HomeMy WebLinkAbout38135 Market Square (8)ONCOLOGY EXPANSION G L� AT<i<pw pk q Ne�+JG CpOp ESCAMI/Rlp Pt y W17 38135 MARKET SQUARE-AjCY � �n�YhN�CoRH��Ef ORNp 068 z FLORIDA 33542''�,�F� pyy�-2MIN�� ! S 1 GENERAL NOTES CONSTRUCTION NOTES SYM OL LEGEND (BUILDING CODE INFORMATION WILDING CODE IWORMATION CONT. INDEX 01= DRAWINGS I. ALL WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF THE NATIONAL FIRE CODE FLORIDA BUILDING CODE, FLORIDA PLUMBING CODE, FLORIDA MECHANICAL I. INTERIOR FINISH MATERIALS APPLIED TO WALL AND CEILING SHALL BE IN ACCORDANCE WITH ASTM E84. ALL FINISH MATERIALS SHALL MEET A CLASS B INTERIOR FINISH RATING APPLICABLE CODES. - MEANS OF EGRESS: (EXISTING BUILDING) T1 TITLE SHEET, CODE I1 F0WATION AND CODE;' "NATIONAL ELECTRICAL CODE," AND ALL OTHER APPLICABLE LOCAL, STATE, AND IN EXIT AND EXIT ACCESS AREA. GLASS "C" ELSEWHERE. x THE FLORIDA BUILDING CODE, FIFTH EDITION (2014) DRAWING INDEX FEDERAL CODES AND ORDINANCES, AND ALL AUTHORITIES HAVING LOCAL JURISDICTION. • BUILDING FBC - BUILDING, CHAPTER 10 2. ALL EXIT DOORS SHALL BE OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A xx • PLUMBING a EXISTING BUILDING MAXIMUM FLOOR AREA PER OCCUPANT LSi LIFE SAFETY PLAN 2. THE GENERAL CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH THE KEY, TOOL, SPECIAL KNOWLEDGE OR EFFORT. MANUALLY OPERATED FLUSH BOLTS OR BUILDING SECTION MECHANICAL . ELECTRICAL TABLE 1004.1.1: 100 SF CURRENT EDITION OF THE "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION" SURFACE BOLTS SHALL NOT BE USED. SYMBOL ACCESSIBILITY 2,514 SF 26 PERSONS AIA DOCUMENT A201. Al EXISTIWs/DEMOLITION PARTIAL FLOOR PLAN 3. THE CONTRACTOR SHALL, UPON DISCOVERY, GIVE WRITTEN NOTICE TO THE ARCHITECT OF 3. ALL GLAZING WITHIN A 24 INCH ARC OF DOORS WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE FLOOR AND GLASS BELOW 18" A.F.F. AND ALL GLAZING IN DOORS FLORIDA FIRE PREVENTION CODE FIFTH EDITION NFPA 101 LIFE SAFETY CODE FLORIDA EDITION EGRESS WIDTH PER OCCUPANT -TABLE 1005.3.2 AND NEW PARTIAL FLOOR PLAN ANY MATERIALS, EQUIPMENT, OR DESIGN FEATURES WHICH HE BELIEVES TO BE SHALL BE SAFETY GLASS, TEMPERED GLASS OR ACRYLIC PLASTIC SHEET. PER x NATIONAL ELECTRICAL CODE 2011 EDITION AZ EXISTING/DEMOLITION PARTIAL REFLECTED INADEQUATE OR UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES, OR RULES AND F15C-2406.1 xx 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN 26 x 0.2 = 5.2" CEILING PLAN AND NEW PARTIAL REFLECTED REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION OVER THE WORK, AND OF ANY ALLOW. PROVIDED CEILING PLAN NECESSARY ITEMS OR WORK OMITTED FROM THE DRAWINGS. 4. OBJECTS PROTRUDING FROM WALLS WITH THEIR LEADING EDGES BETWEEN 21" AND 80" WALL SECTION OCCI,IPANCY CLASSIFICATION (EXISTING BUILDING) MIN. CLEAR DOOR OPENING - 1000.1.1 3211 2 34" Aid INTERIOR ELEVATIONS ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4" INTO WALKS, HALLS, SYMBOL FBC - BUILDING, CHAPTER 3 MIN. CLEAR STAIR WIDTH - 1009.4 4411 2 48" A3b INTERIOR ELEVATIONS 4. ALL SUBCONTRACTORS SHALL USE ONLY SKILLED CRAFTSMEN, EXPERIENCED IN THE WORK OF THEIR TRADE, TO ENSURE FIRST CLASS WORKMANSHIP. ANY WORK NOT EQUAL CORRIDORS, PASSAGEWAYS, OR AISLES. OBJECTS MOUNTED AT OR BELOW 27" ABOVE FINISHED FLOOR MAY NOT PROTRUDE ANY AMOUNT. FREE STANDING OBJECTS MOUNTED SECTION 304: BUSINESS OCCUPANCY - GROUP B - SPRINKLERED COMMON PATH OF TRAVEL - 1014.3 100 FT <100 FT A4 CABINET DETAILS EXIT ACCESS TRAVEL DIST. -TABLE 1016.2 300 FT < 300 FT TO BEST TRADE STANDARDS SHALL BE REMOVED AND REPLACED AT NO ADDITIONAL ON POST OR PYLONS MAY OVERHANG 12". PROTRUDING OBJECTS SHALL NOT REDUCE THE x MIN. CORRIDOR WIDTH - 1018,2 44" 2 44" A5 DOOR SCHEDULE, ROOM FINISH SCHEDULE COST. SHOULD ANY SUBCONTRACTOR REFUSE TO REMOVE AND REPLACE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING SPACE. xx CLASSIFICATION OF WORK DEAD END CORRIDOR - 1018.4 50 FT <50 FT AND FINISH FLOOR PLAN UNSATISFACTORY WORK, THE CONTRACTOR MAY REMOVE AND REPLACE IT, AND CHARGE DETAIL FEBC -EXISTING BUILDING -SECTION 504 MIN. NUMBER OF EXITS - 1021.1 / 1021.2 2 4 THE COST TO THE SUBCONTRACTOR 5. PROVIDE DEADWOOD BLOCKING WITHIN WALL CAVITIES AT LOCATIONS INCLUDING, BUT NOT TO, MOUNTED SYMBOL ALTERATION LEVEL •2 NI LIMITED WALL CABINETRY, FIRE EXTINGUISHER CABINETS, TOILET NUMBER AND SIZE OF EXITS ARCHITECTURAL SPECIFICATIONS 5. IT IS THE GENERAL CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION ACCESSORIES, GRAB BARS, WALL STOPS, ETC.. 18GA, GALV, FLAT METAL MAY BE USED IN PROCEDURE AND SEQUENCE TO ENSURE THE SAFETY OF PEOPLE AND OF THE BUILDING LOCATIONS APPROVED BY ARCHITECT. SINGLE ENTRANCE DOORS 34" x 1 = 34" P0. 1 PLUMBING -LEGEND, NOTES AND DETAILS AND ITS COMPONENT PARTS DURING CONSTRUCTION. THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION WHATEVER TEMPORARY BRACING OR TIE DOWNS THAT MAY x AND BUILDIAREA: (EXISTING BUILDING) HEIGHTNG TENANT EXIT DOOR 34" x 3 = 102" P PLUMBING - PARTIAL FLOOR PLANS OF BE 6. ALL RATED PARTITIONS SHALL EXTEND FROM THE TOP OF THE FLOOR TO THE CEILING xx TOTAL EXIT WIDTH 136" NECESSARY. SUCH MATERIAL SHALL BE REMOVED AND SHALL REMAIN THE PROPERTY AND BE SECURELY ATTACHED THERETO. WHERE SAID CEILING IS NOT PART OF AN ,•� DETAIL FBG - BUILDING, CHAPTER 5: TYPE II-5, SPRINKLERED P10.1 PLUMBING - ISOMETRIC DIAGRAMS OF THE CONTRACTOR AFTER COMPLETION OF THE PROJECT. ASSEMBLY HAVING A FIRE RESISTANCE RATING AT LEAST EQUAL TO THAT REQUIRED FOR THE PARTITION, THE PARTITION SHALL BE CONSTRUCTED TIGHT AGAINST THE FLOOR OR SYMBOL �`� AREA MODIFICATION FOR FRONTAGE INCREASE - 506.2 0.00% SPACES WITH SINGLE EXIT - N/A 6. ALL PRODUCTS AND PARTS SHALL FIT TOGETHER NEATLY, WITHOUT DAMAGE OR THE ROOF DECK ABOVE. AREA MODIFICATION FOR AUTOMATIC SPRINKLER SYSTEM - 506.3 20.00% TABLE 1015.1 / 1021.2 M0.1 MECHANICAL -LEGEND, NOTES, CODE DISFIGUREMENT, EXCEPT FOR SPECIFIED CURVED SURFACES, ALL PRODUCTS AND PARTS ALLOWED PROVIDED CRITERIA AND AIR TERMINAL SCHEDULE SHALL BE CONSTRUCTED/ FABRICATED AND INSTALLED TRUE, IN LINE, AND PLUMB. ALL 1. PENETRATION OF FIRE RATED WALLS, FLOORS, OR FLOOR/ CEILING ASSEMBLIES FOR TABLE 503: HEIGHT AND BUILDING AREA INTERIOR FINISHES: M J MECHANICAL - PARTIAL FLOOR PLANS NON CONFORMING WORK SHALL BE REJECTED AND RE -ACCOMPLISHED BY THE GENERAL ELECTRICAL, TELEPHONE, PLUMBING, I-I.V.A.C. DUCTS, COMMUNICATION SYSTEMS OR SIMILAR 0'-011 ELEVATION MARK MI2.1 MECHANICAL - SCHEDULESCONTRACTOR AT NO ADDITIONAL COSTS TO THE OWNER. FACILITIES SHALL BE PERMITTED BY NON-COMBUSTIBLE PIPE OR CONDUIT WHEN ALL 70P OF SLAB MAXIMUM BUILDING HEIGHT 55' 25' FBG -BUILDING, CHAPTER 8 BUSINESS - GROUP B (SPRINKLERED) MI4.1 MECHANICAL - DETAILS OPENINGS AROUND THE PIPE OR CONDUIT ARE FIRESTOPPED WITH APPROVED MAXIMUM STORIES 4 1 INTERIOR WALL AND CEILING FINISH REQUIREMENTS - TABLE 803.9 1. ALL WORK SHOWN ON THE DRAWINGS SHALL BE CONSTRUCTED OF NEW COMPONENTS. NON-COMBUSTIBLE MATERIALS OR WHEN THE PENETRATION IS PROTECTED WITH A SYSTEM AREA PER FLOOR UNLIMITED 2,514 SF VERTICAL EXITS AND EXIT PASSAGEWAYS: CLASS B WHICH HAS AN "F" RATING EQUAL TO OR GREATER THAN THE ASSEMBLY IN WHICH THE EXIT ACCESS CORRIDORS / EXITWAYS: CLASS C E0.1 ELECTRICAL - LEGEND, NOTES AND CODE S. ALL BIDS SHALL BE PREPARED FROM A COMPLETE SET OF CONSTRUCTION DOCUMENTS. PENETRATION OCCURS. x�A INTERIOR ELEVATION ROOMS AND ENCLOSED SPACES: CLASS C CRITERIA COMPLETE SETS OF DOCUMENTS SHALL NOT BE BROKEN UP FOR BID PURPOSES. SUCH ACTION MAY RESULT IN A LACK OF INFORMATION IN REFERENCE TO THE SCOPE OF WORK 8. WALL AND ROOF/ CEILING ASSEMBLIES NOTED AS U.L., G.A. OR OTHER APPROVED TESTING MARK CONSTRUCTION TYPE: (EXISTING BUILDING) INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED IN ACCORDANCE E5.1 ELECTRICAL LIGHTING - PARTIAL FLOOR TO BE PERFORMED. AGENCIES ARE CONSIDERED PROPRIETARY. PROPRIETARY ASSEMBLIES MUST BE BUILT KEYED DRAWING NOTES FBG - BUILDING, CHAPTER 6 WITH ASTM E 84, PLANS UTILIZING THE COMPONENTS, MEANS, AND METHODS SPECIFIED BY THE TESTING AGENCY. TABLE 601 - FIRE RESISTANCE RATING FOR BUILDING ELEMENTS Eb•I ELECTRICAL POWER - PARTIAL FLOOR 9. IT SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO PERSONALLY FIELD REQ'D PROVIDED SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED IN PLANS INSPECT THE PROJECT SITE PRIOR TO THE PREPARATION AND SUBMITTAL OF HIS BID. 9. PROVIDE AND INSTALL PORTABLE FIRE EXTINGUISHERS AS SHOWN IN THESE DOCUMENTS STRUCTURAL FRAME INCLUDING ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND ASTM C 636, EI0.1 ELECTRICAL - LIGHT FIXTURE SCHEDULE AND THIS INSPECTION IS REQUIRED SO THAT THE CONTRACTOR SHALL BE TOTALLY FAMILIAR OR AS OTHERWISE DIRECTED BY THE LOCAL FIRE MARSHAL. DOOR NUMBER 000 BEAMS, COLUMNS, GIRDERS, TRUSSES 0 HR 0 HR WITH THE EXISTING CONDITIONS AND THEIR INTERFACE WITH THE NEW CONSTRUCTION AS SYMBOL -- - BEARING WALLS, EXTERIOR 0 HR - 0-HR MATERIAL, OER O H TRIM SHA T I T I TI A AM THAN FPLASTIC USED AS INTERIOR RLL AVE A OTHER - - _ PANEL_ SCHEDULES - - - DEFINED IN THESE -CONSTRUCTION DOCUMENTS. 10. SIGNAGE SHALL BE PROVIDED AS REQUIRED AND AS STATED IN THE 2012 FLORIDA BEARING WALLS, INTERIOR 0 HR 0 HR MINIMUM GLASS C FLAME SPREAD AND SMOKE -DEVELOPED INDEX WHEN EI4J ELECTRICAL - DETAILS ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION AND SHALL COMPLY WITH CHAPTER 1 NONBEARING WALLS, INTERIOR 0 HR 0 HR TESTED IN ACCORDANCE WITH ASTM E 54. 10. UNLESS OTHERWISE SPECIFIED, THE G.C. SHALL FURNISH A WRITTEN GUARANTEE FOR ALL SECTION 103 SIGNS. ROOM NUMBER SYMBOL FLOOR CONSTRUCTION INCLUDING WORK (EQUIPMENT, MATERIALS, AND LABOR), AGAINST ANY DEFECTS IN SAID WORK FORA 000 SUPPORTING BEAMS 4 JOISTS 0 HR 0 HR PERIOD OF ONE (1) YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION, WITH ALL ROOF CONSTRUCTION INCLUDING APPROPRIATE REPAIRS OR REPLACEMENTS AT NO ADDITIONAL COST TO THE OWNER. SUPPORTING BEAMS 4 JOISTS 0 HR 0 HR 11. IT SHALL BE THE RESPONSIBILITY OF THE G.G. AND/OR CONTRACTORS TO COMPLY WITH Ox WINDOW ALL THE REQUIREMENTS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT OF IcJ10 BY SYMBOL TABLE 602 -FIRE RESISTANCE RATING FOR EXTERIOR WALLS BEARING THE U.S. DEPARTMENT OF LABOR, AND REQUIRE ALL ITS SUBCONTRACTORS AND AND NON BEARING BASED ON FIRE SEPARATION DISTANCE EMPLOYEES TO COMPLY WITH THIS LAW, AND ANY RELATED STATE OR LOCAL LAWS, LESS THAN 5' 1 HR N/A 12. THE DATA GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. X 1 T 10' I HR N/A 10 t0 2(d 0 HR N/A /�p� � 1ECT 8CVPE V V /�/+ /� /y� /� LOCATION MAP THEIR ABSOLUTE ACCURACY IS NOT GUARANTEED, AND THE G.C. SHALL OBTAIN EXACT REVISION 20' TO 30' 0 HR N/A LOCATIONS, MEASUREMENTS, LEVELS, ETC. AT THE SITE AND SHALL SATISFACTORILY 30' AND OVER 0 HR 0 HR $ ADAPT HIS WORK TO THE ACTUAL CONDITIONS OF THE BUILDING. DO NOT SCALE PRINTS. Dauphtery Vakenoli Ave : t�+)� oa 4 Rd VERIFY ALL DIMENSIONS WITH THE ARCHITECT PRIOR TO COMMENCING WORK. INTERIOR RENOVATIONS FOR A MEDICAL OFFICE WITHIN AN EXISTING 5 Pli FIRE RESISTANCE (EXISTING BUILDING) FREE STANDING MASONRY MEDICAL OFFICE BUILDING. "tt� ,� 13. THESE DOCUMENTS AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE ALTERED IN nKyA. A ANYWAY BY THE CONTRACTOR OR THE OWNER ALTERATIONS SHALL BE MADE ONLY BY FBC - BUILDING, CHAPTER 1 REQ'D OPENING FIRE PROTECTION SYSTEM TO BE DESIGNED AND SUBMITTED UNDER A THE ARCHITECT OF RECORD. FIRE BARRIER ASSEMBLY PROTECTION SEPARATE PERMIT BY A LICENSED FIRE PROTECTION CONTRACTOR. ? MankmWe Ave � ~;pkkQ.,ea• 14. THE EXISTING FACILITY IS ACCOMMODATED WITH A FIRE SPRINKLER SYSTEM. ANY AND ALL (TABLE 115.4) FIRE WALL - 106.1 AND TABLE 106.4 N/A - Q p _ A HartLn BountyLA n 1 a INSTALLATIONS, CHANGES, ADDITIONS, RELOCATIONS, IMPROVEMENTS AND/OR MODIFICATIONS TO THE FIRE SPRINKLER SYSTEM NECESSITATED BY THE WORK IN THIS C3 WALL TYPES SHAFT / EXIT ENCLOSURES - 113.4 / 1018.1 LESS THAN 4 STORIES N/A - /�' PROJECT TEAM 25 o v PROJECT werte (h p a �'` SoT1I PERMIT SHALL BE DONE AS PER NFPA-13 2001 EDITION, BY A LICENSED FIRE SPRINKLER OCCUPANCY SEPARATION-101.3.9 / 508 N/A - CaDe Cod Ur CONTRACTOR WITH SEPARATE PERMIT AND PLANS. TENANT SEPARATION - 108.1 I HR - 3londq Med cat eMic„ MNw• wd l)a- Bentkvor ARCHITECT MECHANICAL 15. THE EXISTING FACILITY IS ACCOMMODATED WITH A FIRE ALARM SYSTEM, ANY AND ALL 2 EXIT PASSAGEWAY - 101.3.4 / 1023.3 N/A HORIZONTAL EXIT - 101.3.5 / 1025.1 N/A - 80smn Aw Market Square INSTALLATIONS, CHANGES, ADDITION, RELOCATIONS, IMPROVEMENTS AND/OR MODIFICATIONS TO THE FIRE ALARM SYSTEM SHALL BE DONE AS PER NFPA-�2 2001 KEY PLAN SINGLE OCCUPANCY FIRE AREA - 101.3.10 N/A - OLIVERI ARCHITECTS I.C. THOMASSON ASSOCIATES, INC. N aand'E o f EDITION, BY A LICENSED FIRE ALARM CONTRACTOR WITH SEPARATE PERMIT AND PLANS. SECTION SYMBOL CORRIDORS (OCCUPANT LOAD > 30) - 1015.1 (UNSPRINKLERED) N/A - 32101 U.S. HWY.19 5005 WEST LAUREL STREET, SUITE 205 cvsw.m« • C i 3 o Q a PALM HARBOR, FLORIDA 34684 TAMPA, FL 33601 ndewd EllandBNd Fil-dei•,d 16. ALL FIRE PROTECTION SYSTEMS SHALL REMAIN IN SERVICE DURING CONSTRUCTION AT ALL 121-181-1525 813-882-4415 wwg-. TIMES. 9 � •, r aa��.a1� 11�� - 1''I Tin UM151 ELECTRICAL Aaha Tan Pk.3IN .2 I.C. THOMA55ON.ASSOCIATES, INC. I.C. THOMASSON ASSOCIATES, INC. m L^ zeDMrA��Hph lelad 5005 WEST LAUREL STREET, SUITE 205 5005 WEST LAUREL STREET, SUITE 205 TAMPA, FL 33601 TAMPA, FL 33601 aarnlyntd ._ 813-882-4415 813-882-4415 ,. �n "try yW Newal Ave 1�y{`s g , S N REVISIONS BY ' Ncc Cn uJ L Lz. Or- ' N =xti ~ U 4 -�Ex C\1 Li. ./ N C CD• U C), 1-~ C)U N Q ;0- O 3 3 O N t` N O 4 N U W a 4 . "1 M ' . S O x � Q N O U_ (z Z 'O v, N J "I O L Ile) a 0 X �jLLi - Q N v •L U p O O 0 LLJ vi Lo t 0 00 -C a M aai OL. N 0_ 0 L- Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet T1 gal LIFE SAFETY LEGEND 9�—? FIRE EXTINGUISHER - IN CABINET FIB EXTINGUISHER - WALL MOUNTED ®� ® EXIT LIGHTS - SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFOF41ATION —� PRIMARY PATH OF TRAVEL. ---------� SECONDARY PATH OF TRAVEL. EXIT EXISTING CMU WALL ONE (1) HOUR FIRE RATED SEPARATION PARTITION MANUAL FIRE ALARM PULL STATION - SEE ELECTRICAL FOR MORE INFORMATION VISUAL SIGNALING DEVICE - SEE ELECTRICAL FOR MORE INFORMATION COMBINATION HORN / STROBE SIGNALING DEVICE - � SEE ELECTRICAL FOR MORE INFORMATION II COMBINATION SPEAKER / STROBE SIGNALING DEVICE -SEE ELECTRICAL FOR MORE INFORMATION ------------------------ r� He'-Im• ----------------------- - EXISTING FIRE EXTINGUISHER - IN CABINET — _ — — — — — — — — — — — Frl — — — — — — — — — — — — — — — E EXISTING FIRE EXTINGUISHER - WALL MOUNTED ®E ZE ®E �F EXISTING EXIT LIGHTS - SEE ELECTRICAL DRAWINGS > I FOR ADDITIONAL INFORMATION I i ��,,�� I ❑� EXISTING MANUAL FIRE ALARM PULL STATION - SEE E ELECTRICAL FOR MORE INFORMATION ! I EXISTING VISUAL SIGNALING DEVICE - SEE ELECTRICAL FOR MORE INFORMATION 1 I I ©E EXISTING NATION SIGNALING �FOR 1 I r------- • DEVICE -SEE ELECTRICAL MORE L_J — IE o EXISTING COMBINATION SPEAKER / STROBE SIGNALING DEVICE - SEE ELECTRICAL FOR MORE INFORMATION ET`------------------------- 20m'-2' -------------------- CNR4L NOTES 1. STENCIL - "1 HOUR FIRE / SMOKE WALL - PROTECT ALL OPENINGS" ABOVE THE FINISH CEILING OF ALL FIRE AND SMOKE PARTITIONS. 2. MAINTAIN INTEGRITY OF ALL EXISTING FIRE RATED WALLS DURING CONSTRUCTION LIFE 5 TY SUMMARY THE FLORIDA BUILDING CODE, FIFTH EDITION (2014) • BUILDING • PLUMBING 0 EXISTING BUILDING • MECHANICAL 0 ELECTRICAL • ACCESSIBILITY FLORIDA FIRE PREVENTION CODE FIFTH EDITION NFPA 101 LIFE SAFETY CODE FLORIDA EDITION NATIONAL ELECTRICAL CODE 2011 EDITION 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN C4"Tf%=10N I Yi°Es FBC - TYPE II-B CONSTRUCTION UNPROTECTED, FULLY SPRINKLERED �..�. p NFPA �.-. EXISTING BUSINESS 0=11PANCYs FBC - BUSINESS NFPA - NEW BUSINESS FIRE PRO CTIONs BUILDING IS FULLY SPRINKLERED KEY PLAN I I I = it I , I I a I I CD I F X I r -, ❑ I ❑ DI LIFES,4 = MAN SCALE: 3/32" ■ V-0" REVISIONS BY 'Lnw d" N into 4. `o ti o E u g Cu O u . ti Q rn , o �00 3 ti y 3 i- 3 o z ti C ti o o a N Cn W a p: 00 lg; . •�� 00 N O O a. V O U O N U m u7 v o M a M � w -o — Q N 'o °' o m L M Lj oLo 0o M m O N L. L. O J L.L. 03. 16 NOTED gr: AAY p S Job: 16-062 Sheet LS 1 GsENERAL NOTES KEYED NOTES (CONT.) KEYED NOTES (CONT.) KEYED NOTES WALL LEGEND KEY PLAN 1. CONTRACOR TO PATC44 AND REPAR ALL AFFECTED R12=1REDTTO MATCH AND ALIGN WITH EXISTING ADJACENT FINISHES. FINISHES AS RETAINED FORLRENSTALLEXISTING DUCTESS FUMEA ION SEE FLOOR PLAN. OD AND STAND TO BE MOVED AND ARD. PATCH AN t1 RREEPAIR EXISTING SLAMOVE EXISTING B RFORINNEW FINISHES. EEFI-044ES AND FIFINIvH SCHEDULED OI EXISTING SPACE - NO WORK THIS AREA EXISTING DOOR SYSTEM 2. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL. INFORMATION. 25 EXISTING WATER HEATER TO REMAIN 12 ALIGN NEW WALL WITH EXISTING WALL. O REMOVE EXISTING PARTITION WALL IN ITS ENTIRETY TO EXTENTS AS INDICATED DASHED. EXISTING WALL PARTITION AREA Or- 3. SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. 4. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION . 26 RECLINER CARELINER WITH ARMS - PROVIDED BY TENANT. 21 PROVIDE AUTO -CLOSER AT THIS DOOR O 13 PATCH AND REPAIR EXISTING WALL AS REQUIRED. FINISH TO MATCH EXISTING ADJACENT WALL. O REMOVE PORTION OF EXISTING PARTITION WALL AS INDICATED 1 DASHED TO ACCOMMODATE NEW V-6" x '-m" DOOR - — — — - EXISTING ONE (1) HOUR RATED SEPARATION PARTITION EXISTING EXTERIOR WALL SYSTEM WORK S. SEE SHEET A5 FOR FINISH SCHEDULES. "LYNX" 14 STAINLESS STEEL SINK - SEE PLUMBING DRAWINGS. O REMOVE EXISTING DOOR, HOLLOW METAL FRAME AND PORTION OF 6. GENERAL CONTRACTOR TO NOTIFY ARCHITECT UPON DISCOVERY OF ANY SPACE DISCREPANCIES PRIOR TO COMMENCING WITH ANY WORK. 28 RELOCATED MOBILE INVENTORY MANAGEMENT SYSTEM - O VERIFY LOCATION WITH TENANT. 15 BASE CABINET / COUNTERTOP - SEE INTERIOR ELEVATIONS. EXISTING PARTITION WALL AS INDICATED DASHED TO ACCOMMODATE NEW V-6" x "I'-m" DOOR RETAIN DOOR FOR REINSTALLATION PER OWNER'S DIRECTION. �__ CONTRACT��ODMA�IN�gIDURING CONSTRUCTION EXISTING 1. ELEMENTS AS REQUIRED. 29 RELOCATED DUCTLESS FUME HOOD AND STAND -VERIFY LOCATION 16 WALL MOUNTED UPPER CABINETS -SEE INTERIOR ELEVATIONS. 0REFRIGERATOR BY TENANT. O REMOVE EXISTING FIXED GLASS WINDOW SYSTEM IN ITS ENTIRETY. __� EXISTING DOOR SYSTEM TO BE REMOVED __________= EXISTING WALL PARTITION TO BE REMOVED 8. ALL INTERIOR WALLS ARE NOMINAL 4" METAL STUDS U.O S. PATCH AND REPAIR EXISTING CONCRETE SLAB AS REQUIRED AND PREPARE Q REMOVE EXISTING CONCRETE LINTEL ABOVE 31 NEW CONCRETE LINTEL. FILL CELLS ON EACH SIDE OF OPENING. SEE O 18 FIXED SHELVING MILLWORK -SEE DETAIL 11/A4 O REMOVE EXISTING STOREFRONT DOOR /WINDOW SYSTEM IN ITS ENTIRETY. 411 TyP , ; TO RECEIVE NEW FINISHES. DETAIL 3/A3b. 19 1� AS TO I HOUR FIRE O� REMOVEUPPERAND LOWER MILLWORK TO EXTENTS AS 1m. GENERAL CONTRACTOR TO ODORDINATE WITH BUILDING MANAGER ALL NEW LNG FINISH TTOPENING ADJACENT WALDLE MATCH EXISTINGREQUIRED INDICTEEXDASHE DOOR SYSTEM - REFER TO DOOR SCHEDULE PLUMBING AND ELECTRICAL WORK REQUIRED BELOW THE SLAB. 32 EXISTING VENDING MACHINES TO BE REMOVED AND RELOCATED O PER OWNERS DIRECTIONS. 2m INFILL EXISTING OPENING IN WAY OF REMOVED WINDOW SYSTEM. FINISH O 8 EXISTING PLUMBING FIXTURE t0 BE REMOVED -GAP OFF PIPES O - METAL STUD SOUND INSULATED PARTITION - REFER TO TYPICAL NON -RATED WALL PARTITION DETAIL 5/A2b. / 11. NEW GYPSUM WALLBOARD FINISH TO MATCH EXISTING FINISH. 12. GENERAL CONTRACTOR TO PROVIDE WOOD BLOCKING IN WALLS AS REQUIRED 33 NEW 1 HOUR FIRE RATED SEPARATION WALL. SEE DETAIL 4/A3B. TO MATCH EXISTING ADJACENT WALL. 21 NEW FLOOR FINISHES AND BASEBOARDS. PATCH AND REPAIR BELOW SLAB OR IN WALL AS REQUIRED - SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. ___ _ _ _ NEW ONE lU HOUR RATED SEPARATION WALL, SEE DETAIL 4/A3b. FOR NEW CABINETRY, ACCESSORIES, ETC. 34 NEW IS" x 36" WINDOW WITH CLEAR GLAZING WITH WOOD FRAME TO MATCH EXISTING HOLLOW METAL FRAME PROFILE. 1'-0" AFF WINDOW SLAB AS REQUIRED TO RECEIVE NEW FINISHES. SEE FINISH SCHEDULE. O EXISTING REFRIGERATOR TO BE REMOVED. VERIFY WITH OWNER FOR FINAL DISPOSITION. 13. ALL EXISTING GYPSUM WALLBOARD TO BE PATCHED AND REPAIRED AS REQUIRED TO LOOK LIKE NEW. PROVIDE 1/4" VENEER IF REQUIRED. HEAD TO ALIGN WITH CASED OPENING HEAD, SEE DETAIL B/A5. 22 UNDERCOUNTER REFRIGERATOR BY TENANT. Im REMOVE EXISTING SOLID CORE WOOD DOOR AND HOLLOW METAL 14. SEE DETAIL 6/A31v FOR CONCRETE SLAB SAW CUT / PATCH DETAIL. 35 WOOD CASE OPENING TO MATCH EXISTING HOLLOW METAL FRAME PROFILE. SEE DETAIL G/A5. 23 "LYNX" MOBILE INVENTORY MANAGEMENT SYSTEM TO BE REMOVED FRAME IN THEIR ENTIRETY AS INDICATED DASHED. STORE FOR RE -USE PER OWNER'S DIRECTIONS. AND RETAINED FOR REINSTALLATION - SEE FLOOR PLAN. EXISTING CORRIDOR EXISTING CORRIDOR EXISTING CORRIDRO19 21 EXISTING CORRIDOR �r---- II -- — — —— — --= t //,-1 I— — — — — — — 1 O ------- _--- --- /. I I I I�--------- ---- -1,1 i EXISTING 1 6----� — — — — — — — — — — EXISTING _ CLOSET — — ❑ - - _----- -�---------� -----� -- _-----� I I Z T I I T T I I T T I I T T I I Z T I I T---T I I Z-- T I I Z---T I I--- I I I I--- I I I I--- I I I I--- I I I I —__ , I I I--- I I I I--- I I I I I I I I I I I I I I I I I I I I V v I I I lu 11 11 `� — — — — — — — — — — — .^� o -- !.' `. . r — — EXISTING CLOSET ❑ \'t I 1 I `I 1 J _ _ lJ L� _ _ L� _ _ lJ L� _ _ l� L- _ _ lJ LJ _ _ l_� L� _ _ - _ �L - \ 8 1 OFFICE OFFICE m1 O 26 26 --- --7 ' I I 2 3 4 6 XAMEXISTING 115✓ O i� O L__J L__J L__ I L__J L__J L__J L__J L__J' I I `E O /�4 ----'I I 2 / 2 I 1----i1 1 /' I t I I I 1 1 IN USION o 14 , , 1 I EiC_ / a, --(D EXISTING I III------- ----- __-- BREAKROOM I 11 1 ' r------------� �/J, r------------------- I I i i Imt 26 CLOSET 21 15 I I it I6 19 114 21 O _ 22 Ili/ `/ I I II� �� I I I I I IO2 f_--7 1---7 I---7 12 I I I I I , Cr 1 2 11 I r — EXISTING 1 EXISTING EXISTING EXISTING I I ' I I TOILET TOILET $ 11 ' 1 OFFICE I I OFFICE 4 i' I tm 1 I 1 O I I I I I tm I 1 u L__J __LI I EXISTING EXISTING O L__J L__J LJ --� 26 31 TOILET TOILET 25 26 I I 16 3/A3a ' 15 I� 14 I 1 O 1 EXISTING 11 11 I I n 7-- I _ JAN. 'fc -A II I I I 1 1 0 'I / I ,� 1m I I I I I I I I 1 ' "" EXISTING t I INFUSION 11 I I I I - - - - - - I I 1 1 I I I I I I I I I I I I I I I I---1 I 11---i I 11---1 I 21 I I 1 S/A3a I I \/ 1 I - - ---� 10 14 i i 21 TOit i ` o I � 1 � � I 2 I i i ' i i i 2 3'-0"` ---'I �� I `^ I 11 i p o ---------------� 13 I I O I I 15 I 1 16 'o I� _J� _� I 1 �___—_—_--__—__--_ -_]--� I----------------------------------- I I II _ `,��� \\\\ 3 I I cn` 25 � ---J�--1 ;=-lie III —L___JI1I t5 -mi-6 m1 1 I1 10 �` I--L-- 1 -- -- cr--I -----� E \ A I I �_ 112 II11 21 1 O - i1 EXISTING EXISTING II 6 COMPUTER REPAIR 1 OFFICE I' II--- 1 ___ I 1 1 1OFFICE I -- -- -- -- L �04 ___J L 103 --- J 13 14 15 r 16 I I I I I -- -- 21 L__J L--J L_-J L 1 I 1� I 41 1 21 q 21 11 q i i O I 26 26 21- O�1 (II _T I I I 1, I I I 1 , I 21 1/A38 5'_qn 1 I I- 1 L 1I I ij I 11 34 35 I 12 CORRIDOR �/ I I I 5 8 1 1 ---- 1 —11 © 12 O © zm 21 .G I tm I — r — —J 1 O I II C1 I I Y1 LAD I 6u ; ,� ,Q I -- -- �+ I I I I 13 1 I ;EXISTING a I O ; 2t I 16 15 __ __U1 1 I EXISTING OFFICE EXISTING ROOM 11 I O i----- i 'MIXING ram— U = t 1 O 11 I l7 -- O 11 EXISTING 1 1 8 I TOILET 11 f— _ v O d I I X 24 1 I 23 I w ❑ I I I I EXISTING CONFERENCE ROOM 1 O I ( I 1 1 I _ I J I �14 1 22 I . i o� z9 I 0 N, I - - --------- 7 1 � tm9 1 __� TOILET G �T-- — ; O I -- IY 1 O l� Z� ❑ �� 0 O X W U c 1 Ld MEDS-- - I EXISTING EXISTING i i i i Ii I SERVER ROOM CORRIDOR i I-� I I ► 11 I EXISTING EXISTING SERVER ROOM CORRIDOR 105 I 21 18 I N 1 1 I 21 oo I oo I I 1 I O O i_____�______� I EXISTING RECEPTION 1 O I O O I EXISTING RECEPTION 1 0 1 EXISTING �0 CORRIDOR � O I EXISTING CORRIDOR I 1 O I 21 1 I O I; o 0 LJ 11 I O I o o L I zl I EXISTING OFFICE � V �--� I EXISTING OFFICE � a O 1 L-- uu O EXISTING OFFICE I 1 I O EXISTING OFFICE _ 1 EXISTING OFFICE O I I I EXISTING OFFICE O 1 I i _ 1 I I I EXISTING OFFICE O EXISTING WAITING I 0 I i I 1 1 1 EXISTING OFFICE 0 EXISTING WAITING O 0 x� �0 ILUO ' O x� 1 ----------------- --------------� -- —--------- U El----------- 1 U DU U \5d) I E] ME] Ulm o------� I �— 9 Nv I o —------� Iw -- — I I>< I I I I I I -0 I I I I I I 1 1 �V I I I I EXISTING 1 I w4 I I I I I EXISTING 1 i jq I I I CLEAN ; I I I I I I CLEAN 1 I I I ROOM ; I I I I I ROOM I � I I I I I I O 1 I I i I I I I I I I I I I I I 1 i t O 1 i I III 0 I II --- O O I I E (STING COVERII Y II -O El E�II CISTING GONE �II Y I �i �ii�i ❑ ORE iii OBE II O EXISTING , DEMOLITION PARTIAL FLOOR PLAN 0 PARTIAL FLOOR MAN SCALE: 3/16" ■ 1'-0" SCALE: 3/16" ■ I'-m" REVISIONS B JY N 0. 00 M� U M N uL. �—, - I_, `o -° E N co I—U ti vS Y E x v / N5a G-L U O • 00 co N d • [�` Q E 3 ti 3 w N O ��� ti O f- Cn 1 tx • \`� • �•�` ��. 00 ' N O O O n. 0 0 U � Z O N -J U (D Lr) D f7 I� a -M w Q N a 0) m 0 0 0 L. O N M i � Q N 0 00 .0 M m O N li OO Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet A 1 3 5/8" 25 GA. (MIN.) METAL 3 5/8" 25 GA. (MIN.) METAL STUD FRAMING AT 16" O.C. STUD FRAMING AT 16" O.G. - SECURE TO STRUCTURE - SECURE TO STRUCTURE ABOVE ABOVE Ah MATCH -�--�- --- - -- MATCH Ilk My EXISTING EXISTING SUSPENDED ACOUSTICAL SUSPENDED CEILING SYSTEM ACOUSTICAL CEILING SYSTEM (4) 010 TEK SCREWS AT EACH CONNECTION (TYP.) • • • 5/8" G.U1.B. 8'-0" AFF. BOTTOM G.W.B. OF SOFFIT L DAI CE IL INCH DETAIL SCALE: 1 1/2" - I'-0" GENERAL NOTES I. ALL NEW CEILING AND SOFFIT HEIGHTS SHALL MATCH EXISTING, UNLESS OTHERWISE NOTED. 2. ALL METAL FRAMING FOR GYPSUM WALLBOARD CEILING SHALL BE 25 GAUGE TYPICAL (UN.OJ. 3. METAL STUDS SHALL BE CONNECTED TO STRUCTURAL STEEL WITH (3) 0.145"0 RAMSET POWDER DRIVEN FASTENERS. 4. METAL STUDS/CLIP ANGLE SHALL BE CONNECTED TO METAL STUDS WITH MIN (4) 012-14 TEK SCREWS. 5. CONTINUOUS TRACK SHALL BE CONNECTED TO STRUCTURAL STEEL WITH (2) 0,145"0 RAMSET POWDER DRIVEN FASTENERS AT 16" O.G. 6. CONTINUOUS TRACK/STUDS/CLIP ANGLES SHALL BE CONNECTED TO CONCJCMU WITH (2) 1/44 X 1 I/4" TAPCON FASTENERS AT 24" O.C. 1. CONNECT SHEATHING TO METAL STUDS WITH 012-14 TEK SCREWS AT 6" O.C. 8. AS REQUIRED, THE CONTRACTOR SHALL PROVIDE CLIP ANGLES FOR ALL METAL STUDS SO PROPER ALIGNMENT CAN BE ATTAINED. CLIP ANGLES SHALL MATCH OR EXCEED THE STUD GAGE. S. CONTRACTOR TO COORDINATE CEILING HEIGHTS WITH HVAC PROPOSED WORK AND EXISTING STRUCTURE HEIGHT. NOTIFY ARCHITECT WITH ANY DISCREPANCIES UPON DISCOVERY. KEYED NOTES 0 EXISTING SUSPENDED ACOUSTICAL TILE CEILING SYSTEM. NO WORK THIS AREA. 20 EXISTING SUSPENDED ACOUSTICAL TILE CEILING SYSTEM TO BE REMOVED TO EXTENTS AS INDICATED DASHED. 30 EXISTING GYPSUM BOARD HEADER t0 BE REMOVED TO EXTENTS AS INDICATE DASHED. OWALL MOUNTED TELEVISION - SEE ELECTRICAL DRAWINGS. (D EXISTING 2' x 4' FLUORESCENT LIGHT FIXTURE TO BE REMOVED AND RETAINED FOR REINSTALLATION. CLEAN AND RELAMP AS REQUIRED PRIOR TO REINSTALLATION. O6 EXISTING MECHANICAL SUPPLY AIR DIFFUSER TO BE REMOVED AND RETAINED FOR REINSTALLATION. CLEAN AS REQUIRED PRIOR TO REINSTALLATION. 0 EXISTING MECHANICAL RETURN REGISTER TO BE REMOVED AND RETAINED FOR REINSTALLATION. CLEAN AS REQUIRED PRIOR TO REINSTALLATION. 0 EXISTING GYPSUM WALLBOARD WRAPPED HEADER 0 GYPSUM WALLBOARD SOFFIT - SEE CEILING DETAILS. 10 LINE OF NEW CEILING SYSTEM TO MATCH AND ALIGN WITH EXISTING CEILING SYSTEM. II OUTLINE OF NEW WALL MOUNTED UPPER CABINETS. 12 PATCH AND REPAIR EXISTING CEILING SYSTEM AS REQUIRED TO MATCH AND ALIGN WITH EXISTING 13 EXITING CAN LIGHT FIXTURE TO BE REMOVED. XISTING CORRI OR 8 EXISTING rl RIDOR 0 O --- --- -------T--- --- --- --- ------rt---- _I I I I I I I I I I I I I I I I EFIr-E-��EXTING i i ii i IOC 110ACE I 1 1 11 1 1I 1 All I I ie-I6 I I 4II --- 4II ---ZIIirII =4I1I1 ---II II 1I1I IIII II II II11I 11I �IJ I I11 II II II IIII10I1I1 I1I1 2 1I1I O0I1 011 0 1I I I I I II I I II II IIlI OlIlI II II IIlI IlIIlI III III II1II1 OII1II1 IIII -1I1`I1L ==�1I�1l1 -i ,---�I =II 1 1LI JI ILI _pII == JlI1LI1 IIII ==1 11 ---L I L I I II II I I II II I I II II I I I K--r I I I I I I I I I I I I I I IL__JI I I IL__JI I I IL__JI I I 11 �' I I I I I I I I I I I I ---�---�---�---�-----�---�---�---rt----t----1 I I ir?'�y I I I I I I I I I I I I I 1 I 1 EX�ST Irq& 1 1 1 1 1 1 1 F___a r__1___1___1___1____LJ L_L___L___L___L___ L_ r-r---r---r---r---r- I 1 I I I I I 1 I I I I I I I I I� I I 1 I 6 1 11 I 16 I I -L_J L-L--- L------L___L_ Ir- r R EXISTING 6EFIVER RO M 0 ®0® I I I I ---r---r--� I I I I I 1 I I I II 11 I I I I 11l y III I I I I I I 11 I I i III II II II I I I II II1 �-•� I II II I I II II II 5 II I I I II 5 IL'� ==yJ1 s� II I I II 5 II 2 L'L—_"JI 5 II II II I I I II II II II I I II II I II II ISTI I I I I I I I I II III I I II II O II II I I II II I II II II I I 11 11 II 11 1 1 II II I II II A ITO II -iL== J11 I I I I I I I I I III I IEXI$TIN(� I I I I IEXI$TIN(� 1 O ---r ---r ---1 I I III I ICFICE I I I I I :OFFICE I I I a I I I I II I III I I I I I I I I I I I I I I II I III I I I I I I I I I I I I r �r_-^(---T---T---T---T---T---T---T---T---T---T- I 1 -T---T --- T- I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I E�kISTI�ICx I I I I I I I I C6MPWTER RE0AIRII I I I I I I Tr==�T-------�---- 11 I-r==�I---- I---- r==� --- --- ---.---+----I----+ II 11 II I I II II I IL II II I fR--r�1011 I II II I II II I II II I II II I II II I :101i LJI101 I ::Q: O I k 110, :l I Il 011 I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 0 EXIST IS VO INCsNE NCE RO M FH+HrO, rO` EiLi 0 ® "o" X EXISTING OFF ICE m 0 70m EXIST 1�� O EXISTIN CLEAN FOC 02 E> ISTI Cx I IM--1---1---1---1--- 1 C OS T -T---T --1-Ir---iI Ir---iI Ir--��---T--- n II u n u n I II II 11 11 II 11 1 0 II O II M O IL --- Jl OII 0❑ of N a Z� +_ N II n u my-�1u n I II II II III � I II II I I I 1 6 I 1 I 1 I I I I I I I 1 I I I I I I I I I I I I 13 I 11II 11 I IL _ 1 1-3IEXI ON `�i -- 11 11 �� i 11 5 01 1 I I I I l r _ie y I 1 IL__J I 13 1 6 I 13 1 I I I I I I 2 I I I I I I I I I I 13 I II II I I I I I I II II I I I II II I I I I I I II 5 II I I I I I I II II I I I I II II I I 1 1313 I I I �I -,I I II II II II I I I I 1 II 5 II I I I I 1 II II I I I I I II II I I I I I I 1 I I I I I I I I Effl-MEN Em EXISTING EC PTI N 8 0 Well EXIST tbL4ITIIs 0 V/ W 0 mI Iml 0❑ i ❑o REFLECTED CE IL INCH LEGEND (CONT.) EXISTING 2' x 4' FLUORESCENT LIGHT FIXTURE TO 11 II BE REMOVED AND RETAINED FOR REINSTALLATION - SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION EXISTING MECHANICAL SUPPLY REGISTER - SEE IMT MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION EXISTING MECHANICAL RETURN REGISTER - SEE FZ1 MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION r—_—_—� EXISTING MECHANICAL SUPPLY REGISTER TO BE 11 Yj 11 REMOVED AND RETAINED FOR REINSTALLATION - j SEE MECHANICAL DRAWINGS FOR ADDITIONAL `---J INFORMATION r—_—_—� EXISTING MECHANICAL RETURN REGISTER TO BE I I REMOVED AND RETAINED FOR REINSTALLATION - j SEE MECHANICAL DRAWINGS FOR ADDITIONAL `---� INFORMATION. RELOCATED MECHANICAL SUPPLY REGISTER - SEE ® MECHANICAL DRAWINGS FOR MORE INFORMATION RELOCATED MECHANICAL RETURN REGISTER - SEE MECHANICAL DRAWINGS FOR MORE INFORMATION EXISTING FIRE SPRINKLER HEAD ® ® ® EXISTING EXIT LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION ELECTED CE IL INCH LEGEND EXISTING 2' x 2' SUSPENDED CEILING GRID SYSTEM WITH 2' x 2' LAY -IN ACOUSTICAL CEILING TILES EXISTING 2' x 4' SUSPENDED CEILING GRID SYSTEM WITH 2' x 4' LAY -IN ACOUSTICAL CEILING TILES NEW 2' x 4' SUSPENDED CEILING GRID SYSTEM WITH 2' x 4' LAY -IN ACOUSTICAL CEILING TILES. PATCH, REPAIR AND MATCH EXISTING GRID SYSTEM CONFIGURATION WHERE NECESSARY. EXISTING GYPSUM BOARD SOFFIT / HEADER NEW GYPSUM BOARD SOFFIT / HEADER ��� EXISTING RECESSED CAN DOWN LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION EXISTING 2' x 2' FLUORESCENT LIGHT FIXTURE - SEE a ELECTRICAL DRAWINGS FOR MORE INFORMATION EXISTING x 4' FLUORESCENT LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION KEY PLAN lollSO =�—�mmmmm 101 Ell 13 M64 mm mm Him Him ME on INS ommmmmmmmmmENE I m Ulm goEm IN MM MM MM MM EmmWAM91MMMEEMEMEMEMEMEN IN immem FEE 11�m 1111111 MISS IN M HE MM MM ME ml MEMO o •inmug mmommoranomm"Im9mium IMMMIMIMNIMMMMII ore IN NINE== ERNE I= Em 9111" 0 Z 111111P7 C! m No loonMe i i N i -. 0 0 Will EMO .00 -welpffim � ■ mmmmm MEN OMMOM MO1MMMMoNO ME � o � 9111 1 — o 0 0 i M No 10010 M M smo MMOMM imommo 010111 mumu ZOOM; INNE 511111111101 ME 010110 1 OMMOM 0, - na. MIN ME loom" mm ME mom IN B • MEMEN2ding -Vigil 1MM MICS211011 IN ME MM N EM NIM • o MMM MOME Em NOMINEE! 10110 0 � o 0 oMENJENNE (DIEXISTING / DEMOLITION PARTIAL LECTE0 CEILING PLAN O PARTIAL FREFLECTED CEILING* PLAN SCALE: 3/16" ■ I'-0" SCALE: 3/16" ■ I'-0" REVISIONS EIY �i r u r 0 ►—• CO L CO o 0 a Z ti u • U . p 1�� b (. U N (I O it ¢E� °O 3 3 N o • 0 N 1 � W a • lJ •s I h� L. tsO N � � Q a. a� ® C U � Z_ O N ') J '. Lr) a 0 M X :3 LLJ o o Q 0W � Q M 1E V) 00 t O 0 N �0 Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet A2 6 (01 CORRI1�O R SCALE: 3/8" ■ 1'-0" 1@1 EXIST,INCx„ C MRIDO1R RM Ill E d 101 NU"ES RM �116 SCALE: 3/8" ■ 1'-0" "M1 KEYED NOTES 0 BASEBOARD - SEE FINISH SCHEDULE O2 OPEN SPACE / KNEE SPACE BELOW COUNTER OOPEN BEYOND OKEYBOARD DRAWER OREFRIGERATOR BY TENANT OUNDERCOUNTER REFRIGERATOR BY TENANT OSTAINLESS STEEL SINK - SEE PLUMBING DRAWINGS OLAMINATED END PANEL OLAMINATED BACKSPLASH 10 LAMINATED COUNTER TOP II SOLID SURFACE COUNTER TOP - SEE CABINET DETAILS AND FINISH SCHEDULE. 12 GYPSUM WALLBOARD WRAPPED HEADER / SOFFIT - SEE REFLECTED CEILING PLAN. 13 LAMINATED SUPPORT LEG. 14 FALSE LAMINATED PANEL. 15 3/4" WIDE x 3/4" DEEP REVEAL - SEE DETAIL -I/A3b. 16 "LYNX" MOBILE CABINET PACKAGE BY TENANT. rl 40 INCH WIDE DUCTLESS FUME HOOD BY TENANT. 18 DOOR SYSTEM - SEE FLOOR PLAN AND DOOR SCHEDULE. RM 0112 C-AN iUL NOTES I. SEE REFLECTED CEILING PLAN FOR ALL CEILING HEIGHTS AND DECORATIVE CEILING DIMENSIONS AND DETAILS. 2. SUBMIT SHOP DRAWINGS TO ARCHITECT PRIOR TO FABRICATION OF CABINETRY FOR APPROVAL. 3. SEE SHEET A4 FOR CABINET DETAILS. 4. SEE SHEET A5 FOR FINISH SCHEDULES AND MATERIALS. lei NUftES =>C4M 101 ! RMmIr101 i -0" RM M12 L1ALE` 3/S = -0" A ID RM 1101 I 1G)l1""10N SCALE: 3/8" ■ I'-0" G)l INMSION RMil101 SCALE: 3/8" ■ 1'-O" O NURSES RM 101 SCALE: 3/8" I'-0" O NURSES RM h07 SCALE: 3/8" ■ I'-0" RM moll REVISIONS BY ' o ~—' N N " M cp 4 U. �r O E Y x ti u N � ro cXd r+ 0 o V N Q 0 o °O 3 3 ti 3 o = ti a c ti o M W a LL, 0. f > N O Z = o .� QCD �] d C1 O O ..7 U_ � Z O N _I d U (D u-) 0 a o M w Q N v 0 Q 0 U LJJ >D 0 '^ •— M Q N 0 00 -C O M a 0 N L. 0 J L.- Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet A3a �9 H 5 SEE FLOOR PLAN J(DIL O L O OPENINCx IN EXISTINCs CM UJ�41..L SCALE: 3/8" I'-0" RM 106 SCALE: 3/8" I'-0" RM "906 SCALE: NONE EXISTING BI TO REMAIN INTERIOR NEW 4" x 3' STEEL ANGI EXPANSION AT I6" OTC. EXISTTNG BLOCK WALL TO BE REMOVED EXTERIOR EXISTING CONCRETE SLAB --\ PROVIDE A MIN. /\ a VAPOR BARRIER \j EQUIVALENT TO STEGOWRAP BELOW NEW CONCRETE - TAPE \\ NEW VAPOR BARRIER TO EXISTING. PROVIDE CLEAN COMPACTED TERMITE TREATED FILL AS REQUIRED NEW (2) 4" X 3 1/2" X 1/4" STEEL ANGLE WITH 3/8" THRU BOLTS AT 16" O.G. EXISTING BLOCK WALL TO REMAIN REMOVE EXISTING CONC. BLOCK SEE FLOOR PLAN AND WINDOW SCHEDULE. SAWCUT CONCRETE SLAB MIN. 1 1/2" DEEP AND BREAK OUT EXISTING CONCRETE 3000 PSI CONCRETE INFILL CEMENT STABILIZED SAND NEW PLUMBING PIPING OR CONDUIT AS REQUIRED DECK EXTEND WALL TO UNDERSIDE OF ROOF DECK PER U.L. DESIGN U.465 STEEL CHANNEL "I HOUR FIRE WALL - DO NOT PENETRATE" SIGNS WITH FOUR (4) INCH LETTERING, SHALL BE PLACED EVERY TEN (10) FEET MAXIMUM ABOVE CEILING LEVEL ON BOTH SIDES OF WALL. SIGNS MAY BE STICK ON SIGNS IN CONTRASTING COLORS OR STENCILED PAINT ON WALLS. FIRE BLOCKING AS PER IBC 111 LAY -IN ACOUSTICAL OR GYPSUM BOARD CEILING. 5/8" x 48" WIDE TYPE "X" GYPSUM WALLBOARD APPLIED HORIZONTALLY OR VERTICALLY, CORNER JOINTS OVER STUDS, STAGGER 16" O.G. OPPOSITE SIDES. ATTACH TO STUDS AND RUNNERS WITH I" LONG TYPE "S" SCREWS AT THE JOINTS 4 RUNNER CHANNELS 1/2" TO 3/4" FROM EDGES OF GNU$. SCREWS SHALL BE SPACED 8" O.G. ALONG EDGES OF BOARD AND 12" O.G. IN THE FIELD, COVER JOINTS WITH TAPE AND JOINT COMPOUND PER GA - WP - 1200. INCREASE METAL STUD THICKNESS AS REQUIRED FOR PLUMBING AND ELECTRICAL. FIRE BLOCKING AS PER IBC 111 I SEE UL DESIGN NO. U465 I R-11 BLANKET INSULATION AT SOUND PROOF PARTITIONS ONLY. 8" GALVANIZED METAL STUDS (SEE FLOOR PLAN) AT 16" O.C, 20 GA. STUDS AT WALL MOUNTED EQUIPMENT 25 GA. GALV. STEEL CHANNEL FASTEN TO SLAB AT 24" O.G. FLOOR SLAB 104 1 TYP�C,4L FIRE RATED 10AWITION 101 LINTEL■ 1DETAIL J(DI 11 gAALE:1 ICUT ,/ SLA5 PATC 4 DETAIL I It REVEAL DETAIL SCALE: 3" ■ I'-0" WOOD VENEER PANEL OVER 3/4" PLYWOOD BLACK LAMINATE AT REVEAL LOCATIONS TYP. 3/4" PLYWOOD Design No. U465 September 27, 2005 Nonbearing Wall Rating - 1 HR n } 1. Floor and Ceiling Runners - (not shown) - Channel shaped runners, 3-5/8 in. wide (min), 1-1/4 in. legs, formed from min No. 25 MSG galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max. 2. Steel Studs - Channel shaped, 3-5/8 in. wide (min), 1-1/4 in. legs, 3/8 in. folded back returns, formed from min No. 25 MSG galv steel spaced 24 in. OC max. 3. Batts and Blankets* - (Optional) - Mineral wool or glass fiber batts partially or completely filling stud cavity. See Batts and Blankets (BZJZ) category for names of Classified companies. 3A. Fiber, Sprayed* - As an alternate to Batts and Blankets (Item 3) - Spray applied cellulose material. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. Nominal dry density of 3.0 lb/ft3. Alternate application method: The fiber is applied with U.S. Greenfiber LLC Type AD100 hot melt adhesive at a nominal ratio of one part adhesive to 6.6 parts fiber to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. Nominal dry density of 2.5 IWO. U S GREENFIBER L L C - Cocoon2 Stabilized or Cocoon-FRM (Fire Rated Material) 3B. Fiber, Sprayed* - As an alternate to Batts and Blankets (Item 3) and Item 3A - Spray applied cellulose insulation material. The fiber is applied with water to interior surfaces in accordance with the application instructions supplied with the product. Applied to completely fill the enclosed cavity. Minimum dry density of 4.3 pounds per cubic ft. NU -WOOL CO INC - Cellulose Insulation 4. Gypsum Board* - 5/8 in. thick, 4 ft wide, attached to steel studs and floor and ceiling track with 1 in. long, Type S steel screws spaced 8 in. OC. along edges of board and 12 in. OC in the field of the board. Joints oriented vertically and staggered on opposite sides of the assembly. When attached to item 6 (resilient channels) or 6A (furring channels), wallboard is screw attached to furring channels with 1 in. long, Type S steel screws spaced 12 in. OC. AMERICAN GYPSUM CO - Types AG-C, AGX-I BEIJING NEW BUILDING MATERIALS PUBLIC LTD CO - Type DBX-1. BPB AMERICA INC - Types 1, EGRG, ProRoc Type X, ProRoc Type C. BPB CANADA INC - ProRoc Type C, ProRoc Type X or ProRoc Type Abuse -Resistant. CANADIAN GYPSUM COMPANY - Types AR, C, IP-AR, IP-X1, IP-X2, IPC-AR SCX, SHX, WRC or WRX. G-P GYPSUM CORP, SUB OF GEORGIA-PACIFIC CORP - Types 5, 9, C, DAP, DD, DA, DGG, DS, GPFS6. LAFARGE NORTH AMERICA INC - Types LGFC2, LGFC2A, LGFC6, LGFC6A, LGFC-C, LGFC-C/A. NXTTONAL GYP9W CO - Types FSK,_F$K-C, FSK-G, FSW-C, FSW-G, FSW, FSW-3 , FSW-5. PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM - Type PG-C or PG-9 . PANEL REY S A - Type PRX. SIAM GYPSUM INDUSTRY (SARABURI) CO LTD - Type EX-1 STANDARD GYPSUM L L C - Types FRX-6, VPBX-6, FRWRX-6, SHTGX-6, FRX-6 Exterior Gypsum Soffit Board, SG-C. TEMPLE -INLAND FOREST PRODUCTS CORP - Type X, Veneer Plaster Base - Type X, Water Rated - Type X, Sheathing - Type X, Soffit - Type X, TG-C. UNITED STATES GYPSUM CO - Type AR, C, FRX-G, IP-AR, IP-XI, IP-X2, IPC-AR, SCX, SHX, WRC or WRX. USG MEXICO S A DE C V - Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC or WRX. 4A. Gypsum Board* - (As alternate to Item 4) - Nom 5/8 in. thick gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Horizontal edge joints and horizontal buttjoints on opposite sides of studs need not be staggered or backed. Panels attached to steel studs and floor runner with 1 in. long Type S steel screws spaced 8 in. OC when applied horizontally, or 8 in. OC along vertical and bottom edges and 12 in. OC in the field when panels are applied vertically. CANADIAN GYPSUM COMPANY - Types AR, C, IP-AR, IP-XI, IP-X2, IPC-AR, SCX, SHX, WRC or WRX. UNITED STATES GYPSUM CO - T ype AR, C, FRX-G, IP-AR, IP-Xl, IP-X2, IPC-AR, SCX, SHX, WRC or WRX. USG MEXICO S A DE C V - Type AR, C, IP-AR, IP-Xl, IP-X2, IPC-AR, SCX, SHX, WRC or WRX. 4B. Gypsum Board* - (As an alternate to Items 4 or 4A) - Nom 3/4 in. thick, 4 ft wide, installed as described in Item 4A with screw length increased to 1-1/4 in. CANADIAN GYPSUM COMPANY - Types AR, IP-AR. UNITED STATES GYPSUM CO - Types AR, IP-AR. USG MEXICO S A DE C V - Types AR, IP-AR. 5. Joint Tape and Compound - Vinyl, dry or premixed joint compound, applied in two coats to joints and screw heads; paper tape, 2 in. wide, embedded in first layer of compound over all joints. As an alternate, nominal 3/32 in. thick gypsum veneer plaster may be applied to the entire surface of Classified veneer baseboard. Joints reinforced. 6. Resilient Channel - (Optional -Not Shown) - 25 MSG galv steel resilient channels spaced vertically max 24 in. OC, flange portion attached to each intersecting stud with 1/2 in. long type S- 12 panhead steel screws. 6A. Steel Framing Members (Not Shown)* - As an alternate to Item 3, furring channels and resilient sound isolation clip as described below: a. Furring Channels - Formed of No. 25 MSG gals steel. 2-3/8 in. wide by 7/8 in. deep, spaced 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Ends of adjoining channels are overlapped 6 in. and tied together with double strand of No. 18 SWG gals steel wire near each end of overlap. As an alternate, ends of adjoining channels may be overlapped 6 in. and secured together with two self -tapping #6 framing screws, min. 7/16 in. long at the midpoint of the overlap, with one screw on each flange of the channel. b. Steel Framing Members* - Used to attach furring channels (Item a) to studs (Item 1). Clips spaced 48 in. OC., and secured to studs with 1-5/8 in. wafer or hex head Type S steel screw through the center grommet. Furring channels are friction fitted into clips. PAC INTERNATIONAL INC - Type RSIC-1. *Bearing the UL Classification Mark UL DESIGN NO. U465 SCALE: N T.S. KEYED NOTES OBASEBOARD - SEE FINISH SCHEDULE OOPEN SPACE / KNEE SPACE BELOW COUNTER OOPEN BEYOND OKEYBOARD DRAWER OREFRIGERATOR BY TENANT OUNDERCOUNTER REFRIGERATOR BY TENANT OSTAINLESS STEEL SINK - SEE PLUMBING DRAWINGS OLAMINATED END PANEL OLAMINATED BACKSPLASH 10 LAMINATED COUNTER TOP 11 SOLID SURFACE COUNTER TOP - SEE CABINET DETAILS AND FINISH SCHEDULE. 12 GYPSUM WALLBOARD WRAPPED HEADER / SOFFIT - SEE REFLECTED CEILING PLAN. 13 LAMINATED SUPPORT LEG. 14 FALSE LAMINATED PANEL. 15 3/4" WIDE x 3/4" DEEP REVEAL - SEE DETAIL 1/A3b. I6 "LYNX" MOBILE CABINET PACKAGE BY TENANT. 11 40 INCH WIDE DUCTLESS FUME HOOD BY TENANT. 18 DOOR SYSTEM - SEE FLOOR PLAN AND DOOR SCHEDULE. G PEW- EFRAL NOTES I. SEE REFLECTED CEILING PLAN FOR ALL CEILING HEIGHTS AND DECORATIVE CEILING DIMENSIONS AND DETAILS. 2. SUBMIT SHOP DRAWINGS TO ARCHITECT PRIOR TO FABRICATION OF CABINETRY FOR APPROVAL. 3. SEE SHEET A4 FOR CABINET DETAILS. 4. SEE SHEET A5 FOR FINISH SCHEDULES AND MATERIALS. REVISIONS BY i .—.. co ram. ►� ¢ ;0, O ti t- 0 N U ' E x y N o 2 0o u N ro ti > 0 Cn ti o ti co I W a ii oo 6v I cv y 0 co o v� O � � Q C1. C U_ � Z O (V U W Ln D L. o N) 0-- w Q cn v -� O O Q O L � a LLB 0 y Lo Q M L °° o. 0 a — m O N L. J LL Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet A3b d a d e N 0 0 0 0 10 0 0 0 0 0 0 0 0 0 6 0 0 o 0 0 0 101 C IN T 1� T,41L 101 C INET DETAIL 101 CABINET DETAIL 101 CA5INET DETAIL SCALE. 1-1/2" • 1'-0" SCALE: 1-1/2" = I'-0" SCALE: 1-1/2" ■ 1'-0" SCALE: 1-1/2" ■ I'-0" 2'-1" m 4 N v wi IG)lCABINET DETAIL J(DI CADINET DETAIL 1C)l CAZIN T DETAIL I SCALE: 1-1/2" = V-0" 1' SCALE: 1-1/2" = -0" SCALE: 1-1/2" : I'-0" ®■ An i'-4° KEYED NOTES 0 3/4" PLYWOOD WITH PLASTIC LAMINATE SURFACE - SEE FINISH SCHEDULE FOR MORE INFORMATION O1/2" SOLID SURFACE MATERIAL WITH FULL 1-1/2" BULLNOSE - SEE FINISH SCHEDULE FOR MORE INFORMATION O3/4" x 4" PLYWOOD c O 4" HIGH BACKSPLASH. FINISH TO MATCH COUNTERTOP FINISH - SEE FINISH SCHEDULE FOR MORE INFORMATION 5O 5/8" MELAMINE WITH PLASTIC LAMINATE SURFACE - SEE FINISH SCHEDULE FOR MORE INFORMATION 6O 5/8" THICK MELAMINE INTERIORS (BOXES) O1/2" THICK MELAMINE DRAWER STOCK z_ SO 5/8(THICK MELAMINE DRAWER STOCK 4 Q O9 5/8" THICK ADJUSTABLE MELAMINE SHELVES U Lu 10 LINE BORING FOR ADJUSTABLE SHELVES z w 11 3/4" PLYWOOD SUPPORT LEG WITH PLASTIC LAMINATE SURFACE AT i LOCATIONS INDICATED ON INTERIOR ELEVATIONS 12 5/6" MELAMINE FIXED SHELVING - SHELVING DEPTH SHALL BE AS SHOWN UNLESS NOTED OTHERWISE ON FLOOR PLAN 13 "ZARCsON" 6036 / 6026 SLIDE SYSTEM (OR EQUAL) 14 KEYBOARD DRAWER SYSTEM - SEE SPECIFICATIONS 15 3/4" BLACK REVEAL 16 "GRASS" FILE RAILING SYSTEM (OR EQUAL) 17 5/6" x 4" MELAMINE IS STAINLESS STEEL SINK - SEE PLUMBING 19 2x BLOCKING AS REQUIRED 20 3/4" x 4" OR 3" PLYWOOD BASE GENERAL NOTES 1. ALL INTERIOR MELAMINE SURFACE TO BE WHITE U.N.O. 2. GROMMET LOCATIONS NOT SHOWN ON CABINET DETAILS - REFER TO GROMMET DETAIL BELOW FOR TYPICAL REQUIREMENTS 3. REFER TO COUNTER PLAN BELOW FOR TYPICAL COUNTER LAYOUT NOTE: FIELD CUT CABLE HOLES IN CABINETS AFTER EQUIPMENT HAS BEEN PLACED IN DESIRED LOCATION BY OFFICE STAFF 3" O.D. GROMMET WITH I RETRACTABLE, SELF STORING SLOT COVER 3" O rMICAL C ET DETAIL SCALE: N.T.S. 101 ECA51NET DETAIL O CAMINET DETAIL O C,5INET DETAIL �� CA51WT DETAIL O rrPICAL COUNTER PLANALE: 1-1/2" ■ I'-0" SCALE: 1-1/2" ■ I'-0" SCALE: 1-1/2" ■ I'-0" SCALE: 1-1/2" ■ I'-0" SCALE: N.T.S. REVISIONS BY V o ch M Q� 00 ~~ a0Uo y ti _ E U tXd .U.� o u O U N ¢. Q � ti o 3 N O ti ti o ti 0. N co a 0.ov ! rY c-; �.• i� finr S N C> z po CD - n. a� o ° U c Z O N 'v, _ J C U m � v L- M a _ J_r� w Q to D '�- rn m o — o 0 LLJ O rn u-) •_ � Q M � O Q ()0 a _ CL N J LL. Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet A 4 5/8" GYPSUM WOOD WALLBOARD DOOR 2 x 4 WOOD BUCK XMD INSULATION METAL STUDS ETAL STUDS At IAt 16" O.C. ------- --Irv"A .C. SEE WALLTYPES. GYPSUM 4LLBOARD BUCK rJ,iJAMBL 1 ANCHOR WOOD TRIM 1/4" CLEAR TEMPERED GLASS �)I INTERIOR WINDOW WEADIMS SCALE: 3" - 1'-0" METAL STUDS AT O.G. SEE WALLTY' 1/2" GYPSUM WALLBOARD 2x BUCK WOOD TRIM �OI UJOOD 1C,4"D OPENINCX I FINISH FLOOR MAN SCALE: 3/16" - 1'-0" 7A)I DOOR HEADIJ SCALE. 3" ■ I'-0" SEALANT HOLLOW METAL DOORFRAME DOOR 4 FRAME TYPE A SOLID CORE WOOD DOOR IN HOLLOW METAL FRAME IN INTERIOR METAL STUD WALL EXISTING REr—OVERY DOOR GENERUL NOTES 1. ALL DOORS/DOOR OPENINGS SHALL COMPLY WITH FLORIDA FIRE PREVENTION CODE 2004 EDITION / NFPA 101 LIFE SAFETY CODE 12.12 WIDTH 12.1.4 SWING AND FORCE TO OPEN 12.1b LOCKS AND LATCHES AND ALARM DEVICES 12.1.E SPECIAL LOCKING ARRANGEMENTS 12.1.1 PANIC HARDWARE AND FIRE EXIT DEVICES 12.1.8 SELF CLOSING DEVICES 2. ALL DOOR HANDLES SHALL BE LEVER TYPE MEETING A.D.A. REQUIREMENTS. 3. ALL INTI=RIOR DOOR HANDLES SHALL MATCH EXISTING. 4. ALL DOORS WITH AUTO CLOSERS SHALL HAVE BALL BEARING TYPE HINGES 5. ALL NEW INTERIOR DOORS SHALL MATCH EXISTING. 6. DOOR CLOSER SHALL BE INSTALLED SUCH THAT THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 10% THE DOOR WILL TAKE AT LEAST 3 SECONDS TO MOVE TO A POINT 3 INCHES (16MM) FROM THE LATCH, MEASURED TO THE LEADING EDGE OF THE DOOR. 1. THE MAXIMUM FORCE FOR PUSHING OR PULLING AN INTERIOR DOOR SHALL BE 51bf (222N). S. PROVIDE EITHER WALL OR FLOOR STOPS FOR ALL DOORS AS REQUIRED. S. SUBMIT HARDWARE SCHEDULE AND REVIEW WITH ARCHITECT PRIOR TO PLACING ORDER (3 COPIES) 10. PATCH, REPAIR AND REFINISH ALL EXISTING DOORS AS REQUIRED TO LOOK LIKE NEW. DOOR ,410 WARD"RE SCHEDULE EXISTING DOOR SYSTEM. PATCH, REPAIR AND REFINISH AS REQUIRED. VERIFY WORKING CONDITION OF EXISTING HARDWARE, REPLACE IF NEEDED. ROOM NO. 101 ® 3'-0" x 71'-0" x 1-3/4", SOLID CORE WOOD DOOR AND HOLLOW METAL FRAME TO MATCH EXISTING WITH PASSAGE LOCK SET. SEE DETAIL A/A5. 102 103 © 3'-6" x 1'-0" x 1-3/4" SOLID CORE WOOD DOOR AND HOLLOW METAL FRAME TO MATCH EXISTING WITH OFFICE LOCK SET. SEE DETAIL A/A5. 104 105 © V-6" x 1'-0" x 1-3/411, 45 MINUTE RATED SOLID CORE WOOD DOOR AND HOLLOW METAL FRAME TO MATCH EXISTING WITH OFFICE LOCK SET. SEE DETAIL A/A5. 106 107 3'-0" x 1'-0" x 1-3/4" SOLID CORE WOOD DOOR AND HOLLOW METAL FRAME TO MATCH EXISTING WITH STOREROOM LOCK SET. SEE DETAIL A/A5. 108 109 110 111 112 HINGES CAL -ROYAL - US260 - 553lxUS26 TBH3lxUS26 CLOSER LCN - US260 - 146OA441 WALL STOP CAL -ROYAL - US260 - CONW542 FLOOR STOP : CAL -ROYAL - US26D - DSHP18 PASSAGE SET : SCHLAGE - U826D - SATURN AL10S PRIVACY SET : SC 4LAGE - US26D - SATURN AL40S LOCK SET : SC 4LAGE - US26D - SATURN AL50PD SINGLE DUMMY TRIM : SCHLAGE - US26D - SATURN AL110 STOREROOM LOCK : SC 4LAGE - US26D - SATURN AL8010D CLASSROOM LOCK : SCHLAGE - US26D - SATURN AL10PD THRESHOLD : PEMKO - ALUM - 210A or 110A DOOR SWEEP : P£MKO - ALUM - 315CN PULL HANDLE : DON-JO - US26D - 1114 KICK PLATE : DON-JO - ALUM - J102 PANIC DEVICE : MONARCH - MAL - ISIOLDANE 113 115 11 116 ROOM FINISH gCI-IEDULE ROOM NAME BASE FLOORS N E S W CEILING REMARKS ROOM NO. INFUSION CB-1 CT-1 P-1 P-9 P-1 P-1 ACT 101 CLOSET CB-1 CT_1 P7 P-1 P-1 P-1 ACT 102 OFFICE CPT CPr P-1 P-1 P-1 P-1 ACT 103 OFFICE CPT CPr P-1 P-1 P-1 P-1 ACT 104 BEDS CB-1 CT-1 P1 Pi P-1 P1 ACT 105 LAB CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 106 NURSESTATION CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 107 EXIT ACCESS CORRIDOR CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 108 OFFICE CPT CPT P 1 P-1 P-1 P-1 ACT 109 NOT USED CB-1 CT-1 I P-1 P-1 P-1 P-1 ACT 110 CORRIDOR CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 111 NURSESTATION CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 112 EXAM CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 113 EXAM CB-1 CT-1 P-1 P-1 P-1 P-1 ACT 114 EXAM CB-1 CT-1 P7 P-1 P-1 P-1 ACT 115 EXISTING CORRIDOR CB-1 CT-1 P 1 I P-1 P-1 I P-1 ACT 116 FINISH M-ATELEGEND Material IAbb. I Maker. Model. Manufacturer Flooring Caf bridge "Agenda" AGN04 Ex plain; 12' w ide; 1.6"w x 1.2"l pattern repeat; 30 Carpet CPT oz.; Avalar SDX Nylon with Puralex; Solution Dyed; Direct Glue Down; Contact: Debra Folsom (813) 902-0297 Porcelain Tile Dal Tile "Veranda" ColorBody Porcelain Tile "Sand" P505; 20" x 20"; Grout: Custom Building Products "Fawn" 156; 1/16" Grout Joint Base Porcelain Wall Tile Base PNTB Dal Tile "Veranda" Colorbody Porcelain Tile 13x20 "Zen Garden" P530; Grout: Custom Building Products "Fawn 156; 1/16" Grout joint Vinyl Cove Base VB1 Johnsonite "White Sand" 68; 4" V132 Roppe "Gingko" 633; 4" Walls Femt P1A ICI "Cieio Blanco" 43YY 81/051; Eggshell Finish P1B IG "Ciao Blanco" 43YY 81/051; Epoxy Finish -- - P2A IG "White Lagoon" 41 BG 76/025; Eggshell Finish P2B IG "White Lagoon" 41BG 76/025; Epoxy Finish P313 ICI "Marian's" Meadow" 10GY 39/136; Epoxy Finish P413 IG "Capitol Blue" 301313 181190; Epoxy Finish P5B ICI "Rne Forest Green" 10GY 29/158; Epoxy Finish P6B la "Blueberry Bud" 3OBB 331163; Epoxy Finish P7B IG "Serengeti Plain" 90YY 481255; Eggshell Finish TCL Brand Tile "Earth Naturals" Herrp; 12" x 18" Installed Subway style w ith Porcelain Wall Tile RNT coordinating builnose cap; Grout: Custom Building Products "Fawn" 156; 1/16' Grout Joint York Contract "Droplet' SG1712 Pistachio; 54"-55.5"wide;12 5I8" Straight Match VVallcovering WC Repeat; 20 oz.; Contact: Eykon - Jean Carrasco (800) 222-7866, Ext. 1121 Wood or Laminate Panels VVDP Stain to match Wilsonart"Shaker Cherry" 7935K-07 Plastic Laminate Miscellaneous Corner Guards CIS SM20MN; Color: "Vanilla" 313; Contact: Copeland Architectural Systems (813) 831-3344 Cubicle Curtains (123) CC1 Maharam"Steppes" 500925; Color: 007 Baronet; 72"w; 1.125"v x 3"h repeat; Contact: Ayson Mnett (813) 463-6428 Cubicle Curtains (189) CC2 Maharam"Adjourn" 511350; Color: 006 Tendril; 72"w; Contact: Ayson Mnett (813) 463-6428 Crash Rails CIS SCR48K Color: "Vanilla" 313; Contact: Copeland Architectural Systems (813) 831-3344 Doors Mohawk "Dark Brown" on Birch (see Door Schedule for location) CIS Acrovyn "Shaker Cherry" 380 (see Door Schedule for location); Contact: Copeland Architectural Systems (813) 831-3344 Door Frames P1T ICI "Cieb Blanco" 43YY 81/051; Semi Gloss Enamel Finish Door Frames (102, 103, 104)4r P'7T ICI "Serengeti Plain" 90YY 48/255; Semi Gloss Enamel Finish Counters & Cabinets Counters (104 Counters on South Wa11,102 Beverage Counter); Cabinets (102,104,107,113,114,123,148,149, PL1 Wllsonart "Shaker Cherry" 7935K-07 189,192); Built-ins (111,112A,112B); Fagade (104 check in) Counters(123,148,149,156) PL6 Wilsonart"Sprout"4918-60 Counters (189) PL3 VVilsonart "V"Iamai Brush" 4746-60 Counters (107, 113, 114, 192) PL4 Formica "Navy Graf ix" 7018-58 Counters (122,133,137,175,185) PL5CH Ronite "Bride of the Sea" AB291; ChemGuard Finish; Contact: Donna Burdulis (508) 243-8172 for Pricing Cabinets (122,133,137,156,175,185) PL7CH Pionite "Writer White: SW836; CherrGuard Finish; Contact: Donna Burdulis (508) 243-8172 for Pricing Counters (104 check in) SS1 Carribria "VNldehall" 0120 Counters (105, 106) SS2 Carrbria "Snowdon White" 0110 Counters (127, 128, 130, 131) PL8 Pionite "Rock of Ages" AW141 G.IEWW AL NOTES I. ALL RECEPTACLE AND SWITC 4PLATES TO MATCH EXISTING. 2. PROVIDE SAMPLES OF ALL FINISHES FOR REVIEW AND APPROVAL TO ARCHITECT AND OWNER BEFORE ORDERING, 3. ALL FINISHES TO MATCH EXISTING FINISHES. 4. APPROPRIATE LOW PROFILE VINYL TRANSITION STRIP SHALL BE USED BETWEEN DISSIMILAR FLOORING MATERIALS. REVISIONS BY N GO CO ► Y CO N a. �~ ¢ ;0 U ^ E x y N a L • U pco U N ¢_o . ortiCn ti o V a. co l; �1 1 W a O: r! v • <v y it N o - o J Q R. a� O O U C Z O •inn N J .�• v a M W Q N O Q O i O Li. LJ H O � LO — 0 OO L O O N 4 L_O J LL Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet A5 DIVISION 1 GENERAL NOTES DIVISION Z SITE WORK DIVISION 10 SPECIALTIES 1.03 INTERIOR FIRE RATED WOOD DOORS 1.05 JOINT TREATMENT SYSTEMS A 20 MINUTE - PROVIDE DOORS 1 3/4", 5 OR -1 PLY, PARTICLE BOARD CORE, A SYSTEM SHALL BE PERFORATED TAPE AND CEMENT RECOMMENDED THE SECTION 01340 SHOP DRAWWA, PRODUCT DATA AND SA VLES NONE SPECIFIED CONFORMING TO AWI SECTION 1300, FACE VENEER SHALL BE PREMIUM GRADE, TO MATCH EXISTING. EDGE STRIPS SHALL BE HARDWOOD, STILE EDGE SHALL NOT BE GYPSUM MANUFACTURER SECTION kM22 FIRE EXTWA116HM PART I GENERAL LESS THAN 2 3/8" THICK EDGE BEFORE TRIMMING AND SHALL BE SPECIES B. APPLY MATERIALS IN STRICT ACCORDANCE TO MANUFACTURER'S PART 1 GENERAL COMPATIBLE WITH FACE VENEER TOP AND BOTTOM AND BOTTOM EDGE SHALL NOT RECOMMENDATIONS. FILL JOINTS WITH JOINT COMPOUND, EMBED PERT --GRATED 1.01 REQUIREMENTS INCLUDED A SUBMIT SHOP DATA AND SAMPLES REQUIRED BY CONTRACT DIVISION 3 CONCRETE BE LESS THAN 1 1/8" BEFORE TRIMMING. APPROPRIATE FIRE DOOR LABEL TO BE TAPE AND APPLY A SKIM COAT OF JOINT COMPOUND OVER TAPE. APPLY TWO 1.01 SUBMITTALS DRAWINGS, PRODUCT ATTACHED. ADDITIONAL COATS OF JOINT COMPOUND ALLOWING AT LEAST 24 HOURS A PRODUCT DATA: REQUIRED DOCUMENTS, OR AS NECESSARY WHERE NOT INDICATED, SO ARCHITECT CAN REVIEW, BETWEEN EACH COAT. SAND EACH COAT. FINISH SURFACES SHALL BE UNIFORMLY B. SHOP DRAWINGS: NOT REQUIRED SELECT, CHECK FOR CONFORMANCE, ETC., AS REQUIRED. B. 45 THRU 90 MINUTE - PROVIDE DOORS 1 3/4", 5 OR -1 PLY, NONCOMBUSTIBLE, SMOOTH, TRUE AND IN SATISFACTORY CONDITION TO RECEIVE PAINT. C. SAMPLES: NOT REQUIRED 102 RELATED REQUIREMENTS NOW SPECIFIED NON -ASBESTOS MINERAL CORE, ENGINEERED TO MEET LABELING REQUIREMENTS. PART 2 PRODUCTS A DESIGNATED IN THE CONSTRUCTION SCHEDULE, OR IN A SEPARATE COORDINATE CONFORMING TO NFPA 80 AND AWI SECTION 1300 FACE VENEER SHALL BE PREMIUM GRADE, STAIN GRADE RED OAK EDGE STRIPS SHALL BE 1 1/2" WITH 5/8" END OF SECTION 09250 �'1I�/(SIGN DIVISION SCHEDULE, THE DALESS FOR SUBMISSION AND THE DATES THAT REVIEWED SHOP DRAWINGS, PRODUCT DATA AND SAMPLES WILL BE NEEDED. ALLOW SUFFICIENT TIME MATCHING HARDWOOD EDGE AND 7/8" COMPOSITE BACKING. APPROPRIATE FIRE DOOR LABEL TO BE ATTACHED. SECTION f' WII ACOUSTIC PANEL CEILIN_* 2.01 MANUFACTURERS/PRODUCTS A COORDINATE WITH LOCAL MUNICIPALITIES AND PROVIDE FIRE EXTINGUISHERS. IN THE SCHEDULE FOR ARCHITECT REVIEW AND POSSIBLE RESUBMITTALS IF PART I GENERAL B. FIRE EXTINGUISHERS: SEE DRAWINGS FOR SPECIFICATIONS. REQUIRED. I.04 HARDWARE PART 3 EXECUTION 1.03 SHOP DRAWINGS NOW SPECIFIED A PREPARE DOOR TO RECEIVE HARDWARE IN ACCORDANCE WITH THE DOOR . 101 GENERAL 3.01 SCHEDULES A DRAWINGS SHALL BE PRESENTED IN A CLEAR AND THOROUGH MANNER SCHEDULE AND TEMPLATES PROVIDED BY THE HARDWARE MANUFACTURER. A COORDINATE LAYOUT AND INSTALLATION OF ACOUSTICAL CEILING UNITS A INSTALL AS REQUIRED. I. DETAILS SHALL BE IDENTIFIED BY REFERENCE TO SHEET AND DETAIL, SCHEDULE PREPARATION OF FIRE DOORS TO BE DONE AT THE FACTORY OR AN APPROVED AND SUSPENSION SYSTEM GOMPOONENTS WITH OTHER CONSTRUCTION THAT OR CONTRACT DRAWINGS.B. OSHALL PULP OR "WARNOGK HERSEY" SHOP. PENETRATES CEILINGS OR IS SUPPORTED BY THEM, INCLUDING LIGHT END OF SECTION 10522 2. SWEET BEE LABELED WITH CORRECT JOB NAME, LOCATION, ARCHITECT'S FIXTURES AND HVAC EQUIPMENT. PROJECT NUMBER, AND SUBCONTRACTOR'S COMPANY NAME, ADDRESS, PHONE Q METALS DIVISION 5 METALS END OF SECTION 05211 NUMBER AND NAME OF RESPONSIBLE REPRESENTATIVE OF COMPANY. 102 MINERAL -FIBER ACOUSTICAL PANELS 3. DRAWINGS, DETAILS, ETC. SHALL CLEARLY ILLUSTRATE ALL COMPONENTS AND SECTION M110 FINISH WARDWARE A PROVIDE ACOUSTICAL PANELS AS MANUFACTURED TO MATCH EXISTING, 24 DIVISION 11 EQUIPMENT ADJACENT COMPONENTS OF THE WOW.ECIFIED NONE SPECIFIED INCHES BY 24 INCHES I INCH THICK WHITE. REFER TO DRAWINGS FOR LIMITS 1.04 PRODUCT DATA PART I GENERAL OF TILE INSTALLATION. A PREPARATION: B. INSTALL IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED Y MARK EACH COPY TO IDENTIFY PERTINENT PRODUCTS OR-MODIELS�y L CLEAWHICH RARESPECIFICALLY � p /� �t Q DIVISION >S WOOD and PLASTICS S 1 ICS 101 GENERAL INSTRUCTIONS. ARRANGE ACOUSTICAL UNITS AND ORIENT DIRECTIONAL NONE SPECIFIED COVERED BY THE SUBMITTAL. REFERENCE ALL A OBTAIN EACH TYPE OF AS SPECIFIED IN THE pOOR/HARDWARE SCHEDULE HARDWARE FROM A SINGLE PATTERN OF TILES FOR A UNIFORM APPEARANCE. REST PANELS ON NUMBERS TO CORRESPOND TO THOSE IN CONTRACT DOCUMENTS. PONCHARACTERISTICS TOTHOSE EIAND MANUFACTURER ALTHOUGH SEVERAL MAY BE INDICATED AS OFFERING PRODUCTS COMPLYING WITH THE FLANGES OR INVERTED TEES WITH TILE UNITS FITTING NEATLY AGAINST 2. SHOW PERFORMANCE CAPACITIES. SECTION 06410 CUSTOM CASEWORK REQUIREMENTS. BUTTING SURFACE AND SUPPORT BY WALL ANGLES. 3. SHOW DIMENSIONS AND CLEARANCES REQUIRED. 4. SHOW WIRING OR PIPING DIAGRAMS AND CONTROLS. PART I CABINETS B. FURNISH ALL HARDWARE, IN THEIR ORIGINAL PACKAGING, COMPLETE WITH 1.03 METAL SUSPENSION SYSTEM � DIVISION 12 FURNISHIN 6 5. DELETE MODEL NUMBERS, DIAGRAMS, DETAILS, ETC., NOT APPLICABLE TO THE 1.01 DOOR FRONTS, DRAWER FRONTS, KICKS AND SPLASHES ACCESORIES OF PROPER SIZE AND DESIGN REQUIRED FOR THE PURPOSE FOR A PROVIDE SYSTEM AS MANUFACTURED TO MATCH EXISTING SHALL BE EXPOSED SUBMITTAL. A KICKS, SPLASHES AND COUNTER LOPS SHALL BE 3/4" THICK PLYWOOD SURFACED WHICH THEY ARE TO BE USED AND WITH ALL SCREWS, SHIELDS, AND OTHER ANCHORAGE DEVICES NECESSARY FOR A COMPLETE INSTALLATION. HARDWARE TEE -GRID, DOUBLE WEB, INTERMEDIATE DUTY (ASTM C635), ELECTROGALVANIZED, GOLD -ROLLED STEEL, 15/16 INCHES WIDE, CAPPED B. MANUFACTURER'S STANDARD SCHEMATIC DRAWINGS AND DIAGRAMS: I. AND DIAGRAMS TO DELETE INFORMATION WHICH IS NOT WITH HIGH PRESSURE DECORATIVE PLASTIC LAMINATE ON EXTERIOR FACE AND SCHEDULE SHOWN ON THE DRAWINGS. BOTTOM FLANGE. WHITE IN COLOR SYSTEM TO INCLUDE ALL CROSS TEES, NONE SPECIFIED MODIFY DRAWINGS APPLICABLE TO THE WORK EDGES. C. INSTALL EACH HARDWARE ITEM IN COMPLIANCE WITH THE NATIONAL BUILDERS BRIDGING TREES, INTERSECTION CLIPS, SPLICES, COMPLETE EXPOSED GRID 2. SUPPLEMENT STANDARD INFORMATION TO PROVIDE INFORMATION SPECIFICALLY B. DOOR FRONTS, DRAWER FRONTS AND CABINET BODIES SHALL BE 5/8" BLACK HARDWARE ASSOCIATION AND THE MANUFACTURER'S INSTRUCTIONS AND SYSTEM APPLICABLE TO THE WORK MELAMINE WITH HIGH PRESSURE DECORATIVE PLASTIC LAMINATE ON EXTERIOR RECOMMENDATIONS. WHEREVER CUTTING AND FITTING IS REQUIRED TO INSTALL B, LAY OUT PATTERN IN ACCORDANCE WITH THE DRAWINGS, LEVEL, TRUE TO 1�5 SAMPLES FACES AND EDGES. C. STYLE SHALL FLUSH OVERLAY WITH SQUARE EDGES. HARDWARE ONTO OR INTO SURFACES WHICH ARE LATER TO BE PAINTED OR FINISHED IN ANOTHER WAY, COORDINATED REMOVAL, STORAGE, AND PLANE AND AT THE REQUIRED ELEVATION. FRAME AROUND ALL OPENINGS IN /� DIVISION 13 SPECIAL CONSTRUC ION BE CEILING LIGHTS AND GRILLES WITH MAIN RUNNERS. HANGERS ARE TO BE 1t A OFFICE SAMPLES SHALL BE OF SIZE INDICATED, OR OF SUPPiCiENt SIZE AND 102 CABINET BACKS REINSTALLATION OR APPLICATION OF SURFACE PROTECTIONS WITH FINISHING WORK SPACED At 4'-0" ON CENTER MAXIMUM. PROVIDE ADDITIONAL HANGERS AS QUANTITY TO CLEARLY ILLUSTRATE: A 5/8" BLACK MELAMINE BOXES ON BASE AND UPPERS. FINISH INTERIOR FACE TO D. SET UNITS LEVEL PLUMB AND TRUE TO LINE AND LOCATION. ADJUST AND REQUIRED TO SUPPORT LIGHT FIXTURES AND HVAC REGISTERS AND GRILLES I. FUNCTIONAL CHARACTERISTICS OF THE PRODUCT, WITH INTEGRALLY RELATED MATCH CABINET INTERIOR. REINFORCE THE ATTACHMENT SUBSTRATE AS NECESSARY FOR PROPER AND INTERFERENCES OF DUCT WORK NOW SPECIFIED PARTS AND ATTACHMENT DEVICES AND TECHNIQUES. 1.03 DRAWERS INSTALLATION AND OPERATION. DRILL AND COUNTERSINK UNITS NOT FACTORY a SECURES WIRES BY LOOPING AND WIRE -TYING, EITHER DIRECTLY TO 2. FULL RANGE OF COLOR, TEXTURE AND PATTERN FOR ARCHITECT SELECTION AT PREPARED FOR ANCHORAGE FASTENERS. SPACE FASTENERS AND ANCHORS IN STRUCTURES OR TO INSERTS, EYE SCREWS, OR OTHER DEVICES NO ADDITIONAL COST. SUBMIT ONLY SPECIFIED COLOR RANGE IF DIFFERENT A DRAWER FRAMES SHALL BE GRASS ZARGEN DRAWER SLIDE SYSTEM OR ACCORDANCE WITH INDUSTRY STANDARDS. SET THRESHOLDS FOR EXTERIOR APPROPRIATE FOR SUBSTRATE. SCREW ATTACH EDGE MOLDINGS TO FROM MANUFACTURER'S STANDARD RANGE. EQUIVALENT. ALL EXPOSED VIEW PORTIONS SHALL BE FINISHED TO MATCH DOORS IN FULL BED OF BUTYL -RUBBER OF POLYIOSBUTYLENE MASTIC SEALANT. SUBSTRATE AT INTERVALS NOT OVER 16 INCHES ON CENTER AND NOT MORE B. ALL SAMPLES OF A PARTICULAR PRODUCT, ASSEMBLY, UNIT, ETC., SHALL BE INTERIOR OF CABINET BODIES. E ADJUST AND CHECK EACH OPERATING ITEM OF HARDWARE AND EACH DOOR TO THAN 3 INCHES FROM ENDS. LEVEL GRID TO A TOLERANCE OF 1/S" IN 12 FEET. DIVISION 14 CONVEYING SYSTEMS SUBMITTED At THE SAME TIME TO ALLOW PROPER REVIEW AND COMPARISON 1.04 SHELVES, DIVIDERS, AND BOTTOMS ENSURE PROPER OPERATION. REPLACE UNITS THAT CANNOT BE ADJUSTED TO END OF SECTION 09511 BETWEEN SAMPLES. A SHELVES ON THE INTERIOR OF CABINETS (BEHIND DOORS), BOTTOM IN CABINET, OPERATE FREELY AND SMOOTHLY AS INTENDED FOR THE APPLICATION MADE. 1.06 SUBMITTALS AND VERTICAL DIVIDERS SHALL BE 5/8" WHITE MELAMINE. EXPOSED FACES SHALL INSTRUCT OWNERS IN PROPER ADJUSTMENT AND MAINTENANCE OF HARDWARE A PERMITS, LICENSES, AND CERTIFICATES: FOR THE OWNER'S RECORDS, SUBMIT MATCH CABINET BODY INTERIOR FINISH, ALL EXPOSED FRONT EDGES, INCLUDING DURING FINAL ADJUSTMENT. SECTION 0M80 CARPETNG NONE SPECIFIED COPIES OF PERMITS, LICENSES, CERTIFICATIONS, INSPECTION REPORTS, RELEASES, SHELF EDGES, SHALL BE FINISHED WITH ONE (1) TAPED FRONT EDGE. 1.02 KEYING PART 1 GENERAL JURISDICTIONAL SETTLEMENTS, NOTICES, RECEIPTS FOR FEE PAYMENTS, 1.05 PLASTIC LAMINATE A KEYING SHALL BE PER THE OWNERS REQUIREMENTS. TAG KEYS AND PROVIDE 1.01 SUMMARY `' /�' DIVISION ISION �S M CN IC/�i. JUDGMENTS, AND SIMILAR DOCUMENTS, CORRESPONDENCE AND RECORDS ESTABLISHED IN CONJUNCTION WITH COMPLIANCE WITH STANDARDS AND �� A 1/16 THICK MATERIAL ON HORIZONTAL SURFACES AND 1/32 ON VERTICAL SURFACES (GENERAL NOTE: ALL EXTERIOR CORNERS OF COUNTER TOPS TO HAVE A RADIUS TO OWNER AT SUBSTANTIAL COMPLETION. A PROVIDE TYPE AND STYLE AS SCHEDULED IN THE FINISH MATERIAL SCHEDULE. REGULATIONS BEARING UPON PERFORMANCE OF THE WORK OF 1 I/2") B. ADHESIVES. 1.01 CONTRACTOR RESPONSIBILITIES PART 2 PRODUCTS 1.03 GUARANTEE A PROVIDE ONE-YEAR GUARANTEE FOR ALL HARDWARE. PERIOD OF GUARANTEE I. PROVIDE WHITE LATEX CARPET ADHESIVE SUCH AS W.W. HENRY A REVIEW SHOP DRAWINGS, PRODUCT DATA AND SAMPLES PRIOR TO SUBMISSION. 2ldl HARDWARE SHALL BEGIN FROM DATE OF OWNERS ACCEPTANCE. COMPANY NO 356, ROBERTS COMPANY NO. 41-0504, OR AN EQUAL APPROVED BY THE ARCHITECT AND RECOMMENDED FOR THE B. DETERMINE AND VERIFY: A HINGES: "GRASS 120 DEGREE SNAP -ON 3,000 SERIES" FULL OVERLAY SELF CLOSING PURPOSE BY THE MANUFACTURER OF THE SELECTED CARPET. SEE �Ci-iANICAL L FIELD MEASUREMENTS. B. PULLS: 3" BRUSHED ALUMINUM FINISH BY STANLEY OR EQUAL FINAL SELECTION TBD END OF SECTION 08110 2. FIELD CONSTRUCTION CRITERIA. C. DRAWER GLIDES: SEE SPECIFICATION ABOVE 2. PROVIDE SEAM ADHESIVE SUCH AS W.W. HENRY COMPANY NO. 246, 3. CATALOG NUMBERS AND SIMILAR DATA. D. LOCK: NATIONAL LOCK "123-26D (DOOR), "-9136-26D (DRAWER. ROBERTS COMPANY NO. 41-0502, OR AN EQUAL APPROVED BY THE Q DIVISION 9 INISI�ES 4. CONFORMANCE WITH SPECIFICATIONS AND DRAWINGS. C. COORDINATE EACH SUBMITTAL WITH REQUIREMENTS OF THE WORK AND THE E. KEYBOARD DRAWER: AGCURIDE CBER30 - TRAY 200 KEYBOARD SYSTEM BY ACCURIDE ARCHITECT AND RECOMMENDED FOR THE PURPOSE BY THE MANUFACTURER OF THE SELECTED CARPET. DIVISION �� ELECTRICAL CONTRACT DOCUMENTS. DO NOT SUBMIT NON -CONFORMING PRODUCTS. PART 3 INSTALLATION C. AT INTERSECTION OF CARPET AND FLOOR TILE, PROVIDE ROPPE COMPANY, INC. D NOTIFY THE ARCHITECT IN WRITING, AT THE TIME OF SUBMISSION, OF ANY DEVIATIONS 3.01 INSTALLATION VINYL TILE CARPET JOINER PISS OR EQUIVALENT. IN THE SUBMITTALS FROM REQUIREMENTS OF THE CONTRACT DOCUMENTS, OR OF ANY DISCREPANCIES WITHIN THE CONTRACT DOCUMENTS. A PROVIDE WOOD BACK BLOCKING AT PROPER LOCATIONS IN PARTITIONS FOR SECTION 09110 METAL SYSTEMS D. PROVIDE OTHER MATERIALS, NOT SPECIFICALLY DESCRIBED BUT REQUIRED FOR SEE ELECTRICAL E. BEGIN NO FABRICATION OR WORK WHICH REQUIRES SUBMITTALS UNTIL RETURN OF CASEWORK ATTACHMENT. METAL STUDS A COMPLETE AND PROPER INSTALLATION, AS SELECTED BY THE CONTRACTOR, SUBMITTALS WITH ARCHITECT'S CONFORMANCE REVIEW. END OF SECTION 06410 SUBJECT TO THE APPROVAL OF THE ARCHITECT. /� SPECIFICATIONS OF F. SUBMITTALS NOT PROPERLY REVIEWED BY CONTRACTOR FOR CONFORMANCE WITH CONTRACT DOCUMENTS SHALL BE RETURNED WITHOUT ARCHITECT'S REVIEW OR A AT INTERIOR METAL STUD PARTITIONS, UNLESS OTHERWISE SHOWN ON THE DRAWINGS, PROVIDE STANDARD PUNCH STEEL STUDS OF THE SIZES E. ALLOW THE OWNER TO INSPECT AND SELECT FROM SCRAP CARPET REMAINING AFTER THE INSTALLATION. WRAP IN AND DIVISION I T�-IERMAL AND MOISTURE BUNDLE, BURLAP, DELIVER TO THE ACCEPTANCE. SHOWN ON THE DRAWINGS, EITHER NOT -DIP GALVANIZED OR FACTORY OWNER THE CARPET SCRAPS SO SELECTED. IDS SUBMISSION REQUIREMENTS CTION PRE -PAINT: 25 GA. UNLESS SHOWN OTHERWISE ON THE DRAWINGS. 20 END OF SECTION 09680 GA. AT ALL DOOR OPENINGS. A MAKE SUBMITTALS PROMPTLY IN ACCORDANCE WITH APPROVED SCHEDULE, AND IN SUCH SEQUENCE AS TO CAUSE NO DELAY IN THE WORK OR IN THE WORK OF ANY SECTION "I0 BUILDM INSULATION B. ACCESSORIES: PROVIDE ALL ACCESSORIES INCLUDING, BUT NOT SECTION 090" PAINTING OTHER CONTRACTOR PART I GENERAL NECESSARILY LIMITED TO, TRACKS, CLIPS, ANCHORS, FASTENING DEVICES, SOUND ATTENUATION PENCIL RODS AND RESILIENT CLIPS, AND PART I GENERAL B. NUMBER OF SUBMITTALS REQUIRED: 1.02 GENERAL BUILDING INSULATION OTHER ACCESSORIES REQUIRED FOR A COMPLETE AND PROPER I. SHOP DRAWINGS: SUBMIT THE NUMBER OF OPAQUE REPRODUCTIONS WHICH THE A BLANKET INSULATION TO BE UNPAGED, MINERAL FIBER WITH THERMOSETTING RESINS, INSTALLATION, AND AS RECOMMENDED BY THE MANUFACTURER OF THE STEEL STUDS USED. I.01 GENERAL A It IS THE INTENT OF THIS SPECIFICATION TO PRODUCE A PREMIUM JOB, WHICH WILL CONTRACTOR REQUIRES, PLUS THREE (3) COPIES WHICH WILL BE RETAINED BY TYPE 1. MINERAL FIBER SHALL BE MANUFACTURED FROM GLASS. PROVIDE THE MAXIMUM DURABILITY, WHICH CAN REASONABLY BE EXPECTED F RO THE ARCHITECT. MAXIMUM ACCEPTABLE SIZE IS 24" x 36" FOR ANY ONE SHEET. G. MEET OR EXCEED MINIMUM REQUIREMENTS OF FEDERAL SPEC. A PAINTED SURFACE. 2. PRODUCT DATA: SUBMIT THE NUMBER OF COPIES WHICH THE CONTRACTOR B. INSTALL INSULATION UNITS COMPLYING WITH MANUFACTURER'S RECOMMENDATIONS. QQ-S-698 AND FEDERAL SPEC. QQ-S-1-15D, GLASS D. REQUIRES, PLUS THREE (3) WHICH WILL BE RETAINED BY THE ARCHITECT. INSTALL BLANKET INSULATION IN STUD WALLS. BOND UNITS TO SUBSTRATE WITH B. "PAINT" INCLUDES COATING SYSTEMS MATERIALS, PRIMERS, EMULSIONS, ENAMELS, 3. SAMPLES: SUBMIT THE NUMBER STATED IN EACH SPECIFICATION SECTION. IF NO ADHESIVE OR USE MECHANICAL ANCHORAGE TO PROVIDE PERMANENT PLACEMENT. METAL TRIM STAINS, SEALERS, AND FILLERS, AND OTHER APPLIED MATERIALS WHETHER USED NUMBER IS GIVEN, VERIFY CORRECT NUMBER WITH ARCHITECT PRIOR TO 1.03 SOUND ATTENUATING INSULATION A FORM FROM GALVANIZED STEEL NOT LIGHTER THAN 26 GAUGE, AS PRIME, INTERMEDIATE, OR FINISH COAT. SUBMITTAL. MINIMUM OF TWO (2) SAMPLES. 4. PROVIDE SUBMITTALS AS REQUIRED BY THE INDIVIDUAL SECTION, BUT NO LESS A SOUND INSULATION SHALL BE AS MANUFACTURED BY OWENS-CORNING FIBERGLASS, COMPLYING WITH FEDERAL SPEC QQ-5-1-15, CLASS D. C. SPECIFIED PRODUCTS BELOW ARE MANUFACTURED BY SHERWIN WILLIAMS, EXCEPT THAN THAT STATED ABOVE. FIBERGLASS NOISE BARRIER BATTS. INSTALL IN STUD WALLS AND CEILINGS WHERE B. CASING BEADS: U.S.G.0200-B. WHERE OTHER MANUFACTURERS ARE INDICATED, AND ESTABLISH A STANDARD OF QUALITY. EQUIVALENT PRODUCTS OF OTHER ACCEPTABLE MANUFACTURERS MAY INDICATED ON THE DRAWINGS. FIT INSULATION TIGHTLY BETWEEN STUD MEMBERS. C. SUBMITTALS SHALL CONTAIN: NOT BE USED UNLESS APPROVED BY ARCHITECT. I. THE DATE OF SUBMISSION AND THE DATES OF ANY PREVIOUS SUBMISSIONS. END OF SECTION O'1210 END OF SECTION 09110 D. PROVIDE BEST GRADE AND QUALITY MATERIALS AND PRODUCTS MANUFACTURED 2. THE PROJECT TITLE AND NUMBER SECTION 01900 JOINT SEALERS BY SHERWIN WILLIAMS. MATCH COLORS AS INDICATED ON THE DRAWINGS. USE 3. CONTRACT IDENTIFICATION. PART, I GENERAL SECTION OW50 GYPSUM WALLBOARD PREMIXED PAINTS INSOFAR AS POSSIBLE. THIN ONLY AS PERMITTED ANY 4. THE NAMES OF: MANUFACTURER'S LABEL INSTRUCTIONS, AND AVOID UNNECESSARY THINNING. a. CONTRACTOR 1.01 GENERAL PART I GENERAL b. SUBCONTRACTOR A PROVIDE JOINT SEALERS, JOINT FILLERS, AND OTHER RELATED MATERIALS THAT E. PROTECT FINISHED SURFACES, WORK OF OTHER TRADES, AND PROPERTY UP THE OWNER FROM DAMAGE AND DEFACEMENT. COVER FLOORS AND FIXED EQUIPMENT a a SUPPLIER ARE COMPATIBLE WITH ONE ANOTHER AND WITH JOINT SUBSTRATES UNDER 1O1 �� WITH DROP CLOTHS. MANUFACTURER CONDITIONS OF SERVICE AND APPLICATION, AS DEMONSTRATED BY SEALANT A GYPSUM WALLBOARD WORK SHALL CONFORM TO THE GYPSUM ASSOCIATION 5 . IDENTIFICATION OF THE PRODUCT, WITH THE SPECIFICATION SECTION NUMBER 5NUFACTURER BASED AND FIELD EXPERIENCE. PROVIDE COLORS TO RECOMMENDED SPECIFICATIONS FOR THE APPLICATION AND FINISHING OF F. PREPARE SURFACES ACCORDING TO PAINT MANUFACTURER'S INSTRUCTIONS. . FIELD DIMENSIONS, CLEARLY IDENTIFIED AS SUCH. MAF NSH SURFACES. GYPSUM WALLBOARD. EXAMINE FACTORY FINISHED AND PRIMED SURFACES t0 BE PAINTED, AND VERIFY 1. RELATION TO ADJACENT OR CRITICAL FEATURES OF THE WORK OR MATERIALS. COMPATIBILITY OF EXISTING MATERIAL WITH PAINT TO BE APPLIED. APPLY PAINT 8. APPLICABLE STANDARDS SUCH AS, BUT NOT LIMITED TO ASTM OR FEDERAL B. PROVIDE SEALANT BACKINGS OF MATERIAL AND TYPE WHICH ARE NONSTAINING, B. EXAMINE SUBSTRATES TO WHICH DRY WALL CONSTRUCTION ATTACHES OR IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS ONLY SPECIFICATION NUMBERS. ARE COMPATIBLE WITH JOINT SUBSTRATE, SEALANTS, PRIMERS, AND OTHER FILLERS, gBUTTS, PRESET HOLLOW METAL FRAMES, CAST-IN-ANCORS, AND STRUCTURAL TO SURFACES WHICH ARE THOROUGHLY DRY, SMOOTH, EVEN, GLEAN, FREE OF DUST 11 IDENTIFICATION OF DEVIATIONS FROM CONTRACT DOCUMENTS. AND ARE APPROVED FOR APPLICATIONS INDICATED BY SEALANT MANUFACTURER FRAMING FOR COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION TOLERANCE AND PROPERLY PREPARED TO RECEIVE THE INTENDED FINISH. 10. IDENTIFICATION OF OPTIONS AVAILABLE, BUT NOT INDICATED IN THE a SEALANTS: SEALANTS SHALL BE AS FOLLOWS OR EQUAL: AND OTHER CONDITIONS AFFECTING PERFORMANCE OF DRY WALL 1.02 PAINTING SPECIFICATIONS, SUCH AS COLOR, FINISH, TEXTURE, ETC. WITH COMPLETE SAMPLES 1. ONE -PART POLYURETHANE: CONSTRUCTION. DO NOT PROCEED WITH INSTALLATION UNTIL UNSATISFACTORY OR LISTING INCLUDED IN THE SUBMITTAL FOR ARCHITECT'S SELECTION. 2. TWO-PART POLYURETHANE: CONDITIONS HAVE BEEN CORRECTED. A ACCEPTABLE MATERIALS 11. INDICATION OF TERMS TO BE INCLUDED IN THE WORK AND SHOWN ON THE SHOP 3. SILICONE: G. DO NOT CAPE AND FINISH GYPSUM BOARD WHEN THE TEMPERATURE IS BELOW 60 L ALL PAINTING TO BE SCHEDULED IN THE FINISH SCHEDULE. DRAWINGS SHALL BE DIMENSIONED AND COORDINATED FOR PROPER FIT AND D. COMPLY WITH JOINT SEALER MANUFACTURER'S PRINTED INSTALLATION INSTRUCTION DEGREES FAHRENHEIT. THE TEMPERATURE OF THE ROOMS SHALL BE HELD AT 2. EQUIVALENT PRODUCTS OF THE FOLLOWING ARE ALSO ACCEPTABLE: TIMELY INCLUSION. APPLICABLE TO PRODUCTS AND APPLICATIONS INDICATED. CLEAN OUT JOINTS 60 DEGREES FAHRENHEIT FOR 45 HOURS BEFORE TAPING AND FINISHING IS TO PRATT t LANBERTT 12. ID IDENTIFICATION OF REVISIONS ON SUBMITTALS. IMMEDIATELY BEFORE INSTALLING JOINT SEALERS. PRIME WHERE RECOMMENDED B BEGIN. MAINTAIN 60 DEGREES FAHRENHEIT DURING AND AFTER INSTALLATION.- GLIDDEN 13. 8" x 3" BLANK SPACE FOR CONTRACTOR AND ARCHITECT SCAMPS. - SEALER MANUFACTURER DO NOT ALLOW MIGRATION OF PRIMER ONTO ADJACENT VENTILATES AS -REQUIRED TO REMOVE: EXCESS HUMIDITY.- PORT`ER - - 14. CONTRACTOR'S STAMPS, INITIALED OR SIGN, CERTIFYING THE REVIEW OF SURFACES. MASK WHERE REQUIRED TO PROTECT ADJOINING SURFACES FOR STAININ BENJAMINE MOORE SUBMITTAL, VERIFICATION OF PRODUCTS, FIELD MEASUREMENTS AND FIELD OR DAMAGE BY CLEANING METHODS TO REMOVE SMEARS. 1.02 GYPSUM WALLBOARD CONSTRUCTION CRITERIA, AND COORDINATION OF: THE INFORMATION WITHIN THE A GYPSUM WALLBOARD SHALL BE MANUFACTURED BY U.S. GYPSUM. WALLBOARD IS B. UNDERCOATS AND THINNERS SUBMITTAL WITH REQUIREMENTS OF THE WORK AND OF CONTRACT DOCUMENTS. E. APPLY SEALANTS IN A MANNER SO THAT APPEARANCE IS THAT OF A SMOOTH, TO MEET. ASTMI C36-84A AND 85-L-30d 1/2 INCHES THICK, 48 INCHES WIDE WITH L PROVIDE UNDERCOAT PAINT PRODUCED BY THE SAME MANUFACTURER OF UNIFORM, SLIGHTLY CONCAVE BEAD. TOOL WITH CAULKING TOOL AS REQUIRED WITHI TAPERED EDGES. FINISH COAT. IDS RESUBMISSION REQUIREMENTS 10 MINUTES OF APPLICATION. ALL SEALED JOINTS ARE TO BE WATER -TIGHT. A MAKE ANY CORRECTIONS OR CHANGES IN THE SUBMITTALS REQUIRED BY THE F. BACKER ROD: POLYETHYLENE FOAM BACKER ROD, NONSTAINING, B. AT FIRE RATED PARTITIONS INSTALL WALLBOARD TO MEET SEPARATE 2. USE ONLY THINNERS RECOMMENDED BY THE PAINT MANUFACTURER AND USE ONLY THE RECOMMENDED LIMITS. ARCHITECT AND RESUBMIT UNTIL ACCEPTED. CHEMICLOSCAL E HLFO EXPANDED POLYETHYLENE FOAM AS MANUFACTURED BY DOW CHEMICAL ETHLFOAM REQUIREMENTS, USE TYPE III, GRADE X CLASS 1, 5/8 INCHES THICK FIRE B. SHOP DRAWINGS AND PRODUCT DATA: FURNISH WITH ROUND EDGE IN THICKNESS REQUIRED. . RETARDANT WALLBOARD G. COLOR SCHEDULES L REVISE INITIAL DRAWINGS OR DATA, AND RESUBMIT AS SPECIFIED FOR THE END OF SECTION 0i900 C. INSTALL GYPSUM BOARD WITH TRUE, EVEN SURFACES AND STRAIGHT, SHARP L PROVIDE PAINTING AS SCHEDULED IN THE FINISH MATERIALS SCHEDULE. INITIAL SUBMITTAL. CORNERS. USE FULL LENGTH BOARDS WHERE POSSIBLE. END JOINTS ON THE a. ON GYPSUM DRYWALL, USE: 2. INDICATE ANY CHANGES WHICH HAVE BEEN MADE OTHER THAN THOSE SAME SIDE OF A WALL SHALL BE STAGGERED AND JOINTS ON OPPOSITE SIDE REQUESTED BY THE ARCHITECT. C. SAMPLES: SUBMIT NEW SAMPLES AS REQUIRED FOR INITIAL SUBMITTAL. Q �Q /� �y� �Q DIVISION S DOORS WINDOWS SHALL NOT OCCUR OVER THE SAME SUPPORT. DO NOT LOCATE NORMAL END L FIRST COAT - PIGMENTED PRIMER/SEALER 2. SECOND COAT - ACRYLIC LATEX ENAMEL FIND JOINTS AT EDGE OF OPENINGS. FORM JOINTS NEATLY. BUTT BOARDS TOGETHER BUT DO NOT FORGE INTO PLACE. DO NOT BUTT EDGES AGAINST TAPERED 3. THIRD COAT - ACRYLIC LATEX ENAMEL 1.10 DISTRIBUTION A DISTRIBUTE REPRODUCTION OF SHOP DRAWINGS AND COPIES OF PRODUCT DATA EDGES. NO JOINT SHALL HAVE A GAP GREATER THAN 1/4 INCH. b. ON FERROUS METAL, USE: L FIRST COAT -TRUST INHIBITIVE ALKYD METAL PRIMER SECTION M211 FLUSH WOOD DOORS WHICH CARRY THE ARCHITECT'S STAMP OF CONFORMANCE TO: PART (GENERAL D. IN GENERAL, INSTALL GYPSUM BOARD ON CEILING BEFORE WALLS. CONSTRUCT 2. SECOND GOAL - SEMI -GLOSS ALKYD ENAMEL L JOB SITE FILE. CEILINGS WITH LONG DIMENSION OF GYPSUM BOARD APPLIED At RIGHT ANGLES 3. THIRD GOAL -SEMI-GLLOSSOSS ALKYD LKYD ENAMEL 2. RECORD DOCUMENTS FILE. 1.01 GENERAL TO SUPPORT. 3. SUBCONTRACTORS. A DO NOT DELIVER DOORS OR INSTALL UNTIL CONDITIONS FOR TEMPERATURE AND RELATIVE HUMIDITY HAVE BEEN STABILIZED AND WILL BE MAINTAINED IN STORAGE E. SCREW GYPSUM BOARD TO FRAMING WITH SCREWS NOT OVER S INCHES ON CENTER a ON WOOD DOORS, USE: 4. SUPPLIER OR FABRICATOR 5. OWNER (TO BE DISTRIBUTED BY THE ARCHITECT). AND INSTALLATION AREAS DURING REMAINDER OF CONSTRUCTION PERIOD. FASTEN GYPSUM BOARD BEGINNING At THE CENTER AND WORK TOWARDS OUTER EDGES. HOLD BOARD FIRMLY AGAINST WOOD FRAMING WHILE FASTENING. L FIRST GOAT - STAIN (SEE FINISH SCHEDULE) 2. SECOND COAT - STAIN (SEE FINISH SCHEDULE) 1.02 INTERIOR FLUSH WOOD SOLID GORE DOORS FASTENERS AT EDGES OF BOARDS SHALL BE 1/2 INCH FROM THE EDGE. 3. THIRD GOAT - VARNISH LOW SHEEN "RUBBED EFFECT" 1.11 ARCHITECT'S DUTIES 5 OR 7 PLY, PARTICLE BOARD GORE, CONFORMING TO AWI A PROVIDE DOORS 1 3/4„ A REVIEW SUBMITTALS WITH REASONABLE PROMPTNESS AND IN ACCORD WITH , SECTION 1300 FACE VENEER SHALL BE PREMIUM STAIN GRADE BIRCH. EDGE F. OPENINGS FOR ELECTRICAL DEVICES, PIPING, GRILLS, AND REGISTERS SHALL BE END OF SECTION 09900 SCHEDULE. ALLOW A MINIMUM OF TEN (10) WORKING DAYS FOR REVIEW, UNLESS STRIPS SHALL BE HARDWOOD. STILE EDGE SHALL NOT BE LESS THAN 2 3/8" THICK ACCURATELY LOCATED AND NEATLY MADE TO CLOSELY FIT THE DEVICES AND SPECIAL HANDLING IS ARRANGED IN ADVANCE. EDGE BEFORE TRIMMING AND SHALL BE SPECIES COMPATIBLE WITH FACE VENEE BE COMPLETELY COVERED BY PLATES AND ESCUTCHEONS. B. AFFIX STAMP AND INITIALS OR SIGNATURE, AND INDICATE REQUIREMENTS FOR TOP AND BOTTOM AND BOTTOM EDGE SHALL NOT BE LESS THAN 1 1/8" BEFORE 103 TRIM PIECES RESUBMITTAL OR CONFORMANCE OF SUBMITTAL. ACCEPTANCE IS FOR GENERAL TRIMMING. A PROVIDE TRIM ACCESSORIES OF THE SIZES REQUIRED FOR THE WALLBOARD CONFORMANCE WITH DESIGN CONCEPT AND GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS. QUANTITIES AND DIMENSIONS OF MATERIALS WILL NOT BE APPLICATION AS MANUFACTURED BY U.S. GYPSUM. PROVIDE DUR-A-BEAD REVIEWED. ACCEPTANCE OF A SUBMITTAL DOES NOT WAIVE OR ALTER THE CORNER BEAD AT EXTERNAL CORNERS AND NO. 200-A METAL CASING BEAD REQUIREMENTS OF THE CONTRACT DOCUMENTS. WHERE WALLBOARD ABUTTS OTHER MATERIALS. C. RETURN SUBMITTALS TO CONTRACTOR FOR DISTRIBUTION OR FOR RESUBMISSION. 1.04 FASTENERS A PROVIDE SCREWS, NAILS, CLIPS, TIES, AND OTHER FASTENERS AS RECOMMENDED END OF SECTION 01340 BY THE GYPSUM MANUFACTURER REVISIONS BY u �UU o y M N L Cz. 4 0 � yx� E rom /� / N O •--� C1. U O O ,nN U '::. Lo o -' 00 3 Y 3:- 3 x N c 0 �tiaL. m I I a �v co �` •C .y 9� L OM ,Chi. G� a� co O C0 0 C2 a� O U Z_ O 'm J N It C U m v a v M W Q N O O U O Q LL1 v N O 'a Lo •_ M i Q C) C)o -C O M a- CL OL. N N I 0 J Date: 06. 03. 16 Scale: AS NOTED Project Mgr: AAY Drawn: JDS Job: 16-062 Sheet N1 FIRE PROTECTION LEGEND: SYMBOL DESCRIPTION FPW=+ FIRE SPRINKLER WET PIPING E--FPD======== FIRE SPRINKLER DRY PIPING PROJECT COORDINATION NOTES: THE CONSTRUCTION PHASING OF THIS PROJECT IS OF THE UTMOST IMPORTANCE. ALL CONTRACTORS FOR ALL DIVISIONS OF THE WORK SHALL GUARANTEE THAT THEIR WORK IS IN ACCORD WITH THE PHASING PLANS SHOWN IN THE ARCHITECTURAL CONTRACT DOCUMENTS. SHOULD IT BE NECESSARY TO ACCOMPLISH WORK IN AREAS WHICH ARE NOT INCLUDED IN THE PHASING PLANS, SUCH WORK SHALL BE DONE WITH THE MINIMUM OF DISTURBANCES THAT IS POSSIBLE AND WITHOUT CAUSING THE INTERRUPTION OF EXISTING SERVICES. ALL SERVICE INTERRUPTIONS THAT ARE ESSENTIAL TO THE WORK SHALL BE SCHEDULED WITH THE ARCHITECT AND, THEREBY, WITH THE OWNER. ALL CONTRACTORS FOR ALL TRADES SHALL COOPERATE AND COORDINATE THEIR WORK TO ALLOW THE COMPLETION OF ALL WORK WITH THE LEAST POSSIBLE NUMBER ON INTERFERENCE'S WITH THE SERVICES OF THE EXISTING BUILDING. THE DESIGN DRAWINGS OF ALL CATEGORIES AND TRADES (ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, MEDICAL GAS, MECHANICAL, HEATING, VENTILATING AND AIR CONDITIONING AND ELECTRICAL) AND ALL SPECIFICATIONS AND SHOP DRAWINGS MUST BE COORDINATED AND BE VIEWED IN CONNECTION AND CONJUNCTION WITH EACH OTHER TO INSURE THE PROPER LOCATION OF ALL DEVICES AND EQUIPMENT. MAKE PARTICULAR NOTE OF LOCATIONS AND DIMENSIONS SHOWN ON THE ARCHITECTURAL FLOOR PLANS AND ELEVATIONS. CODE CRITERIA: A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY OR MAY NOT APPLY TO THIS PROJECT. B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER. NFPA-70 (2011) NATIONAL ELECTRICAL CODE NFPA-72 (2010) NATIONAL FIRE ALARM CODE NFPA-90A (2012) INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS NFPA-90B (2012) INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS NFPA-91 (2010) EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND NON-COMBUSTIBLE PARTICULATE SOLIDS NFPA-96 (2011) VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING OPERATIONS. NFPA-101 (2012) LIFE SAFETY CODE FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014) FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014) FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014) FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE ZONES 5TH EDITION (2014) FLORIDA BUILDING CODE, FUEL GAS 5TH EDITION (2014) FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014) FLORIDA ACCESSIBILITY CODE (2014) APPLICABLE STATE ENERGY CODE (2014) STATE OF FLORIDA ADMINISTRATIVE CODE NO.69A-3.012 AND 69A-60. NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE "BUILDING" AND MECHANICAL OR PLUMBING CODES, IT WILL BE ASSUMED THAT THE BUILDING CODE TAKES PRECEDENCE. FIRE PROTECTION GENERAL NOTES: THE CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE AUTOMATIC SPRINKLER SYSTEM FOR THE RENOVATED AREA. ALL SPRINKLERS SHALL BE INSTALLED ACCORDING TO THEIR LISTING. THE SPRINKLER SYSTEM SHALL BE A WET SYSTEM HYDRAULICALLY CALCULATED USING THE FOLLOWING CRITERIA: A. ALL SPRINKLER HEADS SHALL BE FULLY CONCEALED, QUICK RESPONSE TYPE, W/TEMPERATURE RATINGS AS CONDITIONS DICTATE. COORDINATE SPRINKLER COVER CUSTOM COLOR FINISHES WITH ARCHITECT. ASSOCIATED SPRINKLER PIPING SHALL BE RUN IN FURRED SPACES, CHASES, ETC., TO COMPLETELY CONCEAL ALL PIPING. B. ALL SPRINKLER HEADS IN AREAS WITHOUT FINISHED CEILINGS SHALL BE BRASS UPRIGHT HEADS WITH TEMPERATURE RATINGS AS CONDITIONS DICTATE. ASSOCIATED SPRINKLER PIPING SHALL BE RUN EXPOSED AND PAINTED TO MATCH ADJOINING AREAS. C. SPRINKLERS ARE TO BE SUPPLIED FROM AUTOMATIC SPRINKLER RISER ASSEMBLY WHICH SHALL BE FURNISHED COMPLETE WITH STANDARD TRIM AND THE NECESSARY COMPONENTS (A FLAPPER TYPE FLOW SWITCH) TO INTERLOCK WITH THE BUILDING FIRE ALARM SYSTEM. SWITCH BY SPRINKLER CONTRACTOR. WIRING BY ELECTRICAL CONTRACTOR. D. RETURN BENDS SHALL BE USED THROUGHOUT NEW FIRE ZONES. E. THE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF PIPING AND HEADS WITH LIGHT FIXTURES, DIFFUSERS, DUCTWORK, PLUMBING LINES, ETC., AND MAKE MINOR ADJUSTMENTS IN THE SPRINKLER LAYOUT WHERE REQUIRED OR DEEMED NECESSARY BY THE ARCHITECT. F. ALL SPRINKLER HEADS SHALL BE LOCATED SYMMETRICALLY IN ALL AREAS AND CENTERED IN CEILING TILES. G. SPRINKLER CONTRACTOR SHALL INSTALL WIRE GUARDS ON SPRINKLER HEADS IN MECHANICAL AND ELECTRICAL ROOMS. H. FIRE PROTECTION SYSTEM TO CONFORM TO ALL REQUIREMENTS OF NFPA 10, 13, AND 25, ALL LOCAL, COUNTY AND STATE REGULATIONS, AS WELL AS THE INSURANCE UNDERWRITER. COORDINATE WITH ELECTRICAL CONTRACTOR FOR WIRING OF THE TAMPER AND FLOW SWITCHES. I. THE SPRINKLER CONTRACTOR SHALL INSPECT, TEST AND MODIFY EXISTING SPRINKLER SYSTEM AS NEEDED TO COMPLY WITH NFPA AND LOCAL CODES. CONTRACTOR SHALL PROVIDE A LETTER OF ACCEPTANCE FOR THE EXISTING BUILDING. J. ALL SPRINKLER PIPING FROM "EXISTING RISERS" USED FOR SPRINKLER OR STANDPIPE SYSTEM SHALL BE INSTALLED BY A REGISTERED SPRINKLER CONTRACTOR. UNDERGROUND WATER MAINS AND HYDRANTS MUST BE INSTALLED AND IN SERVICE PRIOR TO STARTING CONSTRUCTION. K. PROVIDE DRAIN VALUES AS REQUIRED BY NFPA. L. ALL SPRINKLER HEADS SHALL HAVE 5.6 K FACTOR M. PROVIDE 165 DEGREE F. SPRINKLER HEADS W/LISTED GUARDS IN MECHANICAL ROOMS MECHANICAL ROOMS PROVIDED WITH AIR CONDITIONING. N. SPRINKLER CONTRACTOR SHALL INSTALL TAMPER SWITCHES ON ALL EXTERIOR VALVES. COORDINATE WITH ELECTRICAL CONTRACTOR. 0. PROVIDED FIRE EXTINGUISHER CABINETS SO THAT ALL AREAS OF BUIDLING CAN BE REACH WITHIN 75 FEET OF EXTINGUISHER. PROVIDE WALL HUNG, CO2 TYPE EXTINGUISHERS IN ELECTRICAL & COMMUNICATION ROOMS. PROVIDE WALL HUNG, ABC TYPE EXTINGUISHERS IN MECHANICAL ROOMS. P. PROVIDE HORIZONTAL, DRY TYPE, QUICK RESPONSE HEADS AT EXTERIOR OVERHANGS. Q. PROVIDE ALL -THREAD TO TOP OF PIPE ON HANGER NEAREST TO CEILING -MOUNTED PENDANT SPRINKLERS. APPLIES TO BOTH NEW AND EXISTING PIPING WITHIN AREA OF WORK AND/OR ANY AREA WHERE CEILING IS REMOVED AND/OR REPLACED DURING CONSTRUCTION. REVISIONS .f f • 00 00 M N � �— Q 00 o � �` E Cu ti ° U Ic -. • • N .� o ro EO ULo it ¢ E Q 6 00 o 3 ti 3 E C, tia. N 1 Z Om z U W LL D to U ZO 00 U U s` Z 0 _ •C V C4 0 LO x M - . - C,rLu o V — O V W 8 vs OCO O a— O CL L O Date: 06. 03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet FP0*1 SPOUT DEPTH VARIES SEE SPECS SINK OR LAVATORY RIM TYPICAL GOOSENECK FAUCET REQUIREMENTS No Scale CODE CRITERIA: NOTE: A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY OR MAY NOT APPLY TO THIS PROJECT. B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER. NFPA-70 (2011) NATIONAL ELECTRICAL CODE NFPA-72 (2010) NATIONAL FIRE ALARM CODE NFPA-90A (2012) INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS NFPA-90B (2012) INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS NFPA-91 (2010) EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND NON-COMBUSTIBLE PARTICULATE SOLIDS NFPA-96 (2011) VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING OPERATIONS. NFPA-101 (2012) LIFE SAFETY CODE FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014) FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014) FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014) FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE ZONES 5TH EDITION (2014) FLORIDA BUILDING CQDE, FUEL GAS 5TH EDITION (004) _ FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014) FLORIDA ACCESSIBILITY CODE (2014) APPLICABLE STATE ENERGY CODE (2014) STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60. NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE "BUILDING" AND "MECHANICAL" OR "PLUMBING" CODES, IT WILL BE ASSUMED THAT THE BUILDING CODE TAKES PRECEDENCE. PLUMBING ABBREVIATIONS ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION A MEDICAL AIR LINE MGA MASTER ALARM PANEL ADA AMERICANS WITH DISABILITIES ACT MECH MECHANICAL AFF ABOVE FINISHED FLOOR MTD MOUNTED AVTR ACID VENT THROUGH ROOF 02 OXYGEN LINE BPW BED PAN WASHER OFE OWNER FURNISHED EQUIPMENT CLG CEILING PAT PATIENT CONT CONTINUATION PUB PUBLIC COORD COORDINATION RPBP REDUCED PRESSURE BACKFLOW PREVENTER CO CLEAN OUT RWL RAINWATER PIPING CW COLD WATER LINE SAN SANITARY SEWER PIPING DN DOWN SD UNDERGROUND STORM PIPING DWG DRAWING SF SQUARE FOOT EA EACH SS SOLID SURFACE ECO EXTERIOR CLEAN OUT TMP TEMPERATURE FM FLOOR MOUNTED TMV THERMOSTATIC MIXING VALVE FPD FIRE PROTECTION DRY PIPE TYP TYPICAL FPW FIRE PROTECTION WET PIPE V MEDICAL VACUUM PIPING FV FLUSH VALVE VTR VENT THROUGH ROOF GN GOOSENECK W/ WITH GPM GALLONS PER MINUTE WB WRIST BLADE HW HOT WATER LINE WC WATER CLOSET HWR HOT WATER RETURN WCO WALL CLEAN OUT LAV LAVATORY WH WALL HUNG PLUMBING FIXTURE CONNECTION SCHEDULE COLD HOT TYPE DESCRIPTION WASTE VENT WATER WATER P-1 SINK (DROP -IN, GN, WB, ADA/BF) 1-1/2" 1-1/4" 1/2" 1/2" P-2 SINK (DROP -IN, GN, WB, ADA/BF) 1-1/2" 1-1/4" 1/2" 1/2" P-3 WALL BOX (CW) --- --- 1 /2" --- NOTES: 1. ALL EXPOSED P-TRAPS SHALL BE PROVIDED W/LAV SHIELDS. 2. PROVIDE BACKFLOW PREVENTER AT CONNECTION TO OWNER FURNISHED EQUIPMENT PER FPC. 3. IN ADDITION TO SERVICE VALVES SHOWN ON PLANS, PROVIDE AND INSTALL ISOLATION VALVES ON HOT AND COLD WATER SUPPLY PIPING TO EACH PLUMBING FIXTURE, INCLUDING TRAP PRIMERS. 4. PROVIDE OFFSET GRID DRAINS AT BARRIER FREE LOCATIONS. 5. COORDINATE EXACT LOCATIONS W/ MECHANICAL EQUIPMENT. PLUMBING LEGEND: SYMBOL DESCRIPTION REDUCED PRESSURE BACKFLOW PREVENTER ® P TRAP BALL VALVE CONNECTION TO EXISTING @'L7 O�.i3�7 FLOOR DRAIN P- No. PLUMBING FIXTURE DESIGNATION C END CAP �E�CWMMMEMEBM COLD WATER SUPPLY H!^, HOT WATER SUPPLY 0--HWIRSEESEEM HOT WATER RETURN 140 H!^.SEEEES 140° HOT WATER SUPPLY 140 HWREMEa 1400 HOT WATER RETURN SANITARY VENT SS SANITARY WASTE '�^•�� ACID WASTE ��- ACID VENT RAIN WATER LEADER ,RD OVERFLOW ROOF DRAIN Sn STORM DRAIN G NATURAL GAS LINE PROJECT COORDINATION NOTES: THE CONSTRUCTION PHASING OF THIS PROJECT IS OF THE UTMOST IMPORTANCE. ALL CONTRACTORS FOR ALL DIVISIONS OF THE WORK SHALL GUARANTEE THAT THEIR WORK IS IN ACCORD WITH THE PHASING PLANS SHOWN IN THE ARCHITECTURAL CONTRACT DOCUMENTS. SHOULD IT BE NECESSARY TO ACCOMPLISH WORK IN AREAS WHICH ARE NOT INCLUDED IN THE PHASING PLANS, SUCH WORK SHALL BE DONE WITH THE MINIMUM OF DISTURBANCES THAT IS POSSIBLE AND WITHOUT CAUSING THE INTERRUPTION OF EXISTING SERVICES. ALL SERVICE INTERRUPTIONS THAT ARE ESSENTIAL TO THE WORK SHALL BE SCHEDULED WITH THE ARCHITECT AND, THEREBY, WITH THE OWNER. ALL CONTRACTORS FOR ALL TRADES SHALL COOPERATE AND COORDINATE THEIR WORK TO ALLOW THE COMPLETION OF ALL WORK WITH THE LEAST POSSIBLE NUMBER ON INTERFERENCE'S WITH THE SERVICES OF THE EXISTING BUILDING. THE DESIGN DRAWINGS OF ALL CATEGORIES AND TRADES (ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, MEDICAL GAS, MECHANICAL, HEATING, VENTILATING AND AIR CONDITIONING AND ELECTRICAL) AND ALL SPECIFICATIONS AND SHOP DRAWINGS MUST BE COORDINATED AND BE VIEWED IN CONNECTION AND CONJUNCTION WITH EACH OTHER TO INSURE THE PROPER LOCATION OF ALL DEVICES AND EQUIPMENT. MAKE PARTICULAR NOTE OF LOCATIONS AND DIMENSIONS SHOWN ON THE ARCHITECTURAL FLOOR PLANS AND ELEVATIONS. PLUMBING GENERAL NOTES: 1. PROVIDE AND INSTALL TRAP PRIMERS FOR ALL FLOOR DRAINS. TRAP PRIMER SUPPLY LINE TO CONNECT TO 1-1/4" CW LINE MAXIMUM. PROVIDE SERVICE VALVE. TRAP GUARDS SHALL NOT BE ACCEPTED. 2. PROVIDE ACCESSIBLE SERVICE VALVE(S) IN EACH WATER LINE SERVING EACH PLUMBING FIXTURE OR OWNER FURNISHED EQUIPMENT, IN ADDITION TO STOPS. 3. BV4W DENOTES BALANCING VALVE AND GPM SETTING. 4. CONNECT ALL NEW PLUMBING FIXTURES TO SANITARY SEWER MAINS AS INDICATED OR NOTED ON THE PLANS. 5. COLLECT AND ROUTE ALL NEW SANITARY SEWER VENT PIPING FROM NEW PLUMBING FIXTURES TO SANITARY VENTS AS INDICATED OR NOTED ON THE PLANS. 6. ROUTE ALL NEW CW AND HW PIPING FROM NEW PLUMBING FIXTURES TO MAINS AS INDICATED OR NOTED ON THE PLANS. 7. COORDINATE ALL PLUMBING PIPING WITH NEW AND EXISTING MECHANICAL DUCTWORK. SPECIAL ATTENTION SHALL BE PAID TO PIPING UNDERGROUND OR ON OTHER FLOORS NOT WITHIN THE DIRECT SCOPE OF THE PROJECT. 8. PROVIDE CLEAN -OUTS ON SANITARY SEWER AND RAIN WATER LEADER PIPING AT ALL CHANGES IN DIRECTION GREATER THAN 45 DEGREES AND AT THE BASE OF EACH STACK. 9. AS MUCH AS POSSIBLE, ROUTE PLUMBING WITHIN STRUCTURAL JOIST SPACE. 10. CONTRACTOR TO PROVIDE A SHOCKTROL AT ALL WATER CLOSETS, URINALS, CLINICAL SINKS, OR WHERE ANY QUICK -CLOSING VALVES ARE UTILIZED. SHOCKTROL TO BE ZURN SERIES Z-1700 OR EQUAL. SHOCKTROL SIZE TO BE A #100 FOR SINGLE FIXTURES AND A #200 FOR BACK TO BACK FIXTURES. INSTALL SHOCK ARRESTORS IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. PROVIDE ACCESS TO ALL SHOCKTROLS THRU ACCESS PANELS, LAY -IN CEILINGS, WALL IN CHASE. 11. THESE DOCUMENTS SHALL FOLLOW THE ADA GUIDELINES FOR ACCESSIBILITY TO PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL FACILITIES BY INDIVIDUALS WITH DISABILITIES. THESE GUIDELINES ARE TO BE APPLIED DURING DESIGN, CONSTRUCTION AND ALTERATION OF SUCH BUILDING AND FACILITIES TO THE EXTENT REQUIRED BY REGULATIONS ISSUED BY FEDERAL AGENCIES, INCLUDING THE DEPARTMENT OF JUSTICE, UNDER THE AMERICANS WITH DISABILITIES ACT (ADA) AND THE REQUIREMENTS OF ANSI A117.1 12. THE SIZE AND LOCATION OF EXISTING PIPING IS SHOWN ACCORDING TO RECORDED INFORMATION. THE PLUMBING CONTRACTOR SHALL MAKE AN APPROPRIATE PRE -BID SITE INSPECTION IN ORDER TO ASCERTAIN EXISTING CONDITIONS AND SHALL INCLUDE IN HIS BID THE COST OF ALL WORK RESULTING FROM EXISTING CONDITIONS, WHETHER THIS WORK IS SHOWN OR NOT ON THESE DRAWINGS. 13. PRIOR TO ANY EXCAVATION OR DEMOLITION THIS CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES, THE FACILITY MAINTENANCE DEPARTMENT AND ANY OTHER AVAILABLE SOURCE OF INFORMATION AS TO ABOVE OR BELOW GROUND SERVICES THAT SHALL BE AVOIDED. CONTRACTOR SHALL INFORM THE OWNER ONE WEEK IN ADVANCE OF ANY DISRUPTION OF SERVICES TO THE FACILITY AND SHALL NOT PROCEED WORK WITHOUT WRITTEN APPROVAL FROM THE OWNER. CONTRACTOR SHALL REPAIR ANY SERVICES (ABOVE OR BELOW GROUND) DAMAGED BY WORK THE CONTRACTOR PERFORMED. REPAIRS SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER. 14. CEILING TILES, FIXTURES AND GRID THAT ARE REQUIRED TO BE REMOVED IN EXISTING AREAS IN ORDER TO FACILITATE NEW WORK SHALL BE PERFORMED BY THE GENERAL CONTRACTOR. 15. CUT AND PATCH AS REQUIRED FOR INSTALLATION. 16. ALL PIPING SHALL BE INSTALLED AS CLOSE TO PLANS AS POSSIBLE. REVISIONS TO PIPING SHALL BE MADE ONLY WHEN A CONFLICT WITH OTHER TRADES OCCURS AND SHALL BE APPROVED BY THE ARCHITECT/ENGINEER. 17. THE LOCATION OF ALL CLEANOUTS, VALVES, GAUGES, ETC. SHALL BE LOCATED FOR ACCESS OR SERVICE IN REFERENCE TO THE FINISHED BUILDING. REFER TO THE DRAWINGS FOR APPLICABLE DETAILS. WALL CLEANOUTS SHALL BE 18" A.F.F. AND FLOOR CLEANOUTS SHALL BE LOCATED WITHIN 12" OF AN ADJACENT WALL. 18. WHERE PLUMBING SERVICES ARE REQUIRED FOR EQUIPMENT FURNISHED UNDER OTHER SECTIONS OR PROVIDED BY THE OWNER (OFCI), THE CONTRACTOR SHALL DETERMINE ACCURATE ROUGHING REQUIREMENTS IN ADVANCE OF WORK, SET EQUIPMENT IN PLACE, MAKE NECESSARY SERVICE CONNECTIONS AND PROVIDE ACCESSORIES AS REQUIRED. REFER TO "EQUIPMENT SCHEDULE (OFCI)" AND KITCHEN EQUIPMENT DRAWINGS WHERE APPLICABLE. 19. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION AND ROUGHING DIMENSIONS OF ALL PLUMBING FIXTURES, DRAINS, ETC... 20. ALL FLOOR DRAINS SHALL BE SERVED BY AN APPROVED TRAP PRIMER. EXCEPTION: SHOWER AND KITCHEN DRAINS. 21. ALL HOSE BIBBS, WALL HYDRANTS AND HOSE END CONNECTIONS BE EQUIPPED WITH AN APPROVED INTEGRAL VACUUM BREAKER. 22. DIELECTRIC UNIONS SHALL BE INSTALLED AT ALL CONNECTIONS OF DISSIMILAR METALS (SUCH AS COPPER TO GALVANIZED STEEL). 23. ALL VENT PENETRATIONS THRU THE ROOF SHALL BE LOCATED A MINIMUM OF 25'-0" FROM ALL FRESH AIR INTAKES. 10'-0" CLEARANCE IS ACCEPTABLE FOR NON -HEALTHCARE PROJECTS. 24. UNLESS OTHERWISE NOTED, ALL WALL HYDRANTS AND HOSE BIBBS SHALL BE INSTALLED 24" ABOVE FINISHED FLOORS OR GRADE. 25. FOR UNDERGROUND SANITARY WASTE PIPING, CAST IRON SHALL BE INSTALLED FOR THE FIRST TEN FEET ON THE DRAIN SERVING ANY STERILIZER OR OTHER EQUIPMENT THAT MAY DISCHARGE WASTE WATER ABOVE 140TF. - -- - -- - - --- - - PLUMBING SHEET LIST SHEET NUMBER SHEET NAME P0.1 PLUMBING - LEGEND, NOTES, DETAILS P5.1 PLUMBING - PARTIAL FIRST FLOOR PLANS P10.1 PLUMBING ISOMETRIC DIAGRAMS REVISIONS N 00 00 N I Q� o °°� o 08 ��ti 5 NSa�'- c ►--� o o ro U , N ro '� it ¢ E ~' Q o �-" o=ti o E oa. N co 1 Z OV/ Z U W D LL 0 U ZO 00 U V c Z O .� U 04 Q. -X M -- NNNNJILIJ < H O � V o `s _ O 0 O U W c vi � O L0 CO r O M ImNNNNNI O N CL CL O Date: 06. 03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet Poe I EXISTING CORRIDOR rl-- --I ----� ---- - - - - ---------------------------- ------------------ , ----------L=-JJ---------- -- EXISTING 1 OFFICE x ,x EXISTING I I OFFICE �! I L1 EXISTING -----ILI------------ BREAKROOM ii i-------------i i ------------------- EXISTING EXISTING EXISTING EXISTING OFFICE OFFICE TOILET TOILET 1 2 2 EXIS ING =� JAN. __� 11 � I I I <, I I _- <\\ EXISTING EXISTING COMPUTER REPAIR OFFICE I i III I III I <\ I I I 11 EXISTING -- - -- �- OFFICE EXISTING III CONFERENCE ROOM I I I I I EXISTING EXISTING CORRIDOR SERVER ROOM -�J -_ --, I I I I I I EXISTING CORRIDOR I II I I EXISTING OFFICE E -- - - E EXISTITI NG OFFICE I EXISTING OFFICE `--' 1 II I L__I III i I I I Ij I -� EXISTING OFFICE - � 0 LLJ 0 OU, " z I I I I xU W Q EXISTING I II j CLEAN ROOM III I I I � I E� STING RECOVERY r' -- -- - -- - -- - -I I I PLUMBING - DEMOLITION - PARTIAL FLOOR PLAN ' II' SCALE: 3/16" = 1'-0" EXISTING CORRIDOR 1=x1CT1K1(, EXISTING MIXING ROOM I II II II II 1 II 11 11 I TEXISTINg EXISTING OFFICE ; �i I= TOILET II I ' O ' GXICTInI(; � UEXISTING EEWAITING [Ell EE L] [[_J I - I I L=J I Ll a EXISTING CORRIDOR -- --- ----aEI==-:D --: 3 C: -- - � C---� ---� j, l,�- _ -- -L-)' L _ _ -iJ V- _ _ -k-J lJ- _ _ -kJ lam- _ _ -�_J I 1 2 3 1 4 1 5 6 1 1 7 8 1 INFUSION 48'-6" x 29'-9" EXISTING I I EXISTING TOILET I I TOILET uLLJ1 u O I I I I EXITING 9F ICE I I I 11 i t -My�I I III _ � = J i EXISTING EXISTING SERVER ROOM CORRIDOR 13 1 I 1 1 10 11 12 ---I �_I 3„ 1 I I I I I I I I I I I C---� C---� C-� 2" SUPPLIES 9'-7" x 6'-8" , 14 15 1 16 17 UR E I --1---I --1 -- -1 ,-7,x -8" EXISTING OFFICE I 2"� I I I� LAB I 8'-7" x 10'-5" 1 2" I I EXISTING 1 CONFERENCE ROOM C MEDS 5'-0" x 10'-5" PXICTIAI(, EXISTING OFFICE EXISTING OFFICE ill ---I \ P-3 C 1 1/2" LSV II 1 /2" P-1 1 1 /2" 2" 77 1/2" 3/4"- 3/4 I �- _ 2" " P12 i I1,/2 IIII 1/2" 1' /2" I I I I I I I I I I I I I IPA EXISTING OFFICE 0 0 -__-----------------_--_—=_-__=-=J-__-_-_--=---- - - ----- xO IU) W c> I'1 X U CLEAN EXISTING W Q ROOM I I � I I I IIII, I I I E) �ISTING RECOVERY 1 - I it I I PLUMBING - NEW WORK PARTIAL FLOOR PLAN\ SCALE: 3/16" = 1'-0" GENERAL NOTES: CODED NOTES: O GENERAL NOTES: CODED NOTES: O A. PRIOR TO BID, CONTRACTOR SHALL VISIT SITE AND BECOME 1. REMOVE EXISTING PLUMBING FIXTURE. CAP EXISTING A. PRIOR TO BID, CONTRACTOR SHALL VISIT SITE AND BECOME 1. EXTEND NEW 3" SANITARY VENT PIPING TO EXISTING VENT FAMILIAR WITH -ALL EXISTING WORK UNDERGROUND AND ABOVE -- SANITARY BELOW SLAB. VALVE AND -CAP EXISTING WATER PIPING - - -- - - - -- - - FAMILIAR WITFTALL EXISTING WORK -UNDERGROUND -AND ABOVE— - - PIPING OR PROVIDE NEW 3"VENT THRUROOF.--FIELD VERIFY - - CEILINGS. COORDINATE ALL NEW WORK WITH EXISTING ABOVE CEILING. CEILINGS. COORDINATE ALL NEW WORK WITH EXISTING EXACT LOCATION. VENT SHALL BE MINIMUM 10 FEET FROM ANY CONDITIONS. FIELD VERIFY EXACT LOCATION OF NEW PIPE CONDITIONS. FIELD VERIFY EXACT LOCATION OF NEW PIPE OUTSIDE AIR INTAKE. ROUTING AND TIE-IN TO EXISTING LOCATIONS. 2. CLEAN AND REPAIR AS REQUIRED OR REPLACE AT OWNER'S ROUTING AND TIE-IN TO EXISTING LOCATIONS. DIRECTION EXISTING PLUMBING FIXTURES TO REMAIN. 2. EXTEND NEW 3/4" HWR, 1" HW AND 1" CW TO EXTEND MAINS OF B. FIELD VERIFY EXACT SIZE, ROUTING AND LOCATIONS OF B. FIELD VERIFY EXACT SIZE, ROUTING AND LOCATIONS OF EQUAL OR GREATER SIZE. FIELD VERIFY EXACT LOCATION. EXISTING SANITARY AND DOMESTIC WATER PIPING MAINS OR EXISTING SANITARY AND DOMESTIC WATER PIPING MAINS OR RISERS. RISERS. 3. EXTEND NEW 2" SANITARY UNDERGROUND TO EXISTING 4" OR LARGER SANITARY PIPING. FIELD VERIFY EXACT LOCATION AND C. SLOPE ALL SANITARY PIPING 3" AND LARGER AT MINIMUM 1/8" INVERTS. PER FOOT. SLOPE ALL 2" SANITARY PIPING AT MINIMUM 1/4" PER FOOT. FIELD VERIFY EXISTING EXACT INVERT ELEVATIONS. D. CLOSELY COORDINATE INSTALLATION OF PLUMBING WITH HVAC AND ALL OTHER TRADES. E. REFER TO ISOMETRIC DIAGRAMS ON SHEET P10.1 AND FIXTURE CONNECTION SCHEDULE ON SHEET P0.1 FOR ADDITIONAL SIZES. r FCO� 1 /2" 1 1/2" u)/ /2" 1/2" ' 'S' S 1" S Pr2 I 1 1 1 /2" 2"1 2" I�- I RSE 1 _ - - -- - 3/4" = T „ x 12'-8„ 8'-7" < 't � �I I� = U U) 1 I 2" EXISTING CORRIDOR 1/2" 433/4�" c /2" OF� 1 1 8'-7" x 9'-6" I I 11 I I II I I 1 EXISTING 1 I 1 RECEPTION I 1 0 FXICT1N1r_' EXISTING CLOSET EXISTING IA71 WAITING_ L—r L ICI C REVISIONS � � v N C Go M N .2 to '—• ¢ 0 0 7.1 td l� U yzti N ram. p • U po ro in ro U • N c- ¢ E ti ¢ °' °° 3 ti 3 ti 3 :D o '--• 0 � N M 1 Z 0 (n Z U W D I..L D (n U Z0 0 0 U U Z O .� U C4 0 � a M uxa Q Qa U _o m O u Lu ° _y L._ O L4) t CO O 0 CL a— O O ~ CL Oo_ J IL Date: 06. 03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet P501 DOMESTIC WATER ISOMETRIC DIAGRAM SCALE: 1 1/2" 1 1/2" SANITARYIVENT ISOMETRIC DIAGRAM SCALE: GENERAL NOTES: A. REFER TO FLOOR PLANS AND FIXTURE CONNECTION SCHEDULE ON DRAWING P0.0.1 FOR ADDITIONAL SIZES. B. PROVIDE CLEAN -OUTS ON SANITARY SEWER PIPING AT ALL CHANGES IN DIRECTION GREATER THAN 45 DEGREES AND METHOD OF CLEANOUT AT THE BASE OF EACH STACK AND AT EACH PLUMBING FIXTURE. 3. PROVIDE P-TRAPS ON ALL FLOOR DRAINS AND FLOOR SINKS, TYPICAL. PROVIDE AND INSTALL TRAP PRIMERS FOR ALL FLOOR DRAINS AND FLOOR SINKS. REFER TO GENERAL NOTES ON SHEET P0.0.1 FOR ADDITIONAL REQUIREMENTS. �.� NOEL k4 j O'e .� O ..•' LI CF . i '• S48 .(� F • • / 00 ti ENG\��`�� REVISIONS .fi Y M CO � I� Q O E a � � O V • O Fes+ it p cot[7 c�-d U • N ¢ E E o 3 ti 3 o ►—� ti o a.. N Z O (n z U w D V) U Z O O C) U V Z 0 .0 J V IT a) a K M - M -- Lu Q h a o V 0 0 m 0 Ae u Lu � a C N 0 NO GO s O �"� ID. O ~ CL 0 a J LL. Date: 06. 03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet P1091 AIR TERMINAL SCHEDULE SYMBOL ADAPTER/NECK SIZE FACE SIZE MAX CFM MAX NC MAX SP THROW RUNOUT SIZE MANUFACTURER/MODEL NO. E-EX --- --- --- --- --- --- --- EXISTING TO REMAIN EB 8"x8" 241lx24" 200 28 .05 --- 8" 0/10"x6" TITUS 50-F WITH EGG -CRATE CORE R-EX --- --- --- --- --- --- --- EXISTING TO REMAIN RPA --- 12"x12" 300 --- --- --- --- TITUS 50-F WITH EGG -CRATE CORE RPB --- 241lx24" 1500 --- --- --- --- TITUS 50-F WITH EGG -CRATE CORE S-EX --- --- --- --- --- --- --- EXISTING TO REMAIN SA 6" 0/6"x6" 12"x12" 75 20 .07 4-WAY BLOW 6" 0/8"x4" TITUS TDC SB 8' Q1/9"x9" 241lx24" 230 20 .07 4-WAY BLOW 8" 0/10"x6" TITUS TDC AIR TERMINAL PERFORMANCE NOTES: 1. CONTRACTOR TO USE DUCT SPIN -IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL TO GENFLEX MODEL SM-2DEL OR APPROVED EQUAL. 2. FACE SIZE FOR CEILING MOUNTED AIR TERMINALS SHALL BE 24"x24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN GRIDS UNLESS OTHERWISE SPECIFIED. 3. ALL LINEAR SLOT DIFFUSERS SHALL BE CONCEALED MOUNT TYPE WITH ADJUSTABLE DISCHARGE. 4. PROVIDE INSULATED PLENUM - MPI-38 FOR ALL LINEAR SLOT DIFFUSERS. CODE CRITERIA: NOTE: A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY OR MAY NOT APPLY TO THIS PROJECT. B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER. NFPA-70 (2011) NATIONAL ELECTRICAL CODE N F PA-72 (2010) NATIONAL FIRE ALARM CODE NFPA-90A (2012) INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS NFPA-90B (2012) INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS NFPA-91 (2010) EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND NON-COMBUSTIBLE PARTICULATE SOLIDS NFPA-96 (2011) VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING OPERATIONS. NFPA-101 (2012) LIFE SAFETY CODE FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014) FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014) FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014) FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE ZONES 5TH EDITION (2014) FLORIDA BUILDING CODE, FUEL GAS 5TH EDITION (2014) FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014) FLORIDA ACCESSIBILITY CODE (2014) APPLICABLE STATE ENERGY CODE (2014) STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60. NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE BUILDING AND MECHANICAL OR PLUMBING CODES, IT WILL BE ASSUMED THAT THE BUILDING CODE TAKES PRECEDENCE. MECHANICAL LEGEND: MEDIUM PRESSURE TEE RECTANGULAR DUCT TURNING DOWN ROUND DUCT TURNING DOWN DUCT TURNING DOWN TO SIDEWALL REGISTER DOUBLE LINE TO DUCTWORK DUCT LINER IN LOW PRESSURE DUCT OR DOUBLE WALL INSULATED MEDIUM PRESSURE DUCT BRANCH TAP OFF MAIN W/450 BOOT FITTING OR SPIN -IN FITTING W/DAMPER (LOW PRESSURE) TRANSITION IN DUCT (NOT DIRECTION OF AIRFLOW) REGISTER TAPPING INTO BOTTOM 11 OF DUCT FD ® FIRE DAMPER ® FIRE/SMOKE DAMPER FSD DUCT SMOKE DETECTOR SD SMOKE DETECTOR AD ACCESS DOOR AFF ABOVE FINISHED FLOOR BFC BELOW FINISHED FLOOR VFD VARIABLE FREQUENCY DRIVE TAD TRANSFER AIR DUCT TAO TRANSFER AIR OPENING BAS BUILDING AUTOMATION CONTROL SYSTEM © PRESSURE SENSOR MD MOTORIZED DAMPER DUCT TERMINATION 450 FULL RADIUS TURN SQUARE ELBOW jj W/TURNING VANES FULL RADIUS TURN CO CO2SENSOR OTHERMOSTAT OH HUMIDISTAT MVDF MANUAL VOLUME DAMPER VAV VARIABLE VOLUME BOX EA INDICATES A SIZE "A" EXHAUST 100 REGISTER SET FOR 100 CFM RB INDICATES A SIZE "B" RETURN 200 REGISTER SET FOR 200 CFM SB INDICATES A SIZE "B" SUPPLY 200 DIFFUSER SET FOR 200 CFM ® SUPPLY DIFFUSER zRETURN GRILLE ® EXHAUST GRILLE UNDERCUT DOOR 3/4" UNLESS OTHERWISE NOTED PIPING LEGEND: CD MOISTURE CONDENSATE DRAIN LINE L REFRIGERANT LIQUID S REFRIGERANT SUCTION HGR HOT GAS REHEAT -� DIRECTION OF WATER FLOW PIPE TURNING DOWN PIPE TURNING UP PIPE SHUT OFF VALVE MECHANICAL GENERAL NOTES: CONTRACT REQUIREMENTS AFFECTING ALL TRADES: IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR AND EACH SUBCONTRACTOR TO REVIEW ALL DRAWINGS TO ASSURE COORDINATION OF ALL WORK AFFECTING EACH TRADE. 1. FIBERGLASS DUCT INSULATION SHALL NOT PENETRATE RATED WALLS. SPACE BETWEEN STUDS, HEADERS AND DUCT SHALL BE PACKED WITH MINERAL FIBER SAFING INSULATION. WHERE A FIRE DAMPER IS REQUIRED THE SPACE BETWEEN THE SLEEVE AND THE STUDS OR HEADERS SHALL BE OF THE PROPER CLEARANCE FOR THE SIZE OF THE DUCT IN ACCORDANCE WITH SMACNA REQUIREMENTS. FIRE DAMPER SLEEVES SHALL BE INSTALLED AND SECURED IN ACCORDANCE WITH SMACNA STANDARDS. FIRE DAMPERS SHALL BE INSTALLED IN THE PLANE OF THE RATED ASSEMBLY AND BE U.L. LISTED AS AN ASSEMBLY COMPLYING WITH U.L. 555. 2. CONTRACTOR SHALL FURNISH AND INSTALL ACCESS PANELS IN WALLS, NON -ACCESSIBLE CEILINGS, DUCTWORK AS REQUIRED AND ELSEWHERE AS INDICATED ON CONTRACT DOCUMENTS WHERE SERVICE ADJUSTMENT TO MECHANICAL, PLUMBING OR ELECTRICAL EQUIPMENT IS REQUIRED. 3. COORDINATE INSTALLATION OF PLUMBING, VENT STACKS AND CONDUIT TO PERMIT INSTALLATION OF RECESSED TOILET ACCESSORIES, FIRE EXTINGUISHER CABINETS AND OTHER RECESSED EQUIPMENT. WHERE SUCH ITEMS ARE RECESSED IN CORRIDOR, SMOKE OR FIRE/SMOKE WALLS THEY SHALL BE INSTALLED IN A FIVE -SIDE ENCLOSURE. 4. THE CONTRACTOR SHALL ASSEMBLE A LOG OF CERTIFICATES AND INSPECTIONS ORGANIZED IN C.S.I. FORMAT PRIOR TO FINAL INSPECTION INCLUDING MANUFACTURER'S CERTIFICATION OF FLAME SPREAD, SMOKE AND RADIANT PANEL TEST, AND CERTIFICATE OF TESTS FOR MEDICAL GAS, RADIATION SHIELDING, HVAC TEST AND BALANCE, FIRE ALARM, FIRE PUMP, EMERGENCY GENERATOR, ETC. AS APPLICABLE TO THE PROJECT AND MAKE AVAILABLE AT FINAL INSPECTION. 5. CONTRACTOR SHALL VERIFY CONSTRUCTION IS COMPLETE AND IN ACCORDANCE WITH THE CONTRACT DOCUMENTS PRIOR TO FINAL INSPECTION. NOTIFY THE DESIGNER PRIOR TO INSPECTION OF ANY DEFICIENCIES OBSERVED. 6. CONTRACTOR SHALL SEAL ALL METAL JOINTS WITH GLASSFAB AND MASTIC PRIOR TO INSTALLATION OF INSULATION AND PRESSURE TEST DUCTWORK FOR LEAKAGE. 7. MANUAL VOLUME DAMPERS SHALL BE PROVIDED AT ALL RUNOUTS TO SUPPLY AIR DIFFUSERS, RETURN AIR REGISTERS, EXHAUST AIR REGISTERS, DIVISIONS IN DUCTWORK (SUPPLY, RETURN AND EXHAUST), AND ELSEWHERE NOTED ON PLANS AND IN SPECIFICATIONS FOR BALANCING SYSTEM. DAMPERS IN REGISTERS GRILLES AND DIFFUSERS ARE PROVIDED FOR FINAL ADJUSTMENTS DURING TEST AND BALANCING. DO NOT RELY ON DISTRIBUTION DEVICE DAMPERS FOR SYSTEM BALANCING. 8. COORDINATION OF ALL TRADES IS OF THE UTMOST IMPORTANCE. CEILING SPACE TO ROUTE WORK IN IS MINIMAL AT BEST. CONTRACTOR SHALL LAY OUT SYSTEMS IN CONJUNCTION WITH ALL TRADES TO AVOID CONFLICTS PRIOR TO INSTALLATION OF WORK. 9. PLUMBING VENT STACKS AND HVAC EXHAUST SHALL BE KEPT A MINIMUM OF 25' FROM ANY OUTSIDE AIR INTAKE. OUTSIDE AIR INTAKE MAY BE AS CLOSE AS 10' AWAY FROM EXHAUST FOR NON -HEALTHCARE FACILITIES. 10. CONTRACTOR SHALL REVIEW PLACEMENT OF ALL HVAC EQUIPMENT ON ROOF WITH STRUCTURAL DRAWINGS PRIOR TO INSTALLATION. 11. PROVIDE SEALED ROOF CURB AROUND ALL DUCTWORK AND PIPING PENETRATIONS THRU ROOF. 12. CONTRACTOR SHALL MAINTAIN A MINIMUM OF 6" CLEARANCE BETWEEN DUCTWORK, PIPING, AND ANY PRIORITY WALLS (TWO HOUR FIRE, TWO HOUR FIREISMOKE, ONE HOUR SMOKE). 13. PROVIDE ACCESS DOORS IN DUCTWORK FOR FIRE DAMPERS, REHEAT COILS, DUCT MOUNTED SMOKE DETECTORS, AND ELSEWHERE WHERE SERVICE OR ADJUSTMENT TO MECHANICAL, PLUMBING OR ELECTRICAL EQUIPMENT IS REQUIRED. 14. PROVIDE "YOUNG" REMOTE VOLUME REGULATOR FOR ALL DAMPERS LOCATED ABOVE INACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FINISH SCHEDULE FOR CEILING TYPES. 15. ALL OUTSIDE AIR INTAKES ON ROOF SHALL BE KEPT A MINIMUM OF 36" ABOVE ROOF FOR HEALTHCARE FACILITIES, 12" FOR NON -HEALTHCARE. PROVIDE DUCTWORK OR CURB EXTENSIONS AS NECESSARY TO PROVIDE CLEARANCE. 16. INSTALL SMOKE DETECTORS IN RETURN AIR DUCTWORK (PRIOR TO DILUTION OF OUTSIDE AIR) AND SUPPLY AIR DUCTWORK WITH SAMPLING TUBES IN AIRSTREAM ACCORDING TO MANUFACTURER'S INSTALLATION REQUIREMENTS. FOR ALL DUCT MOUNTED SMOKE DETECTORS PROVIDE AN AIR DIFFERENTIAL TEST ACROSS DETECTOR SAMPLING TUBES, RELOCATE OR ADJUST THE SAMPLING TUBES WHERE NECESSARY TO PROVIDE AN AIR DIFFERENTIAL WITHIN THE ACCEPTABLE RANGE ESTABLISHED BY THE MANUFACTURER. RESULTANT TEST DATA SHALL BE MADE AVAILABLE AT THE FINAL SURVEY AND WILL BE INCLUDED IN LOG OF CERTIFICATES. DUCT MOUNTED SMOKE DETECTORS TO BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. 17. MAINTAIN THE CLEAR SPACES AROUND, OVER AND UNDER EQUIPMENT, ELECTRICAL PANELS, SYSTEMS AND SYSTEM COMPONENTS IN CEILING CAVITIES NECESSARY FOR CONVENIENT OBSERVATION, OPERATION AND MAINTENANCE. PAY SPECIAL ATTENTION TO ACCESS TO FIRE DAMPERS, FIRE AND SMOKE DAMPERS, DUCT SMOKE DETECTORS, ELECTRIC DUCT HEATER CONTROLS, FILTER ACCESS DOORS, MEDICAL GAS VALVES, FIRE PROTECTION SYSTEM VALVES, ETC. DO NOT INSTALL DUCTWORK OR PIPING OF ANY KIND ABOVE ELECTRICAL PANELS PER NEC. COORDINATE AND FIELD VERIFY FINAL LOCATION OF ELECTRICAL PANELS WITH ELECTRICAL CONTRACTOR BEFORE INSTALLATION OF DUCTWORK AND PIPING. 18. DO NOT INSTALL EQUIPMENT, SYSTEMS OR SYSTEM COMPONENTS WHERE THEY MAY ENCROACH ON THE CLEAR SPACES NECESSARY FOR OPERATION OR MAINTENANCE OF ITEMS INSTALLED BY OTHER TRADES WITHOUT CONFIRMING THAT THE CLEAR SPACE REQUIREMENTS OF THE OTHER TRADE WILL BE MAINTAINED. 19. WHERE THE WORK OF OTHER TRADES MAY ENCROACH ON CLEAR SPACES REQUIRED FOR WORK INSTALLED UNDER THESE SECTIONS, COORDINATE WITH THE OTHER TRADES AND THE GENERAL CONTRACTOR TO MAINTAIN THE REQUIRED CLEAR SPACES. 20. PRIOR TO THE FINAL INSPECTION, DEMONSTRATE TO THE OWNER THAT ACCESS AND CLEAR SPACES FOR ALL INSTALLED ITEMS THAT REQUIRE ROUTINE OBSERVATION, OPERATION AND MAINTENANCE HAVE BEEN MAINTAINED. 21. MECHANICAL EQUIPMENT AND PIPING INSTALLED ON ROOF SHALL BE SECURED TO MEET FBC WIND LOADING REQUIREMENTS. 22. UNLESS SPECIFIED BY THE ARCHITECT, EXTERIOR AIR LOUVERS SHALL BE RUSKIN MODEL ELF6375DXD (NOA 12-0601.22) OR APPROVED EQUAL CONSTRUCTED OF EXTRUDED ALUMINUM WITH INSECT SCREEN. DUCT CONNECTION SHALL BE SLOPED TOWARD EXTERIOR. 23. ALL THROUGH PENETRATTION FIRESTOP SYSTEMS SHALL BE INSTALLED BY AN EXPERIENECED INSTALLER PER THE MANUFACTURERS INSTALLATION INSTRUCTIONS. 24. REFER TO SPECIFICATIONS SECTION 15890 AND 15910 FOR SHEETMETAL - LOW PRESSURE DUCTWORK AND SHEETMETAL SPECIALTIES MATERIAL, SEALING AND INSTALLATION REQUIREMENTS. MECHANICAL GENERAL NOTES CONT.:1 25. REFER TO SPECIFICATIONS SECTION 15250 FOR DUCT AND REFRIGERANT PIPING INSULATION MATERIAL, SEALING AND INSTALLATION REQUIREMENTS. 26. PROVIDE COMMISSIONING OF NEW HVAC SYSTEMS OVER 40 TON TOTAL CAPACITY PER FLORIDA ENERGY EFFICIENCY CODE. 27. MECHANICAL EQUIPMENT SHALL NOT BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS. MECHANICAL EQUIPMENT AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES IN ACCORDANCE WITH FLORIDA BUILDING CODE. HIGH WIND PROTECTION OF EQUIPMENT: IN COMPLIANCE WITH FMC-301.15; MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH FBC. APPLIANCES SHALL NOT BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL DAMAGE UNLESS PROVIDED WITH PROTECTION FROM HIGH -VELOCITY IMPACT IN ACCORDANCE WITH FMC-303.4. THE PROTECTIVE BARRIER MUST BE TESTED AND LABELED AS MEETING THE HIGH -VELOCITY IMPACT TEST OF FBC SECTIONS 1626.2 OR 1626.3 OR MUST BE ONE OF THE FOLLOWING: 1. EXTERIOR CONCRETE MASONRY WALLS OF MINIMUM NOMINAL 8-INCH THICKNESS, CONSTRUCTED IN ACCORDANCE WITH CHAPTER 21 (HIGH - VELOCITY HURRICANE ZONES) OF FBC. 2. EXTERIOR FRAME WALLS OR GABLE ENDS CONSTRUCTED IN ACCORDANCE WITH CHAPTER 22 AND CHAPTER 23 (HIGH -VELOCITY HURRICANE ZONES) OF FBC, SHEATHED WITH A MINIMUM 19/32-INCH CD EXPOSURE 1 PLYWOOD AND CLAD WITH WIRE LATH AND STUCCO INSTALLED IN ACCORDANCE WITH CHAPTER 25 OF FBC. 3. EXTERIOR FRAME WALLS AND ROOFS CONSTRUCTED IN ACCORDANCE WITH CHAPTER 22 (HIGH -VELOCITY HURRICANE ZONES) OF FBC SHEATHED WITH A MINIMUM 24-GAGE RIB DECK -TYPE MATERIAL AND CLAD WITH AN APPROVED WALL FINISH. 4. EXTERIOR REINFORCED CONCRETE ELEMENTS CONSTRUCTED OF SOLID NORMAL WEIGHT CONCRETE (NO VOIDS), DESIGNED IN ACCORDANCE WITH CHAPTER 19 (HIGH -VELOCITY HURRICANE ZONES) OF FBC AND HAVING A MINIMUM 2-INCH THICKNESS. 5. ROOF SYSTEMS CONSTRUCTED IN ACCORDANCE WITH CHAPTER 22 OR CHAPTER 23 (HIGH -VELOCITY HURRICANE ZONES) OF FBC, SHEATHED WITH A MINIMUM 19/32-INCH CD EXPOSURE 1 PLYWOOD OR MINIMUM NOMINAL 1- INCH WOOD DECKING AND SURFACED WITH AN APPROVED ROOF SYSTEM INSTALLED IN ACCORDANCE WITH CHAPTER 15 OF FBC. ALL CONNECTORS SHALL BE SPECIFIED BY THE BUILDING STRUCTURAL DESIGNER OF RECORD FOR ALL LOADS EXCEPT IMPACT. GENERATOR FUEL OIL TANK ENCLOSURE, PIPING, VALVES, AND OTHER APPURTENANCES SHALL BE SECURED AND PROTECTED FOR CONTINUED OPERATION AND HAVE HURRICANE WIND RESISTANCE AND HURRICANE DEBRIS IMPACT PROTECTION DESIGNED BY A STRUCTURAL ENGINEER TO COMPLY WITH FBC. PRIOR TO FINAL ACCEPTANCE OF PROJECT, GENERAL CONTRACTOR SHALL PROVIDE WIND RESISTANCE AND HIGH -VELOCITY IMPACT PROTECTION DESIGN DOCUMENTS THAT ARE SIGNED, SEALED, AND DATED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF FLORIDA IN COMPLIANCE WITH FBC. PROJECT COORDINATION NOTES: THE CONSTRUCTION PHASING OF THIS PROJECT IS OF THE UTMOST IMPORTANCE. ALL CONTRACTORS FOR ALL DIVISIONS OF THE WORK SHALL GUARANTEE THAT THEIR WORK IS IN ACCORD WITH THE PHASING PLANS SHOWN IN THE ARCHITECTURAL CONTRACT DOCUMENTS. SHOULD IT BE NECESSARY TO ACCOMPLISH WORK IN AREAS WHICH ARE NOT INCLUDED IN THE PHASING PLANS, SUCH WORK SHALL BE DONE WITH THE MINIMUM OF DISTURBANCES THAT IS POSSIBLE AND WITHOUT CAUSING THE INTERRUPTION OF EXISTING SERVICES. ALL SERVICE INTERRUPTIONS THAT ARE ESSENTIAL TO THE WORK SHALL BE SCHEDULED WITH THE ARCHITECT AND, THEREBY, WITH THE OWNER. ALL CONTRACTORS FOR ALL TRADES SHALL COOPERATE AND COORDINATE THEIR WORK TO ALLOW THE COMPLETION OF ALL WORK WITH THE LEAST POSSIBLE NUMBER ON INTERFERENCE'S WITH THE SERVICES OF THE EXISTING BUILDING. THE DESIGN DRAWINGS OF ALL CATEGORIES AND TRADES (ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, MEDICAL GAS, MECHANICAL, HEATING, VENTILATING AND AIR CONDITIONING AND ELECTRICAL) AND ALL SPECIFICATIONS AND SHOP DRAWINGS MUST BE COORDINATED AND BE VIEWED IN CONNECTION AND CONJUNCTION WITH EACH OTHER TO INSURE THE PROPER LOCATION OF ALL DEVICES AND EQUIPMENT. MAKE PARTICULAR NOTE OF LOCATIONS AND DIMENSIONS SHOWN ON THE ARCHITECTURAL FLOOR PLANS AND ELEVATIONS. M0.1 MECHANICAL - LEGEND, NOTES, ETC... M5.1 HVAC - PARTIAL FIRST FLOOR PLANS M12.1 MECHANICAL - SCHEDULES M14.1 MECHANICAL - DETAILS M14.2 MECHANICAL - DETAILS REVISIONS v . v N 00 Y N CM F v ro ti u � vi " E x it o C: g C5 u • N t ¢ E Qom_. o 00 I-� 0 = N 3 o o a N Z OV/ z U W L.L F V) U ZO 00 U V_ c Z O .� J a V C4 4)M J Wx n- Q a � o V sn m O U Lu C a H O Wz d Q �• CO t O M N Q. O � ~ L Oa. J LL. Date: 06. 03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet Mo* I S-EX R-EX _ EXISTING H+E -,_ _ =0F„Ft�F,EXISC7 S-EX - S-EX 0FFI(I S-EXv 3 ��� I \( !S-EX Zj iL � EXISTING---/�- ------� I -- -' ^ , r--------- BREAKROOM- Ili I I � I I x 7 S-EX -----Ii I S-EX /\ I FD I �xlslrlc EXISTG EXISTING FFICE OFFICE TOILET II 3 I I -. EXIS11 � II I I I I I I <\ 11 \\ II I ------ � I FD IIIFD r FD ��- EXISTING RECOVERY 1 HVAC - DEMOLITION - PARTIA SCALE: 3/16" = V-0" I L FLOOR PLAN CODED NOTES: A. PRIOR TO BID, MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND _ THE REQUIREMENTS TO RENOVATE THE SYSTEM PER THE NEW WORK PLAINS. EXISTING WORK SHOWN 01 THE PLANS AS BASED ON AS -BUILT DRAWINGS AND ARE, IN PART, UNVERIFIED. CODED NOTES: 0 1. HATCHED AREA INDICATES SCOPE OF DEMOLITION WORK, ABOVE AND BELOW CEILING. MECHANICAL CONTRACTOR IS TO REMOVE ALL HVAC EQUIPMENT AND ANY ASSOCIATED DUCTWORK, PIPING, CONTROLS, ETC. THAT SERVES THIS SPACE ONLY. DO NOT REMOVE ANY EXISTING WORK THAT SERVES SPACES OUTSIDE THE HATCHED AREA. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF DEMOLITION WORK. MECHANICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING AND FIRE SPRINKLER CONTRACTORS TO VERIFY EXISTING PIPING ABOVE CEILING TO REMAIN THAT MAY NEED TO BE REWORKED TO ALLOW FOR INSTALLATION OF NEW HVAC WORK. TYPICAL. 2. HVAC SYSTEMS SERVING THIS AREA ARE EXISTING TO REMAIN. IF ANY PART(S) OF THE EXISTING HVAC SYSTEMS SERVING THIS SPACE IS WITHIN THE SCOPE OF DEMOLITION PER CODED #1, THOSE PARTS SHALL REMAIN IN SERVICE AND/OR BE RELOCATED AS REQUIRED. TYPICAL. 3. REMOVE AND DISPOSE OF DUCTWORK, DAMPERS, AIR DEVICES, AND CONTROLS AS INDICATED BY BOLD, DASHED LINES. TYPICAL. 4. REMOVE SUPPLY GRILLE IN EXISTING OFFICE AND CAP SUPPLY AT MAIN. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS. EXISTING CLEAN ROOM I,I ,.I EXISTING 1-1 R-EX S-EX 40 I I I I i I I I I f I I I I f E. ISTING RECOVERY HVAC - NEW WORK PARTIAL FLOOR PLAN SCALE: 3/16" = V-0" GENERAL NOTES: A. COORDINATE INSTALLATION OF NEW DUCTWORK WITH EXISTING SYSTEMS ABOVE CEILING. FIELD VERIFY ALL CONDITIONS PRIOR TO DUCT FABRICATION AND NOTIFY ENGINEER OF ANY UNFORSEEN CONFLICTS. CODED NOTES: 0 1. REBALANCE EXISTING RTU TO SCHEDULED AIRFLOW. VERIFY OPERATION OF DUCT MOUNTED SMOKE DETECTORS. REVISIONS �—, �00 00 y N � Z.0 U U. 70 Lw � 'u ro t-- a=ti v m • p • U C' rn ro U • ` ¢d E tiLo o = ti o ►—� r- V � n� F� N C") Z V V) Z U W :D L.L (n U Z 0 00 U V Z 0 .� V C4 `� a X J M M Lu a by o V O u Lu v , N W)• O :E Nt O CO C fl. N- C. 0 J LL Date: 06.03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet M50 I EXHAUST FAN SCHEDULE MARK --- EF1.1 AIR QUANTITY CFM 200 E.S. P. IN. H2O 0.25 FAN TYPE --- CENTRIFUGAL FAN SPEED RPM 1694 DRIVE TYPE --- I DIRECT INTERLOCK - --- RTU-1 SOUND CRITERIA SONES 5.5 MOTOR POWER HP 1/10 TIP SPEED FPM 3604 ELECTRICAL V/PHIHZ 115/1/60 UNIT LOCATION --- ROOF UNIT MANUFACTURER --- GREENHECK UNIT MODEL NO. --- G-065-VG AREA SERVED --- ONCOLOGY LAB MECHANICAL SYSTEMS SUMMARY SHEET PROJECT NAME: FLORIDA MEDICAL CLINIC - ZEPHYRHILLS ONCOLOGY EXPANSION PROJECT OWNER: FLORIDA MEDICAL CLINIC PROJECT ADDRESS: 38135 Market Square Zephyrhills, Florida 33542 TOTAL AREA: 3,124 SQ. FT. DESIGN CRITERIA OUTDOOR AIR SUMMER TEMP DB/WB 937/78`'F OUTDOOR AIR WINTER TEMP DB 340F INDOOR AIR TEMP DB 750F INDOOR HUMIDITY 50-60%RH BUILDING ENVELOPE CMU WALL + INSULATION R-11 METAL ROOF + INSULATION R-19 WINDOW, MEDIUM SOLAR GRAY TINT U-0.41 WINDOW SHADING COEFFICIENT SHGC-0.25 ENVELOPE CONDITIONS PRESENTED FOR REFERENCE ONLY REFER TO ARCHITECTURAL PLANS FOR ACTUAL CONSTRUCTION. SIZING METHOD ASHRAE COMPUTER PROGRAM + SUPPLEMENTAL CALCULATIONS TOTAL COOLING REQUIRED WITH OUTSIDE AIR 116,089 BTUH TOTAL SENSIBLE GAIN 88,484 BTUH TOTAL LATENT GAIN 27,605 BTUH TOTAL GRAINS WATER DEHUMIDIFICATION 19.0 GRAINS HEATING 12.0 KW TOTAL HEATING REQUIRED WITH OUTSIDE AIR 40,956 BTUH 5/25/16 2:36 PM SCHEDULE NOTES: 1. INSULATED ALUMINUM ROOF CURB, DISCONNECT SWITCH, AND BACKDRAFT DAMPER FOR ROOF MOUNTED EXHAUST FANS. 2. EXHAUST FANS SHALL BE WIRED SUCH THAT THEY RUN CONTINUOUSLY WITH RESPECTIVE AIR HANDLING UNIT. 3. FOR PURPOSES OF FIRE CONTROL ALL FANS ARE TO BE INTERLOCKED - WITH AIR HANDLING UNIT INDICATED ON SCHEDULE. IF AIR HANDLING UNIT IS SHUT DOWN MANUALLY OR BY THE FIRE ALARM SYSTEM THEN RESPECTIVE EXHAUST FANS SHALL SHUT DOWN. ROOF MOUNTED FANS SHALL BE CONSTRUCTED AND INSTALLED FOR IGH WIND APPLICATION TO MEET FBC WIND LOAD REQUIREMENTS. IANUFACTURER SHALL PROVIDE SIGNED AND SEALED STRUCTURAL PLANS OR SECUREMENT TO STRUCTURE. VARIABLE AIR VOLUME BOX SCHEDULE WITH ELECTRIC HEAT ON SELECT BOXES EXISTING SCHEDULE NOTES. - BASIS OF DESIGN: PRICE PROVIDE: PRESSURE INDEPENDENT, DOUBLE WALL CONSTRUCTION WITH 3/4" 4LB/FT3 INSULATION COORDINATE WITH CONTROL SYSTEM INSTALLER FOR APPROPRIATE SELECTION OF THERMOSTATS AND COORDINATE WITH TEMPERATURE CONTROL SYSTEM FOR DDC OPERATION. CONTROL SYSTEM SUPPLIER WILL PROVIDE DDC CONTROLLERS FOR FACTORY INSTALLATION. PROVIDE ACCESS AND NECESSARY CLEARANCE FOR MAINTENANCE. WHERE RUNOUT SIZE IS SHOWN ON DRAWING, FOLLOW DRAWING OTHERWISE PROVIDE MIN. CONNECTION SIZE SHOWN. EQUIVALENT RECTANGULAR DUCT SIZES MAY BE USED. PROVIDE FACTORY MOUNTED HEAVY DUTY DISCONNECTS OR REMOTE DISCONNECTS WHERE REQUIRED. MARK B1.1 B1.2 B1.3 B3.28 AREA SERVED INFUSION CONFERENCE OFFICES EXAM RMS TOTAL AIR CFM 1540 1040 950 575 HEATING AIR CFM 616 416 380 345 MANUFACTURER Price Price Price Price MODEL NO. SDV Size -12 SDV Size -10 SDV Size -10 SDV Size -8 MAX. UNIT PD IN. WC 0.8 0.8 0.8 0.8 MIN. INLET SP IN. WC 0.05 0.04 0.03 0.03 UNIT INLET SIZE 12"%%C 10"0/00/0C 10"%0/0C 8"%%C MIN. DUCT RUNOUT FROM MAIN 16"0/60/aC 14"%%C 14"%%oC 12"%%C ENTERING AIR TEMP%%DF 60 60 50 60 LEAVING AIR TEMP %%DF HEAT 90 90 90 90 HEATING CAPACITY KW 5 3 3 3 STEPS CONTROL SCR SCR SCR SCR ELECTRICAL - VIPH 277/1 27711 277/1 277/1 AMPS 1 18.05 1 10.83 1 10.83 1 10.83 5/31116 9:22 AM EXISTING PACKAGE ROOFTOP UNIT SCHEDULE SCHEDULE NOTES: MARK RTU-1 RTU-1 ADJUSTED RTU-3 RTU-3 ADJUSTED COOLING CAPACITY MBH 229 116 460 460 SENSIBLE CAPACITY MBH 89 SUPPLY AIR MAX CFM 5600 3530 12,000 12,000 OUTSIDE AIR MAX CFM 560 445 1200 1200 EXTERNAL STATIC PRESSURE IN. WTR 2.0 2.0 EVAPORATOR FAN MOTOR HP 5 15 MAX. FAN SPEED RPM 800 875 ENT. COIL AIR TEMP. DBIWB OF/OF 81/67 81/67 LVG. COIL TEMP. DBIWB °F/°F 54/53.8 54.8/54.8 AMBIENT CONDENSER TEMP. OF 95 95 ELECTRIC HEAT KW NONE NONE FILTER EFFICIENCY % 30% 30% FILTER THICKNESS INCHES 2" 2" ELECTRICAL V/PHIHZ 460/3160 460/3/60 MINIMUM CIRCUIT AMPACITY A 53 100 MAX. OVERCURRENT PROTECT. A 60 125 DIMENSIONS LxWxH IN. OPERATING WEIGHT LBS LOCATION ROOF ROOF MANUFACTURER TRANE TRANE MODEL TCH240 MANUFACTURE DATE 08/94 AREA SERVED ONCOLOGY SPEC. DIV. 5/25/16 2:39 PM Building: FMC, ZEPHYRHILLS - ONCOLOGY EXPANSION RTU-1 System Tag/Name: maximum cooling Operating Condition Description: Units (select from pull -down list) IP w/o diversity w/ diversity Inputs for System Name Units System Diversity F-Systern Check Figures Floor area served by system Population of area served by system As PS sf 3,024 P 44 D 60% 26 8.7 P/1000 sf Design primary supply fan airflow rate Vpsd cfm 3,390 D 70% 2,373 0.78 cfm/sf OA req'd per unit area for system (Weighted average) Ras cfm/sf 0.06 0.06 ave cfm/sf OA re 'd per person fors stem area (Weighted average) R s cf m/p 5.0 5.00 ave cfm/p Outdoor air intake provided for system OA cfm Inputs for Potentially Critical zones Potentially Critical Zones Zone Name Zone title turns purple italic for critical zone(s) 61.1 B1.2 BA2.3 Totals/averages Zone Tag Waiting Conference Offices Occupancy Category Select from pull -down list: Offices ace Offices ace Offices ace Floor Area of zone Az sf 1,242 788 994 3,024 total sf Design population of zone Pz P (default value listed,- may be overridden_) 20 17 7 44 total P Design total supply to zone (primary plus local recirculated) Vdzd cfm 1,500 1040 850 3,390 total cfm Induction Terminal Unit, Dual Fan Dual Duct or Transfer Fan? Select from pull -down list or leave blank if N/A: Frac. of local recirc. air that is representative of system RA Er 1.00 average Inputs for Operating Condition Analyzed Percent of total design airflow rate at conditioned analyzed Ds % 30% 30% 30% 30% 30% average Air distribution type at conditioned analyzed Select from pull -down list: CSCRH CSCRH CSCRH Zone air distribution effectiveness at conditioned analyzed Ez 0.80 0.80 0.80 0.80 average Primary air fraction of supply air at conditioned analyzed Ep 1.00 average Results of Minimum ASHRAE 62.1 Ventilation Rate Procedure (EQp1) System Ventilation Efficiency Ev 0.91 Outdoor air intake required for system (EQp1) Vot cfm 344 Outdoor air per unit floor area VotfAs cfm/sf 0.11 Outdoor air per person served by system (including diversity) VotlPs cfm/p 13.0 Outdoor air as a % of design primary supply air Ypd % 10% OP�\EL L I C F�.•••2 No $4 tS'�•N =0: :D- �-n• �O D OAS gS116 REVISIONS f, • 0' y 00 N C� O E N C ./ .� it o � • E O O1, U • N -L ¢ E o �--� ti ��i N C� 1 u C� Fz (n _O Z U L.LJ (n U ZO 00 U U_ c Z O .H J U CV WM X- _J M- - LU U O O u LU ° _H � O M 00 t O M Q O ~ 6- CL 0 J 1.1.. Date: 06.03. 16 Scale: AS NOTED Project Mgr: DAN Drawn: DEG Job: 16-062 Sheet M12*1 ALL ELBOWS TO BE FULL RADIUS OR TO BE PROVIDED WITH TURNING VANES. MEDIUM PRESSURE RUN MIN. 4'-0" STRAIGHT DUCT. TRUNK DUCT PRIOR TO ANY TRANSITIONS OR TAKE -OFF. REHEAT BOX MANUAL VOLUME DAMPER \ (TYP) LOCATED AS CLOSE TO THE TAP AS POSSIBLE. SHEET METAL BOOT NOTE #3 INSIDE CLEAR 12" PROVIDE A MIN. OF 2-90 PRESSURE DIMINSION SHALL BE MIN. DEG. TURNS FROM DUCT DUCT AS INDICATED ON MAIN TO EACH AIR REGISTER RUN -OUT DEVICE. -- � CONTROL PANEL SCHEDULE.00 CONICAL TAP NOTE #4 RETURN AIR FITTING 1/2"INTERNAL TO RETURN ROUND DUCT. NOTE #2 SOUND LONER PLENUM SEE SPECIFICATIONS REFER TO VARIABLE AIR FOR ACCEPTABLE TAPS. VOLUME BOX SCHEDULE MAXIMUM 30 DEGREE FOR RUNOUT SIZE. TRANSITION LAY -IN CEILING MIN. 4'-0"/MAX. TYPICAL AIR FLOW FOR FLEXIBLE DUCT SUPPLY, RETURN AND (TYP.) NOTES EXHAUST AIR DEVICE 1. NOT USED. 2. BOXES 1,400 CFM OR LESS TO BE SUPPORTED WITH 1/2"x1/2"x1"GALVANIZED BAND IRON TYPICAL RETURN REGISTER (TYP.) ON FOUR CORNERS BOXES GREATER THAN 1,400 CFM SHALL HAVE TRAPEZE SUPPORT OF REINFORCING ANGLE WITH 3/8" GALVANIZED ALL THREAD ROD HANGERS. 3. PROVIDE A MINIMUM LENGTH OF 2 INLET DIAMETER OF STRAIGHT RIGID SHEET METAL FROM THE DUCT TRANSITION PIECE TO THE VAV BOX INLET. 4. BOXES WITH ELECTRICAL REHEAT COILS TO HAVE 3'-6" MINIMUM WORKING CLEARANCE ON TERMINAL BOX SIDE. PROVIDE REMOTE DISCONNECT FOR INSTALLATIONS WITH RESTRICTED SPACE ABOVE CEILING. TYPICAL LOW PRESSURE SUPPLY, VARIABLE VOLUME BOX CONNECTION DETAIL � RETURN REGISTER SOUND BOOT DETAIL 2 RETURN AND EXHAUST DUCT DETAIL 3 No Scale No Scale No Scale NOTES (VERTICAL MOUNTING SHOWN -HORIZONTAL MOUNTING SIMILAR) FIRE DAMPER 1. DAMPER SHALL BE SECURED TO COLLAR WITH 1/4" DIAMETER NUTS AND BOLTS; MIN.16 GA.SLEEVE OR WELDED IN THE MOUNTING HOLES PROVIDED; OR No. 10 SHEET METAL WALL SCREWS 8" ON CENTER; OR 3/16" STEEL POP RIVETS. DAMPER MUST BE REFER TO SPECIFICATIONS FOR --MAX. 2. ANGLES SHALL BE A MINIMUM OF 1-1/2"x1-1/2"x1/8". FASTEN TO COLLAR 16REAKER FROM SELF-SUPPORTING PROTRUSION OF FIRE ONLY WITH 1/4" DIAMETER NUTS AND BOLTS; OR WELDING 8" ON CENTER; INDEPENDENT OF DAMPER BLADE/SUPPORT OR No. 10 SHEET METAL SCREWS 8" ON CENTER; OR 3/16" STEEL POP RIVETS. DUCT ASSEMBLY INTO AIR STREAM SEE NOTE 5 FOR CLEARANCE AND OVERLAP. RESPECTIVE AHU DUCT INSULATION - 3. COLLARS SHALL BE MINIMUM 16 GAUGE FOR DAMPERS UP TO 36"Wx24"H AND INTERLOCK 14 GAUGE IF WIDTH EXCEEDS 36" OR HEIGHT EXCEEDS 24". GAUGES SHALL M REFER TO CONFORM TO SMACNA DUCT STANDARDS FOR HEAVIER GAUGES. SPECIFICATIONS FOR FLARRING OF 4. THE FOLLOWING DUCT -COLLAR CONNECTIONS MAY BE USED ON ALL SYSTEMS: THERMAL. SWITCH DUCT AT WALL. A. PLAIN "S" SLIP STATUS CT DUCT B. BAR SLIP D1 C. REINFORCED BAR SLIP (CLEAT) D. ANGLE SLIP E. DRIVE SLIP TYPICAL SINGLE PHASE EXHAUST FAN CONTROL FIRE DAMPER SLEEVE DUCT ACCESS 5. DAMPERS SHALL HAVE A CLEARANCE OF 1/4" PER FOOT ON HEIGHT AND MUST EXTEND CLEAR DOOR WIDTH, AND ANGLES SHALL INCREASE IN SIZE PROPORTIONATELY SO THAT THROUGH WALL WALL THERE WILL BE A MINIMUM OF 1" OVERLAP ON THE PARTITION. 1/4" DIA. NUTS AND 1-1/2" X 1-1/2" X 1/8" RETAINING 6. AS WITH ALL JOINTS, CONTRACTOR MUST SEAL COLLAR IN FIELD AFTER BOLTS OR WELDED 8" ANGLE TOP BOTTOM &SIDES, INSTALLATION. ON CENTER BOTH SIDES OF WALL 7. CAULK THE EXTERIOR OF THE FIRE/SMOKE AND SMOKE DAMPER RETAINING ANGLES TO PREVENT THE PASSAGE OF SMOKE. CAULK TO BE EQUAL TO 3M FIRE BARRIER CP-25. EXHAUST FAN INTERLOCK TYPICAL FIRE DAMPER DETAIL 4 FIRE DAMPER MOUNTING NOTES 5 CONTROL SCHEMATIC 6 No Scale No Scale No Scale LOW 00 aa� LF1 4, oP��EL •` L I C No ��s`•2 e • >y 6 .y_ I.C. Thomasson Associates, Inc. m i • ' CONSULTING ENGINEERS t ���AI�••t 5005 WEST LAUREL STREET, SUITE 205 �I V' •• , • •/•Q �� TAMPA, FL. 33607 MECHANICAL ENGINEER yI R 'D A • `4-`V PHONE (813) 582-4415 DAN A NESMAN, P.E. • • • • • •' • • • ` " ��` W W W.ICTHOMASSON.COM FLORIDA #54888 ��`��i E N G\� s� ICT PROJECT NO.160273.00 ELECTRICAL ENGINEER FIRM CERTIFICATE OF AUTHORIZATION PHILIP GARRETT, P.E. FLORIDA REG. NCA-0001276 FLORIDA #63289 REVISIONS � M aU+ UNFUSED DISCONNECT SWITCH MOTOR REMAINS OUT - OF AIR STREAM BIRDSCREEN ROOF CURB & —\ FLASHING SEE SPECIFICATIONS FOR HEIGHT PROVIDE TYPE DAMPER SCHEDULED NOTES: EXHAUST DUCT REMOVABLE HOUSING EXHAUST FAN SPUN ALUMINUM CAP SECURE FAN TO CURB BY BOLTING OF FIELD WELDING i6• 1. PROVIDE RUBBER VIBRATION ISOLATORS TO PREVENT MOTOR AND BEARING NOISE FROM TRANSMITTING TO THE FAN HOUSING. 2. ROUTE POWER LEADS TO FAN INSIDE CORNER OF CURB. 3. BELT DRIVEN CENTRIFUGAL EXHAUST FAN SHOWN. DETAIL IS SIMILAR FOR DIRECT DRIVE CENTRIFUGAL EXHAUST FAN. 4. SUPPORT CURB TO BE PERMANENTLY ATTACHED TO BUILDING STRUCTURE BY BOLTING OR WELDING. CENTRIFUGAL EXHAUST FAN 1 No Scale REVISIONS Q' 2 00 N 'ITN yCl) 0 . 0 a z ti E x i., 0, Ll. G2 .0 • U p Q U • N 4, ti _00 �--� o z ti . o r--• • aEi ~o a N Cl) 1 Z O (n z U w D :2 fj� V) U Z O O 0 U U Z 0 ._ U C4 °' a XUi M — ' ai-- Q h a � U o — � o U LU O v y �•_ W)CO O a O CL OQ_ J LA. Date: 06. 03. 16 Scale: AS NOTED Project Mgr: Checker Drawn: Author Job: 16 -062 Sheet M1 4.2 SYMBOLS GENERAL NOTES: A. ALL MOUNTING HEIGHTS GIVEN IN THE LEGEND, SCHEDULES, PLANS, AND DRAWING NOTES ARE TO THE CENTERLINE OF THE DEVICE, UNLESS OTHERWISE NOTED. B. INSTALL ALL SWITCHES AT A CENTERLINE HEIGHT OF 46" A.F.F. UNLESS OTHERWISE NOTED. WHERE SWITCHES OR RECEPTACLES ARE MOUNTED ABOVE CASEWORK OR MILLWORK, LOCATE AT A HEIGHT OF 3'-8" MAX. ABOVE FINISH FLOOR OR 3" ABOVE BACKSPLASH TO CENTERLINE. C. WHERE COVERPLATES CONFLICT WITH CASEWORK OR MILLWORK, SLIGHTLY ADJUST THE MOUNTING HEIGHTS OF THE WIRING DEVICES TO MAKE THE COVERPLATES CLEAR THE COUNTERTOP OR BACKSPLASH BY 1". D. ADDITIONAL SYMBOLS MAY BE SHOWN OR DENOTED ON OTHER SHEETS. E. ALL SYMBOLS, NOTES, AND ABBREVIATIONS SHOWN ON THE LEGEND ARE NOT NECESSARILY USED IN THIS SET OF CONTRACT DOCUMENTS. F. NUMERICAL SUBSCRIPT ADJACENT TO DEVICE FIXTURE, EQUIPMENT OR JUNCTION BOX SYMBOL ON THE DRAWINGS DENOTES THE PANELBOARD CIRCUIT NUMBER TO WHICH DEVICE, FIXTURE, EQUIPMENT OR WIRING IN JUNCTION BOX IS CONNECTED. CODE CRITERIA: NOTE: A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY OR MAY NOT APPLY TO THIS PROJECT. B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER. NFPA-70 (2011) NATIONAL ELECTRICAL CODE NFPA-72 (2010) NATIONAL FIRE ALARM CODE NFPA-90A (2012) INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS NFPA-90B (2012) INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS NFPA-91 (2010) EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND NON-COMBUSTIBLE PARTICULATE SOLIDS NFPA-96 (2011) VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING OPERATIONS. NFPA-101 (2012) LIFE SAFETY CODE FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014) FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014) FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014) FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE ZONES 5TH EDITION (2014) FLORIDA BUILDING CODE, FUEL GAS 5TH EDITION (2014) FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014) FLORIDA ACCESSIBILITY CODE (2014) APPLICABLE STATE ENERGY CODE (2014) STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60. NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE "BUILDING" AND "MECHANICAL" OR "PLUMBING" CODES, IT WILL BE ASSUMED THAT THE BUILDING CODE TAKES PRECEDENCE. SYMBOLS DESCRIPTION {) PRIMEX GPS WIRELESS CLOCK (14159) 12.5" ANALOG D SINGLE FACE WIRELESS MASTER CLOCK (SEE SPECIFICATIONS) c z DOUBLE FACE WIRELESS MASTER CLOCK (SEE SPECIFICATIONS) c INTERVAL TIMER - SIMPLEX #6306-9103 FURNISHED BY ELECTRICAL (INCLUDE CONTRC SIT INTERVAL TIMER CONTROL SWITCH - SIMPLEX #6303-9202 FURNISHED BY ELECTRICAL �fl MASTER CLOCK (GPS PRIMEX WIRELESS CLOCK SYSTEM) EA MASTER CLOCK &-PROGRAMMER a]J' PROGRAM BELL MASTER CLOCK SYSTEM JUNCTION BOX ALL STROBE UNITS MUST BE MOUNTED 80" AFF TO BOTTOM OF LAMP NOT DEVICE. FLASHING LIGHT SPEAKER/FLASHING LIGHT COMBINATION (CONNECT TO EXISTING AUDIO SYSTEM) © SPEAKER/FLASHING LIGHT COMBINATION (PROVIDE TONE GENERATOR FOR USE WITH SPEAKE © HORN/FLASHING LIGHT COMBINATION MANUAL PULL STATION Dss DUCT -SMOKE DETECTOR (SUPPLY) DSR DUCT -SMOKE DETECTOR (RETURN) D SMOKE DETECTOR D L SMOKE DETECTOR WITH LOCAL ALARM eID BEAM TYPE SMOKE DETECTOR DSD DUCT -SMOKE DETECTOR (DAMPER) OR (EXHAUST) L DUCT -SMOKE DETECTOR INDICATOR LIGHT (WALL MOUNTED 10"BELOW CEILING) HD AUTOMATIC HEAT DETECTOR (RATE OF RISE TYPE) SIDS SYSTEM CONNECTED SMOKE DETECTOR SIDE SYSTEM CONNECTED SMOKE DETECTOR FOR FIREMAN'S RECALL D FIRE SMOKE DAMPER [EEJ SMOKE DOOR HOLDER Ts TAMPER SWITCH FL FLOW SWITCH FJ FIREMAN'S PHONE JACK sF DWELLING UNIT FIRE SPEAKER ❑L @- FLASHING LIGHT SPEAKER SIGNAL STATION FACP CONTROL PANEL FAPc PULL CABINET Fa+ REMOTE ANNUNCIATOR FR FIRESTAT (PROVIDED BY OTHERS) MONITOR WITH FIRE ALARM SYSTEM FAPu CENTRAL PROCESSING UNIT FFAcq I COMMAND CENTER FAST TRANSPONDER Fs I FIRE ALARM SPEAKER s TWO BUTTON (CODE BLUE & STAFF ASSIST) EMERGENCY CALL STATION ;P SINGLE PATIENT STATION WITH CALL CORD D STAFF DUTY STATION D NURSE CALL DOME LIGHT z NURSE CALL ZONE LIGHT -P EMERGENCY PULL CORD (CORD WITHIN 6" AFF) ACCESS CONTROL CARD READER (SEE SPECIFICATIONS) ACCESS CONTROL DOOR REMOTE RELEASE PUSH BUTTON PPI IACCESS CONTROL DOOR PUSH PLATE MqN MEDICAL GAS ALARM LPA LINE PRESSURE ALARM Rom+ REMOTE GENERATOR ANNUNCIATOR SeA BLOOD BANK ALARM MSA MOISTURE SENSOR ALARM DPA ROOM DIFFERENTIAL PRESSURE ALARM (COORDINATE W/DIVISION 15) we VARIABLE LIGHT INTENSITY CONTROLLER (BY OTHERS) FOR EXAM LIGHT b x DATA ONLY OUTLET(S) WITH "X" NUMBER OF CATEGORY 6 CABLE(S) IG - VOICE/DATA OUTLET(S) WITH "X" VOICE AND "Y" DATA CATEGORY 6 CABLE(S) N " VOICE ONLY OUTLETS WITH "X" VOICE CATEGORY 6 CABLE(S) Q- X ABOVE COUNTER DATA ONLY OUTLET(S) WITH "X" NUMBER OF CATEGORY 6 CAI 14- xn ABOVE COUNTER VOICE/DATA OUTLET(S) W/ "X" VOICE & "Y" DATA CATEGORY 6 14- X ABOVE COUNTER VOICE ONLY OUTLETS WITH "X" VOICE CATEGORY 6 CABLE (PM) CABLE(S) INTENDED FOR USE BY PATIENT MONITORING SYSTEM (MED) CABLE(S) INTENDED FOR USE BY AUTOMATED MEDICATION DISPENSER N `" VOICE ONLY WALL PHONE OUTLET AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABV MOUNT ABOVE COUNTER ABC ABOVE CEILING EDF ELECTRIC DRINKING FOUNTAIN FBE FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR FBO FURNISHED BY OTHERS, INSTALLED BY ELECTRICAL CONTRACTOR GND GROUND LION UNLESS OTHERWISE NOTED WH WATER HEATER WP WEATHER PROOF, NEMA 3R ELECTRICAL SHEET LIST SHEET NUMBER SHEET NAME ELECTRICAL LEGEND MOUNTING HEIGHT TO CENTERLINE SYMBOL DESCRIPTION LION �1 CONDUIT CONCEALED IN WALL OR CEILING T-0" CONDUIT CONCEALED IN FLOOR OR BELOW GRADE ON SITE PLAN SEE SPEC'S CONDUIT EXPOSED ON WALL OR CEILING SEE SPEC'S HOMERUN CONDUIT, 2 CIRCUIT 3#12 AWG SEE DETAIL /T\ TELEPHONE CONDUIT CONCEALED LION (MIN %%131") /D\ DICTATION SYSTEM CONDUIT CONCEALED LION MIN %%131" /P\ INTERNAL WIRING FURNISHED ON PRE-FAB PARTITION FBO /TP INTERNAL TELEPHONE RACEWAY FURNISHED WITH PRE-FAB PARTITION FBO 7'-0" CONDUIT TURNING UP CONDUIT TURNING DOWN ❑ SURFACE MOUNTED INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT ® SURFACE MOUNTED INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT ® SURFACE MOUNTED INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH 80" ❑ RECESSED INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT 80" ® RECESSED INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT 80" ® RECESSED INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH 80" SURFACE MOUNTED WALL INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT 46" SURFACE MOUNTED WALL INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT SURFACE MOUNTED WALL INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH RECESSED WALL INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT CEILING RECESSED WALL INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT CEILING P0 RECESSED WALL INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH ❑ ®I SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT ®® SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT ® ® SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH ❑ ® RECESSED FLUORESCENT LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT CEILING ® RECESSED FLUORESCENT LIGHT FIXTURE ON LIFE SAFETY BRANCH CIRCUIT CEILING ® ® RECESSED FLUORESCENT LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT 18" ® SURFACE MOUNTED FLUORESCENT FIXTURE CONNECTED TO NORMAL BRANCH CIRCUIT 6-0" ® SURFACE MOUNTED FLUORESCENT FIXTURE CONNECTED TO CRITICAL BRANCH CIRCUIT ® SURFACE MOUNTED FLUORESCENT FIXTURE CONNECTED TO LIFE SAFETY BRANCH CIRCUIT CEILING ® EXIT LIGHT, CEILING MOUNTED 46" F-0 EXIT LIGHT, WALL MOUNTED vc=Y TWO HEAD BATTERY POWERED EMERGENCY EGRESS LIGHT 80" E REMOTE EMERGENCY BATTERY PACK 5" LIGHTING FIXTURE TYPE DESIGNATION -SEE LIGHTING FIXTURE SCHEDULE AREA OR STREET LIGHT FIXTURE °--0 AREA OR STREET LIGHT FIXTURE ® FACTORY WIRED CONTROLLER OR EQUIPMENT CONNECTION, FBO. DISCONNECTS FBE AS REQUIRED ® MOTOR CONTROLLER OR CONTACTOR, F.B.O. W/DISCONNECT, F.B.O. W/EQUIPMENT B COMBINATION MOTOR STARTER DISCONNECT qm DISCONNECT SWITCH, NON -FUSIBLE DISCONNECT SWITCH, FUSIBLE 112!1 RT DISCONNECT SWITCH, NON -FUSIBLE RT DENOTES NEMA-3R 'o RT DISCONNECT SWITCH, FUSIBLE RT DENOTES NEMA-3R 44" `qK MOTOR CONNECTION WITH APPROXIMATE HORSE -POWER SHOWN 44" T THERMOSTAT FBO SEE MECH. 44" SOLENOID VALVE CEILING SPE PHOTO -ELECTRIC SWITCH CEILING Tc ON -OFF TIME CLOCK Ps PRESSURE SWITCH Q FLOAT SWITCH FL FLOW SWITCH ® RELAY ® TRANSFORMER O JUNCTION BOX Pe PULL BOX LIGHTING PANELBOARD ® MAIN SWITCHBOARD OR DISTRIBUTION PANEL 01 ENCLOSED CIRCUIT BREAKER sM PM WALL MOUNTED PIR OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. PWA 00 oc CEILING MOUNTED OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. LMDC-100 SLv I Lv WALL MOUNTED LOW VOLTAGE SWITCH - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. LMSW-101 MANUAL ON/AUTO OFF SLvz 62 WALL MOUNTED LOW VOLTAGE TWO BUTTON SWITCH - BY ELECTRICAL- WATTSTOPPER NO. LMSW-102 AUTO 50%/MANUAL 100%/AUTO 0 soc hoc WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL- WATTSTOPPER NO. DW-100 AUTO ON/AUTO OF S30C 6c THREE WAY WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR - BY ELECTRICAL - WATTSTOPPER NO. DW-103 MANUAL ON/AUTO oc ; WEATHER RESISTENT CEILING MOUNTED OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. CB-100 18" I ocwP WEATHER RESISTENT WALL MOUNTED OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL 18" S SINGLE POLE SWITCH -(IVORY) 18" Sz TWO POLE SWITCH -(IVORY) 6"ABC OR 46"AFF s3 THREE-WAY SWITCH -(IVORY) 6"ABC OR 46"AFF s4 FOUR WAY SWITCH -(IVORY) 6"ABC OR 46"AFF SD SINGLE POLE DIMMER SWITCH 600 WATT 46" EO.1 ELECTRICAL - LEGEND, NOTES, ETC... E5.1 ELECTRICAL - PARTIAL FIRST FLOOR PLANS_ E6.1 ELECTRICAL - PARTIAL FIRST FLOOR PLANS E14.1 ELECTRICAL - DETAILS - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. RT-100 SD3 THREE-WAY DIMMER SWITCH 600 WATT sT THERMAL MOTOR SWITCH-(FBE) s- THERMAL MOTOR SWITCH, WEATHERPROOF-(FBE) STP THERMAL MOTOR SWITCH, WITH PILOT LIGHT FBE SK KEY OPERATED SWITCH sP SINGLE POLE SWITCH WITH PILOT LIGHT SWP SINGLE POLE SWITCH, WEATHERPROOF iPD SINGLE POLE, DOUBLE THROW, CENTER OFF SWITCH RED - DARK ROOM tic VARIABLE INTENSITY CONTROL, F.B.O. WITH FIXTURES - SEE O.F.E. BROCHURE FOR INSTALLATION SEE DETAIL I; SINGLE POLE SWITCH ON EMERGENCY BRANCH CIRCUIT RED z DOUBLE POLE SWITCH ON EMERGENCY BRANCH CIRUIT RED 113 THREE-WAY SWITCH ON EMERGENCY BRANCH CIRUIT RED �P SINGLE POLE SWITCH WITH PILOT LIGHT ON EMERGENCYE BRANCH CIRCUIT B-- SINGLE RECEPTACLE, AMPERAGE, VOLTAGE, NEMA CONFIGURATION AS REQUIRED BY EQUIP. SUPPLIER OR AS NOTED Q= 120V. DUPLEX RECEPTACLE IVORY IQ= E 1120V. DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT RED 120V. DUPLEX RECEPTACLE ABOVE COUNTER(IVORY) E 120V. DUPLEX RECEPTACLE ABOVE COUNTER ON EMERGENCY BRANCH CIRCUIT RED �Tv 120V. DUPLEX RECEPTACLE FOR TV POWER (IVORY) * 6" TO CENTERLINE BELOW FINISH CEILING 120V. QUADRAPLEX RECEPTACLE -(IVORY) �)=0 120V. QUADRAPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -(RED) 4)-- 1120V. QUADRAPLEX RECEPTACLE -(IVORY) JD-= E 120V. QUADRAPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -(IVORY) S 120V. DUPLEX RECEPTACLE -SAFETY TYPE -(IVORY) Qr=SE 120V. DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -SAFETY TYPE -(RED) E -- S 120V. DUPLEX RECEPTACLE -SAFETY TYPE -(IVORY) e--SE. 120V. DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -SAFETY TYPE -(RED) &- T SINGLE RECEPTACLE-TWISTLOCK TYPE 120V: 20A. UNLESS OTHERWISE SPECIFIED GFI GROUND FAULT TYPE RECEPTACLE -(IVORY) GFI OH GROUND FAULT TYPE RECEPTACLE -ON EMERGENCY BRANCH CIRCW T�-- - - GFI�WF GROUND FAULT RECEPTACLE WEATHERPROOF OO 120V. DUPLEX RECEPTACLE IN CONSOLE -(I RY OO E 120V. DUPLEX RECEPTACLE IN CONSOLE ON EMERGENCY BRANCH CIRCUIT RED O° s 120V. DUPLEX RECEPTACLE IN CONSOLE -SAFETY TYPE -(IVORY) OO SE 120V. DUPLEX RECEPTACLE IN CONSOLE ON EMERGENCY BRANCH CIRCUIT -SAFETY TYPE -(RED) Oo - 120V. DUPLEX RECEPTACLE IN CONSOLE- IVORY AMPERES, VOLTAGE, & NEMA CONFIGURATION AS SPECIFIED Do- E 120V. DUPLEX RECEPTACLE IN CONSOLE ON EMERGENCY BRANCH CIRCUIT- RED AMPERES, VOLTAGE, & NEMA CONFIGURATION AS SPECI o0-T 120V. TWISTLOCK RECEPTACLE IN CONSOLE- IVORY AMPERES, VOLTAGE, & NEMA CONFIGUARATION AS SPECIFIED Q 120V. SQUARE OR ROUND FLOOR BOX WITH (1) DUPLEX RECEPTACLE -(IVORY) ❑• E OE 120V. SQUARE OR ROUND FLOOR BOX WITH (1) DUPLEX RECEPTACLE EMERGENCY -(RED) EW I TWO GANG FLOOR BOX WITH ONE DUPLEX RECEPTACLE AND ONE TELEPHONE OUTLET F97MA THREE GANG FLOOR BOX WITH ONE DUPLEX RECEPTACLE, ONE TELEPHONE OUTLET, & ONE DICTATION OUTLET F-T-711 THREE GANG FLOOR BOX WITH TWO DUPLEX RECEPTACLES, & ONE TELEPHONE OUTLET @r= P 120V. DUPLEX RECEPTACLE PREWIRED IN PRE-FAB PARTITION (FBO) O- SINGLE RECEPTACLE NON -EXPLOSION PROOF (HUBBELL 23000 HG) ® DUPLEX RECEPTACLE 20 AMP 120 VOLT ®E DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT 20 AMP 120 VOLT -(RED) ® DUPLEX RECEPTACLE 20 AMP 120 VOLT -(MOUNTED ABOVE COUNTER) @*sR DUPLEX RECEPTACLE AND SINGLE POLE SWITCH UNDER COMMON PLATE ®- PORTABLE C-ARM OUTLET HUBBELL #2610 R 120V. DUPLEX FOR RADIO EQUIPMENT POWER SIGI DUPLEX RECEPTACLE, ISOLATED GROUNDING, IG DUPLEX RECEPTACLE, ISOLATED GROUNDING, INSTALL ABOVE COUNTER SIG QUADRAPLEX RECEPTACLE, ISOLATED GROUNDING (Q---WEATHERPROOF DUPLEX RECEPTACLE -w- WIREMOLD m PLUGMOLD #3000 WITH HUBBELL 5252 DUPLEX RECEPTACLES 24" ON CENTER MOUNTING HEIGHT TO CENTERLINE LION AS NOTED AS NOTED AS NOTED 46" CEILING 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" 46" BOTTOM 46" 46" 46" 46" 46" 18" 18" 18" AS SPECIFIED AS SPECIFIED AS NOTED 18" 18" AS SPECIFIED AS SPECIFIED 18" 18" AS SPECIFIED AS SPECIFIED 18" AS SPECIFIED -AS SPECIFIES AS SPECIFIED SEE DETAIL SEE DETAIL SEE DETAIL SEE DETAIL SEE DETAIL SEE DETAIL SEE DETAIL FLOOR BOX FLOOR BOX FLOOR BOX FLOOR BOX FLOOR BOX BOTTOM 61" 18" 18" 46" BOTTOM 61" 18" 18" 46" 18" 46" ei,�111i111/1/flop G G ''•. • 40 - No e328Q L �/A r A : STATE '°.c�• RID R gyp. ••+�,�.•``' �Jfltt/� REVISIONS ✓ i (n V' DD 'IT CO u � r-^ Q ti ov v m ti N U X U CD 8O tCd Ln U N '" Lo Q Q�(-)oo 3 �-' 3 r 3 o ti o I- N SAIL 0 V/ Z U Ld 1 D (n U Z0 0 m U U c Z O •C V C4 -a X J M ; M- Lu o V _ - O O LL. u Lu C ° H � CO O o O- o N QL O J LL Date: 06. 03. 16 Scale: AS NOTED Project Mgr: PGG Drawn: MCF Job: 16-062 Sheet E0. I EXISTING ---------- 'I 7 III i{ �\ IS G BR K 0 I EXISTING EXISTING TOILET TOILET EX ING l JA \ - - � I III I I I II �I 2 I I, j IS G O ICE !I I I O I I it �I I O � I EXISTING EXISTING SERVER ROOM CORRIDOR j. F-1 II O - �I I I� I IS G E TI O CE FF E I� I I III 3 �' I I- -- --- ---I - - - -- - - - - - - --- I II III I I �i I I li E I IS G OF 0 IC II I I �-- 1I EXISTING OFFICE �I I, I EXISTING CONFERENCE ROOM 1 EXISTING CORRIDOR QI C EXISTING OFFICE U3 EXISTING OFFICE E` h O j EXISTING OFFICE Of O I, O O _-_ - �© _- -------- _-- _---_- _-- - - - -_ _ - - co zco - O - - -- -- - o `i i - � W - L U EXISTING W Q j CLEAN ROOM IIIII ELECTRICAL - DEMOLITION - PARTIAL FLOOR PLAN SCALE: 3/16" = V-0" GENERAL NOTES: A. REFER TO THE ARCHITECTURAL PLANS FOR THE FULL EXTENT -OF DEMOLITION. B. REFER TO DEMOLITION NOTES ON THIS SHEET. CODED NOTES: O 1. LIGHTING IN THIS ROOM/SPACE IS EXISTING TO REMAIN 2. DASHED LINES INDICATED WALLS TO BE REMOVED. ELECTRICAL CONTRACTOR IS TO REMOVE ALL ELECTRICAL DEVICES AND CIRCUITS PER THE DEMOLITIONS NOTES ON THIS SHEET. ABANDONED WIRES AND CONDUITS ARE TO BE COMPLETD REMOVED. 3. HATCHED AREAS INDICATE THE APPROXIMATE EXTENT OF ABOVE CEILING WORK. ALL ELECTRICAL DEVICES ARE TO BE REMOVED AND REINSTALLED OR TURNED OVER TO THE OWNER PER THE DEMOLITION NOTES. EXISTING CORRIDOR EXISTING 2 I (TYP O II II II I II II II I I / I EXISTING - �i LJ OFFICE J� EXISTING ��01 i- TOi T �- I I I I I I I I ��o I I EXISTING RECEPTION I o I II I EXISTING WAITING 0 EXISTING EXISTING CORRIDOR CORRIDOR I I I E� ISTING RECOVERY j I LIGHTING - NEW WORK PARTIAL FLOOR PLAN SCALE: 3/16" = V-0" GENERAL NOTES: A. ALL CIRCUITS ARE REQUIRED TO HAVE DEDICATED NEUTRALS. B. ALL OCCUPANCY SENSORS ARE TO BE SET FOR "MANUAL ON" AND "AUTO OFF". C. ALL FIXTURES PROVIDED WITH AN EMERGENCY BALLAST ARE TO BE PROVIDED WITH A CONTINUOUS "HOT" WIRE. IN THE EVENT OF A POWER OUTAGE, THE FIXTURE SHALL ILLUMINATE REGARDLESS OF THE SWITCH POSITION. CODED NOTES: O 1. LIGHTING IN THIS ROOM/SPACE IS EXISTING TO REMAIN. 2. PROVIDE NEW OCCUPANCY SENSOR AS INDICATED AND RELOCATE SWITCH AS NECESSARY TO ACCOMMODATE THE NEW DOOR LOCATION. `eeetttttttttt�i��i Q G. G •. No 63280 STATE � L �''"rtttttt�e� REVISIONS • 4Q .0 Cl) N �. u _J COp �-I ~, ¢ to 0 v ro ti E 0 N C 0. • U p O L0 O U • L ` Q E Q00 O 3 0 w 3 r 3 ti O L N ti 0. M • 1 1 Z O t) Z U W D L.L D (n U ZO O0 U V Z O .0 J C4 0LO M M tX V o _ O 0 m O he = u Lu c ° H � _ 0 L NfA O M d Q O �/ N L- CL O J LL. Date: 06. 03. 16 Scale: AS NOTED Project Mgr: PGG Drawn: MCF Job: 16-062 Sheet E5.1 1�-------- — - - -— -�- — — — — — — — rr --i 2 --�-- I JI I i--- FI 1 1 2 1 3 1 4 5 1 6 7 1 8 1 INFUSION ILJI O 48'-6" z 29'-9" AL 13 1 1 L L 1 10 1 11 1 12---I--� EX F L � � EX ` I � i EXAM 2 7'-6" x 9'-6" Ia II f� e I XISTING EXISTIN TOILET TOILET J pII j--J L--J L--J O , - _ nl O O' - o U) SUPPLIES ry U)'' I' 141 11 I I 2 W 9'-7" x 6-8" U 1----, --_--- Q', w EXITING - - J 14 I 15 16 17 ~ x '--_---- - NURSE = wl OF ICE 1----I-1 ---1 r� r� 9'-7" x 6-8" II II II II I ! ! RPO-1 C'-=-':D c'---'D C_- :D B1.2 L II � I PP1-4 LAB 8'-7" x 10'-5" 1 WP/GFI ' 1 I -��- -. ICON ROOF) EXISTING CONFERENCE ROOM I T_ EXISTING EXISTING SERVER ROOM CORRIDOR 3 EXISTING OFFICE EXISTING OFFICE MEDS I 5'-0" x 10'-5" =11L EXISTING OFFICE EXISTING OFFICE af O p _----------------_—__--- ----�--------- -- - --_-- WO -- --- --- - Z - - - -- W = � 0 wQ I � EXISTING CLEAN ROOM I I� rr E ISTING RECOVERY 11 II l -----� ------ �----- �— ------ ----- -_ `.L`---);Ili SYSTEMS - NEW WORK PARTIAL FLOOR PLAN it SCALE: 3/16" = 1'-0" GENERAL NOTES: A:-ALL-81RCUITS ARE REQUIRED T6-HAVE DEDIEATED NEUTRALS: - - - - - - - - B. COORDINATE THE EXACT LOCATION ALL EQUIPMENT WITH MECHANICAL CONTRACTOR. PROVIDE FUSES AS REQUIRED BY THE EQUIPMENT NAMEPLATE RATINGS. C. ALL COMMUNICTIONS CABLING TO BE ROUTED TO EXISTING TERMINATION POINTS. FIELD COORDINATE WITH OWNER. CODED NOTES: 0 1. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCTION OF TELEVISIONS. i T b L NURSE 7'-0" x 12'-8" EXAM 1 _ 8'-7" x 9'-6' Ic OFFICE EXISTING $"T i9=6-i TOILET II� i EXISTING I I' RECEPTION EXISTING CLOSET PP1-6 ZT B3.28 EXISTING WAITING 2 U U n EXISTING CORRIDOR — — — GFI 1 1 I I I RPO-46 1 L - - -_�J - - - - {� _ - - i= - -L= RPO-6-J lJ - - LJ_ RPO-4 RPO-8 I ---I I ---I I-- I I- -I I --- I I rG FI 1 1 2 3 4 15 6 7 1 8 1 1 RPO-2 - - - - - - I RPO-10 INF SIONIL 3 1 F_ 48'-6' x 29'-9" • FIi� TV "RPO" I I - "T--RPO' - - - - I 13 1 I I I 1 0 (ABOVE 11 12 EXISTING EXISTING CEILING)'] _ RPO-14- -1 L - - LJ TOILET TOILET -- — - i RPO 2 j RPO-42 I—� FT FT O - - - C - - - — 4JV RPO-20 1 --- I II II 1 II II - - - j- 1--RPO-30 RPO-28 EXISTING - OF ICE i II II II II EXISTING SERVER ROOM 9'-7" x 6-8" \ - - - RPO-16 1 14 15 I 16 I 1 17 _-� -- r 1 (� -- I 1 RPO-18 EXISTING OFFICE LAB 8'-7" x 10'-5" EXISTING CONFERENCE ROOM RPO-22 I I cr O p 0 U U) U) W U U Q F- X W li lr�Ti-1f�T� 1LVGFI I J �RPO-32 RPO-3 6 M 3 T-9" x 10'-0" EXAM 2 T-6" x 9'-6" �G I / GF'I ii ii it / -� RPO-381 I 1 ' NURSE - - - T-0" x 12'-8" RPM-36 EXAM 1 I ram' 8'-7" x 9'-6" 4 / RPO-24�—J RPO-40fr- __I I[ _ 1 I II II J O _OFFICE I RPO-42 O8 -7" x 9'-6" ! Ll '7— RPO-44 r - 1 II I MEDS RPO-26 - - - 5'4" x 10'-5" 7 - I rvinTll.li+ EXISTING CLOSET EXISTING RECEPTION EXISTING 0 1 CORRIDOR II o 0 —#�N I EXISTING OFFICE EXISTING OFFICE I I I EXISTING OFFICE L_ E -- \cr_ - p �ry --------------------------------------- L"'Jo I XU I EXISTING wQ CLEAN I ROOM EXISTING RECOVERY 1! i POWER - NEW WORK PARTIAL FLOOR PLAN SCALE: 3/16" = 1'-0" GENERAL NOTES: A.- ALL CIRCUITS ARE REQUIRED TO HAVE DEDICATED NEUTRALS. B. REFER TO ARCHITECTURAL PLANS FOR ALL CASEWORK ELEVATIONS AND ENSURE THAT DEVICES ARE COORDINATED WITH THE SHOP DRAWINGS AND ELEVATIONS. CODED NOTES: 0 1. DEDICATED 20A RECEPTACLE FOR REFRIGERATOR. 2. DEDICATED 20A RECEPTACLE FOR ICE MAKER. 3. DEDICATED 20A RECEPTACLE FOR UC REFRIGERATOR. I �❑ EXISTING WAITING `%%0%%lm###ttto %G. G '•. No 63289 •• • * 3 %�/ I.C. Thomasson Associates, Inc. i CONSULTING ENGINEERS STATECONSULTING WEST LAUREL STREET, SUITE 205 ��0 • `\\ TAMPA, FL. 33607 MECHANICAL ENGINEER �O R I ` • t� `\ PHONE (813) 882-4415 DAN A NESMAN, P.E. 0j�6`SA/ j• • s •�`�`o`�V,'% ICT PROCJECT NO. 602 3.00 FLORIDA #54888 �IY/1L E`� lea ELECTRICAL ENGINEER FIRM CERTIFICATE OF AUTHORIZATION PHILIP GARRETT, P.E. FLORIDA REG. NCA-0001276 FLORIDA 063289 REVISIONS • 200 � ILD � N y� ~~ 0 ti U 4; ti -EXy N cam 03 • U o F to ro i Q¢ ti E _ 3 ti 3 �.--• o = J o -a N z Om ~z U w N� L.L 0 U zO O0 U U c Z 0 .0 J Q C4 � M Lu o _ O O u Lu a � C N O Lg)s M b G Q M a Q Fe � O O N CL OQ` "II LL Date: 06.03. 16 Scale: AS NOTED Project Mgr: PGG Drawn: MCF Job: 16-062 Sheet E691 PANEL: PNL LP 1 OC DEVICE TYPE: Breaker ENCLOSURE: NEMA 1 MAINS( A) : 225A ML❑ CONT I NU❑US( A) : 225 LOCATI❑N: 1ST FLR MAIN ELEC RM DEVICE FAMILY: Bolt On M❑UNTING: Surface WIRING: 3-Phase 4-Wire BUS SC RATING(A) 14000 FED FROM: EXISTING PANEL VOLTAGE: 480/277 FAULT CURRENT(A): 12663 NORMAL POWER EXISTING PANEL CKT DESCRIPTI❑N NOTES DEMAND VA ❑C PHASE OC VA DEMAND NOTES DESCRIPTION CKT CODE AMPS P AMPS P CODE 1 EXISTING LTG EXISTING LTS 1663 20 1 A 20 1 1663 LTS EXISTING EXISTING LTG 2 3 SPACE ONLY SPACE 0 0 1 B 20 1 1663 LTS EXISTING EXISTING LTG 4 5 EXISTING LTG EXISTING LTS 1663 20 1 C 20 1 1663 LTS EXISTING EXISTING LTG 6 7 EXISTING LTG EXISTING LTS 1663 20 1 A 20 1 3210 LTS NEW BREAKER INFUSI❑N LTG 8 9 EXISTING LTG EXISTING LTS 1663 20 1 B 0 1 0 SPACE SPACE ONLY 10 11 EXISTING LTG EXISTING LTS 1663 20 1 C 0 1 0 SPACE SPACE ONLY 12 13 EXISTING LTG EXISTING LTS 1663 20 1 A 0 1 0 SPACE SPACE ONLY 14 15 EXISTING LTG EXISTING LTS 1663 20 1 B 0 1 0 SPACE SPACE ONLY 16 17 EXISTING LTG EXISTING LTS 1663 20 1 C 0 1 0 SPACE SPACE ONLY 18 19 EXISTING LTG EXISTING LTS 1663 20 1 A 0 1 0 SPACE SPACE ONLY 20 21 EXISTING LTG EXISTING LTS 1663 20 1 B 0 1 0 SPACE SPACE ONLY 22 23 EXISTING LTG EXISTING LTS 1663 20 1 C 0 1 0 SPACE SPACE ONLY 24 25 EXISTING LTG EXISTING LTS 1663 20 1 A 20 1 1663 LTS EXISTING EXISTING LTG 26 27 EXISTING LTG EXISTING LTS 1663 20 1 B 20 1 1663 LTS EXISTING EXISTING LTG 28 29 SPACE ONLY SPACE 0 0 1 C 20 1 1663 LTS EXISTING EXISTING LTG 30 31 T-RPO PRI FDR NEW BREAKER NONE 6807 45 3 A 20 1 1663 LTS EXISTING EXISTING LTG 32 33 of 7240 B 20 1 1663 LTS EXISTING EXISTING LTG 34 35 of 7120 " C 20 1 1663 LTS EXISTING EXISTING LTG 36 37 EXISTING LOAD EXISTING 3326 20 3 A 20 1 1663 LTS EXISTING EXISTING LTG 38 39 "" 3326 "" B 20 1 1663 LTS EXISTING EXISTING LTG 40 41 "" 3326 "" C 20 1 1663 LTS EXISTING EXISTING LTG 42 ALL CONNECTED KVA 3P AVE AMPS )K PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 75.06 90, 3 * A-N 28022,6 101, 1 CONNECTED 75. 06 TOTAL DEMAND 63.79 76. 7 )K B-N 23579.7 85, 1 DEMAND 63,79 TOTAL DESIGN 77.27 92, 9 )K C-N 23460, 0 84, 7 DES I GN 77,27 ALL BREAKERS ARE EXISTING UNLESS OTHERWISE NOTED. PANEL: PNL PP ❑C DEVICE TYPE: Breaker ENCLOSURE: NEMA 1 MAINS(A): 225A ML❑ CONTINUOUS(A): 225 LOCATION: 1ST FLR MAIN ELEC RM DEVICE FAMILY: Bolt On MOUNTING: Surface WIRING: 3-Phase 4-Wire BUS SC RATING(A) 14000 FED FROM: EXISTING PANEL VOLTAGE: 480/277 FAULT CURRENT(A): 12237 NORMAL POWER EXISTING PANEL CKT DESCRIPTION NOTES DEMAND VA ❑C PHASE OC VA DEMAND NOTES DESCRIPTI❑N CKT CODE AMPS P AMPS P CODE 1 VAV B3-2 AND 7 EXISTING HEAT 2771 20 1 A 25 1 5000 HEAT NEW BREAKER VAV B1.1 INFUSION 2 3 VAV B1-5 THROUGH 9 EXISTING HEAT 2771 20 1 B 15 1 3000 HEAT NEW BREAKER VAV B1.2 INF. C❑NF. 4 5 VAV B1-1 AND 4 EXISTING HEAT 2771 20 1 C 15 1 3000 HEAT NEW BREAKER VAV B3.28 EXAM RMS 6 7 VAV B3-9 THROUGH 13 EXISTING HEAT 2771 20 1 A 20 3 2494 HEAT EXISTING VAV B4-7 8 9 VAV B3-16 AND 71 EXISTING HEAT 2771 20 1 B "" 2494 "" 10 11 VAV B3-6 AND 24 EXISTING HEAT 2771 20 1 C "" 2494 "" 12 13 VAV B3-22 EXISTING HEAT 2494 20 3 A 20 3 2494 HEAT EXISTING VAV B4-3 14 15 "" 2494 "" B "" 2494 "" 16 17 "" 2494 "" C "" 2494 "" 18 19 VAV B3 „ 5, & 6 EXISTING HEAT 3048 20 1 A 20 3 0 SPACE EXISTING SPACE ONLY 20 21 HWH RM 1M112 STG EXISTING HEAT 5000 30 1 B "" 0 "" 22 23 HWH RM 5B103 EXISTING HEAT 5000 30 1 C "" 0 "" 24 25 HWH RM 10107 EXISTING HEAT 5000 30 1 A 20 3 2494 HEAT EXISTING VAV B3-28 26 27 HWH RM 1B105 EXISTING HEAT 3000 30 1 B "" 2494 "" 28 29 HWH RM 1A105 EXISTING HEAT 5000 30 1 C "" 2494 "" 30 31 VAV B4-1 EXISTING HEAT 2494 20 3 A 20 3 0 SPARE EXISTING SPARE 32 33 "" 2494 "" B "" 0 "" 34 35 "" 2494 "" C "° 0 "" 36 37 VAV B4-4 EXISTING HEAT 2494 20 3 A 20 3 2494 HEAT EXISTING VAV 131-3 38 39 "" 2494 "" B "" 2494 "" 40 41 "" 2494 "" C "" 2494 "" 42 ALL CONNECTED KVA 3P AVE AMPS x PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 106,05 127.6 * A-N 36050.0 130. 1 CONNECTED 106. 05 TOTAL DEMAND 63, 63 76.5 )K B-N 34001.6 122.7 DEMAND 63.63 TOTAL DESIGN 63,63 76.5 )K C-N 36001. 6 129.9 DESIGN 63. 63 ALL BREAKERS ARE EXISTING UNLESS ❑THERWISE NOTED, PANELi RPO OC DEVICE TYPEi Breaker ENCL❑SUREi NEMA 1 MAINS( A) i 100A MCB CONT I NUOUS(A) , 100 LOCATIONi ELECTRICAL ROOM DEVICE FAMILY, Bolt On MOUNTINGS Surface WIRINGi 3-Phase 4-Wire BUS SC RATING(A) 10000 FED FROMi T-LP1 SEC VOLTAGE, 208/120 FAULT CURRENT(A)i 1759 NORMAL POWER NEW PANEL CKT DESCRIPTION NOTES DEMAND VA ❑C PHASE OC VA DEMAND NOTES DESCRIPTI❑N CKT CODE AMPS P AMPS P CODE 1 EF1.1 MOTOR 500 15 1 A 20 1 900 REC INFUSION 2 3 SPARE SPARE 0 20 1 B 20 1 1080 REC INFUSION 4 5 SPARE SPARE 0 20 1 C 20 1 1080 REC INFUSI❑N 6 7 SPARE SPARE 0 20 1 A 20 1 540 REC INFUSI❑N 8 9 SPARE SPARE 0 20 1 B 20 1 1080 REC INFUSION 10 11 SPARE SPARE 0 20 1 C 20 1 900 REC ❑FFICE 12 13 SPARE SPARE 0 20 1 A 20 1 1080 REC OFFICE 14 15 SPARE SPARE 0 20 1 B 20 1 900 REC INFUSI❑N 16 17 SPARE SPARE 0 20 1 C 20 1 900 REC INFUSION 18 19 SPARE SPARE 0 20 1 A 20 1 1080 REC NURSE 20 21 SPARE SPARE 0 20 1 B 20 1 900 REC MEDS 22 23 SPARE SPARE 0 20 1 C 20 1 1080 REC MEDS 24 25 SPARE SPARE 0 20 1 A 20 1 1080 REC EXAM2 26 27 SPARE SPARE 0 20 1 B 20 1 1080 REC EXAMS 28 29 SPARE SPARE 0 20 1 C 20 1 1080 REC EXAM1 30 31 SPARE SPARE 0 20 1 A 20 1 720 REC NURSE 32 -33--SPARE- - SPARE - 0 20 1 a 20 1 1200 EQ MEDS -- - 34 35 SPARE SPARE 0 20 1 C 20 1 1000 REC MEDS 36 37 SPACE ONLY SPACE 0 0 3 A 20 1 1000 EQ MEDS 38 39 0 B 20 1 1000 EQ INFUSION 40 41 0 C 20 1 1080 REC INFUSION TELEVISIONS 42 ALL CONNECTED KVA 3P AVE AMPS w PHASE TOTALS VA AMPS BUS TOTALS KVA TOTAL CONNECTED 21. 16 58.7 w A-N 6806,6 56.7 CONNECTED 21, 16 TOTAL DEMAND 9.87 27.4 w B-N 7240.0 60.3 DEMAND 9. 87 TOTAL DESIGN 9.87 27.4 w C-N 7120,0 59.3 DESIGN 9. 87 PNL LP 1 PANEL LP1 FDR CableSize 4/0 AWG QtyPerPhase 1 Length 125.0 ft PANEL PP 1 FDR CableSize 4/0 AWG ConductorType Copper QtyPerPhase 1 Length 135.0 ft ConductorType Copper PANEL LP I X NominalSysVoltage 480.0 V PANEL PP1 InitSymRMS 3P 12662.61 A NominalSysVoltage 480.0 V InitSy nRMS SLG 9470.48 A InitSymRMS 3P 12236.50 A DemandLoad 63.79 kVA InitSymRMS SLG 9077.44 A DesignLoad 77.27 kVA DemandLoad 63.63 kVA PNL PPl DesignLoad 63.63 kVA 45A T-RPO BRKR Description 15-IOOA InterruptingRating 14.0 kA Manufacturer SQUARE D Type EH Frame/Model EH Frame/Rating 45.0 A Sensor/Trip 45.0 A Plug 0.0 A Settings Fixed T-RPO PRI FDR CableSize 6 AWG QtyPerPhase 1 Length 25.0 ft ConductorType Copper A' XFMR T-RPO S Nominal kVA 30 kVA Pri RatedVoltage 480 V Sec RatedVoltage 208 V T-RPO SEC FDR CableSize 1 AWG QtyPerPhase 1 Length 10.0 ft ConductorType Copper I OOA RPO MCB Description 70-250A InterruptingRating 10.0 kA Manufacturer SQUARE D Type QB Frame/Model QB Frame/Rating 100.0 A Sensor/Trip 100.0 A Plug 0.0 A Settings Fixed PANEL RPO NominalSysVoltage 208.0 V InitSymRMS 3P 1738.37 A InitSymRMS SLG 1758.98 A DemandLoad 9.87 kVA DesignLoad 9.87 kVA 20A PNL RPO LGST Description 15-70A InterruptingRating 10.0 kA Manufacturer SQUARE D Type QO, 1-Pole Frame/Model QO Frame/Rating 20.0 A Sensor/Trip 20.0 A Plug 0.0 A Settings Fixed (730-3) NEW WORK 25A NEW BRKR i) Description 15-I OOA InterruptingRating 14.0 kA Manufacturer SQUARE D Type EH Frame/Model EH Frame/Rating 25.0 A Sensor/Trip 25.0 A Plug 0.0 A Settings Fixed NEW WORK "CAUTION*" ALL CABLE/FEEDER LENGTHS ARE FOR ENGINEERING CALCULATIONS ONLY, AND SHOULD NOT BE USED FOR PROJECT BUDGETING OR ESTIMATES OF MATERIALS TO BE USED. CONTRACTOR IS TO FIELD VERIFY ALL LENGTHS. LIGHT FIXTURE SCHEDULE TYPE I MANUFACTURER MODEL NO. I LAMP I MOUNT REMARKS 7 LITHONIA 213LT4 40L ADP MVOLT EZ1 LP835 LED RECESSED 2'x4' LED VOLUMETRIC TROFFER 7E LITHONIA 2BLT4 40L ADP MVOLT EZ1 LP835 EL14L LED RECESSED 2'x4' LED VOLUMETRIC TROFFER WITH 1400L BATTERY BACKUP 171' LITHONIA EDGR 1 R EL LED UNIVERSAL SINGLE SIDED EDGE LIT CEILING MOUNT EXIT SIGN W/ EMERGENCY BATTERY ONO 63280 STATE O0 AN i # REVISIONS • ♦ v 00 M N o�ti E r_ " E X o O. p U o ro 'n ro Q E ~ , 3 ti 3 :D o v 0 N o. N Cl) 1 Z O V) Z U L,J D 12 L.L_ D V) U ZO OC) U U c Z O_ •C U '4 a� Q X J M CV) UJ Q h v U _o O 0 a>' O L+. u Lu C ° y � _ 0 W) M L CO N 0 O _ CL O d CL L 0 J Date: 06. 03. 16 Scale: AS NOTED Project Mgr: PGG Drawn: MCF Job: 16-062 Sheet El 091 I REVISIONS 9 STRUCTURE ABOVE MINIMUM OF 3 TWISTS 150 SIDE NOTE (SURFACE MOUNTED LIGHT FIXTURE - SEE CEILING DETAIL) L2"x2"x1/8"x2" TACKWELD TO BM FLANGE ATTACH ANGLE BRACKET WITH #10 SELFTAPPING SHEETMETAL SCREW V_ #10 GAUGE GALVINIZED WIRE HANGER (TYPICAL) 150 TYPICAL LIGHTING FIXTURE BOTTOM END TYPICAL 2'x4' & 2'x2' LIGHT FIXTURE HANGING DETAIL No Scale MINIMUM 15 OFF VERTICAL IVORY DEVICE & PLATE AS APPLICABLE PER CODE ON Q SWITCH DEVICE PLATE - ENGRAVED — 1/4" HIGH LETTERS, BLACK FILL ON IVORY IUND UP _\ a RECEPTACLE DEVICE PLATE GLUE ON LETTERS OF ANY TYPE WILL NOT BE ACCEPTABLE ENGRAVING TYPICAL FOR ALL EMERGENCY AND NORMAL CIRCUITS DETAIL ENGRAVING AT CRITICAL/NORMAL 5 BRANCH CIRCUITS No Scale RECEPTACLE SCREW CONDUIT-----, FINISHED WALL SURFACE GROUND WHIP #12 (TYP.) 777 DEVICE BOX COVER BOX SCREW WIRE NUT 'TO OTHER OUTLETS 1 /8" MAX. GAP NOTES: _ _ _ 1. ELECTRICAL DEVICE BOX COVER TO BE FLUSH WITH FINISHED WALL SURFACE. 2. ALL DEVICE BOX COVERS TO BE SQUARE CUT MANDATORY. DEVICE RING INSTALLATION No Scale TYPICAL ELECTRICAL DEVICE EMERGENCY CONDUIT WIRING MUD RINGS SHALL NOT BE GREATER THAN 1/8" FROM FACE OF FINISHED DRYWALL SURFACE (TYP. FOR ALL BOXES) NORMAL CONDUIT WIRING GROUND WHIP #12 (TYP.) TYPICAL LIGHT SWITCH BOX WITH NORMAL AND CRITICAL SWITCHES 2 No Scale INTERNALPANEL BOARD IDENTIFICATION CARDS SHALL BE TYPED WITH EXACT ROOM NAME AND NUMBER ��— CONDUITS AND BOXES SHALL BE COLOR CODED i/ AS FOLLOWS: LIFE SAFETY - YELLOW, CRITICAL - ORANGE, EQUIPMENT - GREEN, FIRE ALARM -RED. CONDUITS SHALL BE MARKED WITHIN 6 INCHES OF TERMINATIONS, EVERY 10 FEET AND WHEN ENTERING AND LEAVING A WALL. ALL JUNCTION BOXES SHALL BE MARKED WITH THE PANEL NAME AND NUMBER OF CIRCUITS IN THE BOX. 4" 3" PANELBOARD NORMALBRANCH 120/208/60/3 WHITE ON BLACK GENERAL NOTES: 1. VERIFY FINAL COLOR CODING AND NAMING CRITERIA WITH THE FACILITY STANDARDS. 3 TYPICAL ENGRAVING & COLOR CODING 4 No Scale ,`t11f�1f1ffff�,, ONO 63289 • STATE ; *� �0,11" IONAL EWZ� �pf0 fffftflttt Z O () U Z D W D V) U Z O on U U c Z O .� C4 X J- M y ° o U 4) 0 O o �d: v Lu 0 H c � _ O W) m Q 00 �. 0 0 M O �/ N CL CLO Date: 06. 03. 16 Scale: AS NOTED Project Mgr: PGG Drawn: MCF Job: 16-062 Sheet El 1