HomeMy WebLinkAbout5320 1st St_ L L GENERAL NOTES: THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2020 FLORIDA BUILDING CODE 7 TH EDITION ARKAY ENGINEERING A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING COMPANY; HAS APPLIED 'RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN OF THIS STRUCTURE. THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE FOLLOWING SUPERIMPOSED LOADS: SLAB: LIVE LOAD - 50 P.S.F. DEAD LOAD - 10 P.S.F. ROOF: LIVE LOAD (TRUSS TOP CHORD) - 20 P.S.F. DEAD LOAD (TRUSS TOP CHORD) - 10 P.S.F. DEAD LOAD (TRUSS BOTTOM CHORD)- 10 P.S.F. ASSUMED TRUSS SELF WEIGHT (DEAD LOAD) - 7 P.S.F. WIND: BUILDING IS DESIGNED TO CONFORM TO ASCE 7-16, CHAPTERS 26 THRU 31; PER 2014 FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R301.2.1.1. AND 2014 FLORIDA BUILDING CODE SECTION 1609.1.1. WIND DESIGN ASSUMPTIONS: BUILDING EXPOSURE - B BUILDING RISK CATEGORY - II MEAN ROOF HEIGHT 30' OR LESS HEIGHT & EXPOSURE ADJUSTMENT COEFFICIENT = 1.0 ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT = +/- 0.18 WIND SPEED SHOWN AT THE BOTTOM RIGHT CORNER OF THIS SHEET ALL STRUCTURAL ELEMENTS, EXTERIOR WALLS AND INTERIOR WALLS SHALL BE TYPE V CONSTRUCTION PER FBC 602.5 SOIL BEARING & COMPACTION: COMPONENT & CLADDING WIND LOADS ALL OTHER BUILDING ROOF OVERHANG COMPONENT ZONE LOADS LOADS 1 NIA +32.3/-35.3 2 -65.7 +32.3/-56.2 3 -110.6 +32.3/-89.0 4 N/A +35.3/-38.2 5 NIA +35.3/-472 THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. (MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. ARKAY ENGINEERING A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE NOR PERFORMING ANY SOIL TESTING. ARKAY ENGINEERING SHALL NOT BE RESPONSIBLE FOR THE SITE SOILS ABILITY TO SUPPORT THE BUILDING LOADS. BUILDING DATA TOTAL AREA 3588 SQ. FT. OCCUPANT LOAD 120 STUDENTS USE AND OCCUPANCY: EDUCATIONAL GROUP E CONSTRUCTION TYPE: VB FIRE PROTECTION: NON SPRINKLED PLUMBING FIXTURES SHOWN PER TABLE 403.1 FLORIDA BUILDING CODE 2020 7 EDITION PLUMBING ENEMY& I& ► ■ ■■■w %k i IW- D E S I G N S I N C BUILDING DESIGNS 13821 U.S. HWY 98 BY PASS DADE CITY, FLORIDA 33523 OFFICE 352-523-2077 INTERIOR RENOVATION DRAWINGS FOR THE ACADEMY OF SPECTRUM DIVERSITY 5320 1 ST STREET ZEPHYRH I LLS, FLORIDA JOB SITE LOCATION MAP FLORIDA FIRE PREVENTION CODE 7TH EDITION 7 TH EDITION 2020 FLORIDA BUILDING CODE 7 TH EDITION 2020 FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 FLORIDA PLUMBING CODE NFPA 10 (STANDARD FOR PORTABLE FIRE EXTINGUISHERS) 2017 NATIONAL ELECTRICAL CODE (NFPA 70) BUILDING HAS WOOD ROOF SYSTEM LIGHT FRAME CONSTRUCTION SIGN REQUIRED RESTROOM FLOORS TO BE A NON ABSORBENT MATERIAL RESTROOM WALLS TO BE A NON ABSORBENT MATERIAL MINIMUM 60" ABOVE FINISH FLOOR INTERIOR FINISHES TABLE 803.11 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY' SPRiNKLEREV NONSPRINKLERED GROUP Interior stairways and ramps and exit passageways' n Corridors and enclosure for exit access stairways and ramps Rooms and enclosed spaces Interior exit stairways and ramps and exit passageways`' Corridors and enclosure for exit access stairways and ramps Rooms and enclosed spaces` A-1 & A 2 B B C A A° i B` A-3', A-4, A-5 B B C A A' C B, E, M, R-1 1 B C C A B R-4 B C , C A B B C C C B C C B B Ca A A B I-1 B C. C A B B 1-2 B B B` A A B I-3 A A' C A A B 1-4 B B B" A A B R-2 C C C B B C R-3 C C C C C C S C C C B B C U No restrictions No restrictions For SI: I inch 15 4 mm, 1 square foot = 0.0929 m'. a. Class C interior finish materials shall be permitted for wainscotting or paneling of not more than 1,0M square feet of applied surface area in the grade lobby where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by Section 803.13.1. b. In other than Group 1-3 occupancies in buildings less than three stories above grade plane, Class B interior finish for nonsprinklered buildings and Class C interior finish for sprinklered buildings shall be permitted in interior exit stainvays and ramps. c. Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions, 'Nhere a fire -resistance rating is required for structural elements, the enclosing partitions .shall extend from the floor to the ceiling. Partitions that do not comply writh this shall be considered enclosing spaces and the rooms or spaces on both sides shall be considered one. In determining the applicable requirements for rooms and enclosed spaces, the specific occupancy thereof.sha l he the governing factor regardless of the group classification of the building or structure. d. Lobby areas in Group A-1, A-2 and A-3 occupancies shall not be less than Class B materials. e. Class C interior finish materials shall be permitted in places of assembly with an occupant load of 300 persons or less. f. For places of religious worship. wood used for ornamental purposes, trusses, paneling or chancel furnishing shall be permitted. g. Class B material is required where the bolding exceeds two stories. h. Glass C interior finish materials shall be permitted in administrative spaces. i. Class C interior finish materials shall he permitted in rooms with a capacity of four persous or less. j. Class B materials shall be permitted as wainscotting extending not more than 48 inches above the finished floor in corridors and exit access stairways and ramps. k. Finish materials as provided for in other sections of this code. 1. Applies when protected by an automatic sprinkler system installed in accordance with Section 9033.1.1 or 903.3.1.2. PROTOLICH CONTRACTING 7051 LEXINGTON CIRCLE BROOKSVI LLE FL 34602 813-446-38221 ray SITE P LAN INDEX SITE PLAN BY OTHERS SHEET B 1: EXISTING FLOOR PLAN SHEET B 2: PROPOSED FLOOR PLAN INTERIOR DOOR DETAIL INTERIOR DOOR SCHEDULE EXTERIOR DOOR AND WINDOW SCHEDULE FIRE CORRIDOR DETAIL EXTERIOR WALL SECTION DETAIL INTERIOR WALL DETAIL OPENING DETAILS S-1 S-2 SHEET M 1: H*r/AC LAYOUT SHEET M 2: HVAC EQUIPMENT DETAILS SHEET E 1: POWER PLAN � ELECTRICAL LEGEND &SCHEDULE SHEET E 2: LIGHTING PLAN SHEET L S: LIFE SAFETY PLAN SHEET P 1: PLUMBING PLAN ADA DETAILS PLUMBING SCHEDULE REVIEW UWE_ ! - 5. �a-y CITY OF ZEPHYs-at.w.. FIRE AND LIFE SAFETY EXAMIl P° aEV AND THE CITY ALL WORK SHALL COMPLY WITH NFFA CODES AND STANDARDS --( CIS a'OF PI I PLAN E_XAAA!,NER ARKAY ENGINEERING INC. structural eng f veers 11358 E. Edgewood Drive, Lakeland Fl 33803 Phone 863-686-w6500 Fax 863-688-6551 State of Florida Certificate of Authorization * EB6341 tin Richard L Kiddey P.E. - Florida License N 31296 0 ARKAY 111955c3 c v a r--—--—-—- - ----- U z 0 Q 0 0 p LL 0 - ul� I X cn 0 u� Z C-) I� wo ►-i � p N Q � p p N W 0 (A N Z QLo A C"7 iw co U co oo LL 0)u- EXISTING LOBBY uj I RECEPTIONIST COUNTER p AND DESK IN THIS AREA N NOT SHOWN °O M i I I � � cn OLDER UNIT TO Q i C = BE REPLACED Q r- `/) m�cov 77' 4" z wo to z QO GOOD 5 TON UNIT iy u- CONDENSER UNIT 10' 9" 10' 9" 10' 8" 10' 9" 12' 5" 6' 8" 5' 4" Q W m z +>U z� u� 1444 FG 1444 FG 1444 FG 1444 FG 1444 FG 34 SH ®� U i 3'0"X6'8" -a cq-J ui p 4i I U ff' 0- w SK I ui ATTIC ACCESS IS AT THE Q APPROXIMATE LOCATION 0 hum c/) u,x j Q4 w I CC) fZ' N N } Lo CV EXISTINGCD LUNCH ROOM EXISTING INTERIOR WALLS ARE NOT SHOW ON THIS Oz TABLES NOT SHOWN DRAWING. ALL INTERIOR WALLS AND WOOD STAGE aY Q In WILL BE REMOVED TO ALLOW FOR RENOVATION O IN THE AREA EXISTING INTERIOR BLOCK WALL. THIS WALL WAS THE PREVIOUS ADDITION ADDED TOT EERIOR BUIILDNEGORE EXISTING DRYWALL CEILING TO REMAIN. THE CEILING a co HEIGHT IS 125" FROM FINISH FLOOR }.. H 1 AIR HANDLER UNIT IS ABOVE CEILING IN ATTIC 0 5 TON 14 SEER UNIT IS 3 YEARS OLD 1 AIR HANDLER UNIT IN ATTIC THAT DOES NOT w WORK AND WILL BE REMOVED AND REPLACED 0 AS NEEDED Z �2 Q ❑ I— w 0 0W�LL 11-- J 00N= o� wM�- � w Lr) [L ® w O< N �'- I ~_ Z I 3'0"X6'8" 1444 FG 1444 FG 1444 FG 1444 FG 1444 FG 34 SH 10, 9" 10, 9" 10' 8" 10, 9" 12' 5" 6' 8" 5' 4" R E N O VAT I O N RKAY ENGINEERING INC. AREA STRUCTURAL ENGINEERS 3588 SQ. FT. 78' 0" EXISTING PARTIAL FLOOR PLAN t`tIl' — 1 11 RI HARD L. KIDDEY P.E. 4 F IDA LICENSE NUMBER 37296 SHEET I HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS B 1 WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE FLORIDA BUILDING CODE 2020 7 TH EDITION AND ASCE 7-16 FOR 139 MPH WIND ZONE RISK CATEGORY 11 ARKAY # 19859 I' z I , 1 EXISTING LOBBY RECEPTIONIST COUNTER AND DESK IN THIS AREA NOT SHOWN , , , , I , I , I I I , I I 1 I , , I , 1 1 1 , , , EXISTING INTERIOR BLOCK WALL. THIS WALL WAS THE PREVIOUS EXTERIOR BEFORE ADDITION ADDED TO THE BUILDING REMOVE EXISTING DOOR AND FRAME FILL OPENING TABLES NOT SHOWN CUT OPENING IN EXISTING BLOCK WALL TO CREATE DOOR OPENING. SEE DETAIL S-1 REMOVE EXISTING DOOR AND FRAME FILL OPENING INTERIOR DOOR SCHEDULE 3'0"X7'0" 1 3/4" SOLID CORE 20 MINUTE LABELED FIRE RATED DOOR WITH 6X36 LAMINATED GLASS A INSERT ❑ 20 MINUTE LABELED STEEL DOOR FRAME DOOR CLOSURE 3-4.5 BB HINGES ADA LEVER CLASS ROOM FUNCTION LOCK 3'0"X7'0" 1 3/4" SOLID CORE WOOD DOOR DOOR FRAME ❑STEEL B DOOR CLOSURE 3-4.5 BB HINGES ADA LEVER PRIVACY LOCK 3'0"X7'0" 1 3/4" SOLID CORE WOOD DOOR STEEL DOOR FRAME 3-4.5 BB HINGES ADA LEVER KEY LOCK DBL 3'0"X7'0" 1 3/4" SOLID CORE 20 MINUTE LABELED FIRE RATED DOOR WITH 6X36 LAMINATED GLASS INSERT EACH DOOR ❑D 20 MINUTE LABELED STEEL DOOR FRAME DOOR CLOSURE EACH DOOR 3-4.5 BB HINGES EACH DOOR PANIC BAR DEVICE EACH DOOR ON CLASS ROOM SIDE PULL HANDLE EACH DOOR LUNCH ROOM SIDE EXTERIOR DOOR & WINDOW SCHEDULE 0 EXISTING 3'0"X6'8" DOOR 8, FRAME TO REMAIN ADD PANIC EXIT DEVICE ON INTERIOR OF DOOR WITH ADA LEVEL KEY LOCK ON EXTERIOR 2❑ REMOVE EXISTING WINDOW AND REPLACE WITH 34 SH WINDOW VINYL FRAME TINTED INSULATED GLASS SITE VERIFY OPENING ON THIS WINDOW 26 SH WINDOW (37"X72") VINYL FRAME TINTED INSULATED GLASS MODIFY EXISTING OPENING SEE DETAIL S-2 TOP OF WINDOW TO BE INSTALLED AT 8'0' A.F.F. INTERIOR DOOR DETAILS 3' 0" 3' 0" DROP CEILING SY; A.\ rti A ^e A A �� ■.� ■�� �� • ■ ■� ■ /A\ /�\ ■'"t � ■ 1. \ ■ I ! I ■■ • ■ A ■■ AC DUCT WITH FIRE DAMPER AT PENETRATION OF FIRE CEILING 0 TEM .17 0 0 �n o O O 3 5/+ v a) FLC ONE SIDI U41 o VARIES, SEE FLOOR PLAN O O 30TTOM CORD OF EXISTNG ROOF TRUSS NITH ONE LAYER OF EXISTING 1/2" REGULAR 3YPSUM BOARD TO REMAIN SEE FIRE RATED DETAIL GA-FC5512 WITH MINIMUM 2 LAYERS 112" TYPE X GYPSUM BOARD P' 20 GA STEEL STUDS @ 16" OC TYPICAL FROM OR TO BOTTOM OF STEEL STUD CEILING JOIST LAYER 5/8" TYPE X FIRE RATED GYPSUM EACH FROM SLAB TO BOTTOM OF CEILING 3 1 HOUR RATED WALL TYPICAL 1 HOUR FIRE RATED AREA Cc) CORRIDOR NOT TO SCALE O d� F 6' 4" CUT DOOR OPENING DETAIL S-1 NOT TO SCALE SAW CUT ABOVE THE OPENING AND INS 1/4"X4"X4" STEEL ANGLE AS SHOWN ANI PUNCH HOLE IN WALL AT SIDE OF SECURE IN PLACE WITH 5/8"X4" EXPANS OPENING BELOW STEEL ANGLE BOLTS AND FILL CELL SOLID WITH CONCRETE EXISTING LINTEL O ' REMOVE CUT SWAY BLOCK i•° , ° EXISTING ► 0 FOR WINDOWlz WINDOW - o• fl o. e' o o ' ea ,.. s� o O ,1. 3' 3" I. MODIFY WINDOW OPENING DETAIL S-2 NnT TO SCAI_F RT )N )UNCH HOLE IN WALL AT EACH TIDE OF OPENING BELOW STEEL ANGLE AND FILL CELL SOLID WITH :ONCRETE CUT SWAY BLOCK FOR DOOR =RT ION XISTING ROOF TRUSSES ,-30 INSULATION IN ATTIC W/ UL ,R[ EXTERIOR WALL DETAIL NOT TO SCALE WOOD TRUSS BOTTOM CORD O 3 5/8" 20 GA TRACK ATTACHED TO BOTTOM CORD OF TRUSS WITH o (2) #8X1 1/2" SCREWS. SECURE STUD TO TRACK WITH (1) #8X1" SCREW AT EACH SIDE DROP CEILING SYSTEM ° 1/2" GYPSUM BOARD ON EACH SIDE OF STUD 3 5/8" 20 GA STEEL STUDS @ 16" OC a, I 3 5/8" 20 GA TRACK ATTACHED TO CONCRETE FLOOR WITH (2) #8XV TAP CONS SCREWS @ 24" OC, SECURE STUD TO TRACK WITH (1) #8X1" SCREW AT EACH SIDE TYPICAL STEEL STUD WALL DETAIL ARKAY ENGINEERING INC. STRUCTURAL ENGINEERS 70SLE I RICHARDL. KIDDEY P.E. ORIDA LICENSE NUMBER 37296 1 HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE FLORIDA BUILDING CODE 2020 7 TH EDITION AND ASCE 7-16 FOR 139 MPH WIND ZONE RISK CATEGORY 11 7 U CV z � Q � c' nCALL z � C.7 U) Z U r-- U— wo~ In 1:)N W 0 , Q co 0 cV W Z cl)< Lo to A 0- _� W � m U oD 00 Lr_ rnLL }O U) ® N 00 M rr �%Qtr�Y cq # 0 � Q) M m%Q0� cqcocou z X N -j tu Lu m , V .` �' / QOL7L �uj iL all ' 0 c{') V W F- Q 0 Z O U3 W ry fY N N } N 04 W cl z O OLL V U) ry > Z ❑ �I ❑1-wWO Z O 00NT_ w2N>- LyL L.L OV L.L C G❑// C W ry W ❑ Q Q LL a N W Z� W I RENOVATION AREA 3588 SQ. FT. SHEET B2 ARKAY # 19859 Y i!" i V N Ul LL 0 13f Q C'� Z�Wo ~ � N —4) co o oN EXISTING W z Q N LOBBY A o a w r RECEPTIONIST COUNTER pop 'D LL AND DESK IN THIS AREA M LL NOT SHOWN 0 Uj I N 00 M , I , I rr AHU1 - 5 Ton FSD = FIRE SMOKE �# OA 542 cfm with 12 DAMPER Upon activation, �� m duct ran to exterior cn o ` smoke detectors shall shut wall or thru roof M m � u down all operational capabilities _ N with bird screen and of the air distribution system. Z "-Iwo to , motorized damper. EF - 1 Minimum 10 from any exhaust outlets. 140 cfm vtr W- or vtw field w C -4 m determined. Z m Q u , Z� L Ul- ia: w �06 �mC 0� 24x24 24x24 24x24 F—F] �0 24 x 24 24 x 24 333 cfm 333 cfm 24 x 24 333 cfm 24 x 24 129 cfm 1011 333 cfm 333 cfm 12 " 12 " 10.1 101, 333 cfm 711 , 1011 ( , 0 RELOCATE ATTIC ACCESS AS O NEEDED IN EXISTING DRYWALL 1 CEILING TO ACCESS AIR HANDLER U) UNITS W tY 24x24 I 24 x 24 667 cfm AHU1 24 x 24 162 cfm 14"�`L'j —�— — — 5Ton 24x14 16x14 10x14 667 cfm O 14" 24x24 8 ® (020 667 N cfm N --————————— — — — — ———————————————————— — — —�-- L0' N N Z O O 11.1 Z 24x24 < Q m EXISTING 24 x 24 12 1 65 cfm 0 0 LUNCH ROOM ' ' , , 5 ,1 TABLES NOT SHOWN 700 cfm — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — E 2 Ton 2 Ton 14 I , 0O� 24 x 24 It 660 cfm — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — W 14"------ 24x24 (D > 1 24 x 24 660 cfm ® z 660 cfm 20 14" Q AHU2 24x14 16x14 10x14 5 5 Ton 1419 I 24 x 24 ry 215 cfm ®� IWLI O , 8" U OW�LL �U)U)U) 24 x 24 ; U J 24 x 24 24 x 24 129 cfm O c� _ ' 24 x 24 24 x 24 24 x 24 .___ 24 x 24 7 1, 330 cfm 330 cfm 330 cfm 330 cfm z 101, 33 Ocfm 3 1 flcfm 10 „ 12 12 W „ 1, ,1 11 M = W In 0- 0 W ® OU N WW I zrI , EF-1 AHU2 - 5 Ton 140 cfm vtr RENOVATION OA - 542 cfm with 12" or vtw field AREA determined. duct ran to exterior HVAC PLAN 1/4 11 = if Of! 3588 SQ. FT. wall or thru roof with bird screen and 1 ARKAY ENGINEERING INC. motorized damper. Minimum 10' from any exhaust outlets. SHEET 1� M 1 RICHARD L. KIDDEY P.E. FLORIDA LICENSE NUMBER 37296 ARKAY # 19859 0 z U Cl) z m 0 Fy Oon J LL zUti W ® C� ~o �"� (Az U) 0 N W Q M Lf) OUTSIDE AIR CALCULATION HVAC EQUIPMENT SCHEDULE NOTE: ELECTRIC REQUIREMENT FOR EQUIPMENT TO BE A Q QM FIELD VERIFIED BY ELECTICTIAN/MECHANICAL CONTRACTOR. < >_ W MN. In AH CATEGORY SQ. FT. AREA CFM/PRSN + CFM/FT OIA. CFM 00 CO 11- MFG.MODEL NO. TOTAL-BTUH AH SEER O!A TONNAGE SENSIBLE LATENT KW VOLTAGE LRA/RLA MCA/MOCP CFM CY } 0 LL 1 School 1219 7.5 x 60 + .06 + 1219 523 "OR EQUAL" "OR EQUAL" COOLING/HEATING �R CFM 2 School 1219 7.5 x 60 + .06 + 1219 523 1 EXISTING EXISTING 5 TONS 60,000 34,121 42,600 17,400 14.0 10 KW 208/230-60-1 134/25 32.8/50 1980 542 ui 3 School 1149 0 x 0+ .06 x 1149 38 TOTAL OA 1084 2 FRANKLIN or Eqv. GSX14060/ASPT61 5 TONS 60,000 34,121 42,600 17,400 14.0 10 KW 208/230-60-1 134/25 32./50 1980 542 co M r 3 FRANKLIN or Eqv. GSX14025/ARUF29 2 TONS 23,600 17,060 17,228 6,372 14.0 5 KW 208/230-60-1 58.3/13.5 17.6/30 700@LOW 0 FAN SCHEDULE MFG. TYPE "OR CFM VOLTS DUCT DIA. EQUAL" 1 BROAN OR EQUAL CEILING EXHAUST FAN 140 120 6 INCHES 1 BROAN OR EQUAL CEILING EXHAUST FAN 140 120 6 INCHES AIR BALANCE SCHEDULE AH1 OUTSIDE AIR INTAKE CFM +542* SUPPLY AIR CFM +1980 RETURN AIR CFM -1457 EXHAUST AIR CFM -140 TOTAL BUILDING PRESSURE 11011 CFM AH2 OUTSIDE AIR INTAKE CFM +542* SUPPLY AIR CFM +1980 RETURN AIR CFM -1577 EXHAUST AIR CFM -140 TOTAL BUILDING PRESSURE 11011 CFM * AH1-2 INCLUDES AH3 OA DIFFERENTIAL PRESSURE GAUGE AIR HANDLING UNIT FILTE SUPPLY AIR FLEXIBLE SECTI DUCT-7 CONNECTION FLOOR DRAIN CEILING/ O HORIZONTAL AIR HANDLING UNIT NOT TO SCALE 12" BASE RAILS PROVIDED BY AHU MANUFACTURER DRAIN OUTSIDE AIR DUCT MOTORIZED DAMPER ACCESS DOOR ° LINED SHEETMETAL RETURN AIR PLENUM 'ING PAD TE FLEXIBLE CONNECTION RETURN AIR DUCT TO AIR HANDLER - THRU FIRST FLOOR CEILING SPACE INSULATED SUCTION LINE (NO JOINTS ALLOWED) SEE FLOOR PLAN FOR PIPE SIZES LIQUID LINE —/ (NO JOINTS ALLOWED) DRILL BLOCKING TO FIT OUTSIDE OF REFRIG. LINES WATER TIGHT -METAL BOOT PAINTED TO MATCH EXTERIOR FACADE IF REFRIG. LINES RUN IN CEILING SPACE FASTENED TO WALL BOTH 'SIDES W/ 1"Xi/8" SCREWS 18" APART -SUCTION CONNECTION -LIQUID CONNECTION -COND. UNIT TO BE SECURED WITH (4) KWIK BOLT 0 3/8"x3" WITH 2 1/2" MIN EMBED 4" CONCRETE SLAB — CAULK W/3M CP-25 OR EQUAL PROVIDE 4" PVC SCH-40 SLEEVE IF REFRIG. LINES RUN UNDER SLAB CONDENSING UNIT MOUNTING DETAIL NTS chg rn m go z X N J Cc la > 0go :z d 0 Lu v m u � � 1 U ti o a -0 }- U -0 in m Y.0 � CON U1 \QU-J W O IZ O IY Q 0 Z 0 En W w N N LO CV CV m � � z o W O Z m p p O i r O� LL W W > z �2i Q a METAL WALL CAP 12 ga. HANGER WIRE ~ O� W/ BACKDRAFT DAMPER I—' W 0 AND BIRD SCREEN Z U ANGER WIRE OR STRAP O W 5'-0" MAX DISTANCE _CL U) BETWEEN SUPPORTS. MAX. SAG 10" PER FOOT METAL SUPPOR f — (n OF SUPPORT SPACING. STRAP MIN. 1\2" WIDE LL RIGID AIR DUCT: ON UL-181 CLASS 1 SPIN -IN W/ 1-1/2" GALV.STEEL BAND BACK DRAFT MANUAL DAMPER DAMPER ® INSULATED MIN. R-6 CLAMP TO MATCH DUCT 7 N SEE "METHODS OF DIAMETER FAN L >- O Of HANGING DUCTS" N FOR REQUIREMENTS OF/H HOUSING W M INSULATED MIN. R-6 FLEXIBLE DUCT W W W UL-181 CLASS 1 Q WALLNN / ® W FLASHING AND � OPENING ` CEILING o U N SEAL WALL CAP AIR DIFFUSER CEILING w REMOVABLE GRILL Q w W W INSTALL STAINLESS STEEL DUCT NOTE: f CLAMPS ON BOTH INNER AND OUTER ALL STRAP SHALL BE A Z JACKETS. SEAL INNER JACKET AIR z TIGHT WITH MASTIC. NYLON DRAWBANDS MINIMUM OF 1-1/2", 26 EXHAUST FAN DETAIL MAY BE USED IN NON PLENUM AREAS, GA. GALVINIZED STEEL. HANGER WIRE SHALL BE IN SUSPENDED CEILING FLEXIBLE DUCT DETAIL A MINIMUM OF 22 GA. SCALE: NT ARKAY ENGINEERING INC. RICHARD L. KIDDEY P.E. FLORIDA LICENSE NUMBER 37296 RENOVATION AREA 3588 SQ. FT. SHEET M2 ARKAY # 19859 0 3 1/2" 20 GA STEEL STUD WITH 5/8" TYPE X GYPSUM BOARD EACH SIDE SEE CORRIDOR SECTION DETAIL BATHROOM PARTITION SYSTEM WALL. MANUFACTURE TO BE CHOSEN BY CONTRACTOR USING A GOOD QUALITY 5 1/2" 20 GA STEEL STUD WITH 1/2" MOISTURE RESISTANT GYPSUM BOARD EACH SIDE 3 1/2" 20 GA STEEL STUD WITH 1/2" GYPSUM BOARD EACH SIDE POWER PLAN 1/411 = 1' O" M N co M Q a� Fy O J LL ZU ti U—' w o~ U) 0 N W Q c7 0 Z Q Lp M W mU 00 ap LL �LL �O N 00 C"M rr r T'Q ��N c0 M mco�o z x N� Z Q)Z ii d 0 i m - IL so ;z m tu tu �a V 0 Y ' ELTRON # 232095 [A � .40 GPM 2.5 POINT tQ� AND WATER HEATER co LINES ABOVE CEILING L j URES IN THIS AREA III) m coo LLI H Q Z O U) w ry fi N N } Lo tV m r 2' Z o p w p O z m O 3 LL V JVJ LLJ V >_ � }Z ` �/ C 0 cQ c.N ry LJ// 0�-W_ O uJ _0 U) VJ >11~ J_ p O _ ®>- w ELTRON # 232098 ry y J .40 GPM 2.5 POINT Q AND WATER HEATERui LINES ABOVE CEILING IN AREA O < N JRES THIS 'va I.L < W w m Z L- ARKAY ENGINEERING INC. STRUCTURAL ENGINEERS RICHARD L. KIDDEY P.E. FLORIDA LICENSE NUMBER 37296 RENOVATION AREA 3588 SQ. FT. SHEET E1 I HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE FLORIDA BUILDING CODE 2020 7 TH EDITION AND ASCE 7-16 FOR 139 MPH WIND ZONE RISK CATEGORY 11 ARKAY # 19859 • 0 3 1/2" 20 GA STEEL STUD WITH 5/8" TYPE X GYPSUM BOARD EACH SIDE SEE CORRIDOR SECTION DETAIL BATHROOM PARTITION SYSTEM WALL. MANUFACTURE TO BE CHOSEN BY CONTRACTOR USING A GOOD QUALITY 5 1/2" 20 GA STEEL STUD WITH 112" MOISTURE RESISTANT GYPSUM BOARD EACH SIDE 3 1/2" 20 GA STEEL STUD WITH 1/2" GYPSUM BOARD EACH SIDE LIGHTING PLAN 1/4" = 1' 0" RELOCATE ATTIC ACCESS AS NEEDED IN EXISTING DRYWALL CEILING TO ACCESS AIR HANDLER UNITS ARKAY ENGINEERING INC. STRUCTURAL ENGINEERS RICHARD L. KIDDEY P.E. FLORIDA LICENSE NUMBER 37296 cl) N lf7 Q 0 ii O 1 LL Z C� c� w ~o (n 0 N w Qm N Z d Lo �c� w � mU 0o w u- (MLL } v� N 00 M r- r InMco 4p O � s m c q u ZZZ4 40 0 w C zm Qi U p 4 3 +1) O�U� l3 Co 0 710 ui m o c m� 0 0 IL d) Ir Ili F- 0 z 0 W tY LO fZ' N N } � r N (y m t Z 0 of W O Z m O I..L OLL vJ �./ (/) > Z Q < Of n O >L.LC/)J OON= w�IN>- Ofw�� flf O C G W 0 v VJ 0 ry O Vl J ry N �Q ww f- z�- _ RENOVATION AREA 3588 SQ. FT. SHEET E2 I HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE FLORIDA BUILDING CODE 2020 7 TH EDITION AND ASCE 7-16 FOR 139 MPH WIND ZONE RISK CATEGORY 11 ARKAY # 19859 EMERGENCY LIGHT WITH BATTERY BACK UP EXIT EXIT / EMERGENCY LIGHT COMBO UNIT WITH BATTERY BACK UP FE e ABC MIN 2A, 20B,C FIRE EXTINGUISHER LIFE SAFETY PLAN 1 /4°' = 1' off ARKAY ENGINEERING INC. STRUCTURAL ENGINEERS RICHARD L. KIDDEY P.E. FLORIDA LICENSE NUMBER 37296 1 HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE FLORIDA BUILDING CODE 2020 7 TH EDITION AND ASCE 7-16 FOR 139 MPH WIND ZONE RISK CATEGORY II z V N Lf) z m 0� Q 0 o' o LL c� z < 0* z wo~ n w w Q c; 0 p fv cn Lf� W Z Q� A cl 0- M J W mU [Y] ap LL rnw �O 2 I ® CV 00 r-'T to gn�(P N cqcU zFT X "-i ,tt L V 0 to V lu 0 Z �1 J U ca Z z cl j -0 f� v lU U1 'm 0 IL o W- w F- e( 0 Z O U) w c0 N N Lo N } r' (V m � � Z O LLI O Z Go O 3 OLL � W Z _> ® Z O � ®ON= w OU C G I— C) W (n LL W w U c/) N}. L Q ry J _ w N ww E- ZF- _ RENOVATION AREA 3588 SQ. FT. SHEET LS ARKAY # 19859 541, MIN TOILET PAPER HOLDER 42" Mild , r— X (1 9 F HANDICAP TOILET DETAIL 18" MIN is" MIN 24" MIN LAY I 1 I _z 1 I CLEAR FLOOR vo I SPACE --------------- CRAB BARS &0" MIN A GRAB BAR SHALL BE PROVIDE. LOCATED 331, INCHES FROM AND PARALLEL TO THE FINISHED FLOOR. MEASURED VERTICALLY TO THE TOP OF THE RAIL 1. SHALL HAVE AN OUTSIDE DIAMETER OF 1 1/2 INCHES 2. SHALL PROVIDE 1 1/2 INCHES OF CLEARANCE BETWEEN THE RAIL AND THE WALL. 3, SHALL BE 50 DESIGNED AND SUPPORTED AS TO WITHSTAND A LOAD OF NOT LE55 THAN 250 LB5 APPLIED AT ANY POINT. DOWNWARD OR HORIZONTALLY. 4, SHALL BE CONTINUOUSLY GRASPABLE ALONG THE ENTIRE LENGTH. SPECIAL NOTE. GRAB BAR MEETING THE APPLICABLE ANSI STANDARDS ARE DEEMED TO BE IN COMPLIANCE WITH THE INTENT OF THE LAW WHETHER CENTER SUPPORTS EXIST OR NOT, 5. SHALL BE AT LEAST 42 INCHES LONG AND SHALL BE CENTERED AT THE LEADING EDGE OF THE WATER CLOSET. 6"MAX.-------- TOE CLEARANCE ! - - - - - - < x¢ I G 1 z z N C') � I I I , ( 1 I I 1 I I 1 17" MAX LAV DEPTH 8" MIN KNEE CLEARANCE HANDICAP SINK DETAIL SINK 1. SINK SHALL BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" FROM THE FINISH FLOOR. EACH SINK SHALL BE MINIMUM OF 6 1/2" DEEP. 2. CLEAR FLOOR SPACE RESTROOMS SHALL HAVE AN UNOBSTRUCTED SPACE OF AT LEAST 60" IN DIAMETER OR 52" BY 72" FINISH INSIDE DIMENSIONS ADJACENT TO THE LAVATORY AREA. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE LAVATORY OR SINK PLUMBING FIXTURE SCHEDULE WATER CLOSET AMERICAN STANDARD 2857.016.02 ADA TOILET WITH MANUAL FLUSH CHROME FITTINGS OR EQUAL AMERICAN STANDARD 0321.023.020 WALL MOUNT COLOR: WHITE LAVATORY SGL LEVER HANDLE 6114.110.002 WITH TEMP CONTROL FAUCET, P TRAP WRAP KIT OR EQUAL TEMP CONTROL UNIT HONEYWELL AQUASTAT CONTROLLERS L6006 ON DEMAND W.H. STIEBEL ELTRON # 232098 2.4 WT 0.40 GPM 2.5 POINT NOTE: MIX VALVE FOR TEMP CONTROLL ON ALL LAV FAUCETS PLUMBING PLAN 1/4" = 1' 0" PLUMBING NOTES: CONTRACTOR DO SITE VISIT PRIOR TO ESTIMATING. 'OR TO CUT SLAB TO INSTALL NEW SANITARY AND ES. CONTRACTOR TO DETERMINE THE BEST CUT 3, PIPING SIZE AND VENT SIZE AS NEEDED. DISTURBED SOIL, TERMITE TREAT AND PATCH NEEDED ARKAY ENGINEERING INC. STRUCTURAL ENGINEERS RICHARD L. KIDDEY P.E. FLORIDA LICENSE NUMBER 37296 i I 44 V M N M M Q 0 _I LL z U r-- (D w o- Ul 0 N W Q co c\l Z Q � W in U m M LL 0)u- �0 vi N co CM >r r m Ocnri m�fl� m42cu z � Z `—° d 0 Q1 - w Lu 0 Z_ m to Is � � �- i -0 Y �3 M 70 LL � m-c co In (P a- d) OC w Q 0 z 0 SQ w ry N N } L N N m r ry z o LIJ 0 O z co 0 LL CD > Z 0 ®H OW�LL 0ON= W�N�" � Ov LL W W Lo Q p c/ J J w N �' Q w I- Z W _ F- RENOVATION AREA 3588 SQ. FT. SHEET P1 I HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE FLORIDA BUILDING CODE 2020 7 TH EDITION AND ASCE 7-16 FOR 139 MPH WIND ZONE RISK CATEGORY 11 ARKAY # 19859