HomeMy WebLinkAbout5200 Airport RdGENERAL NOTES: THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2017 FLORIDA BUILDING CODE 6TH EDITION T.L ' HANSON A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING COMPANY; HAS APPLIED "RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN OF THIS STRUCTURE. THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE FOLLOWING SUPERIMPOSED LOADS: SLAB: LIVE LOAD - 50 P.S.F. DEAD LOAD - 10 P.S.F. ROOF: LIVE LOAD - 20 P.S.F. DEAD LOAD - 10 P.S.F. WIND: BUILDING IS DESIGNED TO CONFORM TO ASCE 7-10, CHAPTERS 26 THRU 31; PER 2017 FLORIDA BUILDING CODE, RESIDENTIAL 6TH EDITION- SECTION R301.2.1.1. AND 2017 FLORIDA BUILDING CODE 6TH EDITION SECTION 1609 WIND DESIGN ASSUMPTIONS: BUILDING EXPOSURE - B BUILDING RISK CATEGORY - 11 MEAN ROOF HEIGHT 30'OR LESS HEIGHT & EXPOSURE ADJUSTMENT COEFFICIENT = 1.0 ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT 0.18 WIND SPEED SHOWN AT THE BOTTOM RIGHT CORNER OF THIS SHEET ALL STRUCTURAL ELEMENTS, EXTERIOR WALLS AND INTERIOR WALLS SHALL BE TYPE V CONSTRUCTION PER FBC 602.5 SOIL BEARING & COMPACTION: COMPONENT & CLADDING WIND LOADS ALL OTHER BUILDING ROOF OVERHANG COMPONENT ZONE LOADS LOADS 1 N/A +32.3/-35.3 2 -65.7 +32.3/-56.2 3 -110.6 +32.3/-89.0 4 N/A +35.3/-38.2 5 N/A +35.3/-47.2 THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. (MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. T.L. HANSON; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE NOR PERFORMING ANY SOIL TESTING. T.L. HANSON SHALL NOT BE RESPONISIBLE FOR THE SITE SOILS ABILITY TO SUPPORT THE BUILDING LOADS. FOUNDATIONS & SLAB -ON -GRADE: BUILDING SITE SHALL BE SCRAPED TO REMOVE ALL ORGANIC MATERIALS WITHIN THE BUILDING AREA. ANY ADDITIONAL FILL PLACED ON THE BUILDING PAD AREA, SHALL BE COMPACTED SUCH THAT IT CAN ADEQUATELY SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. SLAB SHALL BE PLACED OVER A 6 MIL VAPOR BARRIER ON CLEAN, ADEQUATELY COMPACTED AND TERMITE POISONED SOIL. CONCRETE UTILIZED IN THE FOUNDATIONS AND SLABS SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2,500 P.S.I. REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25" FOR #5 REBAR, 30' FOR #6 REBAR & 35- FOR #7 REBAR. PLANS ARE ENGINEERED FOR A MAXIMUM STEMWALL HEIGHT OF 4 COURSES (AFTER FINAL SITE GRADING). THE CONTRACTOR OR BUILDING OWNER SHALL DETERMINE THE EXACT STEMWALL HEIGHT BASED UPON SITE CONDITIONS PRIOR TO POURING THE FOUNDATION AND CONTACT ARKAY ENGINEERING WHEN MORE THAN 4 COURSES ARE REQUIRED. A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON THE SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY THE REQUIRED BUILDING SETBACKS. MASONRY WALLS: CONCRETE MASONRY UNITS SHALL BE HOLLOW UNIT MASONRY IN ACCORDANCE WITH ASTM C-90 AND SHALL HAVE A MINIMUM F-M OF 1,500 P.S.I. MORTAR SHALL CONFORM TO ASTM C-270 AND SHALL BE EITHER TYPE M OR S. REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 251, FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR. BUILDING DATA: GROUT FOR THE POURED CELLS AND LINTELS SHALL HAVE A MAXIMUM COURSE AGGREGATE SIZE OF 3/8", PLACED AT AN 8 TO 11 INCH SLUMP AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2,500 P.S.I. (WHEN TESTED PER ASTM C-1019). PROVIDE CLEAN -OUT OPENINGS (12 SQ, IN.) IN CELLS CONTAINING SPLICED REINFORCEMENT, WHEN THE GROUT POUR EXCEEDS 5 FEET IN HEIGHT. SOIL TERMITE TREATMENT: TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED PEST CONTROL COMPANY BEFORE A"CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE SHALL STATE "THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES." IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION, DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR. THE SYSTEM MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL. INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION, BACKFILLING & COMPACTION ARE COMPLETE ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED (INCLUDING ANY BOXED OR FORMED AREAS) - BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN ADEQUATE SIZE & DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE INITIAL TREATMENT. A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT SHALL BE REQUIRED ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE BUILDING SIDEWALLS (PER FBC R318). AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS. THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION FOR FUTURE TERMITE INFESTATIONS SAFETY GLAZING: THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308: (1) GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR ASSEMBLIES. (2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS THAN 60 INCHES ABOVE THE DRAIN INLET. (3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR OR WALKING SURFACE. (4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS DESCRIBED IN ITEMS (2) AND (3) ABOVE. THAT MEETS ALL OF THE FOLLOWING CONDITIONS: A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQ. FT. B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR. C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR. D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE PLANE OF THE GLAZING. REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING. OCCUPANCY CLASSIFICATION: UTILITY MISC USE COMNSTRUCTION TYPE: VB FIRE PROTECTION: NON SPRINKLED RESTROOM: N/A TOTAL NEW BUILDING AREA 383 SQ. FT. NOT INCLUDING EXISTING STEEL CANOPY BUILDING CITY OF ZEPHYRHILLS EVENT CENTER AIRPORT ROAD ZEPHYRHILLS, FLORIDA 33542 A4, _ vj/ coDE� uRk Si 'S P4 , *bqt.? ., /VA 7-/C)�jb OR/Z) , - LC) livo 'At'Ei A 811/4 0,iyol'lycCl_j��C7-RIC 0ING, "H P'y p- 1114 Op��pcjwoa�� 00,E�, �-/?, , SITE 0 his 0 No. 3§654 - w 6 't, it (f wo S -ft. !:o:w 0 R I'D 110 PLAN INDEX: SHEET B 1: EXISTING FLOOR PLAN EXISTING ELEVATIONS DEMOLITION PLAN SHEET B 2: PROPOSED FLOOR PLAN PROPOSED ELEVATIONS FINISH SCHEDULE DOOR AND WINDOW SCHEDULE SHEET S 1: FOUNDATION PLAN CEILING JOIST PLAN INTERIOR STEEL STUD WALL DETAIL BUILDING CUT SECTION DETAIL SHEET S 2: EXISTING STEEL COLUMN WRAP DETAIL RAMP RAILING DETAIL REAR STAIR AND LANDING DETAIL FLAGPOLE DETAIL SHEET SHEET E 1: ELECTRICAL PLAN ELECTRICAL LEGEND SCHEUDLE ELECTRICAL NOTES ELECTRICAL SPECIFICATIONS HANSON HEADLEY PROFESSIONAL ENGINEERS ENGINEERING BUSINESS NO. EB6450 PO BOX 1728 DADE CITY, FL 33526 (352) 521-5848 5290 S. ROMANS AVE, INVERNESS, FIL 34452 (352) 726-2332 15'6" o TOP OF STEEL EXISTING EAST ELEVATION 1/411 = 11 off DIMENSIONS ARE APPROXIMATE AND MUST BE FIELD VERIFIED BY CONTRACTOR PRIOR TO CONSTRUCTIONS EXISTING SOUTH ELEVATION 1/411 = 11 oll EXISTING WEST ELEVATION 1/411 = 11 off EXISTING NORTH ELEVATION 1/411 = 11 off ECTRIC PANEL THAT STRUCTURE AND ;ITE IS LOCATED ON I WEST OF STRUCTURE. '0 SCALE _TOP Cf ST�EL _ S 15'9" _ __LO� OF �TAGE_ S 2'7 1/2" __.pR6QE_ fo 0'0" EXISTING METER AND ELECTRIC PANEL THAT SERVICES THE EXISTING STRUCTURE AND OTHER ELECTRICAL ON SITE IS LOCATED ON A PEDESTAL AT IS SOUTH WEST OF STRUCTURE. LOCATION SHOWN NOT TO SCALE It 0) ;;t C14 29' 7%" EXISTING STEEL COLUMNS EXISTING STEEL COLUMNS IN CONCRETE FOOTINGS IN CONCRETE FOOTINGS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - TO EXISTING MODULAR BUILDING . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. .. .. ... .. .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... EXISTING RAILING- .. ... .. ... .. ... .. ... . ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... EXISTING CONCRETE 61STINi3 RAILWG "7' RAISED STAGE . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . .. . .. . .. . .. . . . .. . .. . .. . .. . .. . .. DASH LINES REPRESENT STEEL CANOPY ROOF EDGE ABOVE ... .. .. .. ... .. ... .. ... .. ... .. ... .. ... . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. .. ... .. ... .. ... . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. .. ... .. ... EXISTING STEEL COLUMNS EDGE OF EXISTING RAISED CONCRETE ---- EXISTING STEEL COLUMNS IN CONCRETE FOOTINGS STAGE 311/2"ABOVE EXISTING GRADE IN CONCRETE FOOTINGS 27'4" 29'71/4" EXISTING FLOOR PLAN 1/411 = 1 loll: DIMENSIONS ARE APPROXIMATE AND MUST BE FIELD VERIFIED BY CONTRACTOR PRIOR TO CONSTRUCTIONS ----------------------------------------- REMOVE MODULAR BUILDING DISCONNECT ALL ELECTRICAL EXISTING"\ MODULAR BUILDING .. ... .. ... .. .. (L EXISTINGRAILING j EXISTING RAILING a. ... .. ... .. ... .. .. LANDING Ln '8143/4' EXISTING CONCRETE LANDING AND RAMP NO CHANGE TO RAMP OR HAND RAIL .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. . .. .. .. REMOVE ALL WHITE ALUMINUM .. .. ... .. ... .. .. .. ... .. .. NON SUPPORTING BEAM AT THIS ... .. ... .. ... .. . UP .. ... .. ... .. .. . .. ... .. AREA ... .. ... .. .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. 3 ... .. ... .. ... .. .. ... .. ... .. ... .. ... .. ... .. ... .. .. . . .. ... .. ... .. ... .. .. . .. ... .. . .. . . .. ... .. .. ... .. ... .. ... .. ... .. .. .. ... .. ... .. ... ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. . .. . .. . ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . .. . .. . EXISTING CONCRETE ... .... .... ... .... . .. . ... .. ... . ... .. .. .. . .. . .. . .. . .. . .. . .. RAISED STAGE ... .. 3 . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. REMOVE ALL EXISTING ALUMINUM [RE . . . . . . . . . . . . RAILING AT STAGE AREAS . ... .. ... .. ... .. ... .. . .. . ... .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... ... .. .. .. ... .. .. ... .. ... .. ... .. .. .. ... .. ... .. ... .. ... .. .. .. ... .. ... .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . . . .. . .. . .. . .. . .. . .. . .. . M 0% \�, �m %.000 REMOVE ALL EXISTING ALUMINU ... .... .. ... .. RAILING AT RAMP AND LANDING 0 REMOVE EXISTING ELECTRICAL AT BASE OF REMOVE EXISTING FLAG POLE 0 0 mm LLB DEMOLITION PLAN 3/16" 10": VA rn&,ICEWS 38654 'TA B CONCRETE STAGE AND RE INSTALL =BEHIND AND INSTALL NEW ONE AS SHOWN 0.0, .1 28, E 3526 STONE DIMENSIONS ARE APPROXIMATE AND MUSI 00. "'Ill, BE FIELD VERIFIED BY CONTRACTOR PRIOR I HERBY C D SPECIFICATIONS TO CONSTRUCTIONS WERE PREP 0 DIRECT SUPERVISION ARE IN COMPLI 16, SECTION 1609 OF THE FLORIDA BUILDING 6TH EDITION AND ASCE 7-10 FOR 139 MPH WIND ZONE RISK CATEGORY 11 . CINI W uj In 4 m W c/) Z _j < U_ C-4 LU 0 C/) z w w to C6 Z 04 it (D Lc) aCD 0) W w z rn w 04 > Ing- w d Z (41 06 z U) w 9 (1) m z 0 (j) U) a 9 2 cf) wW LL Lu K -N 0 (D z 20 (1) z Lu _j 00 CO ILL. 04 x 04 0 Lu �z (XI b Fj 0<Ip 0-on W z 6 0 C,4 c� w cy) T_ oo 0) c\1 c� 00 z T_ Lij d z co 0 I U) Lu Illl— 0 0 Z LLJ L) w u_ — LU N Z 0 U) _j LL w _j 0 > w w N 12' 7 112"iLik TO BLOCK WALL VI/ 11'11 1/2"a TOP_O�WINDOWOfENINGS V-/ 10'51/2" g�;jk BOTTOM 0- WINDOW OPENINGS W-11 9' 9 1/2' (a LOFIOF [LOOR-QPE� LING - 6'0" 0 TOP OF STONE COLUMN- - 2' 7 1/2"o kU!LD]NqFINISH FL( OR j__ _ 01 0. 0 GRADE 15'6' o TOP OF EXISTING STEEL 12' 71/2"o _jOPBL(:LCKV�ALL _ _ 2' 7 112"o BUILDING FINISH FLOOR - 0'0" o GRADE EXISTING SIGN ADD STONE FACE PROPOSED EAST ELEVATION 1/411 = 11 oil DIMENSIONS ARE APPROXIMATE AND MUST BE FIELD VERIFIED BY CONTRACTOR PRIOR TO CONSTRUCTIONS .. ... .. ... .. CLEAN AND PAINT ALL STEEL OF THE EXISTING STRUCTURE TO MATCH THE EXTERIOR BUILDING COLOR ... .. ... . STEEL STUD FRAMING FROM TOP OF BLOCK WALL TO BOTTOM OF EXISTING ... .. .. I STEEL ROOF DECK WITH 7/8" STUCCO 42" GUARD RAIL REGULAR BLOCK AREA WITH STONE FACE PROPOSED SOUTH ELEVATION 1/411 = 11 off PROPOSED WEST ELEVATION 1/411 = 11 off PROPOSED NORTH ELEVATION 1/419 = 11 off STEEL STUD FRAMING FROM TOP OF BLOCK WALL TO BOTTOM OF EXISTING STEEL ROOF DECK WITH 7/8" STUCCO -SPLIT FACE BLOCK 4" EE ` ADD STONE FACE FLAGPOLE NOT SHOWN ON ELEVATIONS _TOP OF STEEL _ S 15'9" PAINT ALL STEEL OF THE EXISTING STRUCTURE TO MATCH SPLIT FACE BLOCK TOP OF STAGE S 2'71/2" GRADE- o' o" VENEER STACK STONE TYPICAL AT ALL AREAS. DESIGN TO BE CHOSEN BY CITY OF ZEPHYRHILLS. TUD FRAMING FROM TOP OF VALL TO BOTTOM OF EXISTING ,OOF DECK WITH 7/8" STUCCO — — _LOP IILOCIjWA�L 12' 7 1/2" 10� OF V�INDO�ALOP�NIN(�S S11'11 1/2" A,CE BLOCK BUILDING FINISH FLOOR s 2' 7 1/2" GRADE s 0'0" CK AREA WITH STONE FACE DASH LINES REPRESENT STEEL CANOPY ROOF EDGE ABOVE F lu EXISTING METER AND ELECTRIC PANEL THAT SERVICES THE EXISTING STRUCTURE AND OTHER ELECTRICAL ON SITE IS LOCATED ON A PEDESTAL AT IS SOUTH WEST OF STRUCTURE LOCATION SHOWN NOT TO SCALE EXISTING STEEL COLUMN TO REMAIN AS BUILT. PAINT COLUMN TO MATCH) STEEL 04 48"X36"X8"CONCRET SLAB WITH WIRE MESH WITH 4"TO BE ABOVE GRADE 3'4" 6'8" 3' 8" 29'7'/4" 271411 3'4" 6'8" 16'0" 3'4" 5 RISEF S @ 6 5/16' WITH 42"GUARD RAIL .. ... .. ... .. .. 11" TRE kDS UP TO THE CONCRETE LANDING . . . . 36" HAND RAIt: 36" HAND RAIL .. .. ... .. ... .. ... .. .. E/9 .. ... .. ... .. IN 2'0" 1'8" EXISTING STEEL COLUMN TO REMAIN AS BUILT. PAINT COLUMN TO MATCH ALL STEEL [131 .!111jjjjj_M111jj1!jJ #5 VERTICAL RODS FROM FOOTINGS I INDOOR UNITI ELOW TO TOP OF WALL. PLACED AT ALL CORNERS, EACH SIDE OF ALL OPENINGS AND SPACED MAXIMUM 7'6%" 19'4%" 3'4"OC. POUR THESE CELLS WITH 2500 PSI CONCRETE 4%" so 0 x OUTDOOR CONDENSER UNIT TO BE u .4 MOUNTED ON FACE OF BLOCK WALL HEIGHT TO BE FIELD DETERMINED z 0 MITSUBISHI DUCTLESS 18000 BTU 0 STORAGE GATHERING 20 SEER DUAL ZONE UNIT SYSTEM 10' 0- DRYWALL CEILINGS 10'0"DRYWALL CEILINGS MODEL MX2ZC20NA2 / MSZ GL09NA-U1 20 AMP BKR 42"GUARD RAILING (oz- 4111111111011111 ion ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. .. 2 .3.4" 6' 8-1 -e 3'4'; 6' '81, .. ... .. ... .. .. �ANIJIIN*G ... .. ... .. ... .. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . W W 0 .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... ... .. ... .. ... .. .. 36" HANDRAIL cl) uj �6" HAND RAIL. NEW42" GUARD RAILING W .4 a. .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. .. ... .. ... ... .. ... .. ... .. .. 42" GUARD RAII_ 42". GUARD RAIL 0 0 Lu .. ... .. ... .. ... .. ... .. ... .. ... .. ... ... . ... .. ... Lu .. . ... .. ... .. .. U) F/5 .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... NEW42". GUARD.RAILING EXISTING CONCRETE Q .. .. ... .. ... .. ... .. ... .. RMSEDSTAGE 0' z ' Z. .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... (L ... .. ... .. ... .. .. p DASH LINES REPRESENT STEEL C) CANOPY ROOF EDGE ABOVE ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. 42" GUARD RAIL .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. .. .. LANDING ... .. ED 42' GUARD RAIL .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . ... .. ... .. .. ... .. .... *,\' .. ... .. ... .. .. E)(ISTIN . G STE�L COLUMN TO BE W . RAPPED EXISTING CONCRETE LANDING AND RAMP .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... WITH 4"X8!X1 6" BLOCK 72"ABOVE GRADE- - 8'4%" WITH NEW RAILING AS SHOWN ON ELEVATIONS THEN FACE WITH VENEER STACK STONE AND DETAILS IN PLANS AL IIJ.. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . EXISTING STEEL COLUMN TO BE WRAPPED WITH 4"X8"X16"BLOCK 72"ABOVE GRADE .. .. ... THEN FACE WITH VENEER STACK STONE EDGE OF EXISTING RAISED CONCRETE STAGE 311/2"ABOVE EXISTING GRADE LIBERTY FLAG POLE MODEL ECA30 IH 48"X36"X8" CONCRETE STAIN FINISH, SEE INSTALL DETAIL IN SLAB WITH WIRE MESH DRAWINGS WITH 4"TO BE ABOVE GRADE 27'4" 8' 0' 29'7%" PROPOSED FLOOR PLAN 1/411 11 Oil DIMENSIONS ARE APPROXIMATE AND MUST BE FIELD VERIFIED BY CONTRACTOR PRIOR TO CONSTRUCTIONS FINISH SCHEDULE SHERWIN WILLIAMS PRO EXTERIOR REGULAR BLOCK WALLS MULTI SURFACE ACRYLIC COATING. COLOR TO BE CHOSEN BY CITY SHERWIN WILLIAMS PRO EXTERIOR STUCCO FRAMED WALLS MULTI SURFACE ACRYLIC COATING. COLOR TO BE CHOSEN BY CITY EXTERIOR SPLIT FACE BLOCK WALLS FACTORY FINISH BEDROCK ORLANDO MANUFACTURED VENEER STONE FACTORY FINISH ASHER (HOME DEPOT) OR EQUAL SHERWIN WILLIAMS PRO ALL EXISTING STEEL SURFACES OF THE MULTI SURFACE ACRYLIC EXISTING STEEL STRUCTURE ABOVE THE COATING. COLOR TO BE BLOCK EVENT BUILDING CHOSEN BY CITY SHERWIN WILLIAMS INTERIOR WALLS (ALL) INTERIOR LATEX SEMI GLOSS. COLOR TO BE CHOSEN BY CITY EXISTING INSULATION INSTALLED ABOVE STEEL TO BE COVERED DURING PAINTING OF THE STEEL STRUCTURE DOOR AND WINDOW SCHEDULE PLAN SIZE STYLE FRAME HARDWARE FINISH A 3'0"Xl'4" INSULATED TINTED GLASS WHITE ALUMINUM N/A N/A PICTURE WINDOW ADA LEVER SATIN KEYED LOCK SHERWIN WILLIAMS PRO B 3'0"X7'0" FLUSH HOLLOW METAL KD METAL ADA LOW BUMPER THRESHOLD MULTI SURFACE ACRYLIC COATING. COLOR TO BE 3-4.5 BB SATIN HINGES CHOSEN BY CITY SHERWIN WILLIAMS ADA LEVER SATIN KEYED LOCK INTERIOR LATEX SEMI C 3'O'X6'8" 6PANELHARDBOARD WOOD 3-3.5 SATIN HINGES GLOSS. COLOR TO BE HOLLOW CORE CHOSEN BY CITY '%N111M4y'jt NN�'op,S L ly.4 **t N 0 soet*eolpo ��o + o". \GEN *-. o�� A.. % 1,00 4 00 FOUM OF. LlYWO40.38654 00 .4 172& fjADfC$rQFL 33526 00, I HERB OT U&ND SPECIFICATIONS WEREPR MY DIRECT SUPERVISION ARE IN CO ER 16, SECTION 1609 OF THE FLORIDA B ILDIN 1 6TH EDITION AND ASCE 7-10 FOR 139 MPH WIND ZONE RISK CATEGORY 11 Lu U) O� . C14 W Lr) <' A V) uj Z _j < U- Lu 0 cn c� Z W LU W Z C14 0 0 W 64 0, LLJ z m w 04 > Lo Lo W d Z Cgs < z U) 9 0 co Z 0 U ) c/5 0 z ER w U) W LL Lu co C14 z 0 z LLJ Lmn c) _j co'o L� I R � L? x 0 C14 own m 0 04 0 < Lf) a. In a) 0) 0) 1 Z ob & 6 0 N N N 0 " " c� > W cy) T_ oo 0) 00 04 c� z Lu z F- co 0 3 I U) _j 1: W Z 0 0 W _j u- W N Z 0 _j U- W _j o > W < r SECURE WALL AT TOP THRU STEEL ROOF DECK USING #8XI" SCREWS WITH NEO WASHER AT 6"OC CLEAN AND PAINT ALL STEEL OF THE 15'6" TOP OF EXISTING STEEL �N-�-7­SECURE WALL TO TOP OF WOOD 29'7Y4" DECK WITH #8X2" SCREWS 6" OC 3 5/8" STRUCTURAL STEEL STUDS @ 16- OC 27' 4" WITH TOP AND BOTTOM TRACK TYPICAL. 3/4"T&G PLYWOOD GLUED AND 2f 0" 314" 6'8" 3'4" 6'8" 3'4" e 2' 0" 01 NAILED WITH 10D NAILS 6"OC 2X8 #2 PINE RI 2X8 #2 PINE RIM JOIST WALL TO EXTEND TO BOTTOM OF ROOF FORMED AND POURED SOLID CONCRETE DECK AT ALL FOUR SIDES OF BUILDING STEPS WITH 5 RISERS @ 6 5/16- WITH 11" TREADS UP TO THE CONCRETE LANDING 3' 8" 16' 0" 1'8" RISER HEIGHT TO BE VERIFIED IN FIELD AND NOT TO EXCEED TIN HEIGHT. ALL RISERS MUST BE EQUAL 2X8 #2 PINE CEILING JOIST @ 16" OC WITH R-19 BATT INSULATION NAILED TO FACE OF 2X8 RIM JOIST WITH 8D NAILS 3"OC 12' 7 1/2" TOP BLOCK WALL .1 SHEET EXTERIOR FACE OF WALL WITH 1/2" CDX PLYWOOD - ------ --------- -------- ---------- M 'O'S/ AND USE #8X1" SDS AT 3" OC ON VERTICAL STUDS. COVER WITH TYVEK HOUSE WRAP, GALV WIRE LATH AND 7/8- SECURE EACH JOIST TO TOP OF WALL WITH SMOOTH STUCCO DASH LINES REPRESENT STEEL --- -------------------------------------- !2X81*2 !PINE RIM JOIST SIMPSON HETA20 STRAP POURED IN PLACE CANOPY ROOF EDGE ABOVE AND FILL NAIL HOLES WITH 1 0DX1 1/2" NAILS----,,/ COMPAcT SOIL TERMITE TREATMENT NOT v 1/2" CEILING GYPSUM BOARD PLACE GALV PLATE BETWEEN JOIST AND ;0 REQUIRED WITH 4"2500 PSI CONCRETE TOP OF WALL AT EACH JOIST ;t SLAB W TH WIRE MESH SINGLE KNOCK OUT LINTEL BLOCK AT TOP I OF WALL WITH 1 #5 REBAR TIED TO ALL ---------- ----------- - -------------------- VERTICAL RODS AND POURED SOLID WITH i 2500 PSI CONCRETE I . z� 7— �;� z_z1v f—B] TBI ----------------------------------------------------------------------------- SPLIT FACE BLOCK 3/4" TUFF R INSULATION BOARD 3/4" STEEL FURING @ 16" OC 7, 1/2"GYPSUM WALLBOARD COMPACT SOLID IN THIS AREA TERMITE \---TREATMENT 6 MILL VISQUEEN, WIREMESH ------ N\ 4"2500 PSI CONCRETE SLAB #5 VERTICAL RODS AT LOCATION SHOWN ON FLOOR AND FOUNDATION PLAN WITH FILLED CELLS. MINIMUM 25" LAP TYPICAL f2 TYPICAL 4" CONCRETE SLAB WITH WIRE MESH AND 6 MILL VISQUEEN OVER CLEAN COMPACT --------------------------------------------------------------------------- TERMITE TREATED SOIL WIZZA0771,41) M1 -,o(*7,9 F&-1 -------------------------- ---------------- ---- 2' 7 1/2" BUILDING FINISH FLOOR A'8" �3'4' 8" 2'0 VZO REGULAR BLOCK AREA WITH STONE FACE 0101, GRADE .. . ... FT-1 I 2X8 #2 PINE RIM JOIST M'10 m M1l M1 Ell loll loll loll ons� loll 2X8 #2 Ir PINE JOIST @ 16" Ell I1M M111 Ell Ell OC m Ell M11 Ell lose Mill Ell 0 m 0 W, sell loom loll 11ff loll I 0—in SEMI loll loll on I 2X8 #2 PINE RIM JOIST 27'4" CEILING JOIST PLAN 1/411 = 11 off 16" WIDE X 10" DEEP CONCRETE FOOTING WITH 3- #5 REBAR ON CHAIRS TYPICAL BUILDING CUT SECTION DETAIL NOT TO SCALE 3 5/8" NON STRUCTURAL STUDS WITH 1/2"GYPSUM WALL BOARD EACH SIDE. SECURE STUD WALL AT BOTTOM THROUGH STEEL TRACK WITH MASONRY ANCHORS THAT PENETRATE CONCRETE MINIMUM 1" SPACED 24"OC WITH STUD EXTENDING TO BOTTOM OF CEILING JOIST ABOVE TYPICAL INTERIOR METAL STUD WALL DETAIL NOT TO SCALE 48"X36"XB" CONCRETE SLAB WITH WIRE MESH WITH 4"TO BE ABOVE GRADE 04 .. .. ... .. ... EXISTING CONCRETE RAISED STAGE r . .. . . . .. . .. . . . .. . DASH LINES REPRES NT STEEL CANOPY ROOF EDG ABOVE ... .. .. .. .. .. ... .. .. .. .. .. r .. ... .. ... .. ... 29'71/4" FOUNDATION PLAN 1/419 = if off DIMENSIONS ARE APPROXIMATE AND MUST BE FIELD VERIFIED BY CONTRAc'rOR PRIOR TO CONSTRUCTIONS #5 VERTICAL RODS FROM FOOTINGS BELOW AND TO EXTEND INTO SLAB AT TOP. PLACED AT ALL CORNERS AND SPACED MAXIMUM 3'4"OC. POUR ALL CELLS OF LANDING WALL SOLID WITH 2500 PSI CONCRETE TYPICAL 16"WIDE X 8'DEEP FOOTING AT LANDING WITH 245 REBAR ON CHAIRS #5 VERTICAL RODS FROM FOOTIN BELOW TO TOP OF WALL. PLACED AT ALL CORNERS, EACH SIDE OF ALL OPENINGS AND SPACED MAXIMUM 3'4" OC. POUR THESE CELLS SOLID WITH 2500 PSI CONCRETE . .. ... .. .. LIBERTY FLAG POLE MODEL ECA30 IH STAIN FINISH, SEE INSTALL DETAIL IN DRAWINGS 48"X36"XB" CONCRETE SLAB WITH WIRE MESH WITH 4"TO BE ABOVE GRADE 81001 0 �111#i 00 "'q ze N 00 4 0 A C E A=3 8 6 5 4 oom 00 1172, - c li;�G526 I HERBY C I SPECIFICATIONS WERE PREP DIRECT SUPERVISION ARE IN COMPL 6, SECTION 1609 OF THE FLORIDA BUILDING EDITION AND ASCE 7-10 FOR 139 MPH WIND ZONE RISK CATEGORY 11 . N ILL! Lr) Lu W Z -j < LL C\1 w 2 'i c") 0 cn z 0 w w (b z N (D Ln I M� LLJ cj > LIJ z M LLI Ln W (j Z U) 06 <U) Z Lu z z (D 0 rn W.f U) Z ER LU w LL 9 to 04 Z 0 (LLLi) z Lu u') 2 _j co 00 u- X C-4 0 LLI �� 0 c%1 CC 0 0) a) 0) T- T- T- z ob (06 6 0 C14 04 C14 c� w ce) T- oo a) 00 c� C*4 z d z 0 U) "11 < 7: w < 0 0 Z W C) LL W N Z 0 U) -j LL w 0 > >- w < w F- >- 17 si w N __ , � 'I I �_ , -, _. - __ I I I - —1 — 1 FORMED CONCRETE CAP AT TOP OF BA� SLOPED TO FOUR SIDES OF STEEL COLL SILICONE CAULK TO FACE OF STEEL COL AFTER CAP HAS DRIED PRIOR TO PAINTIIS 61 0" TOP OF STON 6- 1/2" VERTICAL REBAR FROM FOOTING BASED AND WILL EXTEND INTO THE CAP 3". FILL ALL CELL OF BLOCK SOLID WITH CONCRETE 2' 7 1/2" ;�_ BUILDING FINI 01011 GRADE 0�_ — — 1 1/2" DIA 42" GUARD 1 12" EXTENSION 1 "Xl " VERTICAL SPINDLES SPACED MAXIMUM 4" APART- 11091 1 1/2" DIA 42" GUARDRAIL-----\ of FACE VIEW RAMP RAILING TO BE INSTALLED AT ONE SIDE ONLY OF RAMP DUE TO LIMITED SPACE L COLUMN EDGE OF NEW CONCRETE BASE AT THE BOTTOM OF THE EXISTING — COLUMN r! 10 1 Of F-r-L %�ULUIVIIN EXISTING TOP OF COLUMN CONCRETE FOOTING PAD FACE WITH VENEER STACK STONE EXISTING STEEL COLUMN --------- 4"X8"Xl6" BLOCK 72"ABOVE GRADE K8"Xl6" BLOCK 72" ABOVE GRADE FACE WITH VENEER STACK STONE 0 10� JSTING STEEL COLUMN 'OUR 8" DEEP CONCRETE AROUND BASED OF 6- 1/2" VERTICAL REBAR FROM FOOTING :XISTING STEEL COLUMN TO ALLOW FOR THE BASED AND WILL EXTEND INTO THE CAP " BLOCK TO SET ON TOP. PLACE 1 # 5 REBAR 3". FILL ALL CELL OF BLOCK SOLID WITH IENT AROUND COLUMN 2" FROM BOTTOM AND CONCRETE 'OP OF CONCRETE POUR ,NCRETE FOOTING GRADE FOR COLUMN TTOM OF CONCRETE AROUND I-IIAIMM 1=nn-r1K1t10- MAM0 A" M01=0 WF L_ AND MINIMUM 4" WIDE -50 NAM) MAIL JSION 1 1/2" DIA 42" GUARD RAIL 1 1/2" DIA 36" HAND RAIL ALL RAILING AND SPINDLES TO BE 1 1/2"SATIN FINISH S. . TOP VIEW COLUMN BASE SECTION DETAIL NOT TO SCALE it 019 I "X1 " VERTICAL SPINDLES SPACED MAXIMUM 4"APART RAMP AND LANDING EXISTING AND NOT BE MODIFIED CORE DRILL CONCRETE AND EPDXY VERTICAL SUPPORT POST OR SECURE TO TOP OF CONCRETE WITH APPROVED ;0 TYPICAL RAMP RAILING HARDWARE THAT CAN SUPPORT MINIMUM 250 LBS OF FORCE NOT TO SCALE Single sheave truck, cast aluminum revolving, non -fouling, internal Model ECA30 lH halyard truck 1/8" x 7xl 9 M il-C-5424 0 Stainless steel aircraft cable Standard flag arrangement: 5' X 8' 9 Neoprene coated 2" diameter steel counterweight I? Nylon beaded retainer ring .0 0 CL 0 C1 X W Revolving non -fouling internal halyard truck, cast aluminum body, 26 stainless steel ball bearings, and 2-1/2" diameter plated steel sheave. co Gearless, self locking direct _i� drive winch with six tumbler 0) cylinder lock 0 > 0 0 0 CD V 0 < c� Winch Detail Aluminum flash collar 3000 PSI concrete 4-) All shafts with overall Ap Hardwood wedges 0 length of more than (supplied by others) 0 38'-6" are shipped in CL two sections. Dry sand tightly tamped after aligning pole .2) Foundation sleeve -16 ga 0 U) hot dip galvanized steel Each section matched marked Steel centering wedges for field assembly. Exposed 0 portion of jam sleeve must 114" Steel base plate I AL 1 U_ be well lubricated prior to ;11 :11 assembly. L 1 61? 1/4" Steel support plate welded to grounding spike 1-1/2" maximum shop 12" gap allowed for field fiffing (ram for tight joint) 16" Filename. F-CA30 1H single sheave�_revolving truck.ai Pro*ect: Ground set tapered aluminum flagpole: ALLOY: 6063T6 EDER FLA(i Date: Location: Exposed height: 30'-0" Overall height; 33�4' MANUFACTURING COMPANY Revision: Architect: Ship in 1 section Butt diameter., 6" 1000 W. Rawson Avenue Contractor Top diameter 3-1/2" Wall thickness: .156" Oak Creek, WI 53154 Customer: Finish: 100 grit polish Job: 1 1/2" D IA 42" GUARD RAIL 4" f-f ALL RAILING AND SPINDLES TO BE 1 1/2" SATIN FINISH S , S. COMPACT SOIL TERMITE TREATMENT NOT RIEQUIRED WITH 4" 2500 PSI CONCRETE SLAB WITH WIRE MESH #5 VERTICAL RODS FROM FOOTINGS BELOW AND EXTEND INTO 4" CONCRETE SLAB AT TOP. PLACED AT ALL CORNERS AND SPACED MAXIMUM 3'4"OC. POUR ALL CELLS SOLID WITH 2500 PSI CONCRETE 16" WIDE X 8" DEEP FOOTING WITH 245 REBAR ON CHAIRS SEE FOUNDATION PLAN FOR MORE DETAILS OF LANDING TREAD WIDTH lift Rim 1 1/2" DIA 42" GUARDRAIL 1 1/2" DIA 36" HAND RAIL _-_-: -1 b J )r ;- im. 1 0" CORE DRILL C011 ID EPDXY 4 A% I VERTICAL SUPPORT POST OR SECURE 5 t TO TOP OF CONCRETE WITH APPROVED 4 HARDWARE THAT CAN SUPPORT MINIMU M 4 4 4 4 250 LBS OF FORCE q.-AL � co RISERS HEIGHT TO BE VERIFIED IN FIELD AND CAN NOT EXCEED 7" IN HEIGHT AND ALL MUST BE EQUAL REAR LANDING AND STAIR DETAIL NOT TO SCALE "X%111111if, OtAAS C 0 . 04 LU LL1 W tn A W Z' -i U_ N W C, 2 C6 C,) 0 C/5 C� Z W W (0 U) Z 04 LU LU Z CD N 0, N > to Z n W W 0 Z 06 < Z (n in LL1 Z 0 Cn =) Z 0 U) Z FR LW1J Cl) W LL W C, 0 Z C11), Z W _J "o co U_ N X 5 C-4 0 W �� (10 a CJ 0 < L0 0- 0 W CF) 1 0) I a) 1 Z ob 6 6 0 C14 C14 04 C� CY) T_ oo (7) 00 CN Z d LU Z co 0 0 N U) _J -_J 1: W NO Z 0 0 W L) _J U_ W N Z 0 U) _J LL W _J 0 > W < W N I HERBY C I 'M WERE PRE 7P 0 P1 ARE IN C Ll FLORIDA BUILDIN FOR 139 MPH WIND E C11.7,41TLN526 0 44� DLA SPECIFICATIONS 1�-, IRECT SUPERVISION 'kVSIE CTION 1609 OF THE \DITION AND ASCE 7-10 CATEGORY 11 S2 ELECTRICAL SPECIFICATIONS 1.1 SCOPE A. WORK INCLUDED: Include the following Work in addition to items normally part of this Section: 01 Wiring for lighting and power. 02 Installation of lighting fixtures with lamps. 03 Lighting panelboards and distribution panelboards. 04 Connection of equipment shown. 05 Control wiring. 06 Disconnection and removal of existing fixtures and wiring not to be reused. 1.2 MINIMUM COMPLIANCE STANDARDS A. All work shall be done in accordance with the requirements of the following: 01 Latest adopted issue of the National Electrical Code, NFPA 70. 02 Other applicable NFPA Codes. 03 Regulation of local authorities having jurisdiction. B. Furnish and install all labor, material and equipment and services necessary for complete and safe installation of the electrical system Indicated on the drawings and noted in the specifications hereinafter. Electrical systems and equipment shall in general include the following: 01 General provisions for electrical work. 02 Wiring, distribution equipment and devices. 03 Lighting fixtures and lamps. 04 Grounding system. 1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK A. DRAWINGS: Electrical drawings considered diagrammatic and indicate general arrangement of work and systems. Refer to other drawings to verify location of equipment, etc. Check drawings of other trades to verify exact space condition or underground lines. Drawing Scales prohibit the indication of all offsets, fittings and accessories required, however these items will be provided by this subcontractor at no extra cost to the owner. B. QUALITY OF MATERIALS: New, best of their respective kind, free from defects, and listed by Underwriter's Laboratories, Inc. or bearing their label. C. SHOP DRAWINGS: Submit four (4) copies of shop drawings for lighting fixtures and panelboards. Obtain approval before equipment is ordered, built or installed. D. EXCAVATION AND BACKFILLING: Excavate, backfill and restore surfaces for all electrical work. E. Visit site and inspect existing facilities before bid in order to ensure proper evaluation of working conditions and location of existing equipment. 1.4 WiRING, DISTRIBUTION EQUIPMENT AND DEVICES A. CONDUCTORS: Copper, in accordance with ASTM Standards, size references AWG. Conductors No. 10 and smaller size solid, No. 8 and larger stranded. Insulation of conductor thermoplastic, type THHN (min. size: No. 12) any wire Installed outside, underground, in slabs, or exposed to moisture shall have THWN insulation. B. RACEWAYS: RIGID STEEL CONDUIT, full weight pipe galvanized, threaded, and minimum 1/2 Inch except as noted or required for wiring. ELECTRICAL METALLIC TUBING (EMT), thin wall pipe, galvanized, threadless, cornression fittings, and minimum 1/2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT, continuous singlestrip, galvanized, and minimum 1/2" size except as noted or required for wiring. PVC CONDUIT, heavy duty type, size as indicated. Type AC or MC cable where permitted. Separate raceways shall be used for each voltage system. C. DISCONNECT SWITCHES: General Duty, horsepower rated for motor loads 600 or 250 volt rating, fused or non -fused as noted; number of poles as indicated, cover interlocked with switch. Enclosure NEMA 1 for Indoor use and NEMA 311 for weatherproof applications. Switch to be Square "D" or equal. ELECTRICAL NOTES .. ... .. ... .. ... .. ... .. . .. . .. . .. . .. . EXISTING METER AND ELECTRIC PANEL THAT .. .. ... .. ... .. 1P20AMPBRK ... .. ... .. WILL SERVICE THE NEW STRUCTURE AND WAECOAcK 6N TIMER OTHER ELECTRICAL ON SITE IS LOCATED ON - - - - - - - - - - - -- - - A PEDESTAL AT IS SOUTH WEST OF STRUCTURE. LOCATION SHOWN NOT TO SCALE -LA III I FM EXISTING BREAKERS TO ACCOMMODATE THE NEW BUILDING ELECTRICAL. ELECTRICAL INDPOR UNITI CONTRACTOR TO VITRIFY IN FIELD. FED NEW BUILDING FROM PANEL IN PVC CONDUIT AS NEE 1 P 20 AMP BRK DED FROM EXISTING PANEL D. CIRCUIT BREAKERS: Molded case, thermal -magnetic quick -make, quick -break, bolt -on type with manually operated Insulated trip -free handle. Multi -pole types with internal common trip bar. Terminals suitable for copper or aluminum conductors. Interrupting capacity minimum 10,000 RMS symmetrical amperes circuit breakers to be Square "D" or equal, type as required. E. PANELBOARDS: Voltage, phasing and ampere ratings as indicated, circuit breaker type as indicated, busbars of hard drawn copper, minimum 98% conductivity, galvanized steel back box, door and trim. All corners lapped and welded, hardware chrome plated with flush lock and catch. Hinges semi - concealed, 5 knuckle steel with nonferrous pins, 180 degree openings. Minimum gutter space 5- 3/4" sides, top and bottom. Increase size where required by code. Directory holder complete with clear plastic transparent cover indicating typewritten list of feeder cables, conduit sizes, circuit numbers, outlets of equipment supplied, and their location. Circuit breaker type panelboards to be Square "D" type NQOD or I -Line, or equal. A plastic label shall be located on exterior of panelboard Identifying the system voltage, phase, and current rating. F. WIRING DEVICES: All devices the product of the same manufacturer. Wall switches sin_qle pole, 20 am ere, 120 volt. Wall switches three-way, 20 ampere, 120 volt. Receptacles duplex, Zwlre; 3 PoPe grounded, 20 ampere, 120 volt. G. DEVICE PLATES: Provide for all outlets where devices are installed. Provide engraved marking for special outlets. Provide blank plates for empty or future outlet boxes. DEVICE AND DEVICE PLATES COLORS TO BE VERIFIED WITH INTERIOR DESIGNER AND OWNER. 1.5 LIGHTING FIXTURES AND LAMPS A. Furnish and install complete system of lighting fixtures, lamps, accessories and supports as specified and indicated. Submittals of equal quality are allowed. 1.6 GROUNDING SYSTEM A. EQUIPMENT: Ground non -current carrying metal parts of panelboard, raceways and all lighting fixtures. All conduits shall have equipment grounding conductors. 1.7 INSTALLATION A. Secure all supports to building structure. Support horizontal runs of metallic conduit not more than 10 feet apart. Run exposed raceways parallel with or at right angles to walls. B. Pass raceways over water, steam or other piping when pull boxes are not required. No raceway within 3 inches of steam or hot water pipes, or appliances, except crossings where raceway shall be at least 2 Inches from pipe cover. C. Cut conduit ends square, ream smooth. Paint male threads of field threaded conduit with graphite base pipe compound. Draw up tight with conduit couplings. D. Leave wire sufficiently long to permit making final connections. In raceways over 50 feet in which wiring is not installed, furnish pull wire. E. Verify locations of outlets and switches. F. Support panel, junction and pull boxes Independently to building structure with no weight bearing on conduits. G. Connect conduit to motor conduit terminal boxes with flexible conduit; minimum 18 inches in length and 50% slack. Do not terminate in or fasten raceways to motor foundation. H. Contractor to remove and salvage all abandoned electrical equiment. 1. This contractor shall warrant all labor and materials for one year from date of final written acceptance. 1. All work to be done in accordance with all current national and local codes and ordinances. 2. Notify Engineer of any discrepancies between these drawings and the actual field conditions. Obtain clarifications from the Engineer or Owners prior to commencing work. 3. Contractor will visit site prior to bidding, no allowances for any extra expenses will be granted as a result of not visiting site. 4. Wire to be THHN/THWN Copper, min. size 14 AWG, unless shown otherwise. 5. RACEWAYS: RIGID STEEL CONDUIT: full weight galvanized threaded pipe, EMT CONDUIT: compression fittings, PVC: schedule 40, all as allowed by local codes. Separate raceways shall be used for each voltage system. 6. Any installation conflict with other trades shall be brought to the attention of the Engineer for clarification before proceeding. 7. Contractor will verify location of equipment and connect as required for clearances and connections. 8. All ourdoor electrical equipment to be NEMA 3R rated. 1P20AMPBRK UJ OUTDOOR CONDENSER UNIT TO BE RK� MOUNTED ON FACE OF BLOCK WALL Z1 1P20AMP B HEIGHT TO BE FIELD DETERMINED 0 MITSUBISHI DUCTLESS 18000 BTU 0 20 SEER DUAL ZONE UNIT SYSTEM MODEL MX2zC20NA2/MSZGLOgNA-Ul 20 AMP BIRK IP 20 AMP BRK //7r2 Q7J 1P20AMPBRK 1_71-12f7hCEN 4fT7T— .. .. ... .. ... .. ... .. ... - - ------ :,� ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . .. . .. . .. . .. . . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . . ... .. ... .. ... .. .. .. .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... . .. .. ... . ... .. ... .. ... .. .. ... .. ... .. .. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. A... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. ... ... .... ... .. . . .. . .. . .. . .. . .. EXISTING CONCRETE .. .. ... RAISED STAGE . ... .. ... .. ... .. ... .. ... .. .. ... . ... .. ... .. ... .. .. . .. . .. . .. . .. . .. .. ... .. ... .. ... .. ... .. ... .. ... . ... .. ... .. ... .. ... ... .. ... .. ... .. .. . ... .. ... .. .. . .. . .. . . .. . .. . .. . .. 3 I.. .. ... .. ... .. ... .. ... .. ... .. .. . .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .. ... .1 . . .. . .. . .. . . ... ... .... ... .... ... .. ... .. ... .. ... .. ... . ... .. ... . ... .. ... .. ... .. ... .. ... .. ... .. . ... .. ... 03m .. ... .. .. .. ... .. LIBERTY FLAG POLE MODEL ECA30 IH STAIN FINISH, SEE INSTALL DETAIL IN DRAWINGS PROPOSED FLOOR PLAN 1/411 = 11 Oil ELECTRICAL LEGEND / SCHEULDE 013- F I LITHONIASBL4LP835 4' LED LITHONIA TWH LED P1 U)P WRAPAROUND FIXTURE DWHXD WHITE WALL PACK 110VWEATHER WIRE TO TIMER AT PANEL PROOF OUTLET C� 13 LITHONIA ECR LED FLUSH CEILING 3 WAY SWITCH COMBO LED UNIT FIXTURE ATTIC AREA C= (b LITHONIA EU2C 110 V OUITLET SWITCH EXIT LED 20 AMP ENCLOSED BIRK XXXXII) 016AY V \j C E 00 LICI*1 38654 00 00 28 ADE� V,3.3526 sees clk;; I HERBY IN ND SPECIFICATIONS WERE PRE Y DIRECT SUPERVISION ARE IN COMPL R 16, SECTION 1609 OF THE FLORIDA BUILDING 6TH EDITION AND ASCE 7-10 FOR 139 MPH WIND ZONE RISK CATEGORY 11 LU L�u (1) Z _J < LL N W 2 R, 0 04 Z LO Z 0 LU UJ Z M (3) > W) 04 W LLJ (j Z 06 Z Cn C) U.1 Z 9 C/) =) Z('0D Z 0 U5 FX LWU Cl) W LL K (0 C, 0 0 Z UM, Z 11.1 LL X 0 N 0 W!2, M 0 C,4 C) < U) 0-de ICD I 1(=) CD Z 0 0) oo C0 04 00 C� Z T_ 6i Z CD 0 N CY) U) CY) < W < ry �- 0 0 Z W CL LL LU N Z 0 U) _J LL W 0 > >_ W < W F_ E 1 W N