HomeMy WebLinkAbout7866 Gall BlvdBUILDING INFORMATION
APPLICABLE CODES
ALL CONSTRUCTION SPECIFIED ON THESE DOCUMENTS SUBMITTED FOR
BUILDING PERMIT SHALL COMPLY WITH ALL CODES AND ORDINANCES
OF CITY OF ZEPHYRHILLS, FLORIDA. INCLUDING REVISIONS,
AMENDMENTS AND APPENDICES TO THE FOLLOWING CODES:
FLORIDA EXISTING BUILDING CODE 7TH EDITION (2020)
FLORIDA ACCESSIBLITY CODE 7TH EDITION (2020)
FLORIDA MECHANICAL CODE 7TH EDITION (2020)
FLORIDA PLUMBING CODE 7TH EDITION (2020)
FLORIDA FIRE PREVENTION CODE 7TH EDITION (2020)
FLORIDA ENERGY CONSERVATION CODE 7TH EDITION (2020)
ADDITIONAL APPLICABLE CODE
NFPA 101 LIFE SAFETY CODE FLORIDA EDITION
NATIONAL ELECTRIC CODE 2017 EDITION
FLORIDA EXISTING BUILDING CODE 7TH EDITION (2020)
OCCUPANCY CLASSIFICATION
FLORIDA BUILDING CODE, CHAPTER 3:
SECTION 304,1: BUSINESS GROUP B CLINIC, OUTPATIENT
BUSINESS GROUP B OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A
BUILDING OR STRUCTURE, OR A PORTION THEREOF, FOR OFFICE,
PROFESSIONAL OR SERVICE -TYPE TRANSACTIONS, INCLUDING STORAGE OF
RECORDS AND ACCOUNTS.
OCCUPANT USE- CLINIC, OUTPATIENT
Buildings or portions thereof used to provide medical care on less than a
24-hour basis to persons who are not rendered incapable of self-
preservation by the services provided FBC 202.
CONSTRUCTION CLASSIFICATION
FLORIDA BUILDING CODE, CHAPTER 6:
TYPE II-B CONSTRUCTION - EXISTING CONSTRUCTION PERMITTED
EXIST SHELL BUILDING INFO
BUILDING HEIGHT: 1 STORY
SPRINKLERED: NO
MEZZANINE: NO
FIRE DISTRICT: NO
e.
INTERIOR FINISHES
FLORIDA BUILDING CODE, CHAPTER 8:
BUSINESS - GROUP B (NON-SPRINKLERED)
INTERIOR WALL AND CEILING FINISHES REQUIREMENTS - TABLE 803.5
EXIT ACCESS CORRIDORS / EXITWAYS: CLASS B
ROOMS AND ENCLOSED SPACES: CLASS C
BUILDING / UNIT INFORMATION
TENANT S F. COMMON AREA S.F. TOTAL FLOOR S.F.
1ST FLOOR = 6,706 S.F. N/A N/A
ADDITIONAL PERMITS
ANY APPLICABLE PERMITS OR APPROVAL REQUIRED BY ANY OTHER
GOVERNMENT AGENCY (DEP, DOT, SWFWMD, COUNTY, ETC.) ARE THE
RESPONSABILITY OF THE APPLICANT TO OBTAIN.
SCOPE OF WORK
INTERIOR FIT -OUT OF NEW 1-STORY SHELL BUILDING (CONSTRUCTED UNDER
SEPARATE PERMIT) - 6,706 S.F.
Occupancy use is for Clinic, outpatient used to provide medical care on
less than a 24-hour basis to persons who are not rendered incapable of self
preservation by the services provided per FBC 202.
Spaces include exam rooms, waiting areas, physician offices, staff break
room, toilets, janitors closet, storage rooms.
TENANT REQUIREMENTS
EXIT REQUIREMENTS
NUMBER AND ARRANGEMENT OF EXITS: REFERENCE DRAWING A0.6
FLOOR MIN NUMBER TRAVEL DISTANCE ARRANGEMENT
OF EXITS I MEANS OF EGRESS
REQUIRED SHOWN ALLOWABLE SHOWN REQUIRED SHOWN
TBL.1021.1 ON PLAN TBL.1016.1 ON PLAN BETWEEN ON PLAN
DOORS
TENANT
300'
55'-7"
CORRIDOR DEAD ENDS (SECTION 1017.3)
COMMON PATH OF TRAVEL (SECTION I014.3)
OCCUPANT LOAD ANnEIDTH
CALCULATED OCUPANT LOAD -
EXISTiNG BUSINESS BUILDING = 6,706 SF
BREAK ROOM: ASSEMBLY 358 SF / 15 NET=COMMUNITY:
394 SF / 15 NET = 27 PERSONWAITING:
179 SF / 15 NET= 12 PERSONS
COMM ROOM: 61 SF / 300 NET = 1 PERSOELEC.
ROOM/F. RISER: 101 SF / 300 NET= 1
STORAGE 1: 33 SF / 300 NET= 1 PERSON
STORAGE 2: 86 SF / 300 NET = 1 PERSON
BIO: 12 SF / 300 NET = 1 PERSON
J.C.: 34 SF ( 300 NET = 1 PERSON
TOTAL OCCUPANCY = 106 PERSONS
PLUMBING FIXTURE REQUIREMENTS
OOR
MALE FEMALE
BUSINESS
REQUIRED
PROVIDED
REQUIRED
PROVIDED
106 PE ONS
TOILETS
2
4
2
4
LAVATORIES
2
4
2
4
SERVICE SINK 1 1
DRINKING 1 1
FOUNTAIN
NOTE: TOILETS EXISTING BUILDING PROVIDED NOT IN SCOPE OF WORK
FIXTURES REQUIRED / (FIXTURES PROVIDED)
LEGAL DESCRIPTION
PARCEL ID#: 35-25-21-0130-00000-0040
ZEPHYR COMMONS PHASE 1 PB 65 PG 132 LOT 4 OR 9254 PG 1646
SITE LOCATION
ARCHITECTURE / INTERIOR DESIGNER
CAMPBELL + VAN DUSEN DESIGN STUDIO
255 SOUTH ORANGE AVENUE
SUITE 1240
ORLANDO, FLORIDA 32801
407.930.6016
CONTACT: FRANK W. CAMPBELL
CONTACT: GLORIA VAN DUSEN
ELECTRICAL ENGINEER
PENINSULA ENGINEERING, INC.
2016 ALDEN ROAD
ORLANDO, FLORIDA 32803
407.246.1688
CONTACT: BRYAN SPANGLER
ADVENT HEALTH
WELL 65+ ZEPHYRHILLS
MECH & PLUMB ENGINEER
PENINSULA ENGINEERING, INC.
2016 ALDEN ROAD
ORLANDO, FLORIDA 32803
407.246.1688
CONTACT: BRYAN SPANGLER
7866 GALL BOULEVARD,
ZEPHYRHILLS, FLORIDA 33541
BUILDING OWNERS CONTRACTOR
ADVENTHEALTH TBD
900 HOPE WAY
ALTAMONTE SPRINGS, FLORIDA 32714
407.963.1014
CONTACT: DANIEL TOM
E1 , v iv, , `� l
1&f l }�
16
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No, AR0016053
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
�I
LU
.J
Lr)
z
LL!
_
LL
Q
�
LJ__f
N
J
H
J
rill
LU
N
n
r J�
IW
Q
00 (")
i� ('7
CONSTRUCTION DOCUMENTS
03.24.2023
PRINCIPAL IN CHARGE
F. CAMPBELL
PROJECT MANAGER
M. TORRES
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
COVER SHEET
ELEC. ROOM/ FIRE RISER
= 101 S.F.
@300=1P
PROPOSED BUSINESS OCCUPANCY
TOTAL TENANT AREA SF = 6,706 SF
BUSINESS AREA: 106 PERSONS
5,448 SF@ 150 GROSS = 37P
BREAK: 358 SFA @ 15 NET A 24P
COIWMU NITY: 374 SF-@ 15-NET= 27P
WAITING: 179 SF @ 15 NET= 12P
COMM ROOM: 61 SF @ 300 NET= 1 I
ELEC. ROOM/F. RISER: 101 SF @ 300
NET= 1 P
STORAGE 1: 33 SF @ 300 NET= 1 P
STORAGE 2: 86 SF @ 300 NET= 1 P
B I O: 12 SF @ 300 NET= 1 P
J. C .: 34 SF @ 300 NET= 1 P
TOTAL OCCUPANCY= 1,06P
OVERALL DIAGONAL= 1 19'-8"
DISTANCE BETWEEN EXITS= 74'-6"
MAX TRAVEL DISTANCE= 55'-9"
LIFE SAFETY LEGEND
ALL DIMENSIONS ARE ON CENTER FROM FINISHED INTERIOR
SYMBOL
DESCRIPTION
DIRECTION OF TRAVEL
TRAVEL PATH
DISTANCE BETWEEN EXITS
DIAGONAL DISTANCE
e
LIGHTED EXIT SIGN: TWO SIDED, FROM DUAL
I l
DIRECTION, W/ BATTERY BACKUP.
CoLIGHTED
EXIT SIGN: SINGLE SIDED, FROM SINGLE
CQ
DIRECTION, W/ BATTERY BACKUP.
®
LIGHTED EXIT SIGN & DUAL EXIT LIGHTING
COMBO: SINGLE AND OR DUAL DIRECTION
.--
W/BATTERY BACKUP.
FECR
'E?
NEW WALL RECESSED FIRE EXTINGUISHER
�I
KEYNOTE SYMBOL
* FOR SYMBOLS AND REQUIREMENTS SEE ELECTRICAL SHEETS.
GENERAL NOTES
THE MINIMUM FLAME SPREAD CLASSIFICATION
OF INTERIOR FINISHES SHALL BE:
FOR EXITS AND EXIT ACCESS CLASS B
FOR ALL OTHER AREAS CLASS C
KEYED NOTES
PROVIDE RECESSED FIRE EXTINGUISHER CABINET.
l0A
B.O.D. LARSENS (OCCULT SERIES WITH BLACK
LETTERING) FINISH SHALL #4 304 STAINLESS STEEL.
LOCATE FIRE EXTINGUISHER CABINETS IN
ACCORDANCE W/LOCAL CODES & PROVIDE
ARCHITECT W/ DRAWING OF LOCATIONS FOR
REVIEW/APPROVAL PRIOR TO FRAMING OF
WALLS. AVOID LOCATING IN FIRE RATED
PARTITION (PROVIDE SECOND LAYER OF 5/8"
TYPE "X" G.W.B. AT BACK SIDE OF CABINET IF
LOCATING IN A FIRE RATED PARTITION).
CONFIRM FINAL LOCATION AND QUANTITIES OF
DEVICES WITH LOCAL FIRE OFFICIAL.
CAMPBELL VAN DUSEN
ARCHITECTUREINTERIOR D SI` I
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite #1240
Orlando, Florida 32301
Phone: 407.930.6016
FL, Lic, No. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
Lj-
ry
W
F=-
IV
J
>
w
w
_
�
m
_
+
—
U
Z
O
af
Q
O
0
w
cl—
LL
<C
S
LU
N
00 c")
1 �
CONSTRUCTION DOCUMENTS
03.24.2023
NO. DATE I DESCRIPTION
1 08/04/2023 IREVISION 1
2 108/25/2023 IREVISION 2
PRINCIPAL IN CHARGE
F. CAMPBELL
---------------
.O
M. TORRES
f
I 011"i a Joe
r
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
LIFE SAFETY PLAN
LIFE SAFETY PLAN
1 /4" = 1 I-0"
—7-t i—TIT-, 1Tc --i--1 --
A0.6
5/8 GYP BOARD
SOUND BATT INSULATIO
WATER HEATER - SEE MEP
FLOOR PLAN SYMBOLS
°
DRAWINGS FOR REQUIREMENTS.
®
ROOM NUMBER
SECTION
3 5/8" 25 GA MTL —
STUDS @16" O.C.
NEW WALL FURRING OVE
INTERIOR OF EXISTING CMU
WALL SYSTEMS
5/8 GYP BOARD
SOUND BATT INSULATION
3 5/8" 25 GA MTL
STUDS @16" O.C.
METAL CORNER BEAD
LOW WALL SUPPORT
BRACKET 1 /8" STEEL
METAL STUDS @ 16" O.C.
0
®
3/4" PLYWOOD SHELF
2"x4" P.T. WD FRAMEING
O
WINDOW TYPE*
DETAIL
HE)DOOR
SYMBOL- SEE DOOR SCHEDULE *
�•�
DOOR CONTACT
_
FINISHED CLEARANCE
C.R.
CARD READER
MINIMUM DIMENSION MAY BE
METAL CORNER
®�
=
C.o.
CASED OPENING*
VERIFY DIMENSION COMBINED
BEAD
I °
°
N
WALL TYPE - SEE WALL LEGEND & SHEET AO.5
R
i -�
RADIUS OF CLEARANCE
_ AL _ _
ALIGNMENT LINE
ITEM ABOVE OR FURNITURE/EQUIPMENT N.I.0
CENTERLINE
o
x
METAL
CORNER BEA
°
BOTTOM CHANNEL
e
2"x4" P.T. WD BRACE
ITEM BELOW
— —
POB
POINT OF BEGINNING FOR LAYOUT
INTERIOR &CABINET ELEVATIONS
*NOTE: SEE SHEET A2.3 FOR DOOR & WINDOW TYPES
®
WALL
EXISTING EXTERIOR WALL SYSTEMS
EXISTING STOREFRONT SYSTEMS
CONNECT WALL BRACKET 0
SUPPORT TO FLOOR, AT
EACH END OF WALL, W/ (2) �7f2r�
1 /4" EXPANSION BOLT
NOTE: SHELF MOUNTING HT. SHALL BE
DETERMINED ON SITE. BASED ON REQUIRED
SPACE FOR EQUIPMENT BELOW
EXISTING EXTERIOR
WINDOW EXISTING WINDOW MULLION
D-1 FRAMING DETAIL - AT EXT. WINDOW JAMB
D-2 FRAMING DETAIL - AT EXT. WINDOW
D-3 LOW WALL SUPPORT BRACKET
p-4 WATER HEATER SHELF DETAIL
*NOTE: SEE SHEET A2.3 FOR DOOR & WINDOW TYPES
AZ.O sc ALE: N.T.s.
AZMULL. sc�LE: u.r_s.
SCALE: N.I.S.N..s.
AZ.O TYPICAL AT ENDS OF LOW WALLSZ.O
PROVIDER WORK
ROOM
132
119 SF
1 CONSTRUCTION PLAN
A2.0 1 /4" = 1'-0"
PLAN NOTES:
(BOXED NOTE NUMBERS ARE KEYED TO PLAN)
IT IS THE CONTRACTOR'S RESPONSIBILITY TO CHECK WITH THE BUILDING OWNER
WITH REFERENCE TO ROOF WARRANTIES AND/OR THE PRESCRIBED
REQUIREMENTS FOR NEW ROOF PENETRATIONS. IN NO CASE SHOULD
CONTRACTOR DO ANYTHING TO VOID ROOF WARRANTIES. CONTRACTOR IS
REQUIRED TO HAVE BUILDING OWNER'S ROOFING CONTRACTOR MAKE,
SUPERVISE, OR APPROVE ALL NEW ROOF PENETRATION.
lA THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL MAKE REDLINE
AS -BUILT NOTES ON THE DRAWINGS OF ALL DEVIATIONS FROM THE PLANS MADE
DURING THE COURSE OF CONSTRUCTION. CONTRACTOR SHALL SUBMIT REDLINE
NOTES AND DRAWINGS TO THE ARCHITECT AT THE COMPLETION OF
CONSTRUCTION. IF NO DEVIATIONS OR CHANGES HAVE BEEN MADE DURING
CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT A LETTER TO THE ARCHITECT
STATING THAT NO CHANGES WERE MADE.
1 B SUBCONTRACTORS SHALL GIVE TO CONTRACTOR PRODUCT LITERATURE FOR
INSTALLED EQUIPMENT AND PRODUCTS THAT REQUIRE MAINTENANCE OF ANY
TYPE (INCLUDING RELAMP OF LIGHT FIXTURES) AND ANY MAINTENANCE
INSTRUCTIONS OR WARRANTIES AND THE CONTRACTOR SHALL OBTAIN PHONE
NUMBERS AND ADDRESSES OF CONTACTS FOR REPAIR/MAINTENANCE AND BIND
ALL OF THIS INFORMATION IN AN 8 1 /2 X i 1 NOTEBOOK. THIS MANUAL SHALL
ALSO INCLUDE A COMPLETE LISTING OF IDENTIFICATION FOR ALL FINISH
MATERIALS INCLUDING CEILING TILE, FLOOR TILE AND CARPET, AND PLASTIC
LAMINATE AND PAINT. CONTRACTOR SHALL DELIVER THIS PROJECT
MAINTENANCE MANUAL TO OWNER AT COMPLETION OF PROJECT.
I THIS IS EQUIPMENT OR FURNITURE, NOT CONSTRUCTION. SEE EQUIPMENT/MEP
DRAWINGS FOR PREPARATION AND COORDINATION REQUIRED BY
CONTRACTOR. ALL SUBCONTRACTORS SHALL CONTACT AND COORDINATE
WITH EQUIPMENT SUPPLIER FOR LAYOUT TEMPLATES AND VERIFICATION/REVIEW
OF ROUGH -INS.
5K GRAB BARS @ HANDICAP TOILETS:
1 1 /2" DIA., 1 1 /2" CLEAR FROM WALL. 33"-36" ABOVE FINISHED FLOOR
ANCHORED TO SUPPORT 250 LBS.
ONE 42" LONG AT SIDE OF TOILET.
ONE 36" LONG BEHIND TOILET.
(SEE TOILET ROOM DETAILS FOR PLACEMENT.)
6A INFILL EXISTING WINDOW OPENING WITH 3 5/8" 25 GA METAL STUDS 24" O.C. W/ 5/8"
DRYWALL FINISH.
6C SEE DRAWING Al.1 SLAB PLAN FOR NEW WALK EXTENSIONS.
6D CHASE WALLS: SEE PARTITION TYPES FOR WALL CONSTRUCTION.
6F PROVIDE 3 1 /2" WIDE 12 GA. MTL BLOCKING STRIPS @ MOUNTING LOCATIONS OF
ALL RAILINGS, CURTAIN TRACKS, AND OTHER BUILT-IN OR SURFACE -MOUNTED
ACCESSORIES. AT CABINETS, PROVIDE 1 X6 FIRE -RETARDANT -TREATED WOOD
BACKING. VERIFY SIZE AND LOCATION OF THIS BLOCKING WITH
PRODUCT/EQUIPMENT/CABINET INSTALLATION RECOMMENDATIONS OR NEEDS.
6K ALL WOOD FRAMING SHALL BE KILN -DRIED AND HAVE A MINIMUM FIBER STRESS
OF 1200 PSI.
6Q CEILING: SEE SECTIONS AND DETAILS ON REFLECTED CEILING PLAN. DIMENSIONS
AND ELEVATIONS SHOWN ON THESE SHEETS ARE FINISHED. ALL CEILING FRAMING
TO BE @ 24" O.C. W/GYPSUM BOARD FINISH.
6R ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE -TREATED OR HAVE AN APPROVED SEPARATING MATERIAL.
6V THE INTENT OF DESIGN IS TO ALIGN NEW WALLS WITH FRAMING AND FINISH OF
EXISTING WALLS
6X PROVIDE 5/8" THICK, 24" X 24" FIRE RETARDANT TREATED PLYWOOD BEHIND GYP.
BOARD FOR WALL HUNG TVs. CENTER TVs ON PLYWOOD.
7A SEALANT: APPLY SEALANT AT JOINING OF ALL DISSIMILAR MATERIALS EXPOSED
TO WEATHER AND AT GAPS EXPOSED TO VIEW.
7B SEALANT: PROVIDE A FULL BED OF SEALANT AT WINDOW AND DOOR FRAMES
(INCLUDING THRESHOLD) AND A CONTINUOUS BEAD AT PERIMETER OF EXTERIOR
AND INTERIOR WINDOWS AND DOORS.
7H SOUND BATT INSULATION IN INTERIOR WALLS AS INDICATED. SEE WALL LEGEND,
THIS SHEET, AND WALL TYPES, SHEET AO.4 AND AO.5
8A ALL GLASS IN DOORS OR SIDELIGHTS SHALL BE TEMPERED AND SHALL COMPLY
WITH THE FLORIDA BUILDING CODE 2017, SECTION 2406, SAFETY GLAZING. GLASS
IN RATED DOORS SHALL COMPLY W/RATING OF DOOR.
8B ALL DOOR HARDWARE SHALL MEET CURRENT ADA AND FLORIDA ACCESSIBILITY
CODES.
8C ALL WINDOW AND DOOR FRAMES SHALL BE SECURED TO SURROUNDING WALL
PER MANUFACTURER RECOMMENDATION FOR WIND ZONE.
8D EXISTING DOOR TO REMAIN. DOOR TO BE LOCKED & HARDWARE TO BE
REMOVED AND OPENINGS CAPPED. CONTINUOUSLY SEAL DOOR USING BASF
MASTERSEAL NP 100, INSTALL PER MFG. RECOMMENDATIONS. COLOR TO MATCH
DOOR AS CLOSE AS POSSIBLE.
8F EXIST ROOF LADDER AND ACCESS HATCH.
9B 1 /2" GYP BOARD MAY BE USED ON SIDES AND BOTTOM OF DROPPED SOFFITS
UNLESS NOTED OTHERWISE.
9C AT ALL CHANGES IN FLOOR MATERIAL, PROVIDE APPROPRIATE ADA-COMPLIANT
TRANSITION STRIP. IF AT DOOR, LOCATE DIRECTLY UNDER DOOR.
9E WHEN NOT INDICATED ON PLANS, VERIFY COLOR AND PATTERN SELECTIONS
WITH OWNER.
9K FILL IN DRYWALL AT DEMOLISHED WALL LOCATIONS. TAPE AND FINISH NEW
DRYWALL TO BE FLUSH WITH ADJACENT REMAINING WALL.
9Y LEAVE 1/2" GAP BETWEEN FINISH FLOOR AND BOTTOM EDGE OF GYPSUM BOARD.
9Z PREPARE ALL WALLS FOR PAINT, TO A GA 216 LEVEL 4 DRYWALL FINISH.
9N ALL TOILETS: USE 5/8" MOISTURE RESISTANT GYPSUM BOARD ON BATHROOM SIDE OF
ALL WALLS BEHIND A TOILET AND/OR LAVATORY.
9Q ALL NEW CARPET & WALLPAPER SHALL BE ANTIMICROBIAL TREATED FROM THE
FACTORY.
IOA PROVIDE AND INSTALL TYPE 2A10 BC FIRE EXTINGUISHER (S) WHERE SHOWN ON
PLAN. THE TOP OF FIRE EXTINGUISHER SHALL NOT BE MORE THAN 5 FT. ABOVE THE
FLOOR (3 1 /2 FT. IF FIRE EXTINGUISHER'S GROSS WEIGHT IS MORE THAN 40 LBS)
AND BOTTOM NOT LESS THAN 4 INCHES ABOVE THE FLOOR.
1 OB RAISED/BRAILLED CHARACTERS & PRACTICAL SYMBOL SIGNS
LETTERS AND NUMERALS SHALL BE RAISED 1 /32 IN, UPPER CASE, SANS SERIF OR
SIMPLE SERIF TYPE, AND SHALL BE ACCOMPLISHED WITH GRADE 2 BRAILLE.
RAISED CHARACTERS SHALL BE AT LEAST 5/8 IN (16 MM) HIGH, BUT NO HIGHER
THAN 2 IN (50 MM). PICTOGRAMS SHALL BE ACCOMPLISHED BY THE EQUIVALENT
VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE PICTOGRAM. THE BORDER
DIMENSION OF THE PICTOGRAM SHALL BE 6 IN (152 MM) MINIMUM IN HEIGHT.
MOUNTING LOCATIONS AND HEIGHT
SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE
TOILET RM DOORS. MOUNTING HEIGHT SHALL BE 60 IN. (1525 MM) ABOVE FINISH
FLOOR TO THE CENTERLINE OF THE SIGN. (IF LATCHSIDE UNAVAILABLE USE
NEAREST ADJACENT WALL FOR SIGN). OWNER TO PROVIDE.
IOC CONTRACTOR TO INSTALL OWNER PROVIDED AED SEMI -RECESSED CABINET
11 A CABINETS AND CASE WORK: SEE ALL DRAWINGS FOR CABINET SIZES, FINISHES,
HARDWARE AND MATERIALS SPECIFICATIONS. THE CONTRACTOR SHALL SUBMIT
SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION.
1 1 B CABINETS AND CASE WORK PROVIDED BY OWNER, CONTRACTOR TO
COORDINATE INSTALLATION W/ OWNER.
IIC AT ALL WALLS RECEIVING CABINETS AND CASE WORK, PROVIDE 4'x8'xl /2" FIRE
RESISTANT PLYWOOD BACKING ON ALL 4 WALLS. AS REQUIRED.
1 1 D TELCOM CLOSET: PROVIDE AND MOUNT (1) SHEET OF 4' X 8' X 1 /2"
FIRE -RETARDANT TREATED BC PLYWOOD WITH TOP AT 8'-0" AFF. AT ALL WALLS.
12A N/A,
12B PROVIDE CAP SHEET FILM TO GLAZING (SOLYX SXWF-WB WHITE BLACK OPAQUE) AT ALL
SPANDREL CONDITIONS WHERE INTERIOR WALLS COVER EXTERIOR STOREFRONTS.
15A CONTRACTOR TO INSTALL OWNER PROVIDED SOAP DISPENSERS AT EACH SINK
AND LAVATORY.
15B CONTRACTOR TO INSTALL OWNER PROVIDED DIAGNOSTIC BOARDS IN ALL
WELLNESS SUITES. CONTRACTOR TO INSTALL DIAGNOSTIC WALL BOARD BRACKET. SEE
DET 2/AO.5 FOR DIAGNOSTIC BOARD NICHE.
15C CONTRACTOR TO INSTALL OWNER PROVIDED SHARP CONTAINERS IN ALL
WELLNESS SUITES, LAB AND MED ROOM
15D CONTRACTOR TO INSTALL OWNER PROVIDED PAPER TOWEL DISPENSERS AT
BREAK ROOM AND COMMUNITY ROOM
15E CONTRACTOR TO INSTALL OWNER PROVIDED REFRIGERATOR LINES FOR ICE
MAKERS IN BREAK ROOM
15F CLOSE AND LOCK EXISTING EXTERIOR DOOR. REMOVE LEVER HARDWARE AND CAP.
CAULK WITH EXTERIOR RATED BUTYL CAULK. PROVIDE CONTNNIOUS BEAD ALL SIDES
AND THRESHOLD INTERIOR AND EXTERIOR.
15G PROVIDE RECESSED SPECIMEN PASS -THROUGH CABINET - BOBRICK B-505
CAMPBELL +
ARCHITECTURE INTERIOR DESIGN
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC,
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. LEC. No. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
J
J
J
rV
a--
n
=
W
F_
IV
J
J
LI_1
W
m
+
J
Zo
Q
UJ
LZLJ�—
i
Q
LLj
Cl—
O �00
co
PRINCIPAL IN CHARGE
F. CAMPBELL
...........................
PROJECT MANAGER
M. TORRES
......................................... I..........................
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
CONSTRUCTION PLAN
A290
Fgq-&Ejlmll M-10-FN
"ma.1,
SEMI
NOTE: ALL PLAN DIMENSIONS ARE TO FACE OF G.W.B. AS
FLOOR PLAN SYMBOLS
SHOWN BELOW, UNLESS SPECIFICALLY NOTED OTHERWISE.
®
ROOM NUMBER
SECTION
aO
WINDOW TYPE*
HIDDOOR
SYMBOL- SEE DOOR SCHEDULE *
5/8" GYP WALL BOARD
6 X 6 WELDED WIRE MESH
IF MORE THAN 24" WiDE
EXISTING SLAB
DETAIL
D•C
DOOR CONTACTS
FINISHED CLEARANCE
{2j 3-5/8" METAL STUDS TIGHT TO
ADJACENT WALL OR CORNER
CHANNEL ANCHOR HOLLOW METAL
FRAME TO STUD
DOOR OPENING TO BEGIN A
MAXIMUM OF 4 1 /2" FROM ADJACENT
4 1 /2" MAX STUD LINE
417
DIMENSIONS ARE TO
FACE OF G.W.B. U.N.O.
GYP WALL BOARD
METAL RUNNERS
TOP & BOTT
3 5/8" MTL STUDS
U.N.O.
4" CONCRETE INFILL
a VAPOR BARRIER
a
61 APPLY NEW
TERMITE TREATMENT
7"a Q AT ALL AREAS THAT
ZZACTUAL
— SOIL IS DISTURBED.
_ T=f I i I=1 f I=1 h(I I
I I I —III=
TO INSURE STABILITY AT SLAB CONNECTION COMPACTED SOIL
C.R.
CARD READERS
MINIMUM DIMENSION MAY BE
C.O.
CASED OPENING*—
VERIFY DIMENSION COMBINED
/
WALL TYPE - SEE WALL LEGEND & SHEET AO.5
—L =R—.�
RADIUS OF CLEARANCE
AL
ALIGNMENT LINE
ITEM ABOVE OR FURNITURE/EQUIPMENT N.I.0
ITEM BELOW
— —
—
CENTERLINE
POB
POINT OF BEGINNING FOR LAYOUT
—
-
INTERIOR &CABINET ELEVATIONS
*NOTE: SEE SHEET A2.3 FOR DOOR & WINDOW TYPES
(1) SIMPSON STRONG -TIE TITEN HD 4' X 4" (MIN.)
@ 16" O.C. 2" INTO EXISTING SLAB AND EXTEND
2" INTO NEW
D-1 DOOR FRAMING DETAIL - TYPICAL
D-2 LAYOUT DIMENSION DETAIL(_D-3__
SLAB INFILL DETAIL
*NOTE: SEE SHEET A2.3 FOR DOOR &WINDOW TYPES
A2.1 HINGE SIDS_ c DOORS s�owN SCALE N.T.s.
A2.1 HCR zoNTa� SEC T�GN sc�LE. N-T.s
� � Sc 3., _ 1'-0°
IN CORNER OF ROOM
C
- ---(:D)
1 DIMENSION PLAN
A2.1 1 /4" = 11-011
PLAN NOTES:
(BOXED NOTE NUMBERS ARE KEYED TO PLAN)
IT IS THE CONTRACTOR'S RESPONSIBILITY TO CHECK WITH THE BUILDING OWNER
WITH REFERENCE TO ROOF WARRANTIES AND/OR THE PRESCRIBED
REQUIREMENTS FOR NEW ROOF PENETRATIONS. IN NO CASE SHOULD
CONTRACTOR DO ANYTHING TO VOID ROOF WARRANTIES. CONTRACTOR IS
REQUIRED TO HAVE BUILDING OWNER'S ROOFING CONTRACTOR MAKE,
SUPERVISE, OR APPROVE ALL NEW ROOF PENETRATION.
1 A THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL MAKE REDLINE
AS -BUILT NOTES ON THE DRAWINGS OF ALL DEVIATIONS FROM THE PLANS MADE
DURING THE COURSE OF CONSTRUCTION. CONTRACTOR SHALL SUBMIT REDLINE
NOTES AND DRAWINGS TO THE ARCHITECT AT THE COMPLETION OF
CONSTRUCTION. IF NO DEVIATIONS OR CHANGES HAVE BEEN MADE DURING
CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT A LETTER TO THE ARCHITECT
STATING THAT NO CHANGES WERE MADE.
1 B SUBCONTRACTORS SHALL GIVE TO CONTRACTOR PRODUCT LITERATURE FOR
INSTALLED EQUIPMENT AND PRODUCTS THAT REQUIRE MAINTENANCE OF ANY
TYPE (INCLUDING RELAMP OF LIGHT FIXTURES) AND ANY MAINTENANCE
INSTRUCTIONS OR WARRANTIES AND THE CONTRACTOR SHALL OBTAIN PHONE
NUMBERS AND ADDRESSES OF CONTACTS FOR REPAIR/MAINTENANCE AND BIND
ALL OF THIS INFORMATION IN AN 8 1 /2 X I 1 NOTEBOOK. THIS MANUAL SHALL
ALSO INCLUDE A COMPLETE LISTING OF IDENTIFICATION FOR ALL FINISH
MATERIALS INCLUDING CEILING TILE, FLOOR TILE AND CARPET, AND PLASTIC
LAMINATE AND PAINT. CONTRACTOR SHALL DELIVER THIS PROJECT
MAINTENANCE MANUAL TO OWNER AT COMPLETION OF PROJECT.
l C THIS IS EQUIPMENT OR FURNITURE, NOT CONSTRUCTION. SEE EQUIPMENT/MEP
DRAWINGS FOR PREPARATION AND COORDINATION REQUIRED BY
CONTRACTOR. ALL SUBCONTRACTORS SHALL CONTACT AND COORDINATE
WITH EQUIPMENT SUPPLIER FOR LAYOUT TEMPLATES AND VERIFICATION/REVIEW
OF ROUGH -INS.
5K GRAB BARS @ HANDICAP TOILETS:
1 1 /2" DIA., 1 1 /2" CLEAR FROM WALL. 33"-36" ABOVE FINISHED FLOOR
ANCHORED TO SUPPORT 250 LBS.
ONE 42" LONG AT SIDE OF TOILET.
ONE 36" LONG BEHIND TOILET.
(SEE TOILET ROOM DETAILS FOR PLACEMENT.)
6A INFILL EXISTING WINDOW OPENING WITH 3 5/8" 25 GA METAL STUDS 24" O.C. W/ 5/8"
DRYWALL FINISH.
6C SEE DRAWING A1.1 SLAB PLAN FOR NEW WALK EXTENSIONS.
6D CHASE WALLS: SEE PARTITION TYPES FOR WALL CONSTRUCTION.
6F PROVIDE 3 1 /2" WIDE 12 GA. MTL BLOCKING STRIPS @ MOUNTING LOCATIONS OF
ALL RAILINGS, CURTAIN TRACKS, AND OTHER BUILT-IN OR SURFACE -MOUNTED
ACCESSORIES. AT CABINETS, PROVIDE 1X6 FIRE -RETARDANT -TREATED WOOD
BACKING. VERIFY SIZE AND LOCATION OF THIS BLOCKING WITH
PRODUCT/EQUIPMENT/CABINET INSTALLATION RECOMMENDATIONS OR NEEDS.
6K ALL WOOD FRAMING SHALL BE KILN -DRIED AND HAVE A MINIMUM FIBER STRESS
OF 1200 PSI.
6Q CEILING: SEE SECTIONS AND DETAILS ON REFLECTED CEILING PLAN. DIMENSIONS
AND ELEVATIONS SHOWN ON THESE SHEETS ARE FINISHED. ALL CEILING FRAMING
TO BE @ 24" O.C. W/GYPSUM BOARD FINISH.
6R ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE -TREATED OR HAVE AN APPROVED SEPARATING MATERIAL.
6V THE INTENT OF DESIGN 1S TO ALIGN NEW WALLS WITH FRAMING AND FINISH OF
EXISTING WALLS
6X PROVIDE 5/8" THICK, 24" X 24" FIRE RETARDANT TREATED PLYWOOD BEHIND GYP.
BOARD FOR WALL HUNG TVs. CENTER TVs ON PLYWOOD.
7A SEALANT: APPLY SEALANT AT JOINING OF ALL DISSIMILAR MATERIALS EXPOSED
TO WEATHER AND AT GAPS EXPOSED TO VIEW.
7B SEALANT: PROVIDE A FULL BED OF SEALANT AT WINDOW AND DOOR FRAMES
(INCLUDING THRESHOLD) AND A CONTINUOUS BEAD AT PERIMETER OF EXTERIOR
AND INTERIOR WINDOWS AND DOORS.
7H SOUND BATT INSULATION IN INTERIOR WALLS AS INDICATED. SEE WALL LEGEND,
THIS SHEET, AND WALL TYPES, SHEET AO.4 AND AO.5
8A ALL GLASS IN DOORS OR SIDELIGHTS SHALL BE TEMPERED AND SHALL COMPLY
WITH THE FLORIDA BUILDING CODE 2017, SECTION 2406, SAFETY GLAZING. GLASS
IN RATED DOORS SHALL COMPLY W/RATING OF DOOR.
8B ALL DOOR HARDWARE SHALL MEET CURRENT ADA AND FLORIDA ACCESSIBILITY
CODES.
8C ALL WINDOW AND DOOR FRAMES SHALL BE SECURED TO SURROUNDING WALL
PER MANUFACTURER RECOMMENDATION FOR WIND ZONE.
8D EXISTING DOOR TO REMAIN. DOOR TO BE LOCKED & HARDWARE TO BE
REMOVED AND OPENINGS CAPPED. CONTINUOUSLY SEAL DOOR USING BASF
MASTERSEAL NP 100, INSTALL PER MFG. RECOMMENDATIONS. COLOR TO MATCH
DOOR AS CLOSE AS POSSIBLE.
8F EXIST ROOF LADDER AND ACCESS HATCH.
913 1 /2" GYP BOARD MAY BE USED ON SIDES AND BOTTOM OF DROPPED SOFFITS
UNLESS NOTED OTHERWISE.
9C AT ALL CHANGES IN FLOOR MATERIAL, PROVIDE APPROPRIATE ADA-COMPLIANT
TRANSITION STRIP. IF AT DOOR, LOCATE DIRECTLY UNDER DOOR.
9E WHEN NOT INDICATED ON PLANS, VERIFY COLOR AND PATTERN SELECTIONS
WITH OWNER.
9K FILL IN DRYWALL AT DEMOLISHED WALL LOCATIONS. TAPE AND FINISH NEW
DRYWALL TO BE FLUSH WITH ADJACENT REMAINING WALL.
9Y LEAVE 1 /2" GAP BETWEEN FINISH FLOOR AND BOTTOM EDGE OF GYPSUM BOARD.
9Z PREPARE ALL WALLS FOR PAINT, TO A GA 216 LEVEL 4 DRYWALL FINISH.
9N ALL TOILETS: USE 5/8" MOISTURE RESISTANT GYPSUM BOARD ON BATHROOM SIDE OF
ALL WALLS BEHIND A TOILET AND/OR LAVATORY.
9Q ALL NEW CARPET & WALLPAPER SHALL BE ANTIMICROBIAL TREATED FROM THE
FACTORY.
ICA PROVIDE AND INSTALL TYPE 2A10 BC FIRE EXTINGUISHER (S) WHERE SHOWN ON
PLAN. THE TOP OF FIRE EXTINGUISHER SHALL NOT BE MORE THAN 5 FT. ABOVE THE
FLOOR (3 1 /2 FT. IF FIRE EXTINGUISHER'S GROSS WEIGHT IS MORE THAN 40 LBS)
AND BOTTOM NOT LESS THAN 4 INCHES ABOVE THE FLOOR.
IOB RAISED/BRAILLED CHARACTERS & PRACTICAL SYMBOL SIGNS
LETTERS AND NUMERALS SHALL BE RAISED 1/32 IN, UPPER CASE, SANS SERIF OR
SIMPLE SERIF TYPE, AND SHALL BE ACCOMPLISHED WITH GRADE 2 BRAILLE.
RAISED CHARACTERS SHALL BE AT LEAST 5/8 IN (16 MM) HIGH, BUT NO HIGHER
THAN 2 IN (50 MM). PICTOGRAMS SHALL BE ACCOMPLISHED BY THE EQUIVALENT
VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE PICTOGRAM. THE BORDER
DIMENSION OF THE PICTOGRAM SHALL BE 6 IN (152 MM) MINIMUM IN HEIGHT.
MOUNTING LOCATIONS AND HEIGHT
SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE
TOILET RM DOORS. MOUNTING HEIGHT SHALL BE 60 IN. (1525 MM) ABOVE FINISH
FLOOR TO THE CENTERLINE OF THE SIGN. (IF LATCHSIDE UNAVAILABLE USE
NEAREST ADJACENT WALL FOR SIGN). OWNER TO PROVIDE.
IOC CONTRACTOR TO INSTALL OWNER PROVIDED AED SEMI -RECESSED CABINET
1 lA CABINETS AND CASE WORK: SEE ALL DRAWINGS FOR CABINET SIZES, FINISHES,
HARDWARE AND MATERIALS SPECIFICATIONS. THE CONTRACTOR SHALL SUBMIT
SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION.
1 1 B CABINETS AND CASE WORK PROVIDED BY OWNER, CONTRACTOR TO
COORDINATE INSTALLATION W/ OWNER.
1 1 C AT ALL WALLS RECEIVING CABINETS AND CASE WORK, PROVIDE 4'x8'xl /2" FIRE
RESISTANT PLYWOOD BACKING ON ALL 4 WALLS. AS REQUIRED.
1 1 D TELCOM CLOSET: PROVIDE AND MOUNT (1) SHEET OF 4' X 8' X 1 /2"
FIRE -RETARDANT TREATED BC PLYWOOD WITH TOP AT 8'-0" AFF. AT ALL WALLS.
12A N/A.
12B PROVIDE CAP SHEET FILM TO GLAZING (SOLYX SXWF-WB WHITE BLACK OPAQUE) AT ALL
SPANDREL CONDITIONS WHERE INTERIOR WALLS COVER EXTERIOR STOREFRONTS.
15A CONTRACTOR TO INSTALL OWNER PROVIDED SOAP DISPENSERS AT EACH SINK
AND LAVATORY.
15B CONTRACTOR TO INSTALL OWNER PROVIDED DIAGNOSTIC BOARDS IN ALL
WELLNESS SUITES. CONTRACTOR TO INSTALL DIAGNOSTIC WALL BOARD BRACKET. SEE
DET 2/AO.5 FOR DIAGNOSTIC BOARD NICHE.
15C CONTRACTOR TO INSTALL OWNER PROVIDED SHARP CONTAINERS IN ALL
WELLNESS SUITES, LAB AND MED ROOM
15D CONTRACTOR TO INSTALL OWNER PROVIDED PAPER TOWEL DISPENSERS AT
BREAK ROOM AND COMMUNITY ROOM
15E CONTRACTOR TO INSTALL OWNER PROVIDED REFRIGERATOR LINES FOR ICE
MAKERS IN BREAK ROOM
15F CLOSE AND LOCK EXISTING EXTERIOR DOOR. REMOVE LEVER HARDWARE AND CAP.
CAULK WITH EXTERIOR RATED BUTYL CAULK. PROVIDE CONTINUOUS BEAD ALL SIDES
AND THRESHOLD INTERIOR AND EXTERIOR.
15G PROVIDE RECESSED SPECIMEN PASS -THROUGH CABINET - BOBRICK B-505
CAMPBELL + VAN DUSEN
ARCHITECTURE INTERIOR DESIGN
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32301
Phone: 407.930.6016
FL. Lic. No. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
J
H
V)
J_
ry
CL
W
E-
IV
_J
J
I
LJJ
LIJ
=
J
m
+
J
U
Z
•o
ry
Q
W_
L Lj
Q
>
W
tV
00 C'7
I", C'r3
CONSTRUCTION DOCUMENTS
03.24.2023
NO, DATE DESCRIPTION
1 08/04/2023 REVISION 1
2 08/25/2023 REVISION 2
A 05/01/2023 ADDENDUM A
B 05/03/2023 ADDENDUM B
PRINCIPAL IN CHARGE
F. CAMPBELL
PROJECT MANAGER
M.TORRES
DIMENSION PLAN
TYP. PLAN @ TOILET
a2.2 1 /2" = 1'-0"
9'-0" A.F.F.
IV —
FINISHED FLOOR
TYP. ELEVATION @ TOILET
1 /2" = 1'-0"
AD SYSTEMS DETAILS
N.T.S.
I.
TYP. ELEVATION @ TOILET
1/2" = 1'-0"
�E�e aE��PPaa,wE�
i' RE oi�OU llFi io
CV I S
z aR PP1-1
o�
14"
A-3 TYP. SECTION @ TOILET
A2.2 1 /2" = 1'-0"
9'-0" A.F.F.
FINISHED FLOOR
O TOILET SYMBOL LEGEND
ALL R/R ACCESSORIES SHALL BE BY BOBRICK WASHROOM
EQUIPMENT OR EQUAL, U.N.O., AND SHALL BE STAINLESS
STEEL FINISH. MOUNT ALL FIXTURES PER ADAAG
REQUIREMENTS.
A. KOHLER K-3493-0 HIGHLINE CLASSIC COMFORT
HEIGHT TWO-PIECE ELONGATED 1.6 GPF TOILET
WHITE WITH KOHLER K-4731-GC-0 STRONGHOLD QUIET
CLOSE ELONGATED TOILET SEAT IN WHITE
* FLUSH LEVER TO BE ON THE APPROACH SIDE
B. KOHLER K-20000-0 CAXTON RECTANGLE UNDER -MOUNT
SINK, WHITE
C. AMERICAN STANDARD 7502.170.002 DOUBLE HANDLE
CENTERSET GOOSENECK BATHROOM FAUCET
D. BOBRICK B-6806.99 X 36 ADA 36" GRAB BAR WITH
PEENED GRIPPING SURFACE
E. BOBRICK B-6806.99 X 42 ADA 42" GRAB BAR WITH
PEENED GRIPPING SURFACE
F. BOBRICK B-2888 CLASSIC SERIES SURFACE -MOUNTED
MULTI -ROLL TOILET TISSUE DISPENSER
G. ECOLAB NEXA 9202-1 188 CLASSIC TOUCH FREE SOAP
DISPENSER - OWNER FURNISHED, CONTRACTOR INSTALLED.
H. EBUN BD11 14 WALL MOUNT PAPER TOWEL DISPENSER,
BAMBOO ORIGINAL
I. BOBRICK B-165 2436 CHANNEL FRAME MIRROR: 24" X36"
J. BOBRICK B-682 SURFACE MOUNTED HAT AND COAT
HOOK. MOUNT CENTERED ON DOOR INSIDE
RESTROOM STALLS PER ADAAG REQUIREMENTS
5s _ n„
TOILET 105
1/2" = 1'-0"
TOILET 120
1/2" = 1'-0"
TOILET 103
1 /2" = 1'-0"
A. - 171
TOILET 130
1/2" = 1'-0"
7' - 9"
H.C.-ACCESSIBLE BATHROOM
60" X 56' CLEAR FLOOR SPACE FOR WATER CLOSET (SIDE APPROACH)
30" X 48" CLEAR FLOOR SPACE FOR LAVATORY
5-0" DIAMETER TURN -AROUND SPACE
30" X 48" ADA TOILET MANEUVERING CLEARANCE
TYPICAL H.C. TOILET ELEVATIONS
\/I FR P 0 R
24' X 36"
;vIiRROR — NOT
rLTE
n�
rr;
12" 42" MIN
36" MIN
17" MIN
MAX
40
GRAB
No
x 8„
8 AN 1 m a
a
< _ MIN
E
x
cD
z
z
< FU S
z HANDLE
0PAPER
N COVER
z_
SHALL BE
;
_
OR
-
ON OPEN
INSULATE
SIDE of
E p GE
0-)
—
W.C. SIDE ELEVATION
TANK (LAV
LAV SIDE ELEVATION
FRONT ELNXTION
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
GRAB BAR MOUNTING DETAIL
GYPSUM WALL
BOARD
METAL STUDS
GRAB BAR 1 1 /2"O
1 1/2" CLEARANCE FROM
WALL
ANCHOR PLATE 12 GA.
STEEL
ALT: USE 2X6 WOOD BETWEEN STUDS
co
co
OO
F\
TYPICAL HC.HILO EWC MOUNTING DETAIL
CLEAR FLOOR
8 1 >>
SPACE MIN.
z
48"x30" 48" M I N y
CENTERED ON I
LOWER 1
00 (HANDICAP
ACCESSIBLE)
z
DRINKING
I z
=
�,
d �I � FOUNTAIN
c r CN ^q N
r�
SPOUT HEIGHT ELEVATION CLEAR FLOOR SPACE
KNEE CLEARANCE AND
SPOUT HEIGHT ELEVATION
HC-1 HC. MOUNTING DETAIL
A.� SCALE N.T.S.
CAMPBELL + VAN DUSEN
ARCHITECTURE INTERIOR DE5;IQN
w.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32301
Phone: 407.930.6016
FL. Lic. No. AR0016053
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
J
L.L
t/)
J
J
OIL
=
O.
Uj
F—
IV
_I
J
Uj
LLJ
+
J
U
Z
.o
Q
J
=
.—
O
C)
LJ__f
C1!
OL-
Q
>>
>
LJJ
tV
00 (y)
I_- ('7
PRINCIPAL IN CHARGE
F. CAMPBELL
PROJECT MANAGER
M. TORRES
.................................. ......... I........................
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
DETAILS
A2.2
LAY -IN
PANEL
NOM. N CROSS TEE
2' CROS i TEE
HANGER WIRE
12 GA MIN. 4' O.C.
SECURE TO STRUCTURE
W/ POWDER ACTUATED
FASTENERS. HILTI X-CX ALH OR EQUAL
MAIN BEAM
NOTE: MINSTALL PER ASTM 636
MAXIMUM DEFLECTION OF HANGER WIRE IS 1:6.
PROVIDE ADDITIONAL SUPPORTS AS REQUIRED.
TEGULAR EDGE
SUSPENDED CEILING DETAIL
STORAGE 1
106
10 n 8
Y
12 GA. HANGER WIRE
WRAP WIRE MIN. 3 TIMES IN 3 INCHES
'T' BAR MAIN BEAM
SCALE: N.T.S.
EXISTING STRUCTURE
POWER DRIVEN
FASTENERS
12 GA. WIRE HANGERS MAX 6" FROM WALL
12 GA. WIRE HANGERS MAX 4' O.0
10'-0 r
ACOUSTICAL CEILING
PERIMETER TRIMS
WALL
CEILING DETAIL
SCALE: I" = Y-0"
STRUCTURE ABOVE
SECURE TRACK TO STRUCTURE -
USE POWER DRIVEN FASTENERS
AT 24" O.C. (MAX.)
3 5/8" GALV. METAL STUD
FRAMING AT 16" O.C. TO
STRUCTURE ABOVE
10'-0" A.F.F OIL
1-7
8'-2" A.F.F.
HEADER
BRACE TO STRUCTURE
10'-0" A.F.F OIL
ACOUSTICAL CEILING
REFER TO CEILING PLAN
FOR HEIGHT
x 5/8" GWB W/
CORNER BEAD
CEILING DETAIL
SCALE: 1 " = 1'-0"
4 Q Q
STRUCTURE ABOVE
3 5/8" GALV. METAL STUD
FRAMING AT 16" O.C. TO
STRUCTURE ABOVE
PARTITION SEE PLAN
°
10'-0" A.F.F
ACOUSTICAL CEILING
REFER TO CEILING PLAN
FOR HEIGHT
CROWN MOLDING WHERE NOTED IN
PLAN; SEE DET. A/A3.0
5/8" DRYWALL (TYP.)
9'-0" A.F.F
DRYWALL (TYP.
CORNER BEAD (TYP.)
WALL
:EILING
DETAIL
SCALE: 1" = 1'-0"
T
11
x x STRUCTURE ABOVE
SECURE TRACK TO STRUCTURE:
USE POWER DRIVEN FASTENERS
AT 24" O.C. (MAX.)
3 5/8" GALV. METAL STUD
FRAMING AT 16" O.C. TO
STRUCTURE ABOVE
10'-0" A.F.F
ACOUSTICAL CEILIN 9'-0" A.F.F
77-
5/8" DRYWALL (TYP.)
Hx'
5/8" DRYWALL (TYP.)
±9' -2"AFF
(CL_5_
CEILING DETAIL
A3.0 SCALE: 1" = Y-0"
mew
OWL
LLEC. ROOM/
FIRE RISER
INN
104
loom I IN I IN IN I MEN I
FAMI
Jim, Owl
loom
10, N'
I
■
rm
Norm,
L11111
lm7rl 01
Ma
p�9'_
0"A.F.F
11001 4- 115.d F&
INEEMENE, 0 FAM"isom
!I
'E' 10 ION FS
ERAft
,gs
!;a
�NLMMWM
a
Jwr
or NMI
IWd
jr%Aj
MEN
'A
ims
1
9'- 0"A.F.F
BE
MIN
Elm
0 11 -10
lam Mai
INN MEMNON
-
'E" pia"Evarm 0 INN
I- F=7
bf ho,
111101111
ME 0 0 0 7NI a FM7
1_7 INA
WE
ormi
Wil LM, Fig, M M E 0 M MMMMMMMM
MOO" 1006"MMA
E'_ uFmourm
NNE ONE
NONE
MENEEMEN
11EMrm a,
mno m
10'-O"A.F.F. -OLMOMM
_wjU rm-sn'NEEL
'1111111walkEENEW
MENEEMEMENER.AME MEN
1 REFLECTED CEILING PLAN
A3.0 1 /4'1 = 1'-011
B
C
ACOUSTICAL CLG. TILE
CROWN MOLDING
FYPON MLD453-16
TYP. CROWN MOLDING DETAIL
SCALE: NTS
CEILING & LIGHTING LEGEND
NEW CEILING GRID WITH 2' x 2' x 5/8"
ACOUSTICAL CEILING TILE -
MANUFACTURED BY USG - OLYMPIC
MICRO TEGULAR, COLOR: WHITE
2' X 2' LAY -IN LED LIGHT IN ACOUSTICAL
TILE CEILING
GYPSUM BOARD CEILING
RECESSED DOWN LIGHT
(SEE ELECT. DWGS.)
PENDANT MOUNTED FIXTURE
(SEE ELECT. DWGS.)
Oo
DECORATIVE PENDANT (SEE ELECT. DWGS.)
24X24 LOCKABLE ACCESS PANEL.
PAINT TO MATCH CEILING
SUPPLY DIFFUSER
0
RETURN DIFFUSER
r
EXHAUST FAN
�s
NEW SOFFIT / HEADER
L• � � J
CEILING/SOFFIT HEIGHT
FIRE SPRINKLER.
REFER TO PLUMBING SHEET FOR LOCATIONS.
•
EXIT LIGHT, SINGLE FACE. LETTER INDICATES FIXTURE TYPE.
BLACK QUADRANT INDICATES DIRECTION OF FACE,
ARROW (S) INDICATE DIRECTION OF TRAVEL. SEE
ELECTRICAL SHEETS.
RECESSED DOWN LIGHT WALL WASHER (SEE ELECT.
DWGS.)
WALL SCONCE. (SEE ELECT. DWGS.)
CROWN MOLDING
NOTE: VERIFY AND COORDINATE LIGHTS AND HVAC EQUIPMENT
PLACEMENT WITH MECHANICAL AND ELECTRICAL DRAWINGS.
REFLECTED CEILING PLAN
C1
LIGHTING PLACEMENT IS EXTREMELY IMPORTANT IN SOME ROOMS. IF
CONTRACTOR BELIEVES THE CEILING GRID WILL NOT LAYOUT EXACTLY AS
DRAWN, ARCHITECT IS TO BE NOTIFIED BEFORE BEGINNING WORK.
C2
SOFFITS: GYP BOARD ON FRAMING @ 16" O.C. SUSPENDED FROM STRUCTURE
ABOVE OR WALL. VERIFY ALL SOFFIT DIMENSIONS WITH CABINET DWGS,
INTERIOR ELEVATIONS OR SECTION DETAILS.
C3
PROVIDE & INSTALL SOUND BATT INSULATION ABOVE ACOUSTICAL CEILINGS
AT H.C. TOILETS, STAFF RM. & I.T. RM.
C4
VERIFY CLIENT'S REQUIREMENTS FOR MUSIC, INTERCOM, VCR/TV LOCATIONS,
AND CONNECTIONS TO BASE LOCATIONS.
C5
SEE MECHANICAL AND ELECTRICAL PLANS FOR EQUIPMENT AND FIXTURES IN
CEILING. IF CONTRACTOR BELIEVES THAT CEILING GRID WILL NOT LAY OUT
EXACTLY AS DRAWN, HE SHALL CONTACT ARCHITECT BEFORE BEGINNING
WORK.
C6
ALL NEW ACOUSTICAL CEILING HT = 10'-0" AFF. U.N.O.
C7
TOP OF EXISTING EXTERIOR WINDOWS & WALL = 12'-0"
ABBREVIATIONS:
AFF ABOVE FINISH FLOOR
CLG CEILING
EQ EQUAL
HDR HEADER
POR POINT OF REFERENCE
PT PREASSURETREATED
TYP TYPICAL
N NEW
ETR EXISTING TO REMAIN
CEILING LAYOUT NOTES:
i NOTE: Xs IN ROOMS ARE FOR REFERENCE AND
COORDINATION OF CEILING PLACEMENT WITH DRAWING.
USE DIMENSIONS, WHERE PRESENT, IN ADDITION TO X.
NOTE:
VERIFY AND COORDINATE LIGHT SELECTIONS AND HVAC EQUIPMENT
PLACEMENT WITH MECHANICAL AND ELECTRICAL.
lr
ARCHITECTURE INTERIOR DISIGI
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AR0016053
•2.
4
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
J
J
z
O
�
n
=
Uj
ry
F—
IV
J
W
W
Q
=
J
m
U
Z
-'0
Q
W
i
L Lj
_
_
O
p
w
W
NO �
�O�
CONSTRUCTION
DOCUMENTS
03.24.2023
NO. DATE DESCRIPTION
1 08/04/2023 REVISION 1
2 08/25/2023 REVISION 2
B OS/03/2023 ADDENDUM B
22-0328-01
REFLECTED CEILING PLAN
A3.0
I /A4.0
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AROO 16053
OC7'
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR001 6053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
H
0
ry
F—
n
n
ry
LU
V)
LU
<
>
n
u-i
JU
-j
F—
z
+
Lr)
-'0
<
0
L-U
>
=
O�
ry
C)
LU
'o Lo
0-
<
3>
rL-L4,
rc 01 1(yy'))
CONSTRUCTION DOCUMENTS
03.24.2023
NO. DATE DESCRIPTION
08.04.2023 REVISION 1
08.25.2023 REVISION 2
PRINCIPAL IN CHARGE
F. CAMPBELL
................. I ............. .......... .................
PROJECT MANAGER
M,TPRRES .........................................................
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
FINISH PLAN
A4.0
PLAN LEGEND:
CEILING
FLOORING, WALL BASE AND TRANSITION STRIPS
PAINT, WALLCOVERING AND WALL TILE
SURFACES
CL1 CEILING TYPE I
BVl VINYL WALL BASE - I
WV9 WALLCOVERING
QZ2] QUARTZ U RFACE COUNTERTOP - 2
OUR
ACOUSTICAL CEILING TILE AND GRID SYS CEILING
MANUFACTURER: ROPPE
DISTRIBUTOR: NATIONAL SOLUTIONS
RLID
MMANUFA DA TILE
MANUFACTURER: USG
r WALL I BASE
STYLE: SIMPLICITY BOLD PV4005
PATTERN: PAVE
COLOR: SIMPLY WHITE NQ76
STYLE: OLYMPIC MICRO TEGULAR
COLOR: 194 BURNT UMBER
COLOR: BEVELED GLASS Y46285PV
FINISH: POLISHED
COLOR: WHITE TILES AND WHITE GRID LFLOORI
SIZE: 4-1/2" HIGH
WIDTH: 54"
THICKNESS: 3 CM
SIZE: 2' X 2' X 5/8"
LOCATION: AS INDICATED; ON MILLWORK BASE CABINETS
LOCATION: AS INDICATED ON PLAN
EDGE PROFILE: EASED EDGE
CEILING TYPE 2
AT FINISHED FLOOR
NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL.
LOCATION: PROVIDER & HUDDLE COUNTERTOPS
CL2
DRYWALL CEILINGS AND SOFFITS
NOTES: PROVIDE PRE -FORMED CORNERS. PROVIDE IN 120' CONTINUOUS
CONTACT KATIE HANNIGAN T (407)446-5043 OR
NOTES: 2" CORNER FOR COUNTER TOPS. CONTACT LORI
FINISH: PT1
COILS.
KATIE.HANNIGAN@NATIONALSOLUTIONS.COM
SCHWARTZ AT (407)716-6447 OR LORI.SCHWARTZ@DALTILE.COM
BV2
VINYL WALL BASE - 2
MANUFACTURER: JOHNSONITE
WV16
WALLCOVERING - 10
DISTRIBUTOR: NATIONAL SOLUTIONS
SS3 SOLID SURFACE COUNTERTOP - 3
FLOORING, WALL BASE AND TRANSITION STRIPS
MANUFACTURER: CORIAN
STYLE: TRADITIONAL WALL BASE
PATTERN: PAVE
COLOR: SPARKLING WHITE
LVTI
LUXURY VINYL COMPOSITION TILE - 1
COLOR: TBS
SIZE: 4" HIGH, 1 /8" THICK
COLOR: CLAY MASK Y47322PV
FINISH: POLISHED
MANUFACTURER: SHAW CONTRACT
WIDTH: 54"
THICKNESS: 1/2"
COVER 4
LOCATION; AS INDICATED
LOCATION: AS INDICATED ON PLAN
E:STYLE:
EDGE PROFILE: EASED EDGE
❑
COLOR: PRESERVVEE 07067
NOTES: PROVIDE IN 120' CONTINUOUS COILS. PROVIDE PRE -FORMED
NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL.
LOCATION: PROVIDED BY MIDMARK- WELLNESS SUITE COUNTEROPS
SIZE: 7" X 59"
CORNERS. TO ORDER CONTACT KELLI RUSSELL AT (407)280-9531 OR
CONTACT KATIE HANNIGAN AT (407)446-5043 OR
NOTES: 2" CORNER FOR COUNTER TOPS
INSTALL PATTERN: STAGGER
KELLI.RUSSELL@TARKETT.COM
KATIE. HANNIGAN@NATIONALSOLUTIONS.COM
LOCATION: AS INDICATED ON PLAN.
WALL TILE 1
NOTES: INSTALL PER MANUFACTURER'S REQUIREMENTS. USE A SHAW
WT1
DISTRIBUTOR: CERAMIC TECHNICS LTD
SS4 SOLID SURFACE COUNTERTOP - 4
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL
STYLE: STUDIO MARMI METRO
MANUFACTURER: CORIAN
FLOORING TRANSITIONS. CONTACT VIRNA MITCHELL AT
TRANSITION STRIP - 1
COLOR: FLAVUS
COLOR: WEATHERED CONCRETE
VIRNA.MITCHELL@SHAWCONTRACT.COM OR (407)405-0422
TS1
MANUFACTURER: SCHLUTER SYSTEMS
SIZE: 4"X12"
FINISH: POLISHED
THICKNESS: 1
LUXURY VINYL COMPOSITION TILE - 2
SIZE: TO BE DETERMINED BY INSTALLER
GROUT: LATICRETE 89 SMOKE
E:
EDGE PROFILE: EASED EDGE
LVT2
MANUFACTURER: SHAW CONTRACT
COLOR:
LOCATION: AS NOTED ON PLAN - LVT TO FT
GROUT JOINT WIDTH: 1/8"
INSTALL PATTERN: HORIZONTAL BRICK
LOCATION: AS INDICATED ON PLAN
STYLE: COVER 4140V
COLOR: SECURE 07068
NOTES: CONFIRM PROFILE IS APPROPRIATE FOR APPLICATION &PER ADAAG.
LOCATION: AS INDICATED ON PLAN
NOTES: 2" CORNER FOR COUNTER TOPS
SIZE: 7" X 59"
TS2
TRANSITION STRIP - 2
NOTES: TO ORDER CONTACT JACQUI ANTLEY AT (407)312-5597
OR JANTLEY@CERAMICTECHNICS.COM
INSTALL PATTERN: STAGGER
MANUFACTURER:
LOCATION: AS INDICATED ON PLAN.
SIZE: TO BE DETERMINED BY INSTALLER
NOTES: INSTALL PER MANUFACTURER'S REQUIREMENTS. USE A SHAW
COLOR:
WT2
WALL TILE 2
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL
LOCATION: AS NOTED ON PLAN - LVT TO VCT
DISTRIBUTOR: TILEBAR
FLOORING TRANSITIONS. CONTACT VIRNA MITCHELL AT
NOTES: CONFIRM PROFILE IS APPROPRIATE FOR APPLICATION & PER ADAAG.
MANUFACTURER: SOHO STUDIO
VIRNA.MITCHELL@SHAWCONTRACT.COM OR (407)405-0422
TRANSITION STRIP - 3
STYLE: ALCHIMIA TLCFALCMBLU3X12
TS3
MANUFACTURER:
COLOR: ALCHIMIA BLUE
ALL WINDOW TREATMENT WILL BE MECHO 1-3 %OPACITY
MANUAL ROLLER SHADE
FINISH
PATTERN KEY:
SIZE: TO BE DETERMINED BY INSTALLER
COLOR:
SIZE: 3"X12"
GROUT: LATICRETE 35 MOCHA
CPT1
CARPET TILE - 1
GROUT JOINT WIDTH: 1/8"
❑ CI CICOLLECTION:
MANUFACTURER: SHAW
COLLECTIVE
LOCATION: AS NOTED ON PLAN - LVT TO CPT
NOTES: CONFIRM PROFILE IS APPROPRIATE FOR APPLICATION &PER ADAAG.
INSTALL PATTERN: HORIZONTAL BRICK I
LOCATION: AS INDICATED ON PLAN
FINISH
PATTERN KEY:WT3
WALL TILE 3 -TOILET 105 & 130-FLOOR TO CEILING
0 o a
DESIGN: SIDE BY SIDE 5T452
NOTES: TO ORDER CONTACT DIANE ARNN AT (689)216-2468
LAY DIRECTION INDICATOR
COLOR: TOGETHER 50210
OR DARNN@TILEBAR.COM
SIZE: 18"X 36"
WALL TILE 3
INSTALL PATTERN: ASHLAR
WT3 I
LVTI /2 LUXURY VINYL TILE 1 & 2 - STAGGER
LOCATION: AS INDICATED ON PLAN.
DISTRIBUTOR: TILEBAR
NOTES: INSTALL PER MANUFACTURER'S REQUIREMENTS. USE SHAW
MANUFACTURER: WOW
PAINT, WALLCOVERING AND WALL TILE
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL
STYLE: TRAPEZIUM
FLOORING TRANSITIONS.
ICE WHITE MATT
PAINT- 1
SIZE:4"X9"
PT1
MANUFACTURER: SHERWIN WILLIAMS
GROUT: LATICRETE 44 BRIGHT WHITE; LATICRETE SMOKE 89 (WHEN MIXED
CARPET TILE - 2
COLOR: NATURAL CHOICE SW7011
WITH WT4)
CPT2
MANUFACTURER: MILLIKEN
SHEEN: EGGSHELL
GROUT JOINT WIDTH: 1/8"
0
COLLECTION: EDGE KIT
LOCATION: THROUGHOUT U.N.O.
INSTALL PATTERN: SEE FINISH PATTERN KEY
00o
DESIGN: EDGE LIT
LOCATION: FLOOR TO CEILING AS INDICATED ON PLAN
0
RCU
COLOR: MERCURY EDG107-133
PTl A
PAINT - 1 A
MANUFACTURER: SHERWIN WILLIAMS
NOTES: TO ORDER CONTACT DIANE ARNN AT (689)216-2468
OR DARNN@TILEBAR.COM
WT3&4 WALL TILE 3&4 - TOILET 103- FLOOR TO CEILING
SIZE: 9.X
INSTALL PATTERN: ASHLAR
COLOR: NATURAL CHOICE SW7011
WT4
WALL TILE 4
CPT2-5 - CARPET TILE 2-5 - ASHLAR
LOCATION: AS INDICATED ON PLAN.
SHEEN: SEMI -GLOSS
DISTRIBUTOR: TILEBAR
NOTES: 30% OF OVERALL PATTERN WHEN INSTALLED WITH CPT3. INSTALL PER
LOCATION: DOOR FRAMES THROUGHOUT
PAINT 2
MANUFACTURER: WOW
MANUFACTURER'S REQUIREMENTS. USE A MILLIKEN
PT2
-
MANUFACTURER: SHERWIN WILLIAMS
STYLE: H
COLOR: ASHY GREY MATT
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL
COLOR: EXTRA WHITE SW7006
SIZE:
FLOORING TRANSITIONS, CONTACT ROSIE STERLING AT
SHEEN: EGGSHELL
T: L
T: L
GROUT: SMOKE 89
ROSIE.STERLING@MILLIKEN.COM OR (407)580-7909
LOCATION: TRIM
GROUT JOINT WIDTH: 1/8"
CPT3
CARPET TILE - 3
PAINT 3
INSTALL PATTERN: SEE FINISH PATTERN KEY
MANUFACTURER: MILLIKEN
PT3
-
COLLECTION: EDGE LIT
MANUFACTURER: SHERWIN WILLIAMS
LOCATION: AS INDICATED ON PLAN
X,�
o°o
o
DESIGN: EDGE LIT
COLOR: BIG CHILL SW 7648
NOTES: TO ORDER CONTACT DIANE ARNN AT (689)216-2468
00o
COLOR: EDG259-120 ARGON
SHEEN: EGGSHELL
OR DARNN@TILEBAR.COM
SIZE: 9.85" X 39.4"
LOCATION: AS INDICATED ON PLAN.
CG1
CORNER GUARD 1
INSTALL PATTERN: ASHLAR
PT4
PAINT - 4
MANUFACTUER: CONSTRUCTION SPECIALTIES
WT3 WALL TILE 3 - TOILET 120- FLOOR TO CEILING
LOCATION: AS INDICATED ON PLAN.
MANUFACTURER: SHERWIN WILLIAMS
PRODUCT NAME: ACROVYN
NOTES: 70% OF OVERALL PATTERN WHEN INSTALLED WITH CPT2. INSTALL PER
COLOR: TARNISHED TRUMPET SW 9026
COLLECTION: SUEDE
MANUFACTURER'S REQUIREMENTS. USE A MILLIKEN
SHEEN: EGGSHELL
WING AT 90 DEGREE CORNERS (VA-024N)
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL
LOCATION: ACCENT WHERE INDICATED
1-1/2" WING @ ANGLES OTHER THAN 90 DEGREES (VA-200MN)
FTI FLOOR TILE 1 - 1 /3 OFFSET
ZX
FLOORING TRANSITIONS. CONTACT ROSIE STERLING AT
WALLCOVERING - 1
COLOR: EGGSHELL # 100
ROSIE.STERLING@MILLIKEN.COM OR (407)580-7909
WV1
MANUFACTURER: COMMAND
SIZE: 8'-0" LENGTHS
CPT4
CARPET TILE - 4
2
COLLECTION: DENSHO
PATTERN: CM139-2708
LOCATION: AS INDICATED ON PLAN
NOTES: PROVIDE NO TAPE VERSION AND INSTALL WITH ADHESIVE IN
MANUFACTURER: MILLIKEN
COLLECTION: COMFORTABLE CONCRETE
COLOR: OATMEAL
THE FIELD. CONTACT KELSEY TRACY AT (813)831-3344 OR
17
DESIGN: URBAN SKETCH
WIDTH: 52"
KTRACY@CAS-CORP.COM
COLOR: URS 180-153 OYSTER SHELL
LOCATION: AS INDICATED ON PLAN
NOTES: MICROPERFORATE WHEN INSTALLED EXTERIOR WALL.
FRP
ENGINEERED PVC FREE RIGID SHEET
SIZE: 19.7" X 19.7
MANUFACTURER: CONSTRUCTION SPECIALTIES
INSTALL PATTERN: TBD
HANNIGAN
CONTACT KATIE HANNIGAN AT 3 OR
3
PRODUCT NAME: CS ACROVYN 4000 SHEET
LOCATION: AS INDICATED ON PLAN.
LUTIONS.0
KATIE.HANNIGAN@NATIONA LSOLUTIONS.COM
COLOR: EGGSHELL # 100
NOTES: INSTALL PER MANUFACTURER'S REQUIREMENTS. USE A MILLIKEN
WV2
MANUFACTURERERING: - 2
MANUFACTURER: COMMAND
TEXTURE: STANDARD SUEDE TEXTURE
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL
COLLECTION: DENSHO
SIZE: 4' X 8' (0.040" THICK)
FLOORING TRANSITIONS. CONTACT ROSIE STERLING AT
ROSIE.STERLING@MILLIKEN.COM OR (407)580-7909
z
PATTERN: CM139-2715
LOCATION: AS INDICATED ON PLAN
GENERAL PLAN NOTES: O
COLOR: LOCAMOTIVE
NOTES: INSTALL WITH MATCHED VINYL TRIM MOULDINGS
VCT2 VINYL COMPOSITION TILE 2 - STACKED
CPTS
CARPET TILE 5
MANUFACTURER: MILLIKEN
WIDTH: 52"
VERTICAL ORIENTATION. INSTALL WITH ADHESIVE IN THE FIELD.
LOCATION: AS INDICATED ON PLAN
INSTALL TO 4' AFF CONTACT KELSEY TRACY AT (813)831-3344
MCOLLECTION: COMFORTABLE CONCRETE NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL.
DESIGN: URBAN VISTA CONTACT KATIE HANNIGAN AT (407)446-5043 OR OR KTRACY@CAS-CORP.COM
COLOR: URV05-219-180 PARCHED SAND KATIE.HANNIGAN@NATIONALSOLUTIONS.COM WEl WALL EDGE - 1
SIZE: 19.7" X 19.7" MANUFACTURER: SCHLUTER SYSTEMS
INSTALL PATTERN: ASHLAR WV3 WALLCOVERING - 3 STYLE: JOLLY
LOCATION: AS INDICATED ON PLAN. DISTRIBUTOR: NATIONAL SOLUTIONS COLOR: STAINLESS STEEL BRUSHED 304
NOTES: 10% OF OVERALL PATTERN WHEN USED WITH CPT6. INSTALL PER PATTERN: PAVE SIZE: TO BE DETERMINED BY INSTALLER
MANUFACTURER'S REQUIREMENTS. USE A MILLIKEN COLOR: METALLO Y46289PV LOCATION: EXPOSED EDGE OF WALL TILES 1 & 2
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL WIDTH: 54" NOTES: TO ORDER CONTACT MATT LONG AT (407)795-0794 OR
FLOORING TRANSITIONS. CONTACT ROSIE STERLING AT LOCATION: AS INDICATED ON PLAN MLONG@SCHLUTER.COM
ROSIE.STERLING@MILLIKEN.COM OR (407)580-7909 NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL. GLASS FILM FOR HUDDLE ROOM ALLOWANCE $10 000
1. NOTIFY THE ARCHITECT REGARDING ANY DISCREPANCIES PRIOR TO PROCEEDING
WITH THE WORK.
2. ALL INTERIOR WALL AND CEILING FINISHES SHALL BE NOT LESS THAN CLASS C
(0.22 WATTS/CM SQ.) FOR MINIMUM CRITICAL FLUX IN ACCORDANCE WITH
NFPA 101 AND MEET FLAME SPREAD REQUIREMENTS AND SMOKE DEVELOPMENT IN
ACCORDANCE WITH ASTM E-84 PER TABLE LISTED BELOW. PROVIDE PRODUCT
CERTIFICATIONS TO AUTHORITY HAVING JURISDICTION FOR PROOF OF
COMPLIANCE.
CONTACT KATIE HANNIGAN AT (407)4465043 OR GF 3. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE ACCURACY OF THE
CPT6 -
CARPET TILE - 6 CONTRACTOR'S MEASUREMENTS AND TOTAL YARDAGE REQUIREMENTS TO BE
MANUFACTURER: MILLIKEN KATIE.HANNIGAN@NATIONALSOLUTIONS.COM WTI WALL TILE 1 - COMMUNITY -HORIZONTAL BRICK FURNISHED. NO REQUESTS FOR MATERIALS OR INSTALLATION EXTRAS WILL BE
COLLECTION: COMFORTABLE CONCRETE WV4 WALLCOVERING - 4 CONSIDERED DUE TO MEASUREMENT OR TAKEOFF ERRORS BY CONTRACTOR.
DESIGN: URBAN SKETCH DISTRIBUTOR: NATIONAL SOLUTIONS
COLOR: URS265-106 FADED ANCHOR PATTERN: PAVE 4. ALL MISCELLANEOUS GRILLES, PLATES, OR OTHER DEVICES SHALL BE PAINTED TO
SIZE: 19.7" X 19.7" COLOR: BIRCH Y46288PV MATCH THE WALL OR CEILING IN WHICH THEY ARE INSTALLED, U.N.O.
INSTALL PATTERN: ASHLAR WIDTH: 54"
LOCATION: AS INDICATED ON PLAN. LOCATION: AS INDICATED ON PLAN 5. PROVIDE TRANSITION STRIPS AT ALL FLOORING MATERIAL CHANGES. TRANSITIONS
NOTES: 907 OF OVERALL PATTERN WHEN USED WITH CPT5. INSTALL PER NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL. SURFACES IN DOOR THRESHOLDS SHALL BE CENTERED DIRECTLY UNDER DOOR. FURNISH
MANUFACTURER'S REQUIREMENTS. USE A MILLIKEN CONTACT KATIE HANNIGAN AT (407)446-5043 OR COLOR SAMPLES FOR REVIEW PRIOR TO INSTALLATION.
MANUFACTURED/APPROVED ADHESIVE. INSTALL A TRANSITION STRIP AT ALL KATIE. HANNIGAN@NATIONALSOLUTIONS.COM PL1 PLASTIC LAMINATE - 1
FLOORING TRANSITIONS. CONTACT ROSIE STERLING AT MANUFACTURER: WILSONART 6. PROVIDE TO CAMPBELL + VAN DUSEN DESIGN STUDIO COLOR SAMPLES OF ALL
ER
ROSIE.STERLING@MILLIKEN.COM OR (407)580-7909 WV5COV
WA DISTRIBUTOR:
NG - 5 COLOR: VERANDA TEAK 8209K-28 NATIONAL SOLUTIONS FINISH: GLOSS LINE FINISH WITH AEON
DISTRRIBUTOFINISHES AND MATERIALS FOR VERIFICATION AND REVIEW PRIOR TO INSTALLATION.
FT1 FLOOR TILE - 1 PATTERN: PAVE HANG ORIENTATION: HORIZONTAL 7. FURNISH ATTIC STOCK OF 5% OVERAGE OF ALL WALL COVERING AND FLOORING
DISTRIBUTOR: TRINITY TILE COLOR: MARSH ROOT Y46292PV LOCATION: COMMUNITY, BREAKROOM LOWER CABINETS FINISHES, NOT LESS THAN 10 YARDS OF EACH TYPE OF CARPET AND NOT LESS THAN
SERIES: SOCIAL WIDTH: 54" NOTES: CONTACT MEGHAN RAWLINS ENGER AT (407)832-5388 20 SQUARE FEET OF EACH TYPE OF RESILIENT FLOORING.
COLOR: GRAY LAKE LOCATION: AS INDICATED ON PLAN OR RAWLINM@WILSONART.COM WT2 WALL TILE 2 - BREAKROOM- HORIZONTAL BRICK
SIZE: 12" X 24" NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL. 8. FLOORING INSTALLATION SHALL BE COORDINATED WITH OWNER REPRESENTATIVE.
GROUT: MAPEI 02 PEWTER CONTACT KATIE HANNIGAN AT (407)446-5043 OR pL2 PLASTIC LAMINATE - 2 PRIOR NOTICE OF ANY EXISTING FIELD CONDITIONS THAT MAY POSE A PROBLEM
GROUT JOINT WIDTH: 1/8" KATIE.HANNIGAN@NATIONALSOLUTIONS.COM MANUFACTURER: WILSONART FOR INSTALLATION SHALL BE GIVEN IN A TIMELY MANNER.
INSTALL PATTERN: 1 /3 OFFSET COLOR: CRISP LINEN 4942-38
LOCATION: RESTROOM FLOOR TILE AS NOTED ON PLAN WV6 WALLCOVERING - b FINISH: FINE VELVET FINISH
NOTES: SEAL GROUT. INSTALL A TRANSITION STRIP AT ALL FLOOR DISTRIBUTOR: NATIONAL SOLUTIONS HANG ORIENTATION: HORIZONTAL 11. PRE -PLAN CARPET SEAMING SO AS TO PROVIDE UNIFORM DIRECTION OF PATTERN
TRANSITIONS. TO ORDER CONTACT JENNIFER HORNING AT (321) 231-2181 LOCATION: COMUNITY &BREAK ROOM UPPER CABINETS
PATTERN: PAVE AND LAY OF PILE. LOCATION OF SEAMS SHALL BE CENTERED UNDER DOORS AND
COLOR: MILLION DOLLAR BEIGE Y46303PV WITHOUT SEAMS IN THE DIRECTION OF TRAVEL. SUBMIT SEAMING DIAGRAM FOR
OR JHORNING@TRINITYSURFACES.COM WIDTH: 54" NOTES: CONTACT MEGHAN RAWLINS ENGER AT (407)832-5388 REVIEW PRIOR TO PLACEMENT OF ORDER.
VCT1 VINYL SHEET 1 LOCATION: AS INDICATED ON PLAN OR RAWLINM@WILSONART.COM
MANUFACTURER: SHAW CONTRACT NOTES: MICROPERFORATE WHEN INSTALLED ON EXTERIOR WALL. 12. TEST CONCRETE SUBSTRATES FOR IRH (INTERNAL RELATIVE HUMIDITY) ACCORDING
LASTYLE: VITALITY SHEET CONTACT KATIE HANNIGAN AT (407)446-5043 OR PL3 PLASTIC LAMINATE - 3 TO ASTM F 2170. CONFIRM MOISTURE CONTENT SUITABLE FOR INSTALLATION OF
COLOR: RESTORE 73518 KATIE.HANNIGAN@NATIONALSOLUTIONS.COM MANUFACTURER: WILSONART SIZE: 6.58' X 65.94' COLOR: PORTICO TEAK 821 OK-28
LOCATION: AS INDICATED ON PLAN. WV7 WALLCOVERING - 7 FLOORING PER MANUFACTURERS RECOMMENDATIONS.
FINISH: GLOSS LINE FINISH WITH AEON NOTES: INSTALL PER MANUFACTURER'S REQUIREMENTS. INSTALL A DISTRIBUTOR: NATIONAL SOLUTIONS HANG ORIENTATION: HORIZONTAL 13. MATCH EXISTING STOREFRONT SYSTEM.
TRANSITION STRIP AT ALL FLOORING TRANSITIONS. CONTACT VIRNA PATTERN: PAVE LOCATION: PROVIDER & HUDDLE
MITCHELL AT VIRNA.MITCHELL@SHAWCONTRACT.COM OR (407)405-0422. COLOR: WHITE GRASS Y46294PV NOTES: CONTACT MEGHAN RAWLINS ENGER AT (407)832-5388
WIDTH: 54" OR RAWLINM@WILSONART.COM 14. BUILD UP CARPET TO BE FLUSH WITH LVT.
VCT2 VINYL COMPOSITION TILE 2 LOCATION: AS INDICATED ON PLAN
MANUFACTURER: ARMSTRONG FLOORING NOTES: CONTACT KATIE HANNIGAN AT (407)446-5043 OR
STYLE: STANDARD EXCELON IMPERIAL TEXTURE KATIE.HANNIGAN@NATIONALSOLUTIONS.COM QZ1 QUARTZ SOLID RDALA TI COUNTERTOP - 1 INTERIOR WALL AND CEILING FINISH REQUIREMENTS
RAO COLOR: BLUE/GRAY 51903 MANUFACTURER: ELE
WV8 WALLCOVERING - 8 COLOR: GOLDEN GATE OQ37
SIZE: 12"X12" DISTRIBUTOR: NATIONAL SOLUTIONS FINISH: POLISHED GROUP EXIT ENCLOSURES & CORRIDORS ROOMS & ENCLOSED
INSTALL PATTERN: STRAIGHT PATTERN: PAVE THICKNESS: 3 CM EXIT PASSAGEWAYS SPACES
LOCATION: AS INDICATED ON PLAN. COLOR: GREAT LAKE Y47320PV EDGE PROFILE: EASED EDGE
NOTES: INSTALL PER MANUFACTURER'S REQUIREMENTS. PROVIDE WIDTH: 54" LOCATION: COMMUNITY AND BREAKROOM COUNTERTOPS BUSINESS B C C
APPROPRIATE FLOOR SEALER. INSTALL A TRANSITION STRIP AT ALL FLOORING LOCATION: AS INDICATED ON PLAN 2" CORNER FOR COUNTER TOPS. CONTACT LORI
TRANSITIONS. CONTACT WILLIAM I. WISE AT (803)728-7077 OR NOTES: CONTACT KATIE HANNIGAN AT (407)446-5043 OR SCHWARTZ AT (407)716-6447 OR LORI.SCHWARTZ@DALTILE.COM (PER FBC 2020 803.11)
WIWISE@ARMSTRONGFLOORING.COM. KATIE.HANNIGAN@NATIONALSOLUTIONS.COM
1 /A4.1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
TIT
T
T
T
T
T
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AR0016053
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
J
Z
J
O
=
ry
F
n
(�
=
W
U
IV
U
Q
�
U
_!
_t
CD
ULLj
I---
Q
LLJ
J
0
0
L U
'O Lo
<C
3:
U
N
� Cr)
CONSTRUCTION DOCUMENTS
03.24.2023
NO. DATE DESCRIPTION
08.04.2023 REVISION 1
08.25.2023 REVISION 2
PRINCIPAL IN CHARGE
F. CAMPBELL
PROJECT MANAGER
M, TQRRES........................................................ .
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
FINISH PLAN LEGEND
A4.1
I
ELEVATION
1 /2t1 = 11-011
HUDDLE ROOM
CLG
2'-0"CT
00,
Qz2
HIDDEN
SUPPORT
BRACKET
6'-0"
OPEN KNEE
SPACE
/
/
10
O
'
O
/
/6'-0"
SOFFIT
2'-0"CT
\
/
,
\
`
/
/
/ / /
Qz2
1
N
O SPACE EE
SUPPORT
/
1=1 1=\/AT1r)K1 fnl I -II innl I` Rf1t1N1
1 /2" = 11-011
SECTION_((
1 /2" = 11-011
CLG
SOFFIT
PRINTER/COPIER
HUDDLE
ELEVATION @ HUDDLE ROOM
1 /211 = 1 1-011
CABINET ABBREVIATIONS:
AS ADJUSTABLE SHELVES
BC BASE CABINET
BD BAFFLE DIVIDER
BS BACK SPLASH
CT COUNTER TOP
DW DRAWER
FD DRAWER FOR HANGING FILES
FS FIXED SHELVES
ID INSIDEDIMENSION
KS KNEE SPACE
OS OPEN SHELF
PG PLASTIC GROMMET FOR WIRE ACCESS
PW PULL-OUT WASTE
SH SHELF/SHELVES
SP SINK PANEL
TS TOE SPACE 4" TYP.
UC UPPER CABINET
I
NI tO
a
zo
I
CLG
0
i0
SOFFIT
2' - 0" CT
9' - 6"
/
9' - 6"
2' - 0" CT
/
/
, '
`
/
/ /
/
00
o
N
Qz2
Qz2
�
�
�
a
HIDDEN
SUPPORT
BRACKET
OPEN KNEE
SPACE
OPEN KNEE
SPACE
OPEN KNEE
SPACE
OPEN KNEE
SPACE
HIDDEN
SUPPORT
BRACKET
/
ELEVATION @ HUDDLE ROOM
1 /211= 11-011
SECTION @ HUDDLE
1 /2" = 11-011
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL, Lic. No. AR0016053
v
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
I
Ll-
cn
J
J_
CY
=
W
E—
IV
J
�
LLI
LLI
J
=
J
m
_
+
J
Z
Q
De
Q
i
O
(-)
W
0—
C)zW
L3._
Q
r-4
p(
i--1 (r)
PRINCIPAL IN CHARGE
F. CAMPBELL
.....................................................................
PROJECT MANAGER
M. TORRES
....................................................................
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-0 l
MILLWORK
A5.1
VC
V �Vvl
/B\
SANITARY WASTE RISER DIAGRAM
NTS
UNZ
off
PICO
GENERAL NOTES:
1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING AND
CONSTRUCTION TO SURVEY EXISTING CONDITIONS.
2. CONTRACTOR SHALL INSTALL APPLIANCES PER
MANUFACTURER'S PLUMBING REQUIREMENTS.
3. CONTRACTOR SHALL COORDINATE THE SANITARY VENTING WITH
THE EXISTING VTR'S ((1) 3- & (1) 2-) PROVIDED IN THE SHELL
PACKAGE. IF THE EXISTING VTR'S ARE WITHIN 10'-0" OF THE
RTU OUTSIDE AIR INTAKES THE CONTRACTOR SHALL
COORDINATE NEW LOCATIONS.
KEY NOTES:
CONTRACTOR SHALL TIE NEW 3- SANITARY WASTE LINE INTO
NEAREST EXISTING SANITARY LINE OF ADEQUATE SIZE.
PROVIDE 3" VENT THRU ROOF. CONTRACTOR SHALL COORDINATE
EXACT LOCATION WITH ROOFTOP AIR HANDLING UNITS TO MAINTAIN A
MINIMUM OF 10'-0" CLEARANCE BETWEEN THE VENT AND THE
ROOFTOP UNIT'S OUTSIDE AIR INTAKE.
FIXTURES PIPE SIZE
FIXTURE
SAN SIZE
VENT SIZE
WATER CLOSET
3"
2
LAV / SINK
3"
1-1/2-
ELECT WATER COOLER
3"
1-1/2-
FLOOR DRAIN
3"
2"
NOTE:
PLUMBING CONTRACTOR SHALL FIELD VERIFY, USING SUCH
METHODS AS A SEWER CAMERA, LOW FREQUENCY GPR (GROUND
PENETRATING RADAR) OR EM (ELECTROMAGNETIC) UTILITY
LOCATING METHODS DURING DEMOLITION PHASE OF PROJECT TO
DETERMINE THE EXACT CONDITION OF PIPE, LOCATION, SIZE,
INVERT AND DIREC11ON OF FLOW OF ALL EXISTING
SANITARY/GREASE WASTE LINES WITHIN SCOPE OF PROJECT.
DISCREPANCIES AND UNFORESEEN CONDITIONS ARE TO BE
BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT AND
PROJECT ENGINEER PRIOR TO PROCEEDING WITH DEMOLITION IN
THE AREA OF CONCERN.
CAMPBELL + VAN DUSEN
ARCHITECTURE INTERIOR DESIGN
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AA26003339
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AROO 16053
COPY OF THIS PLAN 15 NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
\px11II11j///
\,qR JAp
0.
is CO
OP
A.
01?/DA
0-
Taylor J. Lewis, PE,
FL Reg. No. 90018
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
I
Lj-
0
r'-4
ry
I
U
<
0
L/)
L.Lj
L1J
>
I
co
I--
F—
+
Lr)
T
(-)
=
---0
rl.*,
<
LU
LLJ
0
-10 1-
L11
�-o L0
0!!�
<
3�:
or-0,
X
ru--4j
(1yo)
CONSTRUCTION DOCUMENTS
03.24.2023
PRINCIPAL IN CHARGE
F. CAMPBELL
..................... ......... ........... .......... ........
PROJECT MANAGER
M. TORRES
............... I ....................... ........... ........
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
MEP CONSULTING
SANITARY WASTE
ENGINEERS
SINCE 1977
RISER DIAGRAM
FL REG NO. 3089
2016 ALDEN RD.
ORLANDO, FL
32803
(407) 246-1688
WWW.PEIRACOM
P3* I
PEI PROXCT
22121
rio (9
LIGHTING RENOVATION PLAN
1/811 � 1 1-011
GENERAL LIGHTING NOTES
1 . PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT
TO EMERGENCY EGRESS LIGHTS. RUN 3 #12 - 1 #12 GND - 3/4"C TO
INCLUDE UNSWITCHED CONDUCTOR.
2. PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT
TO EXIT SIGNS. RUN 2 # 12 - I # 12 GND - 3/4"C.
3. LIGHT FIXTURES BEING REUSED SHALL BE REPAIRED, CLEANED AND
RELAMPED.
4. SWITCHES SHALL BE GANGED WHEN THEY APPEAR ADJACENT
TO ONE ANOTHER ON PLANS WHEREVER PRACTICABLE. PROVIDE
MULTI -GANG JUNCTION BOX AND COVER PLATE AS REQUIRED.
5. DASHED ARCS INDICATE CONTINUATION OF BRANCH CIRCUIT BUT NOT
SWITCH CONTROL.
6. UNLESS OTHERWISE NOTED, ALL FIXTURES AND DEVICES SHOWN ON
THIS PLAN ARE NEW. ALL NEW FIXTURES AND SWITCHES SHALL
MATCH WELL 65 IN WINTERPARK.
7. VERIFY THAT DIMMER MATCHES LAMP TYPE PRIOR TO ORDER.
& ELECTRICAL CONTRACTOR SHALL PROVIDE A LUMINAIRE DISCONNECT
CONNECTOR FOR ALL FLUORESCENT FIXTURES, AS REQUIRED BY N.E.C,
410.130(g)3 2011. UL LISTED CONNECTORS ARE MANUFACTURER BY
IDEAL, THOMAS AND BETTS AND WAGO, ANY UL LISTED CONNECTOR
WILL BE ACCEPTABLE. INSTALL PER MANUFACTURERS SPECIFICATIONS.
9. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN FROM FIELD
INVESTIGATION AND/OR ORIGINAL DOCUMENTS AND SHOWN FOR
THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND SHALL NOT
BE CONSIDERED "AS -BUILT" CONDITION. BEFORE CONSTRUCTION
BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL BRANCH
CIRCUITS.
10. CONTRACTOR SHALL INCLUDE COMMISSIONING OF LIGHTING
CONTROL SYSTEM BY MANUFACTURER IN BASE BID,
11. VERIFY CEILING TYPES BEFORE ORDERING LIGHT FIXTURES.
LIGHTING PLAN NOTES
FEED FIXTURES FROM EXISTING, LOCAL LIGHTING CIRCUIT. FIELD
VERIFY EXACT CIRCUIT NUMBER. TYPICAL ALL EXIT SIGNS. RUN
AB 2#12 1 #12 GND - 3/4" C.
PROVIDE A NEW EXTERIOR GRADE BUILDING WALL MOUNTED
LED LIGHT FIXTURE (ANPLIGHTING TYPE
ORB220-FR-MOl 6LDD-W-35K-RTCW) COORDINATE MOUNTING
SOURCE, CORD STYLE AND FINISHES WITH ARCHiTECT/OWNER
PRIOR TO ORDERING. CONNECT ALL BUILDING MOUNTED
LIGHTS TO PANEL VIA TIME CLOCK WITH PHOTOCELL. REFER TO
EXTERIOR LIGHTING/SIGNAGE WIRING DIAGRAM.
"N
ROVIDER WORK
ROOM
F-132--1
- ---� Do
� _J
—OF
ONE --
row
q
<
V
1-21541,
V
1-19
1 7
BI- 5
WELLNESS SUITE
5
WELLN�SS SUITE
WELLNESS SUITE I
Ili's
WELLNESS SUIT
8 1
6
F
7
I
L --------
I?%
f
I OL
9
.02F
HUDDLE
Al-31
E;=
I
W limmmoppo-P
51111 L, i
pffa
924 1,
1. d i
wd
.......... ............................ ..
a El I AUTOCLAVE
Al-18
Ik Wo Ali-16
.0111-111�.Al
&A
=A
INC�
--_� 2 POWER RENOVATION PLAN
E3.1) 1/8" = V-0"
GENERAL POWER NOTES
1 . INDICATED CIRCUIT NUMBERS ARE SUGGESTED FROM EXISTING
SPARE BREAKERS AND SPACES IN EXISTING PANELS.
CONTRACTOR MAY USE DIFFERENT CIRCUIT NUMBERS TO MATCH
FIELD CONDITIONS.
2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH INTERIOR
DESIGN PACKAGE FOR ALL MILLWORK AND WALL DESIGNS PRIOR
TO COMMENCING WORK.
3. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN FROM FIELD
INVESTIGATION AND /OR ORIGINAL DOCUMENTS AND SHOWN
FOR THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND
SHALL NOT BE CONSIDERED "AS -BUILT" CONDITION. BEFORE
CONSTRUCTION BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD
VERIFY ALL BRANCH CIRCUITS.
4. PROVIDE TYPED, UPDATED PANEL SCHEDULES UPON COMPLETION
OF WORK.
5. PROVDE SHOW WINDOW RECEPTACLES ABOVE ALL WINDOWS
PER CODE LISTED IN THIS NOTE:
• Definition per Article 100 of NEC for Show Window - Any
window, including windows above doors, used or designed
to be used for the display of goods or advertising material,
whether it is fully or partly enclosed or entirely open at the
rear and whether or not it has a platform raised higher
than the street floor level.
• Article 210.62 of NEC Show Windows - provide at least (1)
receptacle within 18in of top of show window for each 12
feet or major faction thereof (6' or more) of show window
measured horizontally.
• Article 210.14(G) and 220.43(A) regarding load calculations
- 210.14(G) allows calculations for unit load per receptacle
(180VA). We will use this method. 220.43(A) is for show
window linear lighting which does not apply.
6. REFER TO FIRE ALARM NOTES, RISER AND SPKIFICATIONS FOR MORE
INFORMATION.
nr:
�q" Of OUTLET BOX
CONFIGURATION 13'
LCD WDAX LOCATION
POWER PLAN NOTES
0
CONNECT ELECTRIC WATER HEATER. PROVIDE 30A, 3P, 240V,
CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE
N-1, NON -FUSED DISCONNECT SWITCH. COORDINATE WITH
MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL
PLUMBING CONTRACTOR. RUN 3#10, 1 #10 GND - 3/4" C.
CONTRACTOR. FAN HAS MOTION SENSOR CONTROL.
PROVIDE FLUSH MOUNTED FLOOR BOX WITH 120V QUAD
CONNECT SPLIT SYSTEM. PROVIDE 30A, 2P, 240V, N-3R FUSED
RECEPTACLE AND TELE/DATA OUTLETS, WALKER OMNIBOX
DISCONNECT SWITCH ON ROOF, FUSE PER MANUFACTURER'S
SERIES (#88OS2-TWO GANG) OR APPROVED EQUAL. SAWCUT
NAMEPLATE. COORDINATE WITH MECHANICAL CONTRACTOR.
FLOOR AS REQUIRED. RUN 2#12, 1 #12 FOR 120V POWER.
ELECTRICAL POWER IS THROUGH CONDENSING UNIT THEN TO
RUN 1-1/4" CONDUIT WITH PULLSTRING FOR LOW VOLTAGE
INDOOR UNIT.
CABLING. PROVIDE ALL ACCESSORIES REQUIRED FOR A
RUN 2 #10 - 1 #10 GND - 3/4"C TO CONDENSING UNIT AND 2
COMPLETE SYSTEM. COORDINATE EXACT LOCATION, FINISHES,
#10 - 1 #10 GND - 3/4"C TO INDOOR UNIT.
COVERPLATES AND TYPE OF LOW VOLTAGE OUTLETS WITH
PROVIDE 30A, 2P, 240V, N-1, FUSED DISCONNECT SWITCH AT
OWNER.
INDOOR UNIT, FUSE AS MANUFACTURER'S NAMEPLATE.
(D
NEW CARD READER AND ELECTRIC STRIKE. PROVIDE 3/4"
(D
EXTEND CONDUIT (2)4"C. TO NEW COMM ROOM.
RACEWAY TO ACCESSIBLE CEILING FOR LOW VOLTAGE POWER.
COORDINATE WITH CARD READER VENDOR. TENANT SECURITY
PROVIDE RECESSED, FLANGELESS BOX WITH DUPLEX
SYSTEM SHALL BE CONNECTED TO BUILDING FIRE ALARM
RECEPTACLE AT HEIGHT SHOWN DRAWING 2/E3.1. ARLINGTON
SYSTEM TO RELEASE ALL LOCKS UPON ACTIVATION. PROVIDE
MODEL #TVBS81 0.
ALL CONNECTIONS AND ACCESSORIES REQUIRED FOR A FULLY
OPERATIONAL SYSTEM. ANY CARD READERS INSTALLED IN
CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE
SUCH A WAY THAT THEY PREVENT FREE EGRESS SHALL BE IN
MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL
COMPLIANCE WITH SECTION 7.2.1.6.2 FOR ACCESS
CONTRACTOR. FAN SHALL RUN CONTINUOUSLY.
CONTROLLED EGRESS DOOR ASSEMBLIES (NFPA 101)
PROVIDE 36" PROPER CLEARANCE PER NEC IN FRONT OF NEW
PROVIDE RECESSED 2-GANG BOX AT 42" A.F.F FOR AV
PANELS.
CABLING. TYPICAL FOR ALL ALL WELLNESS SUITES. ARLINGTON
MODEL #TVBS81 0,
PROVIDE NEW FLOW AND TAMPER SWITCHES ON EXISTING
BACKFLOW PREVENTER. CONNECT PER MANUFATURERS
PROVIDE JUNCTION BOXES AND 120V CIRCUIT FOR DOOR
SPECIFICATIONS.
OPENER. COORDINATE EXACT REQUIREMENTS WITH VENDOR.
REFER TO ARCHITECT'S DRAWING 2/AO.5 FOR RECESSED
PROVIDE 8'H X 4W X 3/4"D PLYWOOD BACK BOARD ON WALL
DRYWALL NICHE. LOCATE DUPLEX RECEPTACLE IN SIDE WALL OF
(D
FOR TELECOMMUNICATION EQUIPMENT. PAINT WITH GRAY FIRE
NICHE AS SHOWN.
RETARDENT PAINT. INSTALL DOUBLE DUPLEX RECEPTACLE
MOUNTED @ 42" AFF. RUN 2" E.C. TO EXISTING MAIN
TELEPHONE TERMINAL BOARD. PROVIDE #6 GROUND WITH
BUS BAR CONNECTED TO BUILDING GROUND LUG.
PA'nENT CARE AREA SYMBOL LEGEND
<0> GENERAL CARE - CATEGORY 2
NOTES:
1. THERE ARE NO CRITICAL OR WET PATIENT AREAS IN THE SCOPE OF WORK.
2, GENERAL PATIENT CARE AREAS REQUIRE A WIRING METHOD WITH A REDUNDANT
GROUND AS PER ARTICLE 517.13 OF THE NEC.
GROUNDING 0 FALL RECEPTACLES, LIGHTING AND FIXED EQUIPMENT IN PATIENT
CARE AREAS SHALL COMPLY WITH NEC ARTICLE 517.13 (A) AND (B)
Al
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AA26003339
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FLLIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
G. S PA 4,,
r E N
4Z- %
No. 6460'
3
-a STATE OF
ell
Bryan G. Spangler, PE,
FL Reg. No. 64601
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
I
LJ_
V�
ry
0
F—
q
LU
F—
U
I
<
Q
00
U_1
LU
>
I
0
=
F_
F—
+
LO
U
=
Cie
<
LU
LLJ
0
-0 ,1-
�10 U-)
CL_
U-1
n-I
<
3:
or-01
CL
ru-_41
CI*Yl)l
CONSTRUCTION DOCUMENTS
03.24.2023
PRINCIPAL IN CHARGE
F, CAMPBELL
....................................................................
PROJECT MANAGER
M. TORRES
................................................... ...... .........
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
ELECTRICAL
RENOVATION PLANS
NOTE:
CONFIGURATION'A REFERS TO KEYED NOTE
CONFIGURATION 'B' REFERS TO KEYED NOTE (D
11�flll III �i. � I _Tli I lif - I
E3. I
SANITARY WASTE RENOVATION PLAN
P2. 1) 1/411 = 1 1-011
/—OA
- - —OD
OE
OF
GENERAL NOTES:
1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING AND
CONSTRUCTION TO SURVEY EXISTING CONDITIONS.
2. CONTRACTOR SHALL INSTALL APPLIANCES PER
MANUFACTURER'S PLUMBING REQUIREMENTS.
KEY NOTES:
(D CONTRACTOR SHALL TiE NEW 3' SANITARY WASTE LINE INTO
//B\ NEAREST EXISTING SANITARY LINE OF ADEQUATE SIZE.
CONTRACTOR SHALL COORDINATE CENTERING THE WALL CLEANOUT IN
THE SPACE WERE THE ROLL —OUT CABINETRY RESIDES. REFER TO
ARCHITECTURAL PLANS FOR CABINETRY DETAILS.
EXISTING STORM DRAIN AND OVERFLOW PIPING. CONTRACTOR SHAH
COORDINATE ALL DISCIPLINES.
FIXTURES PIPE SIZE
FIXTURE
SAN SIZE
VENT SIZE
WATER CLOSET
3"
2"
LAV / SINK
3*
1-1/2"
WATER COOLER
3'
1-1/2-
-ELECT
FLOOR DRAIN
3m
2"
NOTE:
PLUMBING CONTRACTOR SHALL FIELD VERIFY, USING SUCH
METHODS AS A SEWER CAMERA, LOW FREQUENCY GPR (GROUND
PENETRATING RADAR) OR EM (ELECTROMAGNETIC) UTILITY
LOCATING METHODS DURING DEMOLITION PHASE OF PROJECT TO
DETERMINE THE EXACT CONDITION OF PIPE, LOCATION, SIZE,
INVERT AND DIRECTION OF FLOW OF ALL EXISTING
SANITARY/GREASE WASTE LINES WITHIN SCOPE OF PROJECT.
DISCREPANCIES AND UNFORESEEN CONDITIONS ARE TO BE
BROUGHT TO THE ATTEN11ON OF THE OWNER, ARCHITECT AND
PROJECT ENGINEER PRIOR TO PROCEEDING WITH DEMOLITION IN
THE AREA OF CONCERN.
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC,
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AA26003339
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR001 6053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
\0\1111 I//////
NN \pkmSS4
& . .............
cews
\kp
S-T P'-f E OF
.......... ............ .
N
Ili; SfONA\�
Taylor J. Lewis, PE,
FL Reg. No. 90018
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
I
Lj_
ry
0
LU
r,v
F—
P-4
U
I
<
(/)
U_j
L.LJ
>
_j
F—
F—
+
Lr-)
U-17
__1.0
r1o"
LU
LL]
0
>'IT
C)
Lu
'0 L(.)
0!:�
<
3:
or-2
0-
rL�L_l
(1y"')
CONSTRUCTION DOCUMENTS
03.24.2023
DESCRIPTION
PRINCIPAL IN CHARGE
F. CAMPBELL
... I .... I ................................................
PROJECT MANAGER
M. TORRES
............ I � ...... I ........ I ............ I ........ ..............
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
SANITARY WASTE
RENOVATION
__ - __ - ____ T7__F_ T _'__ 7 -T __F_ I I �. I, . 1—, 11, � i I I , i - 7�7 � I- _]I --I T_T___.1 111 jj , hA i, I j I I I I I - ------ I- -H
I F_ - __ - __ ___T_ , F
(1,0 9
T- �
n rin
--- H
--H
I I
I
Lu
Lj L
U
DOMESTIC WATER RENOVATION PLAN
1/4" = V-0.
r-OA
-- Do
[CE
OF
--\-6G
GENERAL NOTES:
1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING AND
CONSTRUCTION TO SURVEY EXISTING CONDITIONS.
2. CONTRACTOR SHAH INSTALL RECIR. PUMP IN A EASY
ACCESSIBLE LOCATION.
3. CONTRACTOR SHALL INSTALL VALVES FOR PIPING IN EASY
ACCESSIBLE LOCATIONS AND WITHIN A CERTAIN DISTANCE TO
MEET CODE. IF AN ACCESS DOOR IS NEEDED ONE SHALL BE
INSTALLED.
4. CONTRACTOR SHALL INSTALL APPLIANCES PER
MANUFACTURER'S PLUMBING REQUIREMENTS.
KEY NOTES:
CONTRACTOR SHALL PROVIDE 1/2" COLD WATER LINE
WITH LEAD FREE DUAL CHECK BACKFI-OW PREVENTER TO
NEW ICE MACHINE/ICE MAKER. BACKFLOW PREVENTER
SHALL BE WATTS LF007 OR APPROVED EQUAL.
CONTRACTOR SHALL PROVIDE LEAK/FLOOD DETECTION
PROTEC11ON WITH "FLOODSTOP" DEVICE. COORDINATE NTH
BUILDING OWNER ON SPECIFIC LOCA11ONS AND MODEL
NUMBERS PER PLUMBING RENOVATION/INSTALLATION.
CONTRACTOR SHALL INSTALL AND CONNECT NEW
ELECTRIC WATER HEATER (EWH-1). SEE SHEET P1.1 FOR
MORE INFORMATION.
CONTRACTOR SHALL INSTALL NEW RECIRCULATINGPUMP.
SEE ELECTRIC WATER HEATER DETAIL FOR MORE
INFORMATION ON SHEET P1.1.
�D CIRCUIT SOLVER THERMOSTATIC BALANCING VALVE WITH
INTEGRATED UNION, LEAD FREE BALL VALVE AND CHECK
VALVE INSERT. MODEL NO. CSUA-1/2-120—CV1-03
(OR APPROVED EQUAL).
CONTRACTOR SHALL TIE NEW 2- COLD WATER LINE INTO
NEAREST EXISTING 2" COLD WATER LINE.
CONTRACTOR SHALL PROVIDE 112n COLD WATER LINE
WITH LEAD FREE DUAL CHECK BACKFLOW PREVENTER TO
NEW COFFEE MACHINE/COFFEE MAKER. BACKFLOW
PREVENTER SHALL BE WATTS SD-3 OR APPROVED
EQUAL COORDINATE FINAL LOCA11ON NTH ARCHITECT.
FIXTURES' SUPPLY PIPE SIZE
FIXTURE
CW
HW
HWR
WATER CLOSET
1/2"
ELECT WATER COOLER
1/2"
--
LAV / SINK
112n
1/2"
1/21f
MOP SINK T
1/y
1/2',
1 --
WWI 9,111111112111
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AA26003339
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
FL LIC NO. AR001 6053
A\ COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
.......................
No. goo
18
S7-ATE OF
40
N
V117; 0jVA L
\N
, i�-�
3-31-;L,�
Tb�or J. Lewis, PE,
FL Reg. No. 90018
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
__j
U-
V5
ry
0
LU
U
<
ci
C.")
LU
>
I
co
+
U
LU
)>�10
LU
0
LjLj
114-
Lr)
or-?,
ru--4j
(12)
CONSTRUCTION DOCUMENTS
03.24.2023
PRINCIPAL IN CHARGE
F. CAMPBELL
................... I ................... I ............... ......
PROJECT MANAGER
M. TORRES
.......................................... I .............. ..........
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
DOMESTIC WATER
RENOVATION
P2.2
VV
P�o
55 50ITi5
VVO"�00�
10
3 5AN
.^A
AN
SAN
//B\
I -�' V,
" " ' *' " N �' " " " " " " �' '� '� '� '� '� �' "
j00W'4%00W"'%t4h, N
SANITARY WASTE RISER DIAGRAM
N T3
4-
WASIt I-INZ
pco
GENERAL NOTES:
1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING AND
CONSTRUCTION TO SURVEY EXISTING CONDITIONS.
2. CONTRACTOR SHALL INSTALL APPLIANCES PER
MANUFACTURER'S PLUMBING REQUIREMENTS.
3. CONTRACTOR SHALL COORDINATE THE SANITARY VENTING NTH
THE EXISTING VTR'S ((1) 3- & (1) 2-) PROVIDED IN THE SHELL
PACKAGE. IF THE EXISTING VTR'S ARE WITHIN 10'-0" OF THE
RTU OUTSIDE AIR INTAKES THE CONTRACTOR SHALL
COORDINATE NEW LOCATIONS.
KEY NOTES:
CONTRACTOR SHALL TIE NEW 3- SANITARY WASTE LINE INTO
NEAREST EXISTING SANITARY LINE OF ADEQUATE SIZE.
zk PROVIDE 3" VENT THRU ROOF. CONTRACTOR SHALL COORDINATE
EXACT LOCATION NTH ROOFTOP AIR HANDLING UNITS TO MAINTAIN A
MINIMUM OF 10'-0" CLEARANCE BETWEEN THE VENT AND THE
ROOFTOP UNIT'S OUTSIDE AIR INTAKE.
FIXTURES PIPE SIZE
FIXTURE
SAN SIZE
VENT SIZE
WATER CLOSET
3"
2"
LAV / SINK
3"
1-1/2'
ELECT WATER COOLER
30
1-1/2-
FLOOR DRAIN
3-
2-
NOTE:
PLUMBING CONTRACTOR SHALL FIELD VERIFY, USING SUCH
METHODS AS A SEWER CAMERA, LOW FREQUENCY GPR (GROUND
PENETRATING RADAR) OR EM (ELECTROMAGNETIC) UTILITY
LOCATING METHODS DURING DEMOLITION PHASE OF PROJECT TO
DETERMINE THE EXACT CONDITION OF PIPE, LOCATION, SIZE,
INVERT AND DIRECTION OF FLOW OF ALL EXISTING
SANITARY/GREASE WASTE LINES WITHIN SCOPE OF PROJECT.
DISCREPANCIES AND UNFORESEEN CONDITIONS ARE TO BE
BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT AND
PROJECT ENGINEER PRIOR TO PROCEEDING WITH DEMOL111ON IN
THEAREA OFCONCERN.
CAMPBELL + VAN DUSEN
ARCHITECTURE INTERIOR DESIGN
www.CVDstudio.com
CAMPBELL + VAN DUSEN Design Studio, LLC.
255 South Orange Avenue Suite # 1240
Orlando, Florida 32801
Phone: 407.930.6016
FL. Lic. No. AA26003339
ARCHITECT OF RECORD
FRANK W. CAMPBELL AIA
I'LLIC NO. AR0016053
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ARCHITECT OF RECORD
N
�p
Z! No. 'goo 18
-A STATE OF
0,
////�9 ON A L
Tay1or J. Lewis, PE,
FL Reg. No. 90018
COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
SEALED AND DATED BY THE ENGINEER OF RECORD
I
LL-
ry
0
F—
CL
ri
LU
ry
r,4
U
<
L")
LU
LU
>
I
CID
+
LO
U
=
-'0
Lij
Ljj
0
>
110
f:�
LU
10 LJO
OL
<
3�:
rL-U4
00 CO
r-4., Cy")
CONSTRUCTION DOCUMENTS
03.24.2023
NO. DATE DESCRIPTION
5/03/2023 DDENDUM B
7/28/2023 E LTA 1
2 25/2023 IREVISION 2
PRINCIPAL IN CHARGE
F. CAMPBELL
...................... .......................................
PROJECT MANAGER
M. TORRES
............... I ....................................................
ADVENT HEALTH
WELL 65+
ZEPHYRHILLS
22-0328-01
MEP CONSULTING
SANITARY WASTE
ENGINEERS
SINCE 1977
RISER DIAGRAM
FL REG NO. 3089
2016 ALDEN RD.
ORLANDO, FL.
32603
(407) 246-1688
WWPOFLA.COM
P3. 1
PEI PROECT
22121