HomeMy WebLinkAbout6419 Simons Rd (2)FIRE ALARM NOTES: SEQUENCE OF OPERATION: 1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS: A. MANUAL PULL STATION: 1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL 2 SOUND THE LOCAL AUDIBLE ALARM AT THE FACP. 3 ILLUMINATE THE ALARM RED LED. 4 SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES) IN THE BUILDING. B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER — FLOW SWITCH SHALL CAUSE THE FOLLOWING: 1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL. 2 SOUND THE LOCAL AUDIBLE ALARM AT THE FACP. 3 ILLUMINATE THE ALARM RED LED. 4 SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES) IN THE BUILDING. C. SMOKE DUCT DETECTORS 1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL 2 SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP. 3 ILLUMINATE THE SUPERVISORY LED. 4 SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT. D. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: 1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL 2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP. 3 ILLUMINATE THE TROUBLE LED. ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE DISPLAYED ON THE MAIN FIRE ALARM PANEL AS WELL AS ON ALL REMOTE ANNUNCIATOR PANELS. ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE TRANSMITTED TO A LISTED CENTRAL STATION. CENTRAL STATI❑N TRANSMISSI❑N ❑F SIGNALS — ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE CENTRAL STATION. — THE MEANS OF TRANSMISSION WILL BE (2) DEDICATED PHONE LINES. — ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS: A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION, SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW - DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION (FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS OR BUILDING NUMBER. — THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD. CODES & PLAN NOTES — INSTALLATION SHALL BE IN ACCORDANCE WITH FFPC 7TH Edition, NFPA 72 2016 Edition, NFPA 70 2017 Edition, FBC 7th Edition 2020 AND ANY OTHER APPLICABLE CODES. — ALL NEW SYSTEMS SHALL INCLUDE A DOCUMENT CABINET. — ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED. — CONFIRM LOCATION OF POWER SUPPLY PRIOR TO ROUGH IN. — REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR RETURN SIDE), COORDINATE WITH MECHANICAL CONTRACTOR THE ACTUAL LOCATIONS OF THE AHUs. — ALL STROBES WILL BE SET @ 75cd UNLESS NOTED. — CEILING HEIGHT IS 10ft UNLESS NOTED. — FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE. — COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF DUCT SMOKE DETECTORS — ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT PERMIT BY THE ELECTRICAL CONTRACTOR. FBC 107.2 24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE. IF BUILDING IS OCCUPIED DURING THIS TEST, FIREWATCH WILL BE REQUIRED. CEILING MOUNTED 3' (MIN) SMOKE/HEAT PER NFPA 72 4. DE CTOR 24' MIN HANDICAP A/C SUPPLY DIFFUSER / ACCEPTABLE HERE 4" BEDROOM STROBE I AUDIO/VISUAL CEILING MOUNTED NOTIFICATION ALL D7DETECTO 12' (MAX) VISUAL -ONLY DEVICES DEVICE �TO BE WHITE). EA ,j� SEE PLAN OR LOCATION. WAL HEAT TO THE BOTTOM. WALL MOUNTED MORE THAN TWO APPLIANCES 5'-0 SMOKE DETECTO IN THE SAME ROOM OR ADJACENT MAX FROM EXIT DOOR TO THE TOP. SPACE WITHIN THE FIELD OF VIEW SHALL FLASH IN SYNCHRONIZATION. MANUAL �— PULL s STATION REMOTE 80' MIN ® g ANNUNGATOR 96" MAX NFPA 72 2013 MAGNETC D HOLDER (ADAAG) 80' ABOVE HIGHEST FLOOR J LEVEL OR 6' BELOW CEILING Q ; TO THE BOTTOM QU THE x STROBE. WHICHEVER IS LOWER. 48' (ADA) a o TO THE WORKING MECHANISM Q 48" ALSO MEETS THE REQUIREMENTS OF NFPA 72 2013 FINISHED FLOOR IMPORTANT NOTE NOTE NOT ALL DEVICES % MN ON THIS DETAIL APPLY TO THIS PROJECT. SEE CHECK WITH MANUFACTURE'S INSTALLATION SHEET THE PLAN MEN LAYOUT OF THE Fff ALARM SYSTEM TO VEWY *1W FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF DEVICES APPLY, AND *1CH DO NOT. BACK BOXES, AND WIRING REQUIREMENTS. FIRE ALARM DEVICE MOUNTING GUIDE LOW VOLTAGE WIRING WHERE LOW VOLTAGE WIRING IS PERMITTED BY THESE DRAWINGS AND APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION TO BE FREE —WIRED, THESE WIRES SHALL BE PLENUM RATED AND U.L. LISTED FOR THE APPLICATION. FIRE ALARM SYMBOL LEGEND (TYPICAL) NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH DEVICES APPLY, AND WHICH DO NOT. FRCP FIRE ALARM CONTROL PANEL ANN FIRE ALARM ANNUNCIATOR FCPSI NAC POWER SUPPLY FF-A-T-C-1 FIRE ALARM TERMINAL CABINET 2 ADDRESSABLE SMOKE PHOTO DETECTOR t ADDRESSABLE HEAT DETECTOR �- ADDRESSABLE DUCT SMOKE ADDRESSABLE RELAY ADDRESSABLE PULL STATION Fs ADDRESSABLE MONITOR MODULE FOR TAMPER SWITCH FT S] ADDRESSABLE MONITOR MODULE FOR FLOW SWITCH HORN/STROBE WALL MOUNT LF LOW FREQUENCY/STROBE WALL MOUNT LF LOW FREQUENCY HORN WALL MOUNT STROBE WALL MOUNT FSDR FIRE/SMOKE DAMPER RELAY REVIEW DATE CITY OF ZEPHYRHOLLS FIRE AND LIFE SAFETY EXAMINE ALL WORK SHALL COMPLY WITH NFFA CODES AND STANDARDS THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P DEAN: P.E. ON [04.26.2022] USING A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. LST. 2027-A.00 FLORIDA LOW VOLTAGE SYSTEMS 4020 W CAYUGA ST. TAM PA, FL 33614 813-353-0831 EC 13010771 EF 20001786 r L M CD z J IL O to cn r� L) cl) co v 1' uj N CAD DATE: 2/10/2022 NO. ISSUE/REVISION DATE 0 N 39 S TA E L 11� I Y,L.,; APR 2 6 2022 SAMUEL P. DEAN P.E. CONSULTING ENGINEER REGISTRATION NUMBER 83915 CA # 29694 1503-A WEST BUSCH BLVD. TAMPA FLORIDA 33612 PHONE: (813) 961-3075 FAX: (813) 961-1031 email: sdean@beltengineering.com I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF ALL OF THE FIRE ALARM ELEMENTS FOR THIS STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE TOTAL RESPONSIBILITY OF OTHERS. SHEET: FA-1 WF .5� tO FIRST FLOOR a NORTH MA M-5 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P. DEAN. P.E. ON 104.26.20221 USING A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. tSt 20?-! FLORIDA LOW VOLTAGE SYSTEMS 4020 W CAYUGA ST. TAM PA, FL 33614 813-353-0831 EC 13010771 E F 20001786 Lo � � 0 � M M Z Cf) J LL U) Z m0co 0 J J _ _ W N CAD DATE: 2/10/2022 NO. ISSUE/REVISION DATE Nd- w ^"J O• ST * ,_ APR 2 6 2022 SAMUEL P. DEAN P.E. CONSULTING ENGINEER REGISTRATION NUMBER 83915 CA # 29694 1503-A WEST BUSCH BLVD. TAMPA FLORIDA 33612 PHONE: (813) 961-3075 FAX: (813) 961-1031 email: sdean@beltengineering.com I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF ALL OF THE FIRE ALARM ELEMENTS FOR THIS STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE TOTAL RESPONSIBILITY OF OTHERS. SHEET: FA-2 1 /8 =i' 0 NORTH THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P. DEAN, P.E. ON [04.26.20221 USING A SHA-1 AUTHENTICATION CODE, PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. -- J 'T. 20 FLORIDA LOW VOLTAGE SYSTEMS 4020 W CAYUGA ST. TAMPA, FL 33614 813-353-0831 EC 13010771 EF 20001786 vow � M M � � Z — cn � LL Z -- �OCIO) O 2 J J _ _ oo > a, � > W N CAD DATE: 2/10/2022 NO. ISSUE/REVISION DATE 0`�0 � L 1 C ' • � �eee r o O • � • � w APR 2 6 2022 SAMUEL P. DEAN P.E. CONSULTING ENGINEER REGISTRATION NUMBER 83915 CA # 29694 1503-A WEST BUSCH BLVD. TAMPA FLORIDA 33612 PHONE: (813) 961-3075 FAX: (813) 961-1031 email: sdean@beltengineering.com I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF ALL OF THE FIRE ALARM ELEMENTS FOR THIS STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE TOTAL RESPONSIBILITY OF OTHERS. SHEET: FA-3 THIRD FLOOR 0 NORTH THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P. DEAN, P.E. ON (04.26.20221 USING A SHA•1 AUTHENTICATION CODE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA•1 AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. S- T. 20?... FLORIDA LOW VOLTAGE SYSTEMS 4020 W CAYUGA ST. TAM PA, FL 33614 813-353-0831 EC 13010771 EF 20001786 CAD DATE: 2/10/2022 NO. ISSUE/REVISION DATE w No -o r N r) op Yes 11I f i i i i 3 i•k+'." APR 2 6 2022 SAMUEL P. DEAN P.E. CONSULTING ENGINEER REGISTRATION NUMBER 83915 CA # 29694 1503-A WEST BUSCH BLVD. TAMPA FLORIDA 33612 PHONE: (813) 961-3075 FAX: (813) 961-1031 email: sdean@beltengineedng.com I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF ALL OF THE FIRE ALARM ELEMENTS FOR THIS STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE TOTAL RESPONSIBILITY OF OTHERS. SHEET: FA-4 y� VOLT.gC� s� \sT 202/ FLORIDA LOW VOLTAGE SYSTEMS 4020 W CAYUGA ST. TAMPA, FL 33614 813-353-0831 EC 13010771 EF 20001786 VOW � M � � M Z J — co LL to Z .. n0 0� J _ _ J CIO _ m � � T > W N CAD DATE: 2/10/2022 NO. ISSUE/REVISION DATE a No 15 w p V O• � • nY r) F, I fir, APR 2 b 2022 SAMUEL P. DEAN P.E. CONSULTING ENGINEER REGISTRATION NUMBER 83915 CA # 29694 1503-A WEST BUSCH BLVD. TAMPA FLORIDA 33612 PHONE: (813) 961-3075 FAX: (813) 961-1031 email: sdean@beltengineering.com I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF ALL OF THE FIRE ALARM ELEMENTS FOR THIS STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE TOTAL RESPONSIBILITY OF OTHERS. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAh1UEl P. I SHEET: DEAN, P.E. ON [04.26.2022] USING A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON FA=5 ANY ELECTRONIC COPIES. Project Name: SVB Housing Standby Hours: 24 Alarm Minn, 5 AFC-100 Installed BylFlorida Low Voltage Systems Efficiency Factor: 20% Battery & Voltage Drop Designed B lorida Low Voltage Systems SLC Type Class B Calculations Date: 1012022 NAC Source Voltage: 20.4 _ Model #: AFC-100 Max Panel Current (amps): 5 Panel ID:FACP User assumes all responsibility to ensure the quantities and current draw values in this worksheet are accurate prior to submittal. Locatiomist Floor Electrical/Mechanical Room DescriptionAddressable Fire Panel Standby (amps) 4404�*OPS) 1 AFC-100 Analog Addressable FRCP 0.130 0.130 0.220 0.220 Panel Standby: 0.130 Panel Alarm: 0.220 1 UO-2000 / UD-1000 DACT Card 0.016 0.016 0.023 0.023 RA-6075R LCD Annunciator 0.020 0.025 1-650OR(F) Flush Mount LCD Annunciator 0.020 0.020 0.050 0.050 LED-16(F) Flush Mount LED Annunciator 0.025 0.025 LED-16 LED Annunciator LED Power* 0.015 0.210 CA-6075 Class A Module 0.012 0.044 3 P N-1000(E) Power Expander 0.015 0.045 0.015 0.045 PAD100-SLCE-127 SLC Expander 0.060 0.060 1 NOHMI-SLCE-127** SLC Expander 0.060 0.060 0.060 0.060 **REQUIRED IF USING N_OHMI PROTOCOL SLC DEVICES_ (Maximum current draw on P-Link limited to 1 Amp) P-LINK Standby: 0.141 P-LINK Alarm: 0.178 *Only enter quantity if PLINK power is being used to power devices SLC Devices Standby AFC / ARC Series 19 PAD-PD Analog Photo Smoke 0.000300 0.005700 0.000300 0.005700 PAD-PHD Analog Photo Smoke/Heat 0.000300 0.000300 2 P D-HD Analog Fixed Temp Heat 0.000300 0.000600 0.000300 0.000600 PAD -CD Analog Carbon Monoxide Detector 0.000300 0.000300 1 P D-DUCT Addressable Duct Detector 0.000300 0.000300 0.000300 0.000300 PAD-DUCTR* Add. Dud Detector w/Relay 0.000500 0.000500 PAD100-DRTS Dud Remote Test Switch 0.010000 0.015000 17 D100-PSSA/PSDA Add. Pull Station Single/Dual Action 0.000200 0.003400 0.000200 0.003400 PAD100-MIM Micro Input Module 0.000200 0.000200 1 P D100-SIM Single Input Module 0.000240 0.000240 0.000240 0.000240 1 P, D100-DIM Dual Input Module 0.000240 0.000240 0.000240 0.000240 6 AD100-RM Relay Module 0.000240 0.001440 0.000240 0.001440 SLC Loop Alarm LED Current 0,000000 0.000000 0.036000 0.180000 Requires Aux Power (Configure Below) SLC Standby: 0.011920 SLC Alarm: 0.191920 ** See the installation manual for special considerations when installing AIB, SCI devices on Class B loops. ConfigurationNAC Circuits (See NAC below) Description1 0.00000 0.00000 2 0.00000 0.00000 NAC Standby: 0.00000 NAC Alarm: 0.00000 2 0.00000 UO Standby: 0.00000 1/0 Alarm: 0.00000 0.00000 CalculationBattery •. e Panel Current: 0.13000 0.22000 P-Link Current: 0.14100 0.17800 SLC Device Current: 0.01192 0.19192 NAC Circuit Current: 0.00000 0.00000 1/0 Circuit Current: 0.00000 0.00000 SLC Loop Type: Class B Total Stand b M'`'a e" _,. Total Alarm •fi wilt ;101 Device Addresses U m Standby Hours: 24 Alarm Mins: 5 Device Addresses Available: 100 AH Required: 6.80 AH Required: 0.05 Total Combined Standby & Alarm AmpHours Required: 6.85 Safety Margin: 20% Required Battery AmpHours: 8.22 Battery AmpHours Provided: 12 Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries. Total Standb R`L9 Total Alarm ,' ;� 1 Oft Project Name SVB Housing Standby Hours: 24 Alarm Minn 5 -- -- PSN-1000(E) Installed By orida Low Voltage Systems Efficiency Factor. 2oX_- --- - Battery & Voltage Drop Designed Low Voltage Systems SLC Type; Class B calculations Date: 1012022 NAC source voltage: 20.4--- Model #: PSN-1000(E) Max Panel Current (amps): 10 Panel Ili User assumes all responsibility to ensure the quantities and current draw Location l FL ElecbicgVMechaolcal Room values in this worksheet am accurate briar to submittal. Circuits (Sea NAC Contifiguration below) Panel Standby: 0.060 Panel Alarm:- - - Standby (amps) All 0.200 (amps) Ckt use 1 Notification DescriptionNAC 1FL CKT#1 Claw 0,00000 2.84480 2 Notification 1FL CKT#2 Class B 0.00000 1.69CAO 3 Notification 1FL CKT #3 Class B 0.00000 1.94860 4 Notification 2FL CKT #4 Class B 0.00000 1.03860 5 Notification 2FL CKT #5 Class B 0.00000 0.49700 6 class B 0.00000 0.00000 NAC Standby: 0.00000 NAC Alarm: 8,02540 Panel Current: 0.06000 0.20000 Plink Current: 0.00000 0.00000 SLC Device Current: 0.00000 0.00000 NAC Circuit Current 0.00000 8.02540 Total Stand, ,•; •'""' ` Total Alarm `'`; •� Standby Hours: 24 Alarm Mins: 5 AH Required: 1.44 AH Required: 0.69 Total Combined Standby & Alarm AmpHours Required: 2.13 Safety Margin: 20% Required Battery AmpHours: 2,56 _ Battery AmpHours Provided: 71 Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries. NAC Circuit Configuration & #14 Solid 3.19 200 1 276 2.845 16.77 16 6 H Strobes --- 5 Potter LFHS-110 Temporal 3 Normal db Potter 5-24 Strobe, 110ed Gentex GHLF L ors, emporal 3 Norm 0.000000 0 000000 0.000000 0 000000 0.000000 0000000 0.280000 1.680C 0 161000 0.966C 0.099400 0.198E 6 S Total Standb .. .. . - --- Total Alarm `c ....`. >.., Class Class6 Usage Notification Description 1FL CKT#2 #14 Solid 3 19 190 _ 1.212 1.G96 18.34 16 Potter HS-24, 75cd. Hi db 0. 0.000000 0.144000 0.7201 Potter SH-24H-WP 95cd, Med db 0. 0.000000 0. 181000 0.161 ;Potter S24 Strobe, 75cd 0.000000 0.000000 0. 116000 0.696000 Potter LFH-24 LF Hom, Temporal 3 0.000 100 0.000000 0099400 0099400 Total Standb, Total Alarm(_ , , „ l,r Class Class Usage Notification Description 1FL CKT#3 #14 Solid 3.19 160 1.021 1 1.949 18.41 16 4 Ham Strobes Potter HS-24, 75W, Hi db 0.00000 0. 0.144000 0.576000 2 Hom Strobes _ Potter SH-24H-WP 95cd, Mod d6_ - _ 0.00000 _ 0 - -0.181000 0.362000 1 Strobes Potter S24 Strobe, 75cd 0.000000 _ 0.000009_ _ _- 0.1160� 0.116000 9 Horns Potter LFH-24 LF Ham, Temporal 3 Norm 0.00000 0. 0.099406 0.894604 - -- Total Star lb ,�, a:s Total Alarm NAC Circuit Configuration & Voltage Drop (cont'd) classl Class B Usage Notification Description 2FL CKT #4 #14 Solid 3 19 160 1.021 1.039 19.34 16 9 Horns Gentex GHLF LF Horn. Temporal 3 Norm 0.000000 0.000000 0.099400 0.E - j 1 Hqm Strobes Potter HS-24, 75cd, HI db 0.000000 G 000000 0.144000 0.1 - Total Standby Total Alarm Project Name: SVB Housing Standby Hour>r: 24 I Alarm lifi l5 -� PSN-1000(E) Installed ByFll Low Volage Systems \ Efficiency Facto -� Battery & Voltage Drop Designed Low Voltage Systems SLC T pass B Calculations Date: 10/20Y2 NAG Source Voita� Model #: PSN-1000(E) Max Panel Current (amps): 10 Panel ID. FCPS #2 -- User a<sumes all responsibility to ensure the quantities and current draw Location 1FL ElectricaVMechanlcal Room values in this worksheet are accurate odor to submittal. 1 PSN-100l Int6ftent Power Expander 0.050 0,060 0.200 0.200 (See NAC Configuration be" Panel Standby: Standby 0.060 wipe, Panel Alarm: 0.200 Amwi� Use 1 Notification Description 2FL CKT #6 Class Class B TOW O.D0000 Total 1.25580 2 Notification 2FL CKT #7 Class B 0.00000 1. 12780 3 Notification 3FL CKT #8 Class B 0.00000 1.03860 4 Notification 3FL CKT #9 Class B 0.00000 0.49700 5 Notification 3FLCKT#10 Class 0.00000 0.98380 6 Notification 3FL CKT #11 Class B 0.00000 1.12780 - - - NAC Standby: _ _ 0.00000 NAC Alarm: 6.03080 Panel Current: 0.01 0.20000 P-Link Current: 0.00000 0.00000 SLC Device Current: 0.00000 0.00000 NAC Circuit Current: 0.00000 C.03080 Total Standb Total Alarm Standby Hours: 24 Alarm Mins: 5 AH Required: 1.44 AH Required: 0.52 Total Combined Standby & Alarm AmpHours Required: 1.96 Safety Margin: 20% Required Battery AmpHours: 2.35 Battery AmpHours Provided: 71 Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries. NAC Circuit Configuration 8 Voltage Drop SVB housing 2110/2022 Clawl Class B Usage Notification _ Descriptioll2FL CKT #6 #14 Solid 3.19 180 1.148 1.256 18.96 16 2 Horn l do 00000 0.000000 0280000 0 7 Horns potter LFH 24 LFH m,oTelmpo al Potter 3allonn_ 00000 0.000000 0.000000 0.099400 0 655800 - _ Total Stantl6 ,,>-JWJJJJ _ Total AlarmE`, 9. Class Class B Usage Notification Descnptio 2FL CKT #7 414 Solid 3.19 180 1.148 1.128 19.10 16 3 Horn Strobes Potter HS24 75cd, Hi db 0,000000 0,000000 0. 144000 043200 Q 7 Horns Potter LFH-24 LF Ham, Temporal 3 Norm 0.000000 0000000 0.099400 0 65580 4 Total Standblj; OAS - Total Alarm s, 11 MAX Circuit Current lamps): 3 Source volta" Used tvocj4;F7 Class ClassB Usagel Notification Descr(ptlonl 3FL CKT#8 #14 Solid 3.19 - 200 1.276 1.039 19.07 16 1 Horn Strobes Potter HS-24, 75cd, Ht db 0.000000 0.000300 0. 144000 0. 144000 i 9 Horns Potter LFH-24 LF Hom, Temporal 3 dorm 0.000000 1) 100000 0.099400 0 tr94600 Total Standby;; 0,EK160f1 Total Alarm: 1.¢ li clawl Class B usagel Notification Descriptlo 3FL CKT #9 #14 Solid 3.19 200 1 276 0 497 1977 16 5 Horns Clawl Class B Potter LFH-24 LF Ham, Temporal 3 Norm Usage Notification 0000000 Total Standb: .._ 0 000003 0001iG0 Description 0 099400 Total Alarm 3FL CKT #10 0.497000 O,A9TOf� #14 Solid 3.19 170 1,085 0.994 19 33 16 2 Horn Strobes 7 H ins _ Power HS24, 75cd, Hi db IPatter LFH•24 LF Ham, Temporal 3 Cllorm 0.000000 0.000000 0000000 0000000 Total Standb, ( 0,144000 0,099400 Total Alarms >, 0.288009 0,6958 Class Class B Usage Notification D.scriptioll 3FL CKT #11 #14 Solid 3.19 200 1.276 1.128 18.96 16 3 Horn Strobes Potter HS24, 75cd, Hi db 7 Horns Potter LFH24 LF Horn. Temporal 3 Norm 0.000000 0 000000. Total Standby(: _: 0,000000 0 000000 0,01(0@q 0. 144000 0.099400 Total Alarm 043200 0695800 1.1278t1 tat THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P. DEAN, P.E. ON 104.26.20221 USING A SHA-1 AUTHENTICATION CODE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. FLORIDA LOW VOLTAGE SYSTEMS 4020 W CAYUGA ST. TAMPA, FL 33614 813-353-0831 EC 13010771 EF 20001786 L0 in M M 0 Z C0 -� U. Cl Z n =) 0 Ci 0 �_ J a. LLI CAD DATE: 2/10/2022 NO. ISSUE/REVISION DATE No 83 15 '0 p.' S O 441, 0 t ! ��/llllil►� �� APR 2 6 2022 SAMUEL P. DEAN P.E. CONSULTING ENGINEER REGISTRATION NUMBER 83915 CA # 29694 1503-A WEST BUSCH BLVD. TAMPA FLORIDA 33612 PHONE: (813) 961-3075 FAX: (813) 961-1031 email: sdean@beltengineering.com I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF ALL OF THE FIRE ALARM ELEMENTS FOR THIS STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE TOTAL RESPONSIBILITY OF OTHERS. SHEET: FA-6