish, with the exception of the HETAL truss seat which is manufactured from steel meeting ASTM A653 SS Grade 33 with a G90 galvanized finish. Steel thickness is as specified in Table 2. Embedded truss anchor fastener schedule, dimensions, and allowable loads are shown in Table 2 for single installations and Table 3 for double installations. See Figures 3 and 4 for additional details of single and double embedded truss anchors. TO RAFTER TO PLATES H10A - 9-0- 148" x 1 11112" 9-0. 148" X 1 11112" CARRYING MEMBER TOP FACE THA29 - 4=10d 6-10d Threaded Rod To Truss (QUALITY -DIAMETER) (QUALITY -TYPE) MGT - 1-5/8" 22-0. 148"x1-ill 1-5 8 22-0. 148 x 3 FASTENERS ANCHOR DIA,( IN.) NAILS( IN,) BOLTS QTY DIA. ABU66 - 5/8" 12-0. 162 x 3 112" 2 1/2 NAILS QTY-TYPE INTO THE POST AC6 - 8-16d 8-16d 14-16D 14-16D Thornas L Digitally signed by Thomas L Plilllcd 'opies (0-this&'Cument Hanson-AO1410 Hanson:AO 141 ODOOOOO mrc Imf C(msidcl c(tsigned,uld �A D00000177EF31 177EF31 134E00001 5ADA '('�Iled and theS 911atill, must t" Date: 2022.04.12 B4E00001 5ADA 14:29:59 -04'00' O 0 0 0 0 Q) 0 U 0 N IN n 0 U T --I- IT Ti____TT__ 1 - -I- I I l I I C C.J Gj 12 _.� „�..may �„�,,,•_ .; r.> - LEM Q oa QQ �o Q oQQ Q�d oQ��DQo Duo d, o b QpopoQb QQ �Dd Qobo 0 00 I 11N NN- - - FFE-1 0 CLCs. HCs7, WIN/DR HCzT. 0 2: .4' Q TABLE 1405.2 MINIMUM THICKNESS OF WEATHER COVERINGS _j COVERING TYPE MINIMUM THICKNESS (inches) Adhered masonry veneer 025 Aluminum siding 0,019 Anchored masonry veneer 2.525 Asbestos -cement boards 0.125 Asbestos shingles 0.156 Cold -rolled copper 0.0216 nominal Copper shinglesd 0.0162 nominal Exterior plywood (with sheathing) 0.313 Exterior plywood (without sheathing) See Section 2304.6 (HVHZ, see Section 2322) Fiber cement lop siding 0.25 c Fiber cement panel siding 0.25 c Fiberboard siding .05 Glass -fiber reinforced concrete panels 375 Hardboard siding c .025 High -yield copperd 0.0162 nominal Lead -coated copperd 0.0216 nominal Lead -coated high -yield copper 0.0162 nominal Marble slabs 1 Particleboard (with sheathing) See Section 2304. 6 ( HVHZ, see Section 2315.1.11) Particleboard (without sheathing) See Section 2304. 6(HVHZ, see Section 2315.1.11) Porcelain Tile 0.025 Precast stone facing 0.625 Steel (approved corrosion resistant) Stone (cast artificial anchored) 0.0149 1.5 Stone (natural) 2 Structural glass 344 Stucco or exterior Portland cement plaster Three -coat work over: Metal plaster base 0.875 b nominal Unit masonry 0.625 b nominal Cast -in -place or precast concrete 0.625 b nominal Two -coat work over: Unit masonry 0.5 'o nominal Cast -in -place or precast concrete 0.375 b nominal Terra cotta (anchored) 1 Terra cotto (adhered) 0.25 Q Vinyl siding 0.035 j 0.3-1-15 Wood shingles Wood siding (without sheathing) 0.5 For SI: 1 inch = 25. 4 mm. a. Wood siding of thicknesses less than 0.5 inch shall be placed ove-- sheathing that conforms to Section 23C4 r. 'HVHZ, see Section 2322; b. Exclusive of texture. c. As measured at the bottom of decorative grooves. d. 16 ounces per square foot for cold rolled copper and lead -coated copper,12 ounces per square foot for -topper shingles, nigh -yield :ngper and leadcoeted high -yield copper. SECTION R704 INSPECTION FOR TERMITES In order to provide for inspection for te­m,te in ,s'otion, ciea ,.,,e between exterior wall coverings and final eo to d- on the ext t,.. of a building shall not be less than 6 iriches Exceptions: 1. Paint or decorative cementitiou: iniu esa •.hors e inch (17. 1_ trim) thick adhered directly to the mason foundot`-on s dewall. 2. Access or vehicle ramps which rise to t're in�F or- `finish fl,c:or elevation for the width of such romps only. 3. A 4-inch (102 mm) inspection space above pat+c c•,d garage slabs and entry areas. 4. If the patio has been soil treated for termites, the finish elevation may match the building interior finish floor elevations on masonry construction only. 5. ''!asonry veneers constructed in accordance with section R318.4. i = FIBE1�Cx!-ASS SHINGLES CLCa. HGT, 1/4" TOOLED JOINT SMOOTH FINISH - BANDS E : LUIN/DR. H T. d CEMENT ( Q TEXTURED LH LLIO a FINISH LL 24 SH STUcco ROUGH FINISH N R F.F. ELEV. __ > Emn L E ''i 0 1 E CT 1 ,. S Ii;RC(j A IU _ �� ItV l .. lil Digitally signed by hornas L ISin_ aPt tt� ii-nllu- _n r Mil C� v � y Thomas L rintt i € l � � � r�.A 0 � 4 0 are not f,-red sl ,trio Hanson:A01410D00000 l.t'U lll IIIC hf�ll'I(l -l' 1' 11 � n a y�q9� b g `.a' D000001 %7EF31 177EF31B4E000015ADA venilcdon r, C a i ., Ld Date:2021.12,15 B4E000015ADA 08:48:09-05'00'