PI MI LI KI HI GI FI EI DI CI BI AI 1 1 2 3 4 SCOPE OF WORK The new system shall include: New addressable fire panel Firelite ES-20OX External cellular communicator at the panel. An addressable smoke detector installed above panel. A remote ANN-80 annunciator shall be installed at the entrance. Installation of notification appliances as shown on plans. New manual pull station shall be installed within T of each exit. An addressable relay shall be installed within 3' of the Muzak system of audio shunt. Terminations to the Muzak system from JCI supplied relay shall be completed by customer's contractor. A dual monitor module shall be installed at the sprinkler riser for supervision of the waterflow / tamper switch. A weather-proof horn strobe shall be installed above the exterior fire department connection (FDC) All wire shall be open -ran or concealed in wall or ceiling. Where wire is below 10', it shall be installed in 3/4' EMT conduit. Fire alarm panel shall communicate to monitoring station via sole path cellular communication. Duct detectors for HVAC shall be provided by JCI, and installed by customers mechanical contractor. Addressable relays are provided for global RTU shutdown. 61G15NOTES OPERATIONS AND MAINTENANCE ft TEST REQUIREMENTS: 1) THE FIRE ALARM SYSTEM 15 MANUALLY -ACTIVATED BY PULL STATIONS; AUTOMATICALLY ACTIVATED BY SMOKE DETECTORS, HEAT DETECTORS, AND SPRINKLER FLOW. 2) A CERTIFIED LEVEL 3 OR 4 PERSONNEL WITH ACCESS CODE, CAN TURN ON OR OFF THE FACP BY THE ARM/ON AND DISARM/OFF BUTTONS ON THE FACP. 3) THE SYSTEM INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 72 Et NFPA 70. 4) ACCEPTANCE TESTING INCLUDING RE -ACCEPTANCE TESTING IS REQUIRED IN COMPLIANCE WITH THE NFPA 72. 5) PERIODIC INSPECTION ft TESTING IS REQUIRED IN COMPLIANCE WITH NFPA 72, CHAPTER 14. 6) OWNERS DOCUMENTS, WHICH INCLUDE OPERATION -INSTRUCTIONS, MAINTENANCE -PROCEDURES, AND ANY INFORMATION TO ASSIST WITH THE UNDERSTANDING OF THE FIRE ALARM SYSTEM, WILL BE PROVIDED WITH THE CLOSE OUT DOCUMENTS AT THE COMPLETION OF THE JOB. SUPPLIED TO CUSTOMER. THE EXISTING FIRE ALARM SYSTEM SHALL NOT BE DISCONNECTED OR TAKEN OUT OF SERVICE WITHOUT WRITTEN PERMISSION FROM THE OWNER. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH THE OWNER THE TIMING OF ANY EXISTING FIRE ALARM SYSTEM DEMOLITION WORK. APPLICABLE CODES STANDARDS Florida Fire Prevention Code, Eighth Edition (2023) Florida Building Code, Eighth Edition (2023) NFPA 1, Fire Code, 2021 Edition International Building Code (IBC), 2021 Edition NFPA 101, Life Safety Code, 2021 Edition NFPA 70, National Electric Code, 2020 Edition NFPA 72, National Fire Alarm and Signaling Code, 2019 Edition Testing per NFPA 72, 2019 Edition BUILDING INFORMATION USE Et OCCUPANCY CLASSIFICATION BUILDING CONSTRUCTION TYPES I. ASSEMBLY (A) 0 A-1 0 A-2 0 A-3 0 A-4 0 A-5 TYPE 1 0 TYPE I -A 0 TYPE I-B 0 0 BUSINESS (B) TYPE II 0 TYPE II -A 0 TYPE II-B 0 0 EDUCATIONAL (E) TYPE III 0 TYPE III -A 0 TYPE III-B 0 O FACTORY Et INDUSTRIAL (F) O F-1 O F-2 TYPE IV 0 TYPE IV-B 0 0 HIGH HAZARD (H) 0 H-1 0 H-2 0 H-3 0 H-4 0 H-5 TYPE V 0 TYPE V-A 0 TYPE V-B 0 INSTITUTIONAL (1) 0 1-1 0 1-2 0 1-3 1 0 1-4 1 0 1-5 AUTOMATIC SPRINKLER PROTECTION 0 MERCANTILE (M) NO 0 PARTIAL 0 FULL 0 RESIDENTIAL (R) 0 R-1 0 R-2 0 R-3 0 R-4 BUILDING AREA: 5780 Sq.Ft 0 STORAGE (S) 0 S-1 0 S-2 NUMBER OF FLOORS: 1 0 UTILITY 8 MISC. (U) OCCUPANT LOAD: 263 FIRE ALARM CABLE LEGEND ID AWG COND SHIELD CLASS* ID AWG COND SHIELD CLASS" A 18 2 N FPLP B 18 2 Y FPLP C 18 4 N FPLP D 16 2 N FPLP E 16 2 Y FPLP F 16 4 N FPLP G 14 2 N FPLP H 14 4 N FPLP J 12 2 N FPLP K 12 4 N FPLP NOTES DRAWING ACCEPTANCE THIS DRAWING IS TO BE USED ONLY FOR THE PURPOSE OF PLACING AND LOCATING JOHNSON CONTROLS EQUIPMENT AND IS NOT TO BE USED FOR ANY OTHER PURPOSES. IT IS THE RESPONSIBILITY OF THE LOCAL JOHNSON CONTROLS SALES >3 SERVICE OFFICE (SSO) TO REVIEW THE CONTENT OF THESE DRAWINGS FOR ACCURACY AND COMPLIANCE WITH LOCAL AND STATE CODES PRIOR TO RELEASING THEM TO THE FIELD. RECORD DRAWINGS ALL WORK PERFORMED IN THE FIELD SHALL BE ACCURATELY RECORDED ON THESE DRAWINGS AND RETURNED TO THE JOHNSON CONTROLS OFFICE AT THE ADDRESS LISTED ABOVE. MONITORING LOCATIONS JOHNSON CONTROLS ALARM SERVICE CO:360682-221 14200 EXPOSITION AVE. SERVICE CENTER NUMBER:768 AURORA, CO. 80012 UL LISTING: S949-183 1-800-428-7124 2 3 0 I: 5 0 7 0 10 11 12 LONGHORN STEAKHOUSE GENERAL NOTES 1 ALL APPLICABLE PERMITS SHALL BE OBTAINED PRIOR TO STARTING WORK. 2 WORK SHALL COMPLY WITH ALL APPLICABLE CODES. 3 POWER (120VAC) TO ALL FIRE ALARM AND SECURITY PANELS SHALL BE SUPPLIED FROM DEDICATED, UNSWITCHED AND CLEARLY IDENTIFIABLE SOURCES. 4 ALL DOORS WHICH ARE CONTROLLED BY ELECTRONIC LOCKING DEVICES SHALL BE CONFIGURED TO MEET ALL CODES. 5 ALL DEVICES EITHER INSTALLED WITHIN THE SCOPE OF THIS PROJECT OR AFFECTED BY THIS PROJECT SHALL BE TESTED. 6 ALL CABLE SHALL BE RATED FOR THE ENVIRONMENT IN WHICH IT IS INSTALLED. 7 ALL WORK SHALL BE PERFORMED IN A PROFESSIONAL MANNER. 8 AREAS AFFECTED BY THE SCOPE OF THIS PROJECT SHALL BE KEPT CLEAN AND TRASH REMOVED DAILY. 9 FIRE ALARM CABLING SHALL NOT BE PAINTED. EXPOSED CONDUCTORS SHALL BE RUN ALONG CEILING JOISTS AND GIRDERS. ALL WIRING TO BE CONCEALED FROM PUBLIC VIEW. EXPOSED WIRING 10 SHALL NOT BE RUN IN A "SPAN" FASHION BETWEEN BAR JOISTS OR GIRDERS. IF NECESSARY SUCH WIRING SHALL BE SECURED TO THE STRUCTURAL CEILING BETWEEN JOISTS OR GIRDERS. 11 EXPOSED WIRING TO BE SUPPORTED BY BUILDING STRUCTURE AT NO MORE THAN FIVE (5) FOOT INTERVALS. 12 ALL WIRING IN FINISHED AREAS SHALL BE CONCEALED. 13 ALL JUNCTION BOXES AND CABLE SPLICES SHALL BE IN ACCESSIBLE LOCATIONS. 14 ALL CABLE RUNS SHALL BE NEATLY BUNDLED, WRAPPED TIGHT AND PROPERLY SECURED. 15 CONTRACTOR RUNNING WIRE MUST MARK BOTH ENDS OF WIRE AND PROVIDE A WIRE LEGEND FOR ALL LOCATIONS. 16 ALL CABLING SHALL BE TAGGED AT ALL JUNCTION POINTS AND SHALL TEST FREE FROM GROUNDS OR CROSSES BETWEEN CONDUCTORS. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. PROVIDE A MULTI -SYNC MODE SLAVE CONNECTION BETWEEN ALL 17 SYNC MODULES. PROVIDE INDEPENDENT CONTROL OF THE VISUAL AND AUDIBLE SIGNALS. 18 IF REQUIRED BY THE AHJ, PROVIDE SILENCING OF AUDIBLE DEVICES WHILE THE VISUAL DEVICES CONTINUE TO OPERATE. 19 ALL SURFACE -MOUNTED NOTIFICATION APPLIANCES SHALL BE INSTALLED WITH DECORATIVE BACKBOX OR DECORATIVE SKIRT COVERING THE RACO OR OTHER INDUSTRY -STANDARD BACKBOX. 20 ALL CEILING -MOUNTED NOTIFICATION APPLIANCES TO BE INSTALLED ON THE BOTTOMS OF BEAMS OR JOISTS. STROBES SHALL BE VISIBLY UNOBSTRUCTED. CEILING MOUNTED NOTIFICATION APPLIANCE LOCATIONS SHALL BE COORDINATED WITH THE MECHANICAL DUCTWORK TO AVOID VISUAL OBSTRUCTION. NOTIFICATION APPLIANCES THAT ARE VISIBLY OBSTRUCTED BY MECHANICAL DUCTWORK SHALL BE INSTALLED ON A THREADED 21 SUPPORT SUSPENDED BELOW THE BUILDING STRUCTURE AND SHALL BE AT AN ELEVATION TO PROVIDE UNOBSTRUCTED VISUAL NOTIFICATION BELOW THE MECHANICAL DUCT. 22 COORDINATE EXACT PLACEMENT OF ALL DEVICES WITH THE ARCHITECTURAL PLANS, OWNER, AND GENERAL CONTRACTOR PRIOR TO INSTALLATION. SMOKE DETECTORS SHALL BE MOUNTED ON CEILINGS AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE SMOKE DETECTORS A MINIMUM OF 23 THREE (3) FEET FROM MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. 24 SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. 25 PROVIDE CONNECTIONS TO WATER FLOW SWITCHES, SUPERVISORY VALVE TAMPER SWITCHES (SWITCHES PROVIDED BY OTHERS). PROVIDE CABLING AND WIRING CONNECTIONS TO ALL SWITCHES. PROVIDE COORDINATION WITH THE SPRINKLER CONTRACTOR. PROVIDE DEDICATED 120VAC POWER TO FACP AND AUXILIARY POWER SUPPLIES. POWER SHALL BE PROVIDED BY AND COORDINATED WITH THE 26 ELECTRICAL CONTRACTOR. CONDUCTORS MUST BE INSTALLED IN EMT CONDUIT. LABEL THE DEDICATED CIRCUIT BREAKER(S) "FIRE ALARM CIRCUIT." 27 ALL REMOTE BOOSTER POWER SUPPLIES CONNECTED TO A DEDICATED CIRCUIT BREAKER(S) SHALL BE LABELED AND TESTED IN THE OFF POSITION AS PART OF THE 24-HOUR BATTERY TEST PERFORMED. 2g PROVIDE LOCKOUT TAG(S) FOR ALL CIRCUIT BREAKERS FOR THE FIRE ALARM SYSTEM(S). 29 MOUNT THE FIRE ALARM CONTROL PANEL AND AUXILIARY POWER SUPPLIES. COORDINATE EXACT LOCATION WITH THE OWNER PRIOR TO INSTALLATION. THE DIGITAL ALARM COMMUNICATION TRANSMITTERS (DACT) SHALL CLEARLY IDENTIFY THE TRANSMITTED SIGNAL AS 'WATER FLOW", "GENERAL 30 ALARM", AND "SUPERVISORY" OR 'TROUBLE" AS A MINIMUM. 31 HOLES IN WALLS OR FLOOR CUTS MADE DURING THE PERFORMANCE OF THIS WORK SHALL BE PATCHED SO AS TO COMPLETELY CONCEAL THE HOLES AND CUTS WHERE THEY WOULD OTHERWISE BE EXPOSED TO VIEW. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING 32 OF THE ENTIRE SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE ALARM SYSTEM INSPECTION. 33 COORDINATE THE MONITORING OBLIGATION OF THE FIRE ALARM SYSTEM WITH THE LANDLORD AND APPLICABLE CODES. 34 IN NO CASE SHALL THE CONDUCTORS WITHIN METALLIC RACEWAY EXCEED 40% FILL. IN SUCH SITUATIONS LARGER SERIES WIRE MOLD OR OTHER CONDUIT SHALL BE USED. 35 ALL WORK WILL FOLLOW CURRENT NEC STANDARDS FOR CONDUIT, GROUNDING, INSTALLATION OF WIRING AND WIRE TYPES. 61G15 NOTES 61015-32.008 DESIGN OF FIRE ALARM SYSTEM (1) Fire alarms and detection systems include fire protection supervision, emergency alarm circuits, activation of life safety system controls and remote signaling of emergency conditions. Items to be considered in the design or analysis of fire alarm and detection systems are, as applicable to the particular project: occupancy and classification, monitoring, control and communication, cabling and supervision requirements, installation requirements, interoperability and performance requirements. (2) The design specifications shall be based on the Florida Building Code, the Florida Fire Prevention Code, or as required by the local authority having jurisdiction. The Florida Building Code and the Florida Fire Prevention Code are incorporated by reference in rule 61G15-18.011, F.A.C. (3) For systems below the threshold requirements for mandatory use of professional engineering services, the Engineer of Record may specify the minimum system requirements only. (4) To ensure minimum design quality of Fire Alarm and Detection Systems Engineering Documents, said documents shall include as a minimum the following information when applicable: INCLUDED N/A (a) The documents shall be clear, with a symbols legend, system riser diagram showing all initiation and notification components, and cabling requirements. The documents shall indicate locations where fire ratings are required as determined by the system's survivability requirements, and shall identify the general occupancy of the protected property and each room and area unless it is clear from features shown. INCLUDED Ll N/A (b) Locate initiation and notification devices and connections to related systems on the floor plans and sections when needed for clarity. Related systems include elevator controls, smoke control systems, dampers, door release, any other systems or elements directly or indirectly controlled or monitored. INCLUDED N/A (c) Strobe intensity and speaker output ratings for all notification devices. INCLUDED N/A (d) Identify the Class of circuits as listed In NFPA 72, which is contained within and incorporated Into the Florida Fire Prevention Code. INCLUDED N/A I (a) Identify the functions required by the alarm and control systems including the transmission of emergency signals being monitored or annunciated. INCLUDED N/A (f) Indicate whether the fire alarm is conventional or addressable, and indicate all zoning. INCLUDED N/A (g) Locate surge protective devices and required protective features. INCLUDED N/A (h) Identify and locate system devices that are subject to environmental factors, and indicate requirements for the protection of equipment from temperature, humidity or corrosive atmospheres, including coastal salt air. INCLUDED 171 N/A (F) The documents shall include a site plan of the immediate area around the protected building, structure or equipment when alarm devices are required outside the structure. INCLUDED N/A 0) In buildings where smoke detection will be obstructed by walls, beams or ceiling features, the Engineer of Record shall provide applicable design and details to directthe installer to mitigate the obstructions. In buildings with smoke detection under a pitched roof, the plans shall indicate the roof pitch and a building section shall be provided as part of the Engineering Design Documents. INCLUDED N/A (k) For fire detection systems utilizing smoke detection In situations where smoke stratification is anticipated, the design shall provide the necessary criteria to mitigate the detection problems. INCLUDED LJ N/A (1) Systems designed using Performance Based criteria shall be Identified and referenced to design guides or standards approved by the local authority having jurisdiction consistent with standards adopted by the Florida Fire Prevention Code and the Florida Building Code. INCLUDED N/A (m) The system design must indicate if the system is to provide a general evacuation signal or a zoned evacuation for all high-rise buildings or multi -tenanted properties as defined in section 2 of the Florida Building Code, Building. ❑INCLUDED O N/A (n) Wiring requirements for underground, wet locations, campus style wiring, protection against damage and burial depth shall be specified or indicated on the engineering design documents. INCLUDED N/A (o) Requirements for operations and maintenance procedures, manuals, system documentation, and instruction of Owner's operating personnel, as needed to operate the systems as intended over time. INCLUDED N/A (5) In the event that the Engineer of Record elects to specify specific equipment and to show the required wiring, battery and voltage drop (circuit analysis) calculations shall be completed. The calculations shall be completed using the equipment manufacture's data and applicable NFPA 72 procedures. INCLUDED N/A (6) System test requirements shall be noted on the Engineering Design Documents. INCLUDED N/A (7) When the Engineer of Record determines that special requirements are required by the owner, insurance underwriter or local fire code amendments these requirements shall be documented or referenced on the Engineering Design Documents. FIRE ALARM 61 G15 NOTE (4) (A) FIRE ALARM LEGEND ARE LOCATED ON FAIR AND FIRE ALARM RISER ARE LOCATED ON FA1.3. (B) ALL INITIATING DEVICES AND NOTIFICATION APPLIANCES ARE LOCATED ON THE FLOOR PLAN PAGE FA1.4. (C) ALL CANDELA RATINGS HAVE BEEN IDENTIFIED WVH EACH DEVICE TO MEET THE STANDARDS OF CHAPTER 18 NFPA 72. (D) CLASS OF CIRCUITS Will BE CLASS B. (E) THE MATRIX IS SHOWN ON FAI A AND FACILITY IS MONITORED BY SOLE PATH CELLULAR COMMUNICATOR. (F) THE FIRE ALARM SYSTEM WILL BE ADDRESSABLE ON 1 LOOP. (G) (1)120V SURGE SUPPRESSORS WERE ADDED TO THE TRANSPONDER FIRE ALARM PANEL (H) N/A (I) SITE PLAN IS LOCATED ON FAIR. (J) N/A (K) N/A (L) NIA (M) THE FIRE ALARM SYSTEM WILL BE GENERAL ALARM. (N) NIA (0) THE APPLICABLE MANUALS FOR THE FIRE ALARM SYSTEM WILL BE SENT WITH CLOSEOUT DOCUMENTS ON COMPLETION OF THE PROJECT. (6) TESTING PER NFPA 72, 2019 EDITION 7 SYSTEM SURVIVABILITY SCALE 0 Non Sprinkled, No Felocation or partial evacuation 1 5prinkled, No Felocation or partial evacuation 25prinkled, Voice evacuation with partial or designated relocation areas 3 5prinded, Voice evacuation with partial or designated relocation areas 0 5691 7471 GALL BLVD ZEPHYRH I LLS, FL 33541 10 13 14 15 16 FIRE ALARM MATRIX I SEQUENCE OF OPERATION SYSTEM OUTPUTS Z O F= Z Z O ❑ Z O F= O 0 U Z O W Z 0 O U U W Z w Z Z O O F NO Z >_ Z O ¢ 0 J O D I— ¢ Li- W > :) J J W LU .J W Z W I- Z O W a 0 O ¢ Cl) i- m U I Z W J Z I. U) Z H 1= I—W Q t= 0 H Z W ~ Q a C9 J O � Q W O J co w❑❑ ❑ Z 0 F.. ¢¢ (n Z ¢¢ co Z ~ 0¢ (n Z a Z¢ Q) Z 0 Z 0- c� cc O ¢ U J J Z Z O W 1- O W F- Z O 0' 1- - H le F LU 1- J ¢ I- U ❑ Z 0 O Q U) W 1_ 5 m c O 0� C-6 Z .6 � Z U �- oS i f Z 0 Z� 06 Z W ¢ U W O U It> W Z Q ❑ Z O U ❑ J H Z= w (~/) IY 00 U) Z O F_ O Z 0 F- 0 W O 0 F 0 H 0 U 0 F 0 ~Q F- W ¢ > a 2 O O ❑ = ❑ Z p Z (A `-� d Q Q (n ¢ J `-_ (j W H¢ J H LU U) Z o H z F- w J iz U Z F- 0 M U Z F- W� U z� m O z FIX W Z 0 °8 O o w Z U) W ❑ o X O ❑ ❑ t7 ❑ O W ❑ O ❑ C? F- ❑ f- 0 U W U Z Z J J �- Z> > -JJ z Z W Z Z= �' (� Z Z M H¢ Z Z Z LLl LLU F N �� X� W Q > LLLJ F- U F- O 0� ❑ 08 ¢ W O ¢ W O 0 < W O 0 W O w z Z 0 W O IY = cn W J O W F— O Z F O Z O Z O Z❑ F- = I— ❑IU I— H �Q w g z Q m O O O O O < U < Q W �cn0�(n 11 W W I Z o= p F c W �0( W �0��0��ow W� W U F U} Z H UO U F F SYSTEM INPUTS o o Z W > U ¢ ¢ 0 1- ¢ 0 F— <[ 0 F a 0 I - � ¢ �' ¢ J ¢ ¢ CONTROL UNIT FUNCTIONS "ALL SYSTEMS NORMAL" X SYSTEM SILENCE X X SYSTEM RESET ONE POINT FOR RESET X I X ALARM DEVICES WATERFLOW SWITCHES X X X X X X X MANUAL PULL STATIONS X X X X X X SMOKE DETECTORS X X X X_[___ X X KITCHENHOOD SYSTEM X X X X X X SUPERVISORY DEVICES TAMPER SWITCHES X X X DUCT SMOKE DETECTORSI I X X X X TROUBLE FUNCTIONS LOSS OF DIAL TONE OR CELL DIALER CONECTION X X X FIRE ALARM SYSTEM AC POWER FAILURE X X X FIRE ALARM SYSTEM LOW BATTERY X X X ABNORMAL CIRCUIT OR DEVICE X X X 11 12 SHEET INDEX SHEET DESCRIPTION FA1.1 FIRE ALARM COVER PAGE FA1.2 FIRE ALARM GENERAL INFORMATION FA1.3 FIRE ALARM RISER DIAGRAM AND CALCULATIONS FA1.4.1 FIRE ALARM INITIATING DEVICE PLACEMENT PLAN FA1.4.2 FIRE ALARM NOTIFICATION APPLIANCE PLACEMENT PLAN 13 14 17 01Ty CW NPWPMIU.S F1114 MD LIFE SAFETY EXAMINF.R� �3 MULTILEADERS TYPE DESCRIPTION CABLE MULTILEADER REVISION MULTILEADER XX CALLOUT MULTILEADER: XX DETAIL/SHEET NUMBER XXX -XX-XXX DEVICE MULTILEADER: SYSTEM-FLOOR/LEVEL-DEVICE NUMBERS DOOR/DETAIL NUMBERS �(--X TAGS TYPE DESCRIPTION 0 CABLE ID TAG CABLE TAG CABLE TAG DEVICE TAG: SYSTEM TYPE/FLOOR-LEVEL/DEVICE NUMBER SHEET NUMBER/DETAIL XXX-XX-XXXXX-XXX X OSHEET NOTE TAG IDENTIFIERS TYPE DESCRIPTION ELEVATION IDENTIFIER XX DETAIL/SHEET NUMBER X SECTION IDENTIFIER: DETAIL/SHEET NUMBER INITIATING DEVICE ADDRESSING LEGEND DEVICE ADDRESS L1 ' ID-0011 ADDRESSABLE DETECTOR NUMBERING DEVICE DESIGNATOR r (D=DETECTOR, M--MODULE) ADDRESSABLE LOOP L1 •M-001 ADDRESSABLE MODULE NUMBERING L1 : P-001 ADDRESSABLE POINT NUMBERING NOTIFICATION DEVICE ADDRESSING LEGEND CIRCUIT DESIGNATOR FIRE ALARM PANEL NAC DEVICE DESIGNATOR FACP:1-1 HORN / STROBE, HORN ONLY, STROBE ONLY DEVICE NUMBERING W RCUIT DESIGNATOR NAC BOOSTER POWER SUPPLY DEVICE DESIGNATOR # = Booster Panel Number NAC #:1-1 HORN / STROBE, HORN ONLY, STROBE ONLY DEVICE NUMBERING 7yT1 C-�a� bltz�l �® > C CTIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 -- RAYTOWN, MISSOURI 64133 (816) 358-1790 ® TAT °",® f•i� . � NCO I� I6�;'. •ei*���`` .�. ENGINEERING FLORIDA COA #4630 Ol1 N s V�(✓ y b b _ 15 16 17 18 Z _ >;i Q G1 U) cM iillil LO LLI Q F 0 M_ i) OW J Of W wo J O SC)LL o d a 00 W.o ` U >a a-Z oLIU J W— N M W _ QZ �F-U t - U nn -ZN LO vu Uv F- Q V �m a_c30 v� 3 m Z • O Issue Date: 02.05.24 REVISION INFORMATION Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhllls FL 33541 AUTHORIZED FOR: PERMIT/BID ZEPHRYHILLS FL Drawing FIRE ALARM COVER PAGE FA1.1 NI LI KI HI GI FI EI DI BI AI 1 2 1 2 3 FIRE ALARM SYMBOLS 4 5 QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL * FACP FIRE ALARM CONTROL PANEL « * ® POWER PANEL k * NAC NAC CIRCUIT POWER BOOSTER EXTENDER PANEL * BATT BATTERY BOX « * AMP AMPLIFIER PANEL « * EVAC VOICE EVACUATION PANEL * EVAC # REMOTE LOCATED EVACUATION AMPLIFIER CABINET * MIC REMOTE MICROPHONE FOR VOICE EVACUATION SYSTEM * ASCP AIR SAMPLING CONTROL PANEL * DGP DATA GATHERING PANEL * FATC FIRE ALARM TERMINAL CABINET * FCS FIRE COMMAND SYSTEM * FSCP FIRE SYSTEM CONTROL PANEL * RP RELAY PANEL « * * PP PURGE PANEL * HVAC HVAC CONTROL PANEL * FSCP FIRE SUPPRESSION CONTROL UNIT * FACU D FIRE ALARM CONTROL UNIT - DEDICATED * FACI FIRE ALARM CONTROL INTERFACE * ARCM AREA OF REFUGE EMERGENCY COMM. SYSTEM - MASTER UNIT « * ARCR AREA OF REFUGE EMERGENCY COMM. SYSTEM - REMOTE UNIT * WCU WIRELESS CONTROL UNIT * « * DACR DIGITAL ALARM COMMUNICATOR RECEIVER * DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER « * FAC FIRE ALARM COMMUNICATOR * FFI FIRE FIGHTER INTERFACE 01 FAA FIRE ALARM ANNUNCIATOR * k * LED LCD ANNUNCIATOR/DISPLAY « * GAP GRAPHIC ANNUNCIATOR PANEL * TRP FIRE ALARM TRANSPONDER * k * FPC FIRE PUMP CONTROLLER * KHSS KITCHEN HOOD SYSTEM * ESR ELEVATOR STATUS/RECALL 01 DOC FIRE ALARM DOCUMENT BOX « * PRN PRINTER * * UPS UNINTERRUPTIBLE POWER SUPPLY * SS SURGE SUPPRESSOR * TP TRANSIENT PROTECTION * ROTATING BEACON * RB RADIO BOX « k * * ADC DIRECT CONNECT * DH DOOR HOLDER * DCL DOOR CLOSER k « * JB JUNCTION BOX « * PB PULL BOX k k * TB TERMINAL BOX * KB KNOX BOX * © FIREMEN'S PHONE « * J FIREMEN'S PHONE - JACK * © H FIREMEN'S PHONE - HANDSET * « * FM FIREMEN'S MICROPHONE * 00, RI INDICATOR - REMOTE - WALL MOUNTED « « * X RI INDICATOR - REMOTE - CEILING MOUNTED k « * A D ABORT SWITCH * AR ABORT SWITCH - AEROSOL RELEASE * CA ABORT SWITCH - CLEAN AGENT « * DL ABORT SWITCH - DELUGE FIRE SPRINKLER k * DC ABORT SWITCH -DRY CHEMICAL * FO ABORT SWITCH - FOAM « * HL ABORT SWITCH - HALON * ED ABORT SWITCH - MANUAL RELEASE ABORT SWITCH - PREACTION * « * ABORT SWITCH - WATER MIST * * WC ABORT SWITCH - WET CHEMICAL 01 4 A 0 7 FIRE ALARM SYMBOLS N 17 10 QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL * F FIRE ALARM PULLSTATION * S SMOKE DETECTOR k * 5 P SMOKE DETECTOR - PHOTOELECTRIC * S E SMOKE DETECTOR - IONIZATION * S BT SMOKE DETECTOR - BEAM TRANSMITTER * S BR SMOKE DETECTOR - BEAM RECEIVER * S AS SMOKE DETECTOR - AIR SAMPLING * S ID SMOKE DETECTOR - IN DUCT * S R SMOKE DETECTOR - RELAY BASE * S SB SMOKE DETECTOR -SOUNDER BASE « * S SMOKE DETECTOR - DUCT * RTS REMOTE ALARM INDICATING AND TEST SWITCH * HEAT DETECTOR k * R/F HEAT DETECTOR - COMBINATION: RATE OF RISE/FIXED \pj* R/C HEAT DETECTOR - RATE OF COMPENSATION * F HEAT DETECTOR - FIXED TEMPERATURE * R HEAT DETECTOR - RATE OF RISE ONLY * GAS DETECTOR * CO CARBON MONOXIDE DETECTOR * APS COZ CARBON DIOXIDE DETECTOR * HCL HYDROGEN CHLORIDE DETECTOR *fjCH. AM METHANE DETECTOR * FLAME DETECTOR * UV/IR FLAME DETECTOR - COMBINATION OF ULTRAVIOLET/INFRARED * IR FLAME DETECTOR - INFRARED * UV FLAME DETECTOR - ULTRAVIOLET * VR FLAME DETECTOR - VISIBLE RADIATION * S SMOKE/HEAT DETECTOR * S CO SMOKE/CO DETECTOR k * CO (DO HEAT/CO DETECTOR * S CO SMOKE/HEAT/CARBON MONOXIDE DETECTOR * WF FLOW DETECTOR/SWITCH VS VALVE SUPERVISORY (TAMPER) SWITCH * HT HIGH TEMPERATURE SWITCH * LT LOW TEMPERATURE SWITCH * LD LEVEL DETECTOR/SWITCH * PD PRESSURE DETECTOR/SWITCH W WATER DETECTOR * AS FULLY SPRINKLERED SPACE * PARTIALLY SPRINKLERED SPACE * NS NOWSPRINKLERED SPACE k * VS VALVE WITH INTEGRATED SUPERVISORY (TAMPER) SWITCH * CHECK VALVE - GENERAL * RISER * BACKFLOW PREVENTER - DOUBLE CHECK * FREE STANDING SIAMESE FIRE DEPARTMENT CONNECTION * PUBLIC HYDRANT - TWO HOSE OUTLETS * VALVE- GENERAL * * VALVE - IN PIT * POST -INDICATOR VALVE * db KEY OPERATED VALVE * OS 8 Y VALVE * INDICATING BUTTERFLY VALVE * S DAMPER -FIRE * DAMPER -FIRE -SMOKE * M s DAMPER -MOTORIZED -FIRE -SMOKE * S DAMPER -SMOKE 7 01 10 11 FIRE ALARM SYMBOLS 12 13 14 15 QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL 01 AiM ADDRESSABLE INPUT MODULE * 0 ADDRESSABLE OUTPUT MODULE * LO ADDRESSABLE INPUT/OUTPUT MODULE * IM ISOLATION MODULE * SIM SIM MODULE k * AM PAM MODULE * K FA REMOTE RELAY - FORM C - DRY CONTACT RELAY MODULE * R ER ELEVATOR RECALL RELAY FIRE ALARM SYMBOLS QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL * EOL END OF LINE * FEOLj RE END OF LINE - RESISTOR * EOL RL END OF LINE - RELAY * STROBE - WALL MOUNTED * ^ C STROBE - CEILING MOUNTED * SPEAKER/STROBE - WALL MOUNTED * �C SPEAKER/STROBE - CEILING MOUNTED * SPEAKER - WALL MOUNTED * �C SPEAKER - CEILING MOUNTED * N S N SPEAKER CLUSTER * WP [01 HORN/STROBE - WALL MOUNTED * miC HORN/STROBE - CEILING MOUNTED k * F H HORN - WALL MOUNTED * Uv � HORN CEILING MOUNTED * DIM MINIHORN WALL MOUNTED * DC MINIHORN CEILING MOUNTED * q F KJ H HORN - CLUSTER * ODB BELL - WALL MOUNTED * * ODC CHIME WALL MOUNTED * ODG GONG WALL MOUNTED MASS NOTIFICATION SYMBOLS Q QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL * MNS MASS NOTIFICATION SYSTEM INTERFACE * EOL END OF LINE EOL RE END OF LINE - RESISTOR * EOL RL END OF LINE - RELAY * MNS STROBE - WALL MOUNTED * C MNS STROBE - CEILING MOUNTED * MNS - SPEAKER/STROBE - WALL MOUNTED * C MNS - SPEAKER/STROBE - CEILING MOUNTED * MNS - SPEAKER - WALL MOUNTED * C- MNS - SPEAKER - CEILING MOUNTED * M N MNS - SPEAKER CLUSTER * MNS - HORN/STROBE - WALL MOUNTED * Bic MNS - HORN/STROBE - CEILING MOUNTED * E11H MNS - HORN - WALL MOUNTED * Ic MNS - HORN - CEILING MOUNTED * q M �H MNS - SPEAKER CLUSTER * El MNS - FIRE ALARM PULLSTATION 1 11 12 13 14 16 17 ABBREVIATIONS SYMB DESCRIPTION AC ALTERNATING CURRENT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AMP AMPERE AUX AUXILIARY AWG AMERICAN WIRE GAUGE BFG BELOW FINISH GRADE BLDG BUILDING C CM CEILING MOUNTED CIRC CIRCUIT CL CENTER LINE C CHIME COND CONDUIT CO COMPANY DC DIRECT CURRENT DIA DIAMETER DN DOWN DWG DRAWING ° DEG DEGREE ELEC ELECTRICAL EA EACH EXT EXTERIOR EX EXISTING DEVICE EQUIP EQUIPMENT EC ELECTRICAL CONTRACTOR XP EXPLOSION PROOF FA FIRE ALARM FL FLOOR FT FEET GC GENERAL CONTRACTOR GND GROUND HW HARDWIRED H HIGH AUDIBLE SETTING ID IDENIFICATION IN INCHES KW KILOWATT LVL LEVEL L LOW AUDIBLE SETTING MAX MAXIMUM MIN MINIMUM MFR MANUFACTURER MNS MASS NOTIFICATION SYSTEM MTD MOUNTED N4 NEMA 4 - NON CORROSION -PROOF ENCLOSURE N4X NEMA 4 - CORROSION -PROOF ENCLOSURE N12 NEMA 12 - SEALED ENCLOSURE ND NEW DEVICE NAC NOTIFICATION APPLIANCE CIRCUIT # NUMBER PNL PANEL PH 0 PHASE PS POWER SUPPLY QTY QUANITITY REQ'D REQUIRED SEC SECONDARY SLC SIGNAL LINE CIRCUIT TEMP TEMPERATURE TYP TYPICAL UPS UNINTERRUPTED POWER SUPPLY V VOLTAGE VAC VOLTAGE ALTERNATING CURRENT VDC VOLTAGE DIRECT CURRENT W WM WALL MOUNTED W WATTS WP WEATHERPROOF WG WIRE GUARD WD WIRELESS DEVICE W/ WITH 18 GIBBENS DRAKE SCOTT, INC its 6, 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 (816) 358-1790 0 ". QRI ENGINEERING FLORIDA COA #4630 % � 1 f-7-,Zq 15 16 17 18 I I M O Q M 2 LU L J i V Wo C)a O O LL U LU g'SZ m W L U in —Zc� `v�Uv - C p N U Q�mm �30 Vi 3 a� z 6 �911 O O Issue Date: 02.05.24 REVISION INFORMATION Restaurant #: 5691 LONGHORN LH9.3 HK Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM GENERAL INFORMATION FA1.2 NI MI LI KI HI GI FI EI DI CI BI AI 1 2 3 4 5 0 7 CIRCUIT LOAD & VOLTAGE DROP CALCULATIONS Device Description STANDBY: Source: Amps FACP Circuit Number: C1 C2 C3 C4 SCWL CEILING MOUNT STROBE WHITE (30 cd) 0.00000 0.06300 0 0 2 0.126 SPARE.... 0 0 SCWL CEILING MOUNT STROBE WHITE (75 cd} 0.00000 0.11100 1 0.111 0 0 0 0 PC2WL ..--- PC2WL CEILING MOUNT HORN STROBE WHITE (30 cd) . CEILING MOUNT HORN STROBE WHITE (75 cd) 0.00000 .._..__. 0.00000 0.09000 0.14300 0 0 2 ___._._ 3 0.429 2 0.18 -.... 0.286 0 ..... ... --- ..... 0 0 _ ._._...._. 0 PC2WL CEILING MOUNT HORN STROBE WHITE (115 cd) 0.000001 0.187001 3 0.561 0 0 0 0 P2RK IWALL MOUNT HORN STROBE, OUTDOOR (110 cd) 0.000001 0.212001 0 0 0 0 1 0.212 # Devices Circuit Amps Circuit Length (ft) Total Voltage Drop (14aRg) Total EOL VoFta a 14 aR 7 1.101 6 0.592 0 0 1 0,212 1.101i 0.592 0.000 0.212 250 200y 1.76 0.76 18.64 19.64� y,,, „ 0 100 % 0 20.40 20.26 - NOTE: VOLTAGE FORMULA USED IS: VD = LENGTH (CIRCUIT MEASURED ONE-WAY IN FT.) X LOAD (IN AMPERES) X RESISTANCE (.00316 FOR 14AWG) X 2 (FOR RETURN RESISTANCE) WIRE RESISTANCE VALUES REFERENCED FROM NEC TABLE 8 HWF2V-COM BATTERY CALCULATIONS Total Total Qty Part # Description Standby Alarm Standby Alarm 1 HWF2V-COM Cell Dialer 0.23000 0.95000 0.2300 0.9500 02300 0.9500 Standby Current Total Hours = 0.2300 X 24 - 5,5200 (Hours) Alarm Current Total Minutes = 0.9500 X .083 = 0.0789 (5 Mins) Total = 5.5989 20% Battery Safety Margin = 1.1198 Total AH Rated Batteries Needed = 6.7186 Total AH Rated Batteries Supplied 7 75 75 0 /30 EOL RE O O O / C 75 75 75 115 115 0 0 0 0 RE C C C C C 110 SPARE I EOL RE C Ci1 115 A DEDICATED 120 VAC 20 AMP CIRCUIT(LOCKED) (BY OTHERS) CIR4 14 AWG 2 COND FPLP CIR3 14 AWG 2 COND FPLP CIR2 14 AWG 2 COND FPLP CIR1 14 AWG 2 COND FPLP C1 C2 C3 C4 A I55 FIRE LITE ES-20OX FACP SPI BATTERY BATTERY 12V 12AH 12V 12A SSU00672 SYSTEM DOCUMENTATION AS -BUILT DRAWINGS SLC LOOP 0 10 11 12 FACP BATTERY CALCULATIONS Qty Part# Description Standby Alarm Total Standby Total Alarm 1 ES-20OX Fire Alarm Panel 0.14100 0.25700 0.1410 0.2570 1 PWRMOD24 Optional 24volt 3 Amp Transformer (inside the panel) 0.00700 0.00800 0.0070 0.0080 1 IPOTS-COM POTS communicator (inside the panel) 0.04000 0.04100 0.0400 0.0410 1 ANN-80 Remote Annunciator 0.01500 0-04000 0.0150 0.0400 1 SD365 Photoelectric Smoke Detector 0.00020 0.00450 0.0002 0.0045 3 .----... 1 BG-12LX ---- _ MMF-300 Manual Pull Station _._.__._---_..._ .__._..._ Monitor Module with LED (Full Size) 0.00038 0.00038 0.00500 0.00500 0.0011 ----.._ __._.... 0.0004 0.0150 - . _._.. ..... 0.0050 1 MDF-300 Dual Monitor Module 0.00075 0:00640 0.0008 0.0064 6 CRF-300 Relay Control Module 0.00023 0.00650 0.0014 0.0390 3 3 D365PL RTS-151 KEY Intelligent Duct Photo Smoke Detector Remote Test Station 0.00030 0.01200 0.00650 0.10500 0.0009 0,0360 0.0195 0.3150 2 SCWL CEILING MOUNT STROBE WHITE (30 cd) 0.00000 0.06300 0.0000 0.1260 1 SCWL CEILING MOUNT STROBE WHITE (75 cd) 0.00000 0.11100 0,0000 0.1110 2 PC2WL CEILING MOUNT HORN STROBE WHITE (30 cd) 0.00000 0.09000 0.0000 0.1800 5 PC2WL CEILING MOUNT HORN STROBE WHITE (75 cd) 0.00000 0.14300 0.0000 0.7150 3 PC2WL CEILING MOUNT HORN STROBE WHITE (115 cd) 1 0.00000 0.18700 0.0000 0.5610 1 P2RK (110) WALL MOUNT HORN STROBE, OUTDOOR (110 cd) 0.00000 0.21200 0.0000 0.2120 0.2437 2.6554 Standby Current Total Hours = Alarm Current Total Minutes = Total 20% Battery Safety Margin Total AH Rated Batteries Needed Total AH Rated Batteries Supplied 0.2437 2.6554 X 24 (Hours) X .083 (5 Mins) = = = = = 5.8495 0.2204 6.0699 1.2140 7.2839 12 18 AWG -FAA = 4 COND FPLP MCBL-7 MCBL-7 DEDICATED 120 Vi 20 AMP CIRCUIT(LOCRLIJ) (BY OTHERS) RISER DIAGRAM NOTE DEVICE WIRING SHOWN IS CONCEPTUAL. POINT TO POINT CONNECTIONS MAY VARY. REFER TO FLOOR PLANS FOR REQUIRED EQUIPMENT LOCATIONS. THE ELECTRICAL CONTRACTOR SHALL REFERENCE EQUIPMENT INSTALLATION DOCUMENTS, DRAWING TERMINATION DETAILS, AND RISER DIAGRAM FOR COMPLETE EQUIPMENT INSTALLATION. SHOULD ANY CONFLICT ARISE BETWEEN DESIGNED PLANS, BATTERY CALCULATIONS, VOLTAGE DROPS, AND ACTUAL INSTALLATION SHALL BE BROUGHT TO THE ATTENTION OF JCI IN WRITING UPON DISCOVERY AND PRIOR TO ELECTRICAL ROUGH. A RISER DIAGRAM Et CALCULATIONS SCALE: 3/16" =1'-0" v 1 2 3 4 5 6 7 8 9 10 13 14 15 16 WIRE CHART CIRCUIT >MINIMUM SIZE< SYMBOL TYPE CIRCUIT DESCRIPTION AND TYPE OF WIRE SIGNALING LINE CIRCUIT A SLC (POWER LIMITED) 2418AWG ANNUNCIATOR DATA BUS AD ANN (BLK/RD =DATA) 4418AWG (WHT/GRN = PWR) INITIATING DEVICE CIRCUIT D IDC (NON -INTELLIGENT DEVICES) 2418AWG NOTIFICATION APPLIANCE TRIP CKT. C TRIP (COMBINED HORN Et VISUAL CIRCUIT) 2-#14AWG RT TEST REMOTE TEST STATION TEST 4418AWG SH = SHEILDED *WIRE MUST BE SHIELDED AS INDICATED TW = TWISTED GENERALNOTE 1) ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2) WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3) DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED 4) ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 5) WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4" 6) ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. 7) OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. 8) THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. M04 M05 D02 M06 M07 D03 M08 M0 i 1 F AIM s 0 F S 0 0 I T RT I V HVAKHSS HVA !j L: RTSSHUTO RTS OSUDO L: EOL _�j _j RE 11 ® TU r OAU M12 Mil D04 M10 I F 0 S 0 TIC V C HVAC SHUTDOWN RT5 S UTDOWN j T_ U. L. LISTED CENTRAL STATION JOHNSON CONTROLS 14200 E EXPOSITION BLVD. AURORA, CO 80012 PHONE 1-800-428-7124 HWF2V-COM BASIC SYSTEM FUNCTIONAL OPERATION HWF2V-COM BASIC SYSTEM FUNCTIONAL OPERATION WHEN A FIRE ALARM CONDITION (ALARM, SUPERVISORY OR TROUBLE) IS DETECTED, THE FIRE ALARM CONTROL PANEL GOES OFF -HOOK TO DIAL THE CENTRAL STATION. THE HWF2V-COM DIALER CAPTURE MODULE DETECTS THE OFF -HOOK CONDITION AND PROVIDES THE FIRE PANEL WITH A DIAL TONE WHEN THE FIRE PANEL DETECTS THE DIAL TONE, IT BEGINS DIALING THE CENTRAL STATION. AFTER THE DIALING IS COMPLETED, THE DIALER CAPTURE MODULE RETURNS A SIGNAL TO THE FIRE PANEL. THE FIRE PANEL THEN SENDS THE CONTACT ID REPORTS TO THE DIALER CAPTURE MODULE, WHICH IN TURN SENDS A SIGNAL AFTER THE REPORT IS SUCCESSFULLY RECEIVED FROM THE FIRE PANEL. THE DIALER CAPTURE MODULE SENDS THE CONTACT ID REPORTS TO THE HWF2V-COM SERIES COMMUNICATIONS MODULE. WHEN ALL THE REPORTS ARE SENT, THE FIRE PANEL GOES ON -HOOK. THE HWF2V-COM SERIES COMMUNICATIONS MODULE THEN TRANSMITS THE MESSAGES TO THE CENTRAL STATION (EITHER OVER THE LTE NETWORK OR THE INTERNET). 12 13 BATTBN BACKUP EMERGENCY.UGHT RESCUE COMMUNICATIONS PRESS CALL AREA OF RESCUE MAIN ANNUNCIATOR 48" A.F.F. 14 17 NFPA 72 AND ADA DEVICE INSTALLATION REQUIREMENTS m -CONDUIT INSTALL PER NATIONAL ELECTRIC CODE MOUNT ON A APPROVED BOX MOUNT AUDIBLE & VISUAL DEVICES ON APPROVED BOXES. AIR SUPPLY DIFFUSER OR SMOKE/ HEAT RETURN AIR OPENING DETECTOR 17 0'-4' MINIMUM 3'-0* MINIMUM 0'-6' MINIMUM 0'-4" MINIMUM, HORN/ STROBE I - GRAPHIC ANNUNCIATOR CONTROL SMOKE/ H -HORN EAT DETECTOR PANEL BE FIREMAN'S HANDSET A F 96' MAXIMUM TOP OF DEVICE RE MANUAL PULL STATION BO' MINIMUM ❑ - BOTTOM OF DEVICE 1 HINGED SIDE 5'-0" MAXIMUM TCALL 5'-6- AREA OF RESCUE STATION 3'-8" S-8" 48" A.F.F. (3'-6" MINIMUM, 5'-6" MAXIMUM) (3'-6" MINIMUM, 4'-O" MAXIMUM) FINISHED ) FLOOR r / / / / / / / / / / Z-1 7 7 7-7- B MOUNTING HEIGHT REQUIREMENTS SCALE: 15 GIBBENS DRAKE SCOTT, WC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 (816) 358-1790 ,0 ENGINEERING FLOR1DA COA #4630 16 17 MAXIMUM CUE COMMUNICATIONS UFr HANDSET PRESS CALL s`1t1111ti,g0 Si63�r•���Nq,��' AL�� '(7�� 18 Q V ! M � LLJ O a F M_ i� 0J W ° U o W J< U M vi O 0 0 0 E a Q Z LL. � WoQ g�Z ' U i- U t3 QZ u�HUv M U 0� N - Z vU) iJv N H Q y U Q •V 3 m r v � 3 z 0 Issue Date: 02.05.24 REVISION INFORMATION Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM RISER DIAGRAM AND CALCULATIONS FA1.3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Luo 17 �11 m"f I LI KI ©I GI FI EI DI DI AI 1 2 3 4 INITIATING DEVICE PLACEMENT PLAN SCALE: 3/16" =1'-0" 5 M. 7 s E 10 11 12 FIRE ALARM SYMBOLS QTY SYMB DESCRIPTION MANUFACTURER MODEL BACKBOX 1 FACP FIRE ALARM CONTROL PANEL FIRELITE ES-20OX OWN 1 FAA FIRE ALARM ANNUNCIATOR FIRELITE ANN-80 ANN-SB80KIT-R 1 FAC FIRE ALARM COMMUNICATOR HONEYWELL HWF2V-COM OWN 1 DOC FIRE ALARM DOCUMENT BOX SPACE AGE SS000672 OWN 1 S SMOKE DETECTOR - PHOTOELECTRIC FIRELITE SD365 4" SQ x 2.5"D p 3 F FIRE ALARM PULLSTATION FIRELITE BG-12LX 1 GANG 1 AIPR ADDRESSABLE INPUT MODULE FIRELITE MMF-300 4" SQ x 2.5"D 1 AGE � DUAL ADDRESSABLE INPUT MODULE FIRELITE MDF-300 4" SQ x 2.5"D 6 o ADDRESSABLE OUTPUT MODULE FIRELITE CRF-300 4" SQ x 2.5"D 3 S SMOKE DETECTOR - DUCT FIRELITE D365PL 3 19 RTS REMOTE ALARM INDICATING AND TEST SWITCH SYSTEM SENSOR RTS151KEY 1 GANG 10ff% HORN/STROBE - CEILING MOUNT SYSTEM SENSOR PC2WL 4" SQ x 2.5"D 1 l� HORN/STROBE - WALL MOUNT - WEATHERPROOF SYSTEM SENSOR P2RK INCLUDED 3 x- C STROBE - CEILING MOUNT SYSTEM SENSOR SCWL 4" SQ x 2.5"D 1 KHSS KITCHEN HOOD SYSTEM EXISTING 1 g3 SURGE PROTECTOR DITEK DTK-120HW 1 S SURGE PROTECTOR DITEK DTK-2LVLPF 1 wF FLOW DETECTOR/SWITCH EXISTING 1 vs VALVE SUPERVISORY (TAMPER) SWITCH EXISTING 1B KNOX BOX EXISTING EOL END OF LINE - RESISTOR RE CIRCUIT CONTINUATION * CEILING NOTE ALL CEILING TILE AREAS ARE SMOOTH FLAT 1T OR LESS. ALL BEAMED CEILING AREAS ARE SLOPED 18' OR LESS. * AUDIBLE DESIGN NOTE: DESIGN IS BASED ON AVERAGE AMBIENT SOUND LEVEL FOR AN "A-2" OCCUPANCY REFER TO NFPA 72 TABLE A.18.4.3 * WALL NOTE: ALL GREY WALLS ARE PARTIAL HEIGHT. GENERAL NOTE 1) ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2) WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3) DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED 4) ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 5) WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4" 6) ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. 7) OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. 8) THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. 13 14 m WIRE CHART CIRCUIT >MINIMUM SIZE< SYMBOL TYPE CIRCUIT DESCRIPTION AND TYPE OF WIRE SIGNALING LINE CIRCUIT A SLC (POWER LIMITED) 2418AWG ANNUNCIATOR DATA BUS AD ANN (BLK/RD =DATA) 4418AWG (WHT/GRN = PWR) INITIATING DEVICE CIRCUIT D IDC (NON -INTELLIGENT DEVICES) 241 8AWG NOTIFICATION APPLIANCE TRIP CKT. C TRIP (COMBINED HORN Et VISUAL CIRCUIT) 2-#14AWG RT TEST REMOTE TEST STATION TEST 4418AWG SH = SHEILDED *WIRE MUST BE SHIELDED AS INDICATED TW = TWISTED FLAG NOTES 10 NEW FIRE ALARM PANEL SHALL BE CONNECTED TO DEDICATED 120 VAC POWER. LABEL CKT BREAKER "FIRE ALARM". OFIRE ALARM PANEL SHALL COMMUNICATE TO MONITORING STATION VIA SOLE PATH CELLULAR COMMUNICATION. OINSTALL RELAY FOR MUSIC SHUT DOWN WITHIN T OF MUSIC SYSTEM. TERMINATIONS FOR AUDIO SHUNT BY OTHERS. 0 MONITOR MODULE FOR SUPERVISION OF EXISTING KITCHEN HOOD. n FIELD VERIFY LOCATION. QDUCT DETECTORS SHALL BE SUPPLIED BY JCI AND INSTALLED BY OTHERS. ADDRESSABLE DUCT CONNECTS TO SLC. CONNECTIONS TO FIRE ALARM PANEL SHALL BE BY JCI. HVAC SHUTDOWN SHALL BE BY OTHERS. FIELD VERIFY LOCATIONS. p ADDRESSABLE RELAY MOUNT INSIDE DUCT DETECTOR HOUSING. O MOUNT REMOTE TEST STATIONS IN MAIN OFFICE NEXT TO FIRE PANEL. 0DUAL MONITOR MODULE FOR SUPERVISION OF SPRINKLER WATERFLOW AND TAMPER SWITCH. QINSTALL EXTERIOR HORN STROBE ABOVE FDC 10' ABOVE FINISHED GRADE. VERIFY LOCATION. 10 INSTALL STI PROTECTIVE COVER OVER MANUAL PULL STATION. 11 KNOX BOX BY OTHERS. GIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 (816) 358-1790 ENGINEERING FLORIDA COA #4630 15 16 17 M Lo O a M 2 J L E w 8 n W 0 0 0 0co LL a gccooz rn , i3 F_ Lo C� It M _ Lo Lo vc4Uv I— a C 7 N Q •� 3 m c-r C1 � 3 m Z • W 9 O Issue Date: 02.05.24 REVISION INFORMATION Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM INITIATING DEVICE PLACEMENT PLAN FA1.4.1 NI LI KI HI GI FI EI DI BI A 1 2 3 4 5 6 7 8 9 10 H 2 3 4 mill - Hill! 11 NOTIFICATION APPLIANCE PLACEMENT PLAN SCALE: 3/16" =1'-0" 5 7 0 10 11 11 12 12 13 14 FIRE ALARM SYMBOLS 15 16 17 QTY SYMB DESCRIPTION MANUFACTURER MODEL BACKBOX 1 FACP FIRE ALARM CONTROL PANEL FIRELITE ES-20OX OWN 1 FAA FIRE ALARM ANNUNCIATOR FIRELITE ANN-80 ANN-SB80KIT-R 1 FAC FIRE ALARM COMMUNICATOR HONEYWELL HWF2V-COM OWN 1 DOC FIRE ALARM DOCUMENT BOX SPACE AGE SS000672 OWN 1 Op SMOKE DETECTOR - PHOTOELECTRIC FIRELITE SD365 4" SQ x 2.5"D 3 F FIRE ALARM PULLSTATION FIRELITE BG-12LX 1 GANG 1 is ADDRESSABLE INPUT MODULE FIRELITE MMF-300 4" SQ x 2.5"D 1 AIM � DUAL ADDRESSABLE INPUT MODULE FIRELITE MDF-300 4" SQ x 2.5"D 6 a ADDRESSABLE OUTPUT MODULE FIRELITE CRF-300 4" SQ x 2.5"D 3 S SMOKE DETECTOR - DUCT FIRELITE D365PL 3 19 RTS REMOTE ALARM INDICATING AND TEST.SWITCH SYSTEM SENSOR RTS151KEY 1 GANG 10 HORN/STROBE - CEILING MOUNT SYSTEM SENSOR PC2WL 4" SQ x 2.5"D 1 HORN/STROBE - WALL MOUNT - WEATHERPROOF SYSTEM SENSOR P2RK INCLUDED 3 X C STROBE - CEILING MOUNT SYSTEM SENSOR SCWL 4" SQ x 2.5"D 1 Kiss KITCHEN HOOD SYSTEM EXISTING 1 SS SURGE PROTECTOR DITEK DTK-120HW 1 gg SURGE PROTECTOR DITEK DTK-2LVLPF 1 wF FLOW DETECTOR/SWITCH EXISTING 1 v5 VALVE SUPERVISORY (TAMPER) SWITCH EXISTING 1 EB KNOX BOX EXISTING EOL END OF LINE - RESISTOR RE CIRCUIT CONTINUATION * CEILING NOTE ALL CEILING TILE AREAS ARE SMOOTH FLAT 12' OR LESS. ALL BEAMED CEILING AREAS ARE SLOPED 18' OR LESS. * AUDIBLE DESIGN NOTE: DESIGN IS BASED ON AVERAGE AMBIENT SOUND LEVEL FOR AN "A-2" OCCUPANCY REFER TO NFPA 72 TABLE A.18.4.3 * WALL NOTE: ALL GREY WALLS ARE PARTIAL HEIGHT. GENERAL NOTE 1) ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2) WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3) DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED 4) ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 5) WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4" 6) ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. 7) OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. 8) THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. 13 14 WIRE CHART CIRCUIT >MINIMUM SIZE< SYMBOL TYPE CIRCUIT DESCRIPTION AND TYPE OF WIRE SIGNALING LINE CIRCUIT A SLC (POWER LIMITED) 2418AWG ANNUNCIATOR DATA BUS AD ANN (BLK/RD =DATA) 4418AWG (WHT/GRN = PWR) INITIATING DEVICE CIRCUIT D IDC (NON -INTELLIGENT DEVICES) 2418AWG NOTIFICATION APPLIANCE TRIP CKT. C TRIP (COMBINED HORN Et VISUAL CIRCUIT) 2-#14AWG RT TEST REMOTE TEST STATION TEST 4418AWG I SH = SHEILDED *WIRE MUST BE SHIELDED AS INDICATED TW = TWISTED I FLAG NOTES 0 NEW FIRE ALARM PANEL SHALL BE CONNECTED TO DEDICATED 120 VAC POWER. LABEL CKT BREAKER "FIRE ALARM". QFIRE ALARM PANEL SHALL COMMUNICATE TO MONITORING STATION VIA SOLE PATH CELLULAR COMMUNICATION. 0 INSTALL RELAY FOR MUSIC SHUT DOWN WITHIN T OF MUSIC SYSTEM. TERMINATIONS FOR AUDIO SHUNT BY OTHERS. QMONITOR MODULE FOR SUPERVISION OF EXISTING KITCHEN HOOD. FIELD VERIFY LOCATION. ODUCT DETECTORS SHALL BE SUPPLIED BY JCI AND INSTALLED BY OTHERS. ADDRESSABLE DUCT CONNECTS TO SLC. CONNECTIONS TO FIRE ALARM PANEL SHALL BE BY JCI. HVAC SHUTDOWN SHALL BE BY OTHERS. FIELD VERIFY LOCATIONS. 0 ADDRESSABLE RELAY MOUNT INSIDE DUCT DETECTOR HOUSING. O MOUNT REMOTE TEST STATIONS IN MAIN OFFICE NEXT TO FIRE PANEL. 0DUAL MONITOR MODULE FOR SUPERVISION OF SPRINKLER WATERFLOW AND TAMPER SWITCH. OINSTALL EXTERIOR HORN STROBE ABOVE FDC 10' ABOVE FINISHED GRADE. VERIFY LOCATION. 0 INSTALL STI PROTECTIVE COVER OVER MANUAL PULL STATION. 11 KNOX BOX BY OTHERS. 1 �3 s GIBBENS DRAKE SCOTT, INC IQ 46 9201 E. 63rd STREET, SUITE 100 = e RAYTOWN, MISSOURI 64133 (816) 358-1790 ENGINEERING FLORIDA COA #4630 0 j� 111" 6-(7/ 5 16 17 18 Q Z V) O W 0 lm: U �k 4 JU 0 >4c 0i M LO O Q M w W $ i 0 Of m 0 0 o o a'i d y LU 2 g CD CD 8 LnHU� M 3: L O U') vt�Ua H Q Q•� 3m cic- 0 U� 3 4) z UU O O lW Issue Date: 02.05.24 REVISION INFORMATION Restaurant #: 5691 LONGHORN LH9.3 HK Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM NOTIFICATION APPLIANCE PLACEMENT PLAN FA1.4.2 r i� LI HI GI F E C �I 1 3 4 SCOPE OF WORK The new system shall include: New addressable fire panel Firelite ES-20OX External cellular communicator at the panel. An addressable smoke detector installed above panel. A remote ANN-80 annunciator shall be installed at the entrance. Installation of notification appliances as shown on plans. New manual putt station shall be installed within T of each exit. An addressable relay shall be installed within 3' of the Muzak system of audio shunt. Terminations to the Muzak system from JCI supplied relay shall be completed by customer's contractor. A dual monitor module shall be installed at the sprinkler riser for supervision of the waterflow / tamper switch. A weather-proof horn strobe shall be installed above the exterior fire department connection (FDC) All wire shall be open -ran or concealed in wall or ceiling. Where wire is below 10', it shall be installed in 3/4' EMT conduit. Fire alarm panel shall communicate to monitoring station via sole path cellular communication. Duct detectors for HVAC shall be provided by JCI, and installed by customers mechanical contractor. Addressable relays are provided for global RTU shutdown. 61 G1 5 NOTES OPERATIONS AND MAINTENANCE E TEST REQUIREMENTS: 1) THE FIRE ALARM SYSTEM IS MANUALLY -ACTIVATED BY PULL STATIONS; AUTOMATICALLY ACTIVATED BY SMOKE DETECTORS, HEAT DETECTORS, AND SPRINKLER FLOW. 2) A CERTIFIED LEVEL 3 OR 4 PERSONNEL WITH ACCESS CODE, CAN TURN ON OR OFF THE FACP BY THE ARM/ON AND DISARM/OFF BUTTONS ON THE FACP. 3) THE SYSTEM INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 72 EL NFPA 70. 4) ACCEPTANCE TESTING INCLUDING RE -ACCEPTANCE TESTING 15 REQUIRED IN COMPLIANCE WITH THE NFPA 72. 5) PERIODIC INSPECTION Et TESTING IS REQUIRED IN COMPLIANCE WITH NFPA 72, CHAPTER 14. 6) OWNERS DOCUMENTS, WHICH INCLUDE OPERATION -INSTRUCTIONS, MAINTENANCE -PROCEDURES, AND ANY INFORMATION TO ASSIST WITH THE UNDERSTANDING OF THE FIRE ALARM SYSTEM, WILL BE PROVIDED WITH THE CLOSE OUT DOCUMENTS AT THE COMPLETION OF THE JOB. SUPPLIED TO CUSTOMER. THE EXISTING FIRE ALARM SYSTEM SHALL NOT BE DISCONNECTED OR TAKEN OUT OF SERVICE WITHOUT WRITTEN PERMISSION FROM THE OWNER. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH THE OWNER THE TIMING OF ANY EXISTING FIRE ALARM SYSTEM DEMOLITION WORK. APPLICABLE CODES STANDARDS Florida Fire Prevention Code, Eighth Edition (2023) Florida Building Code, Eighth Edition (2023) NFPA 1, Fire Code, 2021 Edition International Building Code (IBC), 2021 Edition NFPA 101, Life Safety Code, 2021 Edition NFPA 70, National Electric Code, 2020 Edition NFPA 72, National Fire Alarm and Signaling Code, 2019 Edition Testing per NFPA 72, 2019 Edition BUILDING INFORMATION USE Et OCCUPANCY CLASSIFICATION BUILDING CONSTRUCTION TYPES ASSEMBLY (A) 0 A-1 0 A-2 0 A-3 0 A-4 0 A-5 TYPE 1 0 TYPE I -A 0 TYPE I-B 0 BUSINESS (B) TYPE II 0 TYPE II -A 0 TYPE II-B 0 0 EDUCATIONAL (E) TYPE 111 0 TYPE III -A 0 TYPE 111-13 0 0 FACTORY 8: INDUSTRIAL (F) O F-1 O F-2 TYPE IV 0 TYPE IV-B 0 0 HIGH HAZARD (H) 0 H-1 0 H-2 0 H-3 0 H-4 0 H-5 TYPE V 0 TYPE V-A 0 TYPE V-B 0 0 INSTITUTIONAL (I) 0 1 1 0 1 2 0 1 3 O 14 O 15 AUTOMATIC SPRINKLER PROTECTION 0 MERCANTILE (M) NO 0 1 PARTIAL 0 FULL 0 RESIDENTIAL (R) 0 R-1 0 R-2 0 R-3 0 R-4 BUILDING AREA: 5780 Sq.Ft 0 STORAGE (S) 0 S-1 0 S-2 NUMBER OF FLOORS: 1 0 UTILITY ft MISC. (U) OCCUPANT LOAD: 263 FIRE ALARM CABLE LEGEND ID AWG COND SHIELD CLASS* ID AWG COND SHIELD CLASS* A 18 2 N FPLP B 18 2 Y FPLP C 18 4 N FPLP D 16 2 N FPLP E 16 2 Y FPLP F 16 4 N FPLP G 14 2 N FPLP H 14 4 N FPLP J 12 2 N FPLP K 12 4 N FPLP NOTES DRAWING ACCEPTANCE THIS DRAWING IS TO BE USED ONLY FOR THE PURPOSE OF PLACING AND LOCATING JOHNSON CONTROLS EQUIPMENT AND IS NOT TO BE USED FOR ANY OTHER PURPOSES. IT IS THE RESPONSIBILITY OF THE LOCAL JOHNSON CONTROLS SALES Et SERVICE OFFICE (SSO) TO REVIEW THE CONTENT OF THESE DRAWINGS FOR ACCURACY AND COMPLIANCE WITH LOCAL AND STATE CODES PRIOR TO RELEASING THEM TO THE FIELD. RECORD DRAWINGS ALL WORK PERFORMED IN THE FIELD SHALL BE ACCURATELY RECORDED ON THESE DRAWINGS AND RETURNED TO THE JOHNSON CONTROLS OFFICE AT THE ADDRESS LISTED ABOVE. MONITORING LOCATIONS JOHNSON CONTROLS ALARM SERVICE CO:360682-221 14200 EXPOSITION AVE, SERVICE CENTER NUMBER:768 AURORA, CO. 80012 UL LISTING: S949-183 1-800-428-7124 5 1.1 7 10 11 12 LONGHORN STEAKHOUSE GENERAL NOTES 1 ALL APPLICABLE PERMITS SHALL BE OBTAINED PRIOR TO STARTING WORK. 2 WORK SHALL COMPLY WITH ALL APPLICABLE CODES. 3 POWER (120VAC) TO ALL FIRE ALARM AND SECURITY PANELS SHALL BE SUPPLIED FROM DEDICATED, UNSWITCHED AND CLEARLY IDENTIFIABLE SOURCES. 4 ALL DOORS WHICH ARE CONTROLLED BY ELECTRONIC LOCKING DEVICES SHALL BE CONFIGURED TO MEET ALL CODES. 5 ALL DEVICES EITHER INSTALLED WITHIN THE SCOPE OF THIS PROJECT OR AFFECTED BY THIS PROJECT SHALL BE TESTED. 6 ALL CABLE SHALL BE RATED FOR THE ENVIRONMENT IN WHICH IT IS INSTALLED. 7 ALL WORK SHALL BE PERFORMED IN A PROFESSIONAL MANNER. 8 AREAS AFFECTED BY THE SCOPE OF THIS PROJECT SHALL BE KEPT CLEAN AND TRASH REMOVED DAILY. 9 FIRE ALARM CABLING SHALL NOT BE PAINTED. EXPOSED CONDUCTORS SHALL BE RUN ALONG CEILING JOISTS AND GIRDERS. ALL WIRING TO BE CONCEALED FROM PUBLIC VIEW. EXPOSED WIRING 10 SHALL NOT BE RUN IN A "SPAN" FASHION BETWEEN BAR JOISTS OR GIRDERS. IF NECESSARY SUCH WIRING SHALL BE SECURED TO THE STRUCTURAL CEILING BETWEEN JOISTS OR GIRDERS. 11 EXPOSED WIRING TO BE SUPPORTED BY BUILDING STRUCTURE AT NO MORE THAN FIVE (5) FOOT INTERVALS. 12 ALL WIRING IN FINISHED AREAS SHALL BE CONCEALED. 13 ALL JUNCTION BOXES AND CABLE SPLICES SHALL BE IN ACCESSIBLE LOCATIONS. 14 ALL CABLE RUNS SHALL BE NEATLY BUNDLED, WRAPPED TIGHT AND PROPERLY SECURED. 15 CONTRACTOR RUNNING WIRE MUST MARK BOTH ENDS OF WIRE AND PROVIDE A WIRE LEGEND FOR ALL LOCATIONS. 16 ALL CABLING SHALL BE TAGGED AT ALL JUNCTION POINTS AND SHALL TEST FREE FROM GROUNDS OR CROSSES BETWEEN CONDUCTORS. 17 PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. PROVIDE A MULTI -SYNC MODE SLAVE CONNECTION BETWEEN ALL SYNC MODULES. PROVIDE INDEPENDENT CONTROL OF THE VISUAL AND AUDIBLE SIGNALS. 18 IF REQUIRED BY THE AHJ, PROVIDE SILENCING OF AUDIBLE DEVICES WHILE THE VISUAL DEVICES CONTINUE TO OPERATE. 19 ALL SURFACE -MOUNTED NOTIFICATION APPLIANCES SHALL BE INSTALLED WITH DECORATIVE BACKBOX OR DECORATIVE SKIRT COVERING THE RACO OR OTHER INDUSTRY -STANDARD BACKBOX. 20 ALL CEILING -MOUNTED NOTIFICATION APPLIANCES TO BE INSTALLED ON THE BOTTOMS OF BEAMS OR JOISTS. STROBES SHALL BE VISIBLY UNOBSTRUCTED. CEILING MOUNTED NOTIFICATION APPLIANCE LOCATIONS SHALL BE COORDINATED WITH THE MECHANICAL DUCTWORK TO AVOID VISUAL 21 OBSTRUCTION. NOTIFICATION APPLIANCES THAT ARE VISIBLY OBSTRUCTED BY MECHANICAL DUCTWORK SHALL BE INSTALLED ON A THREADED SUPPORT SUSPENDED BELOW THE BUILDING STRUCTURE AND SHALL BE AT AN ELEVATION TO PROVIDE UNOBSTRUCTED VISUAL NOTIFICATION BELOW THE MECHANICAL DUCT. 22 COORDINATE EXACT PLACEMENT OF ALL DEVICES WITH THE ARCHITECTURAL PLANS, OWNER, AND GENERAL CONTRACTOR PRIOR TO INSTALLATION. SMOKE DETECTORS SHALL BE MOUNTED ON CEILINGS AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE SMOKE DETECTORS A MINIMUM OF 23 THREE (3) FEET FROM MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. 24 SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. 25 PROVIDE CONNECTIONS TO WATER FLOW SWITCHES, SUPERVISORY VALVE TAMPER SWITCHES (SWITCHES PROVIDED BY OTHERS). PROVIDE CABLING AND WIRING CONNECTIONS TO ALL SWITCHES. PROVIDE COORDINATION WITH THE SPRINKLER CONTRACTOR. PROVIDE DEDICATED 120VAC POWER TO FACP AND AUXILIARY POWER SUPPLIES. POWER SHALL BE PROVIDED BY AND COORDINATED WITH THE 26 ELECTRICAL CONTRACTOR. CONDUCTORS MUST BE INSTALLED IN EMT CONDUIT. LABEL THE DEDICATED CIRCUIT BREAKER(S) "FIRE ALARM CIRCUIT." 27 ALL REMOTE BOOSTER POWER SUPPLIES CONNECTED TO A DEDICATED CIRCUIT-BREAKER(S) SHALL BE LABELED AND TESTED IN THE OFF POSITION AS PART OF THE 24-HOUR BATTERY TEST PERFORMED. 28 PROVIDE LOCKOUT TAG(S) FOR ALL CIRCUIT BREAKERS FOR THE FIRE ALARM SYSTEM(S). 29 MOUNT THE FIRE ALARM CONTROL PANEL AND AUXILIARY POWER SUPPLIES. COORDINATE EXACT LOCATION WITH THE OWNER PRIOR TO INSTALLATION. THE DIGITAL ALARM COMMUNICATION TRANSMITTERS (DACT) SHALL CLEARLY IDENTIFY THE TRANSMITTED SIGNAL AS "WATER FLOW", "GENERAL 30 ALARM", AND "SUPERVISORY" OR 'TROUBLE" AS A MINIMUM. 31 HOLES IN WALLS OR FLOOR CUTS MADE DURING THE PERFORMANCE OF THIS WORK SHALL BE PATCHED SO AS TO COMPLETELY CONCEAL THE HOLES AND CUTS WHERE THEY WOULD OTHERWISE BE EXPOSED TO VIEW. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING 32 OF THE ENTIRE SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE ALARM SYSTEM INSPECTION. 33 COORDINATE THE MONITORING OBLIGATION OF THE FIRE ALARM SYSTEM WITH THE LANDLORD AND APPLICABLE CODES. 34 IN NO CASE SHALL THE CONDUCTORS WITHIN METALLIC RACEWAY EXCEED 40% FILL. IN SUCH SITUATIONS LARGER SERIES WIRE MOLD OR OTHER CONDUIT SHALL BE USED, 35 ALL WORK WILL FOLLOW CURRENT NEC STANDARDS FOR CONDUIT, GROUNDING, INSTALLATION OF WIRING AND WIRE TYPES. 61 G15 NOTES 61G15-32.008 DESIGN OF FIRE ALARM SYSTEM (1) Fire alarms and detection systems include fire protection supervision, emergency alarm circuits, activation of life safety system controls and remote signaling of emergency conditions. Items to be considered in the design or analysis of fire alarm and detection systems are, as applicable to the particular project: occupancy and classification, monitoring, control and communication, cabling and supervision requirements, installation requirements, interoperability and performance requirements. (2) The design specifications shall be based on the Florida Building Code, the Florida Fire Prevention Code, or as required by the local authority having jurisdiction. The Florida Building Code and the Florida Fire Prevention Code are incorporated by reference in rule 61 G15-18.011, F.A.C. (3) For systems below the threshold requirements for mandatory use of professional engineering services, the Engineer of Record may specify the minimum system requirements only. (4) To ensure minimum design quality of Fire Alarm and Detection Systems Engineering Documents, said documents shall include as a minimum the following information when applicable: (a) The documents shall be dear, with a symbols legend, system riser diagram showing all initiation and notification components, and cabling requirements. The documents shall indicate locations where fire ratings are required as determined by the system's survivability requirements, and shall identify the general occupancy of the protected property and each room and area unless it is clear from features shown. (b) Locate Initiation and notification devices and connections to related systems on the floor plans and sections when needed for clarity. Related systems include elevator controls, smoke control systems, dampers, door release, any other systems or elements directly or indirectly controlled or monitored. (c) Strobe intensity and speaker output ratings for all notification devices. (d) Identify the Class of circuits as listed in NFPA 72, which is contained within and incorporated Into the Florida Fire Prevention Code. (e) Identify the functions required by the alarm and control systems including the transmission of emergency signals being monitored or annunciated. (f) Indicate whether the fire alarm is conventional or addressable, and indicate all zoning. (g) Locate surge protective devices and required protective features. (h) Identify and locate system devices that are subject to environmental factors, and indicate requirements for the protection of equipment from temperature, humidity or corrosive atmospheres, including coastal sell air. (i) The documents shall include a site plan of the immediate area around the protected building, structure or equipment when alarm devices are required outside the structure. 0) In buildings where smoke detection will be obstructed by walls, beams or ceiling features, the Engineer of Record shall provide applicable design and details to direct the installer to mitigate the obstructions. In buildings with smoke detection under a pitched roof, the plans shall indicate the roof pitch and a building section shall be provided as part of the Engineering Design Documents. (k) For fire detection systems utilizing smoke detection In situations where smoke stratification Is anticipated, the design shall provide the necessary criteria to mitigate the detection problems. (1) Systems designed using Performance Based criteria shall be identified and referenced to design guides or standards approved by the local authority having jurisdiction consistent with standards adopted by the Florida Fire Prevention Code and the Florida Building Code. (m) The system design must indicate if the system is to provide a general evacuation signal or a zoned evacuation for all high-rise buildings or mum -tenanted properties as defined in section 2 of the Florida Budding Code, Building. (n) Wiring requirements for underground, wet locations, campus style wiring, protection against damage and burial depth shall be specified or Indicated on the engineering design documents. (o) Requirements for operations and maintenance procedures, manuals, system documentation, and instruction of Owner's operating personnel, as needed to operate the systems as intended over time. (5) In the event that the Engineer of Record elects to specify specific equipment and to show the required wiring, battery and voltage drop (circuit analysis) calculations shall be completed. The calculations shall be completed using the equipment manufacture's data and applicable NFPA 72 procedures. (6) System test requirements shall be noted on the Engineering Design Documents. (7) When the Engineer of Record determines that special requirements are required by the owner, insurance underwriter or local fire code amendments these requirements shall be documented or referenced on the Engineering Design Documents. FIRE ALARM 61 G15 NOTES (4) (A) FIRE ALARM LEGEND ARE LOCATED ON FAM AND FIRE ALARM RISER ARE LOCATED ON FA1.3. (B) ALL INITIATING DEVICES AND NOTIFICATION APPLIANCES ARE LOCATED ON THE FLOOR PLAN PAGE FA1 A. (C) ALL CANDELA RATINGS HAVE BEEN IDENTIFIED WITH EACH DEVICE TO MEET THE STANDARDS OF CHAPTER 18 NFPA 72. (D) CLASS OF CIRCUITS WILL BE CLASS B. (E) THE MATRIX IS SHOWN ON FAM AND FACILITY IS MONITORED BY SOLE PATH CELLULAR COMMUNICATOR. (F) THE FIRE ALARM SYSTEM WILL BE ADDRESSABLE ON 1 LOOP. (G) (1)120V SURGE SUPPRESSORS WERE ADDED TO THE TRANSPONDER FIRE ALARM PANEL. (H) NIA (1)NIA PLAN 15 LOCATED ON FAIR, () (K) NIA (L) N/A (M) THE FIRE ALARM SYSTEM WILL BE GENERAL ALARM. (N) NIA (0) THE APPLICABLE MANUALS FOR THE FIRE ALARM SYSTEM WILL BE SENT WITH CLOSEOUT DOCUMENTS ON COMPLETION OF THE PROJECT. (6) TESTING PER NFPA 72, 2019 EDITION SYSTEM SURVIVABILITY SCALE 0 Non Sprinkled, No Relocation or Partial 5vacuaticn 1 51prinkled, No Relocation or Partial Evacuation 2 5prinkled, Voice Evacuation with partial or designated relocation areas 3 5prinkled, Voice Evacuation with partial or designated relocation areas 5691 7471 GALL BLVD ZEPHYRH I LLS, FL 33541 13 14 15 16 FIRE ALARM MATRIX / SEQUENCE OF OPERATION SYSTEM OUTPUTS Z O Z Z O Z O F- O H 0 U Z O w Z O U U w Z w Z Z pit O !Z`S O � = 0 0 ¢ Q J _J O F- > U CO LL. W > 0 � DO wLU U _J W Z _J W Z O W a Z) O ¢ 0) >- m (D I 'S W Z � J Z IW- x a Z Q Z W CO ¢ C� 2 � Lu O J cn c w o Z o O F-- ¢¢ (n Z > cal Z ¢¢ H 2 Z Q Z Z Q O fn ¢ d M m O Q U Z (r Q J =� Z Z C) 1-- Z I-_ 2Z W �' U 0 Z 0(0 ¢ Lu ~ 5 m 06 0 06 IY Z .6 X Z 0 %- 06 X Z 0 Z 06 X Z w W � W Z > Z ZQ Z O U H w 0)0O Z H Z O O t Z O O W 0 0 0 0 0 UL (� ¢° O O � = Z Z_ Q Q ¢ Q to ¢¢ W Q ~Q % W w = m U F- H Elf Q Z p H Z W J Q U Z H fn U Z H U) �' G' U~ Z J M U Z W C0 Z ~ 06 0¢ O LU J Lu Z W tf D O tY O W 0 D O D 0 w D C7 D en - C) W 0 0 U? O D W U Z Z J Z> W Q¢ Z Z W¢ Z Z= X W¢ Z Z W W H¢ Z Z X Z W F- N H >( W Q > W H 0- U C> -'S °8 Cn w 0 a W O to w O y w O W z Z 0 w 0 = cn ¢ J 0 J � ") J W h I•- O ~ Z W I I- p 1= Z W 1- O 1= Z W ►- F- O 1= Z W F- X W F-- 0 w w 1- W H Z%¢ Lu Z¢ H m O O O? O O = U ¢ ¢ X noWf=n 0 Xo X0UX00X0w 0� 00 0 0 SYSTEM INPUTS 0 0 Z W > U ¢ ¢ 0 I- ¢ 0 I- a 0 F- a 0 I- X ¢ ¢ � ¢ ¢ � CONTROL UNIT FUNCTIONS ALL SYSTEMS NORMAL" X SYSTEM SILENCE X X SYSTEM RESET ONE POINT FOR RESET X X ALARM DEVICES WATERFLOW SWITCHES X X X X X X X MANUAL PULL STATIONS X X X X X X SMOKE DETECTORS X X X X X X KITCHENHOOD SYSTEM X X X X X X SUPERVISORY DEVICES TAMPER SWITCHES X X X DUCT SMOKE DETECTORS X X X X TROUBLE FUNCTIONS LOSS OF DIAL TONE OR CELL DIALER CONECTION X X X FIRE ALARM SYSTEM AC POWER FAILURE X X X FIRE ALARM SYSTEM LOW BATTERY X X X ABNORMAL CIRCUIT OR DEVICE X X X SHEET INDEX SHEET DESCRIPTION FA1.1 FIRE ALARM COVER PAGE FA1.2 FIRE ALARM GENERAL INFORMATION FA1.3 FIRE ALARM RISER DIAGRAM AND CALCULATIONS FA1.4.1 FIRE ALARM INITIATING DEVICE PLACEMENT PLAN FA1.4.2 FIRE ALARM NOTIFICATION APPLIANCE PLACEMENT PLAN 1 2 3 4 5 6 7 8 9 10 11 12 13 14 17 MULTILEADERS TYPE DESCRIPTION FO CABLE MULTILEADER REVISION MULTILEADER j XX MULTILEADER: CA LOUTDETAIL/SHEET DETAIL/SHEET NUMBER XXX -XX-XXX DEVICE MULTILEADER: SYSTEM-FLOOR/LEVEL-DEVICE NUMBERS DOOR/DETAIL NUMBERS XXXX XX-XXX-X TAGS TYPE DESCRIPTION 0 CABLE ID TAG CABLE TAG CABLE TAG DEVICE TAG: SYSTEM TYPE/FLOOR-LEVEL/DEVICE NUMBER SHEET NUMBER/DETAIL XXX-XX-XXX XX-XXX X O SHEET NOTE TAG IDENTIFIERS TYPE DESCRIPTION ELEVATION IDENTIFIER XX DETAIL/SHEET NUMBER X SECTION IDENTIFIER: DETAIL/SHEET NUMBER INITIATING DEVICE ADDRESSING LEGEND DEVICE ADDRESS JL1 : D-001 ADDRESSABLE DETECTOR NUMBERING DEVICE DESIGNATOR (D=DETECTOR, M--MODULE) ADDRESSABLE LOOP L1 : M-01 1 ADDRESSABLE MODULE NUMBERING L1 : P-001 ADDRESSABLE POINT NUMBERING NOTIFICATION DEVICE ADDRESSING LEGEND F CIRCUIT DESIGNATOR FIRE ALARM PANEL NAC �DEVICE DESIGNATOR FACP:1-1 HORN / STROBE, HORN ONLY, STROBE ONLY DEVICE NUMBERING r CIRCUIT DESIGNATOR NAC BOOSTER POWER SUPPLY I DEVICE DESIGNATOR # = Booster Panel Number 1I NAC #:1-1 HORN / STROBE, HORN ONLY, STROBE ONLY DEVICE NUMBERING ALL WOPK SHALL COMPLY WITH c ,,� ( `�1 W NFFA CODES LAND STANDARDS Wv REVIEW DATE / ., 1-vd-" CITY OF ZEPWRHiLLS FIRE AND LIFE SAFETY EXAMINE 1e. GIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 (816) 358-1790 ENGINEERING FLORIDA COA #4630 15 16 17 a NO 81099 ' '= iE 9 a , t Is STATE OF %k 111611111110 NAL 1111 .. 18 0 a co Lu W Cl)0Ui O O O o 0 d a WoI' m ' U QCDZ rn P -JW5N M (IM ,L�Zu vtnUv H Q 0 � � 3 Z • KA Issue Date: 02.05.24 REVISION INFORMATION REVISION INFORMATION Q FIELD REVISION PER MECH Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT/BID ZEPHRYHILLS FL Drawing FIRE ALARM COVER PAGE FA1.1 u NI LI KI HI GI FI EI DI BI AI 1 2 3 FIRE ALARM SYMBOLS An 5 QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL ` FACP FIRE ALARM CONTROL PANEL k * ® POWER PANEL k * NAC NAC CIRCUIT POWER BOOSTER EXTENDER PANEL k ` BATT BATTERY BOX * AMP AMPLIFIER PANEL * EVAC VOICE EVACUATION PANEL * EVAC # REMOTE LOCATED EVACUATION AMPLIFIER CABINET k k * MIC REMOTE MICROPHONE FOR VOICE EVACUATION SYSTEM * ASCP AIR SAMPLING CONTROL PANEL * DGP DATA GATHERING PANEL ` FATC FIRE ALARM TERMINAL CABINET ` FCS FIRE COMMAND SYSTEM ` FSCP FIRE SYSTEM CONTROL PANEL * RP RELAY PANEL * PP PURGE PANEL k * HVAC HVAC CONTROL PANEL * FSCP FIRE SUPPRESSION CONTROL UNIT k k * FACU D FIRE ALARM CONTROL UNIT - DEDICATED * FACI FIRE ALARM CONTROL INTERFACE * ARCM AREA OF REFUGE EMERGENCY COMM. SYSTEM - MASTER UNIT * ARCR AREA OF REFUGE EMERGENCY COMM. SYSTEM - REMOTE UNIT * WCU WIRELESS CONTROL UNIT * DACR DIGITAL ALARM COMMUNICATOR RECEIVER * DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER * FAC FIRE ALARM COMMUNICATOR * FFI FIRE FIGHTER INTERFACE k 01 FAA FIRE ALARM ANNUNCIATOR * LED LCD ANNUNCIATOR/DISPLAY k * GAP GRAPHIC ANNUNCIATOR PANEL * TRP FIRE ALARM TRANSPONDER * FPC FIRE PUMP CONTROLLER ` KHSS KITCHEN HOOD SYSTEM ` ESR ELEVATOR STATUS/RECALL 01 DOC FIRE ALARM DOCUMENT BOX * PRN PRINTER * UPS UNINTERRUPTIBLE POWER SUPPLY ` SS SURGE SUPPRESSOR * TP TRANSIENT PROTECTION * k r� ROTATING BEACON * ago RB RADIO BOX k * ADC DIRECT CONNECT * DH DOOR HOLDER * DCL DOOR CLOSER k * JB JUNCTION BOX * PB PULL BOX * TB TERMINAL BOX * KB KNOX BOX k k * © FIREMEN'S PHONE ` ©J FIREMEN'S PHONE - JACK * ©H FIREMEN'S PHONE - HANDSET * FM FIREMEN'S MICROPHONE * Fx RI INDICATOR - REMOTE - WALL MOUNTED * X RI INDICATOR - REMOTE - CEILING MOUNTED * ❑A D ABORT SWITCH k * AR ABORT SWITCH - AEROSOL RELEASE * CA ABORT SWITCH - CLEAN AGENT k k * DL ABORT SWITCH - DELUGE FIRE SPRINKLER * DC ABORT SWITCH -DRY CHEMICAL * FO ABORT SWITCH - FOAM * HL ABORT SWITCH - HALON k ABORT SWITCH - MANUAL RELEASE ABORT SWITCH - PREACTION k * ABORT SWITCH - WATER MIST , * WC ABORT SWITCH - WET CHEMICAL 7 FIRE ALARM SYMBOLS H., 0 10 QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL * FF FIRE ALARM PULLSTATION * L! SMOKE DETECTOR * P SMOKE DETECTOR - PHOTOELECTRIC * I SMOKE DETECTOR - IONIZATION * BT SMOKE DETECTOR - BEAM TRANSMITTER * BR SMOKE DETECTOR - BEAM RECEIVER * AS SMOKE DETECTOR - AIR SAMPLING * ID SMOKE DETECTOR - IN DUCT * S R SMOKE DETECTOR - RELAY BASE * SB SMOKE DETECTOR -SOUNDER BASE * S SMOKE DETECTOR - DUCT * RTS REMOTE ALARM INDICATING AND TEST SWITCH * HEAT DETECTOR * aR/F HEAT DETECTOR - COMBINATION: RATE OF RISE/FIXED \pj* R/C HEAT DETECTOR - RATE OF COMPENSATION \pj* F HEAT DETECTOR - FIXED TEMPERATURE * - R HEAT DETECTOR - RATE OF RISE ONLY * GAS DETECTOR *fjCO CARBON MONOXIDE DETECTOR * CO2 CARBON DIOXIDE DETECTOR * HCL HYDROGEN CHLORIDE DETECTOR *fjCH< AM METHANE DETECTOR * FLAME DETECTOR * UV/IR FLAME DETECTOR - COMBINATION OF ULTRAVIOLET/INFRARED * IR FLAME DETECTOR - INFRARED * UV FLAME DETECTOR - ULTRAVIOLET * VR FLAME DETECTOR - VISIBLE RADIATION * S SMOKE/HEAT DETECTOR * S CO SMOKE/CO DETECTOR * CO HEAT/CO DETECTOR * S CO SMOKE/HEAT/CARBON MONOXIDE DETECTOR * WF FLOW DETECTOR/SWITCH * VS VALVE SUPERVISORY (TAMPER) SWITCH * HT HIGH TEMPERATURE SWITCH * LT LOW TEMPERATURE SWITCH * LD LEVEL DETECTOR/SWITCH PD PRESSURE DETECTOR/SWITCH * WATER DETECTOR * AS FULLY SPRINKLERED SPACE * PARTIALLY SPRINKLERED SPACE * NS NOWSPRINKLERED SPACE * VS VALVE WITH INTEGRATED SUPERVISORY (TAMPER) SWITCH * * N CHECK VALVE - GENERAL * RISER * BACKFLOW PREVENTER - DOUBLE CHECK * FREE STANDING SIAMESE FIRE DEPARTMENT CONNECTION * --�-- PUBLIC HYDRANT - TWO HOSE OUTLETS * �Q VALVE- GENERAL * VALVE - IN PIT *Q POST -INDICATOR VALVE k * KEY OPERATED VALVE * OS @ Y VALVE * INDICATING BUTTERFLY VALVE * S DAMPER -FIRE * S DAMPER -FIRE -SMOKE * M s DAMPER -MOTORIZED -FIRE -SMOKE * t DAMPER -SMOKE 11 FIRE ALARM SYMBOLS 12 13 14 15 QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL 01 kIM ADDRESSABLE INPUT MODULE * ADDRESSABLE OUTPUT MODULE k * kl0 ADDRESSABLE INPUT/OUTPUT MODULE * It; ISOLATION MODULE * SIB SIM MODULE PAM MODULE * K FA REMOTE RELAY - FORM C - DRY CONTACT RELAY MODULE * R ER ELEVATOR RECALL RELAY FIRE ALARM SYMBOLS QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL * EOL END OF LINE * EOL RE END OF LINE - RESISTOR * EOL RL END OF LINE - RELAY ` STROBE - WALL MOUNTED * C STROBE - CEILING MOUNTED * SPEAKER/STROBE - WALL MOUNTED * rWWC SPEAKER/STROBE - CEILING MOUNTED * SPEAKER - WALL MOUNTED * 04C SPEAKER - CEILING MOUNTED ` SPEAKER CLUSTER ` WP Dgj HORN/STROBE - WALL MOUNTED * miC HORN/STROBE - CEILING MOUNTED * 01H HORN WALL MOUNTED * � � HORN CEILING MOUNTED * DIM MINIHORN WALL MOUNTED * C MINIHORN CEILING MOUNTED * F H HORN - CLUSTER * ODB BELL - WALL MOUNTED k * ODC CHIME WALL MOUNTED * ODG GONG WALL MOUNTED MASS NOTIFICATION SYMBOLS QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL / PART NUMBER CSFML/UL MNS I MASS NOTIFICATION SYSTEM INTERFACE * EOL END OF LINE EOL RE END OF LINE - RESISTOR * EOL RL END OF LINE - RELAY * MNS STROBE - WALL MOUNTED * C MNS STROBE - CEILING MOUNTED * MNS - SPEAKER/STROBE - WALL MOUNTED * C MNS - SPEAKER/STROBE - CEILING MOUNTED * MNS - SPEAKER - WALL MOUNTED * C MNS - SPEAKER - CEILING MOUNTED * MNS - SPEAKER CLUSTER * MNS - HORN/STROBE - WALL MOUNTED * C MNS - HORN/STROBE - CEILING MOUNTED * EQH MNS - HORN - WALL MOUNTED * �� MNS - HORN - CEILING MOUNTED * q M jQH MNS - SPEAKER CLUSTER * ❑M MNS - FIRE ALARM PULLSTATION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 17 ABBREVIATIONS SYMB DESCRIPTION AC ALTERNATING CURRENT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AMP AMPERE AUX AUXILIARY AWG AMERICAN WIRE GAUGE BFG BELOW FINISH GRADE BLDG BUILDING C CM CEILING MOUNTED CIRC CIRCUIT CL CENTER LINE C CHIME COND CONDUIT CO COMPANY DC DIRECT CURRENT DIA DIAMETER DN DOWN DWG DRAWING ° DEG DEGREE ELEC ELECTRICAL EA EACH EXT EXTERIOR EX EXISTING DEVICE EQUIP EQUIPMENT EC ELECTRICAL CONTRACTOR XP EXPLOSION PROOF FA FIRE ALARM FL FLOOR FT FEET GC GENERAL CONTRACTOR GND GROUND HW HARDWIRED H HIGH AUDIBLE SETTING ID IDENIFICATION IN INCHES KW KILOWATT LVL LEVEL L LOW AUDIBLE SETTING MAX MAXIMUM MIN MINIMUM MFR MANUFACTURER MNS MASS NOTIFICATION SYSTEM MTD MOUNTED N4 NEMA 4 - NON CORROSION -PROOF ENCLOSURE N4X NEMA 4 - CORROSION -PROOF ENCLOSURE N12 NEMA 12 - SEALED ENCLOSURE ND NEW DEVICE NAC NOTIFICATION APPLIANCE CIRCUIT # NUMBER PNL PANEL PH 0 PHASE PS POWER SUPPLY QTY QUANITITY REQ'D REQUIRED SEC SECONDARY SLC SIGNAL LINE CIRCUIT TEMP TEMPERATURE TYP TYPICAL UPS UNINTERRUPTED POWER SUPPLY V VOLTAGE VAC VOLTAGE ALTERNATING CURRENT VDC VOLTAGE DIRECT CURRENT W WM WALL MOUNTED W WATTS WP WEATHERPROOF WG WIRE GUARD WD WIRELESS DEVICE W/ WITH GIBBENS DRAKE SCOTT INCINC Big tr #' U , 9201 E. 63rd STREET, SUITE 100 : 'd t RAYTOWN, MISSOURI 64133 o 4 ISTATI~C)1= o. ) +LOR►. 816 358-1790 ��` °°� fi q � � � ��''�° '» N ENGINEERING FLORIDA COA #4630�` 15 16 17 18 Q V) Ld OU 0 Z > z Lo O a M w J p E U w W Ix it = O O LL ~ o c a; a E LLJ p Q Q�Z U LnLU �Uv M _ L o vcoUv H Q rCU V Q03m U 3 I 6 �W 9 0 Issue Date: 02.05.24 REVISION INFORMATION Q FIELD REVISION PER MECH Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM GENERAL INFORMATION FA1.2 P N MI LI KI .I� HI GI FI 1 2 3 4 5 C: 7 CIRCUIT LOAD & VOLTAGE DROP CALCULATIONS Device Description STANDBY: Source: Amps FACP Circuit Number: C1 C2 C3 C4 SCWL CEILING MOUNT STROBE WHITE (30 cd) 0.00000 0.06300 0 0 2 0.126 PARE 1 0 0 SCWL CEILING MOUNT STROBE WHITE (75 cd) 0.00000 0.11100 1 0.111 0 0 0 0 PC2WL PC2WL CEILINGNTH RN STROBE WHITE 30 cd MOUNT O S O ( ) _..._._... CEILING MOUNT HORN STROBE WHITE (75 cd) .. 0.00000 0.00000 0.09000 0.14300 0 0 _ _ ...-......... 3 I 0.429 ___._.._ 2 2 0.18 0.286 . 0 0 0 0 PC2WL CEILING MOUNT HORN STROBE WHITE (115 cd) 0.00000 0.18700 3 0.561 1 0 1 0 0 1 0 P2RK WALL MOUNT HORN STROBE, OUTDOOR (110 cd) 1 0.000001 0.212001 0 0 1 0 1 0 1 r 0,212 # Devices Circuit Amps Circuit Length (ft) Total Voltage Drop (14aRg) EOL voltage 14 aft 7 1.101 6 0.592 0 0 1 0,212 1.101 250 0.592 ,.r,. 0.000 0.212 200 0 0 100 .__1 76 F s 18 64 0.76 19.64 4`; ,' 0.00 / ..... , _:' 20.40 �ti,,,., 0.14 20.26 NOTE: VOLTAGE FORMULA USED IS: VD = LENGTH (CIRCUIT MEASURED ONE-WAY IN FT.) X LOAD (IN AMPERES) X RESISTANCE (.00316 FOR 14AWG) X 2 (FOR RETURN RESISTANCE) WIRE RESISTANCE VALUES REFERENCED FROM NEC TABLE 8 HWF2V-COM BATTERY CALCULATIONS Total Total Qty Part # Description Standby Alarm Standby Alarm 1 HWF2V-COM Cell Dialer 0.23000 0.95000 0.2300 0.9500 0.2300 0.9500 Standby Current Total Hours = 0.2300 X 24 = 5.5200 (Hours) Alarm Current Total Minutes = 0.9500 X .083 = 0.0789 (5 Mins) Total = 5.5989 20% Battery Safety Margin = 1.1198 Total AH Rated Batteries Needed = 6.7186 Total AH Rated Batteries Supplied F 7 75 75 0 /30 EOL RE O O O / C 75 775 75 115 115 0 0 0 RE C C C C C RISER DIAGRAM Ft CALCULATIONS SCALE: 3/16" =1'-0" 110 RE SPARE I EOL RE CIR4 14 AWG 2 COND FPLP CIR3 14 AWG 2 COND FPLP CIR2 14 AWG 2 COND FPLP 115 CIR1 I C DEDICATED 120 VAC 20 AMP CIRCUIT(LOCKED) (BY OTHERS) 14 AWG 2 COND FPLP C1 C2 C3 C4 A SS FIRE LITE ES-20OX FACP SP BATTERY BATTERY 12V 12AH 12V 12AH SSU00672 SYSTEM DOCUMENTATION AS -BUILT DRAWINGS SLC LOOP E 10 11 12 FACP BATTERY CALCULATIONS Qty Part# Description Standby Alarm Total Standby Total Alarm 1 ES-20OX Fire Alarm Panel 0.14100 0.25700 0.1410 0.2570 1 PWRMOD24 Optional 24volt 3 Am Transformer ' p p rm r (inside the panel) 0.00700 0.00800 0.0070 0.0080 1 IPOTS-COM POTS communicator (inside the panel) 0.04000 0.04100 0.0400 0.0410 1 ANN-80 Remote Annunciator 0.01500 0.04000 0.0150 0.0400 1 SD365 Photoelectric Smoke Detector 0.00020 0.00450 0.0002 0.0045 3 .....-- ..... 1 BG-12LX . .... _ .... MMF-300 Manual Pull Station _ . __..__ . .._..._... ... ....... . . - .. ..._ ...... . Monitor Module with LED (Full Size) 0.00038 0.00038 0.00500 0.00500 0.0011 0.0004 0.0150 0.0050 1 MDF-300 Dual Monitor Module 0.00075 0.00640 0.0008 0.0064 6 CRF-300 Relay Control Module 0.00023 0.00650 0.0014 0.0390 3 ......... 3 D365PL RTS-151 KEY Intelligent Duct Photo Smoke Detector for g . _. - __--... _--- ... ..... ... .... - ..- - Remote Test Station 0.00030 0.01200 0.00650 0.10500 0.0009 0,0360 0.0195 0.3150 2 SCWL CEILING MOUNT STROBE WHITE (30 cd) 0.00000 0.06300 0.0000 0.1260 1 SCWL CEILING MOUNT STROBE WHITE (75 cd) 0.00000 0.11100 0.0000 0.1110 2 PC2WL CEILING MOUNT HORN STROBE WHITE (30 cd) 0.00000 0.09000 0.0000 0.1800 5 PC2WL CEILING MOUNT HORN STROBE WHITE (75 cd) 0.00000 0.14300 0.0000 0.7150 3 PC2WL CEILING MOUNT HORN STROBE WHITE (115 cd) 0.00000 0.18700 0.0000 0.5610 1 P2RK (110) WALL MOUNT HORN STROBE, OUTDOOR (110 cd} 0.00000 0.21200 0.0000 0.2120 0.2437 2.6554 Standby Current Total Hours = Alarm Current Total Minutes = Total 20% Battery Safety Margin Total AH Rated Batteries Needed Total AH Rated Batteries Supplied 0.2437 2.6554 X 24 (Hours) X .083 (5 Mns) = = = = = 5.8495 0.2204 6.0699 1.2140 7.2839 F 12 13 14 15 16 WIRE CHART CIRCUIT >MINIMUM SIZE< SYMBOL TYPE CIRCUIT DESCRIPTION AND TYPE OF WIRE SIGNALING LINE CIRCUIT A SLC (POWER LIMITED) 2418AWG ANNUNCIATOR DATA BUS AD ANN (BLK/RD =DATA) 4418AWG (WHT/GRN = PWR) INITIATING DEVICE CIRCUIT D UDC (NON -INTELLIGENT DEVICES) 2-#18AWG NOTIFICATION APPLIANCE TRIP CKT. C TRIP (COMBINED HORN It VISUAL CIRCUIT) 2-#14AWG RT TEST REMOTE TEST STATION TEST 4418AWG SH = SHEILDED *WIRE MUST BE SHIELDED AS INDICATED TW = TWISTED GENERAL NOTE 1) ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2) WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3) DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED 4) ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 5) WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4" 6) ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. 7) OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. 8) THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. RTU v RT M01 01 M04 MOS D02 M06 E E M07 M08 M9 D03 E E A 0 S P AIM F AIM S 0 F 0 LI 0 S +-D �- I I I I RT I USICKHSS VA I HVAC I I HVAC SHUTDOWN;02 WF RTS I SHUT O SHUTDO RTS EOL EL EOL RE RE RE 18 AWG FAA 4 FPLP CEL UNI MCBL-7 MCBL-7 DEDICATED 120 VAC 20 AMP CIRCUIT(LOCKED) (BY OTHERS) M12 M11 M10 D4 E F 0 0 IRTI I HVAC I I HVAC I SHUTDOWN � N RTS_j Al ?V-COM BASIC SYSTEM FUNCTIONAL OPERATION N A FIRE ALARM CONDITION (ALARM, SUPERVISORY OR TROUBLE) IS :CTED, THE FIRE ALARM CONTROL PANEL GOES OFF -HOOK TO DIAL 1 FRAL STATION. THE HWF2V-COM DIALER CAPTURE MODULE DETECTS HOOK CONDITION AND PROVIDES THE FIRE PANEL WITH A DIAL TONE N THE FIRE PANEL DETECTS THE DIAL TONE, IT BEGINS DIALING THE FRAL STATION. AFTER THE DIALING IS COMPLETED, THE DIALER -URE MODULE RETURNS A SIGNAL TO THE FIRE PANEL. THE FIRE PAP I SENDS THE CONTACT ID REPORTS TO THE DIALER CAPTURE MODU :H IN TURN SENDS A SIGNAL AFTER THE REPORT IS SUCCESSFULLY :IVED FROM THE FIRE PANEL. THE DIALER CAPTURE MODULE SENDS TACT ID REPORTS TO THE HWF2V-COM SERIES COMMUNICATIONS ULE. WHEN ALL THE REPORTS ARE SENT, THE FIRE PANEL GOES OOK. THE HWF2V-COM SERIES COMMUNICATIONS MODULE THEN ISMITS THE MESSAGES TO THE CENTRAL STATION (EITHER OVER TH BATTEY BACKUP EMERGENCY LIGHT RESCUE COMMUNICATIONS PRESS CALL AREA OF RESCUE MAIN ANNUNCIATOR 48' A.F.F. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 17 NFPA 72 AND ADA DEVICE INSTALLATION REQUIREMENTS -CONDUIT INSTALL PER NATIONAL ELECTRIC CODE MOUNT ON A APPROVED BOX MOUNT AUDIBLE &VISUAL DEVICES ON APPROVED BOXES. AIR SUPPLY DIFFUSER OR SMOKE/ HEAT RETURN AIR OPENING DETECTOR 1 1 0'-4' MINIMUM 3'-0' MINIMUM 0'-6' MINIMUM 0'-4' MINIMUM, HORN/ STROBE I _F I-T GRAPHICDRN ANNUNCIATOR CONTROL SMOKE/ HEAT DEFECTOR PANEL BE VSTFIREMAN'S HANDSET A +96' MAXIMUM TOP OF DEVICE RE MANUAL PULL STATION . 80' MINIMUM ��ii BOTTOM OF DENCE HINGED SIDE 5-0' MAXIMUM 5' 6' AREA OF RESCUE CALL STATION 3'-8" 3'-8" Ale AF.F. (3'-6' MINIMUM, 5'-6" MAXIMUM) (3'-6" MINIMUM, 4'-0" MAXIMUM) FINISHED FLOOR MOUNTING HEIGHT REQUIREMENTS SALE: GIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 (816) 358-1790 ENGINEERING FLORIDA COA #4630 15 16 17 ' MAXIMUM CUE COMMUNICATKWS LIFT HANDSEr PRESS CALL W-F Z six STATE OFZr IONA1. lc�-`��� 18 Q V) co LIJ `O o p a 0 M J W i U E w S _ y 0 � J� LU o 0 iI LL Cn co V H jz g< QZ EnHSv M U En-ZN En 1 6 vU)5a F- of rFjl6 ++ N L 3 N ca CO Q c 3 0 t� 3 z ;> O a Issue Date: 02.05.24 REVISION INFORMATION AFIELD REVISION PER MECH Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM RISER DIAGRAM AND CALCULATIONS FA1.3 1 NI LI KI HI GI FI EI DI AI 1 2 3 4 5 6 7 8 9 10 1 2 3 !-I INITIATING DEVICE PLACEMENT PLAN SCALE: 3/16" =1'-0" 5 1.1 VA E 10 11 11 12 12 13 14 FIRE ALARM SYMBOLS 15 16 17 QTY SYMB DESCRIPTION MANUFACTURER MODEL BACKBOX I FFACP FIRE ALARM CONTROL PANEL FIRELITE ES-20OX OWN 1 FFTJ FIRE ALARM ANNUNCIATOR FIRELITE ANN-80 ANN-SB80KIT-R 1 FAC FIRE ALARM COMMUNICATOR HONEYWELL HWF2V-COM OWN 1 FD07C FIRE ALARM DOCUMENT BOX SPACE AGE SS000672 OWN 1 40 SMOKE DETECTOR - PHOTOELECTRIC FIRELITE SD365 4" SQ x 2.5"D P 3 RF FIRE ALARM PULLSTATION FIRELITE BG-12LX 1 GANG 1 e ADDRESSABLE INPUT MODULE FIRELITE MMF-300 4" SQ x 2.5"D 1 AIM D DUAL ADDRESSABLE INPUT MODULE FIRELITE MDF-300 4" SQ x 2.5"D 6 0a ADDRESSABLE OUTPUT MODULE FIRELITE CRF-300 4" SQ x 2.5"D 3 6 SMOKE DETECTOR - DUCT FIRELITE D365PL 3 RT5 REMOTE ALARM INDICATING AND TEST SWITCH SYSTEM SENSOR RTS151 KEY 1 GANG 10 HORN/STROBE - CEILING MOUNT SYSTEM SENSOR PC2WL 4" SQ x 2.5"D 1 ® HORN/STROBE - WALL MOUNT - WEATHERPROOF SYSTEM SENSOR P2RK INCLUDED 3 X C STROBE - CEILING MOUNT SYSTEM SENSOR SCWL 4" SQ x 2.5"D 1 KHSS KITCHEN HOOD SYSTEM EXISTING 1 EE SURGE PROTECTOR DITEK DTK-120HW 1 EE SURGE PROTECTOR DITEK DTK-2LVLPF 1 WF FLOW DETECTOR/SWITCH EXISTING 1 vs VALVE SUPERVISORY (TAMPER) SWITCH EXISTING 1 KB KNOX BOX EXISTING EOL END OF LINE - RESISTOR RE —a CIRCUIT CONTINUATION * CEILING NOTE ALL CEILING TILE AREAS ARE SMOOTH FLAT 12' OR LESS. ALL BEAMED CEILING AREAS ARE SLOPED 18' OR LESS. * AUDIBLE DESIGN NOTE: DESIGN IS BASED ON AVERAGE AMBIENT SOUND LEVEL FOR AN "A-2" OCCUPANCY REFER TO NFPA 72 TABLE A.18.4.3 * WALL NOTE: ALL GREY WALLS ARE PARTIAL HEIGHT. GENERAL NOTE 1) ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2) WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3) DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED 4) ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 5) WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4" 6) ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. 7) OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. 8) THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. 13 14 WIRE CHART CIRCUIT >MINIMUM SIZE< SYMBOL TYPE CIRCUIT DESCRIPTION AND TYPE OF WIRE SIGNALING LINE CIRCUIT A SLC (POWER LIMITED) 2-#18AWG ANNUNCIATOR DATA BUS AD ANN (BLK/RD =DATA) 4418AWG (WHT/GRN = PWR) INITIATING DEVICE CIRCUIT D IDC (NON -INTELLIGENT DEVICES) 2-#18AWG NOTIFICATION APPLIANCE TRIP CKT. C TRIP (COMBINED HORN Ft VISUAL CIRCUIT) 2-#14AWG RT TEST REMOTE TEST STATION TEST 4418AWG SH = SHEILDED *WIRE MUST BE SHIELDED AS INDICATED TW = TWISTED FLAG NOTES 0 NEW FIRE ALARM PANEL SHALL BE CONNECTED TO DEDICATED 120 VAC POWER. LABEL CKT BREAKER "FIRE ALARM". OFIRE ALARM PANEL SHALL COMMUNICATE TO MONITORING STATION VIA SOLE PATH CELLULAR COMMUNICATION. OINSTALL RELAY FOR MUSIC SHUT DOWN WITHIN 3' OF MUSIC SYSTEM. TERMINATIONS FOR AUDIO SHUNT BY OTHERS. OMONITOR MODULE FOR SUPERVISION OF EXISTING KITCHEN HOOD. FIELD VERIFY LOCATION. ODUCT DETECTORS SHALL BE SUPPLIED BY JCI AND INSTALLED BY OTHERS. ADDRESSABLE DUCT CONNECTS TO SLC. CONNECTIONS TO FIRE ALARM PANEL SHALL BE BY JCI. HVAC SHUTDOWN SHALL BE BY OTHERS. FIELD VERIFY LOCATIONS. p ADDRESSABLE RELAY MOUNT INSIDE DUCT DETECTOR HOUSING. O MOUNT REMOTE TEST STATIONS IN MAIN OFFICE NEXT TO FIRE PANEL. 0DUAL MONITOR MODULE FOR SUPERVISION OF SPRINKLER WATERFLOW AND TAMPER SWITCH. 0INSTALL EXTERIOR HORN STROBE ABOVE FDC 10' ABOVE FINISHED GRADE. VERIFY LOCATION. 0 INSTALL STI PROTECTIVE COVER OVER MANUAL PULL STATION. 11 KNOX BOX BY OTHERS. 12 PER MECHANICAL ENGINEER DUCT SMOKE NOT REQUIRED IN RTU. UNIT SHALL SHUTDOWN IN ALARM ONLY. r IN t 16d -r 61 GIBBENS DRAKE SCOTT, INC 'v� a a CC 9201 E. 63rd STREET SUITE 100 RAYTOWN, MISSOURI 64133 �► 4 IfATE01= (816) 358-1790 •h`.' fiZORVD3 -' ENGINEERING FLORIDA COA #4630 15 16 17 18 9 5 Q W Lo 0 a M OJ W o U E w w 0i o i �< O o o � a >� LL 0 2 :5 z 0)8 E Qi Lo Lo vfAU� H Q y _,10�iuCc (�=mm 3 c r- v : ' B UU O Issue Date: 02.05.24 REVISION INFORMATION Q FIELD REVISION PER MECH Restaurant #: 5691 LONGHORN LH9.3 HK Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT / BID ZEPHRYHILLS FL Drawing FIRE ALARM INITIATING DEVICE PLACEMENT PLAN FA1.4.1 PI NI MI LI KI JI HI GI FI EI DI CI BI AI 1 2 3 L / J �, � I _ ��� / ( 1 ( 1 ( ! ( 1 �—---�® J C3 4 ®�.®�� I I I I E NOTIFICATION APPLIANCE PLACEMENT PLAN SCALE: 3/16" =1'-0" 7 C2 C2 � COOLER �7 10 ..__ �y..�-, 11 12 13 14 FIRE ALARM SYMBOLS 15 16 17 QTY SYMB DESCRIPTION MANUFACTURER MODEL BACKBOX 1 FACP FIRE ALARM CONTROL PANEL FIRELITE ES-200X OWN 1 FAA FIRE ALARM ANNUNCIATOR FIRELITE ANN-80 ANN-SB80KIT-R 1 FAC FIRE ALARM COMMUNICATOR HONEYWELL HWF2V-COM OWN 1 DOC FIRE ALARM DOCUMENT BOX SPACE AGE SS000672 OWN 1 5 SMOKE DETECTOR -PHOTOELECTRIC FIRELITE SD365 4" SQ x 2.5"D P 3 F FIRE ALARM PULLSTATION FIRELITE BG-12LX 1 GANG 1 A�� ADDRESSABLE INPUT MODULE FIRELITE MMF-300 4" SQ x 2.5"D 1 AiNE � DUAL ADDRESSABLE INPUT MODULE FIRELITE MDF-300 4" SQ x 2.5"D 6 ata ADDRESSABLE OUTPUT MODULE FIRELITE CRF-300 4" SQ x 2.5"D 3 S SMOKE DETECTOR -DUCT FIRELITE D365PL 3 RT5 REMOTE ALARM INDICATING AND TEST SWITCH SYSTEM SENSOR RTS151 KEY 1 GANG 10 HORN/STROBE -CEILING MOUNT SYSTEM SENSOR PC2WL 4" SQ x 2.5"D 1 � HORN/STROBE -WALL MOUNT -WEATHERPROOF SYSTEM SENSOR P2RK INCLUDED 3 � STROBE -CEILING MOUNT SYSTEM SENSOR SCWL 4" SQ x 2.5"D C 1 KH55 KITCHEN HOOD SYSTEM EXISTING 1 g8 SURGE PROTECTOR DITEK DTK-120HW 1 gg SURGE PROTECTOR DITEK DTK-2LVLPF 1 wF FLOW DETECTOR/SWITCH EXISTING 1 vs VALVE SUPERVISORY (TAMPER) SWITCH EXISTING 1 � KNOX BOX EXISTING EOL END OF LINE -RESISTOR RE —► CIRCUIT CONTINUATION * CEILING NOTE ALL CEILING TILE AREAS ARE SMOOTH FLAT 12' OR LESS. ALL BEAMED CEILING AREAS ARE SLOPED 18' OR LESS. * AUDIBLE DESIGN NOTE: DESIGN IS BASED ON AVERAGE AMBIENT SOUND LEVEL FOR AN "A-2" OCCUPANCY REFER TO NFPA 72 TABLE A.18.4.3 * WALL NOTE: ALL GREY WALLS ARE PARTIAL HEIGHT. GENERAL NOTE 1) ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2) WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3) DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED 4) ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 5) WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4" 6) ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. 7) OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. 8) THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 WIRE CHART CIRCUIT >MINIMUM SIZE< SYMBOL TYPE CIRCUIT DESCRIPTION AND TYPE OF WIRE SIGNALING LINE CIRCUIT A SLC (POWER LIMITED) 2-#18AWG ANNUNCIATOR DATA BUS AD ANN (BLK/RD =DATA) 4-#18AWG (WHT/GRN = PWR) INITIATING DEVICE CIRCUIT D IDC (NON -INTELLIGENT DEVICES) 2-#1$AWG NOTIFICATION APPLIANCE TRIP CKT. C TRIP (COMBINED HORN 8 VISUAL CIRCUIT) 2-#14AWG RT TEST REMOTE TEST STATION TEST 4-#18AWG SH = SHEILDED *WIRE MUST BE SHIELDED AS INDICATED TW = TWISTED FLAG NOTES 10 NEW FIRE ALARM PANEL SHALL BE CONNECTED TO DEDICATED 120 VAC POWER. LABEL CKT BREAKER "FIRE ALARM". QFIRE ALARM PANEL SHALL COMMUNICATE TO MONITORING STATION VIA SOLE PATH CELLULAR COMMUNICATION. OINSTALL RELAY FOR MUSIC SHUT DOWN WITHIN 3' OF MUSIC SYSTEM. TERMINATIONS FOR AUDIO SHUNT BY OTHERS. OMONITOR MODULE FOR SUPERVISION OF EXISTING KITCHEN HOOD. FIELD VERIFY LOCATION. ODUCT DETECTORS SHALL BE SUPPLIED BY JCI AND INSTALLED BY OTHERS. ADDRESSABLE DUCT CONNECTS TO SLC. CONNECTIONS TO FIRE ALARM PANEL SHALL BE BY JCI. HVAC SHUTDOWN SHALL BE BY OTHERS. FIELD VERIFY LOCATIONS. �6 ADDRESSABLE RELAY MOUNT INSIDE DUCT DETECTOR HOUSING. O MOUNT REMOTE TEST STATIONS IN MAIN OFFICE NEXT TO FIRE PANEL. g0DUAL MONITOR MODULE FOR SUPERVISION OF SPRINKLER WATERFLOW AND TAMPER SWITCH. OINSTALL EXTERIOR HORN STROBE ABOVE FDC 10' ABOVE FINISHED GRADE. VERIFY LOCATION. 10 INSTALL STI PROTECTIVE COVER OVER MANUAL PULL STATION. 11 KNOX BOX BY OTHERS. 12 PER MECHANICAL ENGINEER DUCT SMOKE NOT REQUIRED IN RTU. UNIT SHALL SHUTDOWN IN ALARM ONLY. r F� �� °� ,, �,, �� GIBBENS DRAKE SCOTT, INC � � �� *� � �` 9201 E. 63rd STREET, SUITE 100 �, � I�'T'ATE 01= ; � , RAYTOWN, MISSOURI 64133 � � tack (816) 358-1790 "�" �,$ ��:ORtt3'�'�°,�`�,�,,°'� ENGINEERING FLORIDA COA #4630 ��1������� ra-/$-�� 15 16 17 18 . -- .. s� m 0 Q c� W J I p E W W � o o a��i a O=O I LL � � U H g�Z � � �_ u'> IW— U t19—ZN v M to � _ U � ��—� v to U v I— Q y ���� Q�3m c-_� �� 3 z i W O W Issue Date: 02.05.24 REVISION INFORMATION Q FIELD REVISION PER MECH Restaurant #: 5691 LONGHORN LH9.3 H K Q2-2024 Rev 7495 Gall Blvd Zephyrhills FL 33541 AUTHORIZED FOR: PERMIT /BID ZEPHRYHILLS FL Drawing FIRE ALARM NOTIFICATION APPLIANCE PLACEMENT PLAN FA1.4.2