Sequence of Operation
ACTIVATION OF A MANUAL PULL STATION ON ANY LEVEL THE FACP SHALL -
A. ACTIVATE AUDIBLE AND VISUAL NOTIFICATION APPLIANCES ON FLOOR OF INCIDENT, FLOOR
ABOVE & FLOOR BELOW.
B. THE FACP & AN NUNCIATOR WILL DISPLAY THE ALARM LOCATION & ILLUMINATE THE ALARM
LED.
C. TRANSMIT ANALARM SIGNAL TO A U.L LISTED CENTRAL STATION.
ACTIVATION OF A CEIL114G SMOKE DETECTOR ON ANY LEVEL THE FACP SHALL:
A. ACTIVATE AUDIBLE AND VISUAL NOTIFICATION APPLIANCES ON FLOOR OF INCIDENT, FLOOR
ABOVE & FLOOR BELOW.
B. THE FACP & AN NUNCIATOR WILL DISPLAY THE ALARM LOCATION & ILLUMINATE THE ALARM
LED.
C. TRANSMIT AN LARM SIGNAL TO A U.L. LISTED CENTRAL STATION.
D. SHUT DOWN ALL AHU'S.
ACTIVATION OF ANY SPRINKLER WATER FLOW SWITCH SHALL:
A. ACTIVATE AUDIBLE AND VISUAL NOTIFICATION APPLIANCES ON FLOOR OF INCIDENT, FLOOR
ABOVE & FLOOR BELOW.
B. THE FACP & ANNUNCIATOR WILL DISPLAY THE ALARM LOCATION & ILLUMINATE THE ALARM
LED.
C. TRANSMIT AN ALARM SIGNAL TO A U.L LISTED CENTRAL STATION.
D. THE CONTROL RELAYS WILL SHUTDOWN ALL AHU'S OVER 2000 CFM, CLOSE THE FIRE SMOKE
DAMPERS.
ACTIVATION OF DUCT SMOKE DETECTORS SHALL:
A. THE FACP & ANNUNCIATOR WILL DISPLAY THE SUPERVISORY LOCATION & ILLUMINATE THE
SUPERVISORY LED.
B. TRANSMIT A SUPERVISORY SIGNAL TO A U.L. LISTED CENTRAL STATION.
C. ACTIVATES SHUTDOWN OF ASSOCIATED AHU AND OR CLOSE ASSOCIATED SMOKE DAMPERS.
ACTIVATION OF TAMPER SWITCH SHALL:
A. THE FACP & ANNUNCIATOR WILL DISPLAY THE SUPERVISORY LOCATION & ILLUMINATE THE
SUPERVISORY LED.
B. TRANSMIT A SUPERVISORY SIGNAL TO A U.L. LISTED CENTRAL STATION.
FIRE PUMP MONITORING SHALL:
A. THE FACP & ANNUNCIATOR WILL DISPLAY THE SUPERVISORY LOCATION & ILLUMINATE THE
SUPERVISORY LED.
B. TRANSMIT A SUPERVISORY SIGNAL TO A U.L. LISTED CENTRAL STATION.
ACTIVATION OF THE ALARM SILENCE SWITCH AT THE FACP SHALL:
A. ALL AUDIBLE & VISUAL NOTIFICATION DEVICES ON ALL LEVELS WILL TURN OFF.
B. ANY NEW ALARMS DETECTED AFTER THE NOTIFICATION DEVICES HAVE BEEN SILENCED WILL
REACTIVATE THE AUDIBLE/VISUAL DEVICES.
C. SPRINKLER WATER FLOW ALARMS CANNOT BE SILENCED UNTIL THE WATER FLOW IS SHUT OFF.
THE FACP WILL MONITOR THE SYSTEM FOR REMOVED DEVICES, OPEN FIELD WIRING, GROUNDS ON
SYSTEM WIRING, AC POWER FAILURE, LOW BATTERY VOLTAGE AND PHONE LINES 1 & 2 TROUBLE. ALL
SYSTEM TROUBLES WILL INDICATE AN ALARM AT THE FACP. THE DIALER WILL CALL A U.L. LISTED
CENTRAL STATION THAT WILL DISPATCH THE ALARM SERVICE COMPANY.
ANY ABNORMAL CONDITION SHALL:
A. ANNUNCIATE AT THE MAIN FIRE ALARM PANEL AS A TROUBLE CONDITION SHOWING DEVICE
LOCATION AND ID NUMBER.
B. TRANSMIT A TROUBLE SIGNAL TO A U.L. LISTED CENTRAL STATION.
NOTE: RESTORING ANY TROUBLE CONDITION SHALL RETURN THE SYSTEM TO NORMAL.
NOTE: ALL FIRE ALARM DEVICES SHALL BE SUPERVISED.
NOTE: FIRE ALARM SHALL BE MONITORED BY A U.L. LISTED CENTRAL STATION.
CAJ-1221
F RATING — 2 HR
T RATING — 4 HR
3/4' Metacaulk'
Backer Rod
Backing Mat
A A
ELEVATION
4 1 /2' Concrete Fk
SECTION A —A
CONCRETE FLOOR FIRE CAULK DETAIL
SCALE: NTS
110IM44
1. ALL WIRING, & INITIATING DEVICES, SHALL BE SUPERVISED TO THE POINT OF ANNUNCIATION (F/A
PANEL TO SUPERVISE THE ANNUNCIATOR PANEL ALL CIRCUITS AND INITIATING DEVICES).
2. WIRING SHALL NOT BE LOOPED THROUGH DEVICES: WIRE MUST BE CUT FOR IN AND OUT.
3. ALL DEVICES IN THE FIRE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO
MANUFACTURERS SPECIFICATION.
4. DASHED LINES REPRESENT EXISTING EQUIPMENT TO REMAIN.
5. DASHED LINES WITH A SUBSCRIPT (EX) REPRESENT EXISTING EQUIPMENT TO REMAIN.
6. DEVICES WITH A SUBSCRIPT (N) REPRESENT NEW DEVICES.
7. INSTALLATION SHALL COMPLY WITH NFPA 1, 2018, APPLICABLE CHAPTERS.
8. INSTALLATION SHALL COMPLY WITH NFPA 72, 2016, APPLICABLE CHAPTERS.
9. INSTALLATION SHALL COMPLY WITH NFPA 101, 2018, APPLICABLE CHAPTERS.
10. INSTALLATION SHALL COMPLY WITH NEC 2017 APPLICABLE CHAPTERS.
11. THE DESIGN INSTALLATION COMPLIES WITH F.B.C.20 7TH EDITION.
12. THE DESIGN INSTALLATION COMPLIES WITH THE FLORIDA FIRE PREVENTION CODE (FFPC) 7TH
EDITION.
13. RACEWAYS TO BE EMT, WIREMOLD, PVC & FREEWIRE (FISHED) WHERE CODE PERMITS. MINIMUM
RACEWAY 3/4". 40% CONDUIT FILL MAXIMUM.
14. SYSTEM SHALL BE GROUNDED PER MANUFACTURES SPECIFICATIONS.
15. WIRE RUNS ARE NOT EXACT ROUTE OF CONDUIT OR FREEWIRE.
16. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10'-0" +/— ON SMOOTH FLAT
CEILING UNLESS OTHERWISE NOTED.
17. THIS IS A BATTERY BACKUP SYSTEM, WITH 24 HOURS OF BACKUP & 5 MINUTES... ALARM. SHOULD
LOSS OF NORMAL 120 VAC OPERATING POWER OCCUR, THE FACP WILL AUTOMATICALLY TRANSFER
TO STANDBY BATTERY.
18. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120 VAC,
SINGLE PHASE, 20 AMP, DEDICATED BREAKER.
19. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED FLOOR UNLESS
OTHERWISE NOTED.
20. ALL EQUIPMENT, FIRE CAULK TO BE U.L. LISTED.
21. THIS IS AN EXISTING FULLY SPRINKLERED, 1 STORY BUILDING.
22. THE ROOM CONTAINING THE FACP IS MECHANICALLY VENTED.
23. THIS IS A LISTED CERTIFICATED CENTRAL STATION SERVICE FIRE ALARM SYSTEM.
24. MAXIMUM MOUNTING HEIGHT FOR FACP AND POWER SUPPLIES SHALL BE 6' TO THE TOP ON THE
ENCLOSURES.
CAJ-3026
F RATING —
2 HR Concrete Block (CMU)
T RATING —1-2 HR or Concrete Wall
ELEVATION
Multi —conductor •' . •.
fire cable(FPL) r .
1/4'
Metacaule 950 bead
Metacaulk' 950 .
Forced into Annulus , • `
SECTION A —A
CONCRETE WALL FIRE CAULK DETAIL
SCALE:
NTS
WL-3013
F RATING — 2 HR
T RATING — 1-2 HR
A
CA
2 Layers of 5/8'
UL Classified
Gypsum Wallboard
Multi —conductor
ELEVATION fire cable(FPL)
1/4' Metacaulko 950 bead—
Metacoulk• 950--/
Forced into Annulus
SECTION A —A
GYPSUM WALLBOARD FIRE CAULK DETAIL
SCALE: NTS
WIRING METLIODS
ALWAYS BREAK A WIRE BEFORE CONNECTING IT TO
A FIRE ALARM DEOICE, NEE] ER LOOP AN UNBROKEN
WIRE UNDER ANY TERMINALn
CORRECT INCORRECT
61Z�1 6L'b!
CONNECT ONLY TWO WIRES UNDER EACE] WIRE
NUT OR TERMINALIZ
CORRECT INCORRECT
CORRECT INCORRECT
11
FIRE ALARM SYMBOLS
QUANTITIES
M � EL
SYMBOL
DESCRIPTION
MOUNTING INFORMATION
EX
SK5208
FFAcPl
FIRE ALARM CONTROL PANEL
TOP OF PANEL AT 6' A.F.F.
1
B10R-1640-12OW
ENCLOSE
CO-M-MI
UNIVERSAL DUAL PATH COMMUNICATOR
TOP OF PANEL AT 6' A.F.F.
EX
2W-B
Q
SMOKE DETECTOR
SEE INSTALLATION INSTRUCTIONS
EX
P2W
NC
HORN / STROBE - CEILING MOUNTED
1900 BOX OR TWO GANG OLD WORK
SCOD
jE__ OF WORK -
THE SCOPE OF WORK FOR THIS
PROJECT
IS THE INSTALLATION OF
A SOLE PATH CELLULAR
COMMUNICATOR TO THE EXISTING SK5208
FIRE ALARM SYSTEM TO
REPLACE PHONE LINES.
DEVICE TO BE INSTALLED SHALL
BE LOW
VOLTAGE, POWER LIMITED,
24VDC AND U.L. LISTED
FOR FIRE ALARM USE. DEVICES
TO BE INSTALLED IN ACCORDANCE
WITH FLORIDA FIRE
PREVENTION CODE 7TH EDITION,
NFPA-1
& NFPA —101 CODE 2018
EDITIONS WITH FLORIDA
CHANGES REFERENCE FAC 69A-3.012
FOR OTHER ADOPTED NFPA
STANDARDS.
ALL WORK SHALL COMPLY WffH
NFFA CODES AND STANDAIM
REVIEW DATER 2c':" j-
CITY OF ZE RH
FIRE AND LIFE SAFETY EXAMRM
I MOUNTING REQUIREMENTS I
N.F.P.A_ 72 2013 ED.
FIGURE A_17.3.2.1
NOTE YEAaxtoAENIS SHOW
MTV HE CLOSEST OF T
ACCEPTED HERE
x
Q
TOP
OF DETECTOR
N ACCEPTED HERE WALL OUNTED
SMOKE DETECTOR
SIDE WALL
CEILING MOUNTED
SMOKE / HEAT
DETECTOR—�
CEILING 0 r7
zo
Z Fa
m0aa°°
L.=w
z
�o
y W ,--
W m
U) N aO
�onz
o a F=
maw
0 Lam"'
vz
N.F.P.A. 72 2013 ED_
SECTION A.17.7.4.1 l 4..
S MIN. I ■
z A/C SUPPLY
DIFFUSER ACCEPTED HERE
X W N N
U C-4 AUDIO / VISUAL
n — AND VISUAL -ONLY
m O as m DEVICES NEVER HERE
�w
z
SYNCHRONIZE MORE
THAN TWO APPLIANCES
IN ANY FIELD OF VIEW
N.F.P.A. 72 2013 ED.
SECTION 18.5.5.5.7
wo
0w�
L6
Z Q NCO
O N
O to (n ^ 0
COrnzQF
_jaw
0u:v'
L- z
N.F.P.A. 72 2013 ED-
FIGURE A.17.3.1.3.1
NOTE WASUREW NM SHOW
ARE TO IHE CLOSEST OF THE
<r
X
Q
N
REVISIONS
N
v
L0
�
'�
M
�
J
�
LL
U
�
U)V
,fin
i
CM
cc
t6
LLI
4%
N
w
°6 U
CO
Z
>-
I—
G7 Q
O
C7
Z
WWLLQ
�O
Z
z W W
W
aO
Q
JU)
W
U�
z00
Cn—
Ln
LLJ
F_
cn
_
U
z<
Q�
Q)
>
00
Lo
C�
Q
ry
zQ
U
>
U
LLJ
�
n
Q
Q
-
O�
Oo�-0
I�
U
DD
,
N
cn
(n
N
0
W
WALL MOUNTED
O
HEAT DETECT
DOOR
WIDTH FINISHED
ALL
`E3-1 WALL--,
DWG #: INSERT CAD NAME
o
REVISION: #
MANUAL
DATE: 2/2/2022
MAGNETIC PULL
DOOR -STATION
HOLDER `
SIDE WALL
•
-
WITHIN 5'
-0^r
o0
FROM DOOI
Q z Q p ,,�
PER NFPA
L� 0
72 2013
aoNa�N
17.14.8.4
0
<0C'i
SCALE: AS NOTED
DRAWN BY J.J.
W Iff ► 1
SHEET FA— 1 of 2
COMMUNICATOR
TROUBLE ---\
WWI
- - - I - - - - - -I - - - �- - - - - -
.......................
EXISTI N SYSTEM
DEVICE I THESE
AR�� EMAI N Al
UNCGHA GED
A .
EX
Z5-1<F>
� J
Z6-1(T>
EX E B
I . k IF . 'L —,
Z3-1 - - -EX L-
-Z4-1
NE2�
J>
� 76
uV r FACP X ------
PARTIAL MAIN FLOOR FIRE ALARM PLAN
SCALE: 1 /4" = 1'- 0"
AREA OF WORK 150 SQ FT
ENTIRE FLOOR 15,841 SQ FT
at Communicator
www.boschsecuCity.com BOSCH
- r
Invented for life
The B465 Conettix Universal Dual Path Communicator
converts the Public Switch Telephone Network (PSTN)
digital dialer, or dry contact outputs from an intrusion/
fire control panel to an IP signal for transmission over
the Ethernet or cellular network. The B465 Conettix
Universal Dual Path Communicator is UL 864 10"
Edition approved per NFPA 72 version 2013.
The module can use its built-in Ethernet connection,
and/or an optional Conettbr plug-in cellular module
(64401B441/13442/13443) to send reports to the
central station receiver.
Automation programming for the supported control
panel remains unchanged with the installation of the
B465 module, thus simplifying the installation process
This allows for a smooth transition from the PSTN
realm into IP. All messages generated internally by the
B465 are shown in Contact ID format at the central
station.
The module can be powered from a 16-5 VAC
transformer or 24 VDC power supply.
I V W W F. Q
n----
P. Compatible with any control panel using Contact ID,
SIA, Pulse 3/1 or Pulse 4/2 communication formats
(auto detecting)
► No control panel reprogramming required to install
► Supports Ethernet directly and optional plug-in
cellular communication technologies in single, or
multi -path configurations
► Supports four configurable inputs and three
configurable outputs
► Approved for Commercial Fire/Burglary applications
as sole, primary, or secondary communication path
The B465 simulates dial tone and line voltages when
the digital dialer has a report to send. The module
simulates a PSTN connection to the central station.
The module decodes the control panel's PSTN dialer
report and sends the decoded reports by IP
connection using Bosch's Conetix Protocol to the
Conettix D6600, D61001Pv6, or D6100i
Communication Gateway/Receiver (referred to as the
receiver)- When the receiver acknowledges receipt of
the message, it sends an acknowledgement report to
the module which in turn sends an acknowledgement
to the connected control panel. This process maintains
true end -to -end security.
i A
Calart�-Desrxipfim
Y— kdnnion/firecontrol pawl _ ....... .......
2 — Control panel phmefrte connections
3 — B465 Conettix Universal Dual Path Communicator
4---B44xplug-incellular communicator -
5 — Ethemet connection (LAN/WAN)
6 — Internet
7— Cellular communication tocellularcarrier
8 — Cellular carrier network
9 — Conett'a receiver/gateway
10 — Conettix receiver/gateway
11—Monituringcenter automation -.
PSTN inputs (2)
When the control panel's PSTN dialer sends a
message, the module simulates a PSTN connection to
the central station. The module connects to the host
control panel through either one or both of the Phone
Line inputs. Both Panel Line 1 and Panel Line 2 of the
module run 28 VDC and support Contact ID (4 and 10
digit account codes), Pulse 3/1, Pulse 4/2, and SIA
communication formats. The B465 is setup to auto
detect the communication format which eliminates
programming steps.
IP Communication options
The module uses the on -board Ethernet connector,
and/or optional B440 Conettix Plug-in Communicator,
Cellular (3G), B441 Conettix Plug-in CDMA Cellular
Communicator, B442 Conettix Plug-in GPRS Cellular
Communicator, or B443 Conettix Plug-in HSPA+
Cellular Communicator to communicate with a
Conettix D6600, Conettix D6100i or a Conettix
D61001Pv6 Communications Receiver/Gateway- Using
Conettix IP communication protocol offers a secure
path that includes anti-replay/anti-substitution
features and provides enhanced security with up to
AES 256-bit encryption.
The module supports Domain Name System (DNS) for
central station communication. DNS provides ease of
use, eliminating the need to use static IP addresses as
your reporting destination, and accommodates a
simple solution for central station disaster recovery.
Direct mire inputs
The B465 provides four on -board inputs. Each input
functions independently and does not interfere with
the operation of the others. The module monitors the
input loops for normal, shorted, or open conditions
between an input terminal and any of the input
common terminals. Inputs are disabled by default so
no EOL resistors are required until activated -
These four inputs on the B465 connect to dry contact
outputs on the control panel and generate Contact ID
reports instead of using a phone line connection/or in
addition to using the control panel phone connection.
The available functions are:
• Panel System Trouble
• Panel AC Fail
• Panel Battery Trouble
Fire Alarm
• Fire Trouble
Burg Alarm
Burg Trouble
• Fire Supervisory
Each input allows the use of dry contacts or powered
outputs up to 30 VDC if needed. The inputs use 2-2K
EOLs to monitor the dry contact outputs when
connected to dry contacts. The inputs recognize the
following thresholds when using dry contacts: 2.0 to
3.0 VDC = Normal, 3.7 to 5.0 VDC = Open, 0.0 to 1.3
VDC = Short
Outputs
Includes three programmable output relays rated at 30
VDC, 0.1 A. These outputs can be used to show the
status of the B465 or they can be connected to the
control panel zone inputs for reporting B465 system
faults. The three outputs consist of RELAY 1, RELAY 2,
and RELAY 3.
• RELAY 1 is active (energized) once the B465 is
running. If the B465 detect a problem or loses power,
RELAY 1 de -energizes, which can be used to indicate
a system trouble on the local control panel's zone
inputs, if required. Depending on the configuration
required to create a system trouble on the control
panel, the installer needs to use either the NO and
COM or the NC and COM connections. Refer to the
control panel manual for the required zone
configuration to obtain the proper input response.
RELAY 2 is a normally open (NO) relay with contacts
that dose when the desired function programmed is
detected.
• RELAY 3 is a normally open (NO) relay with contacts
that dose when the desired function programmed is
detected.
B SCH B455 COMMUNICATOR BATTERY CALCULATIONS
Standby battery requirements and calculations
Standby battery calculations
B
C
Standby Power On Normal
Alarm Current (an )
Current (mA)
(Model Number Qtv
Each
Qty Total -
I
Each Unit Qty
Total _
Us�J1
Unit
B4465
150
x 1
-150
230
x 1
- 230
B46
T
23
x 1
= 23
23
x 1
■ 23
1344A-V
1
35
at i = 35
150
x 1
M 150
Total B - 208
Totat C ■
403
Notice!
Maximum power supply current for Total B in the table above is 705 mA; and the maximum
povVer supply current for Total C is 000 rnA_
Total 2 Hours( Total C Alarm Cdntingericy
Operation
r 208 I x 24, 1--
( 3-_-- x _ 0.0833 _ � � 20
v
Refer to the Application environ.ment, page 89 table.
Value = Minutes of alarm operation/60
4 Total Ott requirements must not exceed the Ah capacity of batteries.
- One 12v Battery - 7 Ah
Total Ah'
- 16.03 Ah
COMMUNICATOR WILL BE USED AS A SOLE
PATH COMMUNICATOR AND COMMUNICATE
VIA CELLULAR ONLY.
CELLULAR TROUBLE
Z1-10
120VAC FROM PANEL A
CIRCUIT 14 DISCONNECT
LOCATED NEXT TO FACP
2 #12 AWG THHN
CONDUCTOR CONTROL PANEL
PHONE LINE
CONNECTIONS —
. 1 1
MAIN FLOOR
Intrusion Alarm Systems { 1310R 640 120N1i Medium Contro Panel Enclosure
B10R-1540-1241N1 Medium Ca►ntrat Panel'
Enc1d.s.i e
www.boschsecurity.com (4
BOSCH
Invented for life
The BlOR-1640-12OWI Red Medium Enclosure with
16.5 VAC 40 VA Transformer houses the D1640-120WI
wired -in transformer, and select Bosch control panels
and modules. The enclosures is compatible with an
optional enclosure tamper switch and optional lock
and key set, and holds one 7 or 18 Ah batteries.
Oantdy CorrponeM
f.. 810R 1640-12OWlerxlosure ..
1 Hardware pack
1 Installation Guide (hardC)PY)
KEYPLAN
n&\ 161
► Enclosed 16.5 VAC 40 VA transformer
► Easy to install standoff locations for mounting
supporting modules
► Red matte finish for fire applications
► Punch outs for optional B46 External Annunciator
(for B465 only)
► Additional slow -blow fuse included in fuse block
Properties
Dimensions
14mx12.5inx3in
(35 6 cm x 3L8 Cm x7.6 an)
Material
1.0 min (20gaugel cold-rolledsteel
Cola
lled
Environmental considerations
Temperature (operating)
(rC to+49°C (•32°F to --120T)
Mounting considerations
Mount in dry indoor locations,
Power requirements
voltage (operating)
.. 120VACimunaltofirsebtodt ._.. _.
current(mmamun)
<O-5A .. _
AREA OF
WORK
0-FT 5-FT
1-FT 10-FT
SCALE: 1A
THE DESIGN INSTALLATION COMPLIES
WITH F.B.C. 2020 7TH EDITION,
RE\ASIONS
04
qeA
Iq
■
Y
toM
V
M
U.
VI
�
V
t
�
N
U
�
Q
W
�
0
O
N
lyNN
>-
�0�
QOQZ
Z
WLLQ
- -�
d Z
d
W
W
Q
z 00
tJi
W
cn
=
U
Z<
Q
>
L0
Lo
°�QC
<6
ZQ
oQ
W
>
vQl)
CL
�
DUB
0�
00
LL,(f)o
�
00
►
a�
Ll_
E)
cn
IJ
0
Zo
DO
WO
Do
Jo
Q Lo
>F
I
DWG #: INSERT CAD NAME
REVISION: #
DATE: 2/2/2022
SCALE: 1 /4-=V-0-
DRAWN BY J.J.
CHECKED BY
SHEET F A — 2 of 2