HomeMy WebLinkAbout5935 7th St (2)R \�\ PROPOSED PLAN - SERVICE YARD 1/4" = 1'-0" KEYED NOTES 10 CONTRACTOR SHALL PROVIDE AND INSTALL AN EXHAUST AIR LOUVER EQUAL TO A RUSKIN EME6325D, WITH A MINIMUM FREE AREA OF 0.26 SF, UNDER THE EAVE OF THE ROOF. THE LOUVER SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND AS APPROVED BY THE LISTING OF THE LOUVER. Q CONTRACTOR SHALL PROVIDE AND INSTALL AN OUTSIDE AIR INTAKE LOUVER EQUAL TO A RUSKIN EME6325D, WITH A MINIMUM FREE AREA OF 0.42 SF, UNDER THE EAVE OF THE ROOF. THE LOUVER SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND AS -APPROVED BY-INE LISTINC-QF THE LOLLVER. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF T4E EXISTING ROOF INSULATION. IF THE ROOF INSULATION IS ENTIRELY ABOVE OR ADHERES TO THE BOTTOM OF THE ROOF DECK THE CONTRACTOR SHALL INSTALL THE AHU WITH NO ADDITIONAL REQUIREMENTS. IF THE INSULATION IS INSTALLED ON THE TOP OF THE CEILING, THE GENERAL CONTRACTOR SHALL BUILD AN INSULATED BOX SURROUNDING THE AHU. THE BOX SHALL BE OF PROPER SIZE TO ALLOW FOR A PERSON TO SERVICE THE UNIT, SHALL INCLUDE REQUIRED CLEARANCES, PROPER LIGHTING FOR SERVICE, AND STRUCTURAL SUPPORT FOR THE UNIT, BOX, AND SERVICER. THE MECHANICAL CONTRACTOR SHALL PROVIDE A 4" SPIN -IN FITTING WITH A VOLUME DMAPER ON THE SUPPLY DUCT LOCATED WITHIN THE BOX, BALANCE TO 50 CFM. ROUTE INSULATED CONDENSATE DRAIN PIPING TO EXTERIOR OF BUILDING. TERMINATE INDIRECTLY A MINIMUM OF THREE INCHES ABOVE GRASSY AREA. PIPE ROUTING SHALL NOT BE VISIBLE FROM WINDOW. PAINT WEATHER -EXPOSED PVC PIPING WITH ONE COAT OF UV RESISTANT PAINT. CONTRACTOR SHALL PLACE AHU ABOVE LAY IN CEILINGS OR PROVIDE AN APP.RORIATELY SIZED ACCESS PANEL. CONTRACTOR SHALL PROVIDE AN STALL AN EXHAUST AI}iCOUVER E L TO A RUSKIN EMED6325D, WITH A MINIMUM FREE AREA OF 0.19 SF, UNDER THE EAVE OF THE ROOF. THE LOUVER SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND AS APPROVED BY THE LISTING OF THE LOUVER. O5 CONTRACTOR SHALL ROUTE REFRIGERANT PIPING UNDERGROUND AND RISE UP INSIDE OF BUILDING. SEE DETAIL ON SHEET M402. GENERAL NOTES 1. CONTRACTOR SHALL INSTALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH ALL STATE AND LOCAL CODES, CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK, PIING, SUPPORTS, ETC., NECESSARY FOR A PROPER INSTALLATION AND OPERATION OF NEW HVAC SYSTEM. 2. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. 3. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH A VOLUME DAMPER IN THE BRANCH CONNECTION UNLESS NOTED OTHERWISE. ALL ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED WITH CONICAL SPIN -IN FITTING WITH INTEGRAL VOLUME DAMPER. I� O f��JIT�®IN �1 1FT IAV ■ design styles architecture 70 E Columbus lave TOO, Florida 33605 813 241 6700 f 813 247 3757 designs#ylesarch tecture.com AA0003393 5935 7th Street Zephyrhills, FL 33542 Prepared for JB Realty Partners In Association with: genesis engineering (Eg en e s t group, Ilc. s 2601 cattleman rd., suite 501 sarasota, fl 34232 w .geneng.net coa#29304 project#18-189FL Professional Seal Ilillll!///f�/ /v fl * No. 551 0 •• *5f ill M STATE OF i. OR 1 0 No. Issue Description Date 1 PERMIT AND BID SET 12/10/2018 No. Revision Description Date 1 PERMIT COMMENTS 3/8/19 Drawn By: CTF Checked By: RMH Project Number: 18190 Sheet Title PROPOSED PLAN Original drawing is 24 x 36 Do not scale contents of drawing Sheet Number PROPOSED PLAN ;a, 1/4" = 1'-0" M102 R 1 EXIT ACCESS TRAVEL DISTANCE: 54' - 7" < 200'-0" (FBC T1017.2) DRAFTSTOPPING IN ATTIC: 5/8" GWB ATTACH TO ONE SIDE OF ROOF TRUSS (FBC 718.4) DEAD END: 10'-1" < 20'-0" (FBC 1020.4) 0 •■l% x `%` STORAGE x P R13, s•. 4 I ®` 1 II! w 1 / sl-OR4�E 286SF is M I / % 300 SF/OCC. ;I! a _ / % i \ Co— % \ r I III I! °° O O / / a� N I!! % ®®Ile 1 M N 1 TEAM WORK 1 < vUJ N / 11 1M / co / 11 1 1 = === • q OFrOFFICE � N / �. Np 1 1 BUSINESS AREA j / \\\ - • �� E 1 •• 1S: � N I I // \ 11 ••�� 1 • i 47 q / / I I • • 1 100 SF/OCC. 1 ° LAB 11 � - i T 1 1�1 ��� -� rn I I 11 `� • • ®® ® • • �• • 11• ®®s • • Q • ® • ® • 0111� • ® • 011111111111• • 5/ 01 w 11 ` 00 ELI ' 1 of \..:R,.::. e iIF 1 -L J T EA �A E i LOUNGE _ _ o I If I 1 / O LD •• u`a 1 a QU5 1® I O• \ ssrz-�t�_-rid I / 77-7 • •• (17� / \ If / \\ 11 ACCESSOR 4 11�,C° •o of e .. S'T RGE / Q MEAZICAL0 COMMON PATH OF TRAVEL: 15'-7" < 75" (FBC T1006.2.1) BUSINESS AREA M 279SF (ACCESSORY A-3 M ® 300 SF/OCC. LESS THAN 50 OCC) A, �� ����' ' % � 34" 170 5 32'-1" TC-)RA ¢E-. \El i/� \� \� ® 1 22 � I � ♦ 1'I / / I 317SF �4F / 1 15 SF/OCC. ® / 29'-5" E ST,ELEC. 6 ®------------------------° ROI o' STO R. 0 4 r 1 / ---�— ACCESSORY ACCESSORY ACCESSORY ACCESSORY WILDING; C9F ICIAI_ STORAGE/ STORAGE/ STORAGE/ STORAGE/ MECHANICAL MECHANICAL MECHANICAL MECHANICAL 1 1 1 1 38SF 67SF 47SF 47SF 300 SF/OCC. 300 SF/OCC. 300 SF/OCC. 300 SF/OCC. 1 1 ST FLOOR LIFESAFETY PLAN 3/16" = 1'-0" 11 1!7°' 2 EQUIPMENT - FIRE EXTINGUISHER CABINET 1 1/2" = 1'-0" METAL STUD U.L. 3A-40BC FIRE EXTINGUISHER FINISH WALL SEMIRECESSED F.E.C. DECAL ADA COMPLIANT FLUSH PULL HANDLE LIFE SAFETY LEGEND EGRESS LOAD AISMIlk EGRESS CAPACITY IN # OF OCCUPANT EGRESS WIDTH IN INCHES 24 227 34" = EGRESS CAPACITY = EXIT SIGN}_ EXIT TRAVEL DISTANCE design lyle architecture COMMON PATH OF TRAVEL DISTANCE 708 E Colurynbus Drive / Tampa, pa,Florida3 0 OCCUPANTLOAD P 813 .41 700 II 813 247 3757 �esicI��� _�'��r1'I�,�-�r•r� FIRE EXTINGUISHER - SURFACE MOUNT #A=AO003393 FIRE EXTINGUISHER - SEMI RECESSED All reproduction &intellectual property rights reserved 2017 Project ® = DRAFTSTOPPING )/1—N 10 r..a e Gi DIVIG (FL) - ZEPHYRHILLS 5935 7,h Street Ze hyrh€lls, FL 33542 Prepared for DAVITA MEDICAL GROUP Area Schedule (Gross Building) NAME �— FUNCTION OF SPACE j GROSS ! NET TFTOR OCC. i SF PER AREA ' OCC. 1 OCC. LOAM GAS ACCESSORY STORAGE / MECHANICAL GROSS 36 SF 300 1 BIOHZD. ACCESSORY STORAGE / MECHANICAL GROSS 94 SF 300 1 2 ELEC. STORAGE ACCESSORY STORAGE / MECHANICAL ACCESSORY STORAGE / MECHANICAL GROSS I GROSS 67 SF 27_9 SF 300 300 1 1 STORAGE ACCESSORY STORAGE / MECHANICAL -- ---4 GROSS --� ---286 SF '— 300 1 WAITING BUSINESS AREA (ACCESSORY A-3 LESS THAN 50 OCC) j NET 317 Sr- _ 15 _--_ 22 BUSINESS BUSINESS AREA IGROSS 4700 SF 100 46 BUILDING TOTAL 5780 SF 76 FIRE EXTINGUISHER KEY DESCRIPTION Count MANUFACTURER MODEL COLOR COMMENT FE01 SEMI RECESSED FIRE EXTINGUISHER CABINET 3 SEE SPECS In Association with HEES & ASSOCIATES, INC. CONTACT: KARL HEES 1381 5TH ST SARASOTA, FL 34236 PHONE: 941.955.4555 GENESIS ENGINEER GROUP; LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 Professional Se a AR0015805 ' A e' t, ra AR 9 15805 QED:54 PM No. Revision escption Date 1 PERMIT AND BID SET 12/10/2018 No. Revision Description Date PERMITii 8 Drawn By: AIJ Checked By: SRS Project Number: 18190 Sheet Title FIRST FLOOR LIFE SAFETY PLAN Original drawing is 24 x 36 Do not scale contents of drawing Sheet Number r"0k'0'*J% 1 L Vb..- No OS9 S;7 11