Loading...
HomeMy WebLinkAbout7866 Gall Blvd (6)k 4 August 3, 2023 City of Zephyrhills 5335 &' Street Zephyrhills, Florida 33542 Re: AdventHealth Well 65+ - Zephyrhills PEI Job #22121 To Whom it May Concern, The following letter contains changes made to the above -referenced project: Mechanical Sheet Ml.l Revised diffuser/grille locations per shifts in Architectural Reflected Ceiling Plan. Relocated ductless split indoor unit per shifts in Architectural Floor Plan. Sheet E1.1 Revised drawing to add fire alarm specifications. Sheet E2.1 Revised drawing to reflect actual electrical service layout per updated shell plans. Sheet E31 Revised location of light fixtures per updated reflected ceiling plan from Architect. Revised location of receptacles per updated Architectural Plan. Added fire alarm devices throughout suite. Sheet E3.2 Revised drawing to show fire alarm devices for HVAC units on roof Revised notes accordingly. Sheet E4.1 Revised Panel Schedules. Sheet E5.1 Revised drawing to reflect actual electrical service riser per updated shell plans. Added fire alarm riser diagram. Sheet E5.2 Revised Light Fixture Schedule. EXCELLENCE IN ENGINEERING SINCE 1977 2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 ■ VOICE 407.246.1688 ■ FAX 407.246.1664 ■ www.peifla.com Ll 2 Plumbing Sheet P2.1 Revised Sanitary Plan per shift in Architectural Floor Plan. Sheet P2.2 Revised Domestic Water Plan per shift in Architectural Floor Plan. Sheet P3.1 Revised sanitary riser per shift in Sanitary Plan. Sheet P3.2 Revised domestic water riser per shift in Domestic Water Plan. September 20, 2021 Should you have any questions concerning this matter, please do not hesitate to contact our office_ `�®®a�+�taa�'g�1 ®�®® ��� '''°see•°• SPAV, ��• Sincerely, No.64601 «n Bryan Spangler ;• STATE OF e Vice -President ®�,�. °•°F� 0M0P: FL #64601 coA�® �6' •°ssss esse P� ®6 VON At- BGS ja:d:ggkl �� v3 EXCELLENCE IN ENGINEERING SINCE 1977 2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 ■ VOICE 407.246.1688 . FAX 407.246.1664 . www.peifla.com August 3, 2023 City of Zephyrhills 5335 8"' Street Zephyrhflls, Florida 33542 Re: AdventHealth Well 65+ - Zephyrhills PEI Job #22121 To Whom it May Concern, The following letter contains changes made to the above -referenced project: Mechanical 74 Sheet M1.1 Revised diffuser/grille locations per shifts in Architectural Reflected Ceiling Plan. Relocated ductless split indoor unit per shifts in Architectural Floor Plan. Electrical Sheet E1.1 Revised drawing to add fire alarm specifications. Sheet E2.1 Revised drawing to reflect actual electrical service layout per updated shell plans. Sheet EM Revised location of light fixtures per updated reflected ceiling plan from Architect. Revised location of receptacles per updated Architectural Plan. Added fire alarm devices throughout suite. Sheet E3.2 Revised drawing to show fire alarm devices for HVAC units on roof. Revised notes accordingly. Sheet E4.1 Revised Panel Schedules. Sheet E5.1 Revised drawing to reflect actual electrical service riser per updated shell plans. Added fire alarm riser diagram. Sheet E5.2 Revised Light Fixture Schedule. EXCELLENCE IN ENGINEERING SINCE 1977 2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 ■ VOICE 407.246.1688 ■ FAX 407.246.1664 ■ www.peifla.com 2 September 20, 2021 Plumbing Sheet P2.1 Revised Sanitary Plan per shift in Architectural Floor Plan. Sheet P2.2 Revised Domestic Water Plan per shift in Architectural Floor Plan. Sheet P3.1 Revised sanitary riser per shift in Sanitary Plan. Sheet P3.2 Revised domestic water riser per shift in Domestic Water Plan. Should you have any questioiN%WMbHAt@�9this matter, please do not hesitate to contact our office. G SP`q/!t ®`® -1 mod. Sincerely, QQ , �,O E NSF •• • No.64601 't, STATE OF . Bryan Spangler 0R% '••;cIOR!®P.••r�tt' Vice -President �•••..••••• FL #64601 a It /ONA' �® BGS.ja:tl:gg:kl It ?i:% EXCELLENCE IN ENGINEERING SINCE 1977 2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 a VOICE 407.246.1688 ■ FAX 407.246.1664 a www.peifla.com A2.0 CONSTRUCTION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN PIPES. A2.1 DIMENSION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN PIPES. A2.3 DOOR & WINDOW ELEVATIONS & SCHEDULE - CORNER MULLIONS ADDED TO HUDDLE ROOM STOREFRONT ELEVATIONS. DOOR 123 ADDED TO DOOR SCHEDULE, CHANGES MADE TO HARDWARE SETS. A3.0 REFLECTED CEILING PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN PIPES. A4.0 FINISH PLAN - FINISH PLAN UPDATED TO REFLECT PLAN CHANGES. A4.1 FINISH LEGEND & DETAILS- FINISH LEGEND AND DETAILS UPDATED FINISH SPECIFICATIONS A5.0 MILLWORK - MODIFIED MILLWORK & SPECIFICATIONS. SEE SEPARATE ENGINEERING NARRATIVE FOR ENGINEERING DRAWING CHANGES. Please call or e-mail the contact below at this office for any questions or concerns. Sincerely, Frank W. Campbell AIA Principal CAMPBELL + VAN DUSEN DESIGN STUDIO FLORIDA LICENSE: AR 0016053 Frank@CampVanDesignStudio.com Digitally E OF F( signed by Z' Frank �ARNIM Campbell Date: .w aw q:ira mp<aams re mimwaem.q.a 2023.08.14 09:59:00 -04'00' 2of2 CampVanDesignStudio.com 255 S. Orange Avenue Suite 107, Orlando FL 32801 p. 407-697-9954 f. 407-898-2559 CAMPBELL + VAN DUSEN DESIGN STUDIO 255 SOUTH ORANGE AVENUE STE 1240 ORLANDO, FLORIDA. 32801 407. 930. 6016 NOTICE OF DRAWING REVISIONS - REVISION 1 04 AUGUST 2023 Project Name: Advent Health Well 65+ Zephyrhills Project Address: 7866 Gall Boulevard Zephyrhills, Florida 33541 The following drawings have been revised, clouded, and marked with delta 1, Revision 1, dated August 04, 2023 PLANS EXAMINER COMMENT (BILL BURGESS: AUTOMATIC FIRE SPRINKLER INSTALLATION REQUIRES SEPARATE PERMIT. ARCHITECT'S RESPONSE. PER PRIOR DISCUSSION WITH CITY AUTOMATIC FIRE SPRINKLERS ARE NOT REQUIRED FOR THIS PROJECT DUE TO BUILDING TYPE, USE, SIZE. VISIBILITY IS PROVIDED THROUGH GLASS ENCLOSED NURSE STATION TO ALL PATIENT EXAM ROOMS. PLANS EXAMINER COMMENT (BILL BURGESS: FIRE ALARM REQUIRES SEPARATE PERMIT. ARCHITECT'S RESPONSE: ACKNOWLEDGED. PLANS EXAMINER COMMENT (BILL BURGESS: ADDITIONAL EXIT SIGNS REQUIRED AT DOOR SEPARATING DOCTOR'S WING.. ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6 AND ENGINEERS DRAWING E3.1 FOR ADDED EXIT SIGNS. PLANS EXAMINER COMMENT (BILL BURGESS: WILL REQUIRE EXIT FROM BREAKROOM REMOVING FIRE SPRINKLERS CREATED DEAD-END CORRIDOR OVER 20'. NOTE DEAD END CORRIDOR ON PLAN REVIEW COMMENT. ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6, A2.0, A2.1, A3.0, A4.0 AND ENGINEERS DRAWINGS FOR RECONFIGURED CORRIDOR ELIMINATING DEAD-END. DRAWING REVISION LIST: ALL CHANGES CLOUDED AND MARKED WITH REVISION 1 A0.0 COVER SHEET - MODIFIED LIFESAFETY INFORMATION A0.6 LIFESAFETY PLAN - MODIFIED ROOMS 101, 102, 128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF A2.0 CONSTRUCTION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN PIPES. A2.1 DIMENSION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN PIPES. A2.3 DOOR & WINDOW ELEVATIONS & SCHEDULE - CORNER MULLIONS ADDED TO HUDDLE ROOM STOREFRONT ELEVATIONS. DOOR 123 ADDED TO DOOR SCHEDULE, CHANGES MADE TO HARDWARE SETS. A3.0 REFLECTED CEILING PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN PIPES. A4.0 FINISH PLAN - FINISH PLAN UPDATED TO REFLECT PLAN CHANGES. A4.1 FINISH LEGEND & DETAILS- FINISH LEGEND AND DETAILS UPDATED FINISH SPECIFICATIONS A5.0 MILLWORK - MODIFIED MILLWORK & SPECIFICATIONS. SEE SEPARATE ENGINEERING NARRATIVE FOR ENGINEERING DRAWING CHANGES. Please call or e-mail the contact below at this office for any questions or concerns. Sincerely, Frank W. Campbell AIA Principal CAMPBELL + VAN DUSEN DESIGN STUDIO FLORIDA LICENSE: AR 0016053 Frank@Camr)VanDesianStudio.com Digitally �aFF� signed by -"`°"":: Frank �.APMIM3 Campbell Date: 2023.08.14 09:59:00 -04'00' 2of2 CampVanDesignStudio.com 255 S. Orange Avenue Suite 107, Orlando FL 32801 p. 407-697-9954 f. 407-898-2559 LETTER OF TRANSMITTAL DATE 8/II/23 JOB No. 22121 ATTENTION REPROGRAPHICS MANAGER JOB NAME WELL 65 ZEPHYRHILLS JOB ADDRESS WE ARE SENDING YOU 2016 ALDEN ROAD ® ATTACHED ❑ UNDER SEPARATE COVER VIA THE FOLLOWING ITEMS: ORLANDO, FLORIDA 32803 VOICE 407.246.1688 FAx 407.246.1664 ❑ SHOP DRAWINGS ❑ PRINTS ® PLANS ® PLOTS ❑ SPECIFICATIONS EMAIL PEI@PEIFLA.COM ❑ COPY OF LETTER ❑ ELECTRONIC FILES ® REV I- DELTA I COPIES DATE NO. DESCRIPTION 2 NARRATIVES 2 SETS WETSTAMPED SIGNED AND SEALED DRAWINGS THESE ARE TRANSMITTED AS CHECKED BELOW: ❑ FOR APPROVAL ❑ APPROVED AS SUBMITTED ❑ RESUBMITTED COPIES FOR APPROVAL ® FOR YOUR USE ❑ APPROVED AS NOTED ❑ SUBMIT COPIES FOR DISTRIBUTION ® AS REQUESTED ❑ RETURNED FOR CORRECTIONS ❑ RETURN CORRECTED PRINTS ❑ FOR REVIEW AND COMMENTS ❑ ❑ PRELIMINARY PLANS - NOT FOR BU)M OR CONSTRUCTION ❑ PRINTS RETURNED AFTER LOAN TO US REMARKS NOTE TO REPROGFIPAHICS MANAGER - PLEASE ATTACH THESE DRAWINGS WITH THE ARCHITECTS PLANS COPY TO: FILE THANKS SIGNED: PRINT NAME: JAMES ABT IF ENCLOSURES ARE NOT AS NOTED, KINDLY NOTIFY US AT ONCE. *Constructors integrity in construction August 10, 2023 City of Zephyrhills Building Department 5335 Eighth Street Zephyrhills, FL 33 RE: P# B C-006055-2023 We are submitting revisions for Arch, MEP and r r P# BNC-006055- 2023 located at 7866 Gall Blvd, per building official comments. Please see narrative submitted. Sincerely, David T Smith sq a, sao b CzYV\- One Tampa City Center 201 North Franklin Street, Suite 200 Tampa, FL 33602 P: 813.287.9000 1 F: 813.287.9010 iConstructors.com CAMPBELL + VAN DUSEN DESIGN STUDIO 255 SOUTH ORANGE AVENUE STE 1240 ORLANDO, FLORIDA. 32801 407. 930. 6016 NOTICE OF DRAWING REVISIONS - REVISION 1 04 AUGUST 2023 Project Name: Advent Health Well 65+ Zephyrhills Project Address: 7866 Gall Boulevard Zephyrhills, Florida 33541 The following drawings have been revised, clouded, and marked with delta 1, Revision 1, dated August 04, 2023 PLANS EXAMINER COMMENT (BILL BURGESS: AUTOMATIC FIRE SPRINKLER INSTALLATION REQUIRES SEPARATE PERMIT. ARCHITECT'S RESPONSE: PER PRIOR DISCUSSION WITH CITY AUTOMATIC FIRE SPRINKLERS ARE NOT REQUIRED FOR THIS PROJECT DUE TO BUILDING TYPE, USE, SIZE. VISIBILITY IS PROVIDED THROUGH GLASS ENCLOSED NURSE STATION TO ALL PATIENT EXAM ROOMS. PLANS EXAMINER COMMENT (BILL BURGESS: FIRE ALARM REQUIRES SEPARATE PERMIT. ARCHITECT'S RESPONSE: ACKNOWLEDGED. PLANS EXAMINER COMMENT (BILL BURGESS: ADDITIONAL EXIT SIGNS REQUIRED AT DOOR SEPARATING DOCTOR IS WING.. ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6 AND ENGINEERS DRAWING E3.1 FOR ADDED EXIT SIGNS. PLANS EXAMINER COMMENT (BILL BURGESS: WILL REQUIRE EXIT FROM BREAKROOM REMOVING FIRE SPRINKLERS CREATED DEAD-END CORRIDOR OVER 20'. NOTE DEAD END CORRIDOR ON PLAN REVIEW COMMENT. ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6, A2.0, A2.1, A3.0, A4.0 AND ENGINEERS DRAWINGS FOR RECONFIGURED CORRIDOR ELIMINATING DEAD-END. DRAWING REVISION LIST: ALL CHANGES CLOUDED AND MARKED WITH REVISION 1 A0.0 COVER SHEET - MODIFIED LIFESAFETY INFORMATION A0.6 LIFESAFETY PLAN - MODIFIED ROOMS 101, 102, 128 & 129 AS REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF