HomeMy WebLinkAbout37827 Eiland BlvdFIRE ALARM SYSTEMS - TECHNICAL SPECIFICATIONS
PART I GENERAL
1.1 SUMMARY
A. THIS SECTION COVERS THE FIRE ALARM SYSTEM INCLUDING INITIATING DEVICES, NOTIFICATION
APPLIANCES, CONTROLS, AND SUPERVISORY DEVICES.
B. WORK COVERED BY THIS SECTION INCLUDES THE FURNISHING OF LABOR, EQUIPMENT, AND MATERIALS
FOR INSTALLATION OF THE FIRE ALARM SYSTEM AS INDICATED ON THE DRAWINGS AND
SPECIFICATIONS.
C. THE FIRE ALARM SYSTEM SHALL CONSIST OF ALL NECESSARY HARDWARE EQUIPMENT AND SOFTWARE
PROGRAMMING TO PERFORM THE FOLLOWING FUNCTIONS:
1. FIRE ALARM AND DETECTION OPERATIONS.
2. CONTROL AND MONITORING OF FIRE SUPPRESSION SYSTEMS, AND OTHER EQUIPMENT AS INDICATED
IN THE DRAWINGS AND SPECIFICATIONS.
1.2 ACCEPTABLE MANUFACTURER
A. FIRE-LITES, OR EQUAL BY SIMPLEXGRINNEL, NOTIFIER, EDWARDS SYSTEM TECHNOLOGY, AND SILENT
KNIGHT.
1.3 RELATED DOCUMENT
A. THE SYSTEM AND ALL ASSOCIATED OPERATIONS SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
1. THE FLORIDA BUILDING CODE 2020.
2. FLORIDA FIRE PREVENTION CODE, 6TH EDITION.
3. NFPA 72 (2013), NATIONAL FIRE ALARM CODE.
4. NFPA 70, NATIONAL ELECTRICAL CODE (2017)
5. NFPA 101, LIFE SAFETY CODE (2015)
6. LOCAL JURISDICTIONAL ADOPTED CODES AND STANDARDS.
7. ADA ACCESSIBILITY GUIDELINES.
1.4 SYSTEM DESCRIPTION
A. THE SYSTEM AND ALL ASSOCIATED OPERATIONS SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
1. PROVIDE A COMPLETE, NON -CODED, ADDRESSABLE, MICROPROCESSOR -BASED FIRE ALARM SYSTEM
WITH INITIATING DEVICES, NOTIFICATION APPLIANCES, AND MONITORING AND CONTROL DEVICES. A
SYSTEM GENERAL ALARM SHALL INCLUDE:
a. INDICATION OF ALARM CONDITION AT THE FACP AND ANNUNCIATOR(S).
b. IDENTIFICATION OF THE DEVICE OR ZONE THAT IS THE SOURCE OF THE ALARM AT THE FACP.
c. UNLOCKING OF DESIGNATED DOORS.
d. NOTIFYING THE LOCAL FIRE DEPARTMENT.
e. INITIATION OF ELEVATOR RECALL IN ACCORDANCE WITH ASME/ANSI A17.3, WHEN SPECIFIED
DETECTORS OR SENSORS ARE ACTIVATED.
2. SUPERVISORY OPERATIONS: UPON ACTIVATION OF A SUPERVISORY DEVICE SUCH AS FIRE PUMP
POWER FAILURE, PUMP RUNNING, PHASE REVERSAL, LOW AIR PRESSURE SWITCH, AND TAMPER
SWITCHES, THE SYSTEM SHALL OPERATE AS FOLLOWS:
a. ACTIVATE THE SYSTEM SUPERVISORY SERVICE AUDIBLE SIGNAL AND ILLUMINATE THE LED AT THE
CONTROL UNIT.
b. RECORD THE EVENT IN THE FACP HISTORICAL LOG.
c. TRANSMISSION OF SUPERVISORY SIGNAL TO REMOTE CENTRAL STATION.
d. RESTORING THE CONDITION SHALL CAUSE THE SUPERVISORY LED TO CLEAR AND RESTORE THE
SYSTEM TO NORMAL.
3. IF THE "ALARM SILENCE" BUTTON IS PRESSED, ALL AUDIBLE AND VISIBLE ALARM SIGNALS SHALL
CEASE OPERATION.
a. THE "SYSTEM RESET" BUTTON SHALL BE USED TO RETURN THE SYSTEM TO ITS NORMAL STATE.
DISPLAY MESSAGES SHALL PROVIDE OPERATOR ASSURANCE OF THE SEQUENTIAL STEPS ("IN
PROGRESS", "RESET COMPLETED") AS THEY OCCUR. THE SYSTEM SHALL VERIFY ALL CIRCUITS OR
DEVICES ARE RESTORED PRIOR TO RESETTING THE SYSTEM TO AVOID THE POTENTIAL FOR
RE -ALARMING THE SYSTEM. THE DISPLAY MESSAGE SHALL INDICATE "ALARM PRESENT, SYSTEM
RESET ABORTED."
b. SHOULD AN ALARM CONDITION CONTINUE, THE SYSTEM WILL REMAIN IN AN ALARMED STATE.
4. THE "SYSTEM RESET" BUTTON SHALL BE USED TO RETURN THE SYSTEM TO ITS NORMAL STATE.
DISPLAY MESSAGES SHALL PROVIDE OPERATOR ASSURANCE OF THE SEQUENTIAL STEPS ("IN
PROGRESS", "RESET COMPLETED") AS THEY OCCUR. THE SYSTEM SHALL VERIFY ALL CIRCUITS OR
DEVICES ARE RESTORED PRIOR TO RESETTING THE SYSTEM TO AVOID THE POTENTIAL FOR
RE -ALARMING THE SYSTEM. THE DISPLAY MESSAGE SHALL INDICATE "ALARM PRESENT, SYSTEM
RESET ABORTED.
5. A MANUAL EVACUATION (DRILL) SWITCH SHALL BE PROVIDED TO OPERATE THE NOTIFICATION
APPLIANCES WITHOUT CAUSING OTHER CONTROL CIRCUITS TO BE ACTIVATED.
a. OPENING OF AN INITIATING OR NOTIFICATION APPLIANCE CIRCUIT WIRING SHALL CAUSE THE
AUDIBLE SIGNALS TO VOICE ANNOUNCE THE TROUBLE CONDITION.
b. POWER REQUIREMENTS.
- THE CONTROL UNIT SHALL RECEIVE AC POWER VIA A DEDICATED CIRCUIT BREAKER.
- THE SYSTEM SHALL BE PROVIDED WITH SUFFICIENT BATTERY CAPACITY TO OPERATE THE ENTIRE
SYSTEM UPON LOSS OF NORMAL AC POWER IN A NORMAL SUPERVISORY MODE FOR A PERIOD
OF 24 HOURS WITH15 MINUTES OF ALARM OPERATION AT THE END OF THIS PERIOD. THE
SYSTEM SHALL AUTOMATICALLY TRANSFER TO BATTERY STANDBY UPON POWER FAILURE. ALL
BATTERY CHARGING AND RECHARGING OPERATIONS SHALL BE AUTOMATIC.
1.5 QUALITY ASSURANCE
A. TINSTALLER QUALIFICATIONS: A FACTORY AUTHORIZED INSTALLER SHALL PERFORM THE WORK OF THIS
SECTION.
B. EACH AND ALL ITEMS OF THE FIRE ALARM SYSTEM SHALL BE LISTED AS A PRODUCT OF A SINGLE
FIRE ALARM SYSTEM MANUFACTURER UNDER THE APPROPRIATE CATEGORY BY UNDERWRITERS
LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL.
1.6 MAINTENANCE SERVICE
A. MAINTENANCE SERVICE CONTRACT: PROVIDE MAINTENANCE OF FIRE ALARM SYSTEMS AND EQUIPMENT
FOR A PERIOD OF 12 MONTHS, USING FACTORY -AUTHORIZED SERVICE REPRESENTATIVES.
B. BASIC SERVICES: SYSTEMATIC, ROUTINE MAINTENANCE VISITS ON A QUARTERLY BASIS AT TIMES
SCHEDULED WITH THE OWNER. IN ADDITION, RESPOND TO SERVICE CALLS WITHIN 24 HOURS OF
NOTIFICATION OF SYSTEM TROUBLE. ADJUST AND REPLACE DEFECTIVE PARTS AND COMPONENTS WITH
ORIGINAL MANUFACTURER'S REPLACEMENT PARTS, COMPONENTS, AND SUPPLIES.
C. ADDITIONAL SERVICES: PERFORM SERVICES WITHIN THE ABOVE 12-MONTH PERIOD NOT CLASSIFIED AS
ROUTINE MAINTENANCE OR AS WARRANTY WORK WHEN AUTHORIZED IN WRITING. COMPENSATION FOR
ADDITIONAL SERVICES MUST BE AGREED UPON IN WRITING PRIOR TO PERFORMING SERVICES.
FIRE ALARM SYSTEMS - TECHNICAL SPECIFICATIONS CONT.
SYMBOL
LEGEND
PART I) - EXECUTION
SYMBOL
DESCRIPTIONS
1. ALL WORK SHALL BE INSTALLED AS SHOWN, AND IN ACCORDANCE WITH NFPA 70, NFPA 72,
FACP
FIRE ALARM CONTROL
NFPA 101, FLORIDA FIRE PREVENTION CODE, 6TH EDITION, AND IN ACCORDANCE WITH THE
PANEL
MANUFACTURER'S DIAGRAMS AND RECOMMENDATIONS.
FAA
FIRE ALARM ANNUNCIATOR PANEL
2. CONTROL PANEL SHALL BE LOCATED BETWEEN 12 TO 78 INCHES AFF.
O
ADDRESSABLE PULL STATION
3. DETECTORS SHALL BE LOCATED AT LEAST 12 INCHES FROM ANY PART OF ANY LIGHTING
FIXTURES, 3 FEET FROM DIFFUSERS OF AIR HANDLING SYSTEMS AND CEILING FANS.
OD
DUCT MOUNTED SMOKE DETECTOR WITH RELAYS rOR AHU
SHUTDOWN. PROVIDE REMOTE WALL MOUNTED LEI) PILOT
4. NOTIFICATION APPLIANCES SHALL BE MOUNTED AT 80 INCHES AFF.
INDICATOR LIGHT AND SOUNDER WITH NAMEPLATE,
5. ACCEPTANCE TEST: DO NOT PERFORM ACCEPTANCE TESTING UNTIL THE CERTIFICATE OF
(4)
ADDRESSABLE HEAT DETECTOR
COMPLETION IS SUBMITTED TO THE OWNER. THE RECOMMENDED TESTS LISTED IN NFPA 72
SHALL BE CONSIDERED MANDATORY AND SHALL BE USED TO VERIFY THAT PREVIOUS
O
ADDRESSABLE SMOKE DETECTOR
DEFICIENCIES HAVE BEEN CORRECTED. COMPLETE AND SUBMIT THE NFPA 72, INSPECTION
AND TESTING FORM. THE TEST SHALL INCLUDE ALL REQUIREMENTS OF NFPA 72 AND THE
®
STROBE
FOLLOWING:
A. TEST OF EACH FUNCTION OF THE CONTROL PANEL.
HORN/STROBE
B. TEST OF EACH CIRCUIT IN BOTH TROUBLE AND NORMAL MODES.
®
MONITOR MODULE
C. TEXTS OF EACH ALARM INITIATING DEVICES IN BOTH NORMAL AND TROUBLE CONDITIONS.
®
RELAY
D. TESTS OF EACH CONTROL CIRCUIT AND DEVICE.
®
FLOW SWITCH
E. TESTS OF EACH ALARM NOTIFICATION APPLIANCE.
®
TAMPER SWITCH
F. TESTS OF THE BATTERY CHARGER AND BATTERIES.
G. COMPLETE OPERATIONAL TESTS UNDER EMERGENCY POWER SUPPLY.
H. VISUAL INSPECTION OF WIRING CONNECTIONS.
I. OPENING THE CIRCUIT AT EACH ALARM INITIATING DEVICE AND NOTIFICATION APPLIANCE
TO TEST THE WIRING SUPERVISORY FEATURE.
J. GROUND FAULT.
K. SHORT CIRCUIT FAULTS.
L. STRAY VOLTAGE.
GENERAL NOTES:
1. PROVIDE AN ADDRESABLE FIRE ALARM SYSTEM FOR THIS PROJECT. CONTRACT DRAWINGS
SHOW LAYOUTS BASED ON TYPICAL FIRE ALARM DEVICES/EQUIPMENT. THE CONTRACTOR
SHALL CHECK THE LAYOUT BASED ON ACTUAL DEVICES/EQUIPMENT TO BE PROVIDED AND
MAKE NECESSARY REVISIONS. PROVIDE ALL FIRE ALARM EQUIPMENT, DEVICES, WIRING,
CONDUIT, AND ASSOCIATED COMPONENTS FOR COMPLETE INSTALLATIONS.
2. ALL CONDUIT SHALL BE IN MINIMUM 1 /2" UNLESS NOTED OTHERWISE AND CONDUCTORS
SHALL BE COPPER. CONDUCTORS SHALL BE SIZED PER MANUFACTURER'S
RECOMMENDATIONS. ALL CONDUCTORS SHALL BE IN CONDUIT.
3. CONDUIT FOR THE FIRE ALARM SYSTEM SHALL BE COMPLETELY INDEPENDENT OF ALL OTHER
WIRING.
4. AUDIBLE DEVICES SHALL BE WIRED INDEPENDENTLY FROM VISUAL DEVICES. SILENCING OF
AUDIBLE DEVICES SHALL NOT DE -ACTIVATE FLASHING STROBES UNTIL ALARM CONDITION IS
CLEARED.
5. EQUIPMENT AND DEVICES FOR THE FIRE ALARM SYSTEM SHALL BE LISTED AS A PRODUCT
OF A SINGLE FIRE ALARM SYSTEM MANUFACTURER UNDER THE APPROPRIATE CATEGORY BY
UNDERWRITERS LABORATORIES, INC. (UL), AND SHALL BEAR THE "UL" LABEL.
6. SPLICING OF CONDUCTORS ARE NOT ALLOWED INSIDE THE FACP.
7. VISUAL OR AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED AT 80" TO 96" AFF TO THE
BOTTOM OF THE DEVICE PER NFPA 72.
8. AUDIBLE DEVICES SHALL BE MOUNTED AT A MINIMUM OF 90" AFF TO TOP OF DEVICE AND
NO MORE THAN 6" FROM TOP OF DEVICE TO CEILING PER NFPA 72.
9. MANUAL PULL STATION SHALL NOT BE LESS THAN 3'-6" AND NOT MORE THAN 4'-6" FROM
OPERABLE PART OF DEVICE TO FINISHED FLOOR PER NFPA 72.
10. SMOKE DETECTORS SHALL BE LOCATED AT MAXIMUM 15'-0" AWAY FROM WALL AND 3'-0"
AWAY FROM HVAC DUCT SUPPLY DIFFUSER.
11. ALL FIRE ALARM PULL STATIONS SHALL BE LOCATED WITHIN 5'-0" OF EXIT DOORS.
12. AUDIBLE ALARM SHALL PRODUCE A SOUND THAT EXCEEDS THE PREVAILING EQUIVALENT
SOUND LEVEL IN THE ROOM OR SPACE BY AT LEAST 15 dBA OR EXCEEDS ANY MAXIMUM
SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dBA, WHICHEVER IS LOUDER.
SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 115 dBA. CONTRACTOR SHALL
ADJUST POWER TAPS AND/OR PROVIDE ADDITIONAL MASS NOTIFICATION SPEAKERS AS
NECESSARY TO MEET THIS REQUIREMENT.
13. PROVIDE CONDUCTOR INTEGRITY MONITORING FOR ALL NOTIFICATIONS DEVICES.
14. PROVIDE SURGE PROTECTION FOR THE FIRE ALARM CONTROL PANEL AND INSTALLED IN
ACCORDANCE WITH NFPA 70 & 72. INSTALL SURGE PROTECTION IN A 6" SQ. JUNCTION
BOX. PROVIDE LOW VOLTAGE SURGE PROTECTION FOR ALL FIRE ALARM SIGNALS WIRING
ENTERING OR LEAVING THE BUILDING.
15. ALL NEW FIRE ALARM DEVICES MAY BE ADJUSTED TO SUIT FIELD CONDITIONS.
�Q
�p
ap
Y uj
p0
r
a
00
U.
U.
v�
z
0
a.
w
0
U
N
O
N
0
ITH CORPORATION
10450 BLOOMFIELD HILLS DRIVE
SEFFNER, FLORIDA 33584
PHONE: 813.312.3070
FL CA: #32733
TO THE BEST OF MY KNOWLEDGE,
THE SPECIFICATIONS AND PLANS
SHOWN HEREIN COMPLY WITH THE
APPLICABLE MINIMUM BUILDING
CODES IN EFFECT AT THIS TIME.
THIS DRAWING AND ALL
INFORMATION CONTAINED HEREIN
IS THE EXCLUSIVE PROPERTY OF
ITH CORPORATION, AND IS NOT TO
BE COPIED OR USED IN ANY WAY
WITHOUT THE EXPRESS WRITTEN
CONSENT OF ITH CORPORATION.
AND MUST BE RETURNED UPON
REQUEST. THIS DRAWING IS NOT
FOR GENERAL USE OR
PUBLICATION, ALL RIGHTS
RESERVED.
U
Z
W
LO
W U)
W m M O
U
0 CO vi
W O w
0
IJ o U)
Q ~ J
LL O?
W cD
mCO
LL H CL m
V
Z
/. a
V 0
a �
> GO
t/� m LL
J °z -j
_ _J
OC Q . _
Q w }
a W o IL
_
W r-. W
N LL M N
IRVING HO, PE
No.852 •*
8/ 1882021
���• STATE OF •���
�i'A�••F4ORIDP•' �L+
IONALV
FL PE: #85232
REVISIONS Q
1
2
3
4
5
6
JOB NO: 21034
DRAWN BY: ITH
DESIGNED BY: ITH
ISSUE DATE: 06-22-21
SHEET TITLE:
FIRE ALARM
SYMBOL LEGEND
& NOTES
SHEET NUMBER
FA-1
GENERAL NOTES:
Lab / Blood
FIRE ALARM SYSTEM PLAN
0 1 2 3 4 5 10 15
FEET
SCALE: 1 /8" = V-0"
1. COORDINATE IN FIELD EXACT LOCATION AND QUANTITIES OF
TAMPER AND FLOW SWITCHES. PROVIDE MONITORING
MODULES FOR EACH DEVICES.
2. ALL FIRE ALARM DEVICES MAY BE ADJUSTED TO SUIT FIELD
CONDITIONS.
3. ALL STROBE DEVICES SHALL BE LOCATED WITHIN 15'-0" AT
THE END OF EACH HALLS. PROVIDE SYNCHRONIZED DEVICE
FOR STROBES LOCATED IN THE SAME ROOM.
4. INSTALL SMOKE DETECTORS IN THE CENTER OF EACH
ACOUSTICAL CEILING TILES WHERE APPLICABLE,
5. COORDINATE FINAL LOCATION OF FACP WITH OWNER. 120V
POWER FOR THE FACP TO BE PROVIDED BY OTHERS.
6. VERIFY EXISTENCE AND EXTENT OF NEC —CLASSIFIED AREAS,
IF ANY, AND PROVIDE APPROPRIATE RACEWAYS AND DEVICES
IN THIS AREA.
7. ALL FIRE ALARM DEVICES ON EXTERIOR HVAC EQUIPMENT
SHALL BE IN WEATHERPROOF ENCLOSURES.
KEY NOTES:0
1. PROVIDE
FLUSH
MOUNTED KNOX
BOX MODEL 3200. VERIFY
COLOR WITH OWNER. PROVIDE OPTIONAL TAMPER ALERT
CONNECTED TO
INTRUSION DETECTION
SYSTEM.
2. LOCATE
SMOKE
DETECTOR WITHIN
5'-0" OF FACP AND FAA.
3. PROVIDE
DUCT
MOUNTED SMOKE
DETECTOR FOR ALL RTUs
EXCEED
2,000
CFM FOR SUPPLY
AND 15,000 CFM FOR
RETURN.
N
z
0
0
a
a
U
N
O
N
a
ITH CORPORATION
10450 BLOOMFIELD HILLS DRIVE
SEFFNER, FLORIDA 33584
PHONE: 813.312.3070
FL CA: #32733
TO THE BEST OF MY KNOWLEDGE,
THE SPECIFICATIONS AND PLANS
SHOWN HEREIN COMPLY WITH THE
APPLICABLE MINIMUM BUILDING
CODES IN EFFECT AT THIS TIME.
THIS DRAWING AND ALL
INFORMATION CONTAINED HEREIN
IS THE EXCLUSIVE PROPERTY OF
ITH CORPORATION, AND IS NOT TO
BE COPIED OR USED IN ANY WAY
WITHOUT THE EXPRESS WRITTEN
CONSENT OF ITH CORPORATION.
AND MUST BE RETURNED UPON
REQUEST. THIS DRAWING IS NOT
FOR GENERAL USE OR
PUBLICATION, ALL RIGHTS
RESERVED.
U
Z
y_ w
>
Ing
w (0 o
CO M U
M
w O 0a)w
N_
LL O T—
C/) U- rn
w w < T- n
5 0 oo U)
O
LL r'- I— CL m
V
Z
J Q
Q
Q �
> 00
m LL
w
J � °z �
= J
J W
a. Lea C4 a.
W
N Li m N
IRVING HO, PE
�c • S'
0.8523
8/ 18t021 �a
%���• STATE OF •���
�i��••:C�ORIDP:•'•���`
'��'�SS�ONA4�NC```•
FL PE: #85232
REVISIONS Q
1
2
3
4
5
6
JOB NO: 21034
DRAWN BY: ITH
DESIGNED BY: ITH
ISSUE DATE: 06-22-21
SHEET TITLE:
FIRE ALARM
SYSTEM PLAN
SHEET NUMBER
FA-2
TELEPHONE
120V
POWER
SURGE SUPPRESSOR
FIRE ALARM SYSTEM RISER DIAGRAM
SCALE: NOT TO SCALE
GENERAL NOTES:
1. PROVIDE SURGE PROTECTIVE DEVICE (SPD) FOR ALL FIRE ALARM CIRCUITS ENTERING AND LEAVING THE
FACILITY.
2. THE SPD SHALL BE LISTED IN UL 1449 AND UL 1283, LATEST EDITION. THE SPD SHALL PROVIDE
NORMAL SINE WAVE TRACKING, WITH CATEGORY Al RING WAVE SUPPRESSION (2000 VOLTS, 67
AMPERES, 82.2 DEGREE C [180 DEGREES F]) OF LESS THAN 50V FOR NOMINAL 120VAC. THE SPD
SHALL PROVIDE INDEPENDENT, DISTINCT, AND DEDICATED CIRCUITRY FOR EACH POSSIBLE PROTECTION
MODE (I.E., LINE —TO —NEUTRAL, LINE —TO —GROUND, NEUTRAL —TO —GROUND). SPD CIRCUITRY SHALL BE
FULLY ENCAPSULATED FOR PROTECTION OF THE CIRCUITRY AND TO PROVIDE LONGER LIFE
EXPECTANCY.
3. REFER TO THE "FIRE ALARM SYSTEM FUNCTIONAL MATRIX" ON THIS DRAWING FOR SPECIFIC NUMBER
OF ALARM SIGNALS (E.G., FIRE, SUPERVISORY) TO BE TRANSMITTED TO THE 24 HOUR MONITORING
SERVICE.
4. ENSURE THAT ALL FIRE ALARM MANUAL PULL STATIONS ARE IDENTICAL THROUGHOUT THE FACILITY.
5. NOT ALL FIRE ALARM DEVICES ARE INDICATED ON THE RISER DIAGRAM, REFER TO FLOOR PLANS FOR
ADDITIONAL FIRE ALARM DEVICES.
KEYED NOTES:
DEDICATED CIRCUIT FOR 120V POWER.
O FIRE ALARM STROBE
AND/OR HORN
MANUAL PULL STATION
00
I
iD -
d-
L L FINISHED FLOOR
ADA MOUNTING HEIGHT ELEVATION
SCALE: NONE
0
Y
a
co
N
O
N
C
rn
Q
0
C
.`
a
FIRE ALARM SEQUENCE OF OPERATIONS:
1. THE FIRE ALARM SHALL OPERATE AS FOLLOWS:
1.1. ACTIVATION OF A MANUAL PULL STATION SHALL:
1.1.1. IDENTIFY THE POINT/CONTACT ID ON THE FIRE ALARM CONTROL PANEL (FACP) AND SOUND THE
ALARM AT THE FACP AND FIRE ALARM REMOTE ANNUNCIATOR PANEL (FAA).
1.1.2. ACTIVATE AUDIBLE HORNS AND VISUAL STROBES
1.1.3. SHUT DOWN VENTILATION SYSTEMS.
1.1.4. DEACTIVATE MAGNETIC DOOR LOCKS.
1.1.5. ACTIVATE AUDIBLE HORNS AND VISUAL STROBES.
1.1.6. TRANSMIT THE ALARM SIGNAL TO THE CENTRAL MONITORING STATION.
1.2. ACTIVATION OF A DUCT MOUNTED SMOKE DETECTOR, AN AREA SMOKE DETECTOR OR HEAT DETECTOR,
OR SPRINKLER WATER —FLOW SWITCH SHALL CAUSE THE FOLLOWING:
1.2.1. IDENTIFY THE POINT/CONTACT ID AT THE FACP AND SOUND THE ALARM AT THE FACP AND FAA.
1.2.2. ACTIVATE AUDIBLE HORNS AND VISUAL STROBES.
1.2.3. SHUT DOWN VENTILATION SYSTEMS.
1.2.4. DEACTIVATE MAGNETIC DOOR LOCKS.
1.2.5. A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER —FLOW ALARM SHALL NOT BE ABLE TO BE
SILENCED WHILE THE SPRINKLER SYSTEM IS FLOWING AT A RATE OF FLOW EQUAL TO A SINGLE HEAD
1.2.6. TRANSMIT THE ALARM SIGNAL TO THE CENTRAL MONITORING STATION.
1.3. ACTIVATION OF ANY SUPERVISORY CIRCUIT SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
1.3.1. ANNUNCIATE AND DISPLAY THE SUPERVISORY CONDITION AT THE FACP AND FAA.
1.3.2, TRANSMIT THE SUPERVISORY CONDITION TO THE CENTRAL MONITORING STATION.
1.4. RECEIPT OF A TROUBLE SIGNAL AT THE FIRE ALARM CONTROL PANEL SHALL CAUSE THE FOLLOWING
ACTIONS AND INDICATIONS:
1.4.1. ANNUNCIATE AND DISPLAY THE TROUBLE CONDITION AT THE FACP AND FAA.
1.4.2. TRANSMIT THE TROUBLE CONDITION TO THE CENTRAL MONITORING STATION.
FIRE ALARM SYSTEM SYSTEM OUTPUTS
INPUT/OUTPUT MATRIX FACP ANNUNCIATION -nFIICATIIO REQUIRED FIRE SAFETY CONTROL
h° v0
4 O`er �
A(,)C =Q vAQ- v hQ JQ�
h�P ILI) (�a
Q' v � O� Z� p A V� O O p ?O �. A
�C= Z� �° h -O Q� Ok v �v O O 00 Q 'T �O
h
O �� \�O �v� v Q Az J`' �� C� v <c,`9
LJ y�C9 �� _�! �J �vQ Q��
kF �° wC' ,Z 4 21�, O4 O �v A� tS
*44
A.
AZ 0
J� atiY J� JQ' JP Q' Q• JQ' 3 ��� ��� _�� �`'� �\� y�� pv h4 A.ZJQ. Q-
Q Q Q VT*Q OA�
SYSTEM INPUTS A B C D E F G H I J K L M N R S T U V W
1 FIRE ALARM SYSTEM AC POWER FAILURE • • • 1
2 FIRE ALARM SYSTEM LOW BATTERY • • • 2
3 OPEN CIRCUIT • • • 3
4 GROUND FAULT • • • 4
5 NOTIFICATION APPLIANCE CIRCUIT SHORT • • • 5
6
BUILDING MANUAL PULLSTATIONS
•
•
•
•
•
•
•
•
6
7
CORRIDOR SMOKE DETECTORS
•
•
•
•
•
•
•
•
•
•
•
•
•
7
8
AREA SMOKE DETECTORS
•
•
•
•
•
•
•
•
•
•
•
•
•
8
9
HVAC AIR DUCT SMOKE DETECTORS
•
Fo
T
•
•
•
9
10
AREA HEAT DETECTORS
•
•
•
•
•
•
•
•
•
•
•
•
•
10
12
SPRINKLER TAMPER SWITCH
•
•
•
•
12
13
SPRINKLER WATER FLOW IN BUILDING
•
•
•
•
•
•
•
•
•
•
13
25
AREA OF REFUGE TWO-WAY COMMUNICATIONS STATUS
•
•
•
•
25
A B C D E F G H I J K L I M N R I S T U V W
FIRE ALARM SYSTEM FUNCTIONAL MATRIX
SCALE: NOT TO SCALE
NOTES:
1. FIRE ALARM AND SUPERVISORY ALARM SIGNALS SHALL BE CLEARLY DIFFERENTIATED AT THE FIRE ALARM CONTROL PANEL.
2. ALL TRANSMITTAL SIGNAL SHALL PROVIDE DEVICE DESIGNATION AND LOCATION OF ADDRESSABLE DEVICE VIA POINT ID OR CONTACT ID.
Z
0
0
a
O
U
N
N
0
ITH CORPORATION
10450 BLOOMFIELD HILLS DRIVE
SEFFNER, FLORIDA 33584
PHONE: 813.312.3070
FL CA: #32733
TO THE BEST OF MY KNOWLEDGE,
THE SPECIFICATIONS AND PLANS
SHOWN HEREIN COMPLY WITH THE
APPLICABLE MINIMUM BUILDING
CODES IN EFFECT AT THIS TIME.
THIS DRAWING AND ALL
INFORMATION CONTAINED HEREIN
IS THE EXCLUSIVE PROPERTY OF
ITH CORPORATION, AND IS NOT TO
BE COPIED OR USED IN ANY WAY
WITHOUT THE EXPRESS WRITTEN
CONSENT OF ITH CORPORATION.
AND MUST BE RETURNED UPON
REQUEST. THIS DRAWING IS NOT
FOR GENERAL USE OR
PUBLICATION, ALL RIGHTS
RESERVED.
Z
W (o 0
W m ('M U
oes
M
w O o a,
CC J04
O O cl)
(f) ILL.
W a co
00 U)
O !� a =
LL. I•— CL m
V
Z
v o
a �
> >0
mLL
z
>- J W oc
Ww cm
DC 00 a.
N u. M N
IRVING HO, PE
��Illnl��►,��
ING T/
o. 8523
���• STATE OF •4�(/`
�i F�ORIOP:•'•����
,SIONALENG`�.
1111111"
FL PE: #85232
REVISIONS Q
1
2
3
4
6
6
JOB NO: 21034
DRAWN BY: ITH
DESIGNED BY: ITH
ISSUE DATE: 06-22-21
SHEET TITLE:
FIRE ALARM
RISER DIAGRAM
& MATRIX
SHEET NUMBER
FA=3
ERProject Name: Standby Hours: 124
notflMwaftwoAlarm Mins: 15
PSN-106 Installed By: Safety Margin: 20%
Battery & Voltage Drop Designed By:
Calculations Date: NAC Source Voltage: 120.4
Model #: PSN-106 Max Panel Current (amps): 10
Panel ID: I I User assumes all responsibility to ensure the quantities and
Location: current draw values in this worksheet are accurate prior to
submittal.
1 PSN-106 NAC Power Expander 0.075 0.075 0.075 0.075
Panel Standby: 0.075 Panel Alarm: 0.075
1
Class B
0.00000
1.82000
2
Class B
0.00000
1.82000
3
Class B
0.00000
1.82000
4
Class B
0.00000
1.82000
5
Class B
0.00000
1.53200
6
Class B
0,00000
0.23200
AUX
0,00000
0.00000
NAC Standby:
0.00000 NAC Alarm:
9.04400
Panel Current:
0.07500
0.07500
NAC Circuit Current:
0.00000
9.04400
Total Standby:
0.075000 Total Alarm:
9.11900
Standby Hours:
24 Alarm Mins:
5
AH Required:
1.80 AH Required:
0.76
Total Combined Standby
& Alarm AmpHours Required:
2.56
Efficiency Factor:
209Z
Required Battery AmpHours:
3.07
Battery AmpHours Provided:
Honeyv"
®smumqr
-
1. Control Panel
IntelliKnight 6700 Battery Calculation
Secondary Power Source Requirements
Standby. •Alarm
_4
• • .
6700 Control Panel
1
1xi 0.165000
1 = 1 0.165000
1 1 IxI 0.310000 =
0.310000
2. Addressable SLC Devices
SK-PHOTO (-T)
4
x
0.000300
=
0.001200
4
x
0.000300
=
0,001200
SK-DUCT
4
x
0.000300
=
0.001200
4
x
0.000300
=
0.001200
SK-CONTROL
1
x
0.000375
=
0.000375
1
x
0.000375
=
0.000375
SK-MINIMON
10
x
0.000375
=
0.003750
10
x
0.000375
=
0.003750
SK-PULL-SA
5
x
0.000375
=
0,001875
5
x
0.000375
=
0.001875
SK-RELAY
1 9
1x1
0.000255
1=1
0.002295
1 9
IxI
0.000255
=
0.002295
3. SLC Accessory Bases
4. SLC Isolator Devices
5. Auxiliary Power Draw - SLC Devices
6. Accessory Modules
5860
1
x 0.020000
= 0.020000
1 x 0.025000 -
0.025000
7. Miscellaneous Devices
8. Notification Appliance Circuits
NAC 1
1
0.000000
=
0.000000
=
NAC 2
1
0.000000
=
0.000000
=
Total Standby Load
0.196695
Total Alarm Load
0.346695
HOneyv "
13SURfr
KNXM
IntelliKni ht 6700 Battery Calculation
Note 1: You are fully responsible for verifying these calculations.
Note 2: Use the dropdowns in the yellow cells to enter values.
Calculation in Total Sheet
24 Hours
Standby Load Current
0.19570 Amps
x 24 = 4.697 AH
Required
5 Minutes
Alarm Load Current (Amps) 0.34570 Amps
x 1 0.084 J=
0.029 AH
Total Current Load
4.726 AH
Multiply by the Derating Factor 1.2 1 =
x 1.20
Total Ampere Hours Required
5.67 AH
Recommended Batteries: I BAT-1270 - 7AH Batteries
Battery Check
The batteries can be charged by the 6700 Charger.
The batteries can be housed In the 6700 Cabinet.
0
Y
a
00
N
O
N
C
rn
7
Q
0
ar
C
0-
DPON4MR
NAC Circuit Configuration & Voltage Drop
Class: I Class B Usage: Description:
#12 Solid 2.01 0.000 1 1.820 1 20.40 16
7
System SensorSRLStrobe
0,000000
0.000000
0.116000
0.812000
7
System Sensor P2RL Hom/Strobe
0.144000
1.008000
No lookup function
Total Standby:1 0.00000Total Alarm: 1 1.82000�
Class: F Class B I Usage: I I Description:
7
System SensorSRLStrobe
0.000000
0.000000
0.116000
0.812000
7
System Sensor P2RL Horn/Strobe
0.144000
1.008000
(No lookup function
Total Standby:0.00000Total Alarm: 1 1.820001
E)PCML
NAC Circuit Configuration & Voltage Drop (cont'd)
Class: Gass B-� Usage: Description:
1 #12 Sol i d 1 2.01 1 1 0.000 1 1.820 1 20.40 1 16
7
System SensorSRLStrobe
0.000000
0.000000
0.116000
0.812000
7
System Sensor P2RL Horn/Strobe
0.144000
1.008000
No lookup function
Total Standby: 0.000001 Total Alarm: 1 1.82000�
Class: Class B Usage: Description:
#12 So I i d 1 2.01 1 1 0.000 1 1.820 1 20.40 1 16
7
System Sensor SRL Strobe
0.000000
0.000000
0.116000
0.812000
7
System Sensor P2RL Horn/Strobe
0.144000
1.008000
No lookup function
Total Standby:1 0.000001 Total Alarm: 1 1.820001
P)POTTM
V
NAC Circuit Configuration & Voltage Drop (cont`d)
Class: Classy B Usage: Description:
#12 Solid 1 2.01 0.000 1 1.532 1 20.40 16
7
System SensorSRLStrobe
0.000000
0.000000
0.116000
0.812000
5
System Sensor P2RL Horn/Strobe
0.144000
0.720000
No looku function
Total Standby:I 0.00000l Total Alarm: L_ 1.53200J
Class: Class B Usage: Description:
I #12Solid 1 2.01 1 1 0.000 1 0.232 1 20.40 1 16
2
System SensorSRLStrobe
0.000000
0.000000
0.116000
0.232000
0
System Sensor P2RL Hom/Strobe
0.114000
0.000000
No lookup function
Total Standby: I 0.000W Total Alarm: L 0.232001
ITH CORPORATION
10450 BLOOMFIELD HILLS DRIVE
SEFFNER, FLORIDA 33584
PHONE: 813.312.3070
FL CA: #32733
TO THE BEST OF MY KNOWLEDGE,
THE SPECIFICATIONS AND PLANS
SHOWN HEREIN COMPLY WITH THE
APPLICABLE MINIMUM BUILDING
CODES IN EFFECT AT THIS TIME.
THIS DRAWING AND ALL
INFORMATION CONTAINED HEREIN
IS THE EXCLUSIVE PROPERTY OF
ITH CORPORATION, AND IS NOT TO
BE COPIED OR USED IN ANY WAY
WITHOUT THE EXPRESS WRITTEN
CONSENT OF ITH CORPORATION.
AND MUST BE RETURNED UPON
REQUEST. THIS DRAWING IS NOT
FOR GENERAL USE OR
PUBLICATION, ALL RIGHTS
RESERVED.
V
Z
LU
Il' �
� 0
W WO
(f m M U
06 M
w O C) LL
� N Q
Lf OU r- i-
O
F (J) L @
LU
X W a T- to
rn ao cn
U- I- m
Z
J Q
0
a
o�
J LL
M
J � Z J
= J_
Q J =
Wce
Q. W N =
0.
W M W
N N
IRVING HO, PE
►I1II11ill/
\001
No.852 •'*
8/18'irA021
�0- STATE OF
F4ORIOP•'-���`�
FL PE: #85232
REVISIONS Q
1
2
3
4
5
6
JOB NO: 21034
DRAWN BY: ITH
DESIGNED BY: ITH
ISSUE DATE: 06-22-21
SHEET TITLE:
FIRE ALARM
DETAILS
SHEET NUMBER
FA=4