Envelope Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Vertical Glazing / Wall Area:
Skylight / Roof Area
Construction Site:
2017 Florida Building Code, Energy Conservation
BLOX - Zephyrhills
Zephyrhills, Florida
2a
Addition
12%
0%
Owner/Agent:
Building Area Floor Area
1-Health Care -Clinic : Nonresidential 6495
Envelope Assemblies
Designer/Contractor:
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factor(a)
Perimeter
BLOX ROOF: Insulation Entirely Above Deck, High Albedo Roof
Exemption = Performance data not applicable or available, [Bldg. Use 1
- Health Care -Clinic]
DENTAL CORRIDOR/MED BAY SKYLIGHTS: Metal Frame:Glass,
With Curb, Perf. Specs.: Product ID NA, SHGC 0.31, VT 0.63, [Bldg.
Use 1 - Health Care -Clinic] (b)
BLOX FLOOR: Steel Joist, [Bldg. Use 1 - Health Care -Clinic]
NORTH
DENTAL / LAB: Steel -Framed, 16" o.c., [Bldg. Use 1 - Health Care -
Clinic]
EAST
ENTRY WALL: Steel -Framed, 16" o.c., [Bldg. Use 1 - Health Care -
Clinic]
CLASSROOM WINDOWS: Metal Frame with Thermal Break:Fixed,
Perf. Specs.: Product ID SF1, SHGC 0.23, VT 0.43, [Bldg. Use 1 -
Health Care -Clinic] (b)
VEST ENTRANCE DOORS: Glass (> 50% glazing):Metal Frame,
Entrance Door, Perf. Specs.: Product ID Assa Abloy, SHGC 0.31, PF
0.50, VT 0.44, [Bldg. Use 1 - Health Care -Clinic] (b)
MED / DENTAL: Steel -Framed, 16" o.c., [Bldg. Use 1 - Health Care -
Clinic]
MED BAY WINDOWS (SF2): Metal Frame with Thermal Break:Fixed,
Perf. Specs.: Product ID SF2, SHGC 0.21, VT 0.44, [Bldg. Use 1 -
Health Care -Clinic] (b)
DENTAL BAY WINDOWS: Metal Frame with Thermal Break:Fixed,
Perf. Specs.: Product ID SF3, SHGC 0.23, VT 0.44, [Bldg. Use 1 -
Health Care -Clinic] (b)
SOUTH
CLASSROOM / AUDIOLOGY: Steel -Framed, 16" o.c., [Bldg. Use 1 -
6500
--- 30.0
0.032
0.039
32
--- ---
0.700
0.650
6500
24.6 0.0
0.044
0.033
798
24.6 10.0
0.048
0.077
383
24.6 10.0
0.048
0.077
87
--- ---
0.440
0.500
143 --- ---
0.930
0.830
1026 24.6 10.0
0.048
0.077
111 --- ---
0.440
0.500
73 --- ---
0.440
0.500
653 24.6 10.0
0.048
0.077
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 1 of 37
Assembly
Gross Area
Cavity
Cont.
Proposed
Budget U-
or
R-Value
R-Value
U-Factor
Factor(a)
Perimeter
Health Care -Clinic]
ADJACENT TO ENTRY: Steel -Framed, 16" o.c., [Bldg. Use 1 - Health
135
24.6
10.0
0.048
0.077
Care -Clinic]
WEST
Lab (Rear): Steel -Framed, 16" o.c., [Bldg. Use 1 - Health Care -Clinic]
475
24.6
10.0
0.048
0.077
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
Envelope Compliance Statement
Compliance Statement. The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.3.0 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
IAWWXi.,, V'
a — A 'a. n L* Az
Na - Title Sign D e
C/) .`"�y 0 Y
c
R95 isk4%f ow
Project Title: BLOX - Zephyrhills
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Report date: 11/23/20
Page 2 of 37
�; , « � Y
8
,.
.. �
�;
' y 1 �
COMcheck Software Version 4.1.3.0
Interior Lighting Compliance Certificate
Project Information
Energy Code: 2017 Florida Building Code, Energy Conservation
Project Title: BLOX - Zephyrhills
Project Type: Addition
Construction Site: Owner/Agent: Designer/Contractor:
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Wattg / ft2
D
Allowed Watts
(B X C)
Activity type invalid
0
0.00
0
1-102-Lobby (Common Space Types:Lobby - General)
659
0.90
593
2-101-Vestibule (Common Space Types:Lobby - General)
69
0.90
62
3-104-Exam Work (Healthcare Facility:Exam/Treatment)
619
1.66
1028
4-111-Checkout (Healthcare Facility:Nurses Station)
92
0.71
65
5-112-Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
6-113-Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
7-114-Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
8-126-Exam (Healthcare Facility: Exam/Treatment)
132
1.66
219
9-125-Exam (Healthcare Facility: Exam/Treatment)
132
1.66
219
10-124-Xray/FLex (Healthcare Facility: Exam/Treatment)
133
1.66
221
11-122-Xray/Alcove (Healthcare Facility:Exam/Treatment)
38
1.66
63
12-123-Dictation (Healthcare Facility: Exam/Treatment)
28
1.66
46
13-176-Classroom (Common Space Types:C lass roo m/Lectu re/Trai n i ng)
300
1.24
372
14-174-Toilet (Common Space Types:Restrooms)
53
0.98
52
15-175-Mothers (Common Space Types:Office - Enclosed)
50
1.11
56
16-173-Corridor (Common Space Types: Corridor/Transition <8 ft wide)
77
0.66
51
17-172-Comm/Electric (Common Space Types: Electrical/Mechanical)
106
0.95
101
18-171-Audiology (Healthcare Facility: Exam/Treatment)
106
1.66
176
19-105-Dental Corridor (Common Space Types:Corridor/Transition >=8 ft wide)
313
0.66
207
20-105-Main Corridor (Common Space Types:Corridor/Transition >=8 ft wide)
640
0.66
422
21-151-Breakroom (Common Space Types: Lou nge/Breakroom)
215
0.73
157
22-152-Toilet (Common Space Types:Restrooms)
53
0.98
52
23-153-Lab (Common Space Types: Laboratory For Medical/Industrial/Research)
176
1.81
319
24-161-Clinical Work (Common Space Types:Office - Enclosed)
102
1.11
113
25-162-Exam (Healthcare Facility: Exam/Treatment)
98
1.66
163
26-163-Pretest (Healthcare Facility: Exam/Treatment)
59
1.66
98
27-164-Contacts (Healthcare Facility:Exam/Treatment)
59
1.66
98
28-165-Exam (Healthcare Facility: Exam/Treatment)
98
1.66
163
29-166-OD Wait (Common Space Types:Lobby - General)
66
0.90
59
30-132-Treatment Planning (Healthcare Facility:Exam/Treatment)
46
1.66
76
31-131-Imaging (Healthcare Facility:Exam/Treatment)
39
1.66
65
32-133-Dental Exam (Healthcare Facility: Exam/Treatment)
132
1.66
219
33-134-Dental Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
34-135-Dental Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
35-145-Sterile (Healthcare Facility: Exam/Treatment)
112
1.66
186
36-145A-Mech (Common Space Types: Electrical/Mechanical)
17
0.95
16
Project Title: BLOX - Zephyrhills
Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Page 3 of 37
A
B
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts / ft2
(B X C)
37-144-Dental Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
38-143-Dental Exam (Healthcare Facility:Exam/Treatment)
132
1.66
219
39-142-Toilet (Common Space Types:Restrooms)
47
0.98
46
40-141-EVS (Common Space Types: Electrical/Mechanical)
37
0.95
35
41-151 B-Storage (Common Space Types:Storage <50 sq.ft.)
38
1.24
47
Proposed Interior Lighting Power
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
Total Allowed Watts = 7398
B C D E
Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
Activity type invalid (wattage exempt
for this area)
1-102-Lobby (Common Space Types:Lobby
- General)
LD6:Other:
1
14
21
294
2-101-Vestibule (Common Space Types:Lobby
- General)
LD6:Other:
1
2
21
42
3-104-Exam Work (Healthcare Facility:
Exam/Treatment)
LD6:Other:
1
12
21
252
4-111-Checkout (Healthcare Facility:Nurses
Station)
LD6:Other:
1
2
21
42
LF2:Other:
2
2
20
41
5-112-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
6-113-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
7-114-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
8-126-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
9-125-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
10-124-Xray/FLex (Healthcare Facility:Exam/Treatment)
LT4:Other:
2
2
38
76
11-122-Xray/Alcove (Healthcare Facility:Exam/Treatmeou
LT2:Other:
2
1
28
28
12-123-Dictation (Healthcare Facility:
Exam/Treatment)
LT2:Other:
2
1
28
28
13-176-Classroom (Common Space
Types:Classroom/Lecture/Training)
LT2:Other:
2
6
28
171
14-174-Toilet (Common Space Types:Restrooms)
LF2:Other:
2
1
20
20
15-175-Mothers (Common Space Types:Office
- Enclosed)
LF2:Other:
2
1
20
20
16-173-Corridor (Common Space Types:Corridor/Transition
<8 ft wide)
LD6:Other:
1
2
21
42
17-172-Comm/Electric (Common Space
Types: Electrical/Mechanical)
LS4:Other:
1
2
23
46
18-171-Audiology (Healthcare Facility:
Exam/Treatment)
Project Title: BLOX - Zephyrhills
Report date:
11/23/20
Data filename: P:\CLNT\Retail G\07
Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Page
4 of 37
A
B
C
D
E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
Lamps/
# of
Fixture
(C X D)
Fixture
Fixtures
Watt.
LD6:Other:
1
2
21
42
19-105-Dental Corridor (Common Space Types: Corridor/Transition >=8 ft wide)
LD6:Other:
1
5
21
105
20-105-Main Corridor (Common Space Types: Corridor/Transition >=8 ft wide)
LD6:Other:
1
12
21
252
21-151-Breakroom (Common Space Types: Lou nge/Breakroom)
LT2:Other:
2
4
28
114
22-152-Toilet (Common Space Types:Restrooms)
LT2:Other:
2
1
28
28
23-153-Lab (Common Space Types: Laboratory For Medical/Industrial/Research)
LT4:Other:
2
2
38
76
LT2:Other:
2
2
28
57
24-161-Clinical Work (Common Space Types:Office - Enclosed)
LT4:Other:
2
2
38
76
25-162-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
26-163-Pretest (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
1
38
38
27-164-Contacts (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
1
38
38
28-165-Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
29-166-OD Wait (Common Space Typeslobby - General)
LD4:Other:
1
2
16
31
30-132-Treatment Planning (Healthcare Facility:Exam/Treatment)
LT2:Other:
2
1
28
28
31-131-Imaging (Healthcare Facility:Exam/Treatment)
LT2:Other:
2
1
28
28
32-133-Dental Exam (Healthcare Facility:Exam/Treatment)
LT4:Other:
2
2
38
76
33-134-Dental Exam (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
2
38
76
34-135-Dental Exam (Healthcare Facility:Exam/Treatment)
LT4:Other:
2
2
38
76
35-145-Sterile (Healthcare Facility: Exam/Treatment)
LT4:Other:
2
1
38
38
LT2:Other:
2
1
28
28
36-145A-Mech (Common Space Types: Electrical/Mechanical)
LS2: Other:
1
1
11
11
37-144-Dental Exam (Healthcare Facility:Exam/Treatment)
LT4:Other:
2
2
38
76
38-143-Dental Exam (Healthcare Facility:Exam/Treatment)
LT4:Other:
2
2
38
76
39-142-Toilet (Common Space Types:Restrooms)
LF2:Other:
2
1
20
20
40-141-EVS (Common Space Types: Electrical/Mechanical)
LS4:Other:
1
1
23
23
41-151 B-Storage (Common Space Types:Storage <50 sq.ft.)
LT2:Other:
2
1
28
28
Total Proposed Watts =
3080
Project Title: BLOX - Zephyrhills
Report date:
11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Page
5 of 37
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.3.0 and to comply
with any applicable mandatory requirements listed in the Inspecton Checklist,
Name - Title Si
Project Title: BLOX - Zephyrhills
u
,, m ` '`"'��
E
Nri. 686 1 •
�-O STATE OF
Data filename: P:\CLNT\Retail G\07 Project Manua l\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Date
Report date: 11/23/20
Page 6 of 37
6 COMcheck Software Version 4.1.3.0
�( Exterior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Project Type:
Exterior Lighting Zone
2017 Florida Building Code, Energy Conservation
BLOX - Zephyrhills
Addition
2 (Residentially zoned area)
Construction Site: Owner/Agent: Designer/Contractor:
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts / Unit Wattage (B X C)
Illuminated area of facade wall or surface 470 ft2 0.1 No 47
Total Tradable Watts (a) = 0
Total Allowed Watts = 47
Total Allowed Supplemental Watts (b) = 600
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non -tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
Illuminated area of facade wall or surface (470 ft2): Non -tradable Wattage
EW1:Other: 1 2 59 118
Total Tradable Proposed Watts = 0
Exterior Lighting Compliance Statement
Compliance Statement. The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.3.0 and to comply
with any applicable mandatory requirements listed in the Inspecti n CheMlit
� l �Z`�l /Za
Name - Title Signatur Date
�\C NSF
s
ski No. 686 `� •
-o STATE OF
pY
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Man ual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 7 of 37
COMcheck Software Version 4.1.3.0
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
Mechanical Systems List
Quantity System Type & Description
2017 Florida Building Code, Energy Conservation
BLOX - Zephyrhills
Zephyrhills, Florida
2a
Addition
Owner/Agent:
1 HRU-1 (Single Zone):
VRF Condensing Unit, Air Cooled w/ Heat Recovery Heat Pump
Heating Mode: Capacity = 148 kBtu/h,
Proposed Efficiency = 3.82 COP, Required Efficiency = 3.20 COP
Cooling Mode: Capacity = 183 kBtu/h,
Proposed Efficiency = 13.40 EER, Required Efficiency: 10.60 EER
Fan System: None
Designer/Contractor:
1 AC-1 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-1 Fan I COMM/ELECTRIC -- Compliance (Motor nameplate HP method) : Passes
Fans:
AC-1 Fan Supply, Constant Volume, 918 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 AC-2 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-2 FAN I WAITING/LOBBY -- Compliance (Motor nameplate HP method) : Passes
Fans:
ACU2 FAN Supply, Constant Volume, 883 CFM, 0.2 motor nameplate hp, 0.0 fan efficiency grade
AC-3 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 30 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-3 Fan I CLASSROOM -- Compliance (Motor nameplate HP method) : Passes
Fans:
AC-3 Supply, Constant Volume, 812 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 AC-4 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 18 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-4 FAN I CONTACTS/OD EXAM -- Compliance (Motor nameplate HP method) : Passes
Fans:
ACU4 FAN Supply, Constant Volume, 494 CFM, 0.3 motor nameplate hp, 0.0 fan efficiency grade
AC-5 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 12 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-5 Fan I LAB -- Compliance (Motor nameplate HP method) : Passes
Project Title: BLOX - Zephyrhills
Data filename: P:\CLNT\Retail G\07 Project Manua l\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Report date: 11/23/20
Page 8 of 37
Quantity System Type & Description
Fans:
AC-5 Fan Supply, Constant Volume, 335 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
AC-6 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 18 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: AC-6 Fan I BREAKROOM -- Compliance (Motor nameplate HP method) : Passes
Fans:
AC-6 Fan Supply, Constant Volume, 812 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
AC-7 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-7 FAN I DENTAL EXAM UBER 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
ACU7 FAN Supply, Constant Volume, 883 CFM, 0.2 motor nameplate hp, 0.0 fan efficiency grade
AC-8 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-8 FAN I DENTAL EXAM UBER 2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
ACU8 FAN Supply, Constant Volume, 883 CFM, 0.2 motor nameplate hp, 0.0 fan efficiency grade
AC-9 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 12 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: AC-9 Fan I MED EXAM UBER 2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
AC-9 Fan Supply, Constant Volume, 371 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
AC-10 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity =
No minimum efficiency requirement applies
Fan System: ACU-10 FAN I MED EXAM UBER 1
15 kBtu/h, No Economizer, Economizer exception: None
-- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN ACU10 Supply, Constant Volume, 494 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
AC-11 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 18 kBtu/h, No Economizer, Economizer exception: None
No minimum efficiency requirement applies
Fan System: ACU-11 FAN I EXAM WORK AREA -- Compliance (Motor nameplate HP method) : Passes
Fans:
ACU11 FAN Supply, Constant Volume, 600 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
DOAS-1 (Multiple -Zone):
Heating: 1 each - Central Furnace, Electric, Capacity = 68 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Single Package DX Unit, Capacity = 66 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency = 14.90 EER, Required Efficiency: 11.20 EER + 12.8 IEER
Fan System: DOAS-1 Building Outside Air -- Compliance (Motor nameplate HP method) : Passes
Fans:
DOAS-1 Supply, Constant Volume, 1260 CFM, 1.0 motor nameplate hp, 0.0 fan efficiency grade
DOAS1 EXH Exhaust, Constant Volume, 1050 CFM, 1.0 motor nameplate hp, 0.0 fan efficiency grade
Project Title: BLOX - Zephyrhills
Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 9 of 37
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.3.0 and to comply
with any applicable mandatory requirements listed in the Inspee ioln Checklist.
Name - Title Sign
• EN& •.
• e
*; No. 68h `� •*
►"o, ��• STATE of ; 4
•�'•=�` 0 R 1�A-
Project Title: BLOX - Zephyrhills
Data filename: PACLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck
Date 1( ' h'7 Y/-V
Report date: 11/23/20
Page 10 of 37
COMcheck Software Version 4.1.3.0
Inspection Checklist
Energy Code: 2017 Florida Building Code, Energy Conservation
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
Complies?
Comments/Assumptions
& Req.ID
C103.2
Plans and/or specifications provide all
❑Complies
Requirement will be met.
[PR1]1
Jnformation with which compliance
❑Does Not
,:can be determined for the building
❑Not Observable
envelope and document where
I❑Not Applicable
exceptions to the standard are
claimed.
C103.2
Plans, specifications, and/or
❑Complies
Requirement will be met.
[PR2]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the mechanical
:❑Not
Applicable
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
,handbooks.
C405.6 !Plans,
specifications, and/or❑Complies
Requirement will be met.
[PR17]1
calculations provide all information '❑Does
Not
with which compliance can be
❑Not Observable
determined for the electrical systems
'❑Not
Applicable
.and
equipment and document where
exceptions are claimed. Provisions are
'made
for metering individual tenant
units. Feeder connectors (for feeder
and branch circuits) sized in
accordance with approved plans with
maximum drop of 5% voltage drop
total.
C103.2
Plans, specifications, and/or
❑Complies
Requirement will be met.
[PR4]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the interior lighting
'❑Not
Applicable
and electrical systems and equipment
and document where exceptions to
,the
standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
C103.2 Plans, specifications, and/or
❑Complies
Requirement will be met.
[PR8]1
calculations provide all information
❑Does Not
,with
which compliance can be
❑Not Observable
determined for the exterior lighting
and electrical systems and equipment❑Not
Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 11 of 37
Section
#
Plan Review
Complies?
Comments/Assumptions
& Req.ID
C402.4.1
;The vertical fenestration area <= 30
❑Complies
Requirement will be met.
[PR10]1
percent of the gross above -grade wall❑Does
Not
area.
❑Not Observable
❑Not Applicable
C402.4.1 ;The
skylight area <= 3 percent of the '❑Complies
Requirement will be met.
[PR11]1
gross roof area.
❑Does Not
❑Not Observable
❑Not Applicable
C402.4.2
In enclosed spaces > 2,500 ft2
❑Complies
Requirement will be met.
[PR14]1
directly under a roof with ceiling
❑Does Not
heights >15 ft. and used as an office,
❑Not Observable
lobby, atrium, concourse, corridor,
❑Not Applicable
storage, gymnasium/exercise center,
convention center, automotive
'service,
manufacturing, non -
refrigerated warehouse, retail store,
distribution/sorting area,
;transportation,
or workshop, the
following requirements apply: (a) the
daylight zone under skylights is >_
half the floor area; (b) the skylight
area to daylight zone is >= 3 percent
with a skylight VT >= 0.40; or a
minimum skylight effective aperture
>= 1 percent.
C402.4.2. ',Skylights
in office, storage,
❑Complies
Requirement will be met.
2
automotive service, manufacturing,
❑Does Not
[PR15]1 'non
-refrigerated warehouse, retail
❑Not Observable
store, and distribution/sorting area
Applicable
have a measured haze value > 90 ;❑Not
percent unless designed to exclude
direct sunlight.
C406 Plans, specifications, and/or ❑Complies
Requirement will be met.
[PR9]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the additional energy
�❑Not
Applicable
efficiency package options.
C402.5.9.(',Ceilings with vented dropped ceiling ❑Complies
Requirement will be met.
1-4)
cavities over conditioned spaces have
❑Does Not
[PR16]1
a continuous air barrier between the
❑Not Observable
conditioned space and the vented
unconditioned space and are sealed to'❑Not
Applicable
j
the air barrier of the walls. Unvented
dropped ceiling cavities over
conditioned spaces without air barrier
between the conditioned and
unconditioned space are sealed from
the exterior environment and adjacent
spaces by a continuous air barrier and
is sealed to the air barrier of the walls.
Unconditioned spaces above separate
tenancies contain dividing partitions
between the tenancies to form a
continuous air barrier that is sealed at
the ceiling and roof. Building cavities
designed to be air distribution system
components are sealed according to
the criteria for air ducts, plenums, etc.
in Section C403.2.7.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 12 of 37
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 13 of 37
Section
#
Footing / Foundation Inspection
Complies?
Comments/Assumptions
& Req.ID
C303.2.1
Exterior insulation protected against
❑Complies
Requirement will be met.
[FO6]1
damage, sunlight, moisture, wind,
❑Does Not
landscaping and equipment
❑Not Observable
maintenance activities.
❑Not Applicable
C402.2.6
Radiant heating systems panels
;❑Complies
Exception: Requirement does not apply.
[FO12]3 'insulated
to >=R-3.5 on face opposite "❑Does
Not
space being heated.
❑Not Observable
See the Envelope Assemblies table for values.
❑Not Applicable
C403.2.4. Snow/ice melting system sensors for
❑Complies
Exception: Requirement does not apply.
5, ifuture
connection to controls. Freeze
❑Does Not
C403.2.4.
protection systems have automatic
❑Not Observable
6
[FO9]3
controls installed.
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 14 of 37
Section
#
Framing / Rough -In Inspection
Complies?
Comments/Assumptions
& Re .113
C303.1.3
Fenestration products rated in
❑Complies
Requirement will be met.
[FR12]2
'.accordance with NFRC.
❑Does Not
❑Not Observable
❑Not Applicable
C303.1.3
Fenestration products are certified as
❑Complies
Requirement will be met.
[FR13]1,to
performance labels or certificates
❑Does Not
provided.
❑Not Observable
❑Not Applicable
C402.4.3
Vertical fenestration SHGC value.
❑Complies
See the Envelope Assemblies table for values.
[FR10]1
❑Does Not
❑Not Observable
❑Not Applicable
C402.4.3
Skylight SHGC value.
❑Complies
See the Envelope Assemblies table for values.
[FR11]1
'❑Does
Not
❑Not Observable
❑Not Applicable
C402.4.3, , Vertical fenestration U-Factor. ❑Complies
See the Envelope Assemblies table for values.
C402.4.3.
❑Does Not
4 1
[FR8]
;❑Not
Observable
❑Not Applicable
C402.4.3.
Skylight fenestration U-Factor. ,❑Complies
See the Envelope Assemblies table for values.
4
❑Does Not
[FR9]1
'❑Not
Observable
❑Not Applicable
C402.4.4
U-factor of opaque doors associated
❑Complies
See the Envelope Assemblies table for values.
[FR14]2 !with
the building thermal envelope
❑Does Not
meets requirements.
❑Not Observable
❑Not Applicable
C402.5.1 !The
building envelope contains a❑Complies
Requirement will be met.
[FR16]1
continuous air barrier that is sealed in
❑Does Not
an approved manner and either
Observable
constructed or tested in an approved !MNot
❑Not Applicable
manner. Air barrier penetrations are
sealed in an approved manner.
C402.5.2,
Factory -built fenestration and doors
❑Complies
Exception: Field fabricated fenestration assemblies.
C402.5.4 "are
labeled as meeting air leakage
❑Does Not
[FR18]3
requirements.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 77T 3 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 15 of 37
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.1D
C404.5,
Heated water supply piping conforms
❑Complies
Requirement will be met.
C404.5.1,
'Ao pipe length and volume
❑Does Not
C404.5.2
1 requirements. Refer to section details.
Observable
[PL6]3❑Not
:]Not Applicable
C404.5,
Heated water supply piping conforms
❑Complies
Requirement will be met.
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
'❑Not
Observable
[PL6]3
❑Not Applicable
C404.5, :Heated
water supply piping conforms
❑Complies
Exception: Requirement does not apply.
C404.5.1, 'ito
pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5, Heated water supply piping conforms
❑Complies
Exception: Requirement does not apply.
C404.5.1, Ito
pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑ Not Observable
[PL6]3
❑Not Applicable
C404.5, ! Heated water supply piping conforms
❑Complies
Exception: Requirement does not apply.
C404.5.1, Ito
pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5, I Heated water supply piping conforms "❑Complies
Exception: Requirement does not apply.
C404.5.1, Ito
pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5, Heated water supply piping conforms ❑Complies
Exception: Requirement does not apply.
C404.5.1, 'to
pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5,
Heated water supply piping conforms
❑Complies
Exception: Requirement does not apply.
C404.5.1, 'to
pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
Observable
[PL6]3❑Not
❑Not Applicable
C404.5, Heated water supply piping conforms❑Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2 j
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5, Heated water supply piping conforms ❑Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5, T Heated water supply piping conforms !❑Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details. ,
❑Not Observable
[PL6]3
❑Not Applicable
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 16 of 37
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C404.5,
Heated water supply piping conforms
❑Complies
Exception: Requirement does not apply.
C404.5.1,
'to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
,nNot Observable
[PL6]3
❑Not Applicable
C404.5, 'Heated
water supply piping conforms
❑Complies
Exception: Requirement does not apply.
C404.5.1, 'to
pipe length and volume
'❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.6.3 Pumps that circulate water between a ;❑Complies
Requirement will be met.
[PL7]3
heater and storage tank have controls 11❑Does
Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3 Pumps that circulate water between a '❑Complies
Requirement will be met.
[PL7]3
heater and storage tank have controls
❑Does Not
,that
limit operation from startup to
Observable
<= 5 minutes after end of heating �nNot
❑Not Applicable
cycle.
C404.6.3 Pumps that circulate water between a❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
❑Does Not
,that
limit operation from startup to
Observable
<= 5 minutes after end of heating �nNot
�ENot
Applicable
cycle.
C404.6.3 1, Pumps that circulate water between a IOComplies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3 Pumps that circulate water between a IOComplies
Requirement will be met.
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3 Pumps that circulate water between a❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3 Pumps that circulate water between a
❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
cycle.
❑Not Applicable
C404.6.3 Pumps that circulate water between a '❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3 Pumps that circulate water between a❑Complies
Exception: Requirement does not apply.
[PL7]3 !heater
and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
;❑Not
Applicable
cycle.
C404.6.3 Pumps that circulate water between a
❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
'❑Not
Applicable
cycle.
1 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 17 of 37
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C404.6.3
Pumps that circulate water between a
iOComplies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
<= 5 minutes after end of heating
❑Not Observable
cycle.
,❑ Not Applicable
C404.6.3
Pumps that circulate water between a
❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls❑Does
Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
cycle.
❑Not Applicable
C404.6.3
Pumps that circulate water between a❑Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
'❑Not
Applicable
cycle.
C404.7 'Water
distribution system that pumps❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply !❑Does
Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
;❑Not
Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps IOComplies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
!through
a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps i❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
;through
a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7 !Water
distribution system that pumps ;❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply I❑Does Not
pipe back to the heated -water source
❑Not Observable
;through
a cold -water supply pipe is a i
Applicable
demand recirculation water system. '❑Not
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills
Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 18 of 37
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C404.7
Water distribution system that pumps
❑Complies
Requirement will be met.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
�❑Not Observable
;through scold -water supply pipe is a
'
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7 !Water distribution system that pumps
❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
j
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
,104°F.
C404.7 ;
Water distribution system that pumps
❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
,through
a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
,receiving
a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7 Water distribution system that pumps
❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
;through
a cold -water supply pipe is a
I❑Not
Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 19 of 37
Section
# .
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C404.7
Water distribution system that pumps❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
Not Observable
'through a cold -water supply pipe is a
'demand
❑Not Applicable
recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7 !Water
distribution system that pumps :❑Complies
Exception: Requirement does not apply.
[PL8]3 ,
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
;through
a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps❑Complies
Exception: Requirement does not apply.
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
'❑Not
Observable
,through
a cold -water supply pipe is a
demand recirculation water system. ;❑Not
Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 20 of 37
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C402.2.6
;Thermally ineffective panel surfaces of❑Complies
Exception: Requirement does not apply.
[ME41]3 =sensible
heating panels have
❑Does Not
i
insulation >= R-3.5.
❑Not Observable
❑Not Applicable
C402.5.5,
Stair and elevator shaft vents have
❑Complies
Exception: Requirement does not apply.
C403.2.4.
motorized dampers that automatically
❑Does Not
3
[ME3]3❑Not
close.
Observable
❑Not Applicable
C403.2.12
HVAC fan systems at design
❑Complies
Exception: Requirement does not apply.
.1
conditions do not exceed allowable
❑Does Not
[ME65]3
fan system motor nameplate hp or fan
❑Not Observable
See the Mechanical Systems list for values.
system bhp.
❑Not Applicable
C403.2.12
Fans have efficiency grade (FEG) >= ;❑Complies
Exception: Fans integral to equipment listed under Section
.3
67. The total efficiency of the fan at
❑Does Not
C403.2.3.
[ME117]2
the design point of operation <= 15%
;RNot
Observable
of maximum total efficiency of the
'❑Not
Applicable
fan.
C403.2.9.
HVAC ducts and plenums insulated
❑Complies
Requirement will be met.
1.1
and sealed according to Florida '!❑Does
Not
[ME60]2
Section C403.2.9, Table C403.2.9. 1.
i❑Not
Observable
❑Not Applicable
C403.2.9. ;AII
ducts, air handlers, filter boxes,
❑Complies
Requirement will be met.
2
building cavities, mechanical closets ;F
JDoes Not
[ME79]2 I
and enclosed support platforms that
❑Not Observable
form the primary air containment
❑Not Applicable
passageways for air distribution
systems are constructed and erected
in accordance with Table C403.2.9.2
and with Chapter 6 of the Florida
Building Code, Mechanical. Ducts are
be constructed, braced, reinforced
and installed to provide structural
strength and durability. All transverse
,joints,
longitudinal seams and fitting
connections are securely fastened in
accordance with the applicable
standards of this section.
C403.2.9. ',Duct
insulation is protected from
❑Complies
Requirement will be met.
1.2
damage but not limited to the
❑Does Not
[ME80]2 ;following:
1. Insulation exposed to
❑Not Observable
weather is suitable for outdoor
Applicable
'service.
Cellular foam insulation is❑Not
protected or painted with a coating
that is water retardant and provides
shielding from solar radiation. 2.
Insulation covering cooling ducts
located outside the conditioned space
is vapor retardant located outside the
insulation, all penetrations and joints
of which shall be sealed.
C403.2.9. ;Additional
insulation with vapor ❑Complies
Requirement will be met.
1.3 +
barrier is provided where the ❑Does Not
[ME81]2 ;
minimum duct insulation requirements
❑Not Observable
'determined
of Section C403.2.9.1.1 are
❑Not Applicable
to be insufficient to
prevent condensation.
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: PACLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 21 of 37
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.2.13
Unenclosed spaces that are heated
,❑Complies
Exception: Requirement does not apply.
[ME71]2
use only radiant heat.
❑Does Not
!❑Not Observable
❑Not Applicable
C403.2.3
HVAC equipment efficiency verified.❑Complies
See the Mechanical Systems list for values.
[ME55]2
❑Does Not
❑Not Observable
❑Not Applicable
C403.2.9.
Ducts, air handlers, filter boxes,
❑Complies
Requirement will be met.
3'
building cavities, mechanical closets
❑Does Not
[ME10]2
and enclosed support platforms that
❑Not Observable
form the primary air containment
❑Not Applicable
passageways for air distribution
systems are sealed in accordance with
the applicable criteria of this section
and Table C403.2.9.2.
C403.2.9. ,Cavities
in framed spaces are not
❑Complies
Exception: Requirement does not apply.
4
used to deliver air from or return air to❑Does
Not
[ME78]2
the conditioning system unless they
Observable
contain an air duct insert which is �RNot
❑Not Applicable
insulated in accordance with Section
C403.2.9.1 and constructed and
sealed in accordance with the
requirements of Section C403.2.9.2
appropriate for the duct materials
;used.
C403.2.9. !Air
distribution systems are sized and
❑Complies
Requirement will be met.
5
designed in accordance with
❑Does Not
[ME76]2
recognized engineering standards.
❑Not Observable
Refer to section details.
❑Not Applicable
C403.2.9. IAir-handling
units not installed in
❑Complies
Exception: Requirement does not apply.
6
attics of commercial buildings.
❑Does Not
[ME77]2
;❑Not
Observable
❑Not Applicable
C403.2.4. :Zone
isolation devices and controls
❑Complies
Exception: Exhaust and outdoor air connections having fan
4 1
installed where applicable.
❑Does Not
systems 5000 cfm or smaller.
[ME112]3
❑Not Observable
❑Not Applicable
C403.2.4.
Fault detection and diagnostics ❑Complies
Requirement will be met.
7 !installed
with air-cooled unitary DX ❑Does Not
[ME113]2
units having economizers.
,[:]Not Observable
❑Not Applicable
C408.2.2.
Air system balancing accomplished in ❑Complies
Requirement will be met.
1
a manner to first minimize throttling ❑Does Not
[ME53]3
losses, then for fans with fan system
❑Not Observable
power greater than 1 hp, fan speeds
shall be adjusted to meet design flow ❑Not Applicable
conditions. Balancing procedures shall
be in accordance with NEBB
Procedural Standards, the AABC,
National Standards, or equivalent
procedures.
C403.2.6.
Demand control ventilation provided ❑Complies
Requirement will be met.
1 for spaces >500 ft2 and >25 ❑Does Not
[ME59]1
people/1000 ft2 occupant density and
❑Not Observable
served by systems with air side
Applicable
economizer, auto modulating outside❑Not
air damper control, or design airflow
>3,000 cfm.
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 22 of 37
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.2.6.
Enclosed parking garage ventilation
❑Complies
Exception: Requirement does not apply.
2
has automatic contaminant detection
❑Does Not
[ME115]3
and capacity to stage or modulate
Observable
fans to 50% or less of design capacity.❑Not
❑Not Applicable
C403.2.7
Exhaust air energy recovery on
❑Complies
Requirement will be met.
[ME57]1
systems meeting Table C403.2.7(1)
❑Does Not
and C403.2.7(2).❑Not
Observable
❑Not Applicable
C403.2.8
Kitchen exhaust systems comply with
❑Complies
Exception: Requirement does not apply.
[ME116]3
replacement air and conditioned
❑Does Not
supply air limitations, and satisfy hood
❑Not Observable
rating requirements and maximum
❑Not Applicable
exhaust rate criteria.
C403.3
Air economizers provided where
❑Complies
Requirement will be met.
[ME62]1
required, meet the requirements for
❑Does Not
design capacity, control signal,
ventilation controls, high -limit shut-off,
❑Not Observable
integrated economizer control, and
❑Not Applicable
provide a means to relieve excess
outside air during operation.
C403.4.1. Hydronic and multizone HVAC system❑Complies
Requirement will be met.
1
controls areVAV fans driven by
❑Does Not
[ME75]2
mechanical or electrical variable
❑Not Observable
,
speed drive per Table C403.4.1.1.
❑Not Applicable
C403.4.1. VAV fans have static pressure sensors❑Complies
Exception: Requirement does not apply.
2
located so controller setpoint <=1.2
❑Does Not
[ME67]2
w.c.. ;❑Not
Observable
❑Not Applicable
C403.4.1. Reset static pressure setpoint for DDC ❑Complies
Exception: Requirement does not apply.
3
controlled VAV boxes reporting to
❑Does Not
[ME24]2
central controller based on the zones
❑Not Observable
requiring the most pressure.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3 ;pressure
setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4. Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6 iof
individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls. !❑Not
Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static �❑Does Not
[ME110]3
pressure setpoint reset controls. ❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manua l\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 23 of 37
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6 !
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4. Multiple zone VAV systems with DDC ❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4. !
Multiple zone VAV systems with DDC❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4. Multiple zone VAV systems with DDC
❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C403.4.4. Multiple zone VAV systems with DDC ❑Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
See the Mechanical Systems list for values.
❑Not Applicable
C408.2.2. 'Air
outlets and zone terminal devices
❑Complies
Requirement will be met.
1
have means for air balancing.
❑Does Not
[ME53]3
❑Not Observable
❑Not Applicable
C403.5, Refrigerated display cases, walk-in
❑Complies
Exception: Requirement does not apply.
C403.5.1,
coolers or walk-in freezers served by
❑Does Not
C403.5.2
remote compressors and remote
❑Not Observable
[ME123]3 ,condensers
not located in a
❑Not Applicable
condensing unit, have fan -powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
C403.5.3 Condensing coils installed in cool air
❑Complies
Requirement will be met.
[ME124]3
stream of another air-conditioning
❑Does Not
unit. The condensing coil of one air-
;
conditioning unit shall not be installed
❑Not Observable
in the cool air stream of another air- '❑Not
Applicable
conditioning unit.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 24 of 37
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills
Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manua l\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 25 of 37
Section
#
Rough -In Electrical Inspection
Complies?
Comments/Assumptions
& Req.ID
C405.2.1
Lighting controls installed to uniformly❑Complies
Requirement will be met.
[EL15]1
reduce the lighting load by at least
❑Does Not
50%.
❑Not Observable
!❑Not Applicable
C405.2.1 :
Occupancy sensors installed in
❑Complies
Requirement will be met.
[EL18]1
required spaces.
❑Does Not
i❑Not
Observable
❑Not Applicable
C405.2.1,
Independent lighting controls installed❑Complies
Requirement will be met.
C405.2.2.
per approved lighting plans and all
❑Does Not
3
manual controls readily accessible and
❑Not Observable
[EL23]2
visible to occupants.
❑Not Applicable
C405.2.2.
Automatic controls to shut off all ❑Complies
Exception: Areas such as security or emergency areas that
1
building lighting installed in all
]Does Not
need continuous lighting.
[EL22]2
buildings.
❑Not Observable
❑Not Applicable
C405.2.3
Daylight zones provided with ❑Complies
Requirement will be met.
[EL16]2
individual controls that control the
❑Does Not
lights independent of general area
❑ Not Observable
lighting.
❑Not Applicable
C405.2.3, :
Primary sidelighted areas are
❑Complies
Requirement will be met.
C405.2.3.
equipped with required lighting I❑Does
Not
1,
C405.2.3.
controls.
❑ Not Observable
2
❑Not Applicable
[EL20]1
C405.2.3,
Enclosed spaces with daylight area
❑Complies
Requirement will be met.
C405.2.3.
under skylights and rooftop monitors
❑Does Not
1,
are equipped with required lighting
❑Not Observable
C405.2.3.
3
controls.
❑Not Applicable
[EL21]1
C405.2.4
Separate lighting control devices for ❑Complies
Requirement will be met.
[EL4]1
specific uses installed per approved
❑Does Not
lighting plans.
❑Not Observable
❑Not Applicable
C405.2.4 ;Additional
interior lighting power ❑Complies
Requirement will be met.
[EL8]1 �
allowed for special functions per the
❑Does Not
approved lighting plans and is
❑Not Observable
automatically controlled and
separated from general lighting.
❑Not Applicable
C405.2.5 Automatic lighting controls for exterior',❑Complies
Requirement will be met.
[EL25]nu°
lighting installed. Controls will be
❑Does Not
daylight controlled, set based on
❑Not Observable
business operation time -of -day, or
❑Not Applicable
reduce connected lighting > 30%.
C405.3
Exit signs do not exceed 5 watts per ❑Complies
Requirement will be met.
[EL6]1
face.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills
Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 26 of 37
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 27 of 37
Section
#
Insulation Inspection
Complies?
Comments/Assumptions
& Req.ID
C303.1
Roof insulation installed per
❑Complies
Requirement will be met.
[IN3]1
manufacturer's instructions. Blown or
❑Does Not
poured loose -fill insulation is installed
❑Not Observable
;only where the roof slope is <=3 in
❑ Not Applicable
12,
C303.1
Building envelope insulation is labeled❑Complies
Requirement will be met.
[IN10]2 :with
R-value or insulation certificate
❑Does Not
providing R-value and other relevant
❑Not Observable
data.
❑Not Applicable
C303.2
Above -grade wall insulation installed
❑Complies
Requirement will be met.
[IN7]1
per manufacturer's instructions. ;ODoes
Not
❑Not Observable
❑Not Applicable
C303.2,
Floor insulation installed per
❑Complies
Exception: Requirement does not apply.
C402.2.4
manufacturer's instructions. Cavity or❑Does
Not
[IN9]2 istructural
slab insulation installed in
❑Not Observable
permanent contact with underside of
Applicable
decking or structural slabs.
C303.2.1
Exterior insulation is protected from
❑Complies
Requirement will be met.
[IN14]2
damage with a protective material.
❑Does Not
Verification for exposed foundation
❑Not Observable
'Foundation
insulation may need to occur during
❑Not Applicable
Inspection.
C402.2.1 ':Skylight
curbs are insulated to the
❑Complies
Requirement will be met.
[IN4]3
level of roofs with insulation above
❑Does Not
deck or R-5.
❑Not Observable
❑Not Applicable
C402.2.1
Insulation intended to meet the roof
❑Complies
Requirement will be met.
[IN17]3
insulation requirements cannot be '❑Does
Not
installed on top of a suspended
ceiling. Mark this requirement
[:]Not Observable
compliant if insulation is installed
❑Not Applicable
accordingly.
C104
Installed above -grade wall insulation "OComplies
See the Envelope Assemblies table for values.
[IN6]1
type and R-value consistent with
❑Does Not
insulation specifications reported in
❑Not Observable
plans and COMcheck reports.
❑Not Applicable
C104 ;
Installed floor insulation type and R-
❑Complies
See the Envelope Assemblies table for values.
[IN8]2 'value
consistent with insulation
❑Does Not
specifications reported in plans and
Observable
COMcheck reports. ,❑Not
❑Not Applicable
C402.2.6
Radiant panels and associated
❑Complies
Exception: Requirement does not apply.
[IN18]3
components, designed for heat !'❑Does Not
transfer from the panel surfaces to the
❑Not Observable
:occupants
'insulated
or indoor space are
❑Not Applicable
with a minimum of R-3.5.
C402.3
High-albedo roofs satisfy one of the ;OComplies
Requirement will be met.
[IN5]3
following: 3-year-aged solar ❑Does Not
reflectance >= 0.55 and thermal
❑Not Observable
emittance >= 0.75 or 3-year-aged
!❑Not Applicable
solar reflectance index >= 64.0.
C402.5.1.
All sources of air leakage in the ❑Complies
Requirement will be met.
1
building thermal envelope are sealed, ❑Does Not
[IN1]1
caulked, gasketed, weather stripped
❑Not Observable
or wrapped with moisture vapor-
❑Not Applicable
permeable wrapping material to
minimize air leakage.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills
Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 28 of 37
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 29 of 37
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.ID
C303.3,
Furnished O&M instructions for
❑Complies
Requirement will be met.
C408.2.5.
systems and equipment to the
❑Does Not
2
[F117]3
building owner or designated
representative.
I❑Not Observable
❑Not Applicable
C303.3,
Furnished O&M manuals for HVAC
iRComplies
Requirement will be met.
C408.2.5. 'systems
within 90 days of system
❑Does Not
3
[F18]3
acceptance.
❑Not Observable
❑Not Applicable
C403.2.4.
Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4.
Minimum one humidity control device
❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
�❑Not
Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device
❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device
❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
(F156]3
humidification/dehumidification
❑Not Observable
'system.
Controls prevent
❑Not Applicable
simultaneous operation of
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of❑Not Applicable
humidification and dehumidification
equipment.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 30 of 37
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Re .ID
C403.2.4.
Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
�❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
'system. Controls prevent
'simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4.
Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3 j
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4.
Minimum one humidity control device❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
;❑Not
Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. ',Minimum
one humidity control device
❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of 1EINot
Applicable
humidification and dehumidification
equipment.
C403.2.4. Minimum one humidity control device
❑Complies
Requirement will be met.
2.4
per installed
❑Does Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C403.2.4. :Minimum
one humidity control device
❑Complies
Requirement will be met.
2.4
per installed 1EIDoes
Not
[F156]3
humidification/dehumidification
❑Not Observable
system. Controls prevent
simultaneous operation of
❑Not Applicable
humidification and dehumidification
equipment.
C402.5.3 'Where
open combustion air ducts
❑Complies
Exception: Requirement is not applicable.
[F151]3
provide combustion air to open
❑Does Not
combustion fuel burning appliances,
the appliances and combustion air
❑Not Observable
opening are located outside the
❑Not Applicable
building thermal envelope or enclosed
in a room, isolated from inside the
thermal envelope. Such rooms are
sealed and insulated.
C402.5.6
Weatherseals installed on all loading
❑Complies
Exception: Requirement does not apply.
[F137]1
dock cargo doors. ❑Does Not
;ONot Observable
❑Not Applicable
C402.5.8
Recessed luminaires in thermal ❑Complies
Exception: Requirement does not apply.
[F126]3
envelope to limit infiltration and be IC ❑Does Not
rated and labeled. Seal between
❑Not Observable
interior finish and luminaire housing.
❑Not Applicable
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 31 of 37
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.1D
C403.2.1
HVAC systems and equipment design
❑Complies
Exception: Registered engineer designed mechanical systems
[F150]3
loads calculated in accordance with
I❑Does Not
exercises option of submitting a signed and sealed summary
ANSI/ASHRAE/ACCA Standard 183 or
❑Not Observable
sheet to the building department in lieu of the complete sizing
;ACCA Manual N or by an approved
Applicable
calculation(s).
equivalent computational procedure.❑Not
Design loads shall be attached to the
,,code
compliance form submitted to
,the
building department when the
building is permitted or, in the event
;the
mechanical permit is obtained at a
later time, the sizing calculation shall
be submitted with the application for
the mechanical permit.
C403.2.2
HVAC systems and equipment
❑Complies
Requirement will be met.
[F127]3 'capacity
does not exceed calculated
❑Does Not
loads.
❑Not Observable
❑Not Applicable
C403.2.4.
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
'❑Not
Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4. ; Heating and cooling to each zone is '❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4. Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
,
Minimum one humidity control device
'❑Not
Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4. Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification❑Not
Applicable
system.
C403.2.4. Heating and cooling to each zone is 1❑Complies
Requirement will be met.
1
controlled by a thermostat control. '❑Does
Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification �ONot
Applicable
system.
C403.2.4. 'Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3 !
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4. 'Heating and cooling to each zone is ❑Complies
Requirement will be met.
1
controlled by a thermostat control. �❑Does
Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 32 of 37
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.2.4.
Heating and cooling to each zone is
;❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification❑Not
Applicable
system.
C403.2.4. :
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
per installed I❑Not
Observable
'
humidification/dehumidification ;ONot
Applicable
system.
C403.2.4.
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control. !❑Does
Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control. :,❑Does
Not
[F147]3 j
Minimum one humidity control device
Observable
per installed IFINot
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Heating and cooling to each zone is
❑Complies
Requirement will be met.
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
per installed ;ONot
Observable
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Heat pump controls prevent❑Complies
Requirement will be met.
1.1 -supplemental
electric resistance heat
❑Does Not
[F142]3
from coming on when not needed.
❑Not Observable
❑Not Applicable
C403.2.4. ;Thermostatic
controls have a 5 OF
❑Complies
Requirement will be met.
1.2 ideadband.
❑Does Not
[F138]3
❑Not Observable
❑Not Applicable
C403.2.4. ';Temperature
controls have setpoint IOComplies
Requirement will be met.
1.3 "'
overlap restrictions. '❑Does Not
[F120]3
❑Not Observable
[]Not Applicable
C403.2.4. "''
Each zone equipped with setback ❑Complies
Requirement will be met.
2
controls using automatic time clock or ❑Does Not
[F139]3 ;programmable
control system.
❑Not Observable
❑Not Applicable
C408.2.2 'Construction
documents require that a ,❑Complies
Requirement will be met.
[F154]3
written balance report be provided to ❑Does Not
,the building owner or rep for HVAC
❑Not Observable
systems serving zones with total
❑Not Applicable
condition area > 5,000 sqft. Air
distribution systems shall be tested,
adjusted, and balanced by a licensed
engineer or certified company.
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 33 of 37
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.2.4.
''Automatic Controls: Setback to 550F
❑Complies
Requirement will be met.
2.1,
I (heat) and 85°F (cool); 7-day clock, 2-❑Does
Not
C403.2.4.
hour occupant override, 10-hour
❑Not Observable
2.2
[F140]3
backup
❑Not Applicable
C403.2.4.
Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4.
Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
�❑Not Observable
❑Not Applicable
C403.2.4.
Systems include optimum start ',❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4. Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4.
Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4.
Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4. !,Systems include optimum start ❑Complies
Requirement will be met.
2.3
controls. '❑Does
Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4. Systems include optimum start ;❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3❑Not
Observable
❑Not Applicable
C403.2.4. Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
C403.2.4. !Systems include optimum start❑Complies
Requirement will be met.
2.3
controls. T❑Does
Not
[F141]3
i❑Not
Observable
❑Not Applicable
C403.2.4. Systems include optimum start❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
❑Not Observable
❑Not Applicable
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: PACLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 34 of 37
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.2.4.
Systems include optimum start
❑Complies
Requirement will be met.
2.3
controls.
❑Does Not
[F141]3
,;❑Not Observable
❑Not Applicable
C405.4.1
Interior installed lamp and fixture
❑Complies
See the Interior Lighting fixture schedule for values.
[F118]1
lighting power is consistent with what❑Does
Not
is shown on the approved lighting
'
ONot Observable
,plans,
demonstrating proposed watts
❑Not Applicable
are less than or equal to allowed
watts.
C405.5.1
Exterior lighting power is consistent
❑Complies
See the Exterior Lighting fixture schedule for values.
[F119]1
with what is shown on the approved
❑Does Not
lighting plans, demonstrating
❑Not Observable
'to
proposed watts are less than or equal
❑Not Applicable
allowed watts.
C408.2.1
Commissioning plan developed by
❑Complies
Requirement will be met.
[F128]1
registered design professional or
❑Does Not
approved agency.
'Not
❑ Observable
❑Not Applicable
C408.2.3.
HVAC equipment has been tested to
❑Complies
Requirement will be met.
1
ensure proper operation.
❑Does Not
[F131]1
❑Not Observable
❑Not Applicable
C408.2.3.
HVAC control systems have been
❑Complies
Requirement will be met.
2
tested to ensure proper operation, '❑Does
Not
[FI10]1
calibration and adjustment of controls.
❑Not Observable
❑Not Applicable
C408.2.3.
Economizers have been tested to
❑Complies
Requirement will be met.
3
ensure proper operation.
❑Does Not
[F132]1
❑Not Observable
❑Not Applicable
C408.2.4
Preliminary commissioning report
❑Complies
Requirement will be met.
[F129]1
completed and certified by registered
❑Does Not
design professional or approved
❑Not Observable
agency.
❑Not Applicable
C408.2.5. '
Furnished HVAC as -built drawings
❑Complies
Requirement will be met.
1 'submitted
within 90 days of system
❑Does Not
[F17]3
acceptance.
❑Not Observable
❑Not Applicable
C408.2.5.
Furnished as -built drawings for
❑Complies
Requirement will be met.
1
electric power systems within 90 days ❑Does Not
[F116]3
of system acceptance.
❑Not Observable
❑Not Applicable
C408.2.5. ,An air and/or hydronic system
❑Complies
Requirement will be met.
3
balancing report is provided for HVAC ❑Does Not
[F143]1
systems.
',❑Not Observable
❑Not Applicable
C408.2.5.
Final commissioning report due to ❑Complies
Requirement will be met.
4
building owner within 90 days of ❑Does Not
[F130]1
receipt of certificate of occupancy.
❑Not Observable
❑Not Applicable
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BLOX - Zephyrhills Report date: 11/23/20
Data filename: PACLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 35 of 37
Section
# Final Inspection Complies? Comments/Assumptions
& Rea.ID
C408.3 Lighting systems have been tested to ❑Complies Requirement will be met.
[F13311 ensure proper calibration, adjustment, ❑Does Not
programming, and operation.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low impact (Tier 3)