HomeMy WebLinkAbout22-45511126 210010 01600 0030
Name: JAY & KERRY HOLT
Address: 5935 11Th Street
Z PHYRHILLS, FLORIDA 33542
Phone: (813)334-3221
i Oil,
t \
INSTALLATION PHOTOVOLTAIC SOLAR S
ReviewPlan
City of Zephyrhills
t�S't"�t�\i••i �� ti 1`�\ {UZ s�•': }���1 t`l itt `' 1 lea.. \ ti'
5335 Eighth Street
ephyrhills, FL 3354ELCMISC-004551-2022
...
Phone: (813) 780-0020
Fax: (813) 780-0021 Issue Date; 08108/2022
M
35 11Th Street
5
A �fr1, y$ as
1 £.r
r
�41f�C'
�NTRACTO�RSIGNATU�RE PE IT OFFICE
I✓
�1
x
t city of Zaphyftlls Permit Applicaton FoxrvV£ -MOD21
PF;
use s Adder 93 htrilsti 3 6 ow"tr Phone Nair
t r vmi�r on*Nua tasr x
PooSty i fetus [3 Iith t qhyrhiiis,�L 3354
JOB ADMOSS -3 i ith t. plkv 1 iils, L -142 L T I O kfk cif :(] 3 and all leas 4,5,6
w Lsc1 2l-�}(l1C}�Ci16fi(3-(}EiEi
T M "MATY MX Nonof, �
f"WALL RAs
OTtIER
Ors OF MRX I tali r jmci ut�d Ph2to ltkic Sjl7a 7te:7-
W&MO 30 FOOTA04 NNIONT
MPUMPING
AkA1414A 9 tick It
� t t ,AL � VALUATION O t RANK —AL INVI ALLrADO
=G,AS M ROOT* 0 SPECIALTY C�j OTHER
FINSHM FLOOR t, A IO � FLOODZAREA L :1Yes N
suiLrAft COWANYSAONATUPS
v46
ILIMMAN COMPANY
MWATUAS f sn Y' t i owmq y
d Ucensa A
E=—=]
MOCKMIlm 40WANY
Anirtrksas Llssnss
OTHER r
SONATUR8Rswr��sr sfauRs�
Amdd s t� �...0 �1 a i ry� Lionse ,
' d
RRIMMOMAL ASKh () PW ftnt, () tots 0 SWUM9 Kum: (1) sst of EAOW orAlw wOAN Pamil for ram, tstaown,
N9;rstMM ton UVI kNION o days Met su0mlow data, , ' z dnsa , conowwn Marls, b%mmotor Plans V1 sft''t� m "'%tan <
u1starj proms a f '�Jm sr: SiN wo* * g ft subowislowarp p is
COMMMIALAAWA () complole r f x ttd P€sr€s ips a 110 SuNly psgc (t) $0 0 ptaot&f Fo"" R-0'w Pgmft for newatrcac# kan,
irsimum wn (t ) wwwo lays aft r sikbAiftwi dstn Roqvitod oWto, CmMwcdon ftrw ftftmwwr Plains w At Fonoa rns;ss d,
n;t ry 41cftft a f dutrwor SO W Po it srra $tt now sm, An uwfr met r ueoft*' s gust �-'ti et compunm,
N PERM brad (), d t off rp*v Mans,
"' ip'P"Y SURVEY rsautred for all NEW tatrnsy'rua r
0*4 'A
Omw & COMI'6004, $ipt, t sA of spOtabon notamd
tf ovor $260, a i 0 fs ft4ujrod. JAM 0"'Mags ovor Gil )
kx q ffz�r t acre' sue) �a� fas���r of At#tkng�y ffrar tn� art � ivitt?i s�rr3A= � k�tsar t��rt� s3 sut��s�rr,„tr s�rra
MA THR COMMAOff ;ct"w of olvlttao rogkO )
ROM , f shinoo sevftm sorvkco „fpatt"'. t, Ito: FRm {Ficsl urk�s§ f * 3
anvsm�vwm over own'tar if " n"a (00. ;.... ys meaft ROW
rs47-> city of zophyrtiflis Perinst. Applitationp t
dr,Mog DirponAvitt
AK#14*Wr3fVVht0h they Wilt$ t .gib, It you, ns the nearer aipr, t¢a t eo , r ctcr tr,at nnay to an do fnat an sa whirtoixoty Voensod and
not ent"ted to cormiloftil per. in inafto 0"ua .
P t ' 'it IMP it t�,r i IMPACT AND RESOUR09 ROCOVERY PER$: The urdersigned understandie
thatTWSMWIDA Wpiol Bits$ and rt ar a 4t} ru Fares may apirly to ft 00n of now twildino ohanp of io tm ox,04,V, b0dings, or
0,Vaft& of 0XISVIvi dviadi , ss spooiftdin P _ oo, 0 r ent; Ordimmoo tnitnbw W07 4nd 1041, as smorrdaid The vVinemlatled oft ar d see
%;,01 toff 46 Mer 110 Ana, atf4i kiem"Ified at ;tag Wrie of pofftitting tt is tudror u tad the, Trandpo tirtn ftpmt Foos eta irae ums RoowN
At"rwil N said r owirioa ri"orfinal aq rraf t.ditoaa0jOhre tinvor'ma toofteito a,fu i
air 'ea E , ft r Mun bu Pats pmIrit per"', i a;t , Fumlermom, Y P4600 O•tun y rrmpacg '. Are dut fty .oust W, paid Pry
io psnrA Muorift, dr ae r'4Wota Who Appilvario Paw ;:.sari to diviarsca %_ `
C014$'MWTlok # INN LAW40haltUr 713, sr a tvf#j' as W"). If vaN sry +r),wit 0 i n ro. i roc tsa, €' the � ont
as n tdg0 With a` ` y Of the harltia C",a nx0on Lion as � u �c theta nructo hat€w pamd tit tip f oyids oopartmirii of
ricrtin: fa ono+ �aaieuMw Affo s it the ac p t is s ac v ei tta ati ar he» ti ' vna , t e try that t hive WWnsd a c ,,py of the ti dwoftsii
'n tAnd Pnx I fa t s t#a v sr It to t3ra "Sri#YS !`" 'is�€ ; iF'k lT 4 n .
c tY, l 3Y t 8 a th Irian ate fh a aide ' tf 40UN&W any§ Mot ai# ft?k NhAl to donil to VAth
Oil arnpaca a i mou"atir, on n t tnt nel land da +a o ant. �srlaabr n tr hY2y MOO to QUO, a €envy to do olonk and InStallotiaq
ifs t . i c t 'g 3iE t ikCt',Rvhi'# ati iratskaiiai}{ktE i4'Y n# SPidv tG� $�3aha ( r?31it Dad th4it Ali M** *4 to Poftlffiod to MOO Stft!$S OK 0
to goviatoo our . two crivray11 1AMP166W4, sn the JUN44k,00n tat ifr thot I
oM r'd that € r movia4eoos of o n r t tc as ay iy €e i n `vtt k am that a 14 my mspohvihinyka 04ftfy swot 0�
mutt take to be ,n compotnix Sioba ur tie r t t #t to
Cleirtifterd of FEnviommental Rot"tion-Cypross fifetheads, Welland Areas and Enywonmirritally ettoitlu
WaterNiNifilowater Treatment,
Southwest Florida meter Management Distdot-hells, Cyprvot Saybeads, Wetland Areas. Ayari:gig
AnAy Cntrps of ErVin'ttem4leasralls, Docks, Novi able Watermys,
Department of Health & ReNtolltstW ServittettlEnvironmeiftl Health Unft�Wosis, WostsvmW Tmatmerp,
Septic "nk:
x US Envirtintrientill Pro ikon Ag noy rbostos abatement,
Fedeml Aviation AuthatittRuniclays,
I undaaatand that the kqkwrq reve4tio" a iy of the usv Of till.
a Use of fit W nrit lilloveld in Reed on "fir unless exp It pormitted,
it ft flli material is to be usod in Flood Zone "A', 4 is urrd r tood that a drainage plant addressing
"compensating via ini ! 16 be submittsd at time of pofmiding which is prepared by a professional engineer
is tt y the State of Florida
It the f0i material is to do used in Flood Zore 11A7 In tion ifilth a pet ided building using,atom wall
tronstruction, t irertilly thlit All ovtli be usod only to 0 the amp vAthh, the atom wilL
R It flit material is to be used in any area I ceffidy thM use of such fill W11 not adya ely affect adjacent
prop tt4 a, it use of fill Is found to adversely Affavit 8080ent propeffifts, the owner my be abed for violating
the coMiflons of the bilAiltbrig p rrrrtt issued under the attached pdrriitf applications, for lots losir than of (1)
In
Aifle VO^ c.Iy tie h?bea Ord Kd
,,�°� ,, • �� e�;i ate.
PUMIC
tom =air fir?.r
e N
{`
3�
S
n uN.
x
DIRECTORY OF PAGEC
�
'�s {APE OF W
PV-1 PROJECT SUMMARY
S,
THIS PROJECT INVOLVES THE INSTALLATION OF A GRID-
INTERACTIVE PV SYSTEM, PV MODULES WILL BE MOUNTED
PV-2 SITE PLAN
USING A PREENGINEERED MOUNTING SYSTEM. THE MODULES
if
PV-3 SINGLE -LINE DIAGRAM
WILL BE ELECTRICALLY CONNECTED WITH DC TO AC POWER
INVERTERS AND INTERCONNECTED TO THE LOCAL UTILITY
F74 SAFETY LABELS
USING MEANS AND METHODS CONSISTENT WITH THE RULES
ENFORCED BY THE LOCAL UTILITY AND PERMITTING
PV-5A ATTACHMENT PLAN 5.1
JURISDICTION.
PV=5.2ATTACHMENT PLAN 5.2
PV 6 ATTACHMENT DETAILS
THIS DOCUMENT HAS BEEN PREPARED FOR THE PURPOSE OF
Uj
DESCRIBING THE DESIGN OF A PROPOSED PV SYSTEM WITH
�
PV-7 FIRE SAFETY PLAN
ENOUGH DETAIL TO DEMONSTRATE COMPLIANCE WITH
APPLICABLE CODES AND REGULATIONS, THE DOCUMENT
ELECTRICAL CALCULATIONS
SHALL NOT BE RELIED UPON AS A SUBSTITUTE FOR
MODULE DATASHEET
FOLLOWING MANUFACTURER INSTALLATION INSTRUCTIONS.
co LO
THE SYSTEM SHALL COMPLY WTH ALL MANUFACTURERS
DISCONNECT DATASHEET
LISTING AND INSTALLATION INSTRUCTIONS, AS WELL AS ALL
n APPLICABLE CODES. NOTHING IN THIS DOCUMENT SHALL DE
,
MOUNTING SYSTEM DATASHEET
INTERPRETED IN A WAY THAT OVERRIDES THEM.
ul
CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL
MOUNTING SYSTEM ENGINEERING LETTER
CONDITIONS, DIMENSIONS, AND DETAILS IN THIS DOCUMENT,
CL
MOUNTING SYSTEM ENGINEERING LETTER
2
UL 2703 GROUND AND BONDING CERTIFICATION
�e , nt a �m _. � SYSTEM DETAILSLLj
�j
ANCHOR DATASHEET
i PLAT
DESCRIPTION NEW RID -INTERACTIVE PV SYSTEM
NO
�
YUITH ENERGY STORAGE
PROJECT DETAILS
P-SCALENTS
DC RATING OF SYSTEM 16.08K
PROPERTY OWNER JAY MOLT
AC RATING OF SYSTEM 15.36Kii
PROPERTY ADDRESS 593911TH ST, ZEPHYRILLS; FL
AC OUTPUT CURRENT 63.6A
&
33542 US
INVERTER(S) N/A
ZONING RESIDENTIAL
Pasadena
Hills Richland
MODULE SUNPO R S'R-)(21-33-BLK-E-AC
USE AND OCCUPANCY ONE -OR TWO-FAMILY DWELLING'
(4) BRANCH OF 12 21 345 C AC
CLASSIFICATION GROUP (GROUP'R3)
- = `
ARRAY WRING (INTEGRATED WTH MODULE)
UTILITY COMPANY PROGSS ENERGY FLORIDA INC
RE
t
MICROINVERTERS
ELECTRICAL CODE 2017 NEC (NFPA70)
Z pL t ill
OF
seas
tHI".
M( } DETAILS
I�S i�J.d'�TI�
p° s��.a
FIRE CODE 2013 NFPA 1
OTHER BUILDING 2020 FL BUILDING CODE
POINT OF CONNECTION NEW SUPPLY SIDE AC CONNECTION
PER NEC 705.12(Aj
Co.
CT`FIED
CODES
Zephyrhi<I
PF IL 1I1
West
UTILITY SERVICE 120/240V 1t
'INF RM TI
CONTRACTOR C}
�� T
. ,,,.� _ . ,t.."' : INSIDE PANELBOARD, PROTECTED
�C�
A �� 1 , O
LOCATION BY FUSED EATON DG223NRRB , 2
COMPANY FREEDOM SOLAR ENERGY
Zephyrhilis
POLE, 100A, 240VAG
AL COB
LICENSE NUMBER 56990 (CVC)
South
ADDRESS 36139 PINE BLUFF LOOP'DADE CITY,
FL 33525
SITE DEVILS
PR
ROJECT
ASHRAE EXTREME LOW 1°C (34°F)
SUMMARY
PRONE NUMBER (613) 300 2
#
fa a u � �U _ 2,122 ,ram; ASHRAE 21a HIGH 34 C (93 F)
CONTRACTOR
SIGNATURE
LOCALE
CLIMATE DATA SOURCE ST, PETERSBURG CLEAR (KSPG)
DOC ID:179134 22 943fl-1
WIND SPEED 145 MPH (ASCE7-10)
DATE: 517122
PV-1 SCALD`. NTH
CREATOR: J:V.
RISK CATEGORY I#
R VI R.
WIND EXPOSURE C
CATEGORY
REVISIONS
GENE NOTES
EQUIPMENT LIKELY TO D WORKED UPON ILE
ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT
SATISFY' MINIMUM WORKING CLEARANCES PER NEC
11016,
CONTRACTOR SHALL USE ONLY COMPONENTS LISTED
Y A NATIONALLY RECOGNIZED TESTING LABORATORYFOR THE INTENDED USE.
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL
EQUIPMENT, CABLES, ADDITIONAL CONDUITS,
'
RACEWAYS, AND OTHER ACCESSORIES NECESSARY
FOR A COMPLETE AND OPERATIONAL PV SYSTEM.
Lu
�-
ALL EMT CONDUIT FITTINGS SHALL BE LISTED AS
WEATHERPROOF FITTINGS AND INSTALLED TO ENSURE
C°�!
A RAINTIGHT FIT, PER NEC 358,42.
(N) VISIBLE, LOCKABLE, READILY -ACCESSIBLE A
.�
u-
DISCONNECT LOCATED WITHIN 1OFT OF UTILITY
METER, OUTDOOR
r
(N) TRANSITION SOX; OUTDOOR, OUTPUT CIRCUIT
CONDUCTORS $HALL BE RUN IN EMT CONDUIT OVER
LLJ
ROOF NO CLOSER THAN 0.5 ABOVE ROOF SURFACE
ER, OUTDOOR,OUTPUT
(N) AC COMBINER,CIRCUITCONDUIT
I-_
PVC
ROOF 0.5"
OVER NO CLOSER. THAN ABOVE ROOF`
SURFACE
(N) PROPOSED ROOF -MOUNTED PHOTOVOLTAIC
ARRAY, 5:12 (23®) SLOPED ROOF, 8 PV MODULES
r
(BLACK FRAME, BLACK SACKSHEE1),154' AZIMUTH
°
(N) PROPOSED ROOF -MOUNTED PHOTOVOLTAIC
ARRAY. 5:12 (23" SLOPED HOOF,. 40 PV MODULES
BLACK FRAI Er LACK BACKSHEET), 243° AZIMUTH
SITE PLAN
(
PV-2 SCALE: 1" - 20'
OF
CERTIFIEDI
®Ca
7C,Lo
SITE PLAN
C ID: 17 134-221430-1
DATE: 817/22
CREATOR: V_
REVIEWER:
REVISIONS
PMI 48
� AC N40DULE
MODULES
GENERAL ELECTRICAL
P-1 79134
�„,
` T,33� ...��
_ �
i 2
REF. O1Y.
PM148 48
KEAND EL
SUNP SPR.�2i335BLK-EAG
Pfv (AC) thP,XdUTPUT(XiRBENT
32fi 1.3A
AC VOLTAGE OEGWEIGHTE€2EFFfCtENCY
246:OV 96,4°k
NOTES
I
rm
DISCONNECTS OCPDS
UTILITY HAS 24-HR UNRESTRICTED
t
3
ACCESS TO ALL PHOTOVOLTAIC
REF. QTY. KEANII DEL
RATED CURRENT RATED VOLTAGE RE€. 0 MVOLTAGE
12#N
BR
# 12{N , 12IN 1 12IF1
BRANCH CH' BRANCH
SWI 1 EATONDG223NRBOREQUIV
100A 240VAC CBI-4 4 20A 240VAC
F1-2 2 100A oVAc
SYSTEMCOMPONENTSLOCATEDAT
THE SERVICE ENTRANCE.
"""
s
CONDUCTORS EXPOSED TO
E58YSTEMSUMM7jARYjNOTES
ETEEEE HItt2 H3 H
SUNPOWER, SYSTEM MEETS REQUIREMENTS FOR PHOTOVOLTAIC RAPID SHUTDOWN SYSTEM (iIRSS), AS PER NEC 690 42(f}.
SUNLIGHT SHALL BE LISTED AS
.n
EACGURRENT NCN 15�96A 1596A 15196A 1598A
00 PV CONDUCTORS ARE NOT SOLIDLY -GROUNDED. NO DOPVCONDUCTOR SHALL BEWHITEdRGRAY-COLORED
2 SUNLIGHT RESISTANT PERNE
JUNCTION SOX
ACOUTPUT 3,840W 3, uvs 3,
ARTICLE 300,6 (C) (1) AND ARTICLE
JBI
BRAY STC R ,
ALL AL ENCLOSURES, RAC Y$, CABLES AND EXPOSED 110 CURRENT- RYING AL PARTS OF EQUIPMENT $L BE GROUNDED TO EARTHAS REQUIRED BY
1 1 � {
BRAY PTO POWER 15,
NEC 250.4(B) AND PART IIIOF ARTICLE 250 AND DO EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690,45, THE GROUNDING ELECTRODE
LD)
2
AC GUBRENT 64A
SYSTEM SMALL ADHERE TO NEC 690 47(A) AND NEC 250.166 AND INSTALLED IN COMPLIANCE WITH NEC 250,64,
CONDUCTORS EXPOSED TO WET
Uj
1
LAX AC POWER OUTPUT 15,360W
LOCATIONS SHALL BE SUITABLE FOR
i
3
ERATEDACPO1PIEi?OUTPUT 14,4
AC AGGREGATION PANELBUSBARANDTHEOVERCURRENTPROTECTIONPROTECTINGTHESUSBARSHALLBESIZEDINACCORDANCEWITHNEC705.12(S(#2X3 C),
3
co
4
E IN T LOCATION PER NEC
AC MBINE
51 '•CB4 4
POINT -OF -CONNECTION IS ON THE SUPPLY SIDE OF SERVICE DISCONNECT, INSIDE PANELBOARD ENCLOSURE USING UNUSED TERMINALS, TERMINALS THAT ARE SUITABLE
OTHER 705.12(A). SHALL HAVE
ARTICLE S1 .16 (C):
Lo
1CB2 ICB3
FOR DOUBLE LUGGING, OR USING LOCALLY -APPROVED METHODS AND HARDWARE, IN COMPLIANCE WITH NEC THE PANELBSARD
A 20A 24A OA Cl
SUFFICIENT SPACE TO ALLOW FOR ANY TAP HARDWARE AS REQUIRED BY NEC 110.3 AND NEC 312,8(A)
GROUNDING
5
PV SYSTEM DISCONNECT SHALL BE A VISIBLE KNIFE -BLADE TYPE DISCONNECT THAT' IS ACCESSIBLE AND LOCKABLE BY THE UTILITY. THE DISCONNECT $HALL BE LOCATED
ALL EQUIPMENT SHALL BE
WITHIN 10 FT OF UTILITY METER. DISCONNECT SHALL BE GROUPED IN ACCORDANCEWITH NEC 230 72.
PROPERLY GROUNDED PER THE
`".100A
1
REQUIREMENTS O NEC ARTICLES
�. _� � .�
sW1
CONDUCTOR AND CONDUIT SCHEDULE WIELECTRICAL CALCULATIONS
254 >� 696
p1dOA
CURRENT -CARRYING
t TOR T R
ID TYPICAL CONDUCTOR CdNDUI J E GONDUITTd S #N
MAX TERM
P GC TEMP.CORR. FILL FACTOR CONT. CURRENT BASEAMP DEBATED TEMP AMP.TERM. LENGTH VOLTAGE
OC D E FACTOR CURRENT AMP, TEMP. RATING DROP
SHALL R N
PV MODULES ALL BE GROUNDED DED
CiNDU(TtCAB E
a
(125r) RATING
TO MOUNTING RAILS USING MODULE
=
{2�IDA
SP W1200A MCa}
1 1 12AINGT 2 COPPER I"DWEMT 6
20A 12A THINN-2. 0.96(34°C) of 15 A 19.35A 30A 23.04A 901c 30A 12FT 0.32%.
LUGS OR RACKING INTEGRATED
2: 1 12AWGT 2,COPPER 1"DIA.'EMT 6
20A WP-2:COPPER O96(34gC} D:E' 1596A 14.95A 30A 23.fY4A 9O°O 30A 12FT Oi32%n
3 1 12AWGT 2;COPPER I"DIA;EMT 6
20A WN2,CdPPER 0.96(34'C} 0,$ 15;96A 19.95A 30A 23.04A 90°C 30A 12fT 0.32°k
GROUNDING CLAMP ALLOWEDAS
L£ACiS
4 1 12AWGTNV{dN-2<COPPEft O.5"D(A 2
20A PI.2'COPPER 0.95(34°C} 29 ?5;96A 99.95A 30A 28.8A °C 3#YA 92FF 0.32eta
E4A
Y LOCAL JURISDICTION, ALL OTHER
LLJ
Lli
"`
5 1 2AWGT 2,tX?PPER 125 D1AfC40 2
100A 2,CdPPEB F.96(34C} 1,l fi3.84A 79.6A 130A 124.8A 75°d 115A 48IN O:f4%
EXPOSED METAL PARTS SMALL BE
6 1 2AVVGTHWW2;COPPER; 1,25`E7tAF C40 2
140A -2,CdPPER 0,96{34"C} 1:q $3;84A 79.$A 130A 1248A I5°C 155A 1flF€ 0:1f
GROUNDED UINGUL-LI TEDLAY-IN
�
�,.
L
LUGS,
UTILITY METER
240/120V
INSTALLER SHALL CONFIRM THAT
{E AC
r .i
�
4,3W
MOUNTING SYSTEM HAS SEEN
EC
�P,t
EVALUATED FOR COMPLIANCE WITH
3 UL 2703 "GROUNDING AND BONDING"
WHEN USED WITH PROPOSED PV
MODULE.
IF THE EXISTING MAIN SERVICE
PANEL DOES NOT HAVE A
OF
GROUNDING
,
VERIFIABLE
a $
ELECTRODE, IT IS THE
co
CONTRACTOR'S RESPONSIBILITY TO
CERTIFIEDa,
INSTALL A SUPPLEMENTAL
GROUNDING ELECTRODE,
AC SYSTEM GROUNDING
%OO
ELECTRODE CONDUCTOR (GEC),
E $0
5 SHALL BE A MINIMUM SIZE #;BAWG
WHEN INSULATED, #6AWG IF WE
WIRE.
EQUIPMENT GROUNDING
SINGLE -LINE IAG
CONDUCTORS SHALL BE SIZED
ACCORDING TO NEC ARTICLE 690.45,
6 AND BE A MINIMUM OF #10AWG
PROJECT ID. 179134
WHEN NOT EXPOSED TO DAMAGE,
DATE: 081 7M
AND # "iA IIG SHALL BE USED WHEN
CREATED BY: , J V.
EXPOSED TO DAMAGE
GROUNDING AND BONDING
CHECKED BY.
CONDUCTORS, IF INSULATED, SHALL
VI SIONS
7 BE COLOR CODED GREEN, OR
MARKED GREEN IF ##4AWG OR>
LARGER
1,SINGLE-LINE
yam,
i wi
NEC70512(B)(2)(3)(C) s a s
INSTALLED BY FREEDOM SOLAR ENERGY # 333333
NEC6K56(B),705,10
EACH DISCONNECTING DEANS FOR AC SOLAR DISCONNECT (SWI) AC DISCONNECT (SW1)
PHOTOVOLTAIC EQUIPMENT (SWI
PV SYSTEM DISCONNECT MAXIMUM AC OPERATING CURRENT: 63. A
MAXIMUM AC OPERATING VOLTAGE:240V
NEC6 .10(6) NEC690,54
AMY Ar Pfi Ft'TPl(l..&! PAMP4 TWAT K Pfzn PY
ROOF PROPERTIES
ROOF MATERIAL TRAPEZOIDAL =METAL (I1-131N)
SLOPE 5{12 (22.5«)
MEAN ROOF HEIGHT 12.3FT
DECK SHEATHING 15i32"'OSB Malik
MOUNTING SYSTEV PROPERTIES
20IN NE 3)
MA)C MOUNT SPACING40IN
.� t�
M II
)
MAX, ALLOW,
19.21NO01 AND 2)
ICANTWO
19.61N ONE 3)
GROUNDING AND
l
co
CERTIFIED
tIND ZONE I Lj WINDZONEII Lj WIND ZONE III
NOTES Lj TRUSS LOCATIONS ARE APPROXIMATE. ACTUAL DISTANCE a IS EQUAL TO 10°la OF THE BUILDINGS LEAST I ORIZ ITAL DIMENSION OR 401/o OF THE MEAN ROOF HEIGHT WHICHEVER IS SMALLER, BUT T LESS THAN 41/6 OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET (ACSE 7-
LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED 10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF COW4ERS; RAKES, NIPS, EAVES, MANSARDS, AND RIDGES OF ROOF FACES,
TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THEI N SPACING EXCEED « MOUNT SPACING" a = (I IN(OA * MEAN ROOF HEIGHT, 0.1 * LEAST HORIZONTAL DIMENSION), 0,04 g LEAST HORIZONTAL DIMENSION, 3 FT)
4,9 FT = MIN(OA « 12.3 FT, 0.1 # 75,0 FT), 0,04 * 75.0 FT; 3 FT)
I LAN � 'R , T.
ROOF PROPERTIES
ROOF MATERIAL TRAPEZOIDAL METAL (11-131N)
SLOPE 5/12 (22.6°)
MEAN ROOF HEIGHT 13.8FT
RIDGE
DECK SHEATHING 15132" OSB
CONSTRUCTION TRUSSES (2X4 TOP -CHORD), 241N OC
MODULE MECHANICAL PROPERTIES
MODEL SUNPO R SPR X21 335-BLK-E-AC
Lu
DIMENSIONS (AREA) 61.31N X 41.2IN X 1.81N (17.5 SQ FT)
WEIGHT 41LB
`�
MOUNTING SYSTEM OP RTI S
MAX. ALLOW. RAIL SPAN 48.01N (ZONES 1 AND 2)
24.011 (ZONE 3)
EdVE EAVE� .
EAV
MAX, MOUNT SPACING 48.OIN (ZONES 1 AND 2)
24.01N (ZONE 3)
Lli
MAX. ALLOW, ' 19.21 (ZONES 1 AND 2)
CANTILEVER 9.61N (ZONE 3)
El WIND ZONE I Lj WIND ZONE 11
Lj WIND ZONE III
GROUNDING AND INTEGRAL GROUNDING CERTIFIED
BONDING TO UL 2703 REQUIREMENTS
a
DISTANCEa IS EQUAL TO 1010 OF THE BUILDINGS LEAST HORIZONTAL DIMENSION OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER,
BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET ACSE 7-
10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF CORNERS, RAKES, HIPS, EAVES, MANSARDS; AND RIDGES OF ROOF FACES.
DEAD LOPED CALCULATIONS
a = P AX(MIN(0A* MEAN ROOF HEIGHT, 0.1 " LEAST HORIZONTAL DIMENSION), 0.04 LEAST HORIZONTAL DIMENSION, 3 FT)
°
LOAD QTY LBS ' TOTAL LESS
5.5 FT = (MIN(0.4 13.8 FT, 0.1 75.0 FT). 0.04 75,0 FT, 3 FT)
MODULES 40 41.01640.2
MICROINVERTERS 40 2,0 80.0
1 ATTACHMENT PLAN C1RTFiCICi NAL PROJECTION'
TOTAL ARRAY WEIGHT 1720.2 LBS
V-5, SCALE: 1/8" = 1'
AREA NAME QTY SQFT TOTAL SOFT
OF
MODULES 40 JIT5 700.0
DIST. LOAD (1720.2 LBS;! 700.0 S F1) 2.46 PSF
" q
mmCERTIFIED-
NOTESg
TRUSS LOCATIONS ARE APPROXIMATE. ACTUAL
s * 7
LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED
TO ADJUST MOUNT LOCATIONS, IN NO CASE SHALL THE
MOUNT SPACING EXCEED "MAX: MOUNT SPACING"
ATTACHMENT
PLAN
C ID:17134-221430-1
DATE: 817/22
CREATOR: JV.
REVIEWER:
REVISIONS
I
',,RACKING ELEVATIONffR6NSVERSE /I -
t, SCALE: NTS
RACKING ELEVATION?GITUDINAL V[l O
MOUNTING SYSTEM NOTES
FLASHING SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURERS` INSTRUCTIONS,
IF THERE IS ANY CONFLICT BETWEEN WHAT IS DEPICTED HERE AND INSTRUCTIONS
CLAMPING ZONE - 2 PROVIDED BY A MANUFACTURER, THE MANUFACTURERS INSTRUCTIONS SHALL
IRONRIDCE UNIVERSAL
FASTENI IC OBJECT
IRONRIDCE
PV MODULE XR10 RAIL
S-51 PROTEAE?RACKET-
TRAPEZOIDAL t
METAL ROOFING'
ROOF DECKING
�ROOF
UNDERLAYMENT
ROOF FRAMING
/"ATTACHMENT DETAIL RANSVER E i11E _
t J SCALD: ITS
��-PV MODULE
l % 4
IRONRIDGE
�r ` XR91I RAIL
S-5? PROTEABRACKET t
MGM
ATTACHMENT DETAIL [LONGITUDINAL VI +1
4 °Vr SCALE. NTS
-30
Conductor, Conduit and OCPD Sizing Validation
2. Who, Condulk and OCPD Code Compliarm Wdedon
.1. ft
1.1s
G. Minimum Required EGC Size 12 AWG
see Table 250 922
conductor 12 AWG TH JN 2 C er
AMWROpWft NBC code Vwwdon Tub
Eguipment Ground Corsductor EGC 12 AWG THWN.2, Copper
The smallest EGC size allowed is 12 AWG for OCPD rating 20A
Ariav T Phi "nverter Air ce Circuit m `rnum Voc must not exceed
OCPD s
according to Table .122.
System Description 48 Sunp er SPR-X21-337BLK-E-
U772-
Ra ICabie 1" dia. EMT
H. Minimu t -Recommended Conduit'Size 1 ft did.
AC 33 s
=Eros
Lowest Terminal Temperature 90°C
Rati
sae 3lJll 17
Module SP-X21-335-BLK-E=AC 335
Highest number of modules in series n
Maximum Wire Ternberature JWC
The teal area of all conductors is 0 229W. With a maximum fill rate of
in a PV Souroe Circuit
Power Source Description Branch of 12 X21-3445-C-AC
0.4, the recommendedconduit diameter is 1.
es n Low Te 1 °C
(Integrated sth i0
Module Voc 67.9V
Ilerro.
micrcunverters
D In S z T Area Tots Area
Coefficient Voc-0.197VIC
Power Source Current 15
6 Conductor 12AWG T N-2 0.0133W 0.0798irf "
Volta e 2'
3 Neutral j AWG T N-2 0.OMW 0.1
3 12 AWG T N-2 ` 0.0133W 0, r?
A. Maximum Voltage of PV Source Circuit 72,63V
A. Continuous Current 16,6A
12 0.2295ir?
6957(A}
see;4i /ne 11J3
0. rz 10.4 = 0 5738ir? (Corresponding to a diameter of 1 #)
NEC .7(A) requires that if the PV module manufacturer provides a
temperature coefficient of Oren -circuit voltage, if must be used to
Equipment maximum rated output current is 12 X 1.33A 15.96A
W Cob Vdddm T ub
calculate the PV array's maximum system voltage, It includes an
information note recommendrig the use of theASHRAE'Extreme Annual
S. Ampacity of Conductor 30A
OCPD ring must beat [ 126 ,6 of Continuous
Mean Minimum Design Dry Bulb Temperature' as the design low
see T"e 311T 15(BJ(18)
Current (240,4)
temperature. Using these values, the module Voc (67,9V) will increase to
parity (36°C) fora conductor with °C insulation in
20A >=15 96A X 1.25 = true
72,63V at the design lowtemperature (1 °C),
corn e is
cited to exc PC} rating, rt
(1 °G - 25°C) X-0.187V/C +6T,9V = 72.63V
rating of nexEler PC'(240.4}
F(OCPD
The module Vocat the ign low temperature is 72.63V.
C. Derated Am acity of Conductor 23.34A
23. >- 20Rating) = true
72.63V X 1= 72MVsee
Tile 31D 15tBJf3Jfcj Tab#- 31015(8J()(a) ;artd&4 vle WO
ASS
OCPD rating must not ex m OCPD rating P
The temperature factor for 90°C insulation at WC is 0.96.
for conductor (240.4)
The fill factor for a oonduittcable that has 6 wires is 0.8.
"
(OCPD Rating) - 20A = true
The am ed for Conditions of Use is the product of the210A
conductor a (30A) multiplied by the temperature factor (0.96) andV23,04A
Derated must be greater thanor equal to PASS
It's
by the fill factor (0.8).
u nt (,, �cle 100}
E
30A X 0.96 X 0 8 = 23.04A'
true
D, Max Current for Terminal Terrp. Rating 30AJC;:onfinuous
ctor p 'ty must be at least 125% of PASS
see 110 f#Q
Current (215.2(A)(1))
The lowest temperature rating for this conductor at any termination is
5,A x 1.25 = true
C:
rent for t ' inal must be at least 125%,6 of
Using the method specified in 110,14(C), the maximum current permittedfnuous
Current, (110.14(C))
V30A
to ensure that the device terminal temperature does not exceed is VC
5. A X 1.25 = true
rating would be the amount referencedin the W*C column in Tie
310. t 5(8)(16), Mich is 30A.
EGC mist m t code requir eats for minimum PASS
e (Table 250.122)
[E:. Minimum All ed OOCP Rang 20A
12 A —12 A tG = true
2404
Conduit must meat code recommendation for
NEC 9(B} requires that the7CPD rated for no less than 1.25
minimum sire (346.17j
times the Continuous Current of the circuit.
15 1,25=19.
tin - lin. = true
F, maximum Allowed OCPD Rating 20A
see 2404(D) ;
NEC 240,4(D) requires that OCPD rating not exceed 20A when
protecting a Copper 12 AWG conductor.
Required EGC Size
Recommended',MinitriUm
A. Continuous Current 15.96A
see*#O/e VO
Equipment maximum rated output current is 12 X 1,33A =15. A
B. Ampacity of Conductor ' 30A
seeTable 3y0 y5(B)(9b)
Ampac ity (30TC) for a copper conductor with VC insulation in
condo t able is 30A
C. Cerated Ampacity of Conductor 23.94A
see T s 390 5(Bj(3)(c), Tile XV 9,5fB1121(a), anJAIcle 900
The temperature factor for 90°C insulation at 34'C is 0,96.
The fill factor for a conduit/cable that has 6 wires s 0.8.
The ampacity derated for Conditions of Use is the product of the
conductor am y (304) multiplied by the temperature factor (0.96) and
by the fill factor (0.8).
30AX 0.96 X 08 = 23:04A
C. Max Current for Terminal Temp. Rating 30A
see If0M(C)
The rest temperature rating for this conductor at any termination is
90*C.
Using the method specified in 11014(C), the maximum current permitted
to ensure that the device terminal temperature does not exceed its 9TC
rating would be the amount referenced in the 9VC column in Table
310.15(8)(16), which is 30A,
E. Minimum Allowed OCPD Rating 20A
see 2404
NEC ,9(l3) requires that the OCPD be rated for no less than 115
times the Continuous Current of the circuit.
15.96A X 1,25 =19 95A
F. Maximum Allowed OCPD Rating 20A
see 2404fp)
NEC 240.4(B) requires that OCPD rating not exceed 20A when
protecting aCopper 12 AWG conductor.
ie Continuous Current (Article 100)
3. ', - 15.96A=true
lax cUrrent j1 i.�M YI )A be fl�UltIlIIIIIIwIIIIRI i1w%
�
ie Continuous Current. t
i11 (C))
..
must a li �II requirements for minimum
(Tae able iS,
�
{ meet IIM; f! �I Al " recommendation .or
Animurn size i
NEC Code CakukVM
A. Continuous Current 15.96A
see tbflole 900
Equipment maximum rated output current is 12 X 133A =15 96A
parity of Conductor 30A
[:B.
Tale M 15tB)(M)
Ampacity X*C) for a copper conductor with 900C insulation in
conduit/cable is 30A
C. iterated Ampacity of Conductor 2104A
see Table M f5(B)(3)(oj T 4e 310 f5(B)(}(aj ark ` Pe A 0
The temperature factor for 90°C insulation at WC is 0,96.
The fill factor for a conduiticable that has 6 wires is 0A
The ampacity deraied for Cordticros of Use is the product of the
conductor ampacity (30A) multiplied by the temperature factor (0.96) and
by the fill factor (0.8).
30A X 0,96 X 0,8= 23.04A
D. Max Currant for Terminal Terra, Rating 30A
see f I fJ f `�L)
The lowest temperature rating for this conductor at any termination is
90°C.
Using the method specified in 110.14(C); the maximum current permitted
to ensure that the device terminal temperature does not exceed its 90aC
rating would be the amount referenced in the VC column in Tie
310.15(3)(16), which is 30A.
E. Minimum Allowed OCPD Rating 29A
see 2404
NEC 9(8) requires that the OCPD be rated for no less than 1:25
times the Continuous Current of the circuit.
15 A X 125 = %95A
see 2404(D)
NEC 240,4(D) requires that OCPD satin not exceed 20A when
protecting a Copper 12 A G conductor.
G, Minimum Required EGC Size 12 A t
see TaMe 250 f22
The smallest EGC size allaWed is 12 A for (7CPD rating 20A
according to Table 250,122
H. Minimum 'Recommended Conduit Size 1' dia.
see 300 97
The total area of all conductors is 0. ri . With a maximum fill rate of
0A, the recommended conduit diameter is 1.
Q Clesen lion size T Area To€� Ares
)CPD rating exceed max OCPD rating
mac:
4mustnot
i 11 III 1 1 w��{l 4 t*
je Continuous Current (Mole
'I i�onduqtDr
Ampacity must be at least 1250% of
�ontinuous Current 2(
ne Continuous Current. C
code requirements flut I u..w�irlrl
OG 3=12 AVVG = true
iduit must meet code recnrnrnendaation far
imusn size (300.17)
- Iin, =true
° e TMWMN So to AC CoWner
LL A:Dbooffloct
Ch=k 890don PMPNft
=Minimumquired E C Size 12 UC'
inimum Required EGC Size 4
[�250122(,Rj
conductor 12AWG T 2 Cooper
Conductor 2 AWG Copper
Equipment Ground Co ctor EGC 12 AWG TH 2 C
The smallest EGC size allowed is 12 A for OCPD rating
E mien# Geourrti Co ctor EGC 4 AWG TFI ` -2 C r
ere conductors are oversized, the EGC must be oversized by the
OCPD(s) 20A
according to Table 250122.
�
tJCPD s` 1C�lA
same rate, Table 250,122, gives a minimum EGG size of 8 AWG:
9
Ra 1C 0 5" da. EMT
Raceway/Cable 1,2Y dia. PVC-40
Multiplied by the oversize rate, this yields 26.24829kcmil corresponding
! Terminal Temperature 30°C
H. ? Minimum Recommended Conduit Size 0.5" dia,
lowest Terminal Temperature 75"C
to 4 A
i
see 300 f7
Rati
(66. omH 141.74kcmil) X 16.51kcmil = 26,24829kcmil
Maximum hire 7em afore 34°C
The total area of all conductors is 0.076W. With a maximum fill rate of
Maximum Wire fern ure 34°C
Power Source Description Branch of 12 X21-345-GAG
p.4, the recommended uit diameter is 05
Power < Source Desorption 48 u er SP -T21- -E
Re"Minimumcommended Conduit Site 9.2 C 1 .
(Integr ed ith Module)
AC s
see XO 17
microinuerters
Power Source Current 15.96A
oty tiascri tan T Area
Power Source Current 6384A
The torsi area of all conductors is 0, ins. With a maximum till rate of
V 2
2 Conductor Wo 7 N2 o.ti138ir?
j12A
V e 2
G 4, the recommendedoonduit diameter is 1.25:
1 Neuirai G T N-2 0, riz
g0.0133iff
NEC Cod* Cobtdollilm
a [7essri ban Size Type Area Yard Area
NEC Code Cakulaftm1
E u t Ground WG T N-2 it.0133ii
2: Conductor 2 AWG T N 2 0,115W 0,231ar?
A. Continuous Current 83.84
, Continuous Current 15.
cis foo
1 4A T N•2 4.0824ire 0.0824ii?
JA
see,4rllcle 1til7
0.0765ir 7 0.4 = 0.1913in? (Gorr diru to a dia er of 0.5<)
1 E ui mart Ground 4 AViG TINN2 4.3$24 1° {?.o824i
Equipment maximum rated output current is 63 84A
Equipment maximum rated output current is 12 X 1.33A = 15.96A
WC Code V&Wdm T@dB
Lj 0. tins
pacity f Conductor 130
0. 4ar? 10.4 = 0.991in2 (Corresponding to a diameter of 1.25)
-7
B. act of Conductor 3 Ar2DA
D ng must be at least 12104 of Continuous
see Tate 3?ti 15(8j�1SJ
.see T.t,31� 5'(B)(f6j'
Current t (240.4)
NEC Cob VaNddlon Tgsb
AmpactY (3t7° )fora cord rctorwit i C insulation in
>=15. X 1.25 =true
pasty ;'°C}fora or with °C insulation n
conduftIcable is 130A.
condug! se is 30A
Oersted p 'ty musts OCPD ng, ;or P
PD ruing must be at! least 12510 of Continuous PASS
Cu nt (240.4)
C. Derated pacify of Conductor 28.
rating of next ally OCPD (240,4)
28.E >= 20A
C, Derated pacity of Conductor 124,8
Ta* T
100A- .84A X :25 = try
(c7 Rating) = true
see X01,5(Bj(3j(cj k- 3101,5(Bj(3j(aj, arrd cb fOO
see Title 31015(Bj(3)(c) Ta81e V f5(B)(31(aj, alVA*kr 10ii
Derated p i Must exceed OCPD rating, or PASS
The temperature factor for 90°C insulation at WC is 0 _
OCPD rating trust not exceed max OCPD rating
for conductor (240,4)
The temperature factor for 9G°C insulation at 34°G is 0.96.
The fig factor for a co it/cable that has 2 wires is 1.
rail of next ;oiler OCPD 240.4
( )
The fill factor fora conduit/cable that has 2 wires is 1,
(OCPD Rating} <= 20A `= true
The a ty ed for Conditions of Use is the the
124.8A >=1 (OCPD Rating) = true
The am Berated for Conditions itions of Use is the product of the
tx
or a (1 30A) multiplied by the temperature factor (0.96}
Oersted Am act must be ter than or equal to PASS
p bf 9 eq
conductor ampacity (30A) multiplied by the temperature favor (0,96) and
p pacity must greaterthan or equal to
and by the fill factor (1).
the Continuous Cu att (Article 104
( )
by the fill factor (1).
the Continuous C { de 100)
1 X 0. X 1=124.8A
124.8A r- 63.84A =true
30A X 0,96 X = 28.8A
28.8A-15. = true
`ty
D, Max Current for Te inai Temp. Ruing 115
Conductor pacity must be at 1 t 1251% of
,' lax Current for Te in i Te . Rating 30A
n actor a
Co _ p gust be as least t 125 % of
see �>�l 1�(cj
Continuous Current (215.2(�i)(1))
ee Ifo f#Q
Continuous Cuts t (215.2(A l))
LI75°C.
13(7A > 63, x 1.25 =true
> 15, x 1,25 =true
The lowest temperature rating for this conductor at any termination is
The I temperature rating for this conductor at any termination is
Max current for terminal must be at least 125% of PASS
°C.
Max current for inal must be at 1 12504+ of P
Using the method tied in 110,14(% the maximum current permitted
the Continuous Current 110,14 C
( ())
Using the met in 110.14(C), the mum current permitted
Continuous'C t. (110.14(c))
to ensure that the ice terminal temperature note its 75°
to ensure that the ice terminal temperature ' not ex its C
30A5=15. X 1.25 true
rating would be the amount referee an the 75"C column in Table
115A>= 63.84A X 1.25 = true'
rating would be the amount referenced in the °C column in Table
310.15(8)(16} Mich is 115A.
EGC must meet cede requirements for minimum PASS
31(i.15(Bj{16}, which is 3JA.#
WEIG�Cmustm k e requir ants for minimum
e (labia 250,122)
l lioWod CPD i tifi g 5
Table 250,122)
E. nimum llowed OCPD Rating
4 AWG - 8 AWG = true
EE.�inlmUnl
24f74
12 A >=12 AWG =true
see 24014
NEC .9(B) r Tres that the OCPD tie rated for no less t 1,25
minimue 300.17NEC
( )
Conduit:m:ustm e roc mendatton forffOin,
onduit must rec mendati for
9(8) r ires that the CGPD be rated for no less than 1,25
nimum scze (300,17)times
:7
times the Continuous Curren€ of the circuit.
the Continuous Current of the circuit;
>= 0.5in. = true
63.84A X 1,26 =79.8A
1.25in. >5in. ='true
15:AX1,25=19.95A
F. Maximum hoed�OCPDating 21
set 2aximJ
NEC 240.4(D) requires that 0C PD rating not exceed 20A when
protecting a Copper 12 AWG conductor,
lit
F. Minimum Required EGO Size 4AWG
Where conductors are oversized, the EGC must be oversized by the
same fate. Table 250,122, gives a minimum EGC size of 8 AWG,
Multiplied by the oversize rate� this yields 26.24829kcmil corresponding
to 4AWG.
G. MinimumR,,e�commen�,dewdC;on�,duit Size I
The total area of all conductors is 0.3964irf. With a maidmurn fill rate of
0A the recommended conduit diameter is 1,25
�
NECCoilbCdculdim` `
I ' `~ '` ^` ~ ` ~
F
Product compliance: No Data
Powering Business Worldwide
s e ea"C , '., v
2016 Eaton. All rights reserved,
General Duty Cartridge us
Safety witc
22
UPC:782113144252
Dimensions:
* Height: 7 11
Length: 6.42 IN
Width: 3.32 IN
Weight:Weight:9 L
Notes:Maximum hp ratings apply only when dual
element fuses are used. -Phase hp rating shown is
a grounded B phase rating, UL listed.
Warranties.
Eaten Selling Policy 26-066, one (1) year from
the elate of installation of the product or
eighteen (13) months the from the date of shipment
of the Product, whichever occurs first,
* Type: General Duty/Cartridge Fuse
Amperage Rting:100
* Enclosure atonal: Painted galvanized steel
* Fuss Class Provision: Class H fuses
Fuse Configuration: Fusible with neutral
* Number Of poles; Two -pole:
* Number Of fires: Three -wire
* product Category: General Dusty Safety Switch
Voltage Rating: 240V
Supporting documents.
'23N„ B
Certifications:
UL Listed
/ff
IRONRIDGE
/
Flush Mount System
Iron idge builds the strongest mounting system for pitched roofs in solar, Every component has been tested to
the limit and proven in extreme environments.
Our rigorous approach has led to unique structural features, such as curved ails and reinforced flashings, and
is also why our products are fully certified, code compliant and backed by a 25-year warranty,
/ ra l
Strength Tasted
/
All components evaluated for superior
structural performance.
lass A FireRating
�
/
Certified to maintain the fire resistance
%'.,..,,
rating of the existing roof.
L 2703 Listed System
AV r
Entire system and components meet
newest effective UL. 2703 standard,
r lrPE Certified
Pre -stamped engineering letters
available in most states.
Design Assistant
fOnline
/
software makes it simple to
r
create, share, and price projects:
25-Year Warranty
Products guaranteed to be free
of impairing defects,
ya # i IM
=capabfflty�'
i
capabilityWE" K",
anodizedExtreme load capability
Clear
In
Self-drilling
UNNOWN
screws
UFOs stopper sleeves CAMO Grounding Lugs
Universal Fastening Objects
bond modules to rails.
® Fully assembled & tubed
• single, universal size
• Clear and black finish
Snap onto the UFO to torn
into a bonded end clamp.
• Bonds modules to ails
m sized to match modules
• Clear and black finish
staying completely hidden.
* Tod -less installation
* Fully assembled
Connect arrays to
equipment ground.
Low profile
Single tool installation
a founts in any direction
28375 Industrial Blvd
Hayward, CA 94545
IRONRIDGE I onRid e.c m3
Attn: Gorey Geiger, COO, IronRidge Inc.
Date: May 18'2020
Re: Structural Certification and Span Tables for IronRidge Flush Mount System
This letter addresses the structural performance and code compliance of EronRidge's Flash Mount System, The contents
of the letter shall be read in its entirety before being applied to any project design'. The Flush Mount System is'a
proprietary rooftop mounting system used to support photovoltaic (P) modules installed in portrait or landscape
orientation and set parallel to the underlying roof surface. PV modules are supported by extruded aluminum XR Rails and
cured to the rails with IronRid e mounting clamps. The XR Rails are side mounted to a selected roof attachment with
318" stainless steel bonding hardware and then attached directly to the roof structure or to a stanchion that is fastened to
the underlying roof structure. Assembly details of a typical Flush Mount installation and its core components are shown in
Exhibit EX 15,
The IronRidge Flush Mount System is designees and certified to the structural requirements of the reference standards
listed below, for the load conditions and configurations tabulated in the attached span tables.
0 SCE/SEI 7-10 Minimum Design Loads for Buildings and Other Structures (S E 7-10)
0 2015 International Building Code (IBC-2015)
0 Florida Building Code 6th Edition (2017) Building
0 2015 aluminum Design Manual (ADM-2015)
The tables included in this letter provide the maximum allowable spans of XR Rails in the Flush Mount System for the
respective loads and configurations listed, covering wind exposure categories B, C, & D, roof zones 1, 2 & 3, and roof
slopes from 81, to 450. The span tables are applicable provided that the following conditions are meta
1. Span is the distance between two adjacent roof attachment points (measured at the center of the attachment
fastener)
2. The underlying roof pitch, measured between roof surface and horizontal plane, is 45° or less,
3. The mean roof freight, defined as the average of the roof save height and the roof ridge height measured from
grade, does not exceed 30 feet.
4. Module length shall not exceed the listed maximum dimension provided for the respective span table and module
width shall not exceed 42".
5. All Flush Mount components shall be installed in a professional workmanlike manner per IronRid e's Flash Mount
installation manual and other applicable standards for general roof construction practice.
28375 Industrial Blvd.
r Hayward, CA 94545_
1- 227-23
IRONRIDGE lronRidrge, o hn
The span tables provided in this letter are certified based on the structural performance of IronRidge XR bails only with no
consideration of the structural adequacy of the chosen roof attachments, PV modules, or the underlying roof supporting
members. It is the responsibility of the installer or system designer to verify the structural capacity and adequacy of the
aforementioned system components in regards to the applied or resultant loads of any chosen array configuration.
Sincerely,
Gang Xuan0�
"# G r °^.� This item basbeen electronkaHy
signed and seal by Gang Xuan
1-...: 2
using a t>igital Signature and date.
Printed i"*f this document
...' are notcons`sdered ' dand 0 2 0, 0 5, 2 2
r 3sTfi i �. ' ,t✓ �, sealed and the signature must be
aw t a^ ver oa any electroMr copies,
0
'00'07- 12*032:1
Gang Xuan, P
Senior Structural Engineer
02020 IrcnRidge; Inc, FL Flush Mount System Certification Letter- 1 02020 IrcnRidge, Inc. FL Flush Mount System Certification Letter - 4
�r
r , terIRONRIDGE
Attn: Corey Geiger, COO, lronRidge Inc.
Date: July 1 si, 2021
Re; Structural Certification and Span Tables for the 1ronRidge Flash Mount System
This letter addresses the structural performance and code compliance of 1ronRidge's Flush Fount System. The
contents of the letter shalt be read in its entirety before applying to any project design. The Flush Mount System is a
proprietary rooftop mounting system used to support photovoltaic (PV) modules installed in portrait or landscape
orientation and set parallel to the underlying roof surface. PV modules are supported by extruded aluminum XR Rails
and secured to the rails with fronRidge mounting clamps. The XR bails are side mounted to a selected roof
attachment with 3/8" stainless steel bonding hardware and there attached directly to the roof structure or to a stanchion
that is fastened to the underlying roof structure. Assembly details of a typical Flush Mount installation and its core
components are shown in Exhibit EX-0015.
The 1ronRidge Flush Mount System is designed and certified to the structural requirements of the reference standards
listed below, for the load conditions and configurations tabulated in the attached span tables.
AS E/SE17-16 Minimum Design toads for Buildings and Other Structures (ASCE 7-1 )
2018 International Building Code (IBC-2018)
2020 Florida Building Code (FBC-2020)
2015 Aluminum Design manual (ADi -2015)
Report SEAOC (Structural Engineer Association of California) R1d2-2017 Wnd Design for Solar Arrays
The tables included in this letter provide the maximum allowable spans of XR Rails in the Flush Mount System for
the respective loads and configurations listed, covering vsrind exposure categories B, C, & D, roof zones provided in
ASCE 7-16 for gable & hip roof profiles, and roof slopes of S° to 45°, The tabulated spans are applicable when the
following conditions are met:
1. Span is the distance between two adjacent roof attachment points (measured at the center of the
attachment fastener).
2. Each moduleshall be supported by 2 rails (2 rail system) or 3 rails (3 rail system), Spans are calculated
based on 2 rail systems, and conservatively deemed acceptable for 3 rail systems.
* The underlying roof slope, measured between the roof surface and horizontal plane, is 60 to 450.
4. The mean roof freight, defined as the average of the roof save height and the roof ridge height Measured
from grade, does not exceed 30 feet.
5. A clearance from the underside of the array to the roof surfs of 2" minimum shall be provided and the
height of the array, the distance from the module top surface to the roof surface (defined as h2), shall not
exceed 10'.
6. Module length and area shall not exceed the maximum values listed on the respective span tables.
7. All Flush fount components shall be installed in a professional workmanlike manner per lronRidge's Flush
Moment Installation Manual and other applicable standards for the general roof construction practice.
28357 Industrial Blvd,
Heyward, CA 94545
�r%,� f 1-8t7o-227-9523
r s/,.,IRONRIDGE lronRidge.com
The span tables provided in this letter are certified based on the structural performance of lronR dge SCR Rails only with no
consideration of the structural adequacy of the chosen roof attachments, pv' modules, or the underlying roof supporting
members. It is the responsibility of the installer or system designer to verify the structural capacity and adequacy of the
aforementioned system components in regards to the applied or resultant leads of any chosen array configuration.
Sincerely, t4a X"
rt�
®14 r
r - r �
1't
Gang Xuan, PE
This Item has been eiectronka##y
stomed and sea9 by Gtrrrg %uon
Lomita.tftital ` rture and date.
Printed copies of this document
are not considered signed and
sealed and the signature must be
verified an any electronic copies.
02021 lron.Ridge, Inc. FL Rush Mount System Certification Letter -1 02021 4ronRidge, Inc, FL Rush Mount System Certification Letter - 4
_..,. ,, ,, ., .: ,. ✓, �r .. .. ,,, / -.. .. ..�/. / 2.,.: -; _. .., ram„ /.... ✓, .., ..:.,/ .,. r':. / ✓/ .✓. , .. :..... .. . .....,✓ / „ ,✓ . ,. /r/_ /.. err<.
/ ✓ r a r.
/ ✓ r / r r f i / r ✓ /
,. . / ,./ .. '. / / / 1. / , r:.., / . / .✓. ..,. r ,. ,. ,-„_. r r.,. ,. ,.;•..,c „ ,,....; r..., ....r rr,,,,..,,._rr r, , ,,./c.., r, /r /._ rr, / , / , .,, , ,. , , . r f / . /. ,./,/: /
The RushSystem
„r r.r. ,.
T us Mount � stem`ma be'used to round and/or mount a PV module com l in mA h UL 2703 only when t e as
Y � � py €� It yua h specrficmtxluleh
been evaluated for grounding and/or mounting in compliance with the included Instructions. Unless othervAse noted, "xxx" refers to the Eoosolargy,modules with 35, 40, and 50 mm frame
module power rating and both black and silver frames are included in the certification. ECOxxxYzzA-bbD
Ecosoiargy Where "r can be A, H, S, or T; "zz" can be 125 or 156; "N' can be M or P; "bb° can be 60 or 72; and "D" can
........,.. Where Y�l can be blank i�E; or SE, or SE72
Dehui modules with 30,35 and 4orr m frames
Dehul i7 1-IUfYY fZ xxx
re ` n be 760, ' 772, 872; and 'Tcan be B, For W
1. ✓ , ,.. , ..., / /r ,. r r _,. /, r �.., ... .. .:.. .,,.. , :. ., ,.. a:
r / � u. r r ✓ _
T r, i .., � ,, _�.,,< /r.�r_ ,. �s r �� _.r.�/�, �,. �.. � � < r „/ .✓� r. ,r,,.x � i/l ~ r,, �i �_r, rr, M,......,r ,, ,.
Phono Solar modules m(Ith 35, 40, and 45 mm tames
Phonb Solar PSxxxY: A
Where "Y' can be M, M1, MH, M1 H, M4, M4H or P; " ' can be 20'or 24; and "N' can be F, T, U, UH, orTli
f /
J � r n ri
/l / / /r'/' /. �. / /'� ,l f / f//%l�i:: jr/,// /l ////' /: ✓��j ff/ f✓•'_ f / //f/l
SolarWorid Sunmodule plus, Protect; B€sun, XL, 51sun XL, maybe followed by mono, poly, duo, black, b, or
SolarWorld Americas
clear; modules with 33 mm frames
SWA-xxx'
Somali
Somali Modules with 40 mm frames
SSxxx
,....
Stion
,. _..,. ,,..,. .......:.........,, ..,, .
Stion Thin film modules with 35 mm frames
STCxxx or STO-xxxA
SunEdison Modules with 35, 40 50 mm frames
SunEdison
SE-YxxxZABCDE
n be B C D,E H I J K,L or al . "B" can be 8 or °
Where ''can be 6 F H P R or Z; "Z" can be 0 or 4; "A" ,
W, "C" can be A or C; " U' can be 3, 7, 8, or ; and " E" can be 0, 1 or 2
Suniva modules with 35, 38, 40, 46, and 50 mm frames
OPTxxx-AA-S-YYY-Z
Suniva
x- -B- -
Where "4A" is either 60 or 72 "B" is either 4 or 5; -Y'Y " is either 100,101,700,1 S0, or 1 S1; and'7" is blank
or B
Sunpower standard (G3 or G4) or InvisiMount (G5) 35, 40 and 46 mm frames
Sun over
p
SPR- xxx-YY
'
Where ' Z'' is ether o X; _ " c be blank, 7 1 9 1 or 22 and
can b k L s �, E, P, r , `b an nk, 1 8,1 , 2t�, 2 , , a e blank, B kC,
CO CAC D AC E AC BL E AC GAG SL#4 C-AC or BLIP-D AC
Sunspark modules with 40 mm frames
_
Sunspark
S` Y-xxx2 A
WhereW can be MX or ST; and "Zoan be € , MB, M3, M315> P or W; and "A" can be 60 or 72
Suntech Modules h 35, 40 and 50mm frames
ST y-zzlaa
Surech
ere "y" is blank or S; and "zz" can be 20, 24, A60 or A72U; and "aa"can be Vd, Vem, Vfw, Vh, Wdb, Wde, 5
Wd, or Wfhb
Talespn modules Win 30, 35 and 40mm frames
Taiesun
TAByZ-Laa xxx-b
Where "A" can be D or P; "B" can be 6 or 7; "y" can be blank, F, G, H, I or L; ' " can be 60, 66, 72 or 78;
"aa" can be M, (H), or P; and "b"Sean be blank, B, T, or (H)
Tesia modules with 40 mm frames
Tesia
TxxxY
Where 'Y' can be H or S
Trina Modules with 30, 35,40 and 46mm frames
T s-xxx`tYZ.Z
Where "YY' can be DD05, DD06, DD14, DE14, DE15, DE15V, DEG15, DEGI5VC, DE18t , DEG18 C,
Trina
DE09, DE19, DEG19C,20, DE06X, PA05, PCO5, Pam, PCB, PA14, PC 4, PD14, PE14, or PE15 „ and
"ZZ„ can be blank ,05, 05(11), .i , Z8(li), .10,{ A8, .OSD, 181), 0:32, . , 00S, 05S, , ,20(11), A,A.05,
A.08, A10, A.18, (11), A(ll), A;.05(1I), A.08(11), A.082(11), A.10(ll), AA8(ll), H; H(11), K05(11), H,08(11), HC,20(II),
HC.24(11), try, M(11), DS(11), MC.20(11)
URE modules with 35 mm frames
URE
DyZxxxaa
ere " C>" can be D or r "y" can beA; 6 or 7; "Z" can be K or fa; and "aa" canbe H3A, H4A, H8A, VG -BB,
ESG or E8G-BB
V€kram sour modules with 40 mm frarrms
Vikram
VSyy.ZZ.AAA,bks
Where "yy" can be M, P, MBB, MH, MS, ti HBB, or PBB; ` n be 60 or 72;" " is the module power
rating; and "b" can be 03, 34 or 05
VSUN modules with 30, 35 and 40 mm frames
VSUh1
V UNxxx-YYz-aa
Where "YY" can'be 60, 72, 108, 120, or 144; ' z" can be M, P, MH, PH, or B H; and "as" can be blank, BB,
BW, or,;
i
,. _, s,..,u....... r.. ,r,;: ,,.,r,.,,-s„ ,, .,, �i �,.r..,��„/,-e-'Jri ,.,,. `,,. .,,, �, � .,,,.., �! ,,a,✓., ,, .�. ,.1. /i,.,!,,,,.�: ,i �r�,....df r,.. �r�.r ,.. ,i ��6�,,r..//�/
area modules with 40mm frames
Wearee
WSyy-xxx
where "yy" can be blank, M, or MB
UVinalco modules with 35 and 40 mm frames
Winaico
sy-xxxza
Where "y" can be either P or T; "Z" can be either M, P, or X; and "a" can be blank or 6
Yingli ules with 35 and 40 mm frames
Yingli
YLXxxZ-YY
ere can be D or P yy can be 29b 30b, 34d, 35b 36b or
ZN Shine modules with 35rnm frames
ZPE ShineZXMY-AAA-xxx/
Where "Y" can be 6 or 7, "AAA" can be 72, HH120, NH144, NHD8144, NHLDD144, SH144, SHDB144 or
SHLDD144
Y
f /
Astronergy frameless modules
ronergy Solar
CHS 661OP( )-xxx
Canadian solar frameless, modules
Ca nadian Soler
by xxx Z
Where "b" can be 3 or 6. "Y" is .lG P U or X' and "Z" oan be M-PG MS-FG, P-FG MB-FG or PB-FG
eliene frameless modules
Heliene
YYZZxxxA
Where "YY'can be72; " ' can be ; and "A" can be GH
Jinko frameless modules
Jinko
JKMxxxPP- )
Prism Solar frameless modules
Prism Solar
S )xx
Where "Z" can be 1 or t; "YY" can be 48, 60, 60S, 72 or 72S; and "AAA.' can be blank or BSTC
Risen frameless modules
Risen
RSyy-6-xxxZZ
Where "yy" ban be 60, 72, 120 or 144; and "= can be MDG or PDG
Stion frameless modules
Stion
STL xxx or STLxxxA
Sunpreme frameless modules
Sunpreme
GXB-xxxYY
Where "YY'can be blank or SL
Trina frameless modules
'TSM-xxxYY
Trine
Where"YY"can be either DEGS(11), DEG5,07(11), DEG5.40(11), DEG5.47(11), DEG14(1), DEG140(li),
DEG14C, 7(11), DEG14.40(11), PEGS, PEG5.07, PEG5,40, PEG5.47, PEG14, or PEG14.40
S-51OWarninot Plwso use this productrespondW Distributed by
axe jw by asa P% US. and fwalp p deft raprd[M
112513,