HomeMy WebLinkAbout5320 1st St (3)Photoelectric,A 0
xis AX Intelligent
The low -profile Intelligent Photoelectric Detector, with built-in
dedicated microprocessor, offers a wide range of capabilities to
suit any commercial, industrial, or institutional application.
Distinguished by it's clear dual -alarm LEDs which illuminate red
during alarm, the detector provides a complete 360 °view of
device status. The detector's dual -alarm LEDs can also be
programmed for flashing during quiescent mode.
The Intelligent Photoelectric Detector incorporates a unique
industry method of addressing the detector. Each detector is
individually addressed through it's associated base by a patented
address ("XPerT") card. The address is quickly and easily set by
removing "pips" on the XPerT card according to a chart supplied
with each base. Once the address is set on the XPerT card, it can
be slid into place and locked into the detector base. By addressing
the detector at the base rather than internally to the detector, the
all -too -common errors associated with detector removal and
maintenance are eliminated.
Designed to adapt to changing environments and protect against
unwanted false alarms, the response characteristics of the
detectors have been carefully set to comply with the stringent
requirements of UL 268 and NFPA 72. Each detector is
continuously monitored and tested for proper sensitivity and
operation. If a problem is detected with either the device's
sensitivity or proper operation, a trouble or maintenance signal is
reported back to the fire alarm control panel. In addition, the
detector will compensate for any sensitivity drift of the initial
programmed response/sensitivity value due to environmental
contamination and/or dust build-up. Each detector will maintain the
initially set sensitivity at a constant level even when the chamber is
severely contaminated. When compensation levels exceed normal
values, a maintenance signal will be generated.
In addition to the detector's superior false alarm reduction
features, each detector is capable of being field programmed for
one of five response/sensitivity modes (see Table 1).
Response modes correspond to unique response behaviors of a
detector and the type of environment it is protecting, which can be
broadly related to the characteristics of a fire. The detector
response modes relate to different combinations of smoke
sensitivity characteristics and transient rejection/stabilization times
(see Table 2). Response mode 1 is more sensitive than response
mode 5. Detectors set to response mode 1 would be for
environments in which sources of unwanted alarms are rare.
Response mode 5 set detectors would be suitable for more dusty
or smoky environments (i.e.: factory, light industry areas).
Response mode 3 (default programmed) would be the
mid -sensitivity level used for most normal ionization detector
applications.
0A A(1vati(,,_-e(J
Patented XPerT Detector Base Addressing
Built-in Dedicated Microprocessor
Five Selectable Response/Sensitivity Modes
Ten 7-Day Response/Sensitivity Mode Timers
Sub -Addressing of Ancillary Functions
Dual -Alarm LEDs with 360 ° View
• 100% Digital Communication Protocol
• Integral XPerT Card Address Labeling Tab
ETL ANSI/UL 864 Listed: 101564744NYM-001
UL file: UOXX.S5022 / ML file: S24459
CSFM Approved: 7271-1713:104
NYC MEA: 294-95-E-4
Response mode setting and hysteresis of the individual detectors are stored within the detector's memory. The advantage of storing this
critical information in the detector rather in the fire alarm control panel software is that the detector will maintain the programmed response
settings and compensated values even when power is removed from the detector. If the detector is powered down or inadvertently
replaced in another location, the detector response mode and clean values are not lost, thereby minimizing the errors associated with
inferior products; false alarms due to a dirty detector and non -calibrated response/sensitivity mode parameters.
Equally beneficial as the response mode settings, the detectors are each capable of being programmed for different response/sensitivity
mode settings based on the time of day and day of week. Detectors can be set to one of ten 7-day response mode/sensitivity timers,
allowing the detector to be more or less sensitive due to installation changing environments based on time of day and day of week. Such
changing environments can be i nd ustrial, restaurant, or factory processes that produce smoke, fumes, or excessive dust during normal
working hours.
Another unique industry feature of the Intelligent Photoelectric Detector, in conjunction with the Axis AX Series Intelligent Fire Alarm
Control Panel, is it's ability to sub -address detector base ancillary functions. Each detector is capable of incorporating, based on optional
intelligent base utilization, a remote LED and/ or relay. When these options are utilized, the user is capable of sub -addressing each of
these options (remote LED and/or relay) to activate independently of the detector. This provides 100% free programmability of the
detector base outputs to meet the demanding requirements of today's installations. (For further explanation, refer to Intelligent Detector
Bases and Intelligent Isolator data sheets).
r-31 r:rr liole Rm office -loose Loadr, y Bay Bul v, Rm
Drr pater ,%-r ' ,,@rtmem �+ospita 'A`are ; Restaurans parking ,sa-agc
t'auul y
i
_ y
_r i
1 i 2 ? 4 51 2
Light rt �s
3 45 12 3''A 5!t= 1 f734� 1�2 3t4 5
i }, t f t ;
1 � a %,,,�nse'�anc�t�rity bdC�.�eS
. ta,t"d1 v., t�b e far :ns;a au�n
T,4b!,c 2
Response
Sensitivity
P,ogramrnable
Mode
CharactensUcs
Assessment Tme
1
1.7 WIft
5 sec
2
1 7 %tft
30 sec
3
2 3 %aft
5 sec
4
2 3 ` !'ft
30 sec
5
29WTI
5sec
Voltage
17-28 VDC
Modulation Voltage
5-9 VDC
Operating Current
Quiescent
0.4 mA
Alarm
0.4 mA
With LED's
5.4 mA
Surge Current
1.0 mA
Air Flow
0-300 ft/min
Sensitivity - Smoke
1.16 - 4 %/ft
Environment
Indoor, Dry
Operating Temperature
32 °-120 ° F (0 ° -48 ° C)
Humidity
10-93% (Non -Condensing)
Dimensions
4" x 1 %"
Weight
3.7 oz
Housing
Polycarbonate, 94 VO
58000-650ADV
Intelligent Photoelectric Detector
" Refer to Intelligent Detector Bases and Intelligent Isolator data sheets for specific information.
Check if this document is up to date Give us feedback
9564 Yellowhead Trail NW, Edmonton AB, T5G OW4, Canada T. 1 (866) 462-7100 E: info@harding-tech.com W: www.harding-tech.com
HARD/NG i�� ;
Axis AX Intelligent Photoelectric Detector
The low -profile Intelligent Photoelectric Detector, with built-in
dedicated microprocessor, offers a wide range of capabilities to
suit any commercial, industrial, or institutional application.
Distinguished by it's clear dual -alarm LEDs which illuminate red
during alarm, the detector provides a complete 360 °view of
device status. The detector's dual -alarm LEDs can also be
programmed for flashing during quiescent mode.
The Intelligent Photoelectric Detector incorporates a unique
industry method of addressing the detector. Each detector is
individually addressed through it's associated base by a patented
address ("XPerT") card. The address is quickly and easily set by
removing "pips" on the XPerT card according to a chart supplied
with each base. Once the address is set on the XPerT card, it can
be slid into place and locked into the detector base. By addressing
the detector at the base rather than internally to the detector, the
all -too -common errors associated with detector removal and
maintenance are eliminated.
Designed to adapt to changing environments and protect against
unwanted false alarms, the response characteristics of the
detectors have been carefully set to comply with the stringent
requirements of UL 268 and NFPA 72. Each detector is
continuously monitored and tested for proper sensitivity and
operation. If a problem is detected with either the device's
sensitivity or proper operation, a trouble or maintenance signal is
reported back to the fire alarm control panel. In addition, the
detector will compensate for any sensitivity drift of the initial
programmed response/sensitivity value due to environmental
contamination and/or dust build-up. Each detector will maintain the
initially set sensitivity at a constant level even when the chamber is
severely contaminated. When compensation levels exceed normal
values, a maintenance signal will be generated.
In addition to the detector's superior false alarm reduction
features, each detector is capable of being field programmed for
one of five response/sensitivity modes (see Table 1).
Response modes correspond to unique response behaviors of a
detector and the type of environment it is protecting, which can be
broadly related to the characteristics of a fire. The detector
response modes relate to different combinations of smoke
sensitivity characteristics and transient rejection/stabilization times
(see Table 2). Response mode 1 is more sensitive than response
mode 5. Detectors set to response mode 1 would be for
environments in which sources of unwanted alarms are rare.
Response mode 5 set detectors would be suitable for more dusty
or smoky environments (i.e.: factory, light industry areas).
Response mode 3 (default programmed) would be the
mid -sensitivity level used for most normal ionization detector
applications.
• Patented XPerT Detector Base Addressing
• Built-in Dedicated Microprocessor
• Five Selectable Response/Sensitivity Modes
• Ten 7-Day Response/Sensitivity Mode Timers
• Sub -Addressing of Ancillary Functions
• Dual -Alarm LEDs with 360 ° View
• 100% Digital Communication Protocol
• Integral XPerT Card Address Labeling Tab
ETL ANSI/UL 864 Listed: 101564744NYM-001
UL file: UOXX.S5022 / ML file: S24459
CSFM Approved: 7271-1713:104
• NYC MEA: 294-95-E-4
Response mode setting and hysteresis of the individual detectors are stored within the detector's memory. The advantage of storing this
critical information in the detector rather in the fire alarm control panel software is that the detector will maintain the programmed response
settings and compensated values even when power is removed from the detector. If the detector is powered down or inadvertently
replaced in another location, the detector response mode and clean values are not lost, thereby minimizing the errors associated with
inferior products; false alarms due to a dirty detector and non -calibrated response/sensitivity mode parameters.
Equally beneficial as the response mode settings, the detectors are each capable of being programmed for different response/sensitivity
mode settings based on the time of day and day of week. Detectors can be set to one of ten 7-day response mode/sensitivity timers,
allowing the detector to be more or less sensitive due to installation changing environments based on time of day and day of week. Such
changing environments can be industrial, restaurant, or factory processes that produce smoke, fumes, or excessive dust during normal
working hours.
Another unique industry feature of the Intelligent Photoelectric Detector, in conjunction with the Axis AX Series Intelligent Fire Alarm
Control Panel, is it's ability to sub -address detector base ancillary functions. Each detector is capable of incorporating, based on optional
intelligent base utilization, a remote LED and/ or relay. When these options are utilized, the user is capable of sub -addressing each of
these options (remote LED and/or relay) to activate independently of the detector. This provides 100% free programmability of the
detector base outputs to meet the demanding requirements of today's installations. (For further explanation, refer to Intelligent Detector
Bases and Intelligent Isolator data sheets).
ea`° Rrr Hote
Off
Nlarehuuse
Loading Bay Rode, Rn,
Corrp,ief Rrr,- 1 A
HospitaWwa
i Restaurant
Plarwip Garage
ractory
-
.L_�..�-a
Light Industry
_
t'E � ��
1'- 2 3 4.4{�12
3ia;5
}
t Tt `�j 23745....
>
1 _4
Moles
tar', C f
- r_'a ation
Response seri`_-11 t`y
P og*ammabte
Mode 0`+aaracaer-vms
Assessment Time
5 Sec
2 ' 7r, ft
30 sec:
3 2 3 Vill.
5 sec
4 2 3 `%41
30 sec
5 29`: At
55ec
Specification
Voltage
17-28 VDC
Modulation Voltage
5-9 VDC
Operating Current
Quiescent
0.4 mA
Alarm
0.4 mA
With LED's
5.4 mA
Surge Current
1.0 mA
Air Flow
0-300 ft/min
Sensitivity - Smoke
1.16 - 4 %/ft
Environment
Indoor, Dry
Operating Temperature
32 ° -120 ° F (0 ° -48 ° C)
Humidity
10-93% (Non -Condensing)
Dimensions
4" x 1 %"
Weight
3.7 oz
Housing
Polycarbonate, 94 VO
58000-650ADV
Intelligent Photoelectric Detector
Refer to Intelligent Detector Bases and Intelligent Isolator data sheets for specific information.
Check if this document is up to date Give us feedback
9564 Yellowhead Trail NW, Edmonton AB, T5G OW4, Canada T. 1 (866) 462-7100 E: info@harding-tech.com W: www.harding-tech.com
HFIRO/NG
y ax
Intelligent Detector Bases
The Intelligent Detector Bases from Advanced offer unique fire
alarm industry features that simplify installations and provide
tremendous flexibility. Incorporating sub -addressable and SLC
loop -powered ancillary outputs, these intelligent bases allow for
cost-effective and trouble -free installations.
By sub -addressing ancillary outputs off of the Intelligent Detector
Bases, remote LEDs and relays are independently controlled by
the Axis AX Series Intelligent Fire Alarm Control Panels. In
addition, the remote LEDs and relays are SLC loop -powered
(powered directly from the Axis AX Series fire alarm control panel's
SLC loop) which reduces the need for additional field wiring and
external power supplies. Sub -addressing and SLC loop powering
of ancillary outputs makes installation, programming, and
commissioning of the most complex projects extremely simplistic.
The Intelligent Detector Bases are available in either standard,
E-Z-Fit, relay, or isolating base configurations. The Advanced
Intelligent Detector Bases mount to a 3" or 4" square or octagonal
electrical box. Based on type of base selected, an optional
Advanced adapter kit may be required for 4" square or octagonal
mounting.
Bases are specifically designed to enable "one -way -only"
intelligent detector insertion without any need for force. Simply
insert the detector and rotate clockwise. Incorporating a high
degree of protection against unauthorized removal of detectors,
each base can be locked to its associated detector by a mini
hexagonal screw.
Utilizing the Advanced unique method of addressing intelligent
detectors, the Intelligent Detector Bases incorporate a patented
address ("XPerT") card. The address is quickly and easily set by
removing "pips" on the XPerT card according to a chart supplied
with each base.
To save time during installation pre -addressed XPerT cards are
available. Once the address is set on the XPerT card, it is then slid
into the base and locked in place. By addressing the detector in
the base rather than in the detector, the all -too -common errors
associated with detector removal and maintenance are eliminated.
All bases have a wide interior diameter for ease of access for
wiring to in -out terminals. Though not required for proper
operation, each base has a dedicated earth connection terminal
for clean, isolated, and continuity maintenance of earth ground
connection of wire shield when shielded cable is utilized.
• Patented XPerT Addressing Card
Sub -Addressable Ancillary Outputs
SLC Loop -Powered Ancillary Outputs
• Integral Remote LED Output
• In -Out Terminals for Ease of Wiring
• Dedicated Terminal for Shielded Cable
• ETL ANSI/UL 864 Listed: 101564744NYM-001
• UL file: UROX.S5022 / ML file: S24459
• CSFM Approved: 7300-1713:103
• NYC MEA: 294-95-E-4
-
+AX Swr
Re• -;A* dl
f+InS1P'i '_
E-Z-Fit Base (45681-250ADS)
Designed for mounting flexibility, the E-Z-Fit base mounts to a 4" square or octagonal electrical box. The E-Z-Fit is easy to install and
allows the screws of a 3" or 4" square or octagonal electrical box to be fitted loosely prior to mounting the base. The base is then placed
over the screws and shifted left to right for optimum positioning. Once positioned, the mounting screws are tightened and unique hinged
covers are closed concealing the screws. The intelligent detector when installed, locks the hinged covers in -place. The E-Z-Fit base offers
a sub -addressable remote LED output.
Standard Base (45681-210ADS)
Designed to mount on a 3" octagonal electrical box, the standard base incorporates a sub -addressable remote LED output. The remote
LED output can be programmed to activate from any cause and effect program of the Axis AX Series Intelligent Fire Alarm Control Panel.
To mount to a 4" square or octagonal box, an Advanced adapter kit is required.
Relay Base (45681-242ADS)
The relay base mounts on a 3" octagonal electrical box and incorporates a sub -addressable remote LED output and Form "C" relay
contact. The Form "C" relay contact has a low current draw and is rated 30 VDC/VAC @ 1 Amp (resistive) and can be utilized to control
various remote ancillary functions. The remote LED output and the Form "C" relay contact are capable of being programmed to activate
from any cause and effect program of the Axis AX Series Intelligent Fire Alarm Control Panels.
Adapter Kit (38531-829ADS, 38531-830ADS)
The adapter kits are utilized in installations requiring standard bases, relay bases, and/or isolating bases to be mounted to 4" square or
octagonal electrical boxes. The adapter kit includes a mounting plate for electrical box mounting and trim ring for the base.
Intelligent Isolating Bases
Refer to Intelligent Isolating Bases data sheet.
Remote LED Output Current
Relay Base Only
Relay Voltage/Current
Activation Surge Current
Energized Current
De -energized Current
Terminals
Environment
Operating Temperature
Humidity
Dimensions (Diameter & Height)
Standard & Relay Base
E-Z-Fit Base
Weight
Housing
5 mA (Maximum)
30 VDC/VAC @ 1 Amp. (Resistive)
5 mA
40 pA
Less than 1 pA
Nickel -Plated Steel
Indoor, Dry
32 ° F-120 ° F (0 ° C-48 ° C)
10-93% (Non -condensing)
4" D x 15/16"H
6 3/8"D x 5/8"H
3.5 oz
Polycarbonate, 94 VO
45681-250ADS
E-Z Fit Low Profile Base (Fits 3" or 4" Square or Octagon Electrical Box)
45681-210ADS
Standard Base (Fits 3" Octagon Electrical Box)
45681-242ADS
Relay Base (Fits 3" Octagon Electrical Box)
Adapter Kit:
38531-830ADS
Mounting Bracket
38531-829ADS
Trim Ring
38531-771
Blank XPerT Card
45682-127
Pre -Addressed XPerT Cards (1-127)
Refer to AX Series Intelligent Isolating Bases data sheet for Information and features pertaining to these products.
Check if this document is up to date Give us feedback
9564 Yellowhead Trail NW, Edmonton AB, T5G OW4, Canada T: 1 (866) 462-7100 E: info@harding-tech.com W: www.harding-tech.com
H/9R0/NG
Axis � AX ) ic,! t f ( Ma t i p. a I P t t I I S tat10 11 `
Advanced Intelligent Manual Pull Stations (AX-APS2) consist of a
family of versatile, low profile, and high quality addressable
manual pull stations. Easily recognizable during a fire situation, the
AX-APS2 stations are constructed of rugged die-cast metal for
long life and reliability, with a high gloss red finish and raised white
"FIRE" lettering. A red LED on the front of the station flashes
during polling and turns on steady in alarm. Integrated into the
station is a Form C relay output that activates when in alarm. All
models are fitted with a common key -lock for resetting (CAT B /
CAT 30) which is common with the panel key.
The AX-APS2 stations are ETL Listed to the ANSI/UL- 38
Standard and have been found to be in compliance with the latest
requirements of the Americans with Disabilities Act (ADA).
Activation of the pull station meets the requirements for five pound
maximum pull force, and the single hand activation.
Available in either single (AX-APS2-F1) or dual (AXAPS2-F2)
action configuration, the AX-APS2 stations are designed to
prevent false alarms when bumped, jarred or shaken. The dual
action AX-APS2-F2 further deters malicious false alarms by
requiring a two process function for activation; first push the
"PUSH" bar inwards which then allows the "PULL" bar to be
grasped and pulled outward.
Optional surface back boxes are available for indoor applications.
The Intelligent Manual Pull Stations are available in a variety of
colors to meet various special application requirements. Colored
stations do not include the raised white "FIRE" labeling, but are
capable of accommodating labels for Alert, Alarm, Exit, Evac, etc.
identification. Special applications can include; weather alert, door
release, medical emergency, fire suppression activation and
others.
Operation: The AX-APS2 stations are operated by pulling the
handle marked "PULL" on the front of the station as far down as it
will go. At this point, the station will lock in place and is easily
visible from up to 50 feet away. The activation handle is reset by
opening the station with the reset key (keyed to match Axis AX
Series Intelligent Fire Alarm Control Panels), returning the toggle
switch to its "Normal' position, moving the handle to its upright
position and relocking the station. On the AXAPS2-F2 dual station
model, the 'PUSH" bar must be pushed inward prior to pulling the
handle marked `PULL".
• ADA Compliant
• Single or Dual Action
• Rugged Die -Cast Metal Construction
• Red Status LED
• Integrated Form C Relay Contact
• Low Profile, High Visibility Design
• Visual Indication of Activation including Red Status LED
• Surface or Semi -Flush Mount
• Available in Special Application Colors
• Key -Lock Reset
• ETL ANSI/UL 38 Listed: 3186781NYM-001
• ETL ANSI/UL 864 Listed: 101564744NYM-001
• CSFM Approved: 7165-1713:0101
• NYCFD COA #6105A2
Operating Voltage
Operating Current
Quiescent
Alarm
Operating Temperature
Dimensions
With Surface Mount Backbox
Weight
Analog Value
Address Range
Color
AX-APS2-F 1
AX-APS2-F2
Options:
AX-APS-BB 1
AX-APS-BB 1-D
AX-APS-GLS
? F.^•1- M,Roi. R4141 oR
GRP'"IMS L VJI P
Install the AX-APS2 pull stations
in accordance with local, codes
and regulations. To cornply with
the ADA requirements. locate the
pull station on the wail as fo':c4vs.
Front wheelchair access: < 48"
Side wheelchair access: < 54
17-28 VDC, with Communication Pulses 5-9 VDC
lh °W,
.}: 2
1.7 mA
2.7 mA
32 ° F (0 ° C) to 120 ° F (49 ° C), for Indoor Use Only
43/4"Hx31/4"Wx1.1"D
4 3/4 " H x 3 1/4 " W x 2 1/4 " D (Cast or Sheet Metal)
1.1 lb
16 = Normal, 64 = Alarm, 4 = Trouble
1 - 126 (DIP Switch Programmable)
Red with Raised White Letters, White "PULL" Bar with Raised Red Letters
Intelligent Manual Pull Station, Single Action
Intelligent Manual Pull Station, Dual Action
Interior Surface Mount Backbox - Red (Sheet Metal)
Deep Interior Surface Backbox, Red
Package of Scored Plastic (Acrylic) Break rods (1 Dozen to a Packet)
Check if this document is up to date Give us feedback