HomeMy WebLinkAbout22-5148It of Zephyrhilis
5335 Eighth Street
Zephyrhills, FL 33542
ELCMISC-005148-2022
Phone: (813) 780-0020
Fax: (813) 780-0021
Issue Date: 11/15/2022
Permit Type: Electric Service Replacement/Misc
Z
11 26 21 0010 21200 04A2
Name: JOHN & SHIRLEY PEAVEY Permit Type: Electric Service Replacement/M
Class of Work- Add/Alter Residential
Address: 5029 16Th St
ZEPHYRHILLS, FL 33542
Building Valuation: $15,864.00
Electrical Valuation: $24,000.00
Mechanical Valuation:
Plumbing Valuation:
Total Valuation: $39,864.00
Total Fees: $418.98
Amount Paid: $418.98
Date Paid: 11/15/2022 3:39:36PM
5029 16Th Street
AN -0 1 i i N- I W-6 lal M1 1 6 a-=
. .... ..... -
. . .. .. . . .....
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
I I I I 11EMT
I I � I III 1 1111 M M;,[x I ;I =♦i I,
EMIM. 2ZMEM3='
23131���
Complete Plans, Specifications add fee Must Accompany Application. All work shall be performed in
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
Y4 *rl
671MONTHS WITHOUT APPROVED INSPECTION
1111 1 1 1 . 4111
; 0 0 , '0
2=016:11VA '180,140
760orth Meadowbrook Drive
�o E"N
Alpine, UT 84004
CoApmenD. Larsen, SE PE
office (201) 874-3483
Gnegn/yT. E7veata4 PE
swysoling@wysslinAconsulting.00/n
Modern Concepts Sola
201 North Franklin Stre
Suite 2200
Tampa, FL 33602
!Ke: Engineering Services
Pe�vy Residence
6.480 kW System
ToWhom bMay Concerm.
We have received information regarding solar panel installation on the roof ofthe above referenced
structure, Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
tosupport the additional loads imposed bythe proposed solar system,
1 . Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system,
are constructed of2x4dimensional lumber,
Roof Material:
Composite Asphalt Shingles
Roof
23degneoe
Attic Access:
Inaccessible
Foundation:
Permanent
Dead Load
" Live Load =2Opo (redudbde)—Opofsdlocations ofsolar panels
* Ground Snow Load =Opa
° Wind Load based onASCE7-1G
o Ultimate Wind Speed = 140 mph (based on Risk Category ||)
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the FBC 2020 (71h Edition) including provisions allowing existing structures to not require
strengthening if the new loads do not exceed existing design loads by 105% for gravity elements
and 110% for seismic elements. This analysis indicates that the existing framing will support the
additional panel loading without damage, if installed correctly,
MIZMZ���
'how, RAW, IN I 11FINIIIIIII-01MA I WalIN INNIN *11111111110 WIN" V w -110!
-9 IIWA - 11MINOW I
to us at the time • this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Wyssling Consulting, PLLC
76 N Meadowbrook Drive Alpine UT 84004
Florida License # RY34912
MW
PHOTOVOLTAIC ROOF MOUNT
SYSTEM
PROJECT DATA
GENERAL NOTES
VICINITY MAP
PROJECT
5029 16TH ST,
1.
ALL COMPONENTS ARE UL LISTED AND CEC CERTIFIED, WHERE WARRANTED.
D nr
ADDRESS
ZEPHYRHILLS, FL 33542
san yr'
2.
THE SOLAR PV SYSTEM WILL BE INSTALLED IN ACCORDANCE WITH ARTICLE 690 OF THE NEC 2017.
OWNER:
JOHN PEAVEY
3.
THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL
a;
OPERATION.
`
DESIGNER:
ESR
4.
ALL CONDUCTORS OF A CIRCUIT, INCLUDING THE EGC, MUST BE INSTALLED IN THE SAME RACEWAY, OR CABLE, OR
OTHERWISE RUN WITH THE PV ARRAY CIRCUIT CONDUCTORS WHEN THEY LEAVE THE VICINITY OF THE PV ARRAY.
3'0-s, F " 33542.
SCOPE:
6.480 KW DC ROOF MOUNT
SOLAR PV SYSTEM WITH
5_
WHERE METALLIC CONDUIT CONTAINING DC CONDUCTORS IS USED INSIDE THE BUILDING, IT SHALL BE IDENTIFIED AS
"CAUTION: SOLAR CIRCUIT" EVERY 10FT.
16 JINKO SOLAR: JKM405M-72HL-V
Cryrsta,:,gs
405W PV MONO MODULES WITH
6.
HEIGHT OF THE AC DISCONNECT SHALL NOT EXCEED 6'-7" PER NEC CODE 240.24.
N? ,
16 ENPHASE IQ8PLUS-72-2-US 290W'
MICRQINVERTERS EQUIPPED WITH
7.
A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH CEC 690,47 AND 250.50 THROUGH 60 AND 250-166 SHALL BE
-
'
PROVIDED. PER NEC GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND BONDED TO THE SERVICE
RAPID SHUTDOWN
ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE OR INADEQUATE A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE USED
AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT. GROUND ROD WITH ACORN CLAMP. GROUNDING ELECTRODE
CONDUCTORS SHALL BE NO LESS THAN #8 AWG AND NO LARGER THAN #6 AWG COPPER AND BONDED TO THE EXISTING
HOUSEPHOTO
AUTHORITIES
HAVING JURISDICTION:
GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.
BUILDING: CITY OF ZEPHYRHILLS
ZONING: CITY
OF ZEPHYRHILLS
8
PHOTOVOLTAIC MODULES ARE TO BE CONSIDERED NON-COMBUSTIBLE.
UTILITY: DUKE ENERGY
9.
PHOTOVOLTAIC INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING. MECHANICAL, OR BUILDING ROOF VENTS.
10,
ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE.
WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE.
SHEET
INDEX
11
ALL SINAGE TO BE PLACED IN ACCORDANCE WITH THE LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV
RESISTANT. ALL PLAQUES AND SINAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.
PV-1
COVER SHEET
PV-2
SITE PLAN
12.
INVERTER(S) USED IN UNGROUNDED SYSTEM SHALL BE UL 1741 LISTED.
PV-3
ROOF PLAN & MODULE
PV-4
ELECTRICAL PLAN
13,
THE INSTALLATION OF EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE PERFORMED ONLY BY
QUALIFIED PERSONS [NEC 690.4(C)l
PV-5
STRUCTURAL DETAIL
PV-6
ELECTRICAL LINE DIAGRAM
14.
ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED (OR BETTER), INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND
PV-7
WIRING CALCULATIONS
SWITCHES.
PV-8
LABELS
15,
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH NEC ARTICLE 250.
PV-9
PLACARD
PV-10
MICRO INVERTER CHART
16.
SYSTEM GROUNDING SHALL BE IN ACCORDANCE WITH NEC 690.41,
PV-11+
EQUIPMENT SPECIFICATIONS
17.
PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION IN ACCORDANCE WITH
NEC 690A2
C
MC. S1_"1__LAR
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10/03/2022
tt� s
`f✓s
a
STATE F I
' �
t� q
Wyssling Cons€ ttin , PL C
75 N Meadowbrook Drive Alpine UT 84004
Florida License # RY34912
Date Signed 10/07/2022
PROJECT NAME & ADDRESS
Col
Iq
L0
(')
�. M
J
_
Q U}
{!} _
w p
}
IO _
w
SIGNATURE
18. DISCONNECTING MEANS SHALL BE LOCATED IN A VISIBLE, READILY ACCESSIBLE LOCATION WITHIN THE PV SYSTEM
EQUIPMENT
DRAWN BY
OR A MAXIMUM OF 10 FEET AWAY FROM THE SYSTEM [NEC 690.13(A)]
19, ALL WIRING METHODS SHALL BE IN ACCORDANCE WITH NEC 690.31
PROJECT TO COMPLY WITH THE FOLLOWING:
BS R
SHEET NAME
20. WORK CLEARANCES AROUND ELECTRICAL EQUIPMENT WILL BE MAINTAINED PER NEC 110.26(A)(1), 11026(A)(2) AND 110.26(A)(3).
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)
COVER����
FLORIDA PLUMBING CODE, 7TH EDITION 2020 (FPC)
21. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED & IDENTIFIED IN ACCORDANCE WITH
FLORIDA BUILDING CODE, 7TH EDITION 2020 EDITION (FBC)
UL1703
FLORIDA MECHANICAL CODE, 7TH EDITION 2020 (FMC)
SHEET SIZE
2017 NATIONAL ELECTRICAL CODE
22. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT RUNS AS REQUIRED PER NEC.
FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020
ANSI B
(FFPC)
11 " X 17„
SHEET
gN�UMBER
PV-1
ROOF MOUNTED SOLAR PHOTOVOLTAIC MODULES
DC SYSTEM SIZEi 16 x 405 = 6.48OKW DC
AC SYSTEM SIZE: 16 x 290 = 4.64OKW AC
EQUIPMENT SUMMARY
16 JINKO SOLAR: JKM405M-72HL-V405W MONO MODULES
16 ENPHASE IQ8PLUS-72-2-US 290W MICROINVERTERS
EQUIPPED WITH RAPID SHUTDOWN
ROOF ARRAY AREA #1:- 281.58 SQ FT,
ROOF ARRAY AREA #2:- 64.98 SQ FT.
NOTE: VISIBLE, LOCKABLE, LABELED AC DISCONNECT
LOCATED CLOSE PROXIMITY TO UTILITY 11ETER
(m) ur- 1 /-Aum
STRUCTUF
ROOF #5
(3) JINKO SOLAR: JKM405M-72HL-V
405W MONO MODULES WITH ENPHASE
ZTERTSTRIN,
(E) UTILITY METER
(N) VISIBLE, LOCKABLE,
LABELED FUSED AC DISCONNECT
fLOCATED CLOSE PRO1t1LLtZajMLZL�jLLjL1L
SITE PLAN
SCALE: 1/16" = V- i
N
0
0
m
r
z
Oft
LP
Haram
ROOF #1
(13) JINKO SOLAR: JKM405M-72HL-V
405II I W MONO MODULES WITH ENPHASE
ififil �MIT
DESIGN SPECIFICATION
OCCUPANCY: 11
CONSTRUCTION: SINGLE-FAMILY
ZONING: RESIDENTIAL
GROUND SNOW LOAD: REFER STRUCTURA,
WIND EXPOSURE: REFER STRUCTURAL LE ER
WIND SPEED: REFER STRUCTURAL LETTER I
mc,
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10103/2022
11HI
%
STATE Faye
%
f4 0 R 10'�
Wyssling Consutting, PLLC
76 N Meadowbrook Drive Alpine UT 84004
Florida License # RY34912
Date Signed 10/07/2022
PROJECT NAME & ADDRESS
(N
'IT
Lr)
cy')
CY)
_j LL
C) (1) w
>
< z U)
w w
Z Ui 0-)
N Cr
T_ w 0
>_
o C( Lo =
D_
Lli
N
1DRAWN ®®BY
SR
SHEET NAME
SITE PLAN
SHEET SIZE
ANSI B
11 " X 17"
SHEET NUMBER
PV-2
MODULE TYPE = JINKO SOLAR: JKM405M-72HL-V 405W MONO MODULES
ROOp#2
PITCH -z3'
AoM. 179'
w
ROOF]405W MONO MODULES WITH ENPHA
Ohl C
1 ROOF PLAN & MODULES
ROOF DESCRIPTION
ROOF TYPE
ASPHALT SHINGLE
ROOF LAYER
1 LAYER
ROOF
#OF
MODULES
ROOF
PITCH
AZIMUTH
TRUSS
SIZE
TRUSS
SPACING
ARRAY AREA & ROOF AREA CALC'S
TOTAL PV ARRAY
AREA
TOTAL ROOF
AREA
ROOF
AREA COVERED BY
ROOF #1
405W MONO MODULES WITH ENPHASE
�
J|MKDSOLAR: |
MODERN CONCEPTS SOLAR
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10/03/2022
till I
558
STATE
PONA
Florida License # RY34912
Date Signed 10/07/2022
PROJECT NAME & ADDRESS
NT
LLI
JKM485M-72HL^V DRAWN BY
485VVMODULES || ESR
[�1"
LEGEND
SOLADECK
-------
pVPRODUCTION METER
-INVERTER
COMBINER BOX
-JUNCTION BOX
ACD'
AC DISCONNECT
>
VENT, ATTIC FAN
-'
(ROOF OBSTRUCTION)
S,,.o
-SOLARLOADCENTER
�ROOFATTACUMENT
UTILITY METER
-TRUSS
hmap
��
MAIN SERVICE PANEL
— -
CONDUIT
mm
0
tm
B
ATTACHMENT ! (enlarged
Mi'MaymillsKm`
•
s
•• a
as a�' Wit•^ ss
i u i
n
s s a
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10/03/2022
i
STATE
j'trrrtrrmtttWO
Wyssling Consulting, PLL
76 N Meadowbrook Drive Alpine UT 04004
Florida license # R734912
Date Signed 10/07/2022
PROJECT NAME & ADDRESS
CV
L0
Cr3
> () i1,
U)
w W c~o J
(f�
LO
}
0—
w
N
DRAWN BY
ESR
SHEET NAME
STRUCTURAL DETAIL
SHEET SIZE
ANSI S
11" X 17"
SHEET NUMBER
P Yp`'V
DC SYSTEM SIZE: 16 x 405 = 6.48OKW DC
AC SYSTEM SIZE: 16 x 290 = 4.640KW AC
(16) JINKO SOLAR: JKM405M-72HL-V 405W MONO MODULES
WITH (16) ENPHASE IQ8PLUS-72-2-US 290W MICROINVERTERS
EQUIPPED WITH RAPID SHUTDOWN
LOCATED UNDER EACH PANEL (240V)
(2) BRANCH CIRCUITS OF 8 MODULES CONNECTED IN PARALLEL
JINKO SOLAR: JKM405M-72HL-V
405W MODULES
BRANCH #1
1 2 3 0 0 0 7
f -7 _Vff
BRANCH #2
1 2 3 0 0 0 7
I
+ + _ + 1 _ .1
0 o o
BRANCH
TERMINATOR
(ET -TERM) ENPHASE 108PLUS-72-2-US 29OW
MICROINVERTERS EQUIPPED WITH
RAPID SHUTDOWN
LOCATED UNDER EACH PANEL (240V)
8
8
INTERCONNECTION NOTES:
1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE
DETERMINED IN ACCORDANCE WITH [NEC 705.121, AND [NEC 690.591
2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9],
[NEC 230.951.
3. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING.
4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE
BUSBAR RELATIVE TO THE MAIN BREAKER.
DISCONNECT NOTES:
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN
THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE
CONNECTED TO THE TERMINALS MARKED "LINE SIDE" (TYPICALLY
THE UPPER TERMINALS)
2, AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY
PERSONNEL, BE LOCKABLE, AND BE A VISIBLE -BREAK SWITCH
3. DISCONNECT MEANS AND THEIR LOCATION SHALL BE IN
ACCORDANCE WITH [NEC 225.311 AND [NEC 225.321.
GROUNDING & GENERAL NOTES:
1. PV GROUNDING ELECTRODE SYSTEM NEEDS TO BE INSTALLED IN ACCORDANCE
WITH [NEC 690.431
Z. PV INVERTER IS UNGROUNDED, TRANSFORMER -LESS TYPE,
3. DC GEC AND AC EGG TO REMAIN UNSPLICED, OR SPLICED TO EXISTING
ELECTRODE
4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS
FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL
INSPECTION,
5. SOLADECK QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE
FIELD - SOLADECK DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE
TYPE TRANSITIONS.
6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
7. RACEWAYS AND CABLES EXPOSED TO SUNLIGHT ON ROOFTOPS SHOULD BE
INSTALLED MORE THAN 7/8" ABOVE THE ROOF USING CONDUIT SUPPORTS.
RACKING NOTE:
1. BOND EVERY RAIL WITH #6 BARE COPPER
ENPHASE IQ COMBINER
X-10-AM1-240-4/4C 120/240VAC,
I�, 3W 125A RATED BUS BAR,
NEMA 3R SOLAR LOADS ONLY
UL 1741 COMPLIANT
IQ ENVOY : PER
MANUFACTURER
SPECIFICATIONS, EITHER IQ ENVOY
10A OR 15A BREAKER IS
SUITABLE FOR USE 15A/2P
-0, C--
SOLADECK, 20A/2P
600V NEMA 3R,
UL LISTED o-
20A/2P
SUPPLY SIDE CONNECTION
REF 2017 NEC 230.82(6)/705.12(A)
PV FUSED AC
DISCONNECT# 2,
240V, I�, 3W
60A RATED
NEMA 3R
LINE
30A
LOAD
L2..
N
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
LOCATED CLOSE PROXIMITY
TO UTILITY METER
w.1
'1
1 ELECTRICAL LINE DIAGRAM,
PV-6 SCALE: NITS
TO UTILITY GRID
L 1
I IYI -'--L2
BI-DIRECTIONAL
UTILITY METER
120/240V, 10, 3-W
d (E) MAIN BREAKER TO
150A/21` � HOUSE 240 V,150A/2P
(E) MAIN SERVICE
-_- N DISCONNECT,
G 200A RATED, 240V
(E) MAIN PANEL,
—a
SQUARE D- QO
, 5
200A RATED, 240V
a�
LOAD/LINE SIDE
INTERCONNECTION AT
MAIN PANEL/SUB-PANEL
PER ART.705,12
N
GEC
EXISTING GROUNDING
ELECTRODE SYSTEM TO EARTH
REF, NEC 250.52, 250.53(A)
QTY
CONDUCTOR INFORMATION
CONDUIT TYPE
CONDUIT
SIZE
(4)
#12AWG -
ENPHASE ENGAGE CABLE
(L1 & L2 NO NEUTRAL)
N/A
N/A
(1)
#10AWG
CU,THWN-2GND
(4)
#10AWG -
CU,THWN-2
(1)
#10AWG
CU,THWN-2 GND
EMT OR LFMC IN ATTIC
3/4"
(2)
#6AWG -
CU,THWN-2
O
#6ANS
CU,THWN-2 N
EMT, LFMC OR PVC
3/4"
(1)
#6AWG-
CU,THWN-2 GND -- -- ..--
(2)
#6AWG -
CU,THWN-2
(1 )
1 #6AWG
CU,THWN-2 N
EMT, LFMC OR PVC
3/4"
(1)
1 #6AWG -
CU,THWN-2 GND
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION ^—DATE
REV
INITIAL DESIGN 10/03/2022
tliH #}
STATE
rR Di `�.
Wyssling Consulting, PLLC
76 N Meadowbrook Drive Alpine UT 04004
Florida License # RY34912
Date Signed 10/07/2022
PROJECT NAME & ADDRESS
LO
F C)
r U LL_
w W .I
z (1) _
o
NLO
LL
�
Lij
N
DRAWN BY
ESR
SHEET NAME
ELECTRICAL LINE DIAGRAM
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-6
LABEL-1
LABEL LOCATION
AC DISCONNECT
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
LABEL- 2:
LABEL LOCATION
AC DISCONNECT
COMBINER
MAIN SERVICE PANEL
SUBPANEL
MAIN SERVICE DISCONNECT
CODE REF: NEC 690.13(B)
LABEL- 3:
LABEL LOCATION
UTILITY METER
MAIN SERVICE PANEL
SUBPANEL
CODE REF: NEC 705.12(C) & NEC 690.59
MTI :4 211 ]z Les I Z fw-i I a],
LABEL- 4
LABEL LOCATION
MAIN SERVICE PANEL
SUBPANEL
MAIN SERVICE DISCONNECT
COMBINER
CODE REF: NEC 110,27(C) & OSHA 1910.145 (f) (7)
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL- 5
LABEL LOCATION:
AC DISCONNECT
CODE REF FFPC 11.12,1.1.1.1 & NEC 690.56(C)
LABEL- 6:
LABEL LOCATION:
AC DISCONNECT
CODE REF: NEC 690.56(C)(2)
LABEL- 8-
LABEL LOCATION
MAIN SERVICE PANEL
SUBPANEL
AC DISCONNECT
CODE REF: NEC 690.54
LABEL- 9:
LABEL LOCATION:
MAIN SERVICE DISCONNECT (ONLY IF MAIN SERVICE DISCONNECT IS PRESENT)
CODE REF: NEC 690.13(B)
MC. S
T
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION
DATE
I REV
INITIAL DESIGN
10103/2022
5 558
STATE F
R 0 )
N
{jx111111#£89€St
Wyssling Consulting, PLLC
76 N Mead brook Drive Alpine UT 84004
Florida License # R734912
Date Signed 10/07/2022
PROJECT NAME & ADDRESS
(N
14-
Lr)
(y-)
(Y)
> C) LL
< z U)
w w (0
CL 0
z C/) CN
TZ w 0
o
LU
N
DRAWN BY
ESR
SHEET NAME
LABELS
SHEET SIZE
ANSI B
11 " X 17"
SHEET NUMBER
PV-8
KEY FEATUIRES
11JI11 DiridCell Technology
IINN
E/;
High Voltage
l
-7
7-
4211W
---- ------
--- --- ------ ---- ----- -- ------
'Mw im-16
�u
7
e,
2A
'2
, . TNT -
Higher Mod0e Power
��,H
V
KM1,,',15tA 1-21HL-
'ST
�rc&:t
SVC N111C,
Sf-C
1417
67T
S"', -mr-'r-F
Shade Tolerance
Mwdmm- ww" e-,la"o tllp nP
1v
41AV -3�, �iv'
41 -TV
19 S'V
-Q, P111.
1 "Y"
V1 TV 41, 014
ZAA
F�
"Xnen,dimue "'A'ttagVlxx';
f
4 .V
-is 511e 4 Al
As, W
0 51v
V 49 71V
PID FREE
1', ',"A 2','A
Is
,,vr
Strength and Durability
(- -anchmnd �240G P,, 'emffe, .ox hugh "p,
Pb—ml Td-mmce
45'21811,�111-
LINEAR
PEERFORINIANCE INARZIRANIY
-A 'A
16Yea,,',roduc-,1AojrTaFjry 25 Yeac Linear Power Warranty
ST C V,",
4r sta�ld-d
flj�t,�Oaj Y
NOCTI- -im4
A-nr, 2-1�
A 'A, I
Speed 1-
Mc.
S--
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA , FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL
DESIGN
10/03/2022
1
PROJECT NAME & ADDRESS
L0
CY)
CO
W
W co —1
>
() LL
<
z C/)
W
W -J
✓
0-
0 -j
z
U)T-
T-
W D
o
cj� LCO
NW
DRAWN BY
SR
SHEET SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
Pv-1 1
-x
AS
-
Our newest 108 tvlicroinverters are the =r dustry's first micrcgrid-forming„ softwaare-
def6red microinvieters with spit -phase power conversion capability to convert DC
power to AC power efficiently, The braid of the setnicorlductor-based microinverter
is our proprietary application -specific integrated circuit (ASIC) which enables the
microinverter to operate in grid -tier or off -grid modes, This chip is built it advanced
dDrimr technology with high speed digital logic and x s sups, response times
to changing loads and grid events, alleviating Constraints on battery sizing for home
energy vrvsterr s,
sk'
I u?.rf -,he E Pr er, Energy System, 108 seroo;
Vic nonverlers rt €Wr_ Wdih ,..eEno, aee Ki-ttery,
chase it Gat€ y,and e ErrphaeeAPp mu rP r'g
and anoysso software,
108Seers Microir sractrc'efix;e ei,"aEity
standards e4th assre rran coo r`ffVcis causst.re
hou,nscf,hice-er-or, oiciro,rr€ brigan.;dustiv-
iea rng limrrsd warrarty of up to 25 }ears.
Connect a } modriles re,
ckty and easilyto tC.iS Set e5 108 Series kific user tars or_ UL Li isd as
sficounverters,sarg the rckyled0DCr- 2:adar,:4r PVRpid Shut Drwr, Equipmentand omu'st-,
cable wit ^oug r,:>' MC 4con eintors. .arcsi�s re-, Wx ic ns, when inc.. daaou. dio'g'0
rna r, Lrfacrur-r *o- in rwrrorrs
221022 Enpfeee Enegy, All i_ D reservrc; , G .a e� Me Enp'Pta bylo, foe
comes are cadersaws or _ens are ` ergs fnc, Data eutiocc tricuaugp,
.�ru. -GS Ur3u2-ir-EN Jw 2C",.u.'2-J3-17
Easy to install
Lightweight and compact with
plug_rs-play connectors
Power Line Communication
(PLC) between components
Faster iostai at€on ar th simple
two -wire cabling
High productivity and reliability
Produce power even when the
grid is dowin'
More than one million cumulative
hours Of testing
Class If double -insulated
enclosure
Optimized for the latest high-
powered PV modules
iercregri-fortmiz
Complies with the latest
advanced grid support —
Remote automatic updates for
the latest grid requirements
{:,.
CCiSi€S'9 ttrars3 .e �. to support a wide
range of grid profiles
Meets CA Rule 21(UL 1741-SA)
requirements
and + Microinverters
commonotsme rt dWepainrrgsr
A
235-350
235-440
Module corip it fbility
60-c,e( 20 half-ce€( efJ- Vi/V .rif-c—efl
c°S-LisK32half cerhisd 1 cell/144
hart -cell
3PP' sologe range
`a
2. - 3,,
29 - 45
opwating range
'd
25 -4E
25-.53
pl, i/corx star` 'c^age.
'.1
30 / 48
30 t 58
Max ;i put DC `, ;;a e,
t
50
60
Max Do current' ir^rrdueisc°'
A
1P
aver 'so tAge v.layS 0C. vci;.
it
PPV R„rray c ursflgu,:aticn
3
let, Ungraorided array, N-o ads tEft rai DC side pro terbor, eclurredd AC ade protroc or, ieq tyres , via x 20A Per branch „ E C':, it
Peak ou#,rutpower
WA
245
Soo
Max c rrtlril._xonutPutP"oaac
`{A
240
290
N;;€rkial ; L) soita ehan et
'a
240 i 211- 264
Nax ccrittruou, oontii -; 4ren
R
1.'S
1,21
Nona nal, fr uerov
itz
660
Eneerxk:d frequency range
i#z
50-68
AC short cacu,t foil -anent over
v c{es
Arts
2.
Miciunosp 20A(L-L Erarcr,6rc s'
116g3
alharcnr r,dwortion,
<5 .
ovccoftage uwes,PC;Pcxrt
Ill
AC to ?rt haddeed currenT
aA
30
Paver factor ssonr t
to
Gnat -tee paaer. factor edrt,stanie)
085 waning r` Gagang
Ps r,ryiticien y
%
9r5
976
CEC e^acg * eftown, y
iv
97
97
iYtgr°Y$me Power consumption
,Me
60
A ?. nttompereaurs,fauge
_401Cto,6010Ci 40o'to>1Fi
Perot ve hr rr der. ear,, e
4 nto 100%icc: deming
DD Cc.,nert r type
N 4
viale',xs,orrs(HxV3AD)
212,a'_rst5 Y!x115 curi 6e3.0as35G .mn,21,
oboliv
1:08kgt ,.tssk
C'' olroi
Natural 4f3mect::i r,-€?Gfar's
,Approved for wt',wat.;orx,*
Yes
i c!i =tiondegee
Pus
Encosure.
Coss 'it
doun?e-trisfl ed- corrosion, resociro orcycer,; reciss,ure
env€rear+.category i0Vccricsu.a atin
NEMATyiw6truv or
CA rV ,l:.e 21(CL fool -SA, .,AL 62109A.lA 174WEEE1,547 FCC. Part 15 „firs E.10ES-0003 Class S., r,AN/1_ t C^2C2 NQ 107.1-01
C atih,c.atirns The Product is JL. Listed as No Rapid ShLA ;:toys Eculrs=mrt and urnfof oc, ont%, NEC 2014, NEC 207, a ud NErC 2020 seztsr n
bJ1,12 and C211-22015 0e ie -218 rapid Shutd=own 0f Pil o sterns„or & arw D cor ouu=rs, wi_ r a..'ec a:. viing to
.,r:,rb.hersi„s.al=v.s.i;.h lt:...,,x;er, O.orArc{;er 2, manufacturers iratructions.
ne ist s ',jL 1741 rt No orfisrred DC c; istmi, Se: `..e carriloat oifnv calculator at ftytps://4nkenphase,com/rnroduee -cobei iolifty
108and €elPIus, su ports split ice.24OV ,2)NaxiMo'ricoSs.pusraputDC urent.s10.SAOrNisrnfr,aIVotogsirasuge_ardeextcr,dedI,, or,dromIm,'ir...gusr,
,.s„e ,atiurs or4Y, bythe r.,Nits WLm.i.o Crayvar'a Referm oval tares trett rats to aerrrre *pe numbero .mrcronveenets Per brarr?rn,,;.urarea, i0aw'-CS-0002 u,-EN US-2022-a0;3-i7
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION
DATE
" REV
INITIAL
DESIGN
10/03/2022
PROJECT NAME & ADDRESS
(11
�d
ryry
L JJ
l A
LIJ
W
W
J
CL
r®_�n
vJ
LO
O
� LO }
CL
W
DRAWN BY
ESR
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI E
11" X 17"
SHEET NUMBER
P-12
c- A
E np- n. a S e
-3iintlr 4/4' !Ql 0=1951— wl ul
X-IQ-AMl-240-4
X-IQ-AMl-240-4C
smail
Enph-ise "Aibde --oz-"O'�,'� �-e'Phular
Inc!'joe, sclar sh'Ield fraich EnvhFse Bauer,,
and defilect
-xlljl�- supt"C, I's
F0 cr
upl�flal iic ava!iii--, fc, bridge
d. prcoui:-'v
Sim1pie
Cer---ned M,
st-tull inounhn
Supporis bomcrr-ba-k d s-Ie
Lip to four 2 pnie br.a,;,.,chi --'rcui's f"", 240 V,-',r'
�,urabN- NR L re� iv� 141"MA oe 3'R d
ea, 'Y-6-d �,iar!iwl�
ndu",jl�d b'n2w; I
LISTED X-Ls -A W--240-4
Tb �e-wm, aba,u EnDhase offenngSl visit 0,�npbau�g�owcrl
ENPHASE
Enphase IQ Combiner 4/4C
MODEL NUMSER
x, � nc,� T, w
ra�vF'V
�q 5' Fnph�",-- Mvzlde �rlr�
mL'
r ih" "'arod", —n� ,a._.., m Axf
ACCESSOR�ES AND REPLACEMENT PARTS
tlnc:UlljlzS k;-ullllllllllll"-3 �K� I `J i lard 11131r� 051 5 Yw sp�' p4an iiit
T M 4Gbaned c0ujar rill"Id-Fr, wilh, s, yva; Sprin, data a
G a a ed E, - �mr �eVilfar ma'dirn wil','! 5, few' AT&T c&va plan
BR B. 2rc; BR;/"A_ , r1j.
"BR2
�0" 7rp
2P g
�ine ar6dge'-�"a'g"' quo"a, of* pw'
X
4'-
Al N i
X-'K'411A—Cl-'1254, sc'
ELECTRICAL SPECIFICATWNS
max
Pl'.,
"'T A
Io -,it, '?-'ie 'ne 'G lauf sz"istribAt�,i ,
Ul—ris,mnii'voni lmcmWvr,-, 7 CT 2bc -FFi i-
A Dwi of A
MECHANICAL DATA
virxi, ixo' i's
11"RTL-cerTifi, ed NE A
MC
Sll',-�'LAR
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA,
FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10103/2022
PROJECT NAME & ADDRESS
c1r)
F - cy)
w
w
U) —1
>
C)
LL
c/)
w
w
(,c)
z
co
T-
w
cj
C)
o
LO
wN
AWN BY
--- S R
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-1 3
I&
C'.rossRall System
('I-(3SSjRa'j LILI-X
Mechanical Proper -Lies
6000 Sumwiwn
38 k0 MPaj'
M 'Arvcd;zed
01490,0.3785 cm)
D 40550, i, fl 0287 C"r
Dimensions in [mrn] Inches
� Structural walues and spar-, ,ha -'s de'termined w'g accondance vv!h Aluiminufr, Des;qo and ASSCEE 77-16
I � IL270 id Song"rig
U D3 Llaled System for Ffie ai-
MC
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA,
FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10/03/2022
PROJECT NAME & ADDRESS
C\l
'IT
L0
cy-)
>
C)
IL
u�
w
w
F—
_j (0
CL
0
T_ _j
z
(I)
0) T-
2:
w
C'j
0
0
Lr)
TL_
w
N
DRAWN BY
ESR
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-14
We support PV sys ems
We support PV systems
Formerly Everest Solar Systems #!,
Splice Foot XL
Patent Pending
Technical Data
MC.
S -,tAR
T
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST. SUITE 2200
TAMPA,
FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10/03/2022
PROJECT NAME & ADDRESS
(N
NT
Lf)
CY')
(Y)
LLI
LLI _j
>
() LL
<
z U
Uj
Ld
0-
0
Z
cr)
T-
C\1 of
LLI 0
o
� LO
0-
w
N
DRAWN B
ESR
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-1 5
knockouts* Stamped Seamless Construction
* 18 Gauge Galvanized Steel
* Powder Coated Surfaces
* Flashes into the roof deck
* 3 Roof deck
* 5 Centering dimples for entry/exit
fittings or conduit
* 2 Position Ground lug installed
* Mounting Hardware Included
"Fuse hol ;s, and ten-ninat Mticks
added in the field mast be UL list--',' 0,.
recognized and rne-M 600 VDC 30 AMP
110C for fuse holders, 600V 50 AMP
90C for raft mourked terminal Mocks
and 600 V 5 AMP 90C for roses
Xstnbuttto Blocks, use Copper tV4re
Crinductom,
SolaDeidr Model SD 0783
•
Available Medals.
Model SD 6763 -(3' fixed Dire mail)
Model SD 0786 - (6" slotted Dire Rail)
>
Models SID .07 -41 and SD 0766- 1 are labeled and ETL listed UL STD 1741
according to the UL STD 1741 for Izf atavoltalc Combiner e# closures,
Max Rated - 666 DC, 120AMPS
Model SD 7 3- 3' Fixed Dins Rail fastened Using NOrlock System
*Typical System Configuration
4- Din Rail Mounted Fuse Holders 60OVDC 30 AMP
1- Power Distribution Stock 6 O DC 175AM
1-- Bus Barwith UL lug
Model SD 6 - 1 66' Slotted Din Rail fastened using steel studs
**Typical System Configuration
4 Din Rail Mounted Fuse Holders 6 O DC 36 AMP
4- Dirt bail Mounted Terminal Blocks
Bus Bars with UL lug
conduit Or fitting base- is
center dsrn 4ed for f3tfing
locabons,
Model SO 0783-41. Wired ratty Model So 078 9, wired 3 ,
Dire Rant rnourited fuse rudders, Din Rail mounted fuse h, ers.
bus bar and power dpis rMution terminal blocks and b to bars.
block,
ROTC Enterprises, Inc . 2219 Heintst a l Road - Eau Cliare, W1 54 703
Far rodu t information call 1(855) 857-7782
MODERN CONCEPTS SOLAR
201 N. FRANKLIN ST, SUITE 2200
TAMPA, FL 33602
REVISIONS
DESCRIPTION
DATE
REV
INITIAL DESIGN
10/03/2022
PROJECT NAME & ADDRESS
IT
L0
>i3
U-
-j
IIIW
(0
0 r
z
_0-
co
N Q�
O
tf3
LLi
N
DRAWN BY
SR
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17",
SHEET NUMBER
PV-16