HomeMy WebLinkAboutWalmart Store 00706-249PROTECTION CRITERIA LEGEND HOSE MAXIMUM SPRINKLER OCCUPANCY DISCHARGE PRESSURE ALLOWANCE SPACING DESIGN BASIS CLASSIFICATION (# OPERATING SPRINKLERS - DESIGN AREA) (GPM) (SQ FT) SALES FLOOR/ INTERIOR GARDEN CENTER 30 PSI (2 AS-2S/1 L) CLASS I -IV ON SHELF TO 12'-0" (25'-0" CEILING HEIGHT), 5'-0" AISLES; UL LLC TECHNICAL REPORT PROJECT (SH - OPTION 2A) 18 PSI (9 AS-4S/2L & 1 S/1 L) 250 140 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TEST SRR 06151702 SALES FLOOR/ INTERIOR GARDEN CENTER 25 PSI (2 AS-2S/1L) CLASS I -IV ON SHELF TO 12'-0" (25'-0" CEILING HEIGHT), 5'-0" AISLES; UL LLC TECHNICAL REPORT PROJECT (RNC - OPTION 2B) 10 PSI (12 AS-4S/3L) 250 140 4788122552, NC27954 ; TABLE 2 SUMMARY OF TESTS, TEST GONDOLA 10041702 12 PSI (2 AS-2S/1L) CLASS I -IV RACK STORAGE TO 15-0 (18-0 CEILING HEIGHT), 4-0 /7-6 AISLES; UL LLC TECHNICAL REPORT STOCKROOM -GM/GR (SL -OPTION 4) 7 PSI (12 AS-4S/3L) 250 100 PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TESTS SRR 04191702 / DRR 09191702 / MRR 09211702 CORRIDORS/TENANT SPACES/GROCERY PREP/FOOD 0.2011500 SQ FT 250 130 CLASS I -IV TO 10'-0"; 13: TABLE 13.2.1 AND FIGURE 13.2.1 TENANT/OFFICES (MISCELLANEOUS STORAGE) CLASS I -IV TO V-0", MISCELLANEOUS STORAGE; NFPA 13: FIGURE 13.2.1 CURVE OH2, TABLE 13.2.1 ENTRY CANOPY (MISCELLANEOUS STORAGE) 0.20/7 SPRINKLERS OPERATING 250 130 AND 13:11.2.3.4.2 AND Al1.2.3.4.2 225 LIGHT HAZARD, 13: 11.2.3.1.1, FIGURE 11.2.3.1.1 RESTROOMS/BREAKROOMS (LIGHT HAZARD) 0.1011500 SQ FT 100 AND TABLE 11.2.3.1.2 ENTRY VESTIBULES (ORDINARY HAZARD GROUP 2) MINIMUM 0.20/1500 SQ FT 250 130 ORDINARY HAZARD GROUP 1 (NO STORAGE), 13: 11.2.3.1.1, FIGURE 11.2.3.1.1, AND TABLE 11.2.3.1.2 OR ENTIRE AREA COOLERS/FREEZERS (MISCELLANEOUS STORAGE) MINIMUM 0.20/1500 SQ FT 250 130 CLASS 1-III TO 12'-0" ON SINGLE ROW RACK, 13: TABLE 13.2.1 AND FIGURE 13.2.1 OR ENTIRE AREA 12 SPRINKLERS AT 15 PSI 250 100 RUBBER TIRES TO 13'-6"; ON -SIDE AND ON -TREAD ON FIXED RACKS WITHOUT TIRE STORAGE AREA (RUBBER TIRE STORAGE) EACH OR ENTIRE AREA SOLID SHELVES; NFPA 13:TABLE 18.4(d) K25 ESFR SPRINKLERS USED TIRE STORAGE (RUBBER TIRE STORAGE) MINIMUM 0.19/1500 SQ FT 250 100 RUBBER TIRES TO 5'-0"; ON GRADE, ON TREAD AND ON SIDE; NFPA 13:TABLE 18.4(a) OR ENTIRE AREA GARDEN CENTER CANOPY (EXTRA HAZARD GROUP 1) 0.30/7 SPRINKLERS 500 100 CLASS I -IV ON SHELF TO 12'-0"; NFPA 13:TABLE 13.2.1; 16.2.1.2 AND 11.2.3.4.2 OPERATING RC = RETAIL CEILING/RNC = RETAIL NO CEILING SRR = SINGLE ROW RACK SL = STORAGE LOW/SH = STORAGE HIGH DRR = DOUBLE ROW RACK REFERENCE SPRINKLER PLANS AND SPRINKLER SYMBOL LEGEND FOR SPRINKLERS NECESSARY TO MEET THE DESIGN REQUIREMENTS MRR = MULTIPLE ROW RACK * = EXISTING DESIGN CRITERIA TO REMAIN OWNER FURNISHED SPRINKLERS AND SPRINKLER SYMBOL LEGEND ACCESSORIES SYMBOL SIZE K-FACTOR FINISH MFR MAKE S.I.N. TEMP STYLE QTY SPARE ESCH ESCH ESCH SYMBOL SIZE MFR MAKE S.I.N. FINISH STYLE TEMP K-FACTOR QTY STYLE FINISH QTY SYMBOL LEGEND 3/4" 16.8 BRASS TYCO K17-231 TY7158 155 UPRIGHT 222 6 --- --- --- �!, VARIES VARIES VARIES VARIES VARIES EXISTING PENDENT VARIES VARIES O * 3/4" 16.8 BRASS TYCO K17-231 TY7158 200 UPRIGHT 6 6 --- --- --- , 1' DEMO DEMO DEMO DEMO DEMO DEMO DEMO DEMO SYMBOL DESCRIPTION PENDENT O 3/4" 11.2 BRASS TYCO ELO-231 TY5131 155 UPRIGHT 1246 24 --- - __ - -- • MATCH MATCH MATCH MATCH MATCH NEW MATCH MATCH XX HYDRAULIC REFERENCE NODE EXISTING EXISTING EXISTING EXISTING EXISTING PENDENT EXISTING EXISTING 0 * 3/4" 11.2 BRASS TYCO ELO-231 TY5131 200 UPRIGHT 47 6 --- --- --- ; ` ` VARIES VARIES VARIES VARIES BRASS UPRIGHT STING VARIES VARIES C- CAP � DEMO DEMO DEMO DEMO DEMO DEMO UPRIGHT DEMO DEMO p RISER NIPPLE/DROP NIPPLE 3/4" 8.0 BRASS TYCO TY-B TY4151 286 UPRIGHT 5 2 --- --- --- MATCH MATCH MATCH MATCH MATCH NEW MATCH MATCH ® SPRINKLER RISER EXISTING EXISTING EXISTING EXISTING EXISTING UPRIGHT EXISTING EXISTING WHERE SPRINKLERS ARE CALLED OUT TO "MATCH EXISTING," THE CONTRACTOR 5-ram---F INSPECTOR'S TEST/AUXILIARY DRAIN SHALL PROVIDE SPRINKLERS MANUFACTURED BY TYCO, WHICH ARE EQUIVALENT TO SUBSTITUTIONS WILL NOT BE PERMITTED. REFERENCE SPECIFICATIONS APPENDIX B FOR ADDITIONAL THE EXISTING TO REMAIN SPRINKLERS. SUBSTITUTIONS WILL NOT BE PERMITTED. FIRE DEPARTMENT CONNECTION INFORMATION. WHERE SPRINKLERS ARE INSTALLED BELOW OBSTRUCTIONS (REFRIGERATION PIPING, RTUs, CABLE \ HANGER TRAYS, ETC.) THESE SPRINKLERS SHALL BE REPLACED WITH SPRINKLERS MATCHING THE NEW SPRINKLERS BEING INSTALLED AT THE ROOF DECK LEVEL. TRAPEZE HANGER * INTERMEDIATE TEMPERATURE SPRINKLERS TO BE FURNISHED BY OWNER FOR INSTALLATION BELOW ® NEW CONNECTION SKYLIGHTS AND ON AIR FLOW SIDE (INTERMEDIATE-TEMERATURE ZONE) OF UNIT HEATERS PER NFPA 13. NEW SPRINKLER PIPE **HIGH TEMPERATURE SPRINKLERS TO BE FURNISHED BY OWNER FOR INSTALLATION AROUND UNIT HEATERS. - - - - EXISTING SPRINKLER PIPE THE OWNER WILL FURNISH ONE (1 QTY) SPRINKLER WRENCH (TYPE 38) FOR INSTALLATION PURPOSES FOR THE TY7258 WHEN INSTALLING WITH STYLE 30 ESCUTCHEONS. THE CONTRACTOR IS REQUIRED TO X X-X- DEMOLISHED SPRINKLER PIPE LEAVE THE OWNER FURNISHED SPRINKLER WRENCH INSIDE THE SPARE HEAD CABINET AFTER INSTALLATION HAS BEEN COMPLETED. PROVIDE ADDITIONAL SPRINKLERS AS REQUIRED PER NFPA 13 IN EXISTING SPRINKLER CABINET THE OWNER WILL FURNISH ONE (1 QTY) SPRINKLER WRENCH (TYPE 8) FOR INSTALLATION PURPOSES FOR ANY NEW SPRINKLERS INSTALLED. FOR THE TY7258 WHEN INSTALLING WITH STYLE 65/401 ESCUTCHEONS. THE CONTRACTOR IS REQUIRED TO LEAVE THE OWNER FURNISHED SPRINKLER WRENCH INSIDE THE SPARE HEAD CABINET AFTER INSTALLATION HAS BEEN COMPLETED. THE CONTRACTOR WILL BE RESPONSIBLE FOR ANY DAMAGE TO OWNER FURNISHED SPRINKLERS DURING INSTALLATION. TO REPLACE DAMAGED SPRINKLERS CONTACT HAINES, JONES, CADBURY 1-800-459-7099. THE OWNER WILL FURNISH ADDITIONAL SPRINKLERS FOR THE SPARES CABINET. INSTALL SPARE SPRINKLER QUANTITY INDICATED ON CONTRACT DOCUMENTS PRIOR TO FIRE PROTECTION CONSULTANT SITE OBSERVATION. f- 2 w � N o W ' N O O N N O N h OVERALL FIRE SPRINKLER PLAN 1" = 40'-0" UNDERGROUND PIPING SHOWN FOR HYDRAULIC CALCULATION PURPOSES ONLY. SYSTEM IMPAIRMENT SCOPE OF WORK GENERAL NOTES GENERAL NOTES CONT. REQUIREMENTS 1. THE CONTRACTOR IS RESPONSIBLE FOR THE 1. CONTRACTOR TO FIELD VERIFY EXTENT OF WORK, COORDINATION, VERIFICATION AND PROVISION OF A 2. UPGRADE THE EXISTING FIRE SPRINKLER SYSTEM IN 1. THE DESIGN SHOWN ON THESE CONTRACT 7. THE FIRE PROTECTION ENGINEER OF RECORD FIRE WATCH SUBJECT TO THE REQUIREMENTS OF THE GROCERY STOCKROOM, GENERAL DOCUMENTS IS TO PROVIDE GUIDANCE FOR SHALL NOT BE RESPONSIBLE FOR THE THE LOCAL JURISDICTION. ALL FIRE WATCH COSTS MERCHANDISING STOCKROOM, SALES FLOOR, BIDDING. SUBMIT COMPLETE FIRE SPRINKLER SHOP CONTRACTOR'S FAILURE TO CARRY OUT THE INCURRED AS A RESULT OF THIS PROJECT SHALL BE SEASONAL SHOP, BREAK ROOM AND VISION DRAWINGS AS REQUIRED BY CONTRACT CONSTRUCTION WORK IN ACCORDANCE WITH THE INCLUDED IN THE PROJECT BID AS A SEPARATE LINE CENTER. TO MEET THE DISCHARGE PRESSURE, DOCUMENTS TO THE OWNERS DESIGNATED CONTRACT DOCUMENTS, NOR SHALL THEY BE ITEM. COORDINATION AND VERIFICATION AS TO HOSE ALLOWANCE AND MAXIMUM SPRINKLER REVIEWERS. BASE SPRINKLER DESIGN UPON REQUIRED TO SUPERVISE THE CONDUCT OF THE WHEN A FIRE WATCH MAY BE NEEDED SHALL BE THE SPACING AS REFERENCED IN THE PROTECTION THESE DRAWINGS AND AS REQUIRED BY THE WORK, THE CONSTRUCTION PROCEDURES RESPONSIBILITY OF THE GENERAL CONTRACTOR. CRITERIA LEGEND. SPECIFICATIONS. SHOP DRAWINGS MUST INCLUDE FOLLOWED BY THE CONTRACTOR, 2. THE GENERAL CONTRACTOR SHALL REQUEST THE 3. INSTALL ONE PRV ON EACH SYSTEM RISER AND ELEVATIONS, HANGER LOCATIONS, PIPE LENGTHS, SUBCONTRACTORS, THEIR RESPECTIVE STORE MANAGER TO NOTIFY ALARM CENTRAL OF INSTALL AIR RELEASE VALVE ON EACH SYSTEM IN DIMENSIONS, FABRICATIONS METHODS, MATERIAL EMPLOYEES OR ANY OTHER PERSON AT THE JOB THE SYSTEMS) BEING SHUT OFF FOR WORK AND ACCORDANCE WITH THESE DRAWINGS.SITE DATA ANDADDITIONAL INFORMATION NECESSARY OTHER THAN THAT OF THE ENGINEERING THE DURATION OF THE SHUT OFF. 4. THE EXISTING FIRE SPRINKLER SYSTEMS WILL BE TO CLARIFY THE INTENT OF INSTALLATION. FIRM'S EMPLOYEES. 3. THE GENERAL CONTRACTOR SHALL CALL DIRECT TO MODIFIED AS INDICATED ON THE PROJECT CONTRACTOR SHALL PROVIDE PIPE SIZE, 8. CONTRACTOR MUST REVIEW ALL CONSTRUCTION THE FIRE DEPARTMENT AND ADVISE THAT THE FIRE CONTRACT DOCUMENTS. THE SCOPE OF WORK SPRINKLER SPACING, AND SYSTEM CONFIGURATION DOCUMENTS PRIOR TO BID. SHOULD ALARM SYSTEM IS IN TEST. MAY INCLUDE THE MODIFICATION OF EXISTING AS SHOWN. ALTERNATE MATERIALS MUST BE SENT MODIFICATIONS TO THESE PLANS BECOME 4. AT THE END OF EACH NIGHTS WORK, THE GENERAL BRANCHLINES, INSTALLATION OF NEW TO THE FIRE PROTECTION ENGINEER OF RECORD NECESSARY TO PROPERLY COORDINATE THE CONTRACTOR SHALL CALL DIRECT TO THE FIRE BRANCHLINES, MODIFICATION OF EXISTING RISER(S), OR VIA THE RFI PROCESS AND MUST BE APPROVED SYSTEM WITH ALL OTHER TRADES, IT WILL BE THE DEPARTMENT AND ALARM CENTRAL TO ADVISE THE REMOVAL AND INSTALLATION OF NEW IN RECORD DOCUMENTS PRIOR TO BID. CONTRACTOR'S RESPONSIBILITY TO OBTAIN WORK IS COMPLETE. SPRINKLERS, MODIFICATION OF EXISTING MAINS, 2. COORDINATE LOCATIONS OF FIRE PROTECTION APPROVAL OF THE CHANGES FROM BOTH THE 5. (FIRST FIRE WATCH OPTION) A FIRE WATCH SHALL BE INSTALLATION OF NEW MAINS, REPLACEMENT OF COMPONENTS, INCLUDING PIPING, ALARMS, DRAINS, AUTHORITY HAVING JURISDICTION AND THE REQUIRED WHEN ANY FIRE PROTECTION SYSTEM IS THE EXISTING BACKFLOW PREVENTOR. TEST POINTS, ETC. WITH ARCHITECTURAL, OWNER'S DESIGNATED REVIEW CONSULTANT IN IMPAIRED OR OTHERWISE DOWN FOR ALTERATION. 5. ALL NEW PIPING SHALL HAVE HANGERS INSTALLED STRUCTURAL, MECHANICAL, AND ELECTRICAL ADDITION TO OBTAINING THE NECESSARY THE APPROVED FIRE WATCH SHALL BE CONDUCTED IN ACCORDANCE TO THE DETAILS LOCATED ON THE COMPONENTS. OBSTRUCTION TO SPRINKLER APPROVALS, THE CONTRACTOR MUST MAKE NOTE BY A DEDICATED, TRAINED WALMART EMPLOYEE FIRE PROTECTION DETAILS SHEET. DISCHARGE MUST BE CONSIDERED DURING SHOP OF ANY FIELD OR COORDINATION CHANGES ON THE WHOSE SOLE RESPONSIBILITY WILL BE TO PERFORM 6. ALL 1-INCH ARMOVERS (IF APPLICABLE) SHALL HAVE DRAWING PRODUCTION AND INSTALLATION; INSTALLATION DRAWINGS, AND THEN MUST HOURLY PATROLS OF THE PREMISES AND KEEP A HANGER SECURED TO THE STRUCTURAL STEEL ADDITIONAL SPRINKLERS MAY BE REQUIRED AT NO PROVIDE A SET OF AS -BUILT DRAWINGS ONCE WATCH FOR FIRES AND WILL NEED TO DOCUMENT ONLY, NOT TO THE DECK WHEN THE LENGTH ADDITIONAL COST TO OWNER. REFER TO COMPLETE. THEIR WALK AND REPORT BACK TO THE GENERAL EXCEEDS 2 -0" WHERE STATIC PRESSURES ARE UP SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. RE 9. CONTRACTOR MUST VERIFY ALL DROP DOWN CONTRACTOR AND WALMART MANAGEMENT. THIS TO 100 PSI AND 1'-0" WHERE STATIC PRESSURES 3. CONTRACTOR MUST VISIT THE BUILDING SITE TO LOCATIONS AT EXTERIOR WALLS WITH THE PERSON SHALL BE PROVIDED WITH AT LEAST ONE EXCEEDS 100 PSI. DETERMINE THE FULL EXTENT OF THE EXISTING PROJECT MANAGER PRIOR TO INSTALLATION. APPROVED MEANS FOR NOTIFICATION TO THE FIRE 7, CEILING GRID SHALL BE PERMITTED TO BE REMOVED FIRE PROTECTION WORK AND EXISTING 10, ALL PIPING MUST BE COORDINATED AROUND DEPARTMENT. IN AREAS WHERE REQUIRED IN ORDER TO CONDITIONS, BECOME TOTALLY FAMILIAR WITH THE FRAMING MEMBERS AND PROPERLY INSTALLED 6. (SECOND FIRE WATCH OPTION) A FIRE WATCH SHALL COMPLETE THE WORK NEEDED SUCH AS DEMO AND DISCONNECTIONS, REMOVALS, RELOCATIONS INSIDE THE BAR JOIST. BE REQUIRED WHEN ANY FIRE PROTECTION SYSTEM INSTALLATION OF NEW MAINS OR LONG DROPS. IN AND/OR RECONNECTIONS OF EXISTING FIRE 11. CONTRACTOR SHALL ROUTE PIPING AROUND ALL IS IMPAIRED OR OTHERWISE DOWN FOR THIS CASE THE CONTRACTOR SHALL BE PROTECTION EQUIPMENT REQUIRED, AND OBSTRUCTIONS AND PROVIDE SPRINKLER ALTERATION. THE FIRE SPRINKLER CONTRACTOR RESPONSIBLE FOR REPLACING DAMAGED CEILING CONDITIONS IN THE PROPOSAL FOR THIS PROJECT. PROTECTION UNDER OBSTRUCTIONS, AS DETAILED SHALL HIRE AN APPROVED OFF -DUTY FIRE FIGHTER TILE OR GRID DURING THE INSTALLATION. ALL NO EXTRA COMPENSATION WILL BE PAID FOR LACK IN NFPA 13 STANDARDS AS PART OF THE FIELD TO PERFORM THE REQUIRED FIRE WATCH. FIRE REMOVED CEILING TILES MUST BE REPLACED AT OF SUCH DETERMINATION, FAMILIARIZATION, COORDINATION AT NO ADDITIONAL COST TO WATCH PERSONNEL SHALL BE PROVIDED WITH AT THE END OF BUSINESS DAY. AREAS LEFT EXPOSED AND/OR ALLOWANCE. OWNER. LEAST ON APPROVED MEANS FOR NOTIFICATION OF SUCH AS BUT NOT LIMITED TO REMOVED CEILING 4. SUBMIT A REQUEST FOR INFORMATION FOR 12. ALL SPRINKLER DEFLECTOR DISTANCE THE FIRE DEPARTMENT AND THEIR SOLE DUTY SHALL GRID AND CEILING TILES SHALL NOT BE PERMITTED. QUESTIONS REGARDING THE FIRE PROTECTION REQUIREMENTS SHALL BE IN ACCORDANCE TO THE BE TO PERFORM CONSTANT PATROLS AND WATCH 8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DOCUMENTS PER RFI PROCESS LOCATED IN THE STANDARDS OUTLINED IN NFPA 13. FOR THE OCCURRENCE OF FIRE. FOR HOT WORK PURCHASING AND INSTALLING MATCHING CEILING FIRE PROTECTION SPECIFICATIONS. 13. ALL PIPING PASSING THROUGH CMU WALLS SHALL OPERATIONS, A FIRE WATCH SHALL BE POSTED FOR TILES TO REPLACE ANY CEILING TILES THAT HAVE 5. NEUTRALIZATION WALLS, IF PROVIDED, ARE SHOWN BE INSTALLED WITH ONE INCH CLEARANCE ON ALL THE DURATION OF THE WORK AND 30 MINUTES EMPTY HOLES DUE TO SPRINKLER REPLACEMENT. ON THE ARCHITECTURAL DRAWINGS. REFER TO SIDES. (CORE DIAMETER EQUAL TO PIPE +2"). ALL THEREAFTER. 9. USE EACH EXISTING OUTLETS FOR ONE NEW ARM MECHANICAL DRAWINGS FOR NEUTRALIZATION CORES SHALL BE COORDINATED WITH STRUCTURAL 7. ONLY (1) ONE SYSTEM IS PERMITTED TO BE SHUT OVER TO NEW SPRINKLER LOCATION UNLESS WALL PENETRATION DETAIL. REINFORCING. CONTRACTOR IS RESPONSIBLE FOR DOWN AT ONE TIME. HYDRAULICALLY CALCULATED. CONTRACTOR SHALL 6. PENETRATIONS OF "RATED ASSEMBLIES" SHALL BE PROVIDING ALL CORING WITH PROPER CLEARANCE 8. ANY FIRE DEPARTMENT FEES FOR FAILURE TO INSTALL 1" INCH MECHANICAL TEES IF ADDITIONAL FIRE STOPPED WITH AN APPROVED MATERIAL PER AT ALL CMU WALLS. GENERAL CONTRACTOR SHALL FOLLOW PROCEDURES WILL BE AT THE GENERAL OUTLETS ARE REQUIRED. AFTER THE DEMOLITION IS METHODS REQUIRED BY PROJECT SPECIFICATIONS BE RESPONSIBLE FOR PROVIDING A TWO INCH CONTRACTORS EXPENSE. COMPLETE, THE NEW SPRINKLER SYSTEM SHALL AND THE AUTHORITY HAVING JURISDICTION. CLEARANCE AROUND ALL PIPING PASSING 9. REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED MEET ALL REQUIREMENTS OF NFPA 13. THROUGH CONCRETE SLABS. THE SPRINKLER AT ALL TIMES DURING CONSTRUCTION, DEMOLITION, 10. CONTRACTOR SHALL PROVIDE NEW SPRINKLERS AS CONTRACTOR SHALL FILL ALL CLEARANCES WITH REMODELING ALTERATIONS AND ADDITIONS DUE TO PAINT, ETC.. APPROVED MASTIC. THE WALMART.. ALL EXITS SHALL NOT BE BLOCKED, CONTRACTOR SHALL COORDINATE.NECESSARY FIRE SPRINKLER PIPING AND 14. ON THE SALES FLOOR AND SEASONAL SHOP, PRIME REDUCED OR OTHERWISE MADE INOPERABLE WHICH 11. THE CONTRACTOR IS RESPONSIBLE FOR AL I PANT AND ND PAINTAL L NEWLY INSTALLED PIPE, PIPE ALSO INCLUDES THE EXIT ACCESS, THE EXIT AND MAINTAINING THE FIRE LANES DURING THE DEMOLITION NOTES FSUPPORTS TO MATCH EXISTING EXIT DISCHARGE TO THE PUBLIC WAY. TEMPORARY SPRINKLER SYSTEM UPGRADE PROCESS. THE CEILING. MEANS OF EGRESS ARE ALLOWED. CONTRACTOR SHALL COORDINATE WITH THE STORE 15. PROVIDE FLUSHING CONNECTIONS IN ACCORDANCE 10. ALL SYSTEMS TO BE LEFT IN SERVICE PRIOR TO THE MANAGER A STAGING AREA FOR MATERIALS AND 1. CONTRACTOR MUST VISIT THE BUILDING SITE TO WITH THE STANDARDS OUTLINED IN NFPA 13. END OF EACH WORKDAY. TOOLS TO BE USED FOR PROJECT PRIOR TO START DETERMINE THE FULL EXTENT OF THE EXISTING FIRE 16. PROVIDE ALL NECESSARY OFFSETS, RISES OR OF WORK. PROTECTION WORK AND EXISTING CONDITIONS, DROPS IN PIPING AND AUXILIARY DRAINS REQUIRED 12. THE SPRINKLER CONTRACTOR SHALL BE BECOME TOTALLY FAMILIAR WITH THE BY BUILDING CONDITIONS. HYDROSTATIC TEST RESPONSIBLE FOR PREPARING THE SHOP DISCONNECTIONS, REMOVALS, RELOCATIONS AND/OR RECONNECTIONS OF EXISTING FIRE 17. EXAMINE THE JOB CONDITIONS AND VERIFY ALL MEASUREMENTS, DISTANCES, ELEVATIONS, DRAWINGS, HYDRAULIC CALCULATIONS AND APPROVAL (BY THE ENGINEER OF RECORD AND AHJ) PROTECTION EQUIPMENT REQUIRED, AND CLEARANCES, ETC. AS WELL AS INSTALLATION. CONDITIONS IN THE PROPOSAL FOR THIS PROJECT. 18. ARCHITECTURAL AND ELECTRICAL BACKGROUND 13. THE SPRINKLER CONTRACTOR MUST FIRST SUBMIT NO EXTRA COMPENSATION WILL BE PAID FOR LACK INFORMATION IS SHOWN FOR COORDINATION BUILDING SPRINKLER SYSTEM(S) INVOLVED IN THIS DOCUMENTS, AS OUTLINED IN THE PROJECT OF SUCH DETERMINATION, FAMILIARIZATION, AND/OR PURPOSES ONLY. REFER TO THE CONTRACT SCOPE OF WORK SHALL BE HYDROSTATICALLY TESTED SPECIFICATIONS, TO THE FIRE PROTECTION ALLOWANCE. DOCUMENTS FOR LOCATIONS, SIZES AND IN ACCORDANCE WITH NFPA 13. MOREOVER, THE ENGINEER OF RECORD FOR APPROVAL. AFTER THE 2. UNLESS INDICATED OTHERWISE, DISCONNECT AND QUANTITIES OF OTHER TRADE WORK. FOLLOWING TWO (2) HYDROSTATIC TESTS SHALL BE APPROVAL IS GIVEN, THE CONTRACTOR MUST REMOVE ALL EXISTING FIRE PROTECTION 19. SPRINKLER SPACING SHALL BE PER NFPA 13 PERFORMED BY THE CONTRACTOR: SUBMIT TO THE AUTHORITY HAVING JURISDICTION COMPONENTS NOT INTENDED TO BE REUSED. UNLESS OTHERWISE NOTED ON PLANS AND/ OR 1. THE FIRST HYDROSTATIC TEST SHALL BE FOR INSTALLATION PERMIT. 3. DISCONNECT, RELOCATE, AND RECONNECT PROTECTION CRITERIA LEGEND. PRIOR PERFORMED BY THE CONTRACTOR PRIOR TO 14. THE CONTRACTOR SHALL COORDINATE WITH THE EXISTING FIRE PROTECTION SYSTEMS AND 20. INTERFACE SPRINKLER SYSTEM WITH FIRE START OF SPRINKLER SYSTEM SCOPE STORE MANAGER ON THE AREA TO BE WORKED ON EQUIPMENT WHERE REQUIRED. PROTECTION SUPERVISORY SYSTEM. WORK "PRE -SCOPE HYDRO TEST"); ( ) AT LEAST 24 HOURS IN ADVANCE. 4. NOTE CAREFULLY THAT THE FIRE PROTECTION 21. ALL MATERIALS SHALL BE UL LISTED OR FM 2. THE SECOND HYDROSTATIC TEST SHALL BE 15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DRAWINGS ARE INTENDED TO INDICATE, ONLY APPROVED. SPRINKLER PIPE SHALL BE PERFORMED BY THE CONTRACTOR AFTER DAMAGE TO ANY OF THE STORES CONTENTS DIAGRAMMATICALLY, THE EXTENT AND THE GENERAL MANUFACTURED TO STANDARDS RECOGNIZED BY COMPLETION OF CONTRACT SCOPE WORK (MERCHANDISE), OR THE BUILDING COMPONENTS AS CHARACTER AND LOCATIONS OF THE WORK NFPA 13., THREADED PIPE SHALL HAVE A ("POST -SCOPE HYDRO TEST"). A RESULT OF THE WORK SHOWN ON THE CONTRACT INCLUDED. PROVIDE ALL WORK OBVIOUSLY CORROSION RESISTANCE RATING OF 1.0 OR DOCUMENTS. INTENDED, BUT HAVING MINOR DETAILS OMITTED OR GREATER. CRIMP -TYPE COUPLINGS SHALL NOT BE THE HYDROSTATIC TESTS ON EXISTING SPRINKLER 16. THE CONTRACTOR SHALL REPAIR ANY LEAKS OR NOT SHOWN. COMPLETE AS REQUIRED TO USED. THREADABLE THINWALL PIPE WITH SYSTEM SHALL BE CONDUCTED AT A PRESSURE OF REPLACE ANY LEAKING COMPONENTS AFFECTED BY PERFORM THE FUNCTIONS INTENDED. FOLLOW THE CORROSION RESISTANCE RATING OF LESS THAN 1.0 200 PSI FOR 2 HOURS. NEW SYSTEMS SHALL THIS SCOPE OF WORK AT NO ADDITIONAL COST TO CONTRACT DOCUMENTS FOR BUILDING DETAILS SHALL BE USED ONLY WITH ROLL GROOVE FITTINGS. TESTED PER PRESSURE REQUIREMENTS OF NFPA 13. THE OWNER. AND FIT THE WORK OF THE FIRE PROTECTION 22, IF REQUIRED, PROVIDE 24 VOLT AC, ELECTRIC BELL, DRAWINGS AND SPECIFICATIONS THERETO. MODEL NO. PBA248, ELECTRIC BELL BY POTTER THE CONTRACTOR SHALL NOT BE RESPONSIBLE FOR 5. REMOVE ALL DEMOLITION MATERIALS AND DEBRIS ELECTRIC SIGNAL OF ST. LOUIS, MISSOURI, LOCATE DAMAGE TO CONTENTS OR BUILDING OCCURRING DURING THE "PRE-SCOPEHYDRO TEST" PROVIDED ALLJURISDICTION. WATER SUPPLY TO AN APPROVED DUMPING SITE AND CLEAN FIRE PROTECTION ij ORK PRIOR HE PROJECT AS REQUIRED BHAVINGY AUTHORITIES PROVIDE DEE NEW DOUBLE POLE VANE COMMERCIALLY REASONABLE MEASURES NECESSARY COMPLETION. TYPE FLOW DETECTOR, MODEL NO. VSR-F, BY OR PRUDENT TO PROTECT CONTENTS OR BUILDING INFORMATION 6. PERFORM ALL WORK ACCORDING TO THE PROJECT POTTER ELECTRIC SIGNAL OF ST. LOUIS, MISSOURI. COMPONENTS WERE FOLLOWED FOR APPROPRIATE PHASING SCHEDULE INFORMATION FOR THIS SET ADJUSTABLE DELAYED SIGNAL AT 30 SECONDS. TEST PROCESS. CONTRACTOR SHALL COMPLETE TEST STATIC AT SRC: 55 PSI PROJECT. PROVIDE ALL NECESSARY FIRE MOUNT WATER FLOW INDICATORS NO HIGHER THAN REPAIRS AND / OR REMEDIATION TO EXISTING TEST RESIDUAL AT SRC: 50 PSI AT 1030 GPM PROTECTION WORK, TEMPORARY AND/OR 6 FEET ABOVE FINISH FLOOR. SYSTEMS REQUIRED AS A RESULT OF DEFICIENCIES OTHERWISE, AND USE WHATEVER MEANS 23. ALL SPRINKLER SYSTEMS THAT ARE TO BE IDENTIFIED DURING PRE -SCOPE TESTING AS AN INFORMATION DERIVED FROM A WATER REPORT BY NECESSARY, TO CONFORM TO THE REQUIRED MODIFIED SHALL BE HYDROSTATICALLY TESTED PER ADDITIONAL SERVICE. CI & FROM A FLOW TEST CONSTRUCTION PHASING OF THE PROJECT. NFPA 13 PRIOR TO SPRINKLER SYSTEM THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE CONDUCTED ON 11/05/20. THE TEST WAS CONDUCTED DON 1 /05 CONDUCTED 7• CONTRACTOR IS RESPONSIBLE FOR REPAIRING OR MODIFICATION AND SHALL BE RE -HYDROSTATICALLY FOR DAMAGE TO CONTENTS OR BUILDING OCCURRING AT 10:00 AM EST. REPLACING ITEMS DAMAGED DURING DEMOLITION TESTED AFTER COMPLETION OF WORK. DURING THE "POST -SCOPE HYDRO TEST" PROCEDURE AND CONSTRUCTION. 24. DO NOT HANG OR SUPPORT ANY LOADS OR MAKE ORIGINATING IN EXISTING OR NEW SYSTEM FLOW TEST ELEVATION: 100.0 FT AMSL 8. CONTRACTOR SHALL PATCH ALL HOLES TO MATCH ANY ATTACHMENTS TO THE METAL ROOF DECK OR COMPONENTS. CONTRACTOR SHALL COMPLETE BUILDING PAD ELEVATION: 100.0 FT AMSL ADJACENT SURFACES LEFT UNUSED AFTER EXISTING JOIST BRIDGING. REPAIRS AND / OR REMEDIATION TO EXISTING SPRINKLER PIPING OR EQUIPMENT IS REMOVED AND 25. SAMMY SCREWS ARE NOT PERMITTED. SYSTEMS REQUIRED AS A RESULT OF DEFICIENCIES THE WATER SUPPLY IS MODIFIED BY THE FOLLOWING: VACATED FROM THESE HOLES. 26. CEILING FLANGES ARE NOT PERMITTED. IDENTIFIED DURING POST -SCOPE TESTING AT NO 9. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND 27. PROVIDE RETAINING STRAPS ON HANGERS WHERE ADDITIONAL COST TO WALMART. + 0.0 PSI DUE TO ELEVATION DIFFERENCE MAINTAINING FIRE DEPARTMENT ACCESS ROADS REQUIRED. WHEN CONDUCTING HYDROSTATIC TESTING ON BETWEEN TEST AND BUILDING THROUGHOUT THE PROJECT. 28. CONTRACTOR IS TO COORDINATE FINAL SPRINKLER EXISTING SYSTEMS AS REQUIRED BY NFPA 13, 5.0 PSI WALMART SAFETY FACTOR 10. SPRINKLER SYSTEMS NOT ASSOCIATED WITH THE HEAD LOCATIONS AND PIPE ROUTING SUCH THAT CONTRACTOR SHALL TAKE SUCH ACTIONS AS MAY BE DEMOLITION SHALL BE LEFT IN SERVICE. THEY DO NOT INTERFERE WITH NOR RECEIVE NECESSARY TO REDUCE POTENTIAL DAMAGE TO DESIGN STATIC AT SRC: 50 PSI 11. THE CONTRACTOR SHALL PROPERLY NOTIFY THE DAMAGE FROM THE NORMAL OPERATIONS OF THE CONTENTS AND BUILDING DURING EXECUTION OF DESIGN RESIDUAL AT SRC: 45 PSI AT 1030 GPM LANDLORD. THE LESSOR AND THE ADJACENT AREA. SCOPE OF WORK, INCLUDING BUT NOT LIMITED TO THE TENANTS A MINIMUM OF 48 HOURS IN ADVANCE FOLLOWING: BEFORE PROCEEDING WITH THIS WORK. ALL WORK 1. USE OF LOW CAPACITY PRESSURE PUMP TO SHALL BE SCHEDULED IN ADVANCE. INCREASE PRESSURE IN SYSTEM AT INCREMENTAL RATE TO LIMIT SURGES IN APPLICABLE CODES SYSTEM; AND AIR RELEASE VENT GENERAL UNDERGROUND 2. PROVISION OF WORK STAFF DEDICATED TO MONITORING THE IMPACTED SYSTEM AREA NOTES DURING PRESSURE APPLICATION AND DURING CODE STANDARD EDITION HYDROSTATIC TEST FOR SIGNS OF SYSTEM ONE AIR VENT MUST BE INSTALLED ON ALL WET TYPE NFPA 13 2013 COMPROMISE (MINIMUM 1 PERSON / 20,000 SQ. FIRE PROTECTION SYSTEMS INCLUDING SYSTEMS NOT 1. ALL UNDERGROUND IS SHOWN FOR HYDRAULIC 2014 FT. AREA) ; AND AFFECTED BY THE REMODEL SCOPE OF WORK. EACH REFERENCE ONLY. NFPA 25 FFPC 6TH 3. MAINTAINING DEDICATED PERSON AT SYSTEM AIR VENT IS TO BE INSTALLED AT THE HIGHEST POINT 2. SEE CIVIL DRAWINGS FOR EXACT LOCATIONS IF CONTROL VALVE IN CONSTANT OF THE SYSTEM AND PREFERABLY ON THE MAINS. THE AVAILABLE. COMMUNICATION WITH SYSTEM MONITORS TO CONTRACTOR IS RESPONSIBLE FOR LOCATING THE 3, NO NEW WORK UNLESS OTHERWISE NOTED. SHUT OFF TEST PUMP AND DRAIN SYSTEM IN HIGHEST POINT OF EACH SYSTEM AND INSTALLING THE EVENT OF SYSTEM ORIF NO AIR VENT INNINSTALLEID BLE THE AIR CONTACT INFORMATION 4. PROVISO OF REA YILURE SUPPLI SLPRIOR VT IS TO EAD ABOVEAAN EXISTING CEILING START OF TESTING TO FACILITATE DAMAGE THE CONTRACTOR MUST PROVIDE SIGNAGE PER NFPA PLACARD INFORMATION MINIMIZATION 1N EVENT OF SYSTEM FAILURE 13. REF 3-FP3. (TARPS / PLASTIC SHEETING, WET / DRY DOCUMENTS INCLUDE JURISDICTIONAL REQUIREMENTS VACUUM ETC.); AND PROVIDED BY THE FOLLOWING CONTACTS: 5. COVERING HIGH VALUE EQUIPMENT PRIOR TO THE FOLLOWING INFORMATION MUST BE SHOWN ON TESTING; AND THE PLACARDS FOR EACH UL PERFORMANCE BASE CIT OF ZEPHYRHILLS FIRE DEPARTMENT: 6. LIMITATION OF TESTING TO ONE SYSTEM AT A DESIGNS. USE A PLACARD FOR EACH CALCULATED BRIAN SWARTOUT, FIRE CHIEF TIME- AND DESIGN. PLACARDS SHALL BE ENGRAVED METAL (813) 780-0020 7. TESTING OF SYSTEMS DURING OFF HOURS / SIGNS. REFERENCE SPECIFICATIONS FOR ADDITIONAL OVERNIGHT. INFORMATION. PLACARDS THAT ARE INSTALLED WITH THERE IS NO INDICATION OF MIC (MICROBIOLOGICALLY INFLUENCED CORROSION) IN THE EXISTING BUILDING. OLISH EXISTING PIPING AND NKLER IN THIS AREA. CUT AND CAP TING PIPING. RELOCATE AND VIDE NEW SPRINKLER COVERAGE AS UIRED IN NEW BUILDING LAYOUT INFORMATION WRITTEN PERMANENT MARKER WILL NOT BE ACCEPTED. SYSTEM #: X AREA: X SPRINKLERS CALCULATED: X SPRK END HEAD PRESSURE: X HOSE DEMAND: X SYSTEM FLOW DEMAND: X SYSTEM PRESSURE DEMAND: X SYSTEM SAFETY FACTOR: X INSTALLING CONTRACTOR: X UL PERFORMANCE BASE DESIGN PROJECT 4788122552, NC27954 SHEET INDEX FP1 OVERALL FIRE SPRINKLER PLAN FP2 ENLARGED FIRE SPRINKLER PLAN FP2.1 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 1 FP2.2 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 2 FP2.3 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 3 FP2.4 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 4 FP2.5 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 5 FP3 FIRE PROTECTION DETAILS REVI EW DATE S/ �- CITY OF UFE S FIRE AND LIFE SAFETY EXAMINER_, ALL WORK SHALL COMPLY WITH NFFA CODES AND STANDARDS STORE ADDRESS 7631 GALL BLVD ZEPHYRHILLS, FL EXISTING CONDITIONS WERE TAKEN FROM EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING ORIGINAL DRAWINGS AND MAY NOT REFLECT A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND EXACT "AS -BUILT" CONDITIONS. CONTRACTOR SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE x in w a uv��u�lQ Coow a E d Z Z Z 0 W N�OJpOZO W VOZN� ���acnaa=Q�oog O gU- qW?-` O �qwWfO [�?�o �:5wl= TzwrF- 00Z90"MOD Z°j��a50;:,o a� aOholr, Z~Jw�Uw I- z D U) z O U m a N 0 0 CD O J 0 O u- u rn N O O O oa T0 CV M Z O 04 W N O = F- (vn� 1w N w m z m O CHECKED BY: AV DRAWN BY: PO PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 i PAUIL j,%GENSF4 F �i Q No 52186 STATE OF ,• AtORIDP F •• as- 7/20/2021 OVERALL FIRE SPRINKLER PLAN SHALL FIELD VERIFY ALL EXISTING CONDITIONS TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR NOT RELIEVE THE RESPONSIBILITY OF PERFORMING SHALL CAREFULLY COORDINATE NEW WORK AND THE WORK PROPERLY. NO ADDITIONAL SHEET: DEMOLITION WITH ALL OTHER DISCIPLINES AND COMPENSATION SHALL BE ALLOWED BECAUSE OF FP1 EXISTING CONDITIONS. CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. 7 -- MOTHER'S ROOM FIRE PROTECTION CONSTRUCTION PLAN 3/16" = 1'-0" W MOTHER'S ROOM FIRE PROTECTION DEMOLITION PLAN 3/16" = T-0" N u. M M O Oi N O o N N O O ly N n A MONEY CENTER FIRE PROTECION PLAN 3/16" = 1'-0" 1 H BREAKROOM FIRE P 1/8" = T-0" w ra ROTECTION PLAN VISION CENTER FIRE PROTECTION PLAN 118" = 1'-0" its BREAKROOM: RELOCATE EXISTING PENDENT SPRINKLERS AS SHOWN AND TIE INTO THE EXISTING OUTLETS OR NEW MECHANICAL TEE. VISION CENTER: RELOCATE EXISTING PENDENT SPRINKLERS AS SHOWN AND TIE INTO EXISTING OUTLETS OR NEW MECHANICAL TEE. INSTALLATION SHALL COMPLY WITH NFPA 13 AND LOCAL REQUIREMENTS. VERIFY EXISTING FIELD CONDITIONS BEFORE COMMENCING WORK. [ R0 > LL1 D=)0w LLp W-32W5 =OZZh fn w 2 Z W � wY~pQ�Q>wO�Q �=t--LLLL1�C7Z2'~ZZW d W J W Z 0 W W W N � 1_ �� W� U O O g a¢u}Ji'F- Dw LO w mot- ppv� x ¢FO�wuOi Wcwn.0W¢~ Z O �0w N�F��W Ww O if ~ OU m� CD, ow } z�_gQa. -Ww� OZw 1U0;:-o1U���LL�< 7. +�I V) C5 F" F- °- �� Q�i�a�6�a�0 Cox: m a U) 0 0 co co J 0 0 u- N O J cb o Ix 0 r` °- v �J — o o N M LO N O o Z N MM N 0 + O CL N W m Z m O CHECKED BY: AV DRAWN BY: JW PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 VAUIL a A Q No 52186 Q STATE OF !(� �j � •••�LORIO •' � `e 7/20/2021 ENLARGED FIRE SPRINKLER PLAN SHEET: FP2 TY SYSTEM 1 B LLI D:I 0) JI LL1 J IL w NI C. ml m Y V a o J LL J R' a w ' N rn N O O N N_ b W N _o O ' N O N n, � n 13 SALES FLOOR & INTERIOR GARDEN CENTER - (NRC - OPTION 26) 25 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 10 PSI (12 SPRINKLERS - 4 SPRINKLERS / 3 LINES) 250 GPM HOSE 140 SQ FT MAXIMUM SPACING CLASS I -IV ON SHELF TO 12'-0" (26-0" CEILING HEIGHT), 5'-O" AISLES; 1 II 1 1 (` TG(`WK11(`AI DCDOPT DDn =r`T A7Q.Q1'))AR) AIC97QFA _ TARI G 7 Hydraulic Information Remote Area Name System 1 Sales - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 25.00 psi K-Factor 11.2 Total Water Required 362 GPM Total Pressure Required 37.36 psi Base of Riser 362 GPM Base of Riser 37.36 psi Safety Margin +11.92 (24.19%) Hydraulic Information Remote Area Name System 1 Sales - 12s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 10.00 psi K-Factor 11.2 Total Water Required 676 GPM Total Pressure Required 26.78 psi Base of Riser 676 GPM Base of Riser 26.78 psi Safety Margin +20.92 (43.86%) -_ _ __ 1­--------.- STOCKROOM - GM/GR (OPTION 4) 12 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 7 PSI (12 SPRINKLERS - 4 SPRINKLERS / 3 LINES) 250 GPM 100 SQ FT MAXIMUM SPACING CLASS I -IV RACK STORAGE TO 15'-0"/12'-0" (18'-0" CEILING HEIGHT), 4'-0"/0'-6" AISLES; UL LLC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TEST SRR 04191702 / DRR 09191702 & 09261702 / MRR 09211702 Hydraulic Information Remote Area Name System 1 GM Stock - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 12.00 psi K-Factor 16.8 Total Water Required 367 GPM Total Pressure Required 23.70 psi Base of Riser 367 GPM Base of Riser 23.70 psi Safety Margin +25.56 (51.88%) SI (2 SPRINKLERS - 2 SPRINKLERS 11 LINE) SI (9 SPRINKLERS - 4 SPRINKLERS / 2 LINES & 1 SPRINKLER / 3PM HOSE 3Q FT MAXIMUM SPACING 3S I -IV ON SHELF TO 12'-0" (26-0" CEILING HEIGHT), 5'-0" AISLE LC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABI UADv nC TCQTQ TCQTQ (]nA1nn1 A 10M17AI) 2. 10n117n9 / CD[ Hydraulic Information Remote Area Name System 1 Seasonal Shop - 2 Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 30.00 psi K-Factor 11.2 Total Water Required 373 GPM Total Pressure Required 44.05 psi Base of Riser 373 GPM Base of Riser 44.05 psi Safety Margin +5.19 (10.54%) - ,� Hydraulic Information Remote Area Name System 1 Seasonal Shop - 9 Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 9 @ 18.00 psi K-Factor 11.2 Total Water Required 692 GPM Total Pressure Required 38.18 psi Base of Riser 692 GPM Base of Riser 38.18 psi Safety Margin +9.42 (19.79% 10 Hydraulic Information Remote Area Name System 1 GM Stock -12s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 7.00 psi K-Factor 16.8 Total Water Required 804 GPM Total Pressure Required 25.03 psi Base of Riser 804 GPM Base of Riser 25.03 psi Safety Margin +21.81 (46.56%) ♦ 3 10 15' - 0" G F I_ r 1 II ti 1 o , N C) 6 N 6 6 LO n 3'-10 _ _ _ _ - I , 201 12'- 01' - - 202 12'- 0" ty _ 203 � 1 II 1083 38 O 52 11 204 205 208 II b jll N Il 207 208 \ 209 II O ':I I 210 211 I � I 212 II I I co II N m " N00 �r=- II - I II N II 00 � 6 6- -- 6 6 N \ - _ = 3' 11 30' 2' -:6"----11' -`9' = - 11' - 9" r` \ i I - N (0 N �� Ilo r � I �I (0 ; II Z s 3 ♦ 3 ♦ co 3 ♦II 12 1s 0 1. 10' 6" 13'-6" 13'-6" -"11 O II 18 N ♦ ♦ CO ♦ I I 14 II 15 o II N II II j ♦ ♦ ♦ II II N o II ♦ ♦ ♦ II 'I = II 0 N � I I I I! II , N 0 II l N III o I I \\ F N � II � I I II o I I N I ♦ ♦ ♦ II O II II N ♦ ♦ II e II NII ------- II'I ♦ ♦ ♦ II O N PERATIONAL FLEXIBILITY SYSTEM 1A d00 O� U M w _O O F a,A O pp, i ST �a �W -v U V W J Q K M- O I' W LL z Q (n O=ILDSQ 82WWX-wo W w ~pQ-Q>w00a 0 Qat`LOZOW=oauu.�� dW3: WF-�-w.'0 O U_ WN 0ow� [11 -IU0:5 °-¢�F��Foo��= Z i= c<�WM03o8282ZaWQO ~OCSa: 1 3Ug�!zwv�y��1 �Uj �ja gW07'�6o �¢zw"�LL =ZOQu-Wo¢0 WC U) m�W 0000aa Woa U) z J z O U m o_ cn 00 0 0 U- 1­1 I U) � N C� o O Q O N M o w� r o " t N W m Z> D z m O CHECKED BY: AV DRAWN BY: PO PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 I ' pAlit Q No 52186 = ;'o * 4r 0 , STATE OF 7/20/2021 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 1 SHEFFP2.1 SALES FLOOR & INTERIOR GARDEN CENTER - (NRC - OPTION 2B) 25 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 10 PSI (12 SPRINKLERS - 4 SPRINKLERS / 3 LINES) 250 GPM HOSE 140 SQ FT MAXIMUM SPACING CLASS I -IV ON SHELF TO 12'-0" (25'-0" CEILING HEIGHT), 5'-0" AISLES; UL LLC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TESTS GONDOLA 10041702 V N V N N s OPERATIONAL FLEXIBILITY SYSTEM 2B 3/32" = 1'-0" T Hydraulic Information Remote Area Name System 2 Sales - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 25.00 psi K-Factor 11.2 Total Water Required 362 GPM Total Pressure Required 39.78 psi Base of Riser 362 GPM Base of Riser 39.78 psi Safety Margin +9.5 (19.27%) Hydraulic Information Remote Area Name System 2 Sales - 12s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 10.00 psi K-Factor 11.2 Total Water Required 678 GPM Total Pressure Required 39.86 psi Base of Riser 678 GPM Base of Riser 39.86 psi Safety Margin +7.83 (16.42%) 10 1 SEE FP2.3 FOR - !'/1A1T9 A11 I A TIlIAI OPERATIONAL FLEXIBILITY SYSTEM 2A 1 3/32" = 1'-0" o=�=F�°CFZ=Z af=���Oz��zZw Qd-wOzO�=OQN� d w J w- w U H Z 0 � wl� ml-��w�Uoog 6 Z HcnN4wW=�ow O(0W)< �WO W o0z<92SiUw cv=n}w �wZ5�OWO4 aim wU a0wazz U) E�Uj OUcorH JOE0r m' a 00 CO C."::D 00 LL N O O O a r` n- O 7- O N M n% O G {� Z N LU N 0 r O CL N w Z m O 11)1 CHECKED BY: AV DRAWN BY: PO PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 VAUC i &GENgF Q No 52186 = 0 STATE OF f0NAL G 7/20/2021 SHEFFP2.2 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — —1— — — — — — 0 m 111 nl III III III III III III III III III III III III III III III III III Ill III III III III III III --- --- - --- _ III III 70�40 348 1330 90 36 5 7 4 DEMOLISH EXISTING' SPRINKLER HEADS L, AND BRANCH LINE.'. CUT AND CAP AT SPRINKLER MAIN. OPERATIONAL FLEXIBILITY SYSTEM 3 3/32" = 1'-0" N � C� l SEE FP2.4 FOR CONTINUATION —� SEE FP2.1 FOR CONTINUATION UPSIZE EXISTING SYSTEM 2 3" MAIN TO 4" 1 U00 M 0 0 N O O O d •--� 0 Pr LJr i~ N w V¢ 7':0z W W W wCOOWg x0¢L2 oFz0WLLzLL=1w-ow wr~oawa>Op ofxFLLX(!)zWL-ZZW �. a W- J O Z O W U O Z N W N MF--q�jJ W X VOO� cn x z a1W-OOOww Wwww<0 _0 >'OWr,dT =Zuwx�p° 4� ZWQQa-LL J�oz% J V w O W W> 0, xJ2- a. H u) z J U) z 0 U m d %0 �' o C::::)J 0 V- .. U) o N f-- � rr, J_ o a. O N M Z O N w N 0 = O W N re w m D z m 0 ISSUE BLOCK CHECKED BY: AV DRAWN BY: PO PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 t ppuc Vgt���i Q No 52186 i0 STATE OF 7/20/2021 OPERATIONAL FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 3 =HEFFP2.3 Hydraulic Information Remote Area Name System 4 Sales - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 25 GPM Flowing Heads 2 @ 25.00 psi K-Factor 11.2 Total Water Required 137 GPM Total Pressure Required 40.29 psi Base of Riser 137 GPM Base of Riser 40.29 psi Safety Margin +9.59 (19.23%) Hydraulic Information Remote Area Name System 4 Sales - 12s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 10.00 psi K-Factor 11.2 Total Water Required 678 GPM Total Pressure Required 44.75 psi Base of Riser 678 GPM Base of Riser 44.75 psi Safety Margin +2.94 (6.17%) OPERATIONAL FLEXIBILITY SYSTEM 4B 3/32" = V-0" y SALES FLOOR & INTERIOR GARDEN CENTER - (NRC - OPTION 213) 25 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 10 PSI (12 SPRINKLERS - 4 SPRINKLERS / 3 LINES) 250 GPM HOSE 140 SQ FT MAXIMUM SPACING CLASS HV ON SHELF TO 12'-0" (26-0" CEILING HEIGHT), 5'-0" AISLES; UL LLC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TESTS GONDOLA 10041702 OPERATIONAL FLEXIBILITY SYSTEM 4A 3/32" = 1'-0" a ti3u-ZA �cnwg xOZD � OJ�jQ ~Owcai�:1E W wr~pQ�¢>Wo�a QfMMx�OzrrF zOW ¢a—WOZO�xOQNZ wN�nF�2WvO Q105, :,,<Owoh= °otaF Z DQoz�WO° ZcNOHW g 0(g HD W WJ � tnazW�� a =�(3U W m n. %0 N C N O _ o C' r N LO M ry Z O Z N LLI N 0 = F- W N w co O CHECKED BY: AV DRAWN BY: PO PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 pAUIL Q : No 52186 �O STATE OF C Sis10NAI. V ♦�♦ 7/20/2021 SHEFFP2.4 STOCKROOM - GMIGR (OPTION 4) 12 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 7 PSI (12 SPRINKLERS - 4 SPRINKLERS / 3 LINES) 250 GPM 100 SQ FT MAXIMUM SPACING CLASS 1-IV RACK STORAGE TO 15'-0"/12'-0" (18'-0" CEILING HEIGHT), 4'-0"/0'-6" AISLES; UL LLC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TEST SRR 04191702 /DRR 09191702 & 09261702 / MRR 09211702 Hydraulic Information Remote Area Name System 5 GR Stock - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 12.00 psi K-Factor 16.8 Total Water Required 366 GPM Total Pressure Required 26.76 psi Base of Riser 366 GPM Base of Riser 26.76 psi Safety Margin +22.5 (45.68%) Hydraulic Information Remote Area Name System 5 GR Stock - 12s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 7.00 psi K-Factor 16.8 Total Water Required 789 GPM Total Pressure Required 45.91 psi Base of Riser 789 GPM Base of Riser 45.91 psi Safety Margin +1.04 (2.21 %) 3 RE -SPACE SPRINKLERS IN THIS AF TO BE NO MORE THAN 100 SQ. FT. NEW SPRINKLERS SHALL BE SPAC NO MORE THAN 8 FT APART. PLUG EXISTING HEADS AS NECESSARY OPERATIONAL FLEXIBILITY SYSTEM 5B 3/32" = 1'-0" Hydraulic Information Remote Area Name System 5 GR Receiving - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 12.00 psi K-Factor 16.8 Total Water Required 366 GPM Total Pressure Required 23.84 psi Base of Riser 366 GPM Base of Riser 23.84 psi Safety Margin +25.42 (51.61 %) SALES FLOOR & INTERIOR GARDEN CENTER • (NRC - OPTION 2B) 25 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 10 PSI (12 SPRINKLERS -4 SPRINKLERS 13 LINES) 250 GPM HOSE 140 SQ FT MAXIMUM SPACING CLASS I -IV ON SHELF TO 12'-0" (26-0" CEILING HEIGHT), 6-0" AISLES; UL LLC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TESTS GONDOLA 10041702 Hydraulic Information Remote Area Name System 5 Sales - 2s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 2 @ 25.00 psi K-Factor 11.2 Total Water Required 362 GPM Total Pressure Required 39.34 psi Base of Riser 362 GPM Base of Riser 39.34 psi Safety Margin +9.94 (20.17%) Hydraulic Information Remote Area Name System 5 Sales - 12s Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 10.00 psi K-Factor 11.2 Total Water Required 676 GPM Total Pressure Required 38.28 psi Base of Riser 676 GPM Base of Riser 38.28 psi Safety Margin +9.42 (19.75%) Hydraulic Information Remote Area Name System 5 GR Receiving - 12 Occupancy Classification Owner Provided UL Tested Density 0 GPM Total Hose Streams 250 GPM Flowing Heads 12 @ 7.00 psi K-Factor 16.8 Total Water Required 790 GPM Total Pressure Required 38.86 psi Base of Riser 790 GPM Base of Riser 38.86 psi Safety Ma 8 08 (17 22°/ ) IT - 341 346 � 12-_0_ 12- i 1201 I ® 1202 N O 00 1204 1205 b �� 9 ao I I' f �I I 1207 1208 0 N i 00 I 1210 1211 i 0 N `14 87 4 4 `r --- N 87 12' - 0" 100 12' - 0" ih _ o N i - - co \ N 00 G RE -SPACE SPRINKLERS IN THIS AREA TO BE NO MORE THAN 100 SQ. FT. NEW SPRINKLERS SHALL BE SPACED NO MORE THAN 8' APART. PLUG EXISTING HEADS AS NECESSARY - F Nbo ;+ + " _ + ®- + r + I �. + , f 0� STOCKROOM - GM/GR (OPTION 4) 12 PSI (2 SPRINKLERS - 2 SPRINKLERS / 1 LINE) 7 PSI (12 SPRINKLERS -4 SPRINKLERS / 3 LINES) 250 GPM 100 SQ FT MAXIMUM SPACING CLASS I -IV RACK STORAGE TO 16-O'Y12'-0" (18'-0" CEILING HEIGHT), 4'-0"/0'-6" AISLES; UL LLC TECHNICAL REPORT PROJECT 4788122552, NC27954 - TABLE 2 SUMMARY OF TESTS, TEST SRR 04191702 / DRR 09191702 & 09261702 / MRR 09211702 RE -SPACE SPRINKLERS IN THIS AREA TO BE NO MORE THAN 100 SQ. FT. NEW SPRINKLERS SHALL BE SPACED Hydraulic Information Hydraulic Information Remote Area Name TEST 2 Remote Area Name TEST 1 Occupancy Classification Ordinary Group II Occupancy Classification Ordinary Group 11 Density 0 GPM Density 0 GPM Total Hose Streams 25 GPM Total Hose Streams 25 GPM Flowing Heads 2 @ 12.00 psi Flowing Heads 12 @ 7.00 psi K-Factor 16.8 K-Factor 16.8 Total Water Required 152 GPM Total Water Required 641 GPM Total Pressure Required 28.72 psi Total Pressure Required 38.83 psi Base of Riser 152 GPM Base of Riser 641 GPM Base of Riser 28.72 psi Base of Riser 38.83 psi Safety Margin +21.13 (42.39%) Safety Margin +9,09 (18.98%) Margin + o NO MORE THAN 8' APART. PLUG EXISTING HEADS AS NECESSARY ADD 3" SECONDAR AIN 2 TO GRID THE S EM SEE FP2.3 FOR CONTINUATION _ - - --- - 3 --- -- -3 - --- - --3 - 3 = L _- - 3 41 98 _. 347 1057 1058 1059 701 1056 N 1060 } 114'-7" 15'-0" 15'-0" 14'-6" 13'-0" 13 0" 1 -0" 1061 12'-0" 1062 8'-11" S J 1203 �p � GNP MW am ` 114 1341I 1358 1052 12os , I 1 052 142 1341 1358 DEMOLISH EXI TING 1209 -- - 1 �'' II - SPRINKLER HEADS + , , • AND BRANCH LIE Co.CUT AND CAP AT co ' 1142 1341 1358 d I' SPRINKLER MAIN. I.N 1212 .. 0 - 1142 1341 1358 I I N co \ ---- 11331 1332 1333 + , N 351 I RE CATE fF LESS THAN - = =-- 12" FROM HE L 4 - --4 - 4 - _ - --4 345 �4 � \ \ 4 O T WAL N - - / ----- - -- f� - y - - �-1--- 4--- _4--_- -4-__4 s7 14' ;7" 342 15' - 0" 343 - 15' - 0" 344 14' - 6" N 345 13' - 0" 700 99 13' - 0" ♦ 12' - 0" ♦ 702 ;,12� - 0" ♦ 704 $, - 9u 1141 1305 1345 CD L 1 ( 3 C) I 0 065 iP 93 N 00I - 14'-0" 14'_0„ I J N CD -- I o N i - o - N i +T IIuu N O ++' III I ♦ ♦ ♦ ♦ ♦ ♦ ♦ i I�,. i <Aj - N , I l o !V h N rn I� ICI N ' o ih it N CD ill + -- O N ' 1316 OPERATIONAL FLEXIBILITY SYSTEM 5A 3/32" = 1'-0" W 0U. W�� Z ,- W S U< N fn 0=4TS< OwF�wo W wllrRxOQ�iUoo- �2FLL� Vi Z(YLZZ W Z 0 U a J 0 W 3 W W F< XW"I>_ ~ti3aF�6OS Il a FOagM02W� Z�z�0F�=WWU UW��U�W W O �oo Z�< XLLL0=W�Z>_ LLu a �J �a� ~ in �< �LL LL W 4W � UO-f= � s�E z J D rn z O U Ix m a 0) 04 O O 0) LL 't O 04 � O C _J o .. N G9 . . Ch O o Z N W N 0 � 11' N W m z 00 O ISSUE BLOCK CHECKED BY: DRAWN BY: PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 ♦�� PpuL Q No 52186 0 STATE OF Q/�\ ��F '' • �CORiOp' •''?�� IVAL 7/20/2021 OPERATIONAL i FLEXIBILITY FIRE SPRINKLER PLAN SYSTEM 5 =HEFFP2.5 INSTALL PRESSUF REDUCING VALVE F EACH SYSTEM. FLOW SWITCH (TYP. UPSIZE EXISTING RI: FROM STARTER PIE, TOR TO 6" FOR SYSI OS&Y VALVE (TYP.) AMES 8" 3000SS BACKFLOW PREVEN TO 8" UNDERGROUN 2 c FIRE PROTECTION RISER DIAGRAM 1/2" = 1'-01, o r AUT( HIGF MAN AN A MAIN AIR RELEASE VENT 1/2" = 1'-0" 07/27/18 DECK TOP CHORD OF JOIST EC-25 OR JANDARD UPRIGHT PRINKLER II , PRINKL R BRAN I- S�R�G��M�M�NGE BOTTOM CHORD OF ELECTRICAL 3 JOIST CABLE TRAY CABLE TRAY SPRINKLER - F17 3/4" = 1'-0" ROOF DECK NOTE: REFERENCE AIR RELEASE VENT NOTE ON FP1 1" PLUG w z 0 N AUXILIARY DRAIN NTS SPRINKLER MAIN 1" SHOULDER NIPPLE 1" GLOBE VALVE CHAIN -HUNG SIGNAGE MUST BE VISIBLE AT ALL AREAS — HANG 4 AND 6 INCH PIPE WITHIN 3 INCHES OF PANEL POINT PIPE 3 INCH AND SMALLER NOT REQUIRED TO BE WITHIN 3 INCHES OF PANEL POINT FOR 6 AND 8 INCH PIPE, USE THRU BOLT CONNECTION WHERE POSSIBLE. USE TRAPEZE HANGER WHERE JOIST WEB CONFLICTS WITH THRU BOLT JOIST PANEL POINTS TYP MAX �— DECK TYP MAX TOP BEAM CLAMP TYP FINCH AND SMALLER PIPE �— MAINTAIN VISIBLE CLEARANCE BETWEEN PIPE AND JOIST MEMBERS TYP 4,6 AND 81 PIPE 8 INCH PIPE MAXIMUM HANGER SPACING FOR PIPING PERPENDICULAR TO JOISTS BEAM CLAMP THRU-BOLT BEAM CLAMP NOT TRAPEZED NOT TRAPEZED TRAPEZED 4" PIPE EVERY 12'-0" 4" PIPE EVERY 12'-0" 4" PIPE EVERY OTHER JOIST EVERY OTHER JOIST NOT NECESSARY 6" PIPE EVERY 6'-0" 6" PIPE EVERY 12'-0" 6" PIPE EVERY JOIST EVERY OTHER JOIST NOT NECESSARY 8" PIPE 8" PIPE EVERY 6'-0" 8" PIPE EVERY 6'-0" NOT ALLOWED EVERY JOIST EVERY JOIST 1/4"x2"x2" SQUARE WASHER & HEX NUT 1/2" ALL THREAD ROD FENDER WASHER & HEX NUT 3.5" X 2.5" X .25" ANGLE TRAPEZE REQ'D FOR 6" MAINS 4" X 4" X .25" ANGLE TRAPEZE REQ'D FOR 8" MAINS —� PIPE RUNNING PERPENDICULAR TO JOISTS 6" THRU BOLT TYP MAX I 1 � TOP CHORD OF JOIST TYP N ONE OPEN JOIST BAY MINIMUM BETWEEN TRAPEZE HANGERS DO NOT HANG 2 OR MORE 12" MAINS 4" OR LARGER BETWEEN MIN THE SAME JOIST SPACE MAXIMUM HANGER SPACING FOR PIPES PARALLEL TO JOISTS 4" PIPE EVERY 12'-0" 6" PIPE EVERY 12'-0" 8" PIPE EVERY 12'-V NOT TRAPEZED TRAPEZED TRAPEZED BEAM CLAMP THRU BOLT THRU BOLT PIPE RUNNING PARALLEL TO JOIST CONTRACTOR MAY SUBSTITUTE ANGLE IRON TRAPEZE UTILIZE THESE HANGING METHODS FOR ALL SPRINKLER MEMBER WITH PIPE MEMBER. SIZE PIPE MEMBER IN PIPING. SPACE TRAPEZE HANGERS IN ACCORDANCE ACCORDANCE WITH NFPA-13 AND MAINTAIN 12 INCH WITH SCHEDULE. LOCATE HANGERS WITHIN 3 INCHES MAXIMUM DEFLECTOR DISTANCE OF JOIST PANEL POINTS U.N.O. NOTE: DO NOT SUPPORT SPRINKLER PIPING FROM BOTTOM CHORD OF BAR JOISTS PIPE SUPPORT NTS 12" MIN W ui a WJ2jwg OQTctg � HFwZ W 2fnn<,QZw W~pa�a>tYiO�¢ w � ¢LL=wOZ0f20QN?y aw�mwI O LL J2U�2< WN m�-¢ 0-6 dQco- a- pO'-F2-= z a�_o�woi W-wwo=¢~ O ��No?��ww��� Z� N'w0(lsKlZ>w Q �5Vo QULLIA}(/)LLcn< Of Ii�Z W U) lWZi)Z w0�� °- Z- O (n < Z � W W --) 0- o 0 U FOQUOO afddW0wfwn w m Q U) %004 T o co J 00 LL cb o ° — o G�g = a N co E ry O Z N N w N T r O e� N W m z co ISSUE BLOCK CHECKED BY: AV DRAWN BY: PO PROTO CYCLE: 09/25/20 DOCUMENT DATE: 11/06/20 i CENSF Q No 52186 i0 STATE OF %►�` ACOR/OP- •' ?�i ` NAL ct 7/20/2021 FIRE PROTECTION DETAILS SHEET: FP3