HomeMy WebLinkAbout7631 Gall Blvd (10)JBA consulting si JOHNSTON' B►URKHOLDE ASSOCIATES ructural engineers STRUCTURAL FIXTURE ANCHORAGE CALCULATIONS FOR PREPARED FOR Q., • ••'�G E N F • ', ATE OF O •�Z 3 2 930 CENTRAL • KANSAS CITY, MO 64105 (816) 4214200 • WWW.JBAENGR.COM ZEPHYRHILLS STORE NO.: 0706 DRAWING INDEX GENERAL C:1 COVER SHEET ARCHITECTURAL - Al ENLARGED FLOOR PLAN ELECTRICAL Fl POWER PLANS RACKING- FXSI FIXTURE ANCHORAGE PLAN, NOTES, AND DETAILS BUILDING CODE SUMMARY SPECIAL PROJECT ENTERTAINMENT OF THE FUTURE NAME OF PROJECT: ZEPHYRHILLS, FL STREET ADDRESS: 7630 GAL BLVD, ZEPHYRHILLS, FL 33541 STORE MANAGER: KURT PHILLIPS PROPOSED USE: RETAIL BUILDING CODE: FLORIDA BUILDING CODE 6TH EDITION 2017 BUILDING EXISTING BUILDING CODE: FLORIDA BUILDING CODE 6TH EDITION 2017 EXISTING BUILDING MECHANICAL CODE: FLORIDA BUILDING CODE 6TH EDITION 2017 MECHANICAL PLUMBING CODE. FLORIDA BUILDING CODE 6TH EDITION (2017) PLUMBING ELECTRICAL CODE: NATIONAL ELECTRICAL CODE, 2014 FIRE CODE: FLORIDA FIRE PREVENTION CODE 6TH EDITION (2017) ACCESSIBILITY CODE. FLORIDA BUILDING CODE 6TH EDITION (2017) ACCESSIBILITY OCCUPANCY CLASSIFICATION: M-MERCANTILE; WHOLESALE OR RETAIL STORE (MAIN USE) - SECT. 309.1 S1-STORAGE AREA;MOTOR VEHICLE SERVICE STATION AND RECEIVING AND STOCK ROOMS (MIXED USE) - SECT. 311.2 A2-ASSEMBLY USE; BREAK ROOM AND FOOD TENANT (ACCESSORY TO MAIN USE) - SECT. 303.1 B-BUSINESS; NON FOOD TENANT (ACCESSORY TO MAIN USE) - SECT- 304.1 TYPE OF CONSTRUCTION: 2B (SPRINKLERED) PER SECT. 602.5 AND TABLES 601 AND 602 UNLIMITED ALLOWABLE AREA SECTION 507.3 FIRE PROTECTION: BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM AND IS SURROUNDED ON ALL SIDES BY 60 FEET MINIMUM OF PERMANENT OPEN SPACE AND COMPLIES WITH SECTION 507.3. UNLIMITED AREA CRITERIA IS APPLICABLE. CLASSIFICATION OF WORK - (EXISTING BUILDING CODE) LEVEL 1 - ALTERATIONS INCLUDING THE REMOVAL AND REPLACEMENT OR COVERING OF EXISTING MATERIALS, ELEMENTS, EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, EQUIPMENT OR THAT SERVE THE SAME PURPOSES - SECT. 503.1 EGRESS: NO CHANGES PROPOSED TO THE EXISTING BUILDING AREA, OCCUPANCY OR EGRESS. ALL EXISTING EXITS TO REMAIN. NOTE: BUILDING WILL BE OCCUPIED DURING CONSTRUCTION, AREAS WILL BE SECTIONED OFF WITH DUST PARTITIONS OR SECURITY FENCING AS NEEDED. sly M.- -- I __. I-' r I Lin- H F J�1� T I m m HL AREA OF WORK a a o 0 TIH C Ilt ° t,l 1, REF 1,2- 1 9!a .�.. _T d ' r Y , ,�� :N F3 � �;j �-i ICI �;J I —. �• r i.: r � c . I E'] �� -7 -. _ , - - ;c --�-� -- -- r- _ T f - _ kr- :- _ [3 MI L+r fill «I J 4T� E _ I rul I' r � , g. 'I , , T I�, n. ra I� {�T7---'':+r_... lu,r F ,7 44-1 - - n T i.S1 A LL r --• •-,-� '. , z I rl I j r I a 1 '- - '--• c ' i ...._ _ -- - - ,- -. - - - -- - - s� �� f r-, mJ y L � , i� ICI �� �,�-L' _lr 1 � , i � F� -' '-- - �-- -�: :.-.. s .T• , i u', -- ,� fur. I I I I I - - f ,t ... -, - IiR'li I....I. �• '_Ly"' :'" r1i� tr I r: • -, � i .' (,.� ,- T"h ; (�' ;• �: I c ' �ki I' '.... - r.-,. W,,�. a. I �. _: A I d-".1•.� f+-p r3+4 r.n°I _ _ 1-_- i----I ' i {"k -_- I I'� � 'I' III I��� III � i_I.j �I li'I ! -� !� �; 1 � j I I { I I '�:y�r• r hl , is - 1 : I I O � �• ,t � , �, � k++ - .�5 n ...� •YY +r:r �' _r:r r-.. '. �I Ili �I f - - - - :T- nolr_ ? +i a ogle_ , yr ,{ II if q M y • qW.rsor._ f y 'L f . Ne � •.� I ' ' REMODELED SQ FT: EXISTING SQ FT: DATE: 11)560 2051831 04/01/19 GENERAL REQUIREMENTS 1. ALL WORK SHALL BE DONE IN A SAFE MANNER AND IN STRICT ACCORDANCE WITH THE LOCAL AND/OR STATE (IF APPLICABLE) BUILDING CODES, NATIONAL ELECTRIC CODE (NEC), ADA-ADAAGS (ADOPTED HANDICAP ACCESSIBILITY REQUIREMENTS), OSHA AND ALL APPLICABLE CODES, REGULATION, ORDINANCES, AND AUTHORITIES HAVING JURISDICTION. 2. EACH CONTRACTOR AND THEIR SUB -CONTRACTORS ARE RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT HIMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE HIM OF ANY RESPONSIBILITY FOR PERFORMING HIS WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE- 3. THE EXISTING BUILDING SHALL BE PROTECTED FROM MOISTURE, DUST AND DEBRIS. INSTALL DUST PARTITIONS OR DRAPES AS REQUIRED AND/OR DIRECTED BY THE WALMART CONSTRUCTION MANAGER TO KEEP DUST AND MOISTURE FROM THE OPERATING AREAS OF THE STORE. 4 ANY DAMAGE TO WALMART PROPERTY, WHICH OCCURS DURING THE PROCESS OF CONSTRUCTION, SHALL BE REPAIRED/REPLACED AT NO ADDITIONAL COST TO WALMART, THIS INCLUDES ALL MERCHANDISE. THE CONTRACTOR SHALL PAY WALMART THE RETAIL COST FOR ALL DAMAGED MERCHANDISE. 5. THE CONTRACTOR SHALL KEEP WORK AREA CLEAN AND FREE OF DEBRIS AND SHALL REMOVE ALL TRASH AND DEBRIS FROM THE CONSTRUCTION AREA DAILY. NO FLAMMABLE MATERIALS OR LIQUIDS MAY BE STORED IN THE EXISTING BUILDING OR CONSTRUCTION AREAS. 6. REMOVE ANY EXISTING ITEMS, SERVICES, FINISHES OR SURFACES AS REQUIRED FOR THE INSTALLATION OF NEW CONSTRUCTION- PROVIDE FURRING FOR CONDUITS AND PIPING, SHOWN OR NOT, AND FINISH OUT FURRING TO MATCH ADJACENT FINISHES. 7. ALL ADJACENT TENANT SPACES SHALL REMAIN IN SERVICE DURING DEMOLITION AND CONSTRUCTION. 8. SCHEDULE ALL WORK TO KEEP DISRUPTIONS TO THE STORE OPERATIONS AT A MINIMUM. COORDINATE UTILITY DISRUPTIONS WITH THE WALMART STORE MANAGER. 9. WHERE EXISTING FINISHES ARE TO REMAIN, CLEAN, REPAIR, PATCH, AND/OR REPAINT AS NECESSARY TO BLEND WITH ADJACENT SURFACES. COORDINATE WITH WALMART CONSTRUCTION MANAGER. 10. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE TIMELY ORDERING OF MATERIALS TO PROHIBIT DELAYS OF THE CONSTRUCTION SCHEDULE OF THIS PROJECT- IT IS THE RESPONSIBILITY S ONSIBILITY OF THE CONTRACTOR TO COORDINATE DELIVERY OF MATERIALS IN A TIMELY MANNER. 11. CONTRACTOR TO MAINTAIN ACCESS TO ALL EMERGENCY EGRESS EXITS DURING CONSTRUCTION OPERATIONS. 12. EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS -BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITION. DEMOLITION NOTES 1. CONTRACTOR IS RESPONSIBLE FOR ALL JOBSITE SAFETY AND COMPLIANCE WITH OSHA REGULATIONS. CONTRACTOR WILL INSTALL TEMPORARY WALL AND CONSTRUCTION BARRIERS AND TAKE ALL PRECAUTIONS TO PROTECT CUSTOMERS AND ASSOCIATES FROM CONSTRUCTION OPERATIONS. 2. THE CONTRACTOR SHALL FIELD VERIFY THE EXTENT OF DEMOLITION. IF DISCREPANCIES ARE FOUND, CONTACT THE ARCHITECT AND WALMART CONSTRUCTION MANAGER. 3. WHEN UTILITIES ARE REMOVED, CAP AND SEAL A MINIMUM OF 8" BELOW FINISH FLOOR OR A MINIMUM OF 6" ABOVE FINISH CEILING. 4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF CONSTRUCTION WASTE AND DEBRIS. DO NOT USE STORE DUMPSTERS- PREVENT CUSTOMERS AND ASSOCIATES FROM CONTACT WITH CONSTRUCTION WASTE. 5. COORDINATE LOCATION OF CONTRACTOR'S DUMPSTER ON SITE WITH WALMART CONSTRUCTION MANAGER GENERAL SCOPE OF WORK REMOVE, RELOCATE AND ADD NEW FIXTURES- ' ADD POWER TO ENTERTAINMENT AREA AND PHOTO LAB. NEW PHOTO LAB. RELOCATED PHOTO LAB EQUIPMENT- 0 v W O C 4 J Q V W 4 y V� U) 2s r z' ¢ p p V) 0 ui p to S 4J ),. z�r zwtn z3 W, 5:gwwo-L"jZzww Of 0- p¢ Ww ooz�� O ow < zz¢caa`a mr-000 LLI U V)p ¢ ¢ Z wtn O 3o�ow\� �wM5za�r¢ w zb la1 po]4'w of zz QZV)gz d01-v)OW-j ov)o aF- 0 00Y2: 4 J2OW WwL,UKdLuz" ZU�w �w�wtO3 w005¢O =0Dwaaa� Qwa.womm>- w a cO O 00 z o w � F CD w E. W o 0, a--� � w cl) co CQ 4 N 0 ISSUE BLOCK CHECKED BY: RD DRAWN BY: SFvF PROTO: EOTF DOCUMENT DATE: 04/01 /19 COVER SHEET ARCHITECTURAL: ELECTRICAL: RACKING BUILDING OFFICIAL ADDRESS CUHACI & PETERSON CUHACI & PETERSON JOHNSTON BURKHOLDER ASSOCIATES CITY OF ZEPHYRHILLS BUILDING DEPARTMENT ROBERT S. DAY JAISON P. MORAS BART J. HALVERSON BILL BURGESS 1925 PROSPECT AVE, 1925 PROSPECT AVENUE 930 CENTRAL 5335 8TH STREET ORLANDO, FL 32814 ORLANDO, FLORIDA 32814 KANSAS CITY, MISSOURI 64105 ZEPHYRHILLS, FL 33542 —661- 7-661-91 —,+LI— SHEET: c 1 IL GC TO PURCHASE 525 SQFT OF VCT FOR SPOT REPLACEMENT NtW hIX IUKtJ ANU tUUIF'MtN I VERIFY LOCATION WITH WALMART FINAL MERCHANDISE PLAN (TYP) ENLARGED FLOOR PL 1 /16"=1'-O" RELOCATI PRINTER RELOCATED DL PRINTER wCOW RN'SH KEY REF SPECIFICATIONS FOR EXACT COLORS REQUIRED MARK FINISH COLOR DESCRIPTION VCT9 VINYL COMPOSITE TILE WHITE 12"X12"X " 3 PHOTO LAB 1/4"=l'-O" r- I I -r77 F k, L J II fTl r-T� FT-1 F--1 fTl rT� REMOVE PHOTO LAB MILLWORK I 1 11 III I I I I I I I I I I I I I AND RELOCATE EQUIPMENT. L J LJ r iii iL iJ l i L-'I iii rT1 I I LI I I I k+l 4- -4 I +-4 rT-1 -4-, I- I I I I I I I I I I I I I I I I I I I 1 1 1 It. I I I I I I I I I I I.t1 rt-1 I-t-I rT1 rt-I L 1J I I I I I I I I I I I I I I I I I I I LL I I I I I I I I I L1J I I I 1 f fTl rT1 rT1 fTl ~ -4 r-- L1J L1J L1J -A L I J L_J L_J L_J L _J L_J I } I L_J r--t IL I fTl rT� r`T-i r� TJ I I I I I I I I I I I r I L L1J LIJ L1J I I 1 T I -a I I I I I I I I I I I I f- -_i _r k + a F- + -! F- + -4 I j I I I I I I I 11 F F' , I I I I I I I I I I I I I I I I r 1 rtl rt1 rt-1 I j I I I I I I I I I I 1 I I I F fTl rT1 rT1 I I I I I I 'L I I 11 1L. LIi� u L LIJ LIJ // J L_J L_J L_J REMOVE/RELOCATE EQUIPMENT AND FIXTURE SHOWN. VERIFY WITH WALMART FINAL MERCHANDISE PLAN (TYP). OWNER FURNISHED GC INSTALLED PRE -MANUFACTURED WALL SYSTEM RELOCATED COLOR PHASER OWNER FURNISHED GC INSTALLED PRE -MANUFACTURED CABINETS r T-1 r-T1 f — -1 I- T -1 I I I L J I �+ J I I I I I I h t -1 I I I I I I rT1 G C > kM Li Lug ENLARGED DEMOLITION PLAN- 1/16"=l'-O" SHEET NOTES 1. GENERAL CONTRACTOR RESPONSIBLE FOR COORDINATION OF ALL ELECTRICAL WORK. REFERENCE ELECTRICAL FOR POWER REQUIREMENTS AT NEW AND RELOCATED FIXTURES. 2. REFERENCE FXS1 FOR FIXTURE ANCHORING REQUIREMENTS. 3. GENERAL CONTRACTOR CUT AND GRIND FLUSH WITH SLAB ALL ANCHOR BOLTS AT LOCATIONS OF REMOVED FIXTURES. 4. REINSTALL ALL FIRE EXTINGUISHERS IMMEDIATELY FOLLOWING COMPLETION OF FINAL FINISH TO MOUNTING SURFACE. 5. REMOVE AND REINSTALL ALL COLUMN MOUNTED EQUIPMENT AS REQUIRED FOR INSTALLATION OF NEW WORK, INCLUDING BUT NOT LIMITED TO ALL PAPER TOWEL DISPENSERS, PRICE CHECKERS, SPILL STATIONS, ETC. LEGEND EXISTING TO REMAIN DEMOLITION NEW PREMANUFACTURED WALL SCHEDULE A 4'-0" LONG WALL PANEL ASSEMBLY B 2'-0" LONG WALL PANEL ASSEMBLY C CORNER ASSEMBLY D 1'-O" LONG WALL PANEL ASSEMBLY W wy ZN ct) p �ow� a -moo D zWF zVV)ir- w o rw�w a0 ry W '��k',a_N as F—tosg Ryiz LL dfn<}4�rz 0-�QjW�O fn Cc: �W a3aNW�NQY _o 3Uvea=�spgW.zaW,¢ U R z \� O K s U W z ~ zVl a 0Kv) zI�z J~ WwR NF`(v_„))O r -WUW odz-..'uoj zOw=�awWOa0OO} U)a<n V)m�z�wan 2DUONdOwwadWn2"5 w a E- O O O OC9 w 0 w z�z � E ^� CD z Ow � z LLI O 0 F- o i 44 ^� w N z 0 ISSUE BLOCK CHECKED BY: RD DRAWN BY: SFvF PROTO: EOTF DOCUMENT DATE: 04/01 /19 22, 2019 ENLARGED FLOOR PLAN SHEET: Al I ELECTRICAL SYMBOLS LEGEND GENERAL NOTES (SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) SYMBOL DESCRIPTION FO LIGHT FIXTURE 1. FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND LABOR, FOR A 14. SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS AND / O (WALL MOUNTED/CEILING MOUNTED) COMPLETE INSTALLATION IN ALL RESPECTS, READY FOR INTENDED USE BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY LOCAL AND IN STRICT ACCORDANCE WITH NEC, NESC, STATE, AND LOCAL CODES. E-� LIGHT FIXTURE CODES, AND MANUFACTURER'S RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS. 5. EXISTING ELECTRICAL AND ALARM: LIGHT FIXTURE EMERGENCY LIGHT A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS THE A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS LIGHT FIXTURE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR WALLS. EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT SHOWN ON DRAWINGS, NIGHT LIGHT B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE. PROVIDE LABOR AND MATERIALS TO REWORK CIRCUITRY, AS 0 ENCLOSED COOLER/FREEZER LIGHT REQUIRED, TO MAINTAIN EXISTING OPERATION. C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE OPERATIONS. COORDINATE ALL DISRUPTIONS WITH WALMART B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT EXISTING le le le TRACK LIGHTING CONSTRUCTION MANAGER AND STORE MANAGER. UNDERGROUND SERVICES (ELECTRICAL, TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC.) PROVIDE ALL MATERIALS AND LABOR AS /® EXIT FIXTURE D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESS REQUIRED TO REROUTE, SLEEVE, OR OTHERWISE REWORK THESE (WALL MOUNTED/CEILING MOUNTED) BEFORE INSTALLING BOXES. FURNISH AND INSTALL EXTENDED SERVICES TO MAINTAIN THEIR EXISTING OPERATION. BOXES OR BOX EXTENDERS WHERE REQUIRED. EMERGENCY FIXTURE C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED PANELBOARDS DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM AND SWITCH, SINGLE POLE HAVE CIRCUIT BREAKER KNOCKOUTS PROPERLY COVERED AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO THAT SYSTEMS THAT ALL TRIM IS IN GOOD CONDITION, ALLOWING NO ACCESS TO REMAIN OPERATIONAL AT ALL TIMES. LIVE PARTS. $3 SWITCH, 3-WAY D. DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE 2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS: NOTED. $4 SWITCH, 4-WAY A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE STOPPING. B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL. 16. EXISTING ELECTRICAL DEMOLITION: C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM SEALANT. $K SWITCH, KEYED D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR SEALING A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL REQUIREMENTS AT ALL EXTERIOR MOUNTED DEVICES, FIXTURES, EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON THE $D SWITCH, DIMMER ENCLOSURES, AND RACEWAY PENETRATIONS. DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION. REMOVE ALL PANELBOARDS, DISCONNECT SWITCHES, BOXES, RELAYS, TIME 3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE SWITCHES, LIGHTS, DEVICES, ETC., WHICH WILL NOT BE REUSED. $VS SWITCH, VARIBLE SPEED PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS, ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT SHALL BE SIZED PER B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT, $M SWITCH, MANUAL MOTOR NEC BASED ON THWN 600 VOLT COPPER SINGLE CONDUCTORS, PLUS CONDUCTORS AND RELATED DEVICES SERVING SALES AREA THE EQUIPMENT GROUNDING CONDUCTOR. GONDOLAS BEING RELOCATED OR REMOVED. EXISTING CONDUIT 4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM FINISHED AND CONDUCTORS MAY BE REUSED FOR NEW POWER DROPS $OS SWITCH, OCCUPANCY SENSOR FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED OTHERWISE ON WHERE SIZE, RATING, AND CONDITION MEET REQUIREMENTS PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH INDICATED ON PLANS AND ALL U.L. RATINGS. REMOVE ALL UNUSED $$OS SWITCH, BI-LEVEL OCCUPANCY SENSOR MASONRY: CONDUIT AND CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER "SPARE". FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS ES / ® CEILING OCCUPANCY SENSOR AND ASSOCIATED RELAY A. SWITCHES +42" B. RECEPTACLES +20,r PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT BREAKER IN THE "OFF" POSITION. C. VOICE/DATA +20" RECEPTACLE, DUPLEX 5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING SPACES AND CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS. OTHER NON-PUBLIC AREAS (I.E., THROUGH STOCKROOM AREA): RECEPTACLE, DUPLEX, 6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE CUT WIRING LOOSE AND REMOVE FROM RACEWAY(S), LEAVING MOUNTED HORIZONTALLY PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS RACEWAY(S) IN PLACE. CONDUIT TO BE ABANDONED IN WALLS OR AFFECTED BY REMODEL. FLOORS SHALL BE REMOVED BACK TO FINISHED SURFACE AND RECEPTACLE, DOUBLE DUPLEX 7. NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN EXISTING CAPPED INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT. PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE RECEPTACLE, DUPLEX ISOLATED GROUND AND AIC RATING OF EXISTING OVERCURRENT PROTECTIVE DEVICES. D. ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE N ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE 8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG UNLESS PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE ON RECEPTACLE, DOUBLE DUPLEX, NOTED OTHERWISE IN SCHEDULES. WHERE 20A BRANCH CIRCUITS DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT ISOLATED GROUND HAVE #8 AND LARGER WIRE SPECIFIED, #10 AWG WIRE SHALL BE USED BREAKER IN THE "OFF" POSITION. RECEPTACLE, SIMPLEX TWIST LOCK, FOR THE FINAL CONNECTION (15-FT MAXIMUM). L5-15R, UNO 9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND DERATE E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO RECEPTACLE, SIMPLEX TWIST LOCK, CURRENT CARRYING CONDUCTORS PER NEC. SELECTIVE SITE DEMOLITION SPECIFICATION FOR DISPOSAL OF LIGHT FIXTURE. ISOLATED GROUND, L5-15R, LINO 10. PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH n RECEPTACLE, DUPLEX TWIST LOCK, CIRCUITS PER NEC REQUIREMENTS. F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF WORK `�#' L5-15R, LINO SHALL BE SECURED TO PREVENT FALLING, LOOSENING, OR RECEPTACLE, DUPLEX TWIST LOCK, 11. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE SHALL CREATING DAMAGE OF ANY KIND IN THE FUTURE. nn BE MADE TO BRIDGING OR JOIST WEB MEMBERS. UTILIZE ONLY THE `W ISOLATED GROUND, L5-15R, UNO TOP AND BOTTOM CHORDS FOR SUPPORTING THE ELECTRICAL 7. ETHERNET CABLE: RECEPTACLE, SPECIAL SYSTEM INSTALLATIONS. A. FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON PLANS. 12. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE SURFACE PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES AND/OR RECEPTACLE, SIMPLEX MOUNTED UNLESS NOTED OTHERWISE. REFER TO ARCHITECTURAL ORDINANCES. DOCUMENTS FOR CONDUIT INSTALLATION AND SEALING RECEPTACLE, PLUG -MOLD REQUIREMENTS. B. ETHERNET CABLE IS FURNISHED BY OTHERS. 13. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM AND C. ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER POLES. O JUNCTION BOX BRANCH CIRCUITS NOTED BY LEGEND SHALL BE INSTALLED UNDER (WALL MOUNTED/CEILING MOUNTED) SLAB. ALL OTHER FEEDER AND BRANCH CIRCUITS SHALL BE D. ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS OA JUNCTION BOX, ALARM SYSTEM INSTALLED OVERHEAD. PROVIDE EXTERIOR COATED GRC BENDS ON ALL CONDUIT RUNS THAT HAVE 45 DEGREE BENDS OR GREATER. REF DIRECTED BY WALMART CONSTRUCTION MANAGER. (WALL MOUNTED/CEILING MOUNTED) SPECIFICATIONS. ALARM JUNCTION BOX, ® FOR REMOTE TEST/RESET (WALL MOUNTED/CEILING MOUNTED) EQUIPMENT CONNECTION POINT 0 (PROVIDED WITH EQUIPMENT) Eh NON -FUSED DISCONNECT 01 FUSED DISCONNECT SNATCHED/ TRAVELERS NEUTRAL CIRCUIT, CONCEALED IN WALLS OR CEILING, E INDICATES EXISTING Ic HOTS GROUND WIRING CIRCUIT, CONCEALED IN FLOOR SLAB, _ E INDICATES EXISTING WIRING CIRCUIT, EXPOSED, E INDICATES EXISTING WIRING FLUSH MOUNTED PANELBOARD - SURFACE MOUNTED PANELBOARD VOICE/DATA, -/-d/-v d = DATA ONLY, v = VOICE ONLY 0 LOW VOLTAGE CABLE BOX FOR OTHER m VOICE/DATA, FLUSH FLOOR MOTOR 7 8 2-1/2" UNISTRUT STRAP FIRMLY CLAMPED TO CONDUIT 2-1/2" PVC CONDUIT PHOT 1 /8" = 1'-O" �O TELEPOWER POLE I I FURNISH AND INSTALL QUAD I ELECTRICAL CONTRACTOR TO DISCONNECT EXISTING POWER AND RECEPTACLES IN WIRELESS AND DATA AS REQUIRED FOR REPLACEMENT OF GONDOLA BY GENERAL �• PUSH BUTTON CHECKOUT KIOSK THAT DOES NOT CONTRACTOR. RECONNECT POWER AND DATA UPON PLACEMENT ON 3'-2" CONTAIN A POWERPOLE, TYP. NEW GONDOLA. COORDINATE WITH GENERAL CONTRACTOR. In 1 BUZZER ENL OS SMOKE DETECTOR PD2 _ i 3 OENERGY MANAGEMENT I 16.470 S TEMPERATURE SENSOR a' 16.957 E1 10'-8" 10'-4" 9'-8" 10'-0" 5'-7" 0 10'-6" -* 17'-5" OT THERMOSTAT (-- ENG J I0 or FTC TIME CLOCK PD2 87 °I ABBREVIATIONS 16.470 a, b, c LOWER CASE LETTERS INDICATE HD HAND DRYER 16.957 I Ll o sm SWITCHING CONFIGURATION IG ISOLATED GROUND I O AFC ABOVE FINISH COUNTER IRC INTER -REGISTER AFF ABOVE FINISH FLOOR COMMUNICATION AFG ABOVE FINISH GRADE ISP IN-STORE PROCESSOR 1 70 16.470 C CONDUIT LCU LIGHTING CONTROL UNIT 1 1 57 66.957 1 CCT CIRCUIT K KEY OPERATED 16.470 16.470 16.470 16.470 CF CEILING/CIRCULATION FAN N NEUTRAL 16.957 16.957 16.957 16.957 D DATA NTS NOT TO SCALE 16.470 EC ELECTRICAL CONTRACTOR P WITH PILOT LIGHT 16.957 EF EXHAUST FAN RH RADIANT HEATER ENG tPD2 tE 5 LE IPD PN EP EXPLOSION PROOF RC REFRIGERATION �n E1 NG ETR EXISTING TO REMAIN CONTRACTOR J J PD2 EWC ELECTRIC WATER COOLER SC SECURITY CAMERA o 2A SIMILAR,TYP 72A FUT FUTURE SF SUPPLY FAN GR GROUND TR TAMPER RESISTANT 1 15'-11" 1 ;-4" GFEP GROUND FAULT EQUIPMENT TYP TYPICAL 0° PROTECTION WH WATER HEATER GFI GROUND FAULT CIRCUIT WP WEATHERPROOF PD2 PD2 ENT ENT ENT EN ED PD2 INTERRUPTER WR WEATHER RESISTANT GF GABLE FAN UH UNIT HEATER UNO UNLESS I OTHERWISENOTED 1 B11 B 1 g11 B o' 1. 1 BL1 B 1 BL1 B 1 BL1 B 0 PROVIDE 3/8" FLEXIBLE METAL WHIPS FROM JUNCTION BOX AND CONNECT AT TOP OF POWER POLE. CABLE WHIPS TO POWER POLE SHALL BE INSTALLED IN A NEAT AND WORKMAN -LIKE MANNER. ROUTE WHIPS TO TERMINATIONS ALONG UNISTRUT OR STRUCTURE AND SUPPORT EVERY 12" TO 24". EXCESS CABLE SHALL BE KEPT TO A MINIMUM AND TIGHTLY COILED AND ATTACHED TO UNISTRUT OR JOIST. NO CONNECTION OF ANY KIND SHALL BE MADE TO JOIST WEB MEMBERS, JOIST BRIDGING, OR ROOF DECK. MAINTAIN MINIMUM 6" CLEARANCE FROM TOP OF POWER POLE TO ROOF DECK. JUNCTION BOXES AND RACEWAYS SHALL NOT BE MOUNTED WITHIN 1-1/2" OF DECK. EXTEND POWER POLE 12" MIN. WITHIN PVC SLEEVE EXTENDER ARM / POWER POLE FINISHED FLOOR PVC SLEEVE LENGTH 12" MIN. TO 36" MAX. TO ACCOMMODATE VARIATIONS/ IN STRUCTURE HEIGHT. INSTALL CEILING FLANGE PROVIDED WITH POLE FOR STORES WITH LAY -IN CEILING ANCHOR POWER POLE TO FLOOR OR GONDOLA WITH FOOT BRACKET PER MANUFACTURER RECOMMENDATIONS UNISTRUT PROVIDE 1-1/4"\ FENDER WASHER, LOCK WASHER AN NUT, TYP PROVIDE UNISTRUT PER SPECIFICATIONS. LENGTH AS REQUIRED TO SPAN JOISTS. SECURE TO BOTTOM CHORD OF BAR JOIST. POWER POWER POLE CONNECTION, PHOTO LAB 16.492 =CTRCAL DEVICES, CIRCUITRY ANC) O PANEL BOAR___] PROVIDE 1 /4" BOLT AND 1-1/4" FENDER WASHER TYP PROVIDE UNISTRUT P1026 ANGLE FITTING OR EQUAL BOTTOM CHORD OF BAR JOIST 0&3&18 EP42 8 ROUTE POWER AND DATA/VOICE - CONDUITS FROM THE STRUCTURE ABOVE DOWN TO THE PHOTO LAB COUNTERS THROUGH POWER POLE WHEN PHOTO LAB' IS LOCATED ON THE SALES FLOOR. BL1 A BL1 A C16.470 H 16.470 16.957 LAB DEMO POWER PLAN POWER DROP PL. r ALCOA H G.5 0 PHASER- P AND SP UNIT WIDE FORMAT PRINTER PHOTO LAB HP\ \ BL1 A DL PRINTER 16.470 16.957 - BL1 A 16.470 16.957 NOTE GENERAL POWER NOTES 11.19.10 EN09 THAT REUIRES POWER1 ARANGE ALLBOX(ES) TO MOUNTNTO INTERRUPTIONS�ORK THE STORE4TO BE ACCOMPLISHED TOP SI EE OF BOTTSOM CHORD OF BAR: JOIST. INSTALL AFTER NORMAL STORE BUSINESS HOURS. NOTIFY THE FURNISHED POWER POLE AND TERMINATE WIRING TO STORE MANAGER AND THE WALMART CONSTRUCTION JUNCTION BOX. PROVIDE UNISTRUT SUPPORTS AND MANAGER A MINIMUM OF 48 HOURS IN ADVANCE OF ALL HARDWARE TO SECURE TELEPOWER POLE PLUMB TO STORE POWER INTERRUPTIONS. STORE MANAGER MUST BUILDING STRUCTURE. REF POWER POLE ALLOW FOR POWERING DOWN OF COMPUTER SYSTEMS, CONNECTION DETAIL. MOVING AFFECTED PRODUCT, MODIFICATION OF WALMART AFTER-HOURS WORK SCHEDULES, 2. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT COORDINATION WITH OTHER TRADES, AND OTHER AND WIRING FROM DISCONNECT SWITCH OR CRITICAL SCHEDULING CONCERNS. PROVIDE JUNCTION BOX TO EQUIPMENT KNOCKOUT OR TEMPORARY POWER AS REQUIRED. INSTALLATION OF ELECTRICAL CONNECTION POINT. NEW EQUIPMENT SHALL BE COMPLETED AND THE POWER SYSTEM TESTED AND RE -ENERGIZED PRIOR TO 3. WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE START OF BUSINESS THE FOLLOWING MORNING NO RATING DIFFERS FROM SIZE PROVIDED, CHANGE OUT LATER THAN A TIME ESTABLISHED BY THE STORE BRANCH CIRCUIT WIRING AND OVERCURRENT DEVICE MANAGER AND THE WALMART CONSTRUCTION TO APPROPRIATE RATING PER NEC. MANAGER. 4. UPON COMPLETION OF ELECTRICAL INSTALLATION AND PRIOR TO ENERGIZING CIRCUIT: A INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE. B. PERFORM CONTINUITY TEST. C. VERIFY PROPER PHASING CONNECTION TO ALL THREE PHASE MOTOR LOADS. POWER DROP NOTES 03.27.15 EN01 a 1. POWER DROPS WILL BE IDENTIFIED BY AN IPTV TAG OR POWER TAG, I.E. 44A, 46E, ETC. ALL CHECKOUT POWER SHALL BE CONSIDERED POWER DROPS. 2. A REVISION OF THIS PLAN BASED ON THE FINAL MERCHANDISE LAYOUT MAY BE ISSUED TO SHOW FINAL LOCATIONS FOR THE POWER DROPS. IF THE MERCHANDISE PLAN DOES NOT CHANGE, THIS PLAN WILL NOT BE REISSUED. PROVIDE CIRCUITRY TO DISPLAY RACKS AS THE RACKS ARE SET. IN ADDITION, THE FOLLOWING POWER DROP NOTES APPLY: A. THERE WILL BE NO ADDITIONAL CHARGE FOR DROP RELOCATION WITHIN POWER DROP ZONES DEFINED ON DRAWING. B. AT CLOSE OF PROJECT THE GENERAL CONTRACTOR AND CONSTRUCTION MANAGER SHALL REVIEW ADDITIONAL OR DELETED POWER DROPS WITHIN EACH ZONE TO VERIFY ANY ADDITIONAL CHARGES OR CREDITS THAT APPLY DUE TO CHANGES. C. ADDING OR SUBTRACTING A POWER DROP TO ANY ZONE WILL RESULT IN A CHARGE OR CREDIT ACCORDING TO SPECIAL CONDITIONS. 3. PROVIDE JUNCTION BOX AND CIRCUITRY TO NEAREST JOIST ABOVE LOCATION SHOWN ON DRAWING. EXTEND CONDUIT AND CIRCUITRY FROM JUNCTION BOX TO ENDCAP OF DISPLAY RACK (AWAY FROM ACTION ALLEY). 4. PROVIDE CONDUIT, RECEPTACLE(S) AND FINAL CONNECTIONS AT DISPLAY RACK SHELVING PER POWER DROP SCHEDULE UNLESS NOTED OTHERWISE ON DRAWING. VERIFY EXACT HEIGHT AND LOCATION OF RECEPTACLE(S) WITH STORE PLANNING SET-UP SUPERVISOR PRIOR TO INSTALLATION. BL1 A 16.470 5. POWER DROPS FED FROM TRACK BUSWAY:INSTALL 16.957 PLUG-IN UNIT IF REQUIRED ON TRACK BUSWAY AT POINT NEAREST TO POWER DROP(S) 0 POWER DROP SCHEDULE O 07.28.17 ES01 NO DESCRIPTION VOICE/DATA BOX PRE -INSTALLED BY -P CABINET MANUFACTURER. OUTLET BOX PRE -INSTALLED BY CABINET P MANUFACTURER. FURNISH AND INSTALL RECEPTACLE, COVERPLATE, AND CIRCUITRY. ALL EQUIPMENT IS SINGLE PHASE. ROUTE ALL CIRCUITRY THROUGH COUNTERS AND WALLS UNLESS OTHERWISE NOTED. PHOTO LAB POWER 1 /4" = V-0" PD1 MOUNT RECEPTACLE(S) ON TOP OF DISPLAY UNIT (S) OPD2 MOUNT RECEPTACLE(S) 6" ABOVE BASE OF DISPLAY UNIT(S) SO THAT RECEPTACLE(S) AND O CONDUIT DO NOT INTERFERE WITH SHELF HEIGHT ADJUSTMENTS PD3 PROVIDE DIRECT CONNECTION TO EQUIPMENT PD4 OPEN STRUCTURE: MOUNT RECEPTACLE AT BAR JOIST AND INSTALL FURNISHED CORD REEL. LAY -IN CEILING: PROVIDE RECESSED CEILING RECEPTACLE AND INSTALL FURNISHED CORD REEL BELOW CEILING. CORD REEL SHALL BE MOUNTED TO CEILING FAN RATED JUNCTION BOX SECURED TO LAY -IN CEILING WITH T-BAR BOX HANGER. PROVIDE 1 /2" THREADED STEEL ROD FROM JUNCTION BOX TO BOTTOM OF STRUCTURAL JOIST OR CHANNEL STRUT BRIDGING ABOVE FOR SUPPORT. 20A WIRE SIZING SCHEDULE ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE. THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE PLAN WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM. O1 O2 0 O4 O5 (D C) O7 0 0 10 11 12 13 14 BUSWAY BL1A AND BL1B FEED FROM PANEL L1 D2 LOCATED IN ELECTRICAL ROOM 41 � KEY PLAN 120 VOLT #12 #10 #8 #6 1-5 AMPS 200 FT. 325 FT 490 FT 770 FT. 6-10 AMPS 100 FT 160 FT. 245 FT 385 FT, 11-15 AMP 70 FT., 110 FT., 165 FT., 255 FT. 277 VOLT #12 #10 #8 #6 1-5 AMPS 480 FT. 760 FT 1170 F .1865 FT 6-10 AMPS 240 FT. 380 FT 585 FT 930 FT. 11-15 AMPT 160 FTI 250 FTJ 390 FTj 620 FT. ELECTRICAL KEYNOTES 16.470 FURNISH AND INSTALL NEW 20 AMP, 120 VOLT CIRCUIT(S). FEED FROM PANELBOARD AS INDICATED. PROVIDE 20A-1P CIRCUIT BREAKER IF NEEDED. EC SHALL MATCH TYPE AND AIC RATINGS OF EXISTING CIRCUIT BREAKERS. EC SHALL VERIFY PRIOR TO ROUGH -IN THAT EXISTING PANELBOARD HAS SPARE CAPACITY TO ACCOMMODATE ADDITIONAL LOAD. 16,492 EC SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECTURAL DEMOLITION PLANS THE EXTENT OF ELECTRICAL DEMOLITION. REMOVE CONDUITS AND WIRES ALL THE WAY BACK TO ORIGINATING JUNCTION BOXES OR PANELBOARDS. DEMOLITION SHALL NOT AFFECT ACTIVE CIRCUITS. LABEL DEMOLISHED CIRCUIT(S) IN PANELBOARDS AS "SPARE". COORDINATE EXACT REQUIREMENTS WITH EXISTING CONDITIONS PRIOR TO BID. 16.957 CONNECT CIRCUIT(S) TO EXISTING BRANCH CIRCUITRY. MINIMUM WIRE SIZE AND PANELBOARD CIRCUIT ARE NOTED. VERIFY SIZE, RATING AND CONDITION OF EXISTING BRANCH CIRCUIT CONDUIT AND WIRE PRIOR TO USE TO ENSURE THAT THEY MEET REQUIRED SIZE, AND ALL U.L. RATINGS AND REPLACE AS REQUIRED. A EXISTING CONDITIONS WERE TAKEN FROM EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A ORIGINAL DRAWINGS AND MAY NOT REFLECT THOROUGH KNOWLEDGE OF ALL DRAWINGS AND EXACT "AS -BUILT" CONDITIONS. CONTRACTOR SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE SHALL FIELD VERIFY ALL EXISTING CONDITIONS TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR NOT RELIEVE THE RESPONSIBILITY OF PERFORMING SHALL CAREFULLY COORDINATE NEW WORK AND THE WORK PROPERLY. NO ADDITIONAL COMPENSATION DEMOLITION WITH ALL OTHER DISCIPLINES AND SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT EXISTING CONDITIONS. OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. o_ e( N O O p co gn. >r B LIJw ,may, 1,. 0 Iz- TzaF zWaNW,— Owz W 0 I20ulx aSul, a8 � as �~oaoo�=ZaW= 0 ww g 0a aw WP0 � O Z Q JWa'F�� Li O� >z< zo z k F_ F_ p Z aQa��Wa3X�nwoar O z3c�eo ~ vai asokDo'vgi��`w'�aZz Q O-=www>_ U. n0 D xZ a i0-jou.WUWZ0w a LomNw=zkow000 �np��aamN o z a I— D Ln z 0 U a %60 O © O O w � z Q ^rz, O x C/D 0 � z W 0 .-. O F-- o r-I w N z C� 0 ISSUE BLOCK CHECKED BY: JPM DRAWN BY: DG PROTO: EOTF DOCUMENT DATE: 04/01 /19 .% ?fkADEFP Ole Nz�0 .,\C•E•NSc� ��•' Nd769 .(P Mar 29, 2019 POWER PLANS SHEET: El I ! IL - 1L! I __ I I .1 CLOSURE TUBE - NO SLOTTED OPENING AT MID SPAN OF FRAME n OUTSIDE FACE OF END FRAME ANCHOR STRAP (1" WIDE x 22GA THICK) FIELD CUT STRAP AS SHOWN AND ATTACH N cO TO INSIDE FACE OF FRAME WITH (2) 22 GAUGE 1 #12-14x3/4" TEK SCREWS AT SPACING STEEL STRAP SHOWN. REF 3-FXS1 FOR PLACEMENT OF STRAP AND ANCHOR TO SLAB WITH SAME 1/2" DIAMETER BOLT NOTED FOR TYPICAL ANCHOR HOLE 1 o 'a - CONDITION AT THE END FRAME. _ 4Q 1 1/2" •" ALTERNATIVE ANCHOR STRAP/BOLT CONNECTION AT ALTERNATIVE ANCHOR AT END FRAMES - ONLY ALLOWED FOR USE WHEN 4A - TYPICAL SINGLE ANCHOR STRAP HALF GONDOLA END FRAME I CLOSURE TUBES DO NOT HAVE A SLOTTED OPENING CLOSURE TUBE (TYP AT HALF GONDOLA END FRAME) OUTSIDE FACE AT END FRAME LIGHT GAUGE STEEL STRAP (GALVANIZED) 1" WIDE x 22 GA MIN THICKNESS REF 3-FXS1 FOR PLACEMENT OF STRAPS (1) ANCHOR BOLT(S) PER STRAP/PLATE: 3/8" DIA •,d- DEWALT SCREW BOLT+, REF 2-FXS1. .a a 9 , hnom = 2", ho = 2 1/2", (UNO). AT GONDOLA INTERIOR & END FRAMES 94A TYPICAL ANCHOR AT GONDOLA FRAMES 1 112" = T-0" DESIGN SHELF LOADS: 12" SHELF = 50 LBS/SHELF 15" SHELF = 50 LBS/SHELF (APPAREL) 18" SHELF = 125 LBS/SHELF = 50 LBS/SHELF (APPAREL) 24"(+) SHELF = 150 LBS/SHELF = 225 LBS/SHELF (GROCERY) 30" (HD TV) SHELF = 75 LBS/SHELF NO. OF SHELF LEVELS/FIXTURE HEIGHT: (4) LEVELS AT HT. < 48" (5) LEVELS AT 48" < HT. < = 90" (7) LEVELS AT HT. > 90" (4) LEVELS AT "24V" & "24X" (FULL) = 78" & 90" (4) LEVELS AT HD TV = 120" (YZ) (NOTE: ITEMS LISTED MAY NOT EXIST IN PROJECT). VARIES TYPICAL SHELF FRONT VIEW EXISTING WALL STUDS EXISTING WOOD BLOCKING (CONTACT ARCHITECT FOR DIRECTION IF BLOCKING IS NOT FOUND AS SHOWN) �— BOLT ALL UPRIGHTS TO WALL, REF GONDOLA UPRIGHT ANCHORAGE AT WALL GONDOLA UPRIGHT FRAME, REF PLAN NOTE: ANCHOR AT UPRIGHT IS NOT REQUIRED IF FRAME HEIGHT OR ADJACENT WALL HEIGHT IS LESS THAN 72" (6-0") BOLT ALL UPRIGHTS TO WALL AT 6'-0" AFF. USE (1) 1/4"x6" LAG SCREW WITH 1/2" DIA WASHER AT STUD WALLS GONDOLA UPRIGHT FRAME, REF FINAL MERCHANDISE PLAN NOTE: HALF GONDOLAS SHALL BE ANCHORED TO WALL AS SHOWN TO SATISFY OWNER REQUIREMENTS. WALL ANCHORAGE IS NOT REQUIRED FOR SEISMIC DESIGN OR CODE COMPLIANCE. WOOD BLOCKING AT STUD WALLS GONDOLA UPRIGHT ANCHORAGE AT WALL 3, REF XS� REF 3-FXS1 FOR BASE ANCHORAGE WALL ANCHOR AT HALF GONDOLA UPRIGHT NTS 4„ 21/2" MIN 6 1/2" MAX END OF AT 24" HALF GONDOLA FRAME TY EACH S DE I I O Z) z u6 WALL OR FIXTURE FIXTURE a 2 FRAME a U) = w SHELVES CL OF ABOVE 0 9 LL 00 ANCHOR o = i- z BOLTS, TYP l 4A v z a Q w XS UPRIGHT a z FRAME, TYP i - - (2) ANCHOR can z w wz STRAPS, TYP O F U AT INT FRAMES = w U (1) ANCHOR STRAP, Q o } 4A TYP AT END FRAME o Q XS (INSERT STRAP > o w THRU SLOT AT TOP O w OF FRAME LEG) a UL "Ell HALF GONDOLA PLAN VIEW VARIES WALL OR FIXTURE FRAME REF 5-FXS1 FOR HALF GONDOLA SIDE VIEW AT WALL OR FIXTURE FRAME F TYPICAL GONDOLA SHELVING ELEVATIONS 3/8" = T-0" UPRIGHT POST CONNECTION TO ca E d TIGHTENING REQUIREMENTS: - d-'. "SNUG TIGHT" - NO GAP BETWEEN L L HEAD OF ANCHOR BOLT AND BASE 4. PLATE OR ANCHOR STRAP. b t - PLATE/STRAP THICKNESS 4 ° : ~"° hnom - EMBEDMENT DEPTH ` ho - MIN HOLE DEPTH � . 'o , n• -. La - LENGTH OF ANCHOR NOTE: ALL ANCHOR BOLTS SHALL BE DEWALT SCREW BOLT+. THE ANCHORS MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS AND PER ICC ESR-3889 REPORT. (IN CASE OF CONFLICT, THE ICC ESR- 3889 GOVERNS). REF ANCHOR DETAILS FOR DIAMETER AND EMBEDMENT. NOTE: IF CENTERLINE OF ANCHOR BOLTS FALLS WITHIN 1 3/4" OF CONTROL JOINT, SHIFT FIXTURE 2" (MAX) PERPENDICULAR TO THE JOINT, OTHERWISE SUBMIT RFI TO THE ARCHITECT FOR ALTERNATE INSTALLATION BEFORE INSTALLING BOLTS. ANCHOR BOLT DETAIL NTS BASE DECK SHELVING REMOVED FOR CLARIT) INSTALLATION NOTES: 1. GAPS BETWEEN SHELVES SHALL NOT EXCEED 5/8". 2. UPRIGHT DEFLECTION SHALL NOT EXCEED 1 3/8" IN A HORIZONTAL PLANE. 3. SHELVES SHALL NOT SLOPE DOWN TO THE FRONT DUE TO UPRIGHT DEFLECTION. 4. SHELVES ABOVE BASE DECK SHELVING LEVEL SHALL NOT EXTEND BEYOND BASE DECK SHELVING AT ANY TIME. 5. EXTENDERS SHALL NOT BE USED ON ANY HALF GONDOLA THAT WILL CREATE A HEIGHT OF 72" OR TALLER UNLESS IT IS ANCHORED TO THE WALL. ALL HALF GONDOLAS 72" OR TALLER MUST BE ANCHORED TO THE WALL AT 72" AFF, REF GONDOLA UPRIGHT ANCHORAGE AT WALL. DENOTES ANCHOR BOLT(S) AT SHELVING FRAMES REQUIRING ANCHORAGE, REF SHELVING I__24X—I FIXTURE AND ANCHORAGE SCHEDULE FOR REQUIRED ANCHORAGE DETAIL, TYP ONLY THOSE SHELVING FIXTURES NOTED ON THIS PLAN REQUIRE ANCHORAGE (UNO). FIXTURE ANCHORAGE PARTIAL PLAN T. = 20'-0" ui w N J Or Z) O w L cf)0 Z W w L u)�w-ZrO�zu� wLLJ ~zw~�waz�r z Q~ Hu)Lwi W LLOpw�� WpU wwa3~�¢�irawz< O d~ J z cn��n¢p�0=>p��¢ zQJ �0=p �(7pzz LwLI xZNz<a OOF,,�- 1Lz W=-00p EzQ2�o<LLO�Uafwns�_>LLOrnuw wMw(wz ox mo¢ zFt:81286H wa 0u)agXXDN0ui08X<�g w z7 C) c) Q) 'c) i Iv/'� F� O cn M V t Vf LU) n, a cn o a O U < w 0 00 _ w c=) c) 00 0 Z w J Z n n a P-1 ow Z .. w �°r J w CD of T � N i 0 T� 1 w m Wz NO ISSUE BLOCK CHECKED BY.- DGH DRAWN BY: MAV PROTO: EOTF DOCUMENT DATE: 04/01/19 JBA PROJECT NO: 1935000706 �%HAL = N o L" ATE OF O H 1 O'.:•' S I I. I� f� SHEET FXS1i FIXTURE ANCHORAGE PLAN, NOTES AND DETAILS