Uniform Katie f a Low-`t 6 to e Alarm System Project
Owrter's/CustomdrName
Address }
C9ty � C 5t Zip
Phane E-mail
??Address l 7
Tity .�tr+ St 21p¢
-ho,, e M :�DateFrojectComplete
ope of Work: �+ 4, it Ley t i t q -,` o r
i
ignahlre: ��..�
Owner or tenant or contractor or authorized representative
Notice is hereby given that a low -voltage alarm system project has been completed at the address
specified above.I certify that all of the foregoing information is true and accurate.
16/i/13 section 553.793 P9
a
GENERAL NOTES
1. THE FIRE ALARM SYSTEM DESIGN, INSTALLATION AND ALL MATERIALS SHALL BE IN
ACCORDANCE WITH NFPA 70 & 72. THE SYSTEM SHALL ALSO IV1EET ALL APPLICABLE
BUILDING CODES, FIRE CODES AND THE REQUIREMENTS OF THE LOCAL AUTHORITY
HAVING JURISDICTION.
2. LOCATION AND PLACEMENT OF THE FIRE ALARM DEVICES ARE NOT TO BE
CONSIDERED DIAGRAMMATIC IN NATURE. ANY CHANGE IN THE LOCATION OR
PLACEMENT OF BOTH DETECTION AND NOTIFICATION DEVICES MUST BE REVIEWED
AND APPROVED BY THE E.O.R. FINAL APPROVAL OF DEVICE PLACEMENT IS SUBJECT
TO FIELD VERIFICATION FOR CODE COMPLIANCE.
3. THE SMOKE DETECTORS SHALL NOT BE PLACED WITHIN 36" IN FRONT OF THE
DISCHARGE OF THE VENTILATION DUCTS OR WITHIN 36" OF HOLES IN WALLS OR
CEILINGS UNLESS PART OF THE AIR RETURN SYSTEM.
4. HEAT DETECTORS SHALL BE USED IN AREAS WHERE THE ENVIRONMENT OR AMBIENT
CONDITIONS EXCEED SMOKE DETECTORS INSTALLATION GUIDELINES. IN AREAS
CONTAINING SPRINKLERS, HEAT DETECTORS MAY NOT BE REQUIRED.
5. ALL FIRE STROBES WHERE TWO OR MORE OR FLASHES FROM TWO OR MORE ARE
VISIBLE FROM ANY POINT MUST BE SYNCHRONIZED UNLESS SEPARATED B A
MINIMUM DISTANCE OF 55 Y
FEET. WIRING AND HARDWARE CONFIGURATION FOR FIRE
STROBES IN A COMMON SPACE MUST BE PERFORMED CAREFULLY SINCE FEEDING
STROBES FROM DIFFERENT CIRCUITS OF DIFFERENT REMOTE POWER SUPPLIES OR
SYNC MODULES MAY CAUSE A CONDITION WHERE WITHIN THE SAME SPACE
SYNCHRONIZATION DUE
ATI N IS LOST U TO DIFFERENT POWER SOURCES AND
SYNCHRONIZATION TIMING. THE TRIGGER CIRCUIT FOR AUDIBLE SIGNALS SHOULD BE
FROM THE FACP TO INSURE SYNCHRONIZATION. ALL AUDIBLE SIGNALS MUST BE
SYNCHRONIZED WITH THE SAME NOTIFICATION ZONE.
6. PIPER FIRE PROTECTION SHALL MOUNT ALL FIRE ALARM VISUAL STROBE STATIONS TO
THE CODE COMPLIANT MOUNTING HEIGHT OF 80"-96" TO BOTTOM OF LENS.
7. PANELS MUST BE MOUNTED HIGHER THAN 6 FEET AND SYSTEM STATUS DISPLAYS ARE
TO BE EYE LEVEL (+60" AFF). NO EQUIPMENT OR RACEWAY MAY BE LOCATED UNDER A
CABINET CONTAINING BATTERIES.
8. THE AUTOMATIC FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY
AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION AS REQUIRED BY
NFPA 72. THE FACP SHALL REPORT CONTACT ID TO MONITORING AND 911. (WHERE
APPLICABLE)
9. ALL AIR HANDLER UNITS, AND EXHAUST FANS SHALL SHUTDOWN UPON ACTIVATION OF
NEW FIRE ALARM SYSTEM.
10. ALL MAGNETIC DOOR HOLDERS SHALL RELEASE UPON ACTIVATION OF NEW FIRE
ALARM SYSTEM.
11. INSTALL END -OF -LINE DEVICES AS REQUIRED TO MAINTAIN CIRCUIT SUPERVISION.
12. FIRE ALARM SYSTEM CONDUIT SHALL NOT BE USED FOR ANY OTHER WIRING.
13. SPLICING OF FIRE ALARM WIRING IS NOT ALLOWED. ALL TERMINATIONS SHALL BE MADE IN
TERMINAL CABINETS ON TERMINAL BLOCKS OR ON FIRE ALARM EQUIPMENT TERMINALS.
14. A LICENSED ELECTRICAL CONTRACTOR SHALL INSTALL A 120 VAC 20A DEDICATED
CIRCUIT(S) FOR EACH CIRCUIT FEEDING FIRE ALARM EQUIPMENT. CIRCUIT BREAKER AT
PANEL BOARD SHALL BE EQUIPPED WITH A HANDLE LOCK -ON DEVICE AND SHALL BE
IDENTIFIED AS "FIRE ALARM CONTROL CIRCUIT". CIRCUIT NUMBER, ELECTRICAL PANEL
NAME AND LOCATION SHALL BE PERMANENTLY AND CLEARLY MARKED ON THE INSIDE
SURFACE OF THE FIRE ALARM UNIT. ACCESS TO CIRCUIT BREAKER(S) SHALL BE RESTRICTED
TO AUTHORIZED PERSONNEL ONLY. PROVIDE SURGE SUPPRESSOR AT INPUT OF FIRE ALARM
UNIT.
15. ALL FIRE ALARM EQUIPMENT SHALL BE LISTED FOR FIRE SERVICE.
16. ALL WIRING AND CONDUIT TO CONFORM TO NFPA 72 AND NEC ARTICLE 760, 725 & 800.
WIRING SHALL BE SOLID COPPER OR STRANDED COPPER WITH A MAX. OF 7 STRANDS FOR 16
GA NAD 18 GA. STRANDED COPPER WITH A NIAX. OF 19 STRANDS FOR SIZES 14 AND LARGER
PER NEC 760 AND NFPA 70.
17. ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED (NEC) METALLIC CONDUIT
AND SHALL BE SEALED WITH A U.L APPROVED FIRE STOP MATERIAL. (SEE FIRE STOP DETAIL)
18. ROUTING OF ALL FIRE ALARM CONDUIT AND WIRING IS DIAGRAMMATIC ONLY, VERIFY EXACT
REQUIREMENTS IN FIELD AND PROVIDE ACTUAL ROUTING ON AS -BUILT DRAWINGS.
19. ALL FIRE ALARM NOTIFICATION APPLIANCES SHALL ACTIVATE UPON INITIATION OF THE
GENERAL ALARM.
20. ALL FIRE ALARM NOTIFICATION APPLIANCES SHALL HAVE A SOUND LEVEL OF AT LEAST 1S
dba ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
21. MANUAL PULL STATIONS SHALL BE INSTALLED AT 48" INCHES A.F.F.
22. MOUNT AUDIBLE/VISUAL SIGNALS (COMBINATION DEVICES) SUCH THAT THE ENTIRE STROBE
LENS IS 80" A.F.F. OR 6" BELOW CEILING, WHICHEVER IS LOWER.
23. A GENERAL ALARM SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY PULL STATION, FLOW
SWITCH OR DETECTION DEVICE.
24. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF ANY DETECTION!
OR MANUAL DEVICE.
■ 25. A. SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY FIRE SPRINKLER
SYSTEM TAMPER SWITCH.
26. HVAC DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM CONTROL PANEL
AND SHALL INITIATE A SUPERVISORY SIGNAL ONLY.
27. ALL FIRE ALARM INITIATING DEVICES SHALL BE ADDRESSABLE AND ALL FIRE ALARM
CIRCUITS SHALL BE CLASS "S`.
28. THE FIRE ALARM CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO
PROVIDE ADDRESSABLE DUCT SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL
SUPPLY AIR DUCTS FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR
ABOVE.
29. ALL DOORS EQUIPPED WITH TINY ACCESS CONTROL HARDWARE OR DELAYED EGRESS
HARDWARE SHALL RELEASE UPON ALARM ACTIVATION.
30. NOT ALL SYMBOLS, NOTES AND ABBREVIATIONS LISTED HEREIN APPLY TO THIS
PROJECT. REFER TO THE CONSTRUCTION DOCUMENTS FOR SYMBOLS APPLICABLE TO
THIS SCOPE OF WORK.
31. FIRE ALARM DESIGN IS IN ACCORDANCE WITH FLORIDA STATUTES CHAPTER 61G15-32.
WHERE A FIRE ALARM RISER IS INDICATED, IT IS DIAGRAMMATIC IN NATURE AND NOT
INTENDED TO REPRESENT A COMPLETE WIRING AND DEVICE DISPLAY.
REFER TO FLOOR PLANS FOR DESIGN INTENT AND PROPOSED QUANTITY OF THE
FIRE ALARM SYSTEM COMPONENTS.
PROJECT SCOPE
1. PROVIDE NEW FIRE ALARM CELLULAR DIALER FOR AN EXISTING MONITORED
FIRE ALARM SYSTEM.
2. PIPER FIRE PROTECTION V`/AS NOT THE ORIGINAL FIRE ALARM SYSTEM INSTALLER,
THEREFORE FULL SYSTEM BATTERY CALCULATIONS ARE NOT AVAILABLE AT TIME
OF PERMITTING.
3. THE NEW CELLULAR DIALER INCLUDES ITS OWN POWER SUPPLY, AND DOES NOT
REQUIRE ANY AMPERAGE LOAD FROM THE EXISTING FIRE ALARM CONTROL PANEL TO
OPERATE.
4. THE EXISTING FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY
AND TROUBLE EVENTS TO AN APPROVED SUPERVISING STATION ( AND 911) AS REQUIRED
BY NFPA 72.
5. PIPER FIRE PROTECTION WILL INSTALL, PROGRAM, TEST AND INSPECT ALL
PROVIDED AND INSTALLED FIRE ALARM DEVICES REQUIRED BY CODE, THE NEW
SYSTEM IS REQUIRED TO COMPLY WITH (FLORIDA FIRE PREVENTION CODE 7TH
EDITION)
6. CONDUCT A FINAL ACCEPTANCE TEST OF THE FIRE ALARM SYSTEM AND ALL FIRE
ALARM COMPONENTS RELATED TO THE PROJECT'S AREA OF WORK. FINAL
ACCEPTANCE MUST BE WITNESSED BY THE AUTHORITY HAVING JURISDICTION.
FLORIDA FIRE PREVENTION CODE- 7TH EDITION
NFPA 101, THE LIFE SAFETY CODE, 2018 EDITION
NFPA 1, THE FIRE CODE (2018 EDITION)
NFPA 70, THE ELECTRIC CODE (2017 EDITION)
NFPA 72. THE FIRE CODE (2016 EDITION)
PROJECT INTENT
1. OCCUPANCY: PROJECT SQ. FT:
2. SMOKE DETECTION:
FIRE PROTECTION SYSTEM:
NOTIFICATION APPLIANCES:
3. FIRE ALARM CIRCUITS:
3.1. SLC -
3.2. NAC -
3.3. 24 VDC POWER CIRCUITS -
3.4. PATHWAY SURVIVABILITY -
SYSTEM OUTPUTS
CONTROL UNIT ANNUNCIATION NOTIFICATION I REQUIRED FIRE SAFETY CONTROL
z
rc p C
_a
OT c o UT �v z u,
o o e
20 T T n 2J 15ti uT o oo•
J
7 2 2 JT J O O
a o
Q
z �r �o ^v u�
u ur r s ,
rr r a'u Ur p J� Iu rr rq 2 � Q Q ru Q 4 Y J
�
FIRE RESPONSE MATRIX Q
� a C
GENERAL ALARM �� o �z
zT �� ,T ,T
Q
U T U T U T 'T Ca
.14j
J
.. _JT
U U U U U U U U '� 3 ,C'r ,C'r A U CUS O 2 U U U
T T 6 U
T T T T T T O y �T O J T T T
�!
SYSTEM INPUTS A a C D - F G H I J K N r� G R 6 J I N X L
1 FIRE ALARIA SYSTEM AC POWER FAILURE • • • 1
4.
2
FIRE ALARM SYSTEM LOW BATTERY
•
•
Y
q•E.
I
p;€"
t
2
3
OPEN CIRCUIT
•
•
I
4
GROUND FAULT
•
•
I'
•_�I
� �r r154
NOTIrI ATION APP_L,NC� .,IR., JIT SHORT
.1•Oio
a 4
N
i -
! �{
:i
t'
s
`eI
`':[
•�
a
BUILDING MANUAL PULL STATION r=
•
',
•
•
•
•
•
6
i'"
p
' r.
7
SMOKE DETECTOR n�1�
•
•
•
'-
•
•
•
•
•
a
HEAT DETECTOR
•
•
:�-;t)I-:
•
•
•
•I:/'�
•
•
�'-"a
•
9
HVAC AIR DUCT StAOKE OR
•
•
•
•
J
-t�
�r
r`,
T3•
;1
10
-:::
11
HOOD OR ROOM FIR_ SJPPR
SYSTEM aLrRr,1
•
•
-
•
•
•
•
•
•
•
1
y
., FM1^"
12
SPRINKLER S'lSTEF,I TAMPER SU'/l'T.,,
-.:p'•
-
M
•
(�
i..
12
13
SPRINKLER SYSTEM FLOW SWITCH t.
'�r
•
•
•
•
•
•
13
IN BUILDING
p'
141
SPRINKLER SYSTEM FLOW SWITCH
IN ELEVATOR EQUIP Rr:l OR SHAFT
•
•
Ittl�a
C j
•
•
•
•
•
•
14
15
ELEV EQUIP RIA SMOKE DETECTOR
•
•
Ip
•
•
•
•
•
15
16
ELEV SHAFT a ELEV EQUIP Rhl
•
•
-'�
All
{ •
•
•
r
•
t
•
•
•
16
HEAT DETECTOR
R
17
LEV LOBBY SMOKE DETECTORS-
FIRST FLOOR
•
•
•
•
•
'
•
.:+y.
-
•
•
•
•
•
17
'%r.,
Id
v1 EV LOBBY SMOKE DETECTORS-
FLOORS TWO THRU ??
•
•
={•
•
•
>< tl
'
^
•
•
•
•
•
•
I6
19
RLEV CONTROLLER-
POV/ER SHUNT TRIP STATUS
•
•
nid
+ .1
•
19
20
FIRE PUPoIP POWER F:JLPHASE REVERSAL
•
•
•
•
20
21
FIRE PUMP RUNNING
•
•
•
•
•
•
•
•
21
22
FIRE PUNIP SYSTEM NOT IN AUTOIAATIC
•
•
•
•
22
23
REQUIRED GENERATOR- LOW FUEL
•
•
•
•
23
24
REQUIRED GENERATOR- NOT IN AUTONIATC
•
•
•
•
24
25
AREA OF REFUGE
•
•
•
•
25
TWO-WAY COMMUNICATION STATUS
IAI9IGIDIEIF IGIITII IJII,ILIMINIGIPIG IRISITIIJI'✓I-,IX rl=I I
CELLULAR DIALER INSTALLATION
FA1.01-- - -
i scare: N 1 s
FIRE ALARM SEQUENCE NOTES
General Fire Alarm System Sequence of Operation
Alar tem SHALL operate as follows:
1.1 Manual 0: on- operation of a manual free alarm pull station shall:
1-A.A. I ; ` the individual station on the system co panel and sound
r control panel and remote alarm panel'
down ventilation systems.
Sound audible alarms and actuateic
ion d rr ?s
J.I.D. Transmit a signal to the central star
1.1.E. Activate the orinter.
St
m pizo
2.1 ctivation of a ar ok;. I�b _ Dr or heat det or sprink ter -flow switch
HALL causeLn i owing: t
?. Provide ope as descry r anual fir pull sta on.
2. signal deli to. f E" , water alarm SHALL not be able to be
Priced whit' ' r r/siem g at agate of flow equal to a single head.
3.1 ° ctIli f any su spry circuit SHALL cause the following actions and indications:
3.1.Di he on f the supervisory condition report on the alphanumeric LCD
i I
d s 'the panel and remote annunciator panels.
c� a
t P P
.1.B. ; p Activ er sory audible and visual signals at the control panel and remote
remot in r n ato pa els.
Record the occurrence of the event, the time of occurrence and the device initiating
the event.
4.1 Receipt of a trouble signal at the fire alarm control panel SHALL cause the following
actions and indications:
4.1.A. Display at the control panel and remote annunciator panels alphanumeric LCD
display, the origin of the trouble condition report.
4.1.B. Activate trouble audible and visual signals at the fire control panel and remote
annunciator.
4A.C. Record the occurrence of the event, the time of occurrence and the device initiating
the event.
KEY NOTES:
10
r1
rl
C LULAR DIALER. DIALER INCLUDES ITS OWN POWER SUPPLY �N1D DOES NOT
REQUIRE ANY AMPERAGE LOAD FROM THE EXISTING FIRE ALARM CONTROL PANEL TO
OPERATE
FAC
333 Bayriaw Atimua knRyAe, New Yak 11701
Fa Solo and R r>. (900) 6T5-9445 StarLink SLE-LTEV-CFB-PS Fire Alarm Communicator
For iechn H, Sanka, a00) b45-9440 a •dsi us at
(Nate: Piblkiy6adeda NASDAQ ntyS,m6d NI55C r) Standby Battery Calculations
Y NAPCo 2019 V42335LF 4/19
Standby Current Calculations for the model SLE-LTEV-CFB-PS Fire Alarm
Communicator:
Standby Battery Capacity . ...................................... _24-_AH
Standby Current Draw of Communicator: ............. 85mA
De -rating Factor: ...................................................... 0.80
Battery Capacity
Standby Time (Hours) = x 0.80 = _24---Hours
Communicator Current Draw
Exam IP es:
4 AH battery = (4AH / 0.085A) x 0.80 = 37.6 Hours
7 AH battery - (7AH / 0.085A) x 0.80 = 65.9 Hours
FIRE ALARM SYSTEM SYMBOL LEGEND
QTY: SYMBOL
DESCRIPTION:
COUNTING:
ELEVATION:
PART NUMBER:
EX
FAC
FIRE ALARM CONTROL PANEL
EXISTING
EXISTING
Vista 100
1
ELL
CELLULAR DIALER
OWN CABINET
VERIFY IN FIELD
SLE-LTEV-CFB-PS
FIRE ALARM SYSTEM WIRE LEGEND
NOT ALL WIRE TYPES WILL BE USED FOR EVERY PROJECT
SYMBOL CIRCUIT COLOR SCHEME AWG-CONDUCTORS WINDY CITY PART NUMBER
A
SLC Circuit
n
13G-2C FPLP
762369 (Red w/ White Stripe FPLP)
B
NAC Circuit
1 4G-2C FPLP
7679610 Black FPLP
( )
.
C
Voice Circuit
y - 1 y, `
16G-2C FPLP
761362 (Red wl Blue Stripe FPLP)
D
VBUS Circuit
16G-2C FPLP
761366 (Red [^✓/Green Stripe FPLP)
F
Annunciator/SBUS
>r
S .x
"
!SG -,AC FPLP
762380 Red FPLP
G
NAC Trip
+
18G-2C FPLP
762361 (Red w/ Black Stripe FPLP)
s "
Fj
AUXIIIafY Circuit
�, 3 x
' �' �>,
16G-2C FPLP
761363 (Red w/ Yellow Stripe FPLP)
�t,urinY'� L RIB CUr.1MUMICA.TORS REFER TO INSTALLATION INSTRUC110N5 WI1653
I
TELCO I
t DOWNILOAD WARNING -
LINE INCORRECT COIUIECTIC11
MAY RESULT IN IMPROPER II4IILJIIpII F I` ✓`^ `�F";E°'
TELCO 2 OPERATION OR DAMAGE `-` " F..:T
To THE SYsroa.
RJ25
#1
RJ25
#2
+17V
J300 1 �l
nRE AU
X RELAY
REFER TO E--
NOTE I <
2 W1RES_PER TERMINAL, WIRE
POWER SUPPLY 000a 13
CONNECTOR o000
FSCO
FUSE HARNESS
CONNECTOR
On5
SLC 1
UL U57M LL LISM I AYSMTCH o00 0
EOL24C EOL12X l 170T � 0 0 0 � 0
PRIMARY USER INTERFACE r, SLC 2
NOTIFICATION 'AIRING
SUPERVISED
POWLIMI
ER MITED 2A 0 24V CODED AND NON CODED SIGNALING.
ALARM POLARITY SITUAT4 COMMERCIAL/RESIDENTIAL LOCAL, REMOTE AND CENTRAL STATION, TYPE SM MONITORING
UL 05TED EOL NAPCO MODEL E01.22K PROTECTED PREN15E5 CONTROL UNIT/DACT AND/OR TCP�1P. 51JITAULE FOR
NAC CIRCUITS PROCESSING MANUAL, AUTOMATIC, CO, SUPERVISORY AN WATERFLOW ALARMS.
LA3560 WIRING DIAGRAM, FL-32FACP-LTEVS PA102LF 10' X 6"
I
Applicant ID No: 849630-001
Service Center No: 1
Expires: 01-JAN-2023
CERTIFICATE OF COMPLIANCE
THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters
Laboratories Inc. (UL) in its ProcILlct Directories as eligible to use the UL Listing Mark in connection .with
Certificated Alarm Systems. The only evidence of compliance with UL's regUirements is the issuance of a
UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service.
This Certificate does not apply in any way to the commLlnication channel between the protected property and
any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm
Transport Company is specified on the Certificate.
Listed Service From: SYRACUSE, NY (SYRACUSE)
Alarm Service Company: (849630-001) Service Center: (849630-001)
RAPID RESPONSE MONITORING SERVICES RAPID RESPONSE MONITORING SERVICES
INC INC
400 W DIVISION ST 400 W DIVISION ST
SYRACUSE NY 13204-1438 SYRACUSE NY 13204-1438
The Alarm Service Company is Listed in the following Certificate Service Categories:
File - Vol No. CCN Listing Category
BP6716-1 CRZH [Burglar Alarm Systems] National Industrial Security Systems
BP10434-1 CRZM Monitoring Stations, National Industrial Security
BP8585-1 CVSG [Burglar Alarm Systems] Mercantile
S36357-1 UUFO Hosted Central Station
•S3282-1 UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling
Services) Central Station
ALL WORK SHALL COMPLY WITH
NFFA CODES AND STANDARDS
**"THIS CERTIFICATE EXPIRES ON 01-JAN-2023***
"LOOK FOR THE UL ALARM SYSTEM CERTIFICATE"
REVIEW I)ATE_�� 0 7 -d-1-0 a �
;ITY OF ZEPHYRHI LL S
FIRE ANC LIFE SAFETY EXAMINER
_��
PROJECT NORTH
D
u
0
0