HomeMy WebLinkAbout22-3697City of :'hi Eighthyrihills 5339 Zephyrhills, FL 33542 • 780-0021 F� ONTRACTOR SIGNATURE PERMI z L Issue Gate: 03/04/2022 PE IT OFFICE CTION Sequence of Operation ACTIVATION OF A MANUAL PULL STATION ON ANY LEVEL THE FACP SHALL - A. ACTIVATE AUDIBLE AND VISUAL NOTIFICATION APPLIANCES ON FLOOR OF INCIDENT, FLOOR ABOVE & FLOOR BELOW. B. THE FACP & AN NUNCIATOR WILL DISPLAY THE ALARM LOCATION & ILLUMINATE THE ALARM LED. C. TRANSMIT ANALARM SIGNAL TO A U.L LISTED CENTRAL STATION. ACTIVATION OF A CEIL114G SMOKE DETECTOR ON ANY LEVEL THE FACP SHALL: A. ACTIVATE AUDIBLE AND VISUAL NOTIFICATION APPLIANCES ON FLOOR OF INCIDENT, FLOOR ABOVE & FLOOR BELOW. B. THE FACP & AN NUNCIATOR WILL DISPLAY THE ALARM LOCATION & ILLUMINATE THE ALARM LED. C. TRANSMIT AN LARM SIGNAL TO A U.L. LISTED CENTRAL STATION. D. SHUT DOWN ALL AHU'S. ACTIVATION OF ANY SPRINKLER WATER FLOW SWITCH SHALL: A. ACTIVATE AUDIBLE AND VISUAL NOTIFICATION APPLIANCES ON FLOOR OF INCIDENT, FLOOR ABOVE & FLOOR BELOW. B. THE FACP & ANNUNCIATOR WILL DISPLAY THE ALARM LOCATION & ILLUMINATE THE ALARM LED. C. TRANSMIT AN ALARM SIGNAL TO A U.L LISTED CENTRAL STATION. D. THE CONTROL RELAYS WILL SHUTDOWN ALL AHU'S OVER 2000 CFM, CLOSE THE FIRE SMOKE DAMPERS. ACTIVATION OF DUCT SMOKE DETECTORS SHALL: A. THE FACP & ANNUNCIATOR WILL DISPLAY THE SUPERVISORY LOCATION & ILLUMINATE THE SUPERVISORY LED. B. TRANSMIT A SUPERVISORY SIGNAL TO A U.L. LISTED CENTRAL STATION. C. ACTIVATES SHUTDOWN OF ASSOCIATED AHU AND OR CLOSE ASSOCIATED SMOKE DAMPERS. ACTIVATION OF TAMPER SWITCH SHALL: A. THE FACP & ANNUNCIATOR WILL DISPLAY THE SUPERVISORY LOCATION & ILLUMINATE THE SUPERVISORY LED. B. TRANSMIT A SUPERVISORY SIGNAL TO A U.L. LISTED CENTRAL STATION. FIRE PUMP MONITORING SHALL: A. THE FACP & ANNUNCIATOR WILL DISPLAY THE SUPERVISORY LOCATION & ILLUMINATE THE SUPERVISORY LED. B. TRANSMIT A SUPERVISORY SIGNAL TO A U.L. LISTED CENTRAL STATION. ACTIVATION OF THE ALARM SILENCE SWITCH AT THE FACP SHALL: A. ALL AUDIBLE & VISUAL NOTIFICATION DEVICES ON ALL LEVELS WILL TURN OFF. B. ANY NEW ALARMS DETECTED AFTER THE NOTIFICATION DEVICES HAVE BEEN SILENCED WILL REACTIVATE THE AUDIBLE/VISUAL DEVICES. C. SPRINKLER WATER FLOW ALARMS CANNOT BE SILENCED UNTIL THE WATER FLOW IS SHUT OFF. THE FACP WILL MONITOR THE SYSTEM FOR REMOVED DEVICES, OPEN FIELD WIRING, GROUNDS ON SYSTEM WIRING, AC POWER FAILURE, LOW BATTERY VOLTAGE AND PHONE LINES 1 & 2 TROUBLE. ALL SYSTEM TROUBLES WILL INDICATE AN ALARM AT THE FACP. THE DIALER WILL CALL A U.L. LISTED CENTRAL STATION THAT WILL DISPATCH THE ALARM SERVICE COMPANY. ANY ABNORMAL CONDITION SHALL: A. ANNUNCIATE AT THE MAIN FIRE ALARM PANEL AS A TROUBLE CONDITION SHOWING DEVICE LOCATION AND ID NUMBER. B. TRANSMIT A TROUBLE SIGNAL TO A U.L. LISTED CENTRAL STATION. NOTE: RESTORING ANY TROUBLE CONDITION SHALL RETURN THE SYSTEM TO NORMAL. NOTE: ALL FIRE ALARM DEVICES SHALL BE SUPERVISED. NOTE: FIRE ALARM SHALL BE MONITORED BY A U.L. LISTED CENTRAL STATION. CAJ-1221 F RATING — 2 HR T RATING — 4 HR 3/4' Metacaulk' Backer Rod Backing Mat A A ELEVATION 4 1 /2' Concrete Fk SECTION A —A CONCRETE FLOOR FIRE CAULK DETAIL SCALE: NTS 110IM44 1. ALL WIRING, & INITIATING DEVICES, SHALL BE SUPERVISED TO THE POINT OF ANNUNCIATION (F/A PANEL TO SUPERVISE THE ANNUNCIATOR PANEL ALL CIRCUITS AND INITIATING DEVICES). 2. WIRING SHALL NOT BE LOOPED THROUGH DEVICES: WIRE MUST BE CUT FOR IN AND OUT. 3. ALL DEVICES IN THE FIRE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO MANUFACTURERS SPECIFICATION. 4. DASHED LINES REPRESENT EXISTING EQUIPMENT TO REMAIN. 5. DASHED LINES WITH A SUBSCRIPT (EX) REPRESENT EXISTING EQUIPMENT TO REMAIN. 6. DEVICES WITH A SUBSCRIPT (N) REPRESENT NEW DEVICES. 7. INSTALLATION SHALL COMPLY WITH NFPA 1, 2018, APPLICABLE CHAPTERS. 8. INSTALLATION SHALL COMPLY WITH NFPA 72, 2016, APPLICABLE CHAPTERS. 9. INSTALLATION SHALL COMPLY WITH NFPA 101, 2018, APPLICABLE CHAPTERS. 10. INSTALLATION SHALL COMPLY WITH NEC 2017 APPLICABLE CHAPTERS. 11. THE DESIGN INSTALLATION COMPLIES WITH F.B.C.20 7TH EDITION. 12. THE DESIGN INSTALLATION COMPLIES WITH THE FLORIDA FIRE PREVENTION CODE (FFPC) 7TH EDITION. 13. RACEWAYS TO BE EMT, WIREMOLD, PVC & FREEWIRE (FISHED) WHERE CODE PERMITS. MINIMUM RACEWAY 3/4". 40% CONDUIT FILL MAXIMUM. 14. SYSTEM SHALL BE GROUNDED PER MANUFACTURES SPECIFICATIONS. 15. WIRE RUNS ARE NOT EXACT ROUTE OF CONDUIT OR FREEWIRE. 16. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10'-0" +/— ON SMOOTH FLAT CEILING UNLESS OTHERWISE NOTED. 17. THIS IS A BATTERY BACKUP SYSTEM, WITH 24 HOURS OF BACKUP & 5 MINUTES... ALARM. SHOULD LOSS OF NORMAL 120 VAC OPERATING POWER OCCUR, THE FACP WILL AUTOMATICALLY TRANSFER TO STANDBY BATTERY. 18. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120 VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER. 19. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. 20. ALL EQUIPMENT, FIRE CAULK TO BE U.L. LISTED. 21. THIS IS AN EXISTING FULLY SPRINKLERED, 1 STORY BUILDING. 22. THE ROOM CONTAINING THE FACP IS MECHANICALLY VENTED. 23. THIS IS A LISTED CERTIFICATED CENTRAL STATION SERVICE FIRE ALARM SYSTEM. 24. MAXIMUM MOUNTING HEIGHT FOR FACP AND POWER SUPPLIES SHALL BE 6' TO THE TOP ON THE ENCLOSURES. CAJ-3026 F RATING — 2 HR Concrete Block (CMU) T RATING —1-2 HR or Concrete Wall ELEVATION Multi —conductor •' . •. fire cable(FPL) r . 1/4' Metacaule 950 bead Metacaulk' 950 . Forced into Annulus , • ` SECTION A —A CONCRETE WALL FIRE CAULK DETAIL SCALE: NTS WL-3013 F RATING — 2 HR T RATING — 1-2 HR A CA 2 Layers of 5/8' UL Classified Gypsum Wallboard Multi —conductor ELEVATION fire cable(FPL) 1/4' Metacaulko 950 bead— Metacoulk• 950--/ Forced into Annulus SECTION A —A GYPSUM WALLBOARD FIRE CAULK DETAIL SCALE: NTS WIRING METLIODS ALWAYS BREAK A WIRE BEFORE CONNECTING IT TO A FIRE ALARM DEOICE, NEE] ER LOOP AN UNBROKEN WIRE UNDER ANY TERMINALn CORRECT INCORRECT 61Z�1 6L'b! CONNECT ONLY TWO WIRES UNDER EACE] WIRE NUT OR TERMINALIZ CORRECT INCORRECT CORRECT INCORRECT 11 FIRE ALARM SYMBOLS QUANTITIES M � EL SYMBOL DESCRIPTION MOUNTING INFORMATION EX SK5208 FFAcPl FIRE ALARM CONTROL PANEL TOP OF PANEL AT 6' A.F.F. 1 B10R-1640-12OW ENCLOSE CO-M-MI UNIVERSAL DUAL PATH COMMUNICATOR TOP OF PANEL AT 6' A.F.F. EX 2W-B Q SMOKE DETECTOR SEE INSTALLATION INSTRUCTIONS EX P2W NC HORN / STROBE - CEILING MOUNTED 1900 BOX OR TWO GANG OLD WORK SCOD jE__ OF WORK - THE SCOPE OF WORK FOR THIS PROJECT IS THE INSTALLATION OF A SOLE PATH CELLULAR COMMUNICATOR TO THE EXISTING SK5208 FIRE ALARM SYSTEM TO REPLACE PHONE LINES. DEVICE TO BE INSTALLED SHALL BE LOW VOLTAGE, POWER LIMITED, 24VDC AND U.L. LISTED FOR FIRE ALARM USE. DEVICES TO BE INSTALLED IN ACCORDANCE WITH FLORIDA FIRE PREVENTION CODE 7TH EDITION, NFPA-1 & NFPA —101 CODE 2018 EDITIONS WITH FLORIDA CHANGES REFERENCE FAC 69A-3.012 FOR OTHER ADOPTED NFPA STANDARDS. ALL WORK SHALL COMPLY WffH NFFA CODES AND STANDAIM REVIEW DATER 2c':" j- CITY OF ZE RH FIRE AND LIFE SAFETY EXAMRM I MOUNTING REQUIREMENTS I N.F.P.A_ 72 2013 ED. FIGURE A_17.3.2.1 NOTE YEAaxtoAENIS SHOW MTV HE CLOSEST OF T ACCEPTED HERE x Q TOP OF DETECTOR N ACCEPTED HERE WALL OUNTED SMOKE DETECTOR SIDE WALL CEILING MOUNTED SMOKE / HEAT DETECTOR—� CEILING 0 r7 zo Z Fa m0aa°° L.=w z �o y W ,-- W m U) N aO �onz o a F= maw 0 Lam"' vz N.F.P.A. 72 2013 ED_ SECTION A.17.7.4.1 l 4.. S MIN. I ■ z A/C SUPPLY DIFFUSER ACCEPTED HERE X W N N U C-4 AUDIO / VISUAL n — AND VISUAL -ONLY m O as m DEVICES NEVER HERE �w z SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW N.F.P.A. 72 2013 ED. SECTION 18.5.5.5.7 wo 0w� L6 Z Q NCO O N O to (n ^ 0 COrnzQF _jaw 0u:v' L- z N.F.P.A. 72 2013 ED- FIGURE A.17.3.1.3.1 NOTE WASUREW NM SHOW ARE TO IHE CLOSEST OF THE <r X Q N REVISIONS N v L0 � '� M � J � LL U � U)V ,fin i CM cc t6 LLI 4% N w °6 U CO Z >- I— G7 Q O C7 Z WWLLQ �O Z z W W W aO Q JU) W U� z00 Cn— Ln LLJ F_ cn _ U z< Q� Q) > 00 Lo C� Q ry zQ U > U LLJ � n Q Q - O� Oo�-0 I� U DD , N cn (n N 0 W WALL MOUNTED O HEAT DETECT DOOR WIDTH FINISHED ALL `E3-1 WALL--, DWG #: INSERT CAD NAME o REVISION: # MANUAL DATE: 2/2/2022 MAGNETIC PULL DOOR -STATION HOLDER ` SIDE WALL • - WITHIN 5' -0^r o0 FROM DOOI Q z Q p ,,� PER NFPA L� 0 72 2013 aoNa�N 17.14.8.4 0 <0C'i SCALE: AS NOTED DRAWN BY J.J. W Iff ► 1 SHEET FA— 1 of 2 COMMUNICATOR TROUBLE ---\ WWI - - - I - - - - - -I - - - �- - - - - - ....................... EXISTI N SYSTEM DEVICE I THESE AR�� EMAI N Al UNCGHA GED A . EX Z5-1<F> � J Z6-1(T> EX E B I . k IF . 'L —, Z3-1 - - -EX L- -Z4-1 NE2� J> � 76 uV r FACP X ------ PARTIAL MAIN FLOOR FIRE ALARM PLAN SCALE: 1 /4" = 1'- 0" AREA OF WORK 150 SQ FT ENTIRE FLOOR 15,841 SQ FT at Communicator www.boschsecuCity.com BOSCH - r Invented for life The B465 Conettix Universal Dual Path Communicator converts the Public Switch Telephone Network (PSTN) digital dialer, or dry contact outputs from an intrusion/ fire control panel to an IP signal for transmission over the Ethernet or cellular network. The B465 Conettix Universal Dual Path Communicator is UL 864 10" Edition approved per NFPA 72 version 2013. The module can use its built-in Ethernet connection, and/or an optional Conettbr plug-in cellular module (64401B441/13442/13443) to send reports to the central station receiver. Automation programming for the supported control panel remains unchanged with the installation of the B465 module, thus simplifying the installation process This allows for a smooth transition from the PSTN realm into IP. All messages generated internally by the B465 are shown in Contact ID format at the central station. The module can be powered from a 16-5 VAC transformer or 24 VDC power supply. I V W W F. Q n---- P. Compatible with any control panel using Contact ID, SIA, Pulse 3/1 or Pulse 4/2 communication formats (auto detecting) ► No control panel reprogramming required to install ► Supports Ethernet directly and optional plug-in cellular communication technologies in single, or multi -path configurations ► Supports four configurable inputs and three configurable outputs ► Approved for Commercial Fire/Burglary applications as sole, primary, or secondary communication path The B465 simulates dial tone and line voltages when the digital dialer has a report to send. The module simulates a PSTN connection to the central station. The module decodes the control panel's PSTN dialer report and sends the decoded reports by IP connection using Bosch's Conetix Protocol to the Conettix D6600, D61001Pv6, or D6100i Communication Gateway/Receiver (referred to as the receiver)- When the receiver acknowledges receipt of the message, it sends an acknowledgement report to the module which in turn sends an acknowledgement to the connected control panel. This process maintains true end -to -end security. i A Calart�-Desrxipfim Y— kdnnion/firecontrol pawl _ ....... ....... 2 — Control panel phmefrte connections 3 — B465 Conettix Universal Dual Path Communicator 4---B44xplug-incellular communicator - 5 — Ethemet connection (LAN/WAN) 6 — Internet 7— Cellular communication tocellularcarrier 8 — Cellular carrier network 9 — Conett'a receiver/gateway 10 — Conettix receiver/gateway 11—Monituringcenter automation -. PSTN inputs (2) When the control panel's PSTN dialer sends a message, the module simulates a PSTN connection to the central station. The module connects to the host control panel through either one or both of the Phone Line inputs. Both Panel Line 1 and Panel Line 2 of the module run 28 VDC and support Contact ID (4 and 10 digit account codes), Pulse 3/1, Pulse 4/2, and SIA communication formats. The B465 is setup to auto detect the communication format which eliminates programming steps. IP Communication options The module uses the on -board Ethernet connector, and/or optional B440 Conettix Plug-in Communicator, Cellular (3G), B441 Conettix Plug-in CDMA Cellular Communicator, B442 Conettix Plug-in GPRS Cellular Communicator, or B443 Conettix Plug-in HSPA+ Cellular Communicator to communicate with a Conettix D6600, Conettix D6100i or a Conettix D61001Pv6 Communications Receiver/Gateway- Using Conettix IP communication protocol offers a secure path that includes anti-replay/anti-substitution features and provides enhanced security with up to AES 256-bit encryption. The module supports Domain Name System (DNS) for central station communication. DNS provides ease of use, eliminating the need to use static IP addresses as your reporting destination, and accommodates a simple solution for central station disaster recovery. Direct mire inputs The B465 provides four on -board inputs. Each input functions independently and does not interfere with the operation of the others. The module monitors the input loops for normal, shorted, or open conditions between an input terminal and any of the input common terminals. Inputs are disabled by default so no EOL resistors are required until activated - These four inputs on the B465 connect to dry contact outputs on the control panel and generate Contact ID reports instead of using a phone line connection/or in addition to using the control panel phone connection. The available functions are: • Panel System Trouble • Panel AC Fail • Panel Battery Trouble Fire Alarm • Fire Trouble Burg Alarm Burg Trouble • Fire Supervisory Each input allows the use of dry contacts or powered outputs up to 30 VDC if needed. The inputs use 2-2K EOLs to monitor the dry contact outputs when connected to dry contacts. The inputs recognize the following thresholds when using dry contacts: 2.0 to 3.0 VDC = Normal, 3.7 to 5.0 VDC = Open, 0.0 to 1.3 VDC = Short Outputs Includes three programmable output relays rated at 30 VDC, 0.1 A. These outputs can be used to show the status of the B465 or they can be connected to the control panel zone inputs for reporting B465 system faults. The three outputs consist of RELAY 1, RELAY 2, and RELAY 3. • RELAY 1 is active (energized) once the B465 is running. If the B465 detect a problem or loses power, RELAY 1 de -energizes, which can be used to indicate a system trouble on the local control panel's zone inputs, if required. Depending on the configuration required to create a system trouble on the control panel, the installer needs to use either the NO and COM or the NC and COM connections. Refer to the control panel manual for the required zone configuration to obtain the proper input response. RELAY 2 is a normally open (NO) relay with contacts that dose when the desired function programmed is detected. • RELAY 3 is a normally open (NO) relay with contacts that dose when the desired function programmed is detected. B SCH B455 COMMUNICATOR BATTERY CALCULATIONS Standby battery requirements and calculations Standby battery calculations B C Standby Power On Normal Alarm Current (an ) Current (mA) (Model Number Qtv Each Qty Total - I Each Unit Qty Total _ Us�J1 Unit B4465 150 x 1 -150 230 x 1 - 230 B46 T 23 x 1 = 23 23 x 1 ■ 23 1344A-V 1 35 at i = 35 150 x 1 M 150 Total B - 208 Totat C ■ 403 Notice! Maximum power supply current for Total B in the table above is 705 mA; and the maximum povVer supply current for Total C is 000 rnA_ Total 2 Hours( Total C Alarm Cdntingericy Operation r 208 I x 24, 1-- ( 3-_-- x _ 0.0833 _ � � 20 v Refer to the Application environ.ment, page 89 table. Value = Minutes of alarm operation/60 4 Total Ott requirements must not exceed the Ah capacity of batteries. - One 12v Battery - 7 Ah Total Ah' - 16.03 Ah COMMUNICATOR WILL BE USED AS A SOLE PATH COMMUNICATOR AND COMMUNICATE VIA CELLULAR ONLY. CELLULAR TROUBLE Z1-10 120VAC FROM PANEL A CIRCUIT 14 DISCONNECT LOCATED NEXT TO FACP 2 #12 AWG THHN CONDUCTOR CONTROL PANEL PHONE LINE CONNECTIONS — . 1 1 MAIN FLOOR Intrusion Alarm Systems { 1310R 640 120N1i Medium Contro Panel Enclosure B10R-1540-1241N1 Medium Ca►ntrat Panel' Enc1d.s.i e www.boschsecurity.com (4 BOSCH Invented for life The BlOR-1640-12OWI Red Medium Enclosure with 16.5 VAC 40 VA Transformer houses the D1640-120WI wired -in transformer, and select Bosch control panels and modules. The enclosures is compatible with an optional enclosure tamper switch and optional lock and key set, and holds one 7 or 18 Ah batteries. Oantdy CorrponeM f.. 810R 1640-12OWlerxlosure .. 1 Hardware pack 1 Installation Guide (hardC)PY) KEYPLAN n&\ 161 ► Enclosed 16.5 VAC 40 VA transformer ► Easy to install standoff locations for mounting supporting modules ► Red matte finish for fire applications ► Punch outs for optional B46 External Annunciator (for B465 only) ► Additional slow -blow fuse included in fuse block Properties Dimensions 14mx12.5inx3in (35 6 cm x 3L8 Cm x7.6 an) Material 1.0 min (20gaugel cold-rolledsteel Cola lled Environmental considerations Temperature (operating) (rC to+49°C (•32°F to --120T) Mounting considerations Mount in dry indoor locations, Power requirements voltage (operating) .. 120VACimunaltofirsebtodt ._.. _. current(mmamun) <O-5A .. _ AREA OF WORK 0-FT 5-FT 1-FT 10-FT SCALE: 1A THE DESIGN INSTALLATION COMPLIES WITH F.B.C. 2020 7TH EDITION, RE\ASIONS 04 qeA Iq ■ Y toM V M U. VI � V t � N U � Q W � 0 O N lyNN >- �0� QOQZ Z WLLQ - -� d Z d W W Q z 00 tJi W cn = U Z< Q > L0 Lo °�QC <6 ZQ oQ W > vQl) CL � DUB 0� 00 LL,(f)o � 00 ► a� Ll_ E) cn IJ 0 Zo DO WO Do Jo Q Lo >F I DWG #: INSERT CAD NAME REVISION: # DATE: 2/2/2022 SCALE: 1 /4-=V-0- DRAWN BY J.J. CHECKED BY SHEET F A — 2 of 2