HomeMy WebLinkAbout23-6590•
I S
5335 Eighth Street
Zephyrhills, FL 33542
Phone: (813) 780-0020
Fax: (813) 780-0021
�
FIRE-006590-2023
Issue Date:
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
"Warning to owner: Your failure to record a notice of commencement may result in your paying twice M"
' 'Iimprovements to your property. If you intend to obtain financing, consult with your lender or an attorn
efff, 't, � , I I-
Uompiete riarls, Wf-drf,
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
X /
CONTRACTOR SIGNATURE PE IT OFFICE
�IERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PTOTECT CARD FROM WEATHER
WATER SUPPLY
FLOW TEST
FIRE PUMP
DATE OF TEST:
RATED CAPACITY:
TIME OF TEST:
RATED PRESSURE:
STATIC PRESSURE:
PUMP TYPE:
RESIDUAL PRESSURE:
WELL PUMP
GALLONS FLOWING:
GPM AVA10BLE:
TESTED BY
PSI AVAILABLE:
ABBREVIATIONS
=
CENTERLINE
=
ELEVATION
TOS
= TOP OF STEEL
G =
GROOVED PIPE END
T =
THREADED PIPE END
F =
FLANGED PIPE END
C—C
= CENTER TO CENT
FIRE SPRINKLERL-1-1
SCALE: 1 /4" = V-0"
DESIGN CRITERIA
SYSTEM NO.
HAZARD
SPACING
K FACTOR
INSIDE HOSE
OUTSIDE HOSE
RACK GPM
HYDRAULICALLY DESIGNED SYSTEM
LOCATION
NO. OF SPRINKLERS
DENSITY
DESIGN AREA
GPM DISCHARGE
RESIDUAL PSI AT
NOTE: HATCHED AREA NOT IN SCOPE
TYPES OF SPRINKLERS
SYMBOLS QUAN. ORIF. TEMP. MAKE & MODEL TYPE SIN# FINISH
O 18 1/2" 155' RELIABLE FlFR56 PEN RA1414 WHITE
18
TOTAL HEADS THIS SHEET
NO. DATE
Esc. 0 7/5/23
SEMI—REC
REVISION DESCRIPTION
RELEASE FOR PERMITTING
1) FIRE SPRINKLER SYSTEM EXISTING, MODIFY FOR NEW WALL
& CEILINGS
2) -- DENOTES EXISTING FIRE SPRINKLER PIPING TO REMAIN
3) DENOTES NEW FIRE SPRINKLER PIPING (1" 'SCH 40' PIPE)
4) DENOTES HANGER LOCATION.
5) 0 DENOTES EXISTING 1" OUTLETS TO FEED NEW SPRINKLERS,
6) DENOTES EXISTING SPRINKLER HEAD TO REMAIN.
7) DENOTES NEW SPRINKLER HEAD LOCATION.
S) ALL WORK SHALL BE IN ACCORDANCE WITH N.F.P. . # 13
LOCAL CODES
9) ALL MATERIALS TO BE U.L. LISTED & OR F.M. APPROVED FOR FIRE
PROTECTION
10) TOTAL SQUARE FOOTAGE OF PROJECT: 2,619 SQ.FT.
11) AREA DESIGNED: LIGHT HAZARD MEDICAL OFFICE.
12) ANY/ALL EXISTING ATTIC UPRIGHT HEADS WILL REMAIN.
SCOPE OF WO
RELOCATE FIRE SPRINKLER HEADS PER TENANT IMPROVEMENTS.
HATCHED AREA NOT IN SCOPE.
2021 FLORIDA STATUTES/ CHAPTER 633/ FIRE PREVENTION AND CONTROL
PERSONS CERTIFIED AS A CONTRACTOR I, CONTRACTOR N, OR CONTRACTOR IV UNDER THIS
CHAPTER MAY DESIGN NEW FIRE PROTECTION SYSTEMS OF 49 OR FEWER SPRINKLERS, AND
MAY DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
CONSISTS OF THE RELOCATION, ADDITION, OR DELETION OF NOT MORE THAN 249 SPRINKLERS,
NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM.
CONTRACTOR -DEVELOPED PLANS MAY NOT BE REQUIRED BY ANY LOCAL PERMITTING
AUTHORITY TO BE SEALED BY A REGISTERED PROFESSIONAL ENGINEER.
1
j Ili
3
�
l
4
I
-t-
** ARMOVERS GREATER THAN
24" IN LENGTH SHALL BE ry
SUPPORTED BY A HANGER.
SCHEDULE
2. EXISTING BRANCHLINE.
3. 1" ARMOVER.*
4. 1" DROP.
5. NEW FIRE SPRINKLER HEAD
2
3//MY8" SIDEOUTLET SCREW
(SAMSCREW/HANGERMATE)
WOOD TRUSS
IN AJ or JOIST
111
3/8' ALL THREAD ROD
HANGER RING
� IPE
SIDEOUTLET SCRWE HANGER DETAIL
N.T.S.
ALL WORKS t
NFFA CODES AND
REVIEW DATE•_" Z- /
CITY OF ZEPHYRHILLS
FIRE AND LIFE SAFETY
Your Source for Fire Protection....
3781 NE. 11thAvenue. Design* Installation* Inspection
Pompano Beach, FI.33064
PLY WITH
ND.ARDS
3
Availability: Americas
lmellanou � RASCdFLEXS Sprinkler Connections
cULbs Lgtod, FM Ap"cved
Product Description
RASCOFLEX'Sprmk'er Corinections are infended to mreert
a branch the to a spri klar using a flexible stainless steel fcrse
l`S assembly. RCOFLE)C Sprinkler Cori e, t ns are suitable for
tse m suspended and hard ceirmg appi cabons such as T-Ba
ceiling grids, wood, metal stud, or hat furring channel hard Iid
ceilings. Every package contains one (1) fully assembled stainless
steel flexible sprinkler system complete with hose, branch
line connection, and sprinkler connection, as well as the pre -
assembled bracket assembly to attach to the ceiling.
RASCOFLEV Sprinkler Connections are designed for use in
hydraulically calculated wet, preaclion, or dry sprinkler systems
per NFPA 13, 13R, 13D, and FM Global Loss Prevention Data
Sheets.
Technical Data
Maximum Working Pressure
FM: 200 psi (13.8 bar)
UL: 175 psi (12.1 bar)
Ma hn= VAwkbg TeroperaWre
3193'f (849`C) i
Cortrtaefamts
k.nch Line
1' NPT
etrReducer
12"or 3i4"NPF
Minimum Allowable
Bending Radius
Uu 3- (76 msrt)
FM: 7' (178 mm)
Maxmum N mber of Bends
See Friction Ill Chen
Masimum
K-FacEor
3i2` Otl'eS
5.6 (80 metric)
3,:4" W['w
14.0 E200 mew}
Maintenance
RASCOFLEV Sprinkler Connect ons should be inspected and
the sprinkler system maintained in accordance with NFPA 25, as
well as the requirements of any Authorities Havirg Junsd'.ciior.
Patents
RASCOFUEXC Sprinkler Connections may be ca wed by
one or more of the fo!lo++irg US Patent Nos. 10,173.088 and
10,328,296.
Listings and Approvals
FM Approved Class No, 1637 (FM)
UL Listed and UL Certified for Canada to ANSI NL 2443 (cULus)
Bulletin 213 May 2021
Ordering Information
sP—lry:
Mo&" Name
• Model lRFB
Norrfmal Hose Lereh
• 24` 1
610 m. )
• 3f' (7gG mml
• 40' (1015
- 48' (1220 nsn)
• 60' 1525 mm)
• 72" (1830 move)
Reducer OuBet: 12' NPT or 3/4" NPT
Reducer Type
Standard:
• 6-1/8" (155 mm) straight
Optional:
• 4-5/16" (110 mm) straight
• 5-5/16" (135 mm) straight
• 11-3/4' (300 mm) straight
• 5-5/8" (143 mm) elbow
• 7-3/8' (187 mm) elbow
Bracket Assembly Length
• 24' (610 mm) standard
- 48' (1220 mm) optional
Accesaores
- See Table F
` ..",r,vrinlaarmrn
HANGER LOCATION
DETAIL
13*
C
3'-0" MAX.
12'-0" MAX.
3" MIN.
4'-0" MAX.
12'-0" MAX.
3" MIN.
5'-0" MAX.
15'-0" MAX.
3" MIN.
B*
IC
SPRINKLER HEAD
STEEL PIPE
HANGER RING
* MAXIMUM HANGER SPACING FOR THREADED LIGHTWALL
STEEL PIPE IS 12'—O" FOR ALL PIPE SIZES
f 01[93 �ri�
FIRE SPRINKLER PIPING PLAN
DAVITA DIALYSIS
36819 Eiland Blvd, Unit 2
Zephyrhills, FL 33542
DRAWN BY: Remmy Rickel DATE: July 5th, 2023
SPRKS. ON JOB: 18 SCALE: 1/4" = 1'-0"
APPROVALS: Local Authorities
DRAWING NAME: S23-117 Davita Dialysis
#41126500012001 CONTRACT NO. S23-117 SHEET N0. FS-1 OF 1
FLOW TEST
DATE OF TEST:
TIME OF TEST:
STATIC PRESSURE:
RESIDUAL PRESSURE:
GALLONS FLOWING:
TESTED BY:
WATER SUPPLY
FIRE PUMP
RATED CAPACITY:
RATED PRESSURE:
PUMP TYPE:
WELL PUMP
GPM AVAILABLE:
PSI AVAILABLE:
ABBREVIATIONS
€ =
CENTERLINE
=
ELEVATION
TOS
= TOP OF STEEL
G =
GROOVED PIPE END
T =
THREADED PIPE END
F =
FLANGED PIPE END
C—C
= CENTER TO CENT
FIRE !.: PRI INK"'FLERPI A ft I
SCALE: 1 /4" = 1 i-0"
DESIGN CRITERIA
SYSTEM NO.
HAZARD
SPACING
K FACTOR
INSIDE HOSE
OUTSIDE HOSE
RACK GPM
HYDRAULICALLY DESIGNED SYSTEM
LOCATION
NO. OF SPRINKLERS
DENSITY
DESIGN AREA
GPM DISCHARGE
RESIDUAL PSI AT
SYMBC
1
MOTE: HATCHED AREA NOT IN SCOPE
TYPES OF SPRINKLERS
15 1 1/2" 1 155• 1 TYCO TY—FRB I PEN I TY323 I WHITE
15 1 � TOTAL HEADS THIS SHEET
i
F
I/
NO. DATE REVISION DESCRIPTION BY
0 7/5/23 RELEASE FOR PERMITTING RR
SEMI—REC 1 7/17/23 REVISION PER SURVEY RR
GENERAL NOTES:
1) FIRE SPRINKLER SYSTEM EXISTING, MODIFY FOR NEW WALLS
& CEILINGS
DENOTESEXISTING FIRE SPRINKLER
DENOTES SPRINKLER'SCH 40' PIPE
) DENOTES . LOCATION.
• ..R
DENOTES # i FEED NEI&I
DENOTES At TO
LOCAL711 DENOTES NEW SPRINKLER HEAD LOCATION.
8) ALL WORK SHALL BE IN ACCORDANCE WITH N.F.P.A. # 13 &
ii
, ALL MATERIALSTO OR APPROVED FOR FIRE
PROTECTION
TOTAL10) i. t RFOOTAGEOF PROJECT: .; i
DESIGNED: HAZARD MEDICAL OFFICE.
UPRIGHT1-4) ANY/ALL EXISTING ATTIC HEADS
SCOPE WORK:
RELOCATESPRINKLER HEADSPER .. IMPROVEMENTS.
tN OT I N SCO
2021 FLORIDA STATUTES/ CHAPTER 6331 FIRE PREVENTION AND CONTROL
PERSONS CERTIFIED AS A CONTRACTOR I, CONTRACTOR II, OR CONTRACTOR IV UNDER THIS
CHAPTER MAY DESIGN NEW FIRE PROTECTION SYSTEMS OF 49 OR FEWER SPRINKLERS, AND
MAY DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
CONSISTS OF THE RELOCATION, ADDITION, OR DELETION OF NOT MORE THAN 249 SPRINKLERS,
NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM.
CONTRACTOR -DEVELOPED PLANS MAY NOT BE REQUIRED BY ANY LOCAL PERMITTING
AUTHORITY TO BE SEALED BY A REGISTERED PROFESSIONAL ENGINEER.
SCHEDULE
2. EXISTING BRANCHLINE.
3
3. 1" ARMOVER.*
4. 1" DROP.
5. NEW FIRE SPRINKLER HEAD
4 OR�
2
.$I I
'LlJ
t
** ARMOVERS GREATER THAN
24" IN LENGTH SHALL BE
SUPPORTED BY A HANGER.
' I j
ef8" SIDEOUTLET SCREW " ''
AMMY SCREW/HANGERMATE) t 1{
F 1 11I
F
E WOOD TRUSS
i or JOIST
3/8" ALL THREAD ROD
HANGER RING -
w IPE -
SIDEOUTLET SCRWE HANGER DETAIL
N.T.S.
Your Source for Fire Protection....
781 NE. 11th Avenue. Design* Installation* Inspection
ompano Beach, Fl. 33064
hone: 954-419-9377
AvayaDitfl,•: Amzrras
Product Description
sFV'17_ EX- `Pr-4t C4moctivs a a--ridsd earsnast
a bra,-h line n a spoirX_r using a fiez..:e'' -cress _txl tam
—,b,y PASCCFFEX"'So IkIE C. no- are -s mab!a tar
use il, s4spar=.oed and nand cei.:r?g ap'JliLi'�:T3 such as T-9-1
—5i"9 grids. wood. �tai stud, or hat 6s—N c.liaruiet h.,J Sid
�(.rxys. Every p:�kage captains «�a (1) ;�:h a: ,e:. b!r�3 stein,.
less sleet 11-ihla sprinkler system complete with no", branch
line connectior. and sprinkler cennection. as x0 as the pre -as-
sembled bracket assembly to aaach to the c N,g,
RA.SCOFLEX" Sprinkler Connections are designed for use in
hydraulically calculated wet, preaclion, or dry sprinkler sys-
tems per NFPA 13, 1319, 131). and FM Giabai Loss Prevention
Data SheotS.
Technical Data ErRIMM
Maximum Working Pressure W 200 us,
(13.8 bar)
UL: 175 Psi (12.1 bar) I
Maximum Working Temperature
3.X7'F (149"C) �
Canrrecxbns
Inlat@ranch Lino
1"NPT
r'ALiseweduecr 1
r sw h,s
M6•h— Allowable
Bending RaCros-
a 3 (76 nan) !
Mazhnwn Number of sends
"leeF, cue Loss Cra'q i
M336MUM VT ih 13i 1el 1
K-FaMr X4-Outlet
5-6 (so nwoc)
i 14.91_—,-1110 E
6.1flaNn 213 June 2022
RASCOFLEX" Model RFS
Sprinkler Connections
cUlus L_ sd, FM;,pproved
Ordering Information
specily:
kiwo Nar
NsodJ 7 R-G
v— Hose Lr"e,-h
24` (610 —m
31- (790 ram)
40
• 48"(,22..0 own)
• W 1525m,q
• 72- (?8 0 nan)
Maintenance Reducer O fiat: 1;2- NPT a 3,4' NPT
RASCOFLEX Spnr*Wf Conn—J ✓ s snow d be irspecied and
the sW'nider s3 lem m2irta nee in acolyd— mlh NFPA 25, Red ter Type
s %e.Y as the requsct eats of any Aulbor ties Havi •g Jurmcso- Standard
Iron. 7' (178 ram) straight
Optional:
Patents • 11-3nl' (300 ram) straight
• 7-14'(icl,nvn) elbow
E( RASCOFL' Sprinkler Conneeuor,s may on covered by • B-5(76` (211 ram) elbow
one or more of the fo l—ng US Patent Nos. 10. 173.098 and
10,328.2%, Bracket Assembly Length
• 24" (610 ram) standard
• 48" (1220 ram) optional
Listings and Approvals
FM Approved Class No. le37 (FM) Accessones
• Sc-, Tac e F
UL Listed and UL Cegi6ed for Canada to Aria `JL 2443 (cULus)
HANGER LOCATION DETAIL
B*
C
3'-0" MAX.
12'-0" MAX.
3" MIN.
4'-0" MAX.
12'-0" MAX.
3" MIN.
5'-0" MAX.
15'-0" MAX.
3" MIN.
I.-C'
SPRINKLER HEAD
STEEL PIPE
HANGER RING
* MAXIMUM HANGER SPACING FOR THREADED LIGHTWALL
STEEL PIPE IS 12'-0" FOR ALL PIPE SIZES
FIRE SPRINKLER PIPING PLAN
DAVITA DIALYSIS
36819 Eiland Blvd, Unit 2
Zephyrhills, FL 33542
DRAWN BY: Remm Rickel DATE: July 5th, 2023
SPRKS. ON JO.: 15 SCALE: 1/4" = 1'-0"
APPROVALS: Local Authorities
DRAWING NAME: S23-117 Davita Dialysis
CONTRACT NO. S23-117 I SHEET N0. FS-1 OF 1