HomeMy WebLinkAbout4330 20th St (43)GENERAL NOTES SPECIAL INSPECTIONS DESIGN CRITERIA AND LOADS: 1. SPECIAL INSPECTIONS ARE REQUIRED ON THIS PROJECT PER CHAPTER 17 OF THE INTERNATIONAL GOVERNING CODES BUILDING CODE. 2. OWNER SHALL CONTACT THE STRUCTURAL ENGINEER OF RECORD FOR COPY OF STATEMENT OF 2020 FBC, 7TH ED. SPECIAL INSPECTIONS WHICH OUTLINES REQUIRED INSPECTIONS, ASCE STANDARD 7-16 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES" 3. THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS OR TESTING AGENCIES TO PROVIDE SPECIAL INSPECTIONS AS DESCRIBED HEREIN. THE OWNER SHALL BE RESPONSIBLE FOR AISC "MANUAL OF STEEL CONSTRUCTION", FIFTEENTH EDITION THE FEES AND COSTS RELATED TO THE PERFORMANCE OF SPECIAL INSPECTION SERVICES. ACI STANDARD 318-14 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" 4, REFERENCE PROJECT SPECIFICATIONS FOR ANY ADDITIONAL INSPECTION REQUIREMENTS. OSHA, OCCUPATIONAL SAFETY AND HEALTH REGULATIONS (STANDARDS - 29 CFR PART 1910) ASTM STANDARDS IN BUILDING CODES, VOLUME I AND II, LATEST EDITION AWS, AMERICAN WELDING SOCIETY STRUCTURAL WELDING CODE, AWS D1.1, LATEST EDITION DESIGN LOADS 1. LIVE LOADS (LU A. FLOOR LIVE LOAD: 100 PSF 2. SNOW LOAD: NOT APPLICABLE 3. EQUIPMENT LOADS: 95.92 KIPS (TOTAL WEIGHT) (REF KRONES DRAWING K-442-502-DBO, REVISION AO) A. BLOWING MODULE: 76.56 KIPS MAX FLOOR LOAD PER SUPPORT: 25.52 KIPS B. HEATING MODULE: 19,36 KIPS MAX FLOOR LOAD PER SUPPORT: 6.47 KIPS 4. WIND LOADS (W): a. GOVERNING CODE: ASC - 6 b. BUILDING RISK CATEGORY: c. BASIC WIND SPEED (3-SEC GUST), V: 137 PH d. WIND EXPOSURE CLASSIFICATION: C e. INTERNAL PRESSURE COEFFICIENT: ±0.18 f. COMPONENTS AND CLADDING: 20 PSF 5. SEISMIC LOADS (E): a. GOVERNING CODE: ASCE 7-16 b. BUILDING RISK CATEGORY: II c. le (SEISMIC IMPORTANCE FACTOR): 1.0 d, Ss (0.2 SEC SPECTRAL ACCELERATION): 0.058 e. S1 (1,0 SEC SPECTRAL ACCELERATION): 0,032 f. SOIL SITE CLASSIFICATION: E g. SPECTRAL RESPONSE COEFFICIENTS: SDS = 0,092/ SD1 = 0.089 h. SEISMIC DESIGN CATEGORY: B i. BASIC SEISMIC -FORCE RESISTING SYSTEM: STEEL SPECIFICALLY NOT DESIGNED FOR SEISMIC j. Cs (SEISMIC RESPONSE COEFFICIENT): 5 k. R (RESPONSE MODIFICATION FACTOR): 3.0 m. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE PROCEDURE 6. ICE LOADS: NOT APPLICABLE 7, FLOOD LOADS: NOT APPLICABLE 8. SPECIAL LOADS: NOT APPLICABLE 9. FUTURE LOADS: UNLESS SPECIFICALLY NOTED, THERE ARE NO PROVISIONS MADE FOR FUTURE FLOOR, ROOF, OR OTHER LOADS. GENERAL 1. WHERE REFERENCE IS MADE WITHIN THESE GENERAL NOTES, DESIGN DRAWINGS, OR SPECIFICATIONS TO "OWNER'S REPRESENTATIVE", SUCH REFERENCE SHALL REFER: FIRST TO THE OWNER, SECOND TO THE DESIGN ENGINEER, AND THIRD TO A REPRESENTATIVE APPOINTED BY THE OWNER OR DESIGN ENGINEER. 2. WHERE A SECTION IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL LIKE AND SIMILAR CONDITIONS. 3, WHERE REFERENCE IS MADE WITHIN THESE GENERAL NOTES, DESIGN DRAWINGS, OR PROJECT SPECIFICATIONS TO TRADE NAME PRODUCTS OR MANUFACTURER'S NAMES, SUCH REFERENCES ARE MADE TO DESIGNATE AND IDENTIFY QUALITY OF MATERIAL TO BE FURNISHED, ALL "OR EQUAL" MATERIAL SUBSTITUTIONS SHALL BE APPROVED BY OWNER'S REPRESENTATIVE, 4, ANY APPARENT CONFLICTS BETWEEN PLANS, SECTIONS, DETAILS, OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF OWNER'S REPRESENTATIVE IMMEDIATELY FOR CLARIFICATION AND WRITTEN RESOLUTION. 5, PRIOR TO COMMENCEMENT OF WORK, INCLUDING DETAILING, CONTRACTOR SHALL FIELD VERIFY ALL INDICATED RELEVANT DIMENSIONS OF EXISTING STRUCTURES, ELEVATIONS, EXISTING MEMBER SIZES, AND EXISTING CONDITIONS. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY INTERFERENCE. 6, THE STRUCTURE SHOWN HEREIN HAS BEEN DESIGNED TO RESIST LOADS ONLY AS A COMPLETED STRUCTURE. APPLICATION OF CONSTRUCTION LOADS TO THE PARTIALLY COMPLETED STRUCTURE SHALL BE CONSIDERED BY THE CONTRACTOR AND SO INCLUDED IN THE DESIGN OF SHORING, BRACING, FORMWORK, AND OTHER SUPPORTING ELEMENTS PROVIDED FOR CONSTRUCTION OF THE STRUCTURE. 7, THE DESIGN, ADEQUACY, AND SAFETY OF ERECTION BRACING, TEMPORARY SUPPORTS, ETC, IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 8. PROVIDE ADEQUATE STRUCTURAL FRAMING AS APPROVED BY THE ENGINEER FOR ALL REQUIRED MECHANICAL OPENINGS THROUGH SLABS, WALLS, FLOOR DECK, ETC. SUPPORT ALL MECHANICAL EQUIPMENT, OPENING SHALL NOT BE PERMITTED THROUGH STRUCTURAL MEMBERS UNLESS SPECIFICALLY DETAILED BY THE ENGINEER. 9. UNDERGROUND FACILITIES NOT SHOWN ON EXISTING DRAWINGS MAY EXIST, THE CONTRACTOR SHALL PROCEED WITH CAUTION DURING DEMOLITION AND/OR NEW CONSTRUCTION. UNIDENTIFIED PIPES, CABLES OR OTHER ITEMS ENCOUNTERED SHALL BE REPORTED IMMEDIATELY TO THE OWNER'S REPRESENTATIVE AND DISPOSITION MADE AS DIRECTED. 10. FIT -UP OF ALL NEW CONSTRUCTION TO ANY AND ALL EXISTING CONSTRUCTION SHALL BE THE CONTRACTOR'S RESPONSIBILITY. 5. UPON COMPLETION OF ALL SPECIAL INSPECTIONS AND TESTING, THE STRUCTURAL ENGINEER OF RECORD SHALL SUBMIT TO THE OWNER A FINAL REPORT OF SPECIAL INSPECTIONS. FOUNDATIONS 1. THE OWNER'S REPRESENTATIVE SHALL MONITOR ALL SITE PREPARATION, INCLUDING EXCAVATION, SUB GRADE PREPARATION, AND BACKFILLING. ALL EARTHWORK SHALL BE BASED ON THE APPLICABLE GEOTECHNICAL REPORT IF SUPPLIED BY THE OWNER'S REPRESENTATIVE. THE CONTRACTOR SHALL OBTAIN A COPY OF THE REPORT FOR REVIEW AND A COPY SHALL BE MAINTAINED IN THE FIELD OFFICE AT ALL TIMES. 2, ALL BACKFILL MATERIAL SHALL BE SOIL OR SOIL -ROCK MIXTURE THAT IS FREE FROM ORGANIC MATTER OR OTHER DELETERIOUS SUBSTANCE. BACKFILL SHALL CONTAIN NO ROCKS OR LUMPS OVER 6 INCHES IN GREATEST DIMENSION. NOT MORE THAN 15% OF THE ROCKS SHALL BE LARGER THAN 2,Y2" IN GREATEST DIMENSION. BACKFILL SHALL HAVE A LIQUID LIMIT LESS THAN 50, A PLASTICITY INDEX LESS THAN 30, AND A STANDARD PROCTOR MAXIMUM DRY DENSITY (ASTM D698) OF AT LEAST 90 PCF. GENERALLY SOILS CLASSIFIED AS SM, SC, ML, OR CL ACCORDING TO THE UNIFIED SOIL CLASSIFICATION SYSTEM ARE SUITABLE. ALL BACKFILL MATERIAL SHALL BE APPROVED BY THE OWNER'S REPRESENTATIVE. 3. ALL BACKFILL SHALL BE COMPACTED AT MOISTURE CONTENTS WITHIN 3% OF THE STANDARD PROCTOR OPTIMUM MOISTURE CONTENT. IF WET CONDITIONS RESULT IN SUBSURFACE PUMPING THE SUB GRADE SHALL BE STABILIZED BY MEANS APPROVED BY THE OWNER'S REPRESENTATIVE, OR THE PUMPING MATERIAL SHALL BE REMOVED AND REPLACED WITH APPROVED COMPACTED DRY BACKFILL, 4, ALL BACKFILL WITHIN THE LIMITS OF FOUNDATIONS SHALL BE PLACED IN LOOSE LIFTS OF 8 INCH MAXIMUM THICKNESS AND COMPACTED TO NOT LESS THAN 95% OF STANDARD PROCTOR MAXIMUM DRY DENSITY (ASTM D698). THE UPPER ONE FOOT OF BACKFILL MATERIAL SHALL BE COMPACTED TO 98% COMPACTION, ADDITIONALLY THE UPPER 8 INCHES OF SUB GRADE MATERIAL IN AREAS AT -GRADE OR CUT SURFACES SHALL BE SCARIFIED AND COMPACTED TO 98% COMPACTION. 5. ALL BACKFILL OUTSIDE THE LIMITS OF FOUNDATIONS AND PAVEMENTS SHALL BE PLACED IN LOOSE LIFTS OF 8 INCH MAXIMUM THICKNESS AND COMPACTED TO NOT LESS THAN 95% OF STANDARD PROCTOR MAXIMUM DRY DENSITY (ASTM D698). 6. IN -PLACE COMPACTION TESTS AND MOISTURE CONTENT TESTS SHALL BE PERFORMED FOR EACH VERTICAL FOOT OF BACKFILL PLACED WITH THE FOLLOWING TEST FREQUENCY: a. PAVEMENT = 1 TEST PER 5000 SQUARE FEET. b. STRUCTURES = 1 TEST PER 2000 SQUARE FEET. c. ISOLATED FOOTINGS = 1 TEST PER LIFT, 7. ALL TESTS SHALL BE CONDUCTED BY AN INDEPENDENT TESTING LABORATORY APPROVED BY THE OWNER'S REPRESENTATIVE, THE COST OF THE TESTS SHALL BE PAID BY THE OWNER, 8. ALL PIERS SHALL BE SUPPORTED ON SOIL WITH AN ALLOWABLE SOIL BEARING PRESSURE OF 2000 PSF. CONTRACTOR SHALL VERIFY CAPACITY OF ALL SHALLOW FOUNDATION EXCAVATIONS WITH A HAND PENETROMETER OR MECHANICAL CONE PENETROMETER TEST PER ASTM D 3441-05 PRIOR TO CONCRETE PLACEMENT TO ENSURE BEARING IN SUITABLY STRONG AND STABLE SOILS. IF REQUIRED, OVER EXCAVATION OF UNSUITABLE MATERIAL AND SUBSEQUENT BACKFILLING SHALL BE PERFORMED BY THE CONTRACTOR. 9. CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING OF ALL FOUNDATION EXCAVATIONS PER OSHA REGULATIONS. DESIGN OF ALL SHORING IS THE CONTRACTORS RESPONSIBILITY. ANCHOR BOLTS AND OTHER EMBEDDED ITEMS 1. ALL ANCHOR BOLTS AND THREADED RODS SHALL CONFORM TO ASTM F1554-07ae1 AND SHALL HAVE A MINIMUM STRENGTH OF 36KSI (UNLESS NOTED OTHERWISE), AND SHALL BE HOT -DIPPED GALVANIZED PER ASTM A153-09. 2. THE LOCATION OF ANCHOR AND FOUNDATION BOLTS MUST NOT VARY FROM THE DIMENSIONS SHOWN ON THE DESIGN DRAWINGS BY MORE THAN THE FOLLOWING: a. %" CENTER TO CENTER OF ANY TWO BOLTS WITHIN AN ANCHOR BOLT GROUP. AN ANCHOR BOLT GROUP IS DEFINED AS THE SET OF ANCHOR BOLTS THAT RECEIVES A SINGLE FABRICATED STEEL SHIPPING PIECE. b. %" CENTER TO CENTER OF ADJACENT BOLT GROUPS. C. MAXIMUM ACCUMULATION OF PLUS -OR -MINUS Y" ALONG A MINIMUM 100 FOOT LONG COLUMN LINE OF MULTIPLE ANCHOR BOLT GROUPS, d. ELEVATION OF TOP OF ANCHOR BOLTS PLUS -OR -MINUS Y 3. ALL ANCHORS AND EMBEDDED ITEMS REQUIRED FOR ADJOINING WORK OR ITS SUPPORT SHALL BE PLACED PRIOR TO CONCRETING. CONCRETE 1, ALL CONCRETE DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI STANDARD 318-14, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" (UNLESS NOTED OTHERWISE). 2. REFERENCE PROJECT SPECIFICATION OR OWNER'S SPECIFICATIONS FOR CAST -IN -PLACE CONCRETE IF APPLICABLE. 3. MINIMUM ULTIMATE CONCRETE COMPRESSIVE STRENGTH (F'c) SHALL BE 4500 PSI IN 28 DAYS (UNLESS NOTED OTHERWISE). 4, USE OF DIFFERENT CONCRETE CLASSES OF CONCRETE SHALL BE AS SHOWN BELOW, CONCRETE BATCH DESIGN(S) SHALL BE PROPORTIONED AND PRODUCED IN ACCORDANCE WITH ACI 318-14 AND ACI 301-10. SEE CONCRETE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS, MATERIAL PROPERTIES, AND NECESSARY INSPECTIONS/TESTING. F'c = 3000 PSI MINIMUM - ALL CONCRETE FOR SLABS OVER METAL DECK, RETAINING WALLS, BEAMS, COLUMNS, AND FOOTINGS, AND ALL CONCRETE NOT SPECIFICALLY COVERED. F'c = 4000 PSI MINIMUM - ALL CONCRETE FOR EXTERIOR GRADE SUPPORTED SLABS. 5. PORTLAND CEMENT SHALL CONFORM TO ASTM C150 TYPE I OR II. FLYASH SHALL BE LIMITED TO 100 LBS. MAXIMUM PER CUBIC YARD OF CONCRETE. 6. AGGREGATES, BOTH COURSE AND FINE, SHALL CONFORM TO ASTM C33, MAXIMUM LARGE AGGREGATE SIZE SHALL BE 1Y2" (UNLESS NOTED OTHERWISE), 7. CONCRETE MIX DESIGN SHALL ADHERE TO MINIMUM REQUIREMENTS FOR CONCRETE EXPOSURE CLASS F2 AS SHOWN IN ACI 318-14 TABLE 19.3.2.1. 8. CONCRETE SLUMP RANGE SHALL BE: 3-5 INCHES FOR FOUNDATIONS, BEAMS, AND COLUMNS; AND 2-4 INCHES FOR SLABS AND PAVEMENTS. 9. ALL CONCRETE SHALL BE AIR ENTRAINED. AIR ENTRAINING ADMIXTURE SHALL CONFORM TO ASTM C260. AIR CONTENT SHALL BE IN ACCORDANCE WITH ACI 318-14 SECTION 193. 10. WATER -REDUCING, RETARDING, AND ACCELERATING ADMIXTURES SHALL CONFORM TO ASTM C494. 11, MAXIMUM CONCRETE WATER/CEMENT RATIO SHALL BE IN ACCORDANCE WITH ACI 318-14 SECTION 19.3. 12. CALCIUM CHLORIDE, THIOCYANATES, OR ADMIXTURES CONTAINING MORE THAN 0.5% CHLORIDE IONS ARE NOT PERMITTED. 13. HOT WEATHER CONCRETING SHALL CONFORM TO ACI 305, LATEST EDITION. 14. COLD WEATHER CONCRETING SHALL CONFORM TO ACI 306, LATEST EDITION. 15. REINFORCING STEEL SHALL CONFORM TO THE LATEST STANDARDS OF ASTM A615, NEW BILLET STEEL, GRADE 60. ALL REINFORCING SHALL BE DETAILED AND PLACED ACCORDING TO THE LATEST STANDARDS OF THE AMERICAN CONCRETE INSTITUTE, REINFORCING STEEL SHALL BE FREE OF RUST, SCALE, OR ANY OTHER FOREIGN MATERIAL PRIOR TO PLACING CONCRETE. 16. HOOKS SHOWN AT THE END OF REINFORCING BARS SHALL BE "STANDARD HOOKS" PER THE AMERICAN CONCRETE INSTITUTE, UNLESS NOTED OTHERWISE ON THE DESIGN DRAWINGS. 17. REINFORCEMENT EMBEDMENT LENGTHS OR LAP SPLICES FOR REINFORCING SHOWN CONTINUOUS ON THE DESIGN DRAWINGS SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE. BAR SIZE CLASS "B" LAP CLASS "B" LAP EMBEDMENT EMBEDMENT SPLICE FOR SPLICE FOR (INCHES) WITH STANDARD DEFORMED EPDXY HOOK (INCHES) PLAIN BAR COATED BAR (INCHES) (INCHES) #4 25 37 19 12 #5 31 47 24 12 #8 62 93 48 19 SPLICE AND EMBEDMENT LENGTHS SHOWN ABOVE MUST BE INCREASED BY 30% FOR HORIZONTAL REINFORCING WHERE THERE IS MORE THAN 12 INCHES OF CONCRETE BELOW THE BAR. THE ABOVE TABLE IS BASED ON F'c = 4000 PSI CONCRETE, ABSOLUTELY NO WELDING OF REINFORCING BARS OR TORCHING TO BEND REINFORCING BARS SHALL BE ALLOWED. 18. WHEN REINFORCING IS CUT AT OPENINGS, ALL CUT REINFORCING SHALL BE MATCHED WITH CORRESPONDING EXTRA BARS PLACED PROPORTIONATELY AT SIDES OF OPENING, THIS SHALL APPLY TO ALL OPENINGS OVER 10 INCHES IN DIAMETER OR 10 INCHES SQUARE. THIS SHALL APPLY WHETHER EXTRA REINFORCING IS SHOWN ON THE STRUCTURAL DRAWINGS OR NOT. THE RESULTANT BAR SPACING SHALL BE A MINIMUM OF 3 INCHES, THE LENGTH OF THE EXTRA BARS SHALL BE AT LEAST THE LENGTH OF THE OPENING PLUS TWICE THE SPLICE LENGTHS GIVEN IN THE TABLE ABOVE, 19. MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE 2 INCHES (UNLESS NOTED OTHERWISE). 20. WHERE CONCRETE IS POURED DIRECTLY ON THE GROUND, MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE 3 INCHES (UNLESS NOTED OTHERWISE), 21. MINIMUM CONCRETE CLEAR COVER SHALL BE AS FOLLOWS: INTERIOR SLABS ON GRADE - TOPS %" INTERIOR SLABS ON GRADE - BOTTOM 2" EXTERIOR SLABS ON GRADE - TOPS 11/2" EXTERIOR SLABS ON GRADE - BOTTOM 2" PIERS - TOPS 2" PIERS - BOTTOM 3" PIERS - SIDES 3" OTHER COVER REQUIREMENTS SHALL BE AS NOTED IN APPLICABLE DETAILS OR AS SPECIFIED IN ACI 318-14. 22. MOISTURE BARRIER SHALL BE 6-MIL POLYETHYLENE FILM. SEAMS SHALL BE LAPPED A MINIMUM OF 12 INCHES AND GLUED OR TAPED. 23. BONDING AGENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS. AGENTS SHALL BE AS FOLLOWS OR EQUAL: ACRYLIC LATEX: INTRALOK -- BY W. R. MEADOWS ACRYL 60 -- BY THORO SYSTEMS ACRYLBOND 60 -- BY LAMBERT EPDXY: SIKADUR 32 HI -MOD -- BY SIKA CORPORATION MASTEREMACO ADH 326-- BY MASTER BUILDERS P� LAND S�( i��// "Professional Certification. I hereby certify that these 6F �\ 9p i� documents were prepared or approved by me, and that zz No. 90224 I am a duly licensed professional engineer under the laws of the - o a 0 State of Florida, License No. 90224 I 1 REVISION NO CDC O1/29/21 Expiration Date: 2-08-23 0 ISSUE FOR CONSTRUCTION CDC 01/22/21 at�i9�il REV. DESCRIPTION DRWN APPR DATE REV. DESCRIPTION DRWN APPR DATE DRAWING NO, REFERENCE DRAWING CONCRETE (CONTU 24, CONCRETE FORMWORK SHALL CONFORM WITH ACI 301-10 AND APPLICABLE SECTIONS OF ACI 347, LATEST EDITION, CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FORMWORK DESIGN, 25. ALL EXPOSED CONCRETE CORNERS SHALL HAVE A 3/4" BY 45 DEGREE CHAMFER. 26. BAR SUPPORT ACCESSORIES SHALL BE PROVIDED IN ACCORDANCE WITH THE LATEST ACI. MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES, EXCEPT THAT REINFORCING SHALL BE CHAIRED ON THE BOTTOM AND/OR SIDES ON BOLSTERS SPACED NOT MORE THAN 4 FEET ON CENTER. BAR SUPPORTS FOR CONCRETE EXPOSED TO VIEW SHALL HAVE PLASTIC COATED LEGS. BAR SUPPORTS SHALL BE LOCATED AGAINST THE OUTERMOST BAR. 27. FOR GRADE SUPPORTED SLABS, SLAB REINFORCING SHALL BE HELD IN PLACE BY BAR SUPPORTS AND ACCESSORIES AS DESCRIBED IN CHAPTER 3 OF THE CRSI MANUAL OF STANDARD PRACTICE. BAR SUPPORTS SHALL BE SPACED A MAXIMUM OF 4'-0" O.C. BOTH WAYS IN STRAIGHT LINES ON THE MESH GRID. NO ROCKS, CMU, CLAY, TILE, OR BRICK SHALL BE USED TO SUPPORT REINFORCING. 28, INSTALL CORNER BARS AT JUNCTION OF ALL FOUNDATION WALLS, GRADE BEAMS, AND FOOTINGS. 29. ALL ITEMS EMBEDDED IN CONCRETE SHALL BE TIED AND SECURED PRIOR TO PLACEMENT OF CONCRETE. NO "WET STICKING" IS ALLOWED. 30, ALL CONCRETE WORK SHALL CONFORM WITH THE FOLLOWING: ACI 318-14 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" ACI 301-10 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS" CRSI "MANUAL OF STANDARD PRACTICE" 31. PRIOR TO PLACING CONCRETE, THE CONTRACTOR SHALL VERIFY SIZE AND LOCATION OF ALL ANCHOR BOLTS, EMBEDDED ITEMS, OPENINGS, ETC, WITH THE LATEST CERTIFIED INFORMATION, INCLUDING APPLICABLE EQUIPMENT DRAWINGS. ANY DISCREPANCIES SHALL BE REPORTED TO THE OWNER'S REPRESENTATIVE BEFORE COMMENCING CONCRETE PLACEMENT. ALL AREAS TO RECEIVE CONCRETE SHALL BE INSPECTED AND APPROVED BY OWNER'S REPRESENTATIVE PRIOR TO POURING OF CONCRETE, 32. CONCRETE SHALL BE TRANSPORTED FROM THE MIXER TO THE PLACE OF FINAL DEPOSIT BY METHODS THAT PREVENT SEGREGATION OR LOSS OF INGREDIENTS AND DISPLACEMENT OF STEEL. CONCRETE MUST BE PLACED WITHIN 1Y HOURS AFTER ADDITION OF MIX WATER. NO WATER SHALL BE ADDED TO CONCRETE AFTER SLUMP TESTS HAVE BEEN PERFORMED, 33. DURING AND IMMEDIATELY AFTER PLACING, CONCRETE SHALL BE THOROUGHLY COMPACTED BY MECHANICAL VIBRATION, AS APPROVED BY OWNER'S REPRESENTATIVE, TO PROVIDE A DENSE CONCRETE FREE OF HONEYCOMBING, 34, CONSTRUCTION JOINTS AND POINTS OF ENDING A CONCRETE POUR SHALL BE AS SHOWN ON THE DRAWINGS OR AS OTHERWISE DIRECTED BY THE OWNER'S REPRESENTATIVE. 35. ALL CONSTRUCTION JOINTS SHALL BE THOROUGHLY CLEANED AND FREE OF LAITANCE BEFORE THE SECOND POUR IS MADE AGAINST THE FIRST POUR. 36. EXTERIOR SLABS AND INTERIOR SLABS IN WET AREAS SHALL RECEIVE A LIGHT BROOM FINISH. INTERIOR SLABS IN VERY DRY AREAS SHALL RECEIVE A STEEL TROWEL FINISH. 37. FLOOR FLATNESS AND FLOOR LEVELNESS SHALL BE AS FOLLOWS: SPECIFIED FLOOR FLATNESS AND LEVELNESS FF45/FL35 MINIMUM LOCAL FLOOR FLATNESS/LEVELNESS FF35/FL25 38. PREMOLDED EXPANSION JOINT MATERIAL SHALL CONFORM TO THE REQUIREMENTS OF ASTM D994 AND D1751. 39. JOINT SEALANT MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS. JOINT SEALANTS SHALL BE AS FOLLOWS OR EQUAL: POLYURETHANE 2 COMPONENT = MM-80 SEM-RIGID EPDXY JOINT FILLER -- BY METZGER McGUIRE POLYURETHANE 2 COMPONENT = SIKAFLEX 2C NS/SL -- BY SIKA CORPORATION COAL/TAR URETHANE = GARDOX -- BY W. R. MEADOWS 40. CONCRETE SLABS SHALL BE CURED FOR SEVEN (7) DAYS AS OUTLINED IN ACI 308, LATEST EDITION. 41. FOR SLAB SURFACES NOT SCHEDULED TO RECEIVE FLOORING, IMMEDIATELY AFTER SEVEN (7) DAYS WET CURE, APPLY ONE (1) COAT SEALHARD CHEMICAL HARDENER AS MANUFACTURED BY L&M CONSTRUCTION CHEMICALS OR APPROVED EQUAL. APPLICATION OF HARDENER TO CONFORM WITH THE MANUFACTURER'S WRITTEN RECOMMENDATIONS. 42. DIRECTLY AFTER FORMS HAVE BEEN REMOVED, ALL EXPOSED TIE WIRES AND STAPLED ENDS SHALL BE REMOVED BELOW THE CONCRETE SURFACE FROM EXPOSED CONCRETE SURFACES. CUT TIES FLUSH WITH CONCRETE SURFACES FROM NON -EXPOSED CONCRETE SURFACES. RUB SMOOTH OR CUT OFF FINS AND ROUGH PLACES, REMOVE ALL LOOSE CONCRETE AND OTHER IRREGULARITIES WITH CEMENT MORTAR. ON SURFACES TO BE EXPOSED, CORNERS AND ARISES SHALL BE STRAIGHT AND TRUE. AN APPROVED BONDING AGENT SHALL BE USED FOR PATCHING AND FILLING. 43. CONCRETE SHALL BE SAMPLED IN ACCORDANCE WITH ASTM C172-04. TEST CYLINDERS SHALL BE MADE IN ACCORDANCE WITH ASTM C31 AND TESTED IN ACCORDANCE WITH ASTM C39. SLUMP TESTS SHALL BE PERFORMED IN ACCORDANCE WITH ASTM C143. AIR CONTENT SHALL BE MEASURED IN ACCORDANCE WITH ASTM C173 OR C231, CONCRETE TEMPERATURE SHALL BE MEASURED IN ACCORDANCE WITH ASTM C1064, ALL TESTING SHALL BE PERFORMED BY AN INDEPENDENT TESTING AGENCY PER ASTM E329. THE CONTRACTOR SHALL PAY THE COST OF THE INDEPENDENT TESTING AGENCY. 44, A MINIMUM OF 4 TEST CYLINDERS SHALL BE TAKEN FROM EACH DAY OF CONCRETE PLACEMENT OR ONCE FOR EACH 100 CUBIC YARDS OF CONCRETE PLACED. ONE TEST CYLINDER SHALL BE TESTED AT SEVEN DAYS (3 DAYS FOR HIGH EARLY STRENGTH) FOR INFORMATION. TWO TEST CYLINDERS SHALL BE TESTED AT TWENTY-EIGHT DAYS (7 DAYS FOR HIGH EARLY STRENGTH) FOR ACCEPTANCE, ONE TEST CYLINDER SHALL BE HELD AS A SPARE. 45, THE CONTRACTOR SHALL MAINTAIN A WRITTEN RECORD FOR EACH BATCH OF CONCRETE DELIVERED TO THE JOB SITE. THESE RECORDS SHALL INCLUDE DATE AND TIME OF DELIVERY, WEATHER CONDITIONS, TRUCK NUMBER, LOCATION OF PLACEMENT, CUBIC YARDS, TIME AND AMOUNT OF WATER INTRODUCED INTO MIX, MAXIMUM SIZE AGGREGATE, AND TYPE AND AMOUNT OF ANY ADMIXTURES. ALL RECORDS MAINTAINED ARE SUBJECT TO REVIEW BY THE OWNER'S REPRESENTATIVE. NON -SHRINK GROUT 1. ALL GROUT SHALL BE NON -SHRINK, GROUT SHALL BE MIXED AND PLACED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS AND AS NOTED ON DESIGN DRAWINGS. GROUT SHALL BE PLACED IN SUCH A MANNER AS TO PROVIDE FULL BEARING AND NO VOIDS UNDER PLATES. 2, NON -SHRINK CEMENT BASED GROUT SHALL BE USED, IN CHEMICALLY BENIGN ENVIRONMENTS, UNDER STRUCTURAL BASE PLATES AND AROUND PIPE SLEEVES AND DRAINS, SAID GROUT SHALL HAVE A MINIMUM 7 DAY COMPRESSIVE STRENGTH OF 5000 PSI AND SHALL MEET THE REQUIREMENTS OF ASTM C109, C827, C1090, C1107, AND CORPS OF ENGINEERS CRD-C621. DRAWN DATE CDC 01/22/21 CHECKED DATE DBC 01/22/21 SUPERVISOR DATE ALLIANCE AJD 01/22/21 Baltimore, MD Newport News, VA (410)636-9555 (737)599-3300 PROJECT ENGINEER DATE LAS 01/22/21 Richmond, VA (804)275-1404 OWNERS APPROVAL DATE CITY �' L ALL WORK SHALL COMPLY WITH PREVAILING CODES FLORIDA BUILDING CODE, NATIONAL ELECTRIC CODE, AND THE CITY OF ZEPHYRHILLS ORDINANCES NESTLE WATERS ZEPHYRHILLS, FL STRUCTURAL GENERAL NOTES AS NOTED 2002160040 2160040-SOOl.dwg DRAWING NO. 2160040-SO01 EV. 1 go STRUCTURAL STEEL PAINTING STRUCTURAL STEEL ABBREVIATIONS 1. UNLESS OTHERWISE NOTED, HOLLOW STRUCTURAL TUBE SHAPE MEMBERS SHALL BE ASTM 1. ALL PAINTING SHALL BE COORDINATED WITH THE OWNER'S REPRESENTATIVE AND PERFORMED IN & AND A500 GRADE B. STEEL PLATES AND ANGLES SHALL BE ASTM A36. ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS. THE FINAL SURFACE SHALL BE SMOOTH % PERCENT AND EVEN. DRIPS, RUNS, OR SAGS SHALL NOT BE ACCEPTABLE. ± PLUS OR MINUS 2. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE ACI AMERICAN CONCRETE INSTITUTE FIFTEENTH EDITION STANDARDS AND SPECIFICATIONS OF THE AMERICAN INSTITUTE OF STEEL 2, STRUCTURAL STEEL SHALL BE CLEANED IN COMPLIANCE WITH STEEL STRUCTURES PAINTING COUNCIL AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION CONSTRUCTION. SP10 (NEAR WHITE METAL BLAST CLEANING). OIL OR GREASE SHALL BE REMOVED BY SOLVENT ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS CLEANING IN COMPLIANCE WITH SSPC-SP1 PRIOR TO BLAST CLEANING AND AFTERWARDS AS @ AT 3. ALL SHARP CORNERS OF STEEL EXPOSED TO PERSONNEL SHALL BE ROUNDED. REQUIRED, ALL WELD FLUX AND SPLATTER SHALL BE COMPLETELY REMOVED IN COMPLIANCE WITH AWS AMERICAN WELDING SOCIETY SSPC-SP3, ALL SHARP EDGES AND PROJECTIONS SHALL BE GROUND SMOOTH. BLDG BUILDING 4. STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL STRUCTURAL STEEL TO ENGINEER BM BASE MIX FOR APPROVAL PRIOR TO FABRICATION. 3. IMMEDIATELY AFTER SURFACE PREPARATION, ALL STEEL SURFACES SHALL RECEIVE A PRIMER COAT BOT BOTTOM APPROVED BY THE OWNER'S REPRESENTATIVE. IN NO CASE SHALL NEWLY CLEANED STEEL GO B/ BOTTOM OF 5. MODIFICATIONS OR CHANGES TO THE STRUCTURAL STEEL AS NOTED ON THESE DRAWINGS CAN UNPRIMED OVERNIGHT. USE THE FOLLOWING PAINT PRIMERS OR APPROVED EQUAL: 4. CENTERLINE NOT BE MADE DURING DETAILING, FABRICATION, OR CONSTRUCTION WITHOUT PRIOR WRITTEN CO CLEANOUT APPROVAL BY THE ENGINEER OF RECORD. a. CARBOLINE: CARBOCOAT 2900 (MINIMUM 2 MIL DRY FILM THICKNESS) CLR CLEAR b, SHERWIN WILLIAMS MACROPDXY 646 (MINIMUM 4 MIL DRY FILM THICKNESS) CONT'D CONTINUED 6. ERECTOR SHALL PROVIDE ALL TEMPORARY SHORING AND BRACING NEEDED FOR STABILITY CJ CONTROL JOINT UNTIL STRUCTURAL STEEL AND NEW EQUIPMENT IS COMPLETELY INSTALLED. ERECTOR IS 4. THE PRIMED SURFACE SHALL RECEIVE AN INTERMEDIATE COAT APPROVED BY THE OWNER'S RESPONSIBLE FOR THE STABILITY OF THE STRUCTURAL FRAMING DURING CONSTRUCTION. REPRESENTATIVE. USE THE FOLLOWING PAINT SYSTEMS OR APPROVED EQUAL, LYVINYL CHLORIDE PROPER ERECTION SEQUENCING SHALL BE USED TO ENSURE FRAME STABILITY THROUGHOUT CRS CATIONIC RAPID SET CONSTRUCTION, a. CARBOLINE: CARBOTHANE 133 HB (MINIMUM 5 MIL DRY FILM THICKNESS) CRSI-MSP CONCRETE REINFORCING STEEL INSTITUTE -MANUAL OF STANDARD PRACTICE b. SHERWIN WILLIAMS MACROPDXY 646 (MINIMUM 4 MIL DRY FILM THICKNESS) DEMO DEMOLITION DIA, 0 DIAMETER STRUCTURAL STEEL CONNECTIONS 5. THE INTERMEDIATE COAT SHALL RECEIVE A FINAL COAT APPROVED BY THE OWNER'S REPRESENTATIVE. USE THE FOLLOWING PAINT SYSTEMS OR APPROVED EQUAL: DWG DWV DRAWING DRAIN WASTE VENT (E) EXISTING a. CARBOLINE: CARBOTHANE 133 HB (MINIMUM 5 MIL DRY FILM THICKNESS) ETC ETCETERA 1. UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL BEAM CONNECTIONS SHALL BE AISC "SIMPLE (MINIMUM 3 (MMIL DRY FILM b. SHERWIN WILLIAMS 2 N O S IPOLYURETHANE 50 I SO HI -SOLIDS EL EQ ELEVATIONR EQUAL SHEAR CONNECTIONS". THE DETAILER SHALL DESIGN THE CONNECTIONS FOR THE INDICATED THICKNESS) EW EACH WAY SHEAR AND AXIAL LOADS SHOWN ON THE DRAWING, WHERE NO LOADS ARE INDICATED, THE FD FLOOR DRAIN DETAILER SHALL DESIGN BEAM CONNECTIONS PER THE FOLLOWING TABLE: 6, STEEL ERECTOR IS RESPONSIBLE FOR TOUCH UP OF ALL PAINT BLEMISHES. BLEMISHES INCLUDE: WELD FIN FLOOR FINISHED FLOOR BURNS, WELD SCARS, ABRASIONS, BOLTS, FRAYING SURFACES AT BOLTED CONNECTIONS, AND DEPTH OF BEAM 12-14 DAMAGE DURING SHIPPING. ALL TOUCH UP SURFACES SHALL BE CLEANED IN ACCORDANCE WITH FLR FLOOR SSPC-SP3 (POWER TOOL CLEANING). ALL DAMAGED LAYERS OF PAINT SHALL BE REAPPLIED PER IM INTERMEDIATE MIX ROWS OF BOLTS 3 MANUFACTURER'S PRINTED INSTRUCTIONS. INV INVERT SHEAR FORCE IN IPS IRON PIPE SIZE WELDS OR BOLTS (KIPS) 63 7. THE VOLATILE ORGANIC COMPOUNDS (VOC) OF ALL PAINT AND PROTECTIVE COATINGS ON THIS KSI KIPS PER SQUARE INCH PROJECT SHALL NOT EXCEED THE AMOUNT OF VOC'S APPROVED BY THE STATE, LOCAL AUTHORITIES, LG LONG 2. SHOP CONNECTIONS SHALL BE WELDED UNLESS NOTED OTHERWISE. FIELD CONNECTIONS SHALL AND EPA GUIDELINES WITHIN THE AREA OR ZONE IN WHICH THE COATING IS APPLIED. MAX MIN MAXIMUM MINIMUM BE AS NOTED ON DRAWINGS, FIELD CONNECTIONS TO EXISTING STRUCTURES MAY BE FIELD MPH MILES PER HOUR WELDED. NSF NATIONAL SANITATION FOUNDATION SANITARY SEWER DRAIN NO./# NUMBER 3. ALL GUSSET PLATES AND CONNECTION ANGLES SHALL BE MINIMUM %" THICKNESS. OC ON CENTER 4. SHOP OR FIELD SPLICES BETWEEN SUPPORTS WILL NOT BE ALLOWED WITHOUT PRIOR 1. PIPE SHALL BE MANUFACTURED FROM VIRGIN RIGID CPVC (CHLORINATED POLYVINYL CHLORIDE) VINYL OPP OPPOSITE APPROVAL BY THE ENGINEER. COMPOUNDS WITH A CELL CLASS OF 24448 AS IDENTIFIED IN ASTM D1784. PCF POUNDS PER CUBIC FOOT R PLATE 5. 3 UNLESS OTHERWISE NOTED, BOLTS SHALL BE DOMESTIC MANUFACTURED /" DIAMETER HIGH 2. CPVC SCHEDULE 80 PIPE SHALL BE IRON PIPE SIZE (IPS) CONFORMING TO ASTM F441, PSF PSI POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH STRENGTH ASTM A325-N (BEARING TYPE) MECHANICALLY DEPOSITED GALVANIZED PER ASTM REF REFERENCE B695. THREADS ARE PERMITTED IN THE SHEAR PLANE, UNLESS OTHERWISE NOTED. 3. INJECTION MOLDED CPVC SCHEDULE 80 DWV FITTINGS SHALL CONFORM TO ASTM F439. REQ'D REQUIRED 6. BOLT AND NUT ENGAGEMENT SHALL CONFORM TO THE FOLLOWING: 4. PIPE AND FITTINGS SHALL CONFORM TO NSF INTERNATIONAL STANDARD 14. RFI REQUEST FOR INFORMATION SAN SANITARY SEWER a. MINIMUM ENGAGEMENT: DEPTH OF NUT PLUS 2 THREADS SCH SCHEDULE b. MAXIMUM ENGAGEMENT: DEPTH OF NUT PLUS Y2" 5. INSTALLATION OF CPVC PIPE SHALL COMPLY WITH THE LATEST INSTALLATION INSTRUCTIONS PUBLISHED BY THE MANUFACTURER AND SHALL CONFORM TO ALL APPLICABLE PLUMBING, FIRE, AND SIM SIMILAR 7. GALVANIZE NUTS AND WASHERS IN ACCORDANCE WITH ASTM 6695. BUILDING CODE REQUIREMENTS. SS SSPC STAINLESS STEEL SOCIETY FOR PROTECTIVE COATINGS 8. ONE SIDED CONNECTIONS MAY NOT BE USED UNLESS SPECIFICALLY SHOWN ON THE DRAWING OR 6. BURIED PIPE SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D2321 AND ASTM F1668. STD T/ STANDARD TOP OF APPROVED BY THE ENGINEER, WHERE ECCENTRIC CONNECTIONS ARE USED THE COMPONENTS OF TYP TYPICAL THE CONNECTION SHALL BE DESIGNED FOR ALL ECCENTRIC FORCES. 7. SOLVENT CEMENT JOINTS SHALL BE MADE IN A TWO-STEP PROCESS WITH PRIMER CONFORMING TO UNO UNLESS NOTED OTHERWISE ASTM F656 AND SOLVENT CEMENT CONFORMING TO ASTM F493. VDOT VIRGINIA DEPARTMENT OF TRANSPORTATION 9. MINIMUM BOLTED CONNECTIONS SHALL BE TWO BOLTS, UNLESS OTHERWISE NOTED. W/ WITH 8. THE SYSTEM SHALL BE PROTECTED FROM CHEMICAL AGENTS, FIRE -STOPPING MATERIALS, THREAD 10. CONNECTIONS SHALL BE DESIGNED AND DETAILED SO ALL FORCE COMPONENTS WILL BE SEALANT, PLASTICIZED -VINYL PRODUCTS OR OTHER AGGRESSIVE CHEMICAL AGENTS NOT WP WORK POINT TRANSMITTED DIRECTLY THROUGH THE WORK POINTS OF THE INTERSECTING MEMBERS, THE COMPATIBLE WITH CPVC COMPOUNDS. CONNECTIONS SHALL BE DESIGNED FOR ALL RESULTING ECCENTRICITIES. 9. THE SYSTEM SHALL BE HYDROSTATICALLY TESTED AFTER INSTALLATION. 11. FOR CONNECTIONS OF STEEL MEMBERS NOT SPECIFICALLY ADDRESSED BY THESE GENERAL NOTES OR DRAWINGS, PROVIDE FILLET WELDS AT ALL CONTACT JOINTS BETWEEN STEEL MEMBERS SUFFICIENT TO DEVELOP THE TENSILE STRENGTH OF THE WEAKEST MEMBER AT THE JOINT. 12. SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY D1.1-11 "STRUCTURAL WELDING CODE - STEEL". ALL WELDING SHALL BE PERFORMED BY AWS QUALIFIED WELDERS. 13. ELECTRODES FOR WELDED CONNECTIONS SHALL BE E70XX. 14. MINIMUM WELD SIZE SHALL BE 316" UNLESS THINNER PART TO BE JOINED REQUIRES A LARGER WELD SIZE IN ACCORDANCE WITH AISC. TABLE J2.4. 15. MINIMUM WELDED CONNECTION SHALL HAVE THE STRENGTH OF A TWO -BOLT CONNECTION. FIELD WELD NOTES: 1. SURFACES TO RECEIVE WELDING SHALL BE THOROUGHLY CLEANED OF ALL GREASE, PAINT, RUST, ETC., BY USING GRINDER TO EXPOSE CLEAN BASE METAL FOR A DISTANCE OF 2" FROM EACH SIDE OF THE OUTSIDE LINES OF THE WELD. 2. OWNER'S ENGINEER SHALL APPROVE SURFACE PREP PRIOR TO PLACING WELD. 3. VISUALLY INSPECT ALL WELDS PER AWS. 4. WELDS NOT MEETING AWS STANDARDS SHALL BE CORRECTED PER OWNER'S ENGINEERS DIRECTION AND AT NO EXPENSE TO THE OWNER. \\\\\\¢NANO IT //I 'Professional Certification. I hereby certify that these documents were prepared or approved by me, and that No. 90224 I am a duly licensed professional engineer under the * * *E laws of the yip O D 2\� State of Florida, License No. 90224 1 ADDED ABBREVIATION FOR CONTROL JOINT CDC 01/29/21 Nl L ��\\\ Expiration Date: 2-08-23 0 ISSUE FOR CONSTRUCTION CDC 01/22/21 I c/J91z/ REV, DESCRIPTION DRWN APPR DATE REV. DESCRIPTION DRWN APPR DATE DRAWING NO, REFERENCE DRAWING DRAWN DATE CDC 01/22/21 CHECKED DATE DEC 01/22/21 ,- SUPERVISOR DATE ALLIANCE AJD 01/22/21 Baltimore, MD Newport News, VA (410)636-9555 (757)599-3300 PROJECT ENGINEER DATE LAS 01/22/21 Richmond, VA (804)275-1400 OWNERS APPROVAL DATE SCALE NESTLE WATERS AS NOTED qT PROJECT NO. ZEPHYRHILLS, FL 2002610040 FILENAME STRUCTURAL 21DRAWING 0. REV, GENERAL NOTES 2160040-S002 1 —j w z Q d J Q ' 3 00 tD z V) x w 1 2 28'-4" REF REF 29'-4%" REF A - 2160040-S101 ! I INSIDE FACE OF 14'-6"± 24'-0"± EXISTING BUILDINGI EXISTING 10" THICK FOUNDATION I i ' I I F-- - --- - --- ------ - - - - - - - - - n 4 a G ,j! I Ga n 4 o G A C 3'-6' 5'-1Y2 ° 14'-10) ," d ° G a n i - 4 41 ° G 41 4 G ° I ° a WORK POINT n 1 ° ! - d41 a' d n;l i °—�ILL 1 i d li I[ 4— a — — —-- — 71 LL 4 ° d i a a ill G d ? a III III n a III 4 it ° �I 1 d n G f d 6 _ INV EL -1.71' 4 n ° 4 G a ? ° 02 F D , 4 I ° a 1 ` a ° -0 tt H INV EL -1 69` ?. ea G a c v ° a 2160040-S102 l I 2 60040-S102 1 I a n, i CJ' QI T ° L z ETYP FD 2 Q a f i• 1 510 040-2 °L- I 21-10y y ! - -- 1- ICJ - 1 — - - - - - - — - --- - .. � 2 6 040 S10 2� � � � • �: f�2.16;4040=5 402 `^ I '�• � � � I= y�f � f 17 -8 I -g" NEW EQUIPMENT, TYP 1 NEW 10" THICK SLAB fe> ! fit' F /- - o o CJf' 2160040-S102 90 I.' Ir NEW 10" THICK SLAB. TOP OF FINISH FLOOR f" bi EL $4.67' Ci F gY2�, 3 I I- 2 040 S102 Pr~ - L 30'-01, REF I ! I 0 i ac> EXISTING SLAB o CONTROL JOINT, TYP. j 1 Y CJ ' 3 \ 2 FD o 21b0040 S102_ 2160040-S102 ,q `A T ;CJ ; ° °iLn J .,,..il INV EL -1.96' d` q ja j .: 4 I ° 1 CJ L• I ° G d n 4° ° G a I Ln 1 00 LD z z w a O J Q 3 3 w z ! _ i 4 ?" A H- jz 2 6 040-S102 LI d CJ��, a q d INV EL -2.06 1 w d-Z,d a a 4" SAN a n INV EL -2.35' ° a / — _? a c! ° n 4 ° b ? ° 4 G 4 q I q a 3'-6" 4'-0" d� ° 12'-8y„ l 33)/„ n a 4a ? 4 '4 G d� ? a a d J NEW OVERHEAD ? COILING DOOR ° a al d a d d 4� a ' n I' II 22'-7"± I EXISTING 10" THICK FOUNDATION SLAB AND WALL FRAMING PLAN SCALE: 1/4" = V-0" I J --- ? I II I i o i � I Q i Z: I I O o v I = N r ! p LV z V) x w I i I i I ! I 1 ! I I' I i ! ! I ? I ! I I i ! I z!y i{ tion. I hereby certify that these EN SFGC9A documents ared by that were preponal or approved me, and No gp224 d : I am a duly licensed professional engineer under the * * * laws of the State of Florida, License No. 90224 /��A o� \\\\ ExpirationDate: 2-08-23 AI} 9t / 1 REVISED DRAIN LINE ROUTING CDC 01/29121 0 ISSUE FOR CONSTRUCTION CDC 01/22/21 REV. DESCRIPTION DRWN APPR DATE REV. DESCRIPTION DRWN APPR DATE DRAWING NO. REFERENCE DRAWING DRAWN DATE CDC 01/22/21 CHECKED DATE DBC 01/22/21 4A— SUPERVISOR DATE ALLIANCE AJD 01/22/21 Baltimore, MD Newport News, VA (410)636-9555 (757)599-3300 PROJECT ENGINEER DATE LAS 01/22/21 Richmond, VA (804)275-1400 OWNERS APPROVAL DATE AREA OF WORK GENERAL NOTES 1. FOR GENERAL NOTES, SEE DRAWINGS 2160040-SO01 & 2160040-SO02, 2. NEW CONCRETE SLAB SHALL BE 6" THICK, UNLESS NOTED OTHERWISE. F-1 SHEET SPECIFIC NOTES 1. FIELD VERIFY INVERT AT EXISTING SANITARY SEWER LINE, ROTATE NEW WYE TO MATCH. 2. SEE DETAIL 1 ON DRAWING 2160040-S101 FOR FLOOR DRAIN. 3. NEW HSS12x6x% COLUMN, SEE DRAWING 2160040-S101 FOR DETAILS. 4. (2) NEW HSS12x6x% HEADERS, ONE HIGHER THAN CONDUIT AND ONE AT DOOR CAN, SEE DRAWING 2160040-S101 FOR DETAILS. KEY PLAN SCALE: 1/128" = V-0" cc i.r Yz" 0 ANCHORS SET USING HILTI HIT -RE 500 V3 EPDXY OR APPROVED EQUAL, 6'-0" SPACING FROM CENTER OF FRAME, 4Y2" MIN EMBED TOP OF FRAME EL 107.67' N L8x4x% (CONTINUOUS) Y4"O TAPCON ANCHORS AT 24" OC SPACING EXISTING WALL Y" BENT PLATE AROUND EXISTING CONDUIT BANK TOP OF HEADER EL 103.67' TOP OF OPENING EL 102,67' Z, a Gr C B 75'-0" REF 1 1'-101, REF HSS12 COLUMN WELDED CAP PLATE 9 3" x 5Y" x 0'-l%„ I I I 1 I I I I I I i 16 72-12 I I I I I I I I i i T HSS12x6x% Q I a O i I I O I I 0 i � 4„ v (WALL ELEVATION) SECTION A SCALE:1/4" = V-0" 2160040-S100 2160040-SD100 1'-101, REF EXISTING WALL L8x4x% , BREAK AT CONDUIT BANK, SEE SECTION A, THIS SHEET Y" O ANCHORS SET USING HILTI HIT -RE 500 V3 EPDXY OR APPROVED EQUAL (4Y2" MIN EMBED) SEE SECTION A, THIE SHEET FOR SPACING 1 )/4" 0 SELF -DRILLING SCREWS AT 24" OC SPACING I HSS12x6x% I (DOOR HEADER) SECTION B SCALE:1-1/2" = V-0" 2160040-S101 m a W J lJ 0 W z (DOOR FRAME CONNECTION TO WALL) SECTION C SCALE:1-1/2" = V-0" 2160040-S101 HSS12 COLUMN 9y,. 3„ I I V Np s�'�j� � ,� 'Professional Certification. I hereby certify that these E NSA C9Ayi documents were prepared or approved by me, and that T No, 902Y4 O I am a duly licensed professional engineer under the laws of the = ro s r ct State of Florida, License No. 90224 ����/NAE; ���\\\ Expiration Date: iu I 1 2-08-23 1 REVISED FLOOR DRAIN DETAIL, REMOVED CLEAN OUT DETAIL CDC 01/29/21 0 ISSUE FOR CONSTRUCTION CDC 01/22/21 REV. DESCRIPTION DRWN ::= ,= REV. DESCRIPTION DRWN APPRI DATE DRAWING NO. REFERENCE DRAWING DRAWN DATE CDC 01/22/21 CHECKED DATE 4i— DSC 01/22/21 SUPERVISOR DATE ALLIANCE AJD 01/22/21 Baltimore, MID Newport News, VA (410)636-9555 (757)599-3300 PROJECT ENGINEER DATE LAS 01/22/21 Richmond, (804)275-140000 OWNERS APPROVAL DATE GENERAL NOTES 1. FOR GENERAL NOTES, SEE DRAWINGS 2160040-SO01 & 2160040-SO02. Q DEMOLITION NOTES 1. RELOCATE ASSET AND REROUTE ASSOCIATED LINES 2. RELOCATE HAND SINK, REROUTE SUPPLY LINES, AND CAP EXISTING DRAIN LINE 3. f 0 IS I S I H 4, TEMPORARILY REMOVE PORTION OF DUCT IN FRONT OF NEW DOOR OPENING. REINSTALL ONCE DOOR CONSTRUCTION IS COMPLETE, 5. CORE DRILL CORNERS OF WALL DEMOLITION TO PREVENT OVERCUTTING. EXISTING WALL D 3 SIDES TYP>___F BASEPLATE f"x7"xV-6"W/(2) 1Y6" HOLES FOR (2) %" ANCHOR BOLTS ✓D fY'1 LD z w Q a- J O V J O Q 1 3 w z 1'-101, REF HSIS12 COLUMN & PLATE 9/1/2,< 3" I 1'-11Y2„ MIN 001 o PRE -MOLDED EXPANSION JOINT, TYP f NEW UNREINFORCED CONCRETE APRON, AS REQUIRED, TYP HSS12 COLUMN & PLATE 9y HSS12x6x%"COLUMN WITH BASEPLATE 9" I 9" 3/" x 7" x V-6" (BLDG EXTERIOR) (2) %"O ANCHOR BOLTS I I I I I Il i I i PRE -MOLDED EXPANSION JOINT, TYP TOP OF FINISH FLOOR i� II I ' I q G C -1 v 1 1= �i VAPOR BARRIER, TYP 4" #57 STONE, TYP (8) #8 VERTICAL BARS, d EVENLY SPACED ;x \A d �XG A � G� , (14) #4 DOWELS 7 G /\\\ \ I] P q /// T I SHEET d / /, \ EMBED 1'-9" I 3" CLR /, TYP ° A TYP\ h A o °dK \ \ q o X d° A \X/A ^ R ° /,\if\ — -- -- P ° f //f Aw Q //xj\ V-2" 101, EXISTING WALL (8) #8 VERTICAL BARS, EVENLY SPACED (14) #4 DOWELS SECTION D SCALE. 1-1/2" = V-0" 2160040-S102 HSS12 COLUMN, PLATE, & PIER V-0" MIN 1'-0" 1'-01, TYP 3y„ I HSS12x6x%" COLUMN WITH BASEPLATE 4" x 7" x 1'4" (2) %" O ANCHOR BOLTS I cr z PRE -MOLDED EXPANSION I I I JOINT, TYP o I I TOP OF FINISH FLOOR i i 0 G a o °iv V a a n e q #8 VERTICAL BARS P p / q �° (14) #4 DOWELS G \° /X/,, A ° �\/� e /� j�� j \ C \\ j /\ \ \ ° ILI //\% ° / f I \\ \ ZA ° \ ° G \ 3" CLR TYP 2'-0" CONCRETE PIER (TYPICAL PIER DETAIL) DETAIL ri"*� SCALE: 1-1/2" = V-0" 2160040-S101 ANO q � 'Professional Certification. I hereby certify that these GE NSF (9���i documents by that were prepared or approved me, and S O I am a duly licensed professional engineer under the No. 90224 Z C. laws of the s State of Florida, License No. 90224 JAPPRDATEDRAWING 1 REVISED SECTION D CDC 01/29/21 F O NAJ . ���\ Expiration Date: 2-08-23 0 ISSUE FOR CONSTRUCTION CDC 01/22/21 oll�IflEI REV, DESCRIPTION DRWN APPR DATE REV. DESCRIPTION DRWN NO, REFERENCE DRAWING Y" MAXIMUM x 1}2" DEEP SAW DISCONTINUE TOP LAYER OF CUT JOINT, FILL WITH SIKAFLEX REINFORCING AT CONTROL JOINT PRO-3 SL OR APPROVED EQUAL TOP OF FINISH FLOOR EL 84.67' ° ° a -q VAPOR BARRIER j — I 4" #57 STONE cr W (TYPICAL CONTROL JOINT) SECTION E SCALE: 1-1/2" = V-0" 2160040-S100 TOP OF FINISH FLOOR EL 84,67' COLD JOINT, TYP EXISTING FLOOR SLAB TOP OF FINISH FLOOR EL 84.67' c z Q J d W z NEW OR EXISTING FLOOR SLAB nnr ­1 nrn rvn • sirinkf #5 (la 12" EW, TOP & BOTTOM IIIIII1 l i / I j1 I I -I I I�� ill=1 11= `/ VAPOR BARRIER _ 1 _ 4" #57 STONE IIII=-II (TYPICAL SECTION AT EXISTING FLOOR SLAB) SECTION F SCALE: 1-1/2" = V-0" 2160040-S100 EXISTING FLOOR SLAB #5 DOWELS (i1a 2'-0" SPACING, DRILLED #5 C) 12" EW, INTO EXISTING CONCRETE PAD, SET TOP & BOTTOM USING HILTI HIT -RE 500 V3 EPDXY, 6" MIN EMBEDMENT, 6" PROJECTION ,G- C el ° p a ° VAPOR BARRIER ! 1 — 4" #57 STONE ,Ij i (TYPICAL SECTION AT EXISTING 10" SLAB) SECTION rG_�� SCALE: 1-1/2" = V-0" 2160040-S100 #5 0 12" EW VAPOR BARRIER 4" #57 STONE SAND CPVC PIPE (SEE PLAN) BEDDING (TYPICAL SECTION AT NEW DRAIN LINE) SECTION H SCALE- 1-1/2" = V-0" 2160040-5100 DRAWN DATE CDC 01/22/21 CHECKED DATE 41— DBC 01/22/21 SUPERVISOR DATE ALLIANCE AJD 01/22/21 Baltimore, MD Newport News, VA (410)636-9555 (757)599-3300 PROJECT ENGINEER DATE LAS 01/22/21 Richmond, (804)275-140000 OWNERS APPROVAL DATE GENERAL NOTES 1. FOR GENERAL NOTES, SEE DRAWINGS 2160040-SO01 & 2160040-S002. Q G ° _ a � p � Q U ° co N D 1 REF I — 2 3 28'-4" 30'-0" i REF 29'-4y" J SLAB AND WALL DEMOLITION PLAN SCALE: 1/4" = 1'-0" REF ANOISO% 'Professional Certification. I hereby certify that these E NSF C9 i� y\G documents were prepared or approved by me, and that �e 907t4 pp G I am a duly licensed professional engineer under the laws of the � State of Florida, License No. 90224 s/,StONA o��\`\\ Expiration Date: 2-08-23 Pip 1 REVISED DEMO FOR NEW DRAINLINE, EXISTING EQUIPMENT SHOWN CDC 01/29/21CDC 0 ONSTRUCTONRAIN ISSUE FOR CONSTRUCTION CDC 01/22/21 01/22/21 REV. DESCRIPTION IDRWN APPRI DATE REV, I DESCRIPTION DRWN APPRI DATE DRAWING NO, REFERENCE DRAWING DRAWN DATE CDC 01/22/21 CHECKED DATE DBC 01/22/21 SUPERVISOR DATE ALLIANCE AJD 01/22/21 Baltimore, NID Newport News, VA (410)636-9555 (757)599-3300 PROJECT ENGINEER DATE LAS 01/22/21 Richmond, VA (804) 275-1400 OWNERS APPROVAL DATE GENERAL NOTES 1. FOR GENERAL NOTES, SEE DRAWINGS 2160040-SO01 & 2160040-SO02. 2. LIMITS OF DEMOLITION ARE ESTIMATED, ADJUST AS NECESSARY TO PERFORM NEW WORK. 0 DEMOLITION NOTES 1. DEMOLISH AND REMOVE SECTION OF EXISTING WALL PANEL ONLY TO EXTENTS NOTED. 2. USE CAUTION IN THIS AREA TO AVOID DAMAGE TO EXISTING WALL & FOOTER. 3. CUT AND REMOVE INDICATED PORTIONS OF EXISTING FOUNDATION IN THIS AREA. 4. NEW CUT TO FOLLOW CONTROL JOINT IN EXISTING SLAB. 5. CORE DRILL CORNERS OF CONCRETE DEMOLITION TO PREVENT OVERCUTTING, 6. CONCRETE DEMOLITION ASSUMES ALL EXISTING FLOOR MOUNTED EQUIPMENT IN THE AREA OF CONSTRUCTION HAS BEEN REMOVED PRIOR TO START OF NEW WORK. FITT r 4 �tyl -ram I Ai F�15-09 74 rl F, I R �� a AREA OF WORK �I 1i e 1 c T— KEY PLAN SCALE: 1/128" = V-0" — - -