HomeMy WebLinkAbout7320 Gall Blvd (3)- FIRE ALARM DRAWING INDEX - SHEET NO. SHEET DESCRIPTION F000 COVER SHEET F001 RISER AND CALCULATION F002 FLOOR PLAN -SCOPE OF WORK - 1 THIS PROJECT INVOLVES THE REPLACEMENT OF AN EXISTING SILENT KNIGHT 5808 FIRE ALARM PANEL WITH A SILENT KNIGHT 6808 FIRE ALARM PANEL AND NAPCO STARLINK CELLULAR COMMUBICATOR. ALL EXISTING APPROVED DEVICES WILL BE RECONNECTED TO THE FEW FACU. THE SYSTEM SHALL REMAIN BEING MONITORED BY AN APPROVED LISTED CENTRAL STATION. CABLE AND WIRE LEGEND AW RESISTANCE LABEL PART NO G (0/KFT) DESCRIPTION TOTAL LENGTH 18/2 FPLP/R 2 COND. SOLID COPPER FPLP/R ANALOG 485 (RS-485) 18 7.77 UNSHIELDED 43' A 18/2 FPLP/R (SLC) 18 7,77 2 COND. SOLID COPPER FPLP/R 375' ADDRESSABLE UNSHIELDED P 14/2 FPLP/R (AUX) 14 3.07 2 COND, SOLID COPPER FPLP/R 3, UNSHIELDED V 14/2 FPLP/R (NAC) 14 3.07 2 COND. SOLID COPPER FPLP/R ANALOG 518' UNSHIELDED Z 18/2 FPLP/R (IDC) 18 7.77 2 COND. SOLID COPPER FPLP/R ANALOG 6' UNSHIELDED E i AF "STEM "'UBMITTAL o y %a -1/320 `B LVD Qom: �' I FIL- 33541 DEVICE LEGEND SYMBOL QTY EXISTING MANUFACTURER PART NO DESCRIPTION FIRE ALARM CONTROL FEA—C-UTI 1 NEW SILENT KNIGHT 6808 (SK) PANEL, ADDRESSABLE, SK PROTOCOL WIRELESS COMMERCIAL CELL 1 NEW NAPCO SLE-LTEVI-CFB-PS FIRE ALARM COMMUNICATOR FAA 1 EXISTING SILENT KNIGHT 5860R ANNUNCIATOR VS 1 EXISTING GENERIC VALVE TAMPER SUPERVISORY SWITCH ADDRESSABLE MANUAL ------ 4 EXISTING SILENT KNIGHT SK-PULL-DA PULL STATION, DOUBLE -ACTION ADDRESSABLE MONITOR AIM 5 EXISTING SILENT KNIGHT SK-MONITOR MODULE FBO 3 EXISTING GENERIC DUCT DETECTOR ADDRESSABLE 0 2 EXISTING SILENT KNIGHT SK-PHOTO PHOTOELECTRIC SMOKE DETECTOR WF 1 EXISTING GENERIC WATERFLOW SWITCH 1 EXISTING SYSTEM SENSOR P2RK 2-WIRE HORN STROBE, STANDARD CD, WP OUTDOOR 2-WIRE, HORN STROBE,RED 5 EXISTING SYSTEM SENSOR P2RL 24%1IRE, HORN STROBE, C 8 EXISTING SYSTEM SENSOR PC2RL RED C 2 EXISTING SYSTEM SENSOR SRL STROBE, RED PROJECT INFORMATION PROJECT INFORMATION: NAME OF PROJECT: FEI SAVE A LOT #468 ADDRESS: 7320 GALL BLVD ZEPHRYHILLS, FL 33541 PROPOSED USE: MERCANTILE FIRE ALARM INSTALLER: ADT COMMERCIAL FIRE ALARM VENDOR ADT COMMERCIAL 4221 W JOHN CARPENTER FWY IRVING, TX 75067 877-776-1911 FIRE ALARM DESIGNER JODY CONGLETON, SET NICET IV 108686 ADT COMMERCIAL 4221 W JOHN CARPENTER FWY IRVING, TX 75067 REMOTE STATION LISTING CCN File No. Vol. No. UUFX S2684 20 877-776-1911 Jcongleton@adt.com 251-583-7165 CODE SUMMARY • APPLICABLE BUILDING CODES BUILDING FIRE ELECTRICAL W NFPA 72 0 ACCESSIBILITYW STATE FLORIDA FIRE CODE OTHER • OCCUPANCY CLASSIFICATION M • OCCUPANCY USE B, S-1 • FULLY SPRINKLERED BUILDING 2020 FLORIDA BUILDING CODE 2020 FLORIDA FIRE CODE 2017 NATIONAL ELECTRICAL CODE w 2016 NFPA 72 � 0 v t SYSTEM INPUTS REVIEW DATE CITY OF ZEPHYRHI LS FIRE AND LIFE SAFETY EXAMINER, ALL WORK SHALL COMPLY WITH NFFA CODES AND STANDARDS - SITE LOCATION - r SYSTEM OUTPUTS CONTROL UNIT NOTIFICATION REQUIRED FIRE SAFETY SUPPLE - ANNUNCIATION CONTROL MENTAR a • 'ALARM POWER - ■■■■��■■■■�■■■■■■ FIRE ALARM SYSTEM LOW 8ATTERY ULT NOTIFICATION .P .- ■■■■oo■■■■o■■■■■a IN -DUCT SMOKE DETECTORS ■■oo■■■o■o■■■■■■o o R CO • - . ■■oa■■■o■o■■■■■■o . co■■■■000■■■■■■■o OKE DETECTORS SPRINKLER CONTROL VALVE m ■■■■■■■■■■■■■■■■m ® ■■■■■■■■■■■■■■■■m ■ ■■■■■■■■■■■■■■■■m ■ ■■■■■■■■■■■■■■■■■ 112111111111111 ■■■■■■■■■■■■■■■■m m ■■■■■■■■■■■■■■■■m ■■■■■■■■■■■■■■■■m IAIBICIDIEIFIGI"IIIJIKILIMINIQIPI I -INDIVIDUAL HVAC SHUTDOWN '3z0AD c Commercial r ET SHEET: 4221 W JOHN CARPENTER FWY IRVING, TX75067 Web: adt.corrl/corrlmercial FRESH ENCOUNTER INC. FEI SAVE A LOT #468 7320 CALL BLVD ZEPHYRHILLS, FL 53541 FIRE ALARM SYSTEM PREPARED BY: This fire alarm shop drawing was prepared for equipment application only. The information contained herein is intended to aid in the installation of this system. No design changes have been made.. to the engineer of record's contract documents. JODY CONGLETON, SET NICET #108686 rr�IJs✓('�Ng,�iliN FIRE ALARM SYSTEMS LVL IV EXPIRES 06/01/2024 1/9/2023 ADT Commercial, LLC Edward Pleffner Ucense #EC13004155 1309 N Ward St, Tamps, F4 33607 REVISIONS NO. DATE REVISION BY: - Z'. BY: - '4' BY: - �s BY: - 6. BY: - BY: - PREPARED BY: J LC CHECKED BY: PROJECT MANAGER: DATE: 01 f 09/3 PROJECT NO: .. TITLE: ,i COVER SH FIRE ALARM CONTROL UNIT • DEDICATED 120V G ~j) 20 AMP CIRCUIT REPLACE CONTROL PANEL ALL EXISTING DEVICES REMAIN THE SAME N2-01 115cd C M N2.02 N2.03 115cd 115cd N2.04 EOL C C 110cd 8S1BO M001 D002 M002 M003 N3.01 N3.02 N3.03 115cd 115cd 115cd N3.04 N3.05 N3.06 N3.07 N3.08 N3.09 EOL C C C 110cd 15cd 15cd 110cd p 110cd 75cd ANN•1 ANNUNCIATOR • 4UX1.01 WF M005 M006 M007 M008 M009 A- AIM lA i r l V' - F�-- A- - AIM V- AIM FBO FBO �SS� VS I i l N1.01 N1.02 N1-03 EOL 75cd 75cd 115cd C WP C _,,_4 SYSTEM RISER 1 N.T.S. NAPCO CELLULAR DIALER NA -.� Total stand by current 0.08500 X Stand by hours 24 Stand by amp/hours 2.04 Total Alarm Current 0.40 X alarm Minutes (5)/60 0.083 AlarmTotal amp/hours 0.03 Total Amp/hours 2.07 X Derating factor of 20% 1.2 Minimum Battery Size 2.49 Battery Selected COMMUNICATOR CALCULATIONS 2 N.T.S. BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL FIRE ALARM CONTROL PANEL COMPONENTS 1 6808 MAIN BOARD PANEL MAIN BOARD SK 0.17 0.17 0.365 0.365 PROTOCOL CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) ANN IFAAI 1 5860R ANNUNCIATOR 0.02 0.02 0.025 0.025 AUX1 cE 1 SLE-LTEVI-CFB-PS Wireless Commercial Fire 0.071 0.071 0.2 0.2 Alarm Communicator FBO 1 DUCT DETECTOR 0 0 0 0 AIM 5 SK-MONITOR ADDRESSABLE MONITOR 0.000375 0,001875 0.000375 0.001875 MODULE M33 O 2 SK-PHOTO ADDRESSABLE PHOTOELECTRIC SMOKE 0.0003 0.0006 0.0003 0.0006 DETECTOR ADDRESSABLE MANUAL 4 SK-PULL-DA PULL STATION, 0.000375 0.0015 0.000375 0.0015 DOUBLE -ACTION 2-Wire Horn Strobe, Wp 1 P2RK Standard cd, Outdoor 75cd 0 0 0.176 0.176 N1 1 PC2RL 2-Wire, Horn Strobe; Red 0 0 0.143 0.143 C 75cd 1 PC2RL 2-Wire, Horn Strobe, Red 0 0 0.187 0.187 C 115cd 1 P2RL 2-Wire, Horn Strobe, Red 0 0 0.162 0,162 110cd N2 3 PC2RL 2-Wire, Horn Strobe, Red 0 0 0.187 0.561 C 115cd 1 P2RL 2-Wire, Horn Strobe, Red 0 0 0.121 0.121 75cd 3 P2RL 2-Wire, Horn Strobe, Red 0 0 0.162 0.486 N3 11 0cd 3 PC2RL 2-Wire, Horn Strobe; Red 0 0 0.187 0.561 C 115cd 2 SRL Strobe, Red 15cd 0 0 0.043 0.086 TOTAL STANDBY (A) 0.264975 TOTAL ALARM (A) 3.076975 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SECONDARY STANDBY LOAD (A) 0.264975 24 I 6.36 SECONDARY ALARM LOAD (A) 3.076975 0,08 1 0.26 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 6.62 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 7.94 PROVIDE (2) 12V 12AH BATTERIES *BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION. AUX1 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20A Max. Voltage Drop: 0 Min. Operational Voltage: 16 End Of Line Voltage: 20.4 Max. Circuit Current (A): 3 Voltage Drop Percent: 0.02 % Wire Resistance (t2/kFt): 3.07 Total Circuit Current (A): 0.2 Circuit Wiring Properties 'P' 14/2 FPLP/R (AUX) 14 AWG, 2 Cond. Solid Copper FPLP/R Unshielded Total Circuit Length (Ft): 3 Spare Current (A): 2.8 Distance measured using drawn segment lengths with 10,00 % additional length calculated Total Circuit Resistance (Q): 0.019699 Spare Current (A) Percent: 93.33 % DEVICE TOTALS Symbol Part No. Description Qty. Device Current (A) Total Current (A) c- SLE-LTEVI-CFB-PS Wireless Commercial Fire Alarm Communicator 1 0.2 0.2 Calculation Methods: Total Resistance (D) = Wire Resistance (O/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) N1 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.34 Min. Operational Voltage: 16 End Of Line Voltage: 20.06 Max. Circuit Current (A): 3 Voltage Drop Percent: 1.67 % Wire Resistance (.0/kFt): 3.07 Total Circuit Current (A): 0.506 Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded Total Circuit Length (Ft): 110 Spare Current (A): 2.494 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 0.673903 Spare Current (A) Percent: 83.13 % Symbol PartNo. Description Qty, Device Current (A) Total Current (A) C PC2RL 2-Wire, Horn Strobe, Red 75cd 1 0.143 0.143 DEVICE TOTALS Wp P2RK 2-Wire Horn Strobe, 1 Standard cd, Outdoor 75cd 1 0.176 0.176 C PC2RL 2 Wire, Horn Strobe, Red 115cd 1 0.187 0.187 Calculation Methods: Total Resistance (0) = Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A) N2 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20A Max. Voltage Drop: 0.74 Min. Operational Voltage: 16 End Of Line Voltage: 19.66 Max. Circuit Current (A): 3 Voltage Drop Percent: 3.63 % Wire Resistance (t2/kFt): 3.07 Total Circuit Current (A): 0.723 Circuit Wiring Properties: 'V 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded Total Circuit Length (Ft): 167 Spare Current (A): 2.277 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.025244 Spare Current (A) Percent: 75.90 % DEVICE TOTALS Symbol Part No. Description Qty. Device Current (A) Total Current (A) P2RL 2-Wire, Horn Strobe, Red 110cd 1 0.162 0.162 C PC2RL 2-Wire, Horn Strobe, Red 115cd 3 0187 0.561 Calculation Methods: Total Resistance (0) = Wire Resistance ((2/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (Q) x Total Circuit Current (A) N3 LUMP SUM REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20A Max. Voltage Drop: 1.87 Min. Operational Voltage: 16 End Of Line Voltage: 18.53 Max. Circuit Current (A): 3 Voltage Drop Percent: 9.18 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 1.254 Circuit Wiring Properties. 'V 14/2 FPLP/R (NAC) 14 AWG, 2 Cond, Solid Copper FPLP/R Analog Unshielded Total Circuit Length (Ft): 243 Spare Current (A): 1.746 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0), 1,492773 Spare Current (A) Percent: 58.20 % Symbol Part No. Description Qty. Device Current (A) Total Current (A) SRL Strobe, Red 15cd 2 0.043 0.086 DEVICE TOTALS P2RL 2-Wire, Horn Strobe, Red 75cd 1 0.121 0.121 P2RL 2-Wire, Horn Strobe, Red 110cd 3 0.162 0.486 C PC2RL 2-Wire, HornStrobe, Red cd 3 0.187 0.561 Calculation Methods: Total Resistance (D) = Wire Resistance (Q/Ft) x 2 x Total Circuit Length (Ft) Total Voltage Drop = Total Resistance (Q) x Total Circuit Current (A) �F Commercial 4221 W JOHN CARPENTER FWY IiIN, T. 77 Web.- dt,Com/'com m rci l FRESH ENCOUNTER INC. I SAVE A LOT #468 . 7320 GALL BLVD FIRE LA Y TF PREPARED BY: This fire alarm shop drawing was prepared for equipment application only. The informatian' contained herein' is intended to aid in, the instailation;of this system. No design changes have been made,to the engineer of recort3s contract documents. JODY CONGLETON, SET FIIREEA ARM6SYSTEMS LVL IV `Try GJ�l�~f%Jir EXPIRES 06/01/2024 1/9/2023 REVISIONS NO. DATE REVISION BY: �'•. BY: BY: 41 BY: - 5 BY: BY: 7. BY: - PREPARED BY: J LC CHECKED BY: PROJECT MANAGER: DATE: 01 /09/2 PROJECT NO: TITLE: RISER AND CALCULATIONS SHEET: Fool