Loading...
HomeMy WebLinkAbout38235 C Ave (3)I__ u __ _i—Ii... ! --- - - -- .� 1 1- - L" WII �- -- t- - L J-� �, --� -- - — I - - - -- _ - L - —u I_ II1___ — -- 1 _ _l._ n I if!111e� n!n�_1L.1LL� �I _ 44 1� O 12 o r o VATION 1 J> a o�4 A> � � Q�o pro Q�o pro b D t"> D po �Qe aQ o a ° ®rO o boo, 40 17911 NNUM11 12 IF GLG. HGT. — lop WIN/DR. HGT. lip F T S I D E FIBERGLASS Y Sl-11NrzLES _ GLG. HGT. — IWV WIN/DR. HGT. F.F. ELEV. — L rz V A T I O N GLG. HGT. n 0 —` WIN/DR. HGT. TABLE 1405.2 MINIMUM THICKNESS OF WEATHER COVERING`) COVERING TYPE MINIMUM THICKNESS (inches) Adhered masonry veneer 025 Aluminum siding 0.019 Anchored masonry veneer 2.625 Asbestos -cement boards 0.125 Asbestos shingles 0.156 Cold -rolled copper 0.0216 nominal Copper shinglesd 0.0162 nominal Exterior plywood (with sheathing) 0.313 Exterior plywood (without sheathing) See Section 2304.6 (HVHZ, see Section 2322) Fiber cement lap siding 0.25 c Fiber cement panel siding 0.25 c Fiberboard siding .05 Glass -fiber reinforced concrete panels 375 Hardboard siding c 025 High -yield copperd 0.0162 nominal Lead -coated copperd 0.0216 nominal Lead -coated high -yield copper 0.0162 nominal Marble slabs 1 Particleboard (with sheathing) See Section 2304.6 (HVHZ, see Section 2315.1.11) Particleboard (without sheathing) See Section 2304. 6(HVHZ, see Section 2315. 1. 11) Porcelain Tile 0.025 Precast stone facing 0.625 Steel (approved corrosion resistant) 0.0149 Stone (cost artificial anchored) 1.5 Stone (natural) 2 Structural glass .344 Stucco or exterior Portland cement plaster Three -coat work over: Metal plaster base 0.875 b nominal Unit masonry 0.625 b nominal Cast -in -place or precast concrete 0.625 b nominal Two -coat work over: Unit masonry 0.5 b nominal Cast -in -place or precast concrete 0.375 b nominal Terra cotto (anchored) 1 Terra cotta (adhered) -_ 0.25 Vinyl siding _ - 0.035 Wood shingles 0.375 Wood siding (without sheathing) 0.5 i �i I + I I �1 � I , i I s I r 4 00 N I I I 1 , lil h li L, k ro r s. 7_ y _ C• Y h C 1: 11 mMM�11 For SI: 1 inch = 25.4 mm. a. Wood siding of thicknesses less than 0.5 inch shall be placed over sheathing that conforms to Section 2304.6. (HVHZ, see Section 2322) b. Exclusive of texture. c. As measured at the bottom of decorative grooves. d. 16 ounces per square foot for cold -rolled copper and lead -coated copper, 12 ounces per square foot for copper shingles, high -yield copper and leadcoated high -yield copper. SECTION R704 INSPECTION FOR TERMITES In order to provide for inspection for termite infestation, clearance between exterior wall coverings and final earth grade on the exterior of a building shall not be less than 6 inches (152 mm). Exceptions: 1. Paint or decorotive cementitious finish less than j inch (17.1 mm) thick adhered directly to the masonry foundation sidewall. 2. Access or vehicle ramps which rise to the interior finish floor elevation for the width of such ramps only. 3. A 4-inch (102 mm) inspection space above patio and garage slabs and entry areas. 4. If the patio has been soil treated for termites, the finish elevation may match the building interior finish floor elevations on mosonry construction only. 5. Masonry veneers constructed in accordance with Section R318.4. 1/4" TOOLED JOINTL SMOOTH FINISH - BANDS z � a 117 GEMENT f - D TEXTURED 111 2 FINISH II 241 SH I II - 0 - io • ROUGH FINISH STUCCO o ® TOOLED BAND DETAIL- Wo-e FF. ELEV. F.F. ELEV. — — . — . — . — . — . — . — — . — . — . — . — . — . — .� — . — . — . — . — • N.T.S. c ALL WORK SHALL COMPLY WITH PREVAILING CODES FLORIDA BUILDING CODE, NATIONAL ELECTRIC CODE, N I ■r rm r%�orjON1_ ID 2 4 2R j G H * D F r F \/ %� * 1 ON1_ AND THE CITY OF ZEPHYRHILLS I �i, I}( !M■r1 I I I 1( !�1 I ORDINANCES 51A RB 2 5 2OZZ REVIEW DATE___ CITY OF ZEPHYRHILL ' PLAN EXAMINER_ - I i c Digitally signed by Signed and scaled by I HansonI lu;y , Thomas L using❑ Digital stgnalm,,ruld.w ; °,.nx ;c Thomas L Prinled u,prcs ui flu, (1,,, merl S Hanson:A01410 Hdnson:A01410D00000 ' "'°I,nn„`'eredsleneda �: ✓. +"'• scaled and the s'gnaturn nrtlsl be w 177EF31134E000015ADA vented nn any Cie, .h Date: 2021.12.15 B4E000015ADA 08:48:09-05'00' O CN �o ^, '_13 c co f 04 L � W '4: �Q5Lq rJ co z rz UI q 2 � u. e ter.✓ q , G_. • g..o O ck: v vc w ; •v. Simpson HETAiro (or aqua 1) Installed per Manuf. specs_ Net Uplift is less than 1510 lbs. -4" 32'-O" BE-1111 b ----t---1---�I----I--------+---+----F---+----1-----F---W--- ------- - ---------------------------------- -- ----I----I---- I I I I I II I I I I I I I I II � I I XA LI I I I I I I I II ��--- I II I I I I I I I r--ILA I - I -�-�- I I I L4�k� RJ I I I � J�v I'I�j II I I I I I I I I II � l I II III ill( II III II II - - - � lll�- fill IL r---------$- -} ---�- ----%---} ---} --� I r---F--$---------- I I I I I I I I I I I I I I I I I I I I I I I- I I I I I I vl 0 2' 4' I 1 i m WIND DESIGN INFORMATION ROOF fm I. Wind Speeds of 139 MPH Vult k 105 MPH Vasd 2. Risk Category = II 3. Exposure Category B 4. Enclosed Building, (GCpf = +/- 0.10) 5. Component f Cladding Pressures (PSF): R = 31.2,-40.0 W = 33.2,-43.4 OH= -55.6 NOTE: WIND LOAD CALCULATIONS ARE BASED ON WORST CASE' . ALL CONNECTORS WILL BE UNIFORM FOR SIMILAR USES. THIS 5TRUCTURE HAS BEEN DESIGNED TO WITHSTAND INTERNAL PRESSURES, ENCL05ED BUILDING. TABLE 1609. 6( 1) NOMINAL (ASD) GARAGE DOOR AND ROLLING DOOR WIND LOADS FOR A BUILDING WITH A MEAN ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE 8 (PSF) 1, 2, 3, 4, 5 Ell -41' Simpson HETA16 for equal) Installed per ManuF. specs. Net Uplift is less than laI0 lbs. Truss Systems Engineering by others ULTIMATE DESIGN WIND (VU10 DETERMINED IN ACCORDANCE WITH SECTION 1609.3 (MPH - 3 SECOND GUST) Width (ft) Height (ft) 100 MPH 110 MPH 120 MPH 130 MPH 140 MPH 150 MPH 160 MPH 170 MPH 180 MPH 190 MPH 200 MPH Roof Angle 0 - 10 degrees 8 8 +10. 0 -10. 0 -10. 5 -11. 9 +12. 5 -14. 2 +14. 7 -16. 6 +17. 1 -19. 3 +19. 6 -22. 2 +22. 3 -25. 2 +25. 1 -28. 5 +28. 2 -31. 9 +31. 4 -35. 5 +34. 8 -39. 4 10 10 +10. 0 -10. 0 +10. 2 -11. 4 +12. 1 -13. 6 +14. 2 -16. 0 +16. 5 -18. 5 +18. 9 -21. 2 +21. 5 -24. 2 +24. 3 -27. 3 +27. 3 -30. 6 +30. 4 -34. 1 +33. 7 -37. 8 14 14 +10. 0 -10. 0 +10. 0 -10. 8 +11. 5 -12. 8 +13. 5 -15. 0 +15. 7 -17. 4 +18. 0 -20. 0 +20. 5 -22. 8 +23. 1 -25. 7 +25. 9 -28. 8 +28. 9 -32. 1 +32. 0 -35. 6 Roof Angle 0 > 10 degrees 9 7 +10. 0 -10. 9 +11. 4 -12. 9 +13. 7 -15. 5 +16. 1 -18. 2 +18. 5 -20. 9 +21. 3 -24. 1 +24. 3 -27. 5 +27. 6 -31. 2 +30. 6 -34. 6 +34. 2 -38. 6 +38. 0 -43. 0 16 7 +10. 0 -10. 3 +10. 9 -12. 2 +13. 1 -14. 6 -15. 5 -17. 2 +17. 7 -19, 7 +20. 4 -22. 7 +23. 3 -26. 0 +26. 4 -29. 4 +29. 3 -32. 6 +32. 7 -36. 5 +36. 4 -40. 6 78 MPH 85 MPH 93 MPH 101 MPH 108 MPH 116 MPH 124 MPH 132 MPH 139 MPH 147 MPH 155 MPH For SI: 1 foot = 304.8 mm, 1 mile per hour = 1.609 km/h, 1 psf = 47.88 N/m2. Nominal Design Wind Speed (Vosd) converted from Ultimate Desi,,,r, Wind Speed per Section 1609.3.1 1. For door sizes or wind speeds between those given above the load may be interl,,,lated, otherwise use the load associated with the lower door size. 2. Table values shall be adjusted for height and exposure by multiplying by the .-djustment coefficient in table 1609.6(2). minimum positive wind load shall be 10 psf and minimum negative wind load shall be 10 psf. 3. Plus and minus signs signify pressures acting toward and away from the building surfaces. r A KI.-+S"n "--.,.o noo i1,-, kn 0 fool of ,..mill. ,n k.,; 1Ai,, 9� n A �n R Tnhlc " 1-- �I .4. + k . n R 1 A e4, li ^^ fl..� TRUSS MANUFACTURER TO PROVIDE SIGNED AND SEALED TRUSS DRAWINGS INCLUDING BRACING DETAILS. ATTIC VENTILATION - FLORIDA BUILDING CODE Total Area Under Roof 1,024.00 Square Feet (SF) Total Required Ventilation 6.83 SF Total Area / 150 Area Total Required Ventilation 3.41 SF Reqd Area / 2 Area at Soffits Total Required Ventilation Area at Roof 3.41 SF Reqd Area / 2 Overhang Dimension 1.33 Feet Ventilation Examples -Owens Corning Ventilation Required At Soffit Units Units Capacity Vent Triple 4" Center Vent 1.56 sq in / ft 315.08 Feet Triple 4" Full Vent 4.68 sq in / ft 105.03 Feet Double 5" Full Vent 4.25 sq in / ft 115.65 Feet Ventilation Required At Roof Units Units CapacitV Vent Ventsure Metal Dome with Screen 144 sq in 4 Vents Ventsure High Profile Slant Back Roof Vent w/ 50 sq in 10 Vents Exterior Louver Ventsure Plastic Slant Back Roof Vent w / 61 sq in 9 Vents Interior Louver Ventsure Rigid Strip Ridge Vent, Externally 15 sq in / ft 33 Feet Baf f led BUILDING CONSTRUCTION NOTES 1. This Garage is to the lth Edition (2020) FEBC (Florida Building Code) type construction requirements. Construction shall comply with local County and state agencies. 2. All openings around walls, partitions, pipes, ducts, conduits etc.., shall be sealed fully and sound proofed with sealants of type for application. 3. Painting.. All surfaces shall be properly prepared and cured to manufacturer's instruction prior to painting. Paint shall be "first line" produced by PORTER, SHERWIN WILLIAMS, or equal with colors selected by the owner. All painted surfaces shall be painted with materials appropriate for the application in a workmanship manner to the paint manufacturer's instruction. 4. Caulk all exposed ,Joints. Clean, prime, caulk and seal all joints between door and window frames with DOW CORNING; silicon of type for application. Use foam back-up rods as required at wide joints. Use acoustical Foam sealants by DAP or TREMCO at sound proofing applications at openings or cracks. 5. Energy Code - These plans where designed with common design practices. However, this does not guarantee that this plan will pass the "Florida Energy Code". These plans shall be reviewed by a proper HVAC professional and shall pass the "Florida Energy Code" or recommendations from such Professional shall be provided to the Home Designer (Corner Stone Design Group, Inc_) so as to meet such requirements. ■ 2319. 17. 1. 2 Where a ceiling is to be attached directly to the underside of trusses, the trusses shall be laterally braced with continuous 1-inch by 4-inch (25 mm by 102 mm) members nailed with 8d common nails to the upper side of the bottom chord at panel points but not to exceed 10 feet (3 m) apart. This lateral bracing shall be restrained at each end and at 20-foot (6 m) intervals. Drywall may be considered a rigid ceiling in enclosed areas where it is protected from the elements. The drywall ceiling is not to be considered a ceiling diaphragm. 7.. A nMnCC OO A n T Ain I n T nnr TOP/BOTTOM CHORD GABLE END BRACING @ 48" 0. C. MAX FOR THE FIRSi 4 ROWS OF TRUSSES Li J 0 t CONT. BOTTOM CHORD BRACING (1"x4" MIN.) @ 10' -0" MAX. SEE TRUSS SYSTEM ENGINEERING DRAWINGS FOR ANY ADDITIONAL BRACING OR CROSS BRACING REQUIREMENTS REQ. MINIMUM TRUSS BRACING 24" O.C. (2) 16d NAILS 2x4 DIA6. BRACE (FOLLOW TRU55 MANUFACTURERS RECOMMENDATION (2) 16d NAILS \ "L" BRACE CsABLE END TRUSS /2X4x& LATERAL BRACING CONTINOU5 9 45" O.C. / (5) 16d NAILS GABLE END DIAGONAL BRACE DETAIL U n. O 0 c a) 0 O c O (n N c O U N 0 N F- O a- O 0 Thomas L Digitally signed by Signs•daudsc•aled6vT.L..IlansuuPE ,•,\0� 11111fI/ ThomasL usmgalhtpLdSignalurcand dale. Han son:A01410 ,nl(eit,otsidcred sig cdanent Ha nson:A01410D00000 are not � unstderrJ segued and D00000177 EF31 177EF31 134F000015ADA scaled and the agnature must be vrnlicd tin any rlectronnc , LU : ? Date: 2021.12.15 B4E000015ADA 08:48:47-05'00' I I I I i I L _ ., 1 I _, I I 1 _ ill Il I '_I 1 ' 1 1 1LIT 1l ' I 11'I't J1 1 1' !ll e m DOOR SCHEDULE, OUT SWING DOORS DOOR DISCRPTION FRAME ROUGH OPENING BLOCK ROUGH 2868 34" x 80 7/8" 37" x 82 3/8" 3068 38" x 80 7/8" 41" x 82 3/8" 3068 wl SINGLE 1068 LIGHT 51 1/2" x 80 7/8" 54 1 2" x 82 3/8" 3068 w/ DOUBLE 1068 LIGHT 65" x 80 7/8" 68" x 82 3/8" 6068 75" x 80 7/8" 78" x 82 3/8" 2880 34" x 96 7/8" 37" x 98 1/2" 3080 38" x 96 7/8" 41" x 98 1/2" 3080 w/ SINGLE 1080 LIGHT 51 1/2" x 96 7/8" 54 1/2' x 98 1/2" 3080 w/ DOUBLE 1080 LIGHTS 65" x 96 7/8" 68" x 98 1/2" 6080 75" x 96 7/8" 78" x 98 1/2" 6080 w/ DOUBLE 1080 LIGHTS 102 1/4" x 96 7/8" 105 1/4" x 98 1/2" 6080 w/ DOUBLE 3080 LIGHTS 150 1/4' x 96 7/8" 153 1/4" x 98 1 2" 6080 w DOUBLE 2880 LIGHTS 142 1/4' x 96 7/8" 145 1/4" x 98 1 2" 6080 w/ DOUBLE 1280 LIGHTS 69" x 96 7/8" 72" x 98 1/2" *NOTE: THE ABOVE DOOR CHART FITS MOST DOOR MANUFACTURERS DOORS HOWEVER THE CONTRACTOR SHALL VERIFY WITH CHARTS / DOCUMENTATION PROVIDED WITH SPECIFIC DOOR MANUFACTURER WINDOW ROUGH OPENING CHART WINDOW BLOCK CON5TRl1GTION (1/2" FLANGE) FRAME CONSTRUCTION (1/2" FLANGE) CODE WIDTH HEIGHT WIDTH HEIGHT 12 SH 19 7/8"" x 26' 19 1/4- x 26 1/4' 13 SH 19 7/8"" x 38 3/8' 19 1/4' x 38 5 8- 14 SH 19 7/8"' x 50 5/8' 19 1/4" x 50 7/8" 15 SH 19 7/8"' x 63" 19 1/4- x 63 1/4" 16 SH 19 7/8"" x 76 3 4" 19 1/4- x 76 3 4" H32 SH 27 1/4- x 26" 26 5/8" x 26 1/4" H33 SH 27 1/4" x 38 1/4- 26 5/8" x 38 5/8' H34 SH 27 1/4' x 50 5/8* 26 5/8" x 50 7 8" H35 SH 27 1/4- x 63' 26 5/8" x 63 1/4' H36 SH 27 1/4" x 76 3 4' 26 5/8" x 76 3 4" 22 SH 37 3 4" x 26" 37 1 8" x 26 1/4' 23 SH 37 3 4- x 38 1/4' 37 1 8" x 38 5/8" 24 SH 37 3 4" x 50 5/8* 37 1/8 . x 50 7/8" 2WE SH 37 3 4- x 56' 37 1 8" x 56 1/4" 25 SH 37 3 4" x 63' 37 7 8" x 63 1/4" 26 SH 37 3 4- x 76 3 4- 37 ] 8" x 76 3 4' 32 SH 53 7/8" x 26' 53 1/4- x 26 1/4' 33 SH 53 7/8' x 38 1/4- 53 1/4" x 38 5/8' 34 SH 53 7/8' x 50 5/8- 53 1/4" x 50 7/8- 3WE SH 53 7/8' x 56' 53 1/4" x 56 1/4' 35 SH 53 7/8" x 63' 53 1/4" x 63 1/4" 36 SH 53 7 8" x 76 3 4" 53 1/4" x 76 3/4- (2) 22 SH' s 74 3 4" x 26" CHECK WITH MANUF. _ 2 32 SH's 107" x 26" CHECK WITH MANUF. 2 23 SH' s 74 3 4" x 38 1/4- CHECK WI TH MANUF. 2 33 SH's 107" x 38 1/4' CHECK WITH MANUF. 2 24 SH's 74 3 4" x 50 5/8- CHECK WITH MANUF. 2 34 SH's 107" x 50 5/8' CHECK WITH MANUF. 2 25 SH's 74 3 4" x 63" CHECK WITH MANUF. 2 35 SH's 107" x 63" CHECK WITH MANUF. *NOTE: THE ABOVE WINDOW CHART FITS MOST WINDOW MANUFACTURERS WINDOWS HOWEVER THE CONTRACTOR SHALL VERIFY WITH CHARTS / DOCUMENTATION PROVIDED WITH SPECIFIC WINDOW MANUFACTURER v 61 M 32'-0" ■ ■ 2P I I I � I 30'-8" X 301-8" 10'-0" CLG. HGT. I u� -� I Ira I r- I I I I I I I I I I I I LQ� -J - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -I r - - - - - - - - - - - - - - - - - I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I WX 7' OHG.D. I I 8'x 7' OH.G.D. --------------------------------------------- TM 2'-4" I_ 18'-0" IY-4" I. 8'-0" I 2'-4" I FRX1 CINCH NOTES: ALL INTERIOR DIMENSIONS ARE GIVEN TO THE INDICATED R602.1 GENERAL. WOOD AND WOOD -BASED PRODUCTS USED CENTER OF THE STUD UNLESS NOTED OTHERWISE. FORLOAD-SUPPORTING PURPOSES SHALL CONFORM TO THE APPLICABLE PRO -VISIONS OF THIS SECTION. ALL EXTERIOR DIMENSIONS ARE GIVEN TO THE FACE OF THE STUD OR FACE OF BLOCK (AS APPROPRIATE) WHICH LINES R602.1.8 WOOD STRUCTURAL PANELS. WOOD STRUCTURAL WITH THE FOUNDATION BELOW. PANELSHEATHING SHALL CONFORM TO DOC PS 1, DOC PS 2 OR, WHENMANUFACTURED IN CANADA, CSA 0437 OR CSA 0325. ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PANELSSHALL BE IDENTIFIED FOR GRADE, BOND PRESSURE TREATED OR APPROVED CEDAR, OR HAVE 15 LB. CLASSIFICATION, AND PER-FORMANCE CATEGORY BY A GRADE FELT BARRIER. MARK OR CERTIFICATE OFINSPECTION ISSUED BY AN APPROVED AGENCY. SEE SHEETS - S1, S2 AND ADDITIONAL "S" SHEETS R602.1.9 PARTICLEBOARD. PARTICLEBOARD SHALL CONFORM FOR ADDITIONAL STRUCTURAL DETAILS / NOTES TOANSI A208.1. PARTICLEBOARD SHALL BE IDENTIFIED BY THEGRADE MARK OR CERTIFICATE OF INSPECTION ISSUED BY R602.1 GENERAL. WOOD AND WOOD -BASED PRODUCTS USED ANAPPROVED AGENCY. FORLOAD-SUPPORTING PURPOSES SHALL CONFORM TO THE APPLICABLE PRO -VISIONS OF THIS SECTION. R602.1.10 FIBERBOARD. FIBERBOARD SHALL CONFORM TOASTM C208. FIBERBOARD SHEATHING, WHERE USED STRUCTUR-ALLY, R602.1.1 SAWN LUMBER. SAWN LUMBER SHALL BE SHALL BE IDENTIFIED BY AN APPROVED AGENCY AS IDENTIFIEDBY A GRADE MARK OF AN ACCREDITED LUMBER CON -FORMING TO ASTM C208. GRADING ORINSPECTION AGENCY AND HAVE DESIGN VALUES CERTIFIED BY ANACCREDITATION BODY THAT COMPLIES WITH R602.2 GRADE. STUDS SHALL BE A MINIMUM NO. 3, STANDARD DOC PS 20. 1N LIEUOF A GRADE MARK, A CERTIFICATION OF ORSTUD GRADE LUMBER. INSPECTION ISSUED BY ALUMBER GRADING OR INSPECTION EXCEPTION: BEARING STUDS NOT SUPPORTING FLOORS AND AGENCY MEETING THE REQUIRE-MENTS OF THIS SECTION SHALL NON -BEARING STUDS SHALL BE PERMITTED TO BE UTILITY BE ACCEPTED. GRADE LUMBER,PROVIDED THE STUDS ARE SPACED IN ACCORDANCE WITH TABLER602.3(5). R602. 1.2 END -JOINTED LUMBER. APPROVED END-JOINTEDLUMBER IDENTIFIED BY A GRADE MARK R602.3 DESIGN AND CONSTRUCTION. EXTERIOR WALLS OF CONFORMING TO SECTIONR602.1 SHALL BE PERMITTED TO BE WOOD -FRAME CONSTRUCTION SHALL BE DESIGNED AND USED INTERCHANGEABLY WITHSOLID-SAWN MEMBERS OF THE CONSTRUCTED INACCORDANCE WITH THE PROVISIONS OF THIS SAME SPECIES AND GRADE. END -JOINTED LUMBER USED IN AN CHAPTER AND FIGURESR602.3(1) AND R602.3(2), OR IN ASSEMBLY REQUIRED ELSEWHERE INTHIS CODE TO HAVE A ACCORDANCE WITH AWC NDS.COMPONENTS OF EXTERIOR WALLS FIRE -RESISTANCE RATING SHALL HAVE THE SHALL BE FASTENED IN ACCORDANCEWITH TABLES R602.3(1) DES-IGNATION "HEAT RESISTANT THROUGH R602.3(4). WALL SHEATHINGSHALL BE FASTENED ADHESIVE" OR "HRA" INCLUDED INITS GRADE MARK. DIRECTLY TO FRAMING MEMBERS AND, WHEREPLACED ON THE EXTERIOR SIDE OF AN EXTERIOR WALL, SHALL BE CAPA-BLE R602.1.3 STRUCTURAL GLUED -LAMINATED TIMBERS. OF RESISTING THE WIND PRESSURES LISTED IN TABLE GLUED -LAMINATED TIMBERS SHALL BE MANUFACTURED AND R301.2(2)ADJUSTED FOR HEIGHT AND EXPOSURE USING TABLE IDENTIFIED ASREQUIRED IN ANSI/AITC A190.1 AND ASTM R301.2(3) ANDSHALL CONFORM TO THE REQUIREMENTS OF D3737. TABLE R602.3(3). WALLSHEATHING USED ONLY FOR EXTERIOR R602.1.4 STRUCTURAL LOG MEMBERS. STRUCTURAL LOG WALL COVERING PURPOSES SHALLCOMPLY WITH SECTION R703. MEM-BERS SHALL COMPLY WITH THE PROVISIONS OF ICC 400. STUDS SHALL BE CONTINUOUS FROM SUPPORT AT THE SOLE PLATE TO ASUPPORT AT THE TOP PLATE TO RESIST LOADS R602.1.5 STRUCTURAL COMPOSITE LUMBER. PERPENDICULAR TO THEWALL. THE SUPPORT SHALL BE A STRUCTURALCAPACITIES FOR STRUCTURAL COMPOSITE LUMBER FOUNDATION OR FLOOR, CEILING ORROOF DIAPHRAGM OR SHALL SHALL BE ESTAB-LISHED AND MONITORED IN ACCORDANCE WITH BE DESIGNED IN ACCORDANCE WITHACCEPTED ENGINEERING ASTM D5456. PRACTICE. EXCEPTION: JACK STUDS, TRIMMER STUDS AND CRIPPLE STUDS R602.1.6 CROSS -LAMINATED TIMBER. CROSS -LAMINATED ATOPENINGS IN WALLS THAT COMPLY WITH TABLES R602.7(1) TIM-BER SHALL BE MANUFACTURED AND IDENTIFIED AS ANDR602.7(2). REQUIRED BYANSI/APA PRG 320. R602.1.7 ENGINEERED WOOD RIM BOARD. ENGINEERED WOODRIM BOARDS SHALL CONFORM TO ANSI/APA PRR 410 OR SHALLBE EVALUATED IN ACCORDANCE WITH ASTM D7672. STRUCTURALCAPACITIES SHALL BE IN ACCORDANCE WITH EITHER ANSI/APAPRR 410 OR ESTABLISHED IN ACCORDANCE WITH ASTM D7672.RIM BOARDS CONFORMING TO ANSI/APA PRR 410 SHALL REMARKED IN ACCORDANCE WITH THAT STANDARD. GARAGE- 1024 5F LECsEND DOOR SIZE FEET (HGT. (o'-W UNLE55 NOTED OTHERWISE) DOOR 51ZE INCHES 0 P EPRE-HUNG (PH) or WRAP (W) or POCKET (PKT) WINDOW SIZE 34 5H ® PLATE HGT. 19 10'-0" AF.F. ® BEARING WALL ALL CMU WALLS CONSIDERED SHEAR WALL ■ CELL POURED SOLID w/ wil FROM FTG. TO BOND BEAM LOAD SUMMARY DESCRIPTION kVA GENERAL LIGHTING' 1024 Sq. Ft. @ 3 Watts per Sq. Ft. = 3.1 10.0 -10.0 kw x .35 = -3.50 6.8 6.7 TOTAL CALCULATED 20.0 Calculated load for service size is 20.0 kW divided by 230V = 87.0 Amps (Amps 100A SERVICE. First 10 kW @ 100% _ Remainder at 35% HEATING 1-AH Vill = 1-HP = --------------- °21 1� In��.�cTRica� B2 ELECTRICAL SYMBOLS LEGEND CEILING LIGHT m 200 AMP. PANEL ® TELEVISION PRE -WIRE {R} RECESSED CAN LIGHT --------e ill __-----4% SHOP FLUORESCENT LIGHT SZ TELEPHONE PRE -WIRE 0 110V DUPLEX RECEPTACLE - - - - - - - j j 2'X 4' FLUORESCENT Qi ® SMOKE ALARM CARBON MONOXIDE 220V OUTLET LIGHT DETECTOR I 110v G.F.I. OUTLET TRACK LIGHTING O JUNCTION BOX �yy 1�J SWITCHED DUPLEX REC. Idl PUSH BUTTON (GD.O., vOVGOVUOVOOv BEAUTY BAR LIGHT T CHIMES, ETC.) ® OUTLET (HUA4, AH, ETC.) _ FLOOD LIGHT $ SINGLE POLE SWITCH �� ® DOOR BELL CHIME BRACE 4 $3 THREE WAY LIGHT SWITCH 1\ FRE WIRE FOR FAN f'��� ELECTRICAL WIRING ot Vy GARAGE DOOR OPENER / r L , EXHAUST FAN LIGHT/EX. FAN INTERIOR ELECTRICAL OUTLET LOCATIONS PADDLE FAN SWITCH (LOCATE OVER FAN LIGHT SWITCH) LIGHT SWITCH DUPLEX OUTLET AT KITCHEN COUNTER, REFRIG., WASHER AND GARAGE OUTLETS DUPLEX OUTLET AT VANITY COUNTER STANDARD DUPLEX OUTLET 9 250.94 BONDING FOR OTHER SYSTEMS. AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES. THE INTERSYSTEM BONDING TERMINATION SHALL BE ACCESSIBLE FOR CONNECTION AND INSPECTION THE INTERSYSTEM BONDING TERMINATION SHALL HAVE THE CAPACITY FOR CONNECTION OF NOT LESS THAN THREE INTERSYSTEM BONDING CONDUCTORS. THE INTERSYSTEM BONDING TERMINATION DEVICE SHALL NOT INTERFERE WITH OPENING A SERVICE OR METERING EQUIPMENT ENCLOSURE. THE INTERSYSTEM BONDING TERMINATION SHALL BE ONE OF THE FOLLOWING: (1) A SET OF TERMINALS SECURELY MOUNTED TO THE METER ENCLOSURE AND ELECTRICALLY CONNECTED TO THE METER ENCLOSURE. THE TERMINALS SHALL BE LISTED AS GROUNDING AND BONDING EQUIPMENT. (2) A BONDING BAR NEAR THE SERVICE EQUIPMENT ENCLOSURE, METER ENCLOSURE, OR RACEWAY FOR SERVICE CONDUCTORS. THE BONDING BAR SHALL BE CONNECTED WITH A MINIMUM 6 AWG CAPPER CONDUCTOR TO AN EQUIPMENT GROUNDING CONDUCTOR($) IN THE SERVICE EQUIPMENT ENCLOSURE, METER ENCLOSURE, OR EXPOSED NONFLEXIBLE METALLIC RACEWAY. (3) A BONDING BAR NEAR THE GROUNDING ELECTRODE CONDUCTOR THE BONDING BAR SHALL BE CONNECTED TO THE GROUNDING ELECTRODE CONDUCTOR WITH A MINIMUM 6 AWG COPPER CONDUCTOR 1111111 P L A N ELECTRICAL NOTES ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO ALL APPLICABLE CODES SUCH AS THE NATIONAL ELECTRICAL CODE 2011, LOCAL ORDINANCES AND POWER COMPANY REGULATIONS. SUBCONTRACTOR SHALL BE LICENSED, CARRY ALL APPLICABLE.INSURANCE, AND HAVE A CURRENT COUNTY OCCUPATIONAL LICENSE. AS ALLOWED, CONNECT ADDITIONAL ELECTRICAL TO EXISTING CIRCUITS. SUBCONTRACTORS SHALL INCLUDE ALL SPECIAL FEES AND PERMITS, LABOR AND MATERIAL, EQUIPMENT AND ELECTRICAL ENGINEERING NECESSARY TO PROVIDE AN APPROVED WORKING SYSTEM. LIGHT FIXTURES EXCLUDED EXCEPT FOR FLUORESCENT FIXTURES AND RECESSED LIGHTS. CONCRETE -ENCASED ELECTRODE. AN ELECTRODE ENCASED BY AT LEAST 2" OF CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF THE CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER ELECTRICITY CONDUCTIVE COATED STEEL SEIhFORCING BARS OR RODS OF NOT LE88 THAN 1/2 INCH DIAMETER OR CONSISTING OF AT LEAST 20 FEET OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS." 210.12 ARC -FAULT CIRCUIT -INTERRUPTER PROTECTION. (A) DEFINITION, ARC -FAULT CIRCUIT INTERRUPTER (AFCI). A DEVICE INTENDED TO PROVIDE PROTECTION FROM THE EFFECTS OF ARC FAULTS BY RECOGNIZING CHARACTERISTICS UNIQUE TO ARCING AND BY FUNCTIONING TO DE-ENER ,1ZE THE CIRCUIT WHEN AN ARC FAULT IS DETECTED. (B) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, AND OTHER SPECIFIED ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC -FAULT CIRCUIT INTERRUPTER COMBINATION -TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. CARBON MONOXIDE ALARMS R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL -FUEL -BURNING, HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 mm) OF EACH ROOM USED FOR SLEEPING PURPOSES. EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN SECTION R315.13. R315U.1 CARBON MONOXIDE ALARM. THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS: (1) A HARD -WIRED CARBON MONOXIDE ALARM. (2) A BATTERY -POWERED CARBON MONOXIDE ALARM. (3) AHARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE ALARM. (4) A BATTERY -POWERED COMBINATION CARBON MONOXIDE AND SMOKE ALARM. R315.11 COMBINATION ALARMS. COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. R315.13 ADDITION SHALL MEAN: AN EXTENSION OR INCREASE IN FLOOR AREA, NUMBER OF STORIES OR HEIGHT OF A BUILDING OR STRUCTURE ALL ELECTRICAL 6WITCNE6, OUTLETS, ETC. TO BE MOUNTED ABOVE THE BASE FLOOD ELEVATION. (SEE SITE PLAN FOR BASE ELEVATION) (3)2/0,4G Cu, 2'IC 100A MLO 120/240V METER 17 3 WIRE SN FO �mo,4 (3)2/0 Cu, 2"C TO UTILITY_ TRANSFORMER NO. 4 CU GROUND IN ACCORDANCE WITH NEC 250 ELECTRICAL RISER NTS C) S✓ Q_ n O CD a� N C O i (n O C t_ O 0 N O CV O 0 0 Slgnvdand scaled bvTA, HansonPF: .,\'``''ulfl/// Thomas L Digitally signed by ns+„ , rn Ital s� n:,tnrc and dal(. g g Thomas L rnntcd ,>h ,, of d,� <lucnn,cnt r • :- Ha n son:A01410 Hanson:A01410D00000 dfd lot u'nsidcrcd ug"=d a,,.1 ' D00000177 EF31 177EF3164E00001 5ADA s 11` 1311d thr s,gn::t,nr tnusl bC Date 2021.12.15 vII,til Un a„1 CleCtfUnlC Co 0' B4E000015ADA 08:49:26 05'00' I -- I I 1 F a gry'_mn le le _ I 20"x Iro" CONTINUOUS CONCRETE FOOTIN ■ w/(2)05 REBAR ON CHAIRS a 4'-0" O.C. ■ _ N 1 ■ I I I I ■ ■ I I ■ I 3-1/2" CONCRETE w/6"X �o"X I0/10 W.W. MESH =, - I REINFORCING REQUIRED THROUGHOUT THE I v CONCRETE SLAB OR SYNTHETIC FIBER _ REINFORCEMENT ■ I e 0 W/CELL POURED SOLID 6 8'-0" D.G. MAX I ■ N (STEM WALL) BELOW FINISHED FLOOR) I In 100.00, Z ■ I ■ 111 � I I O I r l O R1 J' m I I m ■ I I ■ ■ I I ■ I" DEEP RECESS x 10" WIDE (TYP.) I'-4" s I6'-8" a a,_$m 2'-4" THE FOUNDATION HAS BEEN DESIGNED FOR A MINIMUM LOAD -BEARING PRESSURE OF 2000 POUNDS PER SQUARE FOOT SECTION 1907 MINIMUM SLAB PROVISIONS 1907.1 General. The thickness of concrete floor slabs supported directly on the ground shall not be less than 3 1/2 inches (89 mm). A 6-mil (0.006 inch; 0.15 mm) polyethylene vapor retarder with joints lapped not less than 6 inches (152 mm) shall be placed between the base course or subgrade and the concrete floor slab, or other approved equivalent methods or materials shall be used to retard vapor transmission through the floor slab. Exception: A vapor retarder is not required: 1. For detached structures accessory to occupancies in Group R-3, such as garages, utility buildings or other unheated facilities. 2. For unheated storage rooms having an area of less than 70 square feet (6.5 m2) and carports attached to occupancies in Group R-3. 3. For buildings of other occupancies where migration of moisture through the slab from below will not be detrimental to the intended occupancy of the building. 4. For driveways, walks, patios and other flotwork which will not be enclosed at a later date. 5. Where approved based on local site conditions. PLAN LEGEND ALL CMU WALLS CONSIDERED SHEAR WALL ■ CELL POURED SOLID w/ (I,105 FROM FTG. TO BOND BEAM 054, W/CELL POURED SOLID a 8'-0" O.G. MAX. (STEM WALL) - - CONTROL JOINT (SAW CUT) 100.00' FINISHED FLOOR ELEVATION (ASSUMED DATUM) • TIE MAX BOLTS tv 6'-O" O.G. 4 12" FROM ANY CORNER B WINDOW OR DOOR OPENING LOCATIONS SECTION R318 PROTECTION AGAINST TERP11TE5 R318.1 Termite Protection. Termite protection shall be provided bg registered termiticidee, Including soft applied pesticides, baiting systems, and pesticides applied to wood, or other approved methods of term Re protection labeled for use as a preventative treatment to new construction. See Section 202, REGISTERED TE ITICIDE. Upon completion of the application of the termite protective treatment, a Certificate of Compliance shalt be Issued to the building department by the licensed pest control company that contalns the following statement: • The building has received a complete treatment for the prevention of subterranean termites. Treatment Is In accordance with rules and laws established bg the Florida Department of Agriculture and Consumer Services_ R318.1.1 If Boll treatment is used for subterranean termite prevention, the initial chemical soft treatment inside the foundation perimeter shell be done after all excavation, backfllling and compaction Is complete. R318.12 If soil treatment Is used For subterranean termite prevention, &oil area disturbed after initial chemical soft treatment shell be retreated with a cMmical Boll treatment, including spaces boxed or formed. R318.13 If soil treatment le used for subterranean termite prevention, space in concrete floors boxed out or Formed for the subsequent Installation of plumbing traps, drains or any other purpose shall be created by using plastic or metal permanently placed forms of surrlcient depth to eliminate any planned soil disturbance after Initial cMnmical Boll treatment. R318.1A IF *oil treatment Is used for subterranean termite prevention, chemlcallg treated soft shall be otected with a minimum 6 mil vapor retarder to protect against rainfall dilution. IF rainfall occurs before vapor retarder placement, retreatment is required. Any worm Including placement of reinforcing steel, one after chemical treatment until the concrete floor Is poured, shell be done in such manner as to avoid penetrating or cleturbing treated soft, R318.1b If soil treatment Is used for subterranean termite prevention, concrete overpour or mortar accumulated along the exterior foundation perimeter shall be removed prior to exterior chemical loll treatment to enhance vertical penetration of the chemicals. R318.1.6 If soil treatment Is used for subterranean termite prevention, chemical Boll treatments shell also be applied under all exterior concrete or grade within I foot (305 mm) of the primary structure efdeealle. Also, a vertical chemical barrier shell be applied promptly after construction Is completed, Including Initial landscaping and irrigation/sprinkler installation. Any soil disturbed after the chemical vertical barrier Is applied shall be promptly retreated. R318.1.7 IF a registered termlticlde formulated and registered as a bait system Is used for subterranean termite prevention, Section R318.1.1 through Section R318.Ib do not apply' however, a signed contract assuring the Installation, maintenance and monitoring of the baiting system that Is in compliance with the requirements of Chapter 482, Florida Statutes, shall be provided to the building official prior to the pouring of the slab, and the system must be Installed prior to final building approval. If the baiting system directions for use require a monitoring phase pprrior to installation of the pesticide active Ingredient, the Installation of the monitoring phase components "IT be deemed to constitute Installation of the system. R318.18 If a registered termiticide formulated and registered as a wood treatment Is used for subterranean termlte prevention, Sections R318.1.1 through R318.1.6 do not apply. Application of the wood treatment termlticfde shall be as required by label directions For use, and must be completed prior to final building approval. R3182 Penetration. Protective sleeves around piping penetrating concrete Blab -on -grade floors *hall not be of cellulosecontalning materials. If *all treatment Is used for subterranean termite protection, the sleeve *hall have a maximum wall thickness of 0.010 Inch (025 mm), and be sealed within the slab using a noncorrosive clamping device to eliminate the annular space between the pipe and the sleeve. No termlticldee shall be applied Inside the sleeve. R3183 Cleaning Celle and cavities in masonry unite and air gape between brick. stone or maeorry vereere and the structure shell be cleaned of all nonpreservative-treated or nonnaturally durable wood, or other cellulose -containing material prior to concrete placement. Exception: Inorganic material manufactured for closing cells in foundation concrete masonry unit construction or clean earth fill placed In concrete masonry unit voice below slab level before termite treatment is performed. R318A Concrete bearing ledge. ®rich stone or other veneer shell be supported bg a concrete bearing ledge at least equal to the total thldnese of the bristone or other veneer which le poured Integrally with the concrete foundation. No supplemental concrete foundation pours which will create a hidden cold ,Joint shell be used without supplemental treatment In the Foundation unless there Is an approved physical barrier. An approved physical barrier shall also be Installed rrom below the wall ell[ plate or first block course horizontally to embed In a mortar Joint. If masonry veneer extends below grade, a termite protective treatment must be applied to the cavity created between the veneer and the foundation, In lieu of a physical barrier. Exception: Veneer supported bg a structural member secured to the foundation sldewall in accordance with ACT 530/ASCE 5/T1`16 402, provided at least a 6 Inch (152 mm) clear Inspection space of the Foundation stdewall exterior existe between the veneer and the top of any soil, sod, mulch or other organic landscaping component, deck, apron, porch, walk or any other work immediately adjacent to or adjoining the structure. R3183 Protection against decay and termites. Condensate line, Irrigation/sprinkler system risers for spray heads, and roof downspouts shall discharge at least I foot (305 mm) away fYom the structure eldewall, whether by underground pi Ing, tall extensions or splash blocks. Gutters with downspouts are required on all buildings with eaves of less than 6 Inches (152 mm) horizontal projection except for gable end rakes or on a roof above another roof. R318.6 Preparation of building site and removal of debris. R318A,J All building site* shall be graded to provide drainage under all portlons of the building not occupied by basements. R31862 The foundation and the area encompassed within I foot (305 mm) therein "if have all vegetation, Stumpe, dead roots, cardboard, trash and foreign material removed and the Fill material shall be from of vegetation and foreign material. The fill shall be compacted to assure adequate support of the Foundation. R318b3 After all work Is completed, loose wood and debris shall be completely removed from under the building and within I foot (305 mm) thereof. All wood Forms and supports shall be completely removed. This Includes, but Is not limited to: wooden grade stakes, forms, contraction spacers, tub trap boxes, plumbing supports, bracing, shoring, forms or other cellulose -containing material placed In any location where ouch materials are not clearly visible and readily removable prior to completion or the work Wood shell not be stand In contact with the ground under any building. R318.1 Inspection for tarmftee. In order to provide for Inspection for termite Infestation, clearance between exterior wall coverings and final earth grade on the exterior of a building shell not be lees than 6 Inches (152 mm), Exceptions: I. Paint or decorative cementltious finish lees than 5/5 Inch (11.1 mm) thick adhered directly to the masonry foundation eldewall. 2. Aece&s or vehicle ramps which rise to the Interior finish Floor elevation For the width of such ramps onlyy. 3. A 4-Inch (102 mm) Inspection space above patio and garage slabs and entry areas. 4. If the patio has been soft treated For termites, the finish elevation may match the building Interior finish floor elevations an masonry construction only. 5. Maeonry veneers constructed in accordance with Section R318.4. R318.8 Foam plastic protection. In areas where the probablllty of termite Infestation Is very heavy, as Indicated In %N= R30I2((o), extruded and expanded polystyrene, polyisocyanurate and other foam plastics shall not be Installed on the exterior face or under interior or exterior foundation walls or slab Foundations located below grade. The clearance between foam plastics installed above grade and exposed earth shell be at least 6 Inches (152 mm). Excceepptions: I. BuI dinge where the structural members or walls, floors, callings and roofs are entirely of noncombustible materials or pressure -preservative -treated wood. 2. uhw In addition to the requirements of Section R318.1, an approved method of protecting the foam plastic and structure from subterranean termite damage Is used. 3. On the Interior side of basement walls. ENGINE F�'S NOTES 0.) ALL WORK TO BE DONE ACCORDING TO nth Edition (2020) FBC (Florida Building Code) (2.) ASSUMED SOIL BEARING CAPACITY TO BE 2000 PSF. SOIL CAPACITY TO BE VERIFIED BY CONTRACTOR PRIOR TO CONSTRUCTION. INFORM ENGINEER OF VARIATIONS. FOOTINGS TO BE EXCAVATED TO CLEAN SOIL, FREE OF VEGETATION AND DELETERIOUS MATTER. CONCRETE SHALL BE PLACED ON AN UNDISTURBED BASE. (3.) IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION PROCEDURE AND SEQUENCE TO INSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION. THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION OF WHATEVER TEMPORARY BRACING, GUYS, OR TIE DOWNS THAT MAY BE NECESSARY. SUCH MATERIAL SHALL BE REMOVED AND SHALL REMAIN THE PROPERTY OF THE CONTRACTOR AFTER COMPLETION OF THE PROJECT. (4.) ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE VERIFIED AND SHALL CONFORM TO THE ARCHITECTURAL DRAWINGS. (5.) CONCRETE : MINIMUM COMPRESSIVE CONCRETE STRENGTH TO BE 3000 PSI IN 28 DAYS. ALL CONCRETE SHALL BE READY MIXED" AND IN ACCORDANCE WITH A.S.T.M. SPECIFICATION C-94. ALL CONCRETE MODULAR UNITS SHALL HAVE A COMPRESSIVE STRENGTH OF nOO PSI WITH TYPE M OR S MORTAR, 2000 PSI. (6.) SLAB ON FILL : INTERIOR CONCRETE SLABS POURED ON FILL TO BE POURED OVER WATERPROOF MEMBRANES. ALL SLABS TO BE REINFORCED WITH 6X6 10/10 WELDED WIRE MESH. C1.) LUMBER : 1. STORE LUMBER OFF GROUND, KEEP WELL VENTILATED AND COVERED_ 2. CURRENT EDITION, ASSOCIATION GRADING RULES GOVERN. 3. ALL LUMBER SHALL BEAR GRADE MARK OF AN ASIC BOARD OF REVIEW AGENCY. 4. ANY SPECIES ALLOWED UNLESS OTHERWISE NOTED. 5. SIZES ARE NOMINAL. ACTUAL SIZES SHALL CONFORM TO AMERICAN LUMBEfi£t>gb"tIZVNSS4 IRS 20--10. 6. MOISTURE CONTENT OF LUMBER 2" OR LESS IN THICKNESS SHALL BE 113 OR LESS AT THE TIME OF INSTALLATION. (SJ TERMITE TREATING : SOIL BELOW STRUCTURE TO BE TERMITE TREATED TO A DISTANCE OF 5'-O" BEYOND THE PERIMETER LINES OF THE BUILDING. (cJ.) ALL STEEL SHALL BE 40 KSI WITH A MINIMUM CLEAR COVER OF 3" AGAINST SOIL, AND SHALL HAVE A MINIMUM LAP OF 40 TIMES THE DIAMETER OF THE REBAR (10J 2"X12" HEADERS SHALL BE 2-2"XI2" LAMINATED W/ 1/2" PLYWOOD GLUED W/ CONSTRUCTION ADHESIVE AND NAILED W/ 5-016D COMMONS 16" O.G. TO MEET LOADS AS INDICATED. (11.) ALL FASTENERS SHALL COMPLY WITH THE DESIGN LOADS. (12.) CONTRACTOR SHALL HAVE MANUFACTURERS SPECIFICATIONS (CUT SHEETS) ON SITE AT THE TIME OF INSPECTION, FOR REVIEW BY THE BUILDING INSPECTOR, TO MEET LOADS AS INDICATED. U c Q 0 t_ c V) a) 0 () c 0 V) 0 c 0 U N O N 0 U ry 11 O U Siglicd and seated by'1'.L. I lanson pki „��`•�' I I Illlll//� Thomas L Digitally signed by using a Digital Signature and date. .qt•�.`p Thomas L 1'rinicd copies of this docunienl �p,• a Hanson:A01410 HansoncA01410D00000 ''rr not owideieds:lnedand sealed :uul tLe signature must be ; w D000001 77EF31 177EF3164E000015ADA oilnhy t. , zA verified oaclrrnur Co ' Date: 2021.12.15 0; •., ,,, �" ;�� B4E000015ADA 08:50:00-05'00' %;;' (IN P -1,ll,�ill L I I I I I I I 111 1 1 1 1 1 t I 1 I I _ II - '- .- SHINGLES PER SPECIFICATIONS (w/ 6 FASTENERS WALL CONSTRUCTION PER SHINGLE) FELT UNDERLAYMENT MUST BE 300 FLORIDA BUILDING CODE - RESIDENTIAL 6th EDITION 2017 SECTION R609 OR EQUIVALENT (ASTM D 22(o TYPE II, ASTM D486e EXTERIOR WNDOWS AND DOORS R609. 1 General. OR PEEL AND STICK ROOF UNDERLAYMEN-r O'',I 1/2" This section prescribes performance and construction requirements for exterior windows and doors installed in walls. Windows and doors shall be PLYWOOD OR OSB W/H-CLIPS ON FIRE installed and flashed in accordance with the fenestration manufacturer s written instructions. Window and door openings shall be flashed in -ENGINEERED accordance with Section R703.4. Written installation instructions shall be provided by the fenestration manufacturer for each window or door. 8"X 8"X 16" C.M.U. WOOD TRUSSES Q 24"O.C. (FOR NAILING SCHEDULE R609.2 Performance. SEE SHEET 52C) - SEE ADDITIONAL INFO BELOW Exterior windows and doors shall be designed to resist the design wind loads specified in Table R301.2(2) adjusted for height and exposure in accordance with Table R301.2(3) or determined in accordance with ASCE 7 using the allowable stress design load combinations of ASCE 7. Design wind BRICK MOULD HURRICANE ANCHORS loads for exterior glazing not part of a labeled assembly shall be permitted to be determined in accordance with Chapter 24 of the Florida Building Code, Building. (SEE ROOF PLAN ) R609. 2. 1Custom doors. DOORFRAME MIN. lx2 NAILING STRIPS ATTACH SOFFIT TO STRIPS PER Custom (one-of-o-kind) exterior door assemblies shall be tested by an approved testing laboratory or be designed and engineered in accordance with MANUFACTURERS PRODUCT APPROVAL SPECIFICATIONS R104.2.1 accepted engineering practices by a Florida registered design professional. Signed and sealed copies of the rational analysis and calculations shall be provided to the building official upon permit application. ALUM. DRIP EDGE R609.3 Testing and labeling. u u 3/16 x 2-I/2 TAPCON Exterior windows and slidingdoors shall be tested b an approved independent laboratory,and bear a label identifying manufacturer, performance y pP p y 9 2 X6 SUB FASCIA characteristics and approved inspection agency to indicate compliance with AAMA/WDMA/GSA 101/1.5.2/A440 or TAS 202 (HVHZ shall comply with TAS 202 FASTENERS INTO BLOCK and ASTM E1300). Exterior side -hinged doors shall be tested and labeled as conforming to AAMA/WDMA/CSA 101/I.S.2/A440 or ANSI/WMA 100, or comply 10 I(p" O.G. 1 with Section R609.5. Exterior windows and doors shall be labeled with a permanent label, marking, or etching providing traceability to the FASCIA COVER INSTALLED IN 7 manufacturer and product. The following shall also be required either on o permanent label or on a temporary supplemental label applied b the p 9 q p p y pp aP y ACCORDANCE WITH FASCIA information identifyingthe man t h product m manufacturer: t manufacturer, the p odu oriel/series number, positive and negative design pressure rating, product , J - GH ANNE L maximum size tested, impact -resistance rating if applicable, Florida product approval number or Miami -Dade product approval number, applicable test MANUFACTURERS PRODUCT standard(s), and approved product certification agency, testing laboratory, evaluation entity or Miami -Dade product approval. 3/4" FURRING NAILED APPROVAL SPECIFICATION AND VINYL SOFFIT The labels are limited to one design pressure rating per reference standard. The temporary supplemental label shall remain on the window or door TO BLOCK ID8" O.C. (2) LIMITATIONS OF USE until final approval by the building official. REQUIRED EACH LIFT Exceptions: Sty.. Cod.. DOOR DOORS ATTACH SOFFIT TO FASCIA OR 1.Door assemblies installed in nonhabitable areas where the door assembly and area are designed to accept water infiltration need not be tested for TO NAILING water infiltration. 8"X 8"x 1(0" G.M.U. STRIP (NOT 2. Door assemblies installed where the overhang (OH) ratio is equal to or more than 1 need not be tested for water infiltration. The overhang ratio SHOWN) MAY VARY shall be calculated by the following equation: 3/16" X 1-3/4" TAPCON FASTENERS (IF OVER 12" - OH ratio = OH Length/OH Height INTO CONCRETE BLOCK INTERMIDIATE Where: TEXTURED STUCCO OVEOaRfF3 REQ. OH length = The horizontal measure of how for an overhang over a door projects out from door surface. OH height = The vertical measure of the distance from the door si11 to the bottom of the overhang over a door. ADHESIVE 5EALENT BOTH SURFACES OR PRIOR TO ATTACHING BUCK TO CONC. BLK• 3. Decorative glazed openings. EXTERIOR SIDING OVER 1 X 2 P.T. FURRING 16 " O.C. 4.Poss-through windows for serving from a single-family kitchen, where protected by a roof overhang of 5 feet (1.5 m) or more shall be exempted from the requirements of the water infiltration test. 1/2" DRYWALL R609.3. 1Comparative analysis. Structural wind load design pressures for window and door units different than the size tested in accordance with Section R609.3 shall be permitted to be different than the design value of the tested unit where determined in accordance with one of the following comparative analysis methods: 1.Structural wind load design pressures for window and door units other than the size tested in accordance with Section R609.3 shall be permitted to be different than the design value of the tested unit provided such different pressures are determined by accepted engineering analysis. All components of the alternate size assembly shall be the some as the tested or labeled assembly: however, lineal components shall be permitted to vary in length compared to the tested or labeled assembly. Exceptions: 5"x I" SELF THREADING PHILLIPS FLAT HEAD 1.0perable windows and doors rated in this manner shall comply with the following: a. For windows and doors (other than sliding or bi-fold), the frame area of the alternate size unit shall not exceed the frame area of the tested CADMINUM PLATE SGREW5 24" O.G. MAX. *5 DWL. a roved unit. WITHIN 4u OF CORNER w/ 10n Z b.For sliding or bi-fold doors, the panel area of the alternate size unit shall not exceed the panel area of the tested approved unit. a c.Shall vary from the tested approved unit only in width, height or load requirements. STD. HOOK lU d.Shal1 not exceed 100 percent of the proportional deflection for fiber stress of the intermediate members of the approved unit. e.Shall not exceed 100 percent of the concentrated load at the juncture of the intermediate members and the frame of the approved unit. f.Shall not exceed the air and water infiltration resistance of the tested approved unit. - -A Z g.Shall not exceed the maximum cyclic pressure of the tested approved unit when tested per TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where ►) -4applicable. 3/I6"x 1-3/4" TAPCON FASTENERS N 2.Nonoperable windows and doors rated in this manner shall comply with the following: INTO CONCRETE BLOCKS 3 3 a. The frame area of the alternate size unit shall not exceed the frame area of the tested approved unit. CAULKING b.Shall vary from the tested approved unit only in width, height or load requirements. c.The maximum uniform load distribution (ULD) of any side shall be equal to the uniform load carried by the side divided by the length of the side. (1) 2 0 '- 0" *5 RE BAR TIED TO d.The ULD of any member shall not exceed the ULD of the corresponding member of the tested approved unit. MARBLE STOOL Z FTC. STEEL AND GRND. ROD e. The ULD of each member shall be calculated in accordance with standard engineering onalysis. f. Shall not exceed the air and water Infiltration resistance of the tested approved unit. (BY OTHERS) AT ELECTRICAL _ g.Shall not exceed the maximum cyclic pressure of the tested approved unit when tested per TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where BOX LOCATION N 1/2" DRYWALL ON Ix 3 P.T. 3. In accordance with WDMA 1. s. 11. 3. In accordance FURRING tv 16" O_C. (2)05 REBAR CONT. R609. 4 Garage doors. Garage doors shall be tested for determination of structural performance under uniform static air pressure difference in accordance with ANSI/DASMA (3" MIN. COVER) 108, ASTM E330 Procedure A, or TAS 202. For garage doors tested in accordance with ASTM E330, acceptance criteria shall be in accordance with ANSI/DASMA 108. (HVHZ shall comply with TAS 202.) Design pressures shall be determined from Table 301.2(4) or ASCE 7. The design pressures, as GROUND ROD (BY OTHERS) determined from ASCE 7, are permitted to be multiplied by 0.6. PRECAST SILL R609.4. 1 Garage door labeling. SEE ELEVATIONS FOR ROOF SLOPE I_ L OPTIONAL 1/2" CD OR 5/8" DRYWALL ON CEILING TOP COURSE 8"X 8" X 16" CONC. "U" BLOCK FILLED W/GONG. RE-INF. W/1 *5 REBAR CONT. AT EACH CORNER 4 'a SPACING SHOWN ON FOUNDATION PLAN, POUR 4 FILL BLK. CELL VERTICALLY W/1 *5 REBAR CONT. TIED TO TOP COURSE REBAR 4 TO STEEL IN FTG. (OPTIONAL) . 1/2" GYPSUM DRYWALL OVER 3/4" P.T. FURRING (ON IN5UL.) 11 16" O.C. 8 X 8 X 1(o CONCRETE BLOCKS W/ HORIZONTAL LADDER RE-INF. a 16" O.C. IN SHEAR PANELS PANEL EDGE SUPPORT FOR NARROW WIDTH ROOF 5HEATHING" PER TECHNICAL NOTE *R215A 16-24 'I -DOUBLE PLY CLIP THE SIDE ADJACENT TO THE FULL WIDTH PANEL - NONE REQUIRED AT RIDGE OR HIP. 12" TO 16" - LUMBER ONLY BLOCKING (2x4) FLAT WISE OR ENDWISE ON THE 51DE ADJACENT TO THE FULL WIDTH PANEL NONE REQUIRED AT RIDGE OR HIP. FOR PLYWOOD SHEATHING 12" OR LE55 - LUMBER ONLY BLOCKING, (2x4) FLAT WISE OR EDGEWISE ON BOTH PANEL EDGES_ TOP COURSE ' 5"X5"X16" CONC. K.O. BLOCK W/ `�_• POURED CONC. 4 :: , 1-*5 REBAR CONT. PRECAST CONC. LINTEL or POWERS STEEL LINTEL W/ *5 POURED SOLID .IM. WINDOW RBLE SILL ECA5T CONC. SILL OOD BASE 1 (1) 20'-0" 05 REBAR TIED TO FTG. STEEL AND GRND. ROD (BY OTHERS) AT ELECTRICAL r 000 PSI GONG."x 6"x 10/10 E.W.W. MESH REINFORCING REQUIREDHROUGHOUT THE CONCRETE SLAB OR FIBER MESHER SECTION 11311.2, 2010 FLORIDA BUILDING CODE. Garage doors shall be labeled with a permanent label provided by the garage door manufacturer. The label shall identify the garage door S ax 8 "x 16" C.M.U. 0 I manufacturer, the garage door model/series number, the positive and negative design pressure rating, indicate impact rated if applicable, the �� I CALM WA installation instruction drawing reference number, the Florida product approval or Miami -Dade product approval number if applicable, and the applicable test standards. The required garage door components for an approved garage door assembly may be indicated using a checklist form on the label. If a checklist format is used on the label, the door installer or the garage door manufacturer shall mark the selected components on the checklist that are required to assemble an approved garage door system. The installation instructions shall be provided and available on the job site. t-, I I CURB DET41 roXio-010 WWF OR FIBER MESH 1.50/GU. YD. J HEADER BLOCK W/*54, NOTE: IF WALL HEIGTH EXCEEDS 2'-011 BRACE WALL UNTIL FLOOR 15 POURED * O W/CELL POURED SOLID 9 V-fd" O.C. MAX. "50 DOWEL SPACING PER FOUNDATION PLAN 1 6 MIL. VAP. BARRIER t j � I S I 1611 � I I OI �lY GROUND ROD (BY OTHERS) II 2-*50 J_ OPTION4L (STErl WALL) III * I1 I CONCRETE -ENCASED ELECTRODE. AN ELECTRODE ENCASED BY AT LEAST 2" OF CONCRETE, R609.5 other exterior window and door assemblies. WINDOWS LOCATED WITHIN AND NEAR THE BOTTOM OF THE CONCRETE FOUNDATION OR FOOTING THAT IS IN Exterior windows and door assemblies not included within the scope of Section R609.3 or R609.4 shall be tested in accordance with ASTM E330. Glass in assemblies covered by this exception shall comply with Section R308.5. DIRECT CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZING R609.6 Wind-borne debris protection. �00� ' I II��OI I I ATTACHMENT ���I�� GALVANIZED OR OTHER ELECTRICITY CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS Protection of exterior glazed openings in buildings located in wind-borne debris regions shall be in accordance with Section R301.2. 1.2. WINDOW OF NOT LESS THAN 1/2 INCH DIAMETER, OR CONSISTING OF AT LEAST 20 FEET OF BARE COPPER R609.6. 1 Fenestration testing and labeling. CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED Fenestration shall be tested by an approved independent laboratory, listed by an approved entity, and bear a label identifying manufacturer, TOGETHER BY THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS." performance characteristics, and approved inspection agency to indicate compliance with the requirements of the following specificotion( s) 1.ASTM E1886 and ASTM E1996; or FILLED CELL (3) 1/2"x 8" "J" BOLTS OR 2. AAMA 506. w/ (1) * 5 VERT. HILTI DN50 (OR EQUAL) R609.7 Anchorage methods. The methods cited in this section apply only to anchorage of window and glass door assemblies to the main force -resisting system. CONT. WOOD TRIM R609.7.1 Anchoring requirements. Window and glass door assemblies shall be anchored in accordance with the published manufacturer s recommendations to achieve the design pressure �! specified. Substitute anchoring systems used for substrates not specified by the fenestration manufacturer shall provide equal or greater anchoring performance as demonstrated by accepted engineering practice. R609.7.2 Anchorage details. Products shall be anchored in accordance with the minimum requirements illustrated in Figures R609.7.2(1), R609.7.2(2), R609.7.2(3), R609.7.2(4), R609. 7. 2( 5) R609. 7. 2(6) R609. 7. 2( 7) and R609. 7. 2( 8) . 2X 6 P.T. WOOD JAMB , R609.7.2. 1 Masonry, concrete or other structural substrate. LDOOR AND CONNECTION Where the wood shim or buck thickness is less than 11/2 inches (38 mm), window and glass door assemblies shall be anchored through the jamb, or by PER jamb clip and anchors shall be embedded directly Into the masonry, concrete or other substantial substrate material. Anchors shall adequately GARAGE DOOR MANUFACTURER transfer load from the window or door frame into the rough opening substrate [see Figures R609.7.2(1) and R6097,2(2)]. Where the wood shim or buck thickness is 11in inches mm) more, the buck is securely fastened to the masonry, concrete other substantial I� he be substrate, and the buck extends beyond the interior face of the window or door frame, window and glass door assemblies shall be anchored through ace �� I� O �� E. the jamb, or by jamb clip, or through the flange to the secured wood buck. Anchors shall be embedded into the secured wood buck to adequately I . transfer load from the window or door frame assembly [see Figures R609.7.2(3), R6097.2(4) and R609.7.2(5)]. R609.7.2.2 Wood or other approved framing material. Where the framing material is wood or other approved framing material, window and glass door assemblies shall be anchored through the frame, or by frame clip, or through the flange. Anchors shall be embedded into the frame construction to adequotely transfer load [see F I gures R609.7.2(6), R609. 7. 2( 7) and R609. 7. 2( 8) ] . R609.8 Mullions. Mullions shall be tested by an approved testing laboratory in accordance with AAMA 450, or be engineered in accordance with accepted engineering practice. Mullions tested as stand-alone units or qualified by engineering shall use performance criteria cited in Sections R609.8.1, R609.8.2 and R609.8.3. Mullions qualified by on actual test of an entire assembly shall comply with Sections R609.8. 1 and R609.8.3. R609.8. 1 Load transfer. Mullions shall be designed to transfer the design pressure loads applied by the window and door assemblies to the rough opening substrate. R609.8.2 Deflection. Mullions shall be capable of resisting the design pressure loads applied by the window and door assemblies to be supported without deflecting more than L/175, for spans up to and including 13 foot 6 inches, and L/240 + 1/4 inch for spans over 13 foot 6 inches, where L is the span of the mullion in inches. R609.8.3 Structural safety factor. Mullions shall be capable of resisting a load of 1.5 times the design pressure loads applied by the window and door assemblies to be supported without exceeding the appropriate material stress levels. If tested by an approved laboratory, the 1.5 times the design pressure load shall be sustained for 10 seconds, and the permanent deformation shall not exceed 0.4 percent of the mullion span after the 1.5 times design pressure load is removed. R609.9 Masonry rough openings. Masonry rough opening dimensions shall be within the tolerances specified in Section R606.3.1.1 and, in addition, shall provide for a window perimeter sealant joint a maximum of 1/4 inch (6.4 mm) in width. R609. 10 Door components. Substitution of door components shall comply with either: 1. ANSI /WMA 100; or 2.Be evaluated by an approved product evaluation entity, certification agency, testing laboratory, or engineer and may be interchangeable in exterior door assemblies if the components provide equal or greater structural performance as demonstrated by accepted engineering practices. R609.11 Impact -resistant coverings. R609. 11. 1 Impact -resistant coverings shall be tested at 1.5 times the design pressure (positive or negative) expressed in pounds per square feet as determined by the Florida Building Code, Building Section 1609 for which the specimen is to be tested. The design pressures, as determined from Section 1609 of the Florida Building Code, Building or ASCE 7, are permitted to be multiplied by 0.6. R609. 11. 1. 1 Impact -resistant coverings shall be labeled in accordance with the provisions of Section R609.11. R609.11.2Labels. A permanent label shall be provided by the product approval holder on all impact -resistant coverings. R609. 11. 2. 1 The following information shall be included on the labels on impact -resistant coverings: 1.Product approval holder name and address. 2.All applicable methods of approval. Methods of approval include, but, are not limited to Miami Dade NOA; Florida Building Commission, TDI Product Evaluation; ICC-ES. 3.The test standard or standards specified in Section R301.2.1.2, including standards referenced within the test standards specified in Section R301.2. 1.2 used to demonstrate code compliance. 4.For products with a Florida product approval number or a Miami -Dade County Building and Neighborhood Compliance Department Notice of Acceptance Number (NOA), such numbers shall be included on the label. R609. 11.31_ocation of label. The location of the label on the impact -resistant covering shall be as follows: 1.Accordions: Bottom of the locking bar or center mate facing the exterior or outside. 2.Rollup: On the bottom of the hood facing the exterior or outside or on the bottom slat facing the exterior or outside. 3.Bahama Awning or Colonial Hinged: On the bottom, placed on the back of the shutter. 4.Ponels: For metal and plastic panels the label may be embossed or printed spaced not more than every 3 lineal feet (914 mm) on each panel. The label shall be applied by the holder of the product approval and shall face the exterior or outside. 5.Fromed products: The label shall be on the side or bottom facing the exterior or outside. 6.1-abels on all other products shall face the exterior or outside. R609. 11. 4 Installation. All impact -resistant coverings shall be installed in accordance with the manufacturer s installation instructions and in accordance with the product approval. Installation instructions shall be provided and shall be available to inspection personnel on the job site. Opening protection components, fasteners, and o'_her parts evaluated by an approved product evaluation entity, certification agency, testing laboratory, architect, or engineer and approved by the holder of the product approval may be interchangeable in opening protection assemblies provided that the opening protection components) provide equal or greater structural performance and durability as demonstrated by testing in accordance with approved test standards. C C C C F C C C C C Thomas L Digitally signed by s1, d at„l sealcrn,y r 1. I I,uson PF ` t' i usw1; a Digital tiignahue sari dale. :. �r,,`u ,a-.x • U,t �J Thomas L Panted euptes of this document m Hanson:A01410 Hanson:A01410D00000 arc notusideiedsignedand D00000177EF31 1 77EF31134E00001 SADA sealed and the sig"°`are Must be jA ;'w verified on any electronic co Date: 2021.12.15 B4E000015ADA koe •X�;`+ 08:50:22-05-00' .. I I I I 1 11 I !. 11111 111111 I'll fill 11 r'1 1 11 11I1. : _ I I I III I I I tl 1 1 1 I 111 I"dm7S!1JILH !!.' .Lill I Y Q � H Z 73 PROVIDE MINIMUM 16" 2(o GA VALLEY FLASHING AT ALL ROOF CHANGES AND SIDE WALL AREAS PER FBC 10-1.2.5 /R103.1.5. -103.8., 903.2 AND 1305 PLACE ROOF CEMENT COATING-,: AT ROOF DECKS EDGES OF FLASHING AND ALL LAPS. NAIL FLASHING WITH 1 1/2" ROOF NAILS 12" OC Frame Wall SILL A H UNIT DIMI=NSION WIDTH JAMB / ° 0 0 0 ° ° ° 0 0 ° ° ° 0 0 SIDE WALLS OR CHIMN MINIMUM S"XS" 26 GA ANGLE OR STEP FLASHING, SEE N01 ROOF DECK AT SIDE WALLS t-, ' I TYP. ROOF FLASHI WINDOW < DOOR FASTENING 2011 Florida Building Coda NOTES 1. ALL EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH ANSI/AMMAJNWWDA 1CM62 STANDARD AND BEAR AN AMMA OR WDMA LABEL INDICATING, MANUFACTURERS PERFORMANCE AND APPROVED PRODUCT TESTING ENTITY, IN ACCORDANCE WITH 2O11 Florida Building Coda, SECTION 1101A2.1. 2. ALL EXTERIOR DOORS AND WINDOWS, SHALL BE ANCHORED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS, IN ACCORDANCE WITH 2O11 FLORIDA BUILDING CODE 1101.4.1. 3. WINDOWS AND DOORS FASTENED TO BUCK STRIPS LESS THAN 1 1/2" SHALL BE ANCHORED THROUGH THE JAME TO THE STRUCTURAL SUBSTRATE, IN ACCORDANCE WITH 2O11 Florida Building Coda. 1101AA.2 4. WINDOW AND DOOR MULLION ASSEMBLIES SHALL BE DESIGNED AND TESTED TO TRANSFER 15 TIMES THE INDICATED DESIGN LOADS, TO THE STRUCTURAL SUBSTRATE IN ACCORDANCE WITH, 2011 Florida Building Code 1101A5.1 AND 1101A5.4. ATTACHMENT OF WINDOW TO FRAME WALL TO BE PER MANUFACTURERS RECOMMENDATION. DEOrAl ALL WIDT DOOR ANCHOR4arm (FR4MV REBAFP, IDETAIL TABLE R301. 5 MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS (in pounds per square foot) USE LIVE LOAD Uninhabitable attics without storage b,g 10 Uninhabitable attics with limited storage b,g 20 Habitable attics and attics served with fixed stairs 30 Balconies (exterior) and decks e 40 Fire escapes 40 Guardrails and handrails d 200h Guardrail in —fill components f 50h Passenger vehicle garages a 50a Rooms other than sleeping room 40 Sleeping rooms 30 Stairs 40c For SI: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N. a. Elevated garage floors shall be capable of supporting a 2,000—pound load applied over a 20—square—inch area. b. Uninhabitable attics without storage are those where the maximum clear height between joists and rafters is less than 42 inches, or where there are not two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches high by 24 inches in width, or greater, within the plane of the trusses. This live load need not be assumed to act concurrently with any other live load requirements. c. Individual stair treads shall be designed for the uniformly distributed live load or a 300 —pound concentrated load acting over an area of 4 square inches, whichever produces the greater stresses. d. A single concentrated load applied in any direction at any point along the top. e. See Section R502.2 for decks attached to exterior walls. f. Guard in —fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement. g. Uninhabitable attics with limited storage are those where the maximum clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are me t : 1. The attic area is accessible from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is a minimum of 30 inches. 2. The slopes of the joists or truss bottom chords are no greater than 2 inches vertical to 12 units horizontal. 3. Required insulation depth is less than the joist or truss bottom chord member depth. The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 lb/ft2. h. Glazing used in handrail assemblies and guards shall be designed with a safety factor of 4. The safety factor shall be applied to each of the concentrated loads applied to the top of the rail, and to the load on the in —fill components. These loads shall be determined independent of one another, and loads are assumed not to occur with any other live load. c C c C c a c C C Signed and scaled by1'.1 1lansolsPE •••;t',lunl Thomas L Digitally signed by using a I ligital Signature and date, Thomas L Printed n,pic:. ul Ill is dorunsenl r> Hanson:AO1410 Hanson:A01410D00000 ""'""`"""'de"`1slgned '" ;✓�` sealed awl Ibe slgualure mull be : w D00000177EF31 177EF31B4E000015ADA y sn :u vc•ndied uu:ui cicitruui: m . -. Date: 2021.12.15 B4E000015ADA 08:50:46-05'00' I I I I I I I 1 TABLE 2304. 10. 1 FASTENING SCHEDULE R502.5 Allowable girder spans. The allowable spans of girders fabricated of dimension lumber shall not exceed the values set forth in Tables R502. 5( 1) and R502. 5(2). TABLE R502. 5( 1) GIRDER SPANSo AND HEADER SPANSa FOR EXTERIOR BEARING WALLS (Maximum spans for Douglas fir -larch, hem -fir, southern pine and spruce-pine-firb and required number of jack studs) GIRDERS AND HEADERS SUPPORTING SIZE Building widths (feet) 20 28 36 SPAN Njd SPAN Njd SPAN NJ Roof and ceiling 2-2x4 1 3-6 1 3-2 1 2-10 1 2-2x6 5-5 1 4-8 1 4-2 1 2-2x8 6-10 1 5-11 2 5-4 2 2-2x10 8-5 2 7-3 1 2 6-6 2 2-2x 12 9-9 2 8-5 2 7-6 2 3-2x8 8-4 1 7-5 1 6-8 1 3-2x10 10-6 1 9-1 2 8-2 2 3-2x12 12-2 2 10-7 2 9-5 2 4-2x8 9-2 1 8-4 1 7-8 2 4-2x10 11-8 1 10-6 1 9-5 2 4-2x12 14-1 1 12-2 2 10-11 2 Roof, ceiling and one center -bearing floor 2-2x4 3-1 1 2-9 1 2-5 1 2-2x6 1 4-6 1 4-0 1 1 3-7 2 2-2x8 5-9 2 5-0 2 4-6 2 2-2x10 7-0 2 6-2 2 5-6 2 2-2x12 8-1 2 7-1 2 6-5 2 3-2x8 7-2 1 6-3 2 5-8 2 3-2x10 8-9 2 7-8 2 6-11 2 3-2x12 10-2 2 8-11 2 8-0 2 4-2x8 8-1 1 7-3 1 6-7 2 4-2x10 10-1 1 8-10 2 8-0 2 4-2x12 11-9 2 10-3 2 9-3 2 Roof, ceiling and one clear span floor 2-2x4 2-8 1 2-3 1 2-0 1 2-2x6 3-11 2 3-3 2 2-11 2 2-2x8 5-0 2 4-2 3 3-9 2 2-2x10 6-1 2 5-1 3 4-7 3 2-2x12 7-1 3 5-10 3 5-3 3 3-2x8 6-3 2 5-2 2 4-8 2 3-2x10 7-7 2 6-4 2 5-8 2 3-2x12 8-10 2 7-4 3 6-7 2 4-2x8 7-2 1 6-0 2 5-5 2 4-2x10 8-9 2 7-4 2 6-7 2 4-2x12 10-2 2 8-6 2 7-8 2 Roof, ceiling and two center -bearing floors 2-2x4 2-7 1 2-3 1 2-0 1 2-2x6 3-9 2 3-3 2 2-11 2 2-2x8 4-9 2 4-2 2 3-9 2 2-2x10 5-9 2 5-1 2 4-7 3 2-2x12 6-8 2 5-10 3 5-3 3 3-2x8 5-11 2 5-2 2 4-8 2 3-2x10 7-3 2 6-4 2 5-8 2 3-2x12 8-5 2 7-4 2 6-7 2 4-2x8 6-10 1 6-0 2 5-5 2 4-2x10 8-4 2 7-4 1 2 6-7 2 4-2x12 9-8 2 8-6 2 7-8 2 Roof, ceiling and two clear span floor 2-2x4 1 2-1 1 1-8 1 1-6 2 2-2x6 3-1 2 2-8 2 2-4 2 2-2x8 3-10 2 3-4 2 3-0 3 2-2x10 4-9 2 4-1 3 3-8 3 2-2x12 5-6 2 4-9 3 4-3 3 3-2x8 1 4-10 2 4-2 2 3-9 2 3-2x10 5-11 2 5-1 2 4-7 2 3-2x12 6-10 2 5-11 3 5-4 2 4-2x8 5-7 2 4-10 2 4-4 2 4-2x10 6-10 1 2 1 5-11 1 2 1 5-3 1 2 4-2x12 7-11 1 2 1 6-10 1 2 1 6-2 1 3 For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m2. a. Spans are given in feet and inches. b. Tabulated values assume #2 grade lumber. c. Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated. Cl. NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the header is permitted to be supported by an approved framing anchor attached to the full -height wall stud and to the header. e. Reserved. z�irmi■��r� '7 V1C '41 M=IIVr-C./I111.i11`ltz PHIS. #3 #4 1,..04f= SQL i C� 25" MIN. LAP --S REINFORCING BAR # LAP SPL I SE 3io" MIN_ LAP `IO l�>=IIVr Vl�I..IIv[� PHIS #6 LAP SQL 1 Cr A2" MIN I dP #i L4f= SPLICE. 1011 05 REINFORCING BAR St0_ 'BOO COLLAR TIE 1X6 (MIN.) EVFRi' OTHER RAFTER T-0" OR LONGER 2'-011 O PILASTER 16 MAX. ■ II ^ II �O O� 00 ■O O• � •O O.00 ■O O■ VERTICO4L SCHE=uL r�14SoNR�- 8' PLATE HEIGHT = 8'-0" O.C. 10' PLATE HEIGHT = ro'-O" O.C. 12' PLATE HEIGHT = 4'-0" O.G. "A" 14' PLATE HEIGHT = 2'-0" O.C. MAX. / PILASTERS 10 10'-0" O.C. AT EACH CORNER 4 BOTH 51DES OF DOORS 4 WINDOWS OPENINGS (OVER 5'-0"). BEFORE 4 AFTER SHEARWALL SEGMENTS, 4 (2) BARS -1 EA. 51DE OF OPENING OVER i2'-O" 10 BAR LAP DIST F_ T_ T - - - i0oftwNI� BLOCKING BELOW RIDGE 25" MIN. LAP ROOF SHEATHING FASTENING SCHEDULE a js,,c d e 5d Common (0.13I x 2-1/2 Inches) or Ring -Shank (0.135 X 2-1/2 inches) (Except Uklere Noted) for Exposure 5, Enclosed 6ulldings, Roof Framing Spaced 24 Incise o.c. or Lose Roof Fastening Zone Overhang Wind Main Sheathing -to -Gable (eaves) Velocity Roof End -Wall Framinge (3-Second Panel 1 2 3 2 3 2 3 Gust) Location Fastening Schedule (Inches on center) Supported Panel 6 6 6 6 6 150 mph f'g and and edges 3h Panel field 6 4 3 4 3 Supported Panel 120 mph f19 and and edges ro 6 6 6 6 3 Panel field 12 6 4 6 4 Supported Panel 90 mph and and edges ro 6 6 6 6 6 Panel field 12 12 6 6 6 a. Specific gravity (Cs) of lumber and panels shall be 0.42 or greater. b. For Exposure 5 and a 2-foot overhang. C. For median roof height 35 feet or less. d. Gable wall height of 5 feet or less from top floor ceiling to roof peak e. Provide adequate uplift hardware at truss -to -wall connections. Such connections are beyond the scope of this publication. f. When wind speed is 110 mph or greater and when median roof height Is between 25 and 35 feet, use Sd ring shank nails (0.135 x 2-1/2 Inchesaulthln 45 inches of gable and walls. (IRC Table R6023, footnote f) g. When wind speed i6 100 mph or greater, block panel edges perpendicular to gable -and -wall framing members In the first two baya of framing. Blocking shall be spaced a maximum of 4 feet oc. (Wood Frame Construction Manual, Section 3B.5) h. 10d ring -shank nails (0.14Sx 3 Inches). 1. Blocking not required. ROOF FASTENING ZONES FOR WIND UPLIFT Zones 1,2 and 3 shown below indicate areas of the roof that may have different fastening requirements. GABLE END WALL 3 OVERHANG -1 WALL LINE 3 OVERHANG }}. I I :::: a I t L I L I l I: I 2 1 1 1 2. J o Il: If.I I I I. . '.'..' ..'..'I L ..1.... 3; 3::3 _ 2 X \ WALL LINE A 3 OVERHANG - ` 1 -3 OVERHANG -� U 3 OVERHANG WALL LINE G" ABLE END WALL Distance a-4 ft. In most cases (10q of least building width or OA times building height, whichever is smaller, but not less than either 4% of least building width or 3 ft.) ROOF 1 l AFHRf4M SAILING SCHEDULE (GABLES) 2Xro VERTICAL SCAB OR KNEEWALL MID -POINT IN RAFTER W1 RAFTER SPAN LENGTH GREATER THAN 14 FT OR LONGER. CONN W1 4-10d NAILS AT TOP 4 HURRICANE CLIP af BOTTOM. 2Xro (MIN.) NO. 2 YP VALLEY FRAMINGSIMPSON LSTA12 ITYP. SIM(OfR EQUAL) 2X8 NO. 2 5PF r PLYWOOD SHEATHING RIDGE BOARD CONY VA (1) 05 DOWEL I I I I I IN CORNER (4) 10d e RIDGE BOARD END TRUSSES BELOW SHEATHED PRIOR TO VALLEY FRAMING INSTALLATION OR ro'-0" O.G. TOP CHORD 51MP5ON L5TA12 STRAP OR SIMP50N A22 TIE e EA. RAFTER W1 10-10d NAILS (T''P.) 2Xro CONT. W/SLEEPER, CLIPPED OR STRAPPED TO TRUSS BELOW Y ;:fR,4rV11NCX DrMorAl 25" MIN. LAP � I II I II (1) 05 DOWEL IN CORNER CORNER CONT IN i TY 4 WAL.L R INFORC 1"i NT FOOTING 4 StV(WALL RE INFORCEt*1ENt DESCRIPTION OF BUILDING ELEMENTS NUMBER AND TYPE OF FASTENER SPACING AND LOCATION Roof 3-8d common 2x x 0. 131, or 3-10d box ( 3 0. 128. ) ; or 1. Blocking between calling joists, rafters or trusses to top 3-3" x 0.131"naiIs; or plate or other framing below 3-3" 14 gage staples, its"crown Each end, toenail 2-8d common (2j" X 0. 131") 2-3" x 0.131" nails Each end, toenail Blocking between rafters or truss not at the wall top plate, 2-3" 14 gage staples to rafter or truss 2-16 d common 3 x 0.162") 3-3" x 0.131" nails End nail 3-3" 14 gage staples 16d common ( 3J" X 0. 162") 0 6" a. c. 3"x 0.131" nails 0 6" o.c. Face nail Flat blocking to truss and web filler 3" 14 gage staples 0 6"o.c. 3-8d common �2j" X 0.131")or 3-10d box (3 x 0.128")or Each joist, toenail 2. Ceiling joists to top plate 3-3" 0.131" nails; or 3-3" 14 gage staples crown 3. Ceiling joist not attached to parallel rafter, 3-I6d common (2j" X 0.131")or 4-I0d box (3" x 0.128")or laps over partitions (no thrust) Each hind) toenail (see Section 2308.2)3.1, Table 2308.7.3.1) 4-3"x 0. 131" nails; or 4-3" 14 gage staples, 1j" crown 4. Ceiling joist attached to parallel rafter (heel joint) (see Per $ebt6o830807.2.1 Face nail 6ett&on2208172).1, Table 2308.7.3.1 Per Table 2308.7.3.1 3-10d common 3" X 0. 148 ; or 5. Collar tie to rafter 4-10d box (3" x 0.128");or 5. Collar tie to rafter 4-3" 0.131" nails; or Face nail 4-3" 14 gage staples, ?g" crown 3-10d common( 3 X 0. 148") ; or 6. Rafter or roof truss to top plate 4-10d box (3" x 0.128");or Sagostatlon 2001.0uss to top plate 4-3" 0. 131' nails; or Ifoeea&&cil See Section 2308.7.5, Table 2308.7.5) 4-3" 14 gage staples, �" crown 2-I6d common 3 1/2" X 0. 162;or 3-1Od box ( 3" x 0. 128" ); or 3-3" 0.131" nails; or End nail 7. Roof rafters to ridge valley or hip rafters; or roof 3-3" 14 gage stap Ias, is" crown; or End nail 7of%oftoof6inshtoidtdgbeeml ley or hip rafters; or roof 3-]OB Oommon 3 ! 4Z"t)• 14i8 ; or rafter to 2-Inch ridge beam 8-168 BOX (3 1/2' x00.1855));or 4-100 BOX (3"x•01388J);oior Toenail 4-3" x xQ 131°i ti®nnsr„• or 4-3" 14 qaqe staples, "WTMWn I6d common 3 1 2" X 0.162" 24"o.c. face nail 8. Stud to stud (not at braced wall panels) common ;or 8. Stud to stud (not at braced wall panels) 3"x 0.131" nails; or 16"0. c. face mall 3-3" 14 gage staples, crown 9. Stud to stud and abutting studs at intersecting wall 16d common 3 1/2- X 0.162" I6"o.c. face nalI l6d box 1 3 2" X 0.135 ;or 12 o.c. face nail 8orfibod at intersecting wall corners totslDpdceddwamitA6ngls}uds at braced wall panels) 3"x 0.131 nails; or 3-3" 14 gage staples, ?g" crown 12"a.c. face nail 10. Built-up header (2" to 2" header)) 16d common 3 1 2' X 0.162 16'o.c. face nail 16d box 3 1 2 X 0. 135' ; or 12"o. c. face nail 11. Continuous header to stud 4-8d common (21/2, x 0. 131. ); 4-8d common 2 1 2" X 0. 131-)-,or Toenail 4-10d box 3 X 0. 128 16d common 3 1 2" X 0. 162" ; or 16 o. c. face nail 1 common 3 X 0. 128 ; or 12. Top plots to top plate 3"x 0.131" nails; or 12"o.c. face nail 3" 14 gage staples, ?g" crown 8-16d common 3 1/2' X 0.162 );or Each side of end joint, face 12-I0d box (3" x 0.128");or nail 13. Top plate to top plate, at end joints 12-3" 0.131" nails; or (minimum 24" lap splice length 12-3" 14 gage staples, ?G' crown each side of end joint) I6d common 3 1/2" X 0. 162 ; or I6 o. c. face nail 14. Bottom plate to joist, rim joist, band joist or blocking 16 box 1 2 X 0.13 ;or (not at braced wall panels) 3"x 0.131" nails; or 12"o.c. face nail 3" 14 gage staples, eg" crown 2-16d common 3 1/2" X 0. 162"); or 15. Bottom plate to joist, rim joist, band joist or blocking 3-I6d box (3 1/2" x 0.135");or at braced wall panels 4-3" 0.131' nails; or Toenail 4-3" 14 gage staples, ?g" crown 4-8d common 2 1/2" X 0. 131"); or 4-1Od box ( 3" x 0. 128" ); or Toenail 4-3" 0. 131" nails; or 4-3" 14 gage staples, ?g" crown 16. Stud to top or bottom plate 2-16d common 3 1 2 X 0. 162"); or 3-I0d box (3" x 0.128");or 3-3" 0. 131" no i Is; or End nail 3-3" 14 gage staples, ?g" crown 2-16d common 3 1/2 X 0. 162 ; or 3-10d box (3" x 0. 128"); or 17. IRepeocetlottom plate to stud 3-3" 0.131" not Is; or End nail 3-3" 14 gage staples, ?S" crown 2-I6d common (x 1 2 X ;or 18. Top plates, laps at corners and intersections 3-lOd box (3" x ;or0. );or 18. To plates, laps at corners and intersections p P P 3-3" 0.131' nails; or s;0. or Face Hall 3-3" 14 gage staples, ?g" crown 2-8d common (2 1/2" X 0. 131"); or 19. 1" brace to each stud and plat 2-10d box (3" x 0.128");or 19. 1' brace to each stud and plat 2-3" 0.131" nails; or Face nail 3-3" 14 gage staples, ?g" crown 20. 1"x6" sheathing to each bearing 2-8d common (2 1/2" X 0.131");or 20. 1"x6"sheathin to each bearing3-10d box (3" x 0.128');or Face Hall 21. 1 x8 and wider sheathing to each bearing 3-8d common (2 1/2" X 0.131");or 21. 1"x8" and wider sheathing to each bearing 3-10d box (3" x 0.128");or Face nail Floor 3-8d common (2 1/2" X 0. 131); or 22. Joist to sill, top plate, or girder 3-10d box (3" x 0.128");or 22. Joist to sill, top plate, or girder 3-3" 0.131" noIIs; or Toenail 3-3" 14 gage staples, ?g" crown 8d common (2 1/2" X 0. 131"); or 23. Rim joist, bond joist, or blocking to top plate, sill or IOd box (3" x 0.128");or BEheRitirglimia4,bb4od joist, or blocking to top plate, sill or 3" 0.131" nails; or 6"o.c., toenail other framing below 3" 14 gage staples,?g" crown 2-8d common 2 1/2" X 0. 131"); or 24. 1"x 6"subfloor or less to each joist 2-10d box (3" x 0.128");or Face nail 25. 2" subfloor to foist or girder 2-16d common 3 1/2" X 0.162" Foce Hall 26. 2 planks lank & beam - floor & roof 2-16d common 3 1 2 X 0.162 Each bearing, face nail 32" a. c., face nail at top and 20d common (4"x 0.192") bottom staggered on opposite sides) common t ; or 24' o. c. , face nail at top and 27. Built-up girders and beams, 2, lumber layers 3"x 0.131" nails; or bottom 3" 14 gage staples, ?g" crown staggered on opposite sides) 2-20d common (4" X 0. 192 ); or 3-IOd box (3" x 0.128");or Ends and at each splice, face 3-3" 0.131" nails; or noll 3-3" 14 gage staples, Zg" crown 3-18d common (3 1/2" X 0.162");or 4-1Od box (3" x 0.128");or Each joist or rafter, face nail 28. Ledger strip supporting joists or rafters 4-3" 0.131" nails; or 4-3" 14 gage staples, ?S" crown 3-16d common 3 1/2* X 0. 162 ); or 4-10d box (3" x 0.128");or End nail 29. Joist to band joist or rim joist 4-3" 0.131" nails; or 4-3" 14 gage staples, l�" crown 3-I6d common (3 1/2 X 0. 162);or 4-10d box (3" x 0. 128"); or End nail 30. Bridging or blocking to joist, rafter or truss 4-3" 0.131" nails; or 4-3" 14 gage staples, ?g" crown Yllhzoill ssttrur Wrtsil Waredlss (011391. saritff laver "zcff axdt irrttesriirnr 001111 sitWAHIFnp tiro ffrweliTW arrdJ W=rttiWkittmurdi wbdlll s#fesritftlifW tleo framing a framing a Edges Intermediate (inches) supports (inches) 6d common or deformed (2" x 0.113") 6 12 squbflnor and �wgalll yp y� µmo .rr di Qd1113") a C./fl3 r 6 12 31. 3/8 '- 1/2" 3 "0 " R81 I b 9 f 88F 8R9 --98-f 1 g H 11" 16 gage staple, ?g" crown 4 8 subfloor and wall 21" x 0.113, not (roof) 4 8 1 3/4"I6 gage stople,?g"crown(roof) 3 6 8Pl IQl Ai l bjt; or 6 12 Ge Wtcil 4Qd( 2wp01n31)l" SUBFLOOR AND 32. 19/32 " - 3/4" x , 1 33 nail• or la 14mifigifeare r QUM 131 (OOoi)cRftahR�-301�20/448K9.;1oya") nail g 33. 78 -1 rof Other exterior wall pheothing 4 8 2 x0.113 "no il; or $ "1 Gja9Q4i� i�1a7P F0o nor �Itl191 34. 7/8 "filbb}board sheathing b 1 c �m pg"or 1" ?2 Other ex ter I or w n (4" X 0. 192"); or fiberboard sheathing 11 3"gIlv1Q f7 zgAir%Ofldf9 noll 3 6 i3t;p- hlWdg ti19nWt1&¢1%i9,r8" raven tiberboard sheath Wgd structural panels, combination u&,tdppr un erlayment to framing Ft9Nt�t96'x ((Z "1�x2"0. QZ�1; dv or g 12 30, 32 b and sheathin b f r 11 3 6 W3bmM g41" sX9 gjwood 12 5a structural panels, corMinal _ " d common x 8 o' 6 12 36. 3 4 and less Panel sidin 9 d rdlirfi"e d 2" x 0. 113" 6 12 37. 7 8 1`- 1" 6 d r s -"xb.� s'di 6 12 1 9 6BFW1919ibrl-+�e9i3691;c15ing (2"X 8 IF 38. 1 , 1* less mad 2 1 2"x0. 131" Panei siding Wo rRg)sion-reslstant siding Ad g®FFOl31 6 12 (2j"1/dt"I): DOa"1)3"4r 39. 1/2, or less Interior pa d11W*") 4Q: j178" 42c3)pVfbnX(d. 42✓P ); Sk 080'); or 1p fdpimbs do lr ds ks tb Ot72c s i n 12 c114$ A Q.21 k3 0) 099") ; or 6 12 JQU ne inter far punaliny 4d common (1 1/2"x 0.080"); or 6 12 41. 4d finish 1 1 2"x 0.072" 6d casing (2"x 0.099"); or 6 12 42 tl" 6d finish Panel supports at 24" N O N 0 Digitally signed by Thomas L Thomas L Hanson:A01410 Hanson:A01410D00000 = 177EF3164E000015AD (D D00000177EF31A B4E000015ADA Date:2021.12.15 11 08:51:15-05'00' 0 U Signed and scaled by l.. Hanson YL'`\\\�\\y"n using a Digital signature and date.Y?\� re {SQ1 �Gi� Printed copies of this docunienl ti ��0,% a 54 A arc not considered signed and scaled and the signature must he verified on any electronic co V) Z O Ld iY PROJECT NO. 2021-32 Rr=154R C)ET4 i !. ror an i incn a co. -t mm. a. Nails spaced at 6 inches at intermediate supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing. b. Spacing shall be 6 inches on center on the edges and 12 inches on center at Intermediate supports for nonstructural applications. Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked). c. Where a rafter Is fastened to an adjacent parallel cell Ing joist in accordance with this schedule and the ceiling joist is fastened to the top plate in accordance with this schedule, the number of toenails In the rafter shall be permitted to be reduced by on nail. DWG N0. S 2ri SU8 &F8-05/1T 8F8-013/2T 8F8-15/1T 8F8-15/2T ■ . ■` '� r■MIME 111 11' &RU& 8W6-05/IT 8RF6-05/2T &RFh-I5/1T &W6-I15/2T 8RF10-05/1T 8RF10-05/2T ORF10-113/1T 8RF10-113/2T ill 8W14-013/1T OW14-05/2T 8W14-18/1T 8RF14-113/2T 0 IN MIMM 0 i0 0 0 mom 0 0 0 0 0 0 on all LINTEL SECTIONS 8RF18-05/1T 8RF18-05/2T 8RF18-18/1T 5RF18-I5/2T 8RF22-05AT 8RF22-05/2T 8RF22-15AT 8W22-113/2T 8" IRECE55ED LINTEL 5ECTiON5 SAFE GRAVITY LOADS FOR 8" PRECAST & PRESTRESSED U-LINTELS SAFE LOAD - POUNDS PER LINEAR FOOT TYPE LENGTH SUS 8F8-0B 8F12-08 8F16-0B 8F20-OB BF24-OB 8F28-OB 8F32-OB 8F8-1B BF12-1B BF16-18 8F20-1B 8F24-1B 8F28-1B 8F32-1B 2'-10" (34") PRECAST 2231 3069 4605 6113 7547 8974 10394 11809 3069 4605 6113 7547 8974 10394 11809 3'-6" (42") PRECAST 2231 3069 3719 5163 6607 8054 9502 10951 3069 1 4605 6113 7547 8974 10394 11809 4'-0" (48") PRECAST 1966 2561 2751 3820 4890 5961 7034 8107 2693 4605 6113 7547 8974 10394 11809 4'-6" (54") PRECAST 1599 1969 2110 2931 3753 4576 5400 6224 2189 4375 6113 7547 M 8672 10294 11809 5'-4" (64") PRECAST 1217 1349 1438 1999 2560 3123 3686 4249 1663 3090 5365 7547(se) 7342(10) 8733(10) 10127(to 5'-10" (70") PRECAST 1062 1105 1173 1631 2090 2549 3009 3470 1451 2622 4360 7168(,45) 6036(le) 7181pe 8328 10 6'-6" (78") PRECAST 908 1238 2177 3480 3031 3707 4383 5061 1238 2177 3480 5381 8360 10394M 882514 7'-6" (90") PRECAST 743 1011 1729 2632 2205 2698 3191 3685 1011 1729 2661 3898 5681 8467(44) 6472 1s 9'-4" (112") PRECAST 554 699 1160 1625 2564 306 2818 3302 752 1245 1843 2564 3486 4705 M 6390(4 10'-6"(126") PRECAST 475 535 890 1247 2093 2777 2163 2536 643 1052 1533 2093 2781 3643(ael 4754(.5 11'-4" (136") PRECAST 362 582 945 1366 1846 2423 3127 4006 582 945 1366 1846 2423 3127 4006 12'-0" (144") PRECAST 337 540 873 1254 1684 2193 2805 3552 540 873 1254 1684 2193 2805 3552 13'-4" (160") PRECAST 296 471 755 1075 1428 1838 2316 2883 471 755 1075 1428 1838 2316 2883 14'-0" (168") PRECAST 279 424 706 1002 1326 1697 2127 2630 442 706 1002 1326 1697 2127 2630 14'-8" (176") PRESTRESSED N.R. NR NR NR NR NR NR NR 458 783 1370 1902 2245 2517 2712 15'-4"(184") PRESTRESSED N.R.R .R. NR NR NR NR NR NR 412 710 1250 1733 2058 2320 2513 17'-4" (208") PRESTRESSED N.R. NR NR NR NR NR NR NR300 548 950 1326 1609 1849 2047 19'-4" (232") PRESTRESSED N.R. NR NR NR NR NR NR NR 235 420 750 1037 1282 1515 1716 21'-4" (256") PRESTRESSED N.R. NR NR NR NR NR NR NR 180 1 340 598 845 1114 1359 1468 22'-0" (264") PRESTRESSED N.R. NR NR NR NR NR NR NR 165 315 550 784 1047 1285 1399 24'-0" (288") PRESTRESSED N.R. NR NR NR NR NR NR NR129 250 450 654 884 1092 1222 (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. SAFE LATERAL LOADS FOR 8" PRECAST & PRESTRESSED U-LINTELS SAFE LOAD PLF LENGTH TYPE 8U8 81`8 R MU* C 2'-10" (34") PRECAST 1293 1642 2135 3'-6" (42") PRECAST 1025 1024 1830 4'-0" (48") PRECAST 765 763 1365 4'-6" (54") PRECAST 592 591 1057 5'-4" (64') PRECAST 411 411 734 5'-10- (70") PRECAST 340 339 607 6'-6" (78") PRECAST 507 721 483 7'-6" (90") PRECAST 424 534 357 9'-4" (112") PRECAST 326 512 227 10'-6" (126") PRECAST 284 401 178 11'-4" (136") PRECAST 260 452 152 12'-0- (144") PRECAST 244 402 135 13'-4" (160") PRECAST 217 324 109 14'-0" (168") PRECAST 205 293 98 14'-8"(176') PRESTRESSED N.R. 284 89 15'-4"(184") PRESTRESSED N.R. 259 82 17'-4"(208") PRESTRESSED N.R. 194 63 19'-4"(232") PRESTRESSED N.R. 148 51 21'-4"(256') PRESTRESSED N.R. 125 42 22'-0"(264") PRESTRESSED N.R. 116 39 24'-0"(288") PRESTRESSED N.R. 91 33 * SEE NOTE 18 M�M MEN MIMM 0 -i M__M M M i IN M Mon o M__._M M____ 0 M____M INA m ICI ICI IMA 8F28-013/1T 8F28-05/2T 8F28-15/1T 8F28-113/2T MEN M�M M�M Mxa"M 0 Mi M M M M M 0 0 0 M 0 0 M M 0 0 mom MX0"M M son mom MEMO M 0 0 0 8F32 -15/2T �son i E i�ME mom ■fi i on1 8RF26-015/17' 8W26-08/2T 8RF26-l5/lT 8RF26-113/2T 1111111�10 MEN Ems ME IL�V__A F a 8RF30-013/1T 8RF30-013/2T 8W30-113/1T 8RF30-113/2T *S REBAR AS REQUIRED 130° STANDARD (2 MINIMUM) NOOK 10" MINIMUM (TYPICAL) • • 1Mat CAST-CRETE HIGH STRENGTH all PRECAST BEARING LINTEL FILLED :' WITH GROUTT/ ' SAFE UPLIFT LOADS FOR 8" PRECAST & PRESTRESSED U-LINTELS SAFE LOAD - POUNDS PER LINEAR FOOT TYPE LENGTH - 8F8 1T 8F12-1T 8F16-IT 8F20-1T BF24-1T - 8F28 1T F - 8 32 1T 8F8-2T 8F12-2T BF16-2T 8F20-2T 8F24-2T 8F28-2T BF32-2T 2'-10" (34") PRECAST 1972 3173 4460 5747 7034 8321 9608 1972 3173 4460 5747 7034 8321 9608 3'-6" (42") PRECAST 1569 2524 3547 4569 5591 6613 7636 1569 1 2524 3547 4569 5591 6613 7636 4'-0" (48") PRECAST 1363 2192 3079 3966 4853 5740 6627 1363 2192 3079 3966 4853 5740 6627 4'-6" (54") PRECAST 1207 1940 2724 3508 4292 5077 5861 1207 1940 2724 3508 4292 5077 5861 5'-4" (64") PRECAST 1016 1632 2290 2649 3607 4265 4924 1016 1 1632 2290 2949 3607 4265 4924 5'-10" (70") PRECAST 909 1492 2093 2694 3295 3897 4498 929 1492 2093 2694 3295 3897 4498 6'-6" (78") PRECAST 835 1340 1880 2419 2959 3498 4038 835 1340 1880 2419 2959 3498 4038 7'-6" (90") PRECAST 727 (yy) 1021 1634(12) 2102 1, 2571(io) 3039(to) 3508 727 1166 1634 2102 2571 3039 3508 9'-4" (112") PRECAST 591 680 11 331s 1471 1s 181115 2152 a 2494 1s 591 851 1326 1705 2084 2463 1 2842 10'-6"(126") PRECAST 530 552 914(,$) 1185(,$) 1458(1s) 1732(15) 2007(15 530 686 1183 1 1526 1865 2204 2544 l l'-4" (136") PRECAST 474 485 798 ,s 1034 1s 1272 1s 1510 1s 1749 (1s 494 1 599 1028 1422 1738 2053 2369 12'-0"(144") PRECAST 470 (0 441 723 ,. 936 „ 1151(1s 1366(s) 1582p5 470 543 928 1349 1649 1948 2247 13'-4" (160") PRECAST 418 (ts 373 606 (14 783 (,4 962 (1. 1141(14 1321(14 428 455 770 1145 14" 1718 1993 14'-0" (168") PRECAST 384 (m) 346 559 ,4 723 (m) 887 (u 1052 (14) 1218 (14 410 420 709 1050 1434 p 1694 Is 1954 14'-8" (176") PRESTRESSED 239 323 519 (, 671 („) 823 (1a) 976 (14) 1129(,q 246 390 655 968 1324 (0) 1625 (11) 1874 11 15'-4" (184") PRESTRESSED 224 302 485 (, 626 (1 767 (1 909 (, 1052(13) 230 364 609 897 1224 1562 (14) 1801(14 17'-4" (208") PRESTRESSED 187 255 404 (1 520 (u) 637 (1:) 754 (12) 872 (1s) 192 303 500 732 993 1268(14 1470(u 19'-4" (232") PRESTRESSED 162 222 347 tt 446 11 546 a 646 12 746 1s 166 261 424 616 831 (e 1057 (11) 1225 (11 21'-4" (256') PRESTRESSED 142 198 306 „ 393 (11) 480 (tt 567 11 654 (11 142 230 369 531 713 V 903 (1 1046 1 22'-0" (264") PRESTRESSED 137 192 295 (10 378 (t, 461 (to 545 I„) 629 pi 137 221 354 1 508 1 681 861 (1 997 (1 24'-0" (288") PRESTRESSED 124 175 267 po 341 (10 416 (10 491 (to 566 (10 124 200 316 450 600 756 12) 875 t (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. 05 REBAR IN .• VERTICAL GROUT FILLED CELL •" E' ^ C,ANTiLEVEFRED LINTEL DETA L MASONRY TIES •'::'i' AS SPECIFIED CONCRETE FASTENERS SPLIT FACE y'. WITH MINIMUM 4" MASONRY VENEER EMBEDMENT SPACED AS REQUIRED CAST-CRETE LINTEL FILLED WITH GROUT CONTINUOUS SHELF ANGLE SIZED AS REQUIRED :r CONCRETE FASTENERS _ AS REQUIRED 7:7` CAST-CRETE U-LINTEL FILLED w/ GROUT • 4,. CONTINUOUS SHELF ANGLE SIZED AS REQUIRED 1„i,ASONF��r VENEEFR 5FL iT FACE VENEEFR SAFE GRAVITY LOADS FOR 8" PRECAST w/ 2" RECESS DOOR U-LINTELS 4~ft- iWM SAFE LOAD - POUNDS PER LINEAR FOOT TYPE LENGTH 8RU6 8RF6-0B 8RFIO-08 8RF14-OB 8RF18-OB 8RF22-OB 8RF26-08 8RF30-OB 8RF6-1B 8RF10-1B 8RF14-1B 8RF18-1B 8RF22-1B 8RF26-18 BRF30-1B 4'-4" (52") PRECAST 1635 1749 3355 3280 4349 5421 6493 7567 1891 3699 5206 6639 8060 9479 10893 4'-6" (54") PRECAST 1494 1596 3063 2992 3968 4946 5924 6904 1 556 3699 5206 6639 8060 9479 10893 5'-8" (68") PRECAST 866 920 1770 1716 2277 2839 3402 3966 1167 2481 4567 6389 8060 7917(,o 9311(it 5'-10" (70") PRECAST 810 859 1653 1600 2124 2649 3174 3700 1113 2342 1 4242 6639 ryo 8060(is) 7402(1a) 8706 (,o 6'-8" (80") PRECAST 797 901 1825 3120 5048 7747 9448 7360 901 1825 3120 5048 7915 9479 1089 7'-6" (90") PRECAST 669 755 1490 2459 3776 5743 7239 5623 755 1490 2459 3776 5743 8998(is) 10893(4a 9'-8" (116") PRECAST 411 466 999 1568 2253 3129 4091 3146 526 1 999 1 1568 1 2253 1 3129 4150 5891(/ (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. NOTE: INFORMATION CONTAINED ON THIS SHEET PROVIDED BY AND PERTAINING TO CAST-CRETE CORP. ALTERNATE PRODUCTS OF EQUAL CAPACITY MAY BE USED. ALTERNATE PRODUCT MUST BE ACCOMPANIED BY ENGINEERING DATA TO SUPPORT SUCH PRODUCT. ENGINEERING SPECIFICATI NS PRODUCT DESCRIPTION High strength precast concrete lintels designed to be unfilled or Filled to Form a composite reinforced beam using concrete masonry units. MATERIALS f'c 8" precast lintels = 3500 psi ° Concrete masonry units (CMU) per A5TM C90 with minimum net area f'c 8" prestressed, 6" and 12" precast lintels = 6000 psi compressive strenght : IWO psi f'c 4" precast lintels = 3000 psi ° Rebar per A5TM A615 Grade 60 Grout per A5TM C416 f'g : 3000 psi w/ maximum ° Prestressing strand per A5TM A416 Grade 210 low relaxation 3/8 Inch aggregate and 8 to II inch slump. ° 1/32 inch wire per ASTM A510 ° Mortar per A5TM C210 Type M or S GENERAL NOTES 1. Provide full mortar head and bed joints. 8. Cast -in -place concrete may be provided in composite lintel in lieu of 2. Shore filled lintels as required. concrete masonry units. 3. Installation of lintel must comply with architectural 9. Safe load ratings based on rational design analysis per ACI 318 and AGI 530 and/or structural drawings. 10. Product Approvals: Miami Dade County, Florida Nos. 03-0605.05 4. U-Lintels are manufactured with 5-1/2 inch long notches at and 03-0605,04. Florida Certificate of Product Approval number FL158. ends to accomodate vertical cell reinforcing and grouting. 11. The exterior surface of lintels installed in exterior concrete masonry walls 5. Reference the CAST-CRETE Load Deflection Graph shall have a coating of stucco applied in accordance with A5TM C926 Brochure for lintel deflection Information. or other approved coating. 6. Bottom field added rebar to be located at the bottom 12. Lintels loaded simultaneously with vertical (gravity or uplift) and horizontal of lintel cavity. (lateral) loads should be checked for the combined loading with the 1. 1/32 inch diameter wire stirrups are welded to the bottom following equation: steel for mechanical anchorage. Applied vertical load +Applied horizontal load i 1.0 Safe vertical load Safe horizontal load SAFE LOAD TABLE NOTES 1. All values based on minimum 4 Inch nominal bearing. Exception: Safe loads for unfilled lintels must be reduced by 20 % if bearing length is less than 6-1/2 inches. 2. N.R = Not Rated. 3. Safe loads are superimposed allowable load. 4. Safe loads based on Grade 40 or Grade 60 field rebar. 5. Additional lateral load capacity can be obtained by the designer by providing additional reinforced masonry above the precast lintel. See Reinforced CMU on Page 4. 6. One 01 rebar may be substituted for two 5 rebars in 8" lintels only. 1. The designer may evalute concentrated loads from the safe load tables by calculating the maximum resisting moment and shear at d-away from the face of support. SAFE LATERAL LOADS FOR 8" PRECAST w/ 2" RECESS DOOR U-LINTELS 4WP-4m r SAFE LOAD PLF LENGTH TYPE 8RU6 8RF6 CMU* 4'-4" (52") PRECAST 758 757 1365 4'-6" (54") PRECAST 694 693 1249 5'-8" (68") PRECAST 408 407 734 5'-10" (70") PRECAST 382 381 687 6'-8" (80") PRECAST 595 788 510 7'-6" (90") PRECAST 509 674 393 9'-8" (116") PRECAST 370 490 227 * SEE NOTE 18 8. For composite lintel heights not shown, use safe load from next lower height. 9. For lintel lengths not shown, use safe load from next longest length 10. All safe loads in units of pounds per linear foot. 11. All safe loads based on simply supported span. 12. The number in the parenthesis indicates the percent reduction for grade 40 field added rebar. Example: T-b" lintel Type BF32-15 safe gravity load = 6412 (15) w/ 15% reduction =1E 6412 (B5) = 5501 plf SAFE UPLIFT LOADS FOR 8" PRECAST w/ 2" RECESS DOOR U-LINTELS 4^=64~11111111111 SAFE LOAD - POUNDS PER LINEAR FOOT TYPE LENGTH 8RF6-1T 8RF10-1T 8RF14-1T 8RF18-lT 8RF22-IT BRF26-1T 8RF30-1T 8RF6-2T 8RF10-2T 8RF14-2T BRF18-2T 8RF22-2T 8RF26-2T 8RF30-2T 4'-4" (52") PRECAST 905 1748 2635 3522 4409 5296 6183 905 1748 2635 3522 4409 5296 6183 4'-6" (54") PRECAST 867 1675 2525 3374 4224 5074 5924 867 1675 1 2525 3374 1 4224 5074 5924 5'-8" (68") PRECAST 675 1301 1960 2618 3277 3935 4594 675 1301 1960 2618 3277 3935 4594 5-10"(70") PRECAST 655 1262 1900 2538 3176 3815 4453 655 1262 1900 2538 3176 3815 4453 6'-8" (80") PRECAST 570 1012 1651 2204 2758 3312 3865 570 1097 1651 2204 2758 3312 3865 7'-6" (90") PRECAST 506 797 1462 (e) 1952 M 2442 (e) 2931 e 3257 506 967 1462 1952 2442 2931 3421 9'-8" (116") PRECAST 395 491 931 (1s) 1301(15) 1640(15) 1980 1s 2322 (u 395 1 589 1135 1514 1 1893 2272 2652 (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. 0 C a O i CD C a1 co O O C 0 U) L C L 0 U N 0 N 0 lZ 0 U PROJECT NO. 2021-32 Thomas L Digitally signed by Signed and sealed byl'.L. t(ansun Pl: \ 4 Thomas L using a Digital Signature and date. fir, 1­ - G1.i' Hanson:A01410 Pnntcdcopieso(thlsdocun,enl o, Hanson:AO1410D00000 are not considered signed and _ D00000177EF31 177EF31 B4E000015ADA scaled and the signature must be Uj Vel'die/l on ally cicoront, co Date:2021.12.15 o� F4ua�•""a� B4E000015ADA 08:51:44-05'00' DWG N0. s �a 1 _ I I I I It I I I __L_ _ _ _ _ I IL I I 1 11 1 111!1 __ __ 11 t PRODUCT APPROVAL INFORMATION SHEET (S) COVER SHEET EVALUATION REPORT FROM A PRODUCT EVALUATION ENTITY Ff;;�,10E)UGT AFFFP,0VAL SF G iF i GAT i ON 5I 4EE T MMAs squired by Florida Statute 553.842 and Florida Administration Code 98-12, please provide the information and approval numbers on the building components listed below if they will be utilized on the construction product for which you are applying for a building permit. We recommend you contact your local product supplier should you not know the product approval number for any or the applicable listed products Category / Subcategory Manufacturer Product Description Approval Number(s) Test Pressures 1. EXTERIOR DOORS A. SWINGING ThermaTru Flberclassic FL 5891.1 +E1.0/-E7.0 psf ThermaTru Smooth Star FL 5891.2 4010 / -II per ThermaTru ClassicCraft FL 5891.3 401.0 / -Ei.0 psf 5. SLIDING MI Windows and Doors Series 420/430 FL 15332.1 - FL 15322.5 +40.0 / -40.0 psf C. SECTIONAL Wayne -Dalton, a division of Overhead Door Corporation Model 08,000/8100 01101 - 01104 9' Max width, 14' Max Height FI 0248.1 - FI 8248.4 +22.13 / -26.3 per +46.0 /-52.0 psf Wayne -Dalton, a division of Overhead Door Corporation Model *8000/8100 011211 - 01125 16' Max width, 14' Max Height FI 8248.5 - FI 8248.9 +15.30 / -11.0 per +4F,.0 /-52.0 psf D. OTHER 2. WINDOWS A. SINGLE HUNG MI Windows and Doors Series GA 195 Aluminum SH FL 1521-1.5 +50.0 / -50.0 per MI Windows and Doors Series GSA 5500 PVC SH FL 152111 - FL 1521-1.3 +50.0 / -50.0 psf 5. HORIZONTAL SLIDER MI Windows and Doors Series HS iSS FL 15351.1 - FL 15351.E +50.0 / -50.0 psf MI Windows and Doors Series 1630 Single Slider FL 21638.1 - FL 21638.11 +50.0 / -50.0 psf C. FIXED D. MULLION E. OTHER 3. PANEL WALL A. 51DING James Hardie Building Proclucts,lnc. Artisan®Lap Siding FL 104-11.1 5. SOFFITS Alside Solid and Vented Soffit FL 15212.1 - FL 152-12.2 +-10.0 / -10.0 psf C. VINYL SIDING Certainteed Corp Siding Products CertainTeed Vinyl Vinyl Siding FL15-13.1 +N/A/-1E0.6 4. ROOFING PRODUCTS A. ASPHALT SHINGLES Certain Teed Corporation CT20 land AR), Landmark 30 / 40 (and AR) XT30 (and AR) FL54441 N/A A. Metal Roofing Union Corrugating Company MasterRib Panel FL9555.4 N/A 5. UNDERLAYMENTS Tamko 151b Felt Underlayment FL 12328.E N/A C. ROOFING FASTENERS NOT USED D. ROOF VENTILATION Thompson Arch Metal Comp. Off Ridge Vents FL 5219.1 - FL 5219.4 N/A GAF Attic Ventilation Products Vent RViO FL 621 1 N/A E. ROOFING TILES Bora I Tile villa 900 FL 7849.24 - FL-1,549.28 N/A F. OTHER 5. SHUTTERS Global Protection Products Galvanized Steel Storm Panels FL 15016.1 - FL 15016.2 N/A A. STORM PANELS Global Protection Products GFF Fabric Shutter Series 2000 FL 15088.1 N/A Town and Country Industries Safty Edge Storm Panels FL 12856.1 +54.0 / -54.0 per 6. STRUCTURAL COMPONENTS Fastening Specialists, Inc. Tie Max "Threaded Rod" FL156E.3E A. WOOD CONNECTORS / ANCHORS USP Structura I Conn. See chart Simpson Strong -Tie see chart 5. TRUSS PLATES ITW Building Components Alpine Truss Plates FL 1999l.1 - FL 1999.4 N/A MiTek Industries, Inc. Truss Plates FL 21'31.1 - FL 2191.5 N/A C. ENGINEERED LUMBER Boise Eng. Wood Prod. Versa -Lam SP FL III N/A Boise Eng. Wood Prod. Wood -I -Joists ALL JOIST FL III N/A Weyerhaeuser Engineered lumber - TJI FL 1630.1 - FL 1E30.11 N/A Weyerhaeuser iLevel Rim Board, LVL, PSL, LSL FL 6527.1 - FL 6521.4 N/A D. MATERIAL Cast -Crete Corp. High Strength Concrete Lintels FL i58.1 N/A Powers Steel, Inc. Power Box Lintels FL 3119.1 , 5450.1 , 11383.1 N/A A. SINGLE PLY ROOF SYSTEMS Mule -Hide Products Co., Inc. Thermoplastic polyolefin Single ply roof systems FL12-1-12 1 +N/A /-525 51t-I &ON Connectors Simpson Stock No. FloridaASptaa ova No Product Evaluation Report 5aele A23 FLI0446.1 ESR-2606 HU210-2 FL10531.9 ESR-2549 14UD212 -2 FL 10531.9 E5R-2549 HU26 FL 10531.e ESR-2549 HU28-2 FL10531.9 ESR-2549 HU410 FL10531.9 ESR-2549 HU412 FL10531.9 E61R-2549 14U610 FL10531.9 ESR-2549 W0412 FLI4963 ESR-2549 HD610 FLI4963 ESR-2549 HUCQ410 FL10531.9 SIM200804 HGAIOKT FLi044II SIM200803 HGAMIOKT FLi1413.6 SIM200803 HCP2 FLI0441.4 ESR-2551 HETAI6 FL11413.4 SIM200802 HETA20 FL11413.4 6IM200802 HTTI6 FL11413.5 E5-0130 HTT22 PLI1413B ES-0130 HT516 FL11413.12 ESR-2613 HT620 FLI1413.12 ESR-2613 HT524 FLi1413.12 ESR-2613 PTS30 FLII413.12 ESR-2613 HT5MI6 FLi1413.12 SIM200802 HTSM20 FL11413.11 SIM200802 HGT2 FL10866.1 E5R-2II HGT3 FL 10866.1 ESR-2613 HUS210-2 FL10531.11 ESR-2549 HUS212-2 FL10531.11 E5R-2549 HUs26 FLI0531.11 ESR-2549 HUS28 FLI0531.11 ESR-2549 HUS28-2 FL10531.9 ESR-2549 LU24 FL10531.14 ESR-2549 LU26 FLI0531.14 ESR-2549 LUS210-2 FL10531.14 ESR-2549 LU524 FLI0531.16 ESR-2549 LU526 FL10531.16 E5R-2549 LUS26-2 FLI0531.16 ESR-2549 LUS25 FL 10531.16 ESR-2549 LUS46 FLI0531.16 ESR-2549 MST60 FL 1045620 ESR-2105 LSTA12 FL 13512.5 E5R-2105 LSTAI5 FL13812.5 ESR-2105 LSTAI5 FL 13812.5 ESR-2105 LSTA24 FL 13812.5 E5R-2105 LSTA30 FL13812.4 E5R-2105 LSTA36 FL13812.4 ESR-2105 LTT19 FLI1496 5 ER-130 LTT205 FL11496.5 ER-130 LTT131 FLI149ro.5 ER-130 LTS12 FL13512.8 ESR-2613 LGT2 FLI1410.1 5IM200803 L830 FL 1044620 ESR-2606 A34 FL10446.1 ESR-2606 M5TAI2 FLI045621 ESR-2105 MSTAI5 FLI045II ESR-2105 MSTAIS FLi045621 ESR-2105 M5TA24 FL1045621 ESR-2105 MSTA36 FL1045621 ESR-2105 MSTC40 FLi045622 ESR-2105 M5TC52 FL1045622 ESR-2105 MT512 FL1045633 E5R-2II MTSI6 FLI045634 ESR-2613 MT515 FL1045635 ESR-2613 MTW20 FLI0456.36 ESR-2613 MGT FLMS04.5 SIM200803 1' 15HA356/11.25 FL13904.5 ESR-2616 1" 15HA3.5ro/Ifo F1_13904.5 ESR-2616 ABU44 FLI08602 E5R-1622 A51.166 FL108602 ESR-1622 HDU2-SDS2.5 FLI0441.4 ESR-2330 GLTV3.51ro FLI0661.6 E51R-2615 FGTR FL114132 SIM200802 c516 FLI3812.1 ESR-2105 HI F10456.1 ESR-2613 H10 FL1044II E5R-2613 HIO-2 FLI044II ESR-2613 HIOA FLI044616 ESR-2613 H3 FLI0456.1 ESR-2613 H4 FLI0456.1 E5R-2613 H5 FLI0456.1 ESR-2613 H2.5 FL10456.1 ESR-2613 H2.5A FLI0456.1 ESR-2613 H8 FLI0456.1 SIM200803 SPl FLI0456-R5 E5R-2613 5P2 FLI0456-R5 E5R-2613 SP4 FL10456-R5 ESR-2613 5106 FL10456 -R5 E5R-2613 5108 FLI0456-R5 E5R-2613 SPH4 FLI0456-R5 ESR-2613 SPH6 FLI0456-R5 ESR-2613 SPHB FL10456-R5 ESR-2613 HHU526-2 FL 11468.1 ESR-2549 HHUS410 FLII468.1 ESR-2549 HGU5525/12 FL10531.4 5IM200804 HGUS414THDH414 1=1_10531.4 SIM200804 HDQ8-SD53 FL104413 E5R-2330 MSTAM24 FLI3812.4 SIM200802 MSTAM36 FL13812.9 SIM200802 MSTCM40 FL13612.9 SIM200802 HHETA20 FLI1413.1 SIM200802 LGT3-SD525 11413.8 SIM200803 LGUM211 FL13904.4 SIM200802 U5P Connectors USP Stork No. Florida Statewide Product Approval No. Evaluation Report 5aele A3 FL11244.1 ESR-3455 1-10210-2 FL112323 E5R-3445 HD212 -2 FL112323 ESR-3445 HD216 FL112323 E5R-3445 HD216-3 FL112323 ESR-3445 HD26 FLI12322 ESR-3445 HD25-2 FL112323 ESR-3445 HD410 FLI1232.4 ESR-3445 HD412 FLi1232.4 ESR-3445 HD610 FL11232.4 ESR-3445 HD0410 FLI12212 ER-0201 HGAiOKT FLI1236b E5R-3448 HGAMIOKT FLI-IiI Evaluation Report HWC102 FLi1236.1 E5R-3448 HTAI6-16 FLI1680.4 Evaluation Report HTA20-18 FLI1680.4 Evaluation Report HTT5 FLi12192 ER-0200 WWi& FLI1244.1 ESR-3455 HTW20 FL11244.1 E5R-3455 HTW24 FL11244.1 E5R-3455 HTW30 FL11244.1 E5R-3455 HTWMI6 FLIII Evaluation Report HTWM20 FL62232 ESR-3455 HUGT2 FL62233 Evaluation Report HUGT3 FL62233 Evaluation Report HUS210-2 FL11232.5 ESR-3455 HUS212-2 FLI1232.5 E5R-3455 HUS26 FL11232%o ESR-3455 HUS28 FL11232.6 E5R-3455 HU525-2 FL11232.6 ESR-3455 JL24 FL11232.10 ER-0201 JL26 FL11232.10 ER-0201 JUS210-2 FL11232.12 ESR-3445 JU524 FLi1232.13 ESR-3445 JUS26 FLI1232.14 ESR-3445 JUS26-2 FLi1232.14 E5R-3445 JU528 FLI1232.14 ESR-3445 JU546 FL11232.14 E5R-3445 KLEG3 FL11241 E5R-3444 KST260 FL11244.14 ESR-3445 LSTAi2 FL11244.11 ESR-3445 LSTAI5 FLI1244.11 E5R-3445 LSTA16 FL11244.11 E5R-3445 LSTA24 FL11244.11 ESR-3445 LSTA30 FLI1244.11 ESR-3445 LSTA36 FL11244.11 ESR-3445 LT51e FLI12192 ER-0200 LTS205 FLI1219.2 ER-0200 LTT131 FL112192 ER-0200 LTW12 FLI1244.19 ESR-3455 LUGT2 FLI12403 E5R-3441 MP3 FL1124422 E5R-3455 MP34 FL1124423 ESR-3455 MP41F FL1124424 E5R-3455 MP5 FL11244.25 ESR-3455 MPH3516 FL11240.4 E5R-3441 MSTAI2 FL11244.11 ESR-3455 MSTAI5 FL11244.11 E5R-3455 MSTAIS FLI1244.11 E5R-3455 MSTA24 FL11244.11 E5R-3455 MSTA36 FL11244.11 ESR-3455 MSTC40 FL1124421 ESR-3455 1­15TC52 FL1124421 ESR-3455 MTWI2 FL11244.1 E5R-3455 MTWI6 FL11244.1 ESR-3455 MTW18 FLI1244.1 ESR-3455 MTW20 FL11244.1 ESR-3455 MUGTIS FLI1240b ESR-3441 NFM35X12 FL515.2 Evaluation Report NFM35XI6U FL5183 Evaluation Report PAU44 FLI1239.12 ESR-3449 PAU66 FL11239.12 ESR-3449 PHD2A FL1121133 ER-0200 PHXU3516 FL1124121 ESR-3444 RFUS FL6223.5 Evaluation Report R5150 FLI124426 ESR-3455 RTi5 FLI1236.10 ESR-3448 RTI6 FLI123III E5R-3448 RTI6-2 FLI1236.11 E5R-3448 RTI6A FLI1236.11 ESR-3446 RT3A FLI1236.11 ESR-3448 RT4 FLI1236.10 ESR-3448 RT5 FLI1236.10 E5R-3448 RT1 FLI1236.10 ESR-3448 RT1A FLI1236.10 ESR-3448 RT8A FLI1236.10 ESR-3448 SPT22 FLI124431 ESR-3455 5PT24 FL1124431 e ESR-3455 SPT4 FL1124432 ESR-3455 5PT6 FL1124432 E5R-3455 SPTS FL1124432 ESR-3455 SPTH4 FL1124432 ESR-3455 SPTH6 FLI124432 ESR-3455 SPTH8 FL1124432 ESR-3455 SUH24 FL11232.lrc ESR-3455 THD28 FL 11232.19 E5R-3445 THD28-2 FL11232_ie ESR-3445 THD410 FL11232.19 ESR-3445 THD412 FL11232.19 ESR-3445 THD612 FL11232.19 ESR-3445 THDH414 FL11232.19 E5R-3445 UPHD8 FLI121cJ 5 ER-0200 U5C53 FL20332 Evaluation Report UGT53F FL20332 Evaluation Report UGT653 FL20332 Evaluation Report GELI-10 FL11241.I E6R-1102 GELi-22 FL11241.1 E6R-1102 U C d O 2 CD C Q) V) N W C O 41 N C THE INFORMATION PROVIDED IS OF THE PRODUCTS INTENDED FOR o USE IN THE CONSTRUCTION OF THIS PROJECT. ALTERNATIVE PRODUCTS WITH FLORIDA PRODUCT APPROVAL (S) MAY BE o SUBSTITUTED. SUPPORTING DOCUMENTATION SHALL BE SUPPLIED N AND THE RESPONSIBILITY OF CONTRACTOR AND OR OWNER. 0 F-- C� a- 0 Digitally signed by Signed and sealed by T.L. Hanson Pr Thomas L using a Digital Signature and Printed copies nlthis dneumd date_ �Thomas L ;ar syi, 14Hanson:A01410Hanson:A01410D00000 are noonsidered signed an , �t D00000177EF31 177EF31134E000015ADA sealed II"'ignature must be to verified un any electronic co Date:2021.12.15 %0, •_LoapP'a`' B4E000015ADA 08:52:15-05'00' PROJECT NO. 2021-32 DWG N0. of