HomeMy WebLinkAbout7320 Gall Blvd (3)- FIRE ALARM DRAWING INDEX -
SHEET NO. SHEET DESCRIPTION
F000 COVER SHEET
F001 RISER AND CALCULATION
F002 FLOOR PLAN
-SCOPE OF WORK - 1
THIS PROJECT INVOLVES THE REPLACEMENT OF AN EXISTING SILENT KNIGHT 5808 FIRE
ALARM PANEL WITH A SILENT KNIGHT 6808 FIRE ALARM PANEL AND NAPCO STARLINK
CELLULAR COMMUBICATOR. ALL EXISTING APPROVED DEVICES WILL BE RECONNECTED
TO THE FEW FACU. THE SYSTEM SHALL REMAIN BEING MONITORED BY AN APPROVED
LISTED CENTRAL STATION.
CABLE AND WIRE LEGEND
AW
RESISTANCE
LABEL
PART NO
G
(0/KFT)
DESCRIPTION
TOTAL LENGTH
18/2 FPLP/R
2 COND. SOLID COPPER FPLP/R ANALOG
485
(RS-485)
18
7.77
UNSHIELDED
43'
A
18/2 FPLP/R (SLC)
18
7,77
2 COND. SOLID COPPER FPLP/R
375'
ADDRESSABLE UNSHIELDED
P
14/2 FPLP/R (AUX)
14
3.07
2 COND, SOLID COPPER FPLP/R
3,
UNSHIELDED
V
14/2 FPLP/R (NAC)
14
3.07
2 COND. SOLID COPPER FPLP/R ANALOG
518'
UNSHIELDED
Z
18/2 FPLP/R (IDC)
18
7.77
2 COND. SOLID COPPER FPLP/R ANALOG
6'
UNSHIELDED
E
i
AF
"STEM "'UBMITTAL
o y %a
-1/320
`B LVD
Qom: �' I
FIL- 33541
DEVICE
LEGEND
SYMBOL
QTY
EXISTING
MANUFACTURER
PART NO
DESCRIPTION
FIRE ALARM CONTROL
FEA—C-UTI
1
NEW
SILENT KNIGHT
6808 (SK)
PANEL, ADDRESSABLE,
SK PROTOCOL
WIRELESS COMMERCIAL
CELL
1
NEW
NAPCO
SLE-LTEVI-CFB-PS
FIRE ALARM
COMMUNICATOR
FAA
1
EXISTING
SILENT KNIGHT
5860R
ANNUNCIATOR
VS
1
EXISTING
GENERIC
VALVE TAMPER
SUPERVISORY SWITCH
ADDRESSABLE MANUAL
------
4
EXISTING
SILENT KNIGHT
SK-PULL-DA
PULL STATION,
DOUBLE -ACTION
ADDRESSABLE MONITOR
AIM
5
EXISTING
SILENT KNIGHT
SK-MONITOR
MODULE
FBO
3
EXISTING
GENERIC
DUCT DETECTOR
ADDRESSABLE
0
2
EXISTING
SILENT KNIGHT
SK-PHOTO
PHOTOELECTRIC SMOKE
DETECTOR
WF
1
EXISTING
GENERIC
WATERFLOW SWITCH
1
EXISTING
SYSTEM SENSOR
P2RK
2-WIRE HORN STROBE,
STANDARD CD,
WP
OUTDOOR
2-WIRE, HORN STROBE,RED
5
EXISTING
SYSTEM SENSOR
P2RL
24%1IRE, HORN STROBE,
C
8
EXISTING
SYSTEM SENSOR
PC2RL
RED
C
2
EXISTING
SYSTEM SENSOR
SRL
STROBE, RED
PROJECT INFORMATION
PROJECT INFORMATION:
NAME OF PROJECT:
FEI SAVE A LOT #468
ADDRESS:
7320 GALL BLVD
ZEPHRYHILLS, FL 33541
PROPOSED USE:
MERCANTILE
FIRE ALARM INSTALLER:
ADT COMMERCIAL
FIRE ALARM VENDOR
ADT COMMERCIAL
4221 W JOHN CARPENTER FWY
IRVING, TX 75067
877-776-1911
FIRE ALARM DESIGNER
JODY CONGLETON, SET NICET IV 108686
ADT COMMERCIAL
4221 W JOHN CARPENTER FWY
IRVING, TX 75067
REMOTE STATION LISTING
CCN File No. Vol. No.
UUFX S2684 20
877-776-1911
Jcongleton@adt.com
251-583-7165
CODE SUMMARY
• APPLICABLE BUILDING CODES
BUILDING
FIRE
ELECTRICAL
W
NFPA 72
0
ACCESSIBILITYW
STATE FLORIDA FIRE CODE
OTHER
• OCCUPANCY CLASSIFICATION M
• OCCUPANCY USE B, S-1
• FULLY SPRINKLERED BUILDING
2020 FLORIDA BUILDING CODE
2020 FLORIDA FIRE CODE
2017 NATIONAL ELECTRICAL CODE
w
2016 NFPA 72
�
0
v
t
SYSTEM INPUTS
REVIEW DATE
CITY OF ZEPHYRHI LS
FIRE AND LIFE SAFETY EXAMINER,
ALL WORK SHALL COMPLY WITH
NFFA CODES AND STANDARDS
- SITE LOCATION -
r
SYSTEM OUTPUTS
CONTROL UNIT
NOTIFICATION
REQUIRED FIRE
SAFETY
SUPPLE -
ANNUNCIATION
CONTROL
MENTAR
a
• 'ALARM POWER -
■■■■��■■■■�■■■■■■
FIRE ALARM SYSTEM LOW 8ATTERY
ULT
NOTIFICATION .P .-
■■■■oo■■■■o■■■■■a
IN -DUCT SMOKE DETECTORS
■■oo■■■o■o■■■■■■o
o
R CO • - .
■■oa■■■o■o■■■■■■o
.
co■■■■000■■■■■■■o
OKE DETECTORS
SPRINKLER CONTROL VALVE
m
■■■■■■■■■■■■■■■■m
®
■■■■■■■■■■■■■■■■m
■
■■■■■■■■■■■■■■■■m
■
■■■■■■■■■■■■■■■■■
112111111111111
■■■■■■■■■■■■■■■■m
m
■■■■■■■■■■■■■■■■m
■■■■■■■■■■■■■■■■m
IAIBICIDIEIFIGI"IIIJIKILIMINIQIPI
I -INDIVIDUAL HVAC SHUTDOWN
'3z0AD
c
Commercial
r
ET
SHEET:
4221 W JOHN CARPENTER FWY
IRVING, TX75067
Web: adt.corrl/corrlmercial
FRESH
ENCOUNTER INC.
FEI SAVE A LOT #468
7320 CALL BLVD
ZEPHYRHILLS, FL 53541
FIRE ALARM SYSTEM
PREPARED BY:
This fire alarm shop drawing was prepared
for equipment application only. The
information contained herein is intended
to aid in the installation of this system. No
design changes have been made.. to the
engineer of record's contract documents.
JODY CONGLETON, SET
NICET #108686 rr�IJs✓('�Ng,�iliN
FIRE ALARM SYSTEMS LVL IV
EXPIRES 06/01/2024 1/9/2023
ADT Commercial, LLC
Edward Pleffner
Ucense #EC13004155
1309 N Ward St, Tamps, F4 33607
REVISIONS
NO.
DATE
REVISION
BY:
-
Z'.
BY:
-
'4'
BY:
-
�s
BY:
-
6.
BY:
-
BY:
-
PREPARED BY: J LC
CHECKED BY:
PROJECT MANAGER:
DATE: 01 f 09/3
PROJECT NO: ..
TITLE:
,i
COVER SH
FIRE ALARM
CONTROL UNIT
•
DEDICATED 120V
G ~j) 20 AMP CIRCUIT
REPLACE CONTROL PANEL ALL EXISTING
DEVICES REMAIN THE SAME
N2-01
115cd
C
M
N2.02
N2.03
115cd
115cd
N2.04 EOL
C
C
110cd
8S1BO
M001 D002 M002 M003
N3.01 N3.02 N3.03
115cd 115cd 115cd N3.04 N3.05 N3.06 N3.07 N3.08 N3.09 EOL
C C C 110cd 15cd 15cd 110cd p 110cd 75cd
ANN•1
ANNUNCIATOR
•
4UX1.01
WF
M005 M006 M007 M008 M009
A- AIM lA i r l V' - F�-- A- - AIM V- AIM
FBO FBO
�SS� VS
I
i
l
N1.01 N1.02 N1-03 EOL
75cd 75cd 115cd
C WP C
_,,_4
SYSTEM RISER
1 N.T.S.
NAPCO CELLULAR DIALER
NA -.�
Total stand by current 0.08500
X Stand by hours 24
Stand by amp/hours 2.04
Total Alarm Current 0.40
X alarm Minutes (5)/60 0.083
AlarmTotal amp/hours 0.03
Total Amp/hours 2.07
X Derating factor of 20% 1.2
Minimum Battery Size 2.49
Battery Selected
COMMUNICATOR CALCULATIONS
2 N.T.S.
BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURRENT (AMPS)
QTY
PART NO.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
FIRE ALARM CONTROL
PANEL COMPONENTS
1
6808 MAIN BOARD
PANEL MAIN BOARD SK
0.17
0.17
0.365
0.365
PROTOCOL
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL (A)
ANN
IFAAI
1
5860R
ANNUNCIATOR
0.02
0.02
0.025
0.025
AUX1
cE
1
SLE-LTEVI-CFB-PS
Wireless Commercial Fire
0.071
0.071
0.2
0.2
Alarm Communicator
FBO
1
DUCT DETECTOR
0
0
0
0
AIM
5
SK-MONITOR
ADDRESSABLE MONITOR
0.000375
0,001875
0.000375
0.001875
MODULE
M33
O
2
SK-PHOTO
ADDRESSABLE
PHOTOELECTRIC SMOKE
0.0003
0.0006
0.0003
0.0006
DETECTOR
ADDRESSABLE MANUAL
4
SK-PULL-DA
PULL STATION,
0.000375
0.0015
0.000375
0.0015
DOUBLE -ACTION
2-Wire Horn Strobe,
Wp
1
P2RK
Standard cd, Outdoor 75cd
0
0
0.176
0.176
N1
1
PC2RL
2-Wire, Horn Strobe; Red
0
0
0.143
0.143
C
75cd
1
PC2RL
2-Wire, Horn Strobe, Red
0
0
0.187
0.187
C
115cd
1
P2RL
2-Wire, Horn Strobe, Red
0
0
0.162
0,162
110cd
N2
3
PC2RL
2-Wire, Horn Strobe, Red
0
0
0.187
0.561
C
115cd
1
P2RL
2-Wire, Horn Strobe, Red
0
0
0.121
0.121
75cd
3
P2RL
2-Wire, Horn Strobe, Red
0
0
0.162
0.486
N3
11 0cd
3
PC2RL
2-Wire, Horn Strobe; Red
0
0
0.187
0.561
C
115cd
2
SRL
Strobe, Red 15cd
0
0
0.043
0.086
TOTAL STANDBY (A)
0.264975
TOTAL ALARM (A)
3.076975
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A)
0.264975
24
I 6.36
SECONDARY ALARM LOAD (A)
3.076975
0,08
1 0.26
STANDBY AND ALARM SUBTOTAL (AMP HOURS)
6.62
DERATING FACTOR
1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
7.94
PROVIDE (2) 12V 12AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
AUX1 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20A
Max. Voltage Drop:
0
Min. Operational Voltage:
16
End Of Line Voltage:
20.4
Max. Circuit Current (A):
3
Voltage Drop Percent:
0.02 %
Wire Resistance (t2/kFt):
3.07
Total Circuit Current (A):
0.2
Circuit Wiring Properties 'P' 14/2 FPLP/R (AUX) 14 AWG, 2 Cond. Solid Copper FPLP/R Unshielded
Total Circuit Length (Ft):
3
Spare Current (A):
2.8
Distance measured using drawn segment lengths with 10,00 % additional length calculated
Total Circuit Resistance (Q):
0.019699
Spare Current (A) Percent:
93.33 %
DEVICE TOTALS
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
c-
SLE-LTEVI-CFB-PS
Wireless Commercial Fire
Alarm Communicator
1
0.2
0.2
Calculation Methods:
Total Resistance (D) = Wire Resistance (O/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A)
N1 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.34
Min. Operational Voltage:
16
End Of Line Voltage:
20.06
Max. Circuit Current (A):
3
Voltage Drop Percent:
1.67 %
Wire Resistance (.0/kFt):
3.07
Total Circuit Current (A):
0.506
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
110
Spare Current (A):
2.494
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0):
0.673903
Spare Current (A) Percent:
83.13 %
Symbol
PartNo.
Description
Qty,
Device Current (A)
Total Current (A)
C
PC2RL
2-Wire, Horn Strobe, Red
75cd
1
0.143
0.143
DEVICE TOTALS
Wp
P2RK
2-Wire Horn Strobe, 1
Standard cd, Outdoor 75cd
1
0.176
0.176
C
PC2RL
2 Wire, Horn Strobe, Red
115cd
1
0.187
0.187
Calculation Methods:
Total Resistance (0) = Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A)
N2 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20A
Max. Voltage Drop:
0.74
Min. Operational Voltage:
16
End Of Line Voltage:
19.66
Max. Circuit Current (A):
3
Voltage Drop Percent:
3.63 %
Wire Resistance (t2/kFt):
3.07
Total Circuit Current (A):
0.723
Circuit Wiring Properties: 'V 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
167
Spare Current (A):
2.277
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0):
1.025244
Spare Current (A) Percent:
75.90 %
DEVICE TOTALS
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
P2RL
2-Wire, Horn Strobe, Red
110cd
1
0.162
0.162
C
PC2RL
2-Wire, Horn Strobe, Red
115cd
3
0187
0.561
Calculation Methods:
Total Resistance (0) = Wire Resistance ((2/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop = Total Resistance (Q) x Total Circuit Current (A)
N3 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20A
Max. Voltage Drop:
1.87
Min. Operational Voltage:
16
End Of Line Voltage:
18.53
Max. Circuit Current (A):
3
Voltage Drop Percent:
9.18 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
1.254
Circuit Wiring Properties. 'V 14/2 FPLP/R (NAC) 14 AWG, 2 Cond, Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
243
Spare Current (A):
1.746
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0),
1,492773
Spare Current (A) Percent:
58.20 %
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
SRL
Strobe, Red 15cd
2
0.043
0.086
DEVICE TOTALS
P2RL
2-Wire, Horn Strobe, Red
75cd
1
0.121
0.121
P2RL
2-Wire, Horn Strobe, Red
110cd
3
0.162
0.486
C
PC2RL
2-Wire, HornStrobe, Red
cd
3
0.187
0.561
Calculation Methods:
Total Resistance (D) = Wire Resistance (Q/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop = Total Resistance (Q) x Total Circuit Current (A)
�F
Commercial
4221 W JOHN CARPENTER FWY
IiIN, T. 77
Web.- dt,Com/'com m rci l
FRESH
ENCOUNTER INC.
I SAVE A LOT #468 .
7320 GALL BLVD
FIRE LA Y TF
PREPARED BY:
This fire alarm shop drawing was prepared
for equipment application only. The
informatian' contained herein' is intended
to aid in, the instailation;of this system. No
design changes have been made,to the
engineer of recort3s contract documents.
JODY CONGLETON, SET
FIIREEA ARM6SYSTEMS LVL IV `Try GJ�l�~f%Jir
EXPIRES 06/01/2024 1/9/2023
REVISIONS
NO.
DATE
REVISION
BY:
�'•.
BY:
BY:
41
BY:
-
5
BY:
BY:
7.
BY:
-
PREPARED BY: J LC
CHECKED BY:
PROJECT MANAGER:
DATE: 01 /09/2
PROJECT NO:
TITLE:
RISER AND
CALCULATIONS
SHEET:
Fool