HomeMy WebLinkAbout01-0853
BUILDING PERMIT~2
0853
CITY OF ZEPHYRHILLS
(813) 788~6611
Permit
Date /;J-/~ -oj
~ E~AL PLU~ MECHANICAL
f1~'/1 ~ ~ :file.
Property Owner: ~ ~ ~ q(/tt/lR -' ( _
Job Address: :3&: _ _ ~_ ~
Parcell.D. #
Sewer Conn
Water Conn:
Water Meter:
T,I.F:s:
Zoning:
Description of Work
Energy Code:
floe- <)' o"'-.,,K/u-s
, - I
Radon Gas:
NO OCCUPANCY BEFORE C.O.
FINAL
DATE
Complete Plans, Specifications and Fee Must Accompany Application.
All work shall be performed in accordance with City Codes and Ordinances.
c.o.
DATE
Inspector
P~'mit Fe. I~
~,gnaM~
Compan
Address
,;>delePhone# ($/;) ;;&1?/- /35"7
ROc/a#} r; /e.t. S'hntlirs
Valuation or
Contract Price
~ ptJ
..:J 0, /XJo,.
/
-----"..
City license Registration # ~fi;
State Certified License#
Ftr.
Pre SLB
Lintel
FRM.
Insul. CL
WL
ELECTRICAL
Tp. Servo
Rough In
Meter Can
Const. Pole
Pool
Pre-
Final
SLB
Tub Set
Water
Sewer
Final
MECHANICAL
Breakers
Ducts Ins!.
Compressor
Final/ 3-- ') 7-0~
?~<513-:l-7--tJ0l-
-FD fJf~OI,'~~
Driveway
REINSPECTION FEES: When extra inspection trips are necessary due to anyone of the following reasons, a
charge of Twenty Five and 00/100 Dollars ($25.00) shall be made for each trip for each trade:
a. Wrong Address
b. Condemned work resulting from faulty construction.
C. Repairs or corrections not made when inspection called.
d. Work not ready for inspection when called.
e. Permit not posted on job site.
f. Plans not at job site.
g. Work not accessible.
The payment of inspection fees shall be made before any further permits will be issued to the person owning
same.
~~ f~M y( ~ 1)?g~
APPLICATIO~ FOR PERKIT
CITY OF L:.RPIIYRHIUS
BUILDING DEPARJ1tIEIlT
FW~DA M.W'~ (l..INlG-
~Ltl tR SD'
OWER'S RAKE tM(' ~ 'JG~ I \~.;. PIlOn
OWNER'S ADDRESS ;~\~? ~U,I '-:i1..V~ ~~1*t~ ,f=L 33SttD
.JOB ADDRESS ~~~ M~:f' lflu~
LEGAL DESCRIPTIOlM: LDI'(S) 01-" BLOCK Un SUBDIVISIOlM-Z-1
PARCEL LD.' D1~'t{, ~z"l- DOl D - O'J,q W:.. 0030
WORK PROPOSED:_8ew Construction _Addition
/' Alteration
_Repair
_Install
_Sign
_Hove
_Deaolish
PROPOSED USE:
Single Faaily
__KIF
_, of' Units
_K/H
_~rcia1
_Indust.
_S~. Pool
Other'~
_Rest:aurant & Hea1t:h Depart:.ent Approval
BUILDING SIZE:
x
Square Feet,
Height
RESIDENTIAL :
COHKERCIAL :
A'ITAGH (2) PLOI' PLAliS 5: (2) SEIS OF BUII.DDiG PLAliS 5: (1) SEI' ENERGY FOm,5. *.,...; V
ATTACH (3) SEIS OF BUII.DDilG PLAliS 5: (1) SEI' mmRGY FORKS.*:ll- ----(p ~ r
"CUPl' OF CUllTRACT -~ 1\!<lIlIF.STED d ryT--' ,D I
1'J'~H9
W. R .'.~--=--SJ
_BUILDING
$
Valuation of' Tot:a1 Construct'
_ELECTRICAL
/ ~~ f1~.
_MECHANICAl.
AKP Service
Florida Power Cbrp.
$ '7010W.OO
VaIuation of' Kechanica1 Inst:allation
_PLUMBING GAS ROOFDiG
SPECIALTY
TYPE OF CONSTRUCTI08: _Block _Fraae _Steel
Other
FTIiISHED FLOOR ELEVATIONS: ~ . IS PBOJECT IN FLOOD ZONE AREA? ~
*****ititititititit**ititit*it-&-itit*it***itit***it**CJit;;;a** ~ ~ 1 ~ ~1
~/~ tt.?-l ,-
COn'RACTOR SECTION ~~ ~
CO!fPANY
St:ate Cert:. or Regist:. 41
City License Registration ,
itititititit*ititit***itit**itit*it*******itit***itititit**it*:ll-
BUILDEIl
Signature
ELECTRICIAN
COIiPAlNIY
State Cert. or Regist. ,
SiPIi.;4i.U..f..~
~.~-~- T -=~:":;~_::: R.cg:!.~~-r:1""'i~"),-"" f
*it*ititit****ititititititit*~*ititititit*it***it*it**itit****
PLUMBER
CO!tPARY
St:ate Cert. or Regist:. 4tF
City License Registration f
******it****it***ititititit:ll-it*itit************itit*it*
Signature
PtEClIAliICAL CO!fPAlNIYJoo~ f1 ~ 0ffLt tJ \'-t.i~ I \ NL
~ /} ~ State Cert, or RegisL # ~~'f"'UlOClI'l1
Signature . ,_ City License Registration I {g .
it*it*it*it*itit*"'*',.:-....it**itititit*****itit*****itit**ititit:ll- ~ 1-
0"I'1IF.R CO!tPAlNIY
St:ate Cert. or Regist. j
Signature City License Registration ,
it*it*itit***it*it*it:ll-ititit*it****it****itit**itit*******
APPLIGATIOR APPROVED BY PERKIT OFFICER.
/ '~,
-~,
---
r~---
CONDITIONS uF PERMIT AFFIDAVIT
'A. ~OTICE OF DEED RESTRICTIONS
The undersigned understands that this per.it '.ay ~~ ~ubject to "de~d restrictions" which .ay be .cre restrictive than City
regulations. The undersigned assu.es responsinility for co.pliancf. with any applicable deed restrictions.
B. UNLICENSED CONTRACTOR~ AND CONTRACTOR RESPONSIBILITIES
If the owner has hired a contract~r or,contractors to undertake work, they .ay be required to be licensed in accordance with
state and local regulations. If the contractur ~s n~t licensp.d as required by law, both the owner and contractor .ay be
cited for a .isde.eanor violation under state la.'. if t.he owner or intended contractor are uncertain as to what licensing
require.ents .ay apply for the intended work, the] are advised to contact the City of 2ephyrhills Building Depart.ent, (813)
788-6611.
Further.ore, if the owner has hired a contractor or contractors, he is advised to have the contractor{s) sign portions of the
"Contractor Sections" of this application for whic~ they will be responsible. If you, as the owner sign as the contractor,
you are indicating that you, rather than the contriCtor, are responsible for the work. If the contractor wishes you to sign
as contractor that .ay be an indication that he is not properly licensed and is not entitled to per.itting privileges in the
City of Zephyrhills.
C. TRANSPORTATION IMPACT FEES AND UTILITY CONNECTION FEES
D. CONSTRUCTION LIEN LAW (CHAPTER 713, FLORIDA STATUTES, AS AMENDED)
I certify that I, the applicant, have been provided with a copy of "Florida's Construction Lien LaN - Ho.eowner's Protection
Guide" prepared by the Florida Depart.ent of Agriculture and Consu.er Affairs. If the applicant is so.eone other than the
"owner", I certify that I have obtained a copy of the above described document and prolise in good faith to deliver it to the
"owner" prior to co..ence.ent.
E. CONTRACTOR'S/OWNER'S AFFIDAVIT
I certify that all the infor.ation in this application is accurate and that all work will be done in co.pliance with all
applicable laMS regulating construction, zoning, 'and land develop.ent.
Application is hereby .ade to obtain a per.it to do work and installation as indicated. I certify that no Nork or
installation has co..enced prior to issuance of a p~r.it and that all Nork will be perfor.ed to .eet standards of all laNS
regulating construction, City codes, zoning regulations, and land develop.ent regulations in the jurisdiction. I also
certify that I understand that the regulations of other governmental agencies .ay apply to the intended work, and that it is
.y responsibility to identify Nhat actions I .ust take to be in co.pliance. Such agencies include but are not li.ited to:
f Depart.ent of Environ.ental ReQulation - Cypress B~yheads, Wetland Areas and Environ.entally Sensitive Lands,
~~ter/Wastewater Treataent
f Southwest Florida Water ManaQe.ent t:~'rift - Wells, Cypress Bayheads, Wetland Areas, Altering Watercourses
f Aray Corps of EnQineers - Seawalls, Docks, Navigable Waterways .
. Depart.ent of Health ~ Rehabilitative Services, Environaental Health Unit - Wells, Wastewater Treatlent, Septic Tanks
f US Environaental Protection AQency - Asbestos abate.ent
I also certify that, if fill .aterial is to be used in Flood 20ne "A" or "A,etc.", it is understood that a drainage plan
addressing a "colpensating volu.e" Nill be sub.itted which is prepared by a professional engineer registered in the State of
Florida prior to per.it issuance.
A per.it issued shall be construed to be a license to proceed with the Nork and not as authority to violate, cancel alter, or
set aside any provisions of the technical codes, nor shall issuance of a per.it prevent the Building Official frol thereafter
requiring a correction of errors in plans, construction, or violations of any code. Every perlit issued shall beco.e invalid
unless the Nork authorized by such per.it is cO'lenc~d within six .onths of issuance, or if Nork authorized by the per.it is
suspended Dr abandoned for a period of six .onths after the ti.e the work is cosienced. One 90 day extension of tile, .ay be
allowed,for the per.it with fee charge of $IS.00. The extension shall be requested in writing to the Building Official. An
approved inspection lust be logged during each six month period, or the project will be considered abandoned.
WQRNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR
PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF
COMMENCEMENT. JOBS UNDER $2,500 IN VALUE DO NOT NEED TO HECORD AND POST A "NOTICE OF COMMENCEMENT".
SIGNATURE: OWNER OR RSENT . ~~NT~~T~
was acknowledged
19_ by
STATE OF FLORIDA I
COUNTY OF ~ \ 1~\:;YJYl)\M. h
The foregoing instrJment was acknowledged
befcl\-e me th i s ~. DeC. , -+9-1QQJ.. by
':::>err"f ~YYD vV
who is personally known to me Dr who has
produced
as identification and who did/did not
take.S\tilAtJjtb/\
(Signature)
STATE O~ FLORIDA
COUNTY OF
The foregoing instrument
befc.re me this
who is personally known to me Dr who has
produced
as identification and who did/did not
take an oath.
(Signature)
(Name Typed, Printed or Stamped)
NOTARY PUBLIC
",,,'",,,, Tracie Keeter
,,';.o.y P(j",,'. DO 055811"
!~Jt~~co~n# ~
:Z{ r:-: Expires Sep. 10,2005
~~'" '7&$ Bonded 11uu
.-,;;r iirf\; ,,~ Atld1ltic Bonding Co., Inc.
",n"\
(Name Typed, Printed or Stamped)
NOTARY PUBLIC
II
. . . Fire Protection by Computer Design
RODAN FIRE SPRINKLERS INC.
2501 NORTH 70TH STREET
FAX- 1-813-628-0143
TAMPA FLORIDA 33619
813-621-1357
Job Name
Building
Location
System
Contract
Data File
FLA MED CLINIC - O.H./MEZZ.
OLD PUBLIX STORE - REMODEL TO CLINIC
38135 MARKET SQUARE. ZEPHYRHILLS. FLORIDA
ONE ( 6" )
SO 41650
S041650.WX1
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC.
FLA MED CLINIC - O.H./MEZZ.
Page 2
Date
Hydraulic Design Information Sheet
Date - 11-26-01
Name - FLORIDA MEDICAL CLINIC
Location - 38135 MARKET SQUARE, ZEPHYRHILLS, FLORIDA
Building - OLD PUBLIX STORE - REMODEL TO CLINIC
Contractor - RODAN FIRE SPRINKLERS, INC.
Calculated By - CHET SECKMAN
Construction: ( ) Combustible (X) Non-Combustible
Occupancy - NFPA 13 STAMDARDS - ORDINARY HAZARD GROUP
System No. - ONE (6")
Contract No. - SO 41650
Drawing No. - 3 OF 3
Ceiling Height - 19-4
II OCCUPANCY
S
Y
S
T
E
M
(X) NFPA 13 Lt. Haz. Ord.Haz.Gp. ( ) 1 (X) 2 ( ) 3 ( ) Ex.Haz.
( ) NFPA 231 NFPA 231C ( ) Figure Curve
Other
Specific Ruling PARAGRAPH: 7-2.3.2.4 Made By NFPA 13 Date 1999EDITION
o
E
S
I
G
N
Area of Sprinkler Operation - 900
Density - .20
Area Per Sprinkler - 100 MAX
Elevation at Highest Outlet - 9FT AFF
Hose Allowance - Inside - - 0 -
Rack Sprinkler Allowance - N/A
Hose Allowance - Outside - 250
System Type
(X) Wet
( ) Dry
( ) Deluge
( ) preaction
( ) Other
Sprinkler/Nozzle
Make. GLOBE, Q. RES
Model "J", CH REC
Size 1/2"
K-Factor 5.6
Temp.Rat.155
Note 462.19 GPM DEMAND IS 7.193 PSI UNDER THE WATER SUPPLY CURVE
Cal.culation
Summary
Flow Required - 462.19 Press Required - 49.407 At Test
C-Factor Used: 120 Overhead 150 Underground
Pump Data:
W
A
T
E
R
S
U
P
P-
L
Y
C
0
M
M
S R
T A
0 C
R K
A
G
E
Water Flow Test:
Date of Test - EARLY 2001
Tj.me of Test
Static Press
Residual Press
Flow
Elevation
Rated Cap.-
@ Press
Elev.
- 58
- 50
- 1186
- 2
Tank or Reservoir:
Cap. -
Elev.-
Well
Proof Flow
Location - FLOW HYDRANT NO. 8118. RESIDUAL HYDRANT NO. 8117. ON 8" MAIN ON,
ON NORTH SIDE OF BUILDING
Source of Information - CITY OF ZEPHYRHILLS. FLORIDA
FIRE DEPARTMENT. CAPT. GWYN
CommOdity
Storage Ht.
Storage Method:
Solid Piled
Class
Area
%
Location
Aisle W.
Palletized %
Rack
Single Row
Double Row
Mult. Row
Conven. Pallet
Slave Pallet
( ) Auto. Storage
( ) Solid Shelf
( ) Open Shelf
Encap.
Non
Flue Spacing
Longitudinal
Clearance:Storage to Ceiling
Transverse
Horizontal Barriers Provided:
Computer Programs by Hydratec Inc.
Route III
Windham N.H. USA 03087
('I')
Q) Q)
O\+J
ctl ctl
0.. 0 ctl
+J
ctl,
o
0-
S
0..
H
Ul H -
p., Ul
~~~p.,
r-p.,p.,p.,
~0l9l9l9('f)
Hp.,'<I' 0'1
Ull9 '000'l.-l
p., 0'1.. Lf).-l .
O'I'<I'_N'r-
Lf) .-l .. N
'<I' '.'>,_\0
'<I'NQ).jJ '<1'..
..-l H'rl '0 .. C
CD N ;::l U C '0 .rl
.. (/] ctlCtJ>
:3: (/]'n f:: ctl H
.. 0 Q)'OQ)f::ctl
@~~~O~~
-rl ~ ~ >, -
.jJf::f:: f::.jJ
ctlQ)Q)Q)Q)Q)Q)
>+J+J(/](/]+J4-l
Q) (/] (/] 0 0 (/] ctl
r-l >, >':r: :r: >, Ul
rilUlUl Ul
, I I I I
r-lNN ('f)
000 0
-
-
N
U
-
.
-
-
-
('f)
0
N
0 ~ -
~
I I , I ,
H
Ul
Ho..::E:
Ul 0..
l:..::J 0..0l9
u l:..::J Lf)
Z ril CD \D
H ::E: Lf)..CD
'- (IJr-l
Ul H.-l
p:: :r: (IJ ;::l
ril >, H (/] ..
o-:l 0 r-l ;::l (/] 3:
:.:: 0- (/] (IJ 0
Z 0- (/]Hr-l
H ;::l (IJo..rz..
p:: u Ul H
0.. H o..r-lr-l
Ul Z H ctl ctl
H (IJ U ;::l;::l
J:il o-:l +J -rl '0 '0
p:: u ctl +J -rl -rl
H ~ ctl (/] (/]
rz.. 0 +J(IJ(IJ
ril >, UlP::P::
Z ~ +J I I I
~ -rl .-lNN
~ U UUU
0 o-:l
p::; rz..
o
Lf)
.-l
o
'<I'
.-l
o
('f)
.-l
o
N
.-l
o
.-l
.-l
o
o
.-l
o
0'1
o
CD
o
r-
o
\D
o
Lf)
o
'<I'
o
('f)
o
N
o
.-l
p.,
P::
ril
Ul
Ul
t:l
p::;
ril
o
o
CD
.-l
o
o
\D
.-l
r-
CD
E4 0
fI) l"I
~ 0
111
<Il <Il ~l ,:l;
0> .jJ CI)
III III ::J
p., Cl
:r:
z
0 @
~l .c:
'0
~
.~
~
III rl
~l rl
rl
<Il
.jJ
::l
0
p::
I(
~l u
~
H
U
N <Il
U N +J
Z ~ gj n:l
H ~ !-I
"- '0
CI) ~l :>.
p:: :r: :r:
~
H 0 :>.
:>::: .0
Z I
H f/l
p:: u E:
p., H ~ n:l
CI) Z !-I
H 0>
~ H ~l 0
p:: U !-I
H p.,
[z., Cl
~ !-I
Z ~ Q)
~ ,:l; .jJ
::l
0 H Q\ ~
ex; [z.,
<'l 0
U
RODAN FIRE SPRINKLERS INC.
FLA MED CLINIC - O.H./MEZZ.
Page 6
Date
Fitting Legend
Abbrev.
Name
A
B
C
D
E
F
G
K
L
M
Q
S
T
W
Z
Computer Programs by Hydratec Inc.
Generic Alarm Va
Generic Butterfly Valve
Roll Groove Coupling
Dry Pipe Valve
90' Standard Elbow
45' Elbow
Gate Valve
Detector Check Valve
Long Turn Elbow
Medium Turn Elbow
Flow Control Valve
Swing Check Valve
90' Flow thru Tee
Wafer Check Valve
Flow Switch
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 7
FLA MED CLINIC - O.H./MEZZ. Date
Unadjusted Fittings Table
1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4
A 7.7 21.5 17 .0
B 7 10 12
C 1 1 1 1 1 1 1 1 1 1
D 9.5 17 28
E 2 2 2 3 4 5 6 7 8 10
F 1 1 1 1 2 2 3 3 3 4
G 1 1 1 1 2
K 14 14
L 1 1 2 2 2 3 4 5 5 6
M 2 2 3 3 4 5 6 6 8
Q 18 29 35
S 4 5 5 7 9 11 14 16 19 22
T 3 4 5 6 8 10 12 15 17 20
w 10.3
z 2 2 2 3 4 5 6 7 8 10
5 6 8 10 12 14 16 18 20 24
A 17 27 29
B 9 10 12 19 21
C 1 1 1 1 1 1 1 1 1 1
D 47
E 12 14 18 22 27 35 40 45 50 61
F 5 7 9 11 13 17 19 21 24 28
G 2 3 4 5 6 7 8 10 11 13
K 36 55 45
L 8 9 13 16 18 24 27 30 34 40
M 10 12 16 19 22
Q 33
S 27 32 45 55 65 76 87 98 109 130
T 25 30 35 50 60 71 81 91 101 121
W 13.1 31. 8 35.8 27.4
Z 12 14 18 22 27 35 40 45 50 61
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN j<~IRE SPRINKLERS INC. Page 8
FLA MED CLINIC - O.H./MEZZ. Date
Node Elevation K-Fact pt Pn Flow Density Area Press
No. Actual Actual Added Req. Req.
1 21.5 5.6 12.76 na 20 .2 100 12.76
2 21.5 5.6 13.77 na 20.78 .2 100 12.76
3 21.5 5.6 17 .57 na 23.47 .2 100 12.76
4 21.5 5.6 13.66 na 20.7 .2 100 12.76
5 21. 5 5.6 14.74 na 21. 5 .2 100 12.76
6 21. 5 5.6 18.78 na 24.27 .2 100 12.76
7 20.5 29.08 na
8 20.5 30.75 na
9 21.5 5.6 21. 87 na 26.19 .2 100 12.76
10 21.5 5.6 23.54 na 27.17 .2 100 12.76
11 21.5 5.6 25.18 na 28.1 .2 100 12.76
12 21.5 30.09 na
13 21..5 30.09 na
14 21.5 30.09 na
15 20.5 30.53 na
16 20.5 31. 22 na
17 21.5 31. 95 na
18 21.5 31. 95 na
19 21.5 31. 95 na
20 21.5 31. 95 na
21 20.5 32.38 na
22 20.5 32.38 na
23 1f; 36.04 na
24 15 37.94 na
25 15 41.54 na
26 15 42.09 na
27 15 42.31 na
28 10 44.88 na
29 10 44.92 na
TR 1 48.87 na
BR -3 50.7 na
A -3 50.74 na
B -3 50.87 na 250
C 2 49.12 na
TEST 2 49.41 na
The maximum velocity is 22.56 and it occurs in the pipe between nodes 6 and 7
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 9
FLA MED CLINIC - O.H./MEZZ. Date
Hyd. Qa Dia. Fitting Pipe pt pt
Ref. flC" Ftng's Pe Pv ******* Notes ******
or
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
1 20.00 1.104 10.000 12.760 K Factor = 5.6
to 120
2 20.00 0.1015 10.000 1. 015 Vel = 6.703
2 20.79 1.104 10.000 13.775 K Factor = 5.6
to 120
3 40.79 0.3792 10.000 3.792 Vel = 13 . 671
3 23.47 1.097 1T 6.217 6.000 17.567 K Factor = 5.6
to 120 6.217 0.433
7 64.26 0.9069 12.217 11.079 Vel = 21.813
64.26 29.079 K Factor 11.92
4 20.70 1.104 10.000 13.662 K Factor 5.6
to 120
5 20.70 0.1081 10.000 1. 081 Vel = 6.938
5 21. 50 1.104 10.000 14.743 K Factor = 5.6
to 120
6 42.20 0.4039 10.000 4.039 Vel = 14.144
6 24.27 1. 097 1T 6.217 4.000 18.782 K Factor = 5.6
to 120 6.217 0.433
7 66.47 0.9654 10.217 9.863 Vel = 22.563
7 64.26 2.154 1T 12.224 1.000 29.079
to 120 12.224
8 130.73 0.1262 13.224 1. 669 Vel 11. 510
8 2.635 10.000 30.748
to 120
16 130.73 0.0473 10.000 0.473 Vel = 7.691
130.73 31. 221 K Factor 23.40
9 26.19 1.104 10.000 21. 867 K Factor 5.6
to 120
10 26.19 0.1671 10.000 1.671 Vel = 8.778
10 27.17 1.452 10.000 23.538 K Factor = 5.6
to 120
11 53.36 0.1641 10.000 1. 641 Vel = 10.339
11 28.10 1.452 1T 7.686 6.000 25.179 K Factor = 5.6
to 120 7.686 0.433
15 81. 46 0.3591 13.686 4.914 Vel = 15.783
81. 46 30.526 K Factor = 14.74
12 0 1.104 10.000 30.092 0
to 120 0
13 0 0 10.000 0 0 Vel 0
13 0 1.104 10.000 30.092 0
to 120 0
14 0 0 10.000 0 0 Vel 0
14 0 1. 097 1T 6.217 4.000 30.092 0
to 120 6.217 0.433 0
15 0 0 10.217 0 0 Vel 0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 10
FLA MED CLINIC - O.H./MEZZ. Date
Hyd. Qa Dia. Fitting Pipe pt pt
Ref. "CII or Ftng's Pe Pv ******* Notes ******
Point Qt Pf!UL Eqv. Ln. Total Pf Pn
15 81.46 2.154 1T 12.2.24 1. 000 30.525
to 120 12.224
16 81.46 0.0526 13.224 0.696 Vel 7.172
16 130.73 2.635 10.000 31. 221
to 120
22 212.19 0.1158 10.000 1.158 Vel = 12.484
212.19 32.379 K Factor = 37.29
17 0 1.104 3E 2.565 16.000 31.946 0
to 120 IT 6.413 14.108 0
19 0 0 30.108 0 0 Vel = 0
31. 946 K Factor
18 0 1.104 2.000 31.946 0
to 120 0
19 0 0 2.000 0 0 Vel 0
19 0 1.104 8.000 31. 946 0
to 120 0
20 0 0 8.000 0 0 Vel 0
20 0 1. 097 IT 6.217 4.000 31. 946 0
to 120 6.217 0.433 0
21 0 0 10.217 0 0 Vel 0
21 0.01 2.154 IT 12.224 1. 000 32.379
to 120 12.224
22 0.01 13.224 Vel 0.001
22 212.18 2.635 1E 8.237 6.500 32.379
to 120 8.237 1. 949
23 212.19 0.1158 14.737 1. 707 Vel 12.484
23 2.635 1E 8.237 4.500 36.035
to 120 8.237 0.433
24 212.19 0.1159 12.737 1. 476 Vel 12.484
24 3.26 2E 9.408 48.500 37.944
to 120 1T 20.159 38.974
25 212.19 0.0411 8-7.474 3.594 Vel 8.156
25 4.026 37.500 41. 538
to 120
26 212.19 0.0147 37.500 0.551 Vel 5.348
26 5.047 1E 12.000 33.000 42.089
to 120 12.000
27 212.19 0.0049 45.000 0.220 Vel 3.403
27 5.047 1T 25.000 58.000 42.309
to 120 25.000 2.166
28 212.19 0.0049 83.000 0.406 Vel 3.403
28 6.065 1E 14.000 5.000 44.881
to 120 14 . 000
29 212.19 0.0020 19.000 0.038 Vel 2.356
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 11
FLA MED CLINIC - O.H./MEZZ. Date
Hyd. Qa Dia. Fitting Pipe pt pt
Ref. lie" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
29 6.065 1E 14.000 11. 000 44.919
to 120 14.000 3.898
TR 212.19 0.0020 25.000 0.050 Vel 2.356
TR 6.065 1G 3.000 9.000 48.867
to 120 1A 27.000 44.000 1. 732
BR 212.19 0.0020 1Z 14.000 53.000 0.106 Vel 2.356
BR 6.16 1E 20.084 6.000 50.705
to 140 20.084
A 212.19 0.0014 26.084 0.036 Vel 2.284
A 6.08 1T 45.881 50.000 50.741
to 150 1G 4.588 50.467
B 212.19 0.0013 100.467 0.131 Vel = 2.345
B 250.00 7.98 280.000 50.872 Qa = 250
to 150 -2.166
C 462.19 0.0015 280.000 0.411 Vel = 2.965
C 6.08 1T 45.881 2.000 49.118
to 150 1G 4.588 50.467
TEST 462,19 0.0055 52.467 0.289 Vel 5.107
462.19 49.407 K Factor 65.75
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
,.
. . _ Fire Protection by Computer Design
RODAN FIRE SPRINKLERS INC.
2501 NORTH 70TH STREET
FAX- 1-813-628-0143
TAMPA FLORIDA 33619
813-621-1357
Job Name
Building
Location
System
Contract
Data File
FLA MED CLINIC - L.H. MEZZ.
OLD PUBLIX STORE - REMODEL TO CLINIC
38135 MARKET SQUARE, ZEPHYRHILLS. FLORIDA
ONE (6")
SO 41650
S041650.WX2
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC.
FLA MED CLINIC - L.H. MEZZ.
Page 2
Date
Hydraulic Design Information Sheet
Name - FLORIDA MEDICAL CLINIC
Location - 38135 MARKET SQUARE, ZEPHYRHILLS, FLORIDA
Building - OLD PUBLIX STORE - REMODEL TO CLINIC
Contractor - RODAN FIRE SPRINKLERS, INC.
Calculated By - CHET SECKMAN
Construction: ( ) Combustible
Occupancy - NFPA 13 STANDARDS
Date - 11-27-01
System No. - ONE (6")
Contract No. - SO 41650
Drawing No. - 3 OF 3
(X) Non-Combustible Ceiling Height - 19-4
- LIGHT HAZARD OCCUPANCY
S
Y
S
T
E
M
(X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ) 3 ( ) Ex.Haz.
( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
Other
Specific Ruling PARAGRAPH: 7-2,3,2, 4 Made By NFPA-13 Date 1999EDITION
D
E
S
I
G
N
Area of Sprinkler Operation - 900
Density - .10
Area Per Sprinkler - 196 MAX
Elevation at Highest Outlet - 9FT AFF
Hose Allowance - Inside - - 0 -
Rack S~rinkler Allowance - N/A
Hose Allowance - Outside - 100
System Type
(X) Wet
( ) Dry
( ) Deluge
( ) Preaction
( ) Other
Sprinkler/Nozzle
Make GLOBE, Q. RES
Model "J", CH REC
Size 1/2"
K-Factor 5.6
Temp.Rat.155
Note 286.88 GPM DEMAND IS 6.256 PSI UNDER THE WATER SUPPLY CURVE
Ca~culation
Summary
Flow Required - 286.88 Press Required - 51.165 At Test
C-Factor Used: 120 Overhead 150 Underground
Pump Data:
W
A
T
E
R
S
U
P
P
L
Y
C
0
M
M
S R
T A
0 C
R K
A
G
E
Water Flow Test:
Date of Test - EARLY 2001
Time of Test
Static Press
Residual Press
Flow
Elevation
Rated Cap.-
@ Press
Elev.
- 58
- 50
- 1186
- 2
Tank or Reservoir:
Cap. -
Elev.-
Well
Proof Flow
Location - FLOW HYDRANT NO.8ll8. RESIDUAL HYDRANT NO. 8ll7. ON 8" MAIN,
ON NORTH SrDEOF BUILDING
Sourc€ of Information - CITY OF ZEPHYRHILLS, FLORIDA.
FIRE DEPARTMENT. CAPT. GWYN
Conunodity
Storage Ht.
Storage Method:
Solid Piled
Class
Area
%
Location
Aisle W.
Palletized %
Rack
Single Row
Double Row
Mult. Row
Conven. Pallet
Slave Pallet
( ) Auto. Storage
( ) Solid Shelf
( ) Open Shel f
Encap.
Non
Flue Spacing
Longitudinal
Clearance:Storage to Ceiling]
Transverse
Horizontal Barriers Provided:
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
(Y')
Q) Q)
Ol-l-'
III III
p., 0 III
-I-'
Ill.
o
H
CI) H
p., CI) -
:8:8:80.
If)p.,p.,p.,
:8~(9l9(9~
Ho.rl If)
CI)(9.00CON
0. rl ..OCO .
COIf)~rl .~
If) co .. ~
~ . .. >._CO
~~Q)-I-' N..
'CO H;,-i'O" C
COrl;::lO C'O.,-i
.. CI) l1lCt))
~ CI)...., S l1l H
"OQ)'OQ)Sl1l
5~~F:X:0~:8
,,-i ~~ >. -
-I-' S S S-I-'
l1lQ)Q)Q)Q)Q)Q)
:>-I-'-I-'CI)CI)-I-''H
Q) CI) CI) 0 0 CI) l1l
o-f >. >'::x:: ::x:: >. CI)
~CI)CI) CI)
I I I I
r'iNN (Y)
000 0
-
-
N
0
-
-
-
-
~ ~~ (Y) I-i
0
I I I I
.~
!l.
H
CI)
H!l.:8
CI) !l.
N 0.0(9
0 N If)
Z ~ co ~
H :8 If)..CO
Q)rl
CI) Hrl
l):; ::x:: Q) ;::l
~ >. H CI) ..
H H o-f ;::l CI) ~
x: 0. CI) Q) 0
Z 0. Cl)Ho-f
H ;::l Q)o.[..,
l):; 0 CI) H
0. H o.rlrl
CI) Z H l1l l1l
H Q) U ;::l ;::l
~ H -I-' .,-i '0 '0
l):; 0 l1l -I-'.,-i.,-i
H ~ l1l CI) CI)
[.., 0 -I-'Q)Q)
~ >. Cl)l):;l):;
z :8 -I-' I I I
F:X: ',-i rlNN
0 F:X: 0 uoo
0 H
l):; [..,
o
If)
rl
o
~
rl
o
(Y')
rl
o
N
rl
o
rl
rl
o
o
rl
o
0'\
o
CO
o
r-
o
~
o
If)
o
~
o
(Y)
o
N
o
rl
0.
l):;
w
CI)
CI)
::>
l):;
w
o
o
CO
rl
o
o
~
rl
CXl
C'l
~1
~
C'l
~1
\D
C'l
~1
10
C'l
~1
~
C'l
~1 r-
OO
0
('Y)
0
C"I
N ,:t:
..,. ~1 Ul
OJ OJ ::::J
tJl .jJ
l\l l\l :r::
0.0
Z
10 C'l E:
~ ri C'l l\l
~l :1 ~i .c:
'0
C
OM
~
C"I ri rl
10 ri C'l rl
~1 :1 1 rl
OJ
.jJ
::l
0
~
\D C'l C'l 0
~ ri ri C'l N
; 1 ~p 1 ~1 1 u
C
H
U
OJ
.jJ
N l\l
U N H
Z ril ri \D CJI '0
H ~ C"I CXl ri ri ri >.
~1~1~1:1 1 ::r::
CJ)
~ :r:: >.
ril .Q
H H
~ (IJ
Z I E:
H <1l
~ U H
0. H 0 10 CXl tJl
CJ) Z C'l ~ M M M 0
H ~1~1~1 1 1 H
ril H 0.
~ U
H H
c... 0 OJ
ril .jJ
Z ~ ::l
,:t: ~
0 ,:t:
0 H ~ ~ 0
0:: c... M \D CJI M M U
E-l
en
~
~l r-
eo
0
(Y)
0
0
If) ~l ,:l;
Q) Q) U}
0> +l D
m m
p.. Cl ::x::
Z
III f'i
m
~l .c::
'd
c
-rl
:;:
l( r-I
r-I
~l r-I
Q)
+l
;::l
0
c<:
Ii
~l u
c
H
U
Q)
N .jJ
U N m
Z W ~ \..4
H ::8 'd
>,
U} ~l ::x::
c<: ::x::
w >,
H H .0
:.::
Z (J)
H f'i
c<: U rO
0. H 0\ \..4
U} Z N tJ1
H ~l 0
w H \..4
c<: U 0.
H
ex. Cl \..4
W Q)
Z ::8 .jJ
,:l; ;::l
Cl ,:l; ~
0 H c:o
pc; ex. N 0
U
RODAN FIRE SPRINKLERS INC.
FLA MED CLINIC - L.H. MEZZ.
Page 6
Date
Fitting Legend
Abbrev.
Name
A
B
C
D
E
F
G
K
L
M
Q
S
T
W
Z
Generic Alarm Va
Generic Butterfly Valve
Roll Groove Coupling
Dry Pipe Valve
90' Standard Elbow
45' Elbow
Gate Valve
Detector Check Valve
Long Turn Elbow
Medium Turn Elbow
Flow Control Valve
Swing Check Valve
90' Flow thru Tee
Wafer Check Valve
Flow Switch
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 7
FLA MED CLINIC - L.H. MEZZ. Date
Unadjusted Fittings Table
1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4
A 7.7 21. 5 17 .0
B 7 10 12
C 1 1 1 1 1 1 1 1 1 1
0 9.5 17 28
E 2 2 2 3 4 5 6 7 8 10
F 1 1 1 1 2 2 3 3 3 4
G 1 1 1 1 2
K 14 14
L 1 1 2 2 2 3 4 5 5 6
M 2 2 3 3 4 5 6 6 8
Q 18 29 35
5 4 5 5 7 9 11 14 16 19 22
T 3 4 5 6 8 10 12 15 17 20
W 10.3
Z 2 2 2 3 4 5 6 7 8 10
5 6 8 10 12 14 16 18 20 24
A 17 27 29
B 9 10 12 19 21
C 1 1 1 1 1 1 1 1 1 1
D 47
E 12 14 18 22 27 35 40 45 50 61
F 5 7 9 11 13 17 19 21 24 28
G 2 3 4 5 6 7 8 10 11 13
K 36 55 45
L 8 9 13 16 18 24 27 30 34 40
M 10 12 16 19 22
Q 33
5 27 32 45 55 65 76 87 98 109 130
T 25 30 35 50 60 71 81 91 101 121
W 13.1 31.8 35.8 27.4
z 12 14 18 22 27 35 40 45 50 61
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN 'FIRE SPRINKLERS INC. Page 8
FLA MED CLINIC - L.H. MEZZ. Date
Node Elevation K-Fact pt Pn Flow Density Area Press
No. Actual Actual Added Req. Req.
1 21.5 5.6 7 na 14 .82 .1 77.5 7
2 21.5 5.6 7.58 na 15.42 .1 77.5 7
3 21.5 5.6 10.99 na 18.56 .1 96 7
4 21. 5 5.6 15.22 na 21. 84 .1 96 7
5 21.5 5.6 19.96 na 25.02 .1 196 12.25
6 21.5 5.6 26.75 na 28.96 .1 196 12.25
7 20.5 29.18 na
8 20,5 30.71 na
9 21.5 5.6 11. 84 na 19.27 .1 77.5 7
10 21.5 5.6 13.32 na 20.44 .1 77.5 7
11 21.5 5.6 16.21 na 22.55 .1 96 7
12 21.5 22.84 na
13 21.5 26.49 na
14 21.5 30.46 na
15 20.5 30.89 na
16 20.5 31. 31 na
17 21.5 31. 29 na
18 21.5 31. 29 na
19 21.5 31. 29 na
20 21.5 31. 29 na
21 21.5 31. 29 na
22 20.5 31.73 na
23 20.5 34.96 na
24 16 40.18 na
25 16 41.35 na
26 16 43.59 na
27 16 44.12 na
28 10 47.12 na
29 10 47.15 na
TR 1 51.09 na
BR -3 52.91 na
A -3 52.94 na
B -3 53.04 na 100
C 2 51. 05 na
TEST 2 51.17 na
The maximum velocity is 20.87 and it occurs in the pipe between nodes 11 and 12
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 9
FLA MED CLINIC - L.H. MEZZ. Date
Hyd. Qa Dia. Fitting Pipe pt pt
Ref. "e" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
1 14.82 1.104 10.000 7.000 K Factor = 5.6
to 120
2 14.82 0.0583 10.000 0.583 Vel = 4.967
2 15.42 1.104 2E 2.565 10.500 7.582 K Factor = 5.6
to 120 5.130
3 30.24 0.2180 15.630 3.407 Vel = 10.135
3 18.56 1.104 8.000 10.989 K Factor = 5.6
to 120
4 48.80 0.5284 8.000 4.227 Vel = 16.356
4 21.84 1. 452 2E 3.843 9.500 15.216 K Factor = 5.6
to 120 7.686
5 70.64 0.2758 17.186 4.740 Vel = 13.687
5 25.02 1. 452 IT 7.686 10.500 19.957 K Factor = 5.6
to 120 7.686 0.433
7 95.66 0.4833 18.186 8.789 Vel = 18.535
95.66 29.179 K Factor 17.71
6 28:96 1.104 IT 6.413 3.500 26.752 K Factor 5.6
to 120 6.413 0.433
7 28.96 0.2013 9.913 1. 995 Vel = 9.706
7 95.67 2.154 IT 12.224 1. 000 29.180
to 120 12.224
8 ' 124.63 0.1155 13.224 1. 528 Vel 10.973
8 2.635 14 .000 30.708
to 120
16 124.63 0.0433 14.000 0.606 Vel = 7.332
124.63 31. 314 K Factor 22.27
9 19.27 1.104 2E 2.565 10.500 11. 842 K Factor 5.6
to 120 5.130
10 19.27 0.0947 15.630 1.480 Vel = 6.459
10 20.44 1.104 8.000 13.323 K Factor = 5.6
to 120
11 39.71 0.3609 8.000 2.887 Vel :, 13.309
11 22.55 1.104 8.000 16.210 K Factor = 5.6
to 120
12 62.26 0.8293 8.000 6.634 Vel = 20.867
12 1.452 2E 3.843 9.000 22.844
to 120 7.686
13 62.26 0.2183 16.686 3.643 Vel 12.063
13 1. 452 1T 7.686 10.500 26.487
to 120 7.686 0.433
15 62.26 0.2184 18.186 3.971 Vel = 12.063
62.26 30.891 K Factor = 11. 20
14 0 1.104 IT 6.413 3.500 30.457 0
to 120 6.413 0.433 0
15 0 0 9.913 0 0 Vel 0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
RODAN FIRE SPRINKLERS INC. Page 10
FLA MED CLINIC - L.H. MEZZ. Date
Hyd. Qa Dia. Fitting Pipe pt pt
Ref. "en or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
15 62.26 2.154 1T 12.224 1. 000 30.891
to 120 12.224
16 62.26 0.0320 13.224 0.423 Vel 5.482
16 124.62 2.635 4.500 31.314
to 120
22 186.88 0.0916 4.500 0.412 Vel = 10.995
186.88 31.726 K Factor = 33.18
17 0 1.104 1E 2.565 2.000 31.293 0
to 120 2.565 0
18 0 0 4.565 0 0 Vel 0
18 0 1.104 8.000 31.293 0
to 120 0
19 0 0 8.000 0 0 Vel 0
19 0 1.104 14.000 31.293 0
to 120 0
20 0 0 14.000 0 0 Vel 0
20 0 1.104 12.000 31. 293 0
to 120 0
21 0 0 12.000 0 0 Vel 0
21 -0.01 1.452 9.000 31. 293
to 120 0.433
22 -0.01 9.000 Vel -0.002
22 186.89 2.154 IT 12.224 1.000 31. 726
to 120 12.224
23 186.88 0.2444 13.224 3.232 Vel 16.454
23 2.635 lE 8.237 27.500 34.958
to 120 8.237 1. 949
24 186.88 0.0916 35.737 3.273 Vel 10.995
24 2.635 lE 8.237 4.500 40.180
to 120 8.237
25 186.88 0.0916 12.737 1.167 Vel 10.995
25 3.26 2E 9.408 30.000 41.347
to 120 IT 20.159 38.974
26 186.88 0.0325 68.974 2.241 Vel 7.183
26 4.026 46.000 43.587
to 120
27 186.88 0.0116 46.000 0.535 Vel 4.710
27 5.047 lE 12.000 67.500 44.122
to 120 IT 25.000 37.000 2.599
28 186.88 0.0039 104.500 0.404 Vel 2.997
28 6.065 lE 14 . 000 5.000 47.125
to 120 14.000
29 186.88 0.0016 19.000 0.030 Vel 2.075
29 6.065 lE 14.000 11. 000 47.155
to 120 14.000 3.898
TR 186.88 0.0016 25.000 0.040 Vel 2.075
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087
RODAN ~IRE SPRINKLERS INC. Page 11
FLA MED CLINIC - L.H. MEZZ. Date
Hyd. Qa Dia. Fitting Pipe pt pt
Ref. "e" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
TR 6.065 IG 3.000 9.000 51. 092
to 120 1A 27.000 44.000 1. 732
BR 186.88 0.0016 1Z 14.000 53.000 0.084 Vel 2.075
BR 6.16 1E 20.084 6.000 52.908
to 140 20.084
A 186.88 0.0011 26.084 0.029 Vel 2.012
A 6.08 1T 45.881 50.000 52.937
to 150 1G 4.588 50.467 ,.
B 186.88 0.0010 100.467 0.104 Vel = 2.065
B 100.00 7.98 280.000 53.041 Qa = 100
to 150 -2.166
C 286.88 0.0006 280.000 0.170 Vel = 1. 840
C 6.08 1T 45.881 2.000 51. 045
to 150 1G 4.5,88 50.467
TEST 286.88 0.0023 52.467 0.120 Vel = 3.170
286.88 51.165 K Factor = 40.11
Computer Programs by Hydratec Inc.
Route 111
Windham N.H. USA 03087