HomeMy WebLinkAbout38108 15th AveRENOVATIONS FOR NEW LOCATION MEALS ON WHEELS PASCO COUNTRY GENERAL NOTES: THIS BUILDING HAS BEEN DESIGNEC TO CONFORM TO THE 2017 FLORIDA BUILDING CODE 6TH EDITION T L HANSON & ASSCCIA.TES INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL ENGINEERING COMPANY; HAS APPLIED "RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN OF THIS STRUCTURE. THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE FOLLOWING SUPERIMPOSED LOADS: FLOOR: LIVE LOAD - 50 P.S.F. DEAD LOAD - 10 P.S.F. ROOF: LIVE LOAD - 20 P.S.F. DEAD LOAD - 10 P.S.F. WIND: BUILDING IS DESIGNED TO CONFORM TO ASCE 7-10, CHAPTERS 26 THRU 31; PER 2017 FLORIDA BUILDING CODE 6TH ADDITION SECTION 1609 WIND DESIGN ASSUMPTIONS: BUILDING EXPOSURE - B BUILDING RISK CATEGORY - II MEAN ROOF HEIGHT 30' OR LESS HEIGHT & EXPOSURE ADJUSTMENT COEFFICIENT = 1.0 ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT = +/_ 0.18 WIND SPEED SHOWN AT THE BOTTOM RIGHT CORNER OF THIS SHEET SOIL BEARING & COMPACTION COMPONENT & CLADDING WIND LOADS ALL OTHER BUILDING ROOF OVERHANG COMPONENT ZONE LOADS LOADS 1 N/A +32.3/-35.3 2 -65.7 +32.3/-56.2 3 -110.6 +32.3/-89.0 4 N/A +35.3/-38.2 5 N/A +35.31-47.2 THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. (MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIE I°LE FOR VERIFYING THAT THE SOIL ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. T L HANSON & ASSOCIATES INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL ENGINEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE NOR PERFORMING ANY SOIL TESTING. SOIL TERMITE TREATMENT: TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE SHALL STATE "THE BUILDING F..-,!S RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. THE i REATMv ::NT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES." BUILDING DATA: USE AND OCCUPANCY: MIXED BUSINESS GROUP B 4117 SQ. FT. ASSEMBLEY A-2 FUTURE 2169 SQ. FT. TOTAL AREA 6286 SQ. FT. NO ADDITIONAL AREA ADDED TO BUILDING INTERIOR RENOVATIONS ONLY TYPE CONSTRUCTION: VB FIRE PROTECTION: NON SPRINKLED IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION, ABOVE DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR. THE SYSTEM MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL. INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION, BACKFILLING & COMPACTION ARE COMPLETE ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED (INCLUDING ANY BOXED OR FORMED AREAS) - BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN ADEQUATE SIZE & DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE INITIAL TREATMENT. A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT SHALL BE REQUIRED ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE BUILDING SIDEWALLS AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS. THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION FOR FUTURE TERMITE INFESTATIONS SAFETY GLAZING: THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308: (1) GLAZING IN SWINGING DOORS, -FIXED AND SLIDING PANELS OF SLIDING DOOR ASSEMBLIES. (2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS THAN 60 INCHES ABOVE THE DRAIN INLET. (3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR OR WALKING SURFACE. (4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS DESCRIBED IN ITEMS (2) AND (3) ABOVE. THAT MEETS ALL OF THE FOLLOWING CONDITIONS: A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQ. FT. B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR. C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR. D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE PLANE OF THE GLAZING. PLUMBING PEF2017 FLORIDA BUILDING CODE PLUMBING 6TH EDITION CHAPTER 4, TABLE 403.1. _- D E S I G N S I N C BUILDING DESIGNS 13821 U.S. HWY 98 BY PASS DADE CITY, FLORIDA 33523 OFFICE 352-523-2077 FAX 352-567-2070 38120 15TH AVE ZEPHYRHILLS, FLORIDA SITE LOCATION MAP JOB SITE 6TH EDITION FLORIDA FIRE PREVENTION 6TH EDITION 2017 FLORIDA BUILDING CODE 6TH EDITION 2017 FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017 FLORIDA ENERGY CONSERVATION CODE 6TH EDITION 2017 FLORIDA MECHANICAL CODE 6TH EDITION 2017 FLORIDA PLUMBING CODE 2017 NFPA 10 (STANDARD FOR PORTABLE FIRE EXTINGUISHERS) 2014 NATIONAL ELECTRICAL CODE (NFPA 70) CONTRACTOR TO PROVIDE TACTICAL SIGNS AS PER NFPA 1:14.14.1.3 CONTRACTOR TO PROVIDE SIGNS DESIGNATING TYPE OF ROOF CONSTRUCTION PER FAC 69A-3/012 (6) BUILDING HAS WOOD ROOF SYSTEM LIGHT FRAME CONSTRUCTION SIGN REQUIRED CONTRACTOR TO PROVIDE UL 1037 APPROVED ACCESS BOX PER NFPA 1:18.2.2.1 RESTROOM FLOORS TO BE A NON ABSORBENT MATERIAL RESTROOM WALLS TO BE A NON ABSORBENT MATERIAL MINIMUM 60" ABOVE FINISH FLOOR INTERIOR FINISHES TABLE 803.11 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY" SPRINKLERED' NONSPRINKLERED GROUP Inferior exit stairways and ramps. and exit passageways" ° Corridors and enclosure for exit access stairways and ramps Rooms and i enclosed I spaces` Interior exit stairways and rampsand eways, o passageways' Corridors and enclosure for exit access s mrp'says and ram s Rooms and enclosed spaces` A-1 & A-2 B ---Cq B C A Ad B° A-Y, A-4, A-> .a B, H. NI, R-I B C C A B C F C C C B C C H B B Cr A A B I -I B C C A B B I--2 B B B"' I A A B I-3 A Al C A A B I-4 B B B" ' A A B I R-2 C: C C B B C R-� C C C C C C s C C C B B C IJ No restrictions No restrictions j For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929m-. a. Class C interior finish materials shall be permitted for wainscotting or paneling of not more than 1,000 square feet of applied surface area in the grade lobby where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by Section 803.13:1. b. In other than Group 1-3 occupancies in buildings less that. three stories above made plane, Class B interior finish for nonsprinldered buildings and Class C interior finish for sprindlered bulldings.shall be permitted in interior exit stairways and ramps. c. Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions_ Where afire -resistance rating is required for structural elements, the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered enclosing spaces and the rooms or spaces on both sides shall be considered one. In determining the applicable requirements for rooms and enclosed space,, the specific occupancy thereof shall be the governing factor regardless of the group classification of the building or structure. d. Lobby areas in Group A-1. A-2 and A-3 occupancies shall not be less than Class B materials. e_ Clatis C interior finish materials shall be permitted in places ofassembly with an occupant load of 300 persons or less. f. For places of religious worship, wood used for ornamental purposes, trusses, paneling or chancel furnishing shall be permitted. g. Class B matc h. Class C inter i. Chrss C inter ; Class B naau to finished floor in corridors and exit access stairways and tamps. k. Finish mater L. Applies he .3.1.1 or 903.3.1.2. RYMAN CONSTRUCTION INC 36413 STR RD 54 ZEPHYRHILLS, FL 33541 OFFICE 813-782-0825 PLAN INDEX: SHEET B 1 : EXISTING BUILDING FLOOR PLAN SHEET B 2: DEMOLITION BUILDING FLOOR PLAN SHEET B 3: PROPOSED BUILDING FLOOR PLAN DOOR SCHEDULE CUT DOOR OPENING DETAIL INTERIOR WOOD WALL DETAIL WOOD FIRE WALL DETAIL SHEET E1 : EXISTING ELECTRICAL DRAWINGS SHEET E2 : PROPOSED ELECTRICAL DRAWINGS SHEET M1 : MECHANICAL DRAWINGS SHEET P1 : PLUMBING DRAWINGS �% 41k �'4a �;,3gQes3arAas&®���t4 A��g ftz Vol s per., ii $� T (352) 521-5540 T. L. H,4N&ON 4 ,4550CIATES/ INC;, CO141SULTING ENGINEERS EN&INEERING; 5U6INE88 NO. E55030 Post Office Box 1-728 Dade City, Florida 33526 THOMA5 L. HAN50N, PE 35654 zcy) z M 0 iz o LLo N z LL � z �� C7 7 U M a w xx v� pW W LL Z W C7 U1 ti N ::) m N m 'D 04 N Ln W 20 07 LL ti =iO T N 00 M T 129' 0" 12' 6" 14' 6" 28, 0" 28' 0" 14' 4" 12' 8"--------------------- O ctil U1 C Lou U 3'0"X6'8" 7111113'0"X6'8" 3'0"X6'8" 43'0"X �w Z� � Z W z� av i 0 EO = EO ~ wz� -4 � a� o CDU Q CD DO 0 T Q O - - 90 00 o 4' 0" 4' 0"� 5' 0" UJ ~ a� 16' 7" x 4' 0" 0 4, 0" X 17' 7'/" a o 0 g 0„ 7, 3„ 9, 8„ 0O Z �o \ in 0 o in '� U W co 3'0"X6'8" CV V' 0 90 di O 00 _ N X O o m `1 o N o 0 O LO 3'0"X6'8" CD 3'0"X6'8" o zo O N W CO X 0 90 8' 8" x 11, 11 " 22' 0" 9101, 5' 1 " 9' 7" 1' 10'/" 19' 2" 16' 9" M CD H o Q 3'0"X6'8" Z O 3'0"X6'8" 3'0"X6'8" U1 X i o W ao m X 0 ih O c0 0 0 X Lin LO o - in co (V OD 00 LL( E0 LL O N CV i O O r` 00 O Q O CM 3'0"X6'8" ~ m 5' 6" af <O T 0 c CM CV U o CZ ----------------------------------- ----------------------------------- T z � LO O M CV m co U��C) co �0L-0000 �frC/ci L� CID Z 00 M 0 U) U c) Z 2 LL - Qmal� o� 3'0"X6'8 A11111111113,0" 6'8" 11111 _ago 2 M W O CD 2' 8" 7, 2" 5' 8" 5' 8" 7, 2" 2' 8" Jib aw Yll �s 3'0"X6'8" �OJ 1, 4„ 7, 0„ 3' 8„ 9101, 9.0.. 5, 011 y� 5' 0" 9101, 9' 0" 3' 8" TO" 1' 4" Do DO 0o in Cn 071 li0 0 0 0 0 0 12' 0" 31' 0" ' 0" 41' 0" ' 0" 31' 0" 12' 0" z00000 �z Q Z) VOU Q 129' 0" 0 �0 �cvi)WO w EXISTING FLOOR PLAN 1/411 = 1' 0" z a- Q LL 0--j LL W L J W T — Z = N 0�00� QZ c� � O >Lli O to N Z J �t w w W v. ...... c go E. LjE° NS O.38654 a A'dIFL 33526 1 HERBY CER NS AND SPECIFICATIONS WERE PREPARED, DER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE 1 THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE FLORIDA BUILDING CODE 2017 6TH ADDITION AND ASCE 7-10 AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND FOR 139 MPH WIND ZONE RISK CATEGORY II EXPENSES (INCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE PROJECT. THE DESIGNER WILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF REPAIRS OR DELAY TO THE CONSTRUCTION ZU M N Lo Zi c"M 0 I --I O O cn J N >tn z L9 C7 U 04 cl _ wX zv� p p li W O �' Q dN Z Qo � � m N m a0 L(4 fy � N Lt) th w 2U G7 w IL �O N co CM tp 3,O"X6,8„ 3'O"X6'8" 3'0„X6,8„ 3'O"X6'8" 3'O„X6,8„ 3'p"X6'8" to co v o o I I r m W O o _� II o U w- mE� a z z ao 0o b ' ' _ _ 'U u `o N Do DO (D 1 1 O O zo Z Tf O Z 0D �o ' ' °D „ 90 v O Lu l� ° U Q bo io m '' iD 4 0 4' 0 5 0 11, 101, Z m 0 16'7" o 0 0 wZ x 4' p�� o 0 4' 0" x 1 T 7%„ 9' 0„ T 3,, 9' 8„ I I - o a M Z I L 1 1 REMOVE WATER HEATER, RUN LINES I ~ Q TO EXTERIOR OF BUILDING TO THE I I i I NEW INSTANT PROPANE WATER Eo iD U ° HEATER I ?< m I I o I I I o X _ CD m Eo REMOVE DRYWALL AT THIS WALL AND o , , N REMOVE WALL AND PATCH , , I r 11 v CEILING ABOVE TO EXPOSE DAMAGE M CEILING AND WALL FACESING I ° I ca AND REPAIR AS NEEDED AS NEEDED 0 Lo 3'0"X6'8„ 3'0"X6'8" I I I I - I J LD 0 ' ' REMOVE SINK AND COUNTER TOP 0 p REMOVE SLIDING DOOR AND r - `- I I FRAME FILL OPENING. POSSIBLE cD REMOVE WALL AT OTHER SIDE to TO BE VERIFIED IN FIELD C`7 1 1 1 1 I I 8' 8" x 11' 11" 22' 0" 9' 0" 5' 1" 9' 7" ' '1' 10%2' 19' 2" ' ' 16' 9" 1 1 1 1 I CD 1 1 1 1 I ! I 1 1 1 1 1 1 3'0"X618" I I Q I I i a 3'0"X6`8" 3'O"X6'8" �� REMOVE EXISTING DOOR AND CREATE OPENING TO w REMOVE WALL AND PATCH \,�� o LINE UP WITH NEW DOOR 90 CEILING AND WALL FACESING TO EXTERIOR Q X REMOVE EXISTING DOORS AS NEEDED Z o AND CREATE OPENING TO I I I I 0 m NEW KITCHEN I I I I to II I I w 90 X II I I ih co N II I I �' I I CUT OPENING IN MASONRY DEMOLITION NOTES: I I WALL FOR NEW DOOR UNIT I I 0 1. REMOVE ALL CARPET FLOG="ING. 2. REMOVE ALL EXISTING SURFACE MOUNT LIGHTS AND REPLACE WITH LED RECESSED CAN LIGHT 3. CUT SLAB AS NEEDED TO INSTALL NEW PLUMBING COMPACT AND TERMITE TREAT DISTURBED SOIL COVER WITH 6 MILL VISQUEEN AND PATCH FLOOR ~ CONVERT THIS WALL TO 2 HOUR tO FIRE RATED WALL FROM FLOOR WITH MINIMUM 2500 PSI CONCRETE O TO BOTTOM OF ROOF DECK - ~ u308 3'0"X6'8" ti ElfN N 5' 6„ N o �Ny m I LL co N Q iii z � Q m 0 CD ----------------------------------- OD ----------------------------------- CV U o, Z aD Z Lo CID x _O M CV REMOVE EXISTING DOOR AND INSTALL o 00 NEW 3'0"X6'8" 90 MINUTE FIRE RATED M ()Lr) J OI WOOD DOOR WITH 90 MINUTE HOLLOW D LL 04 METAL FRAME. DOOR TO HAVE DOOR 0 00 CLOSURE. ADA LEVER KEY LOCK AND (q SILL 9'O"X6'8" TO" 6'8" J _M O co = 00 W U Q�dIWL co W O 3'O"X6'8" �- N ti0 0, sti .y�7Fr _ OJ O O O O O O O O O Q- DEMOLITION PLAN 1 /411 = 1' 0" z0� 0 E-- �z Q D v0 Q O U0 J �u w0 z0-Qu o-3�- u-wL0 zw�� = CV o r-- O 0O cn N Z Q w w L • T. A ON P.E. I•'ICEhZE NO. 38654 P.`c, DAB', FL 33526 • • I H TF I I NS AND SPECIFICATIONS WER • � is )ER MY DIRECT SUPERVISION ARE IN �� PTER 16, SECTION 1609 OF THE B 2 THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE FLORIDA �I 114 ,0 17 6TH ADDITION AND ASCE 7-10 AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND FOR 139 MPH WIND ZONE RISK CATEGORY II EXPENSES (INCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE PROJECT. THE DESIGNER WILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF REPAIRS OR DELAY TO THE CONSTRUCTION UL Product iQ' BXUVU308 - FIRE -RESISTANCE RATINGS - ANSI/U!_ 263 Design/System/ConstrucLion/Assembly Usage Disclaimer • Authorities Having Jurisdictionshould be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials. • Authorities Having Jurisdiction should be consulted before construction. • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requ'Irements. The published information cannot always address every construL-tion nuance encountered in the field. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. • Only products which bear UL's Mark are considered Certified. BXUV -'Fire Resistance Ratings - ANSI/UL 263 Certified for United States BXUV7 - Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada "See General Information forFire-resistanceRatings - ANSI/UL 263 Certified for United States Design Criteria and Allowable Variances See General Information for Fire Resistance Ratings - CAN/ULC-S101 !Certified for Canada Design Criteria and Allowable Variances Design No. U308 October 10, 2017 Bearing Wall Rating — 2 Hr This design was evaluated using a load design method other than the Limit States Design Method (e.g., Working Stress Design Method)..For ,jurisdictions employing the Limit States Design Method, such as Canada, a load restriction factor shall be used — See Guide BXUV or BXUV? it Indicates such products shall bear the UL or cUL Certification Mark for d s a jurisdictions employing the UL or cUL Certification (such as Canada), respectively. , r �l 1 . . t 3 At J`� �_� • .{ .., —. 5*•,,.:ref � Alternate Construction 1. Wood Studs — Nom 2 by 4 in. spaced 16 in. OC, effectively cross -braced. 2. Gypsum Board* —5/8 in, thick, with square or tapered edges, applied vertically or horizontally with vertical joints centered over studs. Horizontal joints need not be backed by framing. Base layer fastened to studs and plates with 1-7/8 in. long 6d cement coated nails or 1-7/8 in. tong Type S or W screws spaced 6 in. OC. Face layer fastened to studs and plates: over base layer with 2-3/8 in. long-6d cement coated nails or 2-1/4 in. long Type S or W screws spaced 8 in. OC. Face layer joints offset min 12 in. from base Layer joints_ When used in widths other than 48 in., gypsum panels to be installed horizontally. CGC INC — Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SIX, SHK ULX, USGX, WRC or WRX (Joint tape and compound, item 3, optional for use with Type USG)O, UNITED STATES GYPSUM CO — Types AR, C, FRX-G, IP-AR, IP-X1; IP-X2, [PC -AR, SCX, SHX, ULIX, ULX; WRC, WRX, USGX (Joint tape and compound, Item 3, optional for use with Type USGX) PROPOSED FLOOR PLAN 1/411 = 1' 0" USG BORAL DRYWALL SFZ LLC — Types C, SIX, USGX (Joint tape and compound, Item 3, optional for use with Type USG)O USG MEXICO S A DE C V —Types AR; C, IP-AR, fP-X1, IP-X2, IPC-AR, SCX, SHX, ULX, USGX, WRC or WRX (Joint tape and compound, Item 3, optional for use with Type USG)(). 2a. Gypsum Board* —As an Alternate to Item 2-5/8 in. thick applied either horizontally or vertically. Base layer fastened to framing with 1-1/4 in. long Type W coarse thread gypsum panel steel screws spaced a max 8 in. OC, with last screw 1 in. from edge of board. Face layer fastened to framing with 1-7/8 in.. long Type W coarse thread gypsum panel steel screws spaced a max 8 in. OC with last screw 1 in, from edge of board. Face layer joints offset min 12 in. from base Iayerjoints. When used in widths other than 48 in., gypsum board to be installed horizontally. AMERICAN GYPSUM CO —Types AGX-1, M-Glass, AG-C, LightROC 3, Joints — Exposed joints of gypsum boards covered with joint compound and paper tape._Joint compound and paper tape maybe omitted when square edge boards are used. As an alternate, nom 3/32 in. thick gypsum veneer plaster may be applied to the entire surface of Classified veneer baseboard with the joints reinforced with paper tape. 4. Batts and Blankets* — Min 3 in. thick; mineral wool baits, friction fit between studs. THERMAFIBER INC —Type SAFE, SAFE FF ROCKWOOL — Type SAFEnSOUND e ntitious Backer Units* —12 or in. this installed vertically or horizontal{ with vertical joints 5. C me t 518 k, tal 1 y y } centered over studs. Fastened to studs and plates with corrosion resistant 2-1/4 in. long chamfered, ribbed wafer head screws with a minimum head diameter of A00 inch spaced 8 in. OC. Joints offset min 12 in. from base layer joints. UNITED STATES GYPSUM CO — Type DCE 6. Joints —Joints of cementitious backer units covered with glass fiber mesh tape and latex modified portland cement mortar or basecoat, or Type I organic adhesive. 7. Vapor Retarder, Water Barrier or Weather Resistive Barrier —(Optional, not shown) —As required. ' Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively, Last Updated on 2017-10-10 The appearance of a company's name or product in this database does not itself assure that products so identified have been manufactured under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow -Up Service Always look for the Mark on the product. GREASE TRAP 150 LEIS CAPACITY 75 GPM CONTRACTOR TO VERIFY THE LOCATION IN THE FIELD. NEW 5 TON CONDENSER UNIT III /�uW//i1 I II FOR KITCHEN AREA ONLY EXISTING BOTTOM CORD OF TRUSS ATTACHED WALL AS NEEDED SINGLE 2X4 #2 SPRUCI 2X4 #2 SPRUCE STUC 1/2" GYPSUM WALL B WITH #8X1 5/8" DRYV EACH SIDE OF WALL SINGLE 2X4 P.T. BC U11 JMIVI� MUM LC V Cr\ r-r\I V^%, I LVlrr\. 1 II14IJ1 I 1 %J UL_ %.11 IlJJL1Y BY OWNER 3'0"" HOLLOW CORE LUAN DOOR WITH PAINT GRADE WOOD JAMB ® ADA LEVER PASSAGE LOCK. FINISH TO BE CHOSEN BY OWNER VERIFY HEIGHT OF DOOR IN FIELD BASED ON AIR HANDLER SHELF AND RETURN AIR 3'0"X6'8" 90 MINUTE FIRE RATED DOOR AND FRAME ADA LEVER PASSAGE LOCK. DOOR CLOSURE. LOW BUMPER SILL. FINISH TO BE CHOSEN BY OWNER 60"X68" FLUSH HOLLOW METAL DOOR AND STEEL FRAME. ASTRICAL ON ONE DOOR WITH EDGE BOLTS. ADA LEVER KEY LOCK OPPOSITE DOOR. LOW BUMPER SILL. 3 HINGES EACH DOOR FINISH TO BE CHOSEN BY OWNER INTERIOR FRAME WALL DETAIL NOT TO SCALE a� 3" GABLE END TRUSS ABOVE THIS WALL T� I CUT NOTCH IN WALL AT LOCATION AND INSERT A 1/4"X4"X6" STEEL ANGLE IN NOTCH. SECURE TO FACE OF WALL 4- 1/2"X4" EXPANSION BOLTS 311 N\�k ISTI OUR BON 17 1' 0 0 0 ° O ° 4 ° 4 D D D ° d ° 4 D D C. D ° O ° , 4 •4 �o ° ° CUT AWAY BLOCK FOR DOOR a ° D D D D e d e d ° O ° d ° d ' 14 D D D D D D D o ° 4 d D D D O ° O ° FILL CELL AT EACH SIDE OF OPENING / 6' 4" O CO CUT OPENING IN BLOCK WALL DETAIL°�� ghee NOT TO SCAL,�� e w ha_. v W Z O U) NW W 4 0 Z U M N LID ri M OOo O N cl)LL ti z C7 U M W ~ W 00 C!� p p LL W (D U) Z Qo q Q_N Co N m W L9 O CV CO W 2U Ui LL LL Z)O — CV 00 t+l 4li N � OXO K1 Kl Z Z N W m w o a d) LU u z ILL zz� oT Z W z� o6A �z a� U z� N LU -1LU o . N �z _ W AO 1 N O N O in 0 U Z Z ­t O co CV C0 U� —1C) ���C0 �WCti J M 00 OU)M W of U ram_ Q�aLL 2 M W O N Z �-+- 0� Z U0 OU 0 _J0 �:LLI ww0 Z Q U_ O_3F—J LLWL0J � w = Z CV 0 T— 00 M 0 � >LLJ (n N O Z LLJ LL,! 111f2 THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND EXPENSES (INCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE PROJECT. THE DESIGNER WILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF REPAIRS OR DELAY TO THE CONSTRUCTION " T.L. HAN*N P.E. LI(BENSE10. 38654 .P.O 728, DADEjCL 33526 ocr I HEf a Y THAT E$�` ® AND SPECIFICATIONS WER ` MY DIRECT SUPERVISION ARE IN 911 FAR 16, SECTION 1609 OF THE FLORIDA Q H ADDITION AND ASCE 7-10 FOR 139 MP FSK CATEGORY Il U N CD O Q o LL N z Q 0 0� _ w o z w m cn (� J 11 N m N m 0, L,) Ly N M w =U �O N CD M METERS AND CONDENSER UNITS ARE IN THERE APPROXIMATE LOCATIONS 'n F=--1 -1 F=-, 3'0"X6'8" 3'0"X68" 3'0"X6'8" 3'0"X6'8" 3'0"X6'8" 3'0"X6'8" co FE PFA FE PFA PFA =n EXIT EXIT EXIT EXIT EXIT FL EXIT jQ W O O W W (�/' W W Eo W ���� 0 0 'ff d) To 0 0 M M co CID (o wzLL o 3'0"X6'8" W n 1 O z Q o 0lu Eo LLI % m `) z O90 ® M O z x O (M O o � � O � � 3'0"X6'8" 3'0"X6'8" n In t x 0 9 M io X 0 i+) 3'0"X6'8" PFA EX 3'0"X6'8" 3'0"X6'8" m x 0 90 ih w w o Q ih Z O U) co M 3'0"X6'8" O O � N N O m c6 W Z Q m ----------------------------------- 0 0 f0 ----------------------------------- X r Z M Z 1L0 O M CV EXIT � � M p PFA FE FE (� I .44 1N N N L L= 3'0"X6'8" 3'0"X6'8" ti ~�welfJcy) 0 U) Of w EXIT 0 � } V FE PFA PFA Z 3'0"X6'8" Q co d u- 2Mw0 >- N FIXTRUES ARE SHOWN IN APPROXIMATE LOCATIONS ` � O J O O O O O O O O O rgP� SYMBOLCHART EXISTING ELECTRICAL PLAN 1/491 = 1' 0" EXIT EXIT EMERGENCY COMBO LIGHTED BATTERY BACK UP Z 4'X2' SURFACE MOUNT O LIGHT FIXTURE FLOURECENT EXIt 7 f — L EXIT LIGHTED BATTERY BACK UP U O 4' SURFACE MOUNT U Q LIGHT FIXTURE FLOURECENT O 'EDFE O PFA FIRE EXTINGUISHER LOCATION WcnWO PULL FIRE ALARM J ZEL<LL SURFACE MOUNT BATH FAN O J F— LIGHT FIXTURE LL W J Z W = N 03:�� QZO `� CL >O (n N Z Q W W SL w�q���b�app;aa Oppp.�„y ®, o F .ffi. a � p .�H $@FLIC 14038654 33526 1 HERBY ® AND SPECIFICATIONS WERE PRE MY DIRECT SUPERVISION E 1 ARE IN COMPLI PTER 16, SECTION 1609 OF THE THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE FLORIDA BUILDING CODE 2017 6TH ADDITION AND ASCE 7-10 AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND FOR 139 MPH WIND ZONE RISK CATEGORY II EXPENSES (INCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE PROJECT. THE DESIGNER MILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF REPAIRS OR DELAY TO THE CONSTRUCTION zu N z M O Q Q' r*- > tn 00 LL z 04 FL7 U M _ W v� wp p z Wzo� Z Qo q � dN � m N m M U) � N M w 2U uiFL ti �O N 00 M METERS AND CONDENSER UNITS ARE IN THERE APPROXIMATE LOCATIONS /_'E::�R:EA: SER UNIT ONLY ADD DUCT TO THIS NEW RESTROOM FROM EXISTING HVAC SYSTEM *:1 ADD BATH EXHAUST FAN *0 ""n 3'0"X6'8" 3'0"X6'8" 3'0"X6'8" 3'O"X6'8" 3'0"X6'8" 3V'XB'8" FE PFA FE PFA EXIT EXIT EXIT EXITEXIT o a a a ® a FIRE SUPPRESSION a w [IEXIT O 90 w O 0 w w w EQUIPMENT w Eo CD x ® ® 0 0 M--- - - - - -- cD co® P PANE PROPANE STEAMER 4 BURNER 6BURNER oD Q r EN OVEN PROPANE PROPANE X 0 o X RANGE RANGE o N z w I11 M 144" HOOD SYSTEM M Z z (u/ N m Q 3'0"X6'8" O 7 O !11 w a O • WALK I FREE R toN Z N O M Z o F 111 m20 - S.S. WORKTABLE o X U Z Q aD O X o N Lu • N Z O LU O� 3'0"X6'8" 3'0"X6'8" NEW AHU 5 TON AIR HANDLER `r 90 FOR KITCHEN AREA ONLY XLIN p N 90 M ID x o WALK IN COOLER M REFRIG REFRIG M 3'0"X6'8" Eo Fc PFA O 3'0"X6'8" 3'O"X6'8" OPENING ® OPENING o 0 -coo O O X II I 0 M II I I II I w co H II Q X II I I II I ZO II I I u) II I w IL I 3'0"X6'8" i t O CkIi � N N m � � 06 N N ----------------------------------- 3 W zZ ----------------------------------- Q F- m 0 cl 0 U EXIT z PFA FE FE 3'0"X6'8" 3'O"X6,8" M N CV 00 FE EXIT U J (Yj PFA PFA Z 3'O"X6'8" O C = w U ram_ Q C d Ili. 2mw0 } N rY ELECTRICAL NOTES: ho ld ho O 0 O do 1. REMOVE ALL EXISTING SURFACE MOUNT FLUORESCENT FIXTURES AND ho 0 d INSTALL IN SAME LOCATIONS LED RECESSED CAN FIXTURES N �s'10 2. ADD 110V OUTLETS AT LOCATIONS IN KITCHEN. THESE APPLIANCES �J ARE PROPANE GAS AND REQUIRE 110V TO START ONLY. NO 220V OUTLETS REQUIRED PROPOSED ELECTRICAL PLAN 1 /4" — 1 1 O11 3. ADD ELECTRICAL AS NEEDED FOR NEW AIR HANDLER IN KITCHEN AND Q- CONDENSER UNIT AT EXTERIOR LOCATION. ELECTRICAL CONTRACTOR TO VERIFY IN FIELD WHAT PANEL IN BUILDING AN HANDLE ADDITIONAL LOAD FOR NEW ELECTRICAL z CL' 0 v0U Q O 0 J �u WO z0_QLL 0 3 -i LL W L0 J W r � O = Qzc°�°� O LLJ >O CO N za WW / `� yti;"" •9wwwow• w •'v�GENS ••,� T.L. HAW610N1P.E. LICENIE NO. 386t4 P.O. BI 172A'.DAC,'If fMr335$ 4r I HERBY CERTIFY • L �' CATIONS WERE PREPARED BY" wga'm ' PERVISION ARE IN COMPLIANCE Ni N 1609 OF THE E 2 THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE FLORIDA BUILDING CODE' AND ASCE 7-10 AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND FOR 139 MPH WIND ZONE RIS GORY II EXPENSES QNCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE PROJECT. THE DESIGNER WILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF REPAIRS OR DELAY TO THE CONSTRUCTION zU N z O Q ❑ it o0 N LL '� z L9 04 C7 � U M Q W xq v� p ¢❑ li U)� Z Qo (� 0 d N D M N m 04 p� N LY M W 2U L6 LL U- ziO N 00 CM AH U 1 - OA - 142 cfm with 4" ducted to exterior wall or to soffit with screen and gravity NEW 5 TON CONDENSER UNIT damper, minimum of 10 ft from any FOR KITCHEN AREA ONLY ADD DUCT TO THIS NEW RESTROOM FROM EXISTING HVAC SYSTEM c+l ADD BATH EXHAUST FAN itl ILL m 3'0"X6'8" 3'0"X6'8" 3'0"X6'8" m o o FIRE SUPPRESSION 0 X m ® ® EQUIPMENT ct) Z m Cl) LI K30EOEE 000000 EO z z W� ooz M CLOSET 90 m P OVEN E P OVEN E STEAMER PROPANE PROPANE io io ~ JZ M 0. 1 m Z ® X x X x o V Q EF-1 a o _ - o 0 C. RANGE RANGE 0 -1 M M 3'0"X6'8" 24 x 24 144" HOOD SYSTEM 24 x 24 o M UO Z z a o D70 cfm OFFICE 303 cfm ° 4"vent thru ffit 303 cfm WALK IN FREEZER —� z F 9 911 z — o LZ .a z EO o 90 El X RA thru wall 20 M M 11 24 x 24 24 x 24 or half door 303 cfm 303 cfm O 36x24 3'o"X6'8" 3'0"X6'8" " 9 " 1817 cfm OFFICE 24 x 24 X 24 x 24 NEW AHU 5 TON AIR HANDLER 303 cfm m °' FOR KITCHEN AREA ONLY 303 cfm 911 X WALK IN COOLER REFRIG REFRIG 9 " 3'o"x6'8" OFFICE KITCHEN o 0 EXISTING HVAC SYSTEMS AND 3'0"X6'8" 3'0"x6'8" Q OPENING ® OPENING EITO EXISTING AIR DISTRIBUTION SYSTEMCD z TO REMAIN. HVAC CONTRACTOR o I I I o WILL MOVE REGISTERS TO BREAK AREA M I w ACCOMMODATE RENOVATED AREAS. 90 I I I X II 1 I M co II I io Q I I I I EXISTING HVAC SYSTEMS AND CO X I I I I OFFICE (o WOOD WALL EXTENDS FROM SLAB I I I EXISTING AIR DISTRIBUTION SYSTEM �LU TO BOTTOM OF CEILING. WALL TO HAVE (3) EACH TEMP FIXED GLASS AS SHOWN TO REMAIN. HVAC CONTRACTOR FUTURE ASSEMBLEY AREA WILL MOVE REGISTERS TO ACCOMMODATE RENOVATED AREAS. o 3'0"X6'8" Cl) FOOD STAGING AREA N o LO } rn 0 MECHANICAL CONTRACTOR TO VERIFY THAT HVAC SYSTEM IN THIS w m C ASSEMBLEY AREA DOES NOT HAVE PENETRATIONS IN FIRE WALL z o FROM ANY SYSTEMS FROM OTHER AREAS OF BUILDING EXISTING HVAC SYSTEMS AND Q H Z EXISTING AIR DISTRIBUTION SYSTEM °0 p p O TO REMAIN. HVAC CONTRACTOR to Q WILL MOVE REGISTERS TO RECEPTIONIST-----------------------------------� ACCOMODATE RENOVATED AREAS. w U ~ z FOOD STORAGE Z Nj- LID O Lo CV U��00 U04 0� J M 3'0"X6'8" 3'0"X6'8" O U) = W W' U QCDa U- WO � N 3'C"X6'8" ti0 J� sti OJ �r no 0 no 0 10 0 0 0 0 PROPOSED HVAC PLAN 1 /411 = 1' 0" z 0� �z Q� v00 Q O o J 3:u WO z0-Qu 0_�-j LL. WLO_j zW�� =o � o�� Qp`Y'� >O Cn N zQ W W v No.38654 • �TT - M1 T.L. i'o®• 654 P.O. B S®33526 I I T i llhhk I i 1TiT i ;t1-1F u; i.. ; zi. i I, s e.. 1, 1 r I� ' �- I f I � •�-_.�T._— _ APPROXIMATE LOCATION OF SANITARY C.O. SANITARY LAYOUT PLAN 1 /411 = 1' 0" TILT MIRROR ------------------ 6"MAX.------- TOE CLEARANCE i 2 z z lc:l I , N I , � I 1 I , I I 1 17" MAX LAV DEPTH 8" MIN KNEE CLEARANCE HANDICAP SINK DETAIL SINK 1. SINK SHALL BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" FROM THE FINISH FLOOR. EACH SINK SHALL BE MINIMUM OF 6 1/2" DEEP. 2. CLEAR FLOOR SPACE RESTROOMS SHALL HAVE AN UNOBSTRUCTED SPACE OF AT LEAST 60" IN DIAMETER OR 52" BY 72" FINISH INSIDE DIMENSIONS ADJACENT TO THE LAVATORY AREA. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE LAVATORY OR SINK 54" MIN TOILET PAPER HOLDER 42" MIN HANDICAP TOILET DETAIL rtl 18" MIN � r 18" MIN 24" MIN 16" MIN I , • -----; z LAV I I CLEAR FLOOR C° CO SPACE I ---------------------•: GRAB BARS 1 60" MIN A GRAB BAR SHALL BE PROVIDE. LOCATED 33" INCHES FROM AND PARALLEL TO THE FINISHED FLOOR. MEASURED VERTICALLY TO THE TOP OF THE RAIL WITH VARIATION OF NOT MORE THAN 1/2 INCH AND: 1. SHALL HAVE AN OUTSIDE DIAMETER OF 1 1/2 INCHES 2. SHALL PROVIDE 1 1/2 INCHES OF CLEARANCE BETWEEN THE RAIL AND THE WALL. 3. SHALL BE SO DESIGNED AND SUPPORTED AS TO WITHSTAND A LOAD OF NOT LESS THAN 250 LBS APPLIED AT ANY POINT. DOWNWARD OR HORIZONTALLY. 4. SHALL BE CONTINUOUSLY GRASPABLE ALONG THE ENTIRE LENGTH. SPECIAL NOTE: GRAB BAR MEETING THE APPLICABLE ANSI STANDARDS ARE DEEMED TO BE IN COMPLIANCE WITH THE INTENT OF THE LAW WHETHER CENTER SUPPORTS EXIST OR NOT. 5. SHALL BE AT LEAST 42 INCHES LONG AND SHALL BE CENTERED AT THE LEADING EDGE OF THE WATER CLOSET. lii F- Q 0 z 0 U) W w zcv) z Ln M Q o o �� tn o J N LL ti >m �z }° U) �? (14 U ch U W X Wp Z v] Qp L W L U)"- < Z Qo � d CV 5(� m N m tt Ly DO N M W =U U5u- LL z;0 CV cM m fQ Z 0. Z 111 o 0 Z w z� LU U zz o4 • N �z ~ _ z V w O O N N p m O I 00 W z Q m p 0 0 U z z I O M CV ao U�J� D0u-00 � ofCti J _M 0 U) W U r}_ Q(0aIWi 2Mw0 y- N IY Z O F— F-z Z) VOU Q O � J _ U) W O z�QLL O_3F-C/) LL LLJ LO J W 2 C Z O M Q Q � >O to N ZQ W uJ W 75; m v m m C4 m M THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND EXPENSES (INCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE PROJECT. THE DESIGNER WILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF REPAIRS OR DELAY TO THE CONSTRUCTION T.Li P.O. 100 ® NO. 386,54 p 1 I J 3 .mmr..._-.s_:��-A{-..��--..___—,,.-_--...�. r -._..r ____. __ _��e�• .gym _ _ i x�--m: �� fir'„!?'?!I""_�f�"'I?'fT'I�"!IAI?�R^�i't""'r'�, -'.�-fir., '"f` r. —� .. Y ..^^�iir�ii'rrT�rrrrcrnnm-�ierrn-�i��naa�are��anrrnr�ermm�mn..:. �,.-.-.,�r•-.,r-^mmn-�n�r>—�-nc,_—_..r. __ —,r--- �__—..,.�.-,�:A—...—,� -. — - _ _ ,— - __._... „._�..�_. ._... _ __. _ _._.__