Permit Type: Fire
Class of Work: Fire Alarm
Building Valuation: $4,670.00
Electrical Valuation:
Mechanical Valuation:
40311 Free Fall Avenue
Contractor: FORT KNOX FIRE & COMM
INC
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the inal inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
j
'9 oil A 1 0 0
-111W -m- -A NMI
111*11,11011PI I 1!1111� 111�� 1 1111 1 1
23131���
i ';XA 'A76y", O'c"Iel-Al
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
SIG N PEIMIT OFFICE[)
PERIVIirE';/, S IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
77 7—r I Date Received Phone Contact for Permitting
a a a a a a a a 1 LX_A_X_2_R_JL
Owner's Name HEYL INVESTMENTS 11 LLC Owner Phone Number
Owner's Address I PO BOX 500, AKRON, A 51001 -_0500 Owner Phone Number
Fee Simple Ti6bolder Name Owner Phone Number
Fee Simple Titleholder Address
JOB ADDRESS 140311 FREE FALL AVENUE LOT#
J
SUBDIVISION
PARCEL ID# 18-26-22-0010-02100-0000
(OBTAINED FROM PROPERTY TAX NOTICE)
WORK PROPOSED
NEW CONSTR
ADD/ALT SIGN DEMOLISH
INSTALL 8
REPAIR
PROPOSED USE
SFR
COMM OTHER F_
TYPE OF CONSTRUCTION
BLOCK
FRAME STEEL = E========
DESCRIPTION OF WORK
install a new Fire Alarm
Monitoring System
BUILDING SIZE
SQFOOTAGf1100
HEIGHT
C-EAE -L _'E�
X-Ir I
=BUILDING
$ V
A OF TOTAL CONSTRUCTION
=ELECTRICAL
1$ 4670.00 AMP
SERVICE PROGRESS ENERGY W. R. E. C.
=PLUMBING
$
,
=MECHANICAL
$ VALUATION OF MECHANICAL INSTALLATION
4
=GAS
ROOFING =
SPECIALTY = OTHER
FINISHED FLOOR ELEVATIONS
E==
FLOOD ZONE AREA =YES NO
BUILDER COMPANY
SIGNATURE REGISTERED YIN FEE CURREN L)� / N
Address I License#
ELECTRICIAN COMPANY =
SIGNATURE REGISTERED L_y L N J FEE CURREN Y/N
Address License#
PLUMBER COMPANY
SIGNATURE REGISTERED Y/N FEE CURREN
Address License#
MECHANICAL COMPANY
SIGNATURE REGISTERED L_Z
LN j FEE CURREN I Y/N
Address License#
OTHER COMPANY Fort Knox Fire & Comm., Inc.
17
SIGNATURE REGISTERED Y/N FEE CURREN LILN J
Address , 5 North rk Avenue License# I EF20000876
RESIDENTIAL Attach (2) Plot Plans, (2) sets of Building Plans; (1) set of Energy Forms, R-O-W Permit for new construction,
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans w/ Silt Fence installed,
Sanitary Facilities & 1 clumpster ' Site Work Permit for subdivisions/large projects
COMMERCIAL Attach (2) complete sets of Building Plans plus a Life Safety Page; (1) set of Energy Forms. R-O-W Permit for new construction.
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans w/ Silt Fence installed,
Sanitary Facilities & 1 clumpster. Site Work Permit for all new projects. All commercial requirements must meet compliance
SIGN PERMIT Attach (2) sets of Engineered Plans.
—PROPERTY SURVEY required for all NEW construction.
Directions:
Fill out application completely.
Owner & Contractor sign back of application, notarized
If over $2500, a Notice of Commencement is required. (A/C upgrades over $7500)
** Agent (for the contractor) or Power of Attorney (for the owner) would be someone with notarized letter from owner authorizing same
OVER THE COUNTER PERMITTING (copy of contract required)
Reroofs if shingles Sewers Service Upgrades A/C Fences (Plot/Survey/Footage)
Driveways -Not over Counter if on public roadways..needs ROW
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to "deed" restrictions" which may be more restrictive
than County regulations. The undersigned assumes responsibility for compliance with any applicable deed restrictions,
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or contractors to undertake work, they
may be required to be licensed in accordance with state and local regulations. If the contractor is not licensed as required by law, both the owner and
contractor may be cited for a misdemeanor violation under state law. If the owner or intended contractor are uncertain as to what licensing requirements
may apply for the intended work, they are advised to contact the Pasco County Building Inspection Division —Licensing Section at 727-847- 8009.
Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign portions of the "contractor Block" of this
application for which they will be responsible. If you, as the owner sign as the contractor, that may be an indication that he is not properly licensed and is
not entitled to permitting privileges in Pasco County.
TRANSPORTATION IMPACTIUTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings, change of use in existing buildings, or
expansion of existing buildings, as specified in Pasco County Ordinance number 89-07 and 90-07, as amended. The undersigned also understands, that
such fees, as may be due, will be identified at the time of permitting. It is further understood that Transportation Impact Fees and Resource Recovery
Fees must be paid prior to receiving a "certificate of occupancy" or final power release. If the project does not involve a certificate of occupancy or final
power release, the fees must be paid prior to permit issuance. Furthermore, if Pasco County Water/Sewer Impact fees are due, they must be paid prior
to permit issuance in accordance with applicable Pasco County ordinances.
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2,500.00 or more, I certify that 1, the applicant,
have been provided with a copy of the "Florida Construction Lien Law —Homeowners Protection Guide" prepared by the Florida Department of
Agriculture and Consumer Affairs. If the applicant is someone other than the "owner', I certify that I have obtained a copy of the above described
document and promise in good faith to deliver it to the "owner' prior to commencement.
CONTRACTOR'S/OWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and that all work will be done in compliance with
all applicable laws regulating construction, zoning and land development. Application is hereby made to obtain a permit to do work and installation as
indicated. I certify that no work or installation has commenced prior to issuance of a permit and that all work will be performed to meet standards of all
laws regulating construction, County and City codes, zoning regulations, and land development regulations in the jurisdiction. I also certify that I
understand that the regulations of other government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance. Such agencies include but are not limited to:
Department of Environmental Protection -Cypress Bayheads, Wetland Areas and Environmentally Sensitive
Lands, Water/Wastewater Treatment.
Southwest Florida Water Management District -Wells, Cypress Bayheads, Welland Areas, Altering
Watercourses,
Army Corps of Engineers -Seawalls, Docks, Navigable Waterways.
Department of Health & Rehabilitative Services/Environmental Health Unit -Wells, Wastewater Treatment,
Septic Tanks.
US Environmental Protection Agency -Asbestos abatement.
Federal Aviation Authority -Runways,
I understand that the following restrictions apply to the use of fill:
Use of fill is not allowed in Flood Zone "V" unless expressly permitted.
If the fill material is to be used in Flood Zone "A", it is understood that a drainage plan addressing a
"compensating volume" will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida.
If the fill material is to be used in Flood Zone "A" in connection with a permitted building using stem wall
construction, I certify that fill will be used only to fill the area within the stem wall.
If fill material is to be used in any area, I certify that use of such fill will not adversely affect adjacent
properties. If use of fill is found to adversely affect adjacent properties, the owner may be cited for violating
the conditions of the building permit issued under the attached permit application, for lots less than one (1)
acre which are elevated by fill, an engineered drainage plan is required,
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in this affidavit prior to
commencing construction. I understand that a separate permit may be required for electrical won(, plumbing, signs, wells, pools, air conditioning, gas, or
other installations not specifically included in the application. A permit issued shall be construed to be a license to proceed with the work and not as
authority to violate, cancel, alter, or set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from
thereafter requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid unless the work
authorized by such permit is commenced within six months of permit issuance, or if work authorized by the permit is suspended or abandoned for a
period of six (6) months after the time the work is commenced. An extension may be requested, in writing, from the Building Official for a period not to
exceed ninety (90) days and will demonstrate justifiable cause for the extension. If work ceases for ninety (90) consecutive days, the job is considered
abandoned.
FLORIDA JURAT (F.S. 117,03)
OWNER OR AGENT
Subscribed and swom to (or affirmed) before me this
b
Who is/are personally known to me or has/have produced
as identification.
Notary Public
Commission No.
CONTRACTOF
Subscribed and
this
Who is/are person811y known to me or has/have produced
as identification.
Notary ?ublic
Commission No.
Name of Notary typed, printed or stamped Name of Notary typed, printed or stamped
wgsgrjwagmffgwmwm�2»2 ».2
III A IIzlyNIMS
EF20000876
5005 N. Clark Avenue Phone (813)653-1605
Tampa, FL 33614 Fax (813)653-1710
www.fortknoxfire.com
F-M" "I'll,
flgm�4:»? «
«
tl���t Yx r' �1 h� �3C r� 4+6 {
� S S `k� `�'. � ��' �`• � e4 J � b ',Y 2} �. i. ':. E }�'�f` �4� . `t y� �Fi �45
GF505
GAMEWELL 5 ZONE FIRE ALARM PANEL
-7
GAMEWELL PULL STATION
2W-13
PHOTOELECTRIC 2 WIRE SMOKE DETECTOR
P211
WP HORN STROBE
SSU00691A
SPACE AGE DOCUMENTBOX
SLE-MAXVI-
NAPCO CELL 0
FIRE
DTK-12 HW
DITEK 1220 VOLT SURGE
Initiating device circuits (IDCs) for Flex Series panels are
programmable and operate in Class B (Style B). Each
panel is compatible with conventional input devices such
as two -wire smoke detectors, four -wire smoke detectors,
pull stations, water flow devices, tamper switches and
other normally -open contact devices. This includes System
Sensor P� Series microprocessor -based detectors with
advanced features like drift compensation, maintenance
alert and freeze warning. (See the Gamewell-FCI Device
Compatibility Document, P/N 52195, for a listing of com-
patible devices),
three programmable Form-C relays (factory pre-set for
Alarm, Trouble and Supervisory), and resettable and non
are power limited and operate in Class B (Style Y). The
FACIP supervises wiring, AC voltage and battery level.
in ANN-BUS 4-conductor communication circuit. These
LED driver module, and relay module.
OWN -
an auxiliary control function,
/3— isatrademark mHoneywell International Inc.
m`moregistered trademark uUnderwriter's Laboratories Inc.
5 and 10 Zone Conventional
~ Class B(Style B)initiating device circuits VDCm:
- Flex 505 five programmable IDCs
Flex 51D-ten programmable |DCs
` Built-in digital alarm communicator/transmitter (DACT).
~ Four Class B(Style Y)notification appliance circuits
(NACa)programmable for the following:
-ADAcmnpiiantotrobesynchronization
Selective silence (hom/strobemute)
Temporal orsteady signal
Si|enceab|enrnun-eUenoeob!a
Auto -silence and silence inhibit
~ Three programmable Fmnn-Crelays.
~ 24VDCspecial application power outputs (n*uettab|e
andnnn-nasettab|e).
~ Optional Class Aconverter module for NACnand |DCm
(mode|CAC-5X)
~ Optional transmitter module for municipal box service
and reverse polarity (model 4XTMF)
~ Completely field programmable atkeypad
does not require special software nrextra equipment
two password protected programming levels
^ 80-character, backlit, high-ung|e. LCDdisp|ay
continued unnext page
SIGNALING
`��� <�w�>������ \��N� Reference Certificate
LISTED APPROVED Approved �~`=O wo°"pm""°
S1869 7166-1703:0166 vM^45894'020
Specifications are for information only, are not intended for installation purposes, and are subtect to change without notice. No responsibility is assumed by Garnewell-M for their use.
,�@2013 ld�y Honeywell International Inc, All rights reserved. www.gamewell-fci.com 9021-60293 Rev. C page 1 of 2
GFANN-80
Remote annunciator with 80 charac-
ter, backlit LCD which mimics the
FACP display. Also provides status
indicators for AC Power, Alarm, Trou-
ble, Supervisory and Alarm Silenced
conditions. Packed in its own enclosure,
GFANN-RLY
Relay module provides 10 Form-C
relays. Mounts in FACP.
CAC-5X
Class A conversion module used to
convert Class B (Style B) IDCs to
Class A (Style D) and Class B (Style
Y) NACs to Class A (Style Z). Mounts
in FACP. Two required for GF510.
4XTMF
Transmitter module provides output
for the local energy municipal box
transmitter and the alarm and trouble
reverse polarity. Mounts in FACR
AC Power:
120 VAC, 60Hz, 3.8 A
Supervised, non power -limited
Battery:
Max. charging circuit:
27.6 VDC@ 1 AA
Max. Charger
26 Ah
Capacity:
(two 18 Ah batteries fit inside FACP)
Initiating Device:
Alarm zones I - 5 (Flex 505/Flex 510)
Circuits (IDC):
Alarm zones 6 - 10 (Flex 510 only)
All zones Class B (Style B)
Supervised, Class 2 Power -Limited
circuitry
Operating Voltage:
nominal 20 VDC
Alarm Current:
15 mA minimum
Short Circuit
Current:
40 mA maximum
Standby Current:
2 mA
Maximum Loop
Resistance:
100 ohms
Notification:
Four NACs, Class B (Style Y)
Circuits (NAC):
Supervised, Class 2, Power -Limited
circuitry
Operating Voltage:
nominal 24 VDC
Maximum
Signaling Current:
7,0 A (3,0 A maximum per NAC)
Maximum Wiring
Voltage Drop:
2 VDC
Form-C Relays:
Programmable (factory setting
Trouble, Alarm, Supervisory)
Contact Ratings:
2 A @ 30 VDC (resistive)
0,5 A @ 30 VAC (resistive)
Resettable
Operating Voltage:
nominal 24 VDC
Power:
Class 2 Power -Limited circuitry
Maximum
Available Current:
500 mA
Non-Resettable
Operating Voltage:
nominal 24 VDC
Power:
Class 2 Power -Limited circuitry
Maximum
500 mA
Available Current:
Remote Sync:
24 VDC nominal, max. current: 40 mA
Cabinet -Door:
19.3" x 16.8" x 0.3" (49 x 43 x 1 cm)
Backbox:
19" x 16.6" x 5.2"(48 x 42 x13 cm)
Panel LED annunciating indicators (visible to public)
- Fire Alarm (red)
- AC Power (green)
- Supervisory (yellow)
- Trouble (yellow)
- Alarm Silenced (yellow)
Local FACP piezo sounder differentiates Alarm,
Trouble, Maintenance, and Supervisory.
Membrane key panel (visible when panel door open):
- 25 keys, including a 16 alpha -numeric keypad.
- Function: ACK/STEP, SILENCE, DRILL, RESET
- Service/programming: phone keys, cursor, enter, etc.
256 Event History Log.
24 volt operation with low AC voltage sense.
Automatic battery charger with supervision.
Built-in FLPS-7 power supply (7,0 A total current).
Silent or audible walk test capabilities.
Alarm verification and positive alarm sequence (PAS).
Piezo sounder for Alarm, Trouble, and Supervisory.
Built-in 4-conductor communication bus (ANN-BUS) to
connect remote annunciators, and printer, LED, and
relay modules.
Optional trim ring,
GF605
Flex 505 conventional FACP, 5 zones,
120 VAC, w/ FLPS-7 power supply, red
GF610
Flex 510 conventional FACP, 10 zones,
120 VAC, wl FLPS-7 power supply, red
71252
EOL resistor, 4.7K ohm, 1/2 waft
53164
GF505 & GF510 Series 1/0 Manual
GFANN-80
Remote annunciator, LCD, red
GFANN-80W
Remote annunciator, LCD, white
GFANN-LED
LED annunciator module;
yellow and red LEDs
GFANN-RLY
Relay module, 10 Form-C relays
CAC-5X
Class A converter for IDCs & NACs
(2 for Flex 510)
4XTMF
Transmitter module for remote station
output or municipal box connection
TR-CIE
Trim ring for semi -flush mount, red
ANN-SB80KIT-R Backbox kit, surface mount used with
ANN-80, red
ANN-SB80KIT-W
Backbox kit, angled for better viewing,
surface mount used with the N-ANN-80
(-W), white
ANN-MBIRLY
Optional mounting bracket (ANN-RLY)
GAMEWELL-FC1
12 Clintonville Road, Northford, CT 06472-1610 USA - Tel: (203) 484-7161 - Fax: (203) 484-7118
9021-60293 Rev. C page 2 of 2 www.gamewell-fci.com
stations have a key lock/reset which is keyed alike with
Gamewell-FCI fire alarm control panels and other manual
fire alarm stations.
MS-7AF Velociti Addressable Station
steady red when the s tion has been activated.* The sta-
tion features screw terminals.
The VelocitiO Series stations use a communication proto-
col that substantially increases the speed of communica-
tion between the sensors and certain Gamewell-FCI
analog addressable fire alarm controls. These devices
operate in a grouped fashion. If one of the devices in the
group has a status change, the panel's microprocessor
stops the group poll and focuses on the single device. The
net effect is response speed up to five times greater than
earlier designs.
MS-7 Double Action Station
The MS-7 double action station isused with conventional
fie e|ann control panels. It features e set of single pole
contacts and screw terminals for connection 0oaninitiating
circuit.
voloritivisoregistered trademark ofHoneywell International Inc.
uc^ioaregistered trademark ofUnderwriter's Laboratories Inc.
LEu^*O|uwregistered trademark of GsPlastics, usubsidiary of General
Electric Company.
~ Addressable stations compatible with all Gamewe|l-FC|
analog addressable fire alarm controls
^ Conventional stations suitable for use with any UL=
Listed control panel
~ Both single and double action stations available
~ Tumbler lock for test and reset keyed alike with
GammweU-FC|cnntm|a
^ Surface orsemi-flush mounting
^ Shock and vibration resistant
` Stations (M3-7LOB)Listed for outdoor applications
` Complies with ADApull force requirements
*Only the red LED iaoperative inpanels that donot oper-
ate
SIGNALING
MEA
it
LISTED
APPR—OVED Approved
/1mwnu'mm
7160-1703:0170
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-M for their use.
@2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0616 Rev. E page 1 of 2
MS-7S Single Action Station
F 11,NWRIIIIiul WHOM- MINN
MS-7SP Double Action Station
station, with the additional feature of both English and
Spanish instructions molded into the unit.
MS-7LR Dual -action Agent Release Station
The MS-7LR is designed for use with the Gamewell-FCI
fire alarm control panels with releasing capabilities and
Flex Series releasinp sWerns. It features a set of sinale
tiating circuit.
ities are required, It consists of an MS-7LR mounted on a
plate with an abort switch and LED indicators for system
normal, and system activated status,
MS-7LOB Double Action Station
(Listed for Outdoor Applications)
use with the WP-1 0 backbox. It is intended for use with
conventional control panels and has a set of single pole
contacts and screwterminals,
Mounting
The IVIS-7 interior stations may be surface mounted or
semi -flush mounted on a standard double -gang, or 4-inch
(10.2 cm) square electrical box. An optional trim ring
(BG12TR) may also be used for semi -flush mounting.
station. (See Figure 1).
Figure 1 NYC -Plate
Material:
Lexene
Contact Ratings:
0,25amps. @ 30VACNDC
(resistive)
Dimensions:
5 5/8^Hx41/4^VVx11/4^D
(14x1&1x32cm)
Operating Temperature
(MS-7AF'MS-7ASF):
32,0o120^F(0y1o49~C)
(MS-7LOB):
-30~to150`F(-35^in66^C)
Relative Humidity
(MS-7AF,KDS-7ASF>:
10tz93Y6(nun-condensing)
(MS-7LOB):
85% 5Y6@86^±5.6^
(30^ 2^ C)
Alarm Current:
.DO3Oamp. O,QO7for LED
Supervisory Current
Part Number
Description
MS-7
Double action station
Ve|mdtiaddressable double action
station
MS-7ASF*°
Ve|odUaddressable single action station
MS-7S
Single action station, wire leads
R8S'78P
Double action station, English and
Spanish instructions
MS-7LR
Agent release station, dual -action
MS-7LRA
Agent release station with abort switch,
LED indicators, dual- action
MS-7LOB
Double action station, outdooruoe
(includes SB-|/D-Indoor/outdoor use
baokbox)
SB-1/0
|ndoonou1duoruse backbeukbox
SBA 0
8udaoabanhbox
BG12TR
Trim ring for semi -flush mount, plastic
NY -PLATE
NYC bockp|u\efor manual pu|!atetion
~°Foruse with the Gomewe||'FC|analog addressable
control panels only.
12Clintonville Road, wnrtofom.CTV8*72-m1nUSA ~ Tel: (203)*oo-7161~Fax: (203) 484-7118
Y
System Sensor i3- series smoke detectors represen
significant advancement in conventional detecti,
The i3 family is founded an three principles: instal,--
ease, intelligence, and instant inspection.
Features
Plug-in detector line, mounting base included
Large wire entry port
In -line terminals with SEMS screws
Mounts to octagonal and single -gang back boxes, 4-square back
boxes, or direct to ceiling
Stop-Drop'N Lock attachment to base
Removable detector cover and chamber
Built-in remote maintenance signaling
Drift compensation and smoothing algorithms
Simplified sensitivity measurement
Wide-angle, dual -color LED indication
Loop testing via EZ Walk feature
Built-in test switch
�tt��1�t1115
® ,L'Ok-)"
LISTED APPROVEDy approved approved` us
s9ti 3,.111 2-165�1',2 290-01-2 2i93 3180932
Installation ease. The i3 line redefines installation ease with its
plug-in design.This allows an installer to pre -wire bases (included
with heads). The large wire entry port and in -line terminals provide
ample room for neatly routing the wiring inside the base. The base
accommodates a variety of back box mounting methods as well as
direct mounting with drywall anchors.To complete the installation, P
heads plug into the base with a simple Stop-Drop'N Lock" action.
Intelligence. i3 detectors offer a number of intelligent features
to simplify testing and maintenance. Drift compensation and
smoothing algorithms are standard with the i3line to minimize
nuisance alarms. 2-wire i3 detectors can generate a remote LED -
indicated maintenance signal when connected to the 2W-MOD2
loop test/maintenance module or a panel equipped with the i3
protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3
detectors in terms of percent -per -foot obscuration,
Instant inspection. The i3 series provides wide-angle red and
green LED indicators for instant inspection of the detector's
condition: normal standby, out -of -sensitivity, alarm, or freeze trouble_
When connected to the 2W-MOD2 loop test/maintenance module
or a panel with the i3 protocol, the EZ Walk loop test feature is
available on 2-wire i3 detectors. This feature verifies the initiating loop
wiring by providing LED status indication at each detector.
71p,
Smoke detector shall be a System Sensor i3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The
detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135'F
(57.2`C).The detector shall include a mounting base for mounting to 3'k-inch and 4-inch octagonal, single -gang, and 4-inch square back boxes with a plaster
ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws, The detector shall allow pre -wiring of the
base and the head shall be a plug-in type, The detector shall have a nominal sensitivity of 2.5 percent -per -foot nominal as measured in the UL smoke box.The
detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual -
color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used
in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel
and shall provide a loop testing capability to verify the circuit without testing each detector individually.
Operating Voltage Nominal: 12/24 V non -polarized
Minimum: 8.5V
Maximum: 35 V
Maximum Ripple Voltage 30% peak to peak of applied voltage
Standby Current 2-wire: 50 pA maximum average; 4-wire: 50 NA maximum average
Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24 V
Peak Standby Current 2-wire: 100 pA; 4-wire: n/a
Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC
Dimensions (including base) 53 inches 027 mm) diameter; 2.0 inches (51 mm) height
Weight 6.3 oz (178 g)
Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT--B and 4WT-B: 32°F to 100°F (0°C to 37.8°C)
Operating Humidity Range 0 to 95% PH non -condensing
Thermal Sensor 135°F (57.2°C) fixed
Freeze Trouble 2WT-B and 4WT-B only: 417 (5°C)
Sensitivitv 2.50/o/ft nominal
Input Terminals
14 to 22 AWG
Mounting
3'/z-inch octagonal back box
4-inch octagonal back box
Single -gang back box
4-inch square back box with a plaster ring
Direct mount to ceiling
LED Mode
Green LED Red LED Condition Duration
Power up
Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds
Normal (standby)
Blink every 5 seconds off
Out of sensitivity
off Blink every 5 seconds
Freeze trouble
off Blink every 10 seconds
Alarm
off Solid
Ordering Information
2W-B No 2-wire 130 mA max. limited by control panel
2WT-B Yes 2-wire 130 mA max. limited by control panel
4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24 V
4WT-B Yes 4-wire 20 mA @ 12 V, 23 mA @ 24V
Accessories
2W-MOD2 2-wire loop test/ maintenance module RT Removal / replacement tool
SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter
4 s
3825 Ohio Avenue • St. Charles, IL 60174 P.ou r e �� r ,
Phone: 800 SENSOR2 •Fax: 630 377-6495 c1id `n ` ` ° °
0318-6'1 . o v . n216b
Outdoor Selectable -
Output Horns,
Strobes, and
Horn Strobes for
Applications
p.
SpectrAlertO Advance outdoor audible visible products
are rich with features that cut installation times and
maximize profits.
Fecitures
® Weatherproof per NEMA 4X, IP56
• Listed to UL 1638 (strobe) and UL 464 (horn)
• Compatible with System Sensor synchronization protocol and
legacy SpectrAlert products
• Field -selectable candela settings: 15, 15/753 30, 75, 95, 110, 115,
135, 150, 177, and 185
® Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
• Rotary switch for horn tone and three volume selections
® Horn rated at 88+ dBA at 16 volts
® Rated from -40°F to 151 IF
• Universal mounting plate with an onboard shorting spring that
tests wiring continuity before devices are installed
• Plug-in design with minimal intrusion into the back box
• Tamper -resistant construction
• Listed for ceiling or wall mounting
SIGNAUNG }
k�SS� 73001653,187 touidoor [.obesl
approved 112: 1653 88(ho ,stra es.
S4J11 (ChlnteS, ho , strobes. horns) APPROVED h me si,r bes)
S3593 (outdoor and aleG s'.robes) 3023572 MEA452 05-E 7135-1653-789 (horns, 0k -,s:
SpectrAiert Advance offers the broadest line of outdoor horns,
strobes, and horn strobes in the industry. With white or red plastic
housings, wall or ceiling mounting options, and plain or FIRE -printed
devices, SpectrAlert Advance can meet virtually any application
requirement, including indoor, outdoor, wet, and dry applications in
temperatures from —40°F to 151IF.
Like the entire SpectrAlert Advance line, outdoor horns, strobes,
and horn strobes for wall applications include a variety of features
that increase application flexibility and simplify installation. First,
field -selectable settings, including candela, automatic selection of
12- or 24-volt operation, horn tones, and three volume options enable
installers to easily adapt devices to meet requirements.
Next, SpectrAlert Advance devices use a universal mounting plate
for both wall and ceiling applications. This mounting plate includes
an onboard shorting spring that ensures wiring continuity before
devices are installed, so installers can verify proper wiring without
mounting the devices and exposing them to potential construction
damage. Once the plates are mounted, all SpectrAlert Advance
devices utilize a plug-in design with a single captured screw to
speed installation and virtually eliminate costly ground faults.
Outdoor devices ship with weatherproof plastic back boxes (metal
back boxes are available separately) that accommodate in -and -
out wiring for daisy chaining devices. Plastic back boxes feature
removable side flanges and improved resistance to saltwater
corrosion. Knock -outs located on the back eliminate the need to drill
holes for screw -in mounting. Plastic and metal weatherproof back
boxes come with 3/-inch top and bottom conduit entries and 3/-inch
knock -outs at the back. A screw -in NPT plug with an O-ring gasket
for a watertight seal is included with each back box.
prill
General
SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync*Circ Ulf- Module accessory, shall be powered from a non -coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync -Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17
and 33 volts. Outdoor SpectrAlert Advance products shall operate between -40 and 151 degrees Fahrenheit from a regulated DC or full -wave
rectified unfiltered power supply. Strobes and horn strobes shall have field -selectable candela settings including 15, 15/75, 30, 75, 95, 110,
115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service
The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved
per UL The strobe shall be suitable for use in wet environments
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe
light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to
switch between a temporal three pattern and a non -temporal (continuous) pattern. These options shall be set by a multiple position switch.
On four -wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or
non -coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain Outdoor approved per UL The
horn strobe shall be suitable for use in wet environments.
Operating Temperature -40°F to 151'F (-40°C to 66°C)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall -Mount Dimensions (including lens) 5.6" L x 4.7 " W x 2.5 - D (142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6-L x 4.7-W x 1.3'D (142 mm L x 119 mm W x 33 mm D)
Wall -Mount Weatherproof Back Box Dimensions (SA-WBB) 5.7-L x 5.1 -W x 2.0"D (145 mm L x 130 rum W x 51 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs
2, R S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd
AVDSC112�I
Candela
8-175 Volts
DC FWR
16--33 Volts
DC FWR
Standard
15
123 128
66
71
Candela
15/75
142 148
77
81
Range
30
NA NA
94
96
75
NA NA
158
153
95
NA NA
181
176
110
NA NA
202
195
115
NA NA
210
205
High
135
NA NA
228
207
Candela
150
NA NA
246
220
Range
177
NA NA
281
251
185
NA NA
286
258
R
a
r®•
a.e
3-17.5 Volts
16-•33 Volts
6-175 Volts 16-33 Volts
Sound Pattern dB DC FWR DC FWR
Temporal High 57 55 69 75
Temporal Medium 44 49 58 69
Temporal
Low
38
44
44
48
Non -Temporal
High
57
56
69
75
Non -Temporal
Medium
42
50
60
69
Non -Temporal
Low
41
44
50
50
Coded
High
57
55
69
75
Coded
Medium
44
51
56
69
Coded Low 40 46 52 50
DC Input
15
15175
15
15175
30
75
95
110
115
Temporal High
137
147
79
90
107
176
194
212
218
Temporal Medium
132
144
69
80
97
157
182
201
210
Temporal Low
132
143
66
77
93
154
179
198
207
Non -Temporal High
141
152
91
100
116
176
201
221
229
Non -Temporal Medium
133
145
75
85
102
163
187
207
216
Non -Temporal Low
131
144
68
79
96
156
182
201
210
R Input
Temporal High
136
155
88
97
112
168
190
210
218
Temporal Medium
129
152
78
88
103
160
184
202
206
Temporal Low
129
151
76
86
101
160
184
194
201
Non -Temporal High
142
161
103
112
126
181
203
221
229
Non -Temporal Medium
134
155
85
95
110
166
189
208
216
Non -Temporal Low
132
154
80
90
105
161
184
202
211
16-33 Volts
16-33 Volts
DC Input
135 150
177
185
FWRInput
135 150
177
185
Temporal High
245 259
290
297
Temporal High
215 231
258
265
Temporal Medium
235 253
288
297
Temporal Medium
209 224
250
258
Temporal Low
232 251
282
292
Temporal Low
207 221
248
256
Non -Temporal High
255 270
303
309
Non -Temporal High
233 248
275
281
Non -Temporal Medium
242 259
293
299
Non -Temporal Medium
219 232
262
267
Non -Temporal Low
238 254
291
295
Non -Temporal Low
214 229
256
262
Candela Derating
Horn Tones and SoundOutput
Data
For K series products used
at low temperatures,
listed
candela ratings must be reduced in accordance with
6-175
16--33
24-Volt Nominal
this table.
Switch
Sound Volts
Volts
Reverberant
Aneohoic
®•
Position
Pattern dB CC FWR CC FWR
CC FWR
DC FWR
Listed Candela
Candela rating at —40°F
15
Do not use below 32°F
15/75
30
75
44
95
70
110
110
115
115
135
135
150
150
177
177
185
185
1
Temporal
High
78
78
84
84
88
88
99
98
2
Temporal
Medium
74
74
80
80
86
86
96
96
3
Temporal
Low
71
73
76
76
83
80
94
89
4
Non-
High
82
82
88
88
93
92
100
100
Temporal
5
Non-
Medium
78
78
85
85
90
90
98
98
Temporal
6
Non-
Low
75
75
81
81
88
84
96
92
Temporal
7'
Coded
High
82
82
88
88
93
92
101
101
8'
Coded
Medium
78
78
85
85
90
90
97
98
9' Coded Low 75 75 81 81 88 85 96 92
'Settings 7, 8, and 9 are not available on 2-wire horn strobe. AMS0120
SpectrAlert Advance Diagrams
2.5"
-
Ell
P2RKft
2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
P2RHK"t
2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
P2WK"t
2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
P2WHK''
2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
P4RKt
4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
P4WK
4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
P2RHK-120
2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box)
Wall Strobes
SRK't Strobe, Standard cd, Red. Outdoor (includes plastic weatherproof back box)
SRHK- Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
SWK" Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
SWHK"t Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
Horns
HRKt Horn, Red, Outdoor (includes plastic weatherproof back box)
Accessories
SA-WBB Red, Metal Weatherproof Back Box
SA-WBBW White, Metal Weatherproof Back Box
Notes:
' Add "-P' to model number for plain housing (no "FIRE' marking on cover), e.g., P2RK-P.
t Add '-R" to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW
"Standard cd" refers to strobes that include 15, 15175, 30, 75, 95, 110, and 115 candela settings. "High ed" refers to strobes that include 135, 150, 177, and 185
candela settings. When replacing standard outdoor snits both the device and back box must be replaced.
SYSTEM @201i 2 Syu Se s --
3825 Ohio Avenue ® St. Charles, IL 60174 �lsp ct ,esru c ulangs Nr o not, cc Viso systemse so, co-,
SENSOR'Phone.: BOO-SENSOR2 w Fax: 630-377-6495 .scluent product rho,n'olim, indidingtielatest ve'snn or INS data sheet
AnS01201 4t 2
MET07,91M
0
FEATURES
A cost-effective answer for those looking for
Dimensions: 14 1/4" tall, 14
a durable, code -compliant enclosure to
Sd�sea
1/3" wide and 3" deep
ensure mandated records are maintained at
Velcro strap and inside edge
the fire alarm control unit location.
keep important documents
secure
Every durable box is fabricated from 20
Standard thumb screw
gauge steel with a powder coat finish and
included with a knock -out if
lock is needed
features a formed lift -a -way hinge. Also
(sold separately)
included is a Velcro strap and inside edge to
20 gauge cold rolled steel
keep important documents secure.
construction with durable,
red powder coat finish
SPECIFICATIONS
Lift -a -way hinge door for
easy access
The SDB System Document Box shall be constructed of 20
gauge cold rolled steel and finished with a durable, red powder
coat. Front cover will feature a lift -a -way hinge. Door shall be
secured with a standard thumb screw with a knock -out available
if a lock is needed. Construction shall include a Velcro strap and
inside edge to hold documents in place.
Pg. 1/2
WAY
STYLE
ORDERING INFORMUION
SSU00691 SDB System Document Box
Accessories:
SSU00695
CAT30 Lock kit
SSU00696
PK625 Lock Kit
SSU00697
T45 Lock Kit
SSU03161
Inspection and Maintenance Identification Labels
SSU52020
IRF Inspection Record Frame
M
I
Inspection and Maintenance
Identification Labels for verification
www. I sae.com I toll free 1. 4 .1729 1 fax 508,485.4740
0 Copyright 2018 Space Age Electronics, Inc. I This document subject to change without notice I LT1 0801 1 Rev. A mom
NFW ADA
Pg. 212
°Universal full event sole & dual path 56 LTE-Moellular WoriP commercial
fire alarm reporting from any panel brand, virtually anywhere nationwide
°Cwdm-compUantreplaces 2P0Tslines per FACP
saves thousands ufdollars per year over the leased |aod|ines.
° Supports 12K^24Vcontrol panels and FACPs that communicate using Contact
|Dand 4/2(such asonlegacy poneh),osprimary orbackup.
° Proven $arUnkReliability & Best 56OE'M Performance ' Works where
others can't ' Signal Donst/"Circuitry & unique dual -diversity twin antennas,
maximizing signal acquisition and eliminating the multiphase -effect signal -clash/
drop -outs single -antenna units are prone to.
~ Full data Reporting to any Central Station nationwide, via choice wf
NeMomnwm,AT&TmNetworks. Communicate critical life and safety alarm
reports for maximum life safety&Ua bUhyprotection.
° Easiest installation, powered by panel, NO extra power supply, NO extra
conduit. (Excludes Metal Direct 4EPwwere )
°Lahor-Saving Features Save Time & Money ' Uniquely including 4programmable
EOLRzone inputs; 2Form CRelay outputs (no extra supervision modules mbuy o,io'
stall); plus, 2 Telephone style jacks for easy FACM»onection.Self-supervised oo4wires.
• Preactivated - No -Delay Activation Speeds installation time, even during peak periods.
°LED Status ITmmb|mIndicators 3Radio Status LED Indicators (visible from
outside standard model housing) Green, Signal Strength; Amber- 8usy/AuimUvn;
Red -Trouble (4additional LEDs, not visible, for network status & troubleshooting).
Power LED indicator viewable vnouter metal enclosure models,
°Oxmr-the-4rWpgraclableFirmware for updates w/o atruck-roll
°CLSS Support
-
~FreeFACP-Saver App'5manphunePro sales tool for
calculating /domonstnuingnoount'scellular cost savings
with dealer bynumber oflines Glocations vs. copper
POTslines leased from phone co.
FREE download onApple Store or600g|oPlay,
VLand NRPA72 Fire Code -Compliant, the StarLinkMax Fire Series Wireless
Commercial Fire Alarm Sole Path 8Dual Path Communicators provide universal
support for any brand 12Vm24Vfire alarm control panel, reporting inContact 0
and A/2,With broadest nationwide coverage footprint, Veriznnu,ATQTusing
proven StarLink circuitry, they are also available inlocking metal models.
All provide the most economical solution for easy, versatile installation.
Also regional compliances, ie'CSFM, NYI9D, LAFDand more.
Easy, Universal Installation at Every Application; Panel- PonweredTenhnu<ogym.
StarLink Fire Communicators are easily connected to any panel or Fire Alarm Control Panel
(FACP) stanclardly operating between 12V and 24V. Flexible in any application, StarLink Max
Fire also comes instandard, ormodels |nmetal housings, with code -compliant suyumidoo'
and choice ofpower vpdoos, Panel -Powered Techoo|ogy1m(powered bythe pane|),n/
direct -connect 12OVACmodels, Signal Boost circuitry & dual diversity antennas for maximum
signal acquisition & null avoidance, receiving signals simultaneously on both antennas,
One Model |nSole urDual Path with Cellular + Internet Option.SmrUnk
Fire provides full data reporting, insole and dual path, asaprimary orbackup, m
any central station ofyour choice, without requiring any special equipment on
premises. The units are very easily activated, plans and options are selected, oud
24/7account management isprovided all through www.nupmmmnet.mm.
Napco StarLink Max@ Fire Commercial Alarm Communicators
°56 LTG-MSole mrDual Path Coll Commercial Fire Alarm Communicator |nOne
^ Choice mYNationwide Coverage Networks, Ve,imou,AT&T models
~ Choice ofplans for every requirement. Simply select Cell o/[e|NPService Plan
and check -in period: 2V0seconds, 5minutes, hOminutes, 6hours o,24hours.
°Patamted Signal Bmont1mand Dual Diversity Antennae for maximum signal
acquisition Qnull avoidance, receiving signals simultaneously onboth antennas
°Pro Cmst-SawmrTra6wmpProgram ' Unsurpassed savings, for new and retrofit
installations, replacing POTS, old radios, sunset networks and even new installations
°Bwnum: Full High -Speed NapcoPanel remote up/downloading
° COMPLIANCES: VB85'UUO2J.Vi1hlV.UU070.ULR841NhEd. California State Fire
1
Model No.
7777"
Standard,AB�7
i _N
SLE-MAXAI-FIRE
wil
I
ndard ormetal models onchoice of VerizuorAT&rnetworks Verimnl( t AT&T
)�tO*Seri
Lquipment Panel/Dedicated Circuit Surge Protective Device
General Product Specifications
DITEK's HW series of surge protectors are designed
and manufactured to meet the exacting standards of
the life safety industry. These compact parallel
mount surge protectors are widely used to protect
fire alarm panels and other dedicated branch circuit
loads,
DTK-120H-V1 DTAA 20/240RIT
Product Features
• Diagnostic LED indicates ground presence,
system power and SPD function
• Weatherproof enclosure
• Small footprint enables installation in a variety of
locations
• Available for *jo-,#,ular 120V and 120/240V s�Astems
• Complies with ANSI/IEEE C62.41 and C62.45
Category B standards
• Ten Year Limited Warranty
38
:01
ID
013M
Specifications
Agency Approvals: UL 1449, 3rd Edition, cUL
IEEE Location Category: Category B
Protector Type: SPD Type 2
Protection Modes: L-G, L-N, N-G
Response Time: <lns
Temperature Range: -40'F — 185'F
Maximum Humidity: 95% non -condensing
Operating Frequency: OHz — 40OHz
Dimensions: 2.93" x 2.83" x 1.68"
(74.4mm x 71 .9mm x 42.7mm)
Connection: 1/4" diameter threaded fitting
Weight: .51b. (2279)
Housing: ABS
Model
Peak
UL 1 449, 3rd
Short Circuit
UL1449,
Selection;
Service Wiring
Surge
MCOV
Ed. V.P.R.
Current
3rd Ed. In
DTK-
Current
Rating
Rating
Single 0)
700V L-N, L-G,
120HW
(2W + G), 120VAC
19,500A
130V
600V N-G
10,OOOA
3,OOOA
13,OOOA/
700V L-N, L-G-
Split 4)
Phase
120/240HW
130/260V 600V N-G-'
10, OOOA
3, OOOA
(3W + G), 120/240VAC
6,50OA/
Mode
1200V L-L
One DITEK Center 1-800-753-2345
1720 Starkey Road Technical Support: 1-888-472-6100
Largo, FL 33771 www.drtekcgELcom
Document, SPS-100057-001 Rev 9 2/12
@2011 DITEK Corp.
Specification Subject to Change