Loading...
HomeMy WebLinkAbout5935 7th St (4)A� 21-oy8y City Comments Attention Bill Burgess Subject Revisions for Permit Comments Company Davita Medical Group Date Permit Number U 2019.06.18� 5935 Th St Mr Burgess: In response to Owner request, the following has been revised for the above referenced project; 1. Sheets A100, A101.A Accessible parking spaces have been relocated from north to south of the existing covered walkway to take advantage of the existing parking lot slopes that are in the ranges allowed by the ADAAG. The spaces north of the canopy previously designated to be re -striped as accessible parking spaces will now remain as is. The walkway previously shown at those spaces has been relocated to the newly designated accessible spaces south of the existing canopy. There are two (2) parking spaces and one (1) van -accessible parking space complying with the FBC-Accessibility. Should you have any questions, please feel free to contact me by phone at 813-241-6700 or by e-mail at shellys@emaildsa.com. Sincerely, Andrew J. Dohmen, AR # 15805 Design Styles Architecture Inc. designstylesarchitecture.com 1708 E Columbus Drive Tampa, Florida 33605 813 241 6700 #AA0003393 Page 1 of 1 City Comments Attention Bill Burgess Subject Revisions for Permit Comments Company Davita Medical Group Date 2019.06.18 Permit Number 5935 7th St Mr Burgess: In response to Owner request, the following has been revised for the above referenced project; 1. Sheets Al00, Al OLA Accessible parking spaces have been relocated from north to south of the existing covered walkway to take advantage of the existing parking lot slopes that are in the ranges allowed by the ADAAG. The spaces north of the canopy previously designated to be re -striped as accessible parking spaces will now remain as is. The walkway previously shown at those spaces has been relocated to the newly designated accessible spaces south of the existing canopy. There are two (2) parking spaces and one (1) van -accessible parking space complying with the FBC-Accessibility. Should you have any questions, please feel free to contact me by phone at 813-241-6700 or by e-mail at shellys@emaildsa.com. Sincerely, Andrew J. Dohmen, AR #15805 Design Styles Architecture Inc. designstylesorchitecture.com 1708 E Columbus Drive Tampa, Florida 33605 813 241 6700 #AA0003393 Page 1 of 1 Transmittal Project DaVita Medical Group- Zephyrhills Date June 24, 2019 To: City of Zephyrhills Attn: Jackie Boges- Building Dept. 5335 8th Street Zephyrhills, FL 33542 From: Shelly Strange We Transmit ©Attached ❑ Under separate cover Via EXIOvernight Delivery ❑ Mail ❑ E-mail ❑ E-Fax ❑ Courier ❑ Other For ©Approval / Action ❑ Information ❑ Use as requested ❑ Comment ❑ Distribution ❑ Other The Following © Drawings ❑ Digital Files ❑Specifications ❑ Submittals [:1 Other 2 Owner Changes Letter 2 Revision 3 Drawing Sheets (3)- CS, A 100, A 10] .A 0 0 0 0 0 0 Comments designslylesarchitecture.com 1708 EColumbus Drive Tampa, Fiorido 33605 8132416700 #AA0003393 Page 1 of 1 a 1 EXIT ACCESS TRAVEL DISTANCE: 54' - 7" < 200'-0" (FBC T1017.2) DRAFTSTOPPING IN ATTIC: 5/8" GWB ATTACH TO ONE SIDE OF ROOF TRUSS (FBC 718.4) DEAD END: 10.-1" < 20'-0" (FBC 1020.4) U ♦♦♦ STORAGE x ° R —WI DER ♦ o I / ♦ z x 1 N� W% / 286SF xN/0 o ♦ 300 SF/OCC. o Nt p N ♦♦♦ i 11 NN j V / ♦♦ N 11 ♦ ♦ RI / ♦♦♦ M N / e I' ===7770 \\ i o M IVIED ROOM - I !_ / 11 °° M / 11 1 a -M / 1 CNN 11 C,+'>` CO T � I M I I -�. j l ��'� HOFT \ 1 BUSINESS AREA M I I // 11 ii ••�:• 1 47 M 1 100 SF/OCC. L- MI V. OFFICE 1 IN L i i ti I I N /� 1 i 1� 0 o 11 Sss♦fss✓fsssss��---------------- N OJ�/ I I Ie ® 34" 170 CE CD , ILLJ \ rn 1 J \ 001 1/ 0 0 1 -TM]DLAI 1 WORK , 1 1 � 1 111 tt / 1• • II ••-.,CHECK IN / OUT 11� N ••F—T--] F T -1 F—T--1 Fk 11 N / ACCESS-- ?� N :_. wP r -ST RAGE/ M ANICAI / I Z J 1 279SF ® 34" 170 5 32' -1" 300 SF/OCC. -- ��''------- 4---- --- -------- 1/I 1 1 e I / 1 / R_TDR i ACCESSORY ACCESSORY ACCESSORY ACCESSORY STORAGE/ STORAGE/ STORAGE/ STORAGE/ MECHANICAL MECHANICAL MECHANICAL MECHANICAL 1 1 1 1 38SF 67SF 47SF 47SF 300 SF/OCC. 300 SF/OCC. 300 SF/OCC. 300 SF/OCC. 1 ST FLOOR I IFESAFETY PLAN Nw'� O � BUSINESS AREA (ACCESSORY A-3 V% 3 LESS THAN 50 OCC) 22 � 15 SF/ TCC. 0 29' - 5" i I I I I r�IN Will COMMON PATH OF TRAVEL: 16-T < 75" (FBC T1006.2.1) METALSTUD U.L. 3A-40BC FIRE EXTINGUISHER FINISH WALL SEMIRECESSED F.E.C. DECAL ADA COMPLIANT FLUSH PULL HANDLE EQUIPMENT - FIRE EXTINGUISHER CABINET 1 1 /2" = V-0" LIFE SAFETY LEGEND EGRESS LOAD EGRESS CAPACITY IN # OF OCCUPANT — EGRESS WIDTH IN INCHES 24 227 34" = EGRESS CAPACITY ® = EXIT SIGN --� = EXIT TRAVEL DISTANCE -- = COMMON PATH OF TRAVEL DISTANCE 23 = OCCUPANT LOAD = FIRE EXTINGUISHER SURFACE _A_ - MOUNT �— = FIRE EXTINGUISHER SEMI RECESSED - � . �� = DRAFTSTOPPING Area Schedule (Gross Building) NAME FUNCTION OF SPACE GROSS/ NET OCC. LOAD FACTOR OCC. LOAD AREA SF PER OCC. GAS ACCESSORY STORAGE / MECHANICAL GROSS 38 SF 300 1 BIOHZD. (ACCESSORY STORAGE / MECHANICAL GROSS 94 SF 300 2 ELEC. 'ACCESSORY STORAGE / MECHANICAL GROSS 67 SF 300 1 STORAGE !ACCESSORY STORAGE / MECHANICAL GROSS 279 SF 300 1 STORAGE 'ACCESSORY STORAGE /MECHANICAL GROSS 286 SF 300 1 WAITING I BUSINESS AREA (ACCESSORY A-3 LESS THAN 50 OCC) NET 317 SF 15 22 BUSINESS !BUSINESS AREA GROSS 4700 SF 100 48 BUILDING TOTAL 5780 SF 76 60- design styles architecture 1708 E Columbus Drive Tampa, Florida 33605 p 813 241 6700 f 813 247 3757 designstylesarchitecture.com #AA0003393 All reproduction & intellectual property rights reserved 2017 Project ita Medical Group DMG (FL) - ZEPHYRHILLS 5935 7th Street Zephyrhills, FL 33542 Prepared for DAVITA MEDICAL GROUP In Association with: HEES & ASSOCIATES, INC. CONTACT: KARL HEES 1381 5TH ST SARASOTA, FL 34236 PHONE: 941.955.4555 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 ProfessiortI N , �3 No. Revision Description Date 1 PERMIT AND BID SET 12/10/2018 No. Revision Description Date PERMIT COMMENTS 3/8/19 r, I" Drawn By: WJ Checked By: SRS Project Number: 18190 5neet Tltle FIRST FLOOR LIFE SAFETY PLAN Original drawing is 24 x 36 Do not scale contents of drawing Sheet Number V-0" LS101 FIRE EXTINGUISHER KEY DESCRIPTION Count MANUFACTURER MODEL COLOR COMMENT FE01 SEMI RECESSED FIRE 13 SEE SPECS EXTINGUISHER CABINET PROPOSED PLAN - SERVICE YARD 2 1 /4„ = 1'-0" KEYED NOTES O 1 CONTRACTOR SHALL PROVIDE AND INSTALL AN EXHAUST AIR LOUVER EQUAL TO A RUSKIN EME6325D, WITH A MINIMUM FREE AREA OF 0.26 SF, UNDER THE EAVE OF THE ROOF, THE LOUVER SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND AS APPROVED BY THE LISTING OF THE LOUVER. O CONTRACTOR SHALL PROVIDE AND INSTALL AN OUTSIDE AIR INTAKE LOUVER EQUAL TO A RUSKIN EME6325D, WITH A MINIMUM FREE AREA OF 0.42 SF, UNDER THE EAVE OF THE ROOF. THE LOUVER SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND AS OVED E LISTI F THE L R. 3O CONT ACTOR SHA L FIELD VE IFY THE LOCATION OFT EXISTING OOF INSULATION. IF THE ROOF INSULATION IS ENTIRELY ABOVE OR ADHERES TO THE BOTTOM OF THE ROOF DECK THE CONTRACTOR SHALL INSTALL THE AHU WITH NO ADDITIONAL REQUIREMENTS. IF THE INSULATION IS INSTALLED ON THE TOP OF THE CEILING, THE GENERAL CONTRACTOR SHALL BUILD AN INSULATED BOX SURROUNDING THE AHU. THE BOX SHALL BE OF PROPER SIZE TO ALLOW FOR A PERSON TO SERVICE THE UNIT, SHALL INCLUDE REQUIRED CLEARANCES, PROPER LIGHTING FOR SERVICE. AND STRUCTURAL SUPPORT FOR THE UNIT, BOX, AND SERVICER. THE MECHANICAL CONTRACTOR SHALL PROVIDE A 4" SPIN -IN FITTING WITH A VOLUME DMAPER ON THE SUPPLY DUCT LOCATED WITHIN THE BOX, BALANCE TO 50 CFM. ROUTE INSULATED CONDENSATE DRAIN PIPING TO EXTERIOR OF BUILDING. TERMINATE INDIRECTLY A MINIMUM OF THREE INCHES ABOVE GRASSY AREA PIPE ROUTING SHALL NOT BE VISIBLE FROM WINDOW. PAINT WEATHER -EXPOSED PVC PIPING WITH ONE COAT OF UV RESISTANT PAINT. CONTRACTOR SHALL PLACE AHU ABOV LAY IN CEIL NGS OR PR VIDE AN APPRORIATELY IZED AC�PANEL..CONTRA R SHALL VIDEAN STALL A HAUST A O TO A RUSKIN EMED6325D, WITH A MINIMUM FREE AREA OF 0.19 SF, UNDER THE EAVE OF THE ROOF. THE LOUVER SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND AS APPROVED BY THE LISTING OF THE LOUVER. O CONTRACTOR SHALL ROUTE REFRIGERANT PIPING UNDERGROUND AND RISE UP INSIDE OF BUILDING. SEE DETAIL ON SHEET M402. GENERAL NOTES 1. CONTRACTOR SHALL INSTALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH ALL STATE AND LOCAL CODES. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK, PIING, SUPPORTS, ETC., NECESSARY FOR A PROPER INSTALLATION AND OPERATION OF NEW HVAC SYSTEM. 2. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. 3. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH A VOLUME DAMPER IN THE BRANCH CONNECTION UNLESS NOTED OTHERWISE. ALL ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED WITH CONICAL SPIN -IN FITTING WITH INTEGRAL VOLUME DAMPER. \v O Q 0 Q 61 design styles architecture 1708 E Columbus Drive Tampa, Florida 33605 p 813 241 6700 f 813 247 3757 designstyles©rc hitecture.c om #AA0003393 All reproduction & intellectual property rights reserved 2017 Project LCI Ua Medici Group Davita - Zephyrhills 5935 7th Street Zephyrhills, FL 33542 Prepared for JB Realty Partners In Association with: genesis f genesis engineering Ilc. s group, 2601 cattleman rd., suite 501 sarasota,9 34232 www.geneng.net coa#29304 _ project #1 8-189FL Professional Seal •• .• 9 * ; No. 551 _ • STA* • A, Q, OR ��� O1- A I No. Issue Description Date 1 PERMIT AND BID SET 12/10/2018 No. Revision Description Date 1 PERMIT COMMENTS 3/8/19 Drawn By: CTF Checked By: RMH Project Number: 18190 Sheet Title PROPOSED PLAN Original drawing is 24 x 36 Do not scale contents of drawing 11 Sheet Number PROPOSED PLAN 1 1 /4" = 1'-0r' 5935 7th Street Zephyrhills, FL 33542 NA F:7 Lm) 2: E F:1 Fi CONSTRUCTION RESPONSIBILITY MATRIX LAST UPDATED 11.26.2018 DAVITA F80 PROVIDED BY INSTALLED BY ITEM REQUIRED VENDORS PRICING OWNER GC OWNER GC �s STOREFRONT, ALUMINUM DOORS & GLAZING X X o � o oDOORS, FRAMES & HARDWARE X X VINYL SHEET FLOORING, LVP FLOORING, SHAW X X X CARPET & WALL BASE X INDEPENDENT MOISTURE TESTING IFTI X X PAINTS & PRIMERS SHERWIN-WILLIAMS X X X ACOUSTICAL CEILING SYSTEMS ARMSTRONG X X X C„ WALL PROTECTION CRANE COMPOSITES X X X w CORNER GUARDS INPRO CORPORATION X X X z U_ X X X TOILET ROOM ACCESSORIES FERGUSON EXTERIOR SIGNAGE J.L. GEISLER X X INTERIOR SIGNAGE J.L. GEISLER X X GRAPHICS & ARTWORK ENDLESS EDGE X X X CABINETS, COUNTERTOPS & PROCESS CHASE X X MILLWORK X X X SOLID SURFACE MATERIALS & INTEGRAL BOWLS DUPONT CORIAN U-i -- `� TELEVISIONS / MONITORS & MOUNTING BRACKETS X X FURNITURE OFFICE FURNITURE GROUP X X UJ LL REFRIGERATORS, FREEZERS. DISHWASHER & VARIES X X MICROWAVE z PLUMBING FIXTURES. HARDWARE & FERGUSON X X coACCESSORIES WATER HEATERS FERGUSON X X CL FIRE EXTINGUISHERS & CABINETS FERGUSON X X FIRE SPRINKLER SYSTEM X X U w - X LU FIRE ALARM SYSTEM X 9� - -U_ SECURITY ALARM SYSTEM X X MECHANICAL ROOFTOP EQUIPMENT & CURBS LENNOX X X X J � X EXHAUST FANS & SPLIT A/C UNITS X 'z Q LU MECHANICAL CONTROLS X X DUCTWORK, AIR TERMINALS, DAMPERS & X X ACCESSORIES ELECTRICAL PANELS & DISTRIBUTION EQUIPMENT X X ELECTRICAL RECEPTACLES, DEVICES & WIRING X X ACUITY X X LIGHTING FIXTURES & CONTROLS X J - U LOW -VOLTAGE DISTRIBUTION RACEWAYS X X U w "' I.T. EQUIPMENT, LOW -VOLTAGE DEVICES & WIRING X X NURSE -CALL SYSTEM, DEVICES & WIRING X X NOTES: 1. DAVITA MEDICAL GROUP HAS NEGOTIATED PREFERRED PRICING AND SERVICES WITH "REQUIRED VENDORS". GENERAL CONTRACTOR TO UTILIZE "REQUIRED VENDORS" WHERE INDICATED. SUBSTITUTIONS ARE NOT PERMITTED. 2. ITEMS "PROVIDED BY OWNER" REQUIRE A PURCHASE ORDER DIRECTLY FROM DAVITA MEDICAL GROUP. GENERAL CONTRACTOR TO COORDINATE SCHEDULE AND DELIVERY WITH REQUIRED VENDOR. 3. ITEMS "PROVIDED BY GENERAL CONTRACTOR" ITEMS ARE TO BE ORDERED AND PURCHASED BY GENERAL CONTRACTOR. 4. GENERAL CONTRACTOR RESPONSIBILITY FOR ITEMS "INSTALLED BY OWNER" SHALL INCLUDE COORDINATION OF SCHEDULE AND DELIVERY. 5. GENERAL CONTRACTOR RESPONSIBILITY FOR ITEMS "INSTALLED BY GENERAL CONTRACTOR" SHALL INCLUDE COORDINATION OF SCHEDULE AND DELIVERY, UNLOADING. TEMPORARY STORAGE, INSTALLATION. AND FINAL CONNECTIONS OF THOSE ITEMS. CONFIRM THE USE OF POSSIBLE PREFERRED SUBCONTRACTORS WITH THE DAVITA MEDICAL GROUP PROJECT MANAGER. VENDOR CONTACT SCHEDULE LAST UPDATED 11.26.2018 PRODUCT COMPANY CONTACT RESILIENT & CARPET FLOORING SHAW DAVITA.CUSTOMER@SHAWINC.COM (P) 1.888.393.2830 INDEPENDENT MOISTURE TESTING PAINTS & PRIMERS ACOUSTICAL CEILING SYSTEMS WALL PROTECTION CORNER GUARDS INTERIOR &EXTERIOR SIGNAGE GRAPHICS SOLID SURFACE MATERIAL & INTEGRAL BOWLS FURNITURE MECHANICAL ROOFTOP EQUIPMENT & CURBS LIGHTING FIXTURES & CONTROLS I.T. EQUIPMENT PLUMBING FIXTURES & EQUIPMENT UTILITY REBATES &INCENTIVES INDEPENDENT FLOOR TESTING & INSPECTION, INC. (IFTI) SHERWIN-WILLIAMS ARMSTRONG CRANE COMPOSITES INPRO CORPORATION J.L. GEISLER CORPORATION DAVITA TEAM WISDOM DUPONT CORIAN OFFICE FURNITURE GROUP, INC LENNOX ACUITY BRANDS / CONSOLIDATED ELECTRICAL DISTRIBUTORS DAVITA I.T. PROVISIONING, PROCUREMENT & CONTRACTS DAVITA.SPEC@IFTI.COM (P) 1.925.305.2907 LOCAL RETAIL STORE WM.SHERWIN-WILLIAMS.COM/STORE-LOCATOR/ ACCOUNT MANAGER: RICHARD MAY (P) 484.913.2508 LOCAL DISTRIBUTOR WWW.ARMSTRONG.COM/COMMCEILINGN A/LOCATE DISTRIBUTOR.JSP# JEFF TOLLE DAVITAFRP@CRANECOMPOSITES.COM (P) 815.274.9125 MARK FULLER MFULLER@INPROCORP.COM (P) 800.214.7749 / EXT. 5263 TAMMY KELLY TAMMY@JLGEISLER.COM (P) 1.586.574.1800 / EXT. 101 ETHAN HOOD ETHAN.HOOD@DAVITA.COM DAVID JAMISON DAVID.JAMISON@DUPONT.COM (P) 1.302.545.1246 KRISTY BANTA KBANTA@OFGINC.COM MARY ARENDASH MARENDASH@OFGINC.COM BLACKTEAM@LENNOXIND.COM (P) 1.800.367.6285 / OPT 11 OPT 1 / EXT. 6788 DAVITA@CEDNATIONALACCOUNTS. COM (P) 1.562.926.7202 CIRCUITPROVIS IONING@DAVITA.COM FERGUSON GRAHAM FERGUSON NSCSERVICE@FERGUSON.COM (P) 1.855.775.0600 SCHNEIDER ELECTRIC _J. 1!.f3:?NC: (N/.)V[CIAL KIERA DALEY KIERA.DALEY@EMS.SCHNEIDER-ELECTRIC.COM (P) 1.480.346.5837 DESIGN TEAM CLIENT ARCHITECT MECHANICAL / PLUMBING ENGINEER ELECTRICAL ENGINEER STRUCTURAL ENGINEER CLIENT: DAVITA MEDICAL GROUP FIRM: DESIGN STYLES ARCHITECTURE FIRM: GENESIS ENGINEER GROUP, LLC FIRM: GENESIS ENGINEER GROUP. LLC FIRM: HEES & ASSOCIATES, INC. CONTACT: SARAH MILLER CONTACT: SHELLY STRANGE CONTACT: MIKE HANEY CONTACT: MIKE HANEY CONTACT: KARL HEES PROJECT: DMG (FL) - ZEPHYRHILLS ADDRESS: 1708 E COLUMBUS DRIVE ADDRESS: 1000 N. ASHLEY DR. #900 ADDRESS: 1000 N. ASHLEY DR. #900 ADDRESS: 1381 5TH ST ADDRESS: 5935 7th Street Zephyrhills. FL 33542 TAMPA, FL 33605 TAMPA, FL TAMPA, FL SARASOTA, FL 34236 PHONE: (813) 241-6700 PHONE: 813.523.6455 PHONE: 813.523.6455 PHONE: 941.955.4555 CELL: 609.667.8659 CLIENT: CONTACT: JB REALTY PARTNERS SHALONJANES PROJECT: DMG (FL) - ZEPHYRHILLS ADDRESS: 5935 7TH STREET ZEPHYRHILLS, FL 33542 dsa PHONE: 803.581.4222 PROJECT DATA LOCATION: ZEPHYRHILLS, FL 33542 ADDRESS: 59357TH STREET PROJECT TYPE: NEW CONSTRUCTION: NO ADDITION: NO ALTERATION LEVEL: 2 PROJECT DESCRIPTION: REMODELING AND RENOVATIONS OF A FORMER OUTPATIENT SURGERY CENTER TO BECOME A NEW MEDICAL OFFICE APPLICABLE CODES: 6TH EDITION 2017 FLORIDA BUILDING CODE: ACCESSIBILITY 6TH EDITION 2017 FLORIDA BUILDING CODE: BUILDING 6TH EDITION 2017 FLORIDA BUILDING CODE: EXISTING BUILDING 6TH EDITION 2017 FLORIDA BUILDING CODE: PLUMBING 6TH EDITION 2017 FLORIDA BUILDING CODE: MECHANICAL 6TH EDITION 2017 FLORIDA BUILDING CODE: ENERGY CONSERVATION 6TH EDITION 2017 FLORIDA FIRE PREVENTION CODE FLORIDA SPECIFIC EDITION 2015 NFPA 101 LIFE SAFETY CODE NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2011 NFPA 70 - NATIONAL ELECTRIC CODE OCCUPANCY CLASSIFICATION: B BUSINESS RISK CATEGORY 2 EXPOSURE CATEGORY EXPOSURE B ASCE 7-10 WINDSPEEDS 140 MPH (1609.3(3)) BUILDING INFORMATION CONSTRUCTION TYPE: TYPE IIIB SPRINKLERED: NON-SPINKLERED STORY LIMIT: 2 STORIES (TABLE 504.4) ACTUAL STORIES: 1 HEIGHT LIMIT: 40' (TABLE 504.3) ACTUAL HEIGHT: 30' - 8" BUILDING AREA LIMIT: 19,000 SF (TABLE 506.2) TOTAL ACTUAL AREA: 5785 SF GROSS AREA PROJECT LOCATION MAP - NOT TO SCALE SHEET INDEX - CD SET SHEET NUMBER SHEET NAME REVISION DATE CS COVER SHEET 6/18/19 G001 IGENERALNOTES G002 I PARTITION TYPES SP01 SPECIFICATION SP02 SPECIFICATION SP03 SPECIFICATION SP04 SPECIFICATION SP05 SPECIFICATION SP06 SPECIFICATION SP07 SPECIFICATION SP08 SPECIFICATION SP09 SPECIFICATION LS000 LIFE SAFETY AND CODE INFORMATION LS101 FIRST FLOOR LIFE SAFETY PLAN 3/8/19 AD100 DEMOLITION SITE PLAN AD101 FIRST FLOOR DEMOLITION PLAN 5/15/19 AD101.R FIRST FLOOR DEMOLITION CEILING PLAN A100 SITE PLAN 6/18/19 A100.1 SITE PLAN DETAILS A101.A FIRST FLOOR NOTES PLAN 6/18/19 A101.D FIRST FLOOR DIMENSION PLAN 5/15/19 A101.R FIRST FLOOR REFLECTED CEILING PLAN Al02 SLAB PLAN A201 EXTERIOR ELEVATIONS 5/15/19 A351 WALL SECTIONS WITH DETAILS A401 ENLARGED PLANS A501 ENLARGED DETAILS A601 RESTROOM ENLARGED PLANS AND ELEVATIONS A652 MILLWORK ELEVATIONS A653 MILLWORK ELEVATIONS A654 MILLWORK DETAILS A655 MILLWORK SCHEDULE & DETAILS A701 DOOR AND WINDOW SCHEDULES AND DETAILS 5/15/19 A800 FINISH SCHEDULES & TRANSITION DETAILS A801 FIRST FLOOR FINISH PLAN A802 WALL FINISHES A901 FURNITURE. FIXTURES & EQUIPMENT PLAN 5/15/19 S-001 GENERAL NOTES S-101 FOUNDATION PLAN S-102 ROOF PLAN S-201 SECTIONS & DETAILS P001 PLUMBING LEGEND AND NOTES P002 PLUMBING SPECIFICATIONS PD100 PLUMBING DEMOLITION PLAN P101 PLUMBING NEW WORK PLAN - GRAVITY P102 PLUMBING NEW WORK PLAN - PRESSURE P201 PLUMBING RISER DIAGRAMS P202 PLUMBING RISER DIAGRAMS P301 PLUMBING SCHEDULE P401 PLUMBING DETAILS P402 PLUMBING DETAILS M000 LEGEND AND NOTES M001 SPECIFICATIONS M101 EXISTING PLAN M102 PROPOSED PLAN M301 MECHANICAL SCHEDULES M401 DETAILS M402 DETAILS E000 ELECTRICAL LEGEND, NOTES & ABBREVIATIONS E001 ELECTRICAL SPECIFICATIONS NOTES & SCHEDS E100 SITE PLAN E101 DEMOLITION FLOOR PLAN - ELECTRICAL E102 RENOVATION FLOOR PLAN - POWER E103 RENOVATION FLOOR PLAN - SYSTEMS E104 RENOVATION FLOOR PLAN - LIGHTING E201 ELECTRICAL SCHEDULES E301 POWER RISER DIAGRAM E302 FIRE ALARM SYSTEM RISER DIAGRAM E401 ELECTRICAL DETAIL E402 ELECTRICAL DETAILS Grand total: 70 PRODUCT APPROVALS LEGEND COMPONENT MANUFACTURER FLORIDA PRODUCT APPROVAL # NOA # STOREFRONT WINDOW KAWNEER COMPANY FL7237-R8 PROVIDE BY CONTRACTOR (MATCH EXISTING) dsa, design styles architecture 1708 E Columbus Drive Tampa, Florida 33605 p 813 241 6700 f 813 247 3757 designstylesarc hitecture.com #AA0003393 All reproduction & intellectual property rights reserved 2017 Project Dai ta Medic?! GCQUp DMG (FL) - '� ZEPHYRHILLS 5935 7th Street Zephyrhills, 3 FL 33542 Prepared for DAVITA MEDICAL GROUP In Association with: HEES & ASSOCIATES, INC. CONTACT: KARL HEES 1381 5TH ST SARASOTA, FL 34236 PHONE: 941.955.4555 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 Professional Seal e' C, 015805 � A -t" Andrew J. Dohmen, AR # 6/24/2019 15805 11:01:15 AM No. Revision Description Date 1 PERMIT AND BID SET 12/10/2018 No. Revision Description Date 1 PERMIT COMMENTS 2 OWNER REVISIONS 5/15/19 Drawn By: WJ Checked By: SRS Project Number: 18190 Sheet Title COVER SHEET Original drawing is 24 x 36 Do not scale contents of drawing Sheet Number C S / / W ' SITE PLAN 1 II _ 1 11 n SITE PLAN - PARKING lot = 101-011 SITE PLAN LEGEND design styles architecture 1708 E Columbus Drive Tampa, Florida 33605 p 813 241 6700 f 813 247 3757 designstylescucMecture.com #AA0003393 All reproduction & intellectual property rights reserved 2017 Project D)Nama Medical Group DMG (FL) - ZEPHYRHILLS 5935 7th Street Zephyrhills, FL 33542 Prepared for DAVITA MEDICAL GROUP In Association with: HEES & ASSOCIATES, INC. CONTACT: KARL HEES 1381 5TH ST SARASOTA, FL 34236 PHONE: 941.955.4555 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 rew J. Dohmen, AR # 6/24/2019 15805 11:01:12 AM No. Revision Description Date 4 13CORAIT Aklr% Dirt CCT 4n14/%Mfl40 1 Revision Description Date Drawn By: WJ Checked By: SRS Project Number: 18190 Sheet Title SITE PLAN Original drawing is 24 x 36 Do not scale contents of drawing Sheet Number 1 — 20 -0 Al 00_ > RA I CM LINC (A1 351 1026 A401 — - 1020 1020 W1 � 1111 7 7- ---------- --- - A201 3 i i i I STORAGE 124 s YA401 CARE MGR. I I OFFICE ' 125 I I I I I TEKM WORK I i 126 i\ F � 1103 I � F I Y A601 i i i 127 TEAMMATt 1 O--TO1tET J 128 \ 5 A401 , • I I MA E I I I 903 903 E2 FLEX EXAM 119 ,' 119 EXAM 2B I \\ 116 I 1110 CORRIDOR 120 I I I 1104 -_ I 12 A401 115 EXAM 2A - ' 115 1113 i 1110 MA / CLINIC NURSE STATIONS 118 ---- ----- ------ ---� I I - 1104 � \ -- ------ 107 108 F r � ORIF i-If nRl") — � ADMIN. OFFICE 106 I � J I 108 i71 hFF LAB I ul 107 I In; 1 I �' +I 1101 UI F I I. A401 — d I I 1104 ' 11711 F uI F F F VENIPUNCTURE 0 0 106 9 ��� I i \\ 1108 A401 F F I LAB TOILET 1 1113 1631 WORK _____---- �- , 103 I • I I Y I T AM TOI E1 1 I 7 1021 i I T i I CHECK IN / OUT A601 '2 TEAMMATE! 129 '_J 102 LOUNGE 127 I h F i \ i 131 I IIu------------------------------- _ ------ i i i i i i a i l — — — — — — — — — - - — — — — — 1110 I F li\r J.C. / W.H. 13 1107 1108 130 — 1104 4 � I� 102 WAITING 10 101 A401 STORAGE ' A401 0 E5 131 i EXIST. ELEC. STOR. ROOM COMM. BIOHZD. 134 - 133 132 135 903 90 i f ; . 1111 1106 I E1 1104 i i 1101 1104 3 1112 903 903 T , -- II i--T—i 1111 1111 1111 8 7 A401 PATIENT CORRIDOI 117 VITALS 109 903 A601 15 1036 201 TREATMENT 114 902 1017 � 3 VITALS ; - PATIENT-TL I A351 I � i A601 . 15 a �� 1017 �\ EXAM 1 B 111 `, 111 \ 1 903 T 0 TO 1110 903 EXAM 1A s� `' 1111 1020 1020 FLOOR PLAN - LEGEND 101 DOOR TAG 1 i PARTITION TAG 1 i STOREFRONT TAG Room name 101 A ROOM TAG o PROPOSED NEW WALL EXIST. WOOD STUD WALL PARTIAL HEIGHT WALL EXIST. CMU WALL �— FIRE EXTINGUISHER I� F—F] UNDER CABINET LIGHT GENERAL CONSTRUCTION NOTES 1. ALL WALL CONSTRUCTION SHALL BE SUPPORTED BY STRUCTURAL JOISTS. 2. CONTRACTOR SHALL FINISH ALL NEW AND EXISTING NON -WOOD DOORS AS INDICATED ON THE FINISH SCHEDULE. 3. ALL CEILING ASSEMBLIES SHALL BE NONCOMBUSTIBLE, CLASS W ACOUSTIC PANELS. GYPSUM BOARD SHALL BE NONCOMBUSTIBLE AND CONFORM TO FINAL REQUIREMENTS OF THE GOVERNING AUTHORITIES. 4. PROVIDE EXIT SIGNS AS REQ.'D WHICH SHALL CONFORM TO ALL APPLICABLE CODES. EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED BY TWO ELECTRICAL LAMPS OR SHALL BE OF AN APPROVED SELF -LUMINOUS TYPE. WHEN THE LUMINANCE ON THE FACE OF AN EXIT SIGN IS FROM AN EXTERNAL SOURCE, IT SHALL HAVE AN INTENSITY OF NOT LESS THAN 50 FOOTCANDLES FROM EITHER LAMP. INTERNALLY ILLUMINATED SIGNS SHALL PROVIDE EQUIVALENT ILLUMINESCENCE. THE COLOR AND DESIGN OF LETTERING, ARROWS AND OTHER SYMBOLS ON THE EXIT SIGN SHALL BE IN CONTRAST WITH THEIR BACKGROUND. WORDS ON THE SIGN SHALL BE IN BLOCK LETTERS, 6" IN HEIGHT WITH A STROKE OF NOT LESS THAN 3/4". 5. EXITS SHALL BE ILLUMINATED AT ANY TIME THE BUILDING IS OCCUPIED WITH LIGHT HAVING AN INTENSITY OF NOT LESS THAN 1 FOOTCANDLE AT FLOOR LEVEL. BLOCKING NOTE: GC TO PROVIDE ALL 3/4" THK. FIRE -RETARDANT IN -WALL & IN -MILLWORK PLYWOOD BLOCKING AS REQUIRED FOR TELEVISIONS, PLUMBING ACCESSORIES, COAT HOOKS, MILLWORK AND SIGNAGE. GLAZING FILM NOTE: SEE SHEET A201 FOR GLAZING FILM TYPES. • G2 POST -APPLIED TRANSLUCENT FILM • F1 POST -APPLIED BLACKOUT FILM KEYNOTES 902 TV MTD. ON WALL W/ POWER AND DATA BEHIND (RE: ELEC.) - GC TO PROVIDE BLOCKING AS REQUIRED. COORDINATE HEIGHT W/ A-601. 903 NEW PLAM SILL AT WINDOW SILL (TYP.) 904 PLAM WALL CAP 1016 REPLACE DOOR WITH WINDOW 1017 BLACKOUT FILM FROM INSIDE, INFILL WINDOW WITH FURRING, PATCH AND REPAIR GWB, PTD 1020 BLACKOUT FILM FROM INSIDE 1021 BOTTLE FILLER RECESSED 1022 SPECIMEN PASS THROUGH 1026 NEW WINDOW AS SCHEDULED 1036 EXISTING DOOR INCOPERABLE 1101 SSM COUNTER W/ CABINETS ABOVE & BELOW, TYP. 1103 PLAM COUNTER W/CABINETS ABOVE & BELOW 1104 LINE OF SOFFIT ABOVE 1106 REGIONAL WALL MILLWORK W/ TV - REFER TO MILLWORK DRAWINGS 1107 SSM RECEP COUNTER - REFER TO MILLWORK DRAWINGS 1108 PLAM COUNTER W/CABINETS BELOW 1110 PLAM COUNTER WIBACKSPLASH, SIDESPLASH & SS SINK W/ CABINETS ABOVE & BELOW 1111 G2 POST -APPLIED TRANSLUCENT FILM 1112 NEW PLAM SILL AT WINDOW SILL (TYP.) 1113 PLAM COUNTERTOP W/BACKSPLASH AND SIDESPLASHES design styles architecture 1708 E Columbus Drive Tampa, Florida 33605 p 813 241 6700 f 813 247 3757 designstylesarc hitecture.com #AA0003393 All reproduction & intellectual property rights reserved 2017 Project D)aVita Medical Group DMG (FL) - ZEPHYRHILLS 5935 7th Street Zephyrhills, FL 33542 Prepared for DAVITA MEDICAL GROUP In Association with: HEES & ASSOCIATES, INC. CONTACT: KARL HEES 1381 5TH ST SARASOTA, FL 34236 PHONE: 941.955.4555 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 GENESIS ENGINEER GROUP, LLC CONTACT: MIKE HANEY 1000 N. ASHLEY DR. #900 TAMPA, FL PHONE: 813.523.6455 r Professional SeaC " N J 0 0015905 'A Andrew` er+ AR ; . � /24/2019 15305 "`11:01:14 AM No. Revision Description Date 1 PERMIT AND BID SET 12/10/2018 No. Revision Description Date 3 OWNER REVISIONS 6/19/ 99 Drawn By: WJ Checked By: SRS Project Number: 18190 Sheet Title FIRST FLOOR NOTES PLAN A201 Original drawing is 24 x 36 Do not FIRST FLOOR -NOTE PLAN scale contents of drawing 1 1 /4" = 1'-0" Sheet Number Al 01 ■