HomeMy WebLinkAbout38508 A Ave (2)�- UNITED FIRE 66L mumm- Providing World Me" Service FIRE ALARM SYSTEM WITH VESDA EARLY WARNING DETECTION SYSTEM FOR: VERIZON ZEPHYRHILLS CO 38508 A Ave. Zephyrhills, FL 33542 0 Headquarters 12001 31 st Court N. • St. Petersburg, FL 33716 • (727) 471-0860 • Fax (727) 471-0861 www.united-fire.com ail u 0ALMA j•,o.Ammm : 1111.•4• u1 _,- l lu .IW I:I _ ILh- _ HEIGHT REQUIREMENTS FOR WALL -MOUNTED DEVICES 1. EACH MANUAL FIRE ALARM BOX SHALL BE SECURELY MOUNTED. THE OPERABLE PART FOR EACH MANUAL FIRE ALARM BOX SHALL NOT BE MORE THAN ±48" (1.37 M) ABOVE FLOOR LEVEL. 2. WHERE CEILING HEIGHTS ALLOW, WALL -MOUNTED APPLIANCES SHALL HAVE THEIR BOTTOMS AT ±80" A.F.F. 3. WALL -MOUNTED VISUAL APPLIANCES SHALL BE MOUNTED ±80 IN. (2 M) FROM THE BOTTOM OF THE DEVICE TO THE FINISHED FLOOR. 4. WHERE COMBINATION AUDIBLE/VISIBLE APPLIANCES ARE INSTALLED, THE LOCATION OF THE INSTALLED APPLIANCE SHALL BE DETERMINED BY VISIBLE APPLIANCES. STROBE HORN/STROBE 0 0 CONTROL 1 VESDA PANEL PANEL MANUAL PULL F fso„ t 70" f 48" HEIGHT OF DEVICES DETAIL N.T.S. CODE SUMMARY: FIRE SUPPRESSION SYSTEM DESIGNED IN ACCORDANCE WITH: 1. FLORIDA FIRE PREVENTION CODE, 2010 EDITION. 2. NFPA 72, 2007 EDITION 3. RULES & REGULATIONS OF THE STATE FIRE MARSHALS OFFICE, AND ALL STATE AND LOCAL CODES. INSTALLATION NOTE: THE INTENT OF THE INFORMATION SHOWN ON THIS DRAWING IS TO PROVIDE THE SYSTEM INSTALLER WITH THE NECESSARY INFORMATION AS HOW TO WIRE FIELD DEVICES. ACTUAL CONDUIT ROUTING, CIRCUIT DIVISION, AND FIELD DEVICE LOCATIONS SHALL BE DETERMINED BY THE SYSTEM INSTALLER IN THE FIELD. FRONT -VIEW SECTION A -A F— A , 3 VA L2 4 A 1. GYPSUM WALL ASSEMBLY (U.L CLASSIFIED U300 OR U400 SERIES) 1-HR OR 2-HR FIRE -RATING) (2-HR SHOWN). 2. PENETRATING ITEM TO 8E ONE OF THE FOLLOWING: A. MAXIMUM 30" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER). B. MAXIMUM 30" NOMINAL DIAMETER CAST IRON PIPE. C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT. 3. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT: A. MINIMUM 5/8" DEPTH, FOR A 1-HR FIRE -RATING. B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR FIRE -RATING. 4. MINIMUM 1/2- BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT. NOTES: 1. MAXIMUM DIAMETER OF OPENING: A. 32-1/4" FOR STEEL STUD WALLS. B. 14-1/2' FOR WOOD STUD WALLS. 2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2-1/4". F RATING = 1-HR OR 2-HR. T RATING = O-HR. L RATING AT AMBIENT = LESS THAN 1 CFM/SQ. Fr. L RATING AT 4007 = LESS THAN 4 CFM/SQ. FT. INSTALLATION INSTRUCTIONS FOR UL NO. WL1054 STEP 1 - PREPARATION: ALL. SURFACES MUST BE CLEAN, SOUND, DRY AND FROST FREE PRIOR TO APPLICATION OF RRESTOPPING MATERIALS. STEP 2 - FIRESTOP SEALANT: APPLY THE REQUIRED DEPTH OF FIRESTOP SEALANT WITHIN THE ANNULUS ON BOTH SIDES OF WALL. TOOL WITH A PLiTY KNIFE UNTIL FLUSH WITH BOTH SURFACES. LEAVE COMPLETED SEAL UNDISTURBED FOR 48 HOURS. METAL PIPE THROUGH 1-HR. OR 2-HR. GYPSUM WALL ASSEMBLY N.T.S. TOP VIEW I A 75cd 56 L1-08O C P STOR. ROOM e DIA. (OR SMALLER) STEEL PIPE, COPPER PIPE, EMIT OR CONDUIT MIN. 1/2" DEPTH HILTI — FS 601 FlR(3TOP SEALANT >d� �A MIN. 4-1/2" THICK CONCRETE — FLOOR/WALL OR ANY U.L CLASSIFIED CONCRETE BLOCK WALL SECTION A -A 1/2" BEAD HILTI FS 601 !— MIN. 3" THICK MINERAL WOOL NOTES: (MR 4 PCF) TIGHTLY PACKED 1. MAXIMUM DIAMETER OF OPENING = 6". 2. ANNULAR SPACE = MIN. 0" (POINT CONTACT), MAX. 2". 3. WALLS REQUIRED 1/2" OF SEALANT FLUSH WITH BOTH SIDES. F RATING = 2-HR. T RATING = 0-HR. INSTALLATION INSTRUCTIONS FOR UL NO. CAJJ1149 STEP 1 - PREPARATION: ALL SURFACES MUST BE CLEAN, DAD. DRY AND FROST -FREE PRIOR TO APPLICATION OF MATERIALS. STEP 2 - BACKING MATERIAL: PACK MINERAL WOOL TGny AROUND THE PENETRATION ITEM TO THE DEPTH SHOWN IN THE DRAWINGS, AND RECESS IT BELOW A TOP SURFACE OF THE FLOOR (OR BOTH SURFACES OF A WALL) TO ALLOW PROPER SPACE FOR THE FIRESTOP MATERIAL - STEP 3 - FIRESTOP SEALANT: APPLY THE FIRESTOP SEAM OVER THE BACKNG MATERIAL TO THE DEPTH SHOWN. IF THE PIPE IS OFFSET TO ONE SIDE, APPLY A 1/2" BEAD OF FIRESTOP SEALANT AROUND ITS CIRCUMFERENCE WHERE IT CONTACTS THE WAIL OR FLOOR. WALL PENETRATIONS REQUIRE FIRESTOP SEALANT ON BOTH SIDES. LEAVE COMPLETED SEA. UNDISTURBED FOR 48 HOURS. METAL PIPE THROUGH CONCRETE FLOOR/WALL N.T.S. =L ML_L. I /O — 1 -LI FROM CONTRC PREVIOUS AGENT ICE MANUAL PULL STATION WIRING DIAGRAM N.T.S. 55-045 MINI MONITORING MODULE NOT TO SCALE SLC+1 FROM PANEL OR PREVIOUS DEVICE From Control Panel or Previous Device 0 0 +1 SLC TO NEXT DEVICE 4" OCTAGONAL BOX TRUE CEILING MOUNTING SCREWS ate', JUNCTION BOX OR PULL BOX FLEXIBLE CONDUIT / HEAD FALSE CEILING - CADDIE BAR g�E PART NO. 512 T-BAR FALSE CEILING DETECTOR MOUNTING DETAIL To next Device or EOL Resistor O 0 6 3-1 O 54 DETECTOR BASE N.T.S. 14. CUR T IS #3791 '211 5AX 352-588-19 29775 BAYHIEAD RD. DADE CITY., FL 33523 01-23 GENERATOR 75cd oc_ G 75cd S16r 2Y ZEPH Date amiewer: H 06) f4AVh :R:F,,.: !IItfiV!EWWb FIRE MARSHA1_.'S OFFICE Please be advised tIII, II , vY -lifted is a cursory review to assist flit contractor in : , dliance with applicable fire safety codes. This re ie f ;: �.) intended to be a final approval of the submitied : ,,s. It is file contractor's sole responsibility to ensure t" }; plans re in Lk/4( complete compliance with all applica`1:•: N codes . �d S� local ordinances. In the event th�r, e- : ninatio )r site inspection revez's areas of non -cc,:;:, ,�, it sh ae the contractor's sole responsibility, at the;-- A, exper . to bring those areas in compliance. The C,,., sumes no responsibility for the contractor's failure to b`- I, � compliance �l with all applicable NFPA Codes and local , rdinances. EQUIPMENT SCHEDULE AND LEGEND SYMBOL CITY PART NUMBER MODEL NUMBER DESCRIPTION MANUFACTURER FRCP 1 10-2542 10-2542 CHEETAH Xi CONTROL PANEL FIKE VLP 2 VLP-002 - VESDA LASER PLUS XTRALIS FV_PSj 1 VPS-3000S-120 - VESDA POWER SUPPLY -MULTI ZONE XTRALIS 2 BSL1116 PC1218 18AH BATTERIES INTERSTATE 4 BSL1105 PC12100 12AH BATTERIES INTERSTATE 18 63-1052 SLR-24V PHOTOELECTRIC DETECTOR FIKE <8> 6 60-1039 - HEAT DETECTOR FIKE 24 63-1054 - DETECTOR BASE FIKE ❑F 5 20-1063 - MANUAL PULL STATION FIKE 19 904-1317-002 GEC3-24WR HORN/STROBE 75cd) GENTEX 4 904-1321-002 GES3-24WR STROBE (75cd) GENTEX 2 904-1321-002 GES3-24WR STROBE (75cd) GENTEX MM 13 55-045 - MINI -MONITOR MODULE FIKE sCM 1 55-042 - SUPERVISED CONTROL MODULE FIKE 43 1 VARIES VARIES VESDA SAMPLING POINTS & PIPE XTRALIS _ PN1riL.PuNNnrn F7.. ILAU0r- rRD[ftlLre 5201 BROOK HOLLOW PKWY. SUITE C 10260 N.W. 47TH STREET - - NORCROSs, GA 30071 SUNRISE, FL 33351 (770) 889-6684 (954) 572-0119 (770)888-6685-FAX (954)572-0528-FAX L UNITED FIRE A Ix DOTS D>escx¢�rmx VERIZON ZEPHYRHILLS CO 38508 A Ave. Zephyrhills, FL 33542 FLOOR PLAN PROVIDINE WORLD CLASS SERVICE 1f4�U�iJIP'/A/wIIEG^aID}(o1lWG^�IRT1fIE�9� ORL.AKDO S SHOWN Ds""" BY D.PIERCE n> HyC. NORRIS 12001 31ST COURT N. r_V(0R1nA 31"goII�(Piq/,� 224 W.CENTRAL PARKWAY, SUITE 1020 ST. PETERSBURG, FL 33716 ALTAMONTE SPRINGS, FL 32714 4 JOB xu D):TIDfO AUI�t [� 02/10/14 13-1885TP FS - I OF 3 (727) 471-0860 90068800012000 9023B (407) 830-7000 (727) 471-0861-FAX EFOOOII85 LVA205328 (407) 830-7702-FAX L.L r N m C3 r f7 r v O J J CIL I LLj N 13 N_ 11 Ld I N Z n n J.I i Q J.I J.I Z J J_ T l LL W N Z N_ Y W Ln m m 71 D Ij J J_ LTL L lj N D N Y A 7 7 VLP-002 V-2 DETECTOR TYPE = VLP-002 SAMPLING PORTS = 22 0 9/64" END PORT = 1 0 9/64" RIGID DROP LENGTH = NONE ASPIRATOR SETTING = 3900 RPM END CAP = 3 APPLICATION = Ddp FIRE THRESHOLD = 0.023%/ft TEMPERATURE = 68.07 ABSOLUTE PRESSURE = 1013.OhPa SYSTEM FLOW RATE = 104.8 L/min MANIFOLD PRESSURE = 119 Pa TOTAL PIPE LENGTH = 327'-9" SAMPLE POINTS = 22 MAX TRANSPORT TIME= 53 sec MINIMUM HOLE FLOW = 1.0 L/min AMBIENT PRESSURE = 0 Pa SECTOR PRESSURE = 119 Pa SAMPLING PORTS = 22 Mounting dip r7777= Sampling holes Sampling pipe Ceiling I 1 Mounting clip V Mounting clip Sampling pipe Sampling pipe SAMPLING PIPE DETAIL NOT TO SCALE NUMBER OF PIPES DEPENDS ON DETECTOR TYPE. Vesdo Pipe a m a a a a OL 3/4" ConversAd-tors Ad - Ad tors w _ ®I VESDA DETECTOR N.T.S. Do Not Glue adaptors to Manifold NO VENT INSTALLATION NOTE: THE INTENT OF THIS DRAWING IS TO PROVIDE THE SYSTEM INSTALLER WITH THE NECESSARY INFORMATION AS HOW TO WIRE FIELD DEVICES. ACTUAL CONDUIT ROUTING, CIRCUIT DIVISION, AND FIELD DEVICE LOCATIONS SHALL BE DETERMINED BY THE SYSTEM INSTALLER IN THE FIELD. NO VENT N.T.S. S.P. 2.1 DIA. 9/64 S.P. DIA. 3.1 9/64 3.2 9/64 3.3 9/64 3.4 9 64 3.5 9/64 S.P. DIA. 2.2 9/64 1.1 9.64 2.3 9/64 3.6 9 64 1.2 9/64 3.7 9/64 2.4 9/64 1.3 9/64 2.5 12.6 9/64 3.8 9/64 1.4 9/64 9/64 3.9 9/64 EC 9/64 EC 9/64 EC NON VLP-002 V-1 DETECTOR TYPE = VLP-002 SAMPLING PORTS = 21 0 1/8- END PORT = 2 0 9/64" RIGID DROP LENGTH = NONE ASPIRATOR SETTING = 3900 RPM END CAP = 3 APPLICATION = Ddp FIRE THRESHOLD = 0.0239:/ft TEMPERATURE = 68.07 ABSOLUTE PRESSURE = 1013.OhPa SYSTEM FLOW RATE = 102.8 L/min MANIFOLD PRESSURE = 126 Pa TOTAL PIPE LENGTH = 336'-4" SAMPLE POINTS = 21 MAX TRANSPORT TIME= 53 sec MINIMUM HOLE FLOW = 1.0 L/min AMBIENT PRESSURE = 0 Pa SECTOR PRESSURE = 126 Pa SAMPLING PORTS = 21 INDEPENDENT CONSULTING P.E. JAMES M. CURTIS, P.E. FL P.E. 37912 - - - 11 fLl%wTA F7. LAUlinERDALE NOR BROOK HOLLOW PKWY. SUITE C 10260 N.W. 47TH STREET NORCROSS, GA 30071 SUNRISE, FL 33351 (770) 888-6685 (954) 572- AX (70) 888-668-119 FAX (954) 572-0528-FAX - - - BSVIWN DATE DESCH7710N MES '�' OURTIS #3791 I - 9-7 1A 35 2-54 -1 F VERIZON ZEPHYMR LS CO 38508 A Ave. - - - c� Zephyrhills, FL 33542 a 29775 B ^�YHEAD RD. VESDA ISOMETRICS (868)822-55" PROM 96 WOR10 CLASS SERVICE DADE (CITY F ` 352?j DO 2001 31STT COURT N. �V�� �eR �e /� 224 W.CENTRAL PARKWAY, SUITE FL�ORODA rMEOI��' OA ST. PETERSBURG, FL 33716 ALTAMONTE SPRINGS, FL 32714 (727) 471-0860 90068800012000 9023B (407) 830-7000 (727) 471-0861-FAX EFOOOII85 LVA205328 (407) 830-7702-FAX scAu AS SHOWN D.PIERCE ��� BYC. NORRIS JIM DAWN JOB NUN= DBATM NDIFB� 02 10 14 FS - 2 or 3 13-1885TP In m co r- 0 El U) J J Ix } 2 EL w N 0 N_ IX C7 T� N in I.LI X W W U L3 En IL N Z W i a Ln 113 In J J_ I } EL W N N_// LL _ j eul 10-1874A Comm. Cable C-Linx P2 (A) (A) (^A^^) • • • • • • OO r•�•••••• .. .. .. C INS O CS NC NO j.bFe NO •• •• •• Ff- * - - - - - - P6 P7 + - + - + - SHLD + - SHLD + - SHLD O OACT 11 PERIPHERALS �rrA+�c •w our AMLLARr anoua POWER LIMITED 24VDC AUXILIARY OUTPUTS. 2A max each PR AC POWER ALARM TROUBLE SUPERVISORY SILENCE 0 0 0 0 0 0 0 0 0 0 PRE -DISCHARGE RELEASE RELEASE -DISABLED ABORT GROUND FAULT J 0 DRILL RESET o ACIMOWLEDGE SILENCE a. In 0- JI z I� o" " F 1 F2 F--I 0- P: a ENTER D F5 F6 O F2 F1 T §2 C V Battw Fuca 1 AC Fua 7 CRT TRANSFORMER I BLACK I WHITE TIE INTO BUILDING STEEL OR GROUND PER MANUFACTURERS INSTRUCTIONS. SURGE SUPRESSOR DTK-120 HW i GROU 03 SCF z 3#12, 1/2"C TO DEDICATED (B) IN 0 ESCAPE 2'J1c__LOCATED ON MAIN BOARD BENEATH DISPLAY BATT #1 BATT #2 12VDC 12VDC 7AH TO 40AH 7AH TO 40AH L1-01 L1-02 L1-03 L1-04 L1-05 L1-06 L1-07 L1-08 L1-09 L1-10 L1-1 1 L1-12 L1-24 L1-23 L1-22 L1-21 L1-20 L1-19 L1-18 L1-17 L1-16 L1-15 L1-14 L1-13 II. . L1-25 MMM L1-26 MMM P9 40 N+ • I - D D :: • I K s I • F EOul L I EOL 1310 I PS-2 PS-4 r+ L1-27 MMM L1-28 MMM L1-29 MMM L1--30 MMM L1-31 MMM rs I I • I F EOK F EOL F EOL PS-1 PS-3 PS-5 P11 r w L1-32 MMM L1-33 MMM L1-34 MMM L1-35 MMM L1-36 MMM L1-37 MMM L1-38 MMM L1-39 MMM L1-40 MMM • I POWER VESDA VESDA VESDA VESDA VESDA VESDA VESDA VESDA TROUBLE TROUBLE ALERT ACTION FIRE1 FIRE2 TROUBLE ALERT ACTION - VESDA VESDA #1 VESDA #1 VESDA #1 VESDA #1 VESDA #1 VESDA #2 VESDA #2 VESDA #2 VP-1 O L1-43 SCM ` }c�C S 12 }=C 75cd VESDA tv Si STROBES �=C 75cd EOL S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 FQ 75cd QF 75cd Q 75cd F 75cd F 75cd Q 75cd FQ 75cd QF 75cd F. 75cd F. 75cd F. 75cd EOL CHEETAH Xi (P-1) RELEASE PANEL AND ALARM RISER DIAGRAM GENERAL ELECTRICAL NOTES 1. CONDUCTOR TYPE: - CONVENTIONAL CIRCUITS: THHN - STRANDED. - INTELLIGENT CIRCUITS: TWISTED SHIELDED 2. CONDUCTOR SIZE: - CONVENTIONAL CIRCUITS: #14 MINIMUM. - INTELLIGENT CIRCUITS: #18 MINIMUM. 3. RACEWAY AND SIZES: EMT, 1/2" MINIMUM. 4. IDENTIFICATION OF EQUIPMENT AND CATALOG NUMBERS OF ALL SYSTEM COMPONENTS: SEE SHEET BILL OF MATERIALS. 5. ALL COMPONENTS SHALL REFLECT U.L. LISTING FOR FIRE SERVICE AND SHALL BE COMPATIBLE, SEE ATTACHED SUBMITTAL DATA. 6. POWER LIMITED - 24 VDC. 7. ALL SIGNAL, 24V CIRCUITS, AND WIRING CIRCUITS SHALL BE WIRED USING #14 THHN STRANDED (19 STRAND). 8. 1 /2" MINIMUM CONDUIT OR 3/8" MC FOR RACEWAYS. 9. SYSTEM SHALL CONFORM TO ALL REQUIREMENTS OF NFPA 2001, NFPA 72, NEC CHAPTER 7 ARTICLE 760, CHAPTER 9 TABLE 313, FLORIDA ADMINISTRATIVE CODE, SECTION FOR F.S.S. FOR FIRE ALARM SYS. 69A-48, AND RULES AND REGULATIONS OF THE STATE FIRE MARSHALS OFFICE, F.S. 633.01 & 633.701 AND ALL STATE AND LOCAL CODES. N.T.S. COLOR CODE CONVENTIONAL SYSTEMS DET A=RED(+) & WHITE(-) DET B=ORANGE(+) & GREY(-) PULLSTATION=PURPLE (+) & YELLOW(-) ABORT=BLUE(+) & GREEN(-) TANK CKT=PINK(+) & BROWN(-) AUDIBLES ALL SYSTEMS BELLS=RED(+) & BLACK(-) HORN/STROBES=WHITE(+) & BLUE(-) DISCHARGE STROBES=PINK(+) & GREEN(-) ADDRESSABLE SYSTEMS COMM UNCATION=18/2 TWISTED SHIELDED 24VDC POWER=ORANGE(+) & GRAY(-) AUXILLARY FUNCTIONS PINK PURPLE YELLOW GREEN S13 S14 S15 S16 S17 S19 S20 S21 S22 S23 S24 S25 4.7K (B) •�. 75cd •QF • 75cd �• 75cd ��F 75cd :QF • 75cd •QF. 75cd QF 75cd QF 75cd F 75cd F 75cd FQ 75cd FQ 75cd EOL CIRCUIT CLASS AND WIRING STYLE SLC LOOP = STYLE 4 CLASS 8 24VDC = STYLE B CLASS B IDC = STYLE B CLASS 8 NAC 1 = STYLE Y CLASS B NAC 2 = STYLE Y CLASS B CONDUCTOR & RACEWAY SCHEDULE A = (CONVENTIONAL) 2 #14 STRANDED THHN IN 1/2" CONDUIT A = (INTELLIGENT) 2 #18 TWISTED SHIELDED IN 1/2" CONDUIT B = 3 #12 SOLID THHN IN 1/2" CONDUIT INSTALLATION NOTE: THE INTENT OF THIS DRAWING IS TO PROVIDE THE SYSTEM INSTALLER WITH THE NECESSARY INFORMATION AS HOW TO WIRE FIELD DEVICES. ACTUAL CONDUIT ROUTING, CIRCUIT DIVISION, AND FIELD DEVICE LOCATIONS SHALL BE DETERMINED BY THE SYSTEM INSTALLER IN THE FIELD. L1-41 I MMM I L1-42 I MMM VESDA VESDA FIRE 1 FIRE 2 VESDA #2 VESDA #2 L1-33 MMM MMM L1-34 L1-35 MMM MMM L1-36 MMM TERM. A _.... TERM. B TER SHIELDEll (NO A ® ISOOTEP C A+ ,,......i NC SHIELD NO B_ MINOR C �NC B+ FAULT E) NO +24V j C F� AUL�'f : GND NC POWER - POWER + NO 19 A "'.. ALEC fe- 00 P o 0 OEJ HO 0 Q n IILJ/ �Il ' I" I VESDA LASERPPLUS (V-1 ) L1-38 MMM O 0- L7 -40 M00 MM + OUT , O 0 4:1 L1-39 +OUT 2 O O MMM L1-41 _ fu'i SLC LOOP MMM +OUT °��"AnONY g FROM FACP 0 a u,,� L1-32 VLPPS IrNI MMM ® - _ wPPLY otx L1-42 �MLi NOIG�adl MMM VESDA POWER SUPPLY TERM. C TERMINATION CARD (VP-1) TERM. A TERM. B SHIELD ® AISOL;ATE6C INDN.T.B. R , _ . A+ ® NC SHIELD ® ® N BATTERY BATTERY ® FAULT �NO B+ NC NO ® N PWR F ;WRW' C/r NC 19 POWER - POWER + ® ALE�Ltqm ic `v NC 00 ° 0 0 0 [IFIF] O r1l 0 0 0 VESDA LASERPPLUS (V-2) BATTERY II BATTERY CHEETAH XI (P-1) BATTERY CALCULATIONS ADDED DEVICES STAND-BY DEVICE DEVICE DRAW TOTAL DRAW QUANTITY (AMPS) (AMPS) MAIN BOARD 1 .275 .2750 INTELLIGENT PHOTO DETECTORS 18 .00048 .0086 INTELLIGENT HEAT DETECTORS 6 .00022 .0013 INTELLIGENT PULL STATIONS 5 .00037 .0019 MINI -MONITOR MODULE 13 .00049 .0064 SUPERVISED CONTROL MODULE 1 .00063 .0006 TOTAL DRAW (AMPS) 2938 IN STAND-BY HOURS IN STAND-BY 24 02/10/14 X - AMPS/HOURS 7.051 REQUIRED ALARM DEVICE DEVICE DRAW TOTAL DRAW QUANTITY (AMPS) (AMPS) MAIN BOARD 1 .275 .2750 INTELLIGENT PHOTO DETECTORS 18 .002 .0360 INTELLIGENT HEAT DETECTORS 6 .002 .0120 INTELLIGENT PULL STATIONS 5 .002 .0100 MINI -MONITOR MODULE 13 .002 .0260 SUPERVISED CONTROL MODULE 1 .002 .0020 STROBE (75cd) 6 .116 .6960 HORN/STROBE (75cd) 19 .144 2.166 TOTAL DRAW (AMPS) 3.223 IN ALARM 02/10/14 X 5 MIN. ALARM (.084) .2707 + STAND-BY 7.051 - COMBINED AMP/HOURS 7.32 X DERATING FACTOR 1.2 _ TOTAL AMP/HOURS - 8.78 REQUIRED SPECIFICATIONS; • 2.OA IN STAND-BY • 6.OA MAX. TOTAL OUTPUT IN ALARM • 2.OA EACH FOR N.A.C. CKTS 1 & 2 • ALARM, TRBL, SUP. RELAYS; - 2.OA @ 30VDC - 0.5A 0 120VAC • 2.OA NON-RESETTABLE AUX. POWER • 2.OA RESETTABLE AUX, POWER CHEETAH XI (P-1) SLC LOOP POWER CALCULATIONS DEVICE SLC LOOP #1 SLC LOOP #2 DEVICE QUANTITY DEVICE QUANTITY DETECTORS 24 - MMM 13 - SCM 1 - RCM - - RM - - I CAPACITY - EACH SLC LOOP CAN SUPPORT UP TO 254 ADDRESSABLE DEVICES. TYPICAL V-1 & V-2 BATTERY CALCULATIONS STAND-BY SUMMARY DEVICE QUANTITY DRAW (AMPS) TOTAL AMPS VESDA LASERPLUS 1 2 .240 .480 TOTAL DRAW (STAND-BY) .480 ALARM SUMMARY DEVICE QUANTITY DRAW (AMPS) TOTAL AMPS VESDA LASERPLUS 2 .290 .580 TOTAL DRAW (ALARM) 580 CALCULATION SUMMARY STAN D-BY ALARM CURRENT .480 CURRENT .580 STAND-BY TIME 24 HRS. 24 ALARM TIME 5 MIN. 084 STAND-BY DRAW 11.52 ALARM DRAW 049 STAND-BY DRAW ALARM DRAW = COMBINED DRAW 1152 + 049 AMP/HOURS REQ. 11.57 TWO 12-AH BATTERIES SUPPLIED PER VESDA UNIT TOTAL OF 4 INDEPENDENT CONSULTING P.E. - - - AVLAA[M r/A L[�r- LWU=HOALL� JAMES M. CURTIS, P.E. FL P.E. 37912 NORCROSS, GA 30071 PXwY. SUITE C 10260 SUNRISE, FLS333351 0119 (770) 888-668(954) 5-AX (770)888-6685-FAX (954)572-0528 -FAX UNITED � E A - - - zurwmx IF DATE DESCRU'T= TIES I'A. CDR T IS #37012 81 7 1 - X 352-588-11 Pr VERIZON ZEPHYRHR LS CO 38508 A Ave. Zephyrhills, FL 33542 s lanh 29775 BAYHEAD RD, DADE CITY, FL 3 392 CHEETAH XI (P-1) RISER DIAGRAM (sea)922-SM4 PRO VZOI G IWDALS CLASS SERVICE 1fAMP�E@L4)C(11L ARTERS �fTh IU41�In ID(0� 12001 315T COURT N. K [ 224 W.CENTRAL P AY, SUITE 1020 L LL®L�LLJIA (CaI��L�C�ILU ST. PETERSBURO, FL 33716 ALTAMONTE SP vas, FL 32714 (727) 471 08611-FAX 9Q0EF000111185 00 LVA20 328 (407) 83�7702-FAX 8CALB AS SHOWN DBA11t BY D.PIERCE D1�61ilID BY C. NORRIS 149Dt DATE 02/10/14 JOB xDims� 13-1885TP DRA1nliG BDimse C r - Or