HomeMy WebLinkAbout7631 Gall Blvd (29)ELECTRICAL SYMBOLS
LEGEND
10-m.10 ESM
(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
SYMBOL
DESCRIPTION
/ O
FLUORESCENT / LED OR HID FDCTURE
(WALL MOUNTED/CEILING MOUNTED)
10
FLUORESCENT/ LED FIXTURE
®
FLUORESCENT I LED FIXTURE,
NIGHT LIGHT
®
VOLUMETRIC LED FIXTURE
O
ENCLOSED FREEZER LIGHT
NZ
Aa
TRACK LIGHTING
/ ®
EXIT FIXTURE
(WALL MOUNTED)
EMERGENCY LIGHT
(KA-L MMOLNTED)
SINGLE POLE SWITCH
$3
3-WAY SWITCH
$4
4-WAY SWITCH
$K
KEYED SWITCH
4D
DIMMERSWITCH
*VS
VARIABLE SPED SWITCH
4m
MANUAL MOTOR SWITCH
SINGLE POLE OCCUPANCY
SENSOR SWITCH
DOUBLE POLE OCCUPANCY
SENSOR SWITCH
l
CEILING MOUNTED OCCUPANCY
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX,
MOUNTED HORIZONTALLY
RECEPTACLE, GFI
®
RECEPTACLE, DUPLEX FLUSH FLOOR
®
RECEPTACLE, DUPLEX. ISOLATED
GROUND FLUSH FLOOR
RECEPTACLE, DOUBLE DUPLEX
x
V
RECEPTACLE, DUPLEX
ISOLATED GROUND
RECEPTACLE, DOUBLE DUPLEX,
ISOLATED GROUND
RECEPTACLE, SIMPLEX TWIST LOCI,
L5-15R, UNO
RECEPTACLE, SIMPLEX TWIST LOCK,
ISOLATED GROUND, 1-5-1511, UNO
RECEPTACLE, DUPLEX TWIST LOCK,
1-5-15R, UNO
RECEPTACLE, DUPLEX TWIST LOCK,
ISOLATED GROUND, L5-15R, LINO
RECEPTACLE, SPECIAL
d)
RECEPTACLE, SIMPLEX
�111
RECEPTACLE, PLUG -MOLD
O
JUNCTION BOX
(WALL- MOUNTED)
O
I RMOSTAT
(WALL MOUNTED/CEILING MOUNTED)
�!
ALARM JUNCTION BOX,
(WALL MOUMEDICERM MOUNTED)
ALARM JUNCTION BOX,
®
FOR REMOTE TEST/RESET
(WALL MOUNTEDICEILING MOUNTED)
0
EQUIPMENT CONNECTION POINT
(PROVIDED WITH EQUIPMENT)
NOWFUSED DISCONNECT
Ell
FUSED DISCONNECT
CIRCUIT, CONCEALED N WNL.LS OR
CEILING, E INDICATES EXISTING
WIRING
CIRCUIT, CONCEALED N SLAB FLOOR,
E INDICATES EXISTING WIRNG
CIRCUIT, EXPOSED,
-�T
E INDICATES EXISTING WIRING
1--t
CONDUIT SLEEVE
=
FLASH MOUNTED PANELBOARD
SURFACE MOUNTED PANELBOARD
+------
MANUFACTURED WRING SYSTEM
-
TELEPHONE / DATA BOX FOR ISD
LOW VOLTAGE CABLE
BOX FOR OTHER
m
TELEPHONE, FLUSH FLOOR
O
MOTOR
0
TELEPOWE2 POLE
4
PUSH BUTTON
aBUZZER
SAIL SWITCH
JUNCTION BOX
SO
SMOKE DETECTOR
HORNISTROBE
®
DOOR HOLD OPEN
ABBREVIATIONS
CF (SING FAN
Co CHECK OUT
CW CASHWRAP
EF EXHAUST FAN
ETR EXISTING TO REMAIN
G GROUND
GFI GROUND FAULT CIRCUIT INTERRUPTER
IG ISOLATED GROUND
REC REFRIGERATION ELECTRICAL CONTRACTOR
RC REFRIGERATION CONTRACTOR
RH RADIANT HEATER
Sc SECURITY CAMERA
TR TAMPER RESISTANT
U H UNIT HEATER
WH WATER HEATER
WP WEATHER PROOF COVERPLATE
WR WEATHER RESISTANT RECEPTACLE
O
RELOCATE LIGHT SWITCH TO
V1ALL AND RECONNECT TO
EXISTING LIGHTING CIRCUIT
1
I
3C F��
SEAFOOD INTERNAL HIGH POWER PLAN
10=1'4r
KEY PLAN
1 11W _ V4r
ELECTRICAL KEYNOTES
16.4V E.C. SHALL COORDINATE WffH GENERAL
CONTRACTOR AND ARCI-IITECTURAL
DEMOLITION PLANS THE EXTENT OF
EECTRICAL DEMOLITION_ REAAOVE
CONDIATS AND WIRES ALL THE WAY BACK TO
ORIGINATING JUNCTION BOXES OR
PN*jXV DS- DEMOLITION SHALL NOT
AFFECT ACTIVECVZCUR& LABEL -
DEMOLISHED CIRCUTP N PANE EX) ARDS
AS'SPAW- COORDINATE EXACT
REOLAtEMENTS WITH EXISTING CONDITIONS
PRIOR TO BID.
16_W04 120 VOLT GENERAL PO W R CIRCUIT(S):
FURNISH AND INSTALL NEW 20 AMP,12D VOLT
CRCxUIT(S), OR AS SPECIFIED ON DRAWINGS
Fib FROM NEAREST 120 VOLT PANEL, WITH
ADEQUATE SPACE AND AMPACTTY. A CIRCUIT
BAKER FOR CIRCUITS INDICTED WITH
(GFI) SHALL BE GFCI TYPE FOR PERSONNEL
PROTECTION_
16.W07 208 VOLT GENERAL POWER CIRCUIT:
FURNISH AND INSTALL NEW 208 VOLT
CIRCUIT, AS SPECIFIED ON DRAWINGS. FEED
FROM NEAREST 208 VOLT PANEL, WITH
ADEQUATE SPACE AND AAMPACITY.
GENERAL POWER NOTES
1 TELEPO NM POLE(S): MOUNT JUNCTION BOX(ES) TO TOP
SIDE OF BOTTOM CHORD OF BAR JOIST_ INSTALL
FURNISH® PRE -WIRED POWER POLE AND TERMINATE
PROVIDED FLEXIBLE CONDUIT AND WIRING TO JUNCTION
BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO
SECURE TE EPOWER POLE PL.LI B TO BUILDING
STRUCTURE
2- PROVIDE LIQUID:nGHT FLEXIBLE METAL CONDUIT AND
WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO
EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION
POINT.
3- WIBRE ErQI>pMENT NAMEPLATE PROTECTIVE DEVICE
RATING DEFERS FROM S12E PROVIDED, CHANGE OUT
BRANCH! CIRCUIT WIRING AND OVERCURRENT DEVICE TO
APPROPRIATE RATING PER NEC.
4- ELECTRONIC FIRE PRoTEcTnvsEGuRrry ALARM BOXES
AND CONDUITS SHOWM ON POWER PLANS SHALL BE
PROVIDED UNDER THIS CONTRACT. N ADDITION, UNLESS
NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES
APPLY:
A- ALL ALARM JUNCTION BOXES SHALL BE
4'C4'X2-1/8' MINIMUM.
B- ALARM RACEWAYS SHALL BE 314' MINIMUM WITH
PILL VdRE AND NSt"TNG BUSHINGS AT END OF
VERTICAL RA(EV1AY RUN.
C- VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE
EITHER CONCEALED INSIDE WAALL OR SURFACE
MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL
VERTICAL RUNS SHALL BE TURNED 900EGREES AT
TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND
EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE
BY VERTICAL FLOOR TYPE LIFT.
5- UPON COMPLETION OF ELECTRICAL INSTALLATION AND
PRIOR TO ENERGIZING CRCUIT-
A- INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.
B- PERFORM CONTNUITY TEST.
C- VERIFY PROPER PHASING CONNECTION TO ALL THREE
PHASE MOTOR LOADS.
20A WIRE SIZING SCHEDULE
ALL WIRE SIZES SHOWN ON PANEL SCHEDULES AND
PLANS ARE INTENDED TO BE MINMALIIM ACCEPTABLE
WIRE SIZE -
THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE
WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT).
LENGTHS; (N FEET) ARE INTENDED TO BE MAXIMUM.
FINAL CONNECTIONS: WHERE 20A BRANCH CIRCUITS
HAVE 08 AND LARGER WIRE CALLED OUT, #10AWG WIRE
MAY BE USED FOR THE FINAL CONNECTION (16 MAX.)_
12D VOLT
#12
#10
#8
#6
1S AMPS
200 FT.
325 FT.
4W FT.
7T0 HT.
6-10 AMPS
100 FT.
160 FT.
245 FT.
385 FT.
1145 AMPS
70 FT.
110 FT.
165 FT.
255 FT.
277 VOLT
#12
#10
#8
#6
1S AMPS
4W FT.
760 FT.
1170 FT.
1865 FT.
6-10 AMPS
240 FT.
380 FT.
585 FT.
930 FT.
11-15 AMPS
160 FT.
250 FT.
390 FT.
620 FT.
GENERAL NOTES
06.31.12 EN08
1- FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND
LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS,
READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH
NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURERS
RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS.
A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS
THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR
WVALL.S.
B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE
C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE
OPERATIONS. COORDINATE ALL DISRUPTIONS WITH
WWLMART CONSTRUCTION MANAGER AND STORE MANAGER.
D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESSES
BEFORE INSTALLING BOXES. FURNISH AND INSTALL
EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED.
E- CONTRACTOR SHALL VERIFY THAT ALL AFFECTED
PANEBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS
PROPERLY COVERED AND THAT ALL TRIM IS IN GOOD
CONDITION, ALLOWING NO ACCESS TO LIVE PARTS.
2- PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
A- FIRE RATED WALLS- SEAL PER SPECIFICATIONS FOR FIRE
STOPPING.
B NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL
C FREEZERCOOLER BOXES: SEAL WITH EXPANDING FOAM
SEALANT.
D- EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR
SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED
DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY
PENETRATIONS.
3- PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR
(SIZE PER NEC) N PVC TYPE CONDUIT, POWER CIRCUITS,
ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS.
CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600
VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT
GROUNDING CONDUCTOR
4- WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM
FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED
OTHERWISE ON PLANS. COORDINATE THE STANDARD
MOUNTING HEIGHTS WITH MASONRY:
A. SWITCHES +46'
B. RECEPTACLES +20'
C. VOK;F"TA +20'
5- WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT
IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING
DIAGRAMS.
6- CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
PANELBOARD IDENTIFICATION SCHEDULES FOR PANE BOARDS
AFFECTED BY REMODEL-
7- NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN
EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL
MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT
PROTECTIVE DEVICES
8- BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG THHN
UNLESS NOTED OTHERWISE N SCHEDULES. WHERE 20A
BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10
AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION
(15-FT MAXIMUM)_
9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND
DERATE CURRENT CARRYING CONDUCTORS PER NEC.
10. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE
SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS.
UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR
SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS.
1i. DEVICES SHOWN ON COOLEWFREEZER PANELS SHALL BE
SURFACE MOUNTED UNLESS NOTED OTHERWISE REFER TO
ARCHITECTURAL DOCUMENTS FOR CONDUIT INSTALLATION AND
SEALING REQUIREMENTS.
12. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM
AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE
INSTALLED UNDER SLAB. ALL OTHER FEEDER AND BRANCH
CIRCUITS SHALL BE INSTALLED OVERHEAD. PROVIDE EXTERIOR
COATED GRC BENDS ON ALL CONDUIT RUINS THAT HAVE 45
DEGREE BENDS OR GREATER REF SPECIFICATIONS.
13. SEISMIC ZONE REQUIREMENTS-. PROVIDE EXPANSION COUPLINGS
AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY
LOCAL CODES.
14. EXISTING ELECTRICAL AND ALARM:
A- WHERE DEMOLITION OR NEW INTERRUPTS
EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING
EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT
SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO
REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING
OPERATION.
B• IF DEMOLTION OR NEW CONSTRUCTION WILL DISRUPT
EXISTING UNDERGROUND SERVICES (ELECTRICAL,
TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC-)
PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO
REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES
TO MAINTAIN THEIR EXISTING OPERATION.
C LSE CAUTION AROUND At AND SECURITY CABLES
- EXERC
DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM
AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO
THAT SYSTEMS REMAIN OPERATIONAL AT ALL TINES.
D- DISPOSE OF ALL REMOVED MATERIALS, UNLESS OT'HERWWSE
NOTED.
15. EXISTING ELECTRICAL DEbbLf170N:
A- GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL
EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON
THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION.
SCO NE T SWITCHES BOXES
0
w m m%O Cw0Dy
W p moMaz
wTwww w 1a
ix
~Q���mam°am
lL cFLI 0) aLLF?Wit Wi
z 22 �am�00 rOZp
O g 0 ogj`�fsa-
$� 05 m�� I'i p
D a luo aumn—wom
IL
pmo"'°�g` Sma°cmw S
w x i nook-0 ww-wx
Ego
gZ■
0
� S
Z
z
�_
U
�$
z
w
O O
w
O C=
OO
J
w
O
J
M
$
Z
1.i..
0
Z
O
N
N
w
m
D
z
O
ISSUE BLOCK I
CHECKED BY:
SAG
DRAWN BY:
JOP
FEE N
E1
PROTO CYCLE
07/03/18
DOCUMENT DATE:
07/25/18
REMOVE ALL PANELBOARDS, DI N C ,
RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH
WILL NOT BE REUSED.
B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT,
CONDUCTORS AND RELATED DEVICES SERVING SALES AREA
GONDOLAS BEING RELOCATED OR REMOVED. EXISTING
CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW
POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET
REQUIREMENTS INDICATED ON PLANS AND ALL U.L RATINGS. REL40VE ALL
D CONDUIT AND
CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER ����````0'
FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS'SP,
PROVIDE HANDLE DEVICE TO LOCK'SPARE' CIRCUIT * 19
BREAKER IN THE `OFF` POSITION. = * =
C- CONDUIT AND WIRING TO BE ABANDONED IN CEILING " 78 L ST
SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROU6g,0wk ; uG 0 3 2�t8
STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE�i �iQ "' O pP �� ���
FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE -
CONDUIT
CONDUIT TO 13E ABANDONED IN WALLS OR FLOORS SHALL /lllll
BE REMOVED BACK TO FINISHED SURFACE AND CAPPED
INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT. RIIINI�1 ' ��' P.E.
D- ALL C9RCUT BREAKERS SERVING BRANCH CIRCUITS TO BE FL I179819
ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE
PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE
ON DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK'SPARE`
CIRCUIT BREAKER IN THE'OFF' POSITION.
E- DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO
SELECTIVE SITE SON SPECIFICATION FOR
DISPOSAL OF LIGHT FIXTURE.
F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF
WORK SHALL BE SECURED TO PREVENT FALLING,
LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE
FUTURE.
EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT AS-BUILr CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDIITONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION ION WITH ALL OTHER DIMMES AMID
EXISTING CONDITIONS.
NOTE:
RECEPTACLES, SWITCHES, DATA BOXES
AND THEIR CORRESPONDING COVER
PLATES SHALL BE WHITE NYLON.
EACH SLBCONTRATOR IS RESPONSIBLE FOR HAVING A
THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE
ELECTRICAL
PLANS
SHEET -