HomeMy WebLinkAbout23-7056City of Zephyrhilis
5335 Eighth Street
Zephyrhills, FL 33542
Phone: (813) 780-0020
Fax: (813) 780-0021
Issue Date: 10113/2023
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
lj
[71•011011= '7717717M
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
RE PEVMIT OFFICE[)
f EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTION
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
►., 6580
MATEEN MALIKi i631-63113
W 8024 WHEAT STONEis
ZEPHYR LAKES SUBDIVISIC1111il
71 F1,126-25-21-0140-00100-0050
WORK PROPOSED
NEW CONSTR
ADD/ALT
�
INSTALL
�
REPAIR
PROPOSED USE
SFR
COMM
TYPE OF CONSTRUCTION
BLOCK
Q
FRAME
SIGN DEMOLISH
DESCRIPTION OF WORK INSTAL TI®N �F 1t3.9it T P UST Pi/ SYSTE >
BUILDING SIZE SQ FOOTAGE HEIGHT
BUILDING =27,67=9.61VALUATION OF TOTAL CONSTRUCTION
ELECTRICALLl
$�
PLUMBING $
MECHANICAL $
GAS ROOFING
FINISHED FLOOR ELEVATIONS _,.._..,_
AMP SERVICE 1 0A PROGRESS ENERGY
VALUATION OF MECHANICAL INSTALLATION
SPECIALTY = OTHER
FLOOD ZONE AREA =YES NO
III -- -- ion
BUILDER COMPANY
SIGNATURE REGISTERED Y / N FEE CURREN Y / N
Address License #
ELECTRICI COMPANY SKY SOLAR EER Y INC
SIGNATUR V<" _ REGISTERED Y N FEE CURREN YlN
Address 4D417 CH ' Y RD UNIT 103 ZEPHYRHILLS, FL 335�2 License JEC13010029
PLUMBER COMPANY
SIGNATURE REGISTERED Y 1 N FEE CURREN Y 1 N
Address License#,__
.e�
MECHANICAL COMPANY
SIGNATURE REGISTERED Y / N FEE CURREN Y / N
Address License #
OTHER COMPANY
SIGNATURE [ REGISTERED YIN FEE CURREN Y / N
Address License #
RESIDENTIAL Attach (2) Plot Plans; (2) sets of Building Plans; (1) set of Energy Forms; R-O-W Permit for new construction,
Minimum ten (10) working days after submittal date, Required onsite, Construction Plans, Stormwater Plans wl Silt Fence installed,
Sanitary Facilities & 1 dumpster; Site Work Permit for subdivisionsllarge projects
COMMERCIAL Attach (2) complete sets of Building Plans plus a Life Safety Page; (1) set of Energy Forms. R O-W Permit for new construction,
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans wl Silt Fence installed,
Sanitary Facilities & 1 dumpster. Site Work Permit for all new projects, All commercial requirements must meet compliance
SIGN PERMIT Attach (2) sets of Engineered Plans.
****PROPERTY SURVEY required for all NEW construction.
Directions:
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to "deed" restrictions" which may be more restrictive
than County regulations. The undersigned assumes responsibility for compliance with any applicable dead restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: If the owner has hired a contractor or contractors to undertake work, they
may be required to be licensed in accordance with state and local regulations. If the contractor is not licensed as required by law, both the owner and
contractor may be cited for a misdemeanor violation under state law. If the owner or intended contractor are uncertain as to what licensing requirements
may apply for the intended work, they are advised to contact the Pasco County Building Inspection Division —Licensing Section at 727-847- 8009.
Furthermore, if the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign portions of the "contractor Block" of this
application for which they will be responsible, If you, as the owner sign as the contractor, that may be an indication that he is not property licensed and is
not entitled to permitting privileges in Pasco County,
TRANSPORTATION IMPACT/UTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings, change of use in existing buildings, or
expansion of existing buildings, as specified in Pasco County Ordinance number 89-07 and 90-07, as amended, The undersigned also understands, that
such fees, as may be due, will be identified at the time of permitting. It is further understood that Transportation Impact Fees and Resource Recovery
Fees must be paid prior to receiving a 'certificate of occupancy" or final power release, If the project does not involve a certificate of occupancy or final
power release, the fees must be paid prior to permit issuance. Furthermore, if Pasco County Water/Sewer Impact fees are due, they must be paid prior
to permit issuance in accordance with applicable Pasco County ordinances.
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2,500.00 or more, I certify that 1, the applicant,
have been provided with a copy of the 'Florida Construction Lien Law --Homeowner's Protection Guide" prepared by the Florida Department of
Agriculture and Consumer Affairs, If the applicant is someone other than the "owner", I certify that I have obtained a copy of the above described
document and promise in good faith to deliver it to the "owner' prior to commencement.
CONTRACTOR'SIOWNER'S AFFIDAVIT: I certify that all the information in this application is accurate and that all we* will be done in compliance with
all applicable laws regulating construction, zoning and land development. Application is hereby made to obtain a permit to do work and installation as
indicated, I certify that no work or installation has commenced prior to issuance of a permit and that all work will be performed to meet standards of all
laws regulating construction, County and City codes, zoning regulations, and land development regulations in the jurisdiction. I also certify that I
understand that the regulations of other government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance. Such agencies include but are not limited to:
- Department of Environmental Protection -Cypress Bayheads, Wetland Areas and Environmentally Sensitive
Lands, Water/Wastewater Treatment.
- Southwest Florida Water Management District -Wells, Cypress Bayheads, Wetland Areas, Altering
Watercourses,
- Army Corps of Engineers -Seawalls, Docks, Navigable Waterways.
- Department of Health & Rehabilitative Services/Environmental Health Unit -Wells, Wastewater Treatment,
Septic Tanks.
- US Environmental Protection Agency -Asbestos abatement.
- Federal Aviation Authority -Runways,
I understand that the following restrictions apply to the use of fill:
- Use of fill is not allowed in Flood Zone W" unless expressly permitted.
- If the fill material is to be used in Flood Zone "X, it is understood that a drainage plan addressing a
"compensating volume" will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida.
- If the fill material is to be used in Flood Zone "A" in connection with a permitted building using stem wall
construction, I Certify that fill will be used only to fill the area within the stem wall.
- If fill material is to be used in any area, I certify that use of such fill will not adversely affect adjacent
properties. If use of fill is found to adversely affect adjacent properties, the owner may be cited for violating
the conditions of the building permit issued under the attached permit application, for lots less than one (1)
acre which are elevated by fill, an engineered drainage plan is required.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in this affidavit prior to
commencing construction. I understand that a separate permit may be required for electrical work, plumbing, signs, wells, pools, air conditioning, gas, or
other installations not specifically included in the application. A permit issued shall be construed to be a license to proceed with the work and not as
authority to violate, cancel, alter, or set aside any provisions of the technical codes, nor shall issuance of a permit prevent the Building Official from
thereafter requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid unless the work
authorized by such permit is commenced within six months of permit issuance, or if work authorized by the permit is suspended or abandoned for a
period of six (6) months after the time the work is commenced. An extension may be requested, in writing, from the Building Official for a period not to
exceed ninety (90) days and will demonstrate justifiable cause for the extension. If work ceases for ninety (90) consecutive days, the job is considered
abandoned.
lZrXitl?"DRATITA B'd vi"I J, lij;aIvAg ji ig a 11.114 &0 WAIW
FLORIDA JURAT (F.S. 117.03)
OWNER OR AGENT
Subscribed and sworn to (or affirmed) before me this
11TH DAY OF OCTOBER 2023 by. �ALIK M�ATEEN
Who is/are personally known to me or has/have produced
DRIVERS LICENSE as identification.
Notary Public
Kil
am
identification.
9MI
4Notary Public
—
commi
"M
Z
Notary Public State of Florida
Ka"" Hickey
My Commission KH 149341
Expires 07106/2026
w4o i m* &vAr.*j It v i v&w um oN I wQPWV rkz) A&W-t 1 t-age i or I
10/12/2023 10:23 AM Rcpt: 2633579 Rec: 10.00 DS: 0.00 IT: UO
Nikki Alvarez-Sowles, Esq., Pasco County Clerk & Comptroller
NOTICE OF COMMENCEMENT
FLORIDA county of PASCO
THE UNDERSIGNED hereby gives notice that Imarovement will be made to certain real V, and In accordance with Chal, ;�3 F
ft fbilawingTn-f—ormation, Is provided in this Notice of Commencement:
1 - Description of Property, Parcel identification No. 26-25,-21-0140-00100-0050 - ZEPHYR LAKES SUBDINISION PKASES 1A ZA 28 & 4A BLOCK 1 L
Street Address, I
3, Owner Information or Lessee Informattort if the Lessee contracted for the Improvement:
MATEEN MALJK A
8024 WHEAT M14E DRIVE ZEPHYRHILLS FL
Address city Mate
Interest In Property:
Name of Fee Simple Titleholder
Address Clly State
4, Contractor.
Me"YRRU—s— FL
CityState
Contractors Telephone No.:
�i]11101
Address City -- --- - ------- State
Amount of Bond: $__ Telephone No.
Address City State
Lender's Telephone No.:
7. Persons within the State of Florida designated by the owner upon whom notices or other documents may be served as provided by
Section 713.13(1)(a)(7), Florida Statutes:
Name
Address
Telephone Number of Designated Person,
8. In addition to himself, the owner designates
City state
of
toa copy at the Lianorle Noses as provided in Section 713.1 S(I "), Rpriclo Statvtm ,
Telephone Number of Person or Entity Designated by Owner
9. Expiration date of Notice of Commencement (the expiration date may not be before the completion of construction and final payment to the
contractor, but will be one year from the data of recording unless a different daft Is specified):
Under penalty of perjury, I declare that I have read the foregoing notice of commencement and that the facts stated therein are true 10 the beat
of my knowledge and baW.
ftnSlg.d bY*
STATE OF FLORIDA AUU� AUTf0v
COUNTY OF PASCO F 9fig-MOR610% M®r or Lessee, crownees or LesisedsAuth ad
Officer/Direotor/Portneffmanager
HOMEOWNER
Signatory'sTitle/Office
The foregoing instrument was acknowledged before me this 1111THn day of ��OBER� 2c�L by MALIKMATEEN
-HQMEQ-)yNE[L_ (type ofautharity, e.g., officer, trustee, aft eyinfact)fbir
(nan-La of narthr ambehaM&Mhum instrumn vigj: mc 2Lded
Personally Known [3 QR_ Produced Identification)a Notary Signs
Type of Identification Produced Name (Print)
:MEKmwamYyCwe""lOeMe MwHIiftScSkIeS2yW
N o14F934�
07MOn0H1
L_U C E N T
L N G I N E E R I N G
Solar Professional Engineering Consulting
RE: Engineering Services
Mateen Residence
8024 Wheat Stone Dr, Zephyrhills, FL
8.41 kW` System
Solo Job #4048271
To Whom It May Concern,
814 E 1475 ',%'
Lehi, LIT 84011
1
m: (309) 645-09
admin(a)lucenteng.
The verification of the field observations is the responsibility of the contractor. Prior to commencement of
work, the contractor shall verify the framing sizes, spacings, and spans noted in the sealed plans,
calculations, and/or certification letter and notify the Engineer of Record of any discrepancies.
Roof Finish
Roof Underlayment
Roof Profile
Roof Structural System
Truss Top Chord/Setup
Chord/Rafter Wood Grade
Truss/Rafter Spacing
Roof Slope
Max Top Chord/Rafter Span
Bearing Wall Type
Foundation
Stories
Roof
Asphalt Shingle
OSB
Hip Gable
Metal Plate Trusses
2 x 41 Modified Queen
Southern Pine #2 or better
24" o.c.
22 deg
7.17 ft
Convi Lt-Frame Constr
Permanent Concrete
Single
Code:
2020 FBC, 7th Ed (ASCE 7-16)
Risk Category:
11
Roof Live Load
20 psf (0 psf at panels)
Occupancy Class:
R-3
Ground Snow Load
0 psf
Roof Dead Load
Ult Wind Speed
140 is
PV Dead Load:
a-W
Exposure Category:
C
Total Dead Load :
9.5 psf
C. Summary of Existing Structure Results
Aner W-Ur
building codes and current industry standards, the existing roof structure supporting the proposed
alterations consistinq of the solar array has been determined to be:
1111109MIORM-�* �$�- 1111111V311n l���
Manual", which can be found on the K2 website (http://K2-systems.com/).
2. Manufacturer's Panel Bracket Connection to Roof Chord/Rafter Member:
Fastener: (2) M5x80Self-Piecing Screws per Brack
NDSVVhhdnaw(Value: 217lba/inoh
Min. Thread Length and Pentration Depth : 1.5"
bracket supports shall be placed no greater than 48 in. o/c.
4. Panel supports connections shall be staggered to distribute load to adjacent trusses.
loads imposed by the solar array. This evaluation conforms to 2020 FBC, 7th Ed and current industry
standards. I
Should you this letter orifyou require further information, donot hesitate *z
contact me.
Limits of Scope of Work and Liablity
The existing structure is assumed to have been designed and constructed following appropriate codes at the
time of erection and assumed to have appropriated permits. The calculations performed are only for the roof
framing supporting the solar array installation referenced in the stamped plans and were completed according=
to generally recognized structural analysis standards and procedures, professional engineering, and design N
Existing deficiencies which are unknown or were not observed durinF A
time the site observation are not included in this scope of work. All solar panel modules, racking, and
The Engineer of Record and the engineering consulting firm assume no responsibility for misuse or improper
installation. This analysis is not stamped for water leakage. Framing was determined on information in
provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the
contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and/or
certification letter and notify the Engineer of Record of any discrepancies prior to starting construction. If
during solar panel installation, the roof framing members appear unstable or deflect non -uniformly, our office
should be notified before proceeding with the installation. The contactor shall also verify that there are no
framing that was not addressed in the stamped plans, calculations, and/or certification letter and notify the
Engineer of Record of any concerns prior to starting construction.
October 10, 2023 Lucent Engineering, P.C.
Mateen Residence
#
moina• A` •.
1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690,
AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING
2. PROPER ACCESS AND WORKING CLEARANCE
AROUND AND PROPOSED: a...
EQUIPMENT•' • ARTICLE 110
3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM
PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250
4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL
1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES
5. ALL ! WIRES SHALL BE SIZED ACCORDING TO 690.81
6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.311
TO BE PLACED IN ACCORDANCELOCAL ! # aL BUILDING CODE
ELECTRICAL EQUIPMENT
•T;T#!1
! f !
1*.TTC'4VTel
• l ' � • 1. /
2017 NEC
2020 ! •BUILDING
1 FBC 7TH EDITION,RESIDENTIAL
020 i EDITION, BUILDING
2020 FFPC
SKY SOLAR
•1 1111111TAY-1111111M
8024 WHEAT STONE DR
ZEPHYRHILLS, FL 33540
AC SYSTEM SIZE: 8.41 KW AC
DC SYSTEM SIZE: 10.585 KW DC
LAT, 28.2748829
LONG,-82.1831958
Q.PEAK l • I
PV MODULES
INVERTER(S) I
DUKE ENERGY
DRAWN BY: SoioCAD
10/10/2023
COVER-PV01
i
ii V
t' i 3 MOUNTING PLANE: A71MUTH:
DETAILS:
71— H 1®711
Af C MSC M
a o m
-77�� 0
QQ
DRIVEWAY co
rD
® Cu
B Z N
O
0
Q
EE 0
7 ®® 1®
I
�- 1® 11
EQUIPMENT LEGEND:
VISIBLE, LOCKABUTILITY METER �� AC DISCONNNECTEE, LABELED € v INVERTER SIB SUB PANEL [SD] SERVICE DISCONNECT [:] PV MODULES FIRE ACCESS PATHWAY (3' TYP)
ASP MAIN SERVICE PANEL Pv (MF T R SOCK T METER) COMBINER BOX Lc LOAD CENTER Barr BATTERY(IES) 1g JUNCTION BOX PROPERTY LINE
17 NMI R.I
8024 WHEAT STONE DR
ZEPHYRHILLS, FL 33540
AC SYSTEM SIZE: 8.41 KW AC
DC SYSTEM SIZE: 10.585 KW DC
LAT, 28.2748829
LONG,-82.1831958
(29) HANWHA Q.PEAK DUO BLK-G10+/AC 365
PV MODULES
(29) ENPHASE IQ7PLUS-72-ACM-US
INVERTER(S)
DUKE ENERGY
VISIBLE, LOCKABLE, DRAWN BY: SoloCAD
LABELED AC DISCONNECT 10/10/2023
LOCATED WITHIN 10'
OF UTILITY METER SITE PLAN - PV02
I
ii V
t' i 3 MOUNTING PLANE: A71MUTH:
DETAILS:
71— H 1®711
Af C MSC M
a o m
-77�� 0
QQ
DRIVEWAY co
rD
® Cu
B Z N
O
0
Q
EE 0
7 ®® 1®
I
�- 1® 11
EQUIPMENT LEGEND:
VISIBLE, LOCKABUTILITY METER �� AC DISCONNNECTEE, LABELED € v INVERTER SIB SUB PANEL [SD] SERVICE DISCONNECT [:] PV MODULES FIRE ACCESS PATHWAY (3' TYP)
ASP MAIN SERVICE PANEL Pv (MF T R SOCK T METER) COMBINER BOX Lc LOAD CENTER Barr BATTERY(IES) 1g JUNCTION BOX PROPERTY LINE
17 NMI R.I
8024 WHEAT STONE DR
ZEPHYRHILLS, FL 33540
AC SYSTEM SIZE: 8.41 KW AC
DC SYSTEM SIZE: 10.585 KW DC
LAT, 28.2748829
LONG,-82.1831958
(29) HANWHA Q.PEAK DUO BLK-G10+/AC 365
PV MODULES
(29) ENPHASE IQ7PLUS-72-ACM-US
INVERTER(S)
DUKE ENERGY
VISIBLE, LOCKABLE, DRAWN BY: SoloCAD
LABELED AC DISCONNECT 10/10/2023
LOCATED WITHIN 10'
OF UTILITY METER SITE PLAN - PV02
I
IVIYAIJI
RACKING PART NUMBER:
CROSSRAIL48-XL
ROOF FRAMING:
MODULE COUNT 19.31 FT 55!9!9M
ATTACHMENTS
SPLICE FOOT XL - 4000162
RAFTER/TOP CHORD SIZE:
ROOF AREA:
ATTACH ME NT CITY:
RAFTER/TOP CHORD SPACING:
—F ROOF COVERED:
ATTACHMENT SPACING:
ARRAY WEIGHT:
MODULE COUNT 46 LBS 1334 LBS
MIDCLAMP CITY:
POINT LOAD:
ARRAY LBS/ATTACHMENTS = 18.53
ENDCLAMP CITY:
ISTRIBUTED LOAD: (IbS/ft2)
ARRAY WEIGHT/AREA = 2.38 LBS/FT 2
SKY SOLAR
SITE INFORMATION
MAumMwTEEN
8024VVHeATSTONEoR
ZspnYRH|LLS,FLJ3S4O
ACSYSTEM SIZE: 8.41KVVAC
DC SYSTEM SIZE: 10.585%VVD[
LAT,20.27488Z9
U]mG'-8Z.z83z958
(29) HANVVHAQ.PEAKDUO BLn-GzO+/x[365
PVK8ODULES
<29>ENPHASE|Q7PLU3-72`ACKA-uS
INVERTER(S)
DUKEENERGY
DRAWN BY: SoloCAD
10/10/2023
ROOF PLAN - PV03
EQUIPMENT INFORMATION:
ROOF INFO:
PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA:
RACKING MANUFACTURER:
K2
ROOF TYPE:
ASPHALT SHINGLE
PV MODULE COUNT:
29
RACKING PART NUMBER:
CROSSRAIL 48-XL
ROOF FRAMING:
MANUFACTURED TRUSS
ARRAY AREA:
MODULE COUNT * 19.31 FT'= 559.99
ATTACHMENTS
SPLICE FOOT XL - 4000162
RAFTER[TOP CHORD SIZE:
2x4
ROOF AREA:
3047 FT 2
ATTACH ME NT CITY:
72
RAFTER/TOP CHORD SPACING:
24"
PERCENT OF ROOF COVERED:
18%
SPLICE CITY:
6
ATTACHMENT SPACING:
48"
ARRAY WEIGHT:
MODULE COUNT * 46 LBS = 1334 LBS
MIDCLAMP CITY:
46
POINT LOAD:
ARRAY LBS/ATTACHMENTS = 18.53
ENDCLAMP CITY:
24
DISTRIBUTED LOAD: ([bS/ft2)
ARRAY WEIGHT/AREA = 2.38 LBS/FT'
Sr\'T SOLAR
�q T 1 X, n-.Tfi T
8024wHGAT STONE DR
ZEPHYnH|LLS,FL3]54V
4cSYSTEM SIZE: 8.41GNA[
ocSYSTEM SIZE: 10.585KwD[
LAT,2&l7480Z9
LOmG'-82.185z958
PV MODULES
DUKEENERGY
DRAWN BY: SoloCAD
10/10/2023
MOUNTING DETAIL - PV04
MAX POWER -POINT CURRENT (IMP):
10.56 A
SERIES FUSE RATING:
20A
MAX INPUT VOLTAGE:
60 V
MAX DC SHORT CIRCUIT CURRENT:
15 A
MAXIMUM OUTPUT POWER:
290 W
MAXIMUM OUTPUT CURRENT:
1.21 A
MAX UNITS PER 20A CIRCUIT:
13
J_eox
/,� '
—^— -- --
J-BOX
EQUIPMENT SCHEDULE
TYPE
CITY
DESCRIPTION
RATING
AC COMBINER BOX SOLAR
LOADS ONLY UL 1741
COMPLIANT
CONDUIT & CONDUCTOR SCHEDULE
TAG
QTY
WIRE GAUGE
DESCRIPTION
CONDUIT SIZE
dh
1���mv�
ie>zuu�wm/wTO UTILITY GRID
PV AC DISCONNECT
ewNON-FmED,
VISIBLE, LOCKABLE,
(E)smup
LABELED, upem
|
24Ow.2'poLs
/ /r—e~-
|(N) 50A-2P
(E) 200A SUB PANEL
I(E) GROUNDING
(E) (E) UTILITY METER
,
SITE INFORMATION
MAumMwTEEN
B024WHEAT STONE on
Zsp*YxH|LLS.FLB54O
A[SYSTEM SIZE: 8.41xvvAC
Q[SYSTEM SIZE: 10.585KVvoC
un, 28.2748829
uJmG'-Dz.zO3z958
(29) HANYVH«Q.ps::DUO eLK-5I0+/A[3G5
PvKxODULE3
<29>ENPHA5E|Q7PLUS-72+A[yN-US |
|
DUKEENERGY
DRAWN BY: SoloCAD
10/10/2023
LINE DIAGRAM - PV05
STRING CALCULATIONS
STRING #1
STRING #2
STRING #3
MAX AC CURRENT:
12.10A
12.10A
10.89A
MICRO INVERTERS IN CIRCUIT
10
10
9
NOMINAL STRING VOLTAGE:
240V
240V
240V
MAX AC OUTPUT POWER
2900W
I 290OW
261OW
ARRAY DC POWER:
10585W
TOTAL MAX AC CURRENT:
35.09A
SYSTEM OCPD CALCULATIONS
INVERTER MODEL(S): ENPHASE IQ7PLUS-72-ACM-US
# OF INVERTERS: 29
MAX OUTPUT CURRENT: 1.21A
(# OF INVERTERS) X (MAX OUTPUT CURRENT) X 125% <= OCPD RATING
(29 X 1,21A X 1.25) = 44A <= SEA, OK
BUSBAR CALCULATIONS - 120% RULE
MAIN BUSBAR RATING: 200A
MAIN DISCONNECT RATING:
150A
NUMBER OF CURRENT CARRYING CONDUCTORS
PERCENT OF VALUES
4-6
.80
PV OCPD RATING:
50A
7-9
.70
(MAIN BUS RATING X 120%) - MAIN DISCONNECT RATING >= OCPD RATING
10-20
.50
(200A X 1.2) - 150A = 90A, >= 50A, OK
CONDUIT & CONDUCTOR SCHEDULE
TAG
QTY
WIRE GAUGE
DESCRIPTION
CONDUIT SIZE
CONDUCTOR RATING
CONDUCTOR TEMP. RATE
AMBIENTTEMP
TEMP. DEBATE
# OF CONDUCTORS
DERATE
CONDUCTOR RATING
W/DERATES
CONDUIT FILL
1
(2)
12-2
PV-WIRE, USE-2 COPPER - (LI, L2)
N/A - FREE AIR
30A
90°C
33°C
0.96
N/A - FREE AIR
28.8A
N/A - FREE AIR
(1)
6 AWG
BARE COPPER - (GROUND)
2
(2)
10 AWG
THHNITHWN-2 COPPER - (Ll, L2)
3/4" EMT
40A
90°C
33°C
0.96
1
38AA
11.9%
(1)
10 AWG
THWN-2 COPPER - (GROUND)
3
(6)
10 AWG
THHN/THWN-2 COPPER - (LI, L2)
3/4" EMT
40A
90°C
33°C
0.96
0.8
30.72A
27.8%
(1)
10 AWG
THWN-2 COPPER -(GROUND)
4
(3)
6 AWG
THWN-2 COPPER - (Ll, L2, NEUTRAL)
3/4" EMT
3/4
65A
75°C
33°C
0.94
1
61AA
32,6%
(1)
1 10 AWG
THWN-2 COPPER - (GROUND)
GROUNDING & GENERAL NOTES:
1. PV INVERTER IS UNGROUNDED, TRANSFORM ER -LESS TYPE.
2. DC GEC AND AC EGC TO BE SPLICED TO EXISTING ELECTRODE
3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE
INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION.
4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD -
JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS.
1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE DETERMINED IN ACCORDANCE WITH [NEC
705.121.
2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215,91, [NEC 230.95) AND [NEC 690.411
3. ALL EQUIPMENT TO BERATED FOR BACKFEEDING.
4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUSBAR RELATIVE TO THE MAIN BREAKER.
2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE -BREAK SWITCH
SAJ SOLAR
tip & -I WM -"M 1FAMMIM' 1140MIMIN
mw=�_ 1394smm
7r
SITE INFORMATION
MALIK MATEEN
8024 WHEAT STONE DR
ZEPHYRHILLS, FL 33540
AC SYSTEM SIZE: 8.41 KW AC
DC SYSTEM SIZE: 10.585 KW DC
LAT, 28.2748829
LONG, -82.1831958
(29) HANWHA Q.PEAK DUO BLK-GlO+/AC 365
PV MODULES
(29) ENPHASE IQ7PLUS-72-ACM-US
INVERTER(S)
DUKE ENERGY
DRAWN BY: SoloCAD
10/10/2023
ELECTRICAL CALCS - PV06
o s a •
TERMINALS i
» It I« « «:: » f i i f ' i
IN THE OPEN POSITION
11.21 h 0 « ■ «
SHALLMAIN SUPPLY OVERCURRENT
Il:
AMPACITY ; BUSBAR.
ii NOT RELOCATE
THIS OVERCURRNT ■
` i
f
LABEL 1
FOR PV DISCONNECTING MEANS WHERE THE LINE AND
LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN
POSITION.
[NEC 690.13(B)]
LABEL 2
PLACED ADJACENT TO THE BACK -FED BREAKER FROM
THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE
CONNECTION TO BUSBAR.
[NEC 705.12(8)(2)(3)(c)]
T
PLACED ADJACENT O BACK -FED
BREAKER—
FROMINVERTER CONSISTSOF i,w
SIDE CONNECTION TO BUSBAR.
• »
LABEL 4
EQUIPMENT CONTAINING OVERCURRENT
DEVICES IN CIRCUITS SUPPLYING POWER TO A
BUSBAR OR CONDUCTOR SUPPLIED FROM
MULTIPLE SOURCES SHALL BE MARKED TO
INDICATE THE PRESENCE OF ALL SOURCES
[NEC 705.12(B)(3)]
LABELS
AT POINT OF INTERCONNECTION, MARKED AT
AC DISCONNECTING MEANS.
[NEC 690.541
9
�BELIRG MOTES:
FIELD1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT
REQUIREMENTS IN THE PER i LOCAL CODESAND MAKE APPROPRIATE•..t
BASED2. LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI
3. MATERIAL ON w OF THE AUTHORITY. •
4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENTi
5. LABELS TO BE OF ON iBACKGROUND; i
PERMANENTLY AFFIXED [NEC •.
LABEL 6
AT DIRECT -CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND
ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED
AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS,
PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(G)(3&4)]
LABEL 7
#..
r is i i win' f'
• ; i w w' w •` •i
INDICATESHALL
• O OF i i RAPID SHUTDOWN
SWITCHES IF NOT AT THE SAME LOCATION.
TION
.w
SIGN LOCATED AT RAPID SHUT DOWN
t9 iI
COMBINERPV
i TO
COMBINECIRCUITS ' INVERTER AC DISCONNECT
MAIN SERVICE PANEL
EXISTING SUB PANEL
(ONLY IF WHERE POINT
OF INTERCONNECTION `✓
( IS MADE) } ❑ ❑
ti..:J �.J �.s�4 0 ❑ o
(ONLY IF PV
(ONLY IF PV
INTERCONNECTION
INTERCONNECTION
CONSISTS OF LOAD
CONSISTS OF LOAD
SIDE BREAKER)
SIDE BREAKER)
ilk laollqkTki In
SRT SOLAR
I
I �
SITE INFORMATION
MALIK MATEEN
8024 WHEAT STONE DR
ZEPHYRHILLS, FL 33540
AC SYSTEM SIZE: 8.41 KW AC
DC SYSTEM SIZE: 10.585 KW DC
LAT, 28.2748829
LONG,-82.1831958
(29) HANWHA Q.PEAK DUO BLK-G1O+/AC 365
PV MODULES
(29) ENPHASE IQ7PLUS-72-ACM-US
INVERTER(S)
DUKE ENERGY
DRAWN BY: SOIOCAD
10/10/2023
LABELS - PV07
c"AUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED
SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN:
RAPID SHUTDOWN AC
DISCONNECT SWITCH
MAIN DISTRIBUTION
UTILITY DISCONNECT
COMBINER
SUB PANEL
CEO z
PV ARRAY
8024 Wheat Stone Dr, Zephyrhills FL 33540
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE
SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM.
(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC
8024VvHEAFSTQmEum
3EPHYnH|LLS.pL33s4O
xCSYSTEM SIZE: 8.41mmA[
ocSYSTEM SIZE: I0.585KVm[
LAT, 28.I748839
u3WG.-D3.183l958
PV MODULES
INVERTER(S) 11
�
�
DUKEENERGY
DRAWN BY: SoloCAD
10/10/2023
SKY SOLAR
40417 CHANCEY RD #103
ZEPHYRHILLS FL, 33542
License #EC1 3010029
witalm
ZEURTNENTIT
8024 WHEAT STONE DR
ZEPHYRHILLS, FL 33540
AC SYSTEM SIZE: 8.41 KW AC
DC SYSTEM SIZE: 10.585 KW DC
LAT, 28.2748829
LONG, -82.1831958
(29) HANWHA Q.PEAK DUO BLK-GlO+/AC 3
PV MODULES
(29) ENPHASE IQ7PLUS-72-ACM-US
INVERTER(S) I
DUKE ENERGY
DRAWN BY: SoloCAD
10/10/2023
SITE PHOTOS - PV09
69 Rooftop arrays on
residential buildings
MECHANICAL SPECIFICATIONS
ronna't 67.6in x 41.1 in x 1.57in (including frame)
46.311ds(21.01<g)
cloct ccv�,, 0.13h (3.2mm) thermally pre -stressed glass i +
with anti -reflection technology
F rom Q. Black anodized aluminum
CeU 6 x 20 monocrystalline Q.ANTUM solar half cells
3,ry 209-3.98 x 1.26-2.36 x 0.59-0.71 in (53-101 x 32-60 x 15-18mm),
Protection class P67, with bypass diodes
CaN� 4MM2 Solar cable; (,) >45+3in (1150mm), H s33.5h (850mm)
comlloowr Staubli MCA; IP68
—A "d -near
AD OUTPUT ELECTRICAL CHARACTERISTICS
lQ7PLUS-72-ACM-US OR 107PLUS-72-E-ACM-US
P,8� OApul, Po.w [VA] 295 cD' Ci,,,it va,ft 5.8 Arms
"'Asrt. ccm` nuo,, O.Tpitt , Power [VA] 290 Max, Unim pa,� 20A,,L-L� -0,wa, CrrmAit 13
Nnrrilna' (LIQ Volt>age/qange IV] µ 240/211-264 ,wnitoge C'4s;>s AC Port III
pZj3R lea s Max- Conlmucus Gvtput Current [A] 1.21 AC Port i3pokfeed Current ISmA
'r ""c"'lner [Hzj 60 ,ver cior Sethnc 1
TOP RRMD PV
Extcmde'l -Mqu[Hzl 47-68 Pow_, Fac-,o, 0.85 leading 085 legging
SAM
2021
DC ELECTRICAL CHARACTERISTICS
USA Warranty 0 CELLS
Yi.,d SLrity POWER CLASS 360 365 360 366
Nfilfrv'rLikol PERF1'0r1MAir,,'C AT SIANDARDTEST C,-rVD9Tl0NS, 5-1C- tPOWER
Mn, P't Mpp- Pv11 Iwj 360 366 tviin, Cr,crtt,`, rrlofl, I— [A] 10.49 1C.56
sNu 11�07 rNn, VoPetro �1, M,5PP 34,31 34.58
"T cirroil far, [A] 11,04 V_ IV)
G,ANTUM TECHNOLOGY�, LOW LEVELIZED COST OF ELECTRICITY M�n. 0i 4118 4L21 -20.1 > 20.3
, I ocr, (_�,ccc Voftogw' V- IV] fill 1%]
Higher yield per surface area, lower BOS costs, higher !Measurement tolerances P ±3%: 1,, V� t5% at STC: 1000w/mr,25±2'C, AM 1+5 according to IEC 60904-3
power classes, and an efficiency rate of up to 20.6%. ------
Q CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE
INNOVATIVE ALL-WEATHER TECHNOLOGY Z ------------
1-1— 1 At least 98% of nominal F.werdudrig
Optimal yields, whatever the weather with excellent first year. Thereafter max. 0.5 %
degradation per year. At least 93.5
low -light and temperature behavior, ----------
of nominal power up to 10 years. At
least 86 % of nominal power up to
ENDURING HIGH PERFORMANCE b ---------- 25 years. ------ ----------------
Long-term yield security with Anti LID Technology, Anti PID All data within measurement tolerant,
Technology', Hot -Spot Protect, Traceable Quality Tra.QTm. es. Full warranties in accordance with 00 zea u
the warranty terms of the Q CELLS
c sales organisation of your respective
EXTREME WEATHER RATING country.
Typical module Performance under low irradiance conditions in
High-tech aluminum alloy frame, certified for comparison to STC conditions (25'C, 1000Vllm)
high snow (5400 Pa) and wind loads (4000 Pa).
TEMPERATURE COEFFICIENTS
A RELIABLE INVESTMENT 70 27
Inclusive 25-year product warranty and 25-year 'Ierfinamture Coefftciem of _, y [%/K] -0.34 No,.na.Mddule Ope,atinglo,pem:sre NMOT [*F] 109 5.4 (43 ± 3
linear performance warranty'.
PROPERTIES FOR DC SYSTEM DESIGN
STA7 E OF THE ART MODULE TECHNOLOGY , trio IVI 1000 oV Mcriuie, Ccal'lor, Class If
QLANTUM DUO Z Technology and the integrated high-powered
�,Aa.�mrn Svnea Fu�m PsTin" [A DC] 20 ire o g DP. S f I Ul- 61' 73 0 TYPE 2
Enphase IQ 7+ Microinverter achieving maximum system efficiency. Desipn Ld, [Ibs/W] 75 (3600 Pa) / 55 (2660 Pa) ?err . re It '1011, d; i ir, Ts,,,ic o r u m" -40'F up to +1857
o'n Cro"tirwD.S 0,uty (-40'C up to +85'C)
RELIABLE ENERGY MONITORING M a �, Te � t Do ad, Pc � h i Pu (lbs/ftg 113 (5400 Pa) / 84 1 a
I
Seamless management with the intelligent Enphase S.. I nstalation Manual
Enlighten"m monitoring system. QUALIFICATIONS AND CERTIFICATES
RAPID SHUTDOWN COMPLIANT
S.1,r module: UL 61730,
Built-in rapid shutdown with no additional components required. US, Peent N., 9,893.215(olar coos);
Enphase mlem 111ertar. UL 1741-SA, UL 62109-1,
UL1741/IEEE1547,FCC Pix1,15aa.B,
APT test conditions according to IEC/TS 62804-1:2015, method A (-1500V, 96h) ICES-0003 Class B,AN/CSA_C22.2 NO. 1071-01, C E
See data sheet on rear for further information Rapid Shudov,n O—Vient per NEC-2014
&2017&C221-2015
Note: Installation instructions must be followed. See the installation and operating manual or contact our technical service department for further information on approved installation and use
of this product.
Han7he 0 CELLS America Inc.
Engineered in Germany OCELLS 400Spechum Center Drive, Suite 1400, Irvine, CA 92618, USA I TEL +1949 748 59 96 1 EMML inquiryguso-celfaccrin I WEE www.q-ceIfr.us
Enphase sAlicroinverters
P A MPR C
10 Q + M 7
Enphase s' 11 icros
s y
for AC., Module
Applications
9
To learn more about Enphase offerings, visit enphase.com
Enphase IQ 7+ Microinverter for AC Module Application
INPUT DATA (DC)
107PLUS-72-ACM-US
Commonly used module pairings'
235 W- 440 W +
Module compatibility
60-cell and 72-cell PV modules
Maximum input DC voltage
60 V
Peak power tracking voltage
27V-45V
Operating range
16V-60V
Designed for AC Module (ACM) applications, the smart
Min/Max start voltage
22 V / 60 V
Max DO short circuit current (module Isc)
15 A
grid -ready Enphase IQ 7+ ACM MicroinverterTM is
Overvoltage class DC port
if
built on the latest technology from Enphase. The high
DC port backfeed under single fault
0 A
IQ Microinverters increase energy harvest
PV array configuration
1 x 1 ungrounded array; No additional DC side protection required;
performance
AC side protection requires max 20A per branch circuit
from PV modules while lowering system cost for
OUTPUT DATA (AC)
installers.
Peak output power
295 VA
Maximum continuous outputPower
290 VA
Part of the Enphase IQ System, the IQ 7+ ACM
Nominal (L-L) voltagerrange2
240 V / 211-264 V 20E V/ 183-229 V
microinverters are compatible with the Enphase IQ
Maximum continuous output current
240 V: 1.21 A 209 V: 1.39 A
Nominal frequency
60 Hz
Envoy" and Enphase Enlighten- monitoring and analysis
Extended frequency range
47 - 68 Hz
software.
AG short circuit fault current over 3 cycles
5,8 Arms
Maximum units per 20 A (L-L) branch circuit,
240 V: 13 208 V: 11
Enphase Microinverters set the highest benchmark in
Overvoltage class AC port
III
quality and reliability in the PV industry,
AC port backfeed current
0 A
Power factor setting
10
Power factor (adjustable)
0.85 leading ... 0,85 lagging
EFFICIENCY
@240 V @208 V
Easy to install CEC weighted efficiency 970% 970 %
MECHANICAL DATA
Microinverter pre -mounted on PV modules for easy transport
Ambient tern eratu pre range -400C to +650
and instal(C
Fast installation with Enphase Q Cable Relative humidity range 4% to 100% (condensing)
Connector type Integrated Enphase DC Connector
Built-in rapid shutdown compliant (NEC 2014, 2017 & 2020) Dimensions (WxHxD) r 212 mm x 175 rigor x 30.2 into without bracket)
Weight 92 kg (2,03 lbs)
Cooling Natural convection - No fans
Versatile and Reliable
Available through multiple module suppliers Pollution degree PD3
Optimized for high powered 60-cell and Enclosure Class If double -insulated, corrosion resistant polymeric,enclosure
72-cell modules Environmental category UV exposure rating NEMA Type 6 / outdoor
Adaptable for residential and commercial installations FEATURES
Works with tailless or traditional racking systems Power line
Class 11 double -insulated enclosure Monitoring Enlighten Manager and MyErilighten monitoring options
UL listed Compatible with Enphase IQ Envoy
Smart Grid Ready Compliance CA Rule 21 (UL 1741 -SA)
UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B,
Complies with fixed power factor, voltage and frequency ride- CAN/CSA-C22.2 NO, 1071-01
through requirements This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014, NEC
2017„ and NEC 2020 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV
Remotely updates to respond to changing Systems, for AC and DO conductors, when installed according manufacturer's instructions.
grid requirements
Configurable for varying grid profiles i. No enforced DC/AC ratio, See the compatibility calculator al . . . . . . . . .
Meets CA Rule 21 (UL 1741 -SA) 2. .Nominal voltage range can be extended beyond nominal if required bythe utility.
3. Limits may vary. Refertolocal requirements to define the number of microinverters per branch in your area.
ENPHASE, To learn more about Enphase offerings, visit enphase. com EN PHASE.
0, 2021 Eriphasc 7-no,gv, Al; rights rceerved. Enohase, the Enphase logo, Ennhose IQ 7*, Ennh_ase IQ Elsa er,', Enphase Enhghien, Enphase IQ
Err,,oy, andathe, traciefylanx,_ of :3ervice marnes are ?,he !,adernsrks of Ennhas& Energy, Inc. Data sibiec, Ocharge. 1 1-04`2(121
Data Sl-eel,
Enphase t etv,*rking
Combiner 4/4
X2-IQ- 3-240-4(iEEE 1547:2018)
LISTER
To learn more about Enphase offerings, visit gnphas,Coflri
I Q-C-4-4C-DS-0103-E N-US-12-29-2022
The IQ t"ornbirter /4C with IQ Gateway and
integrated t_T E-Mi1 cell modem (included
only with IQ Combiner 4C) consolidates
interconnection equipment into a single
enclosure, It Streamlines IQ Microlnverters and
storage installations by providing a consistent,
pre -wired solution for residential applications.
It offers up to four 2-pole input circuits and
Eaton BR series isuslaar assembly,
Includes IQ Gateway for communication and control
Includes Mobile Connect cellular modern
(CELLMCIDEM-M1-06-SP-05), included only with
IQ Combiner 4C
Includes solar shield to match Enphase IQ Battery
aesthetics and deflect heat
Supports Wi-Fl, Ethernet, or cellular connectivity
Optional AC receptacle available for PLC bridge
Provides production metering and consumption
monitoring
Simple
Mounts on single stud with centered brackets
Supports bottom, bade and side conduit entry
Allows up to four 2-pole branch circuits for 240VAC
plug-in breakers (not included)
30A total Psi or storage branch circuits
Durable NRTL-certified NEMA type 3R enclosure
Five-year limited warranty
Two years labor reimbursement program coverage
included for both the IQ Combiner SKU`s
UL listed
X2-IQ-AM1-240-4 and X2-IQ-AM1-240-4C comply with
IEEE 1547.2018 (UL 1741-SB, 3rd Ed,)
ENPHASE.
IQ Combiner 4C IQ Combiner 4C with IQ Gateway printed circuit board for integrated revenue grade PV production metering (ANSI C12.20 5 0.5%)
X-ICE-AMi i 240-4C and consumption rnontiorina, (s 2.5%). includes Mobile Connect celfufar modem (CELLMODEM-M 1-06-SP-05), a plug -and -play
X2-IQ-AM1-240-4C (IEEE 1547:2018) industrial -grade call modem for systems up fo 66 m€croirsverters. (Available in the US. Canada, Mexico, Puerto Rica, and me
L1S Virgin Islands, where there is adequate cellular service in the installation area) includes a silver solar shieldto match the
IQ Battery and IQ System Controller and to deflect heat.
ACCESSORIES AND REPLACEMENT PARTS (not included, order separately)
Communications Kit
CGts MS-CEl-i-MODEM-iv.1-05 - Includes GiOMMS-KIT-01 and CELLMQDEM-M?-66-SP-05 with 5-Year Sprint data plan
CELLMODEM-M1-06-SP-05 -4G based LTE-M7 cellular modern with 5-yearSprint data plan
CEL,€..MODEM-M1-06-AT-05 -4G based LTE-M7 Cellular modem With 5-year AT&T data plan
XA-SOLARSHIELD-ES Replacement solar shield for IQ Combiner 414C
XA-PLUG-120-3 Accessary receptacle for Power Line Carrier in IQ Combine( 4/4C (required for EPEC-01)
X-IQ-NA-HD-125A Hold-down k€t for Eaton circuit breaker with. screws
ELECTRICAL SPECIFICATIONS
System voltage
120/240VAC, 60 Hz
Eaton BR series busbar rating
125A
:
Max. continuous current rating
65R
Max, continuous current rating (input from PVfstdrag.:)
'.64A
Max. fuse/cIrcut rat€nc (output)
=90A
Branch circuits (solar and/or storage)
Up to four 2-pale Eaton BR series Distributed Generation (DG) breakers only (nest included)
..Max. total branch circuit breaker rating (input)
80A of distributed generation/95A with IQ Gateway breaker included
10 Gateway breaker
10A or ISA'rating GE/Siemens/Eaton included
Productionmetering CT
200A solid core pre-ins'miled and wired to IQ Gateway
MECHANICAL DATA
'weight 7.5 kg (16.5lbs)
Ambient temperature range 401G to + 61C (-401F to 115*F)
Coo€frig Natural convention, plus heat shield
Enclosure environmental rating Outdoor, N Tf-ter€'died,NEMAtype3;,polycarbonateconstruction
Wire sizes . 20A to 50A breaker inputs: 14to 4 AWG capper conductors
60A breaker branch input 4to 1/0 AWG copper conductors
Main lug combined output: 10 to 2/0 AWG copper conductors
Neutral and ground: 14to 1/0 copperco ,doctors
• Always follow local code requirements for conductor sizing.
Altitude Up to 3,00E meters (9,42 feet)
INTERNET CONNECTION OPTIONS
Cellular CELLMODEM-MI 06SP-05, CELLMDDEM-M1 C6-AT-05 (4G based LTEM1 cellular modem). Note that an Mobile Connect
cellular modem is required for all Enphase Energy System installations.
Compliance, IQ Gateway UL 60601-1/CANC;SA 22.2 No. 61010-1
2r122 En Energy. A,'! rights reserved. Erphpss the Errphase 'logo Q Comb ner 4.,AC, aid .,the. :a ::es are trademarks of
hp: a . Energy, ina C _a su. i ct .o charve. IC-C-4-4C-US-0103-EN-U5-12-29-2022
/ High quality, German -engineered system for residential and commercial installations
/ 4 rail sizes available to suit all structural conditions
Universal components for all rail types
Use 2 innovative components to turn this system into Shared Rail orTilt Up
MK3 technology provides highest rail engagement
Roof attachments for all roof types
100% code compliant, structural validation for all solar states
Fast installation with minimal component count result in tow total installed cost
In -Raft Wire Management
4 open channel rail types available
Wires help with clamps and wire management clips
3 clip types available
K2 Flesh Comp Kit Waterproofing
Water Shield redirects water away from penetration
K2 EverSeaL preassembled on L-Foot
EPDM backed sealing washing on tag screw
II
Components
i
CrossRail 8-
Part Number Description Part Number Description Part Number Description
-- _
4000019 CrossRail 44-X, 166", Mitt 1 4000662 CrossRalt 48 X, 166 , Mill 4000695 CrossRafl 46 XL, I66', Mill
_.._.._. ..........__........_............................................................................. _.._.--...................
4000020 CrossRail 44-X, 166", Dark 4000663 CrossRait 48-X, 166", Dark 4D00705 CrossRail 46-XL, 166", Dark
..._..__._____.—__.____..............__.............._......_._._....._....—i..--...._......._....................... ......................... _.................__.__.._.._..
4000021 CrossRaR 44-X, 180", MIU
4000022 CrossRait 44-X, 180", Dark
Part Plumber Descr's fen Pori Number Description
Part Umber Description
.... ...__.... ..._.... . _... _.. ...____._. ...._...._...... ..4000630 ........i L-Foot Slotted Set Mill .... ___
4000508 CrossRaft 80 168" Rail Mill l _
117
40DD156 ...._ K2 Flesh Comp Kit Mitt ..._.. ..__. .i
P
......._ .__._. __.. _�
4000631 L-Foot Slotted Set, Dark
4000157 K2 Flash Comp Kit, Dark
. _.__ .... ....... ...... ...... _......... _ _ _
4000080 T-Foot X 6" Kit, Mitt
_ _
4000218 Big Foot 6" w/3" + Chem Link CUP Kit
:.._..._.. __._i ..._....... ..........__._.. ........................._�
Tr
a
..mito
Splice Foot X & XL
-� Standard Tile Hooks
'a"
Para number ............Oesor€plain
Part Number ( Description
4000131 SpEfce Foot X, Set, MiU rSl TileHooks......____W._._...._. _____....._.-..
4000034 Fist Tile Hook Sat, w/Lags
4000162 Spice Foot XL, Sat, Mitt i__...___._._.._............
._---)
400129k Tito Hook 3S Wide Base w/Hard
4000115 Splice Foot Screw, m5x60IPart Number Description ware
4000140-B USH, 9", Bake Kit, w/Butyl 4000140 Unfversta! Stanched Hook 9" Base Kit
....................__.......__............................................
4000141-B Fiat Tile Hook X Kit, w/Butyl 4000141 Flat THe Hook X, Kit
i........... ......... ""'----}........_._... _................. _.._.....__.._----_.._._.._..---......
..._.._----.1
4000142 Universal Standard Hook +2, 5.5" Base, Kit
4000142-B USH +2, 5.5' Base Kit, w/Butyl :_._......__.................._..............................._.....:
rep
� w
Standing Seam PowerCLamps Corrugated Power Clamp, Kit Trapezoidal Power Clamp, Kit
................................................i _...._...._......._....-_ _.._..._..... _._.... --- _...._.._..--- - __._... _.l
Part Number Description ! Part Number Description Part Number Description
4000016 Standing Seam PowerClamp, Mini, Set 4000307 Corrugated PowerClamp, Kit ! 4000308 Trapezoidal PowerCtamp, Kit
!. 4000017 :Standing Seam PowerC(amp, Standard, Sat
Part Number Description
Part Number
Description',
Part Number.
Decor! ption
-
4000050 H Yeti Hidden EC for OR, 13mm Hex Sat
i
-
400060i H
......................................................
- 7 13
OR MC Silver, 30 4 mm, 13mm Hex
....
! 4000090
......................................
i C EC Sftver, 30- 0
R 4 mm
4000602-H
OR MC Dark, 30-47mm, 13mm Hex
4000091
OR EC Dark, 30-40mm
4000688-H
OR MC Silvan k0-50mm 93mm Hex
4000092
OR EC Silver, 40-47mm
4000689-H
OR MC Dark, 40-50mm, 13mm Hex
i 4000093
OR EC Dark, 40-47mm
s
4W
Bonding & Grounding
Part Number
Description
4000629-H
OR Microinverter & Opt, 13mm Hex Kit
4000006 H
Everest Ground Lug, 13mm Hex
4000083
MLPE, Module Frame Mount, Kit
Wire Management
y�.
CrossRaR Rail Connector
1 Part Number Description
.._...._ l _._._..._
4000059 Rail Connector OR 44-X, Set, Mitt
4000052 Raft Connector OR 44-X, Set, Dark �i;
4000365 RatICann CR48-X,48-XL Strad Set Mitt
......... ......... .._.._. _ _......__ .III
4000386 RaUConn CR48-X,48-XL Struct Set, Dark
4001196 Raft Conneoctor UL 2703 Set, CR80, Mitt
............._......._._...._...........__..............................................
MW
CR 48-X/48-XL Sleeve
.........
Part Number
...... .......... ... .............
Description
... ........ ....... ............. .._...._ .......__.....
Part Number Description
4000089
Wire Management CUP, TO
' 4000177 Sleeve OR 44-X
4000382
HEYCIi SunRunner Cable SUP SS S6404
P P
4000583 CrosiRail 3" Black Sleeve 48-X 46-XL
h 4005394
Wire Mangement CUP, Omega, Black
4
of
pc -
ON
MOIRMM��
4665 North Ave. Suite I - Oceanside, CA 92056 -
USA +1760.301.5300 - infous@k2-systems.com
www.k2-systems.com
CrossRaR System Data Sheet V10 10323 - Subject to change
Product illustrations are exemplary and may differ from the original.
Rail Shelf
€D Allows for easier rail support
® Aligns CrossRail T-bolt channel
rSl
� Pre -installed butyl flexible flashing
� 20+ years of proven water sealing technology
o TAS 1S[A and Wind Driven Fain tested and approved
Self -Fagging Screws
� Self-sealing, no sealant required
► Self -tapping, no pilot holes required
► 2 screws included per mount
Splice Foot X Er XL
Patent Pending
mart ?durrtree '� 6escriptlo�
4000113 Splice Foot X Kit,Mill
__.... _................ _;._........... ---........ _.._....._...--.... --........
.---..__
4000162 Splice Foot XL Kit, Mill
r All -in -one mount and splice foot
2 EverSeal technology
20+ years of proven eater sealing technology on asphalt
i, Self drilling lag screws = less tools needed
� Optimized for SrossRall systems and components
� No L-Foot needed
� T-Solt hardware included