7952-7954 Gall Blvd
Please be advised this review of plans submitted is a cursory review to assist the contractor in compliance with applicable fire safety codes. This review is not intended to be a final approval of the sulWyNed plans. It is the contractor's sole responsib ity to ensure that the plans are in complete compliance with all g4cabfe NFPA codes and local ordinances. in the event that further examination or site inspection reveals areas of non-compliance, it shall be the contractor's sole responsNty, at their sole expense to bring those areas in compliance. The City assumes no responsibility for the contractor's failure to be in compliance with all applicable NFPA Codes and local ordinances. PROJECT TEAL l ZEPHYR COMMONS SHOPPING CENTER 7954 GALL BOULEVARD ZEPHYRHILLS, FLORIDA 33541 INDEX OF [DRAWINGS Please be advised this review of ^' is a cursory review to assist the ca,n!, < apM*r9ble fire safety codes j to be a final approval of t`1 ;15 the contractor's sole responsibili' : ;Mans are in complete complLnce wi+� ; ?A codes VSHALLCOMPLY WIT] local ordinances. In t' ;r e VAILINio CODES, FLORIDAB site inspection revea' `'piiar CODE,NATIONAL ELECTRIC CO' the contractor's sod °`" LLS ORDINA CITY OF ZEPHYRHI bring those are responsibility r v& d epplimie IV1 ivitvv DATE CITY OF ZEPHYRHIL$ "MITTED PLANS) t1AVE BEEN RFVIEWBO MINER MY ZEPHnHIW E MARSHAL'S OFFICE Date: -[FIR a f4 s• PROJECT CRITERIA GENERAL NOTES KEY PLAN TENANT: ARCHITECTURAL: PROJECT DESCRIPTION: FAST CASUAL BURGER RESTAURANT 1. THE GENERAL CONTRACTOR (G.C.) SHALL VI51T THE PROJECT SITE, INVESTIGATE AND BECOME FAMILIAR WITH ALL V1515LE CONDITIONS PRIOR TO BIDDING OR CONSTRUCTION TYPE: TYPE II-5 BEGINNING CONSTRUCTION. ADDITIONAL COSTS WILL NOT BE AWARDED FOR EXISTING CONDITIONS WHICH ARE VISIBLE AND/OR CAN 13E KEA50NA5LY ANTICIPATED. AEOLUS ZFH, INC 5FEC 51"ECIFICATION5 2. THE G.C. 15 RESPONSIBLE FOR VERIFYING ALL DIMENSIONS, 51TE GRADES, ETC, PRIOR TO CON5TKUCTION AND TO NOTIFY THE ARCHITECT OF ANY DISCREPANCIES THAT dba FIVE GUYS FAMOUS 13UKGEK5 & FRIES A-1 FLOOR PLAN/DOOR SCHEDULE COULD AFFECT THE DESIGN AND COMPLETION OF THE PROJECT. BUILDING LAYOUT TO BE VERIFIED 13Y A LICENSED SURVEYOR WITH A WRITTEN VERIFICATION FORWARDED 19319 AUTUMN WOODS DRIVE FIRE PROTECTION: SPRINKLERED TO THE OWNER AND ARCHITECT. A1.1 LIFE SAFETY PLAN /ELEVATIONS 3. ALL CONSTRUCTION SHALL COMPLY WITH ALL AFFLICA13LE MUNICIPAL AND STATE CODES, ORDINANCES AND STANDARDS. PAMPA, FLORIDA 33647 A1.2 PARTITION TYPES OCCUPANCY GROUP: ASSEMBLY (A-2) 2,866 S.F. 4. THE G.C. 15 KE5FON51BLE FOR COORDINATING THE WORK OF ALL UTILITY COMPANIES AND PERFORMING ALL WORK REQUIRED 13Y THEM. PHONE: : RA 78KOMM A-2 EQUIPMENT PLAN / DETAILS 5. THE G.C. SHALL FAY FOR AND OBTAIN ALL REQUIRED FEKMIT5, TEMFORAKY UTILITIES, TAF FEES, CERTIFICATES OF OCCUPANCY, ETC. CONTACT: RAMA KOMMIREDDY A-3 EQUIPMENT SCHEDULE BUILDING AREA: COMMEUNCONRCIAL KITCHEN AN AREA Y wlo FIXED SEATING - 1,382 5F 6. THE G.C. 15 KE5FON515LE FOR REVIEWING AND CONFORMING TO ALL CONTRACT DOCUMENTS. IN THE CASE OF APPARENT CONFLICTS AND/OR DISCREPANCIES IN THE COMMERCIAL KITCHEN AREAS - 922 5F A-4 FINISH PLAN /LEGEND / INT ELEVATION STORAGE AREA 105 5F CONTRACT DOCUMENTS, G.C. 15 TO NOTIFY ARCHITECT IN WRITING OF SUCH APPARENT CONFLICT5 AND REQUEST CLARIFICATION FROM THE ARCHITECT. NO ADDITIONAL - LANDLORD: A-5 REFLECTED CEILING PLAN / DETAILS AREA TO 13E EXCLUDED FROM NET AREA - 450 5F C05T5 OR DELAYS IN SCHEDULE WILL 5E ACCEPTED DUE TO G.C.'S M15-1NTERFRETATION5 AND FAILURES TO REQUEST CLARIFICATIONS. A-6 INTERIOR ELEVATIONS / RE5TROOM 7. DEVIATION FROM THE CONSTRUCTION DOCUMENTS REQUIRES THE WRITTEN APPROVAL OF THE OWNER AND/OR THE ARCHITECT, ZEPHYR COMMONS, LLC ENLARGED PLAN / ELEV5 NOTE: 8. USE DIMENSIONS A5 SHOWN ON THE DRAWINGS. DO NOT SCALE FROM THE DRAWINGS. WRITTEN DIMENSIONS & ALIGNMENTS SHALL GOVERN, ANY DISCREPANCIES, clo FKIMEKICA GROUP ONE, INC UNCONCENTRATED A55EMBLY w/o FIXED 5EATING - DINING CONFLICTS, OMMI5510N5, OR ERRORS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION AND/OR CORRECTION, G.C. SHALL 3629 MADACA LANE COMMERCIAL KITCHEN AREA5 - FREf KITCHEN, FOOD 5ERVICE AREA VERIFY ALL DIMENSIONS IN THE FIELD AND SHALL BE RESPONSIBLE FOR THEIR CORRECTNESS, NO EXTRA CHARGE OR COMPENSATION SHALL 5E ALLOWED 13ECAU5E OF TAMPA, FLORIDA 33615 STORAGE AREA - WALK-IN COOLER, DIFFERENCES BETWEEN ACTUAL DIMENSIONS AND TH05E INDICATED ON TEH DRAWINGS, UNLE55 THEY CONTRIBUTE TO A CHANGE IN THE SCOPE OF THE WORK. ANY AREA TO DE EXCLUDED FROM NET AREA - TOILET5, CORRIDOK5, WALLS, FIXED DIFFERENCES WHICH MAY BE FOUND SHALL BE 5U5MITTED TO THE ARCHITECT FOR DECISION PRIOR TO PROCEEDING WITH THE WORK. HORIZONTAL DIMENSIONS INDICATED PHONE: (813) 953-0629 MECHANICAL: COUNTEK5, COLUMNS FAX: (813) 935-3420 ,.�� ARE TO/FROM FINISHED FACE OF WALL U.N.O. VERTICAL DIMENSIONS ARE FROM FINISHED FLOOR U.N.O. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT APPROVAL OF � ARCHITECT UNLESS NOTED. CONTACT: CAROL SMIDDY M-1 FLOOR PLAN & NOTES - HVAC CALCULATED UNCONCENTRATED A55EM13LY - 1,368 5F / 15 = 93 FEK5ON5 9. ALL MATERIALS AND METHODS OF CONSTRUCTION SHALL COMPLY WITH E5TAB1_15HED STANDARD5 OR PRACTICES AS FUBLISHED BY RECOGNIZED AGENCIES, M-2 NOTES & DETAILS - HVAC OCCUPANT LOAD: COMMERCIAL KITCHEN - 922 5F / 200 = 5 PERSONS A550CIATION5 AND MAUFCTUKEK5 AND AFFLICASLE TO 5FECIFIC CONSTRUCTION TRADES. ARCHITECTURAL: M-3 FROTOTYFE HOOD INFORMATION (N.I.C.) STORAGE AREA - 105 5F / NA = 0 FEK5ON5 10. ALL CONSTRUCTION FKODUCT5 AND MATERIALS SHALL 5E STORED, HANDLED AND INSTALLED IN ACCORDANCE WITH ALL MANUFACTURER'S INSTRUCTIONS AND M-4 FROTOTYFE HOOD INFORMATION (N.I.C.) TOILETS & CORRIDOR - 450 5F / NA = 0 PERSONS RECOMMENDATIONS. ERIC SAFFRAN ARCHITECT M-5 FROTOTYFE HOOD INFORMATION ) TOTAL 98 PERSONS (N.I.C.) 11. G.C. TO PROTECT ANY EXISTING CONSTRUCTION AND ALL EXISTING ABOVE & 5ELOW GRADE UTILITIES. THE LOCATIONS OF EXISTING UTILITIES AND STRUCTURES SHOWN ( 3155 NORTH POINT PARKWAY, SUITE E-200 M-6 FROTOTYFE HOOD INFORMATION (N.I.C.) ON THE CONSTRUCTION DOCUMENTS ARE APPROXIMATE. THE G.C. 15 RE5FON515LE FOR VERIFYING THE EXISTENCE AND ACTUAL LOCATIONS OF SAME OR ANY NOT SHOWN ALFHAKETTA, GEORGIA 30005 PRIOR TO ANY EXCAVATION OR DEMOLITION. REPAIR OF DAMAGES RESULTING THEREFROM SHALL 5E BORNE BY THE G.C. PHONE: (770) 619-5916 2. IF 51TEWOKK 15 TO BE PERFORMED UNDER A SEPARATE CONTRACT, ALL WORK 15 TO BE COORDINATED WITH THE 51TE WORK DOCUMENTS. PROVIDE ALL WORK SHOWN FAX: (770) 619-5919 EGRESS WIDTH REQUIRED: 98 PERSONS x .2" FER FER50N = 19.6" ,��5 EREIN AND ALL CONNECTIONS TO UTILITY LINES LOCATED APPROX. 5 FT FROM SLDG. G.C. 15 RE5FON515LE FOR COORDINATING AND PERFORMING ALL WORK ADJACENT CONTACT: RICK SAFFRAN, AIA, NCARS PLUMBING: CALCULATIONS: PROVIDED: 3 x 36" WIDE EXIT DOORS = 108" TO AND/OR ABUTTING 51TE WORK, 50 A5 TO PROVIDE A COMPLETE AND FINISHED PRODUCT. IT 15 AL50 THE KE5FON5113ILITYOF THE G.C. TO NOTIFY THE ARCHITECT OF ANY DISCREPANCIES PRIOR TO COMMENCEMENT OF WORK. SANITARY & WATER FLOOR FLANS 13. G.C,TO PROVIDE ALL FIRE PROTECTION IN ACCORDANCE WITH ALL GOVERNING CODES AND AUTHORITIES. ALL FIRE SPRINKLER WORK SHALL BE PERFORMED BY A ELECTRICAL: F-1 SANTRAVEL DISTANCE: MAXIMUM ALLOWED = 200 FT. Zc��� LICENSED SPRINKLER CONTRACTOR PER NFFA 13. FIRE SPRINKLER AND FIRE ALARM PLANS SHALL BE PROVIDED SEPARATELY FOR REVIEW AND PERMITTING PRIOR TO P-2 GAS FLOOR PLAN &PLUMBING NOTED ACTUAL MAXIMUM = 86 FT. 1 I , �l�cl I INSTALLATION. ALL HEADS SHALL BE KECE55ED TYPE AND CENTERED IN ACOUSTICAL PANELS OR A5 SHOWN ON ARCHITECTURAL PLANS. JAMES E. TREMELLING, FE F-3 SANITARY RI5EK & ROUGH -IN SCHEDULE G� S & S- 14. ALL MAIN & BRANCH SPRINKLER LINES ARE TO BE RUN AS HIGH A5 F05515LE WITHIN THE ROOF 5TKUCTUKE SPACE WHEREVER THI5 15 F0551BLE. WHERE LINES ARE 4838 CAMPGROUND ROAD PLUMBING FIXTURES: PER TABLE 2902.1 (403.1) RUN BELOW ROOF STRUCTURE, THEY ARE TO BE HELD AS TIGHT AS F05SIBLE TO BOTTOM OF STRUCTURE. ALL LINES ARE TO BE 51-15FENDED FROM TOF JOI5T AND GIRDER ALEXANDER CITY, ALA13AMA 35010 CALCULATED OCCUPANCY LOAD - 96 PERSONS 2 CHORDS. ANY CHANGES IN LINE ROUTING ARE TO BE A5 900 PARALLEL TO STRUCTURE. PHONE: (250) 329-3557 ELECTRICAL: 98 IF" EK50N5 x 50% - 49 M 9WEN 15. FKOVIDE, LOCATE AND INSTALL ALL FORTASLE FIRE EXTINGUISHERS IN ACCORDANCE WITH NFFA 10 "FORTASLE EXTINGUISHERS". COORDINATE WITH THE LOCAL FIRE FAX: (256) 329-3570 ATEK CLOSETS _ PER 75 MEN = 1 - MARSHALL FOR ASSISTANCE. CONTACT: JIM TREMELLING, FE E-1 5FECIFICATION5/RI5ER DIAGRAM - 1 F WOMEN = 1 �� 16. G.C. 15 KE5FON515LE FOR PROVIDING ALL NECE55AY BLOCKING AS REQUIRED TO 5UFFOKT ELEC PANELS, ACCE55 ROOF LADDER, HANDRAILS, WALL MOUNTED LAVATORIES REQ'D = 1 FEP 200 AL = 1 51GNAGE, TOILET ACCESSORIES, CASEWORK, ETC. E-2 FLOOR FLAN - FOWER / 17. WOOD PRODUCTS THAT ARE USED IN NON-COM13U5TIDLE 5LDG5 SHALL BE FKE55URE-TREATED WITH AN APPROVED FIRE RETARDANT IN ACCORDANCE WITH THE 2000 MECHANICAL -PLUMBING: E-3 FLOOR FLAN - LIGHTING IB CODE. E-4 ROOF FLAN - FOWER / 18. ALL EXPOSED EXTERIOR WALL MOUNTED CONDUITS, GUTTERS, ELEC 13OXE5, PANELS 13OXE5, METERS, PIPES, ETC ARE TO RECEIVE MIN. ONE (1) COAT PRIMER AND TWO TRACY M. WOODALL, FE E-5 SCHEDULES / DETAILS / LEGEND APPLICABLE CODES / YEAR (2) COATS PAINT WITH ARCHITECT SELECTED COLOR. 181 5EDGEFIELD OVERLOOK 19. WOOD BLOCKING, PLYWOOD AND NAILEK5 IN CONTACT WITH CMU OR CONCRETE 5LDG COMPONENTS SHALL 5E FKE55UKE TREATED. DALLAS, GEORGIA 30157 ` 20. GUTTERS AND DOWNSPOUT SHALL 5E 20 GA. MINIMUM. PHONE: (675) 642-7252 FLORIDA BUILDING CODE (IBC 2006), 2007 EDITION, wl 2009 5upplemento 21. PROVIDE CONTINUOUS SEALANT OK CAULKING IN CONTROL AND CONSTRUCTION JOINTS, AROUND BOTH SIDES OF STOREFRONT FRAMING AND METAL DOOR FRAMES, FAX: (770) 406-2381 FLORIDA MECHANICAL CODE (IMC 2006), 2007 EDITION, wl 2009 5upplemente WHERE DISSIMILAR MATERIALS ABUT AND WHEREVER THE POTENTIAL FOR AIR OR MOISTURE INFILTRATION EXISTS, PROVIDE BACKER RODS WHERE SHOWN OR REQUIRED. CONTACT: TRACY M. WOODALL, FE NOTE: FOLLOW ALL MANUFACTURER'S IN5TUCTION5 FOR SURFACE FKEFAKATION AND APPLICATION. COLORS TO MATCH ADJACENT FINISHES. FLORIDA PLUMBING CODE (IPC 2006), 2007 EDITION, wl 2009 Supplements 22. COORDINATE WITH SIGN VENDOR FOR POWER REQUIREMENTS AND JUNCTION 50X LOCATIONS FOR 51GNAGE 51GNAGE SHALL BE PERMITTED SEPARATELY. PROVIDE 1-THE CONTRACTOR 15 RESPONSIBLE FOR CHECKING LL CONTRACT NATIONAL ELECTRICAL CODE (NEC), 2008 EDITION, w/ Amendments ALL REQUIRED IN -WALL BLOCKING. DOCUMENTS, FIELD CONDITIONS AND DIMENSIONS F K ACCURACY AND CONFIRMING THAT WORK IS BUILDABLE AS SHOWN EFORE PROCEEDING. FLORIDA FUEL GAS CODE (IFGC 2006), 2007 EDITION, wl 2009 Supplements 23. FINISH MATERIALS AND SURFACES SHALL BE CLA55 A WITH A FLAME SPREAD RATING NOT TO EXCEED 25. FLORIDA ENERGY CONSERVATION CODE, IECC 20045), 2007 EDITION, wl 2009 Su lements 24. ALL CEILINGS TO 5E CLA55'A' NON-COM5U5TIDLE TYPE. NO COM5U5TI5LE MATERIALS ARE TO BE PERMITTED ABOVE CEILINGS. CEIILNG 5YSTEM5 TO BE CONNECTED IF THERE 15 ANY QUESTION, THE CONTRACTOR 15 K 5FON51BLE` FOR ( pp TO STRUCTURAL MEMBERS AT JOIST TOF CHORDS OK ADDITIONAL 5UFFOKT5 ABOVE. DO NOT ATTACH TO UNDER SIDE OF ROOF DECK. OBTAINING A CLARIFICATION FROM THE ARCHITEC BEFORE FKOCEEDING FLORIDA FIRE FKEVENTION CODE (NFFA 1 & NFFA 101), 2007 EDITION 25. G.C. 15 TO BE RESPONSIBLE FOR PROVIDING ALL NECESSARY BRACING TO STRUCTURE, WHETHER OR NOT NOTED ON THESE DRAWINGS. WITH WORK IN QUESTION. \ FLORIDA STATE ACCE551131LITY CODE, 2007 EDITION 26. THE LOCATION OF MECHANICAL & ELECTRICAL EQUIPMENT AND FIXTURES SHOWN ON ELECTRICAL OR MECHANICAL DRAWINGS ARE FOR SCHEMATIC USE ONLY. REFER 2- NO MODIFICATIONS/REVISIONS/CHANGES 5HA L 5E UNDERTAKEN TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF SUCH EQUIPMENT AND FIXTURES. UNLE55 5FECIFICALLY 50 INSTRUCTED & AFFKOV D 5Y OWNER O� 27. G.C. TO PROVIDE OWNER WITH ORIGINAL WARRANTY DOCUMENTS ON ALL OFEKASLE ITEMS INCLUDING, BUT NOT LIMITED TO, HVAC SYSTEMS, WATER HEATER, ETC. AL50 ARCHITECT. INSURE THAT ALL SYSTEMS- MECHANICAL, ELECTRICAL, LIGHTING, FLUMBING, 5FRINKLER5, ETC ARE IN PROPER WORKING ORDER 13EPFOPIE TURNING OVER TO FRANCHISEE. 1"1 O U N TI N 0 H E 10 14T.5 28. G.C. TO REMOVE FROM THE JOB 51TE OR CONTAIN ALL CONSTRUCTION DEBRIS ON A DAILY 5A515, 29. G.C. 15 TO PERFORM FINAL CONSTRUCTION CLEAN-UF UFON COMPLETION OF WORK. 30. NONE OF THE DRAWINGS HEREIN SHALL BE CONSIDERED A5 COMPLETE OR FINAL, NOR SHALL THEY BE USED FOR CONSTRUCTION FURFO5E5, NOR AS THE 5A515 INTERCOM- FOR CONSTRUCTION CONTRACTS UNLE55 AND UNTIL THE AUTHORITY HAVING JURISDICTION HAS REVIEWED AND GIVEN THEIR FINAL APPROVAL OF THEM. THE APPROVAL NOTE: WHERE MOUNTING HEIGHTS ARE NOT INDICATED ON THE DRAWINGS, INSTALL COMFONENT5.1AT FROCE55 15 A CONTINUATION OF THE "DRAWING FKEFAKATION FHA5E". WHEREAS THE ARCHITECT AND/OR ENGINEERS HAVE MADE EDUCATED AND EXPERIENCED MOUNTING HEIGHTS REQUIRED BY THE M05T RECENT 155UE OF THE A.D.A OR LOCAL CODES FORAY THERMOSTAT SECURITY PANEL[ ��-� - - FIRE ALARM HORN INTERPRETATIONS OF THE VARIOUS AND RELEVENT BUILDING CODES, THE REVIEWING AUTHORITY HAS THE RIGHT TO FINAL AND BINDING INTERPRETATIONS OF SUCH � � � PARTICULAR APPLICATION INDICATED. REFER ANY QUE5TIONA13LE MOUNTING HEIGHT DECISIONS TO OR V15UAL ALARM CODES. FUK5UANT TO A BUILDING AUTHOKITY'5 PLAN REVIEW, THERE MAY BE ADDITIONS, DELETIONS, OR REVI5ION5 REQUIRED IN ORDER TO 05TAIN THEIR FINAL THE ARCHITECT FOR FINAL DECISION. FIRE ALARM FULL 5TRO13E APPROVAL. ANY RESULTING MONETARY C05T OR PROJECT DELAYS RESULTING FROM SUCH REQUIRED CHANGES SHALL NOT BE CONSIDERED THE RE51"ON5151LITY OR STATION o LIABILITY OF THE ARCHITECT AND/OR ENGINEERS. IN PURSUING THI5 PROJECT, ALL PARTIES AGREE TO HOLD THE ARCHITECT AND/OR ENGINEERS HARMLESS IN ALL WAYS IN SUCH MATTERS. 31. STANDARD GENERAL CONDITIONS: "THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION", AIA STANDARD FORM A-201 (COMPLETE CURRENT ADDITION) 15 HEREBY MADE A PART OF THESE CONSTRUCTION DOCUMENTS TO THE SAME EXTENT A5 IF HEREIN WRITTEN IN FULL. 32. PRIOR TO STARTING WORK, G.C. & APPROPRIATE 5U13CONTRACTOR5 SHALL THOROUGHLY EXAMINE THE SITE & THE CONSTRUCTION DOCUMENTS TO ENSURE THEIR O 0z KNOWLEDGE OF ALL RELEVANT FIELD CONDITIONS &REQUIREMENTS AFFECTING THE WORK. NO CLAIM FOR EXTRA COMPENSATION WILL BE ALLOWED FOR THE G.C.'5 OR Ll II0z M5U5CONTKACTOK'5 FAILURE TO COMPLY WITH THE REQUIREMENT. o M W o W J - = m 33. G.C. SHALL COORDINATE ALL ARCHITECTURAL, MECHANICAL, TELEPHONE, ELECTRICAL (INCLUDING LIGHTING), AND FLUMBING TO ENSURE THAT REQUIRED _I Q d Q O < CLEARANCES FOR INSTALLATION & MAINTENANCE OF ALL EQUIPMENT 15 PROVIDED. _ _ � �► o � 34. G.C. 15 KE5FON5113LE FOR ALL FERMIT5 & FEES. o o ~ 0 35 THE WORK SHALL BE DONE IKI ACCORDANCE WITH ALL RULES & REGULATIONS OF ALL APPLICABLE SAFETY & BUILDING CODES A5 WELL A5 THE AMERICANS WITH TRASH RECEPTACLE PAPER TOWEL DI5FEN5EK/TRA5H RECEPTACLE oz_ 12 TOILET/URINAL GRAB BAR PARTITION C dashed line indicates dimensional clearance of protruding objects) PAPER TOWEL SANITARY NAPKIN ELECTRIC COAT SOAP SHELF TELEPHONE FIKEH05E/ DISPENSER DI5FEN5EK HAND DRYER HOOK DISPENSER EXTINGUISHER CABINET 7"(MIN.) 14-1 9"(MAX.) - \ BO �. C� z N � - - Nt .� .;_7 TOILET TISSUE SANITARY ACCE5515LE ACCE55113LE DISPENSER NAPKIN URINAL TOILET P15FO5AL 51-LEVEL DRINKING FOUNTAIN Z Qw -V ^� J _ J U x to z - z w�Qmo� Q LL NIA - CV to N o<<n��� 'e D15ABILITIE5 ACT (ADA) ACCE551P>ILITY GUIDELINES. ALL MATERIALS AND 5Y5TEM5 SHALL BE INSTALLED A5 FEK MANUFACTURER'S RECOMMENDATIONS AND ALL BABY CHILD CONSTRUCTION SHALL 5E OF INDUSTRY STANDARD QUALITY OR BETTER. THE ARCHITECT SHALL BE ULTIMATE JUDGE OF QUALITY A5 5TTED IN AIA DOCUMENT A2-1, AND CHANGING PROTECTION SHALL COORDINATE SUCH WITH THE TENANT. STATION SEAT 36. G.C. SHALL CONTINUOUSLY CHECK ARCHITECTURAL AND STRUCTURAL CLEARANCES FOR ACCE55113ILITY OF EQUIPMENT AND MECHANICAL AND ELECTRICAL SYSTEMS. NO ALLOWANCES OF ANY KIND WILL BE MADE FOR THE G.C.'5 NEGLIGENCE TO FORESEE MEANS OF INSTALLING EQUIFMENT INTO POSITION WITHIN STRUCTURES. 9" MIN 37. G.C. 15 KE5FON5113LE FOR RECEIVING AND ON-51TE STORAGE OF ALL SOFT -GOODS AND EQUIPMENT (5MALLWARE5, ETC.) DURING REGULAR CONSTRUCTION HOURS. 6" 38. G.C. SHALL NOTIFY FRANCHISEE IN WRITING OF ANY DEFICIENCIES IN 5A5E BUILDING WORK FKIOR TO THE COMMENCEMENT OF THE WORK. ANY UNREPORTED ® \ f DEFICIENCIES WILL BECOME THE KE5FON51511-ITY OF THE G.C. TO CORRECT. 0 39. G.C. 15 RESPONSIBLE FOR, AND SHALL PROVIDE PROTECTION FOR ANY EXISTING FINISHES TO REMAIN. G.C. SHALL EXERCISE EXTREME CARE AND PRECAUTION DURING CONSTRUCTION OF THE WORK, AND SCHEDULE THE WORK TO MINIMIZE D15TURBANCE5 TO ADJACENT SPACES AND/OR STRUCTURES AND THEIR OCCUPANTS, - PROPERTY, FUSLIC THOROUGHFARES, ETC. G.C. SHALL TAKE PRECAUTIONS AND BE KE5FON515LE FOR THE SAFETY OF ALL BUILDING OCCUPANTS FROM CONSTRUCTION b N PROCEDURES. G.C. SHALL 5E RESPONSIBLE FOR ANY OVERTIME C05T5 INCURRED THEREBY. s o 40. ANY 1)I5CKEFANCIE5 OR CONFLICTS BETWEEN ARCHITECTURAL AND ENGINEERING DOCUMENTS (LIGHT FIXTURES, SWITCHES, THERMOSTATS, DIFFU5ER5, ETC.), MILLWORK, AND/OR FIELD CONDITIONS SHALL 5E CLARIFIED W/ THE ARCHITECT BEFORE INITIATING WORK. LAVATORY MIRROR CUP (" dashed line indicates DISPENSER dimensional clearance of optional underlavatory enclosure) KE5TROOM TELEPHONE, DATA, & 51GNAGE ELECTRICAL OUTLETS ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 I LIC # AR 12885 I w z w U Ln >* U z rn M Uj 0_ U. OJT O 0 tnCOU_ z O J Vj J O LA >- U _ w oC N CL - .. i_u N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN,ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEETTITLE COVER SHEET PROJECT NO 1030 COVER DRAWN BY DATE 11-23-10 1 OF 1 1 GENERAL REQUIREMENTS 1A-GENERAL REQUIREMENTS 1A-01. STANDARD GENERAL CONDITIONS A. Except as modified below, "The General Conditions of the Contract for Construction", AIA standard form A-201, 1987 Edition, Articles 1-14, is hereby made a part of these specifications to the same extent as if herein written out in full. 1 A-02. TENANT/OWNER/FRANCHISEE A. Wherever the terms "Tenant", "Owner" and/or "Franchisee" occur in the Documents, they shall refer to the following: Aeolus ZPH, Inc dba Five Guys Famous Burgers & Fries 19319 Autumn Woods Drive Tampa, FL 33647 Contact: Rama Kommireddy (813) 789-6115 B. Wherever the term "LANDLORD" occurs in the Documents, they shall refer to the following: Zephyr Commons, LLc c/o Primerica Group One, Inc 3629 Madaca Lane Tampa, FL 33618 Contact: Ms. Carol Smiddy (813) 933-0629 C. All questions or concerns related to these Documents shall be referred to TENANT'S REPRESENTATIVE or FIVE GUYS CONSTRUCTION REP: Mr. Brandon Higginbotham (404) 232-9216 1 A-03. CONTRACTOR A. Wherever the term "Contractor" occurs in the Documents, it shall refer to the General Contractor with whom the Tenant/Owner enters into a contractual agreement for the construction work described in these Drawings and Specifications. B. The Contractor shall coordinate his work and shall cooperate with any other separate Contractor(s) employed by the Owner, so as to avoid delays. 1A-04. DEFINITIONS A. "Furnished" and "supplied" are used interchangeably and have the same meaning. B. "Install" means receive and acknowledge delivery, unload, safely store, protect, assemble, set in place, secure, and connect as required to complete work. C. "Provide" means furnish and install. 1A-05. APPROVALS OF WORK TO BE PERFORMED A. Prior to beginning work, Contractor shall obtain in writing, or verify that approval has been granted by the following parties: 1. The Landlord, Landlord's Architects and Engineers 2. The local Building Inspector and local Fire Marshall 3. State authorities as required 1A-06. CORRELATION AND INTENT OF CONTRACT DOCUMENTS A. Prior to his bid submission, the Contractor shall examine the premises, and verify existing conditions, dimensions and Landlord requirements affecting the work under this Contract. Minor changes of dimensions or conditions necessary to fit new work to the existing in accord with the intent of the Contract Documents, may be made on the job. If major discrepancies are discovered between dimensions or conditions shown in Drawings and those actually existing, the Contractor shall report to the Owner, and shall not proceed with the work until the Contract Documents have been adjusted. 1A-07. BIDS & FORM OF AGREEMENT A. Standard forms of cost breakdown will be provided by the Tenant. B. At the discretion of the Tenant, the form of the Agreement shall be prepared by the Contractor and reviewed/amended by Tenant. 1A-08. COMPLIANCE WITH CODES, PERMITS AND LANDLORD REQUIREMENTS A. All work of the Contractor and Subcontractors shall conform to the provisions of all State, City and County Building Laws, Ordinances and Regulations, and to Landlord Requirements. In case of conflict, the most stringent requirement shall apply. B. G.C. to verify and coordinate all work to meet Landlord Drawings and Specifications, the Contractor shall give the Owner written notice specifying the proposed deviation, the costs involved, and the reason therefor. A Change Order shall be issued as specified in "Changes in the Work". D. Unless the law specifically requires the Owner to do so, the Contractor shall obtain all necessary permits and licenses, give all necessary notices, and pay costs of all incidental fees. E. G.C. to provide Landlord with a complete set of'as-builts', type as required by Landlord. F. G.C. to obtain and comply with any pertinent Landlord exhibits prior to commencement of construction. 1A-9.INSURANCE AND INDENTIFICATION A. The Contractor shall provide insurance as required by Tenant and Landlord. 1 A-10. HOLD HARMLESS AGREEMENT A. The Contractor agrees to indemnify and save harmless the Landlord, the Tenant/Owner, and the Architect, their agents and employees from and against any and all liability and damage arising from injuries to persons or damage to property occasioned by any act or omission of the Contractor, his Subcontractors, agents or employees, including any and all expenses, legal and otherwise, which may be incurred in the defense of any claim, settlement or suit. 1A-11. BARRICADES & SERVICE INTERRUPTIONS A. Contractor shall, at his cost, install and remove barricades required by Landlord. B. Contractor shall perform demolition required by the work, and shall remove from the premises resulting debris. During construction, all debris shall be contained within the tenant space. C. Unless otherwise specifically stated in the Contract Documents, all existing materials to be removed and not required to be reused, shall become the property of the Contractor. D. Services to occupied areas of the Landlord, including but not limited to electricity, water, air conditioning, plumbing, sprinkler, and telephone, must be maintained at all times. When service interruptions are unavoidable they must be arranged in advance with the Landlord. 1A-12. TEMPORARY UTILITIES A. Contractor shall coordinate with Landlord all temporary utility connections required to perform the work, and shall pay all charges for utilities during construction. 1 A-13. STORAGE A. The Contractor shall coordinate with the Landlord the storage of all building materials, tools, and equipment. B. The Contractor shall coordinate with the Landlord the delivery and transportation of materials through the building to the storage area. C. All storage to comply with Landlord requirements. 1A-14. SHOP DRAWINGS A. Prior to ordering equipment or fabricating fixtures, Contractor shall submit to the Tenant reproducible sepia Shop Drawings, product data or samples, if required, which reflect dimensions, utility requirements and installation requirements consistent with the Drawings. 1A-15. SUBSTITUTIONS A. All pricing shall be based on the construction documents without substitution or alteration. The General Contractor shall call out and clearly identify proposed substitutions. Proposed substitutions shall be reviewed by the Architect and Owner and they shall have final authority to accept or reject substitutions as "equal" to the specified item or assembly. Any qualifications to the bid proposing alternative systems, materials, methods, etc. (which in the General Contractors opinion reduce the total cost to the job) shall be outlined and attached to the bid for review by the Architect and Owner. If the General Contractor does not identify and receive Owner approval for substitutions, then the Owner retains the right to demand that the products or construction method originally specified be installed without additional expense to the Owner. 1 A- 16. TAXES A. Contractor shall assume liability for (1) sales taxes, (2) federal and state unemployment compensation and Social Security payments, and (3) all other federal and state required payments. 1 A-17. JOB SAFETY A. The Contractor shall take all necessary precautions for the safety of employees, and comply with applicable provisions of Federal, State and Municipal Safety laws to prevent accidents or injury to persons on or adjacent to the premises. B. Machinery, equipment, and all hazards shall be guarded or eliminated in accordance with the safety provisions of the "AGC Manual of Accident Provision in Construction" to the extent that such provisions are not contrary to applicable law or requirements of OSHA. 1A-18.OWNER'S RIGHT TO TERMINATE THE CONTRACT A. Should the Contractor neglect to prosecute the work properly, or fail to perform any provisions of the Contract, the Owner, after three (3) days written notice to the Contractor, without prejudice to any other remedy it may have, shall make good the deficiencies and may deduct the cost thereof from the payment then or thereafter due the Contractor, or, at its option, may terminate the Contract and take possession of all materials, tools and appliances and finish the work by such means as it sees fit, and if the unpaid balance of the Contract price exceeds the expense of finishing the work, such excess shall be paid to the Contractor, but if such expense exceed such unpaid balance, the Contractor shall pay the difference to the Owner, including administration costs associated with expedition of Section 1 A-18. 1A-19. GUARANTEES A. Unless specifically stated otherwise, all materials and equipment provided under this Contract shall be new and free from defects. B. The Contractor shall guarantee all work for a period of one (1) year from the date of acceptance by the Tenant/Owner/Franchisee. Lamps shall be guaranteed for a period of one month from acceptance. C. Contractor shall promptly correct all deficiencies which may appear in the work within one year of its completion arising from defective or improper material or workmanship, including all costs in connection with removal or replacement of the work. D. A Manufacturer's Warranty on any item shall not relieve the Contractor and/or his Subcontractor from full responsibility under all guarantees called for in the Specifications. E. All warranties or guarantees shall be written to the benefit of both Landlord and Tenant/Owner as their respective interests appear, and shall permit enforcement by either pparty. F. Original copies of all warranties shall be furnished to the Tenant/Owner/ Franchisee at the completion of the job. 1A-20. CLEANING UP A. Premises must always be kept free from waste materials. B. At completion of the work, millwork, floors, etc shall be cleaned. The Contractor shall remove his tools, scaffolding and debris, and shall leave the premises broom clean. C. Contractor shall assemble and transmit to the Tenant/Owner/Franchisee, maintenance and operation manuals, warranties and keys, and shall demonstrate to the Tenant/Owner, the usage of equipment. 1A-21. OWNER -CONTRACTOR AGREEMENT A. All items contained in the Plans and Specifications and the terms and conditions of the Owner - Contractor Agreement shall govern. 1A-22 MISCELLANEOUS CONSTRUCTION PROCEDURES A. The Contractor shall not attach or cause to be attached to any wall or structural member any equipment that may, by virtue of its size and weight, cause structural damage The Contractor shall not do anything that might in any way affect the structural integrity of the building. B. Protect existing building from damage throughout the construction period. Repair any such damage to match existing construction. C. All doors shall be made secure at the completion of each work day. The Contractor shall be solely responsible for the security of the site. D. G.C. shall comply with all Landlord security procedures for workers and vehicles. 5 METAL 5A-01. GENERAL A. All welding to comply with standards set by the American Welding Society's "Structural Welding Code". B. Take field measurements prior to fabrication. 5A-02. MATERIAL A. Exposed fastenings shall be same material, color, and finish as material to which applied. B. Metal shapes: material, size, and manufacturer as shown on Drawings. C. Primer paint to be compatible with required finish paint. 5A-03. INSTALLATION A. Provide fasteners as required to secure metal to existing construction. B. Grind welds smooth. 6 CARPENTRY 6A-CARPENTRY 6A-01. GENERAL A. All wall framing and furring shall be metal studs and channels. B. The Contractor shall submit shop drawings for all casework to Owner for approval prior to fabrication. C. The work of this section shall accommodate built-in electrical & plumbing work, and provide adequate space for lighting, concealed conduit and cable runs, and removable sections of casework where required for access to conduit, wire boxes, ballasts, etc. Verify locations of all such concealed items and indicate same on shop drawings. This work shall be coordinated with electrical & plumbing work. 6A-02. MATERIALS A. Blocking shall be Southern Yellow Pine, No. 2, S4S or cut to shape as required, kiln dried to 19% maximum moisture, treated with Celcure, and be fire -retardant pressure treated. B. Rough hardware shall meet the standards of the trade and the needs of the work. Powder activated fasteners shall be of the type and size suitable for the intended use. C. Medium Density Fiberboard (MDF) shall be attached to metal studs with steel screws. D. Medium Density Fiberboard (MDF) shall be attached to masonry with metal furring and screws. 6A-03. INSTALLATION A. Carpentry work shall conform to the best standards of the practice. Work shall be laid out in accordance with the Drawings, and to accommodate work of other trades. B. Doors and hardware shall be installed so that doors will swing easily, quietly and freely, and close accurately against stops without binding. Latch bolts must engage positively with strikes when doors are closed. C. Provide all necessary bracing to structure for partitions, ceilings, platforms, etc., whether or not called for on Drawings. D. Provide all necessary in -wall framing and blocking required to carry shelving, standards, valances, etc., whether or not called for on Drawings. E. All casework fasteners to be concealed. All casework wiring to be concealed. F. All exposed plywood surfaces, both faces of doors and drawers, and all edges shall be finished in plastic laminate. G. Install all work plumb, level, true, aligned, and straight with tight joints and no distortions. Shim as required using concealed shims. Install to a tolerance of 1/8" in eight feet, 1/32" max. offset in flush adjoining surfaces. H. Scribe and cut work to fit adjoining work, and refinish cut surfaces. J. Install all exposed finish material with minimum number of joints possible, using full length pieces to the greatest possible extent. 8 DOOR & HARDWARE, GLAZING 8A-DOORS & HARDWARE 8A-01. GENERAL A. Doors and hardware shall be of size, material, and finish as shown on Drawings. B. Rolling grilles shall be of material and manufacturer as shown on Drawings. The Contractor to verify exact size required. Submit shop drawings to Tenant for approval prior to fabrication and installation. 8A-02. MATERIALS A. Refer to Drawings for door materials and hardware specifications. B. Provide "Best" cylinders with removable 7-pin cores to match the Landlord's keying system requirements, if applicable. Provide construction cores and keys. 8A-03. INSTALLATION A. All hardware shall be tight, level, and shall operate smoothly and easily. Follow manufacturer's instructions for installation and adjustment. B. Door levers to be mounted 42" o.c. above finished floor, verify finish with Tenant. 8B-GLAZING 8B-01. GENERAL A. Provide glass in sizes and thickness shown on Drawings. If thickness is not shown, provide the minimum thickness required for sheet size and application. 8B-02. MATERIALS A. Glass: clear, tempered glass (glazing quality). B. Mirrors: 1/4" thick, mirror glazing quality tempered plate or float glass with silver coating and electrolytically copper plated back. Provide industry -standard adhesive. C. All glass and mirror to have polished edges. 8B-03. INSTALLATION A. Provide all shims, blocks, glazing compounds, and other appurtenances required for a first-class installation in accordance with standard trade practice. 9 FINISHES 9-01. GENERAL A. Any combustible interior finish material, surface or product shall be provided per the requirements of the respective occupancy chapter of the NFPA 101 Life Safety Code current Edition, that this project is being permitted under. Provide verification at the time of final inspection that the products comply with the requirements. 9A-GYPSUM DRYWALL 9A-01. GENERAL A. All finish materials and surfaces shall be class'C' with a flame spread rating not to exceed 25. B. All wall framing and furring shall be metal studs and channels to ceiling @ 24" o.c. with bracing to structure @ 48" o.c. (max.) C. In -wall blocking shall be provided at all wall -hung items. 9A-02. MATERIALS A. Gypsum wallboard shall be ASTM C36 "Sheetrock" as manufactured by the U.S. Gypsum Co., or equal. Thickness and type as noted, with tapered edges. Use Type X gyp. board where fire rating is required. B. Joint reinforcing tape, adhesive and metal corner reinforcement to be standard products recommended by the Wallboard Manufacturer. C. Fasteners shall be self -drilling, self -tapping, countersunk, bugle -head drywall screws for attachment of wallboard to metal studs. Use gypsum wallboard nails for attachment to wood studs. D. Structural studs shall be punched or unpunched, 16 gauge steel having a minimum yield point of 33,000 psi, sizes as indicated. E. Non -load -bearing studs shall be, channel -type, roll -formed from 20 gauge electro-galvanized steel, sizes as indicated. (unless otherwise shown) F. Furring channels shall be roll -formed, 25 gauge minimum, electro-galvanized steel hat section with wing flanges, sizes as indicated. 9A-03. INSTALLATION A. Installation of "Sheetrock Firecode" shall be in accordance with Manufacturer's Recommendations for fire -rated partitions. B. Gypsum wallboard shall be attached to metal studs with steel screws. All joints shall be taped and finished smooth with spackling compound. C. Gypsum wallboard shall be attached to masonry with metal furring channels and screws with all joints taped and finished smooth. 91191-RESILIENT FLOORING 913-01. MATERIALS A. See Finish Schedule for size,color, and manufacturer. B. Edge and reducer strips shall be molded rubber at all locations where edge of tile would otherwise be exposed. Strips to finish flush with surface of flooring. C. Bases to be set -on type rubber. See Finish Schedule. D. Adhesive shall be type as recommended by Tile Manufacturer. 9B-02. INSTALLATION A. Check floor for clean, dry condition, and the surface for imperfections and unevenness Contractor shall correct surfaces prior to beginning installation. Faulty work due to imperfect slab conditions will not be accepted. Minor imperfections such as pits and scratches shall be filled by Flooring Contractor with "Floor Stone" or other approved non -gypsum, non -lime leveling material, shrink -proof and water resistant. B. Application shall not begin until the work of all other trades, including painting, is complete. Maintain all rooms and sub -floors at a minimum of 70 degrees F. for at least 48 hours before, during, and 48 hours after application of tile. C. Follow printed instructions of the Tile Manufacturer, especially regarding the storage and application of tile, cement and base. D. Upon completion of the installation, clean floors and base as recommended by tile manufacturer and leave in satisfactory condition. 9B-03. GUARANTEE A. Guarantee resilient flooring work in writing against defects in labor and materials for a period of one year from date of acceptance. 9C- TILE 9C-01. GENERAL A. Comply with minimum temperature recommendations of manufacturers for factory mixed setting and grouting materials. 9C-02. MATERIALS A. See Finish Schedule for size and manufacturer / distributor of tile. B. Setting materials: Use mortar formula for thin -set cement of the Tile Council of America, as manufactured by L&M SURCO, Inc., or equal. C. See Finish Schedule for grout specification and manufacturer. D. Provide edge strips as shown on drawings. 9C-03. INSTALLATION A. Apply over concrete, waterproof gypsum wallboard, sealed plywood, or other materials as indicated on Drawings, using approved thin -set cement formula. B. Clean and level all surfaces as necessary to provide even surfaces, level, true and plumb. C. In the event surfaces to receive tile are not acceptable, notify the appropriate party prior to tile installation. D. Center tile within tiled area as shown on Drawings. E. Terminate work neatly at obstructions, edges, and corners without disrupting pattern or joint alignments. F. Jointing pattern: unless otherwise shown, lay tile in grid pattern. Provide uniform joint widths. G. Clean tile as work progresses, preventing accumulation of setting and grouting materials or debris on tile faces. 9D-PAINTING AND FINISHING 9D-01. MATERIALS A. Paint shall be brought to the jobsite in unopened containers. See Finish Schedule for type, colors and manufacturer. B. Mix paint only in accordance with the Manufacturer's printed instructions. Turpentine shall be distilled, and oil shall be boiled and filtered linseed oil. C. Oil -based paints and enamels shall be factory prepared and packaged materials by approved Manufacturers. 9D-02. WORKMANSHIP A. Inspect all surfaces to be painted and report deficiencies prior to beginning painting. B. Point up holes and cracks, remove all grease, stains and excess mortar by wire brushing before painting. C. All surfaces shall be dry and sanded properly. Fill small nail holes with putty, and larger voids with plastic wood and sand smooth. All millwork not primed before delivery shall be primed or sealed immediately upon arrival at the job site. D. Allow ample drying time between coats, and sand properly to give a smooth finish. Carefully cover back edges of trim, edges of doors, and touch up any places marred by installation of hardware or work of other trades. E. Seal door edges immediately after fitting. F. Carefully protect other work and leave the job clean. 9D-03. CLEANING A. On completion remove all surplus materials and scaffolds from the premises and leave the premises clean. B. Remove all paint from floor, hardware, glass and other surfaces not painted. C. Touch-up as necessary after patching and repair of other trades. 9E-ACOUSTICAL WORK 9E-01. MATERIALS A. Acoustical panels shall be as shown on Finish Schedule. Install as per Manufacturer's Recommendations. B. Ceiling suspension system shall include all main tees, cross tees, wall moldings, and all other accessories required for a complete installation. Maximum dimension between supports shall be 48 inches. C. All ceilings to be class 'A' non-combustible type. No combustible materials are to be permitted above ceilings. Acoustical tile ceiling and suspension system shall conform to all applicable codes and standards. 9E-02. FIRE -RATED CEILING A. Where required by the Drawings or where required to conform to fire rating regulations of the Local Building Authority, provide hold-down clips for ceiling tile plus all other accessories necessary for a complete fire -rated installation. 9E-03. INSTALLATION A. Installation of the ceiling shall be the pattern indicated on the reflected ceiling plan, and shall coordinate with mechanical, electrical and sprinkler system requirements. B. All items to be supported shall be hung with wires of the size and spacing to support the ceiling system and all other and all other work supported therefrom. Maximum spacing of wires shall be 48 inches o.c. Hangers shall be not less than 12-gauge galvanized steel wire. Ceiling suspension system to be connected to structural members at joist top chord or additional supports above. C. System shall be square and level with deflection not to exceed 1/8 inch in 10 feet. 9E-04. CLEANING A. Grid and all tiles shall be thoroughly clean and free from marrs, cuts, indentations, spots, foreign paint and other blemishes and imperfections, or shall be replaced. 9E-05. REPLACEMENT MATERIALS A. Contractor shall provide five (5) full tiles of replacement material at the completion of the project. G.C. to mark outside of box "EXTRA CEILING TILES". 9E-06. WARRANTY A. Provide ceiling system guarantee in writing against defects in labor, materials, and maximum deflection of 1/1 80th of the span for a period of one year from the date of owner acceptance. 9F-WALL COVERING 9F-01. MATERIAL A. Adhesive: ready mixed, mildew resistant, non -bleeding, non -staining, freeze/thaw stable, as recommended by the wall covering manufacturer for substrate and compatible with primer. Adhesive shall allow strip -ability without damage to primed wall surface. B. Primer: as recommended by wall covering manufacturer. 9F-02. INSTALLATION A. Prime wall surfaces to receive wall covering. B. Do not overlap wall covering panels. C. Apply adhesive to wall for installation of fabric wall covering, not to wall covering. D. Trim edges tightly against abutting materials, maintaining smooth, even line and tightly bonded edge, unless otherwise shown on details. 10 SPECIALTIES 10A-SPECIALTIES 10A-01. FIXTURES AND EQUIPMENT INSTALLATION A. Contractor shall accept and acknowledge delivery, provide all labor and material necessary to suitably store and install all casework, fixtures and equipment shown to be installed on the Plan. 10A-02. MISCELLANEOUS SPECIALTIES A. Furnish and/or install specialties as shown on the Plan, unless otherwise noted. 10A-03. SIGNS A. Illuminated and non -illuminated STOREFRONT signs and lettering shall be furnished and installed by Contractor unless otherwise noted within these Contract Documents. The Contractor to submit Shop Drawings to Landlord and Tenant for approval prior to fabrication. B. Non -illuminated wall plaques, decals and logos furnished by Tenant and installed by Contractor, if indicated on plans. C. The Contractor shall obtain artwork for all signage from Tenant. D. The G. C. shall apply for, pay for, and provide any separate sign permits that may be required by the Landlord, or local or state governing bodies. 15 MECHANICAL 15A-HVAC 15A-01. GENERAL A. Provide complete Heating, Ventilating and Air Conditioning System to conform with applicable Local, State and National Codes and Standards, and with Landlord's requirements. B. Provide mechanical equipment, grilles and diffusers as scheduled. Provide air distribution system indicated, temperature controls, any necessary control wiring, and fire and smoke protection which may be required. C. Verify the location of existing structural members and coordinate equipment locations. & installations. D. The location of mechanical and electrical equipment and fixtures shown on Mechanical and Electrical Drawings are for SCHEMATIC USE ONLY. Refer to Architectural Drawings for exact location of such equipment and fixtures. The Contractor shall field verify all existing construction to remain and verify that each light fixture, diffuser, etc. will fit where shown on Architectural Drawings. If adjustment is necessary, the Contractor shall notify the Tenant of situation. The Contractor will adjust location of fixtures and equipment (after approval from Tenant) up to 1 U-0" from location shown on Architectural Drawings without Tenant incurring additional charges. 15B-SPRINKLER SYSTEM 15B-01. GENERAL A. The Contractor is to provide all fire protection in accordance with all governing codes and authorities. The Contractor shall provide a sprinkler plan if required by the landlord or authorities. B. The Contractor shall provide for (in his bid) any necessary work to smoke detection and/or life safety systems that may need to be modified or provided. G. C. to verify requirements with Landlord and/or local authorities as to type of system, local company providing servicing of system, etc. C. All new sprinkler heads shall be located to the center of all ceiling tiles unless noted otherwise on construction documents. 16 ELECTRICAL 16A-ELECTRICAL 16A-01. GENERAL A. Electrical work shall conform to applicable Codes and Ordinances, and to Landlord's requirements. Electrical Contractor shall verify sizes and locations of Landlord's stub -ins, and shall connect to the most convenient acceptable point. B. Electrical Contractor shall provide service and make connections to all HVAC, signs and items labeled to be furnished by others and installed by Contractor. C. Fit all work according to the relationships indicated on Drawings. Do not scale Drawings for exact locations. D. Furnish and install all power wiring to motors, heaters and mechanical equipment indicated. Wiring into motor or equipment terminals shall be complete with connections through associated motor starters and disconnect switches. 16A-02. PANELS AND TRANSFORMERS A. All panels shall be UL-labeled. The main distribution panel shall be UL-labeled as service entrance equipment. 16A-03. MATERIALS A. All materials, apparatus and equipment shall be new and bear the UL-label. 16A-04. LIGHTING A. See the "Lighting Schedule". All fixtures shall be installed complete with new lamps of the proper type, wattage and voltage rating. Ballasts shall be high factor CBM and ETL labeled with integral fuse link, energy -saving type, as indicated. 16A-05. TELEPHONE A. Telephone system requirements shall be coordinated with the Tenant/ Owner?franchisee and local Telephone Company, Conduit to be supplied to the points indicated or required. B. Temporary telephone system shall be maintained by the Contractor at the site for use by the Construction Trades and Owner's Site Personnel at the Contractor's C. G.C. shall be responsible for providing telephone service cble from Landlord/telephone service cable from Landlord/telephone distribution points located within the building. D. All wiring must be installed in fire -stopped sleeves when passing through partitions. E. All wiring must be plenum rated. ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 11 �23'l o LIC # AR 12885 REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFYTHE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OFTHE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE SPECIFICATIONS PROJECT NO 1030 DRAWN BY M9pFW C EJ5 DATE 11-23-10 1 1 OF 1 LM Q FLOOR PLAN NOTES: GENERAL: - CONCRETE 5LA5 TO BE PATCHED SMOOTHED AND MADE READY FOR NEW FINISHES. - PATCH (TAPE & 5FACKLE), SAND, AND REPAIR EXTERIOR & DEMISING WALLS. FREFARE FOR NEW FINISH, WHERE APFICASLE - REFER TO PARTITION LEGEND FOR WALL TYPES, SHEET AM - ALL NEW AND EXISTING NON -FIRE RATED PARTITIONS TO RECEIVE 5/6" DUROCK (1/2" MIN), FROM SLAB TO V-4 3/4" AFF INSTEAD OF GYPSUM BOARD IN TILED AREAS. ALL NEW & EXISTING NON -FIRE RATED WALLS TO RECEIVE 5/8" DUROCK (1/2" MIN), FROM SLAB TO 24" AFF INSTEAD OF GYPSUM BOARD IN COOK/KITCHEN/5ERVICE AREAS (5/8" PLYWOOD FROM 24" AFF TO CEILING IN COOK/KITCHEN/SERVICE AREAS). AT FIRE RATED PARTITIONS DO NOT REPLACE GYP. BOARD WITH DUROCK OR PLYWOOD - AT FIRE RATED PARTITIONS, G.C. SHALL MAINTAIN INTEGRITY OF FIRE RATED A55EMBLY AND LAMINATE NEW DUROCK BASE WITH GYP. BOARD OR PLYWOOD ABOVE (A5 SPECIFIED IN NOTE ABOVE) DIRECTLY TO FACE OF FIRE RATED PARTITION - CAULK MILLWORK TO PARTITIONS AND AT ALL CRACKS AND CREVICES - G.C. TO REPAIR/REPLACE WINDOW SHADES WHERE AFFICA5LE - G.C. SHALL FURNISH FIRE -RETARDANT -TREATED WOOD IN ALL ENCLOSED SPACES - ALL EXPOSED CORNERS ON COUNTERS, SHALL BE ROUNDED - REFER TO EQUIPMENT PLAN FOR TRENCH DRAIN LOCATIONS @ SERVICE & PREP AREAS - ALL ROOFING WORK AND PENETRATIONS TO BE PERFORMED BY L.L. ROOF CONTRACTOR @ G.C. EXPENSE. G.C. TO PROVIDE, A5 REQUIRED, VERIFICATION OF EXISTING STRUCTURE TO CARRY ALL NEW ROOF MOUNTED EQUIPMENT. G.C. TO PROVIDE AS REQUIRED, STRUCTURAL DESIGN FOR, AND ALL NECESSARY ADDITIONAL ROOF REINFORCEMENT & BRACING - ALL OUTSIDE CORNERS IN KITCHEN & DINING TO RECEIVE STAINLESS STEEL CORNER GUARDS, 5A5E TO 60" AFF (AT TILED AREAS IN DINING, FROM 5A5E TO TOP OF TILE - SEE DETAIL, SHEET A-4) - WHERE WALL TYPES ARE NOTED AS SIMILAR (SIM), REFER TO FINISH PLAN FOR CLARIFICATION OF WALL FINISHES 1. WORK DESK MILLWORK: G.C. TO FURNISH WHITE PLASTIC LAMINATE (FL-2) COUNTER AND ADJUSTABLE WHITE PLASTIC (FL-2) SHELVING ABOVE. SEE ELEV.,, SHEET A-2 G.C. TO FURNISH 1" METAL CONDUIT, SHOWN DASHED, FROM SANDWICH WALL TO F05 WALL FOR FOS SYSTEM 3. MILLWORK COUNTER - PROVIDE RED CORIAN SOLID SURFACE (C) COUNTERTOP - PROVIDE FRF ON REAR FACE - SEE DETAILS, SHEET A-2 SEE ELEVATIONS, 5HEET A-6 4. NEW HALF HEIGHT PARTITION (HEIGHT VARIES) - SEE INTERIOR ELEVATIONS & PARTITION LEGEND. 5. EXISTING WINDOW/STOREFRONT TO REMAIN (TYF). REKEY D00R5 FER TENANT & PROVIDE PANIC HARDWARE. 6. EXISTING REAR DOOR TO 5E LOCKED IN THE CLOSED POSITION. 7. PROVIDE 24"W x 18"D x 6"H CONCRETE CURB BENEATH SAFE; CONFIRM LOCATION/51ZE W/ FRANCHISEE PRIOR TO CONSTRUCTION 8. PROVIDE 6" METAL STUDS 9 NEW PARTITION AS NEEDED. HATCHED WALL AT OFFICE INDICATES 6" BEARING WALL (15 GA 6" METAL STUDS (6005162-43) 0 12" O.C.) 9. IN SERVICE AND FKEF AREA5, AT EXISTING CMU REAR WALL G.C. SHALL APPLY ONE LAYER 5/8" DUROCK FROM FLOOR UP TO 24" AFF, W/ ONE LAYER 5/8" PLYWOOD FROM 24" AFF TO CEILING W/ FRF FINISH OVER 7/8" FURRING (OR 3 5/5" METAL STUDS AT FLUM5ING WALL). AT EXISTING GYF BD LAMINATE ONE LAYER 5/8" DUROCK FROM FLOOR OF TO 24" AFF, W/ ONE LAYER 5/8" PLYWOOD FROM 24" AFF TO CEILING W/ FRF FINISH. 10. APPROXIMATE LOCATION OF 6" FVC SLEEVE (SHOWN DASHED) FOR 5ODA LINE FROM A50VE CEILING TO INSIDE DRINK CABINET. CONFIRM SLEEVE W/ BEVERAGE VENDOR PRIOR TO INSTALLATION. PROVIDE EXTRA SODA LINES TO RUN BELOW 5LA5. 11. ELECTRICAL PANEL LOCATION - SEE ELECTRICAL DRAWINGS 12. TRENCH DRAIN & FLOOR SINK SHOWN DASHED. SEE FLOOR & EQUIPMENT PLANS AND FLUM5ING DRAWINGS 13. DASHED BOX INDICATES HANDICAP ACCE5515LE FLOOR & APPROACH CLEARANCE (TYP) 14. NEW TELEPHONE BOARD LOCATION - SEE ELECTRICAL DRAWINGS 15. AT PUBLIC AREAS, AT EXISTING CMU WALLS, APPLY 5/8" DUROCK TO 4'-4 3/4" WITH 5/8" GYF BOARD A50VE ON 7/5" FURRING - FINISH WITH CERAMIC TILE AND PAINT (SEE FINISH PLAN AND ELEVATIONS). 16. DASHED LINE INDICATES LOCATION OF NEW WALK-IN COOLER 17. EX15T'G REAR EXIT DOOR TO REMAIN- REKEY PER TENANT, PROVIDE HARDWARE FER SCHEDULE, PROVIDE KICK PLATE ON INTERIOR SIDE. 18. TOILETS AS SHOWN ARE BEING BUILT BY LANDLORD'S CONTRACTOR. SEE ENLARGED TOILET PLANS AND ELEVATIONS ON A-6. PROVIDE ALL FINISHES AND ACCESSORIES NOT PROVIDED BY LANDLORD. 19. PROVIDE 5TAINLE55 STEEL SUPPORT LEG W/ SCREW TYPE LEVELLER @ UNDERSIDE OF MILLWORK COUNTERTOF - FLANGES AT TOP & BOTTOM (SEE PLAN FOR SPACING) 20. EXISTING ONE HOUR FIRE RATED DEM151NG PARTITION (SHOWN HATCHED) TO REMAIN. SEAL ANY OPENINGS W/ UL APPROVED MATERIALS (SEE DETAIL THIS PAGE). LAMINATE 5/8" DUROCK AND 5/5" GYP 51) OR PLYWOOD OVER DEM151NG PARTITION (SEE BOLD NOTES ABOVE). 21, G.C. TO PROVIDE 5TAINLE55 STEEL FINISH, OVER ONE LAYER 5/5" DUKOCK FROM FLOOR TO CEILING BEHIND COOK LINE HOOD. CONFIRM REQUIRED LENGTH OF 5T. 5TL. W/ EQUIPMENT VENDOR. 5TAINLE55 STEEL FINISH SHALL EXTEND A MINIMUM OF 18" BEYOND HOOD ON EACH SIDE ANY WOOD 5LKG IN WALL OR PLYWOOD ON OFF051TE SIDE OF WALL (WITHIN 15" OF HOOD) SHALL 5E FIRE RETARDANT TREATED. 22. PROVIDE H05E BIB CENTERED ON BACK WALL OF WALK-IN AT 18" 5ELOW WALK-IN CEILING (COODINATE WITH WALK-IN SHOP DRAWINGS) 23. NEW 4" THICK CONCRETE SLAB TO 5E PROVIDED AT REAR 10' WIDE SLOCKOUT. NEW 5LA5 TO ALIGN W/ EXISTING ADJACENT 5LA5. NEW 5LA5 TO 5E 3000 F51 CONCRETE (MIN) OVER 10 MIL VAPOR BARRIER, REINFORCED W/ WIRE MESH. DOWEL INTO EXISTING ADJACENT SLAB 6" DEEF W/ #4 BARS 0 4'-0" O.C. DOOR SCHEDULE NO. LOCATION SIZE DOOR FRAME RATING HARDWARE / REMARKS TYPE FINISH MATL FINISH lOOA ENTRY DOOR EXIST'G „ 3 -0 x 7 D 1 ALUM & TEMP GLASS EXIST'G EXTRUDED ALUM EXIST'G ----- - REKEY FER TENANT; PROVIDE PANIC HARDWARE G.C. TO ENSURE THAT: 100E ENTRY POOR EXIST'G 1 ALUM & TEMP EXI5T'G EXTRUDED EX15T'G ----- 3'-0" x 7'-0" GLA55 ALUM A. THRE51HOLD5 DO NOT EXCEED 1/2" B. DOOR FU5H FULL FORCE DOE5 NOT EXI5T'G ALUM & G EX15T'G EXTRUDED EXIST'G ----- IOOC PATIO D00R 3'-0" x 7-0" 1 GLA55 ALUM EXCEEED 8-1/2 1_135. MODEL 5CF-CAFE A5 MFD. 5Y ELIA50N, W/ KITCHEN 5TAINLE55 ALL ARE & ACCESSORIES 5TAINLE55 101 COUNTER GATE FK 1" x 1'-6"W x 2'-2"H EXT. 5C WI) 5TL _--- ---- ----- 5TL F A 5H 5TKAIGHT CUT, MOUNT TO COUNTER MODEL 5CG-3 AS MFD. BY ELIA50N, W/ 15TEEL 5TAINLE55 5TAINLE55 9"X14" WINDOW. FULL LENGTH 5TAINLE55 102A PREP ROOM PR 1" x 1'-6" x 6'-8" 3 EXT. 5C WE) 5TL H.M. 5TL ----- FANEL5 50TH SIDES. ALL HARDWARE & ACCESSORIES 5TAINLE55 5TL 1028 REAR EXIT EX15T'G 4 H.M. FAINT F-4 0 H M FAINT F-4 0 INTERIOR ----- REPLACE W/ HARDWARE SET #2 3-0 x 7-0 INTERIOR 102C PREP ROOM 3'-0" x 7'-0" 2 H.M. PAINT F-4 H.M. PAINT F-4 ----- HARDWARE SET #3 G ND/OR 103 MEN'5 TOILET 31-011 11 3 -0 x 7 -0 2 H.M. FAINT F-4 H.M. FAINT P-4 ----- REPLACE W HA DWAKE 5ET # EXIST'G EXISTING HARDWARE -ADD AND/OR 104 WOMEN'S TOILET 3'-0" x 7,-0" H.M. FAINT P-4 H.M. PAINT F-4 REPLACE W/HARDWARE SET #1 REPLACE HARDWARE SET #3 105 OFFICE 3'-0" x 7'-0" 2 H.M. PAINT P-4 H.M. FAINT P-4 _____ PROVIDE 1" UNDERCUT HARDWARE SET #3 106 OFFICE 3'-0" x 7'-0" 2 H.M. PAINT F-4 H.M. PAINT P-4 ----- FROVIIDE 1" UNDERCUT NOTES: 1. ALL DOOR HARDWARE SHALL BE HANDICAP ACCE5113LE (ADA APPROVED) W/ MAX EFFORT TO 5E 5 L135 INTERIOR; 81/2 LB5 EXTERIOR. 2. LOCK5ET5 TO MFD 5Y 5CHLAGE, "AL 5EKIE5 5ATUKN" DE51GN HANDICAP ACCE515LE LEVER 3. ALL HARDWARE 5HALL 5E HEAVY DUTY COMMERCIAL GRADE. 4. CENTERLINE OF HARDWARE MOUNTING HEIGHT 5HALL BE BETWEEN 33'' AND 44" AFF 5. REKEY ALL EXI5TING HARDWARE - PROVIDE MA5TER KEY FOR ALL DOOK5. 6. ALL HARDWARE 5HALL HAVE FIN15H #U526D (SATIN CHROMIUM PLATED) 7. EACH DOOR LEAF TO HAVE: a. 51LENCER5 A5 MFD BY TRIMCO OR EQ b. DOOR 5TOP5 A5 MFD BY TRIMCO OR EQ 8. AT 5TOREFKONT DOOR5 #100A 1008 & 100C PROVIDE 51GNAGE IN 1" HIGH LETTER5 ON CONTKA5TING BACKGROUND TO READ "THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING 15 OCCUPIED" 9. AT 5TOKEFKONT DOOK5 #100A & 1005 PROVIDE PANIC HARDWARE TO MATCH DOOR MFR STANDARD 10. ALL DOOR5 TO REMAIN KEYLE55 IN THE DIRECTION OF EGRE55 11. PROVIDE 1" UNDERCUT AT OFFICE DOOR5 #105 AND #106 HARDWARE SETS HARDWARE 5ET #1 a. HINGE5 -11/2 PR, 5TEEL, BALL BEARING TYPE D. PRIVACY LOCK5ET (ADA ACCE5515LE) c. C1_05EK -HEAVY DUTY d. DIAMOND PLATE KICK PLATE- 34" H (BOTH 51DE5) e. ADA APPROVED 51GNAGE HARDWARE 5ET #2 a. HINGE5 -11/2 PR, 5RA55, BALL BEARING TYPE W/ NON -REMOVABLE PIN5 b. PU5H BAR EXIT DEVICE W/ ENTRY LOCK5ET TRIIM c. CL05ER - HEAVY DUTY d. ALARM - DETEX V40xE13 W/08-13KN-689 OUT5IDE TRIM\ e. DIAMOND PLATE KICK PLATE- 34" H (INTERIOR 51DE) f. FEEPHOLE & BUZZER #1 #2 #3 3'_21/2" n__r , ,ALE PANIC DEVICE (9 INTERIOR) KICK PLATE (TYF) 45'-4" FLOOR PLAN A-1 f 5CALE:1/4" = 1'-0" ONE HOUR PARTITION A55EM13LY - UL PE51GN #U465 25 MSG. 3 50' W/ 1 1/4" LEGS (MIN) FLOOR AND CEILING RUNNERS ATTACHED TO FLOOR AND CEILING W/ FASTENERS AT 24" O.C. (MAX). ONE LAYER 50' TYFE'X' GYF5UM WALLBOARD ATTACHED TO EACH SIDE OF FLOOR AND CEILING RUNNERS AND 25 MSG. 3 5/8" W/ 1 1/4" LEG5 (MIN) METAL 5TUD5 W/ 50' LIPS (MIN), 5FACED 24" O.C. WITH 1" TYFE'5' DRYWALL SCREWS 8" O.C. ALONG EDGES OF BOARD AND 12" O.C. IN FIELD OF BOARD. JOINTS ORIENTED VERTICALLY AND STAGGERED ON OFF051TE SIDES OF THE A55EMBLY. JOINT COMPOUND APPLIED IN TWO COATS TO JOINTS AND SCREW HEADS. PAPER TAPE 2" WIDE EMBEDDED IN FIRST LAYER OF COMPOUND OVER ALL JOINTS THICKNE55: 4 7/8" (MIN) LIMITING HEIGHT: PER 5TUD5 AFFROX WEIGHT: 6 1'5F ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 LIC # AR 12885 cC W AOL W U �. Ln z M M CL W LL O_joC _ N O �mLL. 0Ln>- U CL N d W N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFYTHE ARCHITECT WITH RESPECT TO: ANY CHANGES MADETOTHE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OFTHE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE FLOOR PLAN PROJECT SHEET NO. NO 1030 HARDWARE 5ET #3 a. HINGES - 1 1/2 PR, BRA55, BALL BEARING TYPE b. CLO5ER -HEAVY DUTY c. DIAMOND PLATE KICK PLATE - 34'' H (50TH 51DE5) d. OFFICE LOCK5ET (ADA ACCE5515LE) DOOR TYPES DRAWN BY EJ5 DATE 11-23-10I 1 OF 8 -L;, &I. -:.11lu.LLa,_! ... I _ _-._,_ 'ter hul 5CREW5 A5 REQUIRED TO EACH 51DE OF LINTEL AND 5CREW5 TO WEB OF JAMB 5TUD A5 REQUIRED JAMB A5 REQUIRED WEB 5TIFFENER A5 REQUIF (3) #10-10 5CREW5 TO EA. ME AT LINTEL BEARING LOC LINTEL A5 REQUIRED MEZ7,4NINE HEADER DETAIL A-1-1, NOT TO SCALE O N & DOOR5 (TYP) ELEV @ DINING SCALE: 5/8" = 1'-0" 0 N �1 ►i B-2 CT-1 ) \-A CT-2 � ELEV @DINING $ SCALE:3/8" = 1'-0" 3/4" PLYWOOD TO BE ATTACHED TO J015T5 W/ #10 WOOD TO METAL - 5ELF DRILLING FASTENERS. PROVIDE 5CREW5 0 6" MAX SPACING AT PANEL EDGE5 AND 12" MAX SPACING AT INTERMEDIATE SUPPORTS - DOUBLE 18 GA METAL 5TUD e RIM TRACK W/(1) #10x3/4" PAN PH 5CREW PER FLOOR GYF BD CEILING IN HEADER 5HOWN W/ HEAVY e J015T AND W/(1) #10x3/4" HEX 5CREW TO TOP PLATE OFFICE5 TO BE ---�--- DOUBLE DASHED LINE - PROVIDE @ 12" O.C. - ATTACH RIM TRACK TO WEB 5TIFFENER FASTENED DBL JACK 5TUD5 BELOW - W/(2) #10x3/4" PAN PH 5CREW5 DIRECTLY TO — LEAVE AREA ABOVE DOOR OPEN BOTTOM OF JOISTS FOR ACCE55 TO MEZZANINE e (600/362)T125-43 WEB - TOF OF JOISTS @ MEZZANINE FRAMING TO BE - STIFFENER W/ 4" ( ) #10x3/4 6-6 5/8" AFF __ �___ „ 18 GA 6 METAL 5TUD5 HEX SCREWS ---�-- (6005162-43) @ 12" O.C. -TOP OF J015T5 C@ 8 6 5/8 AFF ___ COVER Wl 3/4" FKT PLYWOOD ----�---- --- FLOOR - ATTACHED W/ #10 WOOD TO METAL 5ELF DRILLING EXTEND ALL T FA5TENEK5. PROVIDE 5CREW5 9 EXISTING AND NEW 6" MAX 5FACING AT EDGE5 AND - PERIMETER WALLS --- -- 12" MAX 5FACING 0 OF MEZZANINE TO _ INTERMEDIATE SUPPORTS FULL HEIGHT - BEARING WALL BELOW TO BE PERIMETER WALL FIN15H W/ FKF ---- --- 18 GA 6" METAL 5TUD5 FLOOR J015T - CONNECT TO TOP (6005162-43) @ 12 O.C. - PLATE W/(2) #100/4 HEX HEAD WALL 5TUD5 TO BE LOCATED 5CREW5 WALL 5TUD ALIGNED DIRECTLY BELOW FLOOR WITH FLOOR J015T ACCE55 TO JOISTS (TYP). MEZZANINE - OPEN PROVIDE ONE ROW OF BRIDGING AT TH15 SIDE @ MIDPOINT OF 5FAN � MEZZANINE FR,4MING DETAIL A-1•1/ NOT TO SCALE EXISTING STOREFRONT — - (TYP) CORRIDOR �IVC UI- J/1IVIDn l I T r) RETURN TILE FIN15HE5 51DE OF JAM55 (TYP) � MEZZ,4NINE F24MING PLAN (1 Yf ) SCALE:1/4" = 1'-0" P-1 \\ ART - -- 1/2" -- - N ART ' ART AKT I NOTE: INTERIOR DECOR, 51GNAGE AND WALL HUNG ART WORK TO BE 5UPPLIED AND INSTALLED BY FIVE GUYS CORPORATE REPRE5ENTATIVE EXI5TING STOREFRONT & DOOR5 (TYF) B-2 LIFE 50'/,_&_1FETY PLAN A-1,1 SCALE: 3/16" = 1'-0" CT-1 P-7 0 N 3 5/8" 5TUD BRACING TO EX15T'G 5TRUCTURE @ 4' 5ECURE HEAD O.C. - ALTERNATE SIDES CHANNEL TO BRACING CEILIr HALF 3-5/8" 20 GA-- - METAL 5TUD (5T20) AT 24" O.C. 3-5/8" 20 GA METAL 5TUD TRACK 5ECURED TO SLAB 5/8" GYP BD EACH FACE (DUKOCK OR PLYWOOD MAY BE U5ED IN LIEU OF GYP BD AT CERTAIN LOCATION5 - 5EE PLAN) TYPICAL INTERIOR PARTITION SCALE: 3/4" = 1'-0" ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 I-Lo LIC # AR 12885 LU Z lqw W AL.0 Ln z (L W LL U J I. O N m LL. j Fw �! O J Z (n _ � GC � CC W N Al N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN,ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE LIFE SAFETY PLAN INTERIOR ELEVATIONS PROJECT SHEET NO. NO 1030 Amol DRAWN BY EJS ■ DATE 11-23-10 2 OF 8 ERIC J. SAFFRAN 5EE PARTITION DTL., SHEET A-1, FOR BRACING OF ARCHITECT __________ __________ METAL 5TUD5 TO ) ( - \- - ,-" STRUCTURE ABOVE I - - \ V I BY IF SLEEVE S RE QD H ET PARTITION DTL. 5 E 5EE • V, I EVERAGE VENDOR : PVC B - _ HEAD � HEAP SEE PARTITION DTL. SHEET HEAD - �0 � � A 1 FOR BRACING OF HEAD I � PIPE FOR SODA LINE @ BEV _ , SEE PARTITION DTL. SHEET _ A-1, FOR BRACING OF - SHOWN DOTTED. �0 METAL STUDS TO (D A-1 FOR BRACING OF - COUNTER METAL STUDS TO I CONCEAL IN WALLS ABOVE � STRUCTURE ABOVE TYF ; CON , ( ) METAL STUDS TO - CLG AND IN BASE OF STRUCTURE ABOVE TYF STRUC TURE A BOV ETYF BINET CA (TYP ) 'I LAY ACOUSTICAL TILE LAY IN ACOUSTICAL TILE Y IN ACOUSTICAL TILE LA - I LA I TILE IN ACOUST ICAL CAL LAY - CEILING ' >< CEILING W HERESHOWN CE ILING (W HERE SHO WN) )CEILING (WHERE SHOWN) SHOWN GYP BD CEILING WHERE SHOWN � I I ANGLE >: CEILING ANGLE CEILING CEILING ANGLE � 5/8 PLYWOOD ON CEILING ANGLE ,__ 5/8 PLYWOOD ON - - 5/8 PLYWOOD ON - - 6" METAL STUDS - \ - 5/8" GYP BD EA SIDE 6" 3-5/8" FIBEKGLAS 3-5/8 METAL 3-5/8" METAL - 5/8 GYP BD EA SIDE STUDS @ 24 0 C : STUDS @ 24" O.C. - 3-5/8" METAL STU D5 @ 24 O.C. — METAL STUDS INSULATION _\ 5/8" GYP BD EA SIDE C. 77 3-5/8" METAL STU D5 F FRP FR FRF FRF PLAN D OCK ON 6 PLAN _ 5/8 UR 5/8 DURO CK ON 3 5 /8 PLAN PLAN _ LA - - �� METAL STUDS @ 24 O.C. 5/8 DUROCK ON 3 5/8 Preston Ridge Commons METAL STUDS @ 24 0 C METAL STUDS @ 24 O.C. 3155 North Point Parkway CT-1 - CT-1 BuildingSuite 200 E - CT_ CORRIDOR/RESTR M2 T-2 RESTR00MAlpharetta, Geor ia 30005 REP/5ERVIC VI 9 91 P/5ER C T 177 1 5 6 RE e 0 6 REP/5ERVIC �\ REP/5ERVIC - - \- -- \_ �- INING/GORRIDO r KE5TROOM/ BEVERAGE Fax 770 619 5919 RESTROOM CT-1 CT-2 4 7/8" 5/8" DUROCK ON 6° 71/4" 5/8" DUROCK ON 3 5/8" 4 7/8" FASTEN TO METAL RUNNER 5/8" DUROCK ON 3 5/8" — FASTEN TO METAL RUNNER FASTEN TO METAL RUNNER 4 7/ 10 METAL 5TUD5 @ 24" O.C. METAL STUDS @ 24 O.C. FASTEN TO METAL RUNNER METAL STUDS @ 24" O.C. B-1 - B-2 B-1 r B-2 B-2 - - B-2 B-1 SILL 51LL 51LL 51LL I PT /A FT - �23-� PT , ` QT - QT QT QT , ................ LIC # AR 12885 NOTE: ALL SHEETING BEHIND TILES TO BE 5/8" DUROCK. ALL SHEETING BEHIND NOTE: ALL SHEETING BEHIND TILES TO BE 5/8" DUROCK. ALL SHEETING BEHIND NOTE: ALL SHEETING BEHIND TILES TO BE 5/6" DUROCK. ALL SHEETING BEHIND NOTE: ALL 5HEETING BEHIND TILES TO BE 5/8" DUKOCK. ALL SHEETING BEHIND FRP TO BE 5/5" PLYWOOD WITH LOWEST 24" TO BE 5/8" DUKOCK. ALL SHEETING FRP TO BE 5/5" PLYWOOD WITH LOWEST 24" TO BE 5/8" DUROCK. ALL SHEETING FRF TO BE 5/8" PLYWOOD WITH LOWEST 24" TO BE 5/8" DUROCK. ALL SHEETING FRP TO BE 5/8" PLYWOOD WITH LOWEST 24" TO BE 5/8" DUROCK. ALL SHEETING BEHIND PAINTED SURFACES TO BE 5/5" GYPSUM BOARD. ALL GYPSUM BOARD IN BEHIND PAINTED SURFACES TO BE 5/5" GYPSUM BOARD. ALL GYPSUM BOARD IN BEHIND PAINTED SURFACES TO BE 5/8" GYPSUM BOARD. ALL GYPSUM BOARD IN BEHIND PAINTED SURFACES TO BE 5/6" GYPSUM BOARD. ALL GYPSUM BOARD IN KE5TROOM5 TO BE MOISTURE RESISTANT. SEE RCP FOR CEILING HEIGHTS. RE5TKOOM5 TO BE M015TURE KE515TANT. SEE RCP FOR CEILING HEIGHTS. RE5TROOM5 TO BE MOISTURE RESISTANT. SEE RCP FOR CEILING HEIGHTS. KE5TKOOM5 TO BE MOISTURE RESISTANT. SEE RCP FOR CEILING HEIGHTS. PARTITION TYPE'Al'. PARTITION TYPE'AT. PARTITION TYPES' PARTITION TYPE'Cl SCALE: 3" = 1'-0" SCALE: 3" = 1'-0" SCALE: 3" = 1'-0" SCALE: 3" = 1'-0"r W Z w iL U Ln LU rn STAINLESS STEEL w 0 - CAP 5UFFLIED BY U J GC G.C. ALL EDGES, - 3/4" PLYWOOD CAP - � CORNERS, ETC TO FINISH W/ FL-1 @ALL Q 0 SEE PARTITION DTL., BE GROUND EXPOSED SIDES 4 z m SHEET A-1 FOR SMOOTH. N ! HEAD - J J HEAD CAULK TYF 1 CAU HEAD SEE PARTITION DTL , ( ) EA O - — J Q SHEET A-1, FOR BRACING OF N3-518" METALa-< — T METAL STUDS 0 �� 2 HEAD HEAD / PLYWOOD ON BRACING OF STUD TRACK W/ 5 8 cC STRUCTURE ABOVE � M STUDS TO --- 3-5/8 METAL STUDS METAL TYF BLK G ABOVE FRP O Ln STRUCTURE ABOVE ( ) FRP 3-5/8 METAL STUD @ 24 O.0 a` 2 -1 U CT V TYF TRACK W/ BLK G ABO E ( ) 'Ili I CT-1 " _ CT-2 - 5/8 PLYWOOD ON � w - -- -1 \ EXIST. FIRE RATED LAY -IN ACOUSTICAL SS - LAY -IN ACOUSTICAL TILE CEILING WHERE 5/8" PLYWOOD ON \ '\� 3 5/8 METAL = GYP. BD. @ TILE CEILING WHERE ( \ z ^ CT-1 CT-2 5TUD5 @ 24 O.C. SHOWN 3-5/8 METAL • ¢ ¢ cn N Lu J cs� z ) Z H w SHOWN) w DEMISING PARTITION STUDS @ 24 O.C. � - 3 � = CT-2 w O '� �� _ O N C FILING ANGLE ac N Ac O ¢ CE ILING ANGLE _Ilk ¢ - w cn Q _ _ z _ > v_ _ > SERVICE _ - — SERVICE d- w w \ PLAN o w N? u_ PLAN_j z LU 5/8 FIRE RETARDANT O O> L- O coO O w _-\ O w - 5/8 PLYWOOD ON - >- w _ - - 3 5/8" METAL 5/8" DUROCK ON TREATED PLYWOOD �- -� °� ¢ \ N STUDS @ 24 O.C. 3 5/8 METAL ON 3-5/8 METAL "SOFTFORMS SKB" ¢ w 3-5/8 METALSTEEL w z O 5TUD5 @ 24" O.C. STUDS @ 24 O.C. , 3 w 0 O SECURED T w PLAN w PLAN FRP KNEE BRACE KIT MFD ..cn = L- BRACE O O o Z z BY PITTCON - INSTALL O 3-5/8" METAL w w PLAN PER MFR 5 SPECS @ - —STUD SECURED SOFTFORMS 5KB �N LU REVISIONS P FR I MFD ' 4 -D O.C. KNEE BRAC EKT PREP TO STEEL BRACE BY PITTCON -INSTALL 5l8" DUROCK ON FRF NO. DATE REVISION 5/8 PER — DUROCK ON F MFRS SPECS @ 3-5/8" METAL STUDS � SERVICE -\ PREP \ —3-518 METAL 4-0 O.C. @ 24 O.C. \- - — K O N — -- 5/8 DUROG \ 3 5/8 METAL STUDS @ 24 O.C. - STUDS @ 24" O.C. DINING/SERVICE 5/8" DUROCK ON77 41/4" 4 7/8" FASTEN TO METAL COOK 4 7/8" SERVICE 4 7/8 4 7/8 FASTEN TO �� DINING/CORRIDOR 3-5/8" METAL STUDS �� FASTEN TO METAL RUNNER - @ 24" O.C. \METAL RUNNER RUNNER B-1 B-1 B-1 - B-1 B-2 - B-2 B-1 -- 51LL O SILL 51LL 51LL 51LL QT PT FT QT INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, QT Qr - QT QT HOLD HARMLESS, AND INDEMNIFYTHE lX O ARCHITECT WITH RESPECT TO: ANY CHANGES MADETO THE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OFTHE WORK, OR FAILURE BY THE CACC CONSTRUCTIONWITH THDOCUMENTSD IN N T ALL SHEETING BEHIND TILES TO BE 5/8" DUROCK. ALL SHEETING BEHIND NOTE: ALL SHEETING BEHIND TILES TO BE 5/8" DUROCK. ALL SHEETING BEHIND NOTE: ALL 5HEETING BEHIND TILES TO BE 5/8" DUKOCK. ALL NOTE: ALL 5HEETING BEHIND TILES TO BE 5/8" DUKOCK. ALL SHEETING NOTE: ALL 5HEETING BEHIND TILES TO BE 5/8" DUKOCK. ALL ACCORDANCE WITH THESE 0 E. FRF TO BE 5/5" PLYWOOD WITH LOWEST 24" TO BE 5/8" DUROCK. ALL SHEETING FRF TO BE 5/8" FR.T. PLYWOOD WITH LOWEST 24" TO BE 5/5" DUKOCK. ALL 5HEETING SHEETING BEHIND FRP TO BE 5/8" PLYWOOD WITH LOWEST 24 TO BE 5/8 BEHIND FRF TO BE 5/8 PLYWOOD WITH LOWEST 24 TO BE 5/8 DUKOCK. SHEETING BEHIND FRF TO BE 5/8 PLYWOOD WITH LOWEST 24 TO BE 5/8 BEHIND PAINTED SURFACES TO BE 5/8" GYPSUM BOARD. ALL GYPSUM BOARD IN BEHIND PAINTED SURFACES TO BE 5/8" GYPSUM BOARD. ALL GYPSUM BOARD IN DUKOCK. FINISH ENDS WITH CT-1 & CT-2. FINISH ENDS WITH CT-1 & CT-2 DUROCK. COPYRIGHT 2010 RE5TROOM5 TO BE MOISTURE RESISTANT. SEE KCF FOR CEILING HEIGHTS. RE5TROOM5 TO BE MOISTURE RESISTANT. SEE RCF FOR CEILING HEIGHTS. ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN,ARCHITECT E ' T PARTITION TYPE V PARTITION TYPE 'E' PARTITION TYPE T PARTITION TYPE 'G' AND IS NOT TO BE REPRODUCED OR PARTITION TYP C COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, SCALE: 3" = 1'-0" SCALE: 3" = 1'-0" - - INCLUDING USE ON ANY OTHER SCALE: 3" = 1'-0" SCALE: 3 - 1-0 SCALE: 3„ - 1,-0„ PROJECT PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. 5TUP 5PACING @ PARTITION5: PARTITION NOTES: SHEETTITLE 0'-0" TO 14'-0" 5TUD5 ARE 0 24" ON CENTER 1. PROVIDE FIRE RETARDANT TREATED SHEETING AND BLOCKING AT ALL AREAS WITHIN 18" OF PARTITION TYPES 14'-0" TO 15'-8" STUDS ARE @ 16" ON CENTER EXHAUST HOOD AND IT'S ASSOCIATED DUCTWORK. 15'-8" TO 17-10" STUDS ARE @ 12" ON CENTER 2. PROVIDE F.R.T. BLOCKING IN ALL ENCLOSED 5FACE5 AS REQ'D WHETHER INDICATED ALL STUDS ARE 3-5/5" OR 6" (WHERE INDICATED) 20 GAUGE MIN. OR NOT IN THESE DOCUMENTS. PNO ROJECT SHEET NO. 3. ALL BLOCKING 15 TO BE CONCEALED. 1 4. ALL WALL LOCATIONS TO BE FULLY CHALKED -OUT ON THE SLAB (INCLUDING DOOR LOCATIONS) 030 AND APPROVED BY FRANCHISEE BEFORE PROCEEDING WITH WALL CONSTRUCTION. DRAWN BY 5. PROVIDE DIAGONAL METAL STUD BRACING, AS SHOWN ON PARTITION DETAIL 5HEET A-1, TO EJS � ■ 1r_D/_,&N12TIT10 N TYPEs STRUCTURE ABOVE. DATE 11-23-10 3 OF 8 HEAVY DUTY STANDARDS (BLOCKING READ) N OTE: SOUND ATM- DUPLEX & DATA (CAT 6) SYSTEM �J �I° ATM AL50IN DINING; 12"D ADJUSTABLE P05- SERVER = DUPLEX, LAMINATE SHELF COMPUTER = DUPLEX & DATA SECURITY (CAT 6) SYSTEM -° ROUTER = DUPLEX ° F05 ROUTER ° MODEM = DUPLEX SECURITY- BY APT = DEDICATED F05 51TE - QUAD (110 AC) IN 3/4" CONDUIT CONTROLLER -- --- - °� & 1" CONDUIT W/ RING AND STRING (COAX CABLES) POS MODEM - - SOUND SYSTEM- MICROPHONE & SPEAKERS = QUAD; TOUCHBLOCK ROUTER; TELEPHONE- GENERAL CONTR TO RUN LINES FROM DEMARK -' DATA &QUAD RECEPT MONITOR P05 N OR PHONE BOARD TO ALL SERVER POINTS; FURNISH RING & 24"D HEAVY DUTY STRING FROM FOS LOCATION TO MILLWORK COUNTER OFFICE LOCATION AND 1" 0 P05 FRP CONDUIT IN WALL BEHIND OFFICE DESK. D5L GENERAL CONTR TO ADD 24"W x 16"D x 6"T - GROMMET IN COUNTER IN FIELD, CONC CURB. SAFE \ °°I -° Z PHONE `�' VERIFY LOCATION W/ OWNER. REINFORCE W/ STEEL z �\ �- FAX ALL RECEPTACLES TO BE GFI KEBAR WHERE READ COMPUTER 2'-0" � FIN15H NOTE: TOP OF CONC CURB TO BE QT & FIN15H ON EXP05ED SIDES TO BE 8-1- FINI5H ON COUNTER AND LAMINATE SHELVES TO BE FL-2. PROVIDE P.LAM SUPPORTS BELOW AS NEEDED (CONFIRM KNEE 51-ACE CLEARANCE WIDTH W/OWNER PRIOR TO FABRICATION) r2ELEV @ r,1ANAGER'S DESK SCALE:1/2'' SANDWICH UNIT - 5TAINLE55 STEEL CAP FOR 5ANDWICH UNIT O d-. (OPPOSITE HAND) PRINTER SHELF FOR PRINTER, CAT 5 TO SERVER, DEDICATED DUPLEX - WARMER SHELF FOR TABLE - ° Lc) `� <o FOR WARMER 'v" AP - SANDWICH WR TABLE END OF WALL 5'-6" _ / (WALL CONTINUES @ "SHOTGUN" LAYOUTS) FRP L B 1 NOTE: ELECTRICAL/DATA LOCATIONS CAN VARY 0 HALF HT. WALL, DEPENDING ON ADJACENT SANDWICH TABLE LOCATION- GC 5HALL CONFIRM ORIENTATION PRIOR TO CONSTRUCTION ELEV Ca WALL SCALE:1/2'' IF SLEEVE 15 REQ'D BY BEVERAGE VENDOR, - CONFIRM 51ZE & LOCATION OF PVC SLEEVE FOR SODA LINE ACCE55 INTO CABINET - SEE PLUMBING 2 -- NOTE: - PROVIDE ALL NECESSARY MILLWORK BLOCKING FOR SUFFICIENT SUPPORT OF ALL COUNTER TOP EQUIPMENT. CONFIRM EQUIPMENT WEIGHTS (APPROXIMATELY 2200 LB5) WITH VENDOR PRIOR TO FABRICATION - COORDINATE ALL EQUIPMENT ELECTRICAL & PLUMBING REQUIREMENTS, INCLUDING LOCATIONS, AT MILLWORK - ALL EXP05ED CORNERS ON COUNTERS SHALL BE ROUNDED - ALL PLYWOOD SHALL BE MARINE GRADE SECTION @ BF.VERAGE COUNTER SCALE: 11/2"= 1'-0" <> EQUIPI" 1ENT NOTES: GENERAL: - REFER TO EQUIPMENT SCHEDULE, SHEET A-3 - G.C. TO VERIFY KITCHEN EQUIPMENT REQUIREMENTS, LOCATIONS, ETC. WITH KEC CONSULTANT PRIOR TO INSTALLATION. ALL EQUIPMENT SPECIFIED, INCIDENTAL AND CUSTOM, WHETHER NEW OR RECONDITIONED TO INCLUDE ALL TENANT APPROVED OR PROVIDED SUBSTITUTES, SHALL BE OF COMMERCIAL QUALITY & SHALL MEET ALL APPLICABLE IBC, NSF, & UL STANDARDS. - ALL SHELVING, WORK TABLES, AND EQUIPMENT STANDS SHALL BE 5TAINLE55 STEEL & SHALL MEET APPLICABLE N5F 5TANDAR05. - ALL FLOOR MOUNTED EQUIPMENT SHALL BE PLACED ON N5F APPROVED 6" LEGS OR NSF APPROVED CASTERS. ALL COUNTER MOUNTED EQUIPMENT IN EXCE55 OF 80 POUNDS SHALL BE PLACED ON N5F APPROVED 4" LEGS. - N5F APPROVED 5TAINLE55 STEEL SHELVING OR DUNNAGE RACKS IN WALK-IN COOLER, HANGING STORAGE RACK SHALL BE PROVIDED NEXT TO MOP 51NK FOR BROOMS AND MOPS. ALL CLEANING SUPPLIES SHALL BE STORED SEPARATELY FROM ALL FOOD PRODUCTS. - SURFACE MOUNTED LIQUID 5OAP, PAPER TOWEL DISPENSERS, AND WASTE RECEPTACLE SHALL BE PROVIDED AT ALL HAND SINKS. SEE COVER SHEET FOR ADA MOUNTING HEIGHTS - SPLASH GUARDS SHALL BE PROVIDED WHERE 51NK5 ARE WITHIN 6" OF POTENTIAL 5PLA5H CROSS 3 COMPARTMENT SINKS TO HAVE 2 FAUCETS WITH ONE PRE-KIN5E NOZZLE. 4 COMPARTMENT SINKS TO HAVE 2 FAUCETS AND 2 PRE -RINSE NOZZLES. OUTSIDE CORNERS IN KITCHEN TO RECEIVE 5TAINLE55 STEEL GUARDS, BA5E TO 60" AFF. F= G.C. TO PROVIDE ADDITIONAL BLOCKING & REINFORCEMENT AT DRINK COUNTER CASEWORK FOR SUPPORT OF COUNTER TOP EQUIPMENT - CONFIRM EQUIPMENT WEIGHT W/ VENDOR G.C. 5HALL CONFIRM 50UND 5Y5TEM REQUIREMENTS WITH FRANCHISEE AND THIRD PARTY VENDOR G.C. SHALL VERIFY AND PROVIDE ALL REQUIRED STRUCTURAL SUPPORT FOR HOOD, EXHAUST FAN, AND MUA FINAL LOCATIONS AND MOUNTING HEIGHTS FOR ALL WALL MOUNTED SHELVING 5HALL BE CONFIRMED WITH THE D15TRICT MANAGER. G.C. 5HALL NOT INSTALL ANY WALL MOUNTED SHELVING UNTIL ON 51TE WALK- THROUGH WITH FIVE GUYS OPERATIONS MGR. OCONFIRM NEED FOR AND LOCATION OF 6" PVC SLEEVE, CONCEALED IN WALL FOR SODA LINE FROM ABOVE CEILING TO INSIDE OF CABINET WITH EQUIPMENT VENDOR 2. TRENCH DRAIN/AND OR FLOOR SINK SHOWN DASHED (TYP). G.C. SHALL CONFIRM THAT EQUIPMENT LEGS WILL CLEAR DRAINS, PRIOR TO DRAIN INSTALLATION 3. ALL WALK-IN COOLER DIMENSIONS TO BE COORDINATED WITH MANUFACTUREER'5 SHOP DRAWINGS. 4. SEE FLOOR PLAN FOR FLOOR / TRENCH DRAIN & FLOOR SINK DIMENSIONS 5. FKANCH15EE SHALL FIELD VERIFY CLEARANCE BETWEEN COUNTER SUPPORT P05T5 PRIOR TO ORDERING UNDER -COUNTER SHELVING (TYP) 6. IF CEILING HEIGHT ALLOWS, FKANCH15EE SHALL PROVIDE AND G.C. SHALL INSTALL SECOND ROW OF WALL 5HELVING 2'-0" ABOVE FIRST TIER SHOWN ON EQUIPMENT PLAN (TYP) 7. PROVIDE ADJUSTABLE POT RACK HOOKS ABOVE THREE COMPARTMENT DISH SINK 8. APPROXIMATE LOCATION FOR NEW ACCESS PORTS FOR CO2 TANK AND GREASE RECYCLING TANK. COORDINATE EXACT LOCATIONS AND HEIGHTS WITH FRANCHISEE PRIOR TO INSTALLATION. 9. G.C. SHALL INSTALL OWNER PROVIDED, SURFACE MOUNTED LIQUID 5OAP D15PEN5EK AND PAPER TOWEL D15PEN5ER AT SERVICE AREA AND PREP AREA HAND 51NK5. SEE ACCESSORY SCHEDULE SHEET A-6. SEE COVER SHEET FOR ADA REQUIRED MOUNTING HEIGHTS. 10. CONFIRM MOP 51NK DIMENSIONS PRIOR TO CONSTRUCTION OF ADJACENT PARTITION. 11. PROVIDE DIAMOND PLATE ON EXF05ED EXTERIOR SIDES OF WALK-IN COOLER. 0 WALL SHELF LOCATIONS SCALE:1/2'' = 1'-0" -2'-6" (9 P05� 2'-0" (0 ADA P05 & PICK UP) (SEE FLOOR PLAN FOR CLARIFICATION) FL-1 4 7/8" FRP z 3-5/8" METAL STUD ~i TRACK W/ BLOCKING ABOVE 55T SUPPORT LEG W/ 3-5/8" METAL STUDS @ COUNTER MOUNTING - -------- - -- 24" O.C. W/ 5/8" DUROCK PLATE &FLANGE @BOTH SIDES INSTALLED EVERY 36" - 48"; SEE FLOOR - 9T-1 CT-2 PLAN FOR 512ACING i �- - 2" x 2" x 1/4" STEEL TUBE WELDED TO4"x5"x1/2" LOW HEIGHT METRO - Q PLATE, ATTACH TO CONC. SHELF - FACTORY o 5LA13 W/ (4) HILTI HAS - CUT 27" POST - - - -' Nli SUPER RODS 1/2"0 IN HY 150 MAX ADHESIVE, PROVIDE CUSTOM QT w EMBEDMENT, 9 4' O.C. FLANGE BY C&T CUSTOM -- B_1 - B-2 STAINLESS, LLC - __/ CONTACT (972) 878-6341 MASONRY ANCHOR (2)- i 1/4" X 1 1/2" SCREW OR NOTE: ALL SHEETING BEHIND TILES TO BE 5/8" DUROCK. ALL SHEETING BEHIND PIN FLANGE TO CONC. FRP TO BE 5/8" PLYWOOD WITH LOWEST 24" TO BE 5/8" DUROCK. KNEEWALL BRACE 5LA13 EVERY 36" - 48" O.C. SEE FLOOR PLAN FOR CLARIFICATION ON VARYING COUNTER DEPTH & HEIGHT LOCATIONS SECTION @ POS � PICKUP SCALE: 11/2"= 1'-0" MEN OFFICE 106 a 8c OFFICE v ' 105 WOMEN 45 104 46 (69 48 / 53 a . F_1 Lj �J DINING 100 I� 9 10 � 6O O r--------� J MO(A ---- 40 28 7 0 2 } 4�� �7 - 4E) - - - ,\ \ 035�)33 34 44 4 2 PREP 102 1 LI row, 1b r--------, 1 L - --J 1e 2b gb � 9b . X % 24"x60"eg 2a - 1 _X -� _X d X �g X X e N • �/ N N O r� 3 x 431 0 43 43 4 2 >ti N 6 7 9b L 9 40/� 7 i 2 4 �I 40 9 903 a 89 _ 24"x36" L9_- --II_J C I Z22 9b 16 1� 14 L -' 10 01 55 - - SERVICE O Z t EQUIPMENT PLAN A-2 SCALE: 1/4" = 1'-0" 24"x36 N 37 N O ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3 155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 6195919 ILIC # AR 11111 I REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFYTHE ARCHITECT WITH RESPECT TO: ANY CHANGES MADETO THE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN,ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE EQUIPMENT PLAN PROJECT SHEET NO. NO 1030 DRAWN BY Asw2 EJS DATE 11-23-10 4 OF 8 FOOD SERVICE EQUIPMENTSCHEDULE MARK DESCRIPTION MANUFACTURER MODEL SIZE EQUIP REMARKS G W cn 1=im G LU J cn Zm 1 OPEN SIGN OWNER GC NEON SIGN HUNG FROM CEILING-COORD. LOCATION w/ FRANCHISEE 2 TRASH BIN (DINING) CONTINENTAL 5735BN 20"x 20" x 39.5" OWNER GC DINING 2a TRASH BIN (KITCHEWPREP/RR, SLIM) CONTINENTAL 8323BN 20" x 11" x 30" OWNER GC LIDS REQ'D IN PREP & RESTROOMS 2b TRASH BIN (KITCHEN/PREP, ROUND) HUSKEE 320ORD 27 3/8" x 22" OWNER GC KITCHEN & PREP AREA 3 TABLE & BASE (24" X 42") BENNINGTON FURNITURE CORP STEELGRAIN T2442 24" X 42" OWNER GC (PS-37) BASE PLATE - TB-2222 COLUMN - LABOR SAVER COLUMN 3a TABLE & BASE (24" X 24") BENNINGTON FURNITURE CORP STEELGRAIN T24S 24" X 24" OWNER GC 3b TABLE -9 RACE (362 ROUND, BAG HGT) BENNINGTON FURNITURE CORP STEELGRAIN T36R 36" DIA X 40.75" HGT OWNER GC BASE - BLACK BAR HEIGHT 3c TAR' C 8. RACE (30" ROUND, RAG HGT) BENNINGTON FURNITURE CORP STEELGRAIN T30R 30" DIA X 40.75" HGT OWNER GC 3d TABLE & BASE (ADA COMPLIANT) BENNINGTON FURNITURE CORP STEELGRAIN T3048 30" X 48" OWNER GC ADA COMPLIANT, BASE - SRVU-8222, 36" BETWEEN LEGS 4 UMBRELLA COCA -COLA 3402EXT5G 7'-0" TALL VENDOR GC STAND - 3500 4a LEISURE CRAFT INC. R36XWCP - PERF 6-7 5/8"W X 2'-6"H OWNER GC OUTDOOR PATIO - STANDARD TABLE 4b LEISURE CRAFT INC. T46ROP - PERF 6'-9"W X 2'-5 1/4"H OWNER GC OUTDOOR PATIO - ALTERNATE TABLE 4c OUTDOOR 46" ADA TABLE 1AU SEATS LEISURE CRAFT INC. T46ROP - ADA - PERF 6'-9"X5'-3.5"X2'-5.25"H OWNER GC OUTDOOR PATIO - ADA TABLE 4d OUTDOOR STACKABLE CHAIR LEISURE CRAFT INC. C1 -PERF 21 1/2"W X 30"H OWNER GC OUTDOOR PATIO CHAIR 4e LEISURE CRAFT INC. SQ36TAB30 - PERF 36"W X 30"H OWNER GC OTUDOOR PATIO TABLE 5 FIVE GUYS SIT DOWN CHAIR BENNINGTON FURNITURE CORP STEELGRAIN OWNER GC DINING 5a BENNINGTON FURNITURE CORP STEELGRAIN OWNER GC DINING (BAR HEIGHT) 6 PEANUT BOX OWNER GC 7 CORK BOARD OWNER GC 7a DRY ERASE BOARD OWNER GC 8 POS SYSTEM RADIANT SYSTEMS T-160 12" X 13.5" X 13" OWNER GC PRINTER, 16" CASH DRAWER 8a EPSON POS PRINTER EPSON TMT-88 7.64" X 5.98" X 5.83" OWNER GC 8b EPSON REMOTE TICKET PRINTER EPSON TMT-88 7.64" X 5.98" X 5.83" OWNER GC 8c POS SERVER RADIANT S4000 9.65" X 12.4" X 3.47" OWNER GC 9 BOTTLED WATER CONTAINER HAIER BC 110 19.5" X 22" X 38.5' VENDOR VENDOR 10 CONDIMENT CUP DISPENSER SAN JAMAR C9002 10" X 7 1/8" X 17" OWNER GC 10a KETCHUP DISPENSER SERVER SE 07000 17-3/8"X7-1/2"X14-3/16' OWNER GC RECTANGULAR 10b CONDIMENT BIN CAMBRO 12RS12 25-1/8" X 21-1/2" X 14" OWNER GC 12 BIN 10c cull I ED LEMON WRDGE DISREAISEG SAN JAMAR B6183L 18" X 5-3/4" X 5-1/2" OWNER GC 10d PLASTIC CUP HOLDERS GOLD LEAF PLASTICS B12091 12.75" X 4.75" X 10" OWNER GC 11 TEA BREWER BUNN TB3Q 24" X 11.5" X 38.5' OWNER GC 11a TEA DISPENSER BUNN TDO-5 13.6" X 10.6" X 22.1" OWNER GC 11c TEA DISPENSER COCA COLA GOLDEN PEAK 10" X 14.12" X 22.50" OWNER GC 13 SODA DISPENSER (8 VALVE) LANCER IBD 4500 30" X 30.5" X 34' VENDOR GC 6" AIR GAP BETWEEN UNIT AND WALLS, CAULK TO COUNTER IF LEGLESS 13a SODA DISPENSER (12 VALVE) LANCER IBD 4500 44" x 30.5" x34" VENDOR GC 14 ICE MACHINE (8 VALVE) HOSHIZAKI KMD-850M_H 30" X 24" X 28" OWNER GC 14a ICE AAAf H 1 N E (12 VAI VE4 HOSHIZAKI KMD-901MAH 42" X 24" X 28" OWNER GC 15 FOOD PREP TABLE SILVER KING SKP4812 48" X 32" X 44-1/2" OWNER GC SANDWICH / SALAD UNIT 15a FOOD PREP TABLE SILVER KING SKP36/C2 36" X 32" X 44-1/2" OWNER GC SANDWICH / SALAD UNIT 16 SAInIDIAiIGH WRAP TABLE (109"� MARSHALL AIR SYSTEMS INC 146651 108" X 30" X 36" VENDOR GC 15" X 30" WARMER SHELF ON SIDE 16a BACON BASKET SHELF MARSHALL AIR SYSTEMS INC 146828 15.5" X 7.474" VENDOR GC MOUNTED TO MIDDLE OF TABLE 16b DAY DOT SHELF MARSHALL AIR SYSTEMS INC 148403 15.5" X 7.5" X 8.875" VENDOR GC 16c SANDWICH WRAP TABLE (128") MARSHALL AIR SYSTEMS INC 152398 128" X 30" X 36" VENDOR GC 15" X 30" WARMER SHELF ON SIDE 17 PRINTER SHELF MARSHALL AIR SYSTEMS INC 146652 18" X 10" X 6' VENDOR GC FASTENED TO LOW PARTITION 18 COUNTER TOP WARMER APW WYOTT W-3V 14.5" X 22.5" X 9" OWNER GC 19 19a 20 GHEE RASE REFRY ELATION I INIT (84") SILVER KING SILVER KING MAGIKITCH'N SKRCB84H SKRC97H FG-MKG36-STL 84" X 31" X 26.5" 97" X 31.18" X 26.17" 36" X 31.5" OWNER OWNER OWNER GC GC GC UNDER 36" AND 48" GRIDDLES UNDER 36" AND 60" GRIDDLES INSTALL 6" STANDOFF BRACKET CHEF BASE REFRIGERATION UNIT (97") GAS GRIDDLE (36") 20a GAS GRIDDLE (48") MAGIKITCH'N FG-MKG48-STL 48" X 31.5" OWNER GC INSTALL 6" STANDOFF BRACKET 20b GAS GRIDDLE (60") MAGIKITCH'N FG-MKG60-STL 60" X 31.5" OWNER GC 21 FRESH FRY STATION MARSHALL AIR SYSTEMS INC 145485 37" X 20" X 39" OWNER GC 22 GAS FRYING SYSTEM PITCO FG-SGH50/FD/ 50/BT/50-2 78.125" X 30" X 69" OWNER GC WITH REMOTE OIL TANK TIE-IN 23 COOKED FRY STATION MARSHALL AIR SYSTEMS INC 145486 44" X 32" X 56" OWNER GC NO CUP HOLDER OPTION 24 MENU BOARD AFFORDABLE SIGNS & BANNER CUSTOM 95" X 23 1.5" X 1" OWNER GC MOUNT TO ACT FRAME 25 HOOD (19- 0-1 MARSHALL I AIR) MARSHALL AIR SYSTEMS, INC BG3 216" X 39" OWNER GC CAULK TO PARTITIONS AND CEILING 25a HOOD GREASE CUP MARSHALL AIR SYSTEMS, INC 105815 5 3/4" X 5 3/4" X 12" VENDOR GC 6-0" AFF 26 HOOD (18'-0" CAPTIVE-AIRE) CAPTIVE-AIRE SYSTEMS INC 3047BD 216" X 43" OWNER GC CAULK TO PARTITIONS AND CEILING 26a HOOD GREASE CUP CAPTIVE-AIRE SYSTEMS, INC. VENDOR GC 6-0" AFF 27 HAND SINK W/ SIDE SPLASH SOUTHERN STAINLESS FG-007 17" X 15" X 7 3/4" OWNER GC CAULK TO PARTITION, 34" TOP OF BASIN 27a 3 COMPARTMENT SINK (WASHING) SOUTHERN STAINLESS FG-001 CUSTOM (DRAINBOARDS 1 1/2 x COMPARTMENT WIDTH) 132" X 27" X 42" OWNER GC CLEANING, CAULK TO PARTITION 27b 4 COMPARTMENT SINK (FOOD PREP) SOUTHERN STAINLESS FG-002-L FG-002-R 112" X 30" X 44" OWNER GC FOOD PREP, CAULK TO PARTITION. 27c AAOD SINK 8 CAI 10ET (24" X 24") FIAT 36EFS: MSB-2424 830 AA, 889 CC, & 832 AA 24" X 24" X 10" GC GC CAULK TO PARTITION FAUCET - 830 AA, MOP BRACKET - 889 CC, HOSE & BRACKET - 832 AA 27d MOP SINK & FAUCET (36" X 24") FIAT 36EFS: MSB-3624 830 AA, 889 CC, & 832 AA 36" X 24" X 10" GC GC CAULK TO PARTITION FOOD SERVICE EQUIPMENT SCHEDULE MARK DESCRIPTION MANUFACTURER MODEL SIZE EQUIP REMARKS c w N Z LLM o w J H ca Zm 28 POTATO CUTTER NEMCO 56450-211 FRYKUTTER 35.75" X 10.25" X 15.18" OWNER GC 28a pOTATO CI ITTER VOLLRATH 47713 34 1/2" X 23" OWNER GC 29 HOT & COLD WALL HYDRANTS WOODFORD C22C 7" X 3" X 3" GC GC UNDER HAND SINKS 30 WALK-IN COOLER W/ 48" INTERIOR FLUORESCENT LIGHT CONDENSER ON TOP OF COOLER SOUTHERN STAINLESS HEATCRAFT PR03 FG-100 PTN-099H2B INDOOR PT--099H2B OUTDOOR 7'-9" X 12'-0" X 7'-1" H OWNER GC 42" DIAMOND PLATE ON ALL EXPOSED SURFACES. PROVIDE 48" FLUORESCENT LIGHT FIXTURE @ INTERIOR. FIELD VERIFY ALLOWABLE CEILING HEIGHT TO DETERMINE IF SUFFICIENT CLEARANCE FOR MOUNTING CONDENSER ON TOP OF WALK- IN COOLER. SEE ENGINEERING DWGS. FOR LOCATION OF EVAPORATOR COIL. 31b WORK TABLE (36") SOUTHERN STAINLESS FG-010 30" X 36" X 35 1/2" OWNER GC 31c `n►nRKTABLE (4&1 SOUTHERN STAINLESS FG-011 30" X 48" X 35 1/2" OWNER GC 31d WORK TABLE (60") UNDER STORAGE SOUTHERN STAINLESS FG-039 30" X 60" X 33 1/2" OWNER GC STORES UNDERNEATH FG-048 31e WORK TABLE (72") OVER STORAGE SOUTHERN STAINLESS FG-048 30" X 72" X 35 1/2" OWNER GC USE WITH FG-039 31f WORK TABLE (48") UNDER STORAGE SOUTHERN STAINLESS FG-038 30" X 48" X 33 1/2" OWNER GC STORES UNDERNEATH FG-049 31g WORK TABLE (60") OVER STORAGE SOUTHERN STAINLESS FG-049 30" X 60" X 35 1/2" OWNER GC USE WITH FG-038 32 CO2 CHART MVE CARBO-MIZER 450 71.8" X 20" VENDOR GC IF OUTDOORS PROTECT W/ BOLLARDS. WRAP & LABEL SODA LINES 33 BAG-N-BOX COCA -COLA 18" X 30" VENDOR GC WRAP AND LABEL SODA LINES 34 CARBONATOR COCA -COLA VENDOR GC 35 WATER FILTER EVERPURE 9437-10 34.60" X 24.59" X 6.50" OWNER GC OUTLETS: 1. TO SODA MACHINE THROUGH COOLER BOX (50'-0" COIL), 2. TO ICE MACHINE, 3. TO TEA BREWER. SEE ENGINEERING SHEETS 36 WATER HEATER (TANKLESS - WALL MTD) NORITZ N-0931M-DV-ASME 24.4"X18.4"X9.8" GC GC BLOCKING AS REQUIRED 36a ►AIATER HEATER A/0 SMITH BT-80 28 1/2" X 61 1/2" GC GC GAS 36b WATER HEATER A/0 SMITH DVE-80-24 25 1/2" X 60 1/4" GC GC ELECTRIC 37c IAIATER HEATER RHEEM HE 55-130 52" X 32" X 23.5" GC GC BOLT/STRAP IN PLACE, ON SHELF, PER MFR RECOMMENDATION 37 DUNNAGE RACK (36") ADVANCE TABCO DUN-2036 20" X 12" X 36" OWNER GC WALK-IN COOLER/ENTRY DISPLAY 37a DUNNAGE RACK (48") ADVANCE TABCO DUN-2048 20" X 12" X 48" OWNER GC 37b " ADVANCE TABCO DUN-2060 20" X 12" X 60" OWNER GC 38 STORAGE SHELF (4 SHEI VES` ADVANCE TABCO EC-1824 18" X 24" OWNER GC STORAGE SHELF SITTING DIRECTLY NEXT TO 3 COMPARTMENT WASHING SINK SHALL BE EPDXY COATED 38a STORAGE SHELF (4 SHE I VES` ADVANCE TABCO EC-1836 18" X 36" OWNER GC 38b STORAGE SHELF (4 SHEI VFS� ADVANCE TABCO EC-1848 18" X 48" OWNER GC 38c STORAGE SHELF (4 SHELVES` ADVANCE TABCO EC-1860 18" X 60" OWNER GC 39 STORAGE cum=LF ran SHELVES) ADVANCE TABCO EC=2424 24" X 24" X 86" OWNER GC 39a STORAGE RACK (4 SHELVES) ADVANCE TABCO EC-2436 24" X 36" X 86" OWNER GC 39b STORAGE RACK (4 SHELVES) ADVANCE TABCO EC-2448 24" X 48" X 86" OWNER GC 39c STORAGE RACK (4 SHELVES) ADVANCE TABCO EC-2460 24" X 60" X 86" OWNER GC 40 WALL MOUNTED STORAGE SHELF (36") NEW AGE INDUSTRIAL 1121 20" X 36" OWNER GC USE T-BAR WALL SHELF W/ POT RACK, FOR SHELVING ABOVE 3 COMPARTMENT SINK. ALIGN BOTTOM OF SHELF WITH TOP OF DOOR FRAME. IF CEILING HEIGHT ALLOWS, NEXT ROW 24" ABOVE. 40a WALL MOUNTED STORAGE SHELF (48") NEW AGE INDUSTRIAL 1122 20" x 48" OWNER GC 40b WALL MOUNTED STORAGE SHELF (60") NEW AGE INDUSTRIAL 1123 20" x 60" OWNER GC 41 METRO CUSTOM 14" X 24" X 34" OWNER GC POST - 27UPS, CASTER - 5PC, 5PCB, SHELF - A1424NS, A1436NS, A1448NS, A1460NS, POST CUT IN FACTORY TO 27", KEC TO VERIFY SIZES REQUIRED IN FIELD 41a UNDER COUNTER STORAGE SHELF (36" METRO CUSTOM 14" x 36" x 34" OWNER GC 41b METRO CUSTOM 14" x 48" x 34" OWNER GC 41c METRO CUSTOM 14" x 60" x 34" OWNER GC 42 SANITIZER BUCKET SHELF MARSHALL AIR SYSTEMS INC 151459 24" X 12" X 6" VENDOR GC CAULK TO PARTITION UNDER SINK 43 BUN RACK (PREP AREA) BUCKHORN BA2926068405000 29" X 26" X 6.13" OWNER GC DOLLY - DY3027040099000 43a BUN RACK (SERVICE) (36") EAGLE A223665-A 18" X 36" X 80" OWNER GC MOBILE CART W/ CASTERS 44 LOCKERS (6 INDIVIDUAL DOORS) ERNST EL-6DR 12" X 20" X 77" OWNER GC SECURE TO WALL W/O LEGS 6" AFF & PROVIDE ALL BLOCKING AS REQUIRED 45 SAFE CORPORATE SAFE SPECIALISTS MB3020-SGI 20" X 16" 30" OWNER GC 46 FIRE EXTINGUISHER (EXITS) (TYPE ABC) BADGER/KIDDE 4XP87 - TYPE ABC 14.88" X 5.5" GC GC EXITS, WALL MOUNTED, CTR 36" - 48" 46a FIRE EXTINGUISHER (COOK) (TYPE K) BADGER/KIDDE 25074 - TYPE K 19 1/2" X 7" GC GC COOK, WALL MOUNTED, CTR 36" - 48" 47 OIL RECYCLING TANK FRONTLINE INT'L INC 3072-NA-DPO 31" X 31" X 82" OWNER GC DIRECT PIPED TO FRYERS 47a=PEACE rennv FRONTLINE INT'L INC 10SS-NA 12" X 30" X 9.5" OWNER GC 48 CHILD HIGH CHAIR RUBBERMAID 7806-08PLAT OWNER GC 49 FRONT COUNTER PROVIDED BY G.0 GC GC 49a OFFICE COUNTER PROVIDED BY G.C. GC GC 49b DRINK COUNTER PROVIDED BY G.C. GC GC 49c GC GC 50 SNEEZE GUARD (FOR 40" HIGH WAI I AT CRL CONTEMPORARY 201 SERIES OWNER GC 1 1/2" BRUSHED STAINLESS TUBING GLASS ON SLANT & FRONT ONLY. CONTACT FIVE GUYS CONSTR. MGR. BRIAN GILL FOR CLARIFICATION. FIELD VERIFY LENGTH SANDWICH WRAP TARI E� 50a SNEEZE GI IeRD (FOR 481' HIGH WALLAT CRL CRL BRUSHED STAINLESS 18" HIGH 1" ROUND PP56 SLIMLINE SERIES - OWNER GC STRAIGHT FRONT COUNTER/PARTITION CENTER POST. CONTACT FIVE GUYS CONSTR. MGR. BRIAN GILL FOR CLARIFICATION. FIELD VERIFY LENGTH I 8. Ennn PREP TARE 1AiARneINC- SHEI E) 50b SNEEZE r_I IARD ADM P-445 OVERALL AVERAGE HEIGHT 22" OWNER GC 51 BEVERAGE CABINET (STAINI ESS STL 4 SOUTHERN STAINLESS FG-BEV 96 96"W X 37"D X 27"H OWNER GC 52 MUSAK SYSTEM OWNER GC 53 TOUCH BLOCK OWNER GC 54 BUG LIGHT OWNER GC BLOCKING AS REQUIRED 55 FRY TABLE WITH BACKSPLASH (48") SOUTHERN STAINLESS FG-015 30" X 48" X 50" OWNER GC 56 FRY THAW CART MQ BASKETS NEW AGE 1210 19" X 27" X 52 1/2" OWNER GC NOTE: FRANCHISEE TO CONFIRM USE OF EQUIPMENT SHOWN, SIZES, AND QUANTITIES PRIOR TO ORDERING EQUIPMENT. ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916- Fax 770 619 5919 lb LIC # AR 12885 0C z 1qW IF W U I.r, In Z en CL W U _j cC v)0_j c0 U_ 0J J zi U zi = 0 U U _ 0C >- CL W N LL N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFYTHE ARCHITECT WITH RESPECT TO: ANY CHANGES MADETOTHE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OFTHE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE EQUIPMENT SCHEDULE PROJECT SHEET NO. NO 1030 DRAWN BY EIJS NOTE: FRANCHISEE TO CONFIRM USE OF EQUIPMENT SHOWN, SIZES, AND QUANTITIES PRIOR TO ORDERING EQUIPMENT. DATE 11-23-10 1 5 OF 8 wRAAI�I♦� r , I T i EN�IIIRAF19 "7 1 FINISH PLAN 'KONDECCORNER GUARD AS MFD BY SCHLUTER SYSTEMS DUROCK 5U135TKATE WALL CORNER DETAIL 5/5" DUROCK (TYf ) WALL TILE OR FRP (SEE PLAN) CERAMIC TILE COVE BASE "B-1" QUARRY TILE "QT" COVE BASE DETAIL FINISH LEGEND FINISH DESCRIPTION FINISH MANUFACTURER MANUFACTURER NO. COLOR TYPE REMARKS NO QUARRY TILE BASE B-1 IVGORE MATE RIA77 — CMG GREY QUARRY DOUBLE ABRASIVE COVE KITCHEN, SERVICE 6"x12" BASE CERAMIC TILE BASE 13-2 CREATIVE MATERIALS a700029 CMC ODINO STRAIGHT CUT FROM 12" X 12'' TILE CORE TEXTURED CERAMIC TILE BA5E B_3 CREATIVE MATERIALS 1091775 COVE BASE BLACK 6' X6" COVE ALTERNATE TO B-2 WHEN COVE (ALTERNATE) CORD BASE REQ'D BY GO DE CEILING TILE ACT-1 ARMSTRONG CLEAN ROOM VL-870 WHITE 2' X 4' 1 1 PRELUDE ML GRID (WHITE) 5ERVIGE/KITCHEN CEILING TILE ACT-2 AKM5TRONG GORTEGA SQUARE LAY -IN BLACK 2' X 4' 15/16'' PRELUDE ML7501 & ML7323 #769NF GRID (BLACK) DINING CEILING CORTEGA SQUARE LAY -IN 15/16" PRELUDE ML7301 & ML7323 CEILING TILE ACT-3 ARMSTRONG #769NF WHITE 2' X 4' GRID (WHITE) STORAGE RADAR CLIMAPLUS 15/16'' DONN DX/DXL GRID (BLACK) CEILING TILE ACT-4 USG SQUARE LAY -IN #2210-205 BLACK 2' x 2' DINING QUARRY TILE QT CREATIVE M E I L CORD — M E U DOUBLE ABRA5IVE 6" X 6" KITCHEN, C.O.F.=1.25 DRY; 1.05 WET FLOOR CREATIVE MATERIALS 12" X 12", DINING, RE5TKOOM5 PORCELAIN TILE PT CORD 5700029 GMC ODINO TEXTURED C.O.F.= .93 DRY; .76 WET DINING, E M 1 U PORCELAIN TILE GROUT GK-1 HYDROMENT H142 FRENCH GRAY SANDED JOINT) GROUT QUARRY TILE GROUT GK-2 HYDROMENT H151 TAUPE SANDED KITCHEN, SERVICE (1/4'' GROUT JOINT) DINING, KE5TROOM (1/16" GROUT WALL TILE GROUT GR-3 HYDROMENT H152 WHITE UN5ANDED JOINT) 5EKV COUNTER LAMINATE FL-1 FORMICA 559-58 5TOP RED MATTE SERVICEV CABINET LAMINATE MILLWORK MANAGER'S DESK PL-2 FORMICA 459-58 BRIGHT WHITE MATTE MANAGER'5 DESK & SHELVES LAMINATE LAMINATE SERVICE COUNTER C CORIAN HOT (C) SERVICE COUNTER ALTERNATE 50LID SURFACE — UPGRADE COAT 1: 5-W PREPRITE 200 INT. INTERIOR PAINT ACRYLIC LATEX PRIMER, B28W200. (CEILING, DINING P-1 SHERWIN WILLIAMS P-1 FIVE GUYS BLACK FIVE GUYS BLACK SEMI-GLO55 COAT 2 AND 3: 5-W DTM ACRYLIC WALLS) 5EMI-GL055 COATING, B66BW211 COAT 1: DTM 5G BONDING PRIMER, EXTERIOR PAINT P-2 SHERWIN WILLIAMS P-4 FIVE GUYS BLACK FIVE GUYS BLACK ACRYLIC B66A50. (ACCENT) 5EM1-GLO55 COAT 2 AND 3: 5-W DTM ACRYLIC SEMI -GLOSS COATING, 86611 COAT 1: 5-W DTM ACRYLIC INTERIOR PAINT P-3 SHERWIN WILLIAMS P-3 FIVE GUYS RED FIVE GUYS TILE RED ACRYLIC PRIMER/FIN15H, 1366W1. (METAL - GALVANIZED) GLO55 COAT 2 AND 3: 5-W DTM ACRYLIC GLO55 COATING, B66T104 COAT 1: 5-W KEM BOND H5 UNIVERSAL METAL PRIMER, B5OZ PAINT INTERIOR PAINT P-4 SHERWIN WILLIAMS P-3 FIVE GUYS RED FIVE GUYS TILE RED ACRYLIC 5ERIE5. (METAL IRON, STEEL) GLO55 COAT 2 AND 3: 5-W DTM ACRYLIC GLO55 COATING, B66T104 COAT 1: 5-W PREPRITE CLA551C LATEX INTERIOR PAINT P-5 SHERWIN WILLIAMS P-3 FIVE GUYS RED FIVE GUYS TILE RED ACRYLIC GLO55 PRIMER, 1328W101. (WOOD) COAT 2 AND 3: 5-W DTM ACRYLIC GLOSS COATING, B66T104 COAT 1: DTM GLO55 BONDING EXTERIOR PAINT P_6 SHERWIN WILLIAMS P-5 FIVE GUYS RED FIVE GUYS RED ACRYLIC GLOSS PRIMER, B66A50. (ACCENT) COAT 2 AND 3: 5-W DTM ACRYLIC GLO55 COATING, B66T104 COAT 1: 5-W PREPRITE 200 INT. INTERIOR PAINT P-7 SHERWIN WILLIAMS P-2 FIVE GUYS WHITE FIVE GUYS TILE WHITE EGGSHELL LATEX PRIMER, B28W200. (CEILING, WALLS) SATIN COAT 2 AND 3: 5-W DURATION HOME SATIN, A97W151 OUTSIDE CORNER GG-1 5HLUTER 5Y5TEM5 SGHLU NDEC 5TAINLE55 STEEL OUTSIDE CORNERS IN DINING AND AT GUARDS R080E EV/ROb0 _ TYP TILE WALL FINISH CREATIVE MATERIALS 41/4" X 41/4" 13ULLN05E TRIM - DINING, SERVICE, FIELD TILE CT-1 CORD — WHITE GLO55Y KE5TROOM5 DINING, SERVICE (WHERE CREATIVE MATERIALS 41/4'' X 41/4" INDICATED), KE5TROOM5. SEE WALLS ACCENT TILE CT-2 CORP — RED GLO55Y INTERIOR ELEVATIONS FOR ACCENT TILE PATTERN LOCATIONS FIBERGLA55 FRP CRANE GLA513OARD-P WHITE (85) EM13055ED PREP ROOM, SERVICE REINFORCED PLASTIC CLA55 C FULL HEIGHT PANELS BEHIND COOK 5TAINLE55 STEEL 55 CUSTOM 5TAINLE55 STEEL 18 GA LINE & WHERE NOTED IN SERVICE. — FINISH #4 (NOTE: MARSHALL AIR PROVIDES 5TAINLE55 STEEL BEHIND HOOD) NOTES: NATIONAL ACCOUNT FOR TILE AND GROUT: CREATIVE MATERIALS CORPORATION, ATTN; SCOTT 13OCKETTI (518) 713-5366, 5DOCKETTI@CREATIVEMATERIALECORP.COM NATIONAL ACCOUNT FOR PAINT: SHERWIN-WILLIAMS, ATTN: QUANG TRAN (703) 926-6120, ACCT# 9395-8905-7, 5WREP6376@5HERWIN.COM PAINT ORDERING NOTE: WHEN ORDERING PAINT, USE FIVE GUYS ENTERPRISES (FGE) NATIONAL ACCOUNT. DO NOT USE FIVE GUYS OPERATIONS (FGO). VERIFY COLOR 15 SAME AS SPECIFIED ON COLOR COLUMN OF FIN15H SCHEDULE TO BACK EDGE OF F05 2 @ DINING N I N G COUNTER A5 SHOWN NOTE: INTERIOR DECOR, SIGNAGE AND WALL HUNG ART E LEV. WORK TO BE SUPPLIED AND INSTALLED BY FIVE GUYS CORPORATE REPRESENTATIVE A_L�. 5CALE:3/8" = 1'-0" O FINISH PLAN NOTES: GENERAL: - APPLY WATERPROOF MEMBRANE 6" UP AND 12" OUT AT ALL WALL PARTITIONS AT KITCHEN AND SERVICE AREA5- BOTH 51DE5. CHECK WITH THIN SET MANUFACTURER FOR RECOMMENDED PRODUCT AND INSTALLATION. TILE PATTERN TO BE ON ALL WALLS IN DINING, REST ROOMS AND ALL AREAS VISIBLE TO PATRONS. ALL c� SHEETING BEHIND TILES TO BE 5/8" DUPOCK. ALL SHEETING BEHIND PAINTED SURFACES TO BE 5/8" GYPSUM - BOARD. ALL SHEETING IN RE5TROOMS TO BE MOISTURE RESISTANT. FULL TILES START AT 5OTTOM. 13ULLN05E TOP TILE AT ALL WALLS. CUT TILE AT TOP @ MILLWORK. WHITE TILE TO CEILINGS IN COOK AND 5EVICE AREAS. TILE TO WRAP ONTO SILL UP TO MULLIONS AT STOREFRONT KNEEWALL. - EXISTING INTERIOR CONCRETE FLOOR SURFACES TO REMAIN 5HALL BE THOROUGHLY CLEANED, REPAIRED, AND SEALED AS PER FLOOR COVERING MANUFACTURER REQUIREMENTS - PROVIDE CORNER GUARD'RODECA5 MANUFACTURED BY SCHLUTER SYSTEMS AT ALL WALL TILE CORNERS - SEE o DETAIL TH15 SHEET c�1 - PROVIDE REDUCER / TRANSITION 5TKIF'KENO RAMP' #AEPP 100 1365 AS MANUFACTURED BY SCHLUTER SYSTEMS OR EQUAL AT AREAS WHERE PORCELAIN OR QUARRY TILE FLOOR ABUTS CONCRETE FLOOR. OCONTINUE DINING WALL FINISHES TO BACK EDGE OF P05 COUNTER; SEE INTERIOR ELEVATIONS FOR CLARIFICATION 2. TILE PATTERN ON HALF HEIGHT WALL SHALL MATCH PATTERN AT FULL HEIGHT WALLS - SEE ELEVATIONS AT DINING FOP REFERENCE (TYP) 3. PROVIDE FRP FINISH ON THE WALLS ABOVE MOP SINK. RECESS SINK INTO FLOOR AND PROVIDE FLOOR TILES WITH FINISHED EDGES AS REM). 4. PROVIDE BA5E 13-1 ALONG FACE AND QT ON TOP OF CONCRETE CURB AT SAFE 5. PROVIDE A CONTINUOUS WATERPROOF MEMBRANE (SHOWN DOTTED) ALONG DEMI5ING WALL, 1'-0" ABOVE FLOOR ON OUTER EXPOSED SURFACE OF DUROCK, AND UNDER FLOOR FIN15H 4'-0" OUT FROM DEMI5ING WALL IN SERVICE, PREP AND STORAGE AREAS. MEMBRANE SHALL BE LATICRETE HYDR05AN D5-663.0-0509. 6. EXTEND CERAMIC TILE FINISHES ON SILLS AND JAMB5 7. PAINT HORIZONTAL BAND W/ P-1 9 UPPERMOST SECTION OF DINING WALLS -SEE ELEVATIONS FOP CLARIFICATION ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 I 3/LD LIC # AR 12885 w z W U Ln M M CL Q ICL W :O_jc� N O 0 N m LL Z J vi OQ J IIIIIIIIIIIIIJ. IL U1 O L Ua_ 1'i N W N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFYTHE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT. OR CHANGES IN ANY ASPECT OFTHEWORK. OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND. INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEETTITLE FINISH PLAN PROJECT SHEET NO. NO 1030 DRAWN BY EJS Awm4 DATE 11-2-3-10 6 OF 8 3 5/8" 20 GA METAL STUD FRAMING 9 16" O.C. - SECURE TO ROOF 5TRUCTURE 3 5/8" 20 GA METAL STUD 5RACING 5/8" GYF 5D ON METAL STUD FRAMING ANGE - EOLL. (SEEHNT ELEVS) DINING ACT-1 <++ TRACK RUNNER SERVICE AA BOTTOM_ SOFFIT +9'-0" — - — SEE RCF 3 A-3 SEE RCf -- ACT 4 SWAGE COMPK AIRCRAFT CAE 5UFFORTED i DIFFUE SOFFIT SECTION 5CALE:1" = 1'-0" GALVANIZED AIRCRAFT CABLE - SECURE TO 5TRUCTURE ABO'v BLACK GROMMET - MASTER CASTER #00209 2 3/5" DIA (GRAINGER ITEM #1AFU1) LOW PROFILE GRILLE - SEE MECH DRAWINGS FOR 5FEC EXP05ED ROUND DUCT - SEE MECH DRAWINGS NOTE: 5FIRAL DUCT, GRILLES / DIFFUSERS AND HANGER WIRE TO BE FINISHED F-3. FULL TILE AT HANGER WIRE LOCATIONS, GLUE BLACK GROMMET IN HANGER WIRE OPENING. DO NOT BOX OUT 5UFFLY REGISTER 4 SECTION @ SPIRAL DUCT A-5 I 5CALE:1" = 1'-0" 5 OPEN SIGN 5CALE:3/8" = 1'-0" LINE OF MEZZANINE FLOOR AND ACCE55 POINT (BELOW) fACT_C�1llNG_jNPRF:� AREA - TO EXTEND ABOVE STORAGE MEZZANINE LINE OF MEZZANIN� FLOOR AND ACCESS _ POINT (BELOW) A 2 I`'IEZZANINE RELECTED CEILING PLAN A-S NOT TO 5CALE LIGHT FIXTURE LEGEND A/A1 2X4 FLUORESCENT: E o 0 0 0 2X2 FLUORESCENT PENDANT: WHITE (AND/OR RED) (INSIDE AND OUT) DO NOT FAINT WIRING RECESSED DOWNLIGHT 4' TRACK W/ (4) HEADS XA ® LED EXIT SIGN XB EMERGENCY BATTERY PACK W/ TWO HEADS XC LED EXIT 51GN W/ EMERGENCY HEADS NOTE: REFER TO ELECTRICAL SHEETS FOR LIGHTING 51"ECIFICATION5 OREFLECTED CEILING PLAN NOTES: BACK OF OPEN SIGN GENERAL: (TYF OF 3) - WHERE EXPOSED DUCTS ARE 5FECIFIED, DUCTS SHALL BE FINISHED F-3 - AT BLACK ACOUSTICAL CEILING TILE, DIFFUSERS TO 5E FINISHED TO MATCH TILE - CENTER ALL CEILING GRIDS IN SPACE AS SHOWN - SEE ENGINEERING DRAWING5 FOR ADDITIONAL INFORMATION ON ALL CEILING MOUNTED ITEMS - INSTALL SUSPENSION 5Y5TEM5 TO COMELY WITH A5TM C636, WITH HANGERS 5UFFORTED ONLY FROM BUILDING STRUCTURAL MEMBERS. LOCATE HANGERS NOT LE55 THEN 6" FROM EACH END AND SPACES 4'-0" ALONG EACH CARRYING MEMBER, UNLE55 OTHERWISE INDICATED, LEVELING TO TOLERANCE OF 1/5" IN 12'-0" NON -ACCUMULATIVE EXISTING STOREFRONT NOTE: INSURE OPEN 51GN 15 VIEWABLE FROM OUT5IDE. IN51URE V151131LITY 15 NOT BLOCKED BY NEW AWNINGS OR WINDOW MULLIONS. ONO CEILING TILE IN TH15 AREA 2, AFFROXIMATE MENU BOARD LOCATION; CONFIRM PLACEMENT WITH FRANCHISEE 3. HOOD. G.C. SHALL OBTAIN ALL HOOD DRAWINGS FROM CAPTIVE -HIRE. PROTOTYPE HOOD DRAWINGS SHOWN ON MECHANICAL SHEETS ARE FOR INFORMATIONAL FURFO5E5 ONLY 4. HALF HEIGHT WALL 5ELOW, SHOWN DASHED 5. CENTER LIGHT FIXTURE IN CEILING TILE HALF A5 5HOWN (TYP) 6. BOTTOM OF PENDANT LIGHT FIXTURE = 8'-6" AFF 7. CENTER LIGHT FIXTURE IN GYF BD CEILING A5 SHOWN. 8. GYP. BOARD CEILING, FAINT FINISH F-7 9. FENDANT FIXTURES UNDER SERVICE & 5EVEKAGE COUNTER SOFFITS TO 5E HUNG W/ 6" COKD. 10. 50TTOM OF GYF. BD. SOFFIT @ 9'-0" AFF; FAINT F-7 11. LINE OF WALK-IN COOLER BELOW, SHOWN DASHED 12. AFFROXIMATE OPEN SIGN LOCATION; CONFIRM PLACEMENT WITH FRANCHISEE - SEE DETAIL THIS SHEET 13. G.C. SHALL FIELD VERIFY THAT CEILING HEIGHT SHOWN 15 ACHIEVABLE 14. EXHAUST HOOD TO BE 5U5FENDED WITH THREADED RODS FROM ROOF 5TRUCTURE A50VE. G.C. SHALL VERIFY WITH LANDLORD'S ARCHITECT AND/OK STRUCTURAL ENGINEER THAT KOOF CAN ADEQUATELY SUPPORT HOOD EQUIPMENT. 15. TRACK FIXTURE TO 5E LOCATED ON REAR SIDE OF SOFFIT. 16. EXTEND FREF AREA CEILING OVER STORAGE MEZZANINE (SEE 5EFAKATE KCP) n 7 7 -- O B1E B1E 16 q q q - lt " B -----f--------- -- I I 8 11 i 8 A B o-nO 7 O- - 1 ACT-1 B1 E A 8 -1011 I 13 ® O 8' O" B/N L 16 A -I- NA q - lv\�- - - CR C O O XC 3 -1 _ 1 3 14 —� - EQ. EQ. R A A A A A A C1N R ACT-1 B X 6 5 - 10 2 X-B- B B CW A A A A A A C _5 0 5 0 5- _y,01 Y O -- CR CW R pl CW CR = W - 9 9 _ O O O 15 g = c� 14'4IF , C CR C O B/NL O B O B/NL CR � O C O B CR i O B/NL C vv O - B A5 T CR C CR � XB C CR C - CR -� O O O O X B B B B _ 121-0" � B B Ed B CO CR C �- ACT-4 CR I � C I _ � CR I � CW �`� 13 12 d B EB 6 5 CR C CR CR O 0 O X CWI O O O, O 12 1 XC1 -� 12 X � �- _--: t _—_7 --'- - � X REFLECTED CEILING PLAN 5CALE:1/4" = 1'-0" ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 A0 LIC # AR 12885 W Z VIP LLI ULn M Z � M CL W ice. O J 0� ' V)00 V) m U_ O J J J_ � � oC O >- U CL cC Lu N = Lu N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADETOTHE CONSTRUCTION DOCUMENTS BYANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OFTHE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE REFL CEILING PLAN PROJECT SHEET NO. NO 1030 DRAWN BY AmoS EJS DATE 11-23-10 7 OF 8 4 OPEN TO 5ERVICE q-5 AREA W/ 55 WALL FINISH BEYOND / III SIDE OF COUNTEK5 BEYOND ELEV. @ POS � PICKUP COUNTER P-7 i - - - r - CV - v \ CT-2 O B-2-(ZED_ B2 - DOOR & FRAME - FIN15H 5EE DOOR SCHEDULE 4 /e7:2 ELEV. @ BEVERAGE CO U NT�1� A-2 A-0p I 5CALE:5/8'' = 1'-0" � ELEV. @ WOMEN'S RESTROOM A-rp 5CALE:3/8" = 1'-0" N � ELEV. @MEWS RESTROOM A-<p I 5CALE:3/8'' = 1'-O" \ / CE:) IF LI 7"MIN -9"MAX CT-1 aa NOTE: 1. 5EE ENLARGED FLOOR PLAN & 5CHEDULE FOR TOILET ACCE55ORIE5 2. 5EE COVER 5HEET FOR ADDITIONAL MOUNTING HEIGHT5 3. MEN'5 RE5TKOOM ELEV5 NOT SHOWN 51MILAR TO WOMEN'5 KE5TROOM M n • O CV ORDER HERE HALF HEIGHT 5ANDWICH WALL TOP @ 4'-0" AFF (BEYOND) B-2 cavI(ED- NOTE: INTERIOR DECOR, 51GNAGE AND WALL HUNG ART WORK TO BE 5UPPLIED AND IN5TALLED BY FIVE GUYS CORPORATE REPRE5ENTATIVE 12'-0" d- d- X < L9 1'-41/ _ 10'-11 1/2" n �F� I ' 1 111111,Rio ' wAr L! 1 1 N O NI in — DA5HED LINE5 @ RE5TROOM5 INDICATE REQ'D ADA CLEARANCE5 (TYF) APPROXIMATE FLOOR DRAIN o LOCATION (TYF); -I 5EE FLUMBING 6" METAL A- STUDS @ FLUMBING WALL - -- APPROXIMATE VJOMEI� - FLOOR DRAIN LOCATION (TYF); ' 5EE FLUMBING � ENLARGED PLAN Ca-)RESTROOMS A -gyp % 5CALE: 3/5" = 1'-0" RESTROOM FIXTURE $ ACCESSORY SCHEDULE NO. DESCRIPTION MANUFACTURER MANUFACTURER NUMBER COLOR SUPPLIED INSTALLED/CONNECTION REMARKS G C TOWN G C OWN MFS KEC A WALL MTD SOAP DISf EN5ER BOBRICK 8-2111 5T STL * * D15PEN5ER- 48" AFF MAX B COAT HOOK BOBRICK 8-212 ST 5TL * * BACK OF RESTROOM DOOR 38" TO 48" A F F C PAPER TOWEL 1)15f EN5EK GEORGIA-PACIFIC ENMOTION 59457 RED * * 54" MAX C1 PAPER TOWEL D15PEN5ER GEORGIA-PACIFIC ENMOTION 59466 5T 5TL * * RECESSED -FOR ADA COMPLIANCY MTD 48" MAX TO OPERATING MECHANISM p MIRROR BOBRICK 8-293 ST 5TL * * 40" MAX TO BOTTOM OF REFLECTIVE SURFACE E BABY CHANGING TABLE BOBRICK KOALA BEAR KARE VERTICAL #K5101-00 CREAM * * SHELF @ 34" AFF F TOILET T15SUE DISPENSER GEORGIA-PACIFIC COMPACT 53711 RED * * 19" AFF G GRAB BAR BOBRICK 8-6806.99(x18, 36, x42) 5T 5TL * * CENTERLINE OF HORIZONTAL GRAB BAR 33" - 36" AFF BOTTOM OF 18" VERTICAL GRAB BAR 39" - 41" AFF H SANITARY NAPKIN DISPOSAL BOBRICK 5-270 5T 5TL * * 19" MIN j WATER CL05ET WHITE EXISTING TO REMAIN K LAVATORY WHITE EXISTING TO REMAIN L URINAL WHITE * * 5EE PLUMBING DRAWINGS NOTES: 1. ALL FIXTURES & ACCESSORIES SHALL MEET ALL NATIONAL AND LOCAL CODES AND ADA REQUIREMENTS. 2. PROVIDE F.R. SOLID BLOCKING BEHIND GYP 5D WHETHER INDICATED ON THE DRAWINC75 OR NOT AT ALL WALL MOUNTED FIXTURES & ACCE55ORIE5 FOR 5ECURE ACHORING. VERIFY BLOCKING LOCATION WITH MANUFACTUKEK'5 5EPCIFICATION5. 3. CLEAR 51LICONE CAULK AT ALL FIXTUKE5 TO PARTITIONS. 4. REFER TO MOUNTING HEIGHTS ON COVER SHEET 5. PAPER TOWEL, TOILET TISSUE AND 50AP DI5PEN5ER WILL 5E PURCHASED BY FRANCHISEE THROUGH U5FOOD5 / NDG 6. PROVIDE ANY ACCESSORY ITEMS NOT EXISTING. FOR EXISTING ITEMS SUPPLIED BY LANDLORD VERIFY COMPLIANCE WITH FIVE GUYS CON5T MGR NOTE: 1. 5EE ENLARGED FLOOR PLAN & 5CHEDULE FOR TOILET ACCE55ORIE5 2. SEE COVER 5HEET FOR ADDITIONAL MOUNTING HEIGHTS 3. MEN'5 RE5TROOM ELEV5 NOT SHOWN 51MILAK TO WOMEN'5 KE5TROOM TOILET NOTES 1- HANDICAP ACCE551BLE W.C. SHALL HAVE 5EAT AT 17" TO 19" A.F.F., MEA5URED FROM THE TOP OF THE 5EAT TO THE FLOOR. CENTERLINE OF W.C. 5HALL BE LOCATED 18" FROM ADJACENT 51DEWALL. 2- 36" AND 42" GRAB 5AR5 COMPLYING WITH AN5I 117.1, ADA ACCESSIBILITY GUIDELINE5 5HALL BE MOUNTED AT 36" A.F.F. 3- APPROVED TYPE TOILET PAPER HOLDER 5HALL BE WALL MOUNTED AT 51DE OF W.C. AT A MINIMUM OF 19" A.F.F. AND AT A MAXIMUM OF 36" FROM REAR OF W.C. 4- LAVATORY OR VANITY 5HALL BE MOUNTED WITH BOTTOM OF APRON AT 29" A.F.F., WITH NO A13RA51VE 5URFACE5 UNDER. PIPE5 5HALL PROVIDE KNEE CLEARANCE OF 8", TOE CLEARANCE OF 9"' AND FLOOR 5FACE OF 17". IN5ULATE OR 5HIELD HOT WATER AND DRAIN PIPE5. PROVIDE LEVER OPERATED FAUCET5. 5- PROVIDE APPROVED TYPE PAPER TOWEL DI5PEN5ER AND LIQUID 5OAF DISPEN5ER MOUNTED 50 THAT ALL OPERATING MECHANI5M5 ARE NO MORE THAN 48" A.F.F. 6- MIRROR 5HALL BE 1/4" PLATE WITH FOLI5HED EDGE5, A MINIMUM OF 56" HIGH, MOUNTED TO WALL WITH BOTTOM REFLECTING EDGE AT A MAXIMUM OF 40" A.F.F. AND TOP EDGE AT A MINIMUM HEIGHT OF 74" A.F.F. 7- FKOVIDE DOOR 51GN PLAQUE WITH INTERNATIONAL 5YMB0L OF ACCE55I13ILITY. 8- IF URINAL5 ARE INDICATED, THEY 5HALL 5E MOUNTED WITH THE RIM AT A MAXIMUM OF 17" A.F.F. AND WITH A CLEAR FLOOR AREA OF AT LEA5T 50" WIDE BY 48" DEEF IN FRONT. 9- IF WATER FOUNTAIN 15 INDICATED IT 5HALL BE MOUNTED 50 THAT THE 5FOUT 15 NO HIGHER THAN 36" A.F.F. AND THERE 15 A CLEAR FLOOR AREA OF 30" WIDE BY 48" DEEF IN FRONT. ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 LIC # AR 12885 LU W U I.r, Z � M CL CL W 0_ LL O R NCO V) m LL Zi 0 J J 0 Ln >- U O_ N 0- W N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OFTHE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT ISTO BE RETURNED UPON REQUEST. SHEET TITLE INTERIOR ELEVATIONS TOILET PLANS $ DETAILS PROJECT SHEET NO. NO 1030 A,.ro DRAWN BY EJS DATE 11-23-10 g OF 8 6"0 (TYP. O �/ 4 PLACES) 100 H Oi I O' 1 10x8 0 10x10 UP TO EF-B ON ROOF. r; O 12"0 (TYP. 2 PLACES) O i O �k 1 A I_.-_ - 150 2 P 50 - >- -- i-- ' TS J. 150 e I I i ' x' O4 30x18 RTU -A I I O 22"0 r 30 16"0 (TYP. L — 11 2 PLACES) - OTs 450 r 16x18 I , I G i i i 8" 0 I- 02 450 1 LT �XISTING TON RTU O20"0 I -- T -- G RTU-A I L�--J © III500 500 l T.._,._____�—._.. is - --- -- --- -. -: FLOOR PLAN - HVAC SCALE_ V4" = 1'-0" -10x10 UP TO EF-A ON ROOF. L-+ 0 W — 22x14 °h i (() 500 NOTICE TO CONTRACTORS: ALL CONTRACTORS PRIOR TO BID SUBMISSION PROCESS SHALL VISIT PROPOSED WORK SITE AND FIELD VERIFY ALL EXISTING CONDITIONS. ANY CONDITIONS THAT DIFFER FROM THAT SHOWN ON THESE PLANS SHALL BE REPORTED TO ARCHITECT/ENGINEER SO THAT NEW AND REVISED BID DRAWINGS OR INFORMATION MAY BE ISSUED. MODIFICATIONS TO SCOPE OF WORK WHICH RESULTS FROM CONTRACTORS NEGLECT TO VISIT THE SITE PRIOR TO SUBMITTING BID, SHALL BE THE CONTRACTORS OUTSIDE AIR CALCULATION FIVE GUYS RESTAURANT DINING AREA = 92 SEATS * 20 CFM/PERSON = 1840 CFM KITCHEN AREA = 922 SQ.FT. * 20 PEOPLE/1000 SQ.FT. * 15 CFM/PERSON = 277 CFM RESTROOMS = 3 FIXTURES * 75 CFM/FIXTURE = 225 CFM CORRIDOR = 56 SQ.FT. * 0.05 CFM/SQ.FT. = 3 CFM TOTAL OUTSIDE AIR = 2345 CFM KEYED MECHANICAL NOTES O RIGID ROUND SPIRAL SUPPLY AIR DUCT MOUNTED BELOW CEILING FROM STRUCTURE ABOVE. DUCT SHALL BE LINDAB DOUBLE WALL SPIROSAFE MAU-1 ON GASKETED DUCTWORK. ROOF. SEE HOOD DWGS. O2 SUPPLY AIR DUCTWORK MOUNTED ABOVE THE CEILING. FOR SCHEDULE. O3 ABOVE CEILING. PLENUM RATED FLEXIBLE DUCTWORK 4O RETURN AIR DUCTWORK MOUNTED ABOVE THE CEILING. OS EXHAUST AIR DUCTWORK MOUNTED ABOVE THE CEILING. O6 GREASE EXHAUST DUCT ABOVE CEILING AND UP TO ROOF MOUNTED GREASE EXHAUST FAN. O7 GREASE EXHAUST DUCT DOWN TO GREASE EXHAUST HOOD CONNECTION. O8 MAKEUP AIR DUCT DOWN TO GREASE EXHAUST HOOD CONNECTION. (TYP. 4) O9 MAKEUP AIR DUCTWORK MOUNTED ABOVE THE CEILING. 10 MAKEUP AIR DUCT UP TO ROOF MOUNTED MAKEUP AIR FAN. 11 TEMPERATURE SENSOR. 12 THERMOSTAT LOCATION TO BE COORDINATED WITH TENANT. 13 CATEGORY III VENT AND INTAKE PIPING FROM TANKLESS WATER HEATER UP THRU ROOF TO MANUFACTURERS VENT CAP. INSTALL PER MANUFACTURERS RECOMMENDATIONS. MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCES TO COMBUSTIBLES. NOTE: CONTRACTOR TO VERIFY WITH BUILDING STRUCTURAL ENGINEER FOR ADDITION OF HOME EXHAUST, MAKE-UP AIR FANS &NEW ROOFTOP UNITS. SPECIAL EQUIPMENT NOTE: CONTRACTOR TO REFER TO RESTAURANT EQUIPMENT CUT SHEETS AND SCHEDULES FOR COORDINATION WITH ALL INSTALLATIONS WITH EQUIPMENT SUPPLIERS, KITCHEN DESIGNER, AND FIVE GUYS, INC. MAU-1 ON ROOF — SEE DETAIL 4/M-3. 12x12 EXHAUST — DUCT CLEANOUT. 4"STUD WALL WITH 5/8"- 6113E.RETARDANT TREATED PLYWOOD ON HOOD SIDE AND 5/8" DUROCK ON BACK HVAC LEGEND & ABBREVIATIONS ® SUPPLY DIFFUSER z RETURN GRILLE -)� I SUPPLY REGISTER O AIR DISTRIBUTION TAG E) THERMOSTAT cL- )IN(- MANUAL BUTTERFLY DAMPER FLEXDUCT RUNOUT 4=4� SPIN -IN W/DAMPER EF- EXHAUST FAN SD SPLITTER DAMPER RTU- ROOFTOP UNIT FDA FIRE DAMPER SDA SMOKE DAMPER EF-1 ON ROOF SEE DETAIL 3/M-3. I I I I I I EXISTING ROOF i STRUCTURE I I I J I CONTRACTOR SHALL INSTALL IA 1-1/2" LAYER OF FIRE WRAP TYPE INSULATION AROUND ANY ElPORTION OF HOOD EXHAUST DUCT THAT DOES NOT MEET THE 18" TO T I COMBUSTIBLES REQUIREMENT. INSTALL DUCTWRAP PER MANUFACTURERS REQUIREMENTS FOR ACHIEVING 0" 22"X20" SUPPLY CLEARANCE TO COMBUSTIBLES. USE AIR DUCT. FYREWRAP EZ 1.5 DUCT INSULATION OR / 3M FIRE BARRIER DUCT WRAP 15A. � 10"0 SUPPLY DUCT FROM MAU-1. 20x17 GREASE EXHAUST DUCT MADE OF MINIMUM 16 GAGE STEEL OR 18 GAGE STAINLESS STEEL. SLOPE DUCT A MINIMUM OF 2% SLOPE TOWARD THE HOOD. ALL DUCT WELDS TO BE CONTINUOUS LIQUID -TIGHT WELDS OR BRAZE MADE ON THE EXTERNAL SURFACE OF THE DUCT SYSTEM. CONTRACTOR CAN USE LISTED AND FACTORY -BUILT CAPTIVE AIRE HOOD COMMERCIAL KITCHEN GREASE DUCT SEE DETAIL 2/M-3. SYSTEMS. 000ro"c EWPMEH. HOOD PENETRATION DETAIL SCALE NONE TRACY M. WOODALL, P.E. 181 Sedgefield Overlook Dallas, Georgia 30157 T: (678) 642-7282 Florida PE F: (770) 406-2381 #56620 ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 IUA No ski •:;;GRID ' • ♦ ��� LU w Z _ ttJ J �� W (U Ln LU Z 0 LL CL CLL� O �0_j Z -' J l 0UlLL a� LU 1 � Ln ^ a aC w ).- N CL w N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND 15 NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROTECT IS PROHIBITED. IT IS TO BE RETURNED UPON REQUEST. SHEET TITLE HVAC FLOOR PLAN SCALE PROJECT SHEET NO. NO 1030 DRAWN BY TMW DATE II-23-10 1oF6 MECHANICAL NOTES 1. PROVIDE COMPLETE HVAC SYSTEMS TO MEET ALL CODES. HVAC - SUBCONTRACTOR IS RESPONSIBLE FOR SUBMITTING A TOTALLY INCLUSIVE BID WHICH COVERS ALL WORK NECESSARY TO MEET ALL CODES WHETHER SHOWN ON DRAWING OR NOT. 2. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND LOCAL CODES. ROOF TOP AIR CONDITIONING UNIT 3. ALL WORK TO CONFORM TO INDUSTRY STANDARDS AND ALL FEDERAL, STATE AND LOCAL CODES AND REGULATIONS. ACOUSTICAL LINER 4. PROVIDE OWNER WITH ONE (1) YEAR SERVICE AND ONE (1) YEAR UNDER UNIT �- GUARANTEE ON ALL EQUIPMENT AND A FIVE (5) YEAR GUARANTEE WATERTIGHT ON THE AIR CONDITION COMPRESSORS. FLASHING I I I I 5. COORDINATE WITH ALL OTHER TRADES BEFORE STARTING INSTALLATION. I I I MAKE NECESSARY VARIATIONS AT THAT TIME TO FIT INTO SPACE I I I CONDITIONS AT NO EXTRA COST TO THE OWNER. 6. HVAC SUBCONTRACTOR TO COORDINATE WITH ELECTRICAL SUBCONTRAC- TOR PRIOR TO STARTING ANY WORK OR ORDERING ANY MATERIALS TO INSURE COMPLETE COMPATIBILITY WITH ELECTRICAL SYSTEMS AND COMPLIANCE WITH ALL CODES. MECHANICAL SUBCONTRACTOR SHOULD VERIFY VOLTAGES, WIRE SIZES AND BREAKER SIZES AS PART OF THE S.A. -.-ti-- I FLEXIBLE COORDINATION. ---- -� CONNECTION -- 7. OBTAINING ALL REQUIRED PERMITS AND PAYING ALL ASSOCIATED FEES ARE THE RESPONSIBILITY OF THE CONTRACTOR. SUPPLY 8 RETURN DUCTWORK BY TENANT 8. ALL CONTROL WIRING SHALL BE RUN INSIDE WALLS OR ABOVE CEILINGS. IN UNFINISHED AREAS, ROUTE CONTROL WIRING INSIDE CONDUIT IN JOIST SPACE. 9. LOCATION OF ALL PENETRATIONS SHALL BE COORDINATED WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS. 10. ALL FANS 1/8 H.P. AND ABOVE SHALL HAVE FUSED DISCONNECT SWITCHES MOUNTED AT THE FAN. IF APPROVED BY LOCAL AUTHORITIES, NON -FUSED DISCONNECT SWITCHES MAY BE USED. DISCONNECTS PROVIDED BY ELECTRICAL CONTRACTOR. 11. FOR ALL UNITS OVER 2000 CFM PROVIDE ONE SMOKE DETECTOR IN THE RETURN AIR DUCT. 12. GREASE AND OIL ALL EQUIPMENT AS REQUIRED AND REPLACE ALL FILTERS BEFORE TURNING JOB OVER TO OWNER. 13. DUCTS AND DIFFUSERS ARE SHOWN TO CLEAR LIGHT FIXTURES; HOWEVER, SOME SHIFTING MAY BE REQUIRED - VERIFY IN FIELD BEFORE INSTALLATION. 14. THE MECHANICAL DRAWINGS ARE DIAGRAMATIC AND SHOW THE RELATIONSHIP BETWEEN EQUIPMENT AND CONNECTIONS. DO NOT SCALE THE DRAWINGS FOR EXACT SIZE OR LOCATIONS. BUILDING DIMENSIONS SHALL BE TAKEN FROM ARCH. PLANS AND EQUIPMENT DIMENSIONS SHALL BE TAKEN FROM CERTIFIED EQUIPMENT DATA. 15. A CERTIFIED TEST AND BALANCE REPORT BY AN AGENCY OR COMPANY OTHER THAN THE INSTALLER IS TO BE PROVIDED WITH A FOLLOW-UP REPORT ONCE ADJUSTMENTS ARE MADE. 16. PLANS AND SKETCHES ARE SUBMITTED TO LIMIT, EXPLAIN AND DEFINE CONDITIONS, SPECIFIED REQUIREMENTS, PIPE SIZES AND MANNER OF ERECTING WORK. STRUCTURAL OR OTHER CONDITIONS MAY REQUIRE CERTAIN MODIFICATIONS FROM THE DESIGN SHOWN; REQUIREMENTS NECESSARY FOR SATISFACTORY OPERATION SHALL REMAIN UNCHANGED. IT MAY BE NECESSARY TO SHIFT PIPES AND THESE CHANGES SHALL BE MADE AS REQUIRED. ALL SUCH CHANGES OR DESIGN MODIFICATIONS SHALL BE REFERRED TO THE ARCHITECT FOR APPROVAL BEFORE PROCEEDING. EXTRA CHARGES SHALL NOT BE ALLOWED FOR THESE CHANGES. THE SUBCONTRACTOR SHALL REALIZE THAT THE DRAWINGS COULD NOT DELVE INTO EVERY STEP, SEQUENCE OR OPERATION NECESSARY FOR THE COMPLETION OF THE PROJECT WITHOUT DRAWING ON THE SUBCONTRACTOR'S EXPERIENCE OR INGENUITY. HOWEVER, ONLY TYPICAL LAYOUT IS SHOWN ON THE PLANS. IN CASES WHERE THE SUBCONTRACTOR IS NOT CERTAIN ABOUT THE METHOD OF INSTALLATION OF HIS HIS WORK, HE SHALL CONSULT WITH THE ARCHITECT. LACK OF DETAILS SHALL NOT BE AN EXCUSE FOR IMPROPER INTALLATION. IN GENERAL THE DRAWINGS ARE DIAGRAMMATIC AND THE SUBCONTRACTOR SHALL INSTALL HIS WORK IN SUCH MANNER SO THAT INTERFERENCES BETWEEN THE VARIOUS TRADES IS AVOIDED, IN CASES WHERE INTERFERENCES DO OCCUR, THE ARCHITECT IS TO STATE WHICH EQUIPMENT, PIPING, ETC. IS TO BE RELOCATED REGARDLESS OF WICH ITEM WAS INSTALLED FIRST. 17. DUCT SIZES ARE SHOWN AS CLEAR INSIDE DIMENSIONS. PROVIDE FLEXIBLE CONNECTIONS WHERE DUCTS CONNECT TO UNIT. 18. SPIN -IN TAKE -OFF TO BE MADE WITH GENFLEX MODEL SM-1 DEL OR EQUIVALENT. 19. NTPEDAMPERS NSHALL BE OUFFI- CEGAUGEiO RVENTT UCING OWHERE VIBRAT NdAND SHALL BE OPERATED BY A QUADRANT DAMPER ADJUSTER WITH LOCKING FEATURE WHICH WILL HOLD DAMPER SECURELYIN POSITION AT THE DESIRED SETTING. 20. REGISTERS, DIFFUSERS AND GRILLES SHALL BE FURNISHED AND INSTALLED IN SIZES AND AT LOCATIONS AS SHOWN ON DRAWINGS. ALL OUTLETS SHALL BE INSTALLED PLUMB AND LEVEL AND PARALLEL TO THE BUILDING WALLS OR FLOORS. CEILING DIFFUSERS AND GRILLES SHALL BE AS SCHEDULED, OR APPROVED EQUAL. 21. PROVIDE OPERATING MAINTENANCE MANUAL FOR FURNISHED EQUIPMENT. 22. MOUNT ALL THERMOSTATS 48" A.F.F. UNLESS OTHERWISE NOTED. ANY THERMOSTAT LOCATED ON AN EXTERIOR WALL SHALL BE MOUNTED ON AN INSULATING BASE. ALL CONTROL WIRING SHALL BE RUN INSIDE WALLS OR ABOVE CEILINGS. 23. ALL SUPPLY AND RETURN DUCTWORK FROM ROOFTOP UNITS INSTALLED ABOVE CEILINGS TO BE GALVANIZED LOW PRESSURE DUCTWORK WITH EXTERNAL DUCT WRAP INSULATION. ALL DUCTWORK TO BE CONSTRUCTED PER CURRENT SMACNA LOW PRESSURE DUCT REQUIREMENTS. ALL JOINTS SHALL BE SEALED WITH DUCT SEALER. PROVIDE 2" FIBERGLASS DUCT WRAP WITH U.L. LISTED FOIL VAPOR BARRIER AND A MINIMUM R VALUE OF 6.0. ALL EXPOSED SPIRAL DUCT TO BE LINDAB DOUBLE WALL SPIROSAFE GASKETED DUCTWORK. 24. PROVIDE FIRE DAMPERS AT ALL FIRE RATED PENETRATIONS. 25. ALL DUCTWORK SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR CEILING STRUCTURE. ALL DUCTWORK SHALL BE SUPPORTED AND ATTACHED TO STRUCTURE PER CURRENT SMACNA STANDARDS. 26. FLEXIBLE DUCTWORK SHALL BE HART & COOLEY TYPE Rf214 OR EQUAL WITH A MAXIMUM LENGTH OF 6-0". FLEXIBLE DUCTWORK SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE AND SHALL BE ROUTED AND SUPPORTED WITHOUT CAUSING ANY AIR FLOW RESTRICTIONS. 27. PROVIDE A MINIMUM OF 10'-0" SEPERATION BETWEEN ALL FRESH AIR INTAKES AND EXHAUST. 28. THE EXHAUST OUTLETS OF THE COMMERCIAL HOODS SHALL TERMINATE OUTSIDE THE BUILDING AND SHALL BE LOCATED TEN FEET AWAY FROM ANY ADJACENT BUILDING, PARKING AREA, ADJACENT PROPERTY LINE, WINDOW, DOOR OR AIR INTAKE OPENING AND SHALL BE A MINIMUM OF TEN FEET ABOVE ADJOINING GRADE LEVEL AND SHALL TERMINATE 40 INCHES ABOVE ROOF SURFACE WHEN THERE IS A ROOF TERMINATION. 29. ALL KITCHEN HOODS AND FANS SHALL MEET OR EXCEED REQUIREMENTS OF NFPA 96 FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS. 30. THE GREASE HOOD VENT TERMINATION MUST MEET SECTION 506.3.12 OF THE IMC. 31. CLEARANCE FOR TYPE I HOOD SYSTEM SHALL BE INSTALLED WITH A CLEARANCE TO COMBUSTIBLES OF NOT LESS THAN 18 INCHES. 32. ALL FRAMING BEHIND THE GREASE HOODS MUST BE NON-COMBUSTIBLE PER SECTION 507.9 OF THE 2006 IMC. 33. EXTERNAL HOOD JOINTS, SEAMS AND PENETRATIONS FOR TYPE I HOODS SHALL BE MADE WITH A CONTINUOUS EXTERNAL LIQUID -TIGHT WELD OR BRAZE TO THE LOWEST OUTERMOST PERIMETER OF THE HOOD. INTERNAL HOOD JOINTS, SEAMS, PENETRATIONS, FILTER SUPPORT FRAMES AND OTHER APPENDAGES ATTACHED INSIDE THE HOOD SHALL NOT BE REQUIRED TO BE WELDED OR BRAZED BUT SHALL BE GREASE TIGHT. 34. DUCTWORK FROM KITCHEN HOODS TO EXHAUST FANS SHALL BE CONSTRUCTED OF MINIMUM 18 GUAGE STAINLESS STEEL OR 16 GAUGE BLACK IRON ALL WELDED COSNTRUCTION WITH WELDED JOINTS. PROVIDE HINGED ACCESS DOORS AS REQUIRED BY CODE. 35. THE ANSUL PULL STATION FOR THE HOOD IS TO BE RECESSED WITH THE CONDUIT ENCLOSED IN THE WALL. COORDINATE WITH CAPTIVE AIRE DRAWINGS. CONDENSATE DRAIN LINE C--I - FACTORY ROOF CURB T--]�Rh � 0 I ROOFTOP UNIT DETAIL M-2 P SCALE NONE I PRESSURE TREATED WOOD NAILER----'12" 2" ACOUSTICAL FIBERGLASS UNDER UNIT RESILIENT GASKET 90# MINIMUM SURFACE BASE FLASHING ROOF SYSTEM (SEE ARCH. DRAWINGS) METAL ROOF DECKING PREFAB CURB & CANT WITH RIGID INSULATION ROOFTOP UNIT CURB DETAIL SCALE NONE TURNING VANES PER LATEST SMACNA STANDARDS --�, DOUBLE THICKNESS DIVERTING VANE - SPLITTER ROD SPLITTER DAMPER WITH LOCKING QUADRANT 3 \ SPLITTER DAMPER. DETAIL M-2 / SCALE NONE VANES TO BE PRE -ASSEMBLED ON RUNNER PLATE. GALVANIZED VANES DOUBLE THICKNESS TURNING VANES SCALE NONE ROOFTOP UNIT SCHEDULE MARK CFM O.A. CFM ESP W.G. H.P. COOLING HEATING BTU/HR BASIS OF DESIGN CARRIER OR EQUAL SEER/EER NOTES EAT°FDb EAT°Fwb CAP.MBH INPUT OUTPUT RTU-A 3,000 765 0.8" 3.0 80"F 670F 90.1 125,000 103,000 48TCDD008A2 11.0/- 0 i) PROVIDE FULL PERIMETER FACTORY ROOF CURB. COORDINATE VOLTAGE REQUIREMENTS WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING. FAN SCHEDULE MARK CFM E.S.P. WG DRIVE H.P. TYPE BASIS OF DESIGN LOCATION/SERVICE NOTES EF-A 150 1/4" DIRECT 1/30 CENTRIFUGAL GREENHECK G-065-D MOP SINK O EF-B 225 3/8" DIRECT 1/25 CENTRIFUGAL GREENHECK G-075-D RESTROOMS Q2 Q1 INTERLOCK WITH PREP ROOM LIGHTS. Q INTERLOCK WITH TOILETROOM LIGHTS. AIR DISTRIBUTION SCHEDULE MARK TYPE SIZE IN INCHES FINISH O.B.D. BASIS OF DESIGN NOTES NECK FACE O SUPPLY 61-0 12"xl2" 02 NO TITUS PAS Q © SUPPLY 8"0 16"x16" Q2 NO TITUS PAS 1Q © SUPPLY 800 24"x24" 0 NO TITUS PAS Q OD SUPPLY 12"0 24"x24" Q NO TITUS PAS Q OE SUPPLY 16"0 24"x24" 0 NO TITUS PAS 10 0 SUPPLY - 21"x6" Q NO LINDAB RGS-3 © SUPPLY - 25"x9" Q2 NO LINDAB RGS-3 O RETURN 18"0 24"x24" U2 NO TITUS PAR JO EXHAUST 10"0/10"x10" 12"x12" 02 NO TITUS 350FL 0 FLEXDUCT = ROUND NECK SIZE LISTED. 2Q SEE ARCHITECTUAL PLANS FOR FINISH INFORMATION. 0 ADJUST DIFFUSER FOR 2 WAY DISTRIBUTION PATTERN. ® ADJUST DIFFUSER FOR 3 WAY DISTRIBUTION PATTERN TO BLOW AIR AWAY FROM THE HOOD. SUPPLY DUCT - TYPICAL SPIN -IN FITTING W/DAMPER TYPICAL FLEXIBLE DUCTWORK; (MAXIMUM ROUND DUCTWORK TYPICAL CEILI DIFFUSER FLEXIBLE DUCT TAKE -OFF DETAIL SCALE: NONE Q'e�4 CIA I 211 e(a TRACY M. WOODALL, P.E. 181 Sedgefield Overlook Dallas, Georgia 30157 T: (678) 642-7282 Florida PE F: (770) 406-2381 #56620 ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 e `N���114ttltl���i sip %ft lot P �.• �'� 4;� LU W Z i W - U Ln Z Q Q L a 0 J GC N0_j Z -I O Q =J � oC Lz LLI 0cr'.= a W = N a W N ISIONS E REVISION F INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTIO DOCUMENTS BY ANYONE OTHER THA THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS OPYRIGHT 2010 J. SAFFRAN, ARCHITECT WING IS THE PROPERTY OF FRAN, ARCHITECT FSAFFRAN. OT TO BE REPRODUCED OR IN WHOLE OR IN PART. RIZED USE OF ANY KIND, G USE ON ANY OTHER IS PROHIBITED. ITISTOBE RETRNED UPON REQUEST. ESHEE7TITLESCHEDULES, ILS - HVAC PROJECT SHEET NO. NO 1030 DRAWN BY TMW Ms2 DATE 11-23-10 2OF6 r' r It. IERIC J. SAFFRANI ARCHITECT TAIINdffliNA HOOD NO. MODEL LENGTH COOKING TEMP. EXHAUST PLENUM SUPPLY PLENUM HOOD CONSTRUCTION HOOD CONFIG. TOTAL EXH. CFM RISER(S) TOTAL SUP. CFM RISER(S) END TO END ROW WIDTH LENG. DIA. CFM S.P. WIDTH LENG, DIA, CFM S.P. 1 3347 BD-2 9' 0.00" 450 Deg. 1800 10" 17" 1800 -1.026" 0 430 SS Where Exposed LEFT ALONE 2 3347 BD-2 910.001, 450 Deg. 1800 101, 17" 1800 -1.026" 0 430 SS Where Exposed RIGHT ALONE 3 126 MISC-PSP 910.001, 300 Deg. 0 1359 430 SS Where Exposed ALONE ALONE 4 126 MISC-PSP 9' 0.00" 300 Deg. 0 1359 430 SS Where Exposed ALONE ALONE unnn TATFnPvATrnAT SCOPE OF WORK HOOD(S): PROVIDED BY OWNER. INSTALLED BY GC. FIRE SYSTEM(S): PROVIDED & INSTALLED BY OWNER, EXHAUST FAN(S): PROVIDED BY OWNER. INSTALLED BY GC. MAKEUP AIR UNIT(S): PROVIDED BY OWNER. INSTALLED BY GC. ELECTRICAL CONTROL(S): PROVIDED BY OWNER. INSTALLED BY GC. FILTER(S) LIGHT(S) UTILITY CABINET(S) FIRE HOOD NO. TYPE QTY. HEIGHT LENGTH QTY. TYPE WIRE GUARD LOCATION FIRE SYSTEM ELECTRICAL SWITCHES SYSTEM PIPING HOOD HANGING WGHT TYPE SIZE MODEL# QUANTITY LOCATION 1 Captrate Solo Filter wi 3 16" " 5 Incandescent Light Fixt NO Wall Mint t Ansul R102 3.0/3.0 31111002 1 Light g Fan Face Left YES 369 LIES 3 16" 20" 2 Captrate Solo Filterwi 3 16" 16" 5 Incandescent Light Fixt NO YES 354 LEIS 3 161, 20" 3 0 NO 44 LEIS 4 0 NO 44 LIES Nnnn nPTrnAr.4 HOOD NO. OPTION 1 FIELD WRAPPER FOR TOP UTILITY CABINET 38.00" High Front FIELD WRAPPER 38.00" High Left BACKSPLASH 67.00" High X 216.00" Long 430 SS 2 FIELD WRAPPER 38.00" High Front, Right PFRFnPATFn .CTTPPT.Y Pr.FATrnvr.4 ) HOOD NO. POS. LENGTH WIDTH HEIGHT RISER S WIDTH LENG. DIA. CFM S.P. 3 Front 108" 12" 6" 101. 16" 679 0.129" 10" 16" 679 0.129" 4 Front 108" 12" 6" 10" 16" 679 0.129" . 10" 16" 679 0.129" 33" Utility Cabinet 0 -� 1r' 10.1 - 44" T 9,. 101, �-- 17" —� U.L. Listed Incandescent Light Fixture -High Temp Assembly 27" 54" 9' 0.00"Nom./9' 0.00"OD PLAN VIEW — Hood #1 9' 0.00" LONG 3347BD-2 WITH MISC—ESP (FRONT SUPPLY PLENUM) 27" d � imp imp MOM 4I>or FILTER COLLECTION EFFICIENCY 2" Captmnet ase-StopSssolo Filar o.t 1 to PARTICLE DIAMETER (um) SPECIFICATION: CAPTRATE GFTEASE-STOP SOLd FILTER THE CAPTRATE GREASE -STOP SOLO FILTER IS A SINGLE -STAGE FILTER FEATURING A UNIQUE S-BAFFLE DESIGN IN CONJUNCTION WITH A SLOTTED REAR BAFFLE DESIGN, TO DELIVER EXCEPTIONAL FILTRATION EFFICIENCY. FILTER IS CONSTRUCTED OF 430 STAINLESS STEEL, AND SIZED TO FIT INTO STANDARD 2-INCH DEEP HOOD CHANNEL(S). UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO COMPONENTS WHEN ASSEMBLED. GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 75% OF GREASE PARTICLES FIVE MICRONS IN SIZE, AND 90% GREASE PARTICLES SEVEN MICRONS IN SIZE AND LARGER, WITH A CORRESPONDING PRESSURE DROP NOT TO EXCEED 1.0 INCHES OF WATER GAUGE. 3" 10" 33" 17" U.L. Listed Incandescent Light Fixture -High Temp Assembly 27" M. 27" 9' 0.00"Nom./9' 0.00"OD PLAN VIEW — Hood #2 9' 0.00" LONG 3347BD-2 WITH MISC—PSP (FRONT SUPPLY PLENUM INCANDESCENT LIGHT FIXTURE -HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL AND SHOCK RESISTANT GLOBE (L55 FIXTURE) EXHAUST RISER 16" CAPTRATE SOLO FILTER WITH HOOK 3" INTERNAL STANDOFF IT IS THE RESPONSIBILITY OF THE ARCHITECT/OWNER TO ENSURE THAT THE HOOD CLEARANCE FROM LIMITED -COMBUSTIBLE AND COMBUSTIBLE MATERIALS IS IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS. GREASE DRAIN WITH REMOVABLE CUP FIELD INSTALLED QUARTER END PANELS AGENT LINE 33" —i / r 2.75" 4" BACKSPLASH 67.00" HIGH X 216.00" LONG EQUIPMENT BY OTHERS MISC-PSP (SUPPLY PLENUM) SHIPS LOOSE. MOUNT FLUSH WITH DROP CEILING @ 10' AFF. SUPPLY RISER WITH VOLUME DAMPER DROP CEILING 117AFF UTILITY CABINET AND WRAPPERS SHOWN MOUNTED ON TOP OF HOOD SECTION VIEW - MODEL 3347BD-2 WITH MISC-PSP (FRONT SUPPLY PLENUM), DUCT PROTECTION NOZZLE DETECTORS DETECTION LI PLENUM PROTECTION NOZZLE APPLIANCE NOZZLE TYPICAL ANSUL R102 SYSTEM LAYOUT WITH REMOTE MOUNTED AUTOMAN NOTE: FIRE SYSTEM TO INCLUDE ALL NECESSARY PERMITS. FIELD HOOKUP, AND FINAL TEST. REMOTE NOTE: FIVE GUYS FIRE SYSTEM ENCLOSURE WILL BE SYSTEM ENTCONTROL ANKENCLOSN MANUAL FACTORY —MOUNTED ON TOP OF THE HOOD WITH AGENT TANK ENCLOSED PULL STATION i/r DN. ALL T"READ ROD 1/2" DIA. HEAVY Dun NUT ETL LISTING DESCRIPTION BLOCK CONNECTED TO ROOF JOIST ONE ABOVE AND ONE BELOW 71R01t'" ANQ1HQt HANGING HANGING AN` THE CAPTIVE AIRE MODEL ANGLE BD-2 HAS BEEN U.L. 710 TESTED, LISTED, AND APPROVED TO EXHAUST A MINIMUM OF 150 CFM PER LINEAR FOOT sRDD AND NUTS TO BE SUPPLIED BY MrALUNG CONTRACTOR OVER 450 DEGREE COOKING HANM ANGLE IS PRE —PUNCHED AT FACTORY HANGING ANGLE DETAIL 1 EQUIPMENT CAPTIVE-AIRE HOODS ARE BUILT IN COMPLIANCE WITH BUILT IN ACCORMNCE � NFPA [/STEO ,rgT10N V�y� NFPA #96 Intertek ETL SANITATION LISTED ETL LISTED #3054804-001 PROVIDED FOR COORDINATION PURPOSES FOR QUESTIONS, CONTACT: CAPTIVE-AIRE SYSTEMS, INC. STORES NORTH OF FAIRFAX, VA CONTACT: MARK PROFET PHONE 800)) 988-0881 FAX (3 1) 986-1795 EMAIL: REG32@CAPTIVEAIR.COM STORES SOUTH OF FAIRFAX, VA CONTACT: JAYSON NEWMAN PHONE (800) 419-1447 FAX (804) 684-0880 EMAIL: REG28@CAPTIVEAIR.COM r REVISIONS l 1 c DATE: 11/20/2009 DWG.#: DRAB," PWB-32 SCALE: Not To Scale SHEET NO. 1 Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PRO ECT IS PROHIBITED. IT IS TO BE RET RNED UPON REQUEST. SHEET TITLE HOOD DETAILS SCALE NO PROJECT I SHEET NO. 1030 DRAWN BY IM-3 DATE II-23-10 3oF6 J�... ., aa�ia.rnL„aiL�:' � >`t�,_ kl.liliu�.li �.1._ ._"_•�:1r.rdLe,ss�+.l.e.�; �.._.. -a,- ,.. �n.�.d11t,�l_�L.�-�I� FYWATT.4'T FAAT TATFORAlATTOAT FAN DISCHARGE UNIT FAN UNIT MODEL # MODEL TAG CFM S.P. RPM H.P. 0 VOLT FLA VELOCITY WEIGHT (LBS.) NO. 1 HRE-20 HRE-20 3600 2.000 1330 3.000 3 208 9.5 1539 FPM 361.00 W)PATF.PIMTTA Fd1V TATFOPLIA77nAT FAN UNIT FAN UNIT MODEL# BLOWER HOUSING TAG CFM S.P. RPM H.P. 0 VOLT FLA WEIGHT (LBS.) NO. 2 A1-D.250-G10 G10 Al-D.250 2718 0.375 1214 2.000 3 208 6.0 578.57 (_A.4 FrPRn MAWF.—TTP ATP TTATTT(.C'1 FAN OUTPUT UNIT INPUT BTUs TEMP. RISE REQUIRED INPUT GAS PRESSURE GAS TYPE NO. BTUs 2 215903 198631 70 deg F 7 in. w.c. - 14 in. w.c. Natural FA AT n PTTn AT.0 FAN UNIT NO. OPTION (Qty. - Descr.) 1 1 - Rain Cap for HRE-20 2 1 - Inlet Pressure Gauge, 0-35" 1 - Manifold Pressure Gauge, -5 to 15" we 1 - Low Fire Start rTTRR A.C.QFUPT_TF.0 NO. ON FAN ITEM SIZE 1 # 1 Curb 28.000"W x 28.000"L x 20.000"H Vented Hinged 2 # 2 Curb 21.000"W x 71.000"L x 20.000"H Insulated FAN #1 HRE-20 - EXHAUST FAN 36118 29 1/2 3E WHEEL ACCESS DOOR 29 1 /2 RAIN CAP (PROVIDED BY CAPTIVE -AI RE, 10.00" INSTALLED NY HOOD INSTALLER) 56 9. 0" s. 0" 35 7/8 4 3/16 T L OPEN @60" tEMOVE PIN -0 OPEN DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN (BY OTHERS) FEATURES: - ROOF MOUNTED FANS - RESTAURANT MODEL - UL762 - HIGH HEAT OPERATION 300°F (149"C) - GREASE CLASSIFICATION TESTING - CLEANOUT DOOR NORMAL TEMPERATURE TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 300"F (149"C) UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE OPERATION. ABNORMAL FLARE-UP TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING BURNING GREASE VAPORS AT 600"F (316"C) FOR A PERIOD OF 15 MINUTES WITHOUT THE FAN BECOMING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE CONDITION. OPTIONS RAIN CAP FOR HRE-20 SCOPE OF WORK HOOD(S): PROVIDED BY OWNER. INSTALLED BY GC. FIRE SYSTEM(S): PROVIDED & INSTALLED BY OWNER. EXHAUST FAN(S): PROVIDED BY OWNER. INSTALLED BY GC. MAKEUP AIR UNIT(S): PROVIDED BY OWNER. INSTALLED BY GC. ELECTRICAL CONTROL(S): PROVIDED BY OWNER. INSTALLED BY GC. FAN #2 All -D.250-G10 - HEATER 1. DIRECT GAS FIRED HEATED MAKE UP AIR UNIT WITH 10" BLOWER 2. INTAKE HOOD WITH EZ FILTERS 3. DOWN DISCHARGE - AIR FLOW RIGHT- LEFT 4. GAS PRESSURE GAUGE, 0-35", 2.5" DIAMETER, 1/4" THREAD SIZE 5. GAS PRESSURE GAUGE, -5 TO +15 INCHES WC., 2.5" DIAMETER, 1/4" THREAD SIZE 6. LOW FIRE START. ALLOWS THE BURNER CIRCUIT TO ENERGIZE WHEN THE MODULATION CONTROL IS IN A LOW FIRE POSITION. LIFTING LUG EQUIPMENT CURT �ISTEn CURB OUTER V DISCHARGE OPEN 1: 3 7/8" 29 3/4" 20" v WIRING 118 5/8" 32 1 /8. 42 1 /8" AIRrM FLOW • SERVICE DISCONNECT SWITCH BLOWER/MOTOR ACCESS DOOR 71" SUPPLY SIDE HEATER INFORMATION: WINTER TEMPERATURE = 15"F. TEMP. RISE = 70"F. OUTPUT BTUs AT ALTITUDE OF 0.0 ft. = 198631 INPUT BTUs AT ALTITUDE OF 0.0 ft. = 215904 DIRECT FIRED MODULE 39 9/16" 3/4" NPT c 7 13/16" o o PROVIDED FOR COORDINATION PURPOSES AIRFLOW r REVISIONS 1 E u DATE: 11 /20/2009 DWG.#: DRAWN Y PWB-32 SCALE: Not To Scale SHEET NO. 2 ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 W Z LU U Ln Uj en M w, Z Q d '' 0 0 J DC in00 N m PL O -' Q F U cC LU 0Ln>- U n d >- N i IL W N REVISIONS N0. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS RIGHT 2010 FRAN, ARCHITECT FSAFFRAN, IS THE PROPERTY OF ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PRO ECT IS PROHIBITED. IT IS TO BE RET RNED UPON REQUEST. SHEET TITLE HOOD DETAILS SCALE PROJECT SHEET NO. NO 1030 M�4 DRAWN BY DATE II-23-10 4 OF 6 I ..._._ - - - - - --- ERIC J. SAFFRAN PROVIDED FOR COORDINATION PURPOSES ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 4 JAL WAIM eC w F Z w U Ln U M �_ i O rz N 0 OJT O Ln �- 04 pC Lu = CL w N EREVISIONS NO. DATE REVISION ICATION CLAUSE SHALL RELEASE, HOLD 7HARMLESS, D INDEMNIFY THE TH RESPECT TO: ANY E TO THE CONSTRUCTIOY ANYONE OTHER THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT IS TO BE RETURNED UPON REQUEST. FSHEET DETAILS PROJECT SHEET NO. NO 1030 iM�5 DRAWN BY LDATE I I-23-10 501=6 1' 1111 '! kfl III IWO" 11 lthh� 1�=Nili. Jim IERIC J. SAFFRANI ,FT.)7` rTPT('rd T. PA rA'A /'T'.0 NO. TAG PACKAGE # LOCATION SWITCHES ROOFTOP STARTERS OPTION FANS CONTROLLED LOCATION QUANTITY TYPE O H.P. VOLT FLA 1 31111002 Top Utility Cabinet Face Mount Left Side Hood 1 Light 1 Fan Exhaust in Fire Exhaust 3 3.000 208 9.5 Hood # 1 Supply 3 2.000 208 6.0 ELECTRICAL PREWIRE PACKAGE I JOB NAME Five Guys DATE DRAWING NUMBER 31111002 JOB NUMBER DRAWN BY CONTROL INPUT 120VAC H1=LINE, N1=NEUTRAL 15A BKR - DO NOT WIRE TO SHUNT TRIP BREAKER 3 Phase, W/ 1 Exhaust Fan, 1 Suoolv Fan. Exhaust in Fire 1 2 3 4 5 8 7 8 9 10 11 12 13 14 LIGHT INPUT 120VAC H2-H5=LINE, N2-N5=NEUTRAL 15A BKR 15 LS-01 BRr� BK WHr—a Jumper �� H2 •r--p 6 � A �^p I•IL Vr 18 17 3PHASE 209V ST-1OL— T1 is LIINPVT gL2�Tjl—J3WIRE 62 T3 ExH-1 GR 3 PHA IL3 T3 - 19 3 PHASE 208V —2 OL-2 �Ll T120 T2'SUP-2GR T3 T 21 22 23 24 CONTROL PANEL INSTALLATION DRAWING NUMBER COMPONENT PARTS UST Dd JJ�GAT14tl Cantactor starter 120V 15AMP Overload Fa Fan SwNeh (uydwd) NEUTRAL ght Switch•(140OW max) AYeroSw,h ()Mrul/PyroCMm) Relay DPDT — 34.110.0146.0 120V 15AMP NEUTRAL 3 PHASE 208 VOLT 20 AMP SPARE RELAY CONTACTS USED WHEN FIRE SYSTEM DISCHARGES TO SHUT DOWN SHUNT TRIP, EQUIPMENT... OR PROVIDE SIGNALS. R2— WNO CC TERMINAL FOR FIELD WIRING TO BUILDING FIRE PANEL, DRY CONTACTS FOR SIGNAL ONLY Iac REUY SOa10:T S1YLE CLJDN' MS—x C—RD O—A no MkC—RD h n[ Z i NC —PR COIL a NO—BK CO, 5 NC -BR l[Mqt_o_r_FTyPe IPHIVolt IHP I FLA I BREAKER Exh-1 Exh 3 208 3 9.5 20 Am Su —2 Su 3 208 2 6 -- Am DENOTES FIELD WIRING DENOTES INTERNAL WIRING BK — BUCK YW — YELLOW BL — BLUE GY — GRAY BR — BROWN PR — PURPLE OR — ORANGE 01 —ORANGE/BLUE (STRIPE) RD — RED BL/RD — BLUE/RED (STRIPE) WH — WHITE RD/GN — RED/GREEN (STRIPE) NOTE: IF WALL MOUNT PREWIRE, OR FIELD INSTALLED FIRE SYSTEM MICROSWTTCH, THE TERMINALS SHOWING FACTORY WIRING MUST BE FIELD WIRED. 12 x 18 x 6 Box JOB NAME ' I JOB NUMBER HOOD CONTROL PACKAGE DATE MODEL SCOPE OF WORK HOOD(S): PROVIDED BY OWNER. INSTALLED BY GC. FIRE SYSTEM(S): PROVIDED & INSTALLED BY OWNER. EXHAUST FAN(S): PROVIDED BY OWNER. INSTALLED BY GC. MAKEUP AIR UNIT(S): PROVIDED BY OWNER. INSTALLED BY GC. ELECTRICAL CONTROL(S): PROVIDED BY OWNER. INSTALLED BY GC. E~ z W 0 F o = o Cd U a 0 H H (Y x y Z z U) F- 00 o U) z Q z 0 Z Z _0 z w Q WP z x a LL - ° w z U O z O 00 Cl) U) Z F as c9 Z Z a 17) ,s Z O o cn goZ WZO O C) /y E-4 = W J a' W W LL IY W Q >-ZZ O LU > WWW �00 Z J Cf)ZC'3 O > W CQ F W Q U)Z LL W w Hw� 0 U) z 1-1 Z Z 0 O 0av �00 ^ W ~ z Z W Q CO Q " ZzW JOw}aU) EL 0 00 P CO m 0 W NW J of U W W Z Q W W IY>Xw W > ' � Qw� 0 0w0 Lu > = F- COI- W Z W 0 U) U) Z w w Z = J J J 0 < < W U) > > PROVIDED FOR COORDINATION PURPOSES �_:Z_��IF3r•��E��1 I 1 c DATE: 11/20/2009 DWG.#: DRAW PWB-32 SCALE: Not To Scale SHEET NO. 4 ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 t f� W z _ LI<,I U Ln LU (3 M Q Q " CL 0 _j in OO cn m LL OJ_j �yy ma's O L } 04 Joe^ LU = CL N REVISIONS FNO. DATE REVISION U� INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS RIGHT 2010 FRAN, ARCHITECT FSAFFRAN, IS THE PROPERTY OF ARCHITECT O BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. IT IS TO BE RETURNED UPON REQUEST. FSHEETTfTLE DETAILS PROJECT SHEET NO. NO 1030 M�6 DRAWN BY DATE 1 1-23-10 6 OF 6 4"GREASE WASTE TO NEW 1000 GALLON GREASE TRAP PROVIDED CONTRACTOR TO BY TENANT. MINIMUM INVERT CONNECT FIXTURE RESTROOMS AND �- ; TO BE 3'-6'B.F.F. CONTRACTOR TO EXISTING STUBS PROVIDED BY LANDLORD TO VERIFY TIE INTO EXISTING PROVIDED AS PART AS PART OF SHELL BUILDING 3"V. 20V' SANITARY ON SITE AND EXACT UP LOCATION OF GREASE TRAP. OF SHELL BUILDING. WORK. UP I IT FRESH -- - FRESH a I AIR TRAP 7 TD-1 FB ~� CO CO CO y - _r • I � CO 01 - '� _. Al - �_-6 , 1 _ C OR T IN TALL �� tl � �y i' ' __ - --- - I ;� l`SE D SET OF 6 ; i r. '' �, 3 R� l RUP LINES R _ ».. �p Y UNDf�Ft cam: / T - J ' 4 GREASE LOCATE PVC PIPE OVERHEAD FOR SYRUP „ ` f, •'" .. ' .' ±' WASTE 1 — -- — --- - r LINES. COORDINATE f - ` 1 r—T-------= M INSTALLATION WITH ��' _ 1 X `\ COCA COLA, EQUIP. 2"V. Tp=y SUPPLIER, & 94C. j UP ! 1 1 i - BEVERAGE DISPENSER RUN WITH 1-1/2" INDIRECT - - WASTE W/TRAP AT BACK r^ - ? - OF BEVERAGE BAR. SLOPEI;--- j ✓,:. 1/2" PER FOOT TO HD. (TYP. 2) I 3"V. UP --- - -- ----- �l__� f 4"FS ' r -- i 1 -- 27/;, 13 E ' , 14 f F—TD-1 r - I 2W UP t NL`MRACTOR TO INSTALL 2" COPPER DRAIN FROM HOOD EXHAUST FAN TO GREASE l COLLECTION BOX. SEE DETAL ON SHEET M-5 FOR MORE DETAILS. GREASE TRAP SIZING: 92 SEATS * 10 GAUSEAT * 12 HR/12 * 1.0 = 920 GALLONS SI�:R` 1 E' CID I n -i 0 _•� T -_ NOTE: \ CONTRACTOR TO COORDINATE EXACT DIMENSIONS FOR FLOOR SINKS AND TRENCH DRAINS WITH ARCHITECTUAL PLANS. . 1 FLOOR PLAN - SANITARY P-1 SCALE V4" = P-0" NOTICE TO CONTRACTORS: ALL CONTRACTORS PRIOR TO BID SUBMISSION PROCESS SHALL VISIT PROPOSED WORK SITE AND FIELD VERIFY ALL EXISTING CONDITIONS. ANY CONDITIONS THAT DIFFER FROM THAT SHOWN ON THESE PLANS SHALL BE REPORTED TO ARCHITECT/ENGINEER SO THAT NEW AND REVISED BID DRAWINGS OR INFORMATION MAY BE ISSUED. MODIFICATIONS TO SCOPE OF WORK WHICH RESULTS FROM CONTRACTORS NEGLECT TO VISIT THE SITE PRIOR TO SUBMITTING BID, SHALL BE THE CONTRACTORS SOLE RESPONSIBILITY. SITE UTILITY NOTE PLUMBING CONTRACTOR SHALL COORDINATE THE LOCATION AND INVERTS OF ALL PIPING FOR CONNECTION TO THE APPROPRIATE UTILITY AS SHOWN ON UTILITY PLAN. THIS COORDINATION SHOULD TAKE PLACE PRIOR TO GRADING AND INSTALLATION OF PIPES. THIS CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO THE RECEIVING UTILITY. I I, tl �I i! it tl iL. 3"V. UP Y FLOOR DRAIN AND TRENCH DRAIN NOTES: NOTE: FILTERED WATER TO ICE MACHINE TO BE SUPPLIED AFTER SCALE FILTER WHILE CARBONATOR PUMPS TO BE SUPPLIED 1/2"HW TO SERVE BEFORE SCALE FILTER. EXISTING RESTROOMS. ' I � L� 1 "CW & 1 /2" i 110°HW T SERVE EX RESTROOMS. �. ' r r /, cL I� A — I 3/4"CW DN. TO NFWH AT 244A.F.F. v I 3/4"FW VALVE � FOR CONNECTION 13 TO SODA DISPENSER - & ICE MAKER. (TYP. 2) 14 - — - SEPERI I G DN. TO I ,_- - 1 /2"FW VALVE TEA TO AT COUNTER 1 FOR CONNECTION - TO ICE TEA TOWER. - ,I 14 3/4"CW & HW DN. TO 4-COMP. 1/2"CW & Ali 110"HW _ . - --- - .... _it - © it I- REOIRCULATIN PUMP WITH AQUASTAT & I TIMER------ i I 1-1/2"CW & R 3/4"HW E •I �? x 1 I 3/4"CW & 3/4"HW —� _id ` 3/4"CW & HW DN. W/ BFP ON HW LINE TO CHEMICAL SYSTEM.- jj r X361I DN. WITH - SERVICE., 3/4"FCW BFP TO SERVE 1/2"CW & I 1 I-- SODA MACHINES. - J 110 HW CONTRACTOR TO VERIFY' DN. A MIN. OF 40 PSI AT 100 G --- - 27 PER CARBONATOR & A OF 75 PSI FOR INCOMING _ _ - WATER PRESSURE. IF TH WATER PRESSURE IS OVE�. <_ 1. ALL FLOOR DRAINS AND TRENCH DRAINS SHALL HAVE A MINIMUM OF A 5' RADIUS OF CONCRETE REMOVED AROUND THEM DURING THE DEMOLITION PHASE OF CONSTRUCTION. 2. FLOOR DRAINS AND TRENCH DRAIN GRATES WILL BE PLACED AT ONE INCH BELOW FINISHED FLOOR. 3. THE NEW CONCRETE WILL BE SLOPED TO THE DRAIN, AND A 3/4" REVEAL WILL BE LEFT SO THAT THE TILE CAN BE INSTALLED FLUSH WITH THE DRAIN. 4. ALL DRAINS TO HAVE CAST IRON BODIES AND SQUARE GRATES. 75 PSI, INSTALL A PRV. 2 FLOOR PLAN - WATER P-1 I SCALE V4" = r-0" SPECIAL EQUIPMENT NOTE: CONTRACTOR TO REFER TO RESTAURANT EQUIPMENT CUT SHEETS AND SCHEDULES FOR COORDINATION WITH ALL INSTALLATIONS WITH EQUIPMENT SUPPLIERS, KITCHEN DESIGNER, AND FIVE GUYS, INC. r— 3/4"CW & HW 20CW FROM DN. WITH VACUUM EXISTING RISER. TO NREAKER&BFPCONTRACTOR W LINE FOR VERIFY EXACT ECTION TO LOCATION IN FIELD. ICAL SYSTEM. WH-A 36 3/4"FILTERED WATER TO BEVERAGE - BAR. 3/4"CW DN. H BFP 24-4 TO WATER FIL R SYSTEM. I AS REQUIRED CAULK AND TRATIONS 1 /2"CW & 110•HW DN. THERMAL MIXING VALVE TO PROVIDE 110"F WATER. TYP. EACH LAV & HAND SINK. TRACY M. WOODALL, P.E. 181 Sedgefield Overlook Dallas, Georgia 30157 T: (678) 642-7282 Florida PE F: (770) 406-2381 ##56620 ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 �w ��IM, .. A , t�OmA1'�®1����n,� �D 111l1 itty` W Z Its _ i W U Ln VIM � aQTp O J NO � (AoI] OQ tz Uj 0L� ce Lu >- a LU N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCT]O DOCUMENTS BY ANYONE OTHER THA THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS COPYRIGHT 2010 ERIC J. SAFFRAN, ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN, ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. ITIS TO BE RETURNED UPON REQUEST. SHEET TITLE SANITARY & WATER FLOOR PLANS SCALE PROJECT SHEET NO. NO 1030 DRAWN BY TMW DATE II-23-10 1 OF 3 -III . _i—.1,-L. ;� .: . �4 W111111ri11 1JJ�ulu a: lIIJl l 4, I� I : , — E & - e —11 r SITE UTILITY NOTE PLUMBING CONTRACTOR SHALL COORDINATE THE LOCATION AND INVERTS OF ALL PIPING FOR CONNECTION TO THE APPROPRIATE UTILITY AS SHOWN ON UTILITY PLAN. THIS COORDINATION SHOULD TAKE PLACE PRIOR TO GRADING AND INSTALLATION OF PIPES. THIS CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO THE RECEIVING UTILITY. 0 GAS METER (7-WC) 1276 CFH TOTAL LOAD AT 89 EQUIV. LENGTH. 2"GAS r-I . I r:e --- x J ✓r' "L� � � I r 1 RTU-A �CFH 1 "GAS M r.7" [ PA 4_e rd 320 a NOTE: GAS PIPING SIZED PER /4"GAS ' y TABLE 402.4(2) OF THE 1-1 1-1 20061FGC. -- WH-A 250 CFH j. .., i:. f x, _ 1-1/2" EXPOSIcB 6ft9Id, --} WITH CLAMPING DEVI� - T AND AUTO SHUT-O CONNECTION TO F PROTECTION SY I CONTRACTOR OORDINATE EXACT GAS IN A LATION- - WITH FIVE GUYS UCTION REPRESENTATIVE PRI ' INSTALLAT ION. G] I, , x ' 1 "GAS 1 "GAS 90 CFH 216 CFH I I RTU-A 125CFH L----J I � �f 1 FLOOR PLAN - GAS P-2 SCALE: yr = r-0" SPECIAL EQUIPMENT NOTE: CONTRACTOR TO REFER TO RESTAURANT EQUIPMENT CUT SHEETS AND SCHEDULES FOR COORDINATION WITH ALL INSTALLATIONS WITH EQUIPMENT SUPPLIERS, KITCHEN DESIGNER, AND FIVE GUYS, INC. DRAIN LINE 2 x "D" (MIN. 1" CLEARANCE) NOTE: USE AIR GAP DETAIL FOR ALL EQUIPMENT DRAINING TO HUB DRAINS & FLOOR SINKS ON THE FRESH AIR SYSTEM. 6 AIR GAP DETAIL P-2 J SCALE: NONE NOTES: 1. PIPE BATTEN REQUIRED WHEN THIS DETAIL IS USED ON MECHANICALLY ANCHORED SYSTEMS. 2. REMOVE ALL EXISTING FLASHINGS, LEADS ETC. PIPE SURFACE MUST BE FREE OF ALL RUST, GREASE, ETC. 3. PIPE MUST BE ANCHORED TO BOTTOM SIDE OF DECK TO ASSURE STABILITY. 4. INSTALL PER ROOFING MANUFACTURER'S RECOMMENDATIONS. 2 VENT THR-U ROOF DETAIL P-2 SCALE: NONE GAS SUPPLY � I �— GAS COCK G y` UNION DIRT LEG FULL SIZE PRESSUF TEMP RELIEF VALVE DRAIN VALVE WITH HO PLUMBING LEGEND SYMBOLS & ABBREV LEGEND SOIL /WASTE PIPING BELOW FLOOR - - - - - - - - VENT PIPING G GAS PIPING C.W. - COLD WATER SUPPLY H.W. - - HOT WATER SUPPLY --0 --o PIPE RISING - PIPE TURNING DOWN B.V. 101BALL VALVE PRV rS PRESSURE REDUCING VALVE ---+IE---- UNION N.F.W.H. -}- NON -FREEZE WALL HYDRANT CO In FLOOR CLEANOUT F.D. 30 FLOOR DRAIN B.F. BELOW FLOOR A.C. ABOVE CEILING VTR VENT THRU ROOF AFF ABOVE FINISHED FLOOR INV INVERT BFP BACK FLOW PREVENTER ATION E END CONNECTION il"' t_BVV `—DRAIN VALVE WITH HOSE BV END CONNECTION WH-A NORITZ MODEL N-0931M-DV-ASME OR EQUAL. NOTE: CONTRACTOR TO PROVIDE BELL & GOSSETT MODEL #NBF-22U RECIRCULATING PUMP WITH MINIMUM FLOW OF 2 GPM, AQUASTAT TEMPERATURE SENSOR, AND TIMER. ROOFTOP UNIT GAS TANKLESS WATER HEATER SCALE: NONE GAS PIPING CONNECTION DETAIL SCALE NONE PLUMBING NOTES. 1 THE INSTALLATION SHALL INCLUDE ALL NECESSARY APPARATUS, EXCAVATING, CONTROLS, VALVES, AND FITTINGS AS NECESSARY TO MAKE THE PLUMBING INSTALLATION COMPLETE. 2 CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, CONNECTION AND INSPECTION FEES REQUIRED FOR THE CONPLETE INSTALLATION OF THIS WORK. HE SHALL DELIVER TO THE ARCHITECT ALL CERTIFICATES OR SAID INSPECTION ISSUED BY THE AUTHORITES HAVING JURISDICTION. 3 THE PLUMBING SYSTEM SHALL BE TESTED AS REQUIRED BY THE 2006 UPC. 4 PLUMBING FIXTURES: PROVIDE PLUMBING FIXTURES COMPLETE WITH TRIM. ALL FIXTURES, TRIMMINGS AND STOPS SHALL BE GRADE "A" AND SHALL BE OF ONE MANUFACTURER. PLUMBING FIXTURES FOR USE BY HANDICAPPED PERSONS SHALL BE IN ACCORDANCE WITH ACCESSIBILITY REQUIREMENTS. FIXTURES AS SCHEDULED ON DRAWINGS OR APPROVED EQUALS. GROUT BETWEEN PLUMBING FIXTURES AND WALLS AND/OR FLOORS. FOR CONNECTION OF FLOOR -OUTLET WATER CLOSETS, BRASS FLOOR FLANGES SHALL BE USED. THE JOINTS BETWEEN CLOSETS TRAP AND FLANGE SHALL BE MADE TIGHT WITH GASKETS. CONNECTION OF FIXTURE TRAPS FROM LAVATORIES, DRINKING FOUNTAINS, SERVICE SINKS, ETC. TO CAST IRON SHALL BE MAKE WITH D.W.V. TYPE COPPER. CONTRACTOR SHALL SEAL, USING SEALANT MEETING REQUIREMENTS OF FEDERAL SPECIFICATION TT-S-230, JOINT BETWEEN URINAL AND WALL AND AT WATER CLOSET AND FLOOR. 5 FLOOR DRAINS SHALL BE SET WITH TOP FLUSH WITH FINISH FLOOR. 6 WATER PIPING SHALL BE TYPE "L" COPPER WITH COPPER FITTING AND HANGERS. CONTRACTOR MAY SUBSTITUTE PVC IF APPROVED BY LOCAL CODE OFFICIALS. IT IS THE CONTRACTORS RESPONSIBILITY TO GET APPROVAL FOR THE USE OF PVC. 7 SOIL WASTE AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON WITH LEAD AND OAKUM OR MECHANICAL JOINTS AS APPROVED BY THE LOCAL CODE OFFICIALS: USE PVC (SCHEDULE 40) WHERE APPROVED BY CODE. 6 INSULATE ALL WATER LINES WITH 1" OWENS CORNING SSLA 1. ALL FITTINGS SHALL BE INSULATED AND COVERED WITH PVC COVERS. 9 INSULATED HANDICAPPED LAVATORIES WATER & DRAINS LINES W/TUBRO HANDI-LAV-GUARD KITS. 10 PROVIDE ESCUTHEON PLATES WHERE PIPES PENETRATE WALLS THAT ARE EXPOSED. CAULK AND SEAL ALL PIPE SELEVES. 11 CLEANOUTS SHALL BE PROVIDED WHERE REQUIRED BY THE APPLICABLE PLUMBING CODE. CLEANOUTS IN CAST IRON SOIL PIPELINES SHALL CONSIST OF CAST IRON FERRULE AND HEAVY BRASS CLEANOUT PLUG WITH SQUARE HEAD. WHERE PIPING IS CONCEALED IN FLOORS OR WALLS, CLEANOUTS SHALL BE INSTALLED IN AND NEAR SURFACE OF FLOORS OR WALLS AND SHALL HAVE COUNTER SUNK PLUGS AND COVERS. 12 CLEANOUTS FOR FLOORS SHALL BE JOSAM MANUFACTURING COMPANY'S SERIES 58000 WITH INSIDE CAULK OUTLET COATED CAST IRON INTERNAL CLEANOUT WITH LEAD SEAL, BRASS RIM AND INKALOY SCORIATED COVER PLATE FOR LIGHT TRAFFIC SECURED TO PLUG BY COUNTERSUNK SCREW FOR INSTALLATION FLUSH WITH FINISHED FLOOR COMPLETE WITH CARPET MAKER IN CARPETED AREAS. 13 CLEANOUTS IN WALLS, JOSAM MANUFACTURING COMPANY'S SERIES 58710 WITH STAINLESS STEEL COVERS. EQUAL CLEANOUTS MANUFACTURED BY ZURN OR J.R. SMITH ARE ACCEPTABLE. 14 GENERAL: MAKE CONNECTIONS TO ALL FIXTURES, TRAPS AND SIMLAR ITEMS. CONTRACTOR SHALL PLACE INTO OPERATION ALL EQUIPMENT. ARCHITECTURAL DRAWINGS SHALL BE REFERRED TO FOR EXACT LOCATION ALL FIXTURES AND DRAINS. ROUGHING DIMENSIONS SHALL BE DETERMINED FROM THE MANUFACTURER OF THE EQUIPMENT FURNISHED ON THE JOB. 15 SUBMIT 7 SETS OF SUBMITTAL ON ALL FIXTURES INSULATION & EQUIPMENT FOR APPROVAL BEFORE PLACING ORDER FOR EQUIPMENT. INSTALL ALL EQUIPMENT AND FIXTURES ACCORDING TO MANUFACTURERS RECOMMENDATIONS. WARRANTY SHALL BE 1 YEAR ON ALL EQUIPMENT AND WORKMANSHIP, EXCEPT 3 YEARS ON WATER HEATER TANK. 16. ALL SANITARY PIPING LOCATED IN FIRE RATED WALL SHALL BE CAST IRON OR COPPER. COORDINATE LOCATIONS WITH ARCHITECT. 17. ALL SANITARY AND VENT PIPING LOCATED IN RETURN AIR PLENUM SHALL BE CAST IRON. COORDINATE LOCATIONS WITH MECHANICAL DRAWINGS. 18. POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIOR TO USE. THE METHOD TO BE FOLLWED SHALL BE THAT PRESCRIBED BY THE LOCAL HEALTH DEPT. TRACY M. WOODALL, P.E. 181 Sedgefield Overlook Dallas, Georgia 30157 T: (678) 642-7282 Florida PE F: (770) 406-2381 #56620 ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 M W06 No If "'till to oC F VIP w Z w UQ� � M (L CL O cC En OO OQ 04 Lh Ona N a N WL; W REVISIONS NO. DATE REVISION EMNIFICATION CLAUSE NER SHALL RELEASE, HOLD SS, AND INDEMNIFY THE rASPECTOF CT WITH RESPECT TO: ANY S MADE TO THE CONSTRUCTION ENTS BY ANYONE OTHER THA CHITECT, OR CHANGES IN ANY OF THE WORK, OR FAILURE BY NTRACTOR TO BUILD IN ANCE WITH THESE UCTION DOCUMENTS OPYRIGHT 2010 J. SAFFRAN, ARCHITECT AWING IS THE PROPERTY OF FFRAN, ARCHITECT FANDJiSNOT OT TO BE REPRODUCED OR IN WHOLE OR IN PART. ORIZED USE OF ANY KIND, NG USE ON ANY OTHER IS PROHIBITED. IT IS TO BE D UPON REQUEST. ESHEETAN, NOTES ETAILS SECT SHEET NO. O 1030 DRAWN BY TMW P�2 DATE 1 1-23-10 2 OF 3 OUTLET TO 3/4" CARBONATER FNPT OUTLET TO ICE MACHINE 3/4" AND TEA FNPT BREWER NOTE: 74" WATER LINE FOR SODA MACHINE TO PASS THROUGH THE COOLER BOX, COIL 50 FEET OF PIPING ON CEILING OF BOX (HANG AND SUPPORT AS REQUIRED) END AT BALL VALVE NEAR CARBONATER. SEAL PENETRATIONS THROUGH COOLER BOX, CAULK AS REQUIRED WITH NON -SHRINKABLE CAULK. %" WATER LINE FOR ICE MACHINE TO PASS THROUGH COOLER BOX ALSO WHEN SCOTSMAN MACHINES USED NOT HOSHIZAKI, SEE PREVIOUS NOTES. ALL PIPES PASSING THROUGHT COOLER BOXES ARE POST WATER FILTER. WATER FILTRATION SYSTEM P-3 SCALE NONE FIXTURE CONNECTION SCHEDULE FIXTURE DESCRIPTION SUPPLYW WASTE H.W. W FD FLOOR DRAIN - ZURN #Z-415 WITH - 3" NICKLE BRONZE STRAINER. FS FLOOR SINK - ZURN #Z-1901-2, W/NO GRATE 3" SANI-FLOR RECEPTOR, 12"x12"x8"D, CAST IRON BODY WITH ACID RESISTING FINISH & STRAINER. TD-1 TRENCH DRAIN - ZURN #ZN664-3NH-E(2)-Y - 3" 36"x6" DRAIN. PROVIDE WITH SEDIMENT BUCKET, 3" OUTLET. TD-2 TRENCH DRAIN - ZURN #ZN664-3NH-E(3)-Y - 3" 48"x6" DRAIN. PROVIDE WITH SEDIMENT BUCKET, 3" OUTLET. GD URINAL - ZURN MODEL #Z5750, 1.0 GPF - 3/4" 2" WITH ZURN MODEL #Z6003AV FLUSH VALVE. 3"V. II UP V 3* FA I I / / I VTR ( 3"SAN. < I I�_ VTR \ ICI, i I II I 2'V. UP 10, I II I 3"V. / UP / I II // I II I 2"V. / T \ \ 2"V. / / / CO /Tc -1 / I I UP �\ / \ UP ® I I I I \\\\ /� FS I I /// I I I> I I � I TD-2 I ( \ \ I I I I \ \ I 4"GREASE I 11 ( \\\ I WASTE I FRESH i / i CID AIR TRAP 13 14 I I \ FS \ I I , co /// CO / \ I T`\\ 4"GREASE D-1 \ WASTE ®7 \ \ \ TD- 27 TD-1 UFS \ l I I 2"V. I UP I i I I TD-1 I I 27 I�i i CO 2 \ SANITARY RISER P-3 / SCALE NONE KITCHEN EQUIPMENT ROUGH -IN CONNECTION SCHEDULE FIXTURE DESCRIPTION WATER WASTE GAS REMARKS H.W. C.W. INDIRECT DIRECT MBH SIZE 11 TEA TOWER 1/2" FILTERED WATER 13 SODA MACHINE 3/4" 3/4" FILTERED WATER @ 72"A.F.F. 14 ICE MACHINE 3/4" 3/4" FILTERED WATER @ 72"A.F.F. 20 GAS GRIDDLE 90 3/4" GAS GRIDDLE 150 1" 22 GAS FRYING SYSTEM 320 - SEE EQUIPMENT CUT SHEETS SIZE & NO. OF CONNECTIONS 27 HAND SINK 1/2" 1/2" 1-1/2" 3-COMPARTMENT SINK 1/211 1/2" (3) @ 1-1/2" 7 4-COMPARTMENT SINK 1/2" 1/2" (4) @ 1-1/2" MOP SINK 1/2" 1/2" 3" 29 HOSE BIBB 1/2" 1/2" INTEGRAL VACUUM BREAKER 35 WATER FILTER 3/4" 36 TANKLESS WATER HEATER 3/4" 3/4" 250 1-1/4" 4"GREASE WASTE TO NEW 1000 GALLON GREASE TRAP PROVIDED BY TENANT. MINIMUM INVERT TO BE 3'-6"B.F.F. CONTRACTOR TO VERIFY TIE IN TO EXISTING SANITARY ON SITE AND EXACT LOCATION OF GREASE TRAP. SCHEDULE FOR INFORMATIONAL PURPOSES ONLY TRACY M. WOODALL, P.E. 181 Sedgefield Overlook Dallas, Georgia 30157 T: (678) 642-7282 Florida PE F: (770) 406-2381 #56620 ERIC J. SAFFRAN ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 ARM �. �c w Z w — U 0�M ZQQ a momsii.. O oC N0 � cn o0 f vi 0 Q J Ind OLh U^a N w REVISIONS . fNO DATE REVISION MNIFICATION CLAUSE THER SHALL RELEASE, HOLD HAAND INDEMNIFY THE tMADE ARWITH RESPECT TO ANY CHMADE TO THE CONSTRUCTIODOTS BY ANYONE OTHER T THITECT, OR CHANGES IN ANY ASTHE WORK OR FAILURE BY THTRACTOR TO BUILD IN ACNCE WITH THESE COTION DOCUMENTS OPYRIGHT 2010 J. SAFFRAN, ARCHITECT WING IS THE PROPERTY OF FFRAN, ARCHITECT FC OT TO BE REPRODUCED OR IN WHOLE OR IN PART. ORIZED USE OF ANY KIND, G USE ON ANY OTHER IS PROHIBrrED. IT IS TO BE D UPON REQUEST. FSHEETEDULE & ARY RISER SHEET NO. FDRAWN P�3 [DATE23-10 3 of 3 ELECTRICAL SPECIFICATIONS Common Electrical Abbreviations ERIC J. SAFFRAN ARCHITECT GENERAL Before submitting a bid, the Contractor shall visit the site and familiarize himself with the existing conditions. The Contractor shall make such ac justments m work as required by the actual conditions and inform the Engineer ofRecord of any discrepancies between achral conditions and design documents. Coordination, Conflict and Changes: The Contractor shall coordinate his work with other trades, particularly in common areas such as mechanical moms, and chases where multiple trades will be working. In the event ofa coo ic; the Architect shall decide which equipment shall be relocated regardless of which was installed first: g during this coordination, it is discovered that necessary or desirable changes should be made, advise the Engineer and secure his approval in writing. Where- drawings appear to cou ict, provide the more expensive quality or quantity. The Contractor shall base his proposal on the materials specified herein and in the drawings. Reference to a particularptvduct by Manuficturw, trade name, or catalog number establishes the minimum standard ofmaterial and equipment required for this installation. It is not intended to exclude products of similar• design and equal quality. Where two or more standards are listed, the choice shall be by the Contractor. The Engineer reserves the sole right to decide the equality ofmateriais proposed for use in lieu of those specified: Permission to substitute shall be obtained prior to bid in accordance with the Architect's instructions. Warkk under this item of the Contract shall include providing all labor, material, equipment; supplies, and services necessary to install a complete and operational electrical system, both nitaw and exterior, as shown in these plans. All material shall be UL listed as approved and shall be new The Contractor shall comply with applicable local htws, the latest edition of the NEC where not in conflict with those laws, and the rules of the local utility company, Americans with Disabilities (ADA) Act, latest edition of the building code adopted by the Authority Having Jurisdiction over this work, NEMA standards, UL standards, ANSI standards, and the Manufacturer's recommendations regarding their product. The Contractor shall obtain and pay for all required permits. The Contractor shall pay all fees associated with the scope of work as outlined in these documrews. Auer completion of the work, the Contractor shall submit certificate of final inspection and approval from the local electrical inspector certifying that the installation complies with all applicable regulations governing same. The Contractor shall warrant the entire electrical system to be in proper working order Replace at no additional charge all work and/or material which may develop defects, excluding ordinary wear and tear and improper handling, for a period of one year from the date ofaccepmace. RACEWAYS Galvanized Rigid Conduit shall be hot -doped galvanized steel inside and outside including threaded cells. Where field cut and threaded, exposed surface shall be treated with a galvaniziaglaint. Conduit shall be manuAwtmed by Allied Tube, Wheatland, Pittsburgh Staorlarrd, Republic, or Triangle. Galvanized Rigid Coated Conduit shall be coated inside and outside with PVC coating and be ETL listed. Intermediiste Metal Conduit shall be hot galvanized steel with a corrosion resistant coating. Where field cut and breaded, exposed surface shall be treated with a galvanizing paint Conduit shall be manufactured by Allied Tube, Wheatland, Pittsburgh Steel, Republic, or Triangle. No Quick connect couplings are allowed Electrical Metallic Tubing shall be hot galvanized steel with a corrosion resistant coating. Conduit shall be msnufactu rd by Allied Tube, Wbestlam4 Pittsburgh Steel Republic, or Triangle. Fittings shall be set screw type fittings. No quick connect compression figs are allowed Rigid non metallic conduit (PVC) shall be heavy wall schedule 40 polyvinyl chloride as manufachred by Carlos. Condectm and fittings shall be by the same manufacturer: Liquid-tigbt ffe:nble metal conduct shall be type UA with writable fittings as manufactued by Anaconda. Flexible metal conduit shall be used for final connection to vibrating machinery and finer junction box to ligh fixture. Run shall be as short as possible but no more than 72 ". Flexible metal conduit shall be as manufactured by AFC. Conduits shall be sized not smaller than as shown or in accordance with Table 1, Chapter 9 of the NEC, whichever is larger: Conduits shall be supported and substantially fastened to structural members at intervals of no more than 8 fret Supports and fasteners shall be of a type approved for the intended use and appropriate for the application Conduit shall be run concealed in the structue as mucb as practicable. When conduit must be exposed, the conduit shall be instilled with rums atfierparallel orperpendicular to structural members, walls, or vertical intersections. Right angles shall consist of cast metal fittings or symmetrical beads. Co ndurt shall be kept a minimum of 6" away from flues, hot water pipes, steam pipes, or other heat producing devices. Conduit which has been pushed or deformed due to improper bending or nushandim shall not be installed Conduit shall be pit square, threaded, reamed smooth, and drawn up 40L Conduit shall be securely ftstened to all abeet metal outlets, cabinets, junction and pull boxes with locknuts and bushings. Provide bushings at each end of the run. Where spare runs of conduit are mi icated, provide a pull wire in each raceway and cap each end to prevent the collection of debris. Conduit systems shall be installed complete prior to pulling conductors. Conduit shall be installed as follows: Underground - PVC with GRC sweep bends for the vertical turns Exposed Exterior -GRC, IMC Exposed Interior - GRC, )MC, EMT (only above 10' AFF ) Concealed Interior - GRC, IMC, EMT, MC/AC Cable ( only if acceptable to heAHJ) No ENT ( "Sunuf tube') allowed. WIRE AND CABLE Conductors shall be soli drawn copper conforming to ASTM standards runless Ahmunum a specifically indicated on the plans. The maaufscture's name, wire size, and insulation type shall be permanently marked on the conductor jacket at regular intervals in a legible manner. All conductors; shall be labeled at each termination and in all junction boxes with cable tags. Conductors shall be as follows: # 12 AWG - #10 AWG TTHIN or THHW Stranded or solid #8 AWG TRW or TTHIW Stranded #6AWG and huger THW, THHW orXHHHW Stranded Riser General Notes: Conductors shall be color coded as follows: 12012401Ph 1201209 or 1201240 3 Ph 2771480 3 Ph Phase A Black Black Yellow Phase B Blue Blue Orange Phase C N/A Red Brawn Neutral White White White or Grey Ground Green Green Green Any "High Leg" Phase Shall Be Marked with Orange Tape. Wire and cable shall be as manufactured by Southwire, PWC, Carol, Triangle, Anaconda Splices shall be made only in approved locations as follows: #12 AWG - wirenuts #10AWG and larger - compression or camp type slices with insulating hest shrink gym& Fixture wires shall be SF-1 or SF-2 600V minimum #14A WG. AC and MC cables are acceptable where approved by the Authority Having Jurisdiction. BOXES Outlet boxes used in concealed work shall be galvanized or sheradized sheet steel boxes and be adequately sized to accommodate the devices and conductors to be installed (minion 1-112" deep ). Boxes dr tbeirplaster rings shallbe mounted Bush with the finished surface and square with the surfnee. Boxes shall be sized in accordance with NEC Article 314 and be appropriate for the environment in which installed Ceiling boxes shall be 4" octagonal boxes 1-1)2" deep minimum Boxes intended fen mounting ceiling fans shall be rated a minimum of 1001bs weight capacity. Boxes shallbe as manufacdnad by Appleton, Raco, or Steel City. Exposed outlet boxes shall be Crouse -Hinds 7jjw FS or FD or equal. Sectional type boxes shall not be installed in masonry or concrete walls. L,71 1Z ► � Devices shall be as indicated in the Electrical Legend and as shown on the plans. Devices manufwan d by Arnow -Hart, Bryan; or Hubbell and listed in NEMA comparative lists as similar type and quality are approved Finish for devices and cover plates shall be as specified by the Architect. The plans slow apprroximate locations for devices only. The Cwhaictor shall familiarize himself with arrhitoctral and structural details and the rough -in requirements of the equipment to be installed to determine the device location. Devices shall be installed at umifurm heights throughout the installation. Devices installed above countertops shall be installed to avoid eouffict with the backsphusk cabinets, and/or equipment. The final location of devices shall be verified by the Architect. Pull boxes shall be installed in long runs of conduit: Pull boxes shall be galvanized sheet steel construction, sized aeeordilag to NEC Article 314, and installed in an aoecssible location. SAFETY SWITCI w Disconnect sanity switches shall be heavy dirty type 600V or 250V , fused or non -fused as indicated on the plans with the number ofpoles as indicated on the plans. NEMA enclosure type shall be as indicated on the pleas Switch mechanism shall b "quick make - quick break" type ooasbnrcbion The Contactx shall provide mounting frames for switches that can not be securely fastened to a solid structure. Frames shall consist ofgalvanized stool chi are/ set in concrete footings. Hardware (ours, bolts, washers, etc) shall be stainless steel. Switches installed as service entrance disconnects shall be labeled as such and be provided with all accessories and appurtenances required for a service entrance disconnect SERVICE Coordinate with Utility to provide a service as indicated on the plans. Provide all material and labor not supplied by the Utility in order to produce a complete to and operable electrical service complying with NEC and Utility Company regulations. Obtain metering equipment from Utility and install in compliance with Utility Companyregullstiorts. Unless Noted Otherwise, the transformer at the Service Entance will be provided by the Utility. GROUNDING The Contractor shall provide complete system and equipment pumidrng systems Iudbig coadhuctom o�Mm Brood rods, pound buusses, ink all etcfor the service entrance ground, groumcting ofelech ical equipme4 process egiq= n; building steel, or other itms indicated on the drawings. The grounding system shall be installed in accordance with NEC Article 250 and as detailed in the plans. Undiergnoumd connections and connections to building steel shall be exothermic weld. Exposed concoctions shall be irreversible crimp type connections. A green insulated ground conductor as indicated on the plans (nzimimurn size per NEC Table 250.122 ) shall be metalled in each raceway and with each cable.Isolated Ground conductors shall be green with yellow dace. DRY TYPE TRANSFORMERS Transformers of the size and type covered in UL 506 shall be so listed and labeled, ie. Transformers 600V up to and inchding 167 kVA single phase and 500 kVA three phase. Three phase transformers up to 9 kVA shall be Class 180 Insulation System with 80 C Rise. Single Phase transformers and three phase transformers 15 kVA to 500 kVA shall be Class 220 kwiston System with 115 C rise. Cores shall be designed so dot maximum fiuur demsitim are substantially below saturation level. The core volume shall allow efficient operation at 109/9 above the highest tap voltage. All laminators shall be come pasted or annealed, fire of buns and firmly butted The core laminations must be tightly clamped and compressed to provide quiet operation. The entire core and coil assembly must be pedried by hen; napregnsted with silicome varnish, and cured at a minimum of350 F to reduce hotspots and seal out moisture. Coils must be protected with an outer layer ofg1m tape or similar insulation. Transformers 15kVA and larger shall have NEMA standard taps. All tandbimers shall be quiet type. Care and coil assemblies are to be mounted an rubber vibration isolators designed to specifically reduce 120 He sound and multiple harmonics. Enclosure temperature rise shall not exceed 40 C rise above ambient Windings shall be copper Transformers shall be miuuftcdmod by Square 1) A fault current ofLsc-45,242A was obtained from the u duty. IT size or fault current is differen4 notify Architect immediately for resolution 2) Notify Architect Immediately to obtain a resolution ifany discrepancy between field condlitidmns and conduction documents that impacts installation is discovered. 3) Seal Penetrations to Insmre Integrity ofBudding Envelope. Coordinate with Architect NOTICE TO CONTRACTORS: ALL CONTRACTORS PRIOR TO BID SUBMISSION PROCESS SHALL VISIT PROPOSED WORK SITE AND FIELD VERIFY ALL EXISTING CONDITIONS. ANY CONDITIONS THAT DIFFER FROM THAT SHOWN ON THESE PLANS SHALL BE REPORTED TO ARCHITECT/ENGINEER SO THAT NEW AND REVISED BID DRAWINGS OR INFORMATION MAY BE ISSUED. MODIFICATIONS TO SCOPE OF WORK WHICH RESULTS FROM CONTRACTORS NEGLECT TO VISIT THE SITE PRIOR TO SUBMITTING BID, SHALL BE THE CONTRACTORS SOLE RESPONSIBILITY. E r I MOTORS Motors installed under this section shall be TEFC premium efficiency motors suitable for duty in the environment in which they are installed The Contractor shall verify the correct rotation of all motors in the prvjec; whether installed under this section or another PANHXOARDS Paaelboards shall have the number ofphases and wires as indicated on the panel acbedule. The NEMA enclosure type shall be as noted on the panel schedule. Pandboards shall have copper buss, 100% rated neutral with set screw connections, and grand buss with set screw connection The panel box shall not be less than 20 inches wide and be Abritated from galvanized orgalvannea[ed steel. Boxes shall be constivctad with minimum wire bending and gutter dimensions as required by UL and NEC. Tire Box shall have a separate UL label. All miencis willbe factory assembled and braced fora symmetrical fault current as indicated on the panel schedule C'fmuit breakers shall be replaceable without disdubing adjacent units, and without drifting or tapping. All circuit breakkerconnections shall be m a hole tapped by the manufacturer. Circuit breakers shall have common tie trip handles where required. Field ties are not acceptable. Circuit breakers shall have visible trip indication. PAndboards shall be famished with legible, typed panel directories acemaidy identifying the load each circuit breaker saver. Panelboards shall be as manufactured by Square D, Siemens, GE, or Cuder Hammer LIGHT FIXTURES Furnish and install fixduts as indicatod in the Light Fixture Schedule. Catalog numbers indicate base unit: 77w Contra shall fumish all escutcheon plates, p!asw rings, and plates, hanging chains, stems, and other appurtenances necessary for a cOmpklae installation. The Contractor shall match the voltage of the fixture to the voltage of the desigaatod circuit The Engineer reserves the sole right to determine the quality of any fixture proposed for use in lieu of those specified ]matures shall be supported from structure Where installed in lay in acoustic tile ceiling, fixtures shall be supported from structure by two diametrically opposed cornerx Lamps shall be as manukwhu ed by Sylvania, Phillips, or GE. Fluorescent lamps shall be cool whit; unless noted otherwise. Fluorescent ballast shall be high efficiency, low temperature electronic ballasts with less than 10% T HD unless noted otherwise. Ballasts shall be manufactured by Sylvania, Advaoae, or GE. Emergency ballasts shall be manufactured by Bodine. Match the fixture tin to the surface nVon which the fixture is installed Recessed fixtures shall be IC noted fixtures unless noted otherwise Recessed fixtures installed in fire rated assemblies shall be provided with a UL listed method of instillidom to maintain the foe rating of the assembly as designated in the Architectural Plans. Recessed f xtums installed in the building envelope shall be provided with an approved method of installation toprevent air migration through the opening or fixture m accordance with the latest version of the Energy Code. LABELLING Provide engraved phenolic labels white 112" high letters on black background for each pnoelboard>, loadexmter, disconnect switch, service main, etcto identify the equipment served by the device or equipment FIRE RATED SEALS Provide a UL approved fine seal for each and everypenetration of a fire rated assembly ( wal), ceiling; and/or Door) in order to maintain the fire rating of the assembly as indicated in the AmIth ectural plans. Do not install devices within 6" of each other back to back in any fire rated assembly. TELEPHONE Contractor shall coordinate with local utility for exact telephone service roquirameats. The Contractor shall provide a Telephhone Termination Cabin; sized as indicated on the plans, for mounting telephone equipment Provide a #6 A WG ground fain the backboard to the main service ground. Leave s minimmn 6ofslack at the board for termination. CATV Contra shall coordinate with local utility for exact cable television service requirements. The Czatrntor shall provide an AC grade plywood backboard, sized as indicated on the plans, treated with fine retardant paint fur mounting cable television equipment Provide a #6 AWG ground firm the backboard to the main service ground. Leave a minimum 6' of slack at the board for termination A, Amp Amperes EQ Equal, Equipment SBC Standard Building Code AC Alternating Curren; Armored Cable EQUIP Equipment SH Sheet ACT Above Counter Top EX Existing SW switch ADA American's with Disabilities Act FA Fire Alarm TEL Telephone AF Amp Fuse FAAP Fine Alarm Annuciatvr Panel UG Undwgroumd AFF Above Finished Floor FRCP Fine Alarm Cembrol Pawl UL Underwriters Laboratory AFG Above Finished Grade FIX Fixture UNO Unless Noted Otherwise AHU Air Handling Unit FL Floor V Volt AFC[ Arc Fault Circuit Inie7rupter FU Fused W Wire Al Aluminum GFCI Ground Fault Circuit Interrupter WP Weatherproof ANSI American National Standards Institute GFI Ground Fault (Circuit] Inoetrupter )0;11M Transformer Approx Approximately GRC Galvanized Rigid Steel Conduit Arch Architect HP Horsepower, House Panel ASHRAE American Society ofHeating, Refrigeration and Air -Conditioning Engineers HZ Hertz AWG American Wire Gauge IAW In Accordance With BD Board IBC Intemadacal Building Code BLDG Building IEEE Institute of Electrical and Mecironies Engineers C Condui; Centigrade, Celsius IMC Intermediate Metallic Conduit C&P Corp dt Plug ISA Instrument Society ofAmerica C/L Cemteriine JB Junction Box CAB Cabinet KAIC Kilo-Ampew Iotemnrpting Capacity CAP Capacity KVA Kilo Volt Ampere CB Circuit Breaker KVAR Kilo Volt -Ampere Reactive CKT Circuit KW Kilo Watt CLG Ceiling KWH Kilo Wan Hour COL Colulmn MC Metallic Cable Cond Conduit MCB Main Circuit Breaker CONN Connection MECH Mechanical CONT Continua, Continuation MISC Miscellaneous CPT Control Power Transformer Mw Man Lug Only CT Current Transformer AM Motor Rated Switch Cu Copper MT O Mounted DIC Disconnect Switch MTR Mom DET Detail NC Nn maily Closed DF Drinking Fountain NEC National Electric Code DN Down NEMA National Electrical Mmufacdrar's Association DWG Drawing NF Nam -Fused EA Each NFPA National Fire Protection Association EC Empty Conduit; Electrical Contractor NMC NonMetallic Cable, NonMegsllic Conduit EDF Electric Drinking Fountain NO Number, Normally Open EF Exhaust Fan NTS Not To Scale ELEC Electric, Electrical OH Overhead EMT ElectroMetallic Conduit Ph Phase PNL Panel PVC PolyVi TKWaride Conduit RTU Roof Top Uri; Radio Telemetry Unit Riser Diagram Keyed Notes: 01 Existing Wkmmy to Remain ( 8WA ). Field Verify. © Existing Ground To Remain. ® Existing House Panel Discomnect To Remain. Existing Tenant Disconnect To Remain. Currently Vacant © jaxisimir 200A Conductors and Conduit to Remain Field Vey Instan t) ##2IG Continuous to Isolated Ground Buss in Pawl LB. 43 g 200A Safety Disconnect for Tenant Use. Field Verify Fuses Are Class J and 200A. © Existing 200A Conductors and Conduit to Remain. Field Verify. ® Panel LA. 0 (4) #6, (1) #10G, (1) #2IG, 1 "C. ® Panel LB Install (1) #2 IG Continuous firm Main Service Ground to Isolated Ground Buss in Panel. ® Panel LA2. © Lighting Contactor for Exterior Sign(s)/ Lights. 30A EOEff 4 Pole Coniacton(s) in NEMA 1 Enclosure. Square D Class 8903 Type S or Equal. Tirawlock for Control of Exterior Sign(s). Seven Day Skip A Day Astronomic wi Battery Backup, Taxf or Equal. ® Provide Permanently Affixed Label "Five Guys Disconnect 112" ® Provide Pemiatiently Affixed Label "Five Guys Disconnect Z2" ® Provide Permanently Affixed Label 'Fed From Five Guys Disconnect 112" © Provide Permanently Affixed Label "Fed From Five Guys Disconnect 212" PROJECT GENERAL NOTES: 1. Routing sbown a diagrammatic ably. Field verify exact routing of oarduit and coadutcbors. 2. Contractor shall verify do" swings prior to installing light switches. 3. Lay m light fixtures shall be shad on opposite corners from stuct m. 4. No oombuatble material shall be installed m a plenum sp wo Verify Plcenm Spaces with Architectural and Mechanical. 5. Cover plates shall be installed fax• all dmces. Where merle than one device is indicated is the same location, the devices shall be ganged under a common plate 6. No devices shall be mounted within 24" of another device on opposite sides ofa fine rated wall. 7. The Branch Circuit feeding the emergency ligliftWexit signs shall be the saw as that serving the normal lighting to the am and connected ahead of any local switches 8. All wire shall be Capper. 9. Any flexible coodult shall NOT exceed 5'-0" in hngth. 10. Coordinate Mounting Heights for Kitchen Equipment with Kitchen Equipment Supplier, Architectural Plans, and General Contractor Prior to Rougb-In. 11. Device Cove.rph tes Shall Be Stainless Steel. All Devices Shari Be WHITE in Color. Provide Blank Coveiplates Where Devices Are Not Installed 12. All Devices New UNO. EX - Existing to Remain EX R - Existing Shown in Relocated Position. 13. Information contained in these plans regarding existing equipment was supplied by a third party. The Contrator shall field verify exact requirements of the existing equipment. Where that are discrepancies between the design documents and the actual installatiom, the Contractor shall inform the Architect immediately for a resolution. James E. Tremel ling, PE 4838 Campground Road Alexander City, Alabama 35010 r (250 329-3557 F/aidr PEW. Pmjact P P: (2-%) 329-3" 58973 2010022 Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 ``�elalulrr) ��g�' T•REMcc��'. r -� 0 G)51 cc - - .4 .4 li H Z W M LU ZQQ aC "LL I :D-0 LL O J DC ==O O0 tv H O _5 Hm Li- L z Q Q J WV— a Joe 1:� o=C 00 ��_ ^LU @M100011 m ac W N uWLU 3: N REVISIONS NO. DATE REVISION IfQX3MNtFlCATM CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS ERIC 11. SAFFRAW AifCHITKT THIS DRAWING IS THE PROPERTY OF ERIC 1. SAFFRANI ARCHITECT AND IS NOT To BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER WPR ECT ISPROHIBITED. IT IS TO BE RNED UPON REQUEST. L SPECIFICATIONS & RISER DIAGRAM SCALE r) ERIC J. SAFFRAN a SANDWICH UNIT STAINLESS STEEL CAP PRINTER SHELF PRINTER, CAT 3 TO SERVER, DEDICATED NOTES ELECTRICAL/DATA LOCATIONS CAN VARY I HALF HT. WALL, DEPENDING ON ADJACENT SANDWICH TAffi E LOCATION- GC SHALL COFIRN ORIENTATION PRIOR TO CONSTRUCTION ELEVA77ONSHOWNFOR ILLUSTRATION ONLY. COORDINATEDIlVIENSIONS WlINARCIMCTURAL. 21 SANDWICH LINE ELEV 2 scuE: Nrs OOR PLAN - POWER SCALE: 311611=1' 0IE ELEVATION SHOWN FOR ILLUSTRATION ONLY. COORDINATE DD ENSIONS WITH AR . Q OFFICE DESK ELEV 2 scACE: rrrs it POWER GENERAL NOTES: 1) DRefers to Kitchen Equipment. See Kitchen Equipment Schedule for Additional Information. 2) ® Refers to Mechanical Equipment. See Mechanical Equipment Connection Schedule for Additional Information 3) Do Not install back to back devices within 24" of each other in any fine rated wall. 4) Seal all wallpenetrations with UL approved material and methods to maintain the origmal fine rating of the assembly. Coordinate fie wall locations with Architectural plans. 5) Coordinate Exact Plug Configuration with Kitchen Equipment Supplier Price to Rough -in. 6) All Cable Installed in Plenum Spaces Shall be Plenum Rated Unless Installed In Complete Conduit Systems.. 7) EC Shall Run Grounding Conductor To All Kitchen Equipment. 8) All Kitchen Equipment ShallBe Furnished By Others. Electrical Contractor Shall Set In Place and Maloe Final Connections. 9) All Conduit Passing Through the Wall Of a Fr+eeoff/Cooler Shall Be Sealed With Silicone. 10) Kitchen Equipment Receptacles Shall Be NEMA Grounding Type with Brushed Stainless Steel Cover PhdC& 11) All Kitchen Equipment hmction Boxes Shown Shall Include Final Connection to The Respective Kitchen Equipment. 12) Verify Electrical Requimments, Connections, and Exact Location of Connections Prior to Rough -In. Coordinate with Kitchen Equipment Supplier/ Contractor. 13) All Device Covers Shall Have Brushed Stainless Steel Covers. Devices Shall Be WHITE In Color. 14) Interlock Fine Suppression System with Shunt Trips and/or Gas Solenoids for All E Wment Located Under the Hood and Hood Exhaust RmlSupply Fan to Disconnect Power Ups Activation of the System, Shut Off Gas Supply to Gas Fired Equipment, and Notify the Fine Ahum System (If Installed ). 15) Wire Size Applies Throughout Run. Interior Whing Shall be (2) #12, (1) #12G, 3/41C UNO. 16) All Electrical Requirements for the Walk h7 Cooler Shall Be Coordinated with the Mmufacdmer's Shop Drawings. I 7) All 1 SA and 20A 125V Receptacles installed in Kitchens Shall Have Grand Fault Circuit Intern>pter Protection for Personnel Whether or Not the Receptacle Serves Countertop Areas. 18) A 15A or 20A 125V Ground Fault Circuit Interrupter Receptacle Shall Be Installed In An Accessible Location ( Within 2Y) For Servicing Heating; Air-ConditioninX and Refrigeration Equipment. LOW VOLTAGE V4RWG NOTES: 1) EC shall provide conduit, junction boxes, and pullstruigs for security system installation. Coordinate with Owner's Security System Installer for Exact Requirements. 2) EC shall provide conduit, junction boxes, and pallstrings for fire alarm system installation (if fire alarm system is required) Coordinate with Fire Alarm System Installer for Exact Requirements. 3) EC is responsible for smwing any permits required prior to starting any work ( including fine alarm if fire alarm system is required ). 4) Provide separate 3/4" rigid metal conduit for telephone and POS grouphW 5) Provide 3/4"rigid metal conduit from TTC up to ceiling and down to Manager's D=L 6) Provide 3/4" rigid metal conduit from Manager's Desk to Above Rooffor Satellite Dish Connection. Provide weatherhead 7) POS and Telephone widug shall be contained in a complete conduit system from point of origin (POS station, etc. ) to point of termination (TTC or Pull Box at Server). 8) NO flexible conduit is to be used KEYED POWER NOTES: OTelephone Board Provide 2 x2 x3/4" Plywood Trn�atod with Fire Retardant Paint: Provide (1) #60 to Main Service Ground Leave 6' ofSlack for Termination at the Board. Provide I"Conduit to Existing Telephone Cabinet. Field Verify Exact Location. OMaintain 3' Clear from Face ofPanel. O3 (2) #10, (1) #JOG, 314"C. O1 "EC with Pullwire for cable connection to Remote POS printer: OVerify Receptacle Locations with Owner Prior to Rough hL © Storefront Receptacle. Mount Above Storefront Glass. Coordinate with Architect. 0 Junction Box for Signage. EC Shall Provide Connection to Sign. ® Not Used. ® Route Commit Through Millwork to Nearest Full Height Wall. Coordinate with Millwork Inmiler Coordinate Receptacle and Daft Tel lack Mounting Height. Provide 3/49C with pullwire for Each Detw7el Location Routed Through Millwork to Nearest Full Height Wall and Over to Tel Bd for Telephone or to Poll Box at Server at Manager's Desk 10 Refer to Architectural Plans ( Sheet A 2) for Receptacle Dimensions and Amwgement 11 (2) #12, (1)#12G, (1) #12IG, 3/4"C Q I " Conduit Routed Below Slab 13 1 "C Stubbed Above Ceiling for Access. Provide 314" C with Pullwine to Server Location and to T r (3) #10, (1) #JOG, 314"C. 15 Mount Receptacle 18" Below Ceiling, Verify with Equipment Installer Prior to Rougli-In. 1� Refer to Detail 2/E 2 For Additional Infon nation. 0 Refer to Detail 3/lr2 For Additional Information. 1® Not Used 19 Not Used ® (4) #10, (1) #JOG, 3/4"C. 0 Connection for Hood Lights. Coordinate with Hood Installer. Provide for Any Connection between Hood and control Panel. Refer to Manufacturer's Drawings for Additional Information. © Connection for Hood Controls (Control Panel). Coordinate with Hood Installer. Coordinate Location with Hood Supplier and Five Guys CamstimWon Maasgr~r. Provide for Any Connection between Hood and control Panel Refer to Manufacturer's .Drawings for Additional Information. 0 NEMA 6-20R for Cooler. Verify with Cooler Supplier. See Sheet E-3 for Cooler Lights and Heat Trace Connection. ® Receptacle for Hood Grease Lac Heat Tape. Coordinate with Hood Installer for Exact Location. 0 Receptacle for Touchblock Coordinate with Equipment installer for Mounting Height: Coimect to Circuit at Manager's Desk for Touchblock Router ( LB-10 ). ® Not Used © Provide Engraved Covcrplste, - " OUTLET FOR REFRIGERATION ONLY" 2 Receptacle for Bug Light (200*). Mount Receptacle Adjacent to Bug4k Within Reach ofPower Cord ©9 EC Shall Saw Cut Floor to Install Conduit Runs Across Gap Between Millwork. Patch Floor to Match Sannrmding Area. Coordinate with Millwork Installer for Conduit Access. 3g Receptacle Installed Above Ceiling for Security Camera. Coordinate with Owner for Exact Requirements. 3�1 Exterior Doorbell Pushbutton. Refer to Architectural for Additional Infoanation. Wire to Indoor Bell Unit: © Indoor Bell Unit with Transfor itw Verify Exact Location with Owner Prior to Rough -In. Connect to Nearest Convenience Receptacle Chcurit, QReceptacle for Hot Water Recirculating Pump and Timer Coordinate with Mechanical for Location. ® Route Through Contactor. Square D Class 8501 Type C 3QA rated, 120V Coil in NEMA 1 Enclosure. Control Via Switch in Manager's Office. Coordinate Exact Location with Owner. Provide Label "Exterior Receptacles" with Switch. James E. Tremellm* g, PE 4838 Campground Road Alexander- City, Alabama 35010 7` (2W i19.3ss7 Florida Ply: Anjad F: (250329-3570 MM 2010= ARCHITECT Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 �C THE 5 I 41 NAI.E��:�' �rttt1111R�` oC W Z V) W aCeM W ZQ< 2 a�it0 U— nJcC Nb N0-1 HmLL. tee QJJ � W tL (5 Qc E d °L_ CL a� Joe^ N a W N REVISIONS NO. DATE REVISION INDEMNFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN E] THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS . SAFFRAN CHiTECT THIS DRAWING IS THE PROPERTY OF ERIC 1. sAFFRAN ARCHIIEcr AND LS NOT TO BE RE'ItODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PRO ECT IS PROHIBITED. IT IS TO BE RETTIRN� UPON REQUEST. HE FLOOR PLAN - POWER SCALE PROJECT SHEET NO. NO 1030 E-2 DRAWN BY DATE 11-23-10 2 5 OF As ERIC J. SAFFRAN ARCHITECT 1 FLOOR PLAN - LIGHTING It SCALE. 3116" =1' LIGHTING GENERAL NOTES: 1) Do Not install back to back devices within 24" of each otbw in any Sege rated wall. 2) Seal all wall penetrations with UL approved material and methods to maintain the jai fine rat W of the assembly. Coordinate fire wall locations ions with Awhitochusl 3) All Cable Installed in Plenum Spaces Shall be Pkn= Rated Unless Installed In Coarplete Conduit Systems.. 4) All Inttxior Wiring Shall Be (2)#IZ (1) #12G, 314"C UNO. Wire size applies tbwqgbout run. All Exterior Wiring Shall Be (2)#10, (1) #100, 314"C UNO. S) Install rmswitched phase conductor to emergency lights/ exit signs for 24 hour operation, Emergency Lights and Exit Signs Shall be Connected to the Light Circuit Serving the Area in Which they are Installed (NEC 700.12(E). 6) Contractor Shall Supply Lamps for All Fixtures. 7) Low Voltage Wiring Shall be Plenum Rated unless Installed in a complete conduit system 8) Lower Case Letter Denotes Controlling Switch. 9) All Conduit Passing 76nough the Wall Of a FreezedCooler Shall Be Sealed With Silicon 10) NL- Denotes Night Light Cbr int to Remain on 2417. KEYED LIGHTING NOTES: (2) #10, (1) #10G, 314-C. OConnection to Cooler Lights and Heater. Coordinate with Cooler Installer. EC Shall Maine Final Connection. O3 Switch wits Pilot Light Pilot Light ON when Load is ON. Pass & Seymow PS 20AC1 RPL or Equal. ® Install Wad WS 200 Passive Infrared wall Switch Smw set for 10 minute delay to turn off fights in this area when unoccupied LIGHT FIXTURE SCHEDULE DoWmile Descriplin Mmobderer Model Bast watb/!?bdere WISP A 2A Fluorescent Layin Troffer Acrylic Ions EB Fluorescent ll:G4R24l UMX-42g-120 (4) 28W T8 4100K (1) Hochonic 88 120 Smooth Side of Ins Down uboucBdut F29ITSP41/UMXgM B 2ya Fluorescent Lay® Troffer Acrylic Lens EB Fluorescent R0=14Aa-232IXr120 (2) 32W Tit 6" U Lamp (1) Electronic 48 IN Smooth Side of Lens Down a m=Belast 4100K F37I'MR% B1E 2x2 Fluorescent Layin Troffer Acrylic Leas EB Fluorescent Hfr=l-tM ML)6•l20 (2) 32W T86" U Iamp (1) Hxtroeic 48 120 Smooth Side oflns Dawn UkmMUBd st 4100K Flange Mount for Gyp Bond Cvkg F37MSMW6 With Bodine B50 Fmergeacy Ballast CR Single Lamp Pendant wiN 10 of White Cord Seagei ILGX6519-2HU (1)13W CFL (1) E1a tranic 18 120 Red Finish Inside and Oat With Lobe CW Single Lamp Pendant wrkk 10 of White Cord Seagull R&X6519.15BIE (1)13W CFL (1) Electronic 18 120 White Finish laside ad Out With Globe D Not Used E Track Future, White Finish Seaga® SEA-2604-12 (1) 50W PAR20 50 IN Track White Finish Seagull SEA 2512.12 with ShMaRcsistmt Provide end feeds, connectors, etc. as required Scapa SEA2610.12 Coeting to instal a complete and operational tracklightog system. verify Length aad Fedare Chant with Scapa 11T4A428 Architectural drawings. XA FA Sign with Battery Power Astralte R&TP4 -WPM LED 2.5 1" Directional Arrows as Wkated on Plan XB Emergency Light AstraBte IGELW-W (2) 7.2W 14.4 l20 XC Emergency Light/but Siva Combo that Asbalte RDMJ-2-Ii W LID 9 120 Directional Arrows as ladk*cd on Plan (2) SAW Tungsten XCI Emergency Light/Fil Sip Combo trait Asttaite RJCAHJ-2--16-R W-FM LED 9.6 120 Directional Arrows as Wicated on Plan (2) 5AW Tungsten Two (2) Attached Heads +0*1) Remote Heed Edna Battery Capacdy for Additional Head(s) Weatherproof Remote Head RB4tEM-I41-W-6V A Finishes Selected By Architect. AN Fbtures to Include Lamps Coordinate GWing Type with Architectual Plans verity FMM voltage with cm t. EB Fluorescent/SeapiVAstrakc Lightig Pumbm d Thmugh I4atioael Acmat: ludrstrial Lighting Group; Attn: Faroe In or Byron Gordon tc4X&Q&3398), fnc(W376-0816), o-mdl: bm@mdttsuuiotmg.com Provide Disconnecting Means for Fluorescent Fi twes per 2008 NBC 410.130G A0 Futures in the Kitchen, Dish Wash Area, POS Counter, Beverage Counter, and Food Rep Areas shallbe leased orhave shatterproof lamps. La W shag be shattetpmofed witb the fwbwiog: Norman Lamps, Inc. (800) 9924 020 TWO*, NG Denotes Mot Light on Plans James E. Tremellmg, PE 4838 Campground Rood Alexander City, Alabama 35010 7 (2W 329-3ss7 Ftarid. PJW. PA*d & F. (56)32SL3570 58973 2010= Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 cc W 1... W (� U Lh C7�M W Z on- :DLL 0 j at 2 0 ::)v c tb H O -j ym� pd Q -i V) J J Q _ W U UL 0 ad Q Ln 00 ti d N Union a - W N REVISIONS NO. 1 DATE 1 REVISION EFV4RCATK)N CLAUSE NER SHALL RELEASE, HOLD SS, AND INDEMNIFY THE CT WITH RESPECT TO: ANY S MADE TO THE CONSTRUCTION ENTS BY ANYONE OTHER THAN ff CHITECT, OR CHANGES IN ANY OF THE WORK, OR FAILURE BY NTRACTOR TO BUILD IN ANCE WITH THESE UCTIKN DOCUMENTS ERK 1. SAFFRAN ARCHITECT THIS DRAWING 5 THE PROPERTY OF ERIC J. SAFFRAN ARCHITECT ANDS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PR IS PROHIBITED. IT IS TO BE RNA UPON REQUEST. H FLOOR PLAN - LIGHTING SCALE PROJECT NO SHEET NO. 1030 E-3 DRAWW BY DATE II-23-10 3 6 OF ERIC J. SAFFRAN ARCHITECT POWER GENERAL NOTES: 1)ORefers tG Kitclien Equipment See Kitchen Equipamt Schedule for Additional Inf�, 2) ® Refers to Mechanical Fgwpment See Mechanical Equipment Connection Scheduk for Additional Information. 3) Seal aU Wall penetrations with UL approved material and to maimain the adgiml fue rating of the assembly. Coordinate fne wall locations Witb Archrte�ctural plans. 4) All Cable Installed in Plenum Spaces Shall be Plenum Rated Unless Installed In Compkte Conduit Systems.. 5) All Conduit Passing Tbrougb the Wall Of a Freezer/Cooler Shall Be Sealed With Silicone. 6) Interlock Fine &Wprlessio n System With Shunt Trips and/or Gas Sokaoxb for All Equipm nt Located Under the Hood and. Hood Exhaust Faa/34pp1y Fan to Disconnect Power Upon Activation of the System, Shut Off am Supply to Gas Fired Equipment, and Notify the Fire Alarm System (iflnstalled ). 7) Wire Size Applies Throughout Run. Interior Wiring Shall be (2) #12, (1) #12G, 3/41C UNO- 8) All 15A and 2M 125V Receptacles IIstalled in Kitchens Shall Have t i mmd Fault Circuit ha MUPter Proteedon for Personnel Whether or Not the Receptacle Serves Countertop Areas. 9) A 1 SA or 20A 125V Ground Fault Circuit Interrupter Receptacle Shall Be Mofield In An Accessible Lac atiar< ( Within 25') For Servicing Heating, Air-�oning, and Refiteration Equipment: KEYED ROOF NOTES: Ol 60/3/SQAF/3R Heavy Duty Safety Downes + Provide Class RKl Fins. Q (2) #10� (1) #1OG, 3/4"C O3 (3)#14 (1)#10G, 3/4"C. ® 6t1/3/3SAF/3R Heavy Duty Safety Disconnect Provide Class RKl Fuses. OS NEMA 3R Motor Rated Safety Switch. © 30/3/1 OAF13R Heavy Duty Safety Disconnwt Provide Chuss RKl Fuses. Coorddinate Fuse Size with Mans Re Lion. O7 30/3/1 SAF/3R Heavy Duty Safety Disconnect Provide Chuss RKl Fuses. Coordinate Fuse Size with Manufactu rves Reoommendation. ® MainMmme Receptacle. Provide ifnot Integral to Unit or Existing. O9 Route Tbougb Hood Control Pagel Provided By Hood llfiunufsctu nw Refer b manuaCturces Drawmps for Additional Information. Coordinate COD001 Panel Location with Hood Installer. (3)#8, (1)#10Q, 3/4"G OOF PLAN - POWER SCALE: 3116" =1' James E. Tremelling, PE 4838 CamWvumd Rood Alexander City, Alabama 35010 Preston Ridge Commons 31 SS North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 S916 Fax 770 619 5919 ad W UQ� � NW ce Z Q i in a n -j :D-0 C aC =�0 N O J 0 0 cc in coLL. 0<-i � W Uj U. UT ice � °LV _ CO }°C-^N tL W N REVISIONS NO. DATEJ REVISION INDEMMFICATION CLAUSE THE OWNER SHALL RELEASE, HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO. ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK. OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS MACHI�TECT� THIS DRAWING IS THE PROPERTY OF ERIC 1 SAFFRAN ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PRp�ECT a PROHIBITED. IT IS TO BE RETfJRNED UPON REQUEST. I ZANINE PLAN - ER & UGHTING 1030 E=4 r(2M)329-3ss7 FIM*b NW. Aojad* F. OM) 329-35M - 5B973 2010022 11-23-10' 4 OF 5 ERIC J. SAFFRAN ARCHITECT W ELECTRICAL DEVICE LEGEND RECEPTACLES /tlSIMPLEXRECEPTACLE �J WALL MOUNTED 1 CENTERUNQ P & S # 53611 SIMPLEX RECEPTACLE WALL MOUNTED 48" AFF OR 6" ACT TO CENTER UNO DUPLEX RECEPTACLE WALL MOUNTED 18" AFF TO CENTER UNO P & S #: 53621 WP: US S #: WR53621 WiTH W ICU 10-C & WPB SERIES BOX DUPLEX RECEPTACLE WALL MOUNTED 48" AFF OR V ACT TO CENTER UNO P & S #: 53621 WP: USF P & S #: WR53621 WITH WICU10-C & WPB SERIES BOX ADRAPLFX RECEPTACLE WALL MOUNTED 18" AFF TO CENTER UNO 2 P & S #: 53621 GANGED UNDER A SINGLE FACEPLATE WP:USE P & S#: WR53621 WITH W iCU20-C & WPB SERIES BaK UADRAPLEX GROUND FAULT CIRCUIT INTERRUPTER 5mA RECEPTACLE WALL MOUNTED 18" AFF TO CENTER LTAJ 2 P & S k 2095TRWRI GANGED UNDER A SINGLE FACEPLATE WP USE W ICU20-C & WPB SERIES BOX DUPLEX GROUND FAULT CIRCUIT INTERRLJPPER 5mA RECEPTACLE WALL MOUNTED IS- AFF TO CET-F.R UNO DUPLEX GROUND FAULT CIRCUIT INTERRUPTER (5mA) RECEPTACLE WALL MOUNTED 48" AFF OR 6" ACT TO CENTER UNO P & S #: 2095TRWRI WP: USE W ICUIO-C & WPB SERIES BOX SWITCHED DUPLEX RECEPTACLE WALL MOUNTED 18" AFF TO CENTER LJNO - TOP OUTLET SWITCHED SWITCHED DUPLEX RECEPTACLE WALL MOUNTED IS" AFF TO CENTER UNO - BOTTOM OUTLET SWITCHED (t h l�J DUPLEX ISOLATED GROUND RECEPTACLE WALL MOUNTED 18" AFF TO CENTER UNO P & S #: IG $300 ORANGE WP. USE W 1 CU 10-C WPB SMES BOX r}}, j� DUPLEX ISOLATED GROUND RECEPTACLE WALL MOUNTED 48" AFF OR 6" ACT TO CENTER UNO 240V RECEPTACLE WALL MOUNTED 18"AFF TO CENTER UNO ® SPECIAL PURPOSE RECEPTACLE WALL MOUNTED 18' AFF TO CENTER UNO AS SP IFIED ON PLANS ® DUPLEX RECEPTACLE IN FLOOR BOX WITH FLUSH COVER ® DUPLEX UN FAULT CIRCUIT 1NTERRUPTER I 5Ma)RECEPrACLF IN FLUSH FWOR 13OX WiI`H QQVEK DUPLEX ISOLATED GROUND RECEPTACLE IN FLUSH FLOOR BOX WITH COVER ® ®QUADRAPLEX RECEPTACLE IN FLUSH FLOOR BOX WiTH COVER Fig SPECIAL PURPOSE. RECEPTACLE IN FLUSH FLOOR BOX WITH COVER r�5 DUPLEX RECEPTACLE ARC FAULT INTERRUPTER WALL MOUNTED 18" AFF TO CENTER UNO DUPLEX RECEPTACLE .ARC FAULT INTERRUPTER WALL MOUNTED 48" AFF OR 6' ACT TO CENTER IINO DUPLEX RECEPTACLE TAMPER RESISTANT WALL MOUNTED 18" AFF TO CENTER UNO Zffi DUPLEX RECEPTACLE TAMPER RESISTANT WALL MOUNTED 48" .AFF OR 6" ACT TO CENTER UNO D DATA OUTLET WALL MOUNTED 18" AFF TO CENTER UNO. PROVIDE BLANK COVER PLATE. PROVIDE 3/4" EC '1 WI ' STUBBED 6" ABOVE CEILING FOR ACCESS. PROVIDE INSULATING BUSHING ► TELEPHONE OUJI- T WALL MOUNTED 18" AFF TO CENTER UNO. PROVIDE BLANK COVER PLATE. PROVIDE 3/4" EC WITH PULLWIRE STUBBED 6" ABOVE CEILING FOR ACCESS. PROVIDE INSULATING BUSHING DATA/TELEPHONE OUTLET WALL MOUNTED 18" AFF TO CENTER UNO. PROVIDE BLANK COVER PLANE. PROVIDE 3/4"ECWITH PULLWIRFBED " ABOVE CEILING FOR ACCESS. PROVIDFINSULATING BUSHING DATA OUTLET WALL MOUNTED 49" AFF OR 6" ACT TO CENTER UNO. PROVIDE BLANK COVER PLATE. D. D N' PROVIDE 3/4" EC WITH PULL WIRE STUBBED 6" ABOVE CEILING FOR ACCESS. PROVIDE INSULATING BUSHING TELEPHONE OUTLET WALL MOUNTED 48' AFF OR 6" ACT TO CENTER UNO. PROVIDE BLANK COVER PLATE. PROVIDE 3/4" EC WITH PULLWIRE STUBBED 6" ABOVE CEILING FOR ACCESS. PROVIDE INSULATING BUSHING DATA/TELEPHONE OUTLET WALL MOUNTED 48' AFF OR 6" ACT TO CENTER UNO. PROVIDE BLANK COVER PLATE PROVIDE 3/4" EC WiTH PULLWIRE STUBBED 6" ABOVE CEILING FOR ACCESS. PROVIDE INSULATING BUSHING DATA OUTLET IN FLUSH FLOOR BOX WITH COVER . PROVIDE BLANK COVER PLATE, PROVIDE 314" EC WITH PULLWIRE STUBBED 6" ABOVE CEILING FOR ACCESS. PROVIDE INSULATING BUSHING TELEPHONE OUTLET IN FLUSH FLOOR BOX WITH COVER. PROVIDE BLANK COVER PLATE. PROVIDE 3/4" EC WiTH PULLWIRE STUBBED 6" ABOVE: CEILING FOR ACCESS. PROVIDE INSULATING BUSHING EE DATA/TELEPHONE OUTLET IN FLUSH FLOOR BOX. PROVIDE BLANK COVER PLATE. PROVIDE 3/4' EC WFM PULLWIRE TUBBED 6- ABOVE CEILING FORACCESS- PROVIDE INSULATING BUSHING JUNCTION BOX CEILING MOUNTED O JUNCTION BOX WALL MOUNTED 18" AFF TO CENI-ER UNO SWITCHES S WALL SWITCH SPST 48' AFF TO CENTER UNO 20A 120277V P&S#:PS-70AC1-1 S 2 WALL SWITCH DPST 49" AFF TO CENTER UNO 20A 120/277V # A.- WALL SWITCH 3 WAY SPDT 48" AFF TO ('ENTER UNO20A 120277V # PS 20 -1 SWALL SWITCH 4 WAY DPDT 48' AFF TO CENTER UNO 20A 120/277V 4 S DIMMER SWITCH (2000W) 48" AFF TO CENTER UNO INCAN: P&S #: 92080-1 120V FLUOR: P & S #: 93884-1 277V FLUOR: P & S #: 93874-1 S DIMMER SWITCH 3 WAY (150OW) 48" TO CENTER UINO INCAN: P & S #: 91593-1 MOTOR RATED TOGGLE SWITCH 30A 120/277V 2Hp MAX 120/240V S. P & S #: PS30AC2-HP MOTOR RATED TOGGLE SWITCH WITH OVERLOAD PROTECTION C' N FAN SP L - 1) Typical Ground Mat Not to Scale DETAIL NOTES: ELECTRICAL DEVICE LEGEND LIGHTING T4'RECFSSFI) TROFFER ® Ca TX 4' RECESSED TROFFER EQUIPPED WITH EMERGENCY BALLAST AND/OR WIRED AS A NIGHT LIGHT (NL). NL DESIGNATES NIGHT LIGHT. ® D TROFFER TX T RECESSED TROFFER EQUIPPED WITH EMERGENCY BALLAST AND/OR WIRED AS A Ld NIGHT LIGHT` (NL). NL D NA NIGHT LIGHT. F x 4' RECESSED TROFFER, WRAPAROUND OR ENCLOSED STRIP FIXTURE - SURFACE MOUNTED ® OR CHAIN HUNG F x 41'RECESSED TROFFER, WRAPAROUND OR ENCLOSED STRIP FIXTURE - SURFACE MOUNTED ® CHAINQR HUNG. EQUIPPED WITH EMERGENCY BALLAST AND/OR WIRED AS A NIGHT Ll ' L 4' STRIP FLUORESCENT - SURFACE MOUNTED OR CHAIN HUNG hug" 4' TRIP FLUORESCENT - SURFACE MOUNTED OR CHAIN HUNG EQUIPPED WITH EMERGENCY BALLAST AND/OR WIRED AS A NIGHT LIGHT (NL). 8' STRIP FLUORESCENT - SURFACE MOUNTED OR CHAIN HUNG i-�-i B'STRIF FLUORESCENT - SURFACE MOUNTED OR CHAIN HUNG EOLUPED WITH EMERQJENCY 13ALLAST .A O RECESSED DOWNLIGHT O DOWNLIGHT EQUIPPED WITH EMERGENCY BALLAST AND/OR WIRED AS A NIGHT LIGHT L . RECESSED WALL WASH FIXTURE TRACK LIGHTING - LENGTH AS INDICATED VANITY LI H - MOUNT ABOVE MIRROR CEILING FAN WALL MOUNTED LIGHT FIXTURE a 0 WALL PACK- WALL MOUNTED FIXTURE A FLOODLIGHT/ MONOPOINT FIXTURE POLE MOUTTD LIGHT FIXTURE ® EXIT SiGN WITH BATTERY BACKUP CEILING/WALL MOUNTED - FILLED IN SECTION INDICATES / NUMBER OF FACES. ARROWS AS INDICATED ON PLANS - PROVIDE UNSWTTCHED CONDUCTOR FOR 24 HOUR OPERATION. / EMERGENCY LIGHT/F.XIT COMBINATION UNIT CEILING/WALL MOUNTED - Fil t ED IN SECTION INDICATES NUMBER OF FACES. ARROWS AS INDICATED ON PLANS -PROVIDE UNSWiTCHED CONDUCTOR FOR 24 HOUR OPERATION EMERGENCY LIGHT WITH BATTERY POWER ELECTRICAL DEVICE LEGEND CONDUIT/RACEWAY �- -� CONDVIT OR RACEWAY EXPOSED TO VIEW. RUN PARALLEL OR PERPIDICULAR TO STRUCTURE CONCEAL FROM VIEW AS MUCH AS POSSIBLE CONDUIT OR RACEWAY CONCEALED IN CEILING CAVITY OR WALL CONDUIT OR RACEWAY UNDERGROUND OR CONCEALED IN FLOOR SLAB CONDUIT STUB UP O ® CONDUIT STUB DOWN l CONDUIT STUB 1N PHASE CONDUCTOR, NEUTRAL CONDUCTOR, GROUND CONDUCTOR, ISOLATED GROUND CONDUCTOR HOMERUN. ARROW INDICATES NUMBER OF CIRCUITS. TICKS INDICATES NUMBER OF CONDUCTORS NO TICKS INDICATES 1 PHASE, I NEUTRAL, i GROUND CONDUCTOR MISCELLANEOUS _ PANELBOARD,SURFACE MOUNTED = PANELBOARD FLUSH MOUNTED o� TELEPHONE BACKBOARD 4 X8'X3/4' UNO. PAINTED WITH FIRE RETARDANT PAINT DISCONNECT SWITCH, HEAVY DUTY # / # / # AF / # SP1--,C1AL r()TFSI3R-NEanA IR FU9 ti7ZE IN AMPS NUMBER OF NA.FS DISCONNECT FRAW SIZE tpL COMBINATION MOTOR STARTER DISCONNECT SWITCH. SEE LEGEND FOR DISCONNECT l�fl SWITCH ADDITIONAL INFORMATION SUPPLIED ON PLANS CONTACTOR/ RELAY AS SPECIFIED ON PLANS ® TiME CLOCK AS SPECIFIED ON PLANS PHOTOELECTRIC CELL AS SPECIFIED ON PLANS. MOUNT IN INCONSPICUOUS LOCATION ® ABOVE F FACING NORTH () TELEVISION OUTLET 18' AFF TO CENTER UNO WITH 2 RJ45 JACKS AND 1 COAX `I CONNECTION PROVIDE OVER PLATE OUTLET FOR CARD READER - 4 PUSHBUTTON, WALL MOUNTED 48" AFF TO CENTER UNO BELL AND TRANSFORMER IF REQUIRED) WAIL MOUNTED &0- AFF OR 6" BELOW Il CEILING UNO CLOSED CIRCUIT TELEVISION CAMERA am0 /T MOT R -HORSEPOWER AS INDICATED �^A PLUGMOLD 1) All wine for Grmind Mat thrall be #3/0 AWG UNO. 2) Crround Rods shall be 3/4' x 10' Copper Ground Rods. 3) All connections between parnd rods and ground conductors shall be emathermic weld 4) Ghxwd Met shall be insisibd 24" below grade minimum. 5) Ln addition to the ground =K the Contractor shall provide a complete grouding system LA W NEC Article 250. or ERVICE EN7RAN UIP O O rElmAL O"$' O aorawn usmro mum .aoro evoro ME PBIPN L7{VIIRI�PHD evmTO TO r>� 31MM M� I10,W>a STRC1O.LArm O9dA�1 rn.an, mrwsaec� NiAr ll�4ori�/�vie♦f vl WLr)r s/ewo�r �1�rt4,tTl���r•e��rl�bae�4q. (AMW cx. M AMROVIO YFIwL QxD IIw7)9 ar.Mta -EuMam a,d) �rwa vALvs � 4'ENFRAL IV07FS: i) A➢PoevYt aUd. .b. •O AIFt7 Ul1D- aeanoawry 2) See CYi Owl&rAW PW Tr .-,WIZ2 LLAPPROM Neutral Ground Bonding Detail Not to Scale KITCHEN EQUIPMENT LEGEND Fl-tX- 'R1CAL CHARACIUMTKS MARK QTY rnMI VOLT PH AMP ROLGHAIN 8 POS System 120 1 0.7 NEMA 5-20R 8a POS Printer 120 1 L0 NEMA 5-20R 8b Rermte Ticket Printer 120 1 LO NEMA 5-20R 8c POS Server 120 1 5.0 NEMA 5-20R 11 Tea Brewer 120 1 14.8 NEMA 5-20R 13 Soda Dispenser 120 1 14.0 NEMA 5-20R 14 Ice Maker 208 1 9.8 NEMA 14-20R Hoshizaki KMD 8 15 Food Prep Table 48" 120 11 4.3 NEMA 5-20R 16C Sandwich Wrap Table 128" 120 1 2.6 NEMA 5-20R 18 Countertop Warmer 120 1 10.0 NEMA 5-20R 193 Refirigerated Chef Base 97" 120 1 3.0 NEMA 5-20R 20 Gas Griddle (3') 120 t 0.7 NEMA 5-20R 20b Gas Griddle S 1201 1 1.1 NEMA 5-20R 22 Gas Fry Station 120 1 2.8 NEMA 5-20R Cias Fry Station Filter 120 1 5.5 NEMA 5-20R 23 Cooked Fry Station 120 1 8.3 NEMA 5-20R 120 1 8.3 NEM A 5-20R 120 1 1.3 NEMA 5-20R 26 Hood Ca tivaie 19 ) Hood Control 120 1 10.0 Direct Connect i ) Hood Light 120 1 10.0 Direct Connect 1) Hood EF 3 Hp 208 3 9.5 Direct Connect 1 Hood SF 2.0 Hp 208 3 6.0 Direct Connect I ) Hood Heat Trace 120 1 15.0 NEMA 5-20R 1) 30 1 Cooler- hts/Heater 120 1 2.1 Cooler - Condenser 208 1 17.1 33 Bag N Box 34 Cariwnator 1201 1 10.0 NEMA 5-20R 36 Water Heater( Tan Ides s1 120 11 3.1 MRS 47 Crease Storage Unit 120 1 5.0 NEMA 5-20R 3072-NADP 52 Musak System 120 1 9.0 NEMA 5-20R 53 Touch Block NEMA 5-20R 54 Bu lit ht 120 1 1.7 NEMA 5-20R Notes: 1) Field Verify MECHANICAL EQUIPMENT CONNECTION SCHEDULE Id 1% Description i Itc6•ieW Ciwwkristies Circuit Iles' aafim Breaker Feeder Reruarks Vohs Phase Tang kW Hp EI A Amp Pole Dkeoenect Sw i RTU 208 3 4.0 4.5 25.2 LA-31,33,35 35 3 3y#8, 1)♦#1OG�-V4"C 60/3/35AF/3R 1) LA-24,26,28 2 RTU-A 208 3 75 29.8 LA-3739,41 50 3 3 8,(1)#IOG3/4"C 60/3/50AF/3R LA2-38,40,42 3 HD -I ( is Capt ivaie ) 4 MAU-i 208 3 1 2 60 LA-23,25,27 30 3 (3) #10,(I) #IOQ3WC 30/3/I0AF/3R 3),4 5 EF-1 208 3 3 9.5 LA-23,25,27 30 3 3) # 10, (1)# i OG, 3/4" C 30/3/ 15A F/3R 3),4) f WH-A Tankless 120 1 3A LA-18 20 1 2 12,(1)# 1 4"C MRS 7 EF-A 120 1 U20 MRS 3R 2) 1. 11 12 13 U 15 NOTES: 1) Existing Equipmertt. Field Verify Exact Requirements. Connect As Indicated. 2) Interlock EF-A in Prep Area with Prep Area Lts. Interlock EF-A for Restrooms with Restroom fights so that Ether L.t Switch will Energize Fan Prowde Relay - Square D Class 8501 Type C 30A rated, 120V Coll in NEMA 1 Enclosure. Mount In Accessible Location Above Ceiling. 3) Field Verify Fan Characteristics. ProYde Fuse Sized per Manufacturer's Recommendation. 4) Wired Through Food Control Parcel. Refer To Manufacturers Dravrings for Additional Information. PANELBOARD VOLTAGE 120/ZOS VJ 3 PH./ 4 W. BUS SIZE: 200A AMP NO. SERVES LTG R13CP MAINS: TOTALL.OAD: LOAD kVA MTR A/C HTG MIA 60 kVA BREAKER MISC Trip P 11LA11 MOUNTING: SURFACE FAULT DUTY: 42k PHASE BREAKER JA B C IP TRIP IMISC ITT AIC(MIN) LOAD kVA A/C JMTR SCHEDULE Existing REMARKS: RECP 11,TG SERVES NO 1 Spare 20 1 1 201 1.2 Counter Re erator #9 2 3 Tea Brewer # 1 i IS 20 1 2 20 3.8 1 ice Maker # 14 1) 4 5 Soda Dis nser#13 1.7 20 1 6 7 Soda Dis enser # 13 1.7 20 1 2 20 3.8 Ice Maker # 14 I 8 9 Food Prep Table # IS 0.5 20 1 10 Spare 12 i I Sandwich Wrap Table # 16c 1 0.3 1 1 20 1 1 1 20 20 Spare 14 13 Spare 20 1 15 Spare 20 1 1 20 0.8 Mautt Recp 16 17 Spare 20 1 1 20 0.4 Water Heater 18 19 Spare 20 1 1 20 Spare 20 21 Spare 20 1 1 20 Spare 22) 23 EF-UMAU-1 (3) 6 30 3 3 35 9.1 RTU 1 24 25 26 272,8 291 ST (8) 20 1 00 I 20 1 1 1 L2 Hood is (3) 30 31 RTU l) 9.1 35 3 1 20 ST 32 1 20 12 Hood Controls (3) 34 33 35 1 20 ST 8 36 37 RTU-A (1) 13.7 50 3 1 20 0.2 Cooked Fry Station #23 (3) 38 39 1 201 ST 40 41 11 201 Counter Re erator #9 42 (I) HACR Rated Breaker (2) Isolated Ground Circuit (3) Shunt Trip Circuit Breaker (4) Ground Fauit interrupter ( SmA) Circuit Breaker (5) ON/OFF By Tmteclock (6) Provide Ground Fault Deadfront Adjacent to Hood Control Panel. (7) Label "EMERGENCY- DO NOT TURN OFF" - and Provide Lock -On Device (8) Connect Shunt Trip ONLY #'Required By AFU (9) ON/OFF by PE Cell PANELBOARD VOLTAGE: 120/208 V./ 3 PHJ 4 W. MAINS: BUS SiZE: 200A AMP TOTAL LOAD. LOAD (kVA) NO. SERVES LTG RECP MTR A/C HTG MI-k) 59 kVA BREAKER MISC Trip P r'Lm rr MOUNTING: SURFACE FAULT DUTY: 42k PHASE BREAKER A B C P TRIP IMISC JHTU AIC (MiN) LOAD kVA) A/C MTR SCHEDULE Existing REMARKS: 1RECP LTG SERVES NO 1 Cooler#30 3.1 20 2 1 1 1 1 1 1 1 1 1 1 3 3 201 0.3 Gas Griddle #201#20b (3) 2 3 ST 4 5 Carbonator#34 12 20 1 20 0.4 ReffiChefBase#19a 3 6 7 Carbonator#34 12 20 1 ST 8 9lCountertop Warmer # 18 1 1 12 20 1 20 Spare 10 1 i Hood Heat Trace 3) 6 1-8 1 20 1 1. 20 Spare 12 13 ST 20 1.0 Gas Fry Station #22 3) 14 15 Dining Area Lis 1.7 20 1 201 1 ST 16 17 Night is 0.6 20 1 20 1.0 Gas Fry Station #22 3) 18 19 Kitchen Lts 1.9 20 1 ST 20 21 Prep Lis/EF-A/Coolerlts/Htr 1.4 0.1 02 20 1 20 1 E0 Cooked Fry Station #23 3 22 23 Office Its/ RR Its/ EF-A 0.3 0.1 20 1 ST 24 25 Pendant Lights 12 20 1 20 1.0 Cooked Fry Station #23 (3) 26 27 Sign 5) 12 1 1 20 1 ST 28 29 S* n 5 12 20 1 20 Spare 30 31 Sign 5 1.2 20 1 60 15.0 1 Panel B 32 33 Spare 20 1 34 35 Grease Storage Unit #47 1.4 20 1 36 37 Spare 20 1 50 13.7 RTU-A 1 38 39 Recic Pu /Tatter 0.5 20 1 40 411 Lig Control 0.5 T I 42 (1) HACR Rated Breaker (2) Isolated Ground Circuit (3) Shunt Trip Circuit Breaker (4) Ground Fault Interrupter ( 5mA )Cicut Breaker (5) ON/OFF By Tireelock (6) Provide (round Fault Deadfront Adjacent to Hood Control Panel. m Label "EMERGENCY -DO NOT TURN OFF" -and Provide Lock -On Device (8) Connect Shunt Trip ONLY ifRequied By AHJ (9) ON/OFF by PE Cell PANELBOARD VOLTAGE: 120/208 V/ 3 PHJ BUS SiZE 100A Bd >#1 (4)(2) i#2(4) (2) i#3_ 4( )(2) ote Printer 4 W. MAINS: AMP TOTAL LOAD. LOAD(kVA) (1) HACR Rated Breaker (2) Isolated Ground Circuit (3) Shunt Trip Circuit Breaker (4) Ground Fault Interrupter( 5mA ) Circuit Breaker (5) ON/OFF By Timeclock (6) Provide Ground Fault Deadfront Adjacent to Hood Control Panel. (7) label -EMERGENCY- DO NOT TURN OFF" - and Provide Lock -On Device (8) Connect Shunt Trip ONLY if Required By AHJ (9) ON/OFF by PE Cell rrLB11 MI-0 MOUNTING: SURFACE 15 kVA FAULT DUTY: 22k BREAKER PHASE BREAKER cTTW-7p---1 A B C P TRIP imisc IHTi SCHEDULE NEW REMARKS: AIC (MIN) LOAD kVA A/C MTR R13CP ILTG SERVES 02 Desk Rec 02 Desk Rec 0.6 Computer (2) (4 0.5 POS Router (2) 4) 0.6 TouchblockSystem #53 1.0 security 1.0 ATM 1.0 Sound System 0.5 Security Camera Rec OS Security Camera Rec 0-8 Office Recp INSTALL ISOLATED GROUND BUSS James E. Tremelling, PE 4838 Campground Road Alexander City, Alabama 35010 T: (256) 329-3557 Florida PE#: Pmjea # F:(2W329.3570 58973 2010022 Preston Ridge Commons 3155 North Point Parkway Building E - Suite 200 Alpharetta, Georgia 30005 Tel 770 619 5916 Fax 770 619 5919 cl� W Z LU U 0 M V W ZQQ oC 0- U 0 DC tL O j ce 0 O � V)O� N m LL Q < J /W DC O > co^ W N U = LU W N REVISIONS NO. DATE REVISION INDEMNIFICATION CLAUSE THE OWNER SHALL RELEASE HOLD HARMLESS, AND INDEMNIFY THE ARCHITECT WITH RESPECT TO: ANY CHANGES MADE TO THE CONSTRUCTION DOCUMENTS BY ANYONE OTHER THAN THE ARCHITECT, OR CHANGES IN ANY ASPECT OF THE WORK, OR FAILURE BY THE CONTRACTOR TO BUILD IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS ERIC J. SAFFRAN ARCHITECT THIS DRAWING IS THE PROPERTY OF ERIC J. SAFFRAN ARCHITECT AND IS NOT TO BE REPRODUCED OR COPIED IN WHOLE OR IN PART. UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON ANY OTHER PROJECT IS PROHIBITED. iT tS TO BE RETURNED UPON REQUEST. FETT DULES, & DETAILS NO 1030 DRAWN BY I Em5 ,ATE II-23-10 5 OF 5 �� R e r