HomeMy WebLinkAbout23-71545335 Eighth Street
Zephyrhills, FL 33542
Phone: (813) 780-0020
Fax: (813) 780-0021
ELCMISC-007154-2023
Issue Date: 11/06/2023
REINSPECTION FEES: (c) With respect to Reinspection fees will comply with Florida Statute 553.80(2)(c) the
local government shall impose a fee of four times the amount of the fee imposed for the initial inspection or
first reinspection, whichever is greater, for each subsequent reinspection.
Notice: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that
may be found in the public records of this county, and there may be additional permit required from other governmental
entities such as water management, state agencies or federal agencies.
M0133���
accordance with City Codes and Ordinances. NO OCCUPANCY BEFORE C.O.
NO OCCUPANCY BEFORE C.O.
CONTRACTOR SIG ATURE PE IT OFFICE
art ERMIT EXPIRES IN 6 MONTHS WITHOUT APPROVED INSPECTIO
CALL FOR INSPECTION - 8 HOUR NOTICE REQUIRED
PROTECT CARD FROM WEATHER I
813-780-0020 City of Zeptri%,hills Permit Application Fax-813-780-0021
BL,Iding Department
Date Received Phone Coufftactfor Permitiml It
it 4 0 a A If If I I
Owner's Name Owner Phone Number
Owner's Address Owner Phone Number
Fee Simple Titleholder Name Owner Phone Number
Fee Simple Titleholder Address
JOB ADDRESS LOT #
SUBDIVISION EL ID# 1CIO I�so
(OBTAINED FROM PROPERTY TAX NOTICE)
WORK PROPOSED
NEW CONSTR
ADDIALT
SIGN
DEMOLISH
E]
INSTALL
REPAIR
PROPOSED USE
SFR
COMM
OTHER
TYPE OF CONSTRUCTION
BLOCK
FRAME
STEEL
DESCRIPTION OF WORK
BUILDING SIZE = SQ FOOTAGE = HEIGHT [�T
EW_*L&k&kx41`srC%,t1t9k4LtkxILIL%,kJL tkkkx�
=BUILDING rF ---------------- I VALUATION OF TOTAL CONSTRUCTION
=ELECTRICAL
=PLUMBING
=MECHANICAL
AMP SERVICE PROGRESS ENERGY
VALUATION OF MECHANICAL INSTALLATION
=GAS ROOFING = SPECIALTY = OTHER
= W.R.E.C.
FINISHED FLOOR ELEVATIONS == FLOOD ZONE AREA =YES NO
BUILDER COMPANY E;;
SIGNATURE REG IS I FRF D ;;�rl: I . R R E
Address License #E==_==
E S Y/N F E URRN L 1 N
Address Licanse#
PLUMBER COMPANY E
SIGNATURE E:== REGISTERED Y i N �FCE GII�RRUI���
Address License #
MECHANICAL COMPANY
SIGNATURE �� REGISTERED
Address License #
OTHER COMPANY
SIGNATURE E= RECISIERED Y t N�Flzr lu�IIRFNY ! N���
Address License #
RESIDENTIAL Attach (2) Plot Plans: (2) sets of Building Plans: (1) set of Energy Forms; R-O-W Permit for now construction.
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans w/ Silt Fence installed,
Sanitary Facilities & 1 dumpster-1 Site Work, Permit for subdivisions/large projects
COMMERCIAL Attach (2) complete sets of Building Plans plus a Life Safety Page; (1) set of Energy Forms. R-CEW Permit for now construction.
Minimum ten (10) working days after submittal date. Required onsite, Construction Plans, Stormwater Plans w/ Silt Fence installed,
Sanitary Facilities & I dumpster. Site Work Permit for all new projects. All commercial requirements must meet compliance
SIGN PERMIT Attach (2) sets of Engineered Plans.
SURVEY required for all NEW construction.
Directions:
Fill out application completely.
Owner & Contractor sign back of application, notarized
If over $2500, a Notice of Commencement Is required. (NC upgrades over $7500)
- Agent (for the contractor) or Power of Attorney (for the owner) would be someone with notarized letter from owner authorizing same
OVER THE COUNTER PERMITTING (copy of contract required)
Reroofs if shingles Sewers Service Upgrades A/C Fences (Plot/Survey(Footage)
Driveways -Not over Counter if on public roadways -needs ROW
813-780-0020 City of Zephyrhills Permit Application Fax-813-780-0021
Building Department
NOTICE OF DEED RESTRICTIONS: The undersigned understands that this permit may be subject to 'deed" restrictions" which may be more restrictive
than County regulations. The undersigned assumes responsibility for compliance with any applicable deed restrictions.
UNLICENSED CONTRACTORS AND CONTRACTOR RESPONSIBILITIES: if the owner has hired a contractor or contractors to undertake work, they
may be required to be licensed in accordance with state and local regulations. If the contractor is not licensed as required by law, both the owner and
contractor may be cited for a misdemeanor violation Linder state law. If the owner or intended contractor are uncertain as to what licensing requirements
may apply for the intended work, they are advised to contact the Pasco County Building Inspection Division —licensing Section at 727-847- 8009.
Furthermore, it the owner has hired a contractor or contractors, he is advised to have the contractor(s) sign portions of the 'contractor Block' of this
application for which they will be responsible. If you, as the owner sign as the contractor, that may be an indication that he is not properly licensed and is
not entitled to permitting privileges in Pasco County.
TRANSPORTATION IMPACTIUTILITIES IMPACT AND RESOURCE RECOVERY FEES: The undersigned understands
that Transportation Impact Fees and Recourse Recovery Fees may apply to the construction of new buildings, change of use in existing buildings, at
expansion of existing buildings, as specified in Pasco County Ordinance number 89-07 and 90-07, as amended. The undersigned also understands, that
such fees, as may be due, will be identified at the time of permitting. It is further understood that Transportation Impact Fees and Resource Recovery
Fees must be paid prior to receiving a 'certificate of occupancy' or final power release. It the project does not involve a certificate of occupancy or final
power release, the fees must be paid prior to permit issuance. Furthermore, if Pasco County Water/Sewer Impact fees are due, they must be paid prior
to permit issuance in accordance with applicable Pasco County ordinances,
CONSTRUCTION LIEN LAW (Chapter 713, Florida Statutes, as amended): If valuation of work is $2,500.00 or more, I certify that 1, the applicant,
have been provided with a copy of the "Florida Construction Lien Law Homeowners Protection Guide' prepared by the Florida Department of
Agriculture and Consumer Affairs, If the applicant is someone other than the 'awrnae', I certify that I have obtained a copy of the above described
document and promise in good faith to deliver it to the "Owner' prior to commencement.
CONTRACTOR'SIOWNER'S AFFIDAVIT I codify that all the information in this application is accurate and that all work will be done in compliance with
all applicable laws regulating construction, zoning and land development. Application is hereby made to obtain a permit to do we* and installation as
indicated. I certify that no work or installation has commenced prior to issuance of a permit and that all work will be performed to meet standards ofall
laws regulating construction, County and City codes, zoning regulations, and land development regulations in the jurisdiction. I also certify that I
understand that the regulations of other government agencies may apply to the intended work, and that it is my responsibility to identify what actions I
must take to be in compliance. Such agencies include but are not limited to:
Department of Environmental Protection -Cypress Bayheads, Wetland Areas and Environmentally Sensitive
Lands, WaterNuestewater Treatment.
Southwest Florida Water Management District -Wells, Cypress Bayheads, Welland Areas, Altering
Watercourses.
Army Corps of Engineers -Seawalls, Docks, Navigable Waterways.
Department of Health & Rehabilitative Services/Environmental Health Unit -Wells, Wastewater Treatment,
Septic Tanks.
US Environmental Protection Agency -Asbestos abatement,
Federal Aviation Authority -Runways,
I understand that (be following restrictions apply to the use of fill
Use of fill is not allowed in Flood Zone 'V' unless expressly permitted.
If the fill material is to be used in Flood Zone "A", it is understood that a drainage plan addressing a
11 compensating volume" will be submitted at time of permitting which is prepared by a professional engineer
licensed by the State of Florida.
If the fill material is to be used in Flood Zone "A' in connection with a permitted building using stem wall
construction, I certify that fill will be used only to fill the area within the stem wall.
If fill material is to be used in any area, I certify that use of such fill will not adversely affect adjacent
properties. If use of fill is found to adversely affect adjacent properties, the owner may be cited for violating
the conditions of the building permit issued under the attached permit application, for lots less than one (1)
acre which are elevated by fill, an engineered drainage plan is required.
If I am the AGENT FOR THE OWNER, I promise in good faith to inform the owner of the permitting conditions set forth in this affidavit prior to
commencing construction. I understand that a separate permit may be required for electrical work, plumbing, signs, wells, pools, air conditioning, gas, or
other installations not specifically included in the application. A permit issued shall be construed to be a license to proceed with the work and not as
authority to violate, cancel, after, or set aside any provisions of the technical codes. nor shall issuance of a permit prevent the Building Official from
thereafter requiring a correction of errors in plans, construction or violations of any codes. Every permit issued shall become invalid unless the work
authorized by such permit is commenced within six months of permit issuance, or if work authorized by the permit is suspended or abandoned for a
period of six (6) months after the time the work is commenced. An extension may be requested, in writing, from the Building Official for a period not to
exceed ninety (90) days and will demonstrate justifiable cause for the extension. If work ceases for ninety (90) Consecutive days, the job is considered
abandoned.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT
to me or hasthave produced
as identification.
to me or
identification.
Plab
ol�
Commission L Commission
7N_
Name of Notary typed, printed or stamped
`iV "" R TARA N. DEVAULT
Commission # HH 143159
Expires June 22, 2025
Bonded Thru Troy Fain Insurance 800-385-7019
igi:]
Name ofNotary typed, -printed or -stamped
TARA N, DEVAULT
Commission # HH
Expires June 22, 2025
Bonded Thin Troy Fain Insurance 80045-7019
NEE:]
INSTR#2023184037OR BK10902PG2806 Page 1 of
10117/2023 09:55 AM Root: 2634867 Rec� 10,00 DS OrOO IT: 0.00
Nikki Alvarez-Sovilles, Esq., Pasco County Clerk & Comptroller
Permit No. Parcel ID No 5
NOTICE OF COMMENCEMENT
State of — County of
THE UNDERSIGNED hereby gives notice that improvement will be made to certain real property, and in accordance with Chapter 713, Florida Statutes,
the following information is provided in this Notice of Commencement
I Description of Property* Parcel Identification No, 3 -25-2 1 -0 1 )0- 17)_ IN
Street Address:
Z General Description of Improvement
Owner Information or Lessee information if the Lessee contracted W the Improvement
Name
_EL_
Address CRY State
Interest in Property:
Name of Fee Simple Titleholder
(if different from Owner listed
Address
4, Contractor:
Contractors Telephone No.: _� , �305
5, Barely:
CRY State
a
City State
Address
CRY State
Amount of Bond: S
Telephone No,:
6, Lender.
Name
Address
CRY State
Lender's Telephone No.:
7, Persons within the State of Florida designated by the owner upon whom notices or other documents may be served as provided by
Section 713,13tlua)(7); Florida Statutes:
Name
Address
CRY State
Telephone Number of Designated Person:
a In addition to himself, the owner designates
of
to receive a copy of the Lienor's Notice as provided in Section 713,13(1)(b), Florida Slatutes,
Telephone Number of Person or Entity Designated by Owner
9, Expiration date of Notice of Commencement (the expiration date may not be before the completion of construction and final payment to the
contractor, but will be one year from the date of recording unless a different date is specified):
WARNING TO OWNER: ANY PAYMENTS MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICE OF COMMENCEMENT
ARE CONSIDERED IMPROPER PAYMENTS UNDER CHAPTER 713, PART 1, SECTION 713.13, FLORIDA STATUTES, AND CAN
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY, A NOTICE OF COMMENCEMENT MUST BE
RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION, IF YOU INTEND TO OBTAIN FINANCING, CONSULT
NTH YOUR LENDER OR AN ATTORNEY BEFORE COMMENCING WORK OR RECORDING YOUR NOTICE OF COMMENCEMENT.
Under penafty of perjury, I declare that I have read the foregoing notice of commencement and that the facts stated therein are true to the best
of my knowledge and belief,
STATE OF FLORIDA
COUNTY OF 04Mv.
Seminole CocffttySignature of Owner or Lessee, or Owner's or Lessee's Authorized
Officer/Director/Pridner/Manager
Nylkia Santos
Signatory's Title/Office Nylkla Aydit Santos Soto
The foregoing instrument was acknowledged before me this 16th day of October
023
Owner as N/A (type of authority, officer, trustee, attorney in fact) for
Self (name off shelf whom instrument was executed).
Personally Known El QR Produced Identification ly Notary Signature
Type of Identification Produced Florida Driver License Name (Print) ?samara J G,�annelfi
X�QMARA J GIANNLLU
Notary Public - State of Fraud.
z
1� C—mission a HH'53
0
Expi,es on
-,K,f� all-,
A*qfr
wpdatalbcsinoticecoryimencemenLpc053048 Notarized online using audio -video communication
Attn: To Whom It May Concern
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of
the PV system to existing roof framing. From the field observation report, the roof is made of Composite
shingle roofing over 112 inch plywood supported by 2X4 Rafters at 24 inches The slope of the roof was
approximated to be 20 degrees.
After review of the field observation data and based on our structural capacity calculation, the existing roof
framing has been determined tobeadequate tosupport the imposed loads without structural upgrades.
Contractor shall verify that existing framing is consistent with the described above before install. Should they
find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity
calculations were done inaccordance with applicable building codes.
(ode 2O2OFlorida Building Code (AS[E7-16)
U Wind Load (component and Cladding)
Roof Dead Load Dr 10 psf V 140 mph
PV Dead Load DPV 3 psf Exposure B
Roof Live Lr 20 psf
Ground Snow, 5 Upd
Ifyou have any questions onthe above, please donot hesitate tucall,
Sincerely,OWUM
Vincent Mwumvaneza, 9.E
EVEngineering LLC
-Structural Letter for PV Installation
Scope of Work
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of
the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per
manufacturer's approved installation specifications.
Table ofContent
Sheet
Cover
Attachment checks
Roof Framing Check
Seismic Check and Scope ofwork
Code
ZO2UFlorida Bu
aLLgategory
U
Roof Dead Load
Dr
lO psf
yV Dead Load
DpV
3 psf
Roof Live Load
b
20psf
{round Snow_
5
Opsf
Wind Load
(component
and Cladding)
V
WAMmph
Exposure
8
References
Construc ion
Sincerely,
Vincent Mwumvaneza, PE
EVEngineering LL[
M V0111,111,141"
Kd =
0.85 ASCE 7-16 Table 26.6-1
Ke =
1.00 ASCE 7-16 Table 26.9-1
qh= 0.00256K,K,,KdK,V2 =
24.28 psf
Pitch
Degrees
YE—
'0
Ya
"0 "considering 1 module
�
MOMAW-1 Zone(l,Ze) Zone(Zr, 2n) Zone(3e) Zone(3r)
Fig, 30-3-2 GCP= -1.1 -2 -2 -2.4
Eq. 29.4-7 P=qh(GCP)(YE)(Y,,)= -16,03 -29.14 -29.14 -34.96
GCP= 0,5 Figure 30.3-2
P=qh(GCp)(YE)(YJ= 7.28 Equation 29.4-7
mom ENGINEERING
E V
Vertical Load Resisting System Design
Max Length, L=
8.0
Tributary Width, VVr=
24 in
Dr=
lO psf
20 p|f
L=
ZO psf
VVdo°"=
7.28 psf
14.6 p|f
Pv=
3 psf
6 p|f
Pvmax Shear=
10.5|bs
Max Moment, yW,=
255 lb-ft Conservative
Max Shear, V,=wL/2+Pv Point Load =
204 lb
Note: Proposed loading will add less than 596mfthe existing loads.
Member Capacity
Depth g=
3.5 |n
Width, b=
1.5 in
Crnsy Sec1ona|Area,A=
5.25 in
Moment ofInertia, |�=
535938 in
Section Modulus, S"=
3.0625 in
Allowable Moment, Mail =Fb'Sxx= 396.2|b-ft D[R=K8'AMall= 0.64<1
% or Roof with Pv
Dpv and Racking
.ncrease in Dead Load
The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
aTJr*MqFrtTI
-NYLKIA SANTOS. The analysis was according to applicable building codes, professional engineering and design
experience, opinions and judgments. The calculations produced for this structure's assessment are only for the
proposed solar panel installation referenced in the stamped plan set and were made according to generally
ie MEMMEIMM-E= �
SYSTEM DETAILS I
DESCRIPTION
F;YSTEM SI �8 100 KWDC STC
� . ;. � III # III
�4���,��
AC OUTPUT CUR ENT
i (20) HANWHA 0 CELL PEAK DUO BL.
ML-GlO+(405" SOLAR MODULES
ERTEPS
]VIC
'(2)
BRANCHES OF 10 MODULES
NYLKIA SANTOS
NEW GRID -INTERACTIVE PHOTOVOLTAIC SYSTEM
DC SYSTEM SIZE (8.10OKW)
DRIVEWAY
Lq
Co 18" SETBACK rl
co
c)
GOVERNING CODES U—i
I J
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)
FLORIDA BUILDING CODE, 7TH EDMON 2020 (FBC) J
coLORIDA _FRRE PREVENTION CODE, 7TH EDITION 2020 (FFPC) 36-SE-TBACK - 114'- 2
ROOF I
NATIONAL ELECTRICAL CODE, NEC 2017 CODE BOOK, NFPA 70 (N) PV ARRAY
SITE MAP (N.T.S)
VICINITY MAP
WIND FLOW MAP
GREEN
CONTACT: 1823) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
�—T_
z Z
z
I L I
PERMIT DEVELOPER
DATE--- - 09/27/2023 d
DESIGNER OSK
REVIEWER
SHEET NAME
SITE MAP [&l VICINITY MAP
SHEET NUMBER
A-00
MODULE TYPE, DIMENSIONS & WEIGHT
VNITMBER OF MODULES = 20 MODULES
MODULE TYPE = H!Nllfftw�- L PE.,%kft DLW*o)r�j"�4,#mv�
SOLAR MODULES
WEIGHT = 4&5 LBS / 22 KG.
MODULE DIMENSIONS = 74.0"X41 1 21.12 SF
(OUTSIDE HOUS
(N) AC DISCONNE I
(NON-FUSIBL
(OUTSIDE HOUS
(N) COMBINER PANE
(OUTSIDE HOUS
0
U 0
(D � (ID! 0- 10, 1 (D 10 1 (D 1 (D I (D
030 1@1(D02 IVQ)l@ l(DIVO
i
ROOF 1 (N) PV ARRAY
36"SETBACK
ROOF ACCESS POINT
NOTES:
1, LOCATION OF JUNCTION BOX(ES), AC
DISCONNECTS(S), AC COMBINER PANEL(S),
AND OTHER ELECTRICAL EQUIPMENT(S)
RELEVANT TO PV INSTALLATION SUBJECT TO
CHANGE BASED ON SITE CONDITIONS,
2, SETBACKS AT RIDGES CAN BE REDUCED TO
18 INCHES IN COMPLIANCE WITH FBC R 324.6,2:
TOTAL PLAN VIEW AREA ® 2512.26 SOFT
TOTAL PV AREA= 20(74,0 IN)(41,1 IN)/(144 IN A 2)
® 422.42 SQFT
(422.42 SQFT/ 2512.26 SQFT)100 = 16,81 %
TOTAL PV AREA POPULATES 16.81 % OF TOTAL
PLAN VIEW AREA AND IS WITHIN THE 33%
REQUIREMENT,
•
ig
TTIND ZONE 1: MAX SPAN 4'-0" OC.
WIND ZONE 2: MAX SPAN 4'-0" 0,C.
WIND ZONE 3: MAX SPAN 4'-0" OC
2) EXISTING RESIDENTIAL BUILDING ROOF WITH MEAN ROOF
MODULE STRING
( - MODULE STRING 2)
LEGENDS
I--, Lmi
- METER MAIN COMBO
[a],
- JUNCTION BOX
[Nq
- AC DISCONNECT
KP I
- COMBINER PANEL
- FIRE SETBACK
1
0
- STRING TAG
F---�
o
- VENT, ATTIC�AN
(ROOF OBSTRUCTION}
CONDUIT
GREEN
CONTACT: (813) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
ENGINEER Of RECORD
z
LZ � I
cn
PERMIT DEVELOPER
DATE 09/27/2023
DESIGNER 08K
rREVI.
SHEET NAME
ROOF PLAN
& MODULES
SHEET NUMBER
A-01
T77r7777777
ff ;••F #�l
MODULES - 20
ROOF TILT - 20*
ROOF AZIMUTH - 180*
RAFTF
c
tAWU4f
N \4 ..........
N0.6
ir Z
0 STATE OF
tORIVP N
N
..-G N
...........
'0 A L 0 - *--'
///// llxx XN
Exp. 02/28/2025
0 a 0
mc) 0 0 cl (D
0 4. 0 0 -ip 0
0
611-5111 -
ROOF #1
o
VMND LOAD INFORMATION
THIS SYSTEM HAS BEEN DESIGN TO MEET
THE REQUIREMENTS OF THE 7TH EDITION OF
THE FLORIDA BUILDING CODE AND USED
THE FOLLOWING DESIGN PARAMETERS:
ULTIMATE WIND SPEED: 140 MPH
EXPOSURE CATEGORY: B
RISK CATEGORY: 11
MEAN ROOF HEIGHT: 15 FT
ROOF SLOPE: 20'-27'
LEGENDS
FIRE SETBACK
0 VENT, ATTIC FAN
(ROOF OBSTRUCTION)
0 - PV ROOF ATTACHMENT
- 14'RAILS
- 7'RAILS
- 4* RAILS
10 - SPLICE BAR
- RAFTERS / TRUSSES
-METALSEAM
WIND ZONE 1
11 - WIND ZONE I
0 - WIND ZONE 1'
WIND ZONE 2
- WIND ZONE (2)
- WIND ZONE (2r)
- WIND ZONE (2e)
- WIND ZONE (2n)
WIND ZONE 3
El - WIND ZONE (3)
- WIND ZONE (3r)
- WIND ZONE (3e)
GREEN
CONTACT: (813) r.41-48W
4908 DENVER STREET, TAMpA,
FLORIDA 33619, UNITED STATES
+
2
w
F>r
mw I-
-PERMIT DEVELOPER
DATE 09.112023
DESIGNER OSK
REVIEWER
SHEET NAME
LAYOUT
SHEET NUMBER
S-01
PHOTOVOLTAIC MODULE GENERAL NOTES-
2. BOLT DIAMETER AND EMBEDMENT LENGTHS ARE DESIGNED PER NDS(2012)
REQUIREMENTS. ALL BOLT CAPACITIES ARE BASED ON A
WOOD ROOF TRUSS AS EMBEDMENT MATERIAL.
3. ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLE
RESIDENTIAL ROOFS, CONSIDERING FROM A A MAXIMUM 27-TO A
MAXIMUM 6/12 PITCH) ROOF IN SCHEDULE. ALL RESIDENTIAL ROOFS SHALL NOT
EXCEED 0" MEAN ROOF HEIGHT.
4ROOF SEALANTS SHALL CONFORM TO ASTM C920 AND ASTM 6511.
5. THIS SHEET REFLECTS STRUCTURAL CONNECTIONS ONLY. REFER TO
MANUFACTURERS'MANUAL FOR ALL ARCHITECTURAL, MECHANICAL,
ELECTRICAL, AND SOLAR SPECS,
6, ALL ALUMINUM COMPONENTS SHALL BE ANODIZED ALUMINUM 6105-T5 UNLESS
OTHERWISE NOTED.
7. LAG BOLTS SHALL BE ASTM A276 STAINLESS STEEL UNLESS OTHERWISE NOTED.
& ALL RAILING AND MODULES SHALL BE INSTALLED PER
MANUFACTURERS'INSTRUCTIONS.
mm
0
.............
lAWU4ft,///
No. 86986
0 STATE OF
�00
NAL
STRUCTU"RAL ATTACHMENT DETAILE�VG2/28/2025
tilo
GREEN
CONTACT: f813) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
ENGINEER OF RECORD
0
>
w
PERMIT DEVELOPER
DATE 09/27/2023
DESIGNER OSK
REVIEWER
SHEET NAME
STRUCTURAL
i ATTACHMENT
L DETAILS
F-,--
SHEET NUMBER
IL- S-02
EQUIPMENT SPECIFICATIONS
TAG
EQ1 j I Fit, I LEIN7N"I F2ESCRIPTI0N
HANWHA 0
_MODULES CELL PEAK DUO BLK ML-G-10+(405w) SOLAR MODULES
INVERTERJENPHASE108M-72-2-USMICROINVERTERS
JUNCTION BOX —T-606 VAEMA 3R —ULLISTED
COMBINER PANEL Ell
125A ENPHASE 10 COMBINER 4/4C
NECT (NON-FUSIl
PV YS M�
S TE DISCO
'SCO ol MM
ff�AC DISCONNECT PV SYSTEM DISCONNECT (NON -FUSIBLE)
Co CT
PV INTERCONNECTION BACKFEED BREAKER IN MMC
METER MAIN COMBO
NOTE,
CONDUITRI)N-EN17,1MC PVC,RMC FMC,LF?,AC OR EQUWALENTAS PER NEC,
CONDUIT SCHEDULE
TAG DESCRIPTION CONDUIT SIZE
ENPHASEQCABLES,(2)#12AWG THWN-2,(1)18AWG TH 2(G)
(2) #10 AWG THWN-2 (LI),(2) #10 AWG T-H'W-N-2 (1-2),
IN 3/4" CONDUIT RUN
3)N AWO. T 2 (1-1,1.2,N), (1) #10 AWG THVM-2 (G) 71'N,/4--CONDUITRUN
3)W#8 AWG TH 2(Ll,L2,N)(I)#IOAWG TH -2(G) --- --T--
IN 3/4' CONDUIT RUN
INTERCONNECTION
120% RULE -NEC 705A2(B)(2)(3)(b)
r--
UTILITY FEED - SOLAR BACKFEED
150A + 35A = 185 A
BUS RATING Y, 120%
L---n—m- 12n— 2B:IA
`1 i1 150A/2P C
2 L2 0
LI
N -
L
15A �G Ll
[L12y,
5A/2P
6D LI -'T'-
LL21
e
r E
N0.96359
2P
L
20A/2P
STATE OF
P2 0
R
rN
IG
I N G "T
!
NOTE:
1. SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE
REQUIREMENTS OF THE NEC 2017, NFPA 70 AND THOSE SET FORTH BY
THE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING
MAXIMUM NUMBER OF MODULE STRINGS, MAXIMUM NUMBER OF
MODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER
AND MODEL NUMBER, INVERTER MANUFACTURER AND MODEL
NUMBER, AS APPLICABLE,
2, PROVIDE TAP BOX IN COMPLIANCE WITH 31Z8 IF PANEL GUTTER
SPACE IS INADEQUATE,
SOLAR ARRAY (8.100 KW -DC STC)
(20) HANWHA 0 CELL PEAK DUO BLK
lML-010+(405VV) SOLAR MODULES
(2) BRANCHES OF 10MODULES
(E) BI-DIRECTIONAL
UTILITY METER
1-PHASE, 240V
(OUTSIDE HOUSE)
(E) METER MAIN COMBO PANEL,
225 RATED,240V
(OUTSIDE HOUSE)
(E) MAIN BREAKER
15OA/2P, 240V
199�k �
GREEN
CONTACT: (813) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
ENGINEER OF RECORD
-T
W
2
>
ul
J. PERMIT DEVELOPER
DATE 09127/2023
rDESIGNER OSK
REVIEWER
F- --SHEET NAME
ELECTRICAL
LINE DIAGRAM
i-- .-----j
IF - SHEET NUMBER
C—_ E-01
ELECTRICAL CALCULATIONS-
1. CURRENT CARRYING CONDUCTOR
CONDUIT INSTALLED AT • i INCHES ABOVE #
TEMPERATURE DERATE FACTOR - 0.96 ... NEC i t
CONDUCTOR AMPACITY
= (INV O/P CURRENT) x 1.25 / A.T.F / G.F ...NEC 690.8(B)
= [(10 x 1.35) x 1.25] / 0.96 / 0.
= 21.97 A
SELECTED CONDUCTOR - #10 THN-2 ...NEC 310.15(B)(16)
I p Ell 0 ME I mm 0 1 al mp, 4.
=(TOTAL INV O/P CURRENT) x 1.25 / 0.96 / 1 ...NEC 690.8(B)
=[(20x 1.35) x 1.25] /0.96 / 1
=35.16 A
SELECTED CONDUCTOR - #8 -2 ... NEC 310.15(B)(16)
2. PV OVER CURRENT " PROTE r ..NEC 690.9(B)
=TOTAL INVERTER O/P CURRENT x 1.25
=(20 x 1.35) x 1.25 = 33.75 A
SELECTED OCPD = 35A
SELECTED EQUIPMENT GROUNDCONDUCTOR
D1L��%,
No. 96359
STATE OF 1,
S/
LABELED1 ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND
FOR ITS APPLICATION.
2. ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90
DEGREE C WET ENVIRONMENT.THE TERMINALS ARE RATED FOR
DEGREE75
3. CONDUCTOR TERMINATION AND SPLICING AS PER NEC#
.14
4. WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS
SHALL BE ROUTED DIRECTLY # AND LOCATED AS •
POSSIBLE TO THE NEARESTRIDGE,a,
WORKING5. AROUND ALL r EXISTING
EQUIPMENTELECTRICAL #
s
SUPPORTS,. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.
CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,
# ACCESSORIES # FULFILL APPLICABLE
CODES# STANDARDS.
7. WHERE SIZES OF # BOXES,i CONDUITS
ARE NOT # THE CONTRACTOR SHALL SIZE THEM
ACCORDINGLY.
TERMINATIONS8. ALL WIRE s
# READILY
FRAME9. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
r MODULE SUPPORTGROUNDING
MANUFACTURER'SINSTRUCTION.
MODULE10. .. RAIL TOs BONDED TO CONTINUOUS
G.E.C. VIA WEEB LUG OR ILSCOGBL-4DBT LAY -IN LUG.
11. THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE.
12. UTILITY HAS 24-HR UNRESTRICTED ACCESS # ALL
PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE
13. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
14. RACKING CONFORMS # AND IS LISTED UNDER
15. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS
SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 AND ARTICLE
r #
16. CONDUCTORS EXPOSED TO WET LOCATIONS
#' s # 1r
JFACTURER ENPHI
a,
EL NO. # i
DC INPUT # .r
OUTPUT POWER 325
NAL AC OUTPUT VOLTAGEt#
! x
GREEN
CONTACT: (813)641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
ENGINEER OF RECORD
w - 7-
0
�_
Ii
to i
PERMIT DEVELOPER --�
DATE -09-----
*3rz7izoz
DESIGNER ( OSK
REVIEWER
SHEET NAME _+
WIRIl
j CALCULATIONS
�- SHEET NUMBER
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
LABEL LOCATION:
AD DISCONNECT- POINT OF INTrwRWQ2oTmoW"w,?.,
COMBINER PANEL
(PER CODE: NEC 690.13(B))
POWER SOURCE
71BEL LOCATION:
CONDUIT RUNWAY
IVII,BEL LOCATION:
MAIN SERVICE DISCONNECT
\oxjjillllIIIj////
Dzt�
E Nrr
No.96359
STATE OF I
OR VO.'
SIA. (o
I lilt
li lilt
AC DISCONNECT, INVERTER
(PER CODE: NEC 690,54)
Ity-ArAzi
LABEL LOCATION:
COMBINER PANEL, AC DISCONNECT
(PER CODE: NEC 690,52)
AlkKIIAWMIALOMMOMR! i
zraway
ff'kBEL LOCATIOA:
AD DISCONNECT, DC DISCONNECT, POINT OF
INTERCONNECTION
•
lamw "#-ArA.jjfjjj"m
NEC690.56(C)(1) AND NFPA -1 11.12.2,11.1.1,11.12,21A
BeM O.
W1,11 1:1191 Rimy--WI:11
NFPA-1 11,12.2.1,5
�ABEL LOCATION:
MAIN SERVICE PANEL, AC DISCOUVEC
LTHE MATEMAL USED FOR THE PHOTOVOLTAIC SYSTEM LABELS SIHALL BE
REFLEC-IVE, WEATHER RESi;TAN T, AND CONSTRUCTED OF DURABLE ADHESiVE
MATERIAL OR ANOTHER APPROVED MATERIAL SUITABLE FOR THE ENV1PONMEN1
IN Cr MPUANCE WITH NFPA 1 11,12.
2FONT, TEXT HUGHT, CAPITALIZATION, FONT COLOR(S), BACKGROUND
COLOR(S), DIAGRAM COLOR(S)AND CONTEXT OF PHOTOVOLTAIC SYSTEMS LABELS
SHALL COMPLY WITH NFPA 1-11.12 AND NEC 2017 690,56 AS APPLICABLE FOR
THE PHOTOVOLTAIC SYSTEM TO BE INSTALLED.
GREEN
CONTACT: (813) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
929E� �01
TIT
U) z
z 0
0 r-
>
w
> L 4--
PERMIT DEVELOPER
DATE 09/27/2023
D1.IGN.fRj OSK
REVIEWER
SH�EETNAME� _j:
SYSTEM
LABELING
SHEET NUMBER
E-03
C ... TFCMr0_0ey
MOO
MECHANICAL SPECiRCATi10N
74.0inx
I1879mrn. 1045m.m E2mml
46,5ibs(22,0 g)
+
iass.ili,
fim
Black anodized aluminum
6 x 22 rnon0crystaillrut Q.ANTUM sofa, halfpelts - -------- --------- "I - -
2.09-3,98ip x 1-26-2,36in CL9-Er7_tjr
(53101mm, 32-60mm x with bypass s5r0des
4mm2So4arcab�e;(+)s49,2in(1250m (-)49,2inlI250rpm)
Staubn MC4; lP68
Ct�
v, -
Quality
controlled PV ELECTRICAL CHARACTEMSTICS
POWER CLA--
SS
CLR
0
d
0 , 5 390 395 400 405
1],04 11,07 11,10 11,14 1117
[A]
""g,", IV, 45.19 45,23 4&27
45,30 4&34
I I L - 8 - 3 TOP sn"D FV 10,59 10,65 1071 1077
ivy 3&36 36.62 36,88
3713 37.39
19,6 19B Y201 204 �20,6
021
Wal"anty 0 CELLS 'M p IWI 1 2 1 8818
- ----- 292:6 296,3 300 1 303's
8,90 8.92 8,95 8.97 900
v1_ IVj 42,65 42,69
42.62
BREAKING THE 20 EFFICIENCY BARMEP 42,72 4Z76
't �V,
Q,ANTUM DUO Z Technology with zero gap call layout 8,35 841 846 8,51 857
V_
IV] 3459 3481 35.03 35,25 35,46
boosts module efficiency up to 20.9
a CELLS PERfORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE
THI
HOROUGH TESTING PROGRAMME 04 THE INDUSTICZY E hfi0ST T
Q CELLS is the first solar Module manufacturer to pass the ,cost COMprehen lesss 98% Of l,01mal P1 d
siliin the industry: The neQuality C'
6i�ve quality programme w "ontrolled PVof degf-d-, -,intt P,1 Y.,1, At toa,. 9_3 51/1,
the independent certification institute TUV Rheinland. p n m 1 P_ up n, la years, At ------ ------
25 yeas
INNOVATIVE ALL-VIEA7THER TFCHNOLOGY All data qnn
Optimal yields, whatever the weather With excellent F.it
low -light and temperature behavior. e v zrra 4r arms f t�, 0 CELS
ENDURiNG ' HIGH PERFORMANCE Typle d.J. T.,d j,nadI c0ndit.,S,,,
Long-term yod security with Anti LID Technology, Anti PID -pel-t. STC
Technology', TEMPERATURE COEFFICIENTS
Hot-SPOJ: Protect and Traceable Quality Tra,QTm.
1% KI V
!%/Kj NNIOT I'Fj' 109+54(43a3°C} EXTREME WEAFHER PATit4G
High-tech aluminum alloy frame, certified for
high snow (54001's) and wind loads (4000%). PROPERTilES FOR SYSTEM. DESIGN
C Class I
A RELIABLE iNVESTMENT JA Dq 20
TYPE 2
Inclusive 25-year product warranty and 25-year has/ft] 75 (3600Pa)/55 (2660pa)
-40 up to 185'p
linear performance warranty.A-, libs/111 1l3(54--00Pa)/84(4000Pa) (-40'C up to _85"C)
see r.t.41.1r
APT jEC/TS62804-1:2015.,Ie',,,,dA{-150OV,96b}
see aaia she.! h,' further QUALiFICA) "SONS AND CERTIFICA,"!ES PACKAGMG iNFORMA,710N
101, al rili"
-al " C", zlt�- IV TV 1't"j C
,FC u '1215 1201111 C
I N.
76A in 433 in 1656nta 24 24 32
Us 1940thm 1100mm 1220rrm 751 k9 oaPe-,s panels module
: $tal anon rIsrn,cls n"', be 10T..ed S T^e instsl-tiOn -1d opeeefTq na v o, contact fx, further irfcnmat*1 Ott app-o"Ied 'pstriflat and use x,
Hart- 0 CELLS Avlwh Inc.00ULSO' 400Specs Came, D, ive, Surte 1400. It,,-, CA92618, USA i TEL + 1949 748 59 95 EJOAM mq yp?u-. qall I Vyka
IWO
GREEN
CONTACT: (813) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
--Z
0
2
>
Lu
as
IX W
PERMIT DEVELOPER
DATE 09/27J2023
DESIGNER OSK
REAEWER
SHEET NAME
MODULE
DATASHEET
SHEET NUMBER
DS-01
In ENPHASE
Our newest 108 Microinverters are the industry's first microgrid-forming, software defined
microinverters with split -phase power conversion capability to convert DO power to AC
power efficiently. The brain of the semiconductor -based microinverter is out proprietary
application specific integrated circuit (ASIC) which enables the microinverter to operate in
grid -tied or off -grid modes. This chip is built in advanced 55nm technology with high speed
digital logic and has superfast response times to changing loads and grid events, alleviating
constraints on battery sizing for home energy systems.
Part of the Enphase Energy System, 108
Series Microinverters integrate with the
10 Battery, 10 Gateway, and the Enphase
App monitoring and analysis software,
Connect PV modules quickly and easily
to 108 Series Microinverters using the
included O-DCC-2 adapter cable with
plug-n-play MC4 connectors,
*oMy when imt-ged -'in 10 System Co-U-11s, Z meets UL 174L
'108M and 108A support Wn-ph, 24ov jnstwlet orgy,
JOB Series Microinverters redefine
reliability standards with more than one
million cumulative hours of power -on
testing, enabling an industry -leading
limited warranty of up to 25 years,
108 Series Microinverters are UL listed
as PV Rapid Shutdown Equipment and
conform with various regulations, when
installed according to manufacturer's
instructions.
0 2022 Enphase E..rijy. All rights d. Enph the Erphass;.g, boa
-ed -the, names are trade —As m Enphase E-19y, Inc oww t6jecr t. ehrge.
Easy to Install
Lightweight and compact with plug-n-
play connectors
Power Line Communication (PLC)
between components
Faster installation with simple two -wire
cabling
High productivity and rellatiffity
Produce power even when the grid is
down*
More than one million cumulative hours
of testing
Class 11 double -insulated enclosure
Optimized for the latest high-powered
PV modules
"a,•
foe Mcovvefters cannot be mbed together min
Pre're's R—abOns Of Enphase nrcroW-mns 007
Series, K)6 Saries, .1m) in the same systom,
108MA-12A-D,5-0069-03-EN-US-2022-12-27
1Q8M and JQ8A Microinverters
Commonly used module paldriV
W
260-460 295-500
Module compatibility
54-cell / 108 half -cell, 601-cell 120 half -cell, 66-cell 132 haff-cell and 72-cell / 144 half -cell
MPPT voltage range
Y
30-45 32-45
Operating range
v
16-58
Min, / Max- start voltage
V
22/58
Max. input DC voltage
Y
SO
Max, continuous input DC current
A
12
Max. input DC short-circuit current
A
25
Max module I�
A
20
Civervoitage class DC port
11
DC port backfead current
MA
0
PV array configuration
1 x I Ungrounded array; No additional DC side protection required; AC side protection requires max 20A per branch circuit
Peak output power
VA
330 366
Max, continuous output power
VA
325 349
Nominal (L-L) voltage / range'
V
2401211-264
Max. continuous output current
A
t35 1,45
Nominaffirequency
&
60
Extended frequency range
RZ
47-68
AC short circuit fault current over
3 cycles
Arms
2
Max. units per 20 A (L-L) branch circuit"
11
Total harmonic distortionrryr
Over,rottage class AC port
Ni
AC port backfeed current
mA
30
Power factor setting
70
Grid -tied power factor (adjustable)
0,85 leading - 0,85 lagging
Peak efficiency
ry
97-8 97.7
CEC weighted efficiency
%
97,5 97
Night-time Power consumption
mW
60
Ambient temperature range
-4(rC to +WC (-4(rF to 140'F)
Relative humidity range
4% to 1001/ (condensing)
DC Connector type
MC4
Dimensions tH X W A D)
212 mm (8.3") x 175 mm (6.9") x 3D.2 mm (11.21
Weight
LOS kg (2,38 lbs)
Cooling
Natural convection - no fans
Approved for wet locations
yes
Pollution degree
PD3
Enclosure
Class f1double-insuated, corrosion resistant polymeric enclosure
Envirun. category / UV exposure rating
NEMA Type 6 / outdoor
CA Rule 21 (UL 1741-SA), UL 62109-1, JEEE 1547:2018 (UL 1741-Sa 3`Ed.), FCC Pan 15 Class 8, ICES-0003 Class B, CAN / CSA-C222140,107,1-01
Certffications, This product Is UL Listed as PV Rapid Shutdown Equiponstnt and conforms with NEC 2014, NEC 2017, and NEC 2020 section 690,12 and C22J
2018 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed according to manufacturer's instructions,
(1) Railing PY .d.1- Mth ttage above the heft ..y —.It in additiorai clipping losses. see the coripsti.,iiity caicuiator w
(2) Nomraj -Ug- —9- — be sxtended bm-rd r-1r.i if required by the utgrty.
Limits may Limits vary. Refer to JOCxj requirements to define tire numberof IniCreirvertwe per branch inyour area. lQOMA-12A-DS-0059-03-EWUS-2022 -12-27
GREEN
CONTACT: (813)641-4880
4908 DERIVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
Uj
Z
Z 0
0 I=
Of
Uj 0
(a
0
Z
PERMIT DEVELOPER'
DATE 09/27/2023
DESIGNER OSK
REVIEWER
SHEET NAME
INVERTER
DATASHEET
F-SHEET -NUMBER
L DS-02
I
Ill "c3b p".,as'
r
Combioner 41 - CA 14(
X-IQ-AM1 -240-4
X-1Q-AM1-240-4C
Uffito X-40-Affill-240-4
To learn more about Enphase offerings, visit viriphAgg&Q_M
the Erlpriase !Q Cornbinet 4/4C with Frlphas-,
IQ Gateway and integrated LTE-Ml cell
modem (induded ortly with !Q Corribirier 4(1,)
consolidates interconnection equipment
jrlto a sinQle er-,,closrne and stiear-thries IQ
microinverters and storage installafions by
providmig a consisterit, pre wired solution for
,esid , i I i
ten applications It offers up to four
2-pole mPLJ1 CIrCUllS and Faton BP series
busbar asser-r-,,bly,
Includes. IQ Gateway for communication and control
Includes Enpirase Mobile Connect cellular modem
(CELL MODEtai-bill -06 SP-0,j), Included only torth IQ
Combiner 4C
Inciudes solar shield to oratch Eriphasy, IQ Battery
aesthetics and deflect heat
Flexible networking support-, Wi-Fi,
Ethernet, or tuellWa,
Optional AC receptacle available for PLC bridge
Provides production metering and consumption
Monitoring
111=11
Genlered mounting brackets support single
stud mounting
Supports bottron, back and side conduit entry
Up to four 2-pole branch circtli'ts fat 240 VAC
plug-in breakers (not included)
80A total PV Or storage branch circuits
Durable NRTL certified NEMA type 3R enclosure
Five-year firrivled warranty
Two years labor reirnbureentedi program coverage
included for both the IQ Combiner SKU*s
UL listed
HASE
Enphase IQ Combiner 4/4C
10 System Controger 2 arid lis deflect heat,
IQ Coprivnei 4C rilAQ-AMI 240 4C) IQ Greribiaer 4C with Enfireete 10 Gateway printed circut board for intaguared reverWe grade Pit pisducloan metering
(ANStC12,20+/-05r)ap.dconsu;r,ptior,monttorif�(+/-2.5a) lvchodes Enithase Mobil -Convect crdjuI r enx
(CEL LMODEM MI 06 Six 05), a plug -and -play JudUstrial-grave cell mad n n for syleserar up to 60 rnrcroinverfew
(Arousible in the US. Canada, k1swiro, Puerto Rico, and the US Virgin islands, where there is adearrarip radjulaf rearwe In
the installator, area.; Includes a silver sofa; shield to match the lQ Battery and is System Councier and to defiecl seat,
ACCESSORIES AND REPLACEMENT PARTS snot included,
V
C�ncdt breaker, 2 pole, IDA Eepon6ro!"O
Beri-I 5A -2 240V
Cucurt breaker, 2 pole, 15A, Eaton SP215
BRK-20A-2P-240V
Circuit breaker, 2 pole 20A, Faom BR220
BRK-I5A-2P-240V-B
Drcu;-, breaker, 2 pros, 15A, Eaton BR21,56 whir hole, down kit support
BRK-20A 2P 240V B
cinor it breaker, 2 pole, 20A, Eaton BR2208 with hold down. kq suroarst
Ept-C-01
Frower fine carrier ysorrimumeat.nal bridge parr), quantity - are pair
KA-SOLARSHIELD-ES
Fordacernent Solar shisid for 30 Combiner 4/4C
XA-PLUG-120-3
Accersox-yreceloacb, for parner Line Carrier !A IQ Crontan at 4141 (,r, qnrey for EPL-C- 01)
XA ENV PCBA 3
Rainlacerne'd in Gateway printed croui! waaId (PCs) fro Crtvicner 4/4C
X-rQ-NA-H0-J25A
Hold down kit far Eateg-, owivit Weaker hrhh scsovs,
luoirig
6"rntinuous duty
Sysson vortage
120/240 VAC, 60 H7
False So series tracker reaps
125 A
Moo
65A
may cons enurvis currern rating rinw'A forre Ptaxissage)
64A
Max fuso/circuit 'atrog ("r)Uunin
9018,
Branch vicrow (soho land/or storage)
Uptis four 2-pole Eator, PP, coned DrotributedGeneration (DG) breakers only (net tir,,judded)
Max unai brarwir ,arc., , iI rotIng hqpriu
80A of thstributed gerea-abon / 95A with, IQ Gateway b-leake, inchued
Enotreaker
10A or 15A rating GE/Surniens/Eaton incleryket
Plornichon meourng CT..
200 -4 soful cice pre Isuoud and wirrd p.) IQ Gateway
Consonantal, rnoriftoring CT In 7-200 SPLIT,
A, pan of 200 A splu crea current oarisforiners
MECHANICAL DATA
Dimenskuts trad-of,r),
37,5 Y, 49-5 x 16,8 ion (14.15"ir 195'x 6 63'). 4-reight is 21,06'(53 5 ctnt with nuountung brackets
aw�ghl
S
7 ktj l 16, 5 lbs)
Arri.bient temyrendwe rarow
-40" C' ,a +461 C (-ad- 1,- 115- F)
cooij"is
NaturaJ xonre0ron,plus heat shreid
Enclosure forwi,ouohmoil ratfrot
CruddoNRTL cartified, NENIA type 3R, polycarbonerte, cornowction
Wile sizes
20 Ato 50 A breaker mputs
60tibreakei-bran chinput 4101/jintoicaterarcoed uinaws
MainiuvicrantonedoutpW ',,Oto2/OAWGcoppEfcord ,,,jcio,s
Neutral and qmunu, 14 to 1/0 copper conductor,
Aiways follow localc de iequirionerits firf condurn-ir vorni
Alewde
'To 2000 meters (6,560 wet)
INTERNET CONNECTION OPTIONS
integrated Vid-Fi
Cellular
CELLMODEM-MI-06-SP 05,CELLIAODEM tut -06-AT-05 l4G based LTE-M.1 celione modem) Note chi; rrj Entorace
Mobile Con'rect (w1h anu modern is requeed for sit Erisoulep instalof! ns
Ethernet
optionei, 802,3, CaNsE (or (;ay: 6) UTP Ethernet cab (tort included)
COMPLIANCE
rooriterance, IQ Correrlef UL 3741, CAN/CSA C22,2 No, 1071, 47 CF-R, Part 15, Close 8, ICES 003
PokiduCtion nexterhac ANSI C12,20 sicesuracy class O-S fica larxxpjcbon;
COnaUltittyar neederinv accuracy class 2,5
Complarice, IQ Gateway 111 60601 -I/CANCSA 22 2 No 6'010 1
To learn more about Enphase offerings, visit g_npb HASE
_4se �om
GREEN
...............
CONTACT: (813) 641-4880
49M DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
z z
0
2
LL
X
fury I
ul
PERMIT DEVELOPER
DATE 09/27/2023
DESIGNER OSK
REVIEWER
F------SHEET NAME
COMBINER BOX
DATASHEET
I SHEET NUMBER
C DS-03
SOLARMOUNT
SOLARMOUNT defined the standard in solar racking. Features are designed to get installers off the roof
faster, Our grounding & bonding process eliminates copper wire and grounding straps to reduce costs.
Systems can be configured with standard or light rail to meet your design requirements at the lowest cost
possible. The superior aesthetics package provides a streamlined clean edge for enhanced curb appeal, with
no special brackets required for installation, ti
Now Featuring:
g
THE NEW FACE OF SOLAR RMIKINGi
-i i!,) e i o r A e s I h e ", i cs P ri C' - (D"
-4
LOSE ALL OF THE COPPER & LUGS SMALL IS THE NEXT NEW BIG THING ENHANCED OESIGN & 1AYOUT TOOLS
Systom gmefl(luig thrO* Iflabase Wmwrtm ad trw* cables Light Rail is Fully Compatible with all SM Compuflents Featuring Goggle Map Capabilities Withio U-8tulder
ar�'r��sr:rAr:riuraynas;�m;i�
N
GREEN
CONTACT: (813) 641-4880
4908 DENVER STREET, TAMPA,
FLORIDA 33619, UNITED STATES
ENGINEER OF RECORD
0 E—L U.)
C) C")
C-]
'z
< 0 LL
< --Jj
W
x
0
CO 0-
W
P- N
z 0
0
V)
LU ib j I
W
z
----------
PERMIT DEVELOPER
DATE 0911111023
DESIGNER OSK
REVIEMR
SHEET NAME
RACKING
DATASHEET
SHEET NUMBER
A
DS-09+
FLASNI_QC
"OUNIRAC
BETTER SOLAR STARTS HERE
FLASHLOC is the ultimate attachment for composition shiflgle and rolled comp roofs. The all -in -one mount installs
fast — no kneeling off hot roofs to install flashing, no prying or cutting shingles, no pulling nails, Simply drive the
lag bolt and inject sealant into the base. FLASHLOC's patented TRIPLE SEAL technology preserves the roof and
protects the penetration with a permanent pressure seal. Kfitted with lag bolts, sealant, and hardware for maximum
convenience. NO just divert water, LOC it out!
PROTECT THE ROOF
Mthoul lifting, vrrymg ot flamagmg sliiogies,
LOC OUT WATER
ii'lithan
arid-pressuired Sealant chamber lelile Iripff" i0c seal
dFlivers a 100% watefprouf cafelectimn
HIGH-SPEED INSTALL
Simply drwe lag LT11 ai-M, gqv,,q sealalit 1ptfj tlic, part In
10 C;evt?j a permanerit pressu,,, Seaj
FLASH LOC
INSTALLATION GUIDE
"OUNIRAC
BETTER SOLAR STARTS HERE
PRE -INSTALL
Snap chalk lines for attachnneirl rows, On shingle roofs, snap lines I 34. below upslope edge
of shjngke course, locate rafters and mark attachment localions.
At each location, drill a 7/32' 'Pilot hole, Clean roof surface of dirt, debris, snow, arld ice,
then fill pilot hole s6th sealant,
NO Tf: Space imounts per racking syslefil install SPecifications, When dovvni pressure is >34 psf,
span maY Pot exceed 2 ft.
STEP 1: SECURE
Place FIASHL10C ever Pilot fiole iqitj-{ lag on down -slope side, Align indicator frialks on sides of
rnount svt1h chalk. line. Pass included lag bolt and sealifig washer through FLASH! OC into pilot
hole. Drive lag bolt until u-jount is held firrifly bi place
NO - If: The FPDM in the sealing washer sdh expand beyond the edge of the metal -vjas#jcr wilsr!
limper torque is applied.
STEP 2: SEAL
insert tip of UNIRAC provided sealant into port, inject wrtfil sealant exits boll vents
Continue array installation, attaching raos to ruounts siah pmvided I bolts
ri()TftWhen FLASHLOC is installed ever gap belvveen shingle of tabs or veifical Joints
fill i � I
vAlh sealant b0ccen rnourlt annslone, (mwi iif ;mnuiF, rfm,,,zr-
Use only proMed sealant
GREEN
CONTACT: (813) 641-4880
4908 DENVER STREET, TAMPA,
FLORMA 33619, UNITED STATES
7
fl i
z zo
0
00
PERMIT DEVELOPER
DATE 09/27/2023
DESIGNER OSK
REVIEWER
SHEET NAME
ATTACH M NTJ
i L DATASHEET
SHEET NUMBER
DS-05