HomeMy WebLinkAbout6419 Simons Rd (2)FIRE ALARM NOTES:
SEQUENCE OF OPERATION:
1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS:
A. MANUAL PULL STATION:
1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL
2 SOUND THE LOCAL AUDIBLE ALARM AT THE FACP.
3 ILLUMINATE THE ALARM RED LED.
4 SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES)
IN THE BUILDING.
B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER —
FLOW SWITCH SHALL CAUSE THE FOLLOWING:
1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL.
2 SOUND THE LOCAL AUDIBLE ALARM AT THE FACP.
3 ILLUMINATE THE ALARM RED LED.
4 SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES)
IN THE BUILDING.
C. SMOKE DUCT DETECTORS
1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL
2 SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP.
3 ILLUMINATE THE SUPERVISORY LED.
4 SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT.
D. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE
FOLLOWING ACTIONS AND INDICATIONS:
1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL
2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP.
3 ILLUMINATE THE TROUBLE LED.
ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE DISPLAYED ON
THE MAIN FIRE ALARM PANEL AS WELL AS ON ALL REMOTE ANNUNCIATOR PANELS.
ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE TRANSMITTED TO
A LISTED CENTRAL STATION.
CENTRAL STATI❑N TRANSMISSI❑N ❑F SIGNALS
— ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE
CENTRAL STATION.
— THE MEANS OF TRANSMISSION WILL BE (2) DEDICATED PHONE LINES.
— ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS:
A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION,
SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW -
DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION
(FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS
OR BUILDING NUMBER.
— THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE
THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD.
CODES & PLAN NOTES
— INSTALLATION SHALL BE IN ACCORDANCE WITH FFPC 7TH Edition, NFPA 72 2016 Edition,
NFPA 70 2017 Edition, FBC 7th Edition 2020 AND ANY OTHER APPLICABLE CODES.
— ALL NEW SYSTEMS SHALL INCLUDE A DOCUMENT CABINET.
— ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED.
— CONFIRM LOCATION OF POWER SUPPLY PRIOR TO ROUGH IN.
— REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR
RETURN SIDE), COORDINATE WITH MECHANICAL CONTRACTOR THE ACTUAL
LOCATIONS OF THE AHUs.
— ALL STROBES WILL BE SET @ 75cd UNLESS NOTED.
— CEILING HEIGHT IS 10ft UNLESS NOTED.
— FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE.
— COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF DUCT SMOKE DETECTORS
— ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT
PERMIT BY THE ELECTRICAL CONTRACTOR. FBC 107.2
24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE. IF BUILDING IS OCCUPIED
DURING THIS TEST, FIREWATCH WILL BE REQUIRED.
CEILING MOUNTED
3' (MIN)
SMOKE/HEAT
PER NFPA 72
4.
DE CTOR
24' MIN HANDICAP
A/C SUPPLY DIFFUSER /
ACCEPTABLE HERE
4"
BEDROOM STROBE
I
AUDIO/VISUAL
CEILING MOUNTED NOTIFICATION
ALL
D7DETECTO
12' (MAX)
VISUAL -ONLY
DEVICES DEVICE �TO BE WHITE).
EA
,j�
SEE PLAN OR LOCATION.
WAL
HEAT
TO THE BOTTOM.
WALL MOUNTED
MORE THAN TWO APPLIANCES
5'-0
SMOKE DETECTO
IN THE SAME ROOM OR ADJACENT
MAX FROM EXIT DOOR
TO THE TOP.
SPACE WITHIN THE FIELD OF VIEW
SHALL FLASH IN SYNCHRONIZATION.
MANUAL �—
PULL
s
STATION
REMOTE
80' MIN
® g
ANNUNGATOR
96" MAX
NFPA 72 2013
MAGNETC
D
HOLDER
(ADAAG)
80' ABOVE HIGHEST FLOOR
J
LEVEL OR 6' BELOW CEILING
Q ;
TO THE BOTTOM QU THE
x
STROBE. WHICHEVER IS LOWER.
48' (ADA)
a o
TO THE WORKING MECHANISM
Q
48" ALSO MEETS THE
REQUIREMENTS OF NFPA 72 2013
FINISHED
FLOOR
IMPORTANT NOTE
NOTE
NOT ALL DEVICES % MN ON THIS DETAIL APPLY TO THIS PROJECT. SEE
CHECK WITH MANUFACTURE'S INSTALLATION SHEET
THE PLAN MEN LAYOUT OF THE Fff ALARM SYSTEM TO VEWY *1W
FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF
DEVICES APPLY, AND *1CH DO NOT.
BACK BOXES, AND WIRING REQUIREMENTS.
FIRE ALARM DEVICE MOUNTING
GUIDE
LOW VOLTAGE WIRING
WHERE LOW VOLTAGE WIRING IS PERMITTED BY
THESE DRAWINGS AND APPROVED BY THE
LOCAL AUTHORITY HAVING JURISDICTION TO BE
FREE —WIRED, THESE WIRES SHALL BE PLENUM
RATED AND U.L. LISTED FOR THE APPLICATION.
FIRE ALARM SYMBOL LEGEND (TYPICAL)
NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW
LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH DEVICES APPLY, AND WHICH DO NOT.
FRCP
FIRE ALARM CONTROL PANEL
ANN
FIRE ALARM ANNUNCIATOR
FCPSI
NAC POWER SUPPLY
FF-A-T-C-1
FIRE ALARM TERMINAL CABINET
2
ADDRESSABLE SMOKE PHOTO DETECTOR
t
ADDRESSABLE HEAT DETECTOR
�-
ADDRESSABLE DUCT SMOKE
ADDRESSABLE RELAY
ADDRESSABLE PULL STATION
Fs
ADDRESSABLE MONITOR MODULE FOR TAMPER SWITCH
FT S]
ADDRESSABLE MONITOR MODULE FOR FLOW SWITCH
HORN/STROBE WALL MOUNT
LF
LOW FREQUENCY/STROBE WALL MOUNT
LF
LOW FREQUENCY HORN WALL MOUNT
STROBE WALL MOUNT
FSDR
FIRE/SMOKE DAMPER RELAY
REVIEW DATE
CITY OF ZEPHYRHOLLS
FIRE AND LIFE SAFETY EXAMINE
ALL WORK SHALL COMPLY WITH
NFFA CODES AND STANDARDS
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P
DEAN: P.E. ON [04.26.2022] USING A SHA-1 AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
LST. 2027-A.00
FLORIDA LOW VOLTAGE SYSTEMS
4020 W CAYUGA ST.
TAM PA, FL 33614
813-353-0831
EC 13010771
EF 20001786
r
L
M
CD
z
J
IL
O
to
cn
r�
L)
cl)
co
v 1'
uj
N
CAD DATE: 2/10/2022
NO. ISSUE/REVISION DATE
0
N 39
S TA E L
11�
I
Y,L.,;
APR 2 6 2022
SAMUEL P. DEAN P.E.
CONSULTING ENGINEER
REGISTRATION NUMBER 83915
CA # 29694
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
PHONE: (813) 961-3075
FAX: (813) 961-1031
email: sdean@beltengineering.com
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
BE IN COMPLIANCE WITH THE FLORIDA BUILDING
CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
SYSTEMS AND ASSEMBLIES ARE THE TOTAL
RESPONSIBILITY OF OTHERS.
SHEET:
FA-1
WF
.5�
tO
FIRST FLOOR
a
NORTH
MA
M-5
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P.
DEAN. P.E. ON 104.26.20221 USING A SHA-1 AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
tSt 20?-!
FLORIDA LOW VOLTAGE SYSTEMS
4020 W CAYUGA ST.
TAM PA, FL 33614
813-353-0831
EC 13010771
E F 20001786
Lo
�
�
0
�
M
M
Z
Cf)
J
LL
U)
Z
m0co
0
J
J
_
_
W
N
CAD DATE: 2/10/2022
NO. ISSUE/REVISION DATE
Nd- w ^"J
O• ST * ,_
APR 2 6 2022
SAMUEL P. DEAN P.E.
CONSULTING ENGINEER
REGISTRATION NUMBER 83915
CA # 29694
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
PHONE: (813) 961-3075
FAX: (813) 961-1031
email: sdean@beltengineering.com
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
BE IN COMPLIANCE WITH THE FLORIDA BUILDING
CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
SYSTEMS AND ASSEMBLIES ARE THE TOTAL
RESPONSIBILITY OF OTHERS.
SHEET:
FA-2
1 /8 =i'
0
NORTH
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P.
DEAN, P.E. ON [04.26.20221 USING A SHA-1 AUTHENTICATION CODE,
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
-- J
'T. 20
FLORIDA LOW VOLTAGE SYSTEMS
4020 W CAYUGA ST.
TAMPA, FL 33614
813-353-0831
EC 13010771
EF 20001786
vow
�
M
M
�
�
Z
—
cn
�
LL
Z
--
�OCIO)
O
2
J
J
_
_
oo
>
a,
�
>
W
N
CAD DATE: 2/10/2022
NO. ISSUE/REVISION DATE
0`�0 � L 1 C ' • � �eee
r
o O • � • � w
APR 2 6 2022
SAMUEL P. DEAN P.E.
CONSULTING ENGINEER
REGISTRATION NUMBER 83915
CA # 29694
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
PHONE: (813) 961-3075
FAX: (813) 961-1031
email: sdean@beltengineering.com
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
BE IN COMPLIANCE WITH THE FLORIDA BUILDING
CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
SYSTEMS AND ASSEMBLIES ARE THE TOTAL
RESPONSIBILITY OF OTHERS.
SHEET:
FA-3
THIRD FLOOR
0
NORTH
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P.
DEAN, P.E. ON (04.26.20221 USING A SHA•1 AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA•1 AUTHENTICATION CODE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
S- T. 20?...
FLORIDA LOW VOLTAGE SYSTEMS
4020 W CAYUGA ST.
TAM PA, FL 33614
813-353-0831
EC 13010771
EF 20001786
CAD DATE: 2/10/2022
NO. ISSUE/REVISION DATE
w No
-o
r N
r)
op
Yes
11I
f i i i i 3
i•k+'."
APR 2 6
2022
SAMUEL P. DEAN P.E.
CONSULTING ENGINEER
REGISTRATION NUMBER 83915
CA # 29694
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
PHONE: (813) 961-3075
FAX: (813) 961-1031
email: sdean@beltengineedng.com
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
BE IN COMPLIANCE WITH THE FLORIDA BUILDING
CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
SYSTEMS AND ASSEMBLIES ARE THE TOTAL
RESPONSIBILITY OF OTHERS.
SHEET:
FA-4
y� VOLT.gC�
s�
\sT 202/
FLORIDA LOW VOLTAGE SYSTEMS
4020 W CAYUGA ST.
TAMPA, FL 33614
813-353-0831
EC 13010771
EF 20001786
VOW
� M
� � M
Z J
— co LL
to Z ..
n0
0�
J
_ _ J
CIO _
m � �
T >
W
N
CAD DATE: 2/10/2022
NO. ISSUE/REVISION DATE
a
No
15
w
p V
O• � • nY
r) F, I fir,
APR 2 b 2022
SAMUEL P. DEAN P.E.
CONSULTING ENGINEER
REGISTRATION NUMBER 83915
CA # 29694
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
PHONE: (813) 961-3075
FAX: (813) 961-1031
email: sdean@beltengineering.com
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
BE IN COMPLIANCE WITH THE FLORIDA BUILDING
CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
SYSTEMS AND ASSEMBLIES ARE THE TOTAL
RESPONSIBILITY OF OTHERS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAh1UEl P. I
SHEET:
DEAN, P.E. ON [04.26.2022] USING A SHA-1 AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON FA=5
ANY ELECTRONIC COPIES.
Project Name: SVB Housing Standby Hours: 24
Alarm Minn, 5
AFC-100 Installed BylFlorida Low Voltage Systems Efficiency Factor: 20%
Battery & Voltage Drop Designed B lorida Low Voltage Systems SLC Type Class B
Calculations Date: 1012022 NAC Source Voltage: 20.4 _
Model #: AFC-100 Max Panel Current (amps): 5
Panel ID:FACP User assumes all responsibility to ensure the quantities and current draw
values in this worksheet are accurate prior to submittal.
Locatiomist Floor Electrical/Mechanical Room
DescriptionAddressable Fire Panel Standby (amps) 4404�*OPS)
1 AFC-100 Analog Addressable FRCP 0.130 0.130 0.220 0.220
Panel Standby: 0.130 Panel Alarm: 0.220
1 UO-2000 / UD-1000 DACT Card
0.016
0.016
0.023
0.023
RA-6075R LCD Annunciator
0.020
0.025
1-650OR(F) Flush Mount LCD Annunciator
0.020
0.020
0.050
0.050
LED-16(F) Flush Mount LED Annunciator
0.025
0.025
LED-16 LED Annunciator LED Power*
0.015
0.210
CA-6075 Class A Module
0.012
0.044
3 P N-1000(E) Power Expander
0.015
0.045
0.015
0.045
PAD100-SLCE-127 SLC Expander
0.060
0.060
1 NOHMI-SLCE-127** SLC Expander
0.060
0.060
0.060
0.060
**REQUIRED IF USING N_OHMI PROTOCOL SLC DEVICES_
(Maximum current draw on P-Link limited to 1 Amp)
P-LINK Standby:
0.141
P-LINK Alarm:
0.178
*Only enter quantity if PLINK power is being used to power devices
SLC Devices
Standby
AFC / ARC Series
19 PAD-PD Analog Photo Smoke
0.000300
0.005700
0.000300
0.005700
PAD-PHD Analog Photo Smoke/Heat
0.000300
0.000300
2 P D-HD Analog Fixed Temp Heat
0.000300
0.000600
0.000300
0.000600
PAD -CD Analog Carbon Monoxide Detector
0.000300
0.000300
1 P D-DUCT Addressable Duct Detector
0.000300
0.000300
0.000300
0.000300
PAD-DUCTR* Add. Dud Detector w/Relay
0.000500
0.000500
PAD100-DRTS Dud Remote Test Switch
0.010000
0.015000
17 D100-PSSA/PSDA Add. Pull Station Single/Dual Action
0.000200
0.003400
0.000200
0.003400
PAD100-MIM Micro Input Module
0.000200
0.000200
1 P D100-SIM Single Input Module
0.000240
0.000240
0.000240
0.000240
1 P, D100-DIM Dual Input Module
0.000240
0.000240
0.000240
0.000240
6 AD100-RM Relay Module
0.000240
0.001440
0.000240
0.001440
SLC Loop Alarm LED Current
0,000000
0.000000
0.036000
0.180000
Requires Aux Power (Configure Below)
SLC Standby:
0.011920
SLC Alarm:
0.191920
** See the installation manual for special considerations when installing AIB, SCI
devices on Class B loops.
ConfigurationNAC Circuits (See NAC below)
Description1
0.00000
0.00000
2
0.00000
0.00000
NAC Standby:
0.00000
NAC Alarm:
0.00000
2
0.00000
UO Standby: 0.00000 1/0 Alarm:
0.00000
0.00000
CalculationBattery
•.
e
Panel Current: 0.13000
0.22000
P-Link Current: 0.14100
0.17800
SLC Device Current: 0.01192
0.19192
NAC Circuit Current: 0.00000
0.00000
1/0 Circuit Current: 0.00000
0.00000
SLC Loop Type: Class B
Total Stand b M'`'a e" _,. Total Alarm •fi wilt
;101
Device Addresses U m
Standby Hours: 24 Alarm Mins:
5
Device Addresses Available: 100
AH Required: 6.80 AH Required:
0.05
Total Combined Standby & Alarm AmpHours Required:
6.85
Safety Margin:
20%
Required Battery AmpHours:
8.22
Battery AmpHours Provided:
12
Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to
two 55 AH
batteries.
Total Standb R`L9 Total Alarm ,' ;�
1 Oft
Project Name SVB Housing Standby Hours: 24
Alarm Minn 5 -- --
PSN-1000(E) Installed By orida Low Voltage Systems Efficiency Factor. 2oX_- --- -
Battery & Voltage Drop Designed Low Voltage Systems SLC Type; Class B
calculations Date: 1012022 NAC source voltage: 20.4---
Model #: PSN-1000(E) Max Panel Current (amps): 10
Panel Ili
User assumes all responsibility to ensure the quantities and current draw
Location l FL ElecbicgVMechaolcal Room values in this worksheet am accurate briar to submittal.
Circuits (Sea NAC Contifiguration
below)
Panel Standby:
0.060 Panel Alarm:- - -
Standby (amps) All
0.200
(amps)
Ckt use
1 Notification
DescriptionNAC
1FL CKT#1
Claw
0,00000
2.84480
2 Notification
1FL CKT#2
Class B
0.00000
1.69CAO
3 Notification
1FL CKT #3
Class B
0.00000
1.94860
4 Notification
2FL CKT #4
Class B
0.00000
1.03860
5 Notification
2FL CKT #5
Class B
0.00000
0.49700
6
class B
0.00000
0.00000
NAC Standby:
0.00000 NAC Alarm:
8,02540
Panel Current:
0.06000
0.20000
Plink Current:
0.00000
0.00000
SLC Device Current:
0.00000
0.00000
NAC Circuit Current
0.00000
8.02540
Total Stand,
,•; •'""' ` Total Alarm
`'`; •�
Standby Hours:
24 Alarm Mins:
5
AH Required:
1.44 AH Required:
0.69
Total Combined Standby & Alarm AmpHours Required:
2.13
Safety Margin:
20%
Required Battery AmpHours:
2,56
_
Battery AmpHours Provided:
71
Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries.
NAC Circuit Configuration &
#14 Solid 3.19 200 1 276 2.845 16.77 16
6 H
Strobes
---
5
Potter LFHS-110 Temporal 3 Normal db
Potter 5-24 Strobe, 110ed
Gentex GHLF L ors, emporal 3 Norm
0.000000 0 000000
0.000000 0 000000
0.000000 0000000
0.280000 1.680C
0 161000 0.966C
0.099400 0.198E
6 S
Total Standb .. .. . - ---
Total Alarm `c ....`. >..,
Class Class6 Usage Notification Description 1FL CKT#2
#14 Solid 3 19 190 _ 1.212 1.G96 18.34 16
Potter HS-24, 75cd. Hi db 0. 0.000000 0.144000 0.7201
Potter SH-24H-WP 95cd, Med db 0. 0.000000 0. 181000 0.161
;Potter S24 Strobe, 75cd 0.000000 0.000000 0. 116000 0.696000
Potter LFH-24 LF Hom, Temporal 3 0.000 100 0.000000 0099400 0099400
Total Standb, Total Alarm(_ , , „ l,r
Class Class
Usage Notification
Description
1FL CKT#3
#14 Solid
3.19 160
1.021 1
1.949
18.41
16
4 Ham Strobes
Potter HS-24, 75W, Hi db
0.00000
0.
0.144000
0.576000
2 Hom Strobes
_
Potter SH-24H-WP 95cd, Mod d6_ -
_
0.00000
_
0 -
-0.181000
0.362000
1 Strobes
Potter S24 Strobe, 75cd
0.000000
_
0.000009_
_ _-
0.1160�
0.116000
9 Horns
Potter LFH-24 LF Ham, Temporal 3 Norm
0.00000
0.
0.099406
0.894604
- --
Total Star lb
,�, a:s
Total Alarm
NAC Circuit Configuration & Voltage Drop (cont'd)
classl Class B Usage Notification Description 2FL CKT #4
#14 Solid 3 19 160 1.021 1.039 19.34 16
9 Horns Gentex GHLF LF Horn. Temporal 3 Norm 0.000000 0.000000 0.099400 0.E
-
j 1 Hqm Strobes Potter HS-24, 75cd, HI db 0.000000 G 000000 0.144000 0.1
- Total Standby Total Alarm
Project Name: SVB Housing Standby Hour>r: 24 I
Alarm lifi l5 -�
PSN-1000(E) Installed ByFll Low Volage Systems \ Efficiency Facto -�
Battery & Voltage Drop Designed Low Voltage Systems SLC T pass B
Calculations Date: 10/20Y2 NAG Source Voita�
Model #: PSN-1000(E) Max Panel Current (amps): 10
Panel ID. FCPS #2
-- User a<sumes all responsibility to ensure the quantities and current draw
Location 1FL ElectricaVMechanlcal Room values in this worksheet are accurate odor to submittal.
1 PSN-100l
Int6ftent Power Expander
0.050
0,060
0.200
0.200
(See NAC Configuration
be"
Panel Standby:
Standby
0.060
wipe,
Panel Alarm:
0.200
Amwi� Use
1 Notification
Description
2FL CKT #6
Class
Class B
TOW
O.D0000
Total
1.25580
2 Notification
2FL CKT #7
Class B
0.00000
1. 12780
3 Notification
3FL CKT #8
Class B
0.00000
1.03860
4 Notification
3FL CKT #9
Class B
0.00000
0.49700
5 Notification
3FLCKT#10
Class
0.00000
0.98380
6 Notification
3FL CKT #11
Class B
0.00000
1.12780
-
- -
NAC Standby:
_ _
0.00000
NAC Alarm:
6.03080
Panel Current:
0.01
0.20000
P-Link Current:
0.00000
0.00000
SLC Device Current:
0.00000
0.00000
NAC Circuit Current:
0.00000
C.03080
Total Standb
Total Alarm
Standby Hours:
24
Alarm Mins:
5
AH Required:
1.44
AH Required:
0.52
Total Combined
Standby & Alarm AmpHours Required:
1.96
Safety Margin:
20%
Required
Battery AmpHours:
2.35
Battery AmpHours Provided:
71
Note: The cabinet will house two 8 AH or 18 AH batteries. The charging
circuit is rated for up to two 55 AH batteries.
NAC Circuit Configuration
8 Voltage Drop
SVB housing
2110/2022
Clawl Class B
Usage Notification
_
Descriptioll2FL
CKT #6
#14 Solid
3.19 180
1.148
1.256
18.96 16
2 Horn
l do 00000
0.000000
0280000
0
7 Horns
potter LFH 24 LFH m,oTelmpo al
Potter
3allonn_ 00000
0.000000
0.000000
0.099400
0 655800
-
_
Total Stantl6
,,>-JWJJJJ
_
Total AlarmE`,
9.
Class Class B Usage Notification Descnptio 2FL CKT #7
414 Solid 3.19 180 1.148 1.128 19.10 16
3 Horn Strobes Potter HS24 75cd, Hi db 0,000000 0,000000 0. 144000 043200
Q
7 Horns Potter LFH-24 LF Ham, Temporal 3 Norm 0.000000 0000000 0.099400 0 65580
4
Total Standblj; OAS - Total Alarm s, 11
MAX Circuit Current lamps): 3 Source volta" Used tvocj4;F7
Class ClassB Usagel Notification Descr(ptlonl 3FL CKT#8
#14 Solid 3.19 - 200 1.276 1.039 19.07 16
1 Horn Strobes Potter HS-24, 75cd, Ht db 0.000000 0.000300 0. 144000 0. 144000
i 9 Horns Potter LFH-24 LF Hom, Temporal 3 dorm 0.000000 1) 100000 0.099400 0 tr94600
Total Standby;; 0,EK160f1 Total Alarm: 1.¢
li
clawl Class B
usagel Notification
Descriptlo
3FL CKT #9
#14 Solid
3.19 200
1 276
0 497
1977
16
5 Horns
Clawl Class B
Potter LFH-24 LF Ham, Temporal 3 Norm
Usage Notification
0000000
Total Standb: .._
0 000003
0001iG0
Description
0 099400
Total Alarm
3FL CKT #10
0.497000
O,A9TOf�
#14 Solid
3.19 170
1,085
0.994
19 33
16
2 Horn Strobes
7 H ins _
Power HS24, 75cd, Hi db
IPatter LFH•24 LF Ham, Temporal 3 Cllorm
0.000000 0.000000
0000000 0000000
Total Standb, (
0,144000
0,099400
Total Alarms >,
0.288009
0,6958
Class Class B Usage Notification
D.scriptioll
3FL CKT #11
#14 Solid 3.19 200
1.276
1.128
18.96
16
3 Horn Strobes Potter HS24, 75cd, Hi db
7 Horns Potter LFH24 LF Horn. Temporal 3 Norm
0.000000
0 000000.
Total Standby(: _:
0,000000
0 000000
0,01(0@q
0. 144000
0.099400
Total Alarm
043200
0695800
1.1278t1
tat
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P.
DEAN, P.E. ON 104.26.20221 USING A SHA-1 AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES.
FLORIDA LOW VOLTAGE SYSTEMS
4020 W CAYUGA ST.
TAMPA, FL 33614
813-353-0831
EC 13010771
EF 20001786
L0
in
M
M
0
Z
C0
-�
U.
Cl
Z
n
=)
0
Ci
0
�_
J
a.
LLI
CAD DATE: 2/10/2022
NO. ISSUE/REVISION DATE
No 83 15
'0
p.' S O
441,
0
t
! ��/llllil►� ��
APR 2 6 2022
SAMUEL P. DEAN P.E.
CONSULTING ENGINEER
REGISTRATION NUMBER 83915
CA # 29694
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
PHONE: (813) 961-3075
FAX: (813) 961-1031
email: sdean@beltengineering.com
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
BE IN COMPLIANCE WITH THE FLORIDA BUILDING
CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
SYSTEMS AND ASSEMBLIES ARE THE TOTAL
RESPONSIBILITY OF OTHERS.
SHEET:
FA-6