SCALE: 1/4' = 1'-0" FIRE SPRINKLER PIPING PLAN_
%emw6% CROSS SECTION -A.
0' 1 ' 2' 3' 4' SCALE ------------------------------ 1/4" = 1'-0"
0 91)$
2
SCALE: 1/4" 1'-0"
0 1 2 3 4'
SYMBOLS
FIRE SPRINKLER PIPING PLAN
CEILING PLAN
SCALE ------------------------------ 1/4' = 1'-0'j
#TD.4
INSPECTORS TEST AND DRA11'
SEE DETAIL.
�23 - 6
#TD.7
5-1
CALCULATED PER NFPA 13,
R1.WXF
Remote Area 1
HYDRAULICALLY CALCULATED REMOTE AREA
AREA OF 1513 SQ.FT. SPRINKLER COVERAGE
DENSITY OF .20
MAX COVERAGE OF SPRINKLER 130 SQ. FT.
MIN COVERAGE OF SPRINKLER 117.02 SQ. FT.
250 OUT SIDE HOSE DEMAND
W/ORIFFICE OF 3/4 11 = K8.0
# OF SPRINKLERS 13
REQ. FLOW @ BR = 336.81
REQ. PSI @ BR = 42.23
SAFETY MARGIN 14.78 PSI = 23.1%
#R1 HANGER
NO SCALE
D r) 0 E- r) E7 1*'% 1/
D WIDE MOUTH
-AMP
SWIVEL RING
+19'-7"
OMA
PRESSURE 1A.-0 11 TEST AND DRAIN VALVE
—+ 5'- 0" 1'
E,,--,----W/RELIEF VALVE 175 PSI
+4'-3"
+0'-6"
5-1"
INSPECTORS TEST + DRAIN DETAIL
Scale- 1/2" = 1'-0"
0
04 L 12c,
NO
3" RISER CLAMP 96:6
" F. C. V.
f /TT) i I
PRESSURE Gk-�
+17'-B"
3" RISER CLAMP
6" ELEC. BELL 11OV.
6 SPARE HEAD CABINET
5 FlFR80 UP -BRASS 200*
1 FlFR56 PEND-WHITE 155
1 HEAD WRENCH-W2
3" GRxGR CHECK VALVE
u-
'j AU11 1
LL
4"x3" GR REDC COUPLING
4"x2'2"x2'2" FDC
4'
TxM +3'-Olt
C14 FD2
12'-0"
rE
+1'-O"ABOVE FINISH FLOOR
'-�114" TEST AND DRAIN
3" RISER DETAIL
Scale: 1/2" = 1'-0"
-0-
4s'
0.1. PRESSURE 315
BY OTHERS I
+1'-0" ABOVE FINISH FLOOR
(Ellklicu flolknc"
4" STUB UP DETAIL.
Scale: 1/2" = 1'-0"
SEE DRA WING FP1
FOR ALL DESIGN
AND GENERAL NOTES.
<-L> HYDRAULIC CALCULATIONS REFERENCE POINT
ASTERISK INDICATES DISTANCE FROM BOTTOM OF STEEL ROOF TO CENTERLINE OF PIPE
PLUS SIGN INDICATES DISTANCE FROM FLOOR TO CENTERLINE OF PIPE
FIRE RATED PARTITION
S H. 10 PIPE SLEEVE NTH SIZEAENGTH LABEL (SEE SLEEVE LEGEND)
S3
n{.
SYMBOLS
OHYDRAULIC CALCULATIONS REFERENCE POINT
8" ASTERISK INDICATES DISTANCE FROM STEEL ROOF TO CENTERLINE OF PIPE
PLUS SIGN INDICATES DISTANCE FROM FLOOR TO CENTERLINE OF PIPE
- - - FIRE RATED PARTITION
SCH. 10 PIPE SLEEVE WITH SIZEAENGTH LABEL (SEE SLEEVE LEGEND)
S3
C
Cc
n -7' .1 n"
80'-0"
FIRE SPRINKLER PIPING PLAN
FLOOR PLAN
SCALE ------------------------------ 1 /4" = 1'-0"
SCALE: 1 /4" = 1' -0"
01 ' 2' 3' 4'
SEE DRAWING FPI
FOR ALL DESIGN
AND GENERAL NOTES.