A placard shall be conspicuously placed
near each Class K extinguisher that states
that the fire protection system shall be
activated prior to using the fire
extinguisher.
Owners Responsibility:
Safety Set Positioning System to be
installed on all wheeled appliances.
Safety -Set is designed to return
caster -mounted kitchen equipment to a
specific location after cleaning or
maintenance.
Scope of Work for fire suppression system:
Complete final hook up of pre -piped
CaptiveAire Hood.
Shut -Downs and electrician responsibilities:
All Electric and Gas cooking equipment
under the kitchen hood and any outlets shall
shut off upon fire suppression system
actuation. Make Up Air/supply shall
shutdown upon fire suppression system
actuation. Exhaust fan operation to follow
hood manufacturer specification.
Pre -Engineered Fire Suppression System
Shall be connected to the fire alarm. (if any).
Local alarm (horn/strobe or bell) may be
required by the Authority Having
Jurisdiction.
Manual actuation device (push station) shall
be located at the means of egress or at the
location acceptable to the AHJ and installed
at 42"-48" above the floor. The manual
actuation device shall clearly identify the
hazard protected.
New CaptiveAire SP-3 12 - Gallon UL-300 Compliant Wet Chemical Fire Suppression System
FACTORY PIPING EXTENDS A MAXIMUM
OF 6" ABOVE THE TOP OF THE HOOD.
OL—F
OL—F OL—F OL—F
85.0000
OL— F b' 21. 0"
---18.0000 32.0000
OL-F OL-F
32.0000
" 21. 0"
32.0000
OL-F OL-F
TANK OVERLAPPING COVERAGE
Installation shall be done in accordance with:
2023 FFPC 8th ed., NFPA 96 2021 ed., NFPA 17A 2021 ed.,
UL-300 standard, FBC 8th ed., NFPA 1 2021 ed., Florida State
Statue 633-Rule 4A-21, NFPA 101 2021 ed., NFPA 72 2019 ed.,
NFPA 70 2020 ed.
>
21. DpL—F I OL—F
51.6250
21. 0" LN 21.
23.2500
1"
OL-F OL-F
NOZZLE HEIGHT
35-50" FROM
COOKING SURFACE.
Legend - Fire Cabinet Tank System
1 4 Gallon Tank
2 Primary Actuator Release
3 Secondary Actuator Release
4 Pressure Supervision Switch
5 Primary Hose Assembly
6 Secondary Hose Assembly
7 Remote Manual Actuation Device
- SYSTEM REQUIRES A MINIMUM OF 7 FT OF -
EQUIVALENT PIPE LENGTH BETWEEN TANK AND
NEAREST APPLIANCE NOZZLE FOR MOST APPLIAI
EACH 90 DEGREE ELBOW ADDS 1.3 FT OF
EQUIVALENT LENGTH. SEE MANUAL FOR DETAILS
OL—F
S K FIVE
ClUISHHF_
_11EP. SI_11*T
Tank SP-3 12-Gal System:
Hood sizes: 3 - 7' 0"
1 & 2-11'0"
Plenum: Single bank
Amount of Ducts and Size: 3 - 12" Dia., 2
- 18" Dia., 1 - 16" Dia.
Length of supply Line Less than 30'
Detection: 2 - Firestat Heat Detectors
3600 F
Number of Flow Points Available in
System = 60
Number of Flow Points Used in System =
56
Each nozzle (OL-F) uses 4 flow points.
All pipe inside of the hood is 3/8 and
7
conduit 1 /2" used and all penetrations
sealed with UL listed device or welded.
All Pipe & Fittings and nozzles to be
installed in accordance with UL 300 &
manufacture's specs.
All Protected Cooking Appliances Under
the Hood Shall be UL Listed.
ALL WORK SHALL COMPLY WITH
NFFA CODES AND STANDARDS
REVIEW DATE '-)- °2-
CITY OF ZEPHYRHILLS
FIRE AND LIFE SAFETY EXAMINER
6P �SS1
,H7f Clot( bjO
«. FIRE SUPPRESSION SYSTEM
Scale: N.T.S
in
J2-2
BREAK
Ir
EFORE
INSERTING
INTO
1!4 MI (.111116161 I
Firestat Details
CARE PROTECTIDN SENSOR INSTALLATIDN
NOTES: One Sensor per Riser
Multiple Sensors Wired in Parallel
Wire Both Black Wires to One Lead, Both White
Sensor may be installed on inside or outside of
When installed in duct, install on opposite side
1/2" NPT Quik Seal (Adapter Body)
Part # 32-00002----\
I Cf IVY Ul I If C J 1,U 1.
12-F28021-005360
(Normally Open,
Close on rise @ 360°F)
OR
Fenwal Fire Stat
12-G28021-005500
(Normally Open,
Close on rise @ 500°F)
I/ if" uuiK peal (Gasket:
Part # 32-00002
Wires to Second
quick seal. When
of quick seal, or
Lead
installed
as shown
in riser, install as
with access door
shown for sensor
f or cleanability.
1/ C
Part
access from hood.
Grease Duct
(External Surf ace)
NPT Quk Seal
unIn nnnnll
Quik Seal Clock
#32-00002
Washer)
Extension Ring
59361-1/2
,xNOTEi EXTENSION
RING TO BE
TACK WELDED
TO DUCT OR
RISER
Extension
100-BW
Ring Cover
FIRE SUPPRESSION SYSTEM
Scale: N.T.S
Pull Station Details
ELECTRIC WET CHEMICAL (EWC) SPECIFICATION
THE ELECTRIC WET CHEMICAL (EWC) FIRE SUPPRESSION SYSTEM IS A HYBRID FIRE SUPPRESSION SYSTEM FOR USE
IN COMMERCIAL KITCHENS.
THE CORE EWC MICROPROCESSOR -BASED CONTROL BOARD, PCBCORE BOARD, IS ETL LISTED UNDER REPORT
NUMBER 101196419NYM-001 TO THE UL STANDARD 864 AND CAN/ULC-S527-11. THE COREPCB IS DESIGNED TO
CONTROL A 24VDC-BASED, LISTED UL 300 WET CHEMICAL RESTAURANT FIRE SUPPRESSION SYSTEM. THE COREPCB
CONTROLS PROVIDE ALL NECESSARY MONITORING, TIMING AND SUPERVISION FUNCTIONS REQUIRED FOR THE
RELIABLE OPERATION OF THE WET CHEMICAL FIRE SUPPRESSION SYSTEM. ALL DEVICES THAT ARE CRITICAL FOR
PROPER OPERATION ARE SUPERVISED AND INCLUDE AN ELECTRIC THERMAL DETECTOR(S) AND MANUAL PULL
STATION(S)/MANUAL ACTUATION DEVICE(S). THE COREPCB CONTROL BOARD ALSO SUPERVISES FAULTS WITHIN
THE SYSTEM AND WILL ALERT THE USER OF SPECIFIC CONDITION.
I W 3.2511
CORE PROTECTION
HOOD FIRE
SYSTEM
";
LIFT HERE
ELECTRIC WET CHEMICAL MANUAL ACTIVATION STATION DETAIL
THE PUSH/PULL STATION IS A REMOTE MANUAL ACTIVATION DEVICE TO
ACTIVATE THE FIRE SYSTEM. THIS REMOTE MANUAL ACTIVATION DEVICE
(PUSH/PULL STATION) CONTAINS ONE SET OF NORMALLY OPEN
CONTACTS, AND MOUNTS TO ANY STANDARD JUNCTION BOX. WHEN THE
FRONT BUTTON IS PRESSED, THE ELECTRICAL CONNECTION TO THE FIRE
SYSTEM IS COMPLETED, THUS ACTIVATING THE FIRE SYSTEM.
THE REMOTE MANUAL ACTIVATION (PUSH/PULL STATION) SHOULD BE
MOUNTED AT THE POINT OF EGRESS AT 42-48 ABOVE THE FLOOR..
LOCATION OF THE MANUAL PULL STATION SHOULD BE DETERMINED BY
AHJ. TO RESET, TWIST THE PUSH-BUTTON CLOCKWISE UNTIL THE
INTERNAL LATCH IS RELEASED.
THE CLEAR PROTECTIVE COVER MUST BE INSTALLED TO PROTECT THE
DEVICE FROM ACCIDENTAL ACTIVATIONS. THE COVER IS PROVIDED AS
PART OF THE MANUAL ACTIVATION DEVICE.
THE SYSTEM IS CAPABLE OF AUTOMATIC DETECTION AND ACTIVATION AND/OR REMOTE MANUAL ACTIVATION. THE DETECTION
PORTION OF THE FIRE SUPPRESSION SYSTEM ALLOWS FOR AUTOMATIC DETECTION BY MEANS OF AN ELECTRIC THERMAL DETECTOR(S)
LOCATED IN THE HOOD DUCT CONNECTION(S). A PUSH STATION / MANUAL ACTUATION DEVICE IS ALSO PROVIDED TO ALLOW FOR
MANUAL ACTIVATION OF THE FIRE SYSTEM.
WITH THE ELECTRIC THERMAL DETECTION, A BATTERY BACKUP SYSTEM IS PROVIDED. THE BACKUP BATTERY SYSTEM POWERS THE
COREPCB BOARD CONTROLS INCLUDING THE AUTOMATIC DETECTION, PULL STATION/MANUAL ACTUATION DEVICE CIRCUITS, AS WELL
AS SUPERVISES THOSE DEVICES AND ANY AUXILIARY SUPERVISORY EQUIPMENT IN THE EVENT OF A LOSS OF POWER TO THE BUILDING.
UPON A FIRE CONDITION, THE ELECTRIC THERMAL DETECTOR CONTACTS WILL CLOSE AND SEND A SUPERVISED SIGNAL TO THE COREPCB
BOARD. THE COREPCB BOARD THEN SENDS A SIGNAL TO THE 24VDC REGULATED RELEASE SOLENOID, WHICH WILL PUNCTURE A
PRECHARGED WET CHEMICAL AGENT TANK PROPELLING AGENT INTO THE DISTRIBUTION LINES TOWARDS THE DISCHARGE NOZZLES
BREAK� WIRE
BEFOR
INSERTING
INTO
TERMINA:Lz��
MINE
■
2
MANUAL
uATION
DEVICE
«, \FIRE SUPPRESSION SYSTEM
Scale: N.T.S