HomeMy WebLinkAbout37827 Eiland BlvdFIRE ALARM SYSTEMS - TECHNICAL SPECIFICATIONS PART I GENERAL 1.1 SUMMARY A. THIS SECTION COVERS THE FIRE ALARM SYSTEM INCLUDING INITIATING DEVICES, NOTIFICATION APPLIANCES, CONTROLS, AND SUPERVISORY DEVICES. B. WORK COVERED BY THIS SECTION INCLUDES THE FURNISHING OF LABOR, EQUIPMENT, AND MATERIALS FOR INSTALLATION OF THE FIRE ALARM SYSTEM AS INDICATED ON THE DRAWINGS AND SPECIFICATIONS. C. THE FIRE ALARM SYSTEM SHALL CONSIST OF ALL NECESSARY HARDWARE EQUIPMENT AND SOFTWARE PROGRAMMING TO PERFORM THE FOLLOWING FUNCTIONS: 1. FIRE ALARM AND DETECTION OPERATIONS. 2. CONTROL AND MONITORING OF FIRE SUPPRESSION SYSTEMS, AND OTHER EQUIPMENT AS INDICATED IN THE DRAWINGS AND SPECIFICATIONS. 1.2 ACCEPTABLE MANUFACTURER A. FIRE-LITES, OR EQUAL BY SIMPLEXGRINNEL, NOTIFIER, EDWARDS SYSTEM TECHNOLOGY, AND SILENT KNIGHT. 1.3 RELATED DOCUMENT A. THE SYSTEM AND ALL ASSOCIATED OPERATIONS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: 1. THE FLORIDA BUILDING CODE 2020. 2. FLORIDA FIRE PREVENTION CODE, 6TH EDITION. 3. NFPA 72 (2013), NATIONAL FIRE ALARM CODE. 4. NFPA 70, NATIONAL ELECTRICAL CODE (2017) 5. NFPA 101, LIFE SAFETY CODE (2015) 6. LOCAL JURISDICTIONAL ADOPTED CODES AND STANDARDS. 7. ADA ACCESSIBILITY GUIDELINES. 1.4 SYSTEM DESCRIPTION A. THE SYSTEM AND ALL ASSOCIATED OPERATIONS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: 1. PROVIDE A COMPLETE, NON -CODED, ADDRESSABLE, MICROPROCESSOR -BASED FIRE ALARM SYSTEM WITH INITIATING DEVICES, NOTIFICATION APPLIANCES, AND MONITORING AND CONTROL DEVICES. A SYSTEM GENERAL ALARM SHALL INCLUDE: a. INDICATION OF ALARM CONDITION AT THE FACP AND ANNUNCIATOR(S). b. IDENTIFICATION OF THE DEVICE OR ZONE THAT IS THE SOURCE OF THE ALARM AT THE FACP. c. UNLOCKING OF DESIGNATED DOORS. d. NOTIFYING THE LOCAL FIRE DEPARTMENT. e. INITIATION OF ELEVATOR RECALL IN ACCORDANCE WITH ASME/ANSI A17.3, WHEN SPECIFIED DETECTORS OR SENSORS ARE ACTIVATED. 2. SUPERVISORY OPERATIONS: UPON ACTIVATION OF A SUPERVISORY DEVICE SUCH AS FIRE PUMP POWER FAILURE, PUMP RUNNING, PHASE REVERSAL, LOW AIR PRESSURE SWITCH, AND TAMPER SWITCHES, THE SYSTEM SHALL OPERATE AS FOLLOWS: a. ACTIVATE THE SYSTEM SUPERVISORY SERVICE AUDIBLE SIGNAL AND ILLUMINATE THE LED AT THE CONTROL UNIT. b. RECORD THE EVENT IN THE FACP HISTORICAL LOG. c. TRANSMISSION OF SUPERVISORY SIGNAL TO REMOTE CENTRAL STATION. d. RESTORING THE CONDITION SHALL CAUSE THE SUPERVISORY LED TO CLEAR AND RESTORE THE SYSTEM TO NORMAL. 3. IF THE "ALARM SILENCE" BUTTON IS PRESSED, ALL AUDIBLE AND VISIBLE ALARM SIGNALS SHALL CEASE OPERATION. a. THE "SYSTEM RESET" BUTTON SHALL BE USED TO RETURN THE SYSTEM TO ITS NORMAL STATE. DISPLAY MESSAGES SHALL PROVIDE OPERATOR ASSURANCE OF THE SEQUENTIAL STEPS ("IN PROGRESS", "RESET COMPLETED") AS THEY OCCUR. THE SYSTEM SHALL VERIFY ALL CIRCUITS OR DEVICES ARE RESTORED PRIOR TO RESETTING THE SYSTEM TO AVOID THE POTENTIAL FOR RE -ALARMING THE SYSTEM. THE DISPLAY MESSAGE SHALL INDICATE "ALARM PRESENT, SYSTEM RESET ABORTED." b. SHOULD AN ALARM CONDITION CONTINUE, THE SYSTEM WILL REMAIN IN AN ALARMED STATE. 4. THE "SYSTEM RESET" BUTTON SHALL BE USED TO RETURN THE SYSTEM TO ITS NORMAL STATE. DISPLAY MESSAGES SHALL PROVIDE OPERATOR ASSURANCE OF THE SEQUENTIAL STEPS ("IN PROGRESS", "RESET COMPLETED") AS THEY OCCUR. THE SYSTEM SHALL VERIFY ALL CIRCUITS OR DEVICES ARE RESTORED PRIOR TO RESETTING THE SYSTEM TO AVOID THE POTENTIAL FOR RE -ALARMING THE SYSTEM. THE DISPLAY MESSAGE SHALL INDICATE "ALARM PRESENT, SYSTEM RESET ABORTED. 5. A MANUAL EVACUATION (DRILL) SWITCH SHALL BE PROVIDED TO OPERATE THE NOTIFICATION APPLIANCES WITHOUT CAUSING OTHER CONTROL CIRCUITS TO BE ACTIVATED. a. OPENING OF AN INITIATING OR NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL CAUSE THE AUDIBLE SIGNALS TO VOICE ANNOUNCE THE TROUBLE CONDITION. b. POWER REQUIREMENTS. - THE CONTROL UNIT SHALL RECEIVE AC POWER VIA A DEDICATED CIRCUIT BREAKER. - THE SYSTEM SHALL BE PROVIDED WITH SUFFICIENT BATTERY CAPACITY TO OPERATE THE ENTIRE SYSTEM UPON LOSS OF NORMAL AC POWER IN A NORMAL SUPERVISORY MODE FOR A PERIOD OF 24 HOURS WITH15 MINUTES OF ALARM OPERATION AT THE END OF THIS PERIOD. THE SYSTEM SHALL AUTOMATICALLY TRANSFER TO BATTERY STANDBY UPON POWER FAILURE. ALL BATTERY CHARGING AND RECHARGING OPERATIONS SHALL BE AUTOMATIC. 1.5 QUALITY ASSURANCE A. TINSTALLER QUALIFICATIONS: A FACTORY AUTHORIZED INSTALLER SHALL PERFORM THE WORK OF THIS SECTION. B. EACH AND ALL ITEMS OF THE FIRE ALARM SYSTEM SHALL BE LISTED AS A PRODUCT OF A SINGLE FIRE ALARM SYSTEM MANUFACTURER UNDER THE APPROPRIATE CATEGORY BY UNDERWRITERS LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL. 1.6 MAINTENANCE SERVICE A. MAINTENANCE SERVICE CONTRACT: PROVIDE MAINTENANCE OF FIRE ALARM SYSTEMS AND EQUIPMENT FOR A PERIOD OF 12 MONTHS, USING FACTORY -AUTHORIZED SERVICE REPRESENTATIVES. B. BASIC SERVICES: SYSTEMATIC, ROUTINE MAINTENANCE VISITS ON A QUARTERLY BASIS AT TIMES SCHEDULED WITH THE OWNER. IN ADDITION, RESPOND TO SERVICE CALLS WITHIN 24 HOURS OF NOTIFICATION OF SYSTEM TROUBLE. ADJUST AND REPLACE DEFECTIVE PARTS AND COMPONENTS WITH ORIGINAL MANUFACTURER'S REPLACEMENT PARTS, COMPONENTS, AND SUPPLIES. C. ADDITIONAL SERVICES: PERFORM SERVICES WITHIN THE ABOVE 12-MONTH PERIOD NOT CLASSIFIED AS ROUTINE MAINTENANCE OR AS WARRANTY WORK WHEN AUTHORIZED IN WRITING. COMPENSATION FOR ADDITIONAL SERVICES MUST BE AGREED UPON IN WRITING PRIOR TO PERFORMING SERVICES. FIRE ALARM SYSTEMS - TECHNICAL SPECIFICATIONS CONT. SYMBOL LEGEND PART I) - EXECUTION SYMBOL DESCRIPTIONS 1. ALL WORK SHALL BE INSTALLED AS SHOWN, AND IN ACCORDANCE WITH NFPA 70, NFPA 72, FACP FIRE ALARM CONTROL NFPA 101, FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND IN ACCORDANCE WITH THE PANEL MANUFACTURER'S DIAGRAMS AND RECOMMENDATIONS. FAA FIRE ALARM ANNUNCIATOR PANEL 2. CONTROL PANEL SHALL BE LOCATED BETWEEN 12 TO 78 INCHES AFF. O ADDRESSABLE PULL STATION 3. DETECTORS SHALL BE LOCATED AT LEAST 12 INCHES FROM ANY PART OF ANY LIGHTING FIXTURES, 3 FEET FROM DIFFUSERS OF AIR HANDLING SYSTEMS AND CEILING FANS. OD DUCT MOUNTED SMOKE DETECTOR WITH RELAYS rOR AHU SHUTDOWN. PROVIDE REMOTE WALL MOUNTED LEI) PILOT 4. NOTIFICATION APPLIANCES SHALL BE MOUNTED AT 80 INCHES AFF. INDICATOR LIGHT AND SOUNDER WITH NAMEPLATE, 5. ACCEPTANCE TEST: DO NOT PERFORM ACCEPTANCE TESTING UNTIL THE CERTIFICATE OF (4) ADDRESSABLE HEAT DETECTOR COMPLETION IS SUBMITTED TO THE OWNER. THE RECOMMENDED TESTS LISTED IN NFPA 72 SHALL BE CONSIDERED MANDATORY AND SHALL BE USED TO VERIFY THAT PREVIOUS O ADDRESSABLE SMOKE DETECTOR DEFICIENCIES HAVE BEEN CORRECTED. COMPLETE AND SUBMIT THE NFPA 72, INSPECTION AND TESTING FORM. THE TEST SHALL INCLUDE ALL REQUIREMENTS OF NFPA 72 AND THE ® STROBE FOLLOWING: A. TEST OF EACH FUNCTION OF THE CONTROL PANEL. HORN/STROBE B. TEST OF EACH CIRCUIT IN BOTH TROUBLE AND NORMAL MODES. ® MONITOR MODULE C. TEXTS OF EACH ALARM INITIATING DEVICES IN BOTH NORMAL AND TROUBLE CONDITIONS. ® RELAY D. TESTS OF EACH CONTROL CIRCUIT AND DEVICE. ® FLOW SWITCH E. TESTS OF EACH ALARM NOTIFICATION APPLIANCE. ® TAMPER SWITCH F. TESTS OF THE BATTERY CHARGER AND BATTERIES. G. COMPLETE OPERATIONAL TESTS UNDER EMERGENCY POWER SUPPLY. H. VISUAL INSPECTION OF WIRING CONNECTIONS. I. OPENING THE CIRCUIT AT EACH ALARM INITIATING DEVICE AND NOTIFICATION APPLIANCE TO TEST THE WIRING SUPERVISORY FEATURE. J. GROUND FAULT. K. SHORT CIRCUIT FAULTS. L. STRAY VOLTAGE. GENERAL NOTES: 1. PROVIDE AN ADDRESABLE FIRE ALARM SYSTEM FOR THIS PROJECT. CONTRACT DRAWINGS SHOW LAYOUTS BASED ON TYPICAL FIRE ALARM DEVICES/EQUIPMENT. THE CONTRACTOR SHALL CHECK THE LAYOUT BASED ON ACTUAL DEVICES/EQUIPMENT TO BE PROVIDED AND MAKE NECESSARY REVISIONS. PROVIDE ALL FIRE ALARM EQUIPMENT, DEVICES, WIRING, CONDUIT, AND ASSOCIATED COMPONENTS FOR COMPLETE INSTALLATIONS. 2. ALL CONDUIT SHALL BE IN MINIMUM 1 /2" UNLESS NOTED OTHERWISE AND CONDUCTORS SHALL BE COPPER. CONDUCTORS SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS. ALL CONDUCTORS SHALL BE IN CONDUIT. 3. CONDUIT FOR THE FIRE ALARM SYSTEM SHALL BE COMPLETELY INDEPENDENT OF ALL OTHER WIRING. 4. AUDIBLE DEVICES SHALL BE WIRED INDEPENDENTLY FROM VISUAL DEVICES. SILENCING OF AUDIBLE DEVICES SHALL NOT DE -ACTIVATE FLASHING STROBES UNTIL ALARM CONDITION IS CLEARED. 5. EQUIPMENT AND DEVICES FOR THE FIRE ALARM SYSTEM SHALL BE LISTED AS A PRODUCT OF A SINGLE FIRE ALARM SYSTEM MANUFACTURER UNDER THE APPROPRIATE CATEGORY BY UNDERWRITERS LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL. 6. SPLICING OF CONDUCTORS ARE NOT ALLOWED INSIDE THE FACP. 7. VISUAL OR AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED AT 80" TO 96" AFF TO THE BOTTOM OF THE DEVICE PER NFPA 72. 8. AUDIBLE DEVICES SHALL BE MOUNTED AT A MINIMUM OF 90" AFF TO TOP OF DEVICE AND NO MORE THAN 6" FROM TOP OF DEVICE TO CEILING PER NFPA 72. 9. MANUAL PULL STATION SHALL NOT BE LESS THAN 3'-6" AND NOT MORE THAN 4'-6" FROM OPERABLE PART OF DEVICE TO FINISHED FLOOR PER NFPA 72. 10. SMOKE DETECTORS SHALL BE LOCATED AT MAXIMUM 15'-0" AWAY FROM WALL AND 3'-0" AWAY FROM HVAC DUCT SUPPLY DIFFUSER. 11. ALL FIRE ALARM PULL STATIONS SHALL BE LOCATED WITHIN 5'-0" OF EXIT DOORS. 12. AUDIBLE ALARM SHALL PRODUCE A SOUND THAT EXCEEDS THE PREVAILING EQUIVALENT SOUND LEVEL IN THE ROOM OR SPACE BY AT LEAST 15 dBA OR EXCEEDS ANY MAXIMUM SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dBA, WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 115 dBA. CONTRACTOR SHALL ADJUST POWER TAPS AND/OR PROVIDE ADDITIONAL MASS NOTIFICATION SPEAKERS AS NECESSARY TO MEET THIS REQUIREMENT. 13. PROVIDE CONDUCTOR INTEGRITY MONITORING FOR ALL NOTIFICATIONS DEVICES. 14. PROVIDE SURGE PROTECTION FOR THE FIRE ALARM CONTROL PANEL AND INSTALLED IN ACCORDANCE WITH NFPA 70 & 72. INSTALL SURGE PROTECTION IN A 6" SQ. JUNCTION BOX. PROVIDE LOW VOLTAGE SURGE PROTECTION FOR ALL FIRE ALARM SIGNALS WIRING ENTERING OR LEAVING THE BUILDING. 15. ALL NEW FIRE ALARM DEVICES MAY BE ADJUSTED TO SUIT FIELD CONDITIONS. �Q �p ap Y uj p0 r a 00 U. U. v� z 0 a. w 0 U N O N 0 ITH CORPORATION 10450 BLOOMFIELD HILLS DRIVE SEFFNER, FLORIDA 33584 PHONE: 813.312.3070 FL CA: #32733 TO THE BEST OF MY KNOWLEDGE, THE SPECIFICATIONS AND PLANS SHOWN HEREIN COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES IN EFFECT AT THIS TIME. THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THE EXCLUSIVE PROPERTY OF ITH CORPORATION, AND IS NOT TO BE COPIED OR USED IN ANY WAY WITHOUT THE EXPRESS WRITTEN CONSENT OF ITH CORPORATION. AND MUST BE RETURNED UPON REQUEST. THIS DRAWING IS NOT FOR GENERAL USE OR PUBLICATION, ALL RIGHTS RESERVED. U Z W LO W U) W m M O U 0 CO vi W O w 0 IJ o U) Q ~ J LL O? W cD mCO LL H CL m V Z /. a V 0 a � > GO t/� m LL J °z -j _ _J OC Q . _ Q w } a W o IL _ W r-. W N LL M N IRVING HO, PE No.852 •* 8/ 1882021 ���• STATE OF •��� �i'A�••F4ORIDP•' �L+ IONALV FL PE: #85232 REVISIONS Q 1 2 3 4 5 6 JOB NO: 21034 DRAWN BY: ITH DESIGNED BY: ITH ISSUE DATE: 06-22-21 SHEET TITLE: FIRE ALARM SYMBOL LEGEND & NOTES SHEET NUMBER FA-1 GENERAL NOTES: Lab / Blood FIRE ALARM SYSTEM PLAN 0 1 2 3 4 5 10 15 FEET SCALE: 1 /8" = V-0" 1. COORDINATE IN FIELD EXACT LOCATION AND QUANTITIES OF TAMPER AND FLOW SWITCHES. PROVIDE MONITORING MODULES FOR EACH DEVICES. 2. ALL FIRE ALARM DEVICES MAY BE ADJUSTED TO SUIT FIELD CONDITIONS. 3. ALL STROBE DEVICES SHALL BE LOCATED WITHIN 15'-0" AT THE END OF EACH HALLS. PROVIDE SYNCHRONIZED DEVICE FOR STROBES LOCATED IN THE SAME ROOM. 4. INSTALL SMOKE DETECTORS IN THE CENTER OF EACH ACOUSTICAL CEILING TILES WHERE APPLICABLE, 5. COORDINATE FINAL LOCATION OF FACP WITH OWNER. 120V POWER FOR THE FACP TO BE PROVIDED BY OTHERS. 6. VERIFY EXISTENCE AND EXTENT OF NEC —CLASSIFIED AREAS, IF ANY, AND PROVIDE APPROPRIATE RACEWAYS AND DEVICES IN THIS AREA. 7. ALL FIRE ALARM DEVICES ON EXTERIOR HVAC EQUIPMENT SHALL BE IN WEATHERPROOF ENCLOSURES. KEY NOTES:0 1. PROVIDE FLUSH MOUNTED KNOX BOX MODEL 3200. VERIFY COLOR WITH OWNER. PROVIDE OPTIONAL TAMPER ALERT CONNECTED TO INTRUSION DETECTION SYSTEM. 2. LOCATE SMOKE DETECTOR WITHIN 5'-0" OF FACP AND FAA. 3. PROVIDE DUCT MOUNTED SMOKE DETECTOR FOR ALL RTUs EXCEED 2,000 CFM FOR SUPPLY AND 15,000 CFM FOR RETURN. N z 0 0 a a U N O N a ITH CORPORATION 10450 BLOOMFIELD HILLS DRIVE SEFFNER, FLORIDA 33584 PHONE: 813.312.3070 FL CA: #32733 TO THE BEST OF MY KNOWLEDGE, THE SPECIFICATIONS AND PLANS SHOWN HEREIN COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES IN EFFECT AT THIS TIME. THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THE EXCLUSIVE PROPERTY OF ITH CORPORATION, AND IS NOT TO BE COPIED OR USED IN ANY WAY WITHOUT THE EXPRESS WRITTEN CONSENT OF ITH CORPORATION. AND MUST BE RETURNED UPON REQUEST. THIS DRAWING IS NOT FOR GENERAL USE OR PUBLICATION, ALL RIGHTS RESERVED. U Z y_ w > Ing w (0 o CO M U M w O 0a)w N_ LL O T— C/) U- rn w w < T- n 5 0 oo U) O LL r'- I— CL m V Z J Q Q Q � > 00 m LL w J � °z � = J J W a. Lea C4 a. W N Li m N IRVING HO, PE �c • S' 0.8523 8/ 18t021 �a %���• STATE OF •��� �i��••:C�ORIDP:•'•���` '��'�SS�ONA4�NC```• FL PE: #85232 REVISIONS Q 1 2 3 4 5 6 JOB NO: 21034 DRAWN BY: ITH DESIGNED BY: ITH ISSUE DATE: 06-22-21 SHEET TITLE: FIRE ALARM SYSTEM PLAN SHEET NUMBER FA-2 TELEPHONE 120V POWER SURGE SUPPRESSOR FIRE ALARM SYSTEM RISER DIAGRAM SCALE: NOT TO SCALE GENERAL NOTES: 1. PROVIDE SURGE PROTECTIVE DEVICE (SPD) FOR ALL FIRE ALARM CIRCUITS ENTERING AND LEAVING THE FACILITY. 2. THE SPD SHALL BE LISTED IN UL 1449 AND UL 1283, LATEST EDITION. THE SPD SHALL PROVIDE NORMAL SINE WAVE TRACKING, WITH CATEGORY Al RING WAVE SUPPRESSION (2000 VOLTS, 67 AMPERES, 82.2 DEGREE C [180 DEGREES F]) OF LESS THAN 50V FOR NOMINAL 120VAC. THE SPD SHALL PROVIDE INDEPENDENT, DISTINCT, AND DEDICATED CIRCUITRY FOR EACH POSSIBLE PROTECTION MODE (I.E., LINE —TO —NEUTRAL, LINE —TO —GROUND, NEUTRAL —TO —GROUND). SPD CIRCUITRY SHALL BE FULLY ENCAPSULATED FOR PROTECTION OF THE CIRCUITRY AND TO PROVIDE LONGER LIFE EXPECTANCY. 3. REFER TO THE "FIRE ALARM SYSTEM FUNCTIONAL MATRIX" ON THIS DRAWING FOR SPECIFIC NUMBER OF ALARM SIGNALS (E.G., FIRE, SUPERVISORY) TO BE TRANSMITTED TO THE 24 HOUR MONITORING SERVICE. 4. ENSURE THAT ALL FIRE ALARM MANUAL PULL STATIONS ARE IDENTICAL THROUGHOUT THE FACILITY. 5. NOT ALL FIRE ALARM DEVICES ARE INDICATED ON THE RISER DIAGRAM, REFER TO FLOOR PLANS FOR ADDITIONAL FIRE ALARM DEVICES. KEYED NOTES: DEDICATED CIRCUIT FOR 120V POWER. O FIRE ALARM STROBE AND/OR HORN MANUAL PULL STATION 00 I iD - d- L L FINISHED FLOOR ADA MOUNTING HEIGHT ELEVATION SCALE: NONE 0 Y a co N O N C rn Q 0 C .` a FIRE ALARM SEQUENCE OF OPERATIONS: 1. THE FIRE ALARM SHALL OPERATE AS FOLLOWS: 1.1. ACTIVATION OF A MANUAL PULL STATION SHALL: 1.1.1. IDENTIFY THE POINT/CONTACT ID ON THE FIRE ALARM CONTROL PANEL (FACP) AND SOUND THE ALARM AT THE FACP AND FIRE ALARM REMOTE ANNUNCIATOR PANEL (FAA). 1.1.2. ACTIVATE AUDIBLE HORNS AND VISUAL STROBES 1.1.3. SHUT DOWN VENTILATION SYSTEMS. 1.1.4. DEACTIVATE MAGNETIC DOOR LOCKS. 1.1.5. ACTIVATE AUDIBLE HORNS AND VISUAL STROBES. 1.1.6. TRANSMIT THE ALARM SIGNAL TO THE CENTRAL MONITORING STATION. 1.2. ACTIVATION OF A DUCT MOUNTED SMOKE DETECTOR, AN AREA SMOKE DETECTOR OR HEAT DETECTOR, OR SPRINKLER WATER —FLOW SWITCH SHALL CAUSE THE FOLLOWING: 1.2.1. IDENTIFY THE POINT/CONTACT ID AT THE FACP AND SOUND THE ALARM AT THE FACP AND FAA. 1.2.2. ACTIVATE AUDIBLE HORNS AND VISUAL STROBES. 1.2.3. SHUT DOWN VENTILATION SYSTEMS. 1.2.4. DEACTIVATE MAGNETIC DOOR LOCKS. 1.2.5. A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER —FLOW ALARM SHALL NOT BE ABLE TO BE SILENCED WHILE THE SPRINKLER SYSTEM IS FLOWING AT A RATE OF FLOW EQUAL TO A SINGLE HEAD 1.2.6. TRANSMIT THE ALARM SIGNAL TO THE CENTRAL MONITORING STATION. 1.3. ACTIVATION OF ANY SUPERVISORY CIRCUIT SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: 1.3.1. ANNUNCIATE AND DISPLAY THE SUPERVISORY CONDITION AT THE FACP AND FAA. 1.3.2, TRANSMIT THE SUPERVISORY CONDITION TO THE CENTRAL MONITORING STATION. 1.4. RECEIPT OF A TROUBLE SIGNAL AT THE FIRE ALARM CONTROL PANEL SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: 1.4.1. ANNUNCIATE AND DISPLAY THE TROUBLE CONDITION AT THE FACP AND FAA. 1.4.2. TRANSMIT THE TROUBLE CONDITION TO THE CENTRAL MONITORING STATION. FIRE ALARM SYSTEM SYSTEM OUTPUTS INPUT/OUTPUT MATRIX FACP ANNUNCIATION -nFIICATIIO REQUIRED FIRE SAFETY CONTROL h° v0 4 O`er � A(,)C =Q vAQ- v hQ JQ� h�P ILI) (�a Q' v � O� Z� p A V� O O p ?O �. A �C= Z� �° h -O Q� Ok v �v O O 00 Q 'T �O h O �� \�O �v� v Q Az J`' �� C� v <c,`9 LJ y�C9 �� _�! �J �vQ Q�� kF �° wC' ,Z 4 21�, O4 O �v A� tS *44 A. AZ 0 J� atiY J� JQ' JP Q' Q• JQ' 3 ��� ��� _�� �`'� �\� y�� pv h4 A.ZJQ. Q- Q Q Q VT*Q OA� SYSTEM INPUTS A B C D E F G H I J K L M N R S T U V W 1 FIRE ALARM SYSTEM AC POWER FAILURE • • • 1 2 FIRE ALARM SYSTEM LOW BATTERY • • • 2 3 OPEN CIRCUIT • • • 3 4 GROUND FAULT • • • 4 5 NOTIFICATION APPLIANCE CIRCUIT SHORT • • • 5 6 BUILDING MANUAL PULLSTATIONS • • • • • • • • 6 7 CORRIDOR SMOKE DETECTORS • • • • • • • • • • • • • 7 8 AREA SMOKE DETECTORS • • • • • • • • • • • • • 8 9 HVAC AIR DUCT SMOKE DETECTORS • Fo T • • • 9 10 AREA HEAT DETECTORS • • • • • • • • • • • • • 10 12 SPRINKLER TAMPER SWITCH • • • • 12 13 SPRINKLER WATER FLOW IN BUILDING • • • • • • • • • • 13 25 AREA OF REFUGE TWO-WAY COMMUNICATIONS STATUS • • • • 25 A B C D E F G H I J K L I M N R I S T U V W FIRE ALARM SYSTEM FUNCTIONAL MATRIX SCALE: NOT TO SCALE NOTES: 1. FIRE ALARM AND SUPERVISORY ALARM SIGNALS SHALL BE CLEARLY DIFFERENTIATED AT THE FIRE ALARM CONTROL PANEL. 2. ALL TRANSMITTAL SIGNAL SHALL PROVIDE DEVICE DESIGNATION AND LOCATION OF ADDRESSABLE DEVICE VIA POINT ID OR CONTACT ID. Z 0 0 a O U N N 0 ITH CORPORATION 10450 BLOOMFIELD HILLS DRIVE SEFFNER, FLORIDA 33584 PHONE: 813.312.3070 FL CA: #32733 TO THE BEST OF MY KNOWLEDGE, THE SPECIFICATIONS AND PLANS SHOWN HEREIN COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES IN EFFECT AT THIS TIME. THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THE EXCLUSIVE PROPERTY OF ITH CORPORATION, AND IS NOT TO BE COPIED OR USED IN ANY WAY WITHOUT THE EXPRESS WRITTEN CONSENT OF ITH CORPORATION. AND MUST BE RETURNED UPON REQUEST. THIS DRAWING IS NOT FOR GENERAL USE OR PUBLICATION, ALL RIGHTS RESERVED. Z W (o 0 W m ('M U oes M w O o a, CC J04 O O cl) (f) ILL. W a co 00 U) O !� a = LL. I•— CL m V Z v o a � > >0 mLL z >- J W oc Ww cm DC 00 a. N u. M N IRVING HO, PE ��Illnl��►,�� ING T/ o. 8523 ���• STATE OF •4�(/` �i F�ORIOP:•'•���� ,SIONALENG`�. 1111111" FL PE: #85232 REVISIONS Q 1 2 3 4 6 6 JOB NO: 21034 DRAWN BY: ITH DESIGNED BY: ITH ISSUE DATE: 06-22-21 SHEET TITLE: FIRE ALARM RISER DIAGRAM & MATRIX SHEET NUMBER FA=3 ERProject Name: Standby Hours: 124 notflMwaftwoAlarm Mins: 15 PSN-106 Installed By: Safety Margin: 20% Battery & Voltage Drop Designed By: Calculations Date: NAC Source Voltage: 120.4 Model #: PSN-106 Max Panel Current (amps): 10 Panel ID: I I User assumes all responsibility to ensure the quantities and Location: current draw values in this worksheet are accurate prior to submittal. 1 PSN-106 NAC Power Expander 0.075 0.075 0.075 0.075 Panel Standby: 0.075 Panel Alarm: 0.075 1 Class B 0.00000 1.82000 2 Class B 0.00000 1.82000 3 Class B 0.00000 1.82000 4 Class B 0.00000 1.82000 5 Class B 0.00000 1.53200 6 Class B 0,00000 0.23200 AUX 0,00000 0.00000 NAC Standby: 0.00000 NAC Alarm: 9.04400 Panel Current: 0.07500 0.07500 NAC Circuit Current: 0.00000 9.04400 Total Standby: 0.075000 Total Alarm: 9.11900 Standby Hours: 24 Alarm Mins: 5 AH Required: 1.80 AH Required: 0.76 Total Combined Standby & Alarm AmpHours Required: 2.56 Efficiency Factor: 209Z Required Battery AmpHours: 3.07 Battery AmpHours Provided: Honeyv" ®smumqr - 1. Control Panel IntelliKnight 6700 Battery Calculation Secondary Power Source Requirements Standby. •Alarm _4 • • . 6700 Control Panel 1 1xi 0.165000 1 = 1 0.165000 1 1 IxI 0.310000 = 0.310000 2. Addressable SLC Devices SK-PHOTO (-T) 4 x 0.000300 = 0.001200 4 x 0.000300 = 0,001200 SK-DUCT 4 x 0.000300 = 0.001200 4 x 0.000300 = 0.001200 SK-CONTROL 1 x 0.000375 = 0.000375 1 x 0.000375 = 0.000375 SK-MINIMON 10 x 0.000375 = 0.003750 10 x 0.000375 = 0.003750 SK-PULL-SA 5 x 0.000375 = 0,001875 5 x 0.000375 = 0.001875 SK-RELAY 1 9 1x1 0.000255 1=1 0.002295 1 9 IxI 0.000255 = 0.002295 3. SLC Accessory Bases 4. SLC Isolator Devices 5. Auxiliary Power Draw - SLC Devices 6. Accessory Modules 5860 1 x 0.020000 = 0.020000 1 x 0.025000 - 0.025000 7. Miscellaneous Devices 8. Notification Appliance Circuits NAC 1 1 0.000000 = 0.000000 = NAC 2 1 0.000000 = 0.000000 = Total Standby Load 0.196695 Total Alarm Load 0.346695 HOneyv " 13SURfr KNXM IntelliKni ht 6700 Battery Calculation Note 1: You are fully responsible for verifying these calculations. Note 2: Use the dropdowns in the yellow cells to enter values. Calculation in Total Sheet 24 Hours Standby Load Current 0.19570 Amps x 24 = 4.697 AH Required 5 Minutes Alarm Load Current (Amps) 0.34570 Amps x 1 0.084 J= 0.029 AH Total Current Load 4.726 AH Multiply by the Derating Factor 1.2 1 = x 1.20 Total Ampere Hours Required 5.67 AH Recommended Batteries: I BAT-1270 - 7AH Batteries Battery Check The batteries can be charged by the 6700 Charger. The batteries can be housed In the 6700 Cabinet. 0 Y a 00 N O N C rn 7 Q 0 ar C 0- DPON4MR NAC Circuit Configuration & Voltage Drop Class: I Class B Usage: Description: #12 Solid 2.01 0.000 1 1.820 1 20.40 16 7 System SensorSRLStrobe 0,000000 0.000000 0.116000 0.812000 7 System Sensor P2RL Hom/Strobe 0.144000 1.008000 No lookup function Total Standby:1 0.00000Total Alarm: 1 1.82000� Class: F Class B I Usage: I I Description: 7 System SensorSRLStrobe 0.000000 0.000000 0.116000 0.812000 7 System Sensor P2RL Horn/Strobe 0.144000 1.008000 (No lookup function Total Standby:0.00000Total Alarm: 1 1.820001 E)PCML NAC Circuit Configuration & Voltage Drop (cont'd) Class: Gass B-� Usage: Description: 1 #12 Sol i d 1 2.01 1 1 0.000 1 1.820 1 20.40 1 16 7 System SensorSRLStrobe 0.000000 0.000000 0.116000 0.812000 7 System Sensor P2RL Horn/Strobe 0.144000 1.008000 No lookup function Total Standby: 0.000001 Total Alarm: 1 1.82000� Class: Class B Usage: Description: #12 So I i d 1 2.01 1 1 0.000 1 1.820 1 20.40 1 16 7 System Sensor SRL Strobe 0.000000 0.000000 0.116000 0.812000 7 System Sensor P2RL Horn/Strobe 0.144000 1.008000 No lookup function Total Standby:1 0.000001 Total Alarm: 1 1.820001 P)POTTM V NAC Circuit Configuration & Voltage Drop (cont`d) Class: Classy B Usage: Description: #12 Solid 1 2.01 0.000 1 1.532 1 20.40 16 7 System SensorSRLStrobe 0.000000 0.000000 0.116000 0.812000 5 System Sensor P2RL Horn/Strobe 0.144000 0.720000 No looku function Total Standby:I 0.00000l Total Alarm: L_ 1.53200J Class: Class B Usage: Description: I #12Solid 1 2.01 1 1 0.000 1 0.232 1 20.40 1 16 2 System SensorSRLStrobe 0.000000 0.000000 0.116000 0.232000 0 System Sensor P2RL Hom/Strobe 0.114000 0.000000 No lookup function Total Standby: I 0.000W Total Alarm: L 0.232001 ITH CORPORATION 10450 BLOOMFIELD HILLS DRIVE SEFFNER, FLORIDA 33584 PHONE: 813.312.3070 FL CA: #32733 TO THE BEST OF MY KNOWLEDGE, THE SPECIFICATIONS AND PLANS SHOWN HEREIN COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES IN EFFECT AT THIS TIME. THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THE EXCLUSIVE PROPERTY OF ITH CORPORATION, AND IS NOT TO BE COPIED OR USED IN ANY WAY WITHOUT THE EXPRESS WRITTEN CONSENT OF ITH CORPORATION. AND MUST BE RETURNED UPON REQUEST. THIS DRAWING IS NOT FOR GENERAL USE OR PUBLICATION, ALL RIGHTS RESERVED. V Z LU Il' � � 0 W WO (f m M U 06 M w O C) LL � N Q Lf OU r- i- O F (J) L @ LU X W a T- to rn ao cn U- I- m Z J Q 0 a o� J LL M J � Z J = J_ Q J = Wce Q. W N = 0. W M W N N IRVING HO, PE ►I1II11ill/ \001 No.852 •'* 8/18'irA021 �0- STATE OF F4ORIOP•'-���`� FL PE: #85232 REVISIONS Q 1 2 3 4 5 6 JOB NO: 21034 DRAWN BY: ITH DESIGNED BY: ITH ISSUE DATE: 06-22-21 SHEET TITLE: FIRE ALARM DETAILS SHEET NUMBER FA=4