HomeMy WebLinkAbout6923 Gall Blvd (3)a FIRE ALARM SPECIFICATIONS & GENERAL NOTES FIRE ALARM SYSTEM TESTING, INSPECTION, INSTRUCTION r_ E I. GENERAL SCOPE: A. THIS PROJECT WILL REQUIRE THE INSTALLATION OF A SILENT KNIGHT 6808 ADDRESSABLE FIRE ALARM SYSTEM FOR A 3 - STORY SELF STORAGE FACILITY. AS INDICATED ON THESE PLANS A NON-PROPRIETARY SYSTEM SHALL BE INSTALLED. THE FIRE ALARM SYSTEM SHALL MONITOR THE FIRE SPRINKLER SYSTEMS, BDA SYSTEM, AND INTERFACE WITH THE ELEVATORS FOR ELEVATOR RECALL AND SHUT DOWN AS REQUIRED BY NFPA 72, 11. REQUIREMENTS A. THE INSTALLATION SHALL CONFORM TO THE INTENT OF NFPA 72 (2016 ED.), FLORIDA FIRE PREVENTION CODE (2020 ED.), THESE PLANS, AND APPLICABLE REFERENCED DOCUMENTS. B. SECONDARY POWER SHALL CONSIST OF RECHARGEABLE BATTERIES HAVING A CAPACITY TO POWER THE ALARM SYSTEM FOR A PERIOD OF 24 HOURS IN A STANDBY MODE AND OPERATE ALL NOTIFICATION APPLIANCES FOR 5 MINUTES AT THE END OF THE 24 HOUR PERIOD. C. ALL CIRCUITS SHALL BE "POWER LIMITED". THE CIRCUIT TYPES SHALL BE INSTALLED AS INDICATED BELOW: SIGNALING LINE LOOP: CLASS "B" INITIATION DEVICE CIRCUITS (IDC'S): CLASS "B" NOTIFICATION ALARM CIRCUITS (NAC'S): CLASS "B" D. WALL -MOUNTED NOTIFICATION HORN/STROBES ARE TO BE MOUNTED SO THAT THE ENTIRE LENS OF THE DEVICE IS NO LESS THAT 80" AFF AND NO GREATER THAN 96" AFF. CEILING -MOUNTED NOTIFICATION DEVICES ARE TO BE MOUNTED AT A MAXIMUM HEIGHT OF 30 FT. (AS INDICATED ON THE PLANS) E. ALL NEW PULL STATIONS SHALL BE INSTALLED AT 48 INCHES ABOVE THE FINISH FLOOR. F. ALL WIRING CONNECTIONS ARE TO BE IN SINGLE, DOUBLE, TRIPLE OR 4 INCH ELECTRICAL BOXES, AS NEEDED. WIRING CONNECTIONS OUTSIDE OF ELECTRICAL BOXES WILL NOT BE ALLOWED. G. ALL WIRING ON THE INITIATION AND NOTIFICATION CIRCUITS ARE SUPERVISED POWER LIMITED. H. SURGE SUPPRESSION DEVICES SHALL BE INSTALLED ON ALL CIRCUITS THAT ENTER OR EXIT THE BUILDING. TYPICAL DEVICES ARE LISTED BELOW: PANEL POWER: DITEK MODEL DTK-120HW, EDCO (OR EQUAL) INITIATING CKTS: DITEK MODEL DTK-2LVLP-F, EDCO (OR EQUAL) PHONE LINES: DITEK MODEL DTK-MRJ3ISXCPWP, EDCO (OR EQUAL) I. STROBE CIRCUITS SHALL BE SYNCHRONIZED EITHER THROUGH THE MAIN FACP OR SEPARATE SYNCHRONIZATION MODULES (AS NECESSARY). J. FIRE ALARM PATHWAY SURVIVABILITY REQUIRED FOR THIS PROJECT (NFPA 72, CHAPTER 12): PATHWAY LEVEL 1 REQUIRED FOR: PANEL POWER CONDUCTORS (120 VAC) NETWORK\COMMUNICATIONS BETWEEN PANELS PATHWAY LEVEL 0 REQUIRED FOR: SIGNALING LINE LOOP CIRCUITS (SLC) INITIATION DEVICE CIRCUITS (IDC) NOTIFICATION APPLIANCE CIRCUITS (NAC) DEVICE POWER TO NOTIFICATION OR INITIATION DEVICES 111. CONDUIT AND WIRE A. CONDUIT: 1. CONDUIT INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), LOCAL AND STATE REQUIREMENTS. 2. CONDUIT FILL WILL NOT EXCEED 40 PERCENT OF INTERIOR CROSS SECTIONAL AREA WHERE THREE OR MORE CABLES ARE CONTAINED WITHIN A SINGLE CONDUIT. 3. CABLE MUST BE SEPARATED FROM ANY OPEN CONDUCTORS OF POWER, OR CLASS 1 CIRCUITS, AND SHALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX OR RACEWAY CONTAINING THESE CONDUCTORS. B. WIRE: 1. ALL FREE -WIRED FIRE ALARM WIRING SHALL BE FPL TYPE CABLE. WIRING INSTALLED IN CONDUIT SHALL BE A MINIMUM OF THHN. UNDERGROUND WIRE SHALL BE INSTALLED IN CONDUIT AND SHALL BE A MINIMUM OF THWN. 2. WIRING WILL BE IN ACCORDANCE WITH LOCAL, STATE AND NATIONAL CODES (E.G., NEC ARTICLE 760). THE NUMBER AND SIZE OF CONDUCTORS SHALL BE AS INDICATED ON THESE PLANS, BUT SHALL NOT BE LESS THAN #18 AWG FOR INITIATING DEVICE CIRCUITS (INCLUDING SIGNALING LINE CIRCUITS) AND #16 AWG FOR NOTIFICATION DEVICE CIRCUITS. 3. ALL FIELD WIRING OF INITIATION AND NOTIFICATION CIRCUITS ARE TO BE COMPLETELY SUPERVISED BY END OF LINE DEVICES, PER THE MANUFACTURER'S LITERATURE. 4. HORIZONTAL WIRE RUNS ABOVE CEILINGS: HORIZONTAL WIRE RUNS IN AREAS CONTAINING DROP CEILINGS MAY BE 'FREE -WIRED' IF SUPPORTED BY THE BUILDING STRUCTURE. LAYING WIRE ON THE CEILING OR INADEQUATE SUPPORT OF WIRING FROM THE STRUCTURE WILL NOT BE ALLOWED. 5. VERTICAL AND HORIZONTAL WIRE RUNS IN OPEN STRUCTURE AREAS: ALL WIRING IN "OPEN STRUCTURE AREAS" ON THIS PROJECT SHALL BE INSTALLED IN CONDUIT. 6. VERTICAL WIRE RUNS: VERTICAL WIRE RUNS TO DEVICES, PANELS, ANNUNCIATORS, ETC. SHALL BE INSTALLED IN CONDUIT PER THE NATIONAL ELECTRICAL CODE. C. TERMINAL BOXES, JUNCTION BOXES AND CABINETS: ALL BOXES AND CABINETS SHALL BE UL LISTED FOR THEIR USE AND PURPOSE. D. THE FIRE ALARM CONTROL PANEL IS TO BE CONNECTED TO A SEPARATE DEDICATED BRANCH CIRCUIT, MAXIMUM 20 AMPERES. THIS CIRCUIT SHALL BE LABELED AT THE MAIN POWER DISTRIBUTION PANEL AS FIRE ALARM. FIRE ALARM CONTROL PANEL PRIMARY POWER WIRING SHALL BE 12 AWG. THE CONTROL PANEL ',CABINET SHALL BE GROUNDED SECURELY TO EITHER A COLD WATER PIPE OR GROUNDING ROD. A 120 VOLT SURGE SUPPRESSER SHALL BE INSTALLED ON THE AC POWER AND GROUNDED PRIOR TO ENTERING THE FIRE ALARM CONTROL PANEL. THE BREAKER FOR THE ALARM CIRCUIT SHALL BE RED IN COLOR, OR PAINTED RED, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED WITH A PERMANENT LABEL AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT VIA A LABEL INSIDE THE FACP COVER. IV. EXECUTION A. INSTALLATION: 1. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, NFPA 72, LOCAL AND STATE CODES, AS SHOWN ON THE DRAWINGS, AND AS RECOMMENDED BY THE MAJOR EQUIPMENT MANUFACTURER. 2. DURING CONSTRUCTION MEASURES SHALL BE TAKEN TO IPROTECT SMOKE DETECTORS FROM CONTAMINATION AND PHYSICAL DAMAGE UNTIL CONSTRUCTION ACTIVITIES ARE COMPLETE. V. PROGRAMMING 1. A BASELINE PROGRAMMING MATRIX HAS BEEN INCLUDED ON THESE PLANS. 2. ALL SMOKE DETECTORS SHALL BE PROGRAMMED FOR ALARM VERIFICATION. VI. TESTING & FINAL INSPECTION 1. SEE "FIRE ALARM SYSTEM TESTING, INSPECTION, INSTRUCTION" NOTES ON THIS SHEET FOR MINIMUM REQUIREMENTS. VII. SYSTEM MONITORING 1. ALARM, SUPERVISORY, AND TROUBLE SHALL BE MONITORED VIA A REMOTE SUPERVISING STATION, AS INDICATED ON THESE PLANS. VIII. GENERAL 1. THE VOLTAGE DROP CALCULATIONS SHOWN ON THE PLANS ARE BASED ON THE CIRCUIT ROUTING SHOWN. MAJOR CHANGES TO THE CIRCUIT ROUTING SHOWN MAY NEED TO BE JUSTIFIED BY THE FIRE ALARM CONTRACTOR WITH ADDITIONAL CALCULATIONS. 2. THE ALARM CONTRACTOR WILL BE REQUIRED TO SUBMIT A "RECORD OF COMPLETION", PER NFPA 72, TO THE OWNER PRIOR TO FINAL PAYMENT. 3. THE FIRE ALARM CONTRACTOR IS REQUIRED TO MAINTAIN A COMPLETE AND ACCURATE AS -BUILT DRAWING SET. UPON FINAL COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL SUPPLY THE OWNER WITH AN AS -BUILT SET. AS-BUILTS SHALL INDICATE ALL CHANGES TO THE ORIGINAL LAYOUT INCLUDING, BUT NOT NECESSARY LIMITED TO, AS -BUILT DEVICE LOCATIONS, PANEL LOCATIONS, CIRCUIT ROUTING, CONDUIT ROUTING, JUNCTION BOX LOCATIONS, PANEL CIRCUIT BREAKER LOCATIONS, ETC. 4. ALL CONDUIT AND WIRING PENETRATIONS THROUGH FIRE RATED BARRIERS (INCLUDING WALLS AND FLOORS), AND SMOKE BARRIERS THAT EXTEND FROM FLOOR TO CEILING, SHALL BE SEALED WITH A UL LISTED FIRESTOPPING PENETRATION SYSTEM. THE MINIMUM PENETRATION RATING FOR FIRE RATED BARRIERS SHALL MATCH THE RATING OF THE WALL \ FLOOR \ BARRIER. SMOKE BARRIERS SIMPLY NEED TO BE SEALED TO PREVENT THE PASSAGE OF SMOKE THROUGH THE ASSEMBLY. 5. PRIOR TO FINAL PROJECT COMPLETION, ALL DEVICES SHALL BE LABELED ON THEIR EXTERIOR HOUSING SO THAT THE DEVICE NUMBER CAN BE DETERMINED BY VISUAL INSPECTION. ALL FIRE ALARM DEVICES, INCLUDING BUT NOT LIMITED TO DETECTORS, MODULES, HORNS, SPEAKERS, AND STROBES, $HALL HAVE A LABEL AFFIXED TO THEIR FRONT SURFACE. THESE LABELS SHALL CONFORM TO THE FOLLOWING: I. THE LABELS SHALL HAVE LETTERS AT LEAST 1/4" HIGH. II. THE LABELS SHALL MATCH THE DEVICE NUMBER SHOWN ON THE AS -BUILT DRAWINGS. 111. THE LABELS SHALL BE IDENTICAL TO THE DEVICE NUMBER PROGRAMMED INTO AND DISPLAYED ON THE FACP AND ALL REMOTE ANNUNCIATORS. AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE INSTALLER SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY IN EVERY RESPECT. ALL TESTING SHALL BE COMPLETED IN ACCORDANCE WITH NFPA 72. THE LOCAL FIRE AUTHORITY HAVING JURISDICTION, OR THEIR ASSIGNED REPRESENTATIVE, SHALL WITNESS THE SYSTEM TESTING. FIRE ALARM SYSTEM TESTING A. PROVIDE THE SERVICE OF A COMPETENT, FACTORY -TRAINED ENGINEER OR TECHNICIAN AUTHORIZED BY THE MANUFACTURER OF THE FIRE ALARM EQUIPMENT TO TECHNICALLY SUPERVISE AND PARTICIPATE DURING ALL OF THE ADJUSTMENTS AND TESTS FOR THE SYSTEM. REPRESENTATIVE MUST BE STATE CERTIFIED FIRE ALARM CONTRACTOR/INSTALLER. 1. BEFORE ENERGIZING THE CABLES AND WIRES, CHECK FOR CORRECT CONNECTIONS AND TEST FOR SHORT CIRCUITS, GROUND FAULTS, CONTINUITY, AND INSULATION. 2. CLOSE EACH SPRINKLER SYSTEM FLOW VALVE AND VERIFY PROPER SUPERVISORY ALARM AT THE FACP. 3. VERIFY ACTIVATION OF ALL FLOW SWITCHES. 4. OPEN INITIATING DEVICE CIRCUITS AND VERIFY THAT THE TROUBLE SIGNAL ACTUATES. 5. OPEN AND SHORT SIGNALING LINE CIRCUITS AND VERIFY THAT THE TROUBLE SIGNAL ACTUATES. 6. OPEN AND SHORT INDICATING APPLIANCE CIRCUITS AND VERIFY THAT TROUBLE SIGNAL ACTUATES. 7. GROUND ALL CIRCUITS AND VERIFY RESPONSE OF TROUBLE SIGNALS. 8. CHECK PRESENCE AND AUDIBILITY OF TONE AT ALL ALARM NOTIFICATION DEVICES. 9. CHECK EACH STROBE DEVICE TO VERIFY THAT THE SELECTABLE STROBE OUTPUT HAS BE SET AT THE PROPER CANDELA RATING, AS SHOWN ON THE PLANS. 10. CHECK INSTALLATION, SUPERVISION, AND OPERATION OF ALL INTELLIGENT SMOKE DETECTORS USING THE WALK TEST. 11. POWER LOSS TESTING SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 72. TEST LOSS OF PRIMARY POWER AND SYSTEM RESPONSE, AS REQUIRED BY NFPA 72 (2016), CHAPTER 14. 12. EACH OF THE ALARM CONDITIONS THAT THE SYSTEM IS REQUIRED TO DETECT SHOULD BE INTRODUCED ON THE SYSTEM. VERIFY THE PROPER RECEIPT AND THE PROPER PROCESSING OF THE SIGNAL AT THE FACP AND THE CORRECT ACTIVATION OF THE CONTROL POINTS. 13. WHEN THE SYSTEM IS EQUIPPED WITH OPTIONAL FEATURES, THE MANUFACTURER'S MANUAL SHOULD BE CONSULTED TO DETERMINE THE PROPER TESTING PROCEDURES. THIS IS INTENDED TO ADDRESS SUCH ITEMS AS VERIFYING CONTROLS PERFORMED BY INDIVIDUALLY ADDRESSED OR GROUPED DEVICES, SENSITIVITY MONITORING, VERIFICATION FUNCTIONALITY AND SIMILAR. 14. FINAL TESTING SHALL BE IN THE PRESENCE OF THE LOCAL FIRE MARSHALL, OR FIRE INSPECTOR, AND WARRANTY SHALL BEGIN ON DATE OF ACCEPTANCE BY LOCAL FIRE MARSHALL. FINAL INSPECTION A. AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE MANUFACTURER OF THE [MAJOR EQUIPMENT SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY IN EVERY RESPECT. REPRESENTATIVE SHALL BE A STATE CERTIFIED FIRE ALARM CONTRACTOR/INSTALLER. INSTRUCTION A.PROVIDE INSTRUCTION, AS REQUIRED, FOR OPERATING THE SYSTEM. "HANDS-ON" DEMONSTRATION OF THE OPERATION OF ALL SYSTEM COMPONENTS SHALL BE PROVIDED. B. THE CONTRACTOR, AND/OR THE SYSTEMS MANUFACTURER'S REPRESENTATIVE, SHALL PROVIDE A TYPE WRITTEN "SEQUENCE OF OPERATION" TO THE OWNER. PROVIDE A COPY OF THE "SEQUENCE OF OPERATION" AT EACH FACP LOCATION. C. THE CONTRACTOR SHALL PROVIDE A DEVICE LAYOUT SKETCH AT AT EACH FIRE ALARM CONTROL PANEL, TO INDICATE FLOOR PLAN, FIRE ALARM DEVICE LOCATION, ADDRESS AND DEVICE LEGEND FOR EASE OF ALARM LOCATION. THE FIRE ALARM FLOOR PLAN SHALL BE MOUNTED IN A FRAME. FIRE ALARM DEVICE LEGEND SYMBOL QTY DEVICE DESCRIPTION MAKE / MODES DEVICE SPECIFIC NOTES CIO w Z m U FACP 1 FIRE ALARM CONTROL PANEL SILENT KNIGHT 6808 Z ® 1 CELL / ID COMMUNICATOR NAPCO STARLINK DIALER PROVIDED BY OTHERS a z 0 Q 1 WEATHERPROOF P2RK DEVICE TO BE 'RED' I WP HORN / STROBE (WALL MOUNTED) O z 0 Of 2 MANUAL PULL STATION SK-PULL-SA INSTALL AT 48" AFF z 0 v_ 11 PHOTOELECTRIC SMOKE DETECTOR SK-PHOTO-W CEILING MOUNTED DEVICES TO BE 'WHITE' Z `''P Q�F 2 135' FIXED HEAT DETECTOR SK-HEAT-W CEILING MOUNTED DEVICES TO BE 'WHITE' Z ®WP 2 WEATHERPROOF 135' FIXED HEAT 302 SERIES INSTALLED IN ELEVATOR PIT F DETECTOR AIM 16 ADDRESSABLE MONITOR MODULE SK-MONITOR, SK-MONITOR2 MOUNT WITH -IN 3 FEET OF INTERFACE POINT O® 8 ADDRESSABLE RELAY MODULE SK-RELAY MOUNT WITH -IN 3 FEET OF AHU INTERFACE POINT C3 p FLOW SWITCH TAMPER SWITCH -JVVL- END -OF -LINE RESISTOR (EOL) SUPPLIED BY PRODUCT VENDOR INSTALLED AT END OF CIRCUIT LINE 8-0 SURGE SUPPRESSOR ❑K KNOX BOX ❑J JUNCTION BOX FIRE ALARM ABBREVIATIONS LEGEND AH = AIR HANDLER MAX = MAXIMUM C = CEILING MOUNTED MIN = MINIMUM COR = CONTRACTING OFFICER REPRESENTATIVE MNS = MASS NOTIFICATION SYSTEM EXT = EXISTING N/A = NOT APPLICABLE WP = WEATHERPROOF NAC = NOTIFICATION APPUANCE CIRCUIT XP = EXPLOSION PROOF NDU = NETWORK DISPLAY UNIT AFF = ABOVE FINISHED FLOOR NEC = NATIONAL ELECTRIC CODE AHJ = AUTHORITY HAVING JURISDICTION NFPA = NATIONAL FIRE PROTECTION ASSOCIATION ALM = ALARM NIC = NOT IN CONTRACT ANN = ANNUNCIATOR NTS = NOT TO SCALE BMS = BUILDING MANAGEMENT SYSTEM PAP = PRE -ACTION PANEL CD = (eg. 15CD) CANDELA PED = PHOTOELECTRIC SMOKE DETECTOR CSFM = CALIFORNIA STATE FIRE MARSHAL SLC = SIGNALING LINE CIRCUIT DET = DETECTOR SMK = SMOKE EOL = END OF LINE SUPV = SUPERVISORY EPO = EMERGENCY POWER OFF TRBL = TROUBLE FACP = FIRE ALARM CONTROL PANEL IS = TAMPER SWITCH FATC = FIRE ALARM TERMINAL CABINET TYP = TYPICAL FBO = FURNISHED BY OTHERS UFC = UNIFIED FACILITIES CRITERIA FCC = FIRE COMMAND CENTER LINO = UNLESS NOTED OTHERWISE FAA = FIRE ALARM ANNUNCIATOR VCC = VOICE COMMAND CENTER FSD = FIRE SMOKE DAMPER WF = WATER FLOW HT = HEIGHT W = WATT HVAC = HEATING, VENTILATION, & AIR CONDITIONING W/ = WITH IDC = INITIATION DEVICE CIRCUIT W/O = WITHOUT IMS = INFORMATION MANAGEMENT SYSTEM z O In Li O_ w Q 0 O z �ocs a���.,, ••'' �''•��2' =Z * W :U Q O'Z= F tn v C:4- N O O m 0 O O .a1 Li >, V N O ro 4- T !V � `- Q W 0 O z a �F zrzwa�}�., N o�z��wWNau' 2w�¢ Ou, o a�OU s zowz w} Z z O c-7 °'wwazwo¢ =n�F zz��ozw�>u z 3 z m w -'n�_z �mw w= _8 o �I of rt a U Z Q a m L V' Y ^ n Z LL �I Fy _J LLI p9 ui Z Z a R mh b^ �E� m a NSb� nyOti U w a U Z Z U w n lb g t < m`°Q.°' % T y�i I" 2m r'l WN�N^ O q, T m U C w w F 3Cim� ii U a [ w 3 a w 0 V z � n � morn 3!* n* om T 7 O� myrn S n �> MrNl� >7 m -�4 O fV r it Ip Ip - 2 ni Q ,� rlll Q M W m U_ M Q,>rn 03 4t m 11, 1- m A 0 Jza 0 a.. m w Q � OLn O T M J fV O rZ a 0 U Z 0 Q 0 L0 w O EL EL Ld FIRE ALARM DRAWING LEGEND SHEET # DESCRIPTION FAO FIRE ALARM GENERAL NOTES AND SPECIFICATIONS FAt FIRE ALARM PLAN FIRST FLOOR FA2 FIRE ALARM PLAN SECOND FLOOR FA3 FIRE ALARM PLAN THIRD FLOOR FA4 FIRE ALARM DETAILS FA5 FIRE ALARM RISER DIAGRAM AND •CALCULATIONS Lw (10 Ld Z LLI I - O zz a O Q � >M �0 LLI LL,Q F- j -� o u- W U m Z o _j_ a= Ld - Caw o (D N = c�° LLI g fb � Q Q T J LLI LL_ u w U C W a p DESIGNED BY AGO DRAWN BY AGO CHECKED BY RWL PROJECT NO./CAD CODE 2023-2601 DATE 06/27/2023 i DRAWING NO. FAO ME w (D- --------------- IIIII L-- — - — - — - — - ------------- - - — - — - — - — - — - — --------------- II II LOADING AREA SLC 2 -23 0 — - — - — - — - — - — - — - L , ELEVATOR-1 T 109 IID-25 WP E RELAY/MONITOR RELAY/MONITOR 1ID-28 AIM MODULES I I D-21 SLCI I ASSOCIATED IIII-WITH S ELEV. 1 it ELEVATOR MECH. RM. RECALL/CONTROL IID-31r 11 B-26 F — - — - — - — - — - — - — - III II: III 11' III 11 I. - — - — - — - — - — - — - Iljl 0 Ilj — - — - — - — - — - — - — -O - tLILY MECH.'�RM. 104 1ID- 11 -15 Lc SLC IS LC LC SLC M WP SLC L F1 I SID Lil ly 7 MODULES t LOADINGASSOCIATED -17 AREA WITH I Ii IID-21 J - ----- LOADING ELEVATOR ELEVATOR-2 Al IW RECALL/CONTROL SLc I I Lit L it -1 1 _77=1 I qL - - - - - - If - - - - - - - i II It YI Li II II II 5.8 (21 - Al LID-6 22 11sLc 1081 - A,,M BOA SYSTEM AIA I ID-8 105 MONITOR AIM MODULES Al Sl`lRINKLER LR' 103 5 102 if I 7 d 103 K — - — - — - — - — - — - 104 I Bi 101 ELECTRICAL All ii /_ M. SLC RM. 1• A07 2 01- --- lur j Los a STAIR-2 1 7- lit -4 1 DAIM SL Z LD 103 109 11 11 . AMIM IIIV) ar All D-5 :4 > Li L L II 104111 fit III it Li - — - — - — - — - — - < i II Il -- — - — - — - — - — - — - — - — - -- 0 -f =77 7777=7= 1117777_7—_ =73 T A— fill < - — - — - — - — - — - -- 5 J f III !I d it 'I il L 1 - — - — - — - — - — - — p on, I II z >i if !I II I Lj II III i — - — - — - — - — - — ---- z aj < IF a . �83 0 3 6 L u if tz --0 �2 0 > 16 wQ — - — - — - -- - — - — - lilt ____ __ - __ - z z w w� = I- w :j STORAGE Z5 C) — - — - — - — - — - — --- 1:: AGEIL TL_ SLC z w L<L - - - - - - 77 = —7=r, L_ 71 _7 -7 7173 L I if it 0 Z LLu) LL lift I if - - — - — - — - — - — - — J_ _4 — — - -— - — - — - =4 it I l�• I ,; �, - - — - - ifIIIF - — - — - — F LLI Z !if w N t III w Z z k !!I it lit - 0 it z 1it ui :it I u ILI - — - — - — - - — - — - — — - — - — - - — - — - — -- - — - — ---- - — - — - — - - — - — - — --- -- — - — - — - — - — - — - - — - — - — - — - — - F UJI 0 lit if 7 u s:_ II if o < — i— — — A — — — J---- -L--- --1-- - ------- ---- ----- - --------- -- ------_- - — - - - — - — - — — - - -- - - - -- y ? y F— — — i: LL F I'll !If if Lj 10 II I'll II' - - - - - _-- -_._-- -71 -:1 A — — - — - — - — - — _T 7 L - - - - - - - — — — — — -- — — — — L - — — — — — — JTF_ --71 1 - --- - - IT !T TL_� 0 t I 4,1 I !TI !1 jJ III - - - - - - - - - - - -- - — - — - — - - — - — - — If II `JTAl I Flo,] � w I� Iw w � L�_� L — - — - --- — - — - — - - — - — - -- - - - - - - --------------- ---------------- 2 10 11 12 13 14 15 16 17 18 19 260 FIRE ALARM WIRE LEGEND SYMBOL CIRCUIT DESCRIPTION CONDUCTORS (AWG) MINIMUM RATING CABLE TYPE* SLC SIGNALING LINE LOOP 2 - #18 FPL TW ---- ---- ---- ---- RT REMOTE TEST SWIITCH ---- ---- ---- RAP COMMUNICATIONS CIRCUIT (RAP) 4 - #18 FPL TW / SH ---- ---- ---- ---- NAC COMBO AUDIBLE/VISUAL CIRCUIT 2 - #16 FPL TW ---- ---- ---- ---- _AC 120 VAC POWER CIRCUIT 3 - #12 ---- TW DC 24 VDC POWER CIRCUIT— 2 - #14 FPL TW ---- ---- ---- ---- ---- ---- ---- ---- x SPARE WIRE PAIR 2 - #16 FPL TW SH Y SPARE WIRE PAIR 2 - #14 FPL TW SH Z J:7 SPARE WIRE PAIR 2 - #12 FPL TW SH I - I CABLE TYPE DESIGNATIONS: TW = TWISTED, SH = SHIELDED FIRST FLOOR FIRE ALARM PLAN 2 1 0 SCALE: 1 /8" = 1 '-0" 1 1 1 CIRCUIT LABELING EXAMPLE RAP, 3NAC, SLC LONE (1) SIGNALING LINE CIRCUIT IN THIS PATH THREE (3) COMBINATION —NOTIFICATION APPLIANCE CIRCUITS IN THIS PATH ONE (1) REMOTE ANNUNCIATOR COMMUNICATIONS CIRCUIT IN THIS PATH F 1 KEY NOTE DENOTED BY THIS SYMBOL. SEE PLAN. KEY NOTE LEGEND (THIS SHEET): 101. FIRE ALARM CONTROL PANEL (FACII LOCATION, PROVIDE A SMOKE DETECTOR AT THE FACP 107. FIRE ALARM DOCUMENT CABINET PROVIDED AT FACIP. LOCATION, AS INDICATED. COORDINATE WITH OTHER AS REQUIRED BY NFPA 72, PROVIDE A DOCUMENT EQUIPMENT AT THIS WALL -MOUNTED LOCATION. CABINET WITH THE FOLLOWING APPROPRIATE DOCUMENTS IN A CABINET ADJACENT TO THE FIRE 102. CELL I COMMUNICATOR LOCATION ALARM CONTROL PANEL. CABINET SHALL BE SPACE AGE ELECTRONICS OR EQUIVALENT. 103. FIRE ALARM MANUAL PULL STATION INSTALLED AT 48" ABOVE FINISHED FLOOR. 108. PROVIDE FIVE (5) MONITOR MODULES FOR THE BDA SYSTEM, PER NFPA 72 AND THE PROJECT SPECIFICATION 104. FIRE SPRINKLER FLOW AND TAMPER SWITCH LOCATION. PROVIDE FIRE ALARM SYSTEM 109. FIRE ALARM SYSTEM CIRCUITI UP TO FLOOR MONITORING OF ALL FIRE SPRINKLER VALVE ABOVE. TAMPERS, FLOW SWITCHES, AIR PRESSURE SWITCHES, ETC., AS REQUIRED BY THE PROJECT REQUIREMENTS. 110. APPROXIMATELY 20 FEET OF SEALED, "WEATHER 105. FIRE PROTECTION BACKIFLOW PREVENTER LOCATION. PROOF", 11- DIAMETER UNDERGROUND CONDUIT RUN MONITOR THE FIRE PROTECTION BACKIFLOW FROM THE FIRE SPRINKLER RISER LOCATION TO THE PREVENTER TAMPER SWITCHES, AS INDICATED. IF NEW BACKIFLOW PREVENTER LOCATION. PROVIDE THE ARE PROTECTION BACKIFLOW PREVENTER IS MINIMUM 2-#16 AWG THWN CABLE FOR MONITORING LOCATED OUTDOORS (EXTERIOR TO THE BUILDING OF BACKIFLOW PREVENTER VALVE TAMPER SWITCHES. ENVELOPE), PROVIDE SURGE SUPPRESSION MODULES REFERENCE THE SITE UTILITY PLANS FOR THE IN THE SPRINKLER RISER ROOM TO PROTECT THE PRECISE BACKFLOW PREVENTER LOCATION. FIRE ALARM SYSTEM FROM TRANSIENT VOLTAGE SURGES. 111. ELEVATOR CONTROL EQUIPMENT LOCATION. PROVIDE FIRE ALARM INTERFACE AND CONTROL WITH THE 106. EXTERIOR NOTIFICATION DEVICE, AS INDICATED. ELEVATOR EQUIPMENT AS REQUIRED BY NFPA 72 PROVIDE ALL EXTERIOR NOTIFICATION DEVICES WITH AND THE PROJECT DESIGN DOCUMENTS. THE MANUFACTURER'S ASSOCIATED WEATHERPROOF BACK -BOX. SEAL ALL PENETRATION IN EXTERIOR WALL MEMBRANE WITH SILICON SEALANT TO ELIMINATE THE POTENTIAL FOR WATER INTRUSION INTO THE WALL OR BACK -BOX. ------------- (�) z Ln > rn _j _j IF— =u V 111 < > >- 03 u-i 03 1, --j m 0 m _j j u ;-o 0 U-1 CL co Z < 0 F- ci� 0 rn _j 114 0 co z CL < 0 C) V_ :z < 0 0 u.j (If rWn 0 C�4 0W < > Z LU > In 0 0 0 0 Z < m o u c 3-- aw < i 0 'co", Lu u u 0 Ln Lu 0- 1 a DESIGNED BY AGO DRAWN BY AGO CHECKED BY RWL PROJECT NO. ICAD CODE 2023-2601 DATE 06/27/2023 DRAWING NO. FA1 -------------- II II I III II I �— - _ K--------- I I I I II J.4 ---- — "-------- --- II. I LI i _ lil IIII i I'. I I I'I ,-,-------------- -------------------- 2 III SLC I1202 203 I. I I! III, ELEVATOR-1 i l Ir - -— I Ij, I -—-— - — - - -— i— — I, � III I I. I --- -- II --- I II' -- -- -�- +II -------------- I I I I IIII I I I I I I I I II -- - — — — — — — — — — — it I ! T --- s 12UU ---- — — — — — I!, — -- ----- ---- ----- � III T STAIR-, 2oi I � III Iw w � Ilw �I II I I I I I II I l I 1 I \\ I I I I I I 7J 7.12 8� 96 10 11 12 13 FIRE ALARM WIRE LEGEND SYMBOL CIRCUIT DESCRIPTION CONDUCTORS (AWG) MINIMUM RATING CABLE Ti SLC SIGNALING LINE LOOP 2 - #18 FPL TW RT REMOTE TEST SWITCH ---- ---- ---- RAP COMMUNICATIONS CIRCUIT (RAP) 4 - #18 FPL TW / SH NAC COMBO AUDIBLE/VISUAL CIRCUIT 2 - #16 FPL TW -- ---- ---- ---- ---- AC 120 VAC POWER CIRCUIT 3 - #12 ---- TW DC 24 VDC POWER CIRCUIT 2 - #14 FPL TW -- ---- ---- ---- ---- X SPARE WIRE PAIR 2 - #16 FPL TW / SH Y SPARE WIRE PAIR 2 - #14 FPL TW / SH Z SPARE WIRE PAIR 2 - #12 FPL TW / SH CABLE TYPE DESIGNATIONS: TW = TWISTED, SH = SHIELDED CIRCUIT LABELING EXAMPLE RAP, 3NAC, SLC LONE (1) SIGNALING LINE CIRCUIT IN THIS PATH THREE (3) COMBINATION NOTIFICATION APPLIANCE CIRCUITS IN THIS PATH ONE (1) REMOTE ANNUNCIATOR COMMUNICATIONS CIRCUIT IN THIS PATH - - i ! i I I I 16 17 18 2ND FLOOR FIRE ALARM PLAN 20 29 22 23 24 25 I I I I I I I I I I f I I z I + I I + I I i W (r + I I I I i I I 2\D-3G1 cII AIM �II 202 ." 203 - — - — - — - - — - m ji W 'lii a TI 0 - — - — - - - - ate, ^y-. o O O �� Q r�rrrrurrnma��'���tis I dj I -:- 0"aI J BOO ----- � m 'b ._ � � o i^ r� o V N 1-- W C -- �/ !I+ z _ jZ w I I I Q�zw i I MILE III W zw�ao a�a�ou 26 .., ..--- -3q— -�— — — —{ I I w Q x W z mu O w x F' z W z I I! Z z � II II z 2 W�Na6QC7�m W o II Z W -- t-�'----a I' ---------� H 1 (� u VW m II y barn I I i( �I G.2 W �N b^ � E �- ---- — - - - - - --� - — - --- - - - --- ('] W N n�nOh o -�'-� -- - - - - - _ - ,. --- --- Z Z , U CO .� W Z W II I I � Z n --- _--Lu I1 I I F o h+ w W I uT y LIL qT III �I IT I ,IIII I Z - M J M -® - - = >_ �>�. m 'Nm J Q 00 O W W m� lli ----'II--- 5I- Z O ----- I- — - - — —- ------- ----o (i L[) JJ H m `' Q m Iv 0 ! IIII Ijl �I III II''1 II'I z LLJ -- - -- o Q I , Ld I i i I L, I I I I I + it I V z O 20 21 22 23 24 25 0 N < .1 0 j M z SCALE: 1 /8" = 1'—i ?} n a I MUNI SCALE, 1/8' = 1'-0' 0 KEY NOTE DENOTED BY THIS SYMBOL. SEE PLAN. KEY NOTE LEGEND (THIS SHEET): 201. FIRE SPRINKLER FLOW AND TAMPER SWITCH LOCATION. PROVIDE FIRE ALARM SYSTEM MONITORING OF ALL FIRE SPRINKLER VALVE TAMPERS, FLOW SWITCHES, AIR PRESSURE SWITCHES, ETC., AS REQUIRED BY THE PROJECT REQUIREMENTS. 202. FIRE ALARM SYSTEM CIRCUITS) UP TO FLOOR ABOVE. 204. FIRE ALARM SYSTEM CIRCUITS) DOWN TO FLOOR BELOW. _1 W W 0 �O mvi J J LL. ce ZO 0 Ll �z Q V Nz W .�pN Q0 W li LLJ J V u W 0 V 2 0 DESIGNED BY AGO DRAWN BY AGO CHECKED BY RWL PROJECT NO./CAD CODE 2023-2601 DATE 06/27/2023 DRAWING NO. F^A2 (`) ----- - ( ) - — - — - — - — - - — (�J - --- --- - � - - - --- - (J---------- -- 5 8 � � 7fIi2 � � 10 11 12 13 14 15 16 17 18 19 i I I I I I I I I i 'I II i I I I I I I I I I I i I I I I I I I I � --------- --- - - - - - - -— -- --- _ I - - - - II - -- III � � ,III ' J !!I IIII II II I II -- - I -- ,I el— IIII �I i I 2 3ID-4 ELEVATOR-2 II I III •'----- ' II iJ --- ---- ------;�---- --- ----� ------ ------T�------ - - -—-—- - - - - —- — �I -- ------------ --- rt----------- w III I''.I ICI �I I'll -77- ill -- _ -- ---- ----- ----- ---- 1 I I I ill I�'� IIII I I III -- - --- ---- L- --- ---- - - -----1 - - --! I I I I I 1 300 1 1 1 1 1 1 1 1 i In ii II I i u tl J L,I I III I itlllt 1 IIII u 1 i 1 l I I I I � I! `g =� 1''�'• W a J.4 >z aeo 11 L, /H//flllll4iiii,`` N O M 1 >. u M '11 I III i C r II I II y W u, -- --- --- _ -�- — - w ' r- IZ •— -- -------- 0 0 iE it II IIII a w 'I N wO t7 za�wo v�zQw j IT - - V I I I III ,I,. l w 4= �- Z WHO V `-� O v�ao V I' II ====Fozwz za zmwF-ral-F"-o �� t7 ww ZZ p0¢in W H �_—_____{I-j w -W G.2 .. U m W m �� --— - — - — - — Z IL i �I II LL LL . 4 "'� oh W Z 105 �^ .}II ill i �J W N �O a Z U o �C W Zh�N q t ''a -�—_-a�--�_- ---—- — - -—CE u W` Al T� I : 1 I I = II= I ----- -il- ----_ I -__-- ----- a=l l =----- 1 _-- _- _-_-_ �I� - III' IIII II if �I II I'I I I 'I I'I!I I III J I ' II II II — I'll I --- �I-----�--------�I---- ------ ��_—-I� —,�I-�------ '-----'l�l�----�-----'Il----- i�—1---�-----�-- !�1---� ,-�1-- --------�--------- D T I I IIII II -. --- a ---. -- —_ --III U I r-- -_ N I' I I I i I I I I I I I I I I I I II I _ _ " M __ - - - _ -- -- _- __ -=- _—_ _-__ - -_-_ -_ -- ---_- ---__ -_---- J l Illi Ij !r l� l'I !I� III li r w M o `�' - - - - - - - — - - - - - - - - - — - — - - - - — - - - — - - - - - - - — - - — — - — - — - - - - - — - - — - - :itI- — - — - - - — - — - — - — - — - - — - \ / �•• W V J M I 1 m m I It STAIR 1 I I ) I I I ) ( ( I N J= Q00 301 IJ..I co j!I III III I l III I I J I I Ij z o Ln it M J .; I I= ----I--- -- I - i - I I ---I--=-- I-- --- I -----I--- I---- I-----_----- 1------ I---- I---- 1------- I--------------� � m a 1 I I I I I I I I I I I I I I I d I I I I I I I I I I I I I W I I I I I I I I I I I I I I I I I I 76 I 4 I I I I I I I ! I I I I I I \ I I I I I I I I I I I 7I2 �8) 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 3RD FLOOR FIRE ALARM PLAN NT SCALE: 1 f 8" = 11 1 1 1 4 1 1 V FIRE ALARM WIRE LEGEND SYMBOL CIRCUIT DESCRIPTION CONDUCTORS (AWG) MINIMUM RATING CABLE TYPE' SLC SIGNALING LINE LOOP 2- #18 FPL TW - - RT REMOTE TEST SWITCH ---- ---- ---- RAP COMMUNICATIONS CIRCUIT (RAP) 4 - #18 FPL TW / SH NAC COMBO AUDIBLE/VISUAL CIRCUIT 2 - #16 FPL TW -- ---- ---- ---- ---- AC 120 VAC POWER CIRCUIT 3 - #12 ---- TW DC 24 VDC POWER CIRCUIT 2 - #14 FPL TW -- ---- ---- ---- ---- X SPARE WIRE PAIR 2 - #16 FPL TW / SH Y SPARE WIRE PAIR 2 - #14 FPL TW / SH z SPARE WIRE PAIR 2 - #12 FPL TW / SH CABLE TYPE DESIGNATIONS: TW = TWISTED, SH = SHIELDED CIRCUIT LABELING EXAMPLE RAP, 3NAC, SLC t LONE (1) SIGNALING LINE CIRCUIT IN THIS PATH THREE (3) COMBINATION NOTIFICATION APPLIANCE CIRCUITS IN THIS PATH ONE (1) REMOTE ANNUNCIATOR COMMUNICATIONS CIRCUIT IN THIS PATH SCALE, 1/8' = P-0' Q KEY NOTE DENOTED BY THIS SYMBOL. SEE PLAN. KEY NOTE LEGEND (THIS SHEET): 301. FIRE SPRINKLER FLOW AND TAMPER SWITCH LOCATION. PROVIDE FIRE ALARM SYSTEM MONITORING OF ALL FIRE SPRINKLER VALVE TAMPERS, FLOW SWITCHES, AIR PRESSURE SWITCHES, ETC., AS REQUIRED BY THE PROJECT REQUIREMENTS. 302. FIRE ALARM SYSTEM CIRCUITS) DOWN TO FLOOR BELOW. fLLI V Z 0 O � N W 1O o J LLJ jM Z ul J u � 0 W O O m vi O o� H �L- a= Q r,4 J a� W .o w N W = w I"_ M� U H u w O u � w 1I O 1 DESIGNED BY AGO DRAWN BY AGO CHECKED BY RVVL PROJECT NO./CAD CODE 2023-2601 DATE 06/27/2023 DRAWING NO. FA 3 FS PROJECT SPECIFIC NOTES: 1. RELAY MODULES HAVE BEEN PROVIDED IN THE ELEVATOR EQUIPMENT ROOM FOR ELEVATOR CONTROL FUNCTIONS. SEE THE PLAN VIEW LAYOUT FOR DEVICE COUNT. 2. ALL SMOKE DETECTORS ARE TO BE PROGRAMMED WITH ALARM VERIFICATION. 3. THIS CHART IS TO BE USED AS A BASIC PROGRAMMING GUIDE ONLY. ALL OTHER PANEL PROGRAMMING FEATURES SHALL COMPLY WITH NFPA 72 AND THE MANUFACTURERS INSTRUCTIONS. 1 & 2 HOUR GYPSUM WALL PENETRATION DETAIL (NOT TO SCALE) HILTI System No. W-L-1054 F Ratings - 1 and 2 Hr (See Items 1 and 3) T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/Sq Ft L Rating At 400 F - 4 CFM/Sq Ft 1. Wall Assembly -- The 1 or 2 hr fire —rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC. When steel studs are used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw —attached to the steel 3 studs at each end. The framed opening in the wall shall be 4 to 6 in, wider and 4 to 6 in. higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. clearance is present between the penetrating item and the framing on all four sides. B. Gypsum Board* -- 5/8 in. thick, 4 It wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation sholl be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. 2 Max diam of opening is 32-1/4 in. for steel stud walls. Max diam of opening is 14-1/2 in, for wood stud walls. The F Rating of the firestop system is equal to the fire rating of the wall assembly. A 2. Through —Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system- The annular space shall be min 0 in. to max 2-1/4 in. Pipe may be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater then 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit. D. Copper Tubing -- Nam 6 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe -- Nam 6 in. diam (or smaller) regular (or heavier) copper pipe. 3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in, thickness of fill material applied within the annulus, flush with troth surfaces of wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS—One Sealant *Bearing the UL Classification Mark UNDERGROUND FIRE ALARM WIRING ENTRANCE DETAIL (BACKFLOW PREVENTER) (NOT TO SCALE) SURGE SUPPRESSOR W/GROUND IN 4JUNCTION BOX --90 DEGREE PVC ELECTRICAL WIRE PULL BOX BACKFLOW DEVICE SEE CIVIL DWGS FOR DESIGN INFO. 1­_o ATERPROOF PENETRATION WEATHERPROOF PVC ELECTRICAL BOX of WITH UV RESISTANT SILICONE ti 1­_ TAMPER SWITCH X 2 U ----GRAY UV RESISTANT NON-METALLIC PVC CONDUIT Z J --PVC STRAP ANCHORED WITH TAPCON SCREWS INTO MASONRY WALL U o s DROP CONDUIT AROUND FOOTER IF 24 INCH _ COVER CAN NOT BE MAINTAINED BOX MUST BE WITHIN q AVING BACKFLOW HOUSE CU0 ¢ KEEPING SLAB f xw ce FF w X w Z O I BLDG FOOT ER DTK- GENERAL NOTES 1, THE FIRE ALARM CABLE MUST BE INSTALLED PER NFPA 70 TABLE 300.5. 2, ALL WIRING USED UNDERGROUND SHALL BE WEST PENN AQUASEAL TYPE MOISTURE RESISTANT FPL, UL RATED DIRECT BURY OR THWN TYPE INSULATED WIRE, 3. DIRECT BURIAL TYPE CABLE SHALL NOT BE INSTALLED WITHOUT RIGID NON METALLIC CONDUIT. VALUE ENGINEERING WILL NOT BE PERMITTED TO OMIT THIS FEATURE, 4, ALL CONDUIT IS TO RIDGID NON-METALLIC CONDUIT (RNC) CONSTRUCTED OF PVC WITH SOLVENT FITTING CONNECTIONS. ONLY SOLVENT GLUE LISTED FOR USE WITH THE RMC SHALL BE USED.ALL PIPE SHALL BE CLEANED PRIOR TO MAKING THE SOLVENT JOINTS. 5, INSTALL PULL STRING IN CONDUIT TO FACILITATE WIRE REPLACEMENT. FIRE ALARM SURGE PROTECTION DIAGRAM (NOT TO SCALE) 1 1 KEYNOTES: 1 1O HIGH SURGE RISK CONNECTION, TYPICAL PROTECTED COPPER CONNECTION, TYPICAL MINIMUM 3' TO () o a� o 12ovAe o' ,� a POWER ) °' SUPPLY o � 0 0 DTK-120SRD a o e (SERIES CONNECTION) E � o c 120V AC JL 1t TO FRCP 12OV AC-1 SINGLE POLE 25 AMP MAX TO FRCP AUX BRFNCER, TO BE CONTACTS OR FIELD VERIFIED ADDRESSABLE MONITOR MODULE EXAMPLE MWWTORING CIRCUff 120VAC NEUTRAL (-) i. LOAD: 48VDC, 0.6AMP 0 2 FIRE ALARM CONTROL PANEL O PROTECTED EQUIPMENT. NETWORK SURGE PROTECTION NOTES: 1. TO KEEP SURGES FROM ENTERING THE BUILDING AND NETWORK, IT IS RECOMMENDED TO PROVIDE A LAYER OF SURGE PROTECTION. THIS (HARDWIRED) HEAD END PROTECTION POINT IS THE ONLY WAY TO REDUCE THE - DTK-2MHTP RISKS ASSOCIATED WITH METALLIC CONDUCTORS CONNECTING EXTERNAL DEVICES TO INTERNAL NETWORK COMPONENTS. - DTK-2MHLPB-WB (SHORTS TO GROUND) 2.ITIS RECOMMENDED TO PROTECT EACH EXTERNALLY -MOUNTED DTK-2MHLPF-WB DEVICE FROM SURGES THAT ARE INTRODUCED ON THE METALLIC (OPENS CIRCUIT) CONDUCTORS. 3. FAILURE TO INSTALL SURGE PROTECTION DEVICES PLACES ALL INTERNAL NETWORK CONNECTED EQUIPMENT AT RISK. 4. MUST BE GROUNDED AND INSTALLED PER MANUFACTURERS INSTALLATION INSTRUCTIONS. 5. ALL CABLING ROUTED IN PLENUM SPACE SHALL BE PLENUM -RATED CABLE. 6. ALL DIRECT BURIED CABLE SHALL BE GEL FILLED CEILING GRID ELECTRICAL BACK -BOX ATTACHMENT (NOT TO SCALE) "CADDY" T-GRID BOX HANGER SUPPORT, OR EQUAL. "CADDY'—' REFERENCE NO. CEC 30-302(3). ELECTRICAL MOUNTING BOX FOR THE CEILING MOUNTED NOTIFICATION DEVICES. ACOUSTICAL TILE CEILING GRID SUPPORT FRAMING. FIRE ALARM DEVICE MOUNTING GUIDE (NOT TO SCALE) CEILING MOUNTED 24" MIN HANDICAP BEDROOM STROBE MORE THAN TWO APPLIANCES IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW SHALL FLASH IN SYNCHRONIZATION. 80" MIN 96" MAX NFPA 72 2016 (72: 18.5.5) (ADAAG) 80" ABOVE HIGHEST FLOOR LEVEL OR 6" BELOW CEILING TO THE BOTTOM OF THE STROBE. WHICHEVER IS LOWER. FINISHED FLOOR DETAIL NOTES: 3 (MIN) PER NFPA 72 A/C SUPPLY DIFFUSER AUDIO/VISUAL 3r VISUAL -ONLY DEVICES CEILING MOUNTED NOTIFICATION DEVICE (TO BE WHITE). SEE PLAN FOR LOCATION. MANUAL PULL STATION ACCEPTABLE HERE,' DO NOT INSTALL IN THIS AREA WALL MOUNTED HEAT DETECTOR — TO THE BOTTOM. WALL MOUNTED 5'-0 SMOKE DETECTOR — MAX FROM EXrr DOOR TO THE TOP. MAGNETIC D00 HOLDER 48" (ADO) I o w TO THE WORKING MECHANISM a o 48" ALSO MEETS THE REQUIREMENTS OF NFPA 72 ,�01 (72: 17.14.5) A. NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH DEVICES APPLY, AND WHICH DO NOT. B. CHECK WITH MANUFACTURER'S INSTALLATION SHEET FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF BACK -BOXES, AND WIRING REQUIREMENTS. PANEL MOUNTING ON EXTERIOR WALL (NOT TO SCALE) FOR PANELS MOUNTED ON AN EXTERIOR WALL. PROVIDE A 3/4" PLYWOOD BACK BOARD LAYER BETWEEN THE EXTERIOR WALL AND THE FIRE ALARM PANEL EXTEND PLYWOOD BACK BOARD �\ FOR ADJACENT POWER SUPPLIES \\ \ OR SUB -PANELS AS REQUIRED \ \ I Etl III ai 111 I I III III \\ I J 11 \� 11 \ \ II \\ II \ \ II LiJ F- S jam. . S v jz 5 a �+ C: 4J r, o +�+ N O Ei 0) rf3 O O _1 O .N i rv'1 0., z 0 (14 �6 o w i31 LP) r- rr i w U w��xZwoZ�Y o�zz��awa= w o wo-6.0 a= LL a 0 w o Z N 0 U � 1a_ �-a`"�z gym- Z zlaOZo �i to = W NaO¢ l7 Z5 ZW Q a U� m Z tWL 7� h� UUJI W Z PN o^ m E b .. U W .0ncnp� o Z �Uj a 0 W o�om o c L 0 C h •i u UJ <' F o N y'�nN m ro U U ro a 2� Nat,� ° 4Z Z Q * b / cah a —Lt n U- ICSI tJ V Z N V) Ln c, M :::E > M W C0 U_ r14 M urno� VI Q > o� In m�m� H = M p �=a o Lnn W W a m w Q O 1- _Z O Vi U M --1 nl z d Q 0 � r z Q O U 0 rr a W LIR! V Z0 O ' J LLJ> M —J _j U>j J J 5 �'- W W m vi .�_I J CC G Wo �� M � g 0 1— LU 10 W N w J U F U w O U it w CL p DESIGNED BY AGO DRAWN BY AGO CHECKED BY RWL PROJECT NO./CAD CODE 2023-2601 ri DATE 06/27/2023 DRAWING NO. FA4 3-#12 WIRE FROM DEDICATED 120 VAC POWER SUPPLY DITEK ➢TK-120HW SURGE SUPPRESSOR, OR EQUAL ATTACH DIETECH SURGE SUPPRESSER TO GANG BOX AND CONNECT TO ELECTRICAL GROUND OR GROUNDED COLD WATER PIPE IN PROTECTED BUILDING USING #12 WIRE. INSTALL SUPPRESSER OUTSIDE OF FIRE ALARM CONTROL PANEL AND BOOSTER POWER SUPPLY CABINETS WITH A MINIMUM OF 3 FOOT OF WIRE RUN TO PANEL. 0 o, v 0 N M O N c n+ 3 ai v� a 0 cn na N a 3 m t W O CN N r7 N 0 N cv N tl N n U Q Q E a� i 0 0 v 0 II a 0 o, i a� C.J ON -BOARD ANNUNCIATOR ® SLC IN FM+ _ SW OUT + FM PHL7N£ LINES O Q NC 01 � 4 COM� � _ SLC PROG. FR + NO NC FU O O O O 1 COM[ff] NO � e NC O Comofl NO ❑❑ a SH_ z+ o❑ 0 0 ❑❑o 0 ❑ ❑ ❑ KEY �+ B A W 3 O0 + 18 AH MAX BATTERY SIZE WITHOUT ADDITIONAL BATTERY CABINET, 12 VOLT - 12 AH 12 VOLT - 12 AH FIRE ALARM RISER DIAGRAM z O w w Q 0 0 NA Jj r-,o0 ru K f6 J 0 O c 7A z -c � M oQ o 0 N �. L! 1 < w w .Q Z Z w U w N OV t7Za V wWyiaa ~w- - 10 Z nF 0 we w�.�x F-HH z m w F_ V z��O ¢ t N zwz ZOza'^> � n J w w0 ¢t2 mw 3 v N V N n Lj 1} Q �m Z LL m W Ld Z N o n m N bad U W z 4 ° Z Li v W N v�Q� o lb Z L t,, W win^ u o U (.L %s�1 a N V) o M M W m LL N = M U M O` Ln m4t m OI==M tn J = Q _ 00 W W a m w 'L Q O F- Lr) N d pp a Q w Ll IW V rl Z 0 Q 'Q C G 00 j M cr- J w W J _ =) LL. 0 to Q z 6>LJ 0 ca vi Es 0 J J � 0 Z O = W U Lj N 0 .p W I J Q m r U g u Q W V W �-L- -' v ui a o DESIGNED BY AGO DRAWN BY AGO CHECKED BY RWVL PROJECT NO./CAD CODE 2023-2601 DATE 06/27/2023 DRAWING NO. FA5 T