HomeMy WebLinkAbout23-6817Ir -1 Mma"VTORANA-M
Address: 1380 North University Dr
PLANTATION, FL 33322
Phone: (954) 953-1119
INSTALLATION FIRE ALARM -
System Acceptance Inspection Alarm
Fire Permit Fee 50-
5335 Eighth Street
Zephyrhills, FL 33542 FIRE-006817-20 3
Phone: (813) 780-0020 Issue Date: 09/12/2023
- I L2J77
Building Valuation: $2,670.00
Electrical Valuation:
Mechanical Valuation:
Plumbing Valuation:
Total Valuation: $2,670.00
Total Fees: $150.00
Amount Paid: $150.00
Date Paid: 9/12/2023 1:40:45PM
Contractor: COMMERCIAL FIRE &
COMMUNICATION
$50.00 Fire Alarm System Plan Review
$50.00
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
I I ! I i 1 111 1 F I I I , I 1 11 11 1 1 1 1 11
W=-F.t 0 Rol* Z V 0 4
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
IR
50
W 010
PEPT OFFICEU
mr-111""01-110A
SEQUENCE OF OPERATION
SYSTEM OUTPUTS CONTROL UNIT NOTIFlCATION
ANNUNCIATION
o�
ALL INITIATION INDIVIDUALLY
ANNUNCIATED AND WILL TRANSMIT
AS SINGLE POINT TO CENTRAL STATION
FORMATTED AS 'CONTACT ID'. c
o c o
c ci Q Fo 2
hG�'
o is o
m,Cj
Q�F,,�
c
qj
SYSTEM INPUTS
A
I B
I C
D
E
I F
I G
H
1
MANUAL PULL STATION
•
•
•
2
SMOKE DETECTOR
•
•
•
3
SPRINKLER WATERFLOW
•
•
•
4
ISPRINKLER VALVE TAMPER
•
•
5
ISYSTEM TROUBLE
I
10
1
•
Ci— i
75cd
WP DI —I MI-1 MI-2 MI_j
B S P F AIM AIM
(EOL NAC CKT. #1) FA
WF VS
BA ® O
0 �
DO FACU
SS FA1.0
_
120Vac/20Amp Dedicated ckt.
W/Surge Suppression
FA - SPRINKLER SUPERVISORY SYSTEM - RISER DIAGRAM
SCALE: N.T. S
FA - SPRINKLER SUPERVISORY SYSTEM - KEY PLAN
SCALE: NTS
GENERAL FIRE ALARM SYSTEM NOTES
1. WHERE CEILING HEIGHTS ALLOW, WALL MOUNTED AUDIBLE APPLIANCES SHALL HAVE THEIR TOPS
AT HEIGHTS OF NOT LESS THAN 90 in. AFF, AND BELOW THE FINISHED CEILING OF NOT LESS
THAN 6 in.
2. WALL MOUNTED VISUAL OR AUDIBLE/VISUAL APPLIANCES SHALL BE MOUNTED SUCH
THAT THE ENTIRE LENS IS NOT LESS THAN 80 in. A.F.F. BUT NOT MORE THAN 96 in. A.F.F.
WHERE LOW CEILING HEIGHTS DO NOT PERMIT MOUNTING AT A MINIMUM OF 80 in. A.F.F.
THE VISUAL OR AUDIBLE/VISUAL APPLIANCE SHALL BE MOUNTED WITHIN 6 in. OF CEILING.
CEILING MOUNTED VISUAL OR AUDIBLE/VISUAL APPLIANCES SHALL BE PERMITTED AS ALLOWED BY
NFPA72-18.5.4, SPECIFICALLY LISTED FOR APPLICATION AND SPACED IN ACCORDANCE WITH 18.5.4.3.
3. DO NOT MOUNT SMOKE AND/OR HEAT DETECTORS CLOSER THAN 3' TO ANY SUPPLY REGISTER
OF THE A/C SYSTEM.
4. WHEN CEILING MOUNTING SMOKE AND/OR HEAT DETECTORS SHALL BE MOUNTED NO CLOSER
THAN 4" TO A SIDE WALL, OR WHEN WALL MOUNTED NO HIGHER THAN 4" OR LOWER THAN
12" FROM THE TOP OF THE DETECTOR TO THE CEILING.
5. CONTROL RELAYS MUST BE MOUNTED WITHIN 3' OF THE CONTROLLED CIRCUIT OR APPLIANCE.
6. IF FIRE ALARM CONTROL RELAYS ARE TO CONTROL THE EQUIPMENT OF ANOTHER TRADE, THE
OTHER MUST TERMINATE CIRCUITS TO CONTROL RELAY CONTACTS, OR LEADS !F PROVIDED.
7. UNDERGROUND/OVERHEAD WIRING ENTERING OR LEAVING A BUILDING SHALL BE INSTALLED AND
PROTECTED IN ACCORDANCE WITH NFPA72-12.2.4.2/A.12.2.4.2 AND NFPA70-;ARTICLE 280.
WHEN REQUIRED, 'TVSS' SHALL BE INSTALLED IN ACCORDANCE WITH NFPA70-ARTICLE 285.
8. CALCULATIONS ARE BASED ON RACEWAY/WIRE ROUTING AS SHOWN ON PLANS. ANY DEVIATION FROM
THIS DESIGN MAY RESULT IN SYSTEM NOT MEETING PROPER PERFORMANCE STANDARDS. IF
DEVIATION MUST BE MADE IT IS THE INSTALLERS RESPONSIBILITY TO COMMUNICATE TO THE
OFFICE ANY INTENDED OR REQUIRED CHANGES.
9. WHERE HEAT DETECTORS ARE INSTALLED TO SHUT DOWN ELEVATOR POWER PRIOR TO SPRINKLER
OPERATION THE DETECTOR SHALL BE INSTALLED WITHIN 2' OF EACH SPRINKLER HEAD, AND
SHALL BE RATED AT 135' FIXED TEMPERATURE.
10. ONLY ASSOCIATED DEVICE WIRING IS REQUIRED ENTERING INTO BACK -BOX. ALL OTHER WIRING
MAY CONTINUE PAST BACK -BOX.
F M1-1 C
vo 2AD1-1M1-2
o SPA M 1-3
,B AIM PAIN/L B WF
-A WP
75cd EOL NAC
C KT.1
SYSTEM KEY NOTES
O - CONNECT FACU TO 120VAC/20AMP
DEDICATED CIRCUIT WITH SURGE SUPPRESSION.
- CELLULAR COMMUNICATOR INTEGRATED WITHIN
THE FIRE ALARM CONTROL UNIT.
CONNECT TO CELLULAR NETWORK FOR MONITORING.
O - VERIFY EXACT LOCATION AT FIELD.
SYSTEII� NOTES
O UL 1638 WEATHERPROOF APPLIANCE CANDELA RATING VARIES
DUE TO ATMOSPHERIC CONDITIONS. (PLEASE SEE SPEC'S.)
O DEVICE / APPLIANCE NUMBERING SCHEME AS FOLLOWS:
'D' = (DETECTOR)SLC LOOP NUMBER
'M' = (MODULE)SLC LOOP NUMBER
'C' = VISIBLE or AUDIBLE -VISIBLE CKT. NUMBER
SCOPE OF TYORK.-
PROVIDE and INSTALL: FIRE SPRINKLER SUPERVISORY SYSTEM.
AREA of WORK
SQUARE FOOTAGE I 28005
I SPINKLER RISER ROOM
A
FDC OUTSIDE
(Fire Department Connection)
FA - SPRINKLER SUPERVISORY SYSTEM - FLOOR PLAN
SCALE : 3 / 16"=1' -0"
FIRE ALARM SYSTEM SYMBOL LEGEND
SYMBOL
DESCRIPTION
MOUNTING
ELEVATION
FACU
FIRE ALARM CONTROL UNIT
OWN CABINET
66" AFF TO TOP
DOC
DOCUMENT BOX
OWN CABINET
VERIFY IN FIELD
❑F
MANUAL PULL STATION
4" SQ. x 2-1/8"
w/1-GANG P-RING
48" AFF ( TOP )
AIM
ADDRESSABLE MONITOR MODULE
4" SQ. x 1-1/2" MINIMUM
or IN BOX BEHIND DEVICE
S
CP
SMOKE DETECTOR (PHOTOELECTRIC)
4" SQ. x 2-1/8"
SQ. TO RD. P/R
CEILING
SEE NOTE 3&4
N<WP
HORN/STROBE - (WEATHERPROOF)
MANUFACTURE SUPPLIED
BACK BOX
VERIFY IN FIELD
-AW-
END OF LINE SUPERVISORY DEVICE
ON LAST DEVICE
OF CIRCUIT
SS
SURGE SUPPRESSION
GROUND
FIRE ALARM SYSTEM WIRE LEGEND
SYMBOL
I CIRCUIT TYPE
DESCRIPTION —j
A
IS11GNALING LINE CIRCUIT
2 - #16 AWG FPLR
B
INOTIFICATION APPLIANCE CIRCUIT
2 - #14 AWG FPLR
* ALL JACKETED 'FREE -WIRE' CABLE TO BE RATED FOR INSTALLING ENVIRONMENT.
* WHERE REQUIRED: CABLE/WIRING TO BE WITHIN MINIMUM .75" CONDUIT SYSTEM.
FIRE ALARM INSTALL.9TION SHALL COMPLY JPITK.•
- FL. FIRE PREVENTION CODE (7th EDITION-2020)
- NFPA 70 (2017 EDITION)
- NFPA 72 (2016 EDITION)
- FBC (7th EDITION-2020)
DEVICE COUNT
DEVICE TYPE
QUANTITY
FIRE ALARM CONTROL UNIT
01
DOCUMENT
01
PULL STATIONS
01
MONITOR MODULE
02
SMOKE DETECTOR
01
WP HORN STROBE
01
TOTAL
07
—GROUNDING CONDUCTOR SHALL BE MIN. #14 AWG.
—GROUNDING CONDUCTOR SHALL BE CONNECTED
TO BUILDING or STRUCTU(RE) GROUNDING ELECTRODE
or GROUNDING ELECTRODE CONDUCTOR
AS DESCRIBED IN NFPA70.
ALL
RK SHALL COMPLY WITH
NFFAO CODES AND STANDARDS
-- "r-"a3N{W`dX3),1.3�dS 3�{'1 aN�13Yi13
SlliHa 31tlfl rV 3o3a
LANNCO, INC
ENGINEERING CONSULTING
CERTIFICATE OF AUTHORIZATION
# 26222
P.O. BOX 41481
ST.PETERSBURG
FLORIDA 33743
(727) 345-8556
PROFESSIONAL SEAL
FRANK BONGH1
FLORIDA P.E. 54702
FIRE ALARM
CD
N
❑
�.
LO
m
❑
CO
U
�
M
~
_I
U_
_
O
(0
�
�
J
>_
ry
0-
�
W
�
N
�
N
00
LO
a"
N
CD
LO
N
E
0
E
L
0
C
0
No. Revision/Issue Date
r • AL _&W Lam_ ' •
v� v
Commercial FIRE
& Communications, Inc.
P.O. BOX 1350
LARGO, FL. 33773 EF20001347
(727) 530-4521PH.
(727) 531-0596,FAX
Engineering@cfcsystems.com
Sheet Title:
SPRINKLER
SUPERVISORY
SYSTEM
Drawn bv: G 1
Checked by
�j
Project Number: Shale #:
OIX1652 FA01
,
08-11-2023
Scale: 01`of01
3/16" = Y-O"