HomeMy WebLinkAbout21-3236 (2)City of Zephyrhillsvl;
5335 Eighth Street
Zephyrhills, FL 33542
FIR - 03236-2021
Phone: (813) 780-0020
Fax: (813) 780-0021
Issue Date: 1210212021
�
1
.o ».x ,�;+:, l4 "4,.'y" "� Y1�
����T"�'�.t�c�»>'�,, � �: � rr`sP;�'S 'J '.�1�� "•�s v��, "�°3„s J � , '�'.�i1��. �i.,�� ; }��?,
35 25 21 0010 10500 0000 7050 Gall Boulevard
zY 3Y �v}5�';r1Z�117�S
ty. Name: ADVENTIST HEALTH Permit Type: Fire Contractor: COX FIRE PROTECTION,
SYSTEM/SUNBELT INC Class of Work: Sprinkler System INC.
Address: 7050 Gall Blvd Building Valuation: $2,937.00
ZEPHYRHILLS, FL 33541-1347 Electrical Valuation:
Phone: (813) 788-0411 Mechanical Valuation:
Plumbing Valuation:
Total Valuation: $2,937.00
Total Fees: $145.00 `
Amount Paid: $145,00
Date Paid: 12/2/2021 4:01:OOPM
System Acceptance Inspection
Sprinkler System Plan Review
•N FEES: (c) With respect to Reinspection fees will comply• •. Statute 553.80(2)(c)
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
entities such as water management, state agencies or federal agencies.
All- EEM-701r=
Complete Plans, Specifications add fee Must Accompany Application. All work shall be performed in
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE
fe f � -d L
CONTRACTOR SIGNATURE PE IT OFFICER I
PERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTIO
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT
-, i • D. FROM
WEATHER
813-780-0020 City of Zephyrhills Fire Fax-813-780-0021
Permit Application Phone Contact for Permit 813 "�980
Date''R! "�eiv 11/17/2021
3282
ME, O'N""'I" RMIANNOMWIN, R., RN011410M RNMEP 'W' Q�vo'
Owners Name I ADVENTIST HEALTH SYSTEM/SUNBELT INC I Owner's Phone Number
Owner's Address 1 7050 GALL BLVD, ZEPHYRHILLS, FL 33541-1347
Fee Simple Titleholder Name Titleholder Phone Number E=
Fee Simple Titleholder Address
Job Address
Sub Division
Bio-Hazard Waste Storage - ANNUAL
Comm Exhaust Kitchen Hood/Duct
Controlled Bum
Emergency Generator < 30 kw
Emergency Generator > 30 kw
Fire Protection Maintenance - ANNUAL
=] eml Ej] Rter
Sprinkler E3 0 0
Fire Alarm ED El 0
Hood Cleaning El El 0 0
Hood Suppression E] El 0 0
Fire Alarm Installation
Fire Pumps
Contractor
Signature
Address
ELECTRICIAN
Signature
Address
PLUMBER
Signature
Address
MECHANICAL
Signature
Address
OTHER
Signature
Address 7910 Professional Place, Tampa, FL
Directions:
I m
N
Lot #
Fumigation Tent
Hazardous Material (Tier 11 or RQ Facility) ANNUAL
Hood Installation
LP/Natural Gas -Installation
LP/Natural Gas -ANNUAL Sale
Places of Assembly -ANNUAL
Recreational Burn
Sparklers
Sprinkler System 4R9WAe#efte- Sprinkler head relocation - 7 sprinkler heads
Standpipes (Sprinkler Sys)
4-t
Torch Roofing/Tar Kettle (717)
/ —1 jjll_'�
Waste Tire Storage ANNUAL
R
Valuation of,
Company
F_
Registered
L=/ N Fee Current
Y/N
License #
Company
Registered
Fee Current
License #
Company
L�=N —Fee Current
/ �N
Registered
License #
Company
Registered
YIN Fee Current
Y N
Y'
License #
Company
Cox Fire Protection, Inc.
Registered
Fee C !nt
N
Licenseed"'
IFPC14-000005 1
Fill out application completely.
Owner & Contractor sign back of application, notarized (Or, copy of signed contract with owner)
If over $2500, a Notice of Commencement is required (Mechanical work over $5000)
Supply two (2) sets of drawings with applicable documentation
Allow 10-14 days for review after submittal date. Parcel # - obtained from Property Tax Notice (hftp://appraiser.pascogov,com)
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to "deed" restrictions"
which may be more restrictive than County regulations. The undersigned assumes responsibility for compliance with any
applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or
contractors to undertake work, they may be required to be licensed in accordance with state and local regulations. If the
contractor is not licensed as required by law, both the owner and contractor may be cited for a misdemeanor violation
under state law. If the owner or intended contractor are uncertain as to what licensing requirements may apply for the
intended work, they are advised to contact the Pasco County Building Inspection Division —Licensing Section at 727-847-
8009. Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign
portions of the "contractor Block" of this application for which they will be responsible. If you, as the owner sign as the
contractor, that may be an indication that he is not properly licensed and is not entitled to permitting privileges in Pasco
County.
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2,500.00 or more, I
certify that I, the applicant, have been provided with a copy of the "Florida Construction Lien Law —Homeowner's
Protection Guide" prepared by the Florida Department of Agriculture and Consumer Affairs. If the applicant is someone
other than the "owner", I certify that I have obtained a copy of the above described document and promise in good faith to
deliver it to the "owner" prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and
that all work will be done in compliance with all applicable laws regulating construction, zoning and land
development. Application is hereby made to obtain a permit to do work and installation as indicated. I certify
that no work or installation has commenced prior to issuance of a permit and that all work will be performed to
meet standards of all laws regulating construction, County and City codes, zoning regulations, and land
development regulations in the jurisdiction. I also certify that I understand that the regulations of other
government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in
this affidavit prior to commencing construction. I understand that a separate permit may be required for electrical work,
plumbing, signs, wells, pools, air conditioning, gas, or other installations not specifically included in the application. A
permit issued shall be construed to be a license to proceed with the work and not as authority to violate, cancel, alter, or
set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from thereafter
requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid
unless the work authorized by such permit is commenced within six months of permit issuance, or if work authorized by
the permit is suspended or abandoned for a period of six (6) months after the time the work is commenced. An extension
may be requested, in writing, from the Building Official for a period not to exceed ninety (90) days and will demonstrate
justifiable cause for the extension. If work ceases for ninety (90) consecutive days, the job is considered abandoned.
OWNER OR AGENT
Subscribed and sworn to (or affirmed) before me this
by
Who is/are personally known to me or has/have produced
as identification.
Public
Commission
Name of Notary typed, printed or stamped
CONTRACTOR
Subscribed and sworn to (or affirmed) before me this
11/17/2021 by Kevin Scott Cox
Who is/are personally known to me or has/have produced
as identification.
t 'A r`
N- e
,`C Notary Public
Commission No. HH 074222
Sandra C. Cress
Name of Notary typed, printed or stamped
FIRE 7910 PROFESSIONAL PLACE
Co
' L x I PROTECTION JAVPA, FLORIDA 33637
PHONE: (813) 980-3282
FAX: �
�S 13) 980- 0631
WEB: COXFIRE.COV
Jill
7910 PROFESSIONAL PLACE; TAMPA, FLORIDA 33637 1 PHONE: (813)980-3282 1 FAX: (8113)980-0631 I WWW.COXFIRE.COM
PIPE: SCHEDULE 1 O/SCHEDULE 40 BLACK STEEL ..
FITTINGS: BLACK DUCTILE IRON FITTINGS
GROOVED FITTINGS
GROOVED COUPLINGS
HANGERS: LISTED HANGER RINGS
LISTED ALL THREAD ROD
LISTED BEAM CLAMPS
LISTED CONCRETE HANGER
10
CHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49068
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Mimgem Standard and Quick Response Concealed Pendent SphnklerVK402
and HP Sprinkler VK463 are thermosensitive glass -bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of smooth ceiling is
desired,
The sprinkler is pre -assembled with a threaded adapter for installation with a low-pro-
filecoveraanemb|ytho1pmvideouptn}6''(127mm)ofvortine|adjuo(ment.Thehwo-
pieue design allows installation and testing of the sprinkler prior to installation of the
cover plate. The "push -on", "thread -off' design of the concealed cover plate assembly
allows easy ina1e||uhon of the cover plate o#*r the uyn0am has been tested and the
ceiling finish has been applied. The cover assembly can he removed and noinsta||ed,
allowing temporary removal of ceiling panels without taking the sprinkler system out
ofservice orremoving the sprinkler.
2. LISTINGS AND APPROVALS
cWbwsListed: Category VN|V
FM8Approval: Class 2O15
[�J NYC Approved: ME&Q0-82-E.Volume 82
VdSApproved: Certificate G4ODO021
LPCBApproved: Ref. No. 096e/12
CECertified: Standard EN12258-1.EC-certificate ofconformity O832-CPD-2O32
Refer toApproval Chart 1 on page 54x and Design Criteria on page 54d for cULua Listing requiromenta, and refer to
Approval Chart 2 and Design Criteria on page 54e for FM Approval requirements that must be followed.
Specifications:
Available since 2006.
Minimum Operating Pressure: 7psi V].5 bar)*
Maximum Working Pressure: Sprinkler VN463 is rated for use with water working pressures ranging from the minimum
7 psi (0.6 bar) upto260psi (17.2bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by
locating ''250"stamped *nthe deflector. Sprinkler VK462ierated 0uamaximum 176 psi (12bar) vwwp.
Factory tested hydrostatically to5D0psi (34.5bar)
Thread size: 1/2^ (15 mm) NPT
Nominal w-Factor 5,8 US, (808 metrict)
Glass -bulb fluid temperature rated 0u-65^F(-55°C)
Patents Pending
~nuLvs uoun0. FM Approval, and mrPx 13 matana require e minimum of poi (0.5 bar). The minimum operating pressure for LPCe and cc
Approvals ONLY inspsi (o.00ueA
fwomuK-mmo,measurement shown iawhen pressure |omeasured mBar. vvoenpressure |nmeawvommxPa.uwdememetncK-fa*oruxowmuy1o.o.
Material Standards:
Sprinkler Body: BnaaaUNS-C8440O
Deflector: Copper UNG-C1S500for Sprinkler VK4O2 Viking Technical Data may be found on
Phosphor Bronze UNG'C51OUOfor Sprinkler VK463 The Viking Corporation's Web site at
Deflector Pins: Stainless Steel Alloy
Bulb: Glass, nominal 8mmdiameter The Web site may include a more recent
Pip Cap and Insert Assembly: Copper VN8'C11OOOand Stainless 8Vaa| edition of this Technical Data Page.
UNS'S3U4OO
Button: BmaaUNG'C3O00O
Screws: 18-8Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze UNS-Cb1U0O
Cover Adapter: Cold Rolled Steel UNS-G1 0080, Finish: Clear Chromate over Zinc Plating
Form No. F_1U3U05 Replaces page 54a-f,dated April 8.2O11.
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9601 Technical Services: $77-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.col
Cover Assembly Materials:
Cover: Copper UNS-C11000
Base: Brass UNS-C26000 or UNS-C2680#
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: (Also refer tnthe current Viking price |ist.)
Viking MirageO Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must beordered separately:
Sprinkler: Base Part No. 1@5O3AorHPBase Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:
Temperature Suffix: 155°F(68^C)=B. 175°F(79"C)=D.200"F(93,C)=E
For example, sprinkler VK4O3with a155°F(OO^C) temperature rating =13O67A8
Cover Plate Assembly: Base Part No. 135O4(2-3/4^diameier).Base Part No. 13O42(3-5/16^diometer).orBase Part No, 153S4
(square cover plate, 5-5/10^ diameter)
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F'89, Bright Bramn= 8.Andque Bnaao= B-/A, Brushed Brass = B-/B.
Brushed Coppar= Ef8, Painted White = M'AA1, Painted Ivory = M-/|. Painted Black = M-/8
Temperature Suffix: 135"F(5T°C)UL(13&"F(59,C)FMand LPCB)=A. 165~F(74°C)=C
For example, cover 135O4with aPolished Chrome finish and e105°F(74°C)temperature rating =135O4FC.
Note: Square cover plate 1o3awvuLvoListing |vfor the 13o^F(o7`C) temperature rated cover plate only. Refer mthe Approval Chart.
Available Finishes And Temperature Ratings: Refer toTable 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
SphnWerVVrenchwm^°:
A. Heavy Duty Wrench Part No. 14O47W/B(available since 2O08). or
B.Head Cabinet Wrench Part No. 14031°°°(available since 2OOO)
C. Optional Concealed Cover Plate Installer Tool Port No, 14412 for cover 13504. or Pert No. 14867 for the large diameter cover
(available since 2O07)
—Requires a '/2" ratchet (not available from Viking), —Optional for removal of the protective cap, Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731 A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
6. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
Continued heating of the exposed sprinkler causes the heat -sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yuke, pip -cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish orcontrol the fire.
oil
7. AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor nrcontact The Viking Corporation,
8. GUARANTEE
For details of warranty, refer to ViNng's current list price schedule mcontact Viking directly,
January 27, 2012 Sprinkler 54c
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler NPT Thread Nominal Maximu Listings and ApprovaIS4
Base Part No.' SIN __ Size K-Factor 1 Water Wo2king (Refer also t DesIVn C iteria on page 54&)
—Inch7mm I U.S. I metrie I Pressure I cULus' NYC dS1 LPCB
Standard Response Applications
CZ11
Quick Response Applications
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AV1, BX1 AV1, BWV
13667A VK463 1/2" 15 5,6 1 80,6 250 psi (17.2 bar)' AV1, BX1 AV1, BW161 I
Cover Plate Assembly Temperature Ratings' Cover Plate Assembly Finishes"
Sprinkler Temperature Ratings V - 135 'F (57 'C) cULus Listed cover 135041, 136421 (large diam-
eter), or 153941 (square cover plate) 1 - Polished Chrome, Brushed Chrome,
A - 155 -F (68 -C) W - 165 'F (74 'C) cover 135041 or 136421 (large diameter) Bright Brass, Antique Brass,
B - 175 'F (79 'C) and 200 'F (93 'C) X - 165 'F (74 'C) cover 135041, or 136421 (large diameter) Brushed Brass, Brushed Copper,
C - 200 -F (93 -C) Y - 135 'F (57 'C) cover 135041 LPCB Approved as 139 'F (59 'C) Painted White, Painted Ivory, or
Z - 165 *F (74 'C) cover 135041 Painted Black
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0�
The Water Working Pressure rating is stamped on the deflector.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process, Check with the manufacturer for any
additional approvals.
Listed by Underwriter's Laboratories for use in the U.S, and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol, 32,
7 VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021.
(( Certified, Standard EN 12259-1, EC -certificate of conformity 0832-CPD-2032.
The 135/139 'F cover has an orange label. The 165 'F (74 'C) cover has a white label.
"Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Sprinkler 54d January 27, 2012
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-946-9601 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
MirageO Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
For hazard occupancies up to and including Ordinary Hazard, Group 11,
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
• Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in. (102 mm).
Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials,
b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight.
c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-
cies, except in OH4.
NOTES: Due to the design the sprinkler type 'Domed-CCP' shall not be installed in false ceilings in which the false ceiling space is protected by a
water extinguishing system.
Due to the design the sprinkler type 'Domed-CCP' shall not be installed in false ceilings in which during a fire the pressure above the false ceiling
may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
1. Prepare the sprinkler key.
2. Remove the plastic cover.
3. Hold the sprinkler with the wrench and fasten it.
4. Replace the plastic cover and do not remove until the cover is installed.
IMPORTANT- Always refer to Bulletin Form No. F — 091699 - Care and Handling of Sprinklers. Also refer to page
SRI-3 or QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-
dards, whenever applicable.
------- -------
Do
41
Identification of Custom Paint Color;
Alt custom color painted cover plates will
have an identifying label affixed to the
inside of the cover that indicates custom
color and will have a representative sample
(a paint dot) of the paint on the [abet,
Figure 1: Identification of Custom Paint Color for Concealed Covers
_77 DO NOT PAINT
7111
it
--*-3--5/16' C84.1 rnm)
Figure 2: Square Cover Assembly 15394
January 27, 2012 Sprinkler 54e
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-946-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
WMEM=
11111IMMIIIIII
I1 al
NPT Thread Size
Maximum FM Approvals'
Water Working Pressure (Refer also to Design Criteria below.)
175 psi (12 bar) AW1, BX1
Cover Plate Assembly Temperature RatingS4 Cover Plate Assembly Finishes'
Sprinkler Temperature Ratings W - 139 'F (59 'C) cover 135041, 136421 (large diameter), 1 - Polished Chrome, Brushed Chrome, Bright
A - 155 -F (68 -C) or 153941 (square cover plate) Brass, Antique Brass, Brushed Brass,
6 - 175 'F (79 'C) and 200 'F (93 'C) X - 165 'F (74 'C) cover 135041, 136421 (large diameter), or Brushed Copper, Painted White, Painted
153941 (square cover plate) Ivory, or Painted Black
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric Mactor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric Mactor shown by 10.0.
This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any addi
approvals.
The 139 'F (59 'C) cover has an orange label. The 165 'F (74 'C) cover has a white label.
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint c
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non -Storage concealed pendent sprinkler as indicated in the FM
Approval Guide, For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling,
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
11111r. ITIPM 110
standards, whenever applicable.
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49068
Telephone: 269-945-9501 Technical Services: 877-384-6464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler
Wrench
(Part No,
10ww/B*x
is shown)
** //2^ ratchet
3 required (not
Kuhie From V|k|ng)
Step 1' CorePuoy slide the
wrench sideways around
the deflector and pins,
Sprinkler
Frame
Arms
Step 2' Carefully press the
wrench upward and turn slightly
to ensure engagement with the
sprinkler wrench ftuts,
Sprinkler
Wrench
rl«*
w[v[R install the sprinkler
by applying the installation
wrench across the frame arms,
DO NOT o,ertighten,
Use only the designated
sprinkler wrench' Viking Part
Number 14047W/B or 14031.
DO NOT apply more than
25 ft� ibs, of torque, A teak
tight seat should we achieved
by turning the sprinkler
clockwise 1 to 1-1/2 turns
beyond finger tigh+.
Figure 3: Sprinkler Installation and Correct Use mWrenches
Note' Upon sprinkler activation, the deflector descends
to approximately 13/16^ (20.6 nn) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Form No. F_1U3OO5 Replaces page 54a-f,dated April 8.2O11.
11 1`111111 11111 1 1 1 .
1,1, 1 1 , i,i � � Ii I �6=1 - -
0 2 0 0- 0 -0 0
LOJEnIgnmunTay
ASTIVI A795 Specification for Black and Hot -Dipped Zinc Coated (Galvanized)
Welded and Seamless Steel Pipe for Fire Protection Use
ANSI/ASTM A 53 Specification for Black and Hot -Dipped Zinc Coated (Galvanized)
Welded and Seamless Steel Pipe
0=0
Manufacturers may vary. As per Section 6.3.2, 6.3.3 & 6.3.7.10 of NFPA 13-2013 edition, all pipirR
shall be marked along its length to properly identify its type, schedule and manufacturi
standard. I
Additional approvals or listings are not required when:
1 . Steel pipe meeting the above referenced ASTM specifications is used and joined by welding
or roll -grooved pipe and fittings, the minimum nominal wall thickness for pressures up to 300
psi shall be in accordance with Schedule 10 for sizes up to 6 inches and .188 inches for 8" —
10" pipe.
2. Steel pipe meeting the above referenced ASTM specifications is used and joined by threaded
fittings, the minimum wall thickness shall be in accordance with Schedule 40 in sizes less than
8 inches for pressures up to 300 psi.
Exception: Pipe meeting the above referenced ASTM specifications with wall thickness and
pressure limitations less than Schedule 40 for threading or Schedule 10 for welding and roll -
grooving, which have been investigated for suitability in automatic sprinkler installations and listed
for this service, shall be permitted when installed in accordance with their UL or FM listing
limitations.
All steel piping is to be installed in strict accordance with the guidelines of NFPA 13 and therefore
requires no special submittal of specific manufacturer's installation instructions.
atm=•trn
All fittings to be used on this project meets or exceeds the requirements of one or more of the
following standards as required by Section 6.4 of NFPA 13-2013 edition:
ILLI� III �!11111 Jill �11111111 III ... �111 111��l�l�llqllly�-
MTN M11
I
1111 Jill,
ASTrb A 234 Specification for Piping Fittings of Wrought Carbon Steel an,'i
Alloy Steel for Moderate and Elevated Temperatures
Threaded Fittings
All threaded fittings shall have threads cut to ASME 131.20.1, Pipe Threads, General Purpose
(inch), per Section 6.5. 1.1 of NFPA 13-2013 Edition.
Manufacturers may vary. All fittings shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• AnvilStar
• Anvil
• Smith Cooper
• Vanderwater International
•BIS
Lilt 1 1, TWTr7I I
Welded Fittings
All welded fittings shall be in accordance with Section 6.5.2.2 through 6.5.2.6, NFPA 13-2013
Edition. Welded sprinkler pipe shall be it welded.
Manufacturers of welded outlets may vary, All fittings shall be of the same manufacturer for a
single project.
• Aegis technologies
• Sigma Piping Products
• Anvil/Merit
• Smith Cooper
All welded fittings shall be installed in strict accordance with the guidelines of NFPA 13 and
therefore requires no special submittal of specific manufacturer's installation instructions.
Grooved Fittings
All grooved joints shall contain cut, rolled, or cast grooves that are dimensionally compatible with
the couplings, per Section 6.5.3.1 of NFPA 13-2013 Edition. All grooved couplings and fittings
shall be listed in compliance with standardized groove specifications.
Manufacturers may vary. All fittings shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
® Victaulic/Firelock
• Anvil
• Titus
OVUM in, Ow WHO,
LqTOTI - i no r; M, •
All Hangers to be used on this project meets or exceeds the requirements standards required by
Section 9.1 of NFPA 13-2013 Edition.
All sprinkler piping shall be supported from the building structure. The components of hanger
assemblies shall that attach directly to the building structure and pipe shall be listed. Hanger
spacing shall not exceed the limits provided in NFPA 13-2013 Edition.
Hanger Rod
All threaded rod shall meet the requirements of NFPA 13-2013 Edition, Section 9.1.2.
Manufacturers may vary. All rod shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
• Erico
• Caddy
• Anvil
• Vulcan
• FPPI
Concrete Fasteners
Concrete Fasteners shall be a listed insert set in concrete or list post -installed anchor.
Manufacturers may vary. All fasteners shall be of the same manufacturer for a single project.
Acceptable Manufacturers may include:
INUM U01001
Steel Attachment
Steel attachments shall be a listed drilled fastener or listed beam clamp. Drilled fasteners may
attach to the beams, purlins, deck or any other acceptable steel structure.
Manufacturers may vary. All fasteners/clamps shall be of the same manufacturer for a single
project.
Acceptable Manufacturers may include:
• Sammy (Including Sammy Xpress)
• Anvil
• Globe Pipe Hangers
• nVent (Caddy & Erico)