HomeMy WebLinkAbout38051 Market Square. GENER.AL NOTES I KEYED NOTES I WALL LEGEND I. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFE AND LAWFUL DISPOSAL OF ALL MATERIALS DEMOLISHED. HOWEVER, THE OI EXISTING STRUCTURAL COLUMN - MAINTAIN INTEGRITY DURING OWNER SHALL BE GIVEN THE OPPORTUNITY TO SALVAGE ANY CONSTRUCTION. EQUIPMENT, FIXTURES OR MATERIAL. O2 EXISTING EXTERIOR WALL SYSTEM 2. GENERAL CONTRACTOR TO COORDINATE ANY WORK AFFECTING THE FIRST FLOOR WITH THE BUILDING MANAGER O EXISTING ELEVATOR 3. REMOVE ALL EXISTING CARPETING AND ANY OTHER EXISTING FLOOR O NO WORK IN THIS AREA FINISHES AND BASEBOARDS THROUGHOUT. O EXISTING PLUMBING FIXTURE TO BE REMOVED - SEE PLUMBING 4. REMOVE ALL EXISTING CEILING LIGHTING, REMOVE ALL EXISTING DRAWINGS CONDUIT AND WIRING AS REQUIRED. O EXISTING BASE CABINETRY /MILLWORK TO BE REMOVED. 5. REMOVE ALL EXISITNG DUPLEX RECEPTICLES AND SWITCHES IN WALLS AS REQUIRED. REMOVE ALL CONDUIT AND WIRING AS REQUIRED. O REMOVE ALL EXISTING CEILING t INSULATION ABOVE THROUGHOUT 6. SEE SHEET M2 FOR MECHANICAL DEMOLITION SCOPE OF WORK. OS EXISTING ELECTRICAL PANEL TO BE RELOCATED - SEE ELECTRICAL DRAWINGS. -1. SEE SHEET P2 FOR PLUMBING DEMOLITION. O9 EXISTING FIRE EXTINGUISHER TO BE REMOVED. S. SEE FP DRAWINGS FOR FIRE SPRINKLER DEMOLITION. 10 EXISTING FLOORING AND BASEBOARD TO BE REMOVED S. GENERAL CONTRACTOR TO NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO COMMENCING WITH ANY WORK II EXISTING ONE HOUR FIRE RATED WALL, MAINTAIN INTEGRITY DURING CONSTRUCTION. 10. GENERAL CONTRACTOR TO MAINTAIN INTEGRITY OF ALL EXISTING STRUCTURAL ELEMENTS AND FIRE RATED WALLS DURING 12 EXISTI G TO T ARTITION TO B MOVED. CONSTRUCTION AS REQUIRED. �GD EXISTING SERVER EQUIPMENT ON WALL TO BE RELOCATED BY 10. REMOVE ALL EXISTING CEILING SYSTEMS AS REQUIRED. OWNER J/,�� EXISTING DOOR SYSTEM EXISTING WALL PARTITION EXISTING ONE HOUR RATED WALL PARTITION EXISTING EXTERIOR WALL SYSTEM rrrT � I1 rrrr � _� V L_= EXISTING DOOR SYSTEM TO BE REMOVED =========== EXISTING WALL PARTITION TO BE REMOVED Please be advised this r riew of plans submitted is a cursory review to assist the ccntractor in compliance with applicable fire s tfetb c -33s. This rovie�vd is not nter:�ed to be a final approe al ne c In, m,tteu (;1.;ns It 13 contractor's sole resp ;,sib 101 to cr 're til t tt g �i n� e in Complete compli� -lam k11, � _`�.Pior ^;,1� codes �.�°� local ordlran ,s be site inspcctlon CI'1 t3 :vr sole 4 ^itl"ei}ttsP- to the writra';tor'7 vl . n0 bring those a; ec-­ In responsi° Itf for the cap 1 g o C' 4.� compliance with all appli cable NF ` Codes and io-al ordinances. OEXISTING / DEMOLITION FLOOiRr% PLAN SCALE: 3/16" = I'-0" � m -< z m mn ::E m Z < m m� X Z /r�ai�aee �saua(ks LL ,elm & (c) cas�c 5 805 /Y%Rkt1�rvle REVISIONS BY QI 05. IT II AZP � 0 V U � O U "a b0 Q � � o � z 1 E W U i-. . N [1, C'D ,� N U Q Q 'O 3 y 3 ti 3 m a N N ti �G M f` �r N ti \ 1 N i1 a ..� y 00 N _ O O O O 4 y U � C � U ti� 0 U_ Z L O J o U LL_ °' O 4— L a Z } J 04 •L Q (1)N O V 4- LL_ m 0 = M O j. O 0 r— t 4- Ln a � N 0 Li Date: 02. 09. 11 Scale: AS NOTED Project Mgr: AAY Drawn: DC Job: 10-65 Sheet D1 H:\Projects\Projects 201 0\1 065 - FMC ZH Rheumatology Suite\CD\REV I \Architectural\D I -DEMO FLPL.dwg, 6/9/2011 8:22:40 AM, Xerox 6030.pc3, AZP 11 l IFT_ 1 11. 1- 1 O DOOR AND NAFZOWARE SCHEDULE KEYED NOTES CONT. KEYED NOTES WALL LEGEND CABINET IN NON RATED WALL 3'-0" X 1'-0" X 1 3/4" S.G. WOOD DOOR IN H.M. FRAME WITH 20 GA. STEEL CHANNEL MODEL NO. 1021F12 AS MANUFACTURED BY J.L. INDUSTRIES. FASTEN TO STRUCTURE ABOVE ® PASSAGE HARDWARE SET AND AUTO CLOSER SEE DETAIL 5/Alb. 32 EXISTING STAIR - NO WORK THIS AREA. O EXISTING STRUCTURAL COLUMN - MAINTAIN INTEGRITY DURING 33 LIGHTING MANAGER PANEL - SEE ELECTRICAL. CONSTRUCTION 3'-0" X 1'-0" X 1 3/4" S.C. WOOD DOOR IN H.M. FRAME WITH CABINET IN RATED WALL © STOREROOM HARDWARE SET. SEE DETAIL B/Alb. O EXISTING EXTERIOR WALL SYSTEM J MODEL NO. 1021F12 FX AS MANUFACTURED 3 5/8" 25 GA. GALV. STEEL 34 EYE WASH SYSTEM - SEE PLUMBING. 0 EXISTING ELEVATOR EXISTING DOOR SYSTEM © 3'-0" X 1'-0" X 1 3/4" S.C. WOOD DOOR IN H.M. FRAME WITH HARDWARE SEE BY J.L. INDUSTRIES AT 6" WALLS STUDS AT 6'-0" PRIVACY SET. DETAIL B/Alb. 35 3 5/8" METAL STUDS FRAMED PLUMBING WALL. EXISTING WALL PARTITION 0 3'-0" X 1'-0" X 1 3/4" S.G. WOOD DOOR IN HM. FRAME WITH MODEL NO. I FX AS MANUFACTURED O.C. O PATCH AND REPAIR EXISTING WALL TO MATCH AND ALIGN WITH BY J.L. INDUSTRIES S AT 4" WALLS OFFICE HARDWARE SET. SEE DETAIL 5/Alb. 36 R THIS DOOR SHALL BE A WOOD/GLASS PANEL DOOR- ADJACENT EXISTING WALL - — — — - EXISTING ONE HOUR RATED WALL PARTITION TO REMAIN V-0" X 1'-0" X 13/4" S.G. WOOD DOOR IN H.M. FRAME WITH OFFIC ENTRANCE DOOR SET AND AUTOCLOSER SEE DETAIL 31 PROVIDE NEW DOOR SKIN/VENEER ON OFFICE SIDE OF EXISTING O WATER HEATER - SEE PLUMBING EXISTING EXTERIOR WALL SYSTEM 5/Alb. DOOR FINISH TO MATCH ALL NEW DOORS. 38 G I O AL THI SI - SE P M O BASE CABINETS / COUNTERTOP - SEE INTERIOR ELEVATIONS EXISTING DOOR SYSTEM TO REMAIN. VERIFY WORKING CONDITION. REPLACE HARDWARE AS REQUIRED 39 RELOCATED SERVER EQUIPMENT ON WALL BY OWNER O WALL MOUNTED UPPER CABINETS - SEE INTERIOR ELEVATIONS 4" TYP O HINGES :CAL -ROYAL -US26D - BB31xUS26,TBH31xUS26 O 42" HIGH COUNTER -SEE INTERIOR ELEVATIONS DOOR SYSTEM -REFER TO DOOR SCHEDULE CLOSER LGN - U5260 - 1460/1441 WALL STOP GAL -ROYAL - US26D - CONW542 I STAINLESS STEEL SINK - SEE PLUMBING METAL STUD PARTITION - REFER TO TYPICAL NON -RATED FLOOR STOP : CAL -ROYAL - U626D - DSHPI8 PASSAGE SET :SCHLAGE - U826D - SATURN ALIOS 10 U.G. REFRIGERATOR - SELECTED BY OWNER - VERIFY HEIGHT WALL PARTITION DETAIL A/Ala PRIVACY SET SCHLAGE -US26D - SATURN AL40S LOCK SET SCHLAGE - U926D - SATURN AL50PD II ALIGN NEW WALL WITH EXISTING WALL METAL STUD SOUND INSULATED PARTITION - REFER TO SINGLE DUMMY TRIM : SCHLAGE - U8260 - SATURN ALI10 STOREROOM LOCK —SCHLAGE - U9260 - SATURN ALSOPD 12 LINE OF KNEE WALL BELOW TYPICAL NON -RATED WALL PARTITION DETAIL A/Ala CLASSROOM LOCK SCHLAGE - U5260 - SATURN ALIOPD THRESHOLD 210A IIOA 13 BUILT-IN SHELVING -SEE DETAIL II/A4a. PEMKO -ALUM - or DOOR SWEEP : PEMKO - ALUM - 315GN PULL HANDLE DON-JO - U926D - 1114 14 FIRE EXTINGUISHER - SEE DETAIL B/Ala. �I�oA GL NOTES LAY -IN ACOUSTICAL OR GYPSUM BOARD KICK PLATE DON-JO - ALUM - J102 PANIC DEVICE :MONARCH - MAL - 1910LDANE 15 36" HIGH WRITING SURFACE -SEE INTERIOR ELEVATIONS CEILING. �^ /�� DOOR GENEI"L NOTES 16 NEW ELECTRICAL PANEL - SEE ELECTRICAL DRAWINGS 1. GENERAL CONTRACTOR TO NOTIFY ARCHITECT AFTER LAYOUT IS GYPSUM WALLBOARD I/2" x 48" WIDE G.W.B. APPLIED HORIZONTALLY OR VERTICALLY, II NEW PHONEBOARD -SEE ELECTRICAL DRAWINGS DONE AND WALL TRACK IS IN PLACE PRIOR TO FRAMING ANY WALLS. PER WALL TYPE CORNER JOINTS OVER STUDS, OPENINGS SHALL COMPLY WITH FLORIDA FIRE I. ALL PREVENTION PREVENTION CODE 2001 EDITION / NFPA 101 LIFE SAFETY CODE IS O REFRIGERATOR BY TENANT 2. ALL BIDDERS ARE REQUIRED TO VERIFY EXISTING CONDITIONS PRIOR FIRE STAGGER 16" O.C. OPPOSITE SIDES. 12.12 WIDTH TO ANY BIDDING. NOTIFY ARCHITECT FOR ANY DISCREPANCY. EXTINGUISHER SEE SPECS. ATTACH TO STUDS AND RUNNERS WITH I" LONG TYPE 'IS" SCREWS AT 12.1.4 SWING AND FORCE TO OPEN 12.1.5 LOCKS AND LATCHES AND ALARM DEVICES 19 CUBICAL CURTAIN SYSTEM BY EMPERIAL FASTENER COMPANY OR EQUAL, IFG-SO TRACK WITH IFG-100 CARRIERS. 3. ALL NEW GWB TO RECEIVE SMOOTH LEVEL (4) FINISH. THE JOINTS t RUNNER CHANNELS 12.1.6 SPECIAL LOCKING ARRANGEMENTS 1/2" TO 3/4" FROM EDGES OF G.W.B. 12.1.1 PANIC HARDWARE AND FIRE EXIT DEVICES 20 O 4'-0" W. x V-8" H. INTERIOR WINDOWS SYSTEM IN HOLLOW METAL 4. PREP FLOOR SLAB FOR INSTALLATION OF NEW FLOOR FINISHES AS SCREWS SHALL BE SPACED 8" O.C. ALONG EDGES OF BOARD AND 12" 12.1.8 SELF CLOSING DEVICES FRAME - SEE DETAIL D/Alb - WINDOW HEAD TO MATCH DOOR REQUIRED. PROVIDE COMPLETE OVERLAY IF REQUIRED. O.C. IN THE FIELD, COVER JOINTS 2. ALL DOOR HANDLES SHALL BE LEVER TYPE MEETING A.DA. HEADS. 5. CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING CONDITIONS. WITH TAPE AND JOINT COMPOUND REQUIREMENTS. 21 O SLIDING SATIN ANODIZED ALUMINUM GRL WINDOW X-OR-X FORMAT ANY PROPOSED DESIGN AS SHOWN ON THESE PLANS WHICH ARE IN BOTTOM OF CABINET PER GA - WP - 1200. INCREASE METAL STUD THICKNESS AS 3. ALL INTERIOR DOOR HANDLES SHALL BE SCHLAGE "AL" SERIES WITH I/4" TEMPERED CLEAR GLASS AND FIXED GLASS PANELS CONFLICT WITH EXISTING CONDITIONS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT / ENGINEER OF RECORD PRIOR TO ANY TOP OF WALL 4" REQUIRED FOR PLUMBING AND ELECTRICAL. "SATURN" 22 FLAT PANEL TV - PROVIDED BY OWNER - INSTALLED BY G.C. - DEMOLITION OR CONSTRUCTION COMMENCES. METAL STUDS AT 16" O.C. 4. ALL DOORS WITH AUTO CLOSERS SHALL HAVE BALL BEARING TYPE PROVIDE BLOCKING AS REQUIRED. 6, SEE IDI SHEET FOR FINISH SCHEDULES. 0 14 3 5/8" OR ro" (SEE FLOOR PLAN) HINGES 23 HI-LO DRINKING FOUNTAIN -SEE PLUMBING DRAWINGS I, GENERAL CONTRACTOR TO NOTIFY ARCHITECT OF ANY Q GALV. STEEL STUDS AT 16" O.C, 20 5. ALL NEW INTERIOR DOORS SHALL BE BIRCH VENEER 24 30" WRITING SURFACE -SEE INTERIOR ELEVATION DISCREPANCIES PRIOR TO COMMENCING WITH ANY WORK. GA.STUDS AT WALL MOUNTED EQUIPMENT 6. DOOR CLOSER SHALL BE INSTALLED SUCH THAT THE SWEEP PERIOD 25 UNDER COUNTER DISHWASHER BY TENANT 8. GENERAL CONTRACTOR TO MAINTAIN INTEGRITY OF ALL EXISTING STRUCTURAL ELEMENTS AND FIRE RATED WALLS DURING R-11 BLANKET INSULATION AT OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 10-, THE DOOR WILL TAKE AT LEAST 3 SECONDS TO 26 36" GRAB BARS. COORDINATE EXACT LOCATION WITH TENANT. CONSTRUCTION AS REQUIRED. FLOOR SLAB SOUND PROOF PARTITIONS ONLY. MOVE TO A POINT 3 INCHES (16MM) FROM THE LATCH, MEASURED TO THE LEADING EDGE OF THE DOOR 0BOX OUT EXISTING COLUMN WITH I/2" G.W.B. OVER METAL STUD 9, PATCH AND REPAIR EXISTING GWB TO LOOK LIKE NEW. VENEER OVER 25 GA. GALV. STEEL CHANNEL FRAMING AS REQUIRED. KEEP SIZE TO MINIMUM. EXISTING IF REQUIRED. FASTEN TO SLAB AT 24" O.C. 1, THE MAXIMUM FORCE FOR PUSHING OR PULLING AN INTERIOR DOOR SHALL BE 51bf (222N). 28 10. SEE DOOR CLEARANCES DETAIL A/Ald FREEZER UNIT BY TENANT. FLOOR SLAB S. PROVIDE EITHER WALL OR FLOOR STOPS FOR ALL DOORS AS 29 WOOD CASED OPENING - SEE DETAIL C/Alb. 11, GENERAL CONTRACTOR TO COORDINATE WITH BUILDING MANAGER FOR ALL NEW PLUMBING AND ELECTRICAL WORK REQUIRED BELOW REQUIRED. S. SUBMIT HARDWARE SCHEDULE AND REVIEW WITH ARCHITECT PRIOR PLACING ORDER (3 COPIES) 30 31 EQUIPMENT BY TENANT. EXISTING FIRE RATED WALL, MAINTAIN INTEGRITY DURING THE FLOOR SLAB ABOVE CEILING IN THE SUITE BELOW. OTO PI� TYPICAL PARTITION SCALE: 1 1/2" - I'-0" O SCALE: 1 1/2" - I'-0" CONSTRUCTION. 4 I I I I Fel 11] ID-\ - - ---- r---------------- °I 21 I° 9 9 9 9 9 9 9 9 4 4 U I SERVER U I 4 1 11 U I 21 u I I U`` U I U 9 I 6 24 4/A3 I 1 cn 1 I R�"1 Q, 1 I I , I ` I I 4 q, I I Q, I I I q 1 1 I 21 I I Q, 1 I 1 I 21 I I 19 I m 6 I Q I 124 II N I N N I N I N I � N I I I 6 6 I 39 6 I STATION ', EXAM EXAM EXAM 6 I 6 OFFICE EXAM EXAM I 6 I 6 EXAM OFFICE EXAM I 6 EXAM 2/A3c EXAM 121 24 126 125 24 123 24 122 121 24 Ile 24 116 24 111 II6 24 115 24 128 © UC, U U tII U 0 O L1 U U 0 U (1 U 0 0 O U 19 O 8/A3b �/ 19 © 36 E= 129 2/\3c I MIRK ll CORRIDOR 1/A3c 114 1 14 29 Alc MIXING BIOMED 1 ROOM HAZARD ®113 10 14 11 13 _• r 13 C �. � --7-�------}-- _ ° A 0 ELEC. ---iiP Ir UIOW AREA I 110 I 18 III 9 1 I 28 I ', I r ----------------- OILET ----- L---Ju g 3 DRG I \ SET CLOSET Nll FUSIONEXAM SAMPTOILEf 144 145 120 g o 394 II CENTER Q9/A3b 19 N m 0� ---------- E �, � r 8XM 2/`3c L- ----------------------------------131 I ���� CORRIDOR 29 >— 6/A3b 5/A3b 1 r-------r� Q 8 1 OILET F I I OFFICE e �, /\ i 6/A3a 14 105 2 lq Alc O \/ 4 10 6 1 9 9 1 6 24 31 6 6 F(D] 31 1 2 O--\ - J------ 8 I m I I I $uI�F'LIESO 12 � }PTIOTi 1 30 I 1 i-- I I 146 Q 102 Q 1 11 `n 6 6 1 30n 0 ����411111111110 4 O j 8 I I 4/A3a I O ——---- L------. J 'uo I ' _:; 2ro I 1 -------------- --------- e I ---- I 7------ - - , 31 L J 1 ° NG EXISTING iORRIDOR 1/A3c AId 13 • :::,, „ „ r r, I STAIR OWN STAIR ,� 31 4 32 _ _ J J -- ----,I t---- TOILET 32 — — — — — — — 11 23 22 15 21 12 21 $ 12 22 30 a '-7- D 4 I I -----------, I r I i U EXAM EXAM SHARED OFFICE 136 131 136 r , o �- I/A3 r �n j I I 31 I III' ! I � � UlA1TING I I 14 8 25 b 9 OFFICE -- -- ; 24 24 _ _ _ I I l0l IS DRUG / ToLET I 1T I 4/A3b 9 6 38 _ 13 TOILET r 6 6 I I �---Ju r--- SUPPLIES J O I a% I I I II I IIP 106 /�1wy� i3 I I / - CA (AF- ---% I Q� n � I 14 9 °I r, 9 °I I ©I 35 2 Ald 2 2 O FLOOR PLAN SCALE: 3/16" - 1'-O" REVISIONS BY Q05. IT II AZP o N U u v o I� p .ro E _ x \� E W N N = n N V O U ro �I d¢��.o �C)ti ti ✓ ti �. ti x \3\ ;7- r � 0; I" A I 00 N CD �1 O d O # U Z L O J O L / 1 LL. (1) i 3 'p +- J N •L N O U o -p N _ C) (N � ai •v L — m v = 0 �. 0 0 s •� t LO a Q C:) a) 00 N — � M N 0 1L_ Date: 02. 09. 11 Scale: AS NOTED Project Mgr: AAY Drawn: AZP Job: 10-65 Sheet Ala H:\Projects\Projects2010\1065 - FMC ZH Rheumatology Suite\CD\REVl\Architectural\Ala-FLPL.dwg, 6/9/2011 8:22:28 AM, Xerox 6030.pc3, AZP II —IF I METAL STUDS AT 16" 1/2" GYPSUM O.G. SEE WALLTYPES. WALLBOARD METAL STUDS I/2" GYPSUM DOOR AT Iro" O.G. waLLBOARD 2x BUCK ---------- --- I r � I I -------------J L � ;HOLLOW HOLLOW METAL FRAME JAMB ANCHORx 4 WOOD BUCKEALANT METAL HOLLOW METAL FRAME DOOR FRAME OINTERIOR THWE,4D / JAMS DETAIL SCALE. 3" - 1'-0"III 1/2" G.W.B. BASEBOARD - SEE FINISH SCHEDULE 1G)lINTERIOR WINDOW SILL E IEAD/JAMB SM. SCALE: 3" - I'-0" METAL STUDS AT 16" O.C. SEE WALLTYPES. 1/2" GYPSUM WALLBOARD 2x WOOD BUCK Ix POPLAR TRIM TO MATCH METAL DOOR FRAME PROFILE OI WOOD CASED OPENIM11410— ax SCALE: 3" - I'-0" OIENL4D DIMENSIONED FLOOR PLAN SCALE. 3/6" - I'-0" ODIMENSIONED FLOOR PLM SCALE: 3/16" - I'-0" DIMENSION PLAN NOTES I. THIS PLAN IS FOR DIMENSIONAL PURPOSES ONLY 2. FOR DIMENSIONING PURPOSES, METAL STUD WALLS ARE DRAWN AT 4" OR ro" WIDE U.N.O. - BLOCK WALLS ARE DRAWN AT 8" WIDE U.N.O. 3. 8" BLOCK WALLS AND ro" METAL STUD WALLS ARE DIMENSIONED TO FACE OF WALL - 4" METAL STUD WALLS ARE DIMENSIONED TO CENTER OF WALL, U.N.O. 4. GENERAL CONTRACTOR TO NOTIFY ARCHITECT AFTER LAYOUT 15 COMPLETE AND WALL TRACK 15 IN PLACE PRIOR TO FRAMING ANY WALLS 5. SEE SHEETS Alc AND Aid FOR ENLARGED TOILET PLANS. FLOOR PLAN KEYED NOTES OFIXED PANEL - SATIN ANODIZED ALUMINUM CRL WINDOW X-OR-X FORMAT WITH 1/4" TEMPERED CLEAR GLASS AND FIXED GLASS PANELS (D SLIDING PANEL - SATIN ANODIZED ALUMINUM CRL WINDOW X-OR-X FORMAT WITH 1/4" TEMPERED CLEAR GLA55 AND FIXED GLASS PANELS REVISIONS BY QI 05. 11. II AZP E � U I .c ro ---. O0 U co o ` M @) o� E w N r a M C N U ) U N � 3 Y ati 3 p � 70 ti ti N CL x z^ oo N O i > O O 00 a¢ y N 'C rV N V1 Q) } t� U_ Z_ O J o L U LL- aD O '- v z v +. J N •L Cr :3 O N O U LL. m S ` 0 O O -C •� } In d o C Q ap IV — � M � N 0 J Li — Date: 02. 09. 11 Scale: AS NOTED Project Mgr: AAY Drawn: DC Job: 10-65 Sheet A 1 b H:\Projects\Projects 2010\1065 - FMC ZH Rheumatology Suite\CD\REV 1\Architectural\Alb-DIM-FLPL.dwg, 6/9/2011 8:22:23 AM, Xerox 6030.pc3, AZP KEYED NOTES OI DOOR SYSTEM - SEE FLOOR PLAN AND DOOR SCHEDULES. OBASE BOARD - SEE FINISH SCHEDULE. OOPEN SPACE / KNEE SPACE BELOW COUNTER I I I 4 O4 OPEN BEYOND. A4a 4a A4a A4a OKEYBOARD DRAWER OSLIDING SATIN ANODIZED ALUMINUM CRL WINDOW X-OR-X FORMAT WITH 1/4" TEMPERED CLEAR GLASS AND FIXED GLASS PANELS OLAMINATE BACKSPLASH. y "" "'" � 11 8 FIXED GLASS PANEL. O EYE WASH SYSTEM -SEE PLUMBING. � it _ .__ .....�......� ",..,____ ..__. _._. r, � _..__ . ....... __ _. 10 S.S. SINK -SEE PLUMBING. TV PROVIDED BY TENANT INSTALLED BY G.C. 0 IS 0 �0 12 16 10 19 �p 13 12 UNDER COUNTER DISHWASHER BY TENANT. 13 REFRIGERATOR BY TENANT. N N/00 oN UNDER COUNTER REFRIGERATOR BY TENANT. I� 0 15 REFRIGERATOR BY TENANT. — _ 2 2 16 MICROWAVE BY TENANT. N N _= li LAMINATED END PANEL. IS FREEZER UNIT BY TENANT. 19 FALSE PANEL 5 Z 10 1 10 5 12 9 3 A4a A4a A4a A4a A4a A4a A4a A4a A4a 20 CABINET LOCK OUJORK AREA O WORK ARE ,4 O 15REAKROOM SCALE: 3/8" I'-0" RM • 103 SCALE: 3/8" I'-0" RM 0 103 SCALE: 3/8" I'-0" RM 0 10S Ai I I A4a A4a r1 rl I . ..... _. m........... .......... - N 1i _ ...,.,..._ .__._........_. N 10 -1 �0 e r----- _ f l"_ — 12 N I I I I L J 13 6 3 6 12 17 2 17 A4a A4a SIM. A4a A4a A4a OSREAKROOM O INFUSION CENTER O INFUSION CENTER GENERAL NOTES SCALE: 3/8" I'-0" RM: 109 SCALE: 3/8" I'-0" RM " III SCALE: 3/8" I'-0" RM " III 1, GENERAL CONTRACTOR TO FEILD VERIFY ALL MEASURMENTS PRIOR TO FABRICATION. 2. SEE REFLECTED CEILING PLAN FOR ALL CEILING HEIGHTS. 3. SUBMIT SHOP DRAWINGS PRIOR TO FABRICATION OF CABINETRY. I 4. SEE SHEET A4a E A4b FOR CABINET DETAILS. A4a ---------- ----- I I i I I i i I----------J----------J LJ----------J N \ N0 9 0 20 0 N N \ f 20 � 3 10 3 8 3 c 2 li 6 A4a 4b A4a 4b A4a 4b A4a O INFUSION CENTER IOU--lWUSION CENTER 9 O MIXING ROOM SCALE: 3/8" = I'-0" RM " III SCALE: 3/8" = I'-0" RM • Ill SCALE: 3/6" = I'-0" RM M 112 H:\Projects\Projects 2010\1065 - FMC ZH Rheumatology Suite\CD\REV I \Architectural\A3abc-IELEV.dwg,6/9/2011 8:22:16 AM, Xerox 6030.pc3, AZP BY II E AZP 0 U p Q � N O � ~r O p O ro \� N G W N N 0. N U U • _ Q v N 00 rn 3 3 ti 3 '— o x p � • E ti t J O N N ti Co DD ti ti N \ , N -- ; C 1 x Q� _ N O O O O N N � � to 0 }p � i U_ Z L O J o O L v z t J cVCr 'L � Q (D N O t LL. U - : — C) N vi v m —L cc O >. O 0 r .� •L t LO a Q v C C Q E 00 IV — � M � N 0 s J L.- Date: 02. 09. 11 Scale: AS NOTED Project Mgr: AAY Drawn: DC Job: 10-65 Sheet A3c H:\Projects\Projects 2010\1065 - FMC ZH Rheumatology Suite\CD\REV 1\Architectural\A3abc-IELEV.dwg, 6/9/2011 8:22:08 AM, Xerox 6030.pc3, AZP CEILING SUSPENDED ACOUSTICAL CEILING SYSTEM (4) 010 TEK SCREWS AT EACH CONNECTION ---, �DI CE IL INCH DETAIL SCALE: 1 1/2" - P-0" 3 5/8" 25 GA. (MIN.) METAL STUD FRAMING AT 16" O.G. SECURE TO STRUCTURE ABOVE. — LIGHT FIXTURE. SEE ELECTRICAL ­7 ------------- EQ I I \_ 1 1/2" G.W.B. V_0" 3 5/8" 25 GA. (MIN.) METAL STUD FRAMING AT 16" O.G. SECURE TO STRUCTURE ABOVE. — LIGHT FIXTURE. SEE ELECTRICAL VARIES EE PLAN lotCEILINGS DETAIL SCALE: 1 1/2" - I'-0" v CEILING SUSPENDED ACOUSTICAL CEILING SYSTEM (4) 010 TEK SCREWS AT EACH CONNECTION L 2 x 2 x 20 GA CLIP AT EACH OUTER COMER 1'-roll CEILING —LAY-IN ACOUSTICAL TILE CEILING G CEILING �— (4) 010 TEK SCREWS AT EACH CONNECTION VARIES (SEE PLAN) CEILING L 2 x 2 x 20 GA CLIP AT EACH OUTER CORNER 1/2" G.W.B. SUSPENDED ACOUSTICAL CEILING SYSTEM CEILING WAITING (4) 010 TEK SCREWS AT EACH CONNECTION LIGHT FIXTURE. SEE ELECTRICAL RECESS TRACK LEADING EDGE OF TRACK TO ALIGN WITH LEADING EDGE OF G.W.B. 3 5/8" 25 GA. (MIN.) METAL STUD FRAMING AT I6" O.G. SECURE TO STRUCTURE ABOVE. CEILING L 2 x 2 x 20 GA CLIP AT EACH y • • • OUTER CORNER CEILING • • 1/2" GYPSUM WALLBOARD (4) 010 TEK SCREWS • • AT EACH CONNECTION CEILING RECEPTION VARIES IGICE IL INC* DETAIL I SCALE: 1 1/2" - I'-0" LAY -IN ACOUSTICAL TILE CEILING OIL CEILING 1/2" GYPSUM WALLBOARD H5/8' (D CE IL INCH 1)ETAi[ SCALE: 1 1/2" - I'-0" 3 5/8" 25 GA. (MIN.) METAL STUD FRAMING AT I6" O.C. SECURE TO STRUCTURE ABOVE. LAY -IN ACOUSTICAL TILE CEILING SUSPENDED ACOUSTICAL CEILING SYSTEM 8'-0" CEILING 1/2" G.W.B. 3 5/8" 25 GA. (MIN.) METAL STUD FRAMING AT 16" O.C. SECURE TO STRUCTURE ABOVE. 8'-0" CEILING SUSPENDED ACOUSTICAL CEILING SYSTEM La 1'_011 F SEE WOOD CASED HEADER L — — — J OPENING DETAIL SHEET C/Alb. SEE VARIES PLAN FOR LOCATIONS OCEILING DETAIL SCALE: 1 1/2" - I'-0" KEYED NOTES OI OUTLINE OF WALL MOUNTED UPPER CABINETS - SEE INTERIOR ELEVATIONS 2O G.W.B. WRAPPED HEADER / SOFFIT - SEE CEILING DETAILS OCEILING MOUNTED FLAT PANEL T.V. - SEE ELECTRICAL DRAWINGS. CORRDINATE EXACT LOCATION WITH TENANT. GENE. - -NOTES I. ALL CEILING HEIGHTS TO BE 8'-0" UNLESS OTHERWISE NOTED 2. GENERAL CONTRACTOR SHALL PROVIDE ALL GYP. BD. FURRDOWNS / BULKHEADS AS REQUIRED. 3. G.C. RESPONSIBLE FOR PROVIDING LIGHTING VENDOR COUNTS BY TYPE REQUIRED TO PERFORM ALL WORK ACCORDING TO PLANS. 4. ALL METAL FRAMING FOR GYPSUM WALLBOARD CEILING SHALL BE 25 GAUGE - 3 5/S INCH WITH MINIMUM 3" 10 SHEET METAL SCREWS PER CONNECTION. 5. GENERAL CONTRACTOR TO NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO COMMENCING WITH ANY WORK 6. SEE ELECTRICAL DRAWINGS, FOR ALL LIGHT FIXTURES SPECIFICATION° -1. MTL. STUDS SHALL BE CONNECTED TO STRUCTURAL STL. W/ (3) 0.145"0 RAMSET POWDER DRIVEN FASTENERS. 8. MTL. STUDS/CLIP ANGLE SHALL BE CONNECTED TO MTL. STUDS w/ MIN (4) 012-14 TEK SCREWS. 9. CONTINUOUS TRACK SHALL BE CONNECTED TO STRUCTURAL STL. w/ (2) 0,145"0 RAMSET POWDER DRIVEN FASTENERS AT 16" O.C. 10. CONTINUOUS TRACK/STUDS/CLIP ANGLES SHALL BE CONNECTED TO GONG✓CMU w/ (2) 1/4" m x 1 1/4" TAPGON FASTENERS AT 24" O.C. II. CONNECT SHEATHING TO MTL. STUDS w/ 012-14 TEK SCREWS AT ro" O.C. 12. CONTINUOUS TRACK SHALL BE CONNECTED TO ROOF DECK w/ (2) 010 TEK SCREWS AT 24" O.C. 13. AS REQUIRED, THE CONTRACTOR SHALL PROVIDE CLIP ANGLES FOR ALL METAL STUDS SO PROPER ALIGNMENT CAN BE ATTAINED. CLIP ANGLES SHALL MATCH OR EXCEED THE STUD GAGE. 14, SEE FIRE PROTECTION PLAN FOR ALL FIRE SPRINKLER HEAD LOCATION. 15. SEE MECHANICAL DRAWINGS FOR ALL SUPPLIES AND RETURNS 16. 0 SEE IDI SHEET FOR FINISH SCHEDULES. (31 Rdr--�-FLECTED CEILING: PLAN SCALE: 3/16" - I'-0" REFLECTED CE IL INCH LEGEND 2' x 2' SUSPENDED CEILING GRID SYSTEM WITH 2' x 2' LAY -IN ACOUSTICAL CEILING TILES G.W.B CEILING (SMOOTH FINISH) 2' x 4' FLUORESCENT LIGHT FIXTURE, LAY IN AT SUSPENDED CEILING GRID SYSTEM -SEE ELECTRICAL FOR MORE INFORMATION 2' x 4' FLUORESCENT EMERGENCY LIGHT FIXTURE, LAY IN AT SUSPENDED CEILING GRID SYSTEM - SEE ELECTRICAL FOR MORE INFORMATION 2' x 2' FLUORESCENT LIGHT FIXTURE, LAY IN AT SUSPENDED CEILING GRID SYSTEM - SEE ELECTRICAL FOR MORE INFORMATION 2' x 2' FLUORESCENT EMERGENCY LIGHT FIXTURE, LAY IN AT SUSPENDED CEILING GRID SYSTEM - SEE ELECTRICAL FOR MORE INFORMATION I' x 4' FLUORESCENT FIXTURE WITH WRAP AROUND 0 LENS, SURFACE MOUNTED - SEE ELECTRICAL FOR MORE INFORMATION 101 RECESSED CAN DOWN LIGHT FIXTURE - SEE ELECTRICAL FOR MORE INFORMATION ® EXHAUST FAN - SEE MECHANICAL FOR MORE INFORMATION MECHANICAL SUPPLY REGISTER - SEE MECHANICAL FOR MORE INFORMATION MECHANICAL RETURN REGISTER - SEE MECHANICAL FOR MORE INFORMATION REVISIONS BY Di 05. IT 11 AZP � o .c . � � o �� ro 0 _ � E w u N ^ p h c N U` �I Q¢�°ti° q Y �CN l' 3 ~" o ul rJ. LO N G N t` w ti ✓ ti �. ti a U ,..r F" ..ti./ . &c 00 N 2 CD \ � Q 0 O L � u o cn O U_ Z L 0 J 0 L Z U N •L D Q O N O U ILL. (N _y ai m W rn s L m o >, 0 o s .� Q o c ao N - � M O 0 � J LL_ Date: 02. 09. 11 Scale: AS NOTED Project Mgr: AAY Drawn: DC Job: 10-65 Sheet A2 HMTrojects\Projects 2010\1065 - FMC ZH Rheumatology Suite\CD\REVI\ArchltectUral\A02-RCP.dwg, 6/9/2011 8:21:53 AM, Xerox 6030.pc3, AZP —I — FINISH MATERIAL LEGEND P400M FINISH SCHEDULE CONT. Material Abb. Maker, Model, Manufacturer NO. ROOM BASE FLOORS WALLS Floors-m•__._...__ .._...._v...a Carpet (Field) _..__.. _ Porcelain Tile ----------- --- Vinyl Composition Tile .......... Base Carpet Porcelain Tile Base Vinyl Base Walls and Ceilings Paint .�.�_� CPT PT1 PT2 PT3 VCT CB PTB VB P2 P3 .._ �� _� _ ..__.w. _ Provided and Installed by Ow ner (same carpet as FMC LOL) — Provided and Installed by Ow ner (same tile as FMC LOL) Lightest Tile 18" x 18" W . _ Provided and Installed by Ow ner (same tile as FMC LOL) 18" x 18" �- Provided and Installed by Ow ner (same tile as FMC LOL) Darkest Tile 18" x 18" - Tarkett "Oatmeal" 1356; 12" x 12" x 1/8"thick __._ .___,.__ _ Provided and Installed by Ow ner (same carpet as FMC LOL) Provided and Installed by Ow ner (same tile as FMC LOL) Johnsonite "Sandalwood" 45; 4" Cove ICC 21 "Baked Scone"; Eggshell Finish on Walls - Flat Finish on Ceilings; Epoxy Finish on Walls and Ceilings in Toilets ICI "Brow n Bag" 10YY 35/196; Eggshell Finish Sherw in Williams "Nomadic Desert" SW-6107; Eggshell Finish on Walls - Flat Finish on Ceilings; Epoxy Finish on Walls and Ceilings in Toilets N S E W 6 1 P 14= 1 127 WORK STATION PTB PT1 P1 P1 P1 P1 129 EXAM PTB PT1 P1 P1 P1 P2 130 NOT USED 131 EXAM P'TB PT1 P1 P1 P1 P2 132 CORRIDOR PTB PT1 P1 P1 P1 P1 133 EXAM PTB PT1 P1 P1 P2 P1 134 OFFICE CB CPT P1 P2 P1 P1 135 TOILET PTB PT1 P1 P3 P1 P1 136 EXAM PTB PT1 P1 P2 P1 P1 137 EXAM PTB PT1 P1 P2 P1 P1 138 SHARED OFFICE CB CPT P1 P2 P1 P1 139 CORRIDOR PTB PT1 P1 P1 P1 P1 140 NOT USED 141 MEDICAL ASSISTANTS PTB PT1 P3. P3 P3 P3 142 TOILET PTB PT1 P1 P1 P3 P1 143 TOILET PTB PT1 P1 P1 P3 P1 144 DRUG SAMPLE PTB PT1 P1 P1 P1 P1 145 TOILET PTB PT1 P1 P1 P1 P3 146 OFFICE SUPPLIES PTB PT1 P1 P1 P1 P1 147 CORRIDOR PTB PT1 P1 P1 P1 P1 Doors & Trim Doors, Stained DS Algoma Natural Birch; Finish: RA-1052 Or stain to match Wilsonart "Shaker Cherry" 7935-07 Door Trim, Painted DTP ICI "Brow n Bag" 10YY 35/196; Semi Gloss Oil Based Enamel Finish Cabinetry Counters (All except High Transaction Counters at 101 and 147) PL1 Formica "Mineral Sepia" 3446-58; Matte Finish Cabinets (All except 102) PI-2 Wilsonart " Sand" D331-60 High Transaction Counters (101, 147) 1`513 Formica "Mineral Sepia" 3446-RD; Radiance Finish Cabinets (102) PL4 Wilsonart "Shaker Cherry" 7935-07 Toilet Counters and Aprons PL1 Formica "Mineral Sepia" 3446-58; Matte Finish FINISH FLOOR PLM SCALE: 3/16" = I'-0" REMARKS NO. NO. ROOM 26 101 WAITING 127 102 RECEPTION 8 103 WORKAREA 129 104 CORRIDOR 130 105 CORRIDOR 131 106 DRUG STORAGE / SUPPLIES 132 133 107 TOILET 134 108 TOILET 135 109 BREAKROOM 136 110 ELECTRICAL 137 111 INFUSION CENTER 138 112 MIXING ROOM 139 113 BIOMED HAZARD STORAGE 140 141 114 CORRIDOR 142 115 EXAM 143 116 EXAM 144 117 OFFICE 145 118 EXAM 146 147 V20 CLOSET 1 122 OFFICE 3 124 SERVER ROOM ❑ PTI ❑ FT2 El FT3 ��QQQQ REVISIONS BY QI 05. IT 11 AZP -f ` o Y Y ~• L y C (8J � N tcf C U rC W U o Q � � 00 'O m 3 3 ti 3 i—� E ~o 0 N N ti m ti CN UV� e Q _ N ct O . O OLL' O o 0 .—, C/1 U � 8 -7 t U_ Z L 0 J 0 L U 0 L v z J CA •'' N U _ LL- w — V) v� LJ v m - L 0 A 0 0 t — t In m Q v o m E 00 N — M Qf OQf —i LJ- Date: 02. 09. 11 Scale: AS NOTED Project Mgr: AAY Drawn: DC Job: 10-65 Sheet ID1 H:\Projects\Projects 2010\1065 - FMC ZH Rheumatology Suite\CD\REV I\Architectural\]Dl-FFMSH FLPL.dwg, 6/9/2011 8:21:45 AM, Xerox 6030.pc3, AZP I TTI I T- I TI—F r1 rl LL 0 a a; c� Q) 1= . 0 .. •tv JII . Lu u� W z co 0 I 'o100 P'. I _ I - ' �1 4-21 ~' - - --- 1 11-2" �III1 i 4' I ------------------------ 2II „ 13 j ( I 1(.41 ii r — 1 i / ( OFFICE I1 F- � I F II I l --- 1 1/2' Et _ -- - -+ I I 1 2'ILEiUJ=IH I LIPPLiE.,I I REGEF'Tlti� 1/2'I - - - - - - L --------irl ---- --8 — i - — —� L—�J— __71— I i 14 I I I 10, � �_ �� 1 1 i I i J � I _I 2„�GQ 2 I I� EX. 2 1/TR��?, 2 " I - \ _ _ I' I i rn }, _ 1„ - �E I I' 2--4--- I J; _ -�, I moo_ , I _ - " I ; :; u - 1 I OBE L —_ -J 1/211 I •:} i, I g � I , / t 1 1 jZZ 1 I - - -� -�----------- ------------ J L - 1, , r = I �' I ; II I I t >; p i I J �b<- 2" VTR ( 1 �1/411 H II =..xl I>"�r"'1' : ol*il /211 136 - 13, 13 WAITING OFF I r- E— L /- — — ~1\ °; - � , _ � i � 101a�$I 5 i 111 T0ITET 134TOILE III �L 106 _ I r i EO011 411 Z II S 2 1 1 j L-IH I II II W-11 I!I I n _ I II _ I _ 111 III L j - i lS IM_1nr---1 2 S1 I 21I 2 S1 - u 1-- ! f 211 L -- - - - - .. ACO Wei " --- -- 1 �Nf 11 III - M II "`- -T 16 L L L 2WCO Oj PLU15INO SECOND FLOOR RENOVATION PLAN SCALE: 3/1ro" = 1'-0" KEY PLAN PLUMBING KEY NOTES lO CONNECT NEW 2" VENT PIPING TO EXISTING 2" VENT PIPING ABOVE FIRST FLOOR CEILING. (VERIFY EXACT LOCATION). 2O NEW 2" VENT PIPING UP IN NEW WALL FROM FIRST FLOOR EXISTING FIRST FLOOR CEILING. LAN 01 O3 CONNECT NEW 2" VENT PIPING TO EXISTING 2" VENT PIPING ABOVE SECOND FLOOR CEILING. (VERIFY EXACT 1 LAN 02 LOCATION). CONNECT NEW 4" VENT PIPING TO EXISTING 4" VENT LLD PIPING ABOVE FIRST FLOOR CEILING. (VERIFY EXACT LOCATION). ! PLAN NEW 4" VENT PIPING UP IN NEW WALL FROM FIRST FLOOR -� ----- CEILING. jLO® CONNECT NEW 4" VENT PIPING t0 EXISTING 4" VENT J { I I PIPING ABOVE SECOND FLOOR CEILING. (VERIFY EXACT ' / I LOCATION). _ _ O CONNECT NEW 2" VENT PIPING TO EXISTING 4" VENT j Lj j �� I� - PIPING ABOVE SECOND FLOOR CEILING. (VERIFY EXACT j i !�;--� FT] ; LOCATION). j 1 i r --.. � O8 EXISTING 2" VENT PIPING UP IN EXISTING WALL FROM FIRST FLOOR NEW 4 SANITARY PIPING DOWN TO FIRST FLOOR SEE I 311 Q PARTIAL FIRST FLOOR PLAN. ----------- -- - __ S-- T - - -s O NEW 3" WASTE PIPING DOWN TO FIRST FLOOR SEE i I fC -1 j PARTIAL FIRST FLOOR PLAN. I 2" DOMESTIC WATER PIPING FROM FIRST FLOOR SEE { ' I J, _� PARTIAL FIRST FLOOR PLAN. IE022 i --- __JI 1" COLD, 1" HOT, In" HOT WATER RETURN WATER PIPING y f \ I TO t FROM ELECTRIC WATER HEATER 22 13 NEW 2" VENT PIPING ABOVE FIRST FLOOR CEILING. `Q 21 �- — 14 NEW 4" VENT PIPING ABOVE FIRST FLOOR CEILING. , i L1/2" COLD WATER TO TRAP PRIMER, THEN DOWN IN WALL, j ----- ----- I -- ------ 1 Ny i h " 1 411O THEN TO FLOOR DRAIN FUNNEL. I j 22 rr 21 V 16 1-1/4" COLD WATER t 3/4" HOT WATER PIPING DOWN IN % ; ( WALL. SHUT-OFF VALVES ABOVE CEILING. In,, COLD t HOT WATER PIPING DOWN IN WALL TO FIXTURES. SHUT-OFF VALVES ABOVE CEILING. 18 �1 SHUT-OFF VALVES ABOVE CEILING. _ I 0 1 19 CONNECT NEW 2" COLD WATER TO EXISTING 2" COLD WATER ABOVE FIRST FLOOR CEILING. (VERIFY EXACT LOCATION). ® NEW 2" DOMESTIC WATER PIPING UP TO SECOND FLOOR 21 CONNECT NEW 4" SANITARY PIPING TO EXISTING 4" SANITARY PIPING BELOW SLAB. (VERIFY EXACT LOCATION). CUT t PATCH FLOOR AS REQUIRED. Q NEW 4" SANITARY PIPING FROM SECOND FLOOR W/ 4" Z PI,I5N s LIPARTIAL FIRST FLOOR PLM 01 PLUwSI?4 PARTIAL FIRST FLOOR PLAN 02PWs LU151PARTIAL FIRAN FIRST FLOOR PLAN 03 WALL CLEANOUT g BASE OF SLACK SCALE: 3/16" = 1'-0" O SCALE: 3/16" = 1'-0" O SCALE: 3/16" = P-0" 43 REPAIR EXISTING 2" VENT TWRU ROOF. ® CONNECT NEW 3" WASTE PIPING TO EXISTING 4" 4 SANITARY PIPING BELOW SLAB. (VERIFY EXACT I LOCATION). CUT t PATCH FLOOR AS REQUIRED. MT Yf, 1 5 TYP. 1� I NEW 3" WASTE PIPING FROM SECOND FLOOR W/ 3" WALL S-1 11 S-1 S-I 1" 1-1/2" S-1 4 " „ _ S_1 211 CLEANOUT BASE OF STACK f I III 211 =1 111 — 1-1/4 — 1" 1-1/2" — — II 211 55=1 3/4 1-1/2 1/2"Q Z11 O I I __ - - -� - - I _ _Ift, -- - - -_- -- - ' 1 -- - - I 'I • • t —('�47 S-1— 1-1 211 �r ( 11 fI3 TYP. R -1/4" X. 4/41 211 41 31, 2 124 i 1 I 2"=jt� C� DICE EXAM `r� I EkAM 11 2 ' 1 - I x o i OFFICE EXAM ail I x 4�1 AI -'FAT I Ex I`"1 I Ex�;r1 Ex�r� - 1 EXfii'; i 12 I ! 126 125 , 123 I 122 121 1 11— 115 1 u 11i 116 I15 _ - i 1 123 // i 1 4 311 L EX 4" VTR ---. -- 1 I ► ` ®� �/ I T1`211 - - 1 1 1-1/4 x �l'i 11®_ Rf 1�Oi 1 „ 1 211 IO1EI� `I'-2 1- 1-1/411 5 341 1/2 1FLEC i 11/411 WORK -� WU-I _ 11 I�----------- — 1 r TYP. ,- / 1„ OILS i I1/2" �� - J I III 1e�3 I I _ I't I i Z„ 211 ! 1 1/� - \ I i_ _ -1� 1 12 �G. 2" 1 - I r-- ,.... f r 1 M , 43 I ( -/ � ` EX. 211 1'17R !'cool I "��1 r 211 ,_1 I I } I ,2 ; L oi* - - I' I I 144 A11 1�5 211 ( 11:1 I I _i I ^(f� !` — ----- 1i i) 4 1 h l 1°1E I el- I i - - -s' =, I - - - --- --_ _----- - 211 ri /2'! 2 f I 2" VT i I REVISIONS BY QI 05. IT II V K � o aj 1�aj U - O Q, x E w o o ro it ¢ p ti Y 3� E N N t` 1b I- I -- run) `To- v 1 CD Cl) o V Z Q L y Ur15P m CO E W (p ry E LL 0 0'® co a ®I U a oZ m - .� W �,n • 15 -2 ®� °' m a s e® e 0 Z L — 0 J O L U LL. a) v Z v � J N •16- N O ILL. U — 0 V)LAJ — m :E ` 0 L _ t ° •° L a N Q N E 0000 N 0 Q: L. Date: 02. 09. 11 Scale: AS NOTED Project Mgr: RT Drawn: VK Job: 10-65 Sheet P3 N LL 0 a V V C_ Q N 0 O N n m CL a V- C� Ci M O a Ln 0 Cm rn 0 0 ru E V 0 0 M O .1 V �L O O M O 0 W Ln Q O CD REVISIONS BY QI 05. IT 11 YiK o U u U �ti ro / 0000 .? pp ro x E N P-, N . C)� � U � ~ Q � N ti x I � Lo N r ti ti N O Q. o E O O E U Z Co " s C C 0 .n (6 t -�Qi U M m 0. C 00 . E W N '8 00 CD ULL" N m£ p Z •: C o m C SW ®� W � - _ 0 COO N N d s . �,®; a 0 s ♦, U a♦ U_ Z L 0 J 0 L ♦ ♦ � � V 0 L J N Cr N 0 U _ LL. 3 m W 0 >1 0 0 -C.� Q o E C Q co N _ M O� J L.- Date: 02. 09. 11 Scale: AS NOTED Project Mgr: RT Drawn: VK Job: 10-65 Sheet P5 V,4Y UNIT SC44DUL GRAVITY VENTILATOR SC-44EUL =EXWAU3t PAN SC 4EDULE AIR D ISTR15UTION SC44EPULE 1" EC41ANICAL KEY NOTES GENERAL 1" IEC�-1ANICAL NOTES AIR QUANTITY (CFM) ELEC. NON MARK CsRV-;RV MARK EF-1 EF-2,3,4,5,6,1 NECK FACE MARK HEATING OCCUPIED OCGUPIE MARK CFM SIZE SIZE DESCRIPTION I. CONTRACTOR SHALL CONNECT NEW FLEX DUCTWORK t0 I. ALL EXISTING DATA WAS RECEIVED FROM PLANS DATED COOLING MODE HEATING MANUFACTURER GREENHEC AREA SERVED TOILET ROOM RR/BIO-MED (kW) (HOURS) (HOURS) EXISTING DUCTWORK FLEX DUCT SHALL BE SAME SIZE AS 10-5-01 SHEETS M5.2 t M12.1. REFER TO THESES PLANS FOR MAX. SET. MIN SET. CFM Q MODEL SIRE 8 MANUFACTURER GREENHECK GREENHECK SD -I SD-2 100-200 0-100 8"� 6"� 12"x12" 24"x24" SUPPLY DIFFUSER BASIS OF DESIGN: TITUS TMS EXISTING SIZE. PROVIDE TRANSITION AT DIFFUSER NECK IF NEEDED. MORE DETAIL INFORMATION IF NEEDED. 8-3-1 S60 50 350 35 SAM-5PM 6AM-8 VOLUME (CFM) 0-200 MODEL NUMBER SP-5I10 SP-1380 q 0 q � MATERIAL: STEEL COLOR WHITE 2. CONTRACTOR SHALL CONNECT NEW HARD ROUND DUCTWORK TO EXISTING DUCTWORK SEAL AND INSULATEAROUND ALL NEW AND EXISTING DUCTWORK 3. CONTRACTOR SHALL CONNECT NEW DUCTWORK t0 2. CONTRACTOR TO COORDINATE ROUTING OF ALL NEW DUCTWORK AND PIPING WITH EXISTING CONDITIONS. 3. ALL DUCTWORK SHALL BE ROUTED THROUGH JOIST OPENINGS. 8-3-2 430 20 200 2.0 8AM-5PM &AM-8 WEIGHT (LBS) 10 MAX CFM 100 50 101-200 8"# 241144" 8-3-3 550 30 350 35 5AM-5PM 6AM-8 DISCHARCaE (INCHES) 1/2 DESIGN CFM 100 50 201-325 1011m 241144" 8-3-4 805 300 350 3B 5AM-5PM &AM-8 SHUT-OFF HEAD (FEET) 50 EXTERNAL STATIC PRESS. (IWCs) B B 326-410 124 24"x24" 3B 8-3-5 1 30 60 3 DAM-5PM &AM-8 WEIGHT 13 0 DRIVE DIRECT DIRECT 411-640 1411# 24"x24" EXISTING VAV. PROVIDE TRANSITION FROM EXISTING VAV TO NEW DUCTWORK AS INDICATED. 4. ALL EXHAUST DUCTWORK SHALL BE SEAL CLASS "A". 15-340 615 60 450 4B 8AM-5PM &AM-8 1. INSTALL 12xl2xl8" DEEP PLENUM UNDERNEATH DESIGN DRIVE LOSS - - RG-1 0-350 10"x10" 12"xl2" RETURN/EXHAUST GRILLE GRAVITY VENTILATOR AND TRANSITION TO ROOF u- R3-2 0-1S80 22"x22" 24"x24" BASIS OF DESIGN: TITUS 350F MATERIAL: STEEL WHITE 4. CONTRACTOR SHALL CONNECT NEW ROUND DUCT TO 5. CONTRACTOR SHALL ENSURE THAT ALL VOLUME DAMPERS ARE ACCESSIBLE. 8-3-1 915 50 350 3B SAM-5PM 6AM-8 FAN RPM 950 861 O OPENING; AS REQUIRED. 2. ALL PLENUM DUCTWORK SHALL BE SEAL CLASS "A" AND INSULATED FOR CONDENSATION -COLOR EXISTING AND ROUTE TO ENSURE THAT OPENING OF NEW DUCT IS DIRECTLY IN FRONT OF RETURN DUCTWORK 6. CONTRACTOR SHALL INSPECT ALL EXISTING DUCTWORK 8-3-8 IA05 80 350 3B SAi" 1-5PM &AM-SAM MOTOR ((WATTS/HORSEPOWER)) 80 WATTS 54 WATTS NOTES: B-3-S 805 40 350 3B SAM-5PM 6AM-8 CONTROL ELECTRICAL SERVICE 115/1/60 115/1/60 I. NOISE CRITERIA SHALL NOT EXCEED 25. 2. PROVIDE VOLUME DAMPERS. 5. CONTRACTOR SHALL REPLACE EXISTING RETURN DROP AND RE -INSULATE ANY DUCTWORK THAT HAS INSULATION DAMAGED OR MISSING. OCCUPIED MODE: SONES 2.0 3.0 3. PROVIDE A TITUS TRM PLASTER FRAME OR AN APPROVED EQUAL FOR EACH LAY -IN AIR WITH LINED DUCT, FULL SIZE OF UNIT RETURN OPENING WITH MODULATE AIRFLOW BETWEEN MAX AND MIN SETPOINTS TO MAINTAIN DEVICE IN A PLASTER OR GYPSUM -TYPE CEILING. SIDE INLET OPENING; OF 60x20 FACING AWAY FROM 1. ALL RETURN GRILLES SHALL BE LOCATED IN BETWEEN ROOF OPENING REQUIRED SEE M2 SEE M2 ZONE COOLING SETPOINT. 4. THE RUN -OUT DUCT SIZE FOR EACH SUPPLY DIFFUSER SHALL BE THE SAME SIZE AS THE SUPPLY. JOIST SPACE TO SO THAT SOUND ATTENUATORS ARE UNIT WEIGHT (LBS.) 10 9 CYCLE HEAT AS REQUIRED TO MAINTAIN HEATING SETPOINT AND NECK UNLESS OTHERWISE NOTED ON PLANS. THE RUN -OUT DUCT SIZE FOR EACH INSTALLED. RELOCATE IN ROOM AS NEEDED. DELIVER THE SPECIFIED HEATING AIRFLOW (MIN 5F DEADBAND) RETURN/EXHAUST GRILLE SHALL BE AS FOLLOWS (UNLESS OTHERWISE NOTED ON PLANS): 6. PROVIDE TWO LAYERS OF 2" THICK POLYISOCYANURATE NON -OCCUPIED MODE: - AUTOMATIC BELT TENSIONER - - BOARD INSULATION IN ALTERNATING DIRECTIONS TIGHT 8. CONTRACTOR SHALL REPLACE ALL THERMOSTATS WITH BACKDRAFT DAMPER YES YES VAV BOX SHALL CLOSE OFF AND UNIT SHALL SHUT DOWN. CFM DUCT DIAMETER TO DUCTWORK INSIDE ROOFTOP CURB. PROVIDE NEW UPDATED THERMOSTATS. ALL EXISTING DATA WAS RECEIVED FROM SET OF PLANS DATED 0-100 611# SPRAY -FOAM INSULATION TO FILL GAPS AROUND DUCTS, 10-5-01 SHEET M12.1. FACTORY -WIRED DISCONNECT YES YES 101-220 8"# PIPING AND CONDUITS PROVIDE SHEET METAL CAP S. CONTRACTOR SHALL BALANCE ALL DIFFUSERS TO CFMS 221-350 104 BELOW INSULATION UNDER ENTIRE UNIT CURB. INDICATED ON PLANS. FACTORY -SPEED CONTROL YES 351-480 124 481-600 14"0 601-1200 22A0 1. CONTRACTOR SHALL CONNECT EXHAUST DUCT TO NEW .' �l* r��hA /���� ^�It VENTILATION DE COST IO � CONTINUOUS OPERATION - - INTERLOCK WITH LIGHT YES (3) YES (3) Irw�1i�/ IWL irENTIL ! I 1201-IOW 22A4 12xl2 18" DEEP PLENUM BOX CONNECTING t0 NEW GRV ON ROOF. PROVIDE TRANSITION FROM 12xl2 PLENUM BOX TO CO 2 JOUTSIDE AIR OUTSIDE AIR MOTOR STARTER (DIV. 16) - - GRV OPENING AS REQUIRED. PLENUM SHALL BE SEAL YAY-B-3-5 MAX MIN PROVIDE SQUARE TO ROUND TRANSITIONS AS REQUIRED. 5. PROVIDE MINIMUM OF J" FIBERGLASS WITH FOIL/SCRIM VAPOR BARRIER 6. METAL -AIRS AND PRICE ARE APPROVED EQUALS. CLASS"All. 8. MOTORIZED DAMPER SHALL CLOSE WHEN TEMPERA TURE 100 PPM RTU-3 1,090 CFI" I 600 CFM N 1. GOOK AND TWIN CITIES ARE APPROVED EQUALS. 2. DASH (-) DENOTES NOT REQUIRED. 3. CONTRACTOR SHALL ENSURE THAT ALL EXHAUST FAN ARE IF THE CO 2 LIMIT IS EXCEEDED IN THE TABLE, THEN PROVIDE MAX VENTILATION. Z INTERLOCKED WITH LIGHT THAT ARE CONTROLLED BY AN SENSOR DETECTS HEAT AT SUPPLY DIFFUSER IF ALL OF CO 2 LEVELS ARE BELOW THE SET POINTS THEN OCCUPANCY SENSOR AND SHALL HAVE A MINIMUM 20 MIN. TIME PROVIDE MIN VENTILATION M=1 A.. 1 > 1�1111111/1 ��•CO ® v4 ® :2 � '®® '®®®�'11111f1 P R 0 MECHANICAL ANICAL PLAN SCALE: 3/16" = V-0" REVISIONS BY Q05.11.11 MN f, E o U �00> yx� y w O r Q N (D U p � Q ti Y co ��. LO �LO N �- ti ✓ ti N C Q::_.., k f oU)� <w U U ^ g o E € U Z m p U m_ �€ N � r � C W co U) c E coC E Q J N m '^ Y V) d w®®® m Z o3 W iar% C 2 i3 r fr: - W uj m -6 :2 ®: > Ui o a.o ®® U U_ Z 0 eJ 0 LUG°' 0 L a Z 7 J N .L f/') 0 LL. I U .:3 m LLJ L 0 0 0 -C o C Q E ap N O� .J L._ Date: 02. 09. 11 Scale: AS NOTED Project Mgr: CWS/MN Drawn: CWS/AT Job: 10-65 Sheet M3 mr=bi A65'16TANTS AL 1"A In I L r- 1 F-F - —F, I FIF i REVISIONS BY AREVISION I LZH E C q 12 u u M Cn u -3 El u cd 0 E CN • C5 C\I U ,Z) co E] C\J UD CN r- Co ti CIA ti O EH 0 0 131. O0rnf 1 V, 0 0 CQ r- C, <D 0 00 mm CI4 C4 W 0 uCL j) 00 Cq Z m 9L; 10 a R > 5 C) 00 U W 0 0 -#-- 0 LL- m LLI 0 U-) 00 r-4 0fY -i LL- Date: 02. 09. 11 Scale: AS NOTED Project Mgr: SAT Drawn: W.G.H. Job: 10-65 Sheet E4 Of 7 Sheets '' 11 11 ' 111114d�, IL CORRIDOR 139 0 N rn C Q 3 a L0 w , N ti O N U w w N 0 N REVISIONS BY REVISION 1 U*H 1 05-I�-il i E o U U I \ u Cli O 'b �� O .� O U Lt U N C N V y O l � U • i-. Q' C � O o x � �—� E 0 I \ N t- C ti N ti U � O a •A rZ4 WWA �. O U0g: x w o AA., r O O rn 0 0 0 U W W � � a �w n, H • W W O N N o W Z m W O m ��b uio U WN W mod QvU W E-�C7 U_ Z L 0 J 0 L U LL. N 0 L.Q Z v -o J N Q O N O LL- V m 0 �. L 0 o r- s .� Q 0 N C �_ E M O NW I..L _I L.- Date: 02. 09. 11 Scale: AS NOTED Project Mgr: SAT Drawn: W.G.H. Job: 10-65 Sheet E5 Of 7 Sheets LL 6 6 ki WIRE SERVING NO. 1 SPARE 20 • SPARE 2 2s� 3 SPARE 20 • sa S 4 5 SPARE 20 20 10.4 12 EXISTING LTG. -STAIRWELLS 6 � SPARE 2m • 8 9 SPARE 2m • 2>a 11.0 12 EXISTING LTG. STAIRWELLS lm 11 SPARE 20 • P 13 SPARE 20 • 20 l.�0 12 EXISTING E.P. - ELEV. 14 15 SPARE 20 • 20 2.5 12 EXISTING EP-1, EF-2, EF-3 l(o 1� SPARE 20 • 3P 2 .m l,a EXI T NG VH- ,2,3 18 19 SPARE 2,a • 30 24.0 10 20 21 SPARE 2,a • 24.0 lm 22 23 EXISTING TERMINAL BOXES 8 4sa.m 3P • 2,a SPARE 24 25 8 40.0 Sm • 3P 28.0 lm EXISTING TERMINAL BOXES 26 2� 8 4,a.,a • 35 28.0 l,a 28 29 EXISTING TERMINAL BOXES 6 48.3 3P • 28.0 lm 30 31 6 48.3 6,a • 20 SPARE 32 33 /0 48.3 • 20 SPARE 34 3$ EXIST. RECPT. - {-IYDRO 7NERAPY 12 5.0 2sa • 20 SPARE 3(0 3-1 EXIST. RECPT. - HYDRO TI-4ERAPY 12 5.a 20 • 38 3� 39 XIS G G - IG m 4. 3m • 4>a 2m 41 SPARE 30 • 30 1. SPARE 42 A QS B 0 G (� EXISTING PANEL M MAIN: 225 AMPS ❑M.CB. ■ML.O. ❑FUSIBLE SWITCH MANUF,: SQUARED TYPE: E2 BUS: ■COPPER ❑ALUMINUM LOCATION: ELECTRICAL ROOM "11ID" NEMA: ENCLOSURE: ■ TYPE I El TYPE 3R El OTHER VOLTAGE: 12ID/2ID8y 3 PHASE, 4 WIRE TRIM: ❑ SURFACE ■FLUSH FEE[) FROM: ❑ TOP ❑BOTTOM AIG RATING IIDIDIDID ❑ (FULLY RATED) N0. SERVING WIRE LOAD 13RKR A B C BRICR LOAD WIRE SERVING NO. 1 NEW LIGHTING - 115-126 12 14.4 20 • 3P 4,a.,a 8 EXISTING EAST AIR 2 3 NEW Ll�sl-ITMG, EF-5,6,� - lmb-n3 12 9.� 2(d • 5m 4sa.:a 8 TERMINAL 4 5 NEW LICsHTING, EF-2�,4 - Iml-im3, 11m,142-146 12 8.9 20 • 4�D.m 8 ry � NEW LIGHTINCs - Im4,1m5,114,132,139 12 8.9 20 • 20 9.0 12 NEW RECEPTACLES - 111 8 9 NEW LIGHTMG, EF-1 - 12'i-129,131, 133-138 12 132 20 • 20 9.0 12 NEW RECEPTACLES - 111 Im 11 NEW LIGHTING MANAGER "LMl" 12 1.0 20 • 20 '1.0 12 NEW RECEPT'S., REF. - 111 12 13 NEW COFFEE MAKER - 109 12 125 20 • 20 9.0 12 NEW REGEPtAGLES - 111 14 15 NEW DISHWASHER - 109 12 10.0 20 • 20 9.0 12 NEW RECEPTACLES - 11�,118,119 16 1� NEW MICROWAVE - 109 12 125 20 • 20 9.0 12 NEW RECEPTACLES - 116,11i 18 19 NEW RECEPTACLES - 10i 12 15 20 • 20 9.0 12 NEW RECEPTACLES - 115,116 2m 21 NEW RECEPTACLES - 108 12 15 20 • 20 9.0 12 NEW RECEPTACLES - 119,121 22 23 NEW iREC£PT'S., REF. - 109 12 '1.0 20 • 20 9.0 l2 NEW iRECEPTAGL£S - 121,122 24 25 NEW RECEPTACLES - 124-126 12 9.0 20 • 20 9.0 12 NEW RECEPTACLES - 123,124 26 2� NEW RECEPT'S. - 126-128 12 9.0 20 • 20 4.0 12 NEW REF. - 10�0 28 P - 2 12 12 9 2 • 20 4.0 12 NEW REF. - 106 3m 31 NEW RECEPT'S.,RGP-1 - 1m3,114,12m 12 8.0 20 20 9.0 12 NEW RECEPt'S. - 101,102,14� 32 3 - 1 3 • 20 i5 12 NEW RECEPTACLES - 101,102 34 3S NEW RECEPTACLES - t12 12 45 20 • 20 '15 12 NEW RECEPTACLES - Imi,lm2,im6 36 37 NEW RECEPTACLES - 102, 110 12 '15 20 • 3P 50.0 3 NEW PANEL "Nl" 38 39 NEW t.T$. - 110 12 6.0 20 • 100 50.0 3 4,a 41 NEW COPIER, FAX - 102 12 10.0 20 • 50.0 3 42 A � B � C t6 EXISTING PANEL N MAIN: 225 AMPS ❑M.C.B. ■ML.O. ❑FUSIBLE SWITCI-{ MANUF.: SQUARE D TYPE; NG2 BUS: ■COPPER ❑ALUMINUM LOCATION: ELECTRICAL ROOM "IIID" NEMA: ENCLOSURE: ■TYPE 1 El TYPE 3R El OTHER VOLTAGE: 12ID/2ID8V 3 PHASE 4 WIRE TRIM: ❑SURFACE ■FLUSH FEED FROM: ❑ TOP ❑BOTTOM AIG RATING IIDIDIDID ❑ !FULLY RATED) NO. SERVMrs WIi�E LOAD BRICR A B C BRICR LOAD WIRE SERIIINCs NO. 1 NEW RECEPTACLE - 13i,138 12 9.0 20 • 20 9.0 12 NEW RECEPTACLES - 141 2 3 NEW RECEPTACLE - 136,137,139 12 9.0 20 • 20 9.0 12 NEW RECEPTACLES - 141 4 5 NEW RECEPTACLE - 134,136 12 9.0 20 • .20 9.0 12 NEW RECEPTACLES - 133,141 6 � NEW RECEPTACLE - 136,13'1,139 12 �5 20 • 20 4.0 12 NEW EWG'S - 101 8 T i -t I 11 NEW iRECEPTACLE'S - 127 12 6.0 20 • 20 10.0 12 NEW FREEZER - 103 12 15 NEW RECEPTACLES - 102 12 2.0 20 • 40 28B 8 16 1'i NEW RECEPTACLES -ill 12 15 20 • 20 - - SPARE 18 19 SPARE - - 20 • 20 - - SPARE 20 21 SPARE - - 20 • 20 - - SPARE 22 23 SPARE - - 20 • 20 - - SPARE 24 25 • 26 2'i • 28 29 • 30 31 • 32 33 • 34 35 • 36 3� • 38 39 • 40 41 • 42 A � $ � C � NEW PANEL NI MAIN: 125 AMPS ❑M.GS. ■MLA. ❑FUSIBLE SWITCH MANUF.: SQUARE D TYPE: NQOD BUS: �COF'PER ❑ALUMINUM LOCATION: ELECTRICAL ROOM "IIID" NEMA: ENCLOSURE: ■TYPE 1 ❑ TYPE 3R ❑OTHER VOLTAGE: i2IDi2mav_. 3 PHASE d WIRE TRIM: ❑SURFACE ■FLUSH FEED FROM: ❑ TOP ❑BOTTOM AIG RATING ImIDIDID � (FULLY RATED) 1 * y* y * * 1 NOTE: PROVIDE CIRCUIT BREAKER HANDLE TIES TO SIMULTANEAOUSLY DISCONNECT ALL ASSOCIATED NOTE: PROVIDE CIRCUIT BREAKER HANDLE TIES TO SIMULTANEAOUSLY DISCONNECT ALL ASSOCIATED NOTE: PROVIDE CIRCUIT BREAKER HANDLE TIES TO SIMULTANEAOUSLY DISCONNECT ALL ASSOCIATED UNGROUNDED CONDUCTORS SUPPLYING MULTIWIiRE (SHARED NEUTRAL) BRANCH CIRCUITS PER UNGROUNDED CONDUCTORS SUPPLYING MULTIWIiRE (SHARED NEUTRAL) BRANCH CIRCUITS PER UNGROUNDED CONDUCTORS SUPPLYING MULTIWIRE (SHARED NEUTRAL) BRANCH CIRCUITS PER THE N.E.C. 210.4. THE N.E.G. 210.4. j THE N.E.C. 210.4. * PROVIDE A NEW 20 AMP., 1 POLE CIRCUIT BREAKER MATCH EXISTING TYPE. * REUSE EXISTING 20 AMP., I POLE CIRCUIT BREAKER �c * PROVIDE A NEW 100 AMP., 3 POLE CIRCUIT BREAKER MATCH EXISTING TYPE. NOTE: PROVIDE AN ENGRAVED NAMEPLATE "N 120/208V FED FROM MOP". MATCH EXISTING BUILDING STANDARD. 1 1 1 1 1 1 N0. SERVING WIRE LOAD BRKR A B C BRKR LOAD ZVA EXISiINI� i�ANEL "1„I" LOAD CALCULATION O D D S I TI N E A D A T T T L EXISTING LIGHTING 2,568 VA x 125 = 3,21m VA EXISTING FANS 492 VA x 1.00 = 492 VA T TO .25 3 v MIS(. =EXISTI'NG 1,20(d VA x 1.00 = 1,200 vA EXISTING (SIGN) 2,880 vA x 12 = 3�600 V EXISTING AIR CONDITIONING/ HEATING V I = 5 S v GRAND TOTAL = 59,343 VA I 59 360 A = 165 AMPS SUILDINC� LOAD cALcUL,�TIONS LOAD DESCRIPTION DEMAND FACTOR TOTALS A. EXISTING LOADS: THE LARGEST LOAD RECORDED BY FLORIDA POWER CORPORATION IN THE LAST TWELVE MONTHS WAS 188 KW IN AUGUST 2+alfd. ISS,�D00 VA x 125 (NEC ARTICLE 220 - 35) = 235,000 VA B. NEW LOADS: I T C 0 A 125= '1 6 RECEPTACLES 32,052 VA - ISt 10,00fd VA g 10mgo = im,fdtDO VA REM. 22,052 VA +� 5>ago = 11,026 VA 404 - �XIS7INC� i�r4N�L "N" LOAD CALCULATION LOAD DESCRIPTION DEMAND FACTOR TOTALS I 5 = 7 6 NEW RECEPTACLES 32,(d52 VA - 1ST Im,mOm VA m 100go = 1m,000 VA REM. 22,m52 VA � 50go = 11,026 VA NEW FANS 4m4 YA x 1.m0 : 4m4 VA NEW WATER HEALER C6.m KW) 6,0mm VA x I.mm 6,0mm VA NEW MIS(. EQUIPMENT 9,432 VA x I.mm 9,432 VA EXISTING AIR CONDITIONING/ HEATING 1440m VA GRAND TOTAL 59,310 VA I = 59,31mVA = 165 AMPS 36m NEW P�4N�� "N1" LOAD CALCULATION LOAD DESCRIPTION DEMAND FACTOR TOTALS NEW RECEPTACLES 11,580 VA - 1ST Im,mOm VA g 100go = If�,Ofdfd VA REM. 1,580 VA g 50go �90 VA NEW WATER HEATER (6.0 KW) 6,00m VA x 1.,a0 = 6jd00 VA 8 v NEW MIS(. EQUIPMENT 2,352 VA x 1.00 = 2,352 VA GRAND TOTAL = 19,43(d VA I - 19,430VA = 54 AMPS 36m REVISIONS BY REVISION 1 wGH 1 05-I