HomeMy WebLinkAbout21-3051City of Zephyrhills
5335 Eighth Street
Zephyrhills, FL 33542
Phone: (813) 780-0020
Fax: (813) 780-0021
Permit Type: Add/Alter (Residential)
14 26 21 0010 02600 0120
00,1,
Name: MICHAEL & LEE WORNER Permit Type: Add/Alter (Residential)
Class of Work: Add/Alter Residential
Address: 4748 18Th St
ZEPHYRHILLS, FL 33542
OR-21910ma
Building Valuation: $13,300.00
Electrical Valuation: $0.00
Mechanical Valuation: $0.00
Plumbing Valuation: $0.00
Total Valuation: $13,300.00
Total Fees: $106.50
Amount Paid: $106.50
Date Paid: 10/20/2021 2:57:47P]
BAR-003051-2021
Issue Date:
4748 18Th Street
DOORS LLC
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies,
I I I iii I IT I i !I I I I I I I I I I
Complete Plans, Specifications add fee Must Accompany Application. All work shall be performed in
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
CONTRACTOR SIGNATURE
P�Vi oFFICE
:2 :1 1611141TJ
813J80-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Buildng DePahment
Date Received
Phone Contact far Permitting
Owner's Name �'4dlorri,6--n Own�err Phone Number
Owner Phone Number
Owner's Address F�J I �[t �kl
Foe Simple Titleholder Name Owner Phone Number
Fee Simple Titleholder Address
LOT ft
SUBDIVISIONL ESE =PARCEL ID,1:107�'OQ66) -)
(OBTAINED FROM PROPERTY TAX NOTICE)
WORK PROPOSED
NEW CONSTR ADD/ALT SIGN DrMOLISH
INSTALL REPAIR
PRORQSED USE
SFR COMM OTHER
TYPE-'JO CONSTRUCTION
BLOCK ED FRAME STEEL
DESCRIPTION OF WORK
.1
K-06U=bc A-RVIZ�A:A4 =-W
BUILDING SIZE
=SQ
FOOTAGE
=
HEIGHT
t IF cc-PAAr 'ut cc tt`c
D�511UILDING
`CZ�t x 't 't tc t Ct x t c 't it x tit t C t $x T Z F'r x C ic t.,c c t 'r W S. gr Xt t I X $L IL3L C t C CIE
VALUATION OF TOTAL CONSTRUCTION
=ELECTRICAL
AMP SERVICE PROGRESS ENERGY =
W.RLE.C.
=PLUMBING
=MECHANICAL
=GAS ROOFING
FINISHED FLOOR ELEVATIONS =1
VALUATION bF MECHANICAL INSTALLATION
SPECIALTY = OTHER
FLOOD ZONE AREA =YES NO
BUILDER COMPANY
SIGNATURE I ;?--�
I IN FEE CURREN Y/N
Address E 9 15 v 4 -,- �k- -1 License 4
COMPANY
SIGNATURE REGISTERED =L
ELECTRICIAN E:-
Address Licenseti
PLUMBER COMPANY
SIGNATURE �._..._... REGISTERED YIN esEeuNe.
Address License 4
MECHANICAL COMPANY E;;;===
SIGNATURE REGISTERED .c,,
Address License ft
OTHER COMPANY E�=/N
SIGNATURE REGISTERED
Address License# E
RESIDENTIAL Attach (2) Plot Plans; (2) sets of Building Plans; (1) set of Energy Forms; R,O-W Permit for now construction,
Minimum ten (10)%vorRing days after submittal date, Required onsite, Construction Plans-' tarmwatei-Plans w1S4t Fence installed,
Sanitary Facilities & I duopster; Site Work Permit for subdivisionsilarge projects
COMMERCIAL Attach (2) Complete sets of Building Plans plus a Life Safely Page; (1) set of Energy Forms, R-O-W Permit for new construction.
Minimum ten (10) working days after submittal date. Required ons:le, Construction Plans, Stormwzter Plans w/ Silt Fence installed,
Sanitary Facilities & I dumpider. Site Work Permit for all new, projects, Ali commarciat requirements must meet compliance
SIGN PERMIT Attach (2) sets of Engineered Plans_
—*PROPERTY SURVEY required for all NEW construction,
Directions:
Fill out application completely,
Owner & Contractor sign back of application, notarized
If over $2500, a Notice of Commencement Is required. (AIC upgrades over $7500)
Agent (for the contractor) or Power of Attorney (for the Owner) would be someone with notarized letter from owner authorizing same
OVER THE COUNTER PERMITTING (copy of contract required)
Reroofs If shingles Sewers Service Upgrades A/C Fences (Ploi,'Surveyll'ootatie)
Driveways -Not aver Counter if on public roadways.. needs ROW
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to `deed` restrictions" which may be more restrictive
than County regulations. The undersigned assumes responsibility for compliance with any applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILIMIM If the owner has hired a contractoror contractors to undertake we*, they
may be required to be licensed in accordance With state and local regulations, If the contractor is not licensed as required by law, both the owner and
contractor may be cited for a misdemeanor Violation under state law, If the owner or intended contractor are uncertain as to what licensing requilimments;
may apply for the intended work, they are advised to contact the Pasco County Building Inspection Divisions—Utrinsing Section at 727-847- 80M
Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contraclords) sign portions of tho'contractor Block" of this
application for which they wilt be responsible. if you, as the owner sign as the contractor, that may be ariindication that he is not property licensed and Is
not entitled to permitting privileges in Pasco County,
TRANSPORTATION iMPACTILITILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recoures, Recovery Fees may apply to the construction of new buildings, change of use In existing buildings, or
expansion of existing buildings, as sprielfied in Pasco County Ordinance number 89-07 and 90-07, as amended, The undersigned also understands, that
such fees, as may be due, Will be identified at the time of permettinq. 11 is further understood that Transportation Impact Fees and Resource Recovery
Fees must be paid prior to receiving a 'cerblicale of occumancy' or final power release, tf the project does not involve a certificate of occupancy or final
power release, the fees must be paid prior to permit issuance, Furthermore, if Pasco County Waten'Sewer Impact fees are due, they must be paid prior
to permit issuance in accordance with applicable Pasco County artlinturcres,
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2,500,00 or more, I cardly that 1, the applicant,
have been provided with a copy of the 'Florida,Construction Lien Low--Homerowner's Protection Guide" prepared by the Florida Department of
Agriculture and Consumer Affelic, If the applicant Is someone other then tire 'owner', I certify that I have obtained a copy of the above described
document and promise in good faith to deliver it to the "owner" prior to commencement.
CONTRACTOR'SIOWNER'S AFFIDAVIT: I caddy that all the Information in this application is accurate and that all work will be done in compliance'
with
all applicable laws regulating construction. zoolng and land development, Applicator, Is hereby made to obtain a permit to do work and installation 85
indicated, I certify that no work or installation has commenced prior to issuance of a permit and that oil work will be performed to meet standards of all
laws regulating construction, County and City codes, zoning regulations, died land development regulations In the jurisdiction. I also cartify that I ,
understand that the regulations of other government agencies may apply to the Intended work, and that it is my responsibility to identify what actions I
must take to be In compliance. Such agendas Include bar are not limited to:
Department of Environmental Protection-Gypress Baybeads, Wetland Areas and Environmentally Sensitive
Lands, WateraptiVarstewater Treatment,
Southwest Florida Water Management District -Wells, Cypress Bayheads, Welland Areas, Altering
Watercourses.
Army Corps of Engineers-Srravvafls, Docks, Navigable Waterways.
Department of Health & Rehabilitative Services/Environmental Health Unit -Wells, Wastewater Treatment,
Septic Tanks,
US Environmental ProteGbon Agency -Asbestos abatement.
Federal Aviation Authority -Runways.
I understand that the following restrictions apply to the use of fill:
- Use of fit is not allowed in Flood Zone 'V" unless expressly permitted.
- If the fill material is to be used in Flood Zone W, it is understood that a drainage plain addressing a
compensating volume* will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida,
- If the fill material is to be used in Flood Zone "A" in connection With a permitted building using stem wall
construction, I certify that fill will be used only tohis the area within the stern wall.
- If fill material is to be used in any area, I certify that use of such fill Will not adversely affect adjacent
properties, If use of fill is found to adversely affect adjacent properties, the owner may be cited for violating
the conditions of the building permit issued under the attached permit application, for lots less than one (1)
acre which are elevated by fill, an engineered drainage plan is required,
If I am the AGENT FOR THE OWNER, I promise in good faim to Inforrin the tremor of The permitting conditions set forth in this affidavit prior to
commencing construction. I understand that a separate permit may be required for electrical work, plumbing, signs, wells, pools, air conditioning, gas, or
other installations not specifically included in the application, A permit issued shell be construed to be a license to p, ocead with the work and not as
authority to violate, correct, after, or set aside any provisions of the technical codes, nor shell issuance of a pemift prevent the Building Official from
thereafter requiring a correction of ono' in plans, construction or violations of any codes. Every permit issued shall become invalid unless the work
authorized by such permit is commenced within six months of parrift issuanca, or if work authorized by the permit is suspended a, abandoned for a
period of six (6) months after the time the work is commenced, An extension may be requested, in waiting, from the Building Official for a period not to
exceed ninety (90) bays and will demonstrate justifiable cause for the extension. It work ceases for ninety (90) consecutive days, the job Is considered
abandoned,
OWNER OR AGENT CONTRACTOR -�O—
Subscribed and aware to (or affirmed) orders me this Subscribed and sworn a (ar aQartaed) before INS
Who Ware personally known to me or haerhave produced Uavepar=uced
as mardificaborr. idenfification,
-----Notary Public Public
Commission No cominni o'nxkr—''
-4 1111
N eof otary typed. pumle— or stamped NarTia of Notary typillICA"il", st-8 t1l
AW.
0
org. 'ZOV
0 GG
Put
0,F
I
Specs for Windows 8 Slidi6jg glass
door
S
"n
ADDITIONAL NOTES
AS
tO k?W. Cv� 6A441—'D -fo f VC, ex.-terfofz
3-5iDrs; Vlosh-wie-AT,
";Ly,(o +0 p I.JoLo
is r
0
GULFSIDE SALEs AGREEMENT
Windows, Doors & More
R
nb O"",
420 Roberts Road OldsTriar, FL 34677 - 727-754-6648 - 941-777-5511 - 813-77
i,sna,w-gulbsidefl-house - SCC131152122 - info@90sidell,house BBB.
H0F1�1EOWNCRS -NANIC: the C.
14/01-1) Cr—
c-c W01-4,,/`—,
DATE: P tot
, rr
An,RESS:719
TEL: ?I 5
CITY: fM�zip:
�72
EMAIL: -c t1l,' \,votv)
ll:liMATED 111C OF INSTAIIII 10W
eci
,b,
REP;;M
CX
HOA Y E]
N
MH
E] 8LOCK 0 WOOD
REF, ROOM STYLI
$EPICS
V11 H
NEVLAR CRIDS COLOR IMPACT TEMP 001�
PC
73—
—
40 !212—
2 T3
Ole,
6 R
7 p
10
11
6�
12
36
6
All
'LOCATION
on
ADDITIONAL SCOPE or WORK AND OPTIONS NOT SHO',VN AGOVE,
YO N*C1 rough n) eflionisand are also this PrOfiray built prior 10 1978?
�f`YesDie undoM, gned agrees 10 the terms and Conditions of Cullsido WdEEm, altach Outlined OR tile fCSO%�ing
I
0 CaS IS More's Lead Safe 'Aimil Practices, if morierry tests positive for lead,
Goullsidev,411 notify buyer an id FWindowspecificabou Street
I 7V (O
facers, -7, ding 000, specificution Sheaf
wing Door F;pQcifi(,,droq Sheol
Buyer Signature
C:7 ---§TJfporR and Lanai Socciricotle, Sheet
Total Price*.
Down Payment:
CODi
$
Amount Financed:
If Financed, No, Dios_
Payment Method:
Cast) Check Credit/Debit Firianced
Check Number:
"Aff contracts subject to office
apprnvet
Buyer-
Gulfside Representative:
BIJJ YER'S RIG 11T TO CANCEL '
You, The buyvri may va,evi this trallsactioa ntally Hill, prior to
roidtlight Ofthe third businass day after tiln tiara 11"this tratlsnction
13"Ycr 1113YUSr, this contract as that allitke by writing-1 111,1ZEby
CANCEL" at the bottorn Rod addillill buyer's name, address ',',it Signature,
The notice Laust be, defivVicd to the Sailer it the address shidivo RjTuN,e,
FINAL PAY1"IENTS ARE CHECKICASH obiry
Scanned with am canner
GULFSIDE
Windows and Doors
Gulfside Sliding Door SPecification and Detail Sheet
In accordance with Gulftide Purchase Contract
727-754-6648 - $13-773-3000
/W- A Customer Name: 7//� e
Address:
phone: 51-0-'� - other,
Contract Dzj'e: 0/' - / - ;L I
CQ310me, Approval;
DOOR LOC4nON
COLOR
IMPACT
---%FASURE'
ACTUAL
1 5;4
EXT INT
W .
---
CONFIGURA'nON
(WXH) XX' OXXO HARDWARE
----
SCREENS
y N
GRIDS
Y / N ADDR10
I N
00
7ol X
X
X
X
4
.....................
X
X
-
-
7
--------------------
X
X
6
T— X
X
7
X
X
X
INTERIOR COLORS
COD
FRAME COLO V"HrrE BEIGE BRONZE NT. OAK DK- OAK N, CHERRY
(D
WHITE
js 0 BEIGE
— ------------
cr-1 BRONZE
0
R PEBBLE KHAKI
3
U)
0 LU ANODIZE
M
HUNTER GREEN
(D
RED
I RI C 1,
A- SPECIFY THE FOLLOWING:
Ic:"."-r1:no'o
f '�''7Ln'Right'tI.otsira'Ooin. "I
Customer acktunsw9es that the new sliding glass door vrifl
most Rely have a ider back that, the existing sliding gbets
door asaor door that is in the opening. Depending On the
Rat., of the -anpq structure, G.Ifsid. lbilavn Industry
standards for property fining the new door to the opening,
md.ding but not limited to, trimming the exterior Of trimming
the tx;sdnq noofing. in the event the customer has a preference
beeseeR the two methatis, pl.z� nonly Gullsid. H.Adq'�Zna'-
pnor to in'ut4atesn.
GULFSIDE
MOMM
i. a=wd..,� Ah GuNde Conbwt
727-754.6"8 - SUJ71-3000
Customer Name; M 10
Adems: -7 Iz �4-
L2
C. D..
Rzprewntlti.e Nam
cu" mer Apjxval:
Owamer A�
Bark
Left IsUlm Right
Front
Back
Left Znd -Floor Right
Front
GULFSIDE
Windovvs and Doors
U)
0
Cit
CL
3
co
0
W
(D
Cast —el Nerne: /R ,
Address: --qiL2--L9d
Phone: at3
Contract Date:
Representative
—�1� 4
, kmer -1-
LOCATION COLOR IMPACT MEASURE ACTUAL INSERT HANDING JAMS HINGE Sd.L
DOOR F (WXH) (Wxf4) INSERT 0 SIZE RH LH tS OS DEPTH FINISH FINISH HARDIMARE ADDMONAL INFORMATfON
x x
x x
3 x x
4 x
A ACTUAL HANDING_.... o XHT I WX.) TI- -XIMATI.N]
Ttzxl -i
3
r4
x EE6 x x
7 x x
x x
F—SILL FINISHES JAPAB FINISHES SINGLE DOORq,
I p 9
Ile
SMOOTH VVHH`E
f,,I)LL ALUMINUM
ggyy
BRONZE PRUVICO TEXTURED Left Hand Rkya Hand Left H400 Fight Hand
lns,vkq ImWag 0.ts.¢,q Oul%Wnq
JAMB DEPTHS AND TYPES DOVOLEDOOR
6 5 1/4 1 69/16 71/4
I. }Imj fiUht IL114 Wt IWO Waht 11-6
k*VOIaj Insv*9 Nvsv�q
Guffslde Swing Door Specification and Detail Sheet
In accordance with GulNde Purchase Contract
727-754-6648 - 813-773-3000
Product Manufacturer JELD-WEN
Address/Phone/Email 3737 Lakeport Blvd
Klamath Falls, OR 97601
(800) 535-3936
fbcl@jeld-wen,com
Authorized Signature Ryles Sumner Fricks
fbcl@jeld-wen.com
Technical Representative JELD-WEN Corporate Customer Service
Address/Phone/Email 3737 Lakeport Blvd,
Klamath Falls, OR 97601
(800) 535-3936
customerserviceagents@jeld -wen, com
Quality Assurance Representative
Address/Phone/Email
Category Windows
Subcategory Single Hung
Compliance Method Certification Mark or Listing
Certification Agency National Accreditation & Management Institute
Validated By National Accreditation & Management Institute
Referenced Standard and Year (of Standard) 5tan0arg YAM
TAS 201 1994
TAS 202 1994
TAS 203 1994
Equivalence of Product Standards
Certified By
I affirm that there are no changes in the new Florida Building
Code which affect my product(s) and my product(s) are in
compliance with the new Florida Building Code,
Documentation from approved Evaluation or Validation Entity Yes No N/A
M
Product Approval Method Method 1 Caption A
Date Submitted 07/29/2020
Date Validated 07/29/2020
Date Pending FBC: Approval
Date Approved 07/31/2020
Summary of Products
4
IFL# Model, Number or Name
; Description
14095.1 _._ . s Premium Atlantic Vinyl
Single Hung (8100) 36' x 72" Insulated Glass (5/16 in PVB or
SGP Lam - 118 out Annealed )
__-------- .
Limits of Use
( Certification Agency Certificate
i Approved for use in F VHZ., Yes
Approved for use outside HVHZ. Yes
i Quality Assurance Contract Expiration Date
€ Impact Resistant, Yes
04/30/2025
Design pressure, +651-70
Installation Instructions
Other. laminated glazing interiayer material requirements
meet the current edition of the FBC in accordance with Miami
, 7t 36x2 Tampa sta ics i s uctio s tl(
Dade NOA for DuPont SentryGlas and DuPont PVB interlayers.
i FLI 095 R11 T I I Sew s OT252017-,pdf C
White PVC exterior extrusion meet the current edition of the
Verified By: Hermes Norero, PE 73778
FBC in accordance with Miami -Dade NOA for Quanex. IG back
i Crested by independent Third Party: Yes
bedded with Dow 99a. Safety glazing required to the exterior at
Evaluation Reports
? heights above 30 feet.
Fl.1409S_.R_1 AE PER3094 pg
-- — _. _____ __
Created by independent Third Party: Yes
_ _ .. _ .. ..__ . _ __
14095.2 Premium Atlantic Vinyl
'Single Hung (8100) 36" x 72" insulated Glass (1/8 in - 1/8 out
Annealed)
Limits_ of use
Certification Agency Certificate
Approved for use in HVHZ: Yes
E—L95R-U- pdf I
Approved for use outside HVHZ: Yes
T i - Of
Impact Resistant, No
Pressure. +65/-70
Quality Assurance Contract Expiration Dante
� 04/30/2025
Design
Other. White PVC exterior extrusion meet the current edition
Installation Instructions
of the FBC in accordance with Mlami-Dade NOA for Quanex. IG
FL1409S II i011s67.09 R2 Dwgs.OZZ520j7,,pdf
back bedded with Dow 995. Safety glazing required to the
F 1 95 21 ii C3 7 6Pit
exterior at heights above 30 feet.
Verified By: Hermes Norero, PE 73778
j
Created by independent Third Party: Yes
Evaluation Reports
i F 14 95 E 9 7� 6- f
Created by Independent Third Party: Yes
--- .._._ . - --
14095.3 Premium Atlantic Vinyl
: Single Hung (8100) 52 1/8" x 75" Insulated Glass (3/16 in -
3/16 out Annealed)
_.�_
Limits of Use — _— ___ .. — m
( Certification Agency Certificate
Approved for use In HVHZ. Yee
FL14095 Rif C f Aim NI01156�Pdf
Approved for use outside HVHZ: Yes
l FLI4Q95 Rii C AC NI011567 0?-R2 Pdf
i Impact Resistant. No
Quality Assurance Contract Expiration Date
Design Pressure. +65/-70
Other: White PVC exterior extrusion meet the current edition
� 04/30/2025
Installation Instructions
of the FBC in accordance with Miami -Dade NOA for Quanex. IG
&_02 2520;7;pcig
back bedded with Dow 995. Windows with insulated glass wider
j FLl Q95 212_ii P V T H BC 2 75 SS 017-06-26 pdf
than 36" require setting blocks. Safety glazing required to the
Verified By: Hermes Norero, PE 73778
exterior at heights above 30 feet.
Created by Independent Third Party; Yes
Evaluation Reports
i F. 01 A
Created by Independent Third Party: Yes
14095 4 Premium Atlantic Vinyl
Single Hung (8100) 52 1/8" x 75" Insulated Glass (5/16 in PVB
or SGP Lam - 1/8 out Annealed)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ. Yes
FE 4C}95 R7 67 2- 2
Approved for use outside HVHZ. Yes
Quality Assurance Contract Expiration Date
impact Resistant. Yes
04/30/2025
Design pressure. +50/-60
installation Instructions
Other. Laminated glazing intedayer material requirements
095 FL 35 S I DP50-
meet the current edition of the FBC in accordance with Miami-
60 52.2S 5 Import installation strut io s p f
Dade NOA for DuPont SentryGlas and DuPont PVB interlayers.
F I4 Ei95 R2 Ta_ I0672 icyg 0_,.7_2r, I%df
White PVC exterior extrusion meet the current edition of the
i Verified By: Hermes Norero, PE 73778
FBC in accordance with Miami -Dade NOA for Quanex, IG back
Created by Independent Third Party. Yes
bedded with Dow 995. Windows with insulated glass wider than
Evaluation Reports
36" require setting blocks. Safety glazing required to the
FL14095 bill AE PER3091 cif
exterior at heights above 30 feet.
Created by Independent Third Party. Yes
14095,5 Premium Atlantic Vinyl
Single Hung (8100) 52 1/8" x 75" Insulated Glass (5/16 in SGP
Lam 3/16 out Annealed)
...
'
Limits of Use
Approved for use In HVHZ: Yes
Approved for use outside HVHZ: Yes
Impact Resistant, Yes
Design Pressure: +65/-75
Other, Laminated glazing interlayer material requirements
meet the current edition of the FBC In accordance with Miami -
Dade NOA for DuPont SentryGlas and DuPont PVB interlayers.
White PVC exterior extrusion meet the current edition of the
FBC in accordance with Miami -Dade NOA for Quanex, IG back
bedded with Dow 995. Windows with insulated glass wider than
36" require setting blocks, Safety glazing required to the
exterior at heights above 30 feet.
Certification Agency Certificate
Quality Assurance Contract Expiration Date
04/30/2025
Installation Instructions
LUMMILI&
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
Created by Independent Third Party: Yes
The State of Florida Is an AA/E 0 employer. _q2pyr E �lqbt 2007 2p�z13 State of Florida vary Statement �,sslblli .5tateMent t: &fund Statgrient _ jj
Under Florida law, email addresses are public records, If you do not want your e-mail address released In response to a public -records request, do not send electronic
mail to this entity, Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 650.487,1395. -Pursuant to Section 455,27S(I),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S, must provide the Department with an email address If they have one, The emails
provided may be used for official communication with the licensee, However email addresses are public record. If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public. To determine If you are a licensee under Chapter 455, RS„ please click here .
Product Approval Accepts.
M WINEEM
CERTIFICATION NO: N1011567.08-RI
DATE: 05/23/2013
CERTIFICATION PROGRAM: Structural
COMPANY: JELD-WEN_
CODE: 1822-1
REVISION DATE: 01/13/2017
To verify that the "Notice of Product Certification" is valid, please visit www,NAMICertification.com to assize that the
product is active and currently listed. This certification represents product conformity to the applicable specification and
that certification criteria has been satisfied, A NAMI approved certification label must be applied to the product to claim
certification status. Please review and advise NA MT if any corrections are required to this document
COMPANY NAME AND ADDRESS
JELD-WEN
3737 Lakeport Boulevard
Klamath Falls, OR 97601
SPECIFICATION
TAS 202-94
PRODUCT DESCRIPTION
"Premium Atlantic Vinyl Single Hung (8100)"
Vinyl Single Hung Window
(Fin Installation)
Configuration: O/X
Glazing. Insulating Glass (Annealed)
Frame: W-914mm(36") H-1829mm(72")
Sash: W-845mm(33.25") H-883mm(34,75")
PRODUCT RATING
Design Pressure: +65/-70 psf
Product Tested By: National Certified Testing Laboratories
Report No: NCTL-210-3877-1
Expiration Date: April 302025
Administrator's Signature-,
MANAGEMENT INSTITUTE, INC.
4794 George Washington Memorial Highway
Hayes, VA 23072
Tel: (804) 684-5124
Fax: (804) 684-5122
MAX, TARN
NAP IN
W1400W XN011H
TYPICAL ELEVATIQN WITH FASTENER SPACING
Installation Notes;
1, Seat flangelframe to substrate,
2. Use #10 PH or greater fastener though the nail fin with sufficient length to penetrate a minimum of 11/2"
into the wood framing. For 2X wood frame substrate (min. S,G, = O42),
3. Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads to
the structure. The host structure is the responsibility of the architect or engineer of record for the project
of installation. Addendurn to NAMI
Certification No: NI011567,09-R2
Reviewed By: 211Q,"
This schedule addresses only the fasteners required to anchor the Date Reviewed: 0-7/25/2017
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the Installation process and does
not address he sealing consideration that may arise in different wall
conditions. For the complete Installation procedure, see the instructions
packaged with the window or go to
www.field-wen.co.m/resourcesfinstallafion.
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc, 'AS TESTED'
I I/Z' MIN, EMBEDMENT
MIN DISTANCE
POP. EDGE: 3/4'
114'MAX '
CHU SPACE
FRAME 5EMONA7Y�P)
VEPTICAL SECTION
1/4' MAX
5iir.M SPACE
MIN. OISTANC�
F'DA 8DX,
'E3/4
NAIL FIN INSTALLATION
max Frame 1DPRATINGN-PACT11
36 x 72 +65/-70 ' NO
General Notes-
1, The product shown herein is designed, tested and manufactured to comply with the wind load cmeria
of the adopted international Building Code (IBC), the International Residential Code (IRC), the Florida
Building Code (FBC) and the industry requirement for the stated conditions,
2, All glazing shall conform to ASTM El 300
3, At minimum, glazing shall be 3,Omm annealed Insulating glass,
4. Use structural or composite shims where required.
PROJECT ENGINEER:
07/24/2017 1 jEL13r_WEN 3250 Lakeport Blvd
_6R—AWNBY: Klamath Falls, M 97601
J.HAWKINS Nib Phone, (541) 882-3451
CNBY: ME
D , BELAU I
APPROVED BY: i Premium Atlantic Vinyl Single Hung Window
1GOOSSEN 1
IDENT[FIER No. j PUNT
mv� sf'-:
�PiaMAT�V -RE NCTL 210 3877-1 sH Geri A is 3 Of 4
PremATLVInASH Gert I
5.5
MAX,
FROM
CO-E.5
J
A
lit
---- - ------ -
IYPICAL ELEV,�EON_WITIjEA , R 5PACII�G
_ _ _
'—MAX, THRU
dmNB
Installation Notes:
1. Seal flange/frame to substrate.
2, Use #10 PH or greater fastener though the frame with sufficient length to penetrate a minimum of 11/2"
into the wood framing, For 2X wood frame substrate (min, S.G, = 0.42).
1 Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
tothe structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation. Addendum to NAMI
Certification No: NI011567.09-R2
Reviewed By:
This schedule addresses only the fasteners required to anchor the !)ate Reviewed: 07/25/2017
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he sealing consideration that may arise in different wall
conditions. For the complete installation procedure, see the instructions
packaged with the window or go to
�,vww,jeld-nen,com/resourceslip,stallafion.
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELL -WEN Inc. as TEt;TE-D'
MIN, DISTANCE
FOR EDGE: 3/4
EMOR)MENT
2" MIN,
MAX
-TO SHIM SPACE
FRAME SEC17ON (D�Pj
VEPTTCAL SECTION
1/4'MAX
5H7M SPACE
I'HROUGH FRAME
INSTALLA'FION
1112' MIN,
EMBEDMENT
1/4' MAX
SHIM SPACE
MIN. DISTANCE
2
FOR E06E: 3/4" i
JAMS SECTI �qN M�P)
HORIZONTAL SECTION
'r A
Max Frome I DP RATINI&I I41MY11P A C, T II
F
NO
General Notes:
1. The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBQ), the International Residential Code (IRC), the Florida
Building Code (FBC) and the industry requirement for the stated conditions,
Z All glazing shall conform to AST M E1300,
3. At minimum, glazing shall be 3,Omm annealed insulating glass.
4, Use structural or composite shims where required,
eKujt,� 3250 Lake ort Blvd
-3Y 07/p
24/2017 1 JELDvWENK]amath Falls, OR, 97601
DAA YN SC�Li,
J.HAWKINS NTS Phone: (541) 882-3451
CHECKED Or, Tf-RE�
D.BELAU
A PROVED BY; Premium Atlantic Vinyl Single Hung Window
I.GOOSSEN
in—EAMHER —Na —m, ui6a�fopm, _R-EV; -! -SHEff
110-16-135 A ;
2 OF 4
2
5.5,
MAX.
FROM
CORKRE
V.P.
—T
MAX THRU
tAMB
�-- WINDOW WIDTH (36' MAX,) ----I
TYPICAL ELFVATION WITH FASTENER SPACING
6' MAX.
FROM
CORNERS
F— #11N. CITSTANCF MASONRY INSTALLATION
FOP EWE, 2 Ur
BLOCK
—1 1/4'MIN,
3 EMBEDMENT
E919EIDMENT
--!/4- MAX MAX
SHIM SPACE SHIM SPACE
MEN. OTSTA
FOR EDGE: 2 1/2, 11 2
FRAME SECTZ(7N (TYPE �
VERTICAL SECTION
MASONRY
8LOCK
LAMS qCTIQ 5TYP
HORIZONTAL SECTION
J1 1/4' MAX
SHIM SPACE
P
L—+x K Ma— 6::x Frame A TING IMPACT
"a I- 7+65LT__
i� -"LO f3:.� ��
BLOCK
Installation Notes:
1. Seal flange/frame to substrate.
Z Use 3116" ITW Tapoon or equivalent fasteners through frame Mth sufficient length to penetrate a
minimum of 11/4" into concrete or masonry at each location with a 2 1/2' min from edge distance. For
concrete (min, fc= 3000psi) or masonry substrate (CMU shall adhere toASTM C90)
1 Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
packaged with the window or go to
www,jeld-wen.com/resourcesrinstallafion.
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc,
10-
7
0; ir
441
"o
398 East Dan MINTAlvd., 'Lite 338
Dania Beach, FL 33004
General Notes:
1. The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted international Building Gode(IBC), the International Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions,
2. All glazing shall conform to ASTM E1300.
& At minimum, glazing shall be 1/8" annealed insulating glass.
4. Use structural or composite shims where required.
5, Installation methods can be interchanged within the same opening,
6, An impact protective system is required where wind home debris protection is mandated by local
building code. I
7, Maximum sizes are buck sizes and do not include fin or flange.
PROJECT ENGINEER: DATE:
04/26/2017 3250 Lakeport Blvd
FBY. SCALE: JEI Vdamath Falls, OR. 97601
RAWN D-WEN
1HAWKINS NTS Phone: (541) 882-3451
CHECKED BY. TOU:
D.BELALI
APPROVED BY. Premium Atlantic Vinyl Single Hung Window
11300SSEN
PARTUIROWP
1 4------
-X71��3 OF 4
LDENTIFIEii No. PLANT NAME AND L=TION: CAD DWG. No,: REV;
5's,
MAX.
f-7 FROM
CORNESS
p/r v M, 0 7,- ,
6' MAX.
rR am
i CORNERS
I
—a-lo .1.1 (W MAX.) --------- — — i
'TYPICAL ELEVATIQN VVITH FASTENER SPACING
Installation Notes:
1, Sea] flange/frame to substrate,
2. For anchoring into metal framing use #8 TEK Self Tapping
Doing screws with sufficient length to achieve a
minimum embedment of three threads past the frame thickness. Steel substrate min, 18ga, fy = 33 list
3. Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all leads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
window to achieve the rated design pressure up to the size limitations
not address he sealing consideration that may arise in different wall
For the Complete installation , rocedure- see the instructions
packaged with the window or go to
www.jeld-wen,com/resourcesr,nstallabon.
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc.
NA
91
a
MD,L DISTANCE
FOR ENSE: 1/2'
,,an. .1,4ee-0
f thr- threads
Best fvrvne
_ S8 gauge min
5t-A Stud
1/4' MAX
SHIM SPACE
18 gauge min
Steel Stud
MIN, DISTANCE
FOR EDGE, 1/2'
Min, embedment
of three threads
post frame
STEEL INSTALLATION
1/4" MAX
SHIM SPACE
1/4' MAX
5HIAk SPACE
[:tt M3rcI rnn—-' 111'M--P--f
6 x 72 +65/-7
NO
General Notes,
1. The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code(IBC), the International Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTM E1300.
3, At minimum, glazing shall be 118" annealed Insulating glass.
4. Use structural or composite shims where required.
5. Installation methods can be interchanged within the same opening.
6. An impact protective system is required where wind dome debris protection is mandated by local
building code,
7. Maximum sizes are buck sizes and do not include fin or flange,
PROJECT ENCTNEIER: DATE: 04/26 3250 Lakeport Blvd
JELD-WENKJamath Falls, OR. 97601
DRAWN BY; I I
1HAWKINS NTS Phone: (541) 882-3451
--G CHECKED BY: UTLE:
-)3 44J Z D.BELAU
4 PROVED SSPremium Atlanfic Vinyl Single Hung Window
APM
EN I GOO
ARTUiNk
398 East 11..1d fA 19VMd_ Suite 338 1DENnFIER No' PLANT NAME AND LCCATION:
'
Dania Beach, FL 33004
i,A
Product Manufacturer JELD-WEN
Address/Phone/Email 3737 Lakeport Blvd
Klamath Falls, OR 97601
(800) 535-3936
fbcl@jeld-wen.com
Authorized Signature Ryles Sumner Fricks
fbcl@jeld-wen.com
Technical Representative JELD-WEN Corporate Customer Service
Address/Phone/Email 3737 Lakeport Blvd.
Klamath Falls, OR 97601
(800) 535-3936
customerserviceagents@jeId-wen.com
Quality Assurance Representative
Address/Phone/Email
Category Windows
Subcategory Single Hung
Compliance Method Certification Mark or Listing
Certification Agency National Accreditation & Management Institute
Validated By National Accreditation & Management institute
Referenced Standard and Year (of Standard) Sla--nd"r YAM
TAS 201 1994
TAS 202 1994
TAS 203 1994
Equivalence of Product Standards
Certified By
mmzmm���
L"W"11"ANOW,
Documentation from approved Evaluation or Validation Entity Yes No N/A
. 0"o .
Product Approval Method Method I Option A
Date Submitted 07/29/2020
Date Validated 07/29/2020
Date Pending FBC Approval
Date Approved 07/31/2020
Summary of Products
FL # Model, Number or Name
Description
'T
114095,1 1 Premium Atlantic Vinyl
Single Hung (8100) 36" x 72" Insulated Glass (5/16 in PVB or
SGP Lam - 1/8 out Annealed
Limits of Use
i Certification Agency Certificate
Approved for use in HVHZ. Yes
Approved for use outside HVHZ: Yes
Quality Assurance Contract Expiration Date
Impact Resistarillo Yes
04/30/2025
Design Pressure: +65/-70
Installation Instructions
Other. Laminated glazing Interlayer material requirements
meet the current edition of the FBC in accordance with Miami-
; 7Q7R Ista tEo I stru ti S
jj Dade NOA for DuPont SentryGlas and DuPont PVB interlayers.
White PVC exterior extrusion meet the current edition of the
Verified BY: Hermes Norero, PE 73778
FBC in accordance with Miami -Dade NOA for Quanex' IG back
Created by Independent Third Party: Yes
bedded with Dow 995, Safety glazing required to the exterior at
Evaluation Reports
heights above 30 feet.
Created by Independent Third Party: Yes
----- ------
I 14095.2 Premium Atlantic Vinyl
Single Hung (8100) 36" x 72" Insulated Glass (1/8 in - 1/8 out
Annealed)
Lino - ----
i------
of Use
I
Ilts Certification Agency Certificate
j Approved for use in HVHZ.* Yes
Of
Approved for use outside HVHZ. Yes
40f I
Impact Resistant, No
Pressure: +65/-70
Quality Assurance Contract Expiration Date
04/30/2025
Design
Other. White PVC exterior extrusion meet the current edition
Installation Instructions
1 of the FBC In accordance with Miaml-Dade NOA for Quanex, IG
.Q�Q 7 gof
11 back bedded with Dow 99S, Safety glazing required to the
exterior at heights above 30 feet.
Verified By: Hermes Norero, PE 73778
Created by independent Third Party: Yes
Evaluation Reports
Created by Independent Third Party. Yes
140953 i Premium Atlantic Vinyl
Single Hung (8100) 52 1/8" x 75" Insulated Glass (3/16 in -
3/16 out Annealed)
Limits of Use
Certification Agency Certificate
I Approved tor use in HVHZ: Yes
Approved for use outside HVHZ. Yes
impact Resistant. No
Quality Assurance Contract Expiration Date
Design Pressure. +65/-70
04/30/2025
Other: White PVC exterior extrusion meet the current edition
Installation instructions
I of the FBC In accordance with Miami -Dade NOA for Quanex. IG
&RZ_25_2017,p4ff
back bedded with Dow 995. Windows with Insulated glass wider
5 SS 017-0_6-26 Bgf
than 36" require setting blocks. Safety glazing required to the
feet.
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
exterior at heights above 30
Evaluation Reports
--
FL------ -- --PAI
ated by Independent Third Party- Yes
Created
---- ------
14095A Premium Atlantic Vinyl
'Single Hung (8100) 52 1/8" x 75" Insulated Glass (5/16 In PVB
or SGP Lam - 1/8 out Annealed)
I Limits of Use
Certification Agency Certificate
Approved for use In HVHZ: Yes
Approved for use outside HVHZ. Yes
Quality Assurance Contract Expiration Date
impact Resistant. Yes
04/30/2025
Design Pressure: +50/-60
Installation Instructions
Other- Laminated glazing intedayer material requirements
Miami-
i L 0 5 1 1 F AnQr Rq Ty QW;
io s
i meet the current edition of the FBC in accordance with
Dade NOA for DuPont SentryGlas and DuPont PVB interlayers.
st g4f
FC140 5 1291 Ii N 011 67 Q2 R2 Dwgs 07 52017df
White PVC exterior extrusion meet the current edition of the
I Verified By: Hermes Norero, PE 73778
FBC in accordance with Miami -Dade NOA for Quanex. IG back
I Created by Independent Third Party: Yes
bedded with Dow 995, Windows with insulated glass wider than
Evaluation Reports
36" require setting blocks. Safety glazing required to the
Ed40i9_5 Fi11 AE PEit30 1 df
exterior at heights above 30 feet.
F
I Created by Independent Third Party: Yes
1i 14095,5 Premium Atlantic Vinyl
i Single Hung (8100) 52 1/8" x 75" Insulated Glass (5/16 in SGP
Lam - 3/16 out Annealed)
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: Yes
Impact Resistant: Yes
Design Pressure: +65/-75
Other; Laminated glazing interlayer material requirements
meet the current edition of the FBC In accordance with Miami
Dade NCIA for DuPont SentryGlas and DuPont PVB interlaye
White PVC exterior extrusion meet the current edition of the
c FBC in accordance with Miami -Dade NOA for Quanex. IG bal
36" require setting blocks, Safety glazing required to the
exterior at heights above 30 feetI
Certification Agency Certificate
Quality Assurance Contract Expiration Date
04/30/2025
Installation Instructions
9-MMILI&
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
ELUQ21JU1_ALY_MU2LPJf
Created by Independent Third Party: Yes
JZ3_91Lhang;&�
The State of Florida Is an AA/EEO employer. Core qhL2007-_Z0.j3 Sf ptq of Florida, :: LlLvpcKqtittemen essibi lity Statement:: &fUnd Ste 1g,rent
Under Florida law, email addresses are public records. If you do not want your e-mail address released In response to a public -records request, do not send electronic
mail to this entity, Instead, contact the office by phone or by traditional mail, If you have any questions, please contact 850,487,1395, *Pursuant to Section 455,275(7.),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address If they have one. The emalls
provided may be used for official communication with the licensee. However email addresses are public record, If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public. To determine If you are a licensee under Chapter 455, F.S., please click bgeM,
Product Approval Accepts.
ice
WINEgm
Credit Card
Safe
CERTIF41CATION NO.
DATE:
CERTIFICATION PROGRAM:
COMPANY:
CODE:
REVISION DATE:
N1011567.08-R1
05/23/2013
Structural
JELD-WEN
1822-1
01/13/2017
To verify that the "Notice of Product Certification" is valid, please visit www,NTAMICertification.com to assure that the
product is active and currently listed. This certification represents product conformity to the applicable specification and
that certification criteria has been satisfied, ANAMI approved certification label must be applied to the product to claim
certification status, Please review and advise NA MT if any corrections are required to this document.
COMPANY NAME AND ADDRESS
JELD-WEN
3737 Lakeport Boulevard
Klamath Falls, OR 97601
SPECIFICATION
TAS 202-94
PRODUCT DESCRIPTION
"Premium Atlantic Vinyl Single Hung (8100)"
Vinyl Single Hung Window
(Fin Installation)
Configuration: O/X
Glazing: Insulating Glass (Annealed)
Frame: W-914mm(36") H-1829mm(72")
Sash: W-845mm(33,25") H-883mm(34,75")
PRODUCT RATING
Design Pressure: +65/-70 psf
Product Tested By. National Certified Testing Laboratories
Report No: NCTL-210-3877-1
Expiration Date: ApdjR.ML5
Administrator's Signature:
NATIONAL ACCREDITATION AND
MANAGEMENT INSTITUTE, INC.
4794 George Washington Memorial Highway
Hayes, VA 23072
Tel: (804) 684-5124
Fax: (804) 684-5122
MAX. THRU
NAIL FIN dl
13 gg&/
C04NERS
H
XNNDOW VX07 N (36- UAX.) ---------
TYPICAL ELEVATION WITH FASTENER SPACING
Installation Notes:
1, Seat flange/frame to substrate,
Z Use #10 PH or greater fastener though the nail fin with sufficient length to penetrate a minimum of 11/2"
into the wood framing, For 2X wood frame substrate (min, S.U. = 0,42).
1 Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads to
the structure. The host structure is the responsibility of the architect or engineer of record for the project
of installation. Addendum to NAMI
Certification No; N1011567,09-R2
Reviewed By:21 I
This schedule addresses only the fasteners required to anchor the Date Reviewed: 07/2 5/20 17
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he sealing consideration that may arise in different wall
conditions, For the complete installation procedure, see the instructions
packaged with the window or go to
www,jeld-wen.com/resourcesfinstallation,
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc. 'AS TESTED'
NAIL, FIN INSTALLATION
Max Frame iDP RATIN . fM-P�ACTIl
+65/-70 E90C]
General Notes:
1. The product shown herein is designed, tested and manufactured to comply with the Wind load Criteria
of the adopted international Building Code (113G), the Intemational Residential Code (IRC), the Florida
Building Code (FBO) and the industry requirement for the stated Conditions,
Z All glazing shall conform to ASTM E1300,
1 At minimum, glazing shall be 3,0rnm annealed insulating glass,
4. Use structural or composite shims where required,
PROJECT ENGINEM 1 DATA
3250 Lakeport Blvd
07/24/2017 1
- ------ Klamath Falls, OR. 97601
15fVNIII, JELD-WEN
J.HAWKINS i 51
CHECKED BY: 1 ITTLE;
D.BELAU i
APPROVED BY: Premium Atlantic Vinyl Single Hung Window
1GOO SSEN I
:AD DWG, No,; I REV: SHEET
PrerRATI.ViAOSH Cert 1 Al 30F4
a,5,
MAX.
PRO.
COR.ERS
�I lit
g,
- -- - 111.vll. ..'� (36" MAX,) - - - - - - - 1
TYPICAL ELEVATION WITH FASTENER SPACINC
MAX THRU
6" —
FROM
1:OR.ER5
Installation Notes:
1. Sea] flange/frame to substrate,
2, Use #10 PH or greater fastener though the frame with sufficient length to penetrate a minimum of 11/2"
into the wood framing. For 2X wood frame substrate (min, S.G. = CA2).
3. Host structure (wood buck, masonry, steel) to be designed and anchored to properly transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation. Addendum to NAMI
Certification No: N1011567-09-R2
Reviewed By
This schedule addresses only the fasteners required to anchorthe Date Rev.-ewed: 07/25/201')
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he seating consideration that may arise in different wall
conditions, For the complete installation procedure, see the instructions
packaged with the window or go to
wAv.jeld-wen.com/fasources/lnstallabon.
DISCLAIMER
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELL} -WEN Inc, I AS TESTED'
MIN, DISTAIXE
FOP, EDrE; 3/4'
MEN
1/4" MAX
SHIM SPACE
FRAME SKciTC7R3 �TYP
%FE—ATTcAL SEMON
1/4' MAX ,5HW SPACE
RMM71=
THROUGH FRAME
INSTALLATION
11/2" MIN.
EMOEDMENT
1/4' X A&A
SHIM SPACE
�-J - ------
I -
MIN. DISTANCE
FOR Ea6E; 3/4'
r2",
JAMB SECTI9t!LTXP)
HORIZONTAL SECTION
Max Frame DP RATING IMPACT
L
+65
�6 x 72.1 _,__/-70 NO----J'
1. The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (113C), the International Residential Code (IRC), the Honda
Building Code (FBC) and the industry requirement for the stated conditions,
2. All glazing shall conform to ASTIR El 300,
3, At minimum, glazing shall be 3,Omm annealed insulating glass.
4, Use structural or composite shims where required.
3250 Lakeport Blvd
07/24/2017
7-
&k4wWiY—;-- JELD-WENKiamath Falls, OR, 97601
1HAWKINS NTS Phone: (541) 882-3451
CHECAEi3 BY; nTLE;
D,BELAU
WROVED Ey" Premium Atlantic Vinyl Single Hung Window
I.GOOSSEN
IDENnFIER NO, I CAD C7bvG. NO REV:
110-16-135 PremATLVfnySH Cel ASHEET Z Of 4
MAX.
FROM
CORNERS
MAX. TH V
JAMS
CORNERS
� —WJNDOW W107H (36- MAX.) - — -----
Installation Notes:
1, Seal flangelframe to substrate,
Z Use 3116' ITW Tapcon or equivalent fasteners through frame vvith sufficient length to penetrate a
minimum of 1114" into concrete or masonry at each location with a 2 1/2" min from edge distance, For
concrete (min, ft = 3000psi) or masonry substrate (CMU shall adhere to ASTM C90)
3. Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
WAVE
not address he sealing consideration that may arlse in different wall
conditions. For the complete installation procedure, see the instructions
packaged vft the window or go to
www,jeld-wen.corri/resourcesrinstallaton.
DISCIAIMER:
This drawing and its contents are confidential and are not to be
7 1
except as authorized by JELD-WEN Inc,
1114' #M4.
3 V4* MAX
5iffM -' OACE
MM4, DtSTAWE
FOR FN5E: 2 W, 2
MASOMY— U
9LOCK
TAMR 5ECT19 'TIJP AL
HORtZONTAL SECTION
L__�16 x 72
General Notes:
1The product shown herein is designed, tested and manufactured to comply writh the wind load criteria
of the adopted International Building Code(IBC), the international Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTM E1300.
& At minimum, glazing shall be 1/8' annealed insulating glass.
4Use structural or composite shims where required
5Installation methods can be interchanged Within the same opening.
6, An impact protective system is required where Wind bome debris protection is mandated by local
building code,
7. Maximum sizes are buck sizes and do not include fin or flange.
0
.X
PR03ECr ENGINEER:
gpfjJ
DRAWN BY:
JIUS
.HAWN
T T
441
44;
CHECKED BY:
D.BELAU
(D
'N
APPROVED BY:
1GOOSSEN
E
p6r(0497
B
RXEATTIFIER NO,
398 East D.MMINTAlvd- s.ile 338
Dania Beach. FL 33004
3250 Lakeport Blvd
JELRVENKlamath Falls, OR. 97601
Phone: (541) 882-3451
CAD DWG. No.; I aEV11 A I "" 30F4
A
e A
s s"
MAX.
FROM
CORNERS
.1-T. (36- MAX,)
TYPICAL ELEVATION WITH FASTENER SPACING
Installation Notes:
1, Seal flangelframe to substrate.
Z For anchoring into metal framing use #8 TEK Self Tapping screws with Sufficient length to achieve a
minimum embedment of three threads past the frame thickness. Steel substrate min, 18ga,, fy = 33 ksi,
3, Host structure (wood buck, masonry, steel) to be designed and anchored to properly transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
window, to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he sealing consideration that may arise in different wall
conditions. For the complete installation procedure, see the instructions
packaged with the window or go to
www.,ield-wen.comlresourx;esrinstallabon.
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc.
Digitally siggiib) MRY 0,1 ro,P,E.
'
Reason: l'q Date: Reason:
0 0,
T T
-0
781
- :-4-
%
0
Dania Beach, FL 33004
MIN. DISTANCE
FOR ED'Az 1/2'
MR, hlbdment
—'T r-ds
a ga-9—i.
51-1 Stw
1/4' MAX SHIM SPACE
18
Steel Stud
MIN. DISTANCE
FOR EDGE: 1/2'
Min, embedment
of three threads
past frame
STEEL INsTALLATION
1/4' MAX
SHIM SPACE
JAMB SECTION (TYP)
HORIZONTAL SECTION
1/4' MAX
5HrM SPACE
Max Frame DP RATINGTN—PA—C-fl,
M'
P36 x 72 J +65/-70 NO I
General Notes:
I , The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted international Building Code(IBC), the International Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions.
2, All glazing shall conform to ASTM E1300.
3. At minimum, glazing shall be 1/8" annealed insulating glass,
4. Use structural or composite shims where required.
5installation methods can be interchanged within the same opening.
6, An impact protective system is required where wind bome debris protection is mandated by local
building code.
7, Maximum sizes are buck sizes and do not include fin or flange.
PROMCr ENGINEER: DATE: 3250 Lakeport Blvd
04/26/201
DRAWN BY', SCALE. JE LD-WEN Klamath Falls, OR. 97601
1HAWKINS NTS Phone: (541) 882-3451
01ECKED By, nTLE:
D,BELAU I
APPROVED BY: Premium Atlantic Vinyl Single Hung Window
J.GOOSSEN
PARURCOf
No * I
7
OMPTER ft PLANT NAME AND LOCA70N: CAD DWG, NO,: REV-, A ISHEET 4 ORA
Publications Contact Us BCJS Site Map Links Search
d b'
'giproduct Approval
R9 USER: Public User r m f
EM".AQRMMLM_qW > fteluct eL Ap e= > An .Riiogaj�L _p Scat o L,ist > Application Detail
FL #
FL14090-RI2
Application Type
Revision
Code Version
2020
Application Status
Approved
*Approved by DBPR. Approvals by DSPR shall be reviewed and ratified by
the POC and/or the Commission If necessary.
M
Product Manufacturer
Address/Phone/Email
Authorized Signature
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory
IfflZm9asmEflow
Referenced Standard and Year (of Standard)
i
Equivalence of Product Standards
Certified By
Product Approval Method
,JELL -LIEN
3737 Lakeport Blvd
Klamath Falls, OR 97601
(800) 535-3936
fbcl@jeld-wen.com
JELD-WEN Corporate Customer Service
3737 Lakeport Blvd.
Klamath Falls, OR 97601
(800) 535-3936
customerserviceagents@jeld-wen,com
Windows
Horizontal Slider
Certification Mark or Listing
National Accreditation & Management Institute
National Accreditation & Management Institute
Method I Option A
Date Submitted 11/18/2020
I
Date Validated
Date Pending FBC Approval
Date Approved
FL * el, Number om r Marne
_1_111_11 ------- - -------- 0 ol
14090�1 , Premium Atlantic Vinyl
11/19/2020
11124/2020
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ. Yes
Impact Resistant. No
Design Pressure, +50/-55
Other* Windows with insulated glass units wider than 36"
requirements meet the current edition of the FBC in
150.Mt
DuPont PVB interlayers.
14090a2 1 Premium Atlantic Vinyl
Limits of Use
Approved for use in HVHZ- Yes
Approved for use outside HVhZ: Yes
Impact Resistant: No
Design Pressure: +65/-70
Other: Windows with insulated glass units wider than 36"
require setting blocks. Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance with Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB interlayers.
140903 1 Premium Atlantic Vinyl
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ- Yes
Impact Resistant., Yes
Design Pressure: +50/-55
Other. Windows w/ IG units wider than 36" require setting
blocks. These windows do not meet small missile impact
wind-borne requirements of the current edition of the FBC
when the exterior lite Is annealed, they do meet small missile
impact wind-borne protection requirements when the exterior
lite is tempered. Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB Interlayers,
14090A j Premium Atlantic Vinyl
Limits of Use
Approved for use in HVHZ-. Yes
Approved for use outside HVHZ: Yes
Impact Resistant* Yes
Design Pressure: +50/-55
Other: Windows w/ IG units wider than 36" require setting
blocks. These windows do not meet small missile impact
wind-borne requirements of the current edition of the F8C
0�io�'Jhj exte i ior i ite is annealed i the 0 do meet small missile
lite is tempered, Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB intertayers.
14090.5 1 Premium Atlantic Vinyl
Description
Horizontal Slider (8200) 74" x 62' Insulated Glass (3/16 in -
3/16 out Annealed)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
07/31/2025
Installation Instructions
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
ELI4M-RIZ—AL—PER1195—aff
Created by Independent Third Party: Yes
Horizontal Slider (8200) 74" x 54' Insulated Glass (3/16 in -
3/16 out Annealed)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
07/3112025
Installation Instructions
BU
Verified By: Hermes Norero, PE 73778
Created by IndependentT'hird Party: Yes
Evaluation Reports
ELUMAU_Ag.��
Created by Independent Third Party: Yes
Lam in - 3116 Annealed out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
08/30/2025
Installation Instructions
EL14090 R12 11 DP50-
5�4�x6Z l stalta ion Instructonsp F
Verified By: Hermes Norero 73778
Created by Independent Third Party: Yes
Evaluation Reports
EL14090 R12 AE PER3103.pfff
Created by Independent Third Party: Yes
Horizontal Slider (8200) 74" x 54" Insulated Glass (5/16 PVB
Lam in - 1/8 Annealed out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
10131/2025
Installation Instructions
55_74x_54LMI jqsLaA_atio
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
Created by Independent Third Party: Yes
Horizontal Slider (8200) 74" x 54" Insulated Glass (5/16 SGP
Lam in - 118 Annealed out)
Limits of Use Certification Agency Certificate
Approved for use in HVHZ-. Yes
Approved for use outside HVHZ- Yes Quality Assurance Contract Expiration Date
impact Resistant* Yes 08/30/2025
Design Pressure. +60/-65 Installation Instructions
Other., Windows w/ IG units wider than 36" require setting 5�!AQ20_R12 _11DP60-
blocks, These windows do not meet small missile Impact
wind-borne requirements of the current edition of the FBC
Verified By: Hermes Norero, PE 73778
when the exterior lite is annealed, they do meet small missile
Created by Independent Third Party: Yes
impact wind-borne protection requirements when the exterior
Evaluation Reports
lite Is tempered. Laminated glazing interlayer material
requirements meet the current edition of the FBC in
Created by Independent Third Party: Yes
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB interlayem
14090.6 1 Premium Atlantic Vinyl
Limits of Use
Approved for use In HVHZ. Yes
Approved for use outside HVHZ. Yes
Impact Resistant., Yes
Design Pressure: +50/-50
Other, Windows w/ IG units wider than 36" require setting
blocks. These windows do not meet small missile Impact
wind-borne requirements of the current edition of the FBC
when the exterior lite Is annealed, they do meet small missile
Impact wind-borne protection requirements when the exterior
lite Is tempered. Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB interlayers.
14090,7 1 Premium Atlantic Vinyl
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: Yes
Impact Resistant. Yes
Design Pressure; +50/-55
Other. These windows meet small missile impact wind-borne
protection requirements as required by FBC, section
2411.3.3.7 when the exterior lite is tempered. Laminated
glazing interlayer material requirements meet the current
edition of the FBC In accordance with Miami -Dade NOA for
DuPont SentryGlas and DuPont PVB interlayers,
Horizontal Slider (8200) 74" If 62' Insulated Glass (5/16 PVB
Lam In - 3/16 Annealed out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
11/30/2025
Installation Instructions
Verified By: Hermes Norero 73778
Created by Independent Third Party: Yes
Evaluation Reports
Created by Independent Third Party: Yes
Horizontal Slider (8200) 111" x 54" Insulated Glass (5/16
PVB/SGP Lam In - 3/16 Tempered out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
04/3012025
Installation Instructions
Verified By: Joseph A. Reed $8920
Created by Independent Third Party: Yes
Evaluation Reports
F114_0N_R1Z_AL22Q§a-_LPAt
Created by Independent Third Party: Yes
g2atil= : : 2601 _Glair Stone Road, Mlflahassee Fi. 32i93 ftat, V0-487-18at
The State of Florida Is an AA/EEO employer. Q - ri ht 2007-2013 State of mMg :: EqXIStatement :: 8SEll1sibilty Statement :; Refund Statement
Under Florida law, email addresses are public records, If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850,487,1395, -Pursuant to Section 455,275(l),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address It they have one. The ennalls
provided may be used for offical communication with the licensee, However email addresses are public record, If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public. To determine If you are a licensee under Chapter 465, KS., please click bere
Product Approval Accepts:
MWIMEEM
CERTIFICATION NO:
DATE:
CERTIFICATION PROGRAM:
COMPANY:
CODE:
REVISION DATE:
08/19/2013
5tructural
LMIMU
To verify that the "Notice of Product Certification" is -valid, please visit mjA �.NAM�lCertific�afion.coru to assure that the
product is active and currently listed. This certification represents product conformity to the applicable specification and
that certification criteria has been satisfied, A NAMI approved certification label must be applied to the product to claim
certification status. Please review and advise NAMI if any corrections are required to this document,
COMPANY NAME AND ADDRE SS PRODUCT DESCRIPTION
JELD-WEN "Premium Atlantic Vinyl
ny
3737 Lakeport Boulevard Non -Impact Horizontal Slider"
Klamath Falls, OR 97601 Vinyl Horizontal Sliding Window
Configuration.- XO
Glazing: Insulating Glass (Annealed Glass)
Frame: W-1879nim(74.00") E-1574nim(62,00")
Vent: W-939rnm(37.00") H-1504mm(59.25")
DLO: W-854mm(33.62") H-1485nim(58.50")
SPECIFICATION PRODUCT RATING
TAS 202-94 Design Pressure: 2400 Pa (50 psf)
Negative Design Pressure: 2640 Pa (55 psf)
Water Penetration Resistance Test Pressure. 359 Pa (H-01—Li
Product Tested By: National Certified Testing L.aboratories
Report No- NCTL-210-3898-01
Expiration Date: July 31.2025
Administrator's Signature: .....
NATIONAL ACCREDITATION AND
MANAGEMENT INSTITUTE, INC.
4794 George Washington Memorial Highway
Hayes, VA 23072
Tel: (804) 684-5124
Fax: (804) 684-5122
Installation Notes:
1. Seal flangelframe to substrate,
2, Use #10 PH or greater fastener though the nail fin with sufficient length to penetrate a minimum of 1
112" into the wood framing. For 2X wood frame substrate (min. S.G. = 0.42),
1 Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation. Digitally signed by Hermes F. Norero, P.E.
Reason: I am approving this document
Date: 2013.1022 07:06:54 -04'00'
not address he sealing consideration that may arise in different wall
conditions. For the complete installation procedure, see the instructions
packaged with the window or go to
www,jeld-wen.com/resourcesfinstallaton,
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc.
NAIL FIN INSTALLATION
MIN, D15TANCE
2X WOOD FRAME
l FOP EDGE: 3/4'
MrN- DISTANCE
2X WOOD
FOP, E06E: 3/4'
FRAME
SHIM SPADE
2
FRAME SEG'�TYP}
A
VERTICAL SECTION
1 IJ2' MINEMBEOMENT'
H
16
hLLX
GLAZING DETAIL JAMB SECTION (TYP)
HORIZONTAL 5ECTION
NOTE, CMk bmt— WS,v FWr, 6 W.wd dwra�
V4'MAX
-511111SP
ACE I WIN, DISTANCE
FOR EDSE! 3/4, PREMIUM ATLANTIC VINYL SLIDER
aX W00b FRAME
Max Frame OP PATTNG IMPACT
=i-x Ci — 0/ 1'
W'MrN. EMSEDMENT =-f A -75�t NO
MCI M
General Notes:
1The product shown herein is designed, tested and manufactured to comply Min the wind load criteria
of the adopted International Building Code(IBC), the international Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated condition&
2, All glazing shall conform to ASTM E1300.
3. At rninimum, glazing shall be 3/16' annealed insulating glass,
4. Use structural or composite shims where required,
5Installation methods can be interchanged Within the same opening,
6. An impact protective system is required where wind bome debris protection is mandated by local
building code,
T Maximum sizes are buck sizes and do not incidde fin or flange.
DATE: 3737 Lakeport Blvd
09/25/2013 JF
SCALEKarnath Falls, OR. 97601
NTS Phone,(541) 882-3451
MWIfifflt.
APPROVED BY: Premium Atlantic Vinyl Horizontal Slider
I Nail Fin Installation (74" x 62")
00 1.-1 1OF4
Installation Notes:
1, Seal flangelframe to substrate,
2, Use #10 PH or greater fastener though the frame with sufficient length to penetrate a minimum of 11/2'
into the wood framing, For 2X wood frame substrate (min. S.G. = OA2),
S. Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he seating consideration that may arse in different wall
conditions, For the complete installation procedure, see the instructions
packaged with the window or go to
www,jeld-wen.com/resourcesrtnstallafion,
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc.
MIN. DISTANCE
FOR EDGE; 3/4'
11/2' MIN,
EMBEDMENT
1/4' MAX
SHIM SPACE
FRAME SE�TYP
VERTICAL SECTION
31
Dawf CORNING
995 SILICONE
Assam
14.2 mm
GLAZING DETAIL
MAX
$HrM SPACE
3
EMBEDMENT I
Mind, DISTANCE
FOR EDGE; VIP
11/2' MIN,
EMBEDMENT —
1/4'MAX
SHIM SPACE
MIN, 015TANCE
2
FOP, EDG 3/4'
JAMS SECT19NITYP
HORIZONTAL SECTION
General Notes.
1 , The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code(IBC), the International Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions,
2, All glazing shall oonform to ASTI M E13W
3. At minimum, glazing shall be 3/16" annealed insulating glass,
4Use structural or composite shims where required.
5Installation methods can be interchanged within the same opening,
6, An impact protective system is required wheralwind bome debris protection is mandated by local
building code.
7. Maximum sizes are buck sizes and do not include fin or flange.
3737 Lakeport: Blvd
JMDVENKfamath Falls, OR. 97601
Phone: (541) 882-3451
Premium Atlantic Vinyl Horizontal Slider
Through Frame Installation (74" x 62")
001 ...... 2 OF4
Installation Notes:
1. Seal flange/frame to substrate.
2. Use 3116" Tapcon or equivalent fasteners through frame with sufficient length to penetrate a minimum
of 11/4" into concrete or masonry at each location with a 2 1/2" min from edge distance, For concrete
(min, Pe = 3000psi) or masonry substrate (CMU shall adhere to ASTM C90).
1 Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he sealing consideration that may arise in different wall
conditions. For the complete installation procedure, see the instructions
packaged with the window or go to
www.field-wen.comlresourcesfinstallaton,
DISCLAIMER
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-INEN Inc,
MIN. DISTANCE
FOR EWS2112-
9
-MASONRY
CGS
2
BLOCK
•
A
R CIZ.-T
EM9EOMENT
SHM MSSPACE
114* MAX
YMN'DISTANCE SHM SPACE
VERTICAL SECTION
FOR EWE: 2 Vr!Q
2,
16, 3/
i
DOW CORNrW1
995 SILICONE
MASONRY
GLASS RTTE
BLOCK ys
14,2 m
JAMS SE-CTIO±LLTYPI
HORIZONTAL SECTION
ELAZING DETAIL
t14'MAX
5RIA SPACE
M"• MENT
PREMIUM ATLANTIC VINYL -SLIDER
MASONRY
RLOCK
i
Max Frame I DP P. AJTNG IMPACT
74 x 62 +50/-55 NO
General Notes:
I The product shown herein is designed, tested and manufactured to comply Wth the wind load criteria
of the adopted International Building Code(IBC), the international Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated Conditions.
2. All glazing shall conform to ASTM E1300,
1 At minimum, glazing shall be 3/16" annealed insulating glass.
4. Use structural or composite shims where required.
5. Installation methods can be interchanged within the same opening,
6. An impact protective system is required where wind borne debris protection is mandated by local
building code,
7. MaAmurn sizes are buck sizes and do not include fin or flange.
3737 Lakeport Blvd
JELDVENKlamath Falls, OR. 97601
Phone: (541) 882-3451
Premium Atlantic Vinyl Horizontal Slider
Masonry Installation (74" x 62")
Installation Notes:
1, Seal flange/frame to substrate,
Z For anchoring into metal framing use #10 TEK Self Tapping screws with sufficient length to achieve a
minimum embedment of three threads past the frame thickness, Steel substrate min, 189a,, fy = 33 ksL
1 Host structure (wood buck, masonry, steel) or designed and anchored to property transfer all loads
to the structure, The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
vAndow to achieve the rated design pressure up to the size limitations
noted, It is not intended as a guide to the installation process and does
not address he sealing consideration that may adse in different wall
conditions. For the complete installation procedure, see the instructions
packaged with the window or go to
www,jeld-wen,com/resourcesrinstallaton.
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in part or used or disclosed to others
398
except as authorized by JELD-WEN Inc,
STEEL INSTALLATION
MR4 aTSTANCE FM I-OrE, W— I
W'. —Pd—t
M
.f th— th-.[s
P'.t f— 18 gauge mip.
IS 9.�q. Steel slud
St.1 stud
VIM, MAX 1/4' MAX
5 SPACE
fMMLESE �N TiP MIN, DISTANCE SHIM 7
SPACE
VERTICAL SECTION FOR EDGE: 1/2' 2
L-GLASS BITE
143
GLAZING DETAIL JAMS SECTIO=P
HORIZONTAL SECTION
21V MAX
SHM SPACE
10 9.'P.
St.1 51W
General Notes:
1 The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code(IBC), the Intemational Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTM El 3K
3. At minimum, glazing shall be 3/16" annealed insulating glass.
4Use structural or composite shims where required.
5Installation methods can be interchanged within the same opening.
6An impact protective system is required where wind borne debris protection is mandated by local
building code.
T Maximum sizes are buck sizes and do not include fin or flange.
3737 Lakeport Blvd
KJamath Falls, OP. 97601
Phone: 882-3451
(541)
ic Vinyl Horizontal Slider
Steel Installation (74" X 62")
. W I
Product Manufacturer
JELD-WEN
Address/Phone/Email
3737 Lakeport Blvd
Klamath Falls, OR 97601
(800) 535-3936
fbcl@jeld-wen.com
Authorized Signature
Rylee Sumner Fricks
fbcl@jeld-wen.com
Technical Representative
JELD-WEN Corporate Customer Service
Address/Phone/Email
3737 Lakeport Blvd,
Klamath Falls, OR 97601
(800) 535-3936
customerserviceagents@jeld-wen,com
Quality Assurance Representative
Address/Phone/Email
Category Windows
Subcategory Horizontal Slider
Compliance Method Certification Mark or Listing
Certification Agency National Accreditation & Management Institute
Validated By National Accreditation & Management Institute
Referenced Standard and Year (of Standard) gla-a—do-rA
Yom
TAS 201
1994
TAS 202
1994
TAS 203
1994
Equivalence of Product Standards
Certified By
Product Approval Method
EMUM
IMERMIMIMIM
091101M
30
Date Validated
Date Pending FBC Approval
Date Approved
FL # Model, Number or Name
14090,1 Premium Atlantic Vinyl
11/19/2020
0001M
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ* Yes
impact Resistant; No
Design Pressure, +50/-55
Other: Windows with Insulated glass units wider than 36"
require setting blocks. Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance with Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB Interlayers.
14090.2 1 Premium Atlantic Vinyl
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ. Yes
Impact Resistant. No
Design Pressure. +65/-70
Other: Windows with insulated glass units wider than 36"
require setting blocks. Laminated glazing interlayer material
requirements meet the current edition of the FBC in
n-d
DuPont PVB Interlayers.
14090.3 1 Premium Atlantic Vinyl
I
Limits of Use
Approved for use in HVHZ. Yes
Approved for use outside HVHZ: Yes
Impact Resistant; Yes
Design Pressure: +50/-55
Other., Windows w/ IG units wider than 36" require setting
blocks. These windows do not meet small missile impact
wind-borne requirements of the current edition of the FBC
when the exterior lite is annealed, they do meet small missile
Impact wind-borne protection requirements when the exterior
lite is tempered, Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB Intedayers.
14090.4 Premium Atlantic Vinyl
Limits of Use
Approved for use In HVHZ. Yes
Approved for use outside HVHZ: Yes
Impact Resistant. Yes
Design Pressure. +50/-55
Other: Windows w/ IG units wider than 36" require setting
blocks. These windows do not meet small missile impact
wind-borne requirements of the current edition of the FBC
#�#o J�j jjjejijr ji# is annealed, theo Oo oee.; imatt missile
lite is tempered, Laminated glazing interlayer material
requirements meet the current edition of the FBC in
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB interlayers,
14090,5 1 Premium Atlantic Vinyl
Horizontal Slider (8200) 74" x 62" Insulated Glass (3/16 in -
3/16 out Annealed)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
07/31/2025
Installation Instructions
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
fLL49jQ_Rj2_&E_2_ER �1, _df
Created by Independent Third Party: Yes
Horizontal Slider (8200) 74" x 54" Insulated Glass (3/16 in -
3116 out Annealed)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
07/31/2025
Installation Instructions
FL14090 R12 11 DP65-70 74x54 Installation Instructions.Ddf
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
Created by Independent Third Party: Yes
Horizontal Slider (8200) 74" x 62" Insulated Glass (5/16 SGP
Lam in - 3/16 Annealed out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
08/30/2025
Installation Instructions
p _df
Verified By: Hermes Norero 73778
Created by Independent Third Party: Yes
Evaluation Reports
ELII(_)90 P12 AE_PER3103 pdf
Created by Independent Third Party: Yes
Horizontal Slider (8200) 74" x 54" Insulated Glass (5/16 PVB
Lam in - 1/8 Annealed out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
10/31/2025
Installation Instructions
ELIIQKIti2 ii DP 0-
Verified By: Hermes Norero, PE 73778
Created by Independent Third Party: Yes
Evaluation Reports
EIAAQK�PER �
Created by independent Third Party: Yes
Horizontal Slider (8200) 74" x 54" Insulated Glass (5/16 SGP
Lam in - 1/8 Annealed out)
Limits of Use Certification Agency Certificate
Approved for use in HVHZ. Yes
Approved for use outside HVHZ- Yes i Quality Assurance Contract Expiration Date
Impact Resistant: Yes 08/30/2025
Design Pressure: +60/-65 Installation Instructions
Other. Windows w/ IG units wider than 36" require setting 8, 4"
blocks. These windows do not meet small missile impact
wind-borne requirements of the current edition of the FBC Verified By: Hermes Norero, PE 73778
when the exterior lite is annealed, they do meet small missile Created by Independent Third Party: Yes
impact wind-borne protection requirements when the exterior Evaluation Reports
lite Is tempered. Laminated glazing interlayer material ELjA229__Rj2_A9_ff,&U9&PAf
requirements meet the current edition of the FBC in Created by Independent Third Party: Yes
accordance w/ Miami -Dade NOA for DuPont SentryGlas and
DuPont PVB interlayers.
14090.6 1 Premium Atlantic Vinyl
Limits of Use
Approved for use in NVHZ: Yes
Approved for use outside HVHZ. Yes
Impact Resistant., Yes
Design Pressure., +50/-50
Other. Windows w/ IG units wider than 36" require setting
blocks, These windows do not meet small missile Impact
wind-borne requirements of the current edition of the FBC
when the exterior lite is annealed, they do meet small missile
impact wind-borne protection requirements when the exterior
lite is tempered. Laminated glazing Interlayer material
requirements meet the current edition of the FBC in
accordance w/ Miami -Dade NOA for DuPont Sen"Glas and
DuPont PVB interlayers.
14090.7 1 Premium Atlantic Vinyl
Limits of Use
Approved for use in HVHZ, Yes
Approved for use outside HVHZ. Yes
Impact Resistant. Yes
Design Pressure: +50/-55
Other. These windows meet small missile impact wind-borne
Horizontal Slider (8200) 74" x 62" Insulated Glass (5/16 PVB
Lam in - 3/16 Annealed out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
11/30/2025
Installation Instructions
&I-4119P-RIZ U -PEN_Z4.x%Z_1N_ 10AAR
Verified By: Hermes Norero 73778
Created by Independent Third Party: Yes
Evaluation Reports
fl-140
Created by Independent Third Party: Yes
PVB/SGP Lam In - 3/16 Tempered out)
Certification Agency Certificate
Quality Assurance Contract Expiration Date
04/30/2025
Installation Instructions
Verified By: Joseph A. Reed 58920
Created by Independent Third Party: Yes
Evaluation Reports
0 0 -1 nrif
Created by Independent Third Party: Yes
QaLai;&U�:: Tallahassee FL 32399 Ehtlaft: 8 0-4 T• 24
The State of Florida Is an AAJEEO employer, Qpyjr :: A�_esslblll S�tatement:: Refund -Statement
Under Florida law, email addresses are public records, If you do not want your e-mail address released in response to a publlc•recards request, do not send electronic
mail to this entity Instead, contact the office by phone or by traditional mail, If you have any questions, please contact $50,407,1395, *Pursuant to Section 455,275(2),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address If they have one. The ernalls
provided may be used for official communication with the licensee. However email addresses are public record, If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public. To determine If you are a licensee under Chapter 455, KS., please click here .
Product Approval Accepts:
M W1 in Ec3 M
CERTIFICATION NO: N1011635-RI
DATE: 08/19/2013
CERTIFICATION PROGRAM: atructural
COMPANY: JELD-WEN
CODE: 1822-1
REVISION DATE: 06/10/2017
To verify that the "Notice of Product Certification" is valid, Please visit www.NAMICertification,com to assure that the
product is active and currently listed. This certification represents product conformity to the applicable specification and
that certification criteria has been satisfied, A NAMI approved certification label must be applied to the product to claim
certification status. Please review and advise NAM if any corrections are required to this document,
COMPANY NAME AND ADDRESS PRODUCT DESCRIPTION
JELD-WEN "Premium Atlantic Vinyl
3737 Lakeport Boulevard Non -Impact Horizontal Slider"
Klamath Falls, OR 97601 Vinyl Horizontal Sliding Window
Configuration: XO
Glazing: Insulating Glass (Annealed Glass)
Frame. W-1879mm(74.00") H-1574nun(62,00")
Vent: W-939nim(37.00") H-1504rrun(59.25")
DLO: W-854mm(33,62") H-l485n-mi(58,S0")
SPECIFICATION PRODUCT RATING
TAS 202-94 Design Pressure: 2400 Pa (50 psf)
Negative Design Pressure. 2640 Pa (55 psi)
Water Penetration Resistance Test Pressure. 359 Pa (7.5 psi)
Product Tested By, National Certified Testing Laboratories
Report No. NCTL-210-3898-01
Expiration Date: jqjI 31.2025
Administrator's Signature:
NATIONAL ACCREDITATION AND
MANAGEMENT INSTITUTE, INC.
4794 George Washington Memorial Highway
Hayes, VA 23072
Tel: (804) 684-5124
Fax: (804) 684-5122
Installation Notes:
1, Seal flange/frame to substrate.
2, Use #10 PH or greater fastener though the nail fin with sufficient length to penetrate a minimum of 1
112" into the wood framing, For 2X wood frame substrate (min, S,G, = 0.42).
3. Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation. Digitally signed by Hermes F, Torero, P.E.
Reason: I am approving this document
Date, 2013,10.22 07-06:54 -04!OY
NAIL FIN INSTALLATION
• I Ile MIN. EMBEDMENT MIN. DISTANCE
'X WOOD FRAME FOR EDGE: 3/4'
MIN DISTANCE 2X woot)
FOR ED6e, 3/4' FRAME
A SPACE 2
FRAME 5E�TY�P 114'MAX
VERTICAL SECTION SHIM SPACE
FRAME
1/4 MAX
'�M SPACE
i/16" 11/2, MIN,
/M' 3/16- EMBEDMENT
W9
DOW CORNING
95 SILICONE
-----------
GLASS 8114.2 mm TE
GLAZING DETAIL JAMB 5ECT12!2L11PJ
1111,111ZONTAL 5ECTION
NOrCAk b� Nala? F6�� & Wmd Op,,�M,
-114'MAX
SHIM SPACEI
MIN DISTA3vCE
Fort EDGE; 3/4'
PREMIUM ATLANTIC VINYL SLIDER
2 2X WOOD FRAME Max Frame I DP RATING IMPACT
74 x 62 +50/-55 NO
1 112'MIN. EMBEDMENT Max
General Notes:
1. The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code(IBC), the international Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions.
2, All glazing shall conform to ASTM E1300.
1 At minimum, glazing shall be 3/16' annealed insulating glass.
4. Use structural or composite shims where required,
5. Installation methods can be interchanged within the same opening,
6An impact protective system is required where wind borne debris protection is mandated by local
building code,
T Maximum sizes are buck sizes and do not incidde fin or flange.
3737 Lakeport Blvd
JELD-WNYJamath Falls, OR. 97601
Phone: (541) 882-3451
•
rerniurn Atlantic Vinyl Horizontal Slider
Nail Fin Installation (74" x 42")
Installation Notes:
1 Sea] flangelframe to substrate.
2, Use #10 PH or greater fastener though the frame with sufficient length to penetrate a minimum of 11/2"
into the wood framing, For 2X wood frame substrate (min. S.G, = OA2),
1 Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure, The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
�XJ111111111
Window to achieve the rated design pressure up to the size limitations
-XNNEI/
noted. It is not intended as a guide to the installation process and does
not address he sealing consideration that may arise in different wall
conditions. For the complete installation procedure, see the instructions
the to
'N
packaged with window or go
7
www.jell wen.comlresourcesrinstallaton,
— / 11
DISCLAIMER:
CYF
This drawing and its contents are confidential and are not to be
d Sae
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc.
JAMN, OTSTAWE
FOR EDGE 314'.
11/2'MIN.
FM8EDMFNT
114'MAX
SHIM SPACE
FRAME SEC=N =PJ
VERTICAL SECTION
9M
99HIM
D DOW CORNING I MIN, DIST
995 SILICONE FOR EDG -:
M
THROUGH FRAME
INSTALLATION
,TAMB SECTIQL!MP
HORIZONTAL SECTION
c'MEEDM£NT
PREMIUM ATLANTIC VINYL SLIDEP
MaN DrSTANCE Max Prams DP RATINGJI!�MMPACT 1
FOR'EN;E: 3/4"
NO
General Notes:
1. The product shown herein is designed, tested and manufactured to comply Wth the Wind load criteria
of the adopted International Building Code(IBC), the international Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions,
2. All glazing shall conform to ASTM E1300,
1 At minimum, glazing shall be 3116" annealed insulating glass,
4Use structural or composite shims where required.
5, Installation methods can be interchanged Within the same opening.
6, An impact protective system is required where wind borna debits protection is mandated by local
building code.
7, Maximum sizes are buck sizes and do not include fin or flange,
3737 Lakeport Blvd
Kdamath Falls, OR. 97601
Phone: (541) 882-3451
ic Vinyl Horizontal Slider
Through Frame Installation (74" x 62")
Installation Notes:
1, Seal flangelframe to substrate.
2. Use 3116" Tapcon or equivalent fasteners through frame with sufficient length to penetrate a minimum
of 11/4" into concrete or masonry at each location with a 2 112" min from edge distance, For concrete
(min, f c = 3000psi) or masonry substrate (CMU shall adhere to ASTM C90).
3. Host structure (wood buck, masonry, steel) to be designed and anchored to properly transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation,
This schedule addresses only the fasteners required to anchor the
Jta ,mindow to achieve the rated design pressure up to the size fimi tons
noted. It is not intended as a guide to the installabon process and does
not address he seating consideration that may arise in different well
conditions. For the complete installation procedure, see the instrudons
packaged with the window or go to
www,jeld-wen.00m/resourcesTinstafiaton,
DISCLAIMER:
This drawing and its contents are confidential and are not to be
reproduced or copied in whole or in it or used or disclosed to (others
398
except as authorized by JELD-WEN Inc,
AIR DISTANCE
F102 EME; 2 W.
MASONRY INSTALIATION
1" 44" ,,-MASONRY
SLOCK
—1 I/Ir MIN.
41. EMBEDMENT 1114' MTN.
EMBEDMENT
1/4- Mx
SHIM S?Aa
FRAMEjgen=C1
= QtLVERTICAL SECTIOFOR EDGE: 2 Ile
N
`-GLA55,31TE I BLOCK
142 mm TAM$ SECTION {gyp}
ELAZING DETAIL HORIZONTAL SECTION
L/4' MAX
eg
EMBEDMENT
PREMIUM ATLANTIC VINYL SLIDER
NMax WFrame J!bf �RATII A6 qG IMPA_�T
50/ 0
E74 x 62 II A_
General Notes:
1. The product shown herein is designed, tested and manufactured to comply with the wind load criteria
of the adopted International Building Code(IBC), the International Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions,
Z Ali glazing shall conform to ASTM E1300.
3. At minimum, glazing shall be 3116" annealed insulating glass,
4, Use structural or composite shims where required.
5. Installation methods can be interchanged within the same opening,
6. An impact protective system is required where Wind bome debds protection is mandated by local
building code.
7. Ma)dmurn sizes are buck sizes and do not include fin or flange,
3737 Lakeport Blvd
JELDVENlaamath Falls, OR. 97601
Phone: (541) 882-345 1
'111' Le
Premium Atlantic Vinyl Horizontal Slider
Masonry Installation (74" x 62")
Installation Notes:
1 , Seal flange/frame to substrate.
Z For anchoring into metal framing use #10 TEK Self Tapping screws with sufficient length to achieve a
minimum embedment of three threads past the frame thickness, Steel substrate min. 18ga., fy = 33 k5i,
3, Host structure (wood buck, masonry, steel) to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This schedule addresses only the fasteners required to anchor the
window to achieve the rated design pressure up to the size limitations
noted. It is not intended as a guide to the installation process and does
not address he seating consideration that may arise in different wall
conditions. For the complete installation procedure, see the instructions
Z
packaged with the window or go to
www,jeld-wen,comtresourcesfinstallabon,
DISCLAIMER:
This drawing and its contents are confidential and are not to be
C
o�
'see
reproduced or copied in whole or in part or used or disclosed to others
except as authorized by JELD-WEN Inc.
STEEL INSTALLATION
MIN. DISTANCE
'FCAEDGEA/2
18 ilauge MI n
Steel Stud
Steel Stud
1/4' MAX
SHrM SPACE 1/4'MAX
i SHIM SPACE
26sECr;CrN ?Yf 1 1 MIN. DISTANCE
VERTICAL SECTION FOR EDGE: 1/2"
DOW CCqNrNG Mim embedment
995 Silli()NE j of three threads
post frame
li�� L-GLASS SITE
14,2 mm
GLAZING DETAIL
JAMB SECTIO�!"C P
HORIZONTAL SECTION
MAX
�I/V
SNTPA SPACE
S%d
PREMIUM ATLANTIC VINYL ,SLIDER
posy #rmne
MIR DISTANCE
MctxFrarne IDPRATINGTIMPACTI
FOA Ebr'f; 1/2'
�J
General Notes:
I The product shown herein is designed, tested and manufactured to comply with the Wind load coterie
of the adopted international Building Code(IBC), the international Residential Code(IRC), the Florida
Building Code(FBC) including HVHZ and the industry requirement for the stated conditions.
2, All glazing shall conform to ASTM El 300,
3. At minimum, glazing shall be 3116' annealed insulating glass.
4. Use structural or composite shims where required.
5. Installation methods can be interchanged within the same opening,
6, An impact protective system is required where wind bome debris protection is mandated by local
building code.
7. Ma)(Imurn sizes are buck sizes and do not include fin or flange.
DATE�
09/25/201
ELDrVEN 3737 Lakeport Blvd
Klamath Falls, OR. 97601
DRAWN BY' SCALE:
Phone: 882-3451
D. Vezo NTS
(541)
=LE:
Premium Atlantic Vinyl Horizontal Slider
Steel Installation (74" x 62")
Submit Surcharge Stall Facts Publications Contact Us BCIS Site Map Links Search
dbprProduct Approval
USER: Public User
> Application Detail
FL it FL21706-R4,
Application Type Affirmation
Code Version 2020
Application Status Approved
Comments
Archived
Product Manufacturer JELD-WEN
Address/Phone/Email 3737 Lakeport Blvd
Klamath Falls, OR 97601
(800) 535-3936
fbcl@jeld-wen.com
Authorized Signature Rylee Sumner Fricks
fbcl@jeld-wen,com
Technical Representative JELD-WEN Corporate Customer Service
Address/Phone/ Email 3737 Lakeport Blvd.
Klamath Falls, OR 97601
(800) 535-3936
customerserviceagents@jeld-wen.com
Quality Assurance Representative
Address/Phone/Email
Category Exterior Doors
Subcategory Sliding Exterior Door Assemblies
Compliance Method Certification Mark or Listing
Certification Agency National Accreditation & Management Institute
Validated By National Accreditation & Management Institute
Referenced Standard and Year (of Standard) Standard
_Xqar
TAS 201.
1994
TAS 202
1994
TAS 203
1994
Equivalence of Product Standards
Certified By
T affirm that there are no changes in the new Florida Building
Code which affect my product(s) and my product(s) are in
compliance with the new Florida Building Code.
Documentation from approved Evaluation or Validation Entity Yes No N/A
Product Approval Method Method I Option A
Date Submitted 07/29/2020
Date Validated 07/29/2020
Date Pending FBC Approval
Date Approved 08/02/2020
Summary of Products
FL # Model, Number or
Description
Name
21706,1 Premium Vinyl (V-4500)
Multi -Slide Patio Door 280 7/16" x 120 1/16" Insulated Glass (7/16" SGP Lam In
- 3/1.6" Tempered Out) (OXXXXX or XXXXXX)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ: Yes
Uix , ff
Approved for use outside HVHZ: Yes
"_706,02 QXXXXX, 4'jj'x _12 JA
?2,IkAA_G j 0,1_
Impact Resistant- Yes
Quality Assurance Contract Expiration Date
Design Pressure- +60/-60
01/31/2025
Other: Laminated glazing interlayer material
Installation Instructions
requirements meet the current edition of the
F-L-d-TO B-4--B-A i11__QM_LKX,!iV_ffiLF
FBC in accordance with Miami -Dade NOA for
Fjajj706 R4 11_6P4T_XXXX X,P 11 it FELC S X --?-i P aff
Kuraray SentryGlas and Kuraray PVB
Verified By: National Accreditation & Management Institute
interlayers. White ridged PVC exterior
Created by Independent Third Party:
extrusion requirements meet the current
Evaluation Reports
edition of the FBC in accordance with Miami-
F_ Li 2 Li` IQ_ Q c
Dade NOA for VEKA Inc. For fixed glass Shore
-1EI-Q pof
A 70-90 durometer setting blocks are used.
Created by Independent Third Party: Yes
DLO 41,44" x109.06"
21706.2 Premium Vinyl (V-4500)
Multi -Slide Patio Door 191" x 120" Insulated Glass (7/16" SGP Lam In - 3/16"
Tempered Out) (XXXX)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ. Yes
_I0 I \
Approved for use outside HVHZ* Yes
Quality Assurance Contract Expiration Date
Impact Resistant: Yes
01/31/2025
Design Pressure. +60/-60
Installation Instructions
Other: Laminated glazing interlayer material
12 X 07:-
requirements meet the current edition of the
Verified By: National Accreditation & Management Institute
FBC in accordance with Miami -Dade NOA for
Created by Independent Third Party:
Kuraray SentryGlas and Kuraray PVB
Evaluation Reports
interlayers. White ridged PVC exterior
extrusion requirements meet the current
Created by Independent Third Party: Yes
edition of the FBC in accordance with Miami -
Dade NOA for VEKA Inc. Setting blocks are
required for glazing over 3 feet,
217063 Premium Vinyl (V-4500)
Multi -Slide Patio Door 281 1/8" x 96" Insulated Glass (7/16" SGP Lam In - 3/16"
Tempered Out) (OXXXXX Or XXXXXX)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ: Yes
F1,21,706 R4 CCAC NJ "_IjZQh�n_C12XXkk ,f b -
Approved for use outside HVHZ: Yes
7() 28 9
Impact Resistant: Yes
P-LL,/06 _R 1 N-1 1
P (j 1-
Design Pressure* +65/-70
Other. Laminated glazing interlayer material
Quality Assurance Contract Expiration Date
requirements meet the current edition of the
01/31/2025
FBC in accordance with Miami -Dade NOA for
Installation Instructions
Kuraray SentryGlas and Kuraray PVB
I "S12" 2 P Ot Z' F��, I
interlayers, White ridged PVC exterior
LI-i�uQt1x,-,i-_ii-"-Ll�ti-.Xm:CXi-l'-iiUIiiz--FLi(-:,-
extrusion requirements meet the current
Verified By: National Accreditation & Management Institute
edition of the FBC in accordance with Miami-
Created by Independent Third Party:
Dade NOA for VEKA Inc, For fixed glass Shore
Evaluation Reports
A 70-90 durometer setting blocks are used.
EL21
DLO 40.88" x 85"
h24 ,S!E
'
Created by Independent Third Party: Yes
21706,4 Prerniurn Vinyl (V-4500) Multi -Slide Patio Door 195 7/8" x 95 7/8" Insulated Glass (7/16" SGP Lam In
3/16" Tempered Out) (XXXX)
Limits of Use Certification Agency Certificate
Approved for use in HVHZ-. Yes AC h. Xtmm,i(16 _AX_'KX__M1C�L_ __119_C1_X22'(L
Approved for use outside HVHZ: Yes Quality Assurance Contract Expiration Date
Impact Resistant: Yes 12/31/2024
Design Pressure: +65/-70 Installation Instructions
Other: Laminated glazing interlayer material FL21:
R4 11 274P XXXP HVHZ
_Q�
requirements meet the current edition of the Verified By: National Accreditation & Management Institute
FBC in accordance with Miarni-Dade NOA for Created by Independent Third Party:
Kuraray SentryGlas and Kuraray PVB Evaluation Reports
interlayers. White ridged PVC exterior
extrusion requirements meet the current
edition of the FBC in accordance with Miami- Created by Independent Third Party: Yes
Dade NOA for VEKA Inc.Setting blocks are
required for glazing over 3 feet.
21706,5 Premium Vinyl (V-4500) Multi -Slide Patio Door 71 3/4" x 79 13/16" Insulated Glass (1/8" Tempered In -
1/8" Tempered Out) (OX, XX)
Limits of Use
Approved for use in HVHZ-. Yes
Approved for use outside HVHZ-. Yes
Impact Resistant., No
Design Pressure: +65/-70
Other: White ridged PVC exterior extrusion
requirements meet the current edition of the
FBC in accordance with Miami -Dade NOA for
VEKA Inc, For fixed glass Shore A 70-90
durometer setting blocks are used. DLO
28.75" x 69"
21706.6 Premium Vinyl (V-4500)
Limits of Use
Approved for use in HVHZ. Yes
Approved for use outside HVHZ., Yes
Impact Resistant: Yes
Design Pressure. +65/-70
Other; Laminated glazing interlayer material
requirements meet the current edition of the
FBC in accordance with Miami -Dade NOA for
Kuraray SentryGlas and Kuraray PVB
interlayers, White ridged PVC exterior
extrusion requirements meet the current
edition of the FBC in accordance with Miami -
Dade NOA for VEKA Inc.. For fixed glass Shore
A 70-90 clurometer setting blocks are used.
DLO 28,75" x 69"
Certification Agency Certificate 2 df
EL2j )02 X L111,§S -_7 L) /?,�8(j_jL_SL , Q
Quality Assurance Contract Expiration Date
06/30/2023
Installation Instructions
jy,L%,,, 72-x-8a SS__,1,Q --cl,
f L12 -LIPK2L1-,=M Iltt aTratkL)j NI F€3t.,_12 &19 f,_$- L�L-IQ-
L 'L4 LqL
Verified By: National Accreditation & Management Institute
Created by Independent Third Party:
Evaluation Reports
__K4,AL(?-RLj!) S*� al -1 t _{Ll'p
FL21 06 R4 AEFFFdEi�1�3 SS 201 '-L,, it
Created by Independent Third Party: Yes
Multi -Slide Patio Door 72" x 80" Insulated Glass (7/16" SGP Lam In - 3/16"
Tempered Out) (XO, XX)
Certification Agency Certificate
W1_0,U3_760_.Q!-_R' mff
Quality Assurance Contract Expiration Date
06/30/2023
Installation Instructions
U i 1 2 !> kN& !; R X ''ILl _—W-1-111 2 ."'
Verified By: National Accreditation & Management Institute
Created by Independent Third Party:
Evaluation Reports
FL21706 R4 AE PER64
EUL12T(i At
Created by Independent Third Party: Yes
�Con act s :: COI alpir Stone Ftaad, Tallahassee Ft. -32 3139 khantLa5QzIRZ:,1.a24
The Star,, of Florida is an AA/FEO employer. Copyrbiht 2007-2013 State of Flor!&, : 5 R'LCyStatement
r va tateent :: ACC e 'gibi Lity Statement :: Refund State en
—--
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity, instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850,487.1395. -Pursuant to Section 455.275(1
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have one. The ernails
provided may be used for official communication with the licensee.. However email addresses are public record. If you do not wish to supply a personal address, please
provide the Department with ,in email address which can be more available to the public. To determine if you are a licensee under Chapter 455, FS,, please click bg_re_,
Product Approval Accepts:
M_ I U, 10! 11:11 M
1/2'
EMBDWNT
16" 0-C_ MAX — - 4" WAX.
rvP NAS_i1N �iROM
'i GfiiklFERi
t " 9.0
WAX TYI
raRL N
/2MIN.
_
T.i
1/4" kAX. S.I. SPPC€
ez (za-a
99 (5 0
p9p (2 S
T'18
GSS E
997 I25.
'.. 995 G1
96
Gl
t
5caia 2 1
`
RAM F cycr Qb', ..'T
VERT3CA-_ SEC T!LN
1 1 /2" MIN
EMBEDMENT
4.... ..._- _..
EDGE DISTANCE
/4" 3 AX. 5 .M SPACE
FRAVE JAMB St`'Tk_0,
--- 1
f _y _v ORFZONTAL SECTION
P CAL ._ELEVATION WwTN FA, � k E NFR_,S?AC
_ s, atllANCE
EG'"vE DISTANCE
, 'Frame Dr Il`APAC,I
fMae3rnaNT __
Installation Notes General Notes:
1. Seal flange/frame to substrate. Sill shall be set on a continuous serpentine bead of structural grade 1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
cifi na-&-1kri;pn nn f�cfonpr Eq 41 zpH to Anrhnr fh4-. c tl itvnirAh of the adopted International Buildina Code tIBCI. the International Residential Code ORCI, the current,
." MAX.
FROM
CORN,-Rh
cJcc
24" G.C,
MAX TYP,
THRU -Ame
TYPICAL ELEVATION WiTH FASTENER_ SPACING
Installation Notes:
1, Seal flarge/frame to substrate. Sill shall be set on a continuous serpentine bead of structural grade
silicone caulk when no fastener is used to anchor the sill (typical).
Z Use #10 PH or greater fastener through the pre -drilled holes in the head/sill tracks at both towers with
sufficient length to penetrate a minimum of 1 1/2" into the wood framing. See additional details for
location and spacing, For 2X wood frame substrate (min, SO = 0.42)
3. Host structure (wood buck, masonry, steel) to be designed and anchored to properly transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation,
; F`,,
mieve the rated design p-ersaule and imparn. As, formance (whem
applicableI up to the size to phr:ias noted, it is of inlerided as a guyle.
to brie msoilbaton pro -ass and does rol address to saaficc
dons zetation Thal may adse in different waJi oandisDris. For tie
oarratite installation Yoiredum, see his insirrorliars aackaged .9i ttr,
u,rlll a- up lo whwicidnee,
DISCLAIMER
Ph davimo and i's ons are comcentat and angnol lo be
reano4i,c3d or woed ir aholeof ih Pa,,l orused otdir;dQsed to olfrers
excW as autiho,,r7ec by JELD-WEN iro
T! 1 R,() U- G 11 1-11HA-MI, L
IN S'T A LLA T 10
3/="
FT"Gf
General Notes:
1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBC), the International Residential Code (IRC), the current
Florida Building Code (FEC) and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTIM, E1300,
3. At minimum, glazing is 3.Omm tempered - 12,7mm airspace - 5,Omm annealed - 2.3mm SGP
Interlayer by Kuraray - 5.Omm annealed insulating glass,
4. Use structural or composite shims where required.
J10/03/2
CATE:
Ic
DRAWN b-:
J.HAWKINS NTS
CHECKED BY: TrTLE:
J.GOOSSEN
APPROVED BY:
"I
1GOOSSEN
Yv
Vor P"-,J-, - -1Z,
RECORD No:
D014758
p Su T18
REPORI No:
P1310w,
NCTL-210-4150-02
9 3737 LAKEPORT BLVD.
JELWWENKLAMATH FALLS OR, 97601
PHONE: (800) 535-3936
— - ------ -------
Premium Vinyl Multi -Slide Patio Door - HVHZ
2-Panel 2-Track XX Stack
CAD DWG, No., REV' SHEET
PfemVinvITSLDR2 Cert A 2 OF
M4
'/A- —1—
MAX, I. EM DV-C�
ROM,
ORNERS
ON CRETE/MAS ON RY
1'\'CTM T.A'F'TnN
swm SPACE
'
-WOOD �OPTO-Q
2 -/2
D— DiSTANCE
/-7
"U
�P5
5/40"4
CLAZNL_H
.1 DISTANCE
S..ie: 2:1
VERTICAL SECTICN
- HORIZON AL SEC -
ON
Max 7'rome DD WIPACT
71 3/4 x 79 13/1 65/-70 YES
General Notes:
ral grade 1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBC), the International Residential Code (IRC), the current
�s at both Florida Building Code (FBC) and the industry requirement for the stated conditions.
odor o;srnucc
5—
W, Cc..-
u9s
s ode 2�'
FRAIWF 5EC_flQN C11F]i
VERTICA., SECTION
Installation Notes:
1, Seat flangefframe to substrate. Sill shall be set on a continuous serpentine bead of structural grade
silicone caulk when no fastener is used to anchor the sill (typical).
2. For anchoring into metal framing use #10 TEK Self -Tapping screws with sufficient length to achieve a
minimum penetration of three threads past the frame thickness at head/sill through both towers. Steel
substrate min, 18ga.. fy = 33 ksi,
3. Host structure (wood buck, masonry, steel) to be designed and anchored to properly transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation,
This schedule addresses only the fasteners required to anchor in-- unit
to atbrieve the fated design Pressure and irripao! performance Mhere
appii.able) up no tne smiWorns mt,2d It is no', Intended as a guide
no one installadon ruoess and doe s not address ,he sealiag
consideration that ay area In cifeosot wall concitions, Porthe
comp to Installation Procedure set Its instructions packaged witi the
unit or go to
DISCLAIMER
iris crarwing af,' Ps comen's are contnental aro are not to de
fairroduced o, coViied in wrote or in part or used or disciosed to others
except as authorized by JB D-VIEN Ic.
.V.�.
0111-1.
3/4' MINIMUM
EDGE I DS -A NC E
MIN, PENETRATION -
OF THREE 7HREACS
PAST FRAME
3/4" MUNIMUM,
EOCE DISTANCE
S'FEEL !,\STALLATION
�UAGE 18 MIN.
STEEL- E
EL STUD
11/4" VAX
SHIM SPACE
L.RAME _IA
;ICR170NTAL SECTION
'Max 7- "lame DP �M"M'T
/7-70 1, 3/4 x 79 1,3/16 +65,�
General Notes:
1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBC), the International Residential Code (IRC), the current
Florida Building Code {TBC) and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTM El 300.
3, At minimum, glazing is 3.Omm tempered - 12.7mm airspace - 5.0mm annealed - 2.3rum SGP
Interlayer by Kuraray - 5,Omm annealed insulating glass.
4. Use structural or composite shims where required.
*a E Pds,` 'P 11�1
__19/03/2019
DATE:
3737 LAKEPORT BLVD.
JELRWENKLAMATH FALLS OR, 97601
C)
DRAWN BY:
SCALE:
NTS PHONE: (800) 535-3936:
7
1HAWKINS
4Z
0HECKED BY:
J.GOOSSEN
TITLE:
J0 Q-
APPROVED BY:
Premium Vinyl Multi -Slide Patio Door - HVHZ
q oV iZ
k D N'
J.GOOSSEN
RECORD 14co
2-Panel 2-Track XX Stack
I i R ME!�� P.
D014758
398 E'st Dan 4 �H 08
arna Bea
D 'a ;' ,
REPORT No: CAD OWG. No. RE'/,, SHEET
NCTL-210-41SO-02 PremVinvIMT31-DR2 Celt A 4 OF 4
NOTES:
ANCHOR PATTERN LOCATED IN TRACK TOWERS I & 2 SHIFT AS DETAILED
HOLES TO BE OMITTED IF ON CENTER CALCUATIONS FALL WITHIN 2" OF KEEPER LOCATION
ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TOWERS IN JAMB
73 THRU FRAME INSTALLATION
0.172 THRU TYP
L-JO 375 T FIRST & SECOND WALLS lyP
THIS DRAWING NOT INTENDED FOR
FASTENER SPACING REQUIREMENTS
R
�'. 21 OC MAX
NOTES:
1 ANCHOR PATTERN LOCATED IN TRACK TOWER 1 SHIFT AS DETAILED
1. f HOLES TO aE OMITTED IF ON CENTER CALCUATIONS FALL WITHIN 2" OF KEEPER LOCATION!
2 ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TONERS IN 3AMB
3 NAIL FIN INSTALLATION
0.172 THRU ` YP
L-i 0 375 vT FIRST Vie. SECOND WALLS TYP
THIS DRAWING NOT INTENDED FOR
FASTENER SPACING REQUIREMENTS
W1112015! I V ] W" V 3737 Lakepo t aMj
4,
EXT t PATTERN, SYM
DETAIL X
SCALE I / 4
NOTES:
1 ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TOWERS AT HEAD OR SILL
1>TYP 1 ANCHOR PER PANEL LOCATED IN TRACK 1 TOWER AND ALIGNED WITH CENTER POINT
OF EACH CLOSED POSITION PANEL
_j>ANCHOR PATTERN LOCATED IN TRACK I TOWER AT EACH INTERLOCK AREA
I ANCHOR AT ENDS LOCATED IN TRACK I TOWER BOTH HEAD AND SILL
5jTYP 3 ANCHOR PATTERN LOCATED IN TRACK I TOWER APPROXIMATE CENTER OF
EACH CLOSED POSITION PANEL INTERLOCK AREA
FASTENER SPACING REQUIREMENTS
THIS DRAWING NOT INTENDED FOR '6,iCON FIGURATION FOR PG60/65 DOORS WITH NAIL FIN INSTALL
LENGTH/(# OF PANELS)/2—,------ LENGTH/(# OF PANELS) TYP
IN Y 2
EXT LENGTH/f-- OFPANELS)
0.172 THRU
L-J 0,375 T FIRST a SECOND WALLS TYP
DETAIL Z TYPICA4 HOLE
'Z'
00 ODY SCALE DRAW!NC -;ZEPORI AtX ERRORS
�NCES
A Z51ATE Or,
UNDER If32 X ±.l
OVER 101-01 ± 1116 , XX ±.02
ANGULAR IXo±.006
*��3z
HE�%apak,S,$E,
HEIGHT tI/16 WIDTH ±1/16
d,
'198 1,-
6—z RR—h. ',L 2300:
- --- - --------- --
MULLION ± 1/16 FRACTION ± 1/32
rA
9111/2015 3117 LAl--ll Bind.
JELD WEN R.h Falls, OR 97601
AS SHOWN (541)
2-TRACK FRAME
MULTI SLIDE PATIO DOOR
SILL AND HEAD ANCHOR HOLES DETAIL
"'0012967-394,ipt PO 12967
sr—
CC%-r-34TV,L AND RIIRHAky, A
4.272
t
T 1 DETAIL AA
5CALE 1 / 4
t PATTERN, SYM
EXT J DETAIL AB
SCALE 1 / 4
tPATTERN
1 DETAIL AC
EXT SCALE 1 / 4
NOTES.
1 ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACT{ TOWERS AT HEAD OR SILL
2"' TYP 1 ANCHOR PER PANEL LOCATED IN TRACK 1 TOWER AND ALIGNED WITH CENTER POINT
OF EACH CLOSED POSITION PANEL
3 ;ANCHOR PATTERN LOCATED IN TRACK 1 & 2 TOWERS AT EACH INTERLOCK AREA
THIS DRAWING NOT INTENDED FOR9 j1 ANCHOR AT "ENDS LOCATED IN TRACK 1 TOWER BOTH HEAD AND SILL
FASTENER SPACING REQUIREMENTS 5 ,TYP 5 ANCHOR PATTERN LOCATED IN TRACK 1 & 2 TOWERS APPROXIMATE CENTER OF
EACH CLOSED POSITION PANEL INTERLOCK AREA
6 "CONFIGURATION FOR PG 60/65 DOORS WITH THRU FRAME INSTALL
LENGTH/ (A OF PANELS POCKETS)/2LENGTH/(# OF PANELS + POCKETS) TYP ----
t
AB<' 3 _..
AA'
j AC<
/i
I _
.h
E T It PATTERN
t PATTERN, SYM
LENGTH/(-# OF PANELS) iYP
0.172 THRU TYP
U 0.375 T FIRST & SECOND WALLS TYP
DETAIL AD TYPICAL HOLE
Af0
SCALE 1 / 2 ,�
rJa s77r` -aLRAiurEs
i� fi *.t
UNDER W-O1/32 X !-.1
�i� ✓t
•' {�'
HE'R�`y'3
_ANGULAR P .XXX t'006
ua�irasalsiv ro_cay.s.`_
.,Da....�_
HEIGHT t1,16 WIDTH 1; 1/16
D� " az.�,;n vi 310o1
MJLLION f klio FRACTION t U32
9/11/2015 4 3737 LokeFort 3ne
j E L D, W E N .s mth Fans, CR 97&o,
>.AS SHO1VVN ^ „ . , Ph 541) a32-34.51
_-- — ._—
_-----
_
2-TRACK FRAMC
MULTI -SLIDE PATIO DOOR
6"SILL AND HEAD ANCHOR HOLES DETAIL
4 "0012967-397.iat �YFr ') P012967
1 14
A
BCIS Home Log In User Registration Hot Topics submit Surcharge Stats 8, Facts Publications Contact Us Gcls Site Map Links Search
Product Approval
tl yi USER: Public User
dbp. r
-1' '0111 > Application Detail
FL it FL21706-R4,
Application Type Affirmation
Code Version 2020
Application Status Approved
Comments
Archived
Product Manufacturer JELD-WEN
Address/Phone/Email 3737 Lakeport Blvd
Klamath Falls, OR 97601
(800) 535-3936
fbcl@jeld-wen.com
Authorized Signature Rylee Sumner Fricks
fbcl@jeld-wen,com
Technical Representative JELD-WEN Corporate Customer Service
Address/Phone/Email 3737 Lakeport Blvd.
Klamath Falls, OR 97601
(800) 535-3936
customerserviceagents@jeld-weii.com
Quality Assurance Representative
Addi-ess/Phone/Email
Category Exterior Doors
Subcategory Sliding Exterior Door Assemblies
Compliance Method Certification Mark or Listing
Certification Agency National Accreditation & Management Institute
Validated By National Accreditation & Management Institute
Referenced Standard and Year (of Standard) 5tWjlord
YvAr
TAB 201
1994
TAS 202
1994
TAS 203
1994
Equivalence of Product Standards
Certified By
I affirm that there are no changes in the new Florida Building
Code which affect my product(s) and my product(s) are in
compliance with the new Florida Building Code.
Documentation from approved Evaluation or Validation Entity Yes No N/A
Product Approval Method Method I Option A
Date Submitted 07/29/2020
Date Validated 07/29/2020
Date Pending FBC Approval
Date Approved 08/02/2020
Summary of Products
FL # Model, Number or
Description
Name
21706.1 Premium Vinyl (V-4500)
Multi -Slide Patio Door 280 7/16" x 120 1/16" Insulated Glass (7/16" SGP Lam In
- 3/16" Tempered Out) (OXXXXX or XXXXXX)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: Yes
F 2 J,_j C (�k kC__
Impact Resistant: Yes
Quality Assurance Contract Expiration Date
Design Pressure: +60/-60
01/31/2025
Other., Laminated glazing interlayer material
Installation Instructions
requirements meet the current edition of the
FBC in accordance with Miami -Dade NOA for
Kuraray SentryGlas and Kuraray PVB
Verified By: National Accreditation & Management Institute
interlayers. White ridged PVC exterior
Created by Independent Third Party:
extrusion requirements meet the current
Evaluation Reports
edition of the FBC in accordance with Miami -
Dade NOA for VEKA Inc. For fixed glass Shore
�Lcff
A 70-90 durometer setting blocks are used.
Created by Independent Third Party: Yes
DLO 41.44" x109.06"
21706.2 Premium Vinyl (V-4500)
Multi -Slide Patio Door 191" x 120" Insulated Glass (7/16" SGP Lam In - 3/16"
Tempered Out) (XXXX)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ: Yes
F 2LLQ�q_R4._C A XXXX Pr(L. Ix 210,T -'-QLZk,
Approved for use outside HVHZ: Yes
Quality Assurance Contract Expiration Date
Impact Resistant, Yes
01/31/2025
Design Pressure. +60/-60
Installation Instructions
Other: Laminated glazing interlayer material
EL4,LZQ�k d Tj 21 >.' P 'Z
requirements meet the current edition of the
Verified By: National Accreditation & Management Institute
FBC in accordance with Miami -Dade NOA for
Created by Independent Third Party:
Kuraray SentryGlas and Kuraray PVB
Evaluation Reports
interlayers. White ridged PVC exterior
D-1 Qdf
extrusion requirements meet the current
Created by Independent Third Party: Yes
edition of the FBC in accordance with Miami -
Dade NOA for VEKA Inc. Setting blocks are
required for glazing over 3 feet.
21706.3 Premium Vinyl (V-4500)
Multi -Slide Patio Door 281 1/8" x 96" Insulated Glass (7/16" SGP Lam In - 3/16"
Tempered Out) (OXXXXX or XXXXXX)
Limits of Use
Certification Agency Certificate
Approved for use in HVHZ,. Yes
FL21,06 R4 C CAC N1013721.. XXXX EiS=.
Approved for use outside HVHZ. Yes
Impact Resistant, Yes
IIQJ,',,�70vAQj
Design Pressure. +65/-70
Other-, Laminated glazing interlayer material
Quality Assurance Contract Expiration Date
requirements meet the current edition of the
01/31/2025
FBC in accordance with Miami -Dade NOA for
installation Instructions
Kuraray SentryGlas and Kuraray PVB
L221
interlayers. White ridged PVC exterior
extrusion requirements meet the current
Verified By: National Accreditation & Management Institute
edition of the FBC in accordance with Miami-
Created by Independent Third Party:
Dade NOA for VEKA Inc, For fixed glass Shore
Evaluation Reports
A 70-90 durometer setting blocks are used.
DLO 40,88" x 85"
Created by Independent Third Party: Yes
21706.4 Premium Vinyl (V-4500) Multi -Slide Patio Door 195 7/8" x 95 7/8" Insulated Glass (7/16" SGP Lam In -
3/16" Tempered Out) (XXXX)
Limits of Use Certification Agency Certificate
Approved for use in HVHZ. Yes E-2 a I _LrL1mdf
Approved for use outside HVHZ. Yes Quality Assurance Contract Expiration Date
Impact Resistant: Yes 12/31/2024
Design Pressure: +65/-70 Installation Instructions
Other: Laminated glazing interlayer material FL21
tftC__'abaai S S_27-07-25, ff
5 U2_
requirements meet the current edition of the Verified By: National Accreditation & Management Institute
FBC in accordance with Miami -Dade NOA for Created by Independent Third Party:
Kuraray SentryGlas and Kuraray PVB Evaluation Reports
interlayers. White ridged PVC exterior
extrusion requirements meet the current
edition of the FBC in accordance with Miami- Created by Independent Third Party: Yes
Dade NOA for VEKA Inc.Setting blocks are
required for glazing over 3 feet.
21706,.5 Premium Vinyl (V-4500)
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: Yes
Impact Resistant: No
Design Pressure, f65/-70
Other: White ridged PVC exterior extrusion
requirements meet the current edition of the
FBC in accordance with Miami -Dade NOA for
VEKA Inc, For fixed glass Shore A 70-90
durometer setting blocks are used. DLO
28.75" x 69"
21706.6 Premium Vinyl (V-4500)
Limits of Use
Approved for use in HVHZ; Yes
Approved for use outside HVHZ: Yes
Impact Resistant: Yes
Design Pressure. +65/-70
Other: Laminated glazing interlayer material
requirements meet the current edition of the
FBC in accordance with Miami -Dade NOA for
Kuraray SentryGlas and Kuraray PVB
interlayers. White ridged PVC exterior
extrusion requirements meet the current
edition of the FBC in accordance with Miami -
Dade NOA for VEKA Inc. For fixed glass Shore
A 70-90 durometer setting blocks are used.
DLO 28.75" x 69"
Multi -Slide Patio Door 71 3/4" x 79 13/16" Insulated Glass (1/8" Tempered In -
1/8" Tempered Out) (OX, XX)
Certification Agency Certificate
R4 C C.A NI 376( 06 (()Q2) '(0 D '1) 11 TA 01.Ipc!
Quality Assurance Contract Expiration Date
06/30/2023
Installation Instructions
lg1t, ]Lr� FBC,-' , Q,S,,,_,?0 ,9 I
Verified By: National Accreditation & Management Institute
Created by Independent Third Party:
Evaluation Reports
I'll 21,706_ R41 AE IUR!U3 FL21706—R14 AE PER6433 SS 2019-10-041 Rot
Created by Independent Third Party: Yes
Multi -Slide Patio Door 72" x 80" Insulated Glass (7/16" SGP Lam In - 3/16"
Tempered Out) (XO, XX)
Certification Agency Certificate
10L3Z6
Quality Assurance Contract Expiration Date
06/30/2023
Installation Instructions
Fl,2 2 1-1 Ll - r K0 S
_T ut oj_'
_XX - 1 Lij',3 _7x S, , 0 t 1- 1 IIAt
1.11- NI-1 . ..... .
Verified By: National Accreditation & Management Institute
Created by Independent Third Party:
Evaluation Reports
FL21706 R4 AE PER6431.
Created by Independent Third Party: Yes
QOL)t�qs :: Zkaj
_ffidjLStone Rom, jPj �11,95 -487-1 � 24
The. State of Florida is an AA/FFO employer. ropyLighL2007-2.013 State of Florida, Privacy Staternent :; Accessibility_Statement :: g9frld_ Statement
_
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850,487.1395. *Pursuant to Section 455,275(1),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, RS. must provide the Department with an email address if they have one. The smalls
provided may be used for official communication with the. licensee, However email addresses are public record. If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public, To determine if you are a licensee under Chapter 455, FS,, please click hll.rEL.
product Approval Accepts:
mupa'�E3=
of
mom=
1 1/2- M'
MAX.
FROV
CORNEAS
.11)1:= _J
-Do. CORING
95
GLAZING DETA;L
Scale: 2:1
�RAM
VERTICAL SECTION
Installation Notes:
1. Seal flangelframe to substrate Sill shall be set on a continuous serpentine bead of structural grade
silicone caulk when no fastener is used to anchor the sill (typical).
2. Use #10 PH or greater fastener through the nailfin with sufficient length to penetrate a minimum of 11/2"
into the wood framing. For 2x wood frame substrate (min, S.G. = 0,42)
3. Use #10 PH or greater fastener through the pre -drilled holes in the head/sill tracks at the interior tower
with sufficient length to penetrate a minimum of 1 1/2",nto the wood framing. See additional details for
location and spacing.
4, Host structure (wood buck, masonry, steel) to be designed and anchored to properly transfer all loads to
the structure. The host structure is the responsibility of the architect orgrltgtftofCrd for the project
of installation. Digitally signed b
\A11,F1\ TITRU � JAMB
INS'-F' jTFALLA JON
M,ax Fro-ne DP IMOAC-
71 3/4 11 x 79 3/16� +65/-70 Y':_ (S
General Notes:
1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBC), the International Residential Code (IRC), the current
Florida Building Code (FBC) and the industry requirement for the stated conditions-
2. All glazing shall conform to ASTM E1300.
3. At minimum, glazing is 3.Omm tempered - 12.7mm airspace - 5.0rnm annealed - 2.3mm SGP
Interlayer by Kuraray - 5.Omm annealed insulating glass.
4. Use structural or composite shims where required.
eason: am o I -
Date: 2019A06 T
V An
-his sciedue addresses only the fasteners required to a,11mor the oral
toschieve thersbeddesign bressuve and impact oerformao0e{where
applicable) up to the size lirribbons noted. it is not intended as a guide
Nd
J.HAWKINS
CHECKED BY:
N
to the irnpailation proosets and does not address the sealim,
in dip;,erent 0, the
UF
J,G00SS E
Consideration that may arise -all condkrs
APPROOVED BY:
connplete;rstaflatioi prececkne, see the instructions packaged with the
0
I GOOSSEN
unit of go to www.jeld-wen,comiresourcesiirstall-�.'iOI
No
DISCLAIMER:
This drawing and its contents are confidenpai and are not to be
11 T I \ A �
H Ev R M E_191�
RECORD
D0147'58
so 'sclosed to others
reproduo-dorcopii j,.whQjeorjnmyior4Xe ordt
I b�'
Biv ��u 3,
'c,"
REPORT No:
except as aiticrized by JEL D-WEN In,
398 East nial
e� , 'rF q"
Bs.
Doll - '3"
NCTL -210—
DATE: 3737 LAKEPORT BLVD.
10/03/2019
JEL13rWEN LAMATH FALLS OR, 97601
NTS PHONE: (800) 535-3936
TITLE:
Premium Vinyl Multi -Slide Patio Door - HVHZ
2-Panel 2-Track XX Stack
CAD DWG. No.: 1 REV: SHEET
PremV1nvlMTSLDR2 CeM A 1 OF 4
24" C,C
MAX TYP
1HRU -AM8
TYPICAL ELEVATIOtdl' WITH FASTEN'R SPAYING
Installation Notes:
1. Seal flange/frame to substrate. Sill shall be set on a continuous serpentine bead of structural grade
silicone caulk when no fastener is used to anchor the sill (typical),
2. Use #10 PH or greater fastener through the pre -drilled holes in the head/sill tracks at both towers with
sufficient length to penetrate a minimum of 1 1/2" into the wood framing. See additional details for
location and spacing. For 2X wood frame substrate (min. SG = 0.42)
3. Host structure (wood buck, masonry, steel) to be resigned and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation.
This srohear aedressas only the fasteners requtfed to anchor the an,
'a adI the t - rated esip P,,as3ure arid i ' bee, cerfarmance, (where
a0sicable) up to the stsa fintilariornt noted. It s'rot imernhed as a gued
.0 the rsialfabon P, o-ess and does rot address thz- beeline
cat may arise in difftce,it wall cntb>froris. For' me
p,rr_e&,e, see the rnsiaxtions Da - ,rag aj tii the
unit or go to
DISCLAIMER
This drav-'rg and its contenIs are corifidawja! and are not to be
,-earoducad or sopt r hod, or in Pao or used or lisd3seed to ohrs
except as truft"oted by Jr! 0-VIEN Inc
1,----
9ft ...u.
BED. —
!02 T:
197 orc-, I
-SS s'a
zss
3JLAZMXMTAHL
S..l.: 2:1
A-,iCAL SECTION
71-!ROLJClt FRMALI
I ! NSTALLATI ON
EIR ,AME _L �Iv ED , SECTION f 1Y �
- F)
HOPN-
;ZOAL SECTION
Micx Frome DP 1 A C T
71 3/4 x 79 1 3/1, 6 +65/-7 y P-5
General Notes:
1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBC), the International Residential Code (IRC), the current,
Florida Building Code (FBC) and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTM El 300.
3. At minimum, glazing is 3.0mrn tempered - 12.7mm airspace - 5.Omm annealed - 2.3mm SGP
Interlayer by Kuraray - 5.Omm annealed insulating glass.
4. Use structural or composite shims where required,
for
DATE:
3737 LAKEPORT BLVD.
10/03/2019
DRAWN 9Y: JELBrWEN
KLAMATH FALLS OR, 97601
J.HAXAJKINS FITS PHONE: (800) 535-3936
- ---------
CHECKED BY: TrTLE:
I.GOOSSEN
FA- 01- Door - HVHZ
APPROVED BY: Premium Vinyl Multi -Slide Patio
0 I2-Panel 2-Track XX Stack
t J.GOOSSEN
RECORD No -
I I E R M D014758
REPORT No: CAD DVVG. No.: REV: SHEET
398 EasL Dania a �h lr� Sui!"'
D'10� Be'a'�Vj " 3'q'; ' ; a NCTL-210-4150-02 PremVInvIMTSL0R2 Cent A 2 OF 4
CONCTRETE/MASON RY
TN_�'T'Al T A'Pfr)\i
14" OC� WAY. MAX DIVaICE
TYP. T-4�U JAMB FROM -VICOr BUIC,
(OPTIONAL)
-114" MAX
7
SHIM SPACE
51CI to AIAX P.
THRU jAMS i/a Max. IIi. SIACE 1 2 112" MIN MUM
I EDG- 0614N�E
rYs
2
3/4'
GLAZINr DE
H4 EDGE D.STANCL
2:1
VVR71CAE^,TiCN
MQ q T E
_g_,_,Q
HORIZON -AL SEC70N
— - --- ------- -
'PICAL EL"VATION WITH 'ASTENER SPADING
1 1/2- ��" a x rc m e D P WPAC'
71 3/4 x 79 13/16 —65/-70 YES —
installation Notes: General Notes:
1. Seal flangefframe to substrate. Sill shall be set on a continuous serpentine bead of structural grade 1. The product shown herein is designed,tested and manufactured to comply with the wind load crRe
silicone caulk when no fastener is used to anchor the sill (typical). of the adopted International Building Code (IBC), the International Residential Code (IRC), the cui
2. Use 3/16" tapoon or equivalent fasteners through the pre -drilled holes in the head/sill tracks at both Florida Building Code (FBC) and the industry requirement for the stated conditions.
fnmipm with zi iffiriont 1prInth to nIAnp.tr2fe ;; minimum of 1 1/4' into concrete or masonry at each location 2. All olazino shall conform to ASTM E1300.
0_c�
P.
U JAMB
TYPICAL ELEVATION WITH FASTFNER SPACING
� -11 - -- --------- - -
rw� =a
rase vFau[
In? 2j
_J
o95
Sl 2:1
WWI
FR�,ME SEC7iON Cam'
VER7ICX SECrtoq
Installation Notes:
1. Seal flangelframe to substrate. Sill shall be set on a continuous serpentine bead of structural grade
silicone caulk when no fastener is used to anchor the sill (typical).
2. For anchoring into metal framing use #10 TEK Self -Tapping screws with sufficient length to achieve a
minimum penetration of three threads past the frame thickness at head/sill through both towers. Steel
substrate min. 18qa., fv = 33 ksL
3. Host structure (wood buck, masonry, steel') to be designed and anchored to property transfer all loads
to the structure. The host structure is the responsibility of the architect or engineer of record for the
project of installation,
S'I'E_FT;L INSTALLATION
18 GUAGE MIN.
MAX
SHIM SPACE
3/4" MINIMUM
EDGE DISTANCE 2.
MrN. PENFTRATICt+-
OF THREE _HPFACS
PAST FRAME
1 1-- ____
3/-" MINW.u,
EDGE DISTANCE
General Notes:
1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
of the adopted International Building Code (IBC), the International Residential Code (IRC), the current
Florida Building Code ( ' FBC) and the industry requirement for the stated conditions.
2. All glazing shall conform to ASTM E! 300,
3, At minimum, glazing is 3.Omm tempered - 12.7mm airspace - 5.Omm annealed - 2.3mm SGP
Interlayer by Kuraray - 5.Omm annealed insulating glass.
4. Use structural or composite shims where required.
E Aj�
DATE: 3737 LAKEPORT BLVD.
10/0 3/2019
"L13rW1`NKLAMATH FALLS OR, 97601
JE r,
Tris stoierrula, aricnessas oniii the fasteners required to anchor ffis uniur
to achp-re the rated designpressure impact
7'
DRAWN BY: SCALE:
J.HAWKINS ITS PHONE: (800) 535-3936
and performance 1where
app'icaee) up to ?,is size irmiladons roted, It i5 not intended as a guide
-----------
CHECKED BY:
to the process and does not address tro, seating
—0 1" C-
1GOOSSEN
consideration that may a6se in difenait wail condificnis Fxtie
complete arc cure 3ee the r1structions wrtl the
Z A
------ Pre
APPROVED BY: miurn Vinyl Multi -Slide Patio Door - HVHZ
packaged
oak c,� go
A_
- I
flu 4�
J G00SSEN1___ 2-Panel 2-Track XX Stack
RECORD No:
D IELAIMER
Ti crowing and iis cemeras are confidental ano are net to
I z i S
D014758
-00�ed in Fpproducel one Orin Part dir used 0, declosed to others
-st D-IN
by JEL EN 17"'
398 East Dama .1 S,,j� 0)�
REPORT No: CAD DING. No: Ri SHEET
A 4 OF 4
as authorize !Xs_ 'd
carte B Vt
NCTL-210-4150-02 PrerFVinyIMT5LDR2 Cert
0
NOTES:
4.272 ANCHOR PATTERN LOCATED IN TRACK TOWERS I & 2 SHIFT AS DETAILED
HOLES TO BE OMITTED IF ON CENTER CALCUATIONS FALL WITHIN 2*'OF KEEPER LOCATION
1.819 ;L/ ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TOWERS IN )AMB
�-3. � THRU FRAME INSTALLATION
0.172 THRU TYP
L-jO .375 T FIRST & SECOND WALLS TYR
THIS DRAVVING NOT INTENDED FOR
FASTENER SPACING REQUIREMENTS
---- -- -----
13
NOTES:
,- 1.� ANCHOR -
PATTERN LOCATED IN TRACK TOWER 1 SHIFT AS DETAILED
HOLES TO BE OMITTED IF ON CENTER CALCUATIONS FALL WITHIN 2" OF KEEPER LOCATION
ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TOWERS IN JAMB
NAIL FIN INSTALLATION
0.172 THRU TYP
- �.375 T FIRST &SECOND WALLS TYP
THIS DRAWING NOT INTENDED FOR
FASTENER SPACING REQUIREMENTS
_ ---- ----- --
I f- I Ij A'jj 1�' 1%j
x
4,
4.272
EXT i DETAIL W
SCALE I / 4
EXT I t PATTERN, SYM,
DETAIL X
SCALE 1/ 4
DETAIL Y
EXT I SCALE I / 4
NOTES:
1 ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TOWERS AT HEAD OR SILL
DTYP 1 ANCHOR PER PANEL LOCATED IN TRACK I TOWER AND ALIGNED WITH CENTER POINT
OF EACH CLOSED POSITION PANEL
:31)ANCHOR PATTERN LOCATED IN TRACK I TOWER AT EACH INTERLOCK AREA
�4 �> 1. ANCHOR AT ENDS LOCATED IN TRACK I TOWER BOTH HEAD AND SILL
EjTYP 3 ANCHOR PATTERN LOCATED IN TRACK I TOWER APPROXIMATE CENTER OF
EACH CLOSED POSITION PANEL INTERLOCK AREA
THIS DRAWING NOT INTENDED FOR '3)CONFIGLIPATION FOR PG60/65 DOORS WITH NAIL FIN INSTALL
FASTENER SPACING REQUIREMENTS
LENGTH/(# OF PANELS)/2—�--- LENGTH/(# OF PANELS) TYP
x
r
7'
EXT LEfiGTH/(# OF PANELS) TYR
/--0.172THRU
L-j 0375 T FIRST & SECOND WALLS TYP
offl9r.f.im
0
'00 NOT SCALE DRAVN' - REPM-1 ANY ERRrAS K, HERTZOG J
'761
7
'UNLESS SPEOFTIED OTHEMISE)
A BURWELL
J JONES
UNDER IV-0' 1/32 Y ±1
OVER 1C 6 i 1/16 AX —02
ANGULAR t I 0015
1}ONES
F�
gsF�uiy TOE�4CES
HEIGHT ± 1/16 WIDTH s 1116
MULLION i 1/16 FRACTION t 1132
q
11120153737 Lake Blvd,
JELD WEN Alz�th Falls, P0`R`t9760I
SHOWN Ph-e; (541) 862-3451
2-TRACK FRAME
MULTI -SLIDE PATIO DOOR
AND HEAD ANCHOR HOLES DETAIL
Lipt P012967
2
4.
4
EXT DETAIL AA
SCALE 1 / 4
tPATTERN, SYM
E)CT j DETAIL AB
SCALE 1 / 4
DETAIL AC
EXT I SCALE I / 4
5
NOTES:
I ALL HOLES IN ALL POSITIONS TO BE CENTERED WITHIN TRACK TOWERS AT HEAD OR SILL
---!->TYP 1 ANCHOR PER PANEL LOCATED IN TRACK I TOWER AND ALIGNED WITH CENTER POINT
OF EACH CLOSED POSITION PANEL
ANCHOR PATTERN LOCATED IN TRACK I & 2 TOWERS AT EACH INTERLOCK AREA
THIS DRAWING NOT INTENDED FOR - 4> I ANCHOR AT ENDS LOCATED IN TRACK I TOWER BOTH HEAD AND SILL
FASTENER SPACING REQUIREMENTS 5>TYP 5 ANCHOR PATTERN LOCATED IN TRACK I & 2 TOWERS APPROXIMATE CENTER OF
EACH CLOSED POSITION PANEL INTERLOCK AREA
-6 " CONFIGURATION FOR PG 60/65 DOORS WITH THRU FRAME INSTALL
LENGTH/ NGTH/(�� OF PANELS + POCKETS) TYR
(# OF PANELS + POCKETS)/2 LE
AA
ACC
AD
T
tPATTERN
EX I I --- tPATTERN
,,. PATTERN, SYM
LENGTH/(# OF PANELS) TYP- --- —
O172 THRU TYP
L-J 0375 T FIRST & SECOND WALLS TYR
DETAIL AD TYPICAL HOLE
F
SCALE N
I I
.ON11 ES
DO NOT SCkt DRAVYINGREPOR' AW ERRORS
UN L Ess sEtce I -D 0 r E PmSE)
TATE
ul
0" ± 1/32 UNPER 10 A ±j
XXt.02
`CA0
HE
ANGULAR t I' XXX M6
T
Rl HEICT zLso VVIDTH t 1/16
MULLION t 1/16 FRACTION !/32
9/11/2015 3137 Lakeport
JELD WEN Klamath Falls, OR 9?501
hone: (541) 882-3451
MULTI -SLIDE PATIO DOOR
6 >SILL AND HEAD ANCHOR HOLES DETAIL
'-0012967-397.ipt P012967
IT5 N&L