August 3, 2023
City of Zephyrhills
5335 &' Street
Zephyrhills, Florida 33542
Re: AdventHealth Well 65+ - Zephyrhills
PEI Job #22121
To Whom it May Concern,
The following letter contains changes made to the above -referenced project:
Mechanical
Sheet Ml.l
Revised diffuser/grille locations per shifts in Architectural Reflected Ceiling Plan. Relocated
ductless split indoor unit per shifts in Architectural Floor Plan.
Sheet E1.1
Revised drawing to add fire alarm specifications.
Sheet E2.1
Revised drawing to reflect actual electrical service layout per updated shell plans.
Sheet E31
Revised location of light fixtures per updated reflected ceiling plan from Architect. Revised
location of receptacles per updated Architectural Plan. Added fire alarm devices throughout
suite.
Sheet E3.2
Revised drawing to show fire alarm devices for HVAC units on roof Revised notes accordingly.
Sheet E4.1
Revised Panel Schedules.
Sheet E5.1
Revised drawing to reflect actual electrical service riser per updated shell plans. Added fire
alarm riser diagram.
Sheet E5.2
Revised Light Fixture Schedule.
EXCELLENCE IN ENGINEERING SINCE 1977
2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 ■ VOICE 407.246.1688 ■ FAX 407.246.1664 ■ www.peifla.com
Ll
2
Plumbing
Sheet P2.1
Revised Sanitary Plan per shift in Architectural Floor Plan.
Sheet P2.2
Revised Domestic Water Plan per shift in Architectural Floor Plan.
Sheet P3.1
Revised sanitary riser per shift in Sanitary Plan.
Sheet P3.2
Revised domestic water riser per shift in Domestic Water Plan.
September 20, 2021
Should you have any questions concerning this matter, please do not hesitate to contact our
office_ `�®®a�+�taa�'g�1
®�®® ��� '''°see•°• SPAV,
��•
Sincerely,
No.64601
«n
Bryan Spangler ;• STATE OF
e
Vice -President ®�,�. °•°F� 0M0P:
FL #64601 coA�® �6' •°ssss esse P� ®6
VON At-
BGS ja:d:ggkl
�� v3
EXCELLENCE IN ENGINEERING SINCE 1977
2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 ■ VOICE 407.246.1688 . FAX 407.246.1664 . www.peifla.com
August 3, 2023
City of Zephyrhills
5335 8"' Street
Zephyrhflls, Florida 33542
Re: AdventHealth Well 65+ - Zephyrhills
PEI Job #22121
To Whom it May Concern,
The following letter contains changes made to the above -referenced project:
Mechanical
74
Sheet M1.1
Revised diffuser/grille locations per shifts in Architectural Reflected Ceiling Plan. Relocated
ductless split indoor unit per shifts in Architectural Floor Plan.
Electrical
Sheet E1.1
Revised drawing to add fire alarm specifications.
Sheet E2.1
Revised drawing to reflect actual electrical service layout per updated shell plans.
Sheet EM
Revised location of light fixtures per updated reflected ceiling plan from Architect. Revised
location of receptacles per updated Architectural Plan. Added fire alarm devices throughout
suite.
Sheet E3.2
Revised drawing to show fire alarm devices for HVAC units on roof. Revised notes accordingly.
Sheet E4.1
Revised Panel Schedules.
Sheet E5.1
Revised drawing to reflect actual electrical service riser per updated shell plans. Added fire
alarm riser diagram.
Sheet E5.2
Revised Light Fixture Schedule.
EXCELLENCE IN ENGINEERING SINCE 1977
2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 ■ VOICE 407.246.1688 ■ FAX 407.246.1664 ■ www.peifla.com
2 September 20, 2021
Plumbing
Sheet P2.1
Revised Sanitary Plan per shift in Architectural Floor Plan.
Sheet P2.2
Revised Domestic Water Plan per shift in Architectural Floor Plan.
Sheet P3.1
Revised sanitary riser per shift in Sanitary Plan.
Sheet P3.2
Revised domestic water riser per shift in Domestic Water Plan.
Should you have any questioiN%WMbHAt@�9this matter, please do not hesitate to contact our
office. G SP`q/!t ®`®
-1 mod.
Sincerely, QQ , �,O E NSF ••
• No.64601
't, STATE OF .
Bryan Spangler 0R% '••;cIOR!®P.••r�tt'
Vice -President �•••..•••••
FL #64601 a It /ONA' �®
BGS.ja:tl:gg:kl It ?i:%
EXCELLENCE IN ENGINEERING SINCE 1977
2016 ALDEN ROAD ■ ORLANDO, FLORIDA 32803 a VOICE 407.246.1688 ■ FAX 407.246.1664 a www.peifla.com
A2.0 CONSTRUCTION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED
TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109,
110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF
DRAIN PIPES.
A2.1 DIMENSION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO
ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110
& 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN
PIPES.
A2.3 DOOR & WINDOW ELEVATIONS & SCHEDULE - CORNER MULLIONS ADDED TO
HUDDLE ROOM STOREFRONT ELEVATIONS. DOOR 123 ADDED TO DOOR SCHEDULE,
CHANGES MADE TO HARDWARE SETS.
A3.0 REFLECTED CEILING PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS
REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107,
108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST
ROOF DRAIN PIPES.
A4.0 FINISH PLAN - FINISH PLAN UPDATED TO REFLECT PLAN CHANGES.
A4.1 FINISH LEGEND & DETAILS- FINISH LEGEND AND DETAILS UPDATED FINISH
SPECIFICATIONS
A5.0 MILLWORK - MODIFIED MILLWORK & SPECIFICATIONS.
SEE SEPARATE ENGINEERING NARRATIVE FOR ENGINEERING DRAWING CHANGES.
Please call or e-mail the contact below at this office for any questions or concerns.
Sincerely,
Frank W. Campbell AIA
Principal
CAMPBELL + VAN DUSEN DESIGN STUDIO
FLORIDA LICENSE: AR 0016053
Frank@CampVanDesignStudio.com
Digitally
E OF F(
signed by
Z'
Frank
�ARNIM
Campbell
Date:
.w aw q:ira mp<aams
re mimwaem.q.a
2023.08.14
09:59:00
-04'00'
2of2
CampVanDesignStudio.com
255 S. Orange Avenue Suite 107, Orlando FL 32801 p. 407-697-9954 f. 407-898-2559
CAMPBELL + VAN DUSEN
DESIGN STUDIO
255 SOUTH ORANGE AVENUE STE 1240
ORLANDO, FLORIDA. 32801
407. 930. 6016
NOTICE OF DRAWING REVISIONS - REVISION 1
04 AUGUST 2023
Project Name: Advent Health Well 65+ Zephyrhills
Project Address: 7866 Gall Boulevard
Zephyrhills, Florida 33541
The following drawings have been revised, clouded, and marked with delta 1, Revision 1,
dated August 04, 2023
PLANS EXAMINER COMMENT (BILL BURGESS:
AUTOMATIC FIRE SPRINKLER INSTALLATION REQUIRES SEPARATE PERMIT.
ARCHITECT'S RESPONSE. PER PRIOR DISCUSSION WITH CITY AUTOMATIC FIRE SPRINKLERS
ARE NOT REQUIRED FOR THIS PROJECT DUE TO BUILDING TYPE, USE, SIZE. VISIBILITY IS
PROVIDED THROUGH GLASS ENCLOSED NURSE STATION TO ALL PATIENT EXAM ROOMS.
PLANS EXAMINER COMMENT (BILL BURGESS:
FIRE ALARM REQUIRES SEPARATE PERMIT.
ARCHITECT'S RESPONSE: ACKNOWLEDGED.
PLANS EXAMINER COMMENT (BILL BURGESS:
ADDITIONAL EXIT SIGNS REQUIRED AT DOOR SEPARATING DOCTOR'S WING..
ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6 AND ENGINEERS DRAWING E3.1 FOR
ADDED EXIT SIGNS.
PLANS EXAMINER COMMENT (BILL BURGESS:
WILL REQUIRE EXIT FROM BREAKROOM REMOVING FIRE SPRINKLERS CREATED DEAD-END
CORRIDOR OVER 20'. NOTE DEAD END CORRIDOR ON PLAN REVIEW COMMENT.
ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6, A2.0, A2.1, A3.0, A4.0 AND
ENGINEERS DRAWINGS FOR RECONFIGURED CORRIDOR ELIMINATING DEAD-END.
DRAWING REVISION LIST: ALL CHANGES CLOUDED AND MARKED WITH REVISION 1
A0.0 COVER SHEET - MODIFIED LIFESAFETY INFORMATION
A0.6 LIFESAFETY PLAN - MODIFIED ROOMS 101, 102, 128 & 129 AS REQUIRED TO
ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110
& 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF
A2.0 CONSTRUCTION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED
TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109,
110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF
DRAIN PIPES.
A2.1 DIMENSION PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS REQUIRED TO
ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110
& 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF DRAIN
PIPES.
A2.3 DOOR & WINDOW ELEVATIONS & SCHEDULE - CORNER MULLIONS ADDED TO
HUDDLE ROOM STOREFRONT ELEVATIONS. DOOR 123 ADDED TO DOOR SCHEDULE,
CHANGES MADE TO HARDWARE SETS.
A3.0 REFLECTED CEILING PLAN - MODIFIED ROOMS 101, 102,128 & 129 AS
REQUIRED TO ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107,
108, 109, 110 & 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST
ROOF DRAIN PIPES.
A4.0 FINISH PLAN - FINISH PLAN UPDATED TO REFLECT PLAN CHANGES.
A4.1 FINISH LEGEND & DETAILS- FINISH LEGEND AND DETAILS UPDATED FINISH
SPECIFICATIONS
A5.0 MILLWORK - MODIFIED MILLWORK & SPECIFICATIONS.
SEE SEPARATE ENGINEERING NARRATIVE FOR ENGINEERING DRAWING CHANGES.
Please call or e-mail the contact below at this office for any questions or concerns.
Sincerely,
Frank W. Campbell AIA
Principal
CAMPBELL + VAN DUSEN DESIGN STUDIO
FLORIDA LICENSE: AR 0016053
Frank@Camr)VanDesianStudio.com
Digitally
�aFF�
signed by
-"`°""::
Frank
�.APMIM3
Campbell
Date:
2023.08.14
09:59:00
-04'00'
2of2
CampVanDesignStudio.com
255 S. Orange Avenue Suite 107, Orlando FL 32801 p. 407-697-9954 f. 407-898-2559
LETTER OF TRANSMITTAL
DATE 8/II/23
JOB No. 22121
ATTENTION
REPROGRAPHICS MANAGER
JOB NAME
WELL 65 ZEPHYRHILLS
JOB ADDRESS
WE ARE SENDING YOU
2016 ALDEN ROAD ® ATTACHED ❑ UNDER SEPARATE COVER VIA THE FOLLOWING ITEMS:
ORLANDO, FLORIDA 32803
VOICE 407.246.1688
FAx 407.246.1664 ❑ SHOP DRAWINGS ❑ PRINTS ® PLANS ® PLOTS ❑ SPECIFICATIONS
EMAIL PEI@PEIFLA.COM
❑ COPY OF LETTER ❑ ELECTRONIC FILES ® REV I- DELTA I
COPIES DATE NO. DESCRIPTION
2 NARRATIVES
2 SETS WETSTAMPED SIGNED AND SEALED DRAWINGS
THESE ARE TRANSMITTED AS CHECKED BELOW:
❑ FOR APPROVAL ❑ APPROVED AS SUBMITTED ❑ RESUBMITTED COPIES FOR APPROVAL
® FOR YOUR USE ❑ APPROVED AS NOTED ❑ SUBMIT COPIES FOR DISTRIBUTION
® AS REQUESTED ❑ RETURNED FOR CORRECTIONS ❑ RETURN CORRECTED PRINTS
❑ FOR REVIEW AND COMMENTS ❑
❑ PRELIMINARY PLANS - NOT FOR BU)M OR CONSTRUCTION ❑ PRINTS RETURNED AFTER LOAN TO US
REMARKS NOTE TO REPROGFIPAHICS MANAGER - PLEASE ATTACH THESE DRAWINGS WITH THE ARCHITECTS PLANS
COPY TO: FILE
THANKS
SIGNED:
PRINT NAME: JAMES ABT
IF ENCLOSURES ARE NOT AS NOTED, KINDLY NOTIFY US AT ONCE.
*Constructors
integrity in construction
August 10, 2023
City of Zephyrhills
Building Department
5335 Eighth Street
Zephyrhills, FL 33
RE: P# B C-006055-2023
We are submitting revisions for Arch, MEP and r r P# BNC-006055-
2023 located at 7866 Gall Blvd, per building official comments. Please see
narrative submitted.
Sincerely,
David T Smith
sq a, sao b
CzYV\-
One Tampa City Center
201 North Franklin Street, Suite 200
Tampa, FL 33602
P: 813.287.9000 1 F: 813.287.9010
iConstructors.com
CAMPBELL + VAN DUSEN
DESIGN STUDIO
255 SOUTH ORANGE AVENUE STE 1240
ORLANDO, FLORIDA. 32801
407. 930. 6016
NOTICE OF DRAWING REVISIONS - REVISION 1
04 AUGUST 2023
Project Name: Advent Health Well 65+ Zephyrhills
Project Address: 7866 Gall Boulevard
Zephyrhills, Florida 33541
The following drawings have been revised, clouded, and marked with delta 1, Revision 1,
dated August 04, 2023
PLANS EXAMINER COMMENT (BILL BURGESS:
AUTOMATIC FIRE SPRINKLER INSTALLATION REQUIRES SEPARATE PERMIT.
ARCHITECT'S RESPONSE: PER PRIOR DISCUSSION WITH CITY AUTOMATIC FIRE SPRINKLERS
ARE NOT REQUIRED FOR THIS PROJECT DUE TO BUILDING TYPE, USE, SIZE. VISIBILITY IS
PROVIDED THROUGH GLASS ENCLOSED NURSE STATION TO ALL PATIENT EXAM ROOMS.
PLANS EXAMINER COMMENT (BILL BURGESS:
FIRE ALARM REQUIRES SEPARATE PERMIT.
ARCHITECT'S RESPONSE: ACKNOWLEDGED.
PLANS EXAMINER COMMENT (BILL BURGESS:
ADDITIONAL EXIT SIGNS REQUIRED AT DOOR SEPARATING DOCTOR IS WING..
ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6 AND ENGINEERS DRAWING E3.1 FOR
ADDED EXIT SIGNS.
PLANS EXAMINER COMMENT (BILL BURGESS:
WILL REQUIRE EXIT FROM BREAKROOM REMOVING FIRE SPRINKLERS CREATED DEAD-END
CORRIDOR OVER 20'. NOTE DEAD END CORRIDOR ON PLAN REVIEW COMMENT.
ARCHITECT'S RESPONSE: SEE REVISED DRAWING A0.6, A2.0, A2.1, A3.0, A4.0 AND
ENGINEERS DRAWINGS FOR RECONFIGURED CORRIDOR ELIMINATING DEAD-END.
DRAWING REVISION LIST: ALL CHANGES CLOUDED AND MARKED WITH REVISION 1
A0.0 COVER SHEET - MODIFIED LIFESAFETY INFORMATION
A0.6 LIFESAFETY PLAN - MODIFIED ROOMS 101, 102, 128 & 129 AS REQUIRED TO
ALLOW CONSTRUCTION OF CORRIDOR. MODIFIED ROOMS 106, 107, 108, 109, 110
& 114 AS REQUIRED TO ALLOW NEW CONSTRUCTION TO CLEAR EXIST ROOF